Laserfiche WebLink
CONDUIT SCHEDULE <br />TAG CIRCUIT DESCRIPTION CONDUCTOR NEUTRAL GROUND CONDUIT <br />1 Inverter Input (2) 10 AWG (PV WIRE)N/A 6 AWG (BARE)Open Air <br />2 Inverter Input (8) 10 AWG <br />THHN/THWN-2 N/A 8 AWG THHN/THWN-2 3/4 EMT <br />3 Inverter Output (2) 6 AWG <br />THHN/THWN-2 <br />(1) 6 AWG <br />THHN/THWN-2 8 AWG THHN/THWN-2 3/4 EMT <br />4 Load Center Output (2) 1 AWG <br />THHN/THWN-2 <br />(1) 1 AWG <br />THHN/THWN-2 6 AWG THHN/THWN-2 1-1/4 EMT <br />PAGE <br />REV: C1 2/3/2026 <br />OSCAR GONZALEZ <br />2007 N WESTWOOD AVE, <br />SANTA ANA, CA, 92706 <br />2007 1/2 N WESTWOOD AVE. <br />PROJECT NUMBER: <br /> 109R-007GONZ PR-3004301289 <br />SHEET <br />DESIGNER: <br />HIMANSHU VASHIST <br />CUSTOMER RESIDENCE: <br />ADU ADRESS <br />TEL. (714) 222-8870APN: 399-071-01 <br />(415) 580-6920 ex3 <br />PV-4.1 <br />#ESTAMP#SSTAMP <br />2500 WHITE RD. SUITE A, IRVINE CA 92614 <br />PHONE 805.540.7603 <br />FAX 949.215.7778 <br />CA CL #750184 <br />GILBERT CORREIA, C10, C46 <br />ELECTRICAL CONT. <br />MODULE CHARACTERISTICS <br />SILFAB: SIL-440QD-DCA 440 W <br />OPEN CIRCUIT VOLTAGE 38.97 V <br />MAX POWER VOLTAGE 33.41 V <br />SHORT CIRCUIT CURRENT 14.29 A <br />General Notes: <br />• CITY REQUIRES TWO SOURCES OF GROUND - UFER, TWO GROUNDS RODS OR <br />COLD WATER GAS BOND <br />POWER CONTROL SYSTEM (PCS): <br /> • A PCS IS INSTALLED IN ACCORDANCE WITH CEC 2022 705.13 <br /> • THE PCS SHALL LIMIT GENERATION SOURCE OUTPUT SUCH THAT CURRENT FROM ALL SOURCES OF SUPPLY DOES NOT <br />EXCEED THE RATING OF ANY BUSBAR OR CONDUCTOR SUPPLIED BY THE POWER PRODUCTION SOURCES <br /> • ANY BUSBAR OR CONDUCTOR ON THE LOAD SIDE OF THE SERVICE DISCONNECT NOT MONITORED BY THE PCS SHALL <br />COMPLY WITH ARTICLE 705.12. <br /> • ACCESS TO PCS CONTROLS IS RESTRICTED TO QUALIFIED PERSONS IN ACCORDANCE WITH 240.6(C). <br /> • ENERGY STORAGE SYSTEM: (2) TESLA: POWERWALL 3 1707000-XX-Y <br /> • ENABLE PCS <br /> SETPOINTS: <br /> - 180A - MAXIMUM TOTAL CURRENT ON THE CONTROLLED PANEL <br /> - 0A - FAIL SAFE GENERATION BACKFEED CURRENT SUPPLY (120% COMPLIANT) <br />IF THE RELOCATED LOADS EXTEND MORE THAN 6 FEET, AFCI PROTECTION APPLIES PER 2019 CEC 210.12 <br />ANY MULTIWIRE BRANCH CIRCUITS RELOCATED ARE TO BE IDENTIFIED, GROUPED, AND EQUIPPED WITH A 2-POLE OCPD BREAKER PER CEC 210.4(B,D).C1