Laserfiche WebLink
<br /> <br /> Page 98 of 111 <br /> <br />Report No.: 2410B0143SHA-001 <br /> <br />TRF No. ANSI/CAN/UL 9540A_Unit <br /> <br />Attachment 8 Chemical heat release rate measurement <br /> <br />The chemical heat release rate was measured by a measurement system consisting of a paramagnetic <br />oxygen analyzer, non-dispersive infrared carbon dioxide and carbon monoxide analyzer, velocity probe, and <br />a Type K thermocouple. The instrumentation was located in the exhaust duct of the heat release rate <br />calorimeter at a location that minimizes the influence of bends or exhaust devices. <br /> <br />Measured peak chemical heat release rate HRRt= 4.04kW. <br /> <br /> <br /> <br />Chemical heat release rate (HRRt) versus time data curve <br /> <br />