Distribution Panel "DP"
<br />LB_1
<br />Rating 100.0 A
<br />CBL LB1
<br />1 Set(s) of:
<br />#2 AWG Conductors,
<br />#6 Ground Wire
<br />In 1 1/4" Conduit
<br />Length: 5.0 ft
<br />Switchboard "MSB"
<br />CBL DP
<br />3 Set(s) of:
<br />#600 kcmil Conductors,
<br />#4/0 Ground Wire
<br />In 3" Conduit
<br />Length: 20.0 ft
<br />PD-H
<br />Rating 200.0 A
<br />PD-A
<br />Rating 400.0 A
<br />PD-B
<br />Rating 200.0 A
<br />PD-C
<br />Rating 200.0 A
<br />PD-E
<br />Rating 200.0 A
<br />PD-F
<br />Rating 200.0 A
<br />PD-G
<br />Rating 200.0 A
<br />PD-J
<br />Rating 200.0 A
<br />PD-K
<br />Rating 200.0 A
<br />PD-L
<br />Rating 200.0 A
<br />PD-M
<br />Rating 200.0 A
<br />PD-DP
<br />Rating 1000.0 A
<br />MSB-MPD
<br />Rating 2000.0 A
<br />PD-N
<br />Rating 100.0 A
<br />PD-Q
<br />Rating 100.0 A
<br />PD-R
<br />Rating 100.0 A
<br />PD-T
<br />Rating 100.0 A
<br />PD-EV
<br />Rating 175.0 A
<br />MMA-MPD
<br />Rating 1200.0 A
<br />Switchboard "MMA"
<br />PANEL LB1
<br />EXISTING SWITCHBOARD "MSB"
<br />480Y/277V, 3PH, 4W, 2000A, 65KAIC
<br />EXISTING SWITCHBOARD "MMA"
<br />480Y/277V, 3PH, 4W, 1200A, 100KAIC
<br />(SET AT 175.0A)(SET AT 175.0A)
<br />Fault at Device: 25192.88 A
<br />Total Voltage Drop: -1.30 %
<br />Incident Energy: 8.05 Cal/cm^2
<br />Working Distance: 18 inches
<br />Arc Flash Boundary: 59 inches
<br />Connected Load 392.80 kVA
<br />CBL HA
<br />2 Set(s) of:
<br />#3/0 AWG Conductors,
<br />#2 Ground Wire
<br />In 2" Conduit
<br />Length: 400.0 ft
<br />PANEL HA
<br />Fault at Device: 10070.44 A
<br />Total Voltage Drop: 0.67 %
<br />Incident Energy: 1.26 Cal/cm^2
<br />Working Distance: 18 inches
<br />Arc Flash Boundary: 19 inches
<br />Connected Load 232.00 kVA
<br />CBL T-MDF(P)
<br />1 Set(s) of:
<br />#4 AWG Conductors,
<br />#8 Ground Wire
<br />In 1" Conduit
<br />Length: 120.0 ft
<br />HA-CB1
<br />70.0 A Frame
<br />70.0 A Trip
<br />S
<br />P
<br />T-MDF
<br />Fault at Device: 2847.31 A
<br />Z% 3.37 %
<br />LF VD% 2.81 %
<br />Nominal kVA 45 kVA
<br />Utilization 83.43 %
<br />Pri Tap 0.00 %
<br />Pri RatedVoltage 480 V
<br />Sec RatedVoltage 208 V
<br />CBL MDF
<br />1 Set(s) of:
<br />#1/0 AWG Conductors,
<br />#6 Ground Wire
<br />In 1 1/2" Conduit
<br />Length: 5.0 ft
<br />PANEL MDF
<br />Fault at Device: 2804.17 A
<br />Total Voltage Drop: 4.11 %
<br />Incident Energy: 4.89 Cal/cm^2
<br />Working Distance: 18 inches
<br />Arc Flash Boundary: 43 inches
<br />Connected Load 36.00 kVA
<br />MDF_MAIN
<br />150.0 A Frame
<br />150.0 A Trip
<br />CBL HB
<br />1 Set(s) of:
<br />#3/0 AWG Conductors,
<br />#4 Ground Wire
<br />In 2" Conduit
<br />Length: 240.0 ft
<br />PANEL HB
<br />Fault at Device: 9031.24 A
<br />Total Voltage Drop: -0.80 %
<br />Incident Energy: 0.24 Cal/cm^2
<br />Working Distance: 18 inches
<br />Arc Flash Boundary: 7 inches
<br />Connected Load 50.00 kVA
<br />CBL T-LB(P)
<br />1 Set(s) of:
<br />#2 AWG Conductors,
<br />#6 Ground Wire
<br />In 1 1/4" Conduit
<br />Length: 5.0 ft
<br />HB-1
<br />100.0 A Frame
<br />100.0 A Trip
<br />S
<br />P
<br />T-LB
<br />Fault at Device: 5118.35 A
<br />Z% 3.20 %
<br />LF VD% 0.28 %
<br />Nominal kVA 75 kVA
<br />Utilization 8.89 %
<br />Pri Tap 0.00 %
<br />Pri RatedVoltage 480 V
<br />Sec RatedVoltage 208 V
<br />CBL LB
<br />1 Set(s) of:
<br />#4/0 AWG Conductors,
<br />#4 Ground Wire
<br />In 2" Conduit
<br />Length: 5.0 ft
<br />PANEL LB
<br />Fault at Device: 5035.98 A
<br />Total Voltage Drop: -0.51 %
<br />Incident Energy: 9.57 Cal/cm^2
<br />Working Distance: 18 inches
<br />Arc Flash Boundary: 66 inches
<br />Connected Load 6.70 kVA
<br />LB_MAIN
<br />225.0 A Frame
<br />225.0 A Trip
<br />Fault at Device: 4852.63 A
<br />Total Voltage Drop: -0.50 %
<br />Incident Energy: 9.17 Cal/cm^2
<br />Working Distance: 18 inches
<br />Arc Flash Boundary: 64 inches
<br />Connected Load 5.70 kVA
<br />CBL HC
<br />1 Set(s) of:
<br />#4/0 AWG Conductors,
<br />#4 Ground Wire
<br />In 2" Conduit
<br />Length: 540.0 ft
<br />PANEL HC
<br />Fault at Device: 5510.56 A
<br />Total Voltage Drop: 0.48 %
<br />Incident Energy: 0.97 Cal/cm^2
<br />Working Distance: 18 inches
<br />Arc Flash Boundary: 16 inches
<br />Connected Load 94.50 kVA
<br />CBL T-LC(P)
<br />1 Set(s) of:
<br />#2 AWG Conductors,
<br />#6 Ground Wire
<br />In 1 1/4" Conduit
<br />Length: 5.0 ft
<br />HC-1
<br />100.0 A Frame
<br />100.0 A Trip
<br />S
<br />P T-LC
<br />Fault at Device: 4423.26 A
<br />Z% 3.20 %
<br />LF VD% 2.08 %
<br />Nominal kVA 75 kVA
<br />Utilization 65.04 %
<br />Pri Tap 0.00 %
<br />Pri RatedVoltage 480 V
<br />Sec RatedVoltage 208 V
<br />CBL LC
<br />1 Set(s) of:
<br />#4/0 AWG Conductors,
<br />#4 Ground Wire
<br />In 2" Conduit
<br />Length: 5.0 ft
<br />PANEL LC
<br />Fault at Device: 4361.62 A
<br />Total Voltage Drop: 2.62 %
<br />Incident Energy: 0.07 Cal/cm^2
<br />Working Distance: 18 inches
<br />Arc Flash Boundary: 3 inches
<br />Connected Load 47.50 kVA
<br />LC_MAIN
<br />60.0 A Frame
<br />60.0 A Trip
<br />CBL HG
<br />1 Set(s) of:
<br />#2/0 AWG Conductors,
<br />#6 Ground Wire
<br />In 2" Conduit
<br />Length: 850.0 ft
<br />PANEL HG
<br />Fault at Device: 2759.72 A
<br />Total Voltage Drop: 0.05 %
<br />Incident Energy: 4.15 Cal/cm^2
<br />Working Distance: 18 inches
<br />Arc Flash Boundary: 39 inches
<br />Connected Load 32.20 kVA
<br />CBL T-LG(P)
<br />1 Set(s) of:
<br />#2 AWG Conductors,
<br />#6 Ground Wire
<br />In 1 1/4" Conduit
<br />Length: 5.0 ft
<br />HG-1
<br />100.0 A Frame
<br />100.0 A Trip
<br />S
<br />P
<br />T-LG
<br />Fault at Device: 3291.06 A
<br />Z% 3.20 %
<br />LF VD% 0.09 %
<br />Nominal kVA 75 kVA
<br />Utilization 2.94 %
<br />Pri Tap 0.00 %
<br />Pri RatedVoltage 480 V
<br />Sec RatedVoltage 208 V
<br />CBL LG
<br />1 Set(s) of:
<br />#4/0 AWG Conductors,
<br />#4 Ground Wire
<br />In 2" Conduit
<br />Length: 5.0 ft
<br />LG
<br />Fault at Device: 3256.72 A
<br />Total Voltage Drop: 0.15 %
<br />Incident Energy: 5.8 Cal/cm^2
<br />Working Distance: 18 inches
<br />Arc Flash Boundary: 48 inches
<br />Connected Load 2.20 kVA
<br />LG_MAIN
<br />225.0 A Frame
<br />225.0 A Trip
<br />CBL HH
<br />2 Set(s) of:
<br />#4/0 AWG Conductors,
<br />#1 Ground Wire
<br />In 2" Conduit
<br />Length: 980.0 ft
<br />PANEL HH
<br />Fault at Device: 5884.12 A
<br />Total Voltage Drop: 1.46 %
<br />Incident Energy: 0.84 Cal/cm^2
<br />Working Distance: 18 inches
<br />Arc Flash Boundary: 14 inches
<br />Connected Load 150.90 kVA
<br />CBL T-LH(P)
<br />1 Set(s) of:
<br />#2 AWG Conductors,
<br />#6 Ground Wire
<br />In 1 1/4" Conduit
<br />Length: 5.0 ft
<br />HH-1
<br />100.0 A Frame
<br />100.0 A Trip
<br />S
<br />P
<br />T-LH
<br />Fault at Device: 4524.08 A
<br />Z% 3.20 %
<br />LF VD% 0.91 %
<br />Nominal kVA 75 kVA
<br />Utilization 28.42 %
<br />Pri Tap 0.00 %
<br />Pri RatedVoltage 480 V
<br />Sec RatedVoltage 208 V
<br />CBL LH
<br />1 Set(s) of:
<br />#4/0 AWG Conductors,
<br />#4 Ground Wire
<br />In 2" Conduit
<br />Length: 5.0 ft
<br />PANEL LH
<br />Fault at Device: 4459.64 A
<br />Total Voltage Drop: 2.40 %
<br />Incident Energy: 8.33 Cal/cm^2
<br />Working Distance: 18 inches
<br />Arc Flash Boundary: 60 inches
<br />Connected Load 20.80 kVA
<br />LH_MAIN
<br />225.0 A Frame
<br />225.0 A Trip
<br />CBL HJ
<br />2 Set(s) of:
<br />#3/0 AWG Conductors,
<br />#2 Ground Wire
<br />In 2" Conduit
<br />Length: 750.0 ft
<br />PANEL HJ
<br />Fault at Device: 6439.87 A
<br />Total Voltage Drop: -0.78 %
<br />Incident Energy: 0.65 Cal/cm^2
<br />Working Distance: 18 inches
<br />Arc Flash Boundary: 12 inches
<br />Connected Load 33.10 kVA
<br />CBL T-LJ(P)
<br />1 Set(s) of:
<br />#2 AWG Conductors,
<br />#6 Ground Wire
<br />In 1 1/4" Conduit
<br />Length: 5.0 ft
<br />HJ-1
<br />100.0 A Frame
<br />100.0 A Trip
<br />S
<br />P
<br />T-LJ
<br />Fault at Device: 4653.73 A
<br />Z% 3.20 %
<br />LF VD% 0.66 %
<br />Nominal kVA 75 kVA
<br />Utilization 20.65 %
<br />Pri Tap 0.00 %
<br />Pri RatedVoltage 480 V
<br />Sec RatedVoltage 208 V
<br />CBL LJ
<br />1 Set(s) of:
<br />#4/0 AWG Conductors,
<br />#4 Ground Wire
<br />In 2" Conduit
<br />Length: 5.0 ft
<br />PANEL LJ
<br />Fault at Device: 4585.47 A
<br />Total Voltage Drop: -0.10 %
<br />Incident Energy: 8.6 Cal/cm^2
<br />Working Distance: 18 inches
<br />Arc Flash Boundary: 62 inches
<br />Connected Load 15.50 kVA
<br />LJ_MAIN
<br />225.0 A Frame
<br />225.0 A Trip
<br />CBL HK
<br />1 Set(s) of:
<br />#4/0 AWG Conductors,
<br />#4 Ground Wire
<br />In 2" Conduit
<br />Length: 550.0 ft
<br />PANEL HK
<br />Fault at Device: 5428.24 A
<br />Total Voltage Drop: -0.05 %
<br />Incident Energy: 1.01 Cal/cm^2
<br />Working Distance: 18 inches
<br />Arc Flash Boundary: 16 inches
<br />Connected Load 67.00 kVA
<br />CBL T-LK(P)
<br />1 Set(s) of:
<br />#2 AWG Conductors,
<br />#6 Ground Wire
<br />In 1 1/4" Conduit
<br />Length: 5.0 ft
<br />HK-1
<br />100.0 A Frame
<br />100.0 A Trip
<br />S
<br />P
<br />T-LK
<br />Fault at Device: 4399.91 A
<br />Z% 3.20 %
<br />LF VD% 0.29 %
<br />Nominal kVA 75 kVA
<br />Utilization 8.96 %
<br />Pri Tap 0.00 %
<br />Pri RatedVoltage 480 V
<br />Sec RatedVoltage 208 V
<br />CBL LK
<br />1 Set(s) of:
<br />#4/0 AWG Conductors,
<br />#4 Ground Wire
<br />In 2" Conduit
<br />Length: 5.0 ft
<br />PANEL LK
<br />Fault at Device: 4338.91 A
<br />Total Voltage Drop: 0.25 %
<br />Incident Energy: 8.07 Cal/cm^2
<br />Working Distance: 18 inches
<br />Arc Flash Boundary: 59 inches
<br />Connected Load 6.70 kVA
<br />LK_MAIN
<br />225.0 A Frame
<br />225.0 A Trip
<br />CBL HL
<br />1 Set(s) of:
<br />#3/0 AWG Conductors,
<br />#4 Ground Wire
<br />In 2" Conduit
<br />Length: 320.0 ft
<br />PANEL HL
<br />Fault at Device: 7389.10 A
<br />Total Voltage Drop: -0.53 %
<br />Incident Energy: 0.44 Cal/cm^2
<br />Working Distance: 18 inches
<br />Arc Flash Boundary: 10 inches
<br />Connected Load 61.60 kVA
<br />CBL T-LL(P)
<br />1 Set(s) of:
<br />#2 AWG Conductors,
<br />#6 Ground Wire
<br />In 1 1/4" Conduit
<br />Length: 5.0 ft
<br />HL-1
<br />100.0 A Frame
<br />100.0 A Trip
<br />S
<br />P
<br />T-LL
<br />Fault at Device: 4849.89 A
<br />Z% 3.20 %
<br />LF VD% 1.11 %
<br />Nominal kVA 75 kVA
<br />Utilization 34.75 %
<br />Pri Tap 0.00 %
<br />Pri RatedVoltage 480 V
<br />Sec RatedVoltage 208 V
<br />CBL LL
<br />1 Set(s) of:
<br />#4/0 AWG Conductors,
<br />#4 Ground Wire
<br />In 2" Conduit
<br />Length: 5.0 ft
<br />PANEL LL
<br />Fault at Device: 4775.83 A
<br />Total Voltage Drop: 0.62 %
<br />Incident Energy: 9.01 Cal/cm^2
<br />Working Distance: 18 inches
<br />Arc Flash Boundary: 64 inches
<br />Connected Load 25.90 kVA
<br />LL_MAIN
<br />225.0 A Frame
<br />225.0 A Trip
<br />CBL HM
<br />1 Set(s) of:
<br />#3/0 AWG Conductors,
<br />#4 Ground Wire
<br />In 2" Conduit
<br />Length: 75.0 ft
<br />PANEL HM
<br />Fault at Device: 16997.35 A
<br />Total Voltage Drop: -1.26 %
<br />Incident Energy: 0.3 Cal/cm^2
<br />Working Distance: 18 inches
<br />Arc Flash Boundary: 8 inches
<br />Connected Load 26.80 kVA
<br />CBL T-LM(P)
<br />1 Set(s) of:
<br />#2 AWG Conductors,
<br />#6 Ground Wire
<br />In 1 1/4" Conduit
<br />Length: 5.0 ft
<br />HM-1
<br />100.0 A Frame
<br />100.0 A Trip
<br />S
<br />P
<br />T-LM
<br />Fault at Device: 5819.29 A
<br />Z% 3.20 %
<br />LF VD% 0.33 %
<br />Nominal kVA 75 kVA
<br />Utilization 10.31 %
<br />Pri Tap 0.00 %
<br />Pri RatedVoltage 480 V
<br />Sec RatedVoltage 208 V
<br />CBL LM
<br />1 Set(s) of:
<br />#4/0 AWG Conductors,
<br />#4 Ground Wire
<br />In 2" Conduit
<br />Length: 5.0 ft
<br />PANEL LM
<br />Fault at Device: 5713.25 A
<br />Total Voltage Drop: -0.92 %
<br />Incident Energy: 11.07 Cal/cm^2
<br />Working Distance: 18 inches
<br />Arc Flash Boundary: 72 inches
<br />Connected Load 7.80 kVA
<br />LM_MAIN
<br />225.0 A Frame
<br />225.0 A Trip
<br />Fault at Device: 25807.74 A
<br />Total Voltage Drop: -1.34 %
<br />Incident Energy: 28.95 Cal/cm^2
<br />Working Distance: 18 inches
<br />Arc Flash Boundary: 132 inches
<br />Connected Load 642.70 kVA
<br />CBL T-LA(P)
<br />1 Set(s) of:
<br />#2/0 AWG Conductors,
<br />#6 Ground Wire
<br />In 1 1/2" Conduit
<br />Length: 5.0 ft
<br />HA-CB2
<br />175.0 A Frame
<br />175.0 A Trip
<br />S
<br />P
<br />T-LA
<br />Fault at Device: 5548.10 A
<br />Z% 4.49 %
<br />LF VD% 2.75 %
<br />Nominal kVA 112.5 kVA
<br />Utilization 64.49 %
<br />Pri Tap 0.00 %
<br />Pri RatedVoltage 480 V
<br />Sec RatedVoltage 208 V
<br />CBL LA
<br />1 Set(s) of:
<br />#600 kcmil Conductors,
<br />#2 Ground Wire
<br />In 3-1/2" Conduit
<br />Length: 5.0 ft
<br />LA_MAIN
<br />400.0 A Frame
<br />400.0 A Trip
<br />PANEL LA
<br />Fault at Device: 5484.87 A
<br />Total Voltage Drop: 3.48 %
<br />Incident Energy: 10.56 Cal/cm^2
<br />Working Distance: 18 inches
<br />Arc Flash Boundary: 70 inches
<br />Connected Load 70.00 kVA
<br />CBL LA1
<br />1 Set(s) of:
<br />#2 AWG Conductors,
<br />#6 Ground Wire
<br />In 1 1/4" Conduit
<br />Length: 5.0 ft
<br />PANEL LA1
<br />Fault at Device: 5291.62 A
<br />Total Voltage Drop: 3.56 %
<br />Incident Energy: 10.13 Cal/cm^2
<br />Working Distance: 18 inches
<br />Arc Flash Boundary: 68 inches
<br />Connected Load 34.20 kVA
<br />LA_1
<br />200.0 A Frame
<br />200.0 A Trip
<br />CBL HE
<br />1 Set(s) of:
<br />#3/0 AWG Conductors,
<br />#4 Ground Wire
<br />In 2" Conduit
<br />Length: 410.0 ft
<br />PANEL HE
<br />Fault at Device: 6047.53 A
<br />Total Voltage Drop: -0.01 %
<br />Incident Energy: 0.78 Cal/cm^2
<br />Working Distance: 18 inches
<br />Arc Flash Boundary: 14 inches
<br />Connected Load 74.70 kVA
<br />CBL T-LE(P)
<br />1 Set(s) of:
<br />#2 AWG Conductors,
<br />#6 Ground Wire
<br />In 1 1/4" Conduit
<br />Length: 5.0 ft
<br />HE-1
<br />100.0 A Frame
<br />100.0 A Trip
<br />S
<br />P
<br />T-LE
<br />Fault at Device: 4560.65 A
<br />Z% 3.20 %
<br />LF VD% 2.30 %
<br />Nominal kVA 75 kVA
<br />Utilization 71.97 %
<br />Pri Tap 0.00 %
<br />Pri RatedVoltage 480 V
<br />Sec RatedVoltage 208 V
<br />CBL LE
<br />1 Set(s) of:
<br />#4/0 AWG Conductors,
<br />#4 Ground Wire
<br />In 2" Conduit
<br />Length: 5.0 ft
<br />PANEL LE
<br />Fault at Device: 4495.06 A
<br />Total Voltage Drop: 2.37 %
<br />Incident Energy: 8.4 Cal/cm^2
<br />Working Distance: 18 inches
<br />Arc Flash Boundary: 61 inches
<br />Connected Load 52.70 kVA
<br />LE_MAIN
<br />225.0 A Frame
<br />225.0 A Trip
<br />CBL HF
<br />2 Set(s) of:
<br />#2/0 AWG Conductors,
<br />#3 Ground Wire
<br />In 2" Conduit
<br />Length: 640.0 ft
<br />PANEL HF
<br />Fault at Device: 6452.78 A
<br />Total Voltage Drop: -0.52 %
<br />Incident Energy: 0.65 Cal/cm^2
<br />Working Distance: 18 inches
<br />Arc Flash Boundary: 12 inches
<br />Connected Load 49.20 kVA
<br />CBL T-LF(P)
<br />1 Set(s) of:
<br />#2 AWG Conductors,
<br />#6 Ground Wire
<br />In 1 1/4" Conduit
<br />Length: 5.0 ft
<br />HF-1
<br />100.0 A Frame
<br />100.0 A Trip
<br />S
<br />P
<br />T-LF
<br />Fault at Device: 4656.24 A
<br />Z% 3.20 %
<br />LF VD% 0.38 %
<br />Nominal kVA 75 kVA
<br />Utilization 11.98 %
<br />Pri Tap 0.00 %
<br />Pri RatedVoltage 480 V
<br />Sec RatedVoltage 208 V
<br />CBL LF
<br />1 Set(s) of:
<br />#4/0 AWG Conductors,
<br />#4 Ground Wire
<br />In 2" Conduit
<br />Length: 5.0 ft
<br />PANEL LF
<br />Fault at Device: 4587.83 A
<br />Total Voltage Drop: -0.13 %
<br />Incident Energy: 8.6 Cal/cm^2
<br />Working Distance: 18 inches
<br />Arc Flash Boundary: 62 inches
<br />Connected Load 9.00 kVA
<br />LF_MAIN
<br />225.0 A Frame
<br />225.0 A Trip
<br />CBL T-HEV(P)
<br />1 Set(s) of:
<br />#2/0 AWG Conductors,
<br />#6 Ground Wire
<br />In 1 1/2" Conduit
<br />Length: 100.0 ft
<br />HH-2
<br />175.0 A Frame
<br />175.0 A Trip
<br />S
<br />P
<br />T-HEV
<br />Fault at Device: 4437.30 A
<br />Z% 4.49 %
<br />LF VD% 4.70 %
<br />Nominal kVA 112.5 kVA
<br />Utilization 109.91 %
<br />Pri Tap 0.00 %
<br />Pri RatedVoltage 480 V
<br />Sec RatedVoltage 208 V
<br />CBL HEV
<br />1 Set(s) of:
<br />#600 kcmil Conductors,
<br />#2 Ground Wire
<br />In 3-1/2" Conduit
<br />Length: 5.0 ft
<br />PANEL HEV
<br />Fault at Device: 4397.13 A
<br />Total Voltage Drop: 6.84 %
<br />Incident Energy: 8.19 Cal/cm^2
<br />Working Distance: 18 inches
<br />Arc Flash Boundary: 60 inches
<br />Connected Load 115.20 kVA
<br />HEV_MAIN
<br />400.0 A Frame
<br />400.0 A Trip
<br />CBL HN
<br />1 Set(s) of:
<br />#1/0 AWG Conductors,
<br />#6 Ground Wire
<br />In 1 1/2" Conduit
<br />Length: 560.0 ft
<br />PANEL HN
<br />Fault at Device: 3428.64 A
<br />Total Voltage Drop: -0.33 %
<br />Incident Energy: 0.11 Cal/cm^2
<br />Working Distance: 18 inches
<br />Arc Flash Boundary: 4 inches
<br />Connected Load 29.60 kVA
<br />CBL T-LN(P)
<br />1 Set(s) of:
<br />#10 AWG Conductors,
<br />#10 Ground Wire
<br />In 3/4" Conduit
<br />Length: 5.0 ft
<br />HN-1
<br />25.0 A Frame
<br />25.0 A Trip
<br />S
<br />P
<br />T-LN
<br />Fault at Device: 1306.36 A
<br />Z% 2.78 %
<br />LF VD% 0.22 %
<br />Nominal kVA 15 kVA
<br />Utilization 7.99 %
<br />Pri Tap 0.00 %
<br />Pri RatedVoltage 480 V
<br />Sec RatedVoltage 208 V
<br />CBL LN
<br />1 Set(s) of:
<br />#6 AWG Conductors,
<br />#8 Ground Wire
<br />In 3/4" Conduit
<br />Length: 5.0 ft
<br />PANEL LN
<br />Fault at Device: 1277.12 A
<br />Total Voltage Drop: -0.10 %
<br />Incident Energy: 2 Cal/cm^2
<br />Working Distance: 18 inches
<br />Arc Flash Boundary: 25 inches
<br />Connected Load 1.20 kVA
<br />LN_MAIN
<br />60.0 A Frame
<br />60.0 A Trip
<br />CBL HQ
<br />1 Set(s) of:
<br />#1/0 AWG Conductors,
<br />#6 Ground Wire
<br />In 1 1/2" Conduit
<br />Length: 500.0 ft
<br />PANEL HQ
<br />Fault at Device: 3798.23 A
<br />Total Voltage Drop: -0.60 %
<br />Incident Energy: 0.08 Cal/cm^2
<br />Working Distance: 18 inches
<br />Arc Flash Boundary: 3 inches
<br />Connected Load 23.90 kVA
<br />CBL T-LQ(P)
<br />1 Set(s) of:
<br />#10 AWG Conductors,
<br />#10 Ground Wire
<br />In 3/4" Conduit
<br />Length: 5.0 ft
<br />HQ-1
<br />25.0 A Frame
<br />25.0 A Trip
<br />S
<br />P
<br />T-LQ
<br />Fault at Device: 1327.01 A
<br />Z% 2.78 %
<br />LF VD% 0.07 %
<br />Nominal kVA 15 kVA
<br />Utilization 2.65 %
<br />Pri Tap 0.00 %
<br />Pri RatedVoltage 480 V
<br />Sec RatedVoltage 208 V
<br />CBL LQ
<br />1 Set(s) of:
<br />#6 AWG Conductors,
<br />#8 Ground Wire
<br />In 3/4" Conduit
<br />Length: 5.0 ft
<br />PANEL LQ
<br />Fault at Device: 1296.92 A
<br />Total Voltage Drop: -0.53 %
<br />Incident Energy: 2.04 Cal/cm^2
<br />Working Distance: 18 inches
<br />Arc Flash Boundary: 25 inches
<br />Connected Load 0.40 kVA
<br />LQ_MAIN
<br />60.0 A Frame
<br />60.0 A Trip
<br />CBL HR
<br />1 Set(s) of:
<br />#3/0 AWG Conductors,
<br />#4 Ground Wire
<br />In 2" Conduit
<br />Length: 760.0 ft
<br />PANEL HR
<br />Fault at Device: 3580.22 A
<br />Total Voltage Drop: -0.39 %
<br />Incident Energy: 0.1 Cal/cm^2
<br />Working Distance: 18 inches
<br />Arc Flash Boundary: 4 inches
<br />Connected Load 28.90 kVA
<br />CBL T-LR(P)
<br />1 Set(s) of:
<br />#10 AWG Conductors,
<br />#10 Ground Wire
<br />In 3/4" Conduit
<br />Length: 5.0 ft
<br />HR-1
<br />25.0 A Frame
<br />25.0 A Trip
<br />S
<br />P
<br />T-LR
<br />Fault at Device: 1312.16 A
<br />Z% 2.78 %
<br />LF VD% 0.09 %
<br />Nominal kVA 15 kVA
<br />Utilization 3.32 %
<br />Pri Tap 0.00 %
<br />Pri RatedVoltage 480 V
<br />Sec RatedVoltage 208 V
<br />CBL LR
<br />1 Set(s) of:
<br />#6 AWG Conductors,
<br />#8 Ground Wire
<br />In 3/4" Conduit
<br />Length: 5.0 ft
<br />LR_MAIN
<br />60.0 A Frame
<br />60.0 A Trip
<br />CBL HT
<br />1 Set(s) of:
<br />#3/0 AWG Conductors,
<br />#4 Ground Wire
<br />In 2" Conduit
<br />Length: 960.0 ft
<br />S
<br />P
<br />T-LT
<br />Fault at Device: 1265.29 A
<br />Z% 2.78 %
<br />LF VD% 0.07 %
<br />Nominal kVA 15 kVA
<br />Utilization 2.66 %
<br />Pri Tap 0.00 %
<br />Pri RatedVoltage 480 V
<br />Sec RatedVoltage 208 V
<br />CBL LT
<br />1 Set(s) of:
<br />#6 AWG Conductors,
<br />#8 Ground Wire
<br />In 3/4" Conduit
<br />Length: 5.0 ft
<br />LT_MAIN
<br />60.0 A Frame
<br />60.0 A Trip
<br />PANEL LR
<br />Fault at Device: 1283.13 A
<br />Total Voltage Drop: -0.29 %
<br />Incident Energy: 2.01 Cal/cm^2
<br />Working Distance: 18 inches
<br />Arc Flash Boundary: 25 inches
<br />Connected Load 0.50 kVA
<br />PANEL LT
<br />Fault at Device: 1238.20 A
<br />Total Voltage Drop: -0.26 %
<br />Incident Energy: 1.93 Cal/cm^2
<br />Working Distance: 18 inches
<br />Arc Flash Boundary: 24 inches
<br />Connected Load 0.40 kVA
<br />PANEL HT
<br />Fault at Device: 2900.93 A
<br />Total Voltage Drop: -0.33 %
<br />Incident Energy: 0.19 Cal/cm^2
<br />Working Distance: 18 inches
<br />Arc Flash Boundary: 6 inches
<br />Connected Load 24.30 kVA
<br />HT-1
<br />25.0 A Frame
<br />25.0 A Trip
<br />CBL T-LT(P)
<br />1 Set(s) of:
<br />#10 AWG Conductors,
<br />#10 Ground Wire
<br />In 3/4" Conduit
<br />Length: 5.0 ft
<br />S
<br />P
<br />T-EV
<br />Fault at Device: 5961.63 A
<br />Z% 4.49 %
<br />LF VD% 3.11 %
<br />Nominal kVA 112.5 kVA
<br />Utilization 72.75 %
<br />Pri Tap 0.00 %
<br />Pri RatedVoltage 480 V
<br />Sec RatedVoltage 208 V
<br />CBL EV
<br />1 Set(s) of:
<br />#600 kcmil Conductors,
<br />#2 Ground Wire
<br />In 3-1/2" Conduit
<br />Length: 5.0 ft
<br />EV_MAIN
<br />60.0 A Frame
<br />60.0 A Trip
<br />PANEL EV
<br />Fault at Device: 5888.53 A
<br />Total Voltage Drop: 2.26 %
<br />Incident Energy: 0.1 Cal/cm^2
<br />Working Distance: 18 inches
<br />Arc Flash Boundary: 4 inches
<br />Connected Load 80.00 kVA
<br />CBL T-EV(P)
<br />1 Set(s) of:
<br />#2/0 AWG Conductors,
<br />#6 Ground Wire
<br />In 1 1/2" Conduit
<br />Length: 100.0 ft
<br />Fault at Device: 24559.95 A
<br />Total Voltage Drop: -1.30 %
<br />Incident Energy: 8.49 Cal/cm^2
<br />Working Distance: 18 inches
<br />Arc Flash Boundary: 61 inches
<br />Connected Load 416.00 kVA
<br />PRIMARY METERING CABINET
<br />SPARESPARE SPARE SPARE
<br />MVSG-1 50/51-6
<br />Open
<br />MVSG-1 52-6
<br />Rating 600.0 A
<br />MVSG-1 50/51-3
<br />Open
<br />MVSG-1 52-3
<br />Rating 600.0 A
<br />MVSG-1 50/51-4
<br />Open
<br />MVSG-1 52-4
<br />Rating 600.0 A
<br />MVSG-1 50/51-5
<br />Open
<br />MVSG-1 52-5
<br />Rating 600.0 A
<br />MVSG-1 52-2
<br />MVSG-1 50/51-2
<br />GND
<br />SW
<br />89
<br />GND
<br />SW
<br />89
<br />GND
<br />SW
<br />89
<br />GND
<br />SW
<br />89
<br />GND
<br />SW
<br />89
<br />6" SPARE CONDUIT TO BE STUBBED
<br />AND CAPPED ABOVE-GRADE (TYP.)
<br />Rating 600.0 A
<br />CBL MSB
<br />6 Set(s) of:
<br />4 - #400 kcmil (90° CU) Conductors,
<br />1 - #1/0 CU Ground Wire
<br />In 3" Conduit
<br />Length: 90.0 ft
<br />CBL MMA
<br />2 Set(s) of:
<br />8 - #400 kcmil (90° CU) Conductors,
<br />1 - #2/0 CU Ground Wire
<br />In 4" Conduit
<br />Length: 115.0 ft
<br />DLX8-XFMR-BLDG
<br />S
<br />P
<br />BAYONET
<br />Rating 100.0 A
<br />CLF
<br />Rating 165.0 A
<br />GND
<br />SW
<br />89
<br />VOLTAGE
<br />SENSING
<br />CPT
<br />Trip 125.0 A
<br />DLX8-MVSG-1
<br />CBL DLX8-MVSG-1
<br />2 Set(s) of:
<br />3 - #350 KCMIL AL Conductors (15kV, MV-105),
<br />In 6" Conduit
<br />Length: 20.0 ft
<br />CBL DLX8-XFMR-BLDG
<br />1 Set(s) of:
<br />3 - #2 AL Conductors (15kV, MV-105),
<br />1 - #6 CU (600V) Ground Wire
<br />In 6" Conduit
<br />Length: 20.0 ft
<br />DLX8-MVSG-1
<br />600A, NEMA-3R, 6-WAYS
<br />MV UNDERGROUND DISTRIBUTION SWITCHGEAR RATED:
<br />12,500 AIC, 15.5kV, 3-PHASE, 4-WIRE, BIL 95kV
<br />TEMP CBL GEN MSB
<br />Length: 40.0 ft
<br />2 Set(s) of:
<br />4 - #350 kcmil Conductors,
<br />1 - #1 AWG Ground Wire
<br />TEMPORARY PORTABLE GENERATOR
<br />480Y/277V, 3PH, 4W, 500KW
<br />PROVIDE WITH 600A OVERCURRENT PROTECTION
<br />TEMP CBL GEN MMA
<br />Length: 60.0 ft
<br />1 Set(s) of:
<br />4 - #500 kcmil CU Conductors,
<br />1 - #3 AWG CU Ground Wire
<br />TEMPORARY PORTABLE GENERATOR
<br />480Y/277V, 3PH, 4W, 320KW
<br />PROVIDE WITH 400A OVERCURRENT PROTECTION
<br />SECTION 1 SECTION 2 SECTION 3 SECTION 4
<br />12000V, 3PH, 3W, 600A, 60HZ, 40KA ASYM
<br />KWH
<br />PT О | SC FU PT
<br />CT
<br />TS1
<br />751
<br />SEL
<br />TS1
<br />TS1
<br />SCTB
<br />1A
<br />FUPTFU
<br />80A
<br />MCCB
<br />5A
<br />FU
<br />INTLK
<br />TO INTERNAL 120V CIRCUITS
<br />(HEATERS, LIGHTS &
<br />RECEPTACLES)
<br />12000V, 3PH, 3W, 600A, 60HZ, 40KA ASYM
<br />PT ACCESS
<br />KLKL
<br />(2)
<br />(2)DOOR
<br />(2)
<br />0.5E
<br />UTILITY (SCE)
<br />INCOMING CABLE SIZE
<br />#500 KCMIL AL
<br />CABLE/PH 1
<br />CT
<br />600/5A
<br />(3)
<br />VCB-25KA
<br />15KV, 600A
<br />UTILITY PROVIDED
<br />CT'S AND PT'S PER
<br />UTILITY
<br />REQUIREMENTS CT
<br />SIZE: 10-800A
<br />CPT-15KVA
<br />12000V-120/240V
<br />PT 12000V-120V
<br />CPT
<br />METER
<br />UTILITY CUSTOMER
<br />Line to Line Contribution: 6863.00 A
<br />Line to Ground Contribution: 6349.00 A
<br />Rated Voltage: 12000 V
<br />Fault at Device: 6863.00 A
<br />Total Voltage Drop: 0.61 %
<br />Incident Energy: 15.85 Cal/cm^2
<br />Working Distance: 36 inches
<br />Arc Flash Boundary: 187 inches
<br />Connected Load 1058.70 kVA
<br />Fault at Device: 6859.64 A
<br />Total Voltage Drop: 0.61 %
<br />Incident Energy: 15.85 Cal/cm^2
<br />Working Distance: 36 inches
<br />Arc Flash Boundary: 187 inches
<br />Connected Load 1058.70 kVA
<br />Fault at Device: 27453.40 A
<br />Z% 5.75 %
<br />LF VD% -2.17 %
<br />Nominal kVA 1500 kVA
<br />Utilization 65.66 %
<br />Pri Tap -5.00 %
<br />Pri RatedVoltage 12000 V
<br />Sec RatedVoltage 480 V
<br />DLX8-MV-UMC
<br />1
<br />3
<br />5
<br />7
<br />2
<br />10
<br />9
<br />8
<br />6
<br />12
<br />11
<br />4
<br />TEMPORARY POWER
<br />CONNECTION. TO BE REMOVED
<br />UPON PROJECT COMPLETION.
<br />SEE IMPLEMENTATION PLAN.
<br />TEMPORARY POWER
<br />CONNECTION. TO BE REMOVED
<br />UPON PROJECT COMPLETION.
<br />SEE IMPLEMENTATION PLAN.13
<br />11
<br />GENERAL NOTES:
<br />1. ALL FEEDERS ARE COPPER UNLESS NOTED OTHERWISE.
<br />2. HALFTONE LINES DENOTES EQUIPMENT/FEEDERS ARE EXISTING
<br />TO REMAIN.
<br />3. IF POSSIBLE, UTILIZE EXISTING PROVISIONS FOR BUS TAPS
<br />(INDICATED IN KEYNOTES #9 AND #11) WITHOUT REQUIRING
<br />NEW HOLES OR MODIFICATIONS TO THE EXISTING
<br />SWITCHBOARDS' EQUIPMENT. OTHERWISE, IF MODIFICATIONS
<br />TO AN EXISTING SWITCHBOARDS' EQUIPMENT MUST BE MADE,
<br />THEN THE ALTERED SWITCHBOARD(S) MUST BE RE-CERTIFIED
<br />BY A FIELD EVALUATION BODY SUCH AS A NATIONALLY
<br />RECOGNIZED TESTING LABORATORY (NRTL) PRIOR TO RE-
<br />ENERGIZING WITH TEMPORARY OR UTILITY POWER.
<br />#KEYNOTES:
<br />1. CONNECTION TO UTILITY. SUPPLY VOLTAGE OF 12,000 VOLTS.
<br />COORDINATE EXACT REQUIREMENTS WITH SERVING UTILITY,
<br />SOUTH CALIFORNIA EDISON.
<br />PHASE TO PHASE FAULT AVAILABLE (MAXIMUM) SHORT CIRCUIT
<br />CURRENT: 6863 AMPERES (X/R = 4.90).
<br />PHASE TO GROUND FAULT AVAILABLE (MAXIMUM) SHORT CIRCUIT
<br />CURRENT: 6349 AMPERES (X/R = 2.08).
<br />2. THE METERING SECTION REQUIRES PROVISIONS FOR (2) CTS, (2)
<br />PTS AND (3) FUSES FOR METERING PHASES A & C ONLY, THUS
<br />BUSBARS FOR PHASE B ARE REQUIRED. A 15-CLIP METER SOCKET IS
<br />ACCEPTABLE.
<br />3. PROVIDE ONE (1) SET OF THREE (3) #2 ALUMINUM, 15KV
<br />CONDUCTORS AND ONE (1) #1 CU GROUND CONDUCTOR (600V) IN
<br />6" CONDUIT. SEE DUCT BANK DETAIL FOR ADDITIONAL
<br />INFORMATION.
<br />4. REFER TO CONTROL POWER TRANSFORMER CONNECTION DETAIL
<br />ON SHEET EV6.00.
<br />5. PROVIDE ONE (1) SET OF THREE (3) #2 ALUMINUM, 15KV
<br />CONDUCTORS AND ONE (1) #6 CU GROUND CONDUCTOR (600V) IN
<br />6" CONDUIT. SEE DUCT BANK DETAIL FOR ADDITIONAL
<br />INFORMATION.
<br />6. MEDIUM-VOLTAGE TAP SWITCH, 4-POSITION T-BLADE,
<br />SECTIONALIZING LOAD BREAK SWITCH. PROVIDE UNUSED
<br />POSITION WITH 6" SPARE CONDUIT TO BE STUBBED AND CAPPED
<br />ABOVE-GRADE.
<br />7. PROVIDE SIX (6) SETS OF FOUR (4) #400KCMIL CU, AND ONE (1)
<br />#1/0 AWG CU GROUND CONDUCTOR IN 3" CONDUIT. SEE DUCT
<br />BANK DETAIL FOR ADDITIONAL INFORMATION.
<br />8. PROVIDE TWO (2) SETS OF EIGHT (8) #400KCMIL CU, AND ONE (1)
<br />#2/0 AWG CU GROUND CONDUCTOR IN 4" CONDUIT. SEE DUCT
<br />BANK DETAIL FOR ADDITIONAL INFORMATION.
<br />9. PROVIDE A BUS TAP ALONG THE EXISTING MAIN SWITCHBOARD
<br />BUS FOR A TEMPORARY 600-AMPERE CONNECTION.
<br />10. PROVIDE TWO (2) SETS OF FOUR (4) #350KCMIL CU, AND ONE (1)
<br />#1 CU GROUND CONDUCTOR FOR TEMPORARY POWER
<br />CONNECTION. PROVIDE #2/0 AWG CU GROUNDING ELECTRODE
<br />CONDUCTOR AND REFER TO GENERATOR GROUNDING DETAIL ON
<br />SHEET EV6.00 FOR ADDTIONAL INFORMATION. PROVIDE
<br />PROTECTION AND SUPPORT AS REQUIRED BY CEC 590.4.
<br />11. PROVIDE A BUS TAP ALONG THE EXISTING MAIN SWITCHBOARD
<br />BUS FOR A TEMPORARY 400-AMPERE CONNECTION.
<br />12. PROVIDE ONE (1) SET OF FOUR (4) #500KCMIL CU, AND ONE (1)
<br />#3 AWG CU GROUND CONDUCTOR FOR TEMPORARY POWER
<br />CONNECTION. PROVIDE #1/0 AWG CU GROUNDING ELECTRODE
<br />CONDUCTOR AND REFER TO GENERATOR GROUNDING DETAIL ON
<br />SHEET EV6.00 FOR ADDTIONAL INFORMATION. PROVIDE
<br />PROTECTION AND SUPPORT AS REQUIRED BY CEC 590.4.
<br />13. CONTRACTOR TO PROVIDE APPROPRIATE STACKED LUGS FOR
<br />SECONDARY CONDUCTORS.
<br />AT NO POINT SHOULD AN ENERGIZED TRANSFORMER AND A
<br />GENERATOR BE CONNECTED TO THE SAME BUS.
<br />1. THE EXISTING ELECTRICAL DISTRIBUTION SYSTEM FOR THE
<br />BUILDING SHALL REMAIN IN SERVICE UNTIL ALL COMPONENTS OF
<br />THE TEMPORARY POWER CONNECTIONS, EXCEPT FOR THE BUS
<br />TAP AND ENERGIZATION OF THE GENERATORS, ARE PROVIDED.
<br />2. CONTRACTOR TO COORDINATE OUTAGE FOR THE BUILDING WITH
<br />OWNER AND UTILITY.
<br />3. DEACTIVATE (SWITCH OFF) THE EXISTING SWITCHBOARDS'
<br />("MSB" & "MMA") MAIN CIRCUIT BREAKER AND LOCKOUT IN THE
<br />OPEN POSITION (PROVIDE LOCKOUT AS REQUIRED).
<br />4. AFTER EXISTING BUILDING TRANSFORMER HAS BEEN
<br />DE-ENERGIZED, PROVIDE BUS TAPS TO EXISTING SWITCHBOARDS.
<br />5. FINALIZE TEMPORARY CONNECTIONS AND ENERGIZE TEMPORARY
<br />GENERATORS.
<br />6. UPON PROJECT COMPLETION, CONTRACTOR TO COORDINATE
<br />OUTAGE FOR THE BUILDING WITH OWNER. DE-ENERGIZE AND
<br />REMOVE TEMPORARY GENERATORS.
<br />7. DISCONNECT AND REMOVE ALL COMPONENTS OF THE TEMPORARY
<br />POWER CONNECTIONS.
<br />8. UNLOCK AND ACTIVATE (SWITCH ON) EXISTING MAIN CIRCUIT
<br />BREAKERS.
<br />IMPLEMENTATION PLAN:
<br />448 South Hill Street
<br />Suite 1001
<br />Los Angeles, CA 90013
<br />Phone: 310-975-2061
<br />Reviewed By:Proj #:
<br />140 Newport Center Drive,
<br />Suite 100
<br />Newport Beach, CA 92660
<br />O: 949.478.8800
<br />www.kpff.com
<br />KPFF
<br />9/
<br />1
<br />9
<br />/
<br />2
<br />0
<br />2
<br />5
<br />
<br />2
<br />:
<br />0
<br />8
<br />:
<br />3
<br />7
<br />
<br />P
<br />M
<br />
<br />A
<br />u
<br />t
<br />o
<br />d
<br />e
<br />s
<br />k
<br />
<br />D
<br />o
<br />c
<br />s
<br />:
<br />/
<br />/
<br />D
<br />L
<br />X
<br />8
<br />/
<br />D
<br />L
<br />X
<br />8
<br />_
<br />M
<br />E
<br />P
<br />.
<br />r
<br />vt
<br />EV6.01
<br />ONE-LINE DIAGRAM -
<br />ELECTRICAL
<br />DLX8_EVSG
<br />515 E Dyer Rd, Santa Ana, CA 92707
<br />Owner
<br />NM23.0003320.000
<br />1416 NW 46TH Street
<br />Suite 105-138
<br />Seattle, WA 98107
<br />WWW.NELSONWORLDWIDE.COM
<br />Phone: (206) 408-8501
<br />Nelco Architecture, Inc.
<br />NOT TO SCALEEV6.01
<br />1 ELECTRICAL ONE-LINE DIAGRAM
<br />Issue: No: Date:
<br />CD 30 2023/11/03
<br />CD 50 2024/05/22
<br />CD 90 2025/03/11
<br />Issue for Permit 2025/04/21
<br />Plan Check Repsonse 1 1 2025/09/19
<br />1
<br />1
<br />1
<br />1
<br />9-24-2025
|