<br /> <br /> Page 36 of 111 <br /> <br />Report No.: 2410B0143SHA-001 <br /> <br />TRF No. ANSI/CAN/UL 9540A_Unit <br /> <br />ANSI/CAN/UL 9540A <br />Clause Requirement – Test Result - Remark Verdict <br />not exceed the temperature at which thermally <br />initiated cell venting occurs, as determined in <br />7.3.1.8; <br />c) For BESS units intended for installation near <br />exposures, surface temperature measurements on <br />wall surfaces do not exceed 97°C of temperature <br />rise above ambient per 9.2.15; <br /> N/A <br />d) Explosion hazards are not observed, including <br />deflagration, detonation or accumulation (to within <br />the flammability limits in an amount that can cause a <br />deflagration) of battery vent gases; and <br /> N/A <br />e) Heat flux in the center of the accessible means of <br />egress shall not exceed 1.3 kW/m2. N/A <br />Indoor <br />Wall <br />Mounted <br />a) Flaming outside the initiating BESS unit is not <br />observed as demonstrated by no flaming or charring <br />of the cheesecloth indicator; <br /> N/A <br />b) Surface temperatures of modules within the target <br />BESS units adjacent to the initiating BESS unit do <br />not exceed the temperature at which thermally <br />initiated cell venting occurs, as determined in <br />7.3.1.8; <br /> N/A <br />c) For BESS units intended for installation in locations <br />with combustible construction, surface temperature <br />measurements on wall surfaces do not exceed 97°C <br />of temperature rise above ambient per 9.2.15; <br /> N/A <br />d) Explosion hazards are not observed, including <br />deflagration, detonation or accumulation (to within <br />the flammability limits in an amount that can cause a <br />deflagration) of battery vent gases; and <br /> N/A <br />e) The concentration of flammable gas does not <br />exceed 25% LFL for the smallest intended room <br />installation size. <br /> N/A <br />Outdoor <br />Wall <br />Mounted <br />a) Flaming outside the initiating BESS unit is not <br />observed as demonstrated by no flaming or charring <br />of the cheesecloth indicator; <br /> N/A <br />b) Surface temperatures of modules within the target <br />BESS units adjacent to the initiating BESS unit do <br />not exceed the temperature at which thermally <br />initiated cell venting occurs, as determined in <br />7.3.1.8; <br /> N/A <br />c) For BESS units intended for installation in locations <br />with combustible construction, surface temperature <br />measurements on wall surfaces do not exceed 97°C <br />of temperature rise above ambient per 9.2.15; and <br /> N/A