DLX8-XFMR-1 <br />1500KVA, 12kV: 480/277V <br />NEMA 3R, TAPPED AT 12kV <br />KK 2000A, 100% RATED <br />ERMIS, LSIG <br />LVSB-1-MCB <br />400AF/225AT <br />LSI <br />SPD GFP <br />GROUNDING <br />SYSTEM REFER <br />TO GROUNDING <br />SCHEMATIC ON <br />E4.2 <br />400AF/350AT <br />LSI <br />GENERATOR <br />SECTIONDISTRIBUTION SECTION <br />KK 2000A, W/GFCI <br />LVSB-1-GCB <br />TERMINALS FOR FUTURE <br />GENERATOR CONNECTION ONLY. <br />THIS SECTION IS ONLY INSTALLED <br />TO FACILITATE A FUTURE PERMIT <br />OF A GENERATOR, EMERGENCY OR <br />OTHERWISE <br />DSD5-LVSB-1 <br />2000A, 480/277V, 4W, 3PH <br />SWITCHBOARD, NEMA 1 <br />MIN AIC: 35kA <br />DLX8 <br />LV-XFMR-1 <br />DLX8 <br />LV-XFMR-2 <br />480V-208Y/120V <br />150KVA, -2.5% TAP <br />DRY TYPE, NEMA 1 <br />14OF LV2 <br />CHARGERS <br />DLX8 <br />LV-PNL-1600AF <br />600AT <br />94% UTILIZATION <br />400AF/225AT <br />LSI <br />400AF/225AT <br />LSI <br />400AF/350AT <br />LSI <br />400AF/225AT <br />LSI <br />400AF/225AT <br />LSI <br />400AF/225AT <br />LSI <br />SEE PANEL BOARD <br />SCHEDULES FOR <br />BRANCH BREAKER <br />DESIGN. <br />18 OF LV2 <br />CHARGERS <br />DLX8 <br />LV-PNL-2800AF <br />800AT <br />DLX8 <br />LV-XFMR-3 <br />14 OF LV2 <br />CHARGERS <br />DLX8 <br />LV-PNL-3 <br />DLX8 <br />LV-XFMR-4 <br />14 OF LV2 <br />CHARGERS <br />DLX8 <br />LV-PNL-4 <br />DLX8 <br />LV-XFMR-5 <br />18 OF LV2 <br />CHARGERS <br />DLX8 <br />LV-PNL-5800AF <br />800AT <br />DLX8 <br />LV-XFMR-6 <br />14 OF LV2 <br />CHARGERS <br />DLX8 <br />LV-PNL-6 <br />DLX8 <br />LV-XFMR-7 <br />14 OF LV2 <br />CHARGERS <br />DLX8 <br />LV-PNL-7 <br />DLX8 <br />LV-XFMR-8 <br />14 OF LV2 <br />CHARGERS <br />DLX8 <br />LV-PNL-8 <br />400AF/225AT <br />LSI <br />208/120V, 600A <br />3PH, 4W, NEMA 1 <br />AIC: 22KAIC <br />DSD5_EV_OSP <br />L3-EV CHARGER <br />DSD5_EV_OSP <br />L3-EV CHARGER <br />DLX8 <br />LV/L3 PNL-9 <br />480/277V, 225A, MLO <br />3PH, 4W, NEMA 3R <br />AIC: 35KAIC <br />LVSB-1-CB-1 LVSB-1-CB-2 LVSB-1-CB-3 LVSB-1-CB-4 LVSB-1-CB-5 LVSB-1-CB-6 LVSB-1-CB-7 LVSB-1-CB-8 LVSB-1-CB-9 <br />89% OF UTILIZATION <br />81% UTILIZATION 94% UTILIZATION 94% UTILIZATION 81% UTILIZATION 94% UTILIZATION 94% UTILIZATION 94% UTILIZATION <br />LENGTH: 270'LENGTH: 180'LENGTH: 250'LENGTH: 365'LENGTH: 270'LENGTH: 325'LENGTH: 450' <br />(1) SET <br />(3) 300 KCMIL AL <br />(1) #2 AWG GND AL <br />2-1/2" PVC C. <br />LENGTH: 360' <br />(2) SETS <br />(4) 500 KCMIL AL <br />(1) # 1/0 AWG GND AL SSBJ <br />3-1/2" PVC C. <br />LENGTH: 10'LENGTH: 10'LENGTH: 10'LENGTH: 10'LENGTH: 10'LENGTH: 10'LENGTH: 10'LENGTH: 10' <br />(7) SETS <br />(4) 500 KCMIL AL <br />(1) 1/0 AWG GND AL SSBJ <br />3-1/2" PVC C. <br />LENGTH: 35' <br />(2) SETS OF <br /> (3) 4/0 AWG AL <br /> (1) #1 AWG GND AL <br /> 2-1/2" PVC C. <br />(3) SETS <br />(4) 400 KCMIL AL <br />(1) # 1/0 AWG GND AL SSBJ <br />3-1/2" PVC C. <br />(2) SETS OF <br /> (3) 4/0 AWG AL <br /> (1) #1 AWG GND AL <br /> 2" PVC C. <br />LENGTH: 160' <br />(2) 100A/3P <br />LENGTH: 10',30' <br />(4) #2 AWG CU <br />(1) #8 AWG GND CU <br />1-1/4" PVC C. <br />3 #2 AWG (15kV RATED 133% MV-90) AL. <br />1 #4 GND AL., 4" PVC <br />LENGTH: 130' <br />LEGEND <br />(N) EQUIPOMENT OUTLINE <br />(N) ELECTRIAL COMPONENTS <br />AND CIRCUITS <br />(E) ELECTRICAL EQUIPMENT & <br />CIRCUITS <br />EQUIPMENT BUSSING <br />COMMUNICATION <br />KK KIRKOFF KEY <br />INTERLOCK <br />SPD <br />AVAIL. FAULT: 31,961A <br />AVAIL. FAULT: 11,269A <br />BREAKER <br />SWITCH <br />FUSE <br />MV LOAD BREAK <br />CURRENT TRANSFORMER <br />CAPPED CONDUIT <br />GROUND <br />CONTROL POWER <br />TRANSFORMER <br />SURGE PROTECTION <br />DEVICE <br />GFP GROUND FAULT <br />PROTECTION RELAY <br />M METER <br />TRANSFORMER <br />WYE <br />GROUNDED WYE <br />DELTA <br />208/120V, 800A <br />3PH, 4W, NEMA 1 <br />AIC: 22KAIC <br />208/120V, 800A <br />3PH, 4W, NEMA 3R <br />AIC: 22KAIC <br />AVAIL. FAULT: 10,591A AVAIL. FAULT: 5,643A AVAIL. FAULT: 6,420A AVAIL. FAULT: 5,554A AVAIL. FAULT: 6,758A AVAIL. FAULT: 8,228A AVAIL. FAULT: 6,420A AVAIL. FAULT: 14,291A <br />PRIMARY METERING CABINET <br />CBL MVSG-1 <br />2 Set(s) of: <br />#350 AL KCMIL Conductors (MV-105), <br />,In 6" Conduit <br />Length: 20.0 ft <br />SECTION 1 SECTION 2 SECTION 3 SECTION 4 <br />12000V, 3PH, 3W, 600A, 60HZ, 40KA ASYM <br />KWH <br />PTО | SC FU PT <br />CT <br />TS1 <br />751 <br />SEL <br />TS1 <br />TS1 <br />SCTB <br />1A <br />FU FUPT <br />80A <br />MCCB <br />5A <br />FU <br />INTLK <br />TO INTERNAL 120V CIRCUITS <br />(HEATERS, LIGHTS & <br />RECEPTACLES) <br />12000V, 3PH, 3W, 600A, 60HZ, 40KA ASYM <br />PT ACCESS <br />KL KL <br />(2) <br />(2)DOOR <br />(2) <br />0.5E <br />UTILITY INCOMING <br />CABLE SIZE <br />1000KCMIL AL <br />CABLE/PH 1 <br />CT <br />600/5A <br />(3) <br />VCB-25KA <br />15KV, 600A <br />UTILITY PROVIDED <br />CT'S AND PT'S PER <br />UTILITY <br />REQUIREMENTS CT <br />SIZE: 10-800A <br />CPT-15KVA <br />12000V-120/240V <br />PT12000V-120V <br />CPT <br />METER <br />Incoming Voltage: 12000 V <br />DLX8-MVSG-1 <br />Line to Line Contribution: 12500.00 A <br />Line to Ground Contribution: 12499.00 A <br />15.5KV, 600A, NEMA-3R, 6-WAYS <br />MV UNDERGROUND DISTRIBUTION SWITCHGEAR <br />12,500 AIC <br />SPARE SPARE SPARE <br />MVSG-1 50/51-6 <br />Open <br />MVSG-1 52-6 <br />Rating 600.0 A <br />MVSG-1 50/51-3 <br />Open <br />MVSG-1 52-3 <br />Rating 600.0 A <br />150AT/3P <br />LSI <br />MVSG-1 50/51-4 <br />Open <br />MVSG-1 52-4 <br />Rating 600.0 A <br />MVSG-1 50/51-5 <br />Open <br />MVSG-1 52-5 <br />Rating 600.0 A <br />MVSG-1 52-2 <br />MVSG-1 50/51-2 <br />GND <br />SW <br />89 <br />GND <br />SW <br />89 GND <br />SW 89 <br />GND <br />SW <br />89 <br />GND <br />SW <br />89 <br />GND <br />SW <br />89 <br />6" SPARE CONDUIT TO BE STUBBED <br />AND CAPPED ABOVE-GRADE (TYP.) <br />MVSG-1 52-2 <br />MVSG-1 50/51-1 <br />VFI Rating 600.0 A Rating 600.0 A <br />Fault at Device: 12500.00 A <br />Total Voltage Drop: 0.35 % <br />Incident Energy: 28.07 Cal/cm^2 <br />Working Distance: 36 inches <br />Arc Flash Boundary: 269 inches <br />CBL DLX8-XFMR-BLDG <br />DLX8-MVSG1 <br />Fault at Device: 12494.17 A <br />Total Voltage Drop: 0.35 % <br />Incident Energy: 1.82 Cal/cm^2 <br />Working Distance: 36 inches <br />Arc Flash Boundary: 47 inches <br />Length: 20.0 ft <br />1 Set(s) of: <br />#2 AL AWG Conductors (MV-105), <br />#6 Ground Wire <br />In 6" Conduit <br />REFER TO PHASE 0 ELECTRICAL <br />SINGLE LINE FOR CONTINUATION <br />(NOT IN THIS SCOPE OF WORK) <br />480V-208Y/120V <br />225KVA, -2.5% TAP <br />DRY TYPE, NEMA 1 <br />480V-208Y/120V <br />150KVA, -2.5% TAP <br />DRY TYPE, NEMA 1 <br />480V-208Y/120V <br />150KVA, -2.5% TAP <br />DRY TYPE, NEMA 1 <br />480V-208Y/120V <br />225KVA, -2.5% TAP <br />DRY TYPE, NEMA 1 <br />480V-208Y/120V <br />150KVA, -2.5% TAP <br />DRY TYPE, NEMA 1 <br />480V-208Y/120V <br />150KVA, -2.5% TAP <br />DRY TYPE, NEMA 1 <br />480V-208Y/120V <br />150KVA, -2.5% TAP <br />DRY TYPE, NEMA 1 <br />600AF <br />600AT 208/120V, 600A <br />3PH, 4W, NEMA 1 <br />AIC: 22KAIC <br />600AF <br />600AT 208/120V, 600A <br />3PH, 4W, NEMA 1 <br />AIC: 22KAIC <br />600AF <br />600AT 208/120V, 600A <br />3PH, 4W, NEMA 1 <br />AIC: 22KAIC <br />600AF <br />600AT 208/120V, 600A <br />3PH, 4W, NEMA 1 <br />AIC: 22KAIC <br />600AF <br />600AT 208/120V, 600A <br />3PH, 4W, NEMA 1 <br />AIC: 22KAIC <br />(1) SET <br />(3) 300 KCMIL AL <br />(1) #2 AWG GND AL <br />2-1/2" PVC C. <br />(1) SET <br />(3) 300 KCMIL AL <br />(1) #2 AWG GND AL <br />2-1/2" PVC C. <br />(1) SET <br />(3) 300 KCMIL AL <br />(1) #2 AWG GND AL <br />2-1/2" PVC C. <br />(1) SET <br />(3) 300 KCMIL AL <br />(1) #2 AWG GND AL <br />2-1/2" PVC C. <br />(1) SET <br />(3) 300 KCMIL AL <br />(1) #2 AWG GND AL <br />2-1/2" PVC C. <br />(1) SET <br />(3) 300 KCMIL AL <br />(1) #2 AWG GND AL <br />2-1/2" PVC C. <br />PHASE 0 <br />PHASE 1 <br />EPO SWITCH <br />(2) #14 AWG CU <br />EPO SWITCH TO ACT <br />AS A SHUNT TRIP TO <br />MAIN BREAKER. <br />CONNECT TO MCB <br />CONTACTS. SEE E4.7, <br />DETAIL 7 FOR SITE <br />PLACARD <br />600A DEAD-BREAK <br />CONNECTION, PROVIDED <br />BY CONTRACTOR <br />POLYCARBONATE <br />PROTECTIVE <br />CLAMSHELL COVER <br />EQUIPMENT NOTES <br />LV2 CHARGER AX48 48A CHARGER <br />LV3 CHARGER MAXICHARGER DC FAST 60KW <br />60KW UL DUAL PORT DC AIO <br />#UF060A4001 <br />SEE E5.0 FOR EQUIPMENT CUTSHEETS <br />SWITCHBOARD GROUND FAULT <br />PROTECTION SYSTEM (GFP) <br />SHALL BE TESTED, CERTIFIED <br />AND LABELED PRIOR TO BEING <br />ENERGIZED. <br />(2) SETS <br />(4) 500 KCMIL AL <br />(1) # 1/0 AWG GND AL SSBJ <br />3-1/2" PVC C. <br />(2) SETS <br />(4) 500 KCMIL AL <br />(1) # 1/0 AWG GND AL SSBJ <br />3-1/2" PVC C. <br />(3) SETS <br />(4) 400 KCMIL AL <br />(1) #1 /0 AWG GND AL SSBJ <br />3-1/2" PVC C. <br />(2) SETS <br />(4) 500 KCMIL AL <br />(1) # 1/0 AWG GND AL SSBJ <br />3-1/2" PVC C. <br />(2) SETS <br />(4) 500 KCMIL AL <br />(1) # 1/0 AWG GND AL SSBJ <br />3-1/2" PVC C. <br />(2) SETS <br />(4) 500 KCMIL AL <br />(1) # 1/0 AWG GND AL SSBJ <br />3-1/2" PVC C. <br />C <br />C <br />C <br />PH: <br />RE <br />V <br />I <br />S <br />I <br />O <br />N <br />DA <br />T <br />E <br />2/ <br />1 <br />9 <br />/ <br />2 <br />5 <br />Ci <br />t <br />y <br /> <br />o <br />f <br /> <br />C <br />a <br />r <br />l <br />s <br />b <br />a <br />d <br /> <br />C <br />o <br />m <br />m <br />e <br />n <br />t <br />s <br />A <br />45 <br />0 <br /> <br />L <br />A <br />M <br />B <br />E <br />R <br />T <br /> <br />A <br />V <br />E <br />, <br /> <br />P <br />A <br />L <br />O <br /> <br />A <br />L <br />T <br />O <br />, <br /> <br />C <br />A <br /> <br />9 <br />4 <br />3 <br />0 <br />6 <br />(8 <br />8 <br />8 <br />) <br /> <br />3 <br />4 <br />2 <br />- <br />7 <br />3 <br />8 <br />3 <br />ORIGINAL SIZE 24"X36" <br />REV: <br />PROJ: <br />DL <br />X <br />8 <br /> <br />E <br />L <br />E <br />C <br />T <br />R <br />I <br />C <br /> <br />V <br />E <br />H <br />I <br />C <br />L <br />E <br /> <br />C <br />H <br />A <br />R <br />G <br />I <br />N <br />G <br /> <br />S <br />T <br />A <br />T <br />I <br />O <br />N <br />S <br />51 <br />5 <br /> <br />E <br />A <br />S <br />T <br /> <br />D <br />Y <br />E <br />R <br /> <br />R <br />O <br />A <br />D <br />SA <br />N <br />T <br />A <br /> <br />A <br />N <br />A <br />, <br /> <br />C <br />A <br /> <br />9 <br />2 <br />7 <br />0 <br />7 <br />BSE14-2 <br />DLX8_EV_OSP <br />ALEXANDER SHORTS <br />PROFESSIONA L ENGINEER <br />ELECTRICALSTATE OF CALIFORNIA <br />E 21782 <br />7/ <br />1 <br />4 <br />/ <br />2 <br />5 <br />Ut <br />i <br />l <br />i <br />t <br />y <br /> <br />t <br />r <br />e <br />n <br />c <br />h <br /> <br />p <br />a <br />t <br />h <br />B <br />10/22/25 <br />SS <br />B <br />J <br /> <br />U <br />p <br />s <br />i <br />z <br />e <br />, <br /> <br />G <br />e <br />n <br />e <br />r <br />a <br />t <br />o <br />r <br /> <br />s <br />e <br />c <br />t <br />i <br />o <br />n <br />C <br />9/ <br />2 <br />2 <br />/ <br />2 <br />5 <br />ELECTRICAL <br />DIAGRAM <br />E2.0 <br />IFP C