Laserfiche WebLink
M <br />'M''1' <br />PROPOSED NEW "MS-502" <br />4000 AMP MAIN SERVICE <br />480Y277V, 3PH, 4-WIRE <br />NEMA-3R, RAINTIGHT <br />100,000 AIC <br />MCC <br />T <br />NEW "MS1" <br />600 AMP DISTRIBUTION PANEL <br />480Y277V, 3PH, 4-WIRE <br />NEMA-1 INDOOR <br />42,000 AIC MINIMUM <br />T <br />600A BUS <br />4000 AMP BUS <br />400A <br />3P <br />200A <br />3P <br />400A <br />3P <br />200A <br />3P <br />600A <br />3P <br />200A <br />3P <br />200A <br />3P <br />200A <br />3P <br />600A <br />3P <br />1 2 3 4 5 6 7 8 9 10 12 <br />10 2 1 4 7 2 6 <br />4000A <br />UGPS <br />W/LUGS <br />4000A <br />3P <br />100K <br />ISC <br />GFP <br />3/4" - 1#3/0 CU TO C.W. <br />PIPE AND TO GROUND <br />RODS <br />CABLE TRENCH <br />PROPOSED <br />10'X12' <br />CUSTOMER <br />SLAB BOX <br />ONE 5" <br />PROPOSED <br />5'X11' <br />SWITCH PAD <br />ONE 5" PVC SCH. 40 <br />TO SCE SERVICE POINT <br />PRESS <br />#9 A <br />PRESS <br />#9 B <br />200A <br />480Y 277V <br />3PH, 4W <br />MAINT. BUILDING PRESS 7 <br />800A <br />480V <br />3PH, 3W <br />A <br />PRESS <br />#6B <br />PRESS <br />#6A <br />PRESS <br />#5B <br />SEE <br />MS1 <br />357.1A 456.2A 96.0A 226.0A 90.1A 522.2A 100.3A 124.0A 116.3A <br />318.52A <br />UTILITY COMPANY CONTRIBUTION TO <br />THE AVAILABLE FAULT CURRENT <br />WILL NOT EXCEED 54,400 AMPS <br />1735.8 KW <br /> X 1.25 <br />2,169.75 KVA <br />(PEAK DEMAND BRANCH # 1 - #11) <br />CEC 220.87 <br />2,169.75 KVA <br />480 3V =2613 AMPS <br /> 397.7 AMPS (BRANCH #12) <br /> 3,010.7 AMPS <br />NEW 16"X16"X4" <br />(MINIMUM) <br />PULL BOX <br />SEE ABOVE <br />3/4" -1#3/0 CU TO C.W. <br />PIPE AND TO GROUND <br />RODS (AT 516 BUILDING ) <br />NEW 600/3P SERVICE <br />RATED DISCONNECT <br />WITH (3) 600 AF. <br />NEMA 3R <br />8 C <br />9 10 9 11 <br />1 2 3 4 <br />600 A <br />3P <br />MAIN <br />42K <br />ISC <br />50 A <br />3P <br />42K <br />ISC <br />400 A <br />3P <br />42K <br />ISC <br />70 A <br />3P <br />42K <br />ISC <br />200 A <br />3P <br />42K <br />ISC <br />7 <br />37.5 KVA 15 KVA <br />HEAT <br />TREAT <br />OVEN 4A <br />OFFICE <br />47.1A <br />48.8A <br />175.0A <br />211.6 KW <br /> X 1.25 <br />264.5 KVA <br />(PEAK DEMAND) <br />264.5 KVA/480 3 V = 318.52 AMPS <br />PNL LA2 <br />#4 CU <br />100AMP <br />14 <br />3P <br />200AMP 3P <br />15 <br />#4 CU <br />T <br />25 KVA #4 CU <br />14 <br />PNL HA1 PNL LA1 PNL LB <br />PNL HA <br />T <br />75 KVA #4 CU <br />PNL HA2 <br />502B <br />PNL 502A <br />HA <br />600A <br />3P <br />PNL 502B <br />HB <br />07 <br />150A <br />3P <br />PRESS <br />#5A <br />12 <br />100A <br />3P <br />200 AMP <br />75A85A <br />PNL 502A <br />OVEN <br />2 <br />200A <br />3P <br />L=145' <br />VD=.35% <br />L=155' <br />VD=.5% <br />L=65' <br />VD=.21% <br />L=145' <br />VD=.40% <br />L=150' <br />VD=.36% <br />L=170' <br />VD=.44% <br />L=130' <br />VD=.46% <br />L=175' <br />VD=.50% <br />L=180' <br />VD=.64% <br />L=185' <br />VD=.62% <br />L=190' <br />VD=.62% <br />L=220' <br />VD=.62% <br />11 <br />200AMP <br />3P <br />2 <br />PNL B1 <br />100AMP <br />3P <br />#4 CU <br />PNL LB1 <br />200AMP <br />3P <br />2"C-4#3/0 THHN CU <br />(EMT ) 1#4 GRD <br />(EMT) <br />LOAD CALCULATION <br />LOAD CALCULATION <br />MS-502 <br />MS1 <br />L-15' <br />28,471 A <br />26,406 A <br />4000 AMP SERVICE IS ADEQUATE <br />MS1 IS ADEQUATE <br />AIC =44,000 <br />L-10' <br />37,840 A <br />23,798 A 42,340 A 17,123 A <br />17,129 A 23,774 A <br />B <br />15,285 A 33,818 A <br />15,868 A 14,656 A 14,656 A 10,959 A 28,471 A <br />8 <br />PB <br />50AMP 3P 70AMP 3P <br />16 17 <br />(N)(N)(E) <br />(N) <br />(N) <br />(N) <br />(E)(E) <br />(E) <br />(E) <br />(E) <br />(E)(E)(E)(E) <br />(N) <br />(N) <br />(E) <br />(E) <br />(N) <br />(N) <br />(E) <br />(E) <br />(E) <br />(E) <br />(E) <br />(E) <br />(E) <br />(N)(N) <br />1"C-3#2 THHN CU. <br />1#8 CU GRD <br />T-LB1 <br />75 KVA <br />480V-120/208V, 3Ø, 4W <br />150AMP <br />3P <br />PNL LB2 <br />125AMP <br />3P <br />(E) <br />1 <br />COPYRIGHT LEWIS ROSS ASSOCIATES <br />FILE NAME: <br />SHEET <br />NUMBER: <br />DESCRIPTION: <br />PROJECT NAME: <br />DRAWN BY: <br />SCALE: <br />DATE: <br />PROJECT NO.: <br />CLIENT: <br />PROJECT NO. <br />PROJECT: <br />AS SHOWN <br />OST <br />ALUMINUM PRECISION PRODUCTS <br />04-14-2025 <br />24-121 <br />NEC ELECTRIC <br />INC. <br />24-121 <br />ALUMINUM <br />PRECISION <br />PRODUCT <br />ADDRESS: <br />502 E. ALTON AVE. <br />516 E. ALTON AVE. <br />SANTA ANA, CA 92707 <br />17015 SO. BROADWAY ST. <br />GARDENA, CA 90248 <br />REV DESCRIPTION DATE <br />9401 RESEDA BLVD. SUITE 200 <br />NORTHRIDGE, CA 91324 <br />PHONE: (818) 886-2190 FAX: (818) 886-2131 <br />PLAN CHECK 11-13-2024- <br />Lewis Ross Dropbox\Projects\2020\20-180 17806 <br />Lassen\LRA Drawings <br />PLAN CHECK CORRECTIONS 01-16-20251 <br />CORRECTIONS 04-14-20252 <br />E-0.3 <br />SINGLE LINE DIAGRAM <br />SINGLE LINE DIAGRAM <br />N.T.S. <br />FEEDER SCHEDULE <br />TAG FEEDER <br />1 3 1/2" EMT WITH 3#500 MCM AND 1#3 THHN CU <br />2 2 1/2" EMT WITH 3#3/0 AND 1#6 THHN CU <br />3 THREE 3 1/2" EMT WITH 3#400 MCM AND 1#2/0 THHN CU EACH (TRIPLE <br />PARALLEL RUN) <br />4 3" PVC SCH. 40 WITH 4#3/0 AND 1#6 THWN CU <br />5 THREE 3" EMT WITH 3#300 MCM AND 1#1/0 THHN CU EACH(TRIPLE PARALLEL <br />RUN) <br />6 TWO 4" PVC SCH. 40 WITH 4#350 MCM AND 1#1 THWN CU EACH (PARALLEL <br />RUN) <br />7 TWO 3" EMT WITH 3#350 MCM AND 1#1 THHN CU EACH (PARALLEL RUN) <br />8 TWO 3" EMT WITH 4#350 MCM THWN CU EACH AND 1#1 THHN CU <br />9 1 1/2" EMT WITH 3#4 AND 1#8 THHN CU <br />10 4" EMT WITH 3#600 MCM AND 1#2/0 THHN CU <br />11 2" EMT WITH 3#3/0 AND 1#6 THHN CU <br />12 2"-3#1/0, 1#6 THHN CU <br />13 2"-4#3/0, 1#6 THHN CU <br />14 1 1/4"C EMT 4#2 THHN CU, 1#8 GRD CU <br />15 2" EMT 4#3/0 THHN CU, 1#1 THHN CU <br />16 1"C 4#8 THHN CU EMT, 1#8 THHN CU <br />17 1 1/4"C 4#4 THHN CU EMT, 1#8 THHN CU <br />TABLE OF APPROXIMATE <br />AVAILABLE FAULT CURRENTS <br />NODE LOCATION AAFC <br />A PANEL "M"15,285A <br />B MCC-1 33,818A <br />C MS1 28,471A <br />PANEL "M" TO BE BRACED/RATED FOR <br />22,000 AIC MINIMUM. <br />MCC-1 TO BE BRACED/RATED FOR <br />35,000 AIC MINIMUM. <br />MS1 TO BE BRACED/RATED FOR <br />42,000 AIC MINIMUM. <br />REFERENCE NOTES <br />CHANGE EXISTING 800AMP BREAKER TO A 3 POLE, 600AMP, 100 KAIC BREAKER.ITEMS MARKED (N) OR SHOWN <br />DARK ARE NEW. ITEMS SHOWN <br />LIGHTS OR MARKED (E) ARE <br />EXISTING. <br />FAULT CURRENT IS 54,400 AIC. <br />2 <br />CHANGING THE TRIP PLUG TO 600AMP. <br />2 <br />ALL LOADS ARE EXISTING AND IN OPERATION. FED FROM THE EXISTING 1600A <br />OVERHEAD SERVICE. <br />BUILDING GROUND TO BE BONDED TO THE ECG OF THE THE FEEDER ONLY. <br />THE GROUND FAULT PROTECTION SYSTEM SHALL BE PERFORMANCE TESTED WHEN <br />FIRST INSTALLED ON SITE. THIS TESTING SHALL BE CONDUCTED BY A QUALIFIED <br />PERSON(S) USING A TEST PROCESS OF PRIMARY CURRENT INJECTION, IN <br />ACCORDANCE WITH INSTRUCTIONS THAT SHALL BE PROVIDED WITH THE EQUIPMENT. A <br />WRITTEN RECORD OF THIS TESTING SHALL BE MADE AND SHALL BE AVAILABLE TO THE <br />AUTHORITY HAVING JURISDICTION. CEC 230.95(C) <br />2 <br />2 <br />2 <br />2