Laserfiche WebLink
STRUCT. CONC. DECK <br />STRUCT. STL. MEMBER <br />CLG. CLIP <br />12ga. X 3/4" WIDE <br />(MIN.) W/ 0.145" DIA. <br />SHOT-IN ANC. <br />(3) TIGHT TURNS IN 1 1/2" <br />VERT. HANGER WIRE (TEST <br />FOR 200 LBS) <br />SPLAYED BRACING <br />WIRE W/ #10 SMS <br />(TEST FOR 440 LBS) <br />(4) TIGHT TURNS <br />IN 1 1/2" <br />STL. STRAP <br />1" W X 12 ga. (MIN.) <br />HILTI X-CW U27 W/ 2" <br />EMBED - ICC#ESR-2184 <br />(TEST TO 440 LBS)161/256" MAX. 5/8" MAX. <br />45° <br /> <br />M <br />A <br />X <br />. <br />FROM FLUTE EDGE <br />1 1/8" MIN. <br />45° <br /> <br />M <br />A <br />X <br />. <br />CLG. CLIP <br />12 ga. X 3/4" WIDE <br />(MIN.) W/ 0.145" DIA. <br />SHOT IN ANC. <br />(3) TIGHT TURNS IN <br />1 1/2" <br />(4) TIGHT TURNS IN 1 <br />1/2" <br />SPLAYED BRACING WIRE <br />VERT. HANGING WIRE <br />(TEST FOR 200 LBS) <br />STL. STRAP <br />1" W X 12ga. (MIN.) <br />0.15" DIA. SHOT-IN <br />ANC. W/ 1 1/2" EMBED. <br />ICC#ER-1663 TEST TO <br />200 LBS <br />FROM FLUTE EDGE <br />1 1/8" MIN. <br />FROM FLUTE CL <br />1" MAX. <br />5/8" MAX. <br />5/8" MAX. <br />2" MAX.2" MAX. <br />8" MAX.8" MAX. <br />2" MAX <br />. <br />2" MA <br />X <br />. <br />45° MAX. TYP. <br />2" <br />MIN. <br />2" <br />MIN. <br />1 <br />6 <br />SEISMIC COMPRESSION <br />STRUT, SEE NOTE D. <br />12 GA. VERT. HANGER WIRE <br />@ 48" O.C. ALONG MAIN <br />RUNNERS, SEE NOTE E. MIN. <br />(3) TIGHT TURNS IN 1 1/2" <br />BOTH ENDS <br />(4) 12 GA. BRACING WIRES <br />W/ MIN. 4 TIGHT TURNS IN 1 <br />1/2" BOTH ENDS OF WIRE - <br />CONNECT TO MAIN RUNNERS, <br />SEE NOTE B. <br />MAIN RUNNER, SEE NOTE G <br />CROSS RUNNER, SEE NOTE G <br />SEISMIC CLIP AT MAIN <br />RUNNERS AS REQUIRED, SEE <br />NOTE C <br />12 GA. PERM. HANGER WIRE <br />AT ALL RUNNERS ADJACENT <br />TO WALLS ANCHORED TO <br />STRUCTURE ABOVE, SEE <br />NOTE H <br />3/4" MIN. @ (2) ADJACENT <br />UNATTACHED WALLS <br />ARMSTRONG BERC 2 <br />ARMSTRONG SHADOW <br />MOLDING 78723 - TYP. <br />WALL ANGLE <br />PERIMETER STABILIZER BAR OR <br />CLIP AS REQUIRED TO KEEP <br />PERIMETER COMPONENTS <br />FROM SPREADING APART <br />s u s p e n s i o n g r i d a x o n @ l a t e r a l b r a c i n g i n t e r s e c t i <br />o n <br />s u s p e n s i o n g r i d @ w a l l <br />s u s p e n s i o n g r i d a x o n <br />l a y - i n c e i l i n g t i l e c o n c e a l e d s e i s m i c c l i p a x o n <br />ATTACHED ATTACHED UNATTACHED UNATTACHED <br />SEISMIC COMPRESSION <br />STRUT, SEE NOTE D <br />LIGHT OR MECHANICAL <br />FIXTURE, SEE NOTE F <br />SUSPENSION GRID PER RCP <br />12 GA. HANGER WIRE @ 48" <br />O.C. ALONG MAIN RUNNERS, <br />SEE NOTE E <br />MAIN RUNNER, SEE NOTE E <br />CROSS RUNNER, SEE NOTE G <br />MAIN RUNNER <br />SEISMIC CLIP - LOCATED <br />ALONG SEISMIC CONTROL <br />JOINT. SEE CEILING NOTE K <br />CROSS RUNNER <br />LAY-IN TILE SHOWN <br />HIDDEN FOR CLARITY <br />c e i l i n g n o t e s <br />AA <br />1. <br />B.B. <br />1. <br />2. <br />3. <br />4. <br />5. <br />C. C. <br />1. <br />D. <br />1. <br />2. <br />E. E. <br />1. <br />2. <br />F.F. <br />1. <br />2. <br />3. <br />4. <br />5. <br />6. <br />7. <br />8. <br />G.G. <br />1. <br />2. <br />3. <br />H.H. <br />1. <br />I.I. <br />1. <br />J.J. <br />1. <br />K. K. <br />1. <br />PATTERNPATTERN <br />ACOUSTICAL TILE - UNLESS OTHERWISE INDICATED OR SPECIFIED, INSTALL CEILINGS IN A REGULAR PATTERN <br />WITHOUT BORDER AND JOINT LINES PARALLEL TO WALLS. INSTALL ACOUSTICAL UNITS SYMMETRICALLY ABOUT <br />CENTERLINES OF EACH ROOM OR SPACE, AVOIDING NARROW UNITS AT WALL. <br />LATERAL BRACINGLATERAL BRACING <br />LATERAL BRACING FOR SUSPENDED CEILINGS MUST BE PROVIDED (CBC 2501A.5 AND ASCE 7). WHERE CEILING <br />LOADS ARE LESS THAN 5 PSF AND NOT SUPPORTING INTERIOR PARTITIONS, CEILING BRACING SHALL BE PROVIDED BY <br />(4) NO. 12 GAUGE WIRES SECURED TO THE MAIN RUNNER WITHIN 2 INCHES FROM THE CROSS RUNNER INTERSECTION <br />AND SPLAYED 90-DEGREES FROM EACH OTHER AT AN ANGLE NOT EXCEEDING 45-DEGREES FROM THE PLANE OF THE <br />CEILING. THESE HORIZONTAL RESTRAINT POINTS SHALL BE PLACED 4'-0" FEET O.C. IN BOTH DIRECTIONS WITH THE <br />FIRST POINT WITHIN 4'-0" FEET FROM EACH WALL. <br />FASTEN BRACING WIRES WITH FOUR (4) TIGHT TURNS. MAKE ALL TIGHT TURNS WITHIN A DISTANCE OF 11/2". <br />BRACING WIRE ANCHORS TO THE STRUCTURE SHOULD BE INSTALLED IN SUCH A MANNER THAT THE DIRECTION OF <br />THE ANCHOR ALIGNS AS CLOSELY AS POSSIBLE WITH THE DIRECTION OF THE WIRE. ATTACHMENT OF THE RESTRAINT <br />WIRES TO THE STRUCTURE ABOVE SHALL HAVE A MINIMUM CONNECTION STRENGTH OF 200 POUNDS OR BE <br />ADEQUATE FOR THE LOAD IMPOSED. REFER TO DETAIL 5/- FOR ATTACHMENT REQUIREMENTS TO CONCRETE DECK. <br />ALLOWABLE LOAD FOR #10 WIRE IS 343 LBS AND #12 WIRE IS 209 LBS. <br />SUSPENDED ACOUSTICAL CEILING SYSTEMS WITH A CEILING AREA OF 144 SQUARE FEET OR LESS, AND FIRE RATED <br />SUSPENDED ACOUSTICAL CEILING SYSTEMS WITH A CEILING AREA OF 96 SQUARE FEET OR LESS, SURROUNDED BY <br />WALLS WHICH CONNECT DIRECTLY TO THE STRUCTURE ABOVE, DO NOT REQUIRE BRACING ASSEMBLIES WHEN <br />ATTACHED TO TWO ADJACENT WALLS. <br />THE SUSPENDED CEILING LATERAL FORCE-BRACING MEMBERS SHALL BE LOCATED A MINIMUM OF 6 INCHES FROM <br />ALL HORIZONTAL PIPING OR DUCT WORK THAT ARE NOT PROVIDED WITH BRACING RESTRAINTS FOR HORIZONTAL <br />FORCES. CABLE TRAYS AND ELECTRICAL CONDUITS SHALL BE SUPPORTED INDEPENDENTLY OF THE CEILING. <br />LATERAL SUPPORTLATERAL SUPPORT <br />PROVIDE SEISMIC CLIP PER ESR-1308 AT MAIN RUNNERS ON A MINIMUM OF 2-ADJACENT SIDES AND HOLD A <br />MINIMUM OF 3/4" CLEARANCE AT UNATTACHED WALLS. <br />SEISMIC BRACINGSEISMIC BRACING (REQUIRED ONLY FOR CEILING AREAS GREATER THAN 1,000 SF) <br />VERTICAL COMPRESSION STRUTS SHALL BE INSTALLED AT EACH CROSS RUNNER INTERSECTION WHERE LATERAL <br />SUPPORT WIRES ARE INSTALLED (12'-0" FEET O.C. IN BOTH DIRECTIONS, STARTING 6'-0" FEET FROM WALLS). <br />WHERE THE DISTANCE BETWEEN THE CEILING GRID AND THE STRUCTURE ABOVE IS LESS THAN 8'-0" FEET, PROVIDE <br />ONE 3-5/8" (25 GA.) METAL STUD, 8'-10' TWO 1 5/8" 25 GA METAL STUDS ORIENTED PERPENDICULAR (FLANGE OF ONE <br />STUD CONNECTED TO THE WEB OF THE OTHER STUD) AND CONNECTED EVERY 12" ALONG THEIR PATHS. 10'-15', TWO <br />2-1/2" 25GA METAL STUDS, ORIENTED AND CONNECT SIMILAR TO 8'-10". SECURE TO STRUCTURE ABOVE. SCREW WITH <br />#6 DRYWALL SCREW TO CEILING MAIN RUNNER AT SPLAYED CORNERS. <br />HANGER WIRESHANGER WIRES <br />SPACE WIRES AT MAXIMUM 48" CENTERS ALONG MAIN RUNNERS AND CONNECT TO STRUCTURE ABOVE. MINIMUM <br />12-GAUGE GALVANIZED STEEL WIRE TO BE UTILIZED, UNLESS HEAVIER GAUGE REQUIRED BY CODE. FASTEN HANGER <br />WIRES WITH NOT LESS THAN THREE (3) TIGHT TURNS. MAKE ALL TIGHT TURNS WITHIN A DISTANCE OF 11/2". <br />HANGER WIRE ANCHORS TO THE STRUCTURE SHOULD BE INSTALLED IN SUCH A MANNER THAT THE DIRECTION OF THE <br />ANCHOR ALIGNS AS CLOSELY AS POSSIBLE WITH THE DIRECTION OF THE WIRE. REFER TO DETAIL 5/- FOR <br />ATTACHMENT REQUIREMENTS TO CONCRETE DECK. <br />ALLOWABLE LOAD FOR #10 WIRE IS 343 LBS AND #12 WIRE IS 209 LBS. <br />FRAMING FOR LIGHTING & MECHANICAL FIXTURES FRAMING FOR LIGHTING & MECHANICAL FIXTURES <br />OBTAIN NECESSARY DATA FROM OTHER TRADES AND PROVIDE ADDITIONAL HANGERWIRE AND/OR FRAMING IN <br />SUSPENDED GRIDS AS REQUIRED TO SUPPORT LIGHTING AND MECHANICAL FIXTURES. WHERE FIRE RATING IS <br />REQUIRED; PROVIDE FIRE DAMPERS. <br />SEPARATE ALL CEILING HANGER AND BRACING WIRES AT LEAST 6" FROM ALL UNBRACED DUCTS, PIPES, CONDUIT, <br />ETC. <br />LIGHTING FIXTURES AND MECHANICAL DIFFUSERS WEIGHING LESS THAN 56 POUNDS SHALL BE SUPPORTED DIRECTLY <br />BY A MIN. OF 2-12 GA. HANGERWIRES (MAY BE SLACK) LOCATED AT OPPOSITE CORNERS OF THE FIXTURE AND <br />ATTACHED TO THE STRUCTURE ABOVE. ALL LIGHT FIXTURES MUST BE MECHANICALLY ATTACHED TO THE GRID PER <br />NEC 410-16 AT TWO LOCATIONS UNLESS INDEPENDENTLY SUPPORTED. <br />ALL FLUSH OR RECESSED LIGHT FIXTURES AND AIR TERMINALS WEIGHING 56 LBS OR MORE MUST BE INDEPENDENTLY <br />SUPPORTED BY NOT LESS THAN FOUR (4) TAUT #12 GAGE WIRES, EACH ATTACHED TO THE FIXTURE AND TO THE <br />STRUCTURE ABOVE REGARDLESS OF THE TYPE OF CEILING GRID SYSTEM USED. THE FOUR (4) TAUT #12 GAGE <br />WIRES, INCLUDING THEIR ATTACHMENT TO THE STRUCTURE ABOVE, MUST BE CAPABLE OF SUPPORTING FOUR (4) <br />TIMES THE WEIGHT OF THE UNIT. <br />ALL FIXTURES AND AIR TERMINALS SUPPORTED ON INTERMEDIATE DUTY GRID SYSTEMS MUST BE INDEPENDENTLY <br />SUPPORTED BY NOT LESS THAN FOUR (4) TAUT #12 GAGE WIRES EACH ATTACHED TO THE FUXTURE OR TERMINAL, <br />AND TO THE STRUCTURE ABOVE. <br />SUPPORT SURFACE MOUNTED LIGHT FIXTURES BY AT LEAST TWO POSITIVE DEVICES WHICH SURROUND THE CEILING <br />RUNNER AND WHICH ARE EACH SUPPORTED FROM THE STRUCTURE ABOVE BY A #12 GAGE WIRE. SPRING CLIPS OR <br />CLAMPS THAT CONNECT ONLY TO THE RUNNER ARE NOT ACCEPTABLE. PROVIDE ADDITIONAL SUPPORTS WHEN LIGHT <br />FIXTURES ARE 8 FT. OR LONGER. <br />SUPPORT PENDANT MOUNTED LIGHT FIXTURES DIRECTLY FROM THE STRUCTURE ABOVE WITH HANGER WIRES OR <br />CABLES PASSING THROUGH EACH PENDANT HANGER AND CAPABLE OF SUPPORTING FOUR (4) TIMES THE WEIGHT OF <br />THE FIXTURE. A BRACING ASSEMBLY IS REQUIRED WHERE THE PENDANT HANGER PENETRATES THE CEILING. SPECIAL <br />DETAILS ARE REQUIRED TO ATTACH THE PENDANT HANGER TO THE BRACING ASSEMBLY TO TRANSMIT HORIZONTAL <br />FORCES. <br />EXCEPT WHERE RIGID BRACES ARE USED TO LIMIT LATERAL DEFLECTION, SPRINKLER HEADS AND OTHER <br />PENETRATIONS THROUGH THE CEILING TILE REQUIRE MINIMUM 2-INCH RINGS, SLEEVES OR ADAPTERS THAT WILL <br />ALLOW A MINIMUM 1-INCH CEILING MOVEMENT IN ALL HORIZONTAL DIRECTIONS. ALTERNATIVELY, A SWING JOINT <br />CAN BE PROVIDED AT THE TOP OF THE SPRINKLER HEAD EXTENSION TO ACCOMMODATE THE 1-INCH MOVEMENT. <br />SUSPENSION GRIDSUSPENSION GRID <br />SPACE HEAVY DUTY MAIN RUNNERS AT MAXIMUM 48" CENTERS AND INSTALL CROSS RUNNERS TO COMPLETE THE <br />GRID. INSTALL MAIN RUNNERS ALONG EDGES OF MECHANICAL AND LIGHTING FIXTURES. LOCK SUSPENSION PARTS <br />INTO PLACE TO FORM A GRID CAPABLE OF RESISTING A LATERAL FORCE OF 180 POUNDS MINIMUM IN BOTH TENSION <br />AND COMPRESSION. INSTALL ACOUSTICAL UNITS WITH TIGHT FLUSH JOINTS, ALL JOINT LINES STRAIGHT AND <br />ALIGNED. CUT UNITS TO FIT TIGHTLY AROUND CEILING PENETRATIONS, AND EDGES BEARING ON RUNNERS, ALL <br />EDGES SECURED WITH HOLD-DOWN CLIPS. PROVIDE MOLDING AT VERTICAL SURFACES AND AT ALL PENETRATIONS, <br />JOINTS TIGHTLY BUTTED AND MITER CUT AT ANGLES OR CHANNELS. <br />AT THE PERIMETER OF THE CEILING AREA WHERE MAIN OR CROSS RUNNERS ARE NOT CONNECTED TO THE ADJACENT <br />WALL, PROVIDE INTERCONNECTION BETWEEN THE RUNNERS AT THE FREE END TO PREVENT LATERAL SPREADING. A <br />METAL STRUCT OR A #16 GAGE WIRE WITH A POSITIVE MECHANICAL CONNECTION TO THE RUNNER MAY BE USED. <br />WHERE THE PERPENDICULAR DISTANCE FROM THE WALL TO THE FIRST PARALLEL RUNNER IS 12 INCHES OR LESS, <br />THIS INTERLOCK IS NOT REQUIRED. <br />SUSPENDED ACOUSTICAL CEILINGS SHALL CONFORM TO ASTM C 635, ASTM C 636, AND CBC 803.9. <br />DISCONTINUOUS ENDSDISCONTINUOUS ENDS <br />DISCONTINUOUS ENDS OF CROSS RUNNERS AND MAIN RUNNERS SHALL BE VERTICALLY SUPPORTED WITHIN 8" OF <br />SUCH ENDS. HANGER WIRE SLOPE MAXIMUM OF 1:6 OUT OF PLUMB. <br />CEILING PLANE ELEVATION CHANGES CEILING PLANE ELEVATION CHANGES <br />PROVIDE TRIMS AND RIGID SUPPORT WHERE SHOWN OR NECESSARY TO PROPERLY FINISH AT OFFSET OR CEILING <br />BREAKS, TYPES AS INDICATED, DIRECTED AND APPROVED. <br />REPAIR, CLEANING, & COMPLETION REPAIR, CLEANING, & COMPLETION <br />REMOVE AND REPLACE ALL DISCOLORED, BROKEN, OR DAMAGED MATERIALS. COMPLETED CEILINGS SHALL PRESENT <br />A SMOOTH LEVEL SURFACE FREE OF EDGE OR CORNER OFFSETS, CUPPING, SCRATCHES, GOUGES, OR OTHER <br />DEFECTS. CLEAN EXPOSED SURFACES AND REMOVE FOREIGN MATTER. <br />CONTROL JOINTSCONTROL JOINTS <br />PROVIDE A CONTROL JOINT FOR EVERY 2500 SQUARE FEET OF CEILING AREA. WHEN CEILING AREA EXCEEDS 2500 <br />SQUARE FEET LOCATE CONTROL JOINTS THAT DIVIDE CEILING AREA INTO EQUAL/BALANCES AREAS UNLESS <br />OTHERWISE INDICATED ON THE PLANS. <br />CEILING JOIST <br />PER SCHEDULE <br />STUDS <br />CEILING JOIST <br />PER SCHEDULE <br />STUDS <br />3-#8 SMS <br />EA STUD <br />1-LAYER CYP <br />BOARD <br />(5/8" MAX) <br />#8 SMS <br />AT EA STUD <br />(2-TOTAL) <br />CEILING JOIST <br />PER SCHEDULE <br />STUDS <br />3-#8 SMS <br />TYP <br />L1 1/2"X 1 1/2"X 33 <br />MIL CONT W/1-#8 <br />SMS EA LEG, EA <br />STUD AND JOIST <br />c e i l i n g j o i s t c o n n t o e x t e r i o <br />r w a l l <br />c e i l i n g j o i s t c o n n t o w a l l t h r u <br />1 - l a y e r o f g y p <br />STUDS <br />JOIST SIZE & SPACING <br />PER SCHEDULE <br />1" FLANGE CONT <br />TRACK GAUGE PER <br />SCHEDULE W/ #8 <br />SMS EA FLANGE, EA <br />STUD. SEE DETAILS <br />'B' THRU 'E' FOR <br />CONNECTION TO <br />STUD, TYP <br />STUDS <br />c e i l i n g j o i s t <br />NOTES: <br />1. CEILING WHERE JOISTS SHALL SUPPORT NO MORE THAN TWO <br />LAYERS OF 5/8" GYP BOARD. <br />2. WHERE CEILING JOISTS SPANS EXCEED TABULATED VALUES, <br />PROVIDE MID-SPAN SUPPORTS PER 2/- OR 5/- TO CUT TOTAL SPANS <br />i n t e r i o r c e i l i n g j o i s t m a x s p a n s c h e d u l e <br />STUD JOIST SIZE & <br />SPACING <br />UNBRACED JOIST BRACED JOIST <br />16" OC 16" OC <br />9'-5"13'-2" <br />10'-5"14'-4" <br />10'-8"15'-0" <br />12'-0"16'-2" <br />13'-8"16'-11" <br />362S125-33 <br />362S125-43 <br />400S125-43 <br />400S137-43 <br />400S162-43 <br />c e i l i n g j o i s t l a p c o n n <br />A <br />B C D <br />EQ ± 6 EQ ± 6 <br />54 MIL x 1 1/2" CRC <br />W/2-#8 SMS @ EA <br />STUD AT BRACED JOIST <br />(N) METAL DROP CEILING <br />FRAMING <br />CEILING JOIST PER <br />'HARD LID CEILING' <br />SCHEDULE <br />SOFFIT WIDTH PER. PLAN <br />(N) STUD SPACING TO <br />MATCH (E) CEILING <br />JOIST SPACING <br />(N) METAL SOFFIT BRACING <br />FOR FRAME <br />V.I.F. <br />(N)SOFFIT LEVEL WITH (E) SOFFIT <br />(N) GYP. BD. FINISH - PAINT <br />WHERE VISIBLE <br />(E) STRUCTURE <br />(E) CEILING GRID PER RCP 02/A162 <br />d r o p c e i l i n g b e t w e e n t w o e x i s t i n g c e i l i n g s <br />(N) CASING BEAD <br />s o f f i t b e t w e e n t w o e x i <br />s t i n g c e i l i n g s <br />(N) METAL SOFFIT FRAMING <br />(N) STUD SPACING TO <br />MATCH CEILING (E) <br />JOIST SPACING <br />(N) METAL SOFFIT BRACING <br />FOR FRAME <br />V.I.F. <br />(N)SOFFIT LEVEL WITH (E) SOFFIT <br />NEW GYP. BD. FINISH - PAINT <br />WHERE VISIBLE <br />(E)STRUCTURE <br />(E) CEILING GRID PER RCP 02/A162 <br />(N) STUD SPACING TO <br />MATCH CEILING (E) <br />JOIST SPACING <br />(N) CASING BEAD <br />(N) METAL DROP CEILING <br />FRAMING <br />SOFFIT WIDTH PER. PLAN <br />(N) STUD SPACING TO <br />MATCH (E) CEILING <br />JOIST SPACING <br />(N) METAL SOFFIT BRACING <br />FOR FRAME <br />V.I.F. <br />(N)SOFFIT LEVEL WITH (E) SOFFIT <br />(N) GYP. BD. FINISH - PAINT <br />WHERE VISIBLE <br />(E) STRUCTURE <br />(E) CEILING GRID PER RCP 02/A162 <br />a l c o v e c e i l i n g b e t w e e n t w o e x i s t i n g c e i l i n g s <br />(N) CASING BEAD <br />(E) METAL CEILING PER RCP 02/A162 <br />0 5' <br />GRAPHIC SCALES: <br />Issue Date <br />1/16" = 1'-0" <br />50' <br />1/8" = 1'-0"1/4" = 1'-0"1/2" = 1'-0"3/4" = 1'-0"1" = 1'-0"1-1/2" = 1'-0"3" = 1'-0" <br />0 5'25'0 1'12'0 1'6'0 4'0 3'1'0 2'0 1' <br />Chckd By <br />Drwn By <br />Scale <br />Building ID: <br />KP Proj. No. <br />Permit No. <br />Sheet <br />SheetsOf <br />Sheet Title <br />Project <br />Facility <br />This document is the property of the Owner and is <br />Project Architect Approval: <br />Architect/Engineer Of Record: <br />IF THIS SHEET IS NOT 30"x42" , IT IS <br />A REDUCED PRINT - SCALE ACCORDINGLY <br />National Facilities Services <br />Post Office Box 12916 <br />Oakland California 94604 <br />not to be used without owner's written permission. <br />Floor Lev:Section: <br />Revisions <br />By Appr. <br />HGW Proj. No. <br />© <br />A <br />R <br />C <br />H <br />I <br />T <br />E <br />C <br />T <br />S <br /> <br />h <br />a <br />n <br />n <br />a <br /> <br />g <br />a <br />b <br />r <br />i <br />e <br />l <br /> <br />w <br />e <br />l <br />l <br />s <br />, <br /> <br />a <br />l <br />l <br /> <br />r <br />i <br />g <br />h <br />t <br />s <br /> <br />r <br />e <br />s <br />e <br />r <br />v <br />e <br />d <br />. <br /> <br /> <br />A <br />n <br />y <br /> <br />u <br />s <br />e <br /> w <br />i <br />t <br />h <br />o <br />u <br />t <br /> <br />p <br />e <br />r <br />m <br />i <br />s <br />s <br />i <br />o <br />n <br /> <br />i <br />s <br /> <br />e <br />x <br />p <br />r <br />e <br />s <br />s <br />l <br />y <br /> <br />p <br />r <br />o <br />h <br />i <br />b <br />i <br />t <br />e <br />d <br />. <br /> <br /> <br />P <br />l <br />o <br />t <br />t <br />e <br />d <br />1955 Bacon Street. San Diego, CA 92107 <br />Office 619 523 8487 <br />www.hgwarchitecture.com <br />KAISER PERMANENTE <br />BUILDINGS ON BRAND <br />As indicated <br />1/ <br />2 <br />1 <br />/ <br />2 <br />0 <br />2 <br />6 <br /> <br />5 <br />: <br />2 <br />5 <br />: <br />4 <br />7 <br /> <br />P <br />M <br />01/23/2026 <br />Checker <br />Author <br />CAP030945 <br />A820 <br />TYPICAL CEILING DETAILS <br />Santa Ana Medical Offices <br />1900 E. 4th Street <br />Santa Ana, CA, 92701 <br />PL <br />A <br />N <br /> <br />C <br />H <br />E <br />C <br />K <br /> <br />R <br />E <br />S <br />U <br />B <br />M <br />I <br />T <br />T <br />A <br />L <br />2505 <br />SANTA ANA <br /> 3" = 1'-0"10 hanger wire attachment @ ceiling <br /> 3" = 1'-0"18 typical suspended acoustical ceiling details <br /> 3/4" = 1'-0"20 interior hard lid ceiling <br /> 3/4" = 1'-0"05 new drop ceiling between existing ceilings <br /> 3/4" = 1'-0"03 new soffit between existing ceilings <br /> 3/4" = 1'-0"04 new alcove ceiling <br />No.Revisions Date <br />1 SD Set 06/05/2025 <br />2 DD Set 07/03/2025 <br />3 90% CD Set 08/14/2025 <br />4 Plan Check Submittal 09/19/2025 <br />09-2027