TE OLIRFFOAC
<br />LANRP
<br />E 23191
<br />STA
<br />ER
<br />REGIST
<br />ED
<br />INA
<br />N
<br />REENIGE
<br />FO OISSE
<br />E AICLCERTL
<br />Exp. 06/30/26
<br />MIRASOPHOCLISGEORGY
<br />IMEG RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO
<br />THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAW ING
<br />AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG AND SHALL NOT
<br />BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE
<br />EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG.
<br />©2024 IMEG CONSULTANTS CORP.
<br />REF. SCALE IN INCHES
<br />0 1 2 3
<br />222 S. HARBOR BOULEVARD
<br />SUITE 800
<br />ANAHEIM, CA 92805
<br />P: 714.490.5555 F: 714.490.5560
<br />The FUTURE. Built Smarter www.imegcorp.com
<br />PROJECT #24007312.00
<br />0 5'
<br />GRAPHIC SCALES:
<br />Issue Date
<br />1/16" = 1'-0"
<br />50'
<br />1/8" = 1'-0"1/4" = 1'-0"1/2" = 1'-0"3/4" = 1'-0"1" = 1'-0"1-1/2" = 1'-0"3" = 1'-0"
<br />0 5'25' 0 1'12' 0 1'6' 0 4' 0 3'1'0 2' 0 1'
<br />Chckd By
<br />Drwn By
<br />Scale
<br />Building ID:
<br />KP Proj. No.
<br />Permit No.
<br />Sheet
<br />SheetsOf
<br />Sheet Title
<br />Project
<br />Facility
<br />This document is the property of the Owner and is
<br />Project Architect Approval:
<br />Architect/Engineer Of Record:
<br />IF THIS SHEET IS NOT 30"x42" , IT IS
<br />A REDUCED PRINT - SCALE ACCORDINGLY
<br />National Facilities Services
<br />Post Office Box 12916
<br />Oakland California 94604
<br />not to be used without owner's written permission.
<br />Floor Lev: Section:
<br />HGW Proj. No.
<br />©
<br />A
<br />R
<br />C
<br />H
<br />I
<br />T
<br />E
<br />C
<br />T
<br />S
<br />
<br />h
<br />a
<br />n
<br />n
<br />a
<br />
<br />g
<br />a
<br />b
<br />r
<br />i
<br />e
<br />l
<br />
<br />w
<br />e
<br />l
<br />l
<br />s
<br />,
<br />
<br />a
<br />l
<br />l
<br />
<br />r
<br />i
<br />g
<br />h
<br />t
<br />s
<br />
<br />r
<br />e
<br />s
<br />e
<br />r
<br />v
<br />ed
<br />.
<br />
<br />
<br />A
<br />n
<br />y
<br />
<br />u
<br />s
<br />e
<br />
<br />w
<br />i
<br />t
<br />h
<br />o
<br />u
<br />t
<br />
<br />p
<br />e
<br />r
<br />m
<br />i
<br />s
<br />s
<br />i
<br />o
<br />n
<br />
<br />i
<br />s
<br />
<br />e
<br />x
<br />p
<br />r
<br />e
<br />s
<br />s
<br />l
<br />y
<br />
<br />p
<br />r
<br />o
<br />h
<br />i
<br />b
<br />i
<br />t
<br />ed
<br />.
<br />
<br />
<br />P
<br />l
<br />o
<br />t
<br />t
<br />e
<br />d
<br />CAP029271
<br />1955 Bacon Street. San Diego, CA 92107
<br />Office 619 523 8487
<br />www.hgwarchitecture.com
<br />PROJECT #24007312.00
<br />Revisions
<br />By Appr.
<br />KAISER HARBOR MACARTHUR MOB
<br />EXTERIOR SIGNAGE
<br />KAISER PERMANENTE
<br />HARBOR MACARTHUR MOB
<br />1/
<br />2
<br />3
<br />/
<br />2
<br />0
<br />2
<br />6
<br />
<br />1
<br />2
<br />:
<br />4
<br />5
<br />:
<br />5
<br />3
<br />
<br />P
<br />M
<br />01/23/2026
<br />MG
<br />CL
<br />ES004
<br />ELECTRICAL SPECIFICATIONS
<br />3401 South Harbor Boulevard,
<br />Santa Ana, CA 92704
<br />10
<br />0
<br />%
<br />
<br />C
<br />D
<br />
<br />S
<br />E
<br />T
<br />2441
<br />ELECTRICAL SPECIFICATIONS TABLE OF CONTENT
<br />• SECTION 26 05 53 -ELECTRICAL IDENTIFICATION
<br />SECTION 26 05 53 -ELECTRICAL IDENTIFICATION
<br />PART 1 -GENERAL
<br />1.1 SECTION INCLUDES
<br />A.ADHESIVE MARKINGS AND FIELD LABELS
<br />B.NAMEPLATES AND SIGNS
<br />C.PRODUCT COLORS
<br />1.2 REFERENCES
<br />A.NFPA 70E -NATIONAL ELECTRICAL SAFETY CODE
<br />B.CEC CALIFORNIA ELECTRICAL CODE
<br />C.ANSI A13.1 -STANDARD FOR PIPE IDENTIFICATION
<br />D.ANSI Z535.4 -STANDARD FOR PRODUCT SAFETY SIGNS AND LABELS
<br />1.3 QUALITY ASSURANCE
<br />A.ELECTRICAL IDENTIFICATION PRODUCTS SHALL BE SUITABLE FOR THE ENVIRONMENT
<br />INSTALLED. IDENTIFICATION LABELS DAMAGED BY THE ENVIRONMENT DUE TO
<br />ULTRAVIOLET LIGHT FADING, DAMP OR WET CONDITIONS, PHYSICAL DAMAGE,
<br />CORROSION, OR OTHER CONDITIONS SHALL BE REPLACED WITH LABELS SUITABLE FOR
<br />THE ENVIRONMENT.
<br />PART 2 -PRODUCTS
<br />2.1 ADHESIVE MARKINGS AND FIELD LABELS
<br />A.ADHESIVE MARKING LABELS FOR RACEWAY: PRE-PRINTED, FLEXIBLE, SELF-ADHESIVE
<br />VINYL LABELS WITH LEGEND INDICATING VOLTAGE AND SERVICE (EMERGENCY, LIGHTING,
<br />POWER, HVAC, COMMUNICATIONS, CONTROL, FIRE).
<br />1.LABEL SIZE AS FOLLOWS:
<br />a.RACEWAYS: KROY OR BROTHER LABELS 1-INCH (25MM) HIGH BY 12-INCHES
<br />(305MM) LONG (MINIMUM).
<br />2.COLOR: AS SPECIFIED FOR VARIOUS SYSTEMS.
<br />B.COLORED ADHESIVE MARKING TAPE FOR BANDING RACEWAYS, WIRES, AND CABLES:
<br />SELF-ADHESIVE VINYL TAPE NOT LESS THAN 3 MILS THICK BY 1 INCH (25MM) TO 2 INCHES
<br />(50MM) IN WIDTH.
<br />C.WIRE/CABLE DESIGNATION TAPE MARKERS: VINYL OR VINYL-CLOTH, SELF-ADHESIVE,
<br />WRAPAROUND, CABLE/CONDUCTOR MARKERS WITH PREPRINTED NUMBERS AND LETTER.
<br />2.2 PRODUCT COLORS
<br />A.NAMEPLATES AND SIGNS:
<br />1.NORMAL POWER: BLACK LETTERS ON WHITE FACE
<br />2.CONTROL LABELS: BLACK LETTERS ON WHITE FACE
<br />B.RACEWAYS AND CONDUIT:
<br />1.PROVIDE COLOR CODED CONDUIT AS INDICATED BELOW. CONDUIT SHALL BE
<br />COLORED BY THE MANUFACTURER:
<br />a.NORMAL POWER AND GENERAL DISTRIBUTION: SILVER
<br />b.EMERGENCY POWER DISTRIBUTION SYSTEM:
<br />1)ALL EMERGENCY: ORANGE
<br />c.FIRE ALARM SYSTEM: RED
<br />d.LOW VOLTAGE AND TELEPHONE: PURPLE
<br />C.BOX COVERS:
<br />1.BOX COVERS SHALL BE PAINTED TO CORRESPOND WITH SYSTEM TYPE AS FOLLOWS:
<br />a.NORMAL POWER AND GENERAL: SILVER
<br />b.EMERGENCY POWER AND DISTRIBUTION:
<br />1)ALL EMERGENCY: ORANGE
<br />c.FIRE ALARM SYSTEM: RED
<br />d.GROUND: GREEN
<br />e.LOW VOLTAGE AND TELEPHONE: PURPLE
<br />2.BOX COVER COLORS SHALL MATCH CONDUIT COLORS LISTED ABOVE.
<br />D.CONDUCTOR COLOR IDENTIFICATION: REFER TO PART 3 FOR ADDITIONAL INFORMATION.
<br />PART 3 -EXECUTION
<br />3.1 INSTALLATION
<br />A.LETTERING AND GRAPHICS: COORDINATE NAMES, ABBREVIATIONS, COLORS, AND OTHER
<br />DESIGNATIONS USED IN ELECTRICAL IDENTIFICATION WORK WITH CORRESPONDING
<br />DESIGNATIONS SPECIFIED OR INDICATED. INSTALL NUMBERS, LETTERING, AND COLORS
<br />AS APPROVED IN SUBMITTALS AND AS REQUIRED BY CODE.
<br />B.EXPOSED CEILINGS AND FINISHED SPACES: THE PROJECT INCLUDES EXPOSED CEILINGS
<br />IN FINISHED SPACES. THE INSTALLATION OF COLORED RACEWAYS AND LABELING MAY
<br />NOT BE AESTHETICALLY DESIRABLE IN FINISHED SPACES. THE CONTRACTOR SHALL
<br />COORDINATE IDENTIFICATION REQUIREMENTS IN EXPOSED CEILINGS OF FINISHED
<br />SPACES WITH THE A/E PRIOR TO INSTALLATION AND ORDERING OF MATERIALS.
<br />C.INSTALL IDENTIFICATION DEVICES IN ACCORDANCE WITH MANUFACTURER'S WRITTEN
<br />INSTRUCTION AND REQUIREMENTS OF ELECTRICAL CODE.
<br />D.SEQUENCE OF WORK: WHERE IDENTIFICATION IS TO BE APPLIED TO SURFACES THAT
<br />REQUIRE FINISH, INSTALL IDENTIFICATION AFTER COMPLETION OF FINISH WORK. ALL
<br />MOUNTING SURFACES SHALL BE CLEANED AND DEGREASED PRIOR TO IDENTIFICATION
<br />INSTALLATION.
<br />E.CIRCUIT IDENTIFICATION: TAG OR LABEL CONDUCTORS AS FOLLOWS:
<br />1.MULTIPLE POWER OR LIGHTING CIRCUITS IN SAME ENCLOSURE: WHERE MULTIPLE
<br />BRANCH CIRCUITS ARE TERMINATED OR SPLICED IN A BOX OR ENCLOSURE, LABEL
<br />EACH CONDUCTOR WITH SOURCE AND CIRCUIT NUMBER.
<br />2.MULTIPLE CONTROL WIRING AND COMMUNICATION/SIGNAL CIRCUITS IN SAME
<br />ENCLOSURE: FOR CONTROL AND COMMUNICATIONS/SIGNAL WIRING, USE WIRE/CABLE
<br />MARKING TAPE AT TERMINATIONS IN WIRING BOXES, TROUGHS, AND CONTROL
<br />CABINETS. USE CONSISTENT LETTER/NUMBER CONDUCTOR DESIGNATIONS
<br />THROUGHOUT ON WIRE/CABLE MARKING TAPE.
<br />3.MATCH IDENTIFICATION MARKINGS WITH DESIGNATIONS USED IN PANELBOARDS SHOP
<br />DRAWINGS, CONTRACT DOCUMENTS, AND SIMILAR PREVIOUSLY ESTABLISHED
<br />IDENTIFICATION SCHEMES FOR THE FACILITY'S ELECTRICAL INSTALLATIONS.
<br />F.INSTALL LABELS PARALLEL TO EQUIPMENT LINES AT LOCATIONS AS REQUIRED AND AT
<br />LOCATIONS FOR BEST CONVENIENCE OF VIEWING WITHOUT INTERFERENCE WITH
<br />OPERATION AND MAINTENANCE OF EQUIPMENT.
<br />3.2 FEEDER AND BRANCH CIRCUIT DIRECTORIES
<br />A.PRODUCT:
<br />1.ADHESIVE LABELS AND FIELD MARKINGS
<br />2.NAMEPLATES AND SIGNS
<br />B.FEEDER DIRECTORIES BRANCH: PROVIDE EACH FEEDER, BRANCH CIRCUIT, FEEDER
<br />MODIFICATION, AND BRANCH CIRCUIT MODIFICATION WITH A TYPED CIRCUIT DIRECTORY
<br />LABEL. REFER TO TECHNICAL EQUIPMENT SPECIFICATION SECTIONS FOR ADDITIONAL
<br />REQUIREMENTS. INCLUDE THE FOLLOWING WITH EACH LABEL:
<br />1.LOAD DESCRIPTION: LIGHTING, RECEPTACLES, SPECIFIC EQUIPMENT, SPARE, SPACE,
<br />OR SIMILAR DESCRIPTION.
<br />2.LOCATION: ROOM NAME, NUMBER, LOCATION.
<br />C.PROVIDE A FACTORY OR CUSTOM CLEAR PLASTIC SLEEVE FOR EACH BRANCH PANEL
<br />DIRECTORY AND SECURE TO INSIDE PANEL COVER.
<br />3.3 LIGHTING CONTROL AND RECEPTACLE COVER PLATES
<br />A.IDENTIFICATION TO BE ENGRAVED DIRECTLY ON THE STAINLESS STEEL COVERPLATES.
<br />LETTER AND NUMBER SIZE TO 1/8-INCH (3MM) HIGH.
<br />B.PROVIDE IDENTIFICATION ON ALL SWITCH AND RECEPTACLE COVER PLATES.
<br />IDENTIFICATION SHALL INDICATE SOURCE AND CIRCUIT NUMBER SERVING THE DEVICE
<br />(E.G. "C1A -24").
<br />3.4 CONDUIT AND EXPOSED CABLE LABELING
<br />A.PRODUCT:
<br />1.ADHESIVE LABELS AND FIELD MARKINGS
<br />B.CONDUIT IDENTIFICATION: PRE-PRINTED, FLEXIBLE, SELF-ADHESIVE VINYL LABELS WITH
<br />LEGEND AT 20 FOOT (6 METER) INTERVALS TO IDENTIFY ALL CONDUITS RUN EXPOSED OR
<br />LOCATED ABOVE ACCESSIBLE CEILINGS. CONDUITS LOCATED ABOVE NON-ACCESSIBLE
<br />CEILING OR IN FLOORS AND WALLS SHALL BE LABELED WITHIN 3 FEET OF BECOMING
<br />ACCESSIBLE, OR SEPARATED BY ENCLOSURES, WALLS, PARTITIONS, CEILINGS, AND
<br />FLOORS. LABELS FOR MULTIPLE CONDUITS SHALL BE ALIGNED. REFER TO COLOR
<br />REQUIREMENTS IN PART 2 WHEN APPLICABLE IN ADDITION TO THE FOLLOWING:
<br />1.1000 VOLT OR LESS NORMAL/EMERGENCY POWER: INDICATE FEEDER IDENTIFICATION
<br />AND VOLTAGE.
<br />2.FIRE ALARM: INDICATE "FIRE ALARM".
<br />3.GROUNDING: INDICATE "GROUND" AND EQUIPMENT AND DESIGNATION.
<br />4.TELEPHONE SYSTEM: INDICATE "TELEPHONE".
<br />C.BLANK CONDUIT ENDS OR OUTLET BOXES FOR FUTURE EXTENSION OF SYSTEM SHALL
<br />HAVE PERMANENT IDENTIFICATION MARKER INDICATING PURPOSE OF CONDUIT OR BOX
<br />AND WHERE THE RACEWAY ORIGINATED.
<br />3.5 BOX LABELING
<br />A.PRODUCTS:
<br />1.ADHESIVE LABELS AND FIELD MARKINGS
<br />B.IDENTIFY JUNCTION, PULL AND CONNECTION BOXES: LABELING SHALL BE 3/8-INCH (10MM)
<br />KROY TAPE OR BROTHER SELF-LAMINATING VINYL LABEL, LETTERS/NUMBERS COLOR
<br />CODED SAME AS CONDUITS. IN ROOMS THAT ARE PAINTED OUT, PROVIDE LABELING ON
<br />INSIDE OF COVER.
<br />C.ALL JUNCTION, PULL, AND CONNECTION BOXES SHALL BE IDENTIFIED AS FOLLOWS:
<br />1.FOR POWER AND LIGHTING CIRCUITS, INDICATE SYSTEM VOLTAGE AND IDENTITY OF
<br />CONTAINED CIRCUITS ("120V, 1LA1-3,5,7").
<br />2.FOR OTHER WIRING, INDICATE SYSTEM TYPE AND DESCRIPTION OF WIRING ("FIRE
<br />ALARM NAC #1").
<br />3.6 CONDUCTOR COLOR CODING
<br />A.PRODUCTS:
<br />1.ALL WIRE AND CABLES SHALL BE COLOR CODED BY THE MANUFACTURER.
<br />2.WIRE AND CABLES SMALLER THAN 6 AWG SHALL BE COLOR CODED BY THE
<br />MANUFACTURER.
<br />B.WHERE MORE THAN ONE NOMINAL VOLTAGE SYSTEM EXISTS IN A BUILDING OR FACILITY,
<br />EACH UNGROUNDED CONDUCTOR OF A MULTI-WIRE BRANCH CIRCUIT, WHERE
<br />ACCESSIBLE, SHALL BE IDENTIFIED BY PHASE AND SYSTEM.
<br />C.CONDUCTORS SHALL BE COLOR CODED AS FOLLOWS:
<br />1.208Y/120 VOLT, 4-WIRE:
<br />a.A-PHASE -BLACK
<br />b.B-PHASE -RED
<br />c.C-PHASE -BLUE
<br />d.NEUTRAL -WHITE
<br />e.GROUND BOND -GREEN
<br />2.480Y/277 VOLT, 4-WIRE:
<br />a.A-PHASE -BROWN
<br />b.B-PHASE -ORANGE
<br />c.C-PHASE -YELLOW
<br />d.NEUTRAL -GRAY
<br />e.GROUND BOND -GREEN
<br />3.GROUNDING CONDUCTORS:
<br />a.EQUIPMENT GROUNDING CONDUCTORS, MAIN/SYSTEM/SUPPLY-SIDE BONDING
<br />JUMPERS: GREEN.
<br />4.CABLING FOR REMOTE CONTROL, SIGNAL, AND POWER LIMITED CIRCUITS:
<br />a.FIRE ALARM: REFER TO FIRE ALARM AND AUTOMATIC DETECTION SECTION 28 31 00
<br />FOR CABLE COLOR REQUIREMENTS.
<br />b.LOW VOLTAGE SWITCHING: PER MANUFACTURER RECOMMENDATIONS AND CODE
<br />REQUIREMENTS.
<br />END OF SECTION