1' - 0"
<br />EQ.
<br />EQ.
<br />EQ.
<br />TYP.
<br />1' - 0"
<br />EQ.
<br />ATTACHMENT OF LIGHT FIXTURES AND AIR TERMINALS TO CEILING GRID
<br />(SEE NOTE NO. 23 ABOVE)
<br />2 EACH SIDE
<br />4 EACH SIDE
<br />#8 SELF-TAPPING
<br />SHEET METAL
<br />SCREWS
<br />24" LONG FIXTURE
<br />OR AIR TERMINAL
<br />48" LONG FIXTURE
<br />OR AIR TERMINAL
<br />FIXED END
<br />FREE END
<br />FR
<br />E
<br />E
<br />
<br />E
<br />N
<br />D
<br />
<br />FI
<br />X
<br />E
<br />D
<br />
<br />E
<br />N
<br />D
<br />
<br />12 GA. HANGER WIRE
<br />8" OR 1/4 LENGTH OF
<br />END TEE FROM WALL.
<br />SEE NOTE 3 OF THE
<br />CEILING GENERAL
<br />NOTES.
<br />CEILING GRID MEMBER
<br />ATTACHED TO TWO
<br />ADJACENT WALLS
<br />ONLY. SEE NOTE 5 OF
<br />THE CEILING GENERAL
<br />NOTES AND DETAIL
<br />8 / A0.4.4
<br />CEILING GRID MEMBER ATTACHED TO
<br />TWO ADJACENT WALLS ONLY. SEE NOTE 5
<br />OF THE CEILING GENERAL NOTES AND
<br />DETAIL 8 / A0.4.4
<br />12 GA. HANGER WIRES
<br />@48" 0.C. MAXIMUM -
<br />SEE NOTES 1, 2, & 3
<br />OF THE CEILING
<br />GENERAL NOTES
<br />CROSS RUNNERS @
<br />24" O.C. MAXIMUM
<br />MAIN RUNNER @
<br />48" O.C.
<br />MAXIMUM
<br />LIGHT FIXTURES & HVAC
<br />GRILLES - SEE NOTE
<br />19, 20, & 21 OF THE
<br />CEILING GENERAL
<br />NOTES.
<br />SEE NOTES 10A & 10B OF
<br />THE CEILING GENERAL
<br />NOTES DETAIL 1 / A0.4.4
<br />AND FOR SPACING OF
<br />BRACING ASSEMBLIES
<br />SEE NOTES 10A & 10B
<br />OF THE CEILING
<br />GENERAL NOTES
<br />DETAIL 1 / A0.4.4
<br />AND FOR SPACING OF
<br />BRACING ASSEMBLIES
<br />SEE NOTES 10A & 10B OF THE CEILING
<br />GENERAL NOTES DETAIL 1 /A0.4.4
<br />AND FOR SPACING OF BRACING
<br />ASSEMBLIES
<br />TYP. 12 GA SPLAYED BRACING WIRES &
<br />COMPRESSION POST.
<br />SEE NOTES 9 & 10 OF THE CEILING GENERAL
<br />NOTES AND DETAIL 1 / A0.4.4
<br />CEILING GRID MEMBERS NOT
<br />ATTACHED TO ADJACENT WALLS. SEE
<br />NOTE 7 OF THE CEILING GENERAL
<br />NOTES AND DETAIL 8 / A0.4.4
<br />SAME CRITERIA AS
<br />NOTED ABOVE ARE
<br />APPLICABLE AT 24" X
<br />24" GRID.
<br />12 GA SPLAYED
<br />BRACING WIRES &
<br />COMPRESSION POST.
<br />SEE NOTES 9 & 10 OF
<br />THE CEILING GENERAL
<br />NOTES AND DETAIL
<br />1 / A0.4.4
<br />TYP. 12 GA. HANGER
<br />WIRE 8" OR 1/4
<br />LENGTH OF END TEE
<br />FROM WALL.
<br />SEE NOTE 3 OF THE
<br />CEILING GENERAL
<br />NOTES.
<br />12 GA. HANGER
<br />WIRES @48" 0.C.
<br />MAXIMUM -
<br />SEE NOTES 1, 2, & 3
<br />OF THE CEILING
<br />GENERAL NOTES
<br />TYP. HANGER WIRE AND
<br />BRACING WIRE
<br />ATTACHMENT TO
<br />STRUCTURE. SEE NOTE 16
<br />OF THE CEILING GENERAL
<br />NOTES
<br />SEE NOTES 10A & 10B
<br />OF THE CEILING
<br />GENERAL NOTES DETAIL
<br />1 / A0.4.4
<br />AND FOR SPACING OF
<br />BRACING ASSEMBLIES
<br />PLAN
<br />SECTION
<br />1 1/2"
<br />1/2" MIN
<br />1 1/2"
<br />MAXIMUM LENGTH: SEE CHART
<br />1 1/4"
<br />1 1/4"
<br />6" MINIMUM
<br />6" MINIMUM
<br />3/4" MIN.
<br />#12 X 1" SELF-TAPPING SCREWS INTO STEEL DECK,
<br />OR TWO 3/8" DIA. EXPANSION ANCHORS 2"
<br />MINIMUM
<br />EMBED INTO CONCRETE, SEE DETAILS
<br />1/8" X 2" WIDE X 3" X 3" BENT STEEL PLATE
<br />TWO 1/4" DIA. MACHINE BOLTS WITH FLAT WASHER
<br />AT NUTS, AND TWO NUTS EACH. DO NOT CRUSH
<br />EMT.
<br />ELECTRICAL CONDUIT (EMT)
<br />COMPRESSION POST - SEE CHART BELOW FOR SIZE
<br />TWO #12 SHEET METAL SCREWS THROUGH
<br />BOTH SIDES OF SLEEVE & POST
<br />ELECTRICAL CONDUIT (EMT) SLEEVE ONE SIZE
<br />LARGE THAN COMPRESSION POST
<br />ONE 1/4" DIA. MACHINE BOLT WITH FLAT WASHER
<br />AT HEAD AND AT NUTS, AND TWO NUTS,
<br />THROUGHBOTH SIDES OF SLEEVE AND THROUGH
<br />MAIN RUNNER. DO NOT CRUSH MAIN RUNNER.
<br />MAIN RUNNER (TYP.)
<br />ELECTRICAL CONDUIT (EMT) POST
<br />METAL STUD POST
<br />MIN
<br />1 1/4"
<br />MAXIMUM LENGTH: SEE CHART
<br />(TYP.)
<br />6" MINIMUM
<br />2 #10 SHEET METAL SCREWS EACH SIDE OF
<br />TRACK (TYP.)
<br />BOTTOM OF STRUCTURE
<br />1 5/8" X 20 GAUGE METAL STUD TRACK
<br />SPANNING 2 FLUTES W/ FOUR #8 X 1/2"
<br />SELF-TAPPING SCREWS INTO STEEL DECK,
<br />OR TWO 3/8" DIA. EXPANSION ANCHORS
<br />[ICC-ER 1917], 2" MINIMUM EMBED INTO
<br />CONCRETE, SEE DETAILS
<br />1-5/8" X 20 GAUGE METAL STUD COMPRESSION
<br />POST
<br />ATTACH STUD TO MAIN RUNNER W/ ONE 1/4"
<br />DIA. MACHINE BOLT WITH FLAT WASHER AT HEAD
<br />AND TWO NUTS, THROUGH STUD AND MAIN
<br />RUNNER. DO NOT CRUSH MAIN RUNNER.
<br />COMPRESSION POST CHART
<br />COMPRESSION POST MINIMUM
<br />CROSS
<br />SECTIONAL
<br />AREA "A"
<br />MINIMUM
<br />RADIUS OF
<br />GYRATION
<br />"R" OR "Ry"
<br />CEILING TO
<br />STRUCTURE
<br />MAXIMUM LENGTH
<br />OF COMPRESSION
<br />POST
<br />1/2" DIA. EMT
<br />3/4" DIA. EMT
<br />1" DIA. EMT
<br />1 5/8" X 20 GAUGE
<br />METAL STUD
<br />(2) 2 1/2" X 20
<br />GAUGE METAL
<br />"T" STUDS
<br />0.088 IN.2
<br />0.134 IN.2
<br />0.198 IN.2
<br />0.155 IN.2
<br />0.348 IN.2
<br />0.238 IN.
<br />0.309 IN.
<br />0.392 IN.
<br />0.454 IN.
<br />0.71 IN.
<br />3'-10"
<br />5'-0"
<br />6'-6"
<br />7'-6"
<br />15'-0"
<br />NOTE: USE EMT OR METAL STUD COMPRESSION POST WITH ACCEPTABLE CEILING TO STRUCTURE
<br />LENGTH LISTED IN CHART.
<br />OR 8" MAX (TYP)
<br /> LESSER OF 1/4
<br />LENGTH OF RUNNER,
<br />LINE OF WALL (TYP).
<br />MFR'S. APPROVED PERIMETER CLIP @
<br />EACH RUNNER
<br />FIRST RUNNER PARALLEL TO WALL (TYP.)
<br />WALL MOLDING W/ SHEET METAL SCREW INTO EACH STL STUD OR
<br />1/4" EXPANSION ANCHOR, 1 1/4" MINIMUM EMBED, @ 24" O.C.
<br />MAX. AT CONC.WALL (TYP.)
<br />ATTACHED TO WALL
<br />(AT TWO ADJACENT WALLS ONLY - SEE
<br />NOTE 4 OF THE CEILING GENERAL NOTES)
<br />2"
<br />MIN.
<br />3/4" CLR.
<br />8" MAX (TYP)
<br />LESSER OF 1/4 LENGTH
<br />OR RUNNER, OR
<br />NOT ATTACHED TO WALL
<br />(AT OPPOSITE WALLS)
<br />HANGER WIRE - SEE NOTE 1 OF THE
<br />CEILING GENERAL NOTES (TYP.)
<br />A.) 3/4" COLD ROLLED STEEL STABILIZER
<br />CHANNEL
<br />OR
<br />B.) SLOTTED ANGLE INTERLOCKING STRUT -
<br />SEE NOTE 6 OF THE CEILING GENERAL NOTES
<br />A.
<br />B.
<br />(OMIT IF FIRST RUNNER PARALLEL TO WALL IS
<br />WITHIN 12" OF WALL) [REF. DSA IR25-2.10, FIG
<br />2.]
<br />(TYP)
<br />45.00° MAX
<br />(TYP)
<br />45.00° MAX.
<br />12 GA. VERTICAL HANGER WIRES
<br />AT 4' - 0" ON CENTER EACH WAY.
<br />SEE NOTES 1,2, & 3 OF THE
<br />CEILING GENERAL NOTES
<br />FOUR 12 GA, SPLAYED
<br />BRACING WIRES, TWO
<br />PARALLEL TO AND TWO
<br />PERPENDICULAR TO MAIN
<br />RUNNERS. (4 TURNS MIN IN
<br />1-1/2" @ BOTH ENDS) SEE
<br />NOTES 9 & 10 OF THE
<br />CEILING GENERAL NOTES
<br />FOR ATTACHMENT TO STRUCTURE
<br />ABOVE SEE DETAILS:
<br />7 / A0.4.4
<br />5 / A0.4.4
<br />6 / A0.4.4
<br />MAIN RUNNERS
<br />CROSS RUNNERS
<br />2" MAXIMUM FROM BRACING WIRES
<br />TO COMPRESSION STRUT (TYPICAL)
<br />(COMPRESSION POST SHALL
<br />NOT REPLACE HANGER WIRE)
<br />VERTICAL COMPRESSION POST
<br />AT EACH SET OF BRACING
<br />WIRES -
<br />SEE DETAIL 3 / A0.4.4
<br />NOTE:
<br />WHEN MULTIPLE SADDLY
<br />TIES ARE REQ'D, THEY
<br />SHALL
<br />ALTERNATE BACK AND
<br />FORTH, SEE NOTE 7 OF
<br />THE CEILING GENERAL
<br />NOTES.
<br />TRAPEZE
<br />SADDLE TIE W/
<br />DOUBLE LOOP SUPPORT
<br />HANGER WIRES W/ MIN.
<br />3 TIGHT TURNS, SEE OF THE
<br />CEILING GENERAL NOTES
<br />SADDLE TIE
<br />REQ'D FOR ALL
<br />WIDTHS
<br />GREATER THAN
<br />1/4"
<br />HANGER WIRE
<br />BRACING WIRE
<br />MAX
<br />5/8"
<br />STRUCTURAL STEEL
<br />12 GA. X 3/4" WIDE (MINIMUM) STEEL STRAP W/
<br />POWDER
<br />ACTUATED FASTENER (3/4" MIN PENETRATION)
<br />HILTI X-AL-H, 0.177 , 1 1/2" MIN. EMBED [ICC
<br />ESR-1663], TYP.
<br />HANGER WIRE WITH MINIMUM 3 TIGHT TURNS IN
<br />1 1/2" - SEE NOTES 1 & 16 OF THE CEILING
<br />GENERAL NOTES
<br />MAX
<br />45.00°
<br />MAX
<br />5/8"
<br />STRUCTURAL STEEL
<br />12 GA. X 1" WIDE X 2" LONG (MINIMUM) STEEL
<br />STRAP W/ POWDER ACTUATED FASTENER (3/4"
<br />MIN PENETRATION)
<br />BRACING WIRE WITH MINIMUM 4 TIGHT TURNS
<br />IN 1 1/2" - SEE NOTES 10 & 16 OF THE CEILING
<br />GENERAL NOTES
<br />WIRE ATTACHMENT WITH EXPANSION ANCHOR
<br />1" MIN.
<br />EQ EQ MINIMUM 20 GA. STEEL DECK (WITH
<br />CONCRETE FILL)
<br />HILTI HLC-T 1/4" X 1-3/8" EXPANSION ANCHOR
<br />WITH TIE-WIRE HEAD (OR APPROVED EQUAL)
<br />BRACING WIRE WITH MINIMUM 4 TIGHT TURNS IN 1
<br />1/2" - SEE NOTES 10 & 16 OF THE CEILING
<br />GENERAL NOTES
<br />HANGER WIRE
<br />BRACING WIRE
<br />#3 X 12" LONG REBAR
<br />MINIMUM 20 GA. STEEL DECK
<br />(WITH NO CONCRETE FILL)
<br />HANGER WIRE TIED TO #3 REBAR WITH
<br />THREE WRAPS AROUND REBAR AND ONE
<br />WRAP AROUND WIRE -SEE NOTES 1 & 16 OF
<br />THE CEILING GENERAL NOTES.
<br />MAX
<br />45.00°
<br />MINIMUM 20 GA. STEEL DECK ( WITH NO
<br />CONCRETE FILL)
<br />MINIMUM 12 GA. X 3" WIDE X 4" LONG STEEL
<br />STRAP W/ TWO #8 X 1/2" SELF TAPPING SCREWS
<br />BRACING WIRE WITH MINIMUM 4 TIGHT TURNS
<br />IN 1 1/2" - SEE NOTES 10 & 16 OF THE CEILING
<br />GENERAL NOTES
<br />ARMSTRONG CROSS TEE
<br />6
<br />1
<br />6
<br />1
<br />#12 HANGER WIRE ANCHORED
<br />TO STRUCTURE ABOVE OR TO
<br />THE WALL ABOVE THE CEILING
<br />ARMSTRONG STABILIZER BAR, OR
<br />OTHER SUITABLE SYSTEM, TO
<br />KEEP PERIMETER COMPONENTS
<br />FROM SPREADING APART
<br />3/8"
<br />7" MAX.
<br />.
<br />IF-01.
<br />PROJECT
<br />COPYRIGHT LOC, INC
<br />ORIGINAL SHEET SIZE: 42" X 30"
<br />LOC
<br />CLIENT:
<br />ARCHITECT:
<br />CONSULTANTS:
<br />PREPARED UNDER THE SUPERVISION OF:
<br />ALI JEEVANJEE
<br />LOC ARCHITECTS DATE
<br />REVIEWED FOR CONSTRUCTABILITY:
<br />SEAN THOMAS
<br />PRINCIPAL CIVIL ENGINEER
<br />RCE NO.: 80470
<br />DATE
<br />RECOMMENDED FOR CONSTRUCTION:
<br />JASON GABRIEL
<br />PRINCIPAL CIVIL ENGINEER
<br />RCE NO.: 62968
<br />DATE
<br />3/28/2025 6:04:37 PM
<br />2308
<br />TYP CEILING
<br />DETAILS
<br />MARCH 28, 2025
<br />PLAN CHECK
<br />SUBMITTAL 02
<br />G0.6
<br />SANTA ANA ZOO
<br />1821 & 1823 E CHESTNUT AVE, SANTA
<br />ANA, CA 92701
<br />KPFF
<br />STRUCTURAL ENGINEER
<br />LOC ARCHITECTS
<br />KPFF
<br />CIVIL ENGINEER
<br />BORDER
<br />LANDSCAPE ARCHITECT
<br />ABRARI AND ASSOCIATES
<br />MEP ENGINEER
<br />ASSOCIATED SOILS ENGINEERING
<br />GEOTECHNICAL ENGINEER
<br />700 S. FLOWER, SUITE 2100
<br />LOS ANGELES, CA 90017
<br />213 372 5111
<br />Ramzi.hodali@kpff.com
<br />700 S. FLOWER, SUITE 2100
<br />LOS ANGELES, CA 90017
<br />213 372 5111
<br />Sharad.Ganju@kpff.com
<br />724 S. SPRING ST, SUITE 701
<br />LOS ANGELES, CA 90014
<br />213 372 5111
<br />Darren@border-la.com
<br />1713 S. STANDARD AVE
<br />GLENDALE, CA 91201
<br />818 956 1900
<br />Telma@abrari.com
<br />2860 WALNUT AVE.
<br />SIGNAL HILL, CA 90755
<br />562 897 2749
<br />Ted@associatedsoils.com
<br />3203 E. 4TH ST
<br />LOS ANGELES, CA 90063
<br />213 537 0480
<br />Office@loc-arch.com
<br />1801 E. CHESTNUT AVE.
<br />SANTA ANA, CA 92701
<br />714 647 6575
<br />Efisher@santa-ana.org
<br />SANTA ANA ZOO
<br />EDUCATION HUB
<br />MARCH 28, 2025
<br />SUSPENDED LAY-IN PANEL ACOUSTIC
<br />CEILING GENERAL NOTES
<br />THE DESIGN AND INSTALLATION OF SUSPENDED ACOUSTIC CEILING SYSTEMS SHALL COMPLY WITH THE REQUIREMENTS CONTAINED IN TITLE 24, PART 2 - CALIFORNIA BUILDING CODE 2022 (CBC
<br />CHAP 25 AND ASTM C635 AND 636), AND WITH THE FOLLOWING ADDITIONAL REQUIREMENTS AS NOTED:
<br />2019 CITY OF LOS ANGELES BUILDING CODE (CHAPTER 8 AND ASTM C635 AND 636) FOR SUSPENDED CEILING SYSTEMS.
<br />THE FOLLOWING REQUIREMENTS APPLY TO CEILING SYSTEMS WHOSE TOTAL WEIGHT, INCLUDING CEILING MOUNTED AIR TERMINALS, SERVICES AND LIGHT FIXTURES, DOES NOT EXCEED FOUR (4)
<br />PSF. HEAVIER SYSTEMS, AND THOSE SUPPORTING LATERAL LOADS FROM PARTITIONS, WILL REQUIRE SPECIAL DESIGN DETAILS. SEE SPECIFICATIONS SECTION 09510 FOR ADDITIONAL INFORMATION
<br />REGARDING THE SUSPENDED ACOUSTICAL CEILING SYSTEM.
<br />1. THE CEILING GRID SYSTEM MUST BE RATED HEAVY DUTY AS DEFINED BY ASTM C635.
<br />2. #12 GAGE WIRE SHALL BE 0.106 INCHES IN DIAMETER CONFORMING TO ASTM A641. #12 GAGE WIRE SHALL BE SOFT ANNEALED, GALVANIZED STEEL WIRE WITH A CLASS 1 COATING.
<br />3. MAIN RUNNERS, CROSS RUNNERS, SPLICES, EXPANSION DEVICES, INTERSECTION CONNECTORS SHALL BE DESIGNED TO CARRY A MEAN ULTIMATE TEST LOAD OF NOT LESS THAN 180 LBS.
<br />IN COMPRESSION AND TENSION PER ASTM E58 - SECTION 5.1.2.
<br />4. #12 GAGE HANGER WIRES MAY BE USED FOR UP TO AND INCLUDING 4 FT. BY. 4 FT. GRID SPACING AND SHALL BE ATTACHED TO MAIN RUNNERS.
<br />5. PROVIDE #12 GAGE HANGER WIRES AT THE ENDS OF ALL MAIN AND CROSS RUNNERS WITHIN EIGHT (8) INCHES OF THE SUPPORT OR WITHIN ONE-FOURTH (1/4) OF THE LENGTH OF THE
<br />END TEE, WHICHEVER IS LEAST FOR THE PERIMETER OF THE CEILING AREA. THE LENGTH OF THE END TEE IS EIGHT (8) INCHES OR LESS.
<br />6. PROVIDE TRAPEZE OR OTHER SUPPLEMENTARY SUPPORT MEMBERS AT OBSTRUCTIONS TO TYPICAL HANGER SPACING (HANGERS, STRUTS OR BRACES AS REQUIRED AT ALL CEILING BREAKS,
<br />SOFFITS, OR DISCONTINUOUS, AREAS. HANGER WIRES THAT ARE MORE THAN 1 (HORIZONTAL) IN 6 (VERTICAL) OUT OF PLUMB ARE TO HAVE COUNTER-SLOPING WIRES. PERIMETER HANGER WIRES
<br />AT MAIN RUNNERS THAT ARE POSITIVELY ATTACHED TO THE PERIMETER CLOSURE ANGLE, COUNTER-SLOPING IS OPTIONAL.
<br />NOTE: SEE ASTM C-636 FIGURE 1 FOR COUNTER-SLOPING METHODS.
<br />7. CEILING GRID MEMBERS SHALL BE ATTACHED TO TWO (2) ADJACENT WALLS PER ASTM E580 SECTION 5.2.3 CEILING GRID MEMBERS SHALL BE AT LEAST 3/4 INCH CLEAR OF OTHER WALLS. IF
<br />WALLS RUN DIAGONALLY TO CEILING GRID SYSTEM RUNNERS, ONE END OF MAIN AND CROSS RUNNERS SHOULD BE FREE, AND A MINIMUM OF 3/4" INCH CLEAR OF WALL.
<br />8. THE WIDTH OF THE PERIMETER SUPPORTING CLOSURE ANGLE SHALL NOT BE LESS THAN TWO (2) INCHES.
<br />9. AT THE PERIMETER OF THE CEILING AREA WHERE MAIN OR CROSS RUNNERS ARE NOT CONNECTED TO THE ADJACENT WALL, PROVIDE INTERCONNECTION BETWEEN THE RUNNERS AND THE
<br />FREE END TO PREVENT LATERAL SPREADING. A METAL STRUT OR A #16 GAGE WIRE WITH A POSITIVE MECHANICAL CONNECTION TO THE RUNNER MAY BE USED. WHERE THE PERPENDICULAR
<br />DISTANCE FROM THE WALL TO THE FIRST PARALLEL RUNNER IS 12 INCHES OR LESS, THIS INTERLOCK IS NOT REQUIRED.
<br />10. EXPANSION JOINTS SHALL BE PROVIDED IN THE CEILING AT INTERSECTIONS OF CORRIDORS AND AT JUNCTIONS OF CORRIDORS WITH LOBBIES OR OTHER SIMILAR AREAS. - N/A
<br />11. PROVIDE LATERAL-FORCE BRACING ASSEMBLIES CONSISTING OF A COMPRESSION STRUT AND FOUR (4) #12 GAGE SPLAYED BRACING WIRES ORIENTED 90 DEGREES FROM EACH OTHER. -SEE
<br />DETAIL 3 / A0.4.4
<br />EXCEPTION: LATERAL BRACING MAY BE OMITTED FOR SUSPENDED ACOUSTICAL CEILING SYSTEMS WITH A CEILING AREA OF 144 SQUARE FEET OR LESS, AND FIRE RATED SUSPENDED ACOUSTICAL
<br />CEILING SYSTEMS WITH A CEILING AREA OF 96 SQUARE FEET OR LESS, WHEN PERIMETER SUPPORT IN ACCORDANCE WITH DSA IR 25-2.10 AND ASTM E580 SECTIONS 5.2.2 AND 5.2.3 ARE PROVIDED
<br />AND PERIMETER WALLS ARE DESIGNED TO CARRY THE CEILING LATERAL FORCES.
<br />12. THE SPACING OF THE BRACING ASSEMBLIES ARE SHOWN ON THE CONSTRUCTION DOCUMENTS. PROVIDE BRACING ASSEMBLIES AT LOCATIONS NOT MORE THAN ONE HALF (1/2) THE
<br />CALCULATED SPACING IN EACH DIRECTION FROM EACH PERIMETER WALL AND AT THE EDGES OF ANY CHANGE IN ELEVATION OF THE CEILING. SUBSTANTIATING CALCULATIONS OR TEST REPORTS
<br />FOR THE BRACING ASSEMBLIES ARE WAIVED IF THE FOLLOWING REQUIREMENTS ARE MET:
<br />A. BRACING ASSEMBLIES SPACED AT A MAXIMUM OF 12 FEET BY 12 FEET ON CENTERS FOR SCHOOL BUILDINGS AND 8 FEET BY 12 FEET ON CENTERS FOR ESSENTIAL SERVICES BUILDINGS.
<br />B. THE MAXIMUM SLENDERNESS RATIO (KL/R) OF THE COMPRESSION STRUT IS 200 OR LESS.
<br />13. THE SLOPE OF BRACING WIRES SHALL NOT EXCEED 45 DEGREES FROM THE PLANE OF THE CEILING AND WIRES SHALL BE TAUT. SPLICES IN WIRES ARE NOT PERMITTED WITHOUT SPECIAL DSA
<br />APPROVAL.
<br />14. COMPRESSION STRUTS SHALL NOT BE MORE THAN 1 (HORIZONTAL) IN 6 (VERTICAL) OUT OF PLUMB.
<br />15. FOR CEILING AREAS EXCEEDING 2500 SQUARE FEET A SEISMIC SEPARATION JOINT SHALL BE PROVIDED IN ACCORDANCE WITH DETAIL TO DIVIDE THE CEILING INTO AREAS NOT EXCEEDING
<br />2500 SQUARE FEET. ALTERNATIVELY, STRUCTURAL ANALYSIS SHALL BE PERFORMED TO DEMONSTRATE COMPLIANCE WITH ASTM E580-08 SECTION 5.2.9.
<br />16. PENETRATIONS THROUGH THE CEILING FOR SPRINKLER HEADS AND OTHER SIMILAR DEVICES THAT ARE NOT INTEGRALLY TIED TO THE CEILING SYSTEM IN THE LATERAL DIRECTION SHALL
<br />HAVE A TWO (2) INCH OVERSIZED RING, SLEEVE OR ADAPTER THROUGH THE CEILING TILE TO ALLOW FREE MOVEMENT OF ONE (1) INCH IN ALL HORIZONTAL DIRECTIONS. ALTERNATIVELY, SWING
<br />JOINTS MAY BE PROVIDED PER ASTM E580 SECTION 5.2.8.8, A FLEXIBLE HOSE FITTING THAT CAN ACCOMMODATE 1 INCH OF CEILING MOVEMENT SHALL BE PERMITTED TO BE USED IN LIEU OF THE
<br />OVERSIZED RING, SLEEVE OR ADAPTER.
<br />17. FASTEN #12 HANGER WIRES WITH NOT LESS THAN THREE (3) TIGHT TURNS IN 3 INCHES. HANGER WIRE LOOP SHALL BE TIGHTLY WRAPPED AND SHARPLY BENT TO PREVENT ANY VERTICAL
<br />MOVEMENT OR ROTATION OF THE MEMBER WITHIN THE LOOPS (SEE ASTM E580, SECTION 5.2.7.2).
<br />18. FASTEN #10 GAGE OR #12 GAGE BRACING WIRES WITH FOUR (4) TIGHT TURNS. MAKE ALL TIGHT TURNS WITHIN A DISTANCE OF 1-1/2 INCHES. HANGER OR BRACING WIRE
<br />ANCHORS TO THE STRUCTURE SHOULD BE INSTALLED IN SUCH A MANNER THAT THE DIRECTION OF THE ANCHOR ALIGNS AS CLOSELY AS POSSIBLE WITH THE DIRECTION OF THE WIRE.
<br />19. SEPARATE ALL CEILING HANGER AND BRACING WIRES AT LEAST SIX (6) INCHES FROM ALL UNBRACED DUCTS, PIPES, CONDUIT, ETC. HANGER WIRES SHALL NOT ATTACH TO OR BEND
<br />AROUND INTERFERING MATERIAL OR EQUIPMENT.
<br />20. WHEN DRILLED-IN CONCRETE ANCHORS OR SHOT-IN ANCHORS ARE USED IN REINFORCED CONCRETE FOR HANGER WIRES, 1 OUT OF 10 WIRE/ANCHOR ASSEMBLIES MUST BE FIELD
<br />TESTED FOR 200 LBS. IN TENSION. WHEN DRILLED-IN CONCRETE ANCHORS ARE USED FOR BRACING WIRES, 1 OUT 2 WIRE/ ANCHOR ASSEMBLIES MUST BE FIELD TESTED FOR 440 LBS. IN TENSION IN
<br />THE DIRECTION OF THE WIRE. SHOT-IN ANCHORS IN CONCRETE ARE NOT PERMITTED FOR BRACING WIRES.
<br />NOTE: DRILLED-IN OR SHOT-IN ANCHORS REQUIRE SPECIAL DSA APPROVAL PRIOR TO USE IN PRESTRESSED CONCRETE.
<br />21. ALL FIXTURES, TERMINALS, AND OTHER DEVICES SHALL BE MOUNTED IN A MANNER THAT WILL NOT COMPROMISE CEILING PERFORMANCE IN ACCORDANCE WITH SECTION 13.5.6.2.2 (5) OF
<br />ASCE 7-05 AS AMENDED BY 2010 CBC SECTION 1615A.1.16 (1615.10.13*) AND ASTM E580 SECTIONS 5.3 AND 5.4.
<br />22. CEILING PANELS SHALL NOT SUPPORT ANY LIGHT FIXTURES, AIR TERMINALS OR DEVICES.
<br />23. ATTACH ALL LIGHT FIXTURES AND CEILING MOUNTED AIR TERMINALS, TO THE CEILING GRID RUNNERS TO RESIST A HORIZONTAL FORCE EQUAL TO THE WEIGHT OF THE FIXTURES. SCREWS
<br />OR APPROVED FASTENERS ARE REQUIRED. MINIMUM OF TWO ATTACHMENTS ARE REQUIRED AT EACH LIGHT FIXTURE PER ASTM E580 SECTION 5.3.1.
<br />24. RECESSED OR DROP-IN LIGHT FIXTURES, GRILLES, MECHANICAL TERMINALS, AND FLEXIBLE SPRINKLER HOSE FITTINGS OR OTHER SERVICES BE SUPPORTED DIRECTLY ON RUNNERS
<br />CLASSIFIED AS ASTM HEAVY DUTY, BUT THEY MUST ALSO HAVE A MINIMUM OF TWO (2) #12 GAGE SLACK SAFETY WIRES ATTACHED TO THE FIXTURE AT DIAGONAL CORNERS AND ANCHORED TO THE
<br />STRUCTURE ABOVE.
<br />25. ALL FLUSH OR RECESSED LIGHT FIXTURES, MECHANICAL TERMINALS, AND FLEXIBLE SPRINKLER HOSE FITTINGS OR OTHER SERVICES WEIGHING 56 LBS OR MORE MUST BE INDEPENDENTLY
<br />SUPPORTED BY NOT LESS THAN FOUR (4) TAUT #12 GAGE WIRES ATTACHED TO THE HOUSING AND TO THE STRUCTURE ABOVE. THE FOUR (4) TAUT #12 GAGE WIRES, INCLUDING THEIR
<br />ATTACHMENT TO THE STRUCTURE ABOVE, MUST BE CAPABLE OF SUPPORTING FOUR (4) TIMES THE WEIGHT OF THE UNIT. ALL 4FT. X 4FT. LIGHT FIXTURES MUST HAVE SLACK SAFETY WIRES AT EACH
<br />CORNER.
<br />26. SURFACE-MOUNTED FIXTURES SHALL BE ATTACHED TO THE MAIN RUNNER WITH AT LEAST TWO POSITIVE CLAMPING DEVICES MADE OF MATERIAL WITH A MINIMUM #14 GAGE. ROTATIONAL
<br />SPRING CATCHES DO NOT COMPLY. A #12 GAGE SUSPENSION WIRE SHALL BE ATTACHED TO EACH CLAMPING DEVICE TO THE STRUCTURE ABOVE. PROVIDE ADDITIONAL SUPPORTS WHEN LIGHT
<br />FIXTURES ARE 8FT. OR LONGER. MAXIMUM SPACING BETWEEN SUPPORTS SHALL NOT EXCEED 8 FEET.
<br />27. SUPPORT PENDANT MOUNTED LIGHT FIXTURES DIRECTLY FROM THE STRUCTURE ABOVE WITH HANGER WIRES OR CABLES PASSING THROUGH EACH PENDANT HANGER AND CAPABLE OF
<br />SUPPORTING TWO (2) TIMES THE WEIGHT OF THE FIXTURE. A BRACING ASSEMBLY, PER DETAIL 16/A5-73, IS REQUIRED WHERE THE PENDANT HANGER PENETRATES THE CEILING. SPECIAL DETAILS ARE
<br />REQUIRED TO ATTACH THE PENDANT HANGER TO THE BRACING ASSEMBLY TO TRANSMIT HORIZONTAL FORCE. IF THE PENDANT MOUNTED LIGHT FIXTURE IS DIRECTLY AND INDEPENDENTLY BRACED
<br />BELOW THE CEILING, I.E. AIRCRAFT CABLES TO WALLS, THEN BRACE ASSEMBLY IS NOT REQUIRED ABOVE THE CEILING. SEE IR 16-9 FOR ADDITIONAL REQUIREMENT FOR PENDANT MOUNTED FIXTURES.
<br />28. ALL LIGHT-WEIGHT MISCELLANEOUS DEVICES, SUCH AS STROBE LIGHTS, SPEAKERS, ETC., SHALL BE ATTACHED TO THE CEILING GRID PER SECTION 7.1 OR IR 25-2.10. IN ADDITION, DEVICES
<br />WEIGHING MORE THAN 10 LBS SHALL HAVE A #12 SLACK SAFETY WIRE ANCHORED TO THE STRUCTURE ABOVE. DEVICES WEIGHING 20 LBS OR MORE SHALL BE SUPPORTED FROM THE STRUCTURE
<br />ABOVE PER SECTION 7.3 OR IR 25-2.10.
<br />29. FIRE RATED CEILINGS: THE COMPONENTS AND INSTALLATION SHALL CONFORM IN EVERY RESPECT WITH U.L. LISTED DETAILS. POP RIVETS, SCREWS, OR OTHER ATTACHMENTS ARE NOT
<br />ACCEPTABLE UNLESS SPECIFICALLY DETAILED AND APPROVED BY U.L. AND STATE FIRE MARSHALL RECOGNIZED LABORATORIES.
<br />30. METAL PANELS AND PALELS WEIGHING MORE THAN 1/2 PSF, OTHER THAN MINERAL FIBER ACOUSTICAL TILE, ARE TO BE POSITIVELY ATTACHED TO THE CEILING SUSPENSION RUNNERS.
<br />31. THE CEILING GRID SYSTEM MUST BE RATED AS HEAVY DUTY AS DEFINED BY ASTM C635. A LIST OF ACCEPTABLE GRID SYSTEMS SHOWN BELOW. THE GRID SYSTEMS SPECIFIED MUST BE
<br />ACCEPTABLE IN ACCORDANCE WITH IR A-5. THE FOLLOWING INFORMATION MUST BE INCLUDED ON THE DRAWINGS FOR EACH ACCEPTABLE GRID SYSTEM SPECIFIED:
<br />CLASSIFICATION OF CEILING GRID IS HEAVY DUTY.
<br />MANUFACTURER'S CATALOG NUMBER - MAIN RUNNER (1) (2)
<br />MANUFACTURER'S CATALOG NUMBER - CROSS RUNNER (2)
<br />MANUFACTURER'S CATALOG NUMBER OF DETAIL FOR RUNNER SPLICE (2)
<br />(1) RUNNERS MUST BE RATED AS HEAVY DUTY.
<br />(2) SHOW MANUFACTURER, DUTY CLASSIFICATION AND CATALOG NUMBERS.
<br />CLASSIFICATION OF CEILING GRID: HEAVY DUTY
<br />CEILING GRID MANUFACTURERS AND PRODUCT SYSTEMS:
<br />NOTE: SYSTEM COMPONENTS, MATERIALS, RUNNER SPLICES, AND
<br />INSTALLATION SHALL BE IN ACCORDANCE WITH THE REQUIREMENTS
<br />OF THE CALIFORNIA BUILDING CODE, THE RESPECTIVE I.C.C. EVALUATION
<br />REPORT, AND THE DSA PRODUCT APPROVAL (PA) LISTED BELOW FOR EACH
<br />MANUFACTURER AND SYSTEM.
<br />USG INTERIORS, INC.
<br />DONN DX SYSTEM (NON-RATED)
<br />DONN DXL SYSTEM (FIRE-RATED)
<br />ICC EVALUATION SERVICE REPORT NO. ER-2244
<br />DSA PA-030
<br />1/4" = 1'-0"3SUSPENDED CEILING SCHEMATIC PLAN1
<br />3" = 1'-0"5COMPRESSION POST1
<br />3" = 1'-0"9WALL/SUSPENDED CEILING INTERSECTION1
<br />1/8" = 1'-0"2ISOMETRIC OF SUSPENDED CEILING BRACING ASSEMBLY1
<br />3" = 1'-0"4TYP. SADDLE TIE @ TRAPEZE1
<br />3" = 1'-0"8WIRE ATTACHMENT AT STRUCTURAL STEEL1
<br />3" = 1'-0"7WIRE ATTACHMENT AT COMPOSITE DECK1
<br />3" = 1'-0"6WIRE ATTACHMENT AT STEEL DECK1
<br />3" = 1'-0"1TYP. PERIMETER CEILING TILE1
<br />25
<br />No.Description Date
|