Distribution Panel "DP" <br />LB_1 <br />Rating 100.0 A <br />CBL LB1 <br />1 Set(s) of: <br />#2 AWG Conductors, <br />#6 Ground Wire <br />In 1 1/4" Conduit <br />Length: 5.0 ft <br />Switchboard "MSB" <br />CBL DP <br />3 Set(s) of: <br />#600 kcmil Conductors, <br />#4/0 Ground Wire <br />In 3" Conduit <br />Length: 20.0 ft <br />PD-H <br />Rating 200.0 A <br />PD-A <br />Rating 400.0 A <br />PD-B <br />Rating 200.0 A <br />PD-C <br />Rating 200.0 A <br />PD-E <br />Rating 200.0 A <br />PD-F <br />Rating 200.0 A <br />PD-G <br />Rating 200.0 A <br />PD-J <br />Rating 200.0 A <br />PD-K <br />Rating 200.0 A <br />PD-L <br />Rating 200.0 A <br />PD-M <br />Rating 200.0 A <br />PD-DP <br />Rating 1000.0 A <br />MSB-MPD <br />Rating 2000.0 A <br />PD-N <br />Rating 100.0 A <br />PD-Q <br />Rating 100.0 A <br />PD-R <br />Rating 100.0 A <br />PD-T <br />Rating 100.0 A <br />PD-EV <br />Rating 175.0 A <br />MMA-MPD <br />Rating 1200.0 A <br />Switchboard "MMA" <br />PANEL LB1 <br />EXISTING SWITCHBOARD "MSB" <br />480Y/277V, 3PH, 4W, 2000A, 65KAIC <br />EXISTING SWITCHBOARD "MMA" <br />480Y/277V, 3PH, 4W, 1200A, 100KAIC <br />(SET AT 175.0A)(SET AT 175.0A) <br />Fault at Device: 25192.88 A <br />Total Voltage Drop: -1.30 % <br />Incident Energy: 8.05 Cal/cm^2 <br />Working Distance: 18 inches <br />Arc Flash Boundary: 59 inches <br />Connected Load 392.80 kVA <br />CBL HA <br />2 Set(s) of: <br />#3/0 AWG Conductors, <br />#2 Ground Wire <br />In 2" Conduit <br />Length: 400.0 ft <br />PANEL HA <br />Fault at Device: 10070.44 A <br />Total Voltage Drop: 0.67 % <br />Incident Energy: 1.26 Cal/cm^2 <br />Working Distance: 18 inches <br />Arc Flash Boundary: 19 inches <br />Connected Load 232.00 kVA <br />CBL T-MDF(P) <br />1 Set(s) of: <br />#4 AWG Conductors, <br />#8 Ground Wire <br />In 1" Conduit <br />Length: 120.0 ft <br />HA-CB1 <br />70.0 A Frame <br />70.0 A Trip <br />S <br />P <br />T-MDF <br />Fault at Device: 2847.31 A <br />Z% 3.37 % <br />LF VD% 2.81 % <br />Nominal kVA 45 kVA <br />Utilization 83.43 % <br />Pri Tap 0.00 % <br />Pri RatedVoltage 480 V <br />Sec RatedVoltage 208 V <br />CBL MDF <br />1 Set(s) of: <br />#1/0 AWG Conductors, <br />#6 Ground Wire <br />In 1 1/2" Conduit <br />Length: 5.0 ft <br />PANEL MDF <br />Fault at Device: 2804.17 A <br />Total Voltage Drop: 4.11 % <br />Incident Energy: 4.89 Cal/cm^2 <br />Working Distance: 18 inches <br />Arc Flash Boundary: 43 inches <br />Connected Load 36.00 kVA <br />MDF_MAIN <br />150.0 A Frame <br />150.0 A Trip <br />CBL HB <br />1 Set(s) of: <br />#3/0 AWG Conductors, <br />#4 Ground Wire <br />In 2" Conduit <br />Length: 240.0 ft <br />PANEL HB <br />Fault at Device: 9031.24 A <br />Total Voltage Drop: -0.80 % <br />Incident Energy: 0.24 Cal/cm^2 <br />Working Distance: 18 inches <br />Arc Flash Boundary: 7 inches <br />Connected Load 50.00 kVA <br />CBL T-LB(P) <br />1 Set(s) of: <br />#2 AWG Conductors, <br />#6 Ground Wire <br />In 1 1/4" Conduit <br />Length: 5.0 ft <br />HB-1 <br />100.0 A Frame <br />100.0 A Trip <br />S <br />P <br />T-LB <br />Fault at Device: 5118.35 A <br />Z% 3.20 % <br />LF VD% 0.28 % <br />Nominal kVA 75 kVA <br />Utilization 8.89 % <br />Pri Tap 0.00 % <br />Pri RatedVoltage 480 V <br />Sec RatedVoltage 208 V <br />CBL LB <br />1 Set(s) of: <br />#4/0 AWG Conductors, <br />#4 Ground Wire <br />In 2" Conduit <br />Length: 5.0 ft <br />PANEL LB <br />Fault at Device: 5035.98 A <br />Total Voltage Drop: -0.51 % <br />Incident Energy: 9.57 Cal/cm^2 <br />Working Distance: 18 inches <br />Arc Flash Boundary: 66 inches <br />Connected Load 6.70 kVA <br />LB_MAIN <br />225.0 A Frame <br />225.0 A Trip <br />Fault at Device: 4852.63 A <br />Total Voltage Drop: -0.50 % <br />Incident Energy: 9.17 Cal/cm^2 <br />Working Distance: 18 inches <br />Arc Flash Boundary: 64 inches <br />Connected Load 5.70 kVA <br />CBL HC <br />1 Set(s) of: <br />#4/0 AWG Conductors, <br />#4 Ground Wire <br />In 2" Conduit <br />Length: 540.0 ft <br />PANEL HC <br />Fault at Device: 5510.56 A <br />Total Voltage Drop: 0.48 % <br />Incident Energy: 0.97 Cal/cm^2 <br />Working Distance: 18 inches <br />Arc Flash Boundary: 16 inches <br />Connected Load 94.50 kVA <br />CBL T-LC(P) <br />1 Set(s) of: <br />#2 AWG Conductors, <br />#6 Ground Wire <br />In 1 1/4" Conduit <br />Length: 5.0 ft <br />HC-1 <br />100.0 A Frame <br />100.0 A Trip <br />S <br />P T-LC <br />Fault at Device: 4423.26 A <br />Z% 3.20 % <br />LF VD% 2.08 % <br />Nominal kVA 75 kVA <br />Utilization 65.04 % <br />Pri Tap 0.00 % <br />Pri RatedVoltage 480 V <br />Sec RatedVoltage 208 V <br />CBL LC <br />1 Set(s) of: <br />#4/0 AWG Conductors, <br />#4 Ground Wire <br />In 2" Conduit <br />Length: 5.0 ft <br />PANEL LC <br />Fault at Device: 4361.62 A <br />Total Voltage Drop: 2.62 % <br />Incident Energy: 0.07 Cal/cm^2 <br />Working Distance: 18 inches <br />Arc Flash Boundary: 3 inches <br />Connected Load 47.50 kVA <br />LC_MAIN <br />60.0 A Frame <br />60.0 A Trip <br />CBL HG <br />1 Set(s) of: <br />#2/0 AWG Conductors, <br />#6 Ground Wire <br />In 2" Conduit <br />Length: 850.0 ft <br />PANEL HG <br />Fault at Device: 2759.72 A <br />Total Voltage Drop: 0.05 % <br />Incident Energy: 4.15 Cal/cm^2 <br />Working Distance: 18 inches <br />Arc Flash Boundary: 39 inches <br />Connected Load 32.20 kVA <br />CBL T-LG(P) <br />1 Set(s) of: <br />#2 AWG Conductors, <br />#6 Ground Wire <br />In 1 1/4" Conduit <br />Length: 5.0 ft <br />HG-1 <br />100.0 A Frame <br />100.0 A Trip <br />S <br />P <br />T-LG <br />Fault at Device: 3291.06 A <br />Z% 3.20 % <br />LF VD% 0.09 % <br />Nominal kVA 75 kVA <br />Utilization 2.94 % <br />Pri Tap 0.00 % <br />Pri RatedVoltage 480 V <br />Sec RatedVoltage 208 V <br />CBL LG <br />1 Set(s) of: <br />#4/0 AWG Conductors, <br />#4 Ground Wire <br />In 2" Conduit <br />Length: 5.0 ft <br />LG <br />Fault at Device: 3256.72 A <br />Total Voltage Drop: 0.15 % <br />Incident Energy: 5.8 Cal/cm^2 <br />Working Distance: 18 inches <br />Arc Flash Boundary: 48 inches <br />Connected Load 2.20 kVA <br />LG_MAIN <br />225.0 A Frame <br />225.0 A Trip <br />CBL HH <br />2 Set(s) of: <br />#4/0 AWG Conductors, <br />#1 Ground Wire <br />In 2" Conduit <br />Length: 980.0 ft <br />PANEL HH <br />Fault at Device: 5884.12 A <br />Total Voltage Drop: 1.46 % <br />Incident Energy: 0.84 Cal/cm^2 <br />Working Distance: 18 inches <br />Arc Flash Boundary: 14 inches <br />Connected Load 150.90 kVA <br />CBL T-LH(P) <br />1 Set(s) of: <br />#2 AWG Conductors, <br />#6 Ground Wire <br />In 1 1/4" Conduit <br />Length: 5.0 ft <br />HH-1 <br />100.0 A Frame <br />100.0 A Trip <br />S <br />P <br />T-LH <br />Fault at Device: 4524.08 A <br />Z% 3.20 % <br />LF VD% 0.91 % <br />Nominal kVA 75 kVA <br />Utilization 28.42 % <br />Pri Tap 0.00 % <br />Pri RatedVoltage 480 V <br />Sec RatedVoltage 208 V <br />CBL LH <br />1 Set(s) of: <br />#4/0 AWG Conductors, <br />#4 Ground Wire <br />In 2" Conduit <br />Length: 5.0 ft <br />PANEL LH <br />Fault at Device: 4459.64 A <br />Total Voltage Drop: 2.40 % <br />Incident Energy: 8.33 Cal/cm^2 <br />Working Distance: 18 inches <br />Arc Flash Boundary: 60 inches <br />Connected Load 20.80 kVA <br />LH_MAIN <br />225.0 A Frame <br />225.0 A Trip <br />CBL HJ <br />2 Set(s) of: <br />#3/0 AWG Conductors, <br />#2 Ground Wire <br />In 2" Conduit <br />Length: 750.0 ft <br />PANEL HJ <br />Fault at Device: 6439.87 A <br />Total Voltage Drop: -0.78 % <br />Incident Energy: 0.65 Cal/cm^2 <br />Working Distance: 18 inches <br />Arc Flash Boundary: 12 inches <br />Connected Load 33.10 kVA <br />CBL T-LJ(P) <br />1 Set(s) of: <br />#2 AWG Conductors, <br />#6 Ground Wire <br />In 1 1/4" Conduit <br />Length: 5.0 ft <br />HJ-1 <br />100.0 A Frame <br />100.0 A Trip <br />S <br />P <br />T-LJ <br />Fault at Device: 4653.73 A <br />Z% 3.20 % <br />LF VD% 0.66 % <br />Nominal kVA 75 kVA <br />Utilization 20.65 % <br />Pri Tap 0.00 % <br />Pri RatedVoltage 480 V <br />Sec RatedVoltage 208 V <br />CBL LJ <br />1 Set(s) of: <br />#4/0 AWG Conductors, <br />#4 Ground Wire <br />In 2" Conduit <br />Length: 5.0 ft <br />PANEL LJ <br />Fault at Device: 4585.47 A <br />Total Voltage Drop: -0.10 % <br />Incident Energy: 8.6 Cal/cm^2 <br />Working Distance: 18 inches <br />Arc Flash Boundary: 62 inches <br />Connected Load 15.50 kVA <br />LJ_MAIN <br />225.0 A Frame <br />225.0 A Trip <br />CBL HK <br />1 Set(s) of: <br />#4/0 AWG Conductors, <br />#4 Ground Wire <br />In 2" Conduit <br />Length: 550.0 ft <br />PANEL HK <br />Fault at Device: 5428.24 A <br />Total Voltage Drop: -0.05 % <br />Incident Energy: 1.01 Cal/cm^2 <br />Working Distance: 18 inches <br />Arc Flash Boundary: 16 inches <br />Connected Load 67.00 kVA <br />CBL T-LK(P) <br />1 Set(s) of: <br />#2 AWG Conductors, <br />#6 Ground Wire <br />In 1 1/4" Conduit <br />Length: 5.0 ft <br />HK-1 <br />100.0 A Frame <br />100.0 A Trip <br />S <br />P <br />T-LK <br />Fault at Device: 4399.91 A <br />Z% 3.20 % <br />LF VD% 0.29 % <br />Nominal kVA 75 kVA <br />Utilization 8.96 % <br />Pri Tap 0.00 % <br />Pri RatedVoltage 480 V <br />Sec RatedVoltage 208 V <br />CBL LK <br />1 Set(s) of: <br />#4/0 AWG Conductors, <br />#4 Ground Wire <br />In 2" Conduit <br />Length: 5.0 ft <br />PANEL LK <br />Fault at Device: 4338.91 A <br />Total Voltage Drop: 0.25 % <br />Incident Energy: 8.07 Cal/cm^2 <br />Working Distance: 18 inches <br />Arc Flash Boundary: 59 inches <br />Connected Load 6.70 kVA <br />LK_MAIN <br />225.0 A Frame <br />225.0 A Trip <br />CBL HL <br />1 Set(s) of: <br />#3/0 AWG Conductors, <br />#4 Ground Wire <br />In 2" Conduit <br />Length: 320.0 ft <br />PANEL HL <br />Fault at Device: 7389.10 A <br />Total Voltage Drop: -0.53 % <br />Incident Energy: 0.44 Cal/cm^2 <br />Working Distance: 18 inches <br />Arc Flash Boundary: 10 inches <br />Connected Load 61.60 kVA <br />CBL T-LL(P) <br />1 Set(s) of: <br />#2 AWG Conductors, <br />#6 Ground Wire <br />In 1 1/4" Conduit <br />Length: 5.0 ft <br />HL-1 <br />100.0 A Frame <br />100.0 A Trip <br />S <br />P <br />T-LL <br />Fault at Device: 4849.89 A <br />Z% 3.20 % <br />LF VD% 1.11 % <br />Nominal kVA 75 kVA <br />Utilization 34.75 % <br />Pri Tap 0.00 % <br />Pri RatedVoltage 480 V <br />Sec RatedVoltage 208 V <br />CBL LL <br />1 Set(s) of: <br />#4/0 AWG Conductors, <br />#4 Ground Wire <br />In 2" Conduit <br />Length: 5.0 ft <br />PANEL LL <br />Fault at Device: 4775.83 A <br />Total Voltage Drop: 0.62 % <br />Incident Energy: 9.01 Cal/cm^2 <br />Working Distance: 18 inches <br />Arc Flash Boundary: 64 inches <br />Connected Load 25.90 kVA <br />LL_MAIN <br />225.0 A Frame <br />225.0 A Trip <br />CBL HM <br />1 Set(s) of: <br />#3/0 AWG Conductors, <br />#4 Ground Wire <br />In 2" Conduit <br />Length: 75.0 ft <br />PANEL HM <br />Fault at Device: 16997.35 A <br />Total Voltage Drop: -1.26 % <br />Incident Energy: 0.3 Cal/cm^2 <br />Working Distance: 18 inches <br />Arc Flash Boundary: 8 inches <br />Connected Load 26.80 kVA <br />CBL T-LM(P) <br />1 Set(s) of: <br />#2 AWG Conductors, <br />#6 Ground Wire <br />In 1 1/4" Conduit <br />Length: 5.0 ft <br />HM-1 <br />100.0 A Frame <br />100.0 A Trip <br />S <br />P <br />T-LM <br />Fault at Device: 5819.29 A <br />Z% 3.20 % <br />LF VD% 0.33 % <br />Nominal kVA 75 kVA <br />Utilization 10.31 % <br />Pri Tap 0.00 % <br />Pri RatedVoltage 480 V <br />Sec RatedVoltage 208 V <br />CBL LM <br />1 Set(s) of: <br />#4/0 AWG Conductors, <br />#4 Ground Wire <br />In 2" Conduit <br />Length: 5.0 ft <br />PANEL LM <br />Fault at Device: 5713.25 A <br />Total Voltage Drop: -0.92 % <br />Incident Energy: 11.07 Cal/cm^2 <br />Working Distance: 18 inches <br />Arc Flash Boundary: 72 inches <br />Connected Load 7.80 kVA <br />LM_MAIN <br />225.0 A Frame <br />225.0 A Trip <br />Fault at Device: 25807.74 A <br />Total Voltage Drop: -1.34 % <br />Incident Energy: 28.95 Cal/cm^2 <br />Working Distance: 18 inches <br />Arc Flash Boundary: 132 inches <br />Connected Load 642.70 kVA <br />CBL T-LA(P) <br />1 Set(s) of: <br />#2/0 AWG Conductors, <br />#6 Ground Wire <br />In 1 1/2" Conduit <br />Length: 5.0 ft <br />HA-CB2 <br />175.0 A Frame <br />175.0 A Trip <br />S <br />P <br />T-LA <br />Fault at Device: 5548.10 A <br />Z% 4.49 % <br />LF VD% 2.75 % <br />Nominal kVA 112.5 kVA <br />Utilization 64.49 % <br />Pri Tap 0.00 % <br />Pri RatedVoltage 480 V <br />Sec RatedVoltage 208 V <br />CBL LA <br />1 Set(s) of: <br />#600 kcmil Conductors, <br />#2 Ground Wire <br />In 3-1/2" Conduit <br />Length: 5.0 ft <br />LA_MAIN <br />400.0 A Frame <br />400.0 A Trip <br />PANEL LA <br />Fault at Device: 5484.87 A <br />Total Voltage Drop: 3.48 % <br />Incident Energy: 10.56 Cal/cm^2 <br />Working Distance: 18 inches <br />Arc Flash Boundary: 70 inches <br />Connected Load 70.00 kVA <br />CBL LA1 <br />1 Set(s) of: <br />#2 AWG Conductors, <br />#6 Ground Wire <br />In 1 1/4" Conduit <br />Length: 5.0 ft <br />PANEL LA1 <br />Fault at Device: 5291.62 A <br />Total Voltage Drop: 3.56 % <br />Incident Energy: 10.13 Cal/cm^2 <br />Working Distance: 18 inches <br />Arc Flash Boundary: 68 inches <br />Connected Load 34.20 kVA <br />LA_1 <br />200.0 A Frame <br />200.0 A Trip <br />CBL HE <br />1 Set(s) of: <br />#3/0 AWG Conductors, <br />#4 Ground Wire <br />In 2" Conduit <br />Length: 410.0 ft <br />PANEL HE <br />Fault at Device: 6047.53 A <br />Total Voltage Drop: -0.01 % <br />Incident Energy: 0.78 Cal/cm^2 <br />Working Distance: 18 inches <br />Arc Flash Boundary: 14 inches <br />Connected Load 74.70 kVA <br />CBL T-LE(P) <br />1 Set(s) of: <br />#2 AWG Conductors, <br />#6 Ground Wire <br />In 1 1/4" Conduit <br />Length: 5.0 ft <br />HE-1 <br />100.0 A Frame <br />100.0 A Trip <br />S <br />P <br />T-LE <br />Fault at Device: 4560.65 A <br />Z% 3.20 % <br />LF VD% 2.30 % <br />Nominal kVA 75 kVA <br />Utilization 71.97 % <br />Pri Tap 0.00 % <br />Pri RatedVoltage 480 V <br />Sec RatedVoltage 208 V <br />CBL LE <br />1 Set(s) of: <br />#4/0 AWG Conductors, <br />#4 Ground Wire <br />In 2" Conduit <br />Length: 5.0 ft <br />PANEL LE <br />Fault at Device: 4495.06 A <br />Total Voltage Drop: 2.37 % <br />Incident Energy: 8.4 Cal/cm^2 <br />Working Distance: 18 inches <br />Arc Flash Boundary: 61 inches <br />Connected Load 52.70 kVA <br />LE_MAIN <br />225.0 A Frame <br />225.0 A Trip <br />CBL HF <br />2 Set(s) of: <br />#2/0 AWG Conductors, <br />#3 Ground Wire <br />In 2" Conduit <br />Length: 640.0 ft <br />PANEL HF <br />Fault at Device: 6452.78 A <br />Total Voltage Drop: -0.52 % <br />Incident Energy: 0.65 Cal/cm^2 <br />Working Distance: 18 inches <br />Arc Flash Boundary: 12 inches <br />Connected Load 49.20 kVA <br />CBL T-LF(P) <br />1 Set(s) of: <br />#2 AWG Conductors, <br />#6 Ground Wire <br />In 1 1/4" Conduit <br />Length: 5.0 ft <br />HF-1 <br />100.0 A Frame <br />100.0 A Trip <br />S <br />P <br />T-LF <br />Fault at Device: 4656.24 A <br />Z% 3.20 % <br />LF VD% 0.38 % <br />Nominal kVA 75 kVA <br />Utilization 11.98 % <br />Pri Tap 0.00 % <br />Pri RatedVoltage 480 V <br />Sec RatedVoltage 208 V <br />CBL LF <br />1 Set(s) of: <br />#4/0 AWG Conductors, <br />#4 Ground Wire <br />In 2" Conduit <br />Length: 5.0 ft <br />PANEL LF <br />Fault at Device: 4587.83 A <br />Total Voltage Drop: -0.13 % <br />Incident Energy: 8.6 Cal/cm^2 <br />Working Distance: 18 inches <br />Arc Flash Boundary: 62 inches <br />Connected Load 9.00 kVA <br />LF_MAIN <br />225.0 A Frame <br />225.0 A Trip <br />CBL T-HEV(P) <br />1 Set(s) of: <br />#2/0 AWG Conductors, <br />#6 Ground Wire <br />In 1 1/2" Conduit <br />Length: 100.0 ft <br />HH-2 <br />175.0 A Frame <br />175.0 A Trip <br />S <br />P <br />T-HEV <br />Fault at Device: 4437.30 A <br />Z% 4.49 % <br />LF VD% 4.70 % <br />Nominal kVA 112.5 kVA <br />Utilization 109.91 % <br />Pri Tap 0.00 % <br />Pri RatedVoltage 480 V <br />Sec RatedVoltage 208 V <br />CBL HEV <br />1 Set(s) of: <br />#600 kcmil Conductors, <br />#2 Ground Wire <br />In 3-1/2" Conduit <br />Length: 5.0 ft <br />PANEL HEV <br />Fault at Device: 4397.13 A <br />Total Voltage Drop: 6.84 % <br />Incident Energy: 8.19 Cal/cm^2 <br />Working Distance: 18 inches <br />Arc Flash Boundary: 60 inches <br />Connected Load 115.20 kVA <br />HEV_MAIN <br />400.0 A Frame <br />400.0 A Trip <br />CBL HN <br />1 Set(s) of: <br />#1/0 AWG Conductors, <br />#6 Ground Wire <br />In 1 1/2" Conduit <br />Length: 560.0 ft <br />PANEL HN <br />Fault at Device: 3428.64 A <br />Total Voltage Drop: -0.33 % <br />Incident Energy: 0.11 Cal/cm^2 <br />Working Distance: 18 inches <br />Arc Flash Boundary: 4 inches <br />Connected Load 29.60 kVA <br />CBL T-LN(P) <br />1 Set(s) of: <br />#10 AWG Conductors, <br />#10 Ground Wire <br />In 3/4" Conduit <br />Length: 5.0 ft <br />HN-1 <br />25.0 A Frame <br />25.0 A Trip <br />S <br />P <br />T-LN <br />Fault at Device: 1306.36 A <br />Z% 2.78 % <br />LF VD% 0.22 % <br />Nominal kVA 15 kVA <br />Utilization 7.99 % <br />Pri Tap 0.00 % <br />Pri RatedVoltage 480 V <br />Sec RatedVoltage 208 V <br />CBL LN <br />1 Set(s) of: <br />#6 AWG Conductors, <br />#8 Ground Wire <br />In 3/4" Conduit <br />Length: 5.0 ft <br />PANEL LN <br />Fault at Device: 1277.12 A <br />Total Voltage Drop: -0.10 % <br />Incident Energy: 2 Cal/cm^2 <br />Working Distance: 18 inches <br />Arc Flash Boundary: 25 inches <br />Connected Load 1.20 kVA <br />LN_MAIN <br />60.0 A Frame <br />60.0 A Trip <br />CBL HQ <br />1 Set(s) of: <br />#1/0 AWG Conductors, <br />#6 Ground Wire <br />In 1 1/2" Conduit <br />Length: 500.0 ft <br />PANEL HQ <br />Fault at Device: 3798.23 A <br />Total Voltage Drop: -0.60 % <br />Incident Energy: 0.08 Cal/cm^2 <br />Working Distance: 18 inches <br />Arc Flash Boundary: 3 inches <br />Connected Load 23.90 kVA <br />CBL T-LQ(P) <br />1 Set(s) of: <br />#10 AWG Conductors, <br />#10 Ground Wire <br />In 3/4" Conduit <br />Length: 5.0 ft <br />HQ-1 <br />25.0 A Frame <br />25.0 A Trip <br />S <br />P <br />T-LQ <br />Fault at Device: 1327.01 A <br />Z% 2.78 % <br />LF VD% 0.07 % <br />Nominal kVA 15 kVA <br />Utilization 2.65 % <br />Pri Tap 0.00 % <br />Pri RatedVoltage 480 V <br />Sec RatedVoltage 208 V <br />CBL LQ <br />1 Set(s) of: <br />#6 AWG Conductors, <br />#8 Ground Wire <br />In 3/4" Conduit <br />Length: 5.0 ft <br />PANEL LQ <br />Fault at Device: 1296.92 A <br />Total Voltage Drop: -0.53 % <br />Incident Energy: 2.04 Cal/cm^2 <br />Working Distance: 18 inches <br />Arc Flash Boundary: 25 inches <br />Connected Load 0.40 kVA <br />LQ_MAIN <br />60.0 A Frame <br />60.0 A Trip <br />CBL HR <br />1 Set(s) of: <br />#3/0 AWG Conductors, <br />#4 Ground Wire <br />In 2" Conduit <br />Length: 760.0 ft <br />PANEL HR <br />Fault at Device: 3580.22 A <br />Total Voltage Drop: -0.39 % <br />Incident Energy: 0.1 Cal/cm^2 <br />Working Distance: 18 inches <br />Arc Flash Boundary: 4 inches <br />Connected Load 28.90 kVA <br />CBL T-LR(P) <br />1 Set(s) of: <br />#10 AWG Conductors, <br />#10 Ground Wire <br />In 3/4" Conduit <br />Length: 5.0 ft <br />HR-1 <br />25.0 A Frame <br />25.0 A Trip <br />S <br />P <br />T-LR <br />Fault at Device: 1312.16 A <br />Z% 2.78 % <br />LF VD% 0.09 % <br />Nominal kVA 15 kVA <br />Utilization 3.32 % <br />Pri Tap 0.00 % <br />Pri RatedVoltage 480 V <br />Sec RatedVoltage 208 V <br />CBL LR <br />1 Set(s) of: <br />#6 AWG Conductors, <br />#8 Ground Wire <br />In 3/4" Conduit <br />Length: 5.0 ft <br />LR_MAIN <br />60.0 A Frame <br />60.0 A Trip <br />CBL HT <br />1 Set(s) of: <br />#3/0 AWG Conductors, <br />#4 Ground Wire <br />In 2" Conduit <br />Length: 960.0 ft <br />S <br />P <br />T-LT <br />Fault at Device: 1265.29 A <br />Z% 2.78 % <br />LF VD% 0.07 % <br />Nominal kVA 15 kVA <br />Utilization 2.66 % <br />Pri Tap 0.00 % <br />Pri RatedVoltage 480 V <br />Sec RatedVoltage 208 V <br />CBL LT <br />1 Set(s) of: <br />#6 AWG Conductors, <br />#8 Ground Wire <br />In 3/4" Conduit <br />Length: 5.0 ft <br />LT_MAIN <br />60.0 A Frame <br />60.0 A Trip <br />PANEL LR <br />Fault at Device: 1283.13 A <br />Total Voltage Drop: -0.29 % <br />Incident Energy: 2.01 Cal/cm^2 <br />Working Distance: 18 inches <br />Arc Flash Boundary: 25 inches <br />Connected Load 0.50 kVA <br />PANEL LT <br />Fault at Device: 1238.20 A <br />Total Voltage Drop: -0.26 % <br />Incident Energy: 1.93 Cal/cm^2 <br />Working Distance: 18 inches <br />Arc Flash Boundary: 24 inches <br />Connected Load 0.40 kVA <br />PANEL HT <br />Fault at Device: 2900.93 A <br />Total Voltage Drop: -0.33 % <br />Incident Energy: 0.19 Cal/cm^2 <br />Working Distance: 18 inches <br />Arc Flash Boundary: 6 inches <br />Connected Load 24.30 kVA <br />HT-1 <br />25.0 A Frame <br />25.0 A Trip <br />CBL T-LT(P) <br />1 Set(s) of: <br />#10 AWG Conductors, <br />#10 Ground Wire <br />In 3/4" Conduit <br />Length: 5.0 ft <br />S <br />P <br />T-EV <br />Fault at Device: 5961.63 A <br />Z% 4.49 % <br />LF VD% 3.11 % <br />Nominal kVA 112.5 kVA <br />Utilization 72.75 % <br />Pri Tap 0.00 % <br />Pri RatedVoltage 480 V <br />Sec RatedVoltage 208 V <br />CBL EV <br />1 Set(s) of: <br />#600 kcmil Conductors, <br />#2 Ground Wire <br />In 3-1/2" Conduit <br />Length: 5.0 ft <br />EV_MAIN <br />60.0 A Frame <br />60.0 A Trip <br />PANEL EV <br />Fault at Device: 5888.53 A <br />Total Voltage Drop: 2.26 % <br />Incident Energy: 0.1 Cal/cm^2 <br />Working Distance: 18 inches <br />Arc Flash Boundary: 4 inches <br />Connected Load 80.00 kVA <br />CBL T-EV(P) <br />1 Set(s) of: <br />#2/0 AWG Conductors, <br />#6 Ground Wire <br />In 1 1/2" Conduit <br />Length: 100.0 ft <br />Fault at Device: 24559.95 A <br />Total Voltage Drop: -1.30 % <br />Incident Energy: 8.49 Cal/cm^2 <br />Working Distance: 18 inches <br />Arc Flash Boundary: 61 inches <br />Connected Load 416.00 kVA <br />PRIMARY METERING CABINET <br />SPARESPARE SPARE SPARE <br />MVSG-1 50/51-6 <br />Open <br />MVSG-1 52-6 <br />Rating 600.0 A <br />MVSG-1 50/51-3 <br />Open <br />MVSG-1 52-3 <br />Rating 600.0 A <br />MVSG-1 50/51-4 <br />Open <br />MVSG-1 52-4 <br />Rating 600.0 A <br />MVSG-1 50/51-5 <br />Open <br />MVSG-1 52-5 <br />Rating 600.0 A <br />MVSG-1 52-2 <br />MVSG-1 50/51-2 <br />GND <br />SW <br />89 <br />GND <br />SW <br />89 <br />GND <br />SW <br />89 <br />GND <br />SW <br />89 <br />GND <br />SW <br />89 <br />6" SPARE CONDUIT TO BE STUBBED <br />AND CAPPED ABOVE-GRADE (TYP.) <br />Rating 600.0 A <br />CBL MSB <br />6 Set(s) of: <br />4 - #400 kcmil (90° CU) Conductors, <br />1 - #1/0 CU Ground Wire <br />In 3" Conduit <br />Length: 90.0 ft <br />CBL MMA <br />2 Set(s) of: <br />8 - #400 kcmil (90° CU) Conductors, <br />1 - #2/0 CU Ground Wire <br />In 4" Conduit <br />Length: 115.0 ft <br />DLX8-XFMR-BLDG <br />S <br />P <br />BAYONET <br />Rating 100.0 A <br />CLF <br />Rating 165.0 A <br />GND <br />SW <br />89 <br />VOLTAGE <br />SENSING <br />CPT <br />Trip 125.0 A <br />DLX8-MVSG-1 <br />CBL DLX8-MVSG-1 <br />2 Set(s) of: <br />3 - #350 KCMIL AL Conductors (15kV, MV-105), <br />In 6" Conduit <br />Length: 20.0 ft <br />CBL DLX8-XFMR-BLDG <br />1 Set(s) of: <br />3 - #2 AL Conductors (15kV, MV-105), <br />1 - #6 CU (600V) Ground Wire <br />In 6" Conduit <br />Length: 20.0 ft <br />DLX8-MVSG-1 <br />600A, NEMA-3R, 6-WAYS <br />MV UNDERGROUND DISTRIBUTION SWITCHGEAR RATED: <br />12,500 AIC, 15.5kV, 3-PHASE, 4-WIRE, BIL 95kV <br />TEMP CBL GEN MSB <br />Length: 40.0 ft <br />2 Set(s) of: <br />4 - #350 kcmil Conductors, <br />1 - #1 AWG Ground Wire <br />TEMPORARY PORTABLE GENERATOR <br />480Y/277V, 3PH, 4W, 500KW <br />PROVIDE WITH 600A OVERCURRENT PROTECTION <br />TEMP CBL GEN MMA <br />Length: 60.0 ft <br />1 Set(s) of: <br />4 - #500 kcmil CU Conductors, <br />1 - #3 AWG CU Ground Wire <br />TEMPORARY PORTABLE GENERATOR <br />480Y/277V, 3PH, 4W, 320KW <br />PROVIDE WITH 400A OVERCURRENT PROTECTION <br />SECTION 1 SECTION 2 SECTION 3 SECTION 4 <br />12000V, 3PH, 3W, 600A, 60HZ, 40KA ASYM <br />KWH <br />PT О | SC FU PT <br />CT <br />TS1 <br />751 <br />SEL <br />TS1 <br />TS1 <br />SCTB <br />1A <br />FUPTFU <br />80A <br />MCCB <br />5A <br />FU <br />INTLK <br />TO INTERNAL 120V CIRCUITS <br />(HEATERS, LIGHTS & <br />RECEPTACLES) <br />12000V, 3PH, 3W, 600A, 60HZ, 40KA ASYM <br />PT ACCESS <br />KLKL <br />(2) <br />(2)DOOR <br />(2) <br />0.5E <br />UTILITY (SCE) <br />INCOMING CABLE SIZE <br />#500 KCMIL AL <br />CABLE/PH 1 <br />CT <br />600/5A <br />(3) <br />VCB-25KA <br />15KV, 600A <br />UTILITY PROVIDED <br />CT'S AND PT'S PER <br />UTILITY <br />REQUIREMENTS CT <br />SIZE: 10-800A <br />CPT-15KVA <br />12000V-120/240V <br />PT 12000V-120V <br />CPT <br />METER <br />UTILITY CUSTOMER <br />Line to Line Contribution: 6863.00 A <br />Line to Ground Contribution: 6349.00 A <br />Rated Voltage: 12000 V <br />Fault at Device: 6863.00 A <br />Total Voltage Drop: 0.61 % <br />Incident Energy: 15.85 Cal/cm^2 <br />Working Distance: 36 inches <br />Arc Flash Boundary: 187 inches <br />Connected Load 1058.70 kVA <br />Fault at Device: 6859.64 A <br />Total Voltage Drop: 0.61 % <br />Incident Energy: 15.85 Cal/cm^2 <br />Working Distance: 36 inches <br />Arc Flash Boundary: 187 inches <br />Connected Load 1058.70 kVA <br />Fault at Device: 27453.40 A <br />Z% 5.75 % <br />LF VD% -2.17 % <br />Nominal kVA 1500 kVA <br />Utilization 65.66 % <br />Pri Tap -5.00 % <br />Pri RatedVoltage 12000 V <br />Sec RatedVoltage 480 V <br />DLX8-MV-UMC <br />1 <br />3 <br />5 <br />7 <br />2 <br />10 <br />9 <br />8 <br />6 <br />12 <br />11 <br />4 <br />TEMPORARY POWER <br />CONNECTION. TO BE REMOVED <br />UPON PROJECT COMPLETION. <br />SEE IMPLEMENTATION PLAN. <br />TEMPORARY POWER <br />CONNECTION. TO BE REMOVED <br />UPON PROJECT COMPLETION. <br />SEE IMPLEMENTATION PLAN.13 <br />11 <br />GENERAL NOTES: <br />1. ALL FEEDERS ARE COPPER UNLESS NOTED OTHERWISE. <br />2. HALFTONE LINES DENOTES EQUIPMENT/FEEDERS ARE EXISTING <br />TO REMAIN. <br />3. IF POSSIBLE, UTILIZE EXISTING PROVISIONS FOR BUS TAPS <br />(INDICATED IN KEYNOTES #9 AND #11) WITHOUT REQUIRING <br />NEW HOLES OR MODIFICATIONS TO THE EXISTING <br />SWITCHBOARDS' EQUIPMENT. OTHERWISE, IF MODIFICATIONS <br />TO AN EXISTING SWITCHBOARDS' EQUIPMENT MUST BE MADE, <br />THEN THE ALTERED SWITCHBOARD(S) MUST BE RE-CERTIFIED <br />BY A FIELD EVALUATION BODY SUCH AS A NATIONALLY <br />RECOGNIZED TESTING LABORATORY (NRTL) PRIOR TO RE- <br />ENERGIZING WITH TEMPORARY OR UTILITY POWER. <br />#KEYNOTES: <br />1. CONNECTION TO UTILITY. SUPPLY VOLTAGE OF 12,000 VOLTS. <br />COORDINATE EXACT REQUIREMENTS WITH SERVING UTILITY, <br />SOUTH CALIFORNIA EDISON. <br />PHASE TO PHASE FAULT AVAILABLE (MAXIMUM) SHORT CIRCUIT <br />CURRENT: 6863 AMPERES (X/R = 4.90). <br />PHASE TO GROUND FAULT AVAILABLE (MAXIMUM) SHORT CIRCUIT <br />CURRENT: 6349 AMPERES (X/R = 2.08). <br />2. THE METERING SECTION REQUIRES PROVISIONS FOR (2) CTS, (2) <br />PTS AND (3) FUSES FOR METERING PHASES A & C ONLY, THUS <br />BUSBARS FOR PHASE B ARE REQUIRED. A 15-CLIP METER SOCKET IS <br />ACCEPTABLE. <br />3. PROVIDE ONE (1) SET OF THREE (3) #2 ALUMINUM, 15KV <br />CONDUCTORS AND ONE (1) #1 CU GROUND CONDUCTOR (600V) IN <br />6" CONDUIT. SEE DUCT BANK DETAIL FOR ADDITIONAL <br />INFORMATION. <br />4. REFER TO CONTROL POWER TRANSFORMER CONNECTION DETAIL <br />ON SHEET EV6.00. <br />5. PROVIDE ONE (1) SET OF THREE (3) #2 ALUMINUM, 15KV <br />CONDUCTORS AND ONE (1) #6 CU GROUND CONDUCTOR (600V) IN <br />6" CONDUIT. SEE DUCT BANK DETAIL FOR ADDITIONAL <br />INFORMATION. <br />6. MEDIUM-VOLTAGE TAP SWITCH, 4-POSITION T-BLADE, <br />SECTIONALIZING LOAD BREAK SWITCH. PROVIDE UNUSED <br />POSITION WITH 6" SPARE CONDUIT TO BE STUBBED AND CAPPED <br />ABOVE-GRADE. <br />7. PROVIDE SIX (6) SETS OF FOUR (4) #400KCMIL CU, AND ONE (1) <br />#1/0 AWG CU GROUND CONDUCTOR IN 3" CONDUIT. SEE DUCT <br />BANK DETAIL FOR ADDITIONAL INFORMATION. <br />8. PROVIDE TWO (2) SETS OF EIGHT (8) #400KCMIL CU, AND ONE (1) <br />#2/0 AWG CU GROUND CONDUCTOR IN 4" CONDUIT. SEE DUCT <br />BANK DETAIL FOR ADDITIONAL INFORMATION. <br />9. PROVIDE A BUS TAP ALONG THE EXISTING MAIN SWITCHBOARD <br />BUS FOR A TEMPORARY 600-AMPERE CONNECTION. <br />10. PROVIDE TWO (2) SETS OF FOUR (4) #350KCMIL CU, AND ONE (1) <br />#1 CU GROUND CONDUCTOR FOR TEMPORARY POWER <br />CONNECTION. PROVIDE #2/0 AWG CU GROUNDING ELECTRODE <br />CONDUCTOR AND REFER TO GENERATOR GROUNDING DETAIL ON <br />SHEET EV6.00 FOR ADDTIONAL INFORMATION. PROVIDE <br />PROTECTION AND SUPPORT AS REQUIRED BY CEC 590.4. <br />11. PROVIDE A BUS TAP ALONG THE EXISTING MAIN SWITCHBOARD <br />BUS FOR A TEMPORARY 400-AMPERE CONNECTION. <br />12. PROVIDE ONE (1) SET OF FOUR (4) #500KCMIL CU, AND ONE (1) <br />#3 AWG CU GROUND CONDUCTOR FOR TEMPORARY POWER <br />CONNECTION. PROVIDE #1/0 AWG CU GROUNDING ELECTRODE <br />CONDUCTOR AND REFER TO GENERATOR GROUNDING DETAIL ON <br />SHEET EV6.00 FOR ADDTIONAL INFORMATION. PROVIDE <br />PROTECTION AND SUPPORT AS REQUIRED BY CEC 590.4. <br />13. CONTRACTOR TO PROVIDE APPROPRIATE STACKED LUGS FOR <br />SECONDARY CONDUCTORS. <br />AT NO POINT SHOULD AN ENERGIZED TRANSFORMER AND A <br />GENERATOR BE CONNECTED TO THE SAME BUS. <br />1. THE EXISTING ELECTRICAL DISTRIBUTION SYSTEM FOR THE <br />BUILDING SHALL REMAIN IN SERVICE UNTIL ALL COMPONENTS OF <br />THE TEMPORARY POWER CONNECTIONS, EXCEPT FOR THE BUS <br />TAP AND ENERGIZATION OF THE GENERATORS, ARE PROVIDED. <br />2. CONTRACTOR TO COORDINATE OUTAGE FOR THE BUILDING WITH <br />OWNER AND UTILITY. <br />3. DEACTIVATE (SWITCH OFF) THE EXISTING SWITCHBOARDS' <br />("MSB" & "MMA") MAIN CIRCUIT BREAKER AND LOCKOUT IN THE <br />OPEN POSITION (PROVIDE LOCKOUT AS REQUIRED). <br />4. AFTER EXISTING BUILDING TRANSFORMER HAS BEEN <br />DE-ENERGIZED, PROVIDE BUS TAPS TO EXISTING SWITCHBOARDS. <br />5. FINALIZE TEMPORARY CONNECTIONS AND ENERGIZE TEMPORARY <br />GENERATORS. <br />6. UPON PROJECT COMPLETION, CONTRACTOR TO COORDINATE <br />OUTAGE FOR THE BUILDING WITH OWNER. DE-ENERGIZE AND <br />REMOVE TEMPORARY GENERATORS. <br />7. DISCONNECT AND REMOVE ALL COMPONENTS OF THE TEMPORARY <br />POWER CONNECTIONS. <br />8. UNLOCK AND ACTIVATE (SWITCH ON) EXISTING MAIN CIRCUIT <br />BREAKERS. <br />IMPLEMENTATION PLAN: <br />448 South Hill Street <br />Suite 1001 <br />Los Angeles, CA 90013 <br />Phone: 310-975-2061 <br />Reviewed By:Proj #: <br />140 Newport Center Drive, <br />Suite 100 <br />Newport Beach, CA 92660 <br />O: 949.478.8800 <br />www.kpff.com <br />KPFF <br />9/ <br />1 <br />9 <br />/ <br />2 <br />0 <br />2 <br />5 <br /> <br />2 <br />: <br />0 <br />8 <br />: <br />3 <br />7 <br /> <br />P <br />M <br /> <br />A <br />u <br />t <br />o <br />d <br />e <br />s <br />k <br /> <br />D <br />o <br />c <br />s <br />: <br />/ <br />/ <br />D <br />L <br />X <br />8 <br />/ <br />D <br />L <br />X <br />8 <br />_ <br />M <br />E <br />P <br />. <br />r <br />vt <br />EV6.01 <br />ONE-LINE DIAGRAM - <br />ELECTRICAL <br />DLX8_EVSG <br />515 E Dyer Rd, Santa Ana, CA 92707 <br />Owner <br />NM23.0003320.000 <br />1416 NW 46TH Street <br />Suite 105-138 <br />Seattle, WA 98107 <br />WWW.NELSONWORLDWIDE.COM <br />Phone: (206) 408-8501 <br />Nelco Architecture, Inc. <br />NOT TO SCALEEV6.01 <br />1 ELECTRICAL ONE-LINE DIAGRAM <br />Issue: No: Date: <br />CD 30 2023/11/03 <br />CD 50 2024/05/22 <br />CD 90 2025/03/11 <br />Issue for Permit 2025/04/21 <br />Plan Check Repsonse 1 1 2025/09/19 <br />1 <br />1 <br />1 <br />1 <br />9-24-2025