GENERAL NOTESABBREVIATIONSAPPLICABLE STANDARDS
<br />ANNOTATION SYMBOLS
<br />LEGENDLEGEND
<br />E0.1 SYMBOLS, DESIGNATION AND ABBREVIATIONS
<br />E0.2 SINGLE LINE DIAGRAM
<br />E0.3 ELECTRICAL SCHEDULES
<br />E0.4 TITLE-24 COMPLIANCE FORMS
<br />E1.1 PARTIAL FIRST FLOOR DEMOLITION PLAN
<br />E2.1 PARTIAL FIRST FLOOR POWER INSTALLATION PLAN
<br />E2.2 ROOF POWER PLAN
<br />E3.1 PARTIAL FIRST FLOOR LIGHTING INSTALLATION PLAN
<br />E3.2 PARTIAL FIRST FLOOR NORMAL AND EMERGENCY
<br />PHOTOMETRICS PLANS
<br />E5.1 ELECTRICAL DETAILS
<br />E7.1 ELECTRICAL SPECIFICATIONS
<br />E7.2 ELECTRICAL SPECIFICATIONS
<br />E7.3 ELECTRICAL SPECIFICATIONS
<br />E7.4 ELECTRICAL SPECIFICATIONS
<br />1.ELECTRICAL CONTRACTOR SHALL PERFORM ELECTRICAL
<br />INSTALLATION WORK IN CONFORMANCE WITH THE 2022
<br />EDITION OF THE CALIFORNIA ELECTRICAL CODE (CEC) AND
<br />ALL APPLICABLE CODES, ORDINANCES, REGULATIONS AND
<br />CITY/COUNTY STANDARDS.
<br />2.CONDUIT ROUTING AND OUTLET LOCATION AS SHOWN ON
<br />THE ELECTRICAL POWER PLAN ARE DIAGRAMMATIC IN
<br />NATURE. VERIFY FEASIBILITY OF THE INSTALLATION
<br />BEFORE COMMENCING THE JOB. ANY OBSERVATIONS TO
<br />THE EXECUTION OF THE WORK SHALL BE BROUGHT TO
<br />THE ATTENTION OF THE OWNER'S REPRESENTATIVE
<br />IMMEDIATELY.
<br />3.COORDINATE ALL WORK WITH OTHER CONSTRUCTION.
<br />NOTIFY THE OWNER'S REPRESENTATIVE OF ANY
<br />UNRESOLVED ISSUES THAT MAY DELAY INSTALLATION OF
<br />WORK.
<br />4.MAINTAIN PROPER WORKING SPACE PER CALIFORNIA
<br />ELECTRICAL CODE (CEC), PARAGRAPH 110-26.
<br />5.PROVIDE NECESSARY HARDWARE AND SUPPORTS AS
<br />REQUIRED FOR ELECTRICAL CONDUIT/WIRE NOT
<br />SCHEDULED FOR DEMOLITION PER CALIFORNIA
<br />ELECTRICAL CODE (CEC), PARAGRAPH 110-12.
<br />6.CONNECTIONS TO VIBRATING EQUIPMENT AND SEISMIC
<br />SEPARATIONS:
<br />·LIQUID-TIGHT FLEXIBLE STEEL CONDUIT IN DRY
<br />INTERIOR LOCATIONS.
<br />·LIQUID-TIGHT FLEXIBLE STEEL CONDUIT IN AREAS
<br />EXPOSED TO WEATHER, DAMP LOCATIONS,
<br />CONNECTIONS TO TRANSFORMER ENCLOSURES, AND
<br />FINAL CONNECTIONS TO MOTORS.
<br />PROVIDE A SEPARATE INSULATED EQUIPMENT GROUNDING
<br />CONDUCTOR IN FLEXIBLE CONDUIT RUNS. MAXIMUM
<br />LENGTH SHALL BE SIX FEET UNLESS OTHERWISE NOTED.
<br />7.EQUIPMENT OUTLETS, LIGHTING FIXTURES, CONDUIT,
<br />WIRE, AND CONNECTION METHODS IN HVAC AIR-PLENUMS
<br />SHALL BE APPROVED FOR USE IN PLENUMS AND SHALL
<br />CONFORM TO THE CEC.
<br />8.ROUTE EXPOSED CONDUIT AND CONDUIT ABOVE
<br />ACCESSIBLE CEILING SPACES PARALLEL AND
<br />PERPENDICULAR TO WALLS AND ADJACENT PIPING.
<br />ARRANGE CONDUIT TO MAINTAIN HEADROOM AND TO
<br />PRESENT A NEAT APPEARANCE.
<br />9.WHENEVER A DISCREPANCY IN QUANTITY OR SIZE OF
<br />CONDUIT, WIRE, EQUIPMENT DEVICES, CIRCUIT BREAKERS,
<br />GROUND FAULT PROTECTION SYSTEMS, ETC. (ALL
<br />MATERIALS), ARISES ON THE DRAWINGS OR
<br />SPECIFICATIONS, PROVIDE AND INSTALL ALL MATERIAL
<br />AND SERVICES REQUIRED BY THE STRICTEST CONDITIONS
<br />NOTED ON THE DRAWINGS OR IN THE SPECIFICATIONS TO
<br />ENSURE COMPLETE AND OPERABLE SYSTEMS.
<br />10.ALL RECESSED LIGHTING FIXTURES, SPEAKERS,
<br />RECEPTACLES, SWITCHES, ETC., MOUNTED IN THE FIRE
<br />RATED CEILINGS OR WALLS SHALL BE ENCLOSED WITH AN
<br />APPROVED ENCLOSURE CARRYING THE SAME FIRE RATING
<br />AS THE CEILING OR WALL.
<br />2022 CALIFORNIA BUILDING CODE (CBC) PART 2,
<br />VOLUMES 1 AND 2, TITLE 24
<br />(BASED ON 2021 INTERNATIONAL BUILDING CODE)
<br />2022 CALIFORNIA ELECTRIC CODE (CEC) PART 3, TITLE 24
<br />(BASED ON 2020 NATIONAL ELECTRIC CODE)
<br />2022 CALIFORNIA MECHANICAL CODE (CMC) PART 4, TITLE 24
<br />(BASED ON 2021 UNIFORM MECHANICAL CODE)
<br />2022 CALIFORNIA PLUMBING CODE (CPC) PART 5, TITLE 24
<br />(BASED ON 2021 UNIFORM PLUMBING CODE)
<br />2022 CALIFORNIA FIRE CODE (CFC) PART 9, TITLE 24
<br />(BASED ON 2021 INTERNATIONAL FIRE CODE)
<br />2022 CALIFORNIA ENERGY CODE PART 6, TITLE 24
<br />2022 CALIFORNIA GREEN BUILDING STANDARDS (PART 11, TITLE
<br />24, CCR)
<br />2022 CALIFORNIA REFERENCED STANDARD CODE PART 12,
<br />TITLE 24
<br />TITLE 19, PUBLIC SAFETY, STATE FIRE MARSHAL REGULATIONS
<br />PARTIAL LIST OF APPLICABLE NATIONAL FIRE PROTECTION
<br />ASSOCIATION (NFPA) STANDARDS
<br />NFPA 13, 2022 EDITION - INSTALLATION OF SPRINKLER SYSTEMS
<br />(AMENDED BY CSFM)
<br />NFPA 14, 2019 EDITION - INSTALLATION OF STANDPIPE AND HOSE
<br />SYSTEMS (AMENDED BY CSFM)
<br />NFPA 17A, 2021 EDITION - WET CHEMICAL EXTINGUISHING
<br />SYSTEMS
<br />NFPA 24, 2022 EDITION - INSTALLATION OF PRIVATE FIRE SERVICE
<br />MAINS
<br />(AMENDED BY CSFM)
<br />NFPA 25, (2013 CALIFORNIA EDITION, BASED ON NFPA 25, 2011
<br />EDITION) - INSPECTION, TESTING, & MAINTENANCE OF
<br />WATER-BASED FIRE PROTECTION SYSTEMS
<br />NFPA 72, 2022 EDITION - NATIONAL FIRE ALARM AND SIGNALING
<br />CODE (AMENDED BY CSFM)
<br />NFPA 80, 2022 EDITION - FIRE DOORS AND OTHER OPENING
<br />PROTECTIVES
<br />REFER TO CBC CHAPTER 35 FOR ADDITIONAL STANDARDS NOT
<br />PROVIDED ON THIS LIST
<br />WIRING SYSTEM ABOVE FLOOR LEVEL,
<br />CONCEALED IN WALL OR ABOVE CEILING U.O.N
<br />WIRING SYSTEM IN OR UNDER FLOOR OR
<br />CONCEALED IN OR BEHIND STRUCTURE OR
<br />EQUIPMENT
<br />CONDUIT STUB ENDING WITH CAP
<br />E0.1
<br />1
<br />REMOVE/RELOCATE/DEMOLISH
<br />EQUIPMENT/DEVICE
<br />EXISTING
<br />DRAWING INDEX
<br />DUPLEX RECEPTACLE 20A, 5-20R
<br />+18" A.F.F. (U.O.N.)
<br />GROUND CONNECTION
<br />COMBINATION MOTOR
<br />STARTER/DISCONNECT SWITCH
<br />(NUMBER INDICATES STARTER SIZE)
<br />DISCONNECT SWITCH (FUSED),
<br />HORSE POWER RATED
<br />SURFACE MOUNTED PANELBOARD 277V/480V
<br />DISTRIBUTION BOARD
<br />MOTOR
<br />3/4" CONDUIT WITH 2#12 + 1#12 GRD.
<br />SURFACE MOUNTED PANELBOARD 120V/208V
<br />DISCONNECT SWITCH (NON-FUSED)
<br />S
<br />S 3
<br />PLUGMOLD STRIP
<br />DOUBLE DUPLEX (QUAD) RECEPTACLE
<br />20A, 5-20R, +18" A.F.F. (U.O.N.)
<br />LIGHTING FIXTURE IDENTIFICATION
<br />SURFACE MOUNTED METAL
<br />SINGLE/DUAL CHANNEL RACEWAY FOR
<br />RECEPTACLES AND DATA, REFER TO
<br />PLANS FOR RECEPTACLE/DATA
<br />LOCATION.
<br />W W
<br />TELECOM BACKBOARD 8'x4'x3/4", FIRE
<br />TREATED. PROVIDE 1#6 GROUND WIRE
<br />TO SYSTEM GROUND
<br />FX-1
<br />COMMUNICATION OUTLET. 4S BOX WITH 1
<br />GANG PLASTER RING. PROVIDE 1" CONDUIT
<br />STUBBED INTO ACCESSIBLE CEILING SPACE.
<br />"3" INDICATES QUANTITY OF PLENUM RATED
<br />CAT-6 CABLES. (2 DATA AND 1 VOICE)
<br />+18" A.F.F. (UNLESS NOTED OTHERWISE)
<br />208V RECEPTACLE
<br />+18" A.F.F. (U.O.N.)
<br />(NEMA CONFIGURATION AS NOTED ON PLANS)
<br />MANUAL MOTOR STARTER SWITCH
<br />WITH THERMAL OVERLOADS
<br />RATED AT 250V-30A-2P
<br />JUNCTION BOX WITH COVER
<br />(MINIMUM 4" SQUARE OR AS REQUIRED)
<br />120/277V. 20A LIGHT SWITCH
<br />(+42" A.F.F.)
<br />DENOTES 3-WAY SWITCH (+42" A.F.F.)
<br />LOW VOLTAGE ON/OFF DIMMER SWITCH
<br />(+42" A.F.F.)
<br />LOW VOLTAGE CEILING MOUNTED
<br />OCCUPANCY SENSOR
<br />LOW VOLTAGE LIGHTING CONTROLS
<br />POWER/RELAY PACK,
<br />'EM' INDICATES EMERGENCY CIRCUIT
<br />R EM
<br />LOW VOLTAGE ON/OFF MANUAL SWITCH
<br />WITH OCCUPANCY SENSOR (+42" A.F.F.)
<br />CARD READER (+42" A.F.F.)
<br />2-POLE TOGGLE SWITCH FOR
<br />MECHANICAL UNIT
<br />J
<br />ELECTRICAL
<br />SYMBOL
<br />DESCRIPTION ELECTRICAL
<br />SYMBOL
<br />DESCRIPTION
<br />GFCI DUPLEX RECEPTACLE
<br />20A, 5-20R, +42" A.F.F. (U.O.N.)
<br />CR
<br />DM
<br />OS
<br />F
<br />1
<br />SHEET WHERE DETAIL IS DRAWN
<br />OCCURRENCE
<br />DETAIL IDENTIFICATION
<br />(TYP.)
<br />DETAIL
<br />GFCI DUPLEX RECEPTACLE 20A, 5-20R
<br />+18" A.F.F. (U.O.N.)
<br />3
<br />CS
<br />1
<br />INSTALLATION KEY NOTE
<br />DEMOLITION KEY NOTE
<br />REVISION
<br />REVISED AREA
<br />REVISION TAG
<br />A AMPERE
<br />AC ALTERNATING CURRENT
<br />AF AMPERE FUSE
<br />AS AMPERE SWITCH
<br />AFC ABOVE FINISHED CEILING
<br />AFF ABOVE FINISHED FLOOR
<br />AFG ABOVE FINISHED GRADE
<br />AIC AMPERE INTERRUPTING CAPACITY
<br />ANN ANNUNCIATOR
<br />AT AMPERE TRIP
<br />ATS AUTOMATIC TRANSFER SWITCH
<br />AV AUDIO-VISUAL
<br />AWG AMERICAN WIRE GAUGE
<br />BKR BREAKER
<br />BLDG BUILDING
<br />C CONDUIT
<br />CB CIRCUIT BREAKER
<br />CATV CABLE TELEVISION
<br />CEC CALIFORNIA ELECTRICAL CODE
<br />CKT CIRCUIT
<br />CLG CEILING
<br />CO CONDUIT ONLY
<br />COMM COMMUNICATIONS
<br />COMP COMPUTER
<br />DB DISTRIBUTION BOARD
<br />DISC DISCONNECT
<br />DIST DISTRIBUTION
<br />DL DOUBLE LUG
<br />DP DISTRIBUTION PANEL
<br />DWG DRAWING
<br />E EXISTING TO REMAIN
<br />EG EQUIPMENT GROUND
<br />ELEC ELECTRICAL
<br />EM EMERGENCY
<br />EMT ELECTRICAL METALLIC TUBING
<br />EQUIP EQUIPMENT
<br />F FUSE, FUSED
<br />FA FIRE ALARM
<br />FACP FIRE ALARM CONTROL PANEL
<br />FLA FULL LOAD AMPERES
<br />GD GARBAGE DISPOSER
<br />GRD GROUND
<br />GALV GALVANIZE, GALVANIZED
<br />GEN GENERATOR
<br />GFCI GROUND FAULT CIRCUIT INTERRUPTER
<br />HP HORSEPOWER
<br />IHW INSTA-HOT WATER HEATER
<br />JB JUNCTION BOX
<br />KA THOUSAND AMPERES
<br />KCMIL THOUSAND CIRCULAR MILS
<br />KVA KILOVOLT-AMPERE
<br />KW KILOWATT
<br />LTG LIGHTING
<br />MC METAL CLAD CABLE
<br />MCB MAIN CIRCUIT BREAKER
<br />MCM THOUSAND CIRCULAR MILS
<br />MDP MAIN DISTRIBUTION PANEL
<br />MFR MANUFACTURER
<br />MIN MINIMUM
<br />MLO MAIN LUGS ONLY
<br />MTD MOUNTED
<br />MTR MOTOR
<br />NEC NATIONAL ELECTRIC CODE
<br />NF NON-FUSED
<br />NIC NOT IN CONTRACT
<br />P POLE, POLES
<br />PF POWER FACTOR
<br />PNL PANEL
<br />PRI PRIMARY
<br />PWR POWER
<br />PH PHASE
<br />Ø PHASE
<br />R REMOVE
<br />RR REMOVE AND RELOCATE
<br />RL RELOCATED
<br />RECEPT RECEPTACLE
<br />RGS RIGID GALVANIZED STEEL CONDUIT
<br />SEC SECONDARY
<br />SUSP SUSPEND, SUSPENDED
<br />SW SWITCH
<br />SWBD SWITCHBOARD
<br />SWGR SWITCHGEAR
<br />TBB TELECOMMUNICATIONS BACKBOARD
<br />TMH TELECOMMUNICATIONS MAN HOLE
<br />THH TELECOMMUNICATIONS HAND HOLE
<br />TR TAMPER RESISTANT
<br />TYP.TYPICAL
<br />TVSS TRANSIENT VOLTAGE SURGE SUPPRESSION
<br />UON UNLESS OTHERWISE NOTED
<br />V VOLT, VOLTS
<br />VA VOLT-AMPERES
<br />VAV VARIABLE AIR VOLUME
<br />WT WATERTIGHT
<br />W WATT OR WIRE
<br />WP WEATHER PROOF
<br />X'FMR TRANSFORMER
<br />Y WYE CONNECTION
<br />S M
<br />S 2
<br />MISCELLANEOUS
<br />LINE TYPESGROUND BUS BAR
<br />1
<br />1
<br />CAMERA
<br />METERM
<br />CIRCUIT BREAKER
<br />LV TRANSFORMER
<br />T TRANSFORMER
<br />Sheet No.
<br />Project
<br />Agency Plan Check / Permit No.
<br />Petersen Design Project No.
<br />Consultant
<br />5082.1
<br />652 East Dyer Drive
<br />Santa Ana, CA 92705
<br />DYER WAREHOUSE
<br />Staging & Set-Up Space
<br />Tenant Improvements
<br />Sheet Title
<br />Revision / Submittal History
<br />Scale
<br />Status
<br />.
<br />architecture + planning
<br />Agency Approval
<br />Petersen Design Architects, Inc.
<br />17582 Fiesta Way, Tustin, CA 92780
<br />M: 714.904.6720 E: mike@mpdarch.com
<br />www.mpdarch.com
<br />Architect's Stamp
<br />.
<br />255 E. Rincon St., Suite 301
<br />Corona, CA 92879
<br />P 951.340.1977 | F 951.340.1090
<br />www.gossengineering.com
<br />CALOFI
<br />GI
<br />RE
<br />NG
<br />A
<br />E
<br />S
<br />No. E17083
<br />T
<br />E
<br />ET
<br />SAT L CE A
<br />F
<br />RICL
<br />ORNI
<br />EPR
<br />RAET
<br />RED D.D
<br />OF ONABR
<br />L
<br />SSI
<br />NE
<br />RE
<br />IWD
<br />UT
<br />HCE
<br />Project Number: 125-09-07
<br />Date Signed 01-09-2026
<br />1 01/09/2026 PLAN CHECK RESUBMITTAL
<br />SYMBOLS,
<br />DESIGNATION AND
<br />ABBREVIATIONS
<br />E0.1
|