STATEMENT OF SPECIAL INSPECTIONS <br />1. SPECIAL INSPECTIONS AND TESTS SHALL BE PERFORMED BY AN INDEPENDENT QUALIFIED INSPECTION AND/OR TESTING AGENCY <br />APPROVED BY THE JURISDICTION FOR SUCH WORK,AND IN ACCORDANCE WITH CHAPTER 17 OF THE CODE. THESE SPECIAL <br />INSPECTIONS AND TESTS ARE IN ADDITION TO THE INSPECTIONS PERFORMED BY THE BUILDING OFFICIAL. <br />2. THE OWNER SHALL BE RESPONSIBLE FOR RETAINING THE SPECIAL INSPECTION AND/OR TESTING AGENCY. <br />3. THE SPECIAL INSPECTION AND/OR TESTING AGENCY SHALL KEEP RECORDS AND SUBMIT SPECIAL INSPECTION AND TEST REPORTS <br />TO THE BUILDING OFFICIAL AND THE STRUCTURAL ENGINEER OF RECORD IN ACCORDANCE WITH SECTIONS 1704.2.4 AND 1704.5 OF <br />THE CODE AND JURISDICTION-SPECIFIC REQUIREMENTS. <br />4. THE CONTRACTOR SHALL NOTIFY THE TESTING LAB A MINIMUM OF 48 HOURS PRIOR TO TIME OF INSPECTION. <br />5. THE CONSTRUCTION OR WORK FOR WHICH SPECIAL INSPECTION OR TESTING IS REQUIRED SHALL REMAIN ACCESSIBLE AND <br />EXPOSED FOR SPECIAL INSPECTION OR TESTING PURPOSES UNTIL COMPLETION OF THE REQUIRED SPECIAL INSPECTIONS OR <br />TESTS. THE CONTRACTOR SHALL PROVIDE A MINIMUM OF 3 DAYS NOTICE TO THE APPROVED TESTING AGENCY PRIOR TO ANY REQUIRED <br />INSPECTIONS. <br />6. IF INITIAL TESTS OR INSPECTIONS MADE BY THE OWNER'S TESTING OR INSPECTION AGENCY REVEAL THAT ANY PORTION OF THE <br />WORK DOES NOT COMPLY WITH THE CONTRACT DOCUMENTS, ADDITIONAL TESTS, INSPECTIONS, AND NECESSARY REPAIRS OR <br />CORRECTIONS SHALL BE MADE AT THE CONTRACTOR'S EXPENSE. CONTRACTOR SHALL NOTIFY THE ENGINEER AND OWNER IMMEDIATELY <br />OF NON-CONFORMING WORK. THIS NOTIFICATION SHALL SPECIFICALLY ADDRESS THE NON-CONFORMING WORK AND SHALL BE <br />SEPARATE AND IN ADDITION TO THE SPECIAL INSPECTION REPORTS. <br />7. SPECIAL INSPECTION REPORTS SHALL BE SENT TO THE ENGINEER AT THE TIME OF COMPLETION FOR REVIEW OF CONFORMANCE WITH <br />THE REQUIREMENTS OF THE STRUCTURAL DRAWINGS. AND SPECIFICALLY BRING ANY NON-CONFORMING ITEMS TO THE ATTENTION OF <br />THE REVIEWER <br />8. SPECIAL INSPECTIONS AND TESTS FOR SEISMIC RESISTANCE SHALL BE PERFORMED FOR THE DESIGNATED SEISMIC SYSTEM/SEISMIC <br />FORCE RESISTING COMPONENT WHEN APPLICABLE AND AS PER SECTIONS 1705.12 & 1705.13 OF THE CODE. <br />a. DESIGNATED SEISMIC SYSTEM/SEISMIC FORCE RESISTING SYSTEM: WOOD FRAMED DIAPHRAGM & SHEAR WALLS. <br />SEE THE ABOVE-REFERENCED CODE SECTIONS FOR ADDITIONAL SPECIAL INSPECTION AND TEST REQUIREMENTS FOR <br />STRUCTURAL STEEL, STRUCTURAL WOOD, COLD-FORMED STEEL LIGHT-FRAME CONSTRUCTION, DESIGNATED SEISMIC SYSTEMS, <br />ARCHITECTURAL COMPONENTS, MEP COMPONENTS, STORAGE RACKS, SEISMIC ISOLATIONS SYSTEMS, AND COLD-FORMED <br />STEEL SPECIAL BOLTED MOMENT FRAMES. <br />9. SPECIAL INSPECTIONS FOR WIND RESISTANCE SHALL BE PERFORMED FOR THE MAIN WIND FORCE RESISTING SYSTEM AND WIND <br />RESISTING COMPONENTS WHEN APPLICABLE AND AS PER SECTION 1705.11 OF THE CODE. <br />a. MAIN WIND FORCE RESISTING SYSTEM/WIND RESISTING COMPONENT: WOOD FRAMED DIAPHRAGM & SHEAR WALLS. <br />SEE THE ABOVE-REFERENCED CODE SECTIONS FOR ADDITIONAL SPECIAL INSPECTION REQUIREMENTS FOR <br />STRUCTURAL WOOD, COLD-FORMED STEEL LIGHT-FRAME CONSTRUCTION, AND WIND-RESISTING COMPONENTS. <br />10. EACH CONTRACTOR RESPONSIBLE FOR THE CONSTRUCTION OF A MAIN WIND OR SEISMIC FORCE RESISTING SYSTEM, DESIGNATED <br />SEISMIC SYSTEM, OR A WIND OR SEISMIC RESISTING COMPONENT LISTED ABOVE SHALL SUBMIT A WRITTEN STATEMENT OF <br />RESPONSIBILITY TO THE BUILDING OFFICIAL AND THE OWNER PRIOR TO THE COMMENCEMENT OF WORK ON THE SYSTEM OR <br />COMPONENT. THE CONTRACTOR'S STATEMENT OF RESPONSIBILITY SHALL CONTAIN ACKNOWLEDGMENT OF AWARENESS OF THE <br />SPECIAL REQUIREMENTS CONTAINED IN THIS STATEMENT OF SPECIAL INSPECTIONS. <br />11. STEEL CONSTRUCTION: SPECIAL INSPECTIONS FOR STEEL ELEMENTS OF BUILDINGS AND STRUCTURES SHALL BE AS REQUIRED BY <br />SECTION 1705.2 OF THE CODE AND IN ACCORDANCE WITH THE QUALITY ASSURANCE INSPECTION REQUIREMENTS OF AISC 360, <br />INCLUDING THE SPECIAL INSPECTION TABLE SHOWN HEREIN. SEE ADDITIONAL REQUIREMENTS NOTED FOR SEISMIC AND WIND <br />RESISTANCE OF INSPECTION NOTES #8 AND #9. <br />12. CONCRETE CONSTRUCTION: SPECIAL INSPECTIONS AND VERIFICATIONS FOR CONCRETE CONSTRUCTION SHALL BE AS REQUIRED <br />BY SECTION 1705.3 OF THE CODE, INCLUDING THE SPECIAL INSPECTION TABLE SHOWN HEREIN. <br />CONCRETE SPECIAL INSPECTIONS AND TESTS ARE NOT REQUIRED FOR: <br />a. ISOLATED SPREAD FOOTINGS OF BUILDINGS 3 STORIES OR LESS ABOVE GRADE PLANE THAT ARE FULLY SUPPORTED ON <br />EARTH OR ROCK. <br />b. NONSTRUCTURAL CONCRETE SLABS SUPPORTED DIRECTLY ON THE GROUND, INCLUDING PRESTRESSED SLABS ON GRADE <br />WHERE THE EFFECTIVE PRESTRESS IN THE CONCRETE IS LESS THAN 150 PSI. <br />c. CONCRETE PATIOS, DRIVEWAYS AND SIDEWALKS, ON GRADE. <br />13. MASONRY CONSTRUCTION: SPECIAL INSPECTIONS AND VERIFICATIONS FOR MASONRY CONSTRUCTION SHALL BE AS REQUIRED BY <br />SECTION 1705.4 OF THE CODE AND IN ACCORDANCE WITH TMS 402/ACI 530/ASCE 5 AND TMS 602/ACI 530.1/ASCE 6 QUALITY <br />ASSURANCE REQUIREMENTS, INCLUDING THE SPECIAL INSPECTION TABLES SHOWN HEREIN. <br />14. WOOD CONSTRUCTION: SPECIAL INSPECTIONS FOR WOOD CONSTRUCTION SHALL BE AS REQUIRED BY SECTION 1705.5 OF <br />THE CODE. SEE ALSO REQUIREMENTS NOTED FOR SEISMIC AND WIND RESISTANCE OF INSPECTION NOTES #8 AND #9. <br />15. SOILS: SPECIAL INSPECTIONS FOR EXISTING SOIL CONDITIONS, FILL PLACEMENT, AND LOAD BEARING REQUIREMENTS SHALL BE <br />AS REQUIRED BY SECTIONS 1705.6 THROUGH 1705.9 OF THE CODE, INCLUDING THE SPECIAL INSPECTION TABLES SHOWN HEREIN. <br />16. DEEP FOUNDATIONS: SPECIAL INSPECTIONS FOR DRIVEN AND CAST-IN-PLACE DEEP FOUNDATIONS SHALL BE AS REQUIRED BY SECTIONS <br />1705.7 AND 1705.8 OF THE CODE RESPECTIVELY, INCLUDING THE TESTS AND INSPECTIONS CONTAINED WITHIN THE APPROVED <br />GEOTECHNICAL REPORT, AND INCLUDING THE SPECIAL INSPECTION TABLES SHOWN HEREIN. <br />1. INSPECT REINFORCEMENT, INCLUDING <br />PRESTRESSING TENDONS, AND PLACEMENT. <br />2. INSPECT ANCHORS CAST IN CONCRETE. <br />3. INSPECTION OF ANCHORS <br />POST-INSTALLED IN HARDENED <br />CONCRETE MEMBERS.b <br />a. MECHANICAL ANCHORS AND <br />ADHESIVE ANCHORS <br />4. VERIFY USE OF REQUIRED MIX DESIGN. <br />5. PRIOR TO CONCRETE PLACEMENT, <br />FABRICATE SPECIMENS FOR <br />STRENGTH TESTS, PERFORM SLUMP <br />AND AIR CONTENT TESTS, AND <br />DETERMINE THE TEMPERATURE OF <br />THE CONCRETE. <br />6.. INSPECT FORMWORK FOR SHAPE <br />LOCATION, AND DIMENSIONS OF THE <br />CONCRETE MEMBER BEING FORMED. <br />a. WHERE APPLICABLE, SEE ALSO SECTION 1705.12 (SPECIAL INSPECTIONS FOR SEISMIC RESISTANCE). <br />b. SPECIFIC REQUIREMENTS FOR SPECIAL INSPECTION SHALL BE INCLUDED IN THE RESEARCH REPORT FOR THE ANCHOR <br />ISSUED BY AN APPROVED SOURCE IN ACCORDANCE WITH ACI 318-19 SECTION 17.8.2, OR OTHER QUALIFICATION <br />PROCEDURES. WHERE SPECIFIC REQUIREMENTS ARE NOT PROVIDED, SPECIAL INSPECTION REQUIREMENTS SHALL BE <br />SPECIFIED BY THE REGISTERED DESIGN PROFESSIONAL AND SHALL BE APPROVED BY THE BUILDING OFFICIAL PRIOR TO <br />THE COMMENCEMENT OF THE WORK. <br />REQUIRED SPECIAL INSPECTIONS AND TESTS OF CONCRETE CONSTRUCTION <br />(CBC TABLE 1705.3) <br />VERIFICATION AND INSPECTION CONTINUOUS PERIODIC REFERENCED STANDARD CBC REFERENCE <br />- <br />- <br />- <br />- <br />X <br />- <br />X <br />- <br />X <br />X <br />X <br />- <br />X <br />ACI 318: CH. 20, 25.2, <br />25.3, 26.6.1-26.6.3 <br />ACI 318: 17.8.2, 26.13.3 <br />ACI 318: 17.8.2 <br />ACI 318: CH.19, 26.4.3, <br />26.4.4 <br />ASTM C172, ASTM C31, <br />ACI 318: 26.5, 26.12 <br />ACI 318: 26.11.1.2(b) <br />1908.4 <br />- <br />- <br />- <br />1904.1, 1904.2, <br />1908.2, 1908.3 <br />1908.10 <br />- <br />a <br />1. STRUCTURAL WOOD SPECIAL INSPECTIONS FOR SEISMIC <br />RESISTANCE: <br />a. INSPECTION OF FIELD GLUING OPERATIONS OF <br />ELEMENTS OF THE SEISMIC-FORCE RESISTING SYSTEM. <br />b. INSPECTION OF NAILING, BOLTING, ANCHORING AND <br />OTHER FASTENING OF COMPONENTS WITHIN THE <br />SEISMIC-FORCE RESISTING SYSTEM, INCLUDING WOOD <br />SHEAR WALLS*, WOOD SHEAR PANELS*, WOOD <br />DIAPHRAGMS*, DRAG STRUTS, BRACES, AND HOLD-DOWNS. <br />REQUIRED VERIFICATION AND INSPECTION FOR SEISMIC RESISTANCE (CBC SECTION 1705.12) <br />VERIFICATION AND INSPECTION CONTINUOUS REFERENCED STANDARD <br />X <br />- <br />- <br />X <br />CBC SEC. 1705.12.2 <br />* SPECIAL INSPECTIONS <br />NOT REQUIRED WHERE <br />FASTENER SPACING OF <br />SHEATHING IS MORE THAN <br />4" O.C. <br />PERIODIC <br />2. REINFORCED CONCRETE SPECIAL INSPECTIONS FOR <br />SEISMIC RESISTANCE <br />a. PLACEMENT OF REINFORCING STEEL <br />CBS SEC. 1705.12 <br />ACI 318-14, SEC. 26.13 <br />- <br />b. PLACEMENT OF CONCRETE <br />X ACI 318-14 SEC. 26.13.3 <br />X - ACI 318-14 SEC. 26.13.3 <br />Scale <br />Project number <br />Date <br />Drawn by <br />Jen Dunbar, AIA <br />phone: 310.435.3928 <br />12314 La Maida Street <br />Valley Village, CA 91607 <br />jen@dunbararchitecture.com <br />DUNBAR <br />ARCHITECTURE <br />N.T.S. <br />2/ <br />2 <br />5 <br />/ <br />2 <br />0 <br />2 <br />5 <br /> <br />1 <br />: <br />5 <br />5 <br />: <br />5 <br />3 <br /> <br />P <br />M <br />S0.04 <br />SPECIAL <br />INSPECTIONS & <br />TESTING <br />23005.10 <br />CYPRESS STREET <br />FIRE STATION <br />REHABILITATION <br />CITY OF SANTA ANA <br />01/12/2024 <br />IK <br />625 S. CYPRESS <br />S0.04 N.T.S. <br />1 STATEMENT OF SPECIAL INSPECTIONS <br />S0.04 N.T.S. <br />2 MINIMUM TEST AND SPECIAL INSPECTIONS OF <br />CONCRETE CONSTRUCTION <br />S0.04 N.T.S. <br />3 MINIMUM INSPECTION FOR SEISMIC RESISTANCE <br />No. Description Date <br />1 100% DD ISSUANCE 01/12/2024 <br />2 75% CD ISSUANCE 03/15/2024 <br />3 90% CD ISSUANCE 05/03/2024 <br />4 PERMIT SET 05/17/2024 <br />5 BACKCHECK SET 01/17/2025 <br />EXP. 03/31/26 <br />No. C78947 <br />STATEOF CA LIFORNIA <br />REGISTERED PROF E SSIONALENGINEE <br />R <br />NINAAZAD HMAHJOUB <br />E <br />CI V IL <br />DATE SIGNED <br />02/27/2025 <br />6 2 BACKCHECK SETND 02/27/2025