E0.00
<br />Scale
<br />Jen Dunbar, AIA
<br />phone: 310.435.3928
<br />12314 La Maida Street
<br />Valley Village, CA 91607
<br />jen@dunbararchitecture.com
<br />DUNBAR
<br />ARCHITECTURE
<br />No.Description Date
<br />AS NOTED
<br />Engineering Corp
<br />Mechanical Electrical Plumbing
<br />1920 MAIN STREET, SUITE 820
<br />IRVINE, CA 92614
<br />TEL: 949.516.6480
<br />EFORPDERETS
<br />I
<br />G
<br />ER RE
<br />EN
<br />IGNE
<br />LANOISS
<br />CA L I FORNIASTATEOF
<br />LEC T R ICAL
<br />EXP: 3-31-27
<br />EFORPDERETS
<br />I
<br />G
<br />ER RE
<br />EN
<br />IGNE
<br />LANOISS
<br />CA L I FORNIASTATEOF
<br />No. E21819
<br />E
<br />
<br />ALI S A FAIAN
<br />90% CD 5/02/2024
<br />CYPRESS STREET
<br />FIRE STATION
<br />REHABILITATION
<br />CITY OF SANTA ANA
<br />625 S. CYPRESS
<br />SANTA ANA, CA
<br />Project number
<br />Date
<br />Drawn by TP/HH
<br />23004
<br />1/15/2025
<br />PERMIT SET 5/17/2024
<br />BACK CHECK SET 1/15/2025
<br />BACK CHECK SET_V2 4/08/2025
<br />GENERAL NOTES,
<br />ABBREVIATIONS
<br />AND SYMBOLS
<br />UON UNLESS OTHERWISE NOTED
<br />XFMR
<br />WP
<br />VL
<br />WEATHERPROOF
<br />TRANSFORMER
<br />WATTS
<br />VERIFY LOCATION
<br />VOLTAGE
<br />UL
<br />U/G
<br />TYP
<br />TVSS
<br />TS
<br />TBB
<br />SIM
<br />SWB
<br />SW
<br />R
<br />SCA
<br />RGC
<br />UNDER GROUND
<br />UNDERWRITER'S LABORATORIES
<br />TYPICAL
<br />TELEPHONE BACKBOARD
<br />TIME SWITCH
<br />SIMILAR
<br />SWITCHBOARD
<br />SWITCH
<br />EXISTING, TO BE REMOVED
<br />RIGID GALVANIZED CONDUIT
<br />SHORT CIRCUIT AMPERE
<br />P
<br />PL
<br />PNL
<br />(NR)
<br />NIC
<br />NL
<br />NTS
<br />N
<br />MIN
<br />NA
<br />POLE
<br />PROPERTY LINE
<br />PANEL
<br />NOT IN CONTRACT
<br />NIGHT LIGHT
<br />NOT TO SCALE
<br />NOT APPLICABLE
<br />NEW
<br />MINIMUM
<br />EWH ELECTRIC WATER HEATER
<br />MC
<br />MAX
<br />MFR
<br />IG
<br />LTG
<br />LTA
<br />GND
<br />IC
<br />HP
<br />GFCI
<br />F
<br />MECHANICAL CONTRACTOR
<br />MANUFACTURERS
<br />MAXIMUM
<br />ISOLATED GROUND
<br />LET-THRU AMPS FOR FUSES
<br />LIGHTING
<br />GROUND
<br />HORSEPOWER
<br />FUSE
<br />EQ
<br />EQP
<br />(ER)
<br />EA
<br />EC
<br />CO
<br />(E)
<br />(D)
<br />CONN
<br />CLG
<br />CL
<br />EXISTING, TO REMAIN
<br />EQUIVALENT
<br />EQUIPMENT
<br />ELECTRICAL CONTRACTOR
<br />EACH
<br />CONDUIT ONLY
<br />DEMOLISH
<br />CONNECTED
<br />CEILING
<br />CENTER LINE
<br />ABBREVIATIONS
<br />CB
<br />CKT
<br />CATV
<br />C
<br />BR
<br />BCW
<br />AIC
<br />AFF
<br />A
<br />COMMUNITY ANTENNA TELEVISION
<br />CIRCUIT BREAKER
<br />CIRCUIT
<br />BARE COPPER WIRE
<br />CONDUIT
<br />BRANCH
<br />AMPS INTERRUPTING CAPACITY
<br />ABOVE FINISHED FLOOR
<br />AMPERE
<br />NEW FIRE STATION RENOVATION IN EXISTING CONSTRUCTION. ADDING NEW 400A, 120/240V, 1-PHASE,
<br />3-WIRE SERVICE (NEW SCE METER). PROVIDE POWER (GENERAL AND MECHANICAL), LIGHTING AND
<br />LIGHTING CONTROL.
<br />SCOPE OF WORK:
<br />-2022 CALIFORNIA ELECTRICAL CODE.
<br />-2022CALIFORNIA MECHANICAL CODE.
<br />-2022 CALIFORNIA ENERGY CODE.
<br />-2022 CALIFORNIA FIRE CODE.
<br />-2022 CALIFORNIA PLUMBING CODE.
<br />-NFPA 99 STANDARDS APPLICABLE TO PROJECT.
<br />-CITY OF SANTA ANA AMENDMENTS
<br />EXISTING, TO BE
<br />RELOCATED AS
<br />SHOWN
<br />GROUND FAULT
<br />CIRCUIT INTERRUPTER
<br />INTERRUPTING
<br />CAPACITY (RMS SYM.)
<br />APPLICABLE CODES:
<br />INDICATES NEW LOCATION OF
<br />RELOCATED DEVICE. PROVIDE
<br />ADDITIONAL CONDUITS, WIRES,
<br />BOXES, ETC. TO RE-ESTABLISH
<br />CIRCUITRY AS BEFORE.
<br />TRANSIENT VOLTAGE
<br />SURGE SUPPRESSOR
<br />OPEN STRIP FLUCRESCENT
<br />EMERGENCY LIGHT FIXTURE WITH BATTERY PACK
<br />FLUORESCENT LIGHT FIXTURE AS SPECIFIED
<br />WALL WASHER LIGHT FIXTURE, ARROW DENOTES AIMING DIRECTION
<br />JUNCTION BOX, SIZE AS NOTED AND PER CODE.
<br />JUNCTION BOX WITH FLEXIBLE CONDUIT CONNECTED TO DEVICE OR EQUIPMENT.
<br />DISCONNECT SWITCH, 30A, 3-POLE, NON-FUSED
<br />WITH 1-1/4" C.O. AND PULL ROPE STUB UP TO NEAREST ACCESSIBLE CEILING SPACE.
<br />CONDUIT TURNING UP
<br />CONDUIT TURNING DOWN
<br />DISCONNECT SWITCH, 60A, W/45A FUSE, 3-POLE (UON)
<br />HOMERUN TO PANEL A CIRCUITS 1&3
<br />CONDUIT EXPOSED
<br />CONDUIT CONCEALED IN FLOOR SLAB OR UNDERGROUND
<br />GROUND, PER CODE AND AS SPECIFIED
<br />UTILITY METERING
<br />CIRCUIT BREAKER, 150A, 3-POLE
<br />TELEPHONE CONDUIT/HOMERUN, SIZE AS NOTED
<br />SWITCH & FUSE, 100AS, 75 AF, TYPE AS NOTED, 3-POLE (UON)
<br />SWITCHBOARD
<br />LIGHT FIXTURE TYPE F1, 40W EACH, TYPICAL IN A ROOM OR AREA
<br />FLUSH MOUNTED PANEL BOARD, B INDICATES NAME
<br />SURFACE MOUNTED PANEL BOARD, A INDICATES NAME
<br />REFERENCE NOTE #1
<br />REFERENCE TO DETAIL #2 ON SHEET E2.0
<br />OUTLET FOR TELEPHONE/DATA ONLY @+18" (UON) PROVIDE A 5S J-BOX WITH MUD RING AND
<br />FLUSH MOUNTED DUPLEX RECEPTACLE OUTLET 250V 2P, 3W, 20A (NEMA 6-20R)
<br />SYMBOLS
<br />WALLFLOOR CEILING
<br />DM a
<br />OUTLET FOR WAP
<br />HOMERUN TO PANEL A CIRCUITS 1&3 WITH GRAND WIRE
<br />EXIT SIGN, SINGLE FACE, ARROW IF INDICATED DENOTES DIRECTION
<br />SINGLE POLE TOGGLE SWITCH @+48"(UON), SUBSCRIPTS INDICATE THE FOLLOWING:
<br />A - OUTLET 'A' CONTROLLED
<br />DM - DIMMER,
<br />RATING AS NOTED
<br />M - MANUAL MOTOR STARTER
<br />P - PILOT ON LIGHT
<br />PULL ROPE STUB UP TO NEAREST ACCESSIBLE CEILING SPACE.
<br />OUTLET FOR DATA ONLY @+18" (UON) PROVIDE A J-BOX WITH 1-1/4" C.O. AND
<br />OUTLET FOR TELEPHONE ONLY @+18" (UON) PROVIDE A J-BOX WITH 1-1/4" C.O. AND
<br />PULL ROPE STUB UP TO NEAREST ACCESSIBLE CEILING SPACE.
<br />OUTLET FOR DATA ONLY PROVIDE A J-BOX, NUMBER INDICATES QUANTITY
<br />OF THE JACKS IN THE SAME DATA OUTLET
<br />REPRESENTS WITH SINGLE SWITCH; a,b REPRESENTS WITH DUAL SWITCHES
<br />COMBINATION OF MOTOR STARTER AND CIRCUIT BREAKER, NEMA SIZE '1' (UON)
<br />CONDUIT CONCEALED IN CEILING OR WALL, 3/4" CONDUIT, 2#12 WIRES (UON)
<br />1
<br />2
<br />E2.0
<br />OS
<br />1.INFORMATION GIVEN ON THE DRAWINGS REGARDING EXISTING INSTALLATION HAS BEEN OBTAINED
<br />FROM THE BEST SOURCES AVAILABLE. HOWEVER IT CANNOT BE GUARANTEED IN ALL RESPECTS.
<br />VERIFY ALL SUCH INFORMATION BEFORE PROCEEDING WITH THE NEW WORK THAT MAY BE AFFECTED
<br />UPON. INCLUDE AS A PART OF THE CONTRACT ALL WORK THAT ARE REQUIRED TO PRODUCE
<br />INDICATED RESULT BEFORE SUBMITTING THE BID PROPOSAL.
<br />2.THE SCOPE OF WORK SHALL INCLUDE THE FURNISHING OF ALL MATERIALS, EQUIPMENT, SUPPLIES AND
<br />LABOR AND THE PERFORMANCE OF ALL OPERATIONS NECESSARY FOR THE INSTALLATION OF ALL
<br />ELECTRICAL WORK, COMPLETE AND IN OPERATING CONDITION, ALL TO THE SATISFACTION OF
<br />UNIVERSITY'S REPRESENTATIVE. THE ENTIRE INSTALLATION SHALL BE READY IN EVERY RESPECT FOR
<br />SATISFACTORY AND EFFICIENT OPERATION WHEN COMPLETED.
<br />3.PROVIDE ALL MATERIALS AND EQUIPMENT TO MAKE FINAL CONNECTIONS TO ALL EQUIPMENT AND
<br />APPLIANCES.
<br />4.NOTHING DESCRIBED HEREIN OR INDICATED ON THE DRAWINGS SHALL BE CONSTRUED TO PERMIT
<br />WORK NOT CONFORMING TO THE MOST STRINGENT OF THE APPLICABLE CODES AND REGULATIONS.
<br />5.ALL WORK SHALL BE DONE IN FULL COMPLIANCE WITH THE CALIFORNIA ELECTRICAL CODE, 2022
<br />EDITION AND 2022 CALIFORNIA TITLE-24 ENERGY STANDARDS AND IN ACCORDANCE WITH THE
<br />REQUIREMENTS OF THE LOCAL AUTHORITIES HAVING JURISDICTION.
<br />6.ALL EQUIPMENT AND MATERIALS SHALL BE NEW AND SHALL BE LISTED BY THE UNDERWRITER'S
<br />LABORATORIES, MANUFACTURED IN FULL COMPLIANCE WITH ASME, ANSI, IEEE AND NEMA.
<br />7.ELECTRICAL DRAWINGS ARE DIAGRAMMATIC. SIZES, LOCATION OF EQUIPMENT, AND WIRING ARE
<br />SHOWN TO SCALE WHERE POSSIBLE, BUT MAY BE DISTORTED FOR CLARITY. FINAL LOCATIONS OF
<br />OUTLETS AND EQUIPMENT SHALL BE ADJUSTED AS DICTATED BY EXISTING CONDITIONS. IT IS NOT
<br />WITHIN THE SCOPE OF DRAWINGS TO SHOW ALL NECESSARY BENDS, OFFSETS, AND PULLBOXES. IT
<br />SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO INSTALL HIS WORK TO CONFORM TO THE
<br />STRUCTURE. CONDUIT RUNS ARE INDICATED DIAGRAMMATICALLY, DETERMINE EXACT LOCATION IN THE
<br />FIELD.
<br />8.DURING THE PROGRESS OF THE WORK, MAKE A CAREFUL RECORD OF ALL CHANGES BY WHICH THE
<br />ACTUAL INSTALLATION DIFFERS FROM THAT INDICATED ON THE CONTRACT DRAWINGS AND
<br />DOCUMENTS.
<br />9.ANY ERROR, OMISSION OR DESIGN DISCREPANCY ON THE CONSTRUCTION DOCUMENTS SHALL BE
<br />BROUGHT TO THE ATTENTION OF UNIVERSITY'S REPRESENTATIVE FOR CLARIFICATION OR CORRECTION
<br />PRIOR TO INSTALLATION.
<br />10.THE WORD "VERIFY LOCATION" ABBREVIATED AS "V.L." SHALL MEAN TO COORDINATE THE EXACT
<br />LOCATION OF THE DEVICE AND/OR EQUIPMENT BEING REFERRED TO WITH UNIVERSITY'S
<br />REPRESENTATIVE AND TO PROVIDE NECESSARY ADJUSTMENT WITHOUT ANY EXTRA COST TO THE
<br />UNIVERSITY.
<br />11.CONTRACTOR SHALL GUARANTEE ALL WORKMANSHIP, EQUIPMENT AND MATERIALS FOR A PERIOD OF
<br />NOT LESS THAN ONE(1) YEAR FOR THE UNIVERSITY. SHOULD ANY DEFECTS OCCUR DURING THIS
<br />PERIOD, THE CONTRACTOR SHALL PROMPTLY REPAIR OR REPLACE THE DEFECTIVE ITEMS AT NO
<br />ADDITIONAL COSTS TO THE UNIVERSITY, INCLUDING COST OF LABOR AND MATERIALS.
<br />12.ARCHITECTURAL SPECIFICATIONS, GENERAL, SPECIAL AND SUPPLEMENTAL CONDITIONS SHALL FORM A
<br />PART OF THIS CONSTRUCTION DOCUMENT.
<br />13.UPON COMPLETION OF THE WORK, CONDUCT AN OPERATING TEST AND DEMONSTRATE TO THE
<br />UNIVERSITY'S REPRESENTATIVE THAT ALL EQUIPMENT ARE OPERATING IN A SATISFACTORY MANNER
<br />AND IN ACCORDANCE TO THE REQUIREMENTS OF DRAWINGS.
<br />14.USE ELECTRICAL METALLIC TUBING FOR TRADE SIZES OF 3/4 TO 2 INCHES INCLUSIVE IN DRY
<br />LOCATIONS, USE RIGID METALLIC CONDUIT IN EXTERIOR INSTALLATION. USE RIGID METALLIC CONDUIT
<br />FOR ANY FEEDERS.
<br />15.USE FLEXIBLE STEEL CONDUITS FOR SHORT CONNECTIONS TO MOTORS AND IN DRY LOCATIONS I.E.
<br />ABOVE ACCESSIBLE CEILING FOR LIGHTING AND CONVENIENT OUTLETS BRANCH CIRCUITING, AND IN
<br />STUD WALLS WHERE ALLOWED BY THE LOCAL CODE. USE LIQUID TIGHT FLEXIBLE CONDUITS IN AREAS
<br />EXPOSED TO WEATHER. PROVIDE INTEGRAL GROUNDING CONDUCTOR FOR LENGTHS EXCEEDING 6
<br />FEET. FLEXIBLE CONDUITS FOR CONNECTION TO THE ROOF TOP AIR CONDITIONERS SHALL BE
<br />PROVIDED WITH INTEGRAL GROUND WIRE REGARDLESS OF THE LENGTH.
<br />16.OUTLET AND JUNCTION BOXES SHALL BE GALVANIZED PRESSED STEEL WITH PLUGGED HOLES. ALL
<br />BOXES SHALL BE OF CEC CODE SIZE FOR THE NUMBER OF WIRES OR CONDUITS PASSING THROUGH OR
<br />TERMINATING THEREIN BUT IN NO CASE SHALL ANY BOX BE LESS THAN 4 INCHES SQUARE BY 2-1/8
<br />INCHES DEEP. NO PLASTIC BOXES SHALL BE ALLOWED.
<br />17.SINGLE CONDUCTOR COPPER WIRE WITH 600 VOLTS INSULATION SHALL BE USED FOR GENERAL WIRING
<br />IN CONDUIT UNLESS OTHERWISE SHOWN. ALL CONTACTS, GROUNDING AND NEUTRAL BUS BARS SHALL
<br />BE COPPER.
<br />18.CONDUCTORS 8-AWG AND LARGER SHALL BE STRANDED TYPE. CONDUCTORS 10-AWG AND SMALLER
<br />SHALL BE SOLID WITH COLOR CODED INSULATION.
<br />19.PROVIDE CONDUCTORS TYPE THW OR THWN FOR DRY AND WET LOCATIONS AND THHN FOR DRY
<br />LOCATIONS ONLY.
<br />20.MINIMUM SIZE CONDUCTOR FOR USE IN LIGHTING AND POWER BRANCH CIRCUITS SHALL BE 12-AWG.
<br />21.NO WIRE AMPACITY REDUCTION SHALL BE ALLOWED ON THE FEEDERS AND BRANCH CIRCUIT WIRING
<br />INCLUDING NEUTRALS UNLESS APPROVED BY THE UNIVERSITY'S REPRESENTATIVE.
<br />22.LABEL ALL CONDUIT, JUNCTION BOXES, PANELS AND TRANSFORMERS WITH THE VOLTAGE AND CIRCUIT
<br />NUMBER(S).
<br />23.ENGRAVE ALL SWITCHES AND OUTLETS WITH PANEL AND CIRCUIT NUMBER.
<br />24.WIRES AND CONDUITS SIZES INDICATED THROUGHOUT THE DRAWINGS ARE BASED ON COPPER
<br />CONDUCTORS.
<br />25.MINIMUM SIZE OF CONDUIT FOR POWER, LIGHTING, AND MECHANICAL EQUIPMENT SHALL BE 3/4" (UON).
<br />26.SHOP DRAWING SUBMITTALS ARE REQUIRED FOR THE FOLLOWING MATERIAL/EQUIPMENT:
<br />A.LIGHTING FIXTURES.
<br />B.SPECIAL OR BUILT-TO-ORDER EQUIPMENT.
<br />26.LIGHTING FIXTURES SHALL BE COMPLETE WITH ALL GLASSWARE, FITTERS, CANOPIES, SOCKETS,
<br />MOUNTING BRACKETS, REFLECTORS, LAMPS AND ALL ACCESSORIES AS REQUIRED.
<br />27.FIXTURE SCHEDULE INDICATES GENERAL DESCRIPTION OF LIGHTING FIXTURES AND MANUFACTURER'S
<br />CATALOG NUMBERS. IT SHALL BE THE CONTRACTOR'S RESPONSIBILITY TO STUDY THE SCHEDULE AND
<br />CAREFULLY REVIEW ELECTRICAL AND ARCHITECTURAL PLANS AND SPECIFICATIONS TO DETERMINE
<br />THE CORRECT CEILING CONFIGURATION AND FIXTURES TO BE FURNISHED SO THAT BOTH CEILING
<br />SYSTEM AND LIGHT FIXTURE CONSTRUCTION MATCHES.
<br />28.COORDINATE EXACT LOCATION OF THE LIGHTING FIXTURES WITH THE ARCHITECTURAL DRAWINGS. IF
<br />ANY DISCREPANCIES EXIST, THEY SHALL BE BROUGHT TO THE ATTENTION OF THE UNIVERSITY'S
<br />REPRESENTATIVE FOR CLARIFICATION PRIOR TO INSTALLATION.
<br />29.LIGHTING FIXTURES FINISHES WHETHER OR NOT SHOWN ON THE DRAWINGS SHALL BE APPROVED BY
<br />UNIVERSITY'S REPRESENTATIVE.
<br />30.PROVIDE GROUNDING SYSTEM PER 2022 CEC AND AS INDICATED.
<br />31.ALL METAL AND NON-CURRENT CARRYING PART OF THE ELECTRICAL EQUIPMENT SHALL BE BONDED TO
<br />GROUND PER CEC CODE ARTICLE 250.
<br />32.PROVIDE A TYPE-WRITTEN INDEX CARD FOR EACH PANEL BOARD INDICATING NAME OR NUMBER OF THE
<br />ROOM, AREA, OR EQUIPMENT USED BY EACH BRANCH CIRCUIT. USE ROOM NUMBERS AND NAMES
<br />VERIFIED IN THE FIELD AND NOT NECESSARILY THOSE SHOWN ON THE DRAWINGS.
<br />33.PROVIDE FIREPROOFING FOR RECESS MOUNTED FIXTURES. RECEPTACLES, AND CONDUIT IN FIRE
<br />RATED AREAS. SEE ARCHITECTURAL PLANS FOR DETAIL AND LOCATION.
<br />34.ALL SHUTDOWN SHALL BE COORDINATED WITH THE UNIVERSITY'S REPRESENTATIVE.
<br />35.TEMPORARY MATERIALS MUST BE REMOVED WITHOUT SHUTDOWN AS CONSTRUCTION PROGRESSES.
<br />36.RESTORE PERMANENT FACILITIES TO THEIR FORMER OR NEWLY SPECIFIED CONDITION.
<br />GENERAL NOTES
<br />DESCRIPTION
<br />W
<br />V
<br />LIGHT FIXTURE AS SPECIFIED, SUBSCRIPTS WHEN INDICATED DENOTE BRANCH
<br />CIRCUIT/SWITCH LEG
<br />CROSS LINES DENOTE NUMBER OF #12 WIRE, SIZE CONDUIT PER CODE AND AS NOTED ON
<br />PLANS, NOT INCLUDING EQUIPMENT GROUND WIRE
<br />FLUSH MOUNTED DOUBLE DUPLEX RECEPTACLE OUTLET @ +18" U.O.N. 125V 2P, 3W, 20A
<br />(NEMA 5-20R)
<br />FLUSH MOUNTED GFCI DUPLEX RECEPTACLE OUTLET @ +18" UON 125V 2P, 3W, 20A (NEMA 5-20R)
<br />WHITE COLOR
<br />FLUSH MOUNTED DUPLEX RECEPTACLE OUTLET @ +18" UON 125V 2P, 3W, 20A (NEMA 5-20R)
<br />WHITE COLOR
<br />E0.00:GENERAL NOTES, ABBREVIATIONS AND SYMBOLS
<br />E0.10:SINGLE LINE DIAGRAM, AND PANEL SCHEDULES
<br />E0.11:LIGHTING FIXTURE SCHEDULES
<br />E1.00:ELECTRICAL SITE PLAN
<br />E1.01:METER /MAIN LOCATION ELEVATION
<br />E1.10:POWER PLAN
<br />E1.11:MECHANICAL POWER PLAN
<br />E1.12:ELECTRICAL ROOF PLAN
<br />E2.10:LIGHTING PLAN
<br />E2.11:EMERGENCY LIGHTING PHOTOMETRIC PLAN
<br />E2.12:LIGHTING CONTROL DETAILS
<br />E3.01:INDOOR LIGHTING TITLE 24 COMPLIANCE FORMS
<br />E3.02:OUTDOOR LIGHTING TITLE 24 COMPLIANCE FORMS
<br />E3.03:ELECTRICAL POWER DISTRIBUTION TITLE 24 COMPLIANCE FORMS
<br />E4.01:ELECTRICAL DETAILS
<br />ED1.10:ELECTRICAL DEMOLITION PLAN
<br />DRAWING LIST:
|