Laserfiche WebLink
www.hilti.com <br />Hilti PROFIS Engineering 3.1.14 <br />Input data and results must be checked for conformity with the existing conditions and for plausibility! <br />PROFIS Engineering ( c ) 2003-2025 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan <br />6 <br />Company: <br />Address: <br />Phone I Fax: <br />Design: <br />Fastening point: <br /> | <br />DLX8 Transformer ANCHORAGE <br />Page: <br />Specifier: <br />E-Mail: <br />Date: <br />6 <br />4/15/2025 <br />4 Shear load <br />Load Vua [lb]Capacity f Vn [lb]Utilization bV = Vua/f Vn Status <br /> Steel Strength*885 3,067 29 OK <br /> Steel failure (with lever arm)*N/A N/A N/A N/A <br /> Pryout Strength (Concrete Breakout <br /> Strength controls)** <br />885 15,299 6 OK <br /> Concrete edge failure in direction x-**885 3,545 25 OK <br /> * highest loaded anchor **anchor group (relevant anchors) <br /> When the input edge distance is set to "infinity", edge breakout verification is not performed in that direction <br />4.1 Steel Strength <br />Vsa,eq = ESR value refer to ICC-ES ESR-3814 <br />f Vsteel ³ Vua ACI 318-19 Table 17.5.2 <br />Variables <br />Ase,V [in.2]futa [psi]aV,seis <br />0.23 58,000 0.600 <br />Calculations <br />Vsa,eq [lb] <br />4,719 <br />Results <br />Vsa,eq [lb]f steel f Vsa,eq [lb]Vua [lb] <br />4,719 0.650 3,067 885 <br />S-41