GRAB BARS
<br />1. Grab bars with circular section shall have an outside diameter of 1¼ inches minimum and 2 inches
<br />maximum. Grab bars with non-circular cross section shall have a cross-section dimension of 2
<br />inches maximum and a perimeter dimension of 4 inches minimum and 4.8 inches maximum.
<br />[11B-609.2]
<br />2. The space between the wall and the grab bar shall be 1½ inches. The space between the grab bar
<br />and projecting objects below and at the ends shall be 1½ inches minimum. The space between the
<br />grab bar and projecting above shall be 12 inches minimum. The space between the grab bars and
<br />shower controls, shower fittings, and other grab bars above shall be permitted to be 1½ inches
<br />minimum.
<br />3. Grab bars shall be installed in a horizontal position, 33 inches minimum and 36 inches maximum
<br />above the finish floor measured to the top of the gripping surface.
<br />4. Grab bars and any wall or other surfaces adjacent to grab bars shall be free of sharp or abrasive
<br />elements and shall have rounded edges. [11B-609.5]
<br />5. Grab bars shall not rotate within their fittings. [11B-609.6]
<br />6. Allowable stresses shall not be exceeded for materials used when a vertical or horizontal force of
<br />250 pounds is applied at any point on the grab, fastener, mounting device, or supporting structure.
<br />[11B-609.8]
<br />DIVISION 7: COMMUNICATION ELEMENTS AND FEATURES
<br />SIGNS
<br />1. Raised characters shall comply with 11B-703.2 Raised characters and shall be duplicated in
<br />Braille complying with 11B-703.3 Braille. Raised characters shall be installed in accordance with
<br />11B-703.4 Installation Height and Location. §11B-703.2
<br />a. Raised characters shall be 1/32" minimum above their background. §11B-703.2.1
<br />b. Characters shall be uppercase. §11B-703.2.2
<br />c. Characters shall be sans serif. Characters shall not be italic, oblique, script, highly
<br />decorative, or of other unusual forms. §11B-703.2.3
<br />d. Characters shall be selected from fonts where the width of the uppercase letter "O" is 55
<br />60 percent minimum and 110 percent maximum of the height of the uppercase letter "I". §
<br />11B-703.2.4
<br />e. Characters height measured vertically from the baseline of the character shall be 5/8”
<br />minimum and 2”maximum based on the height of the uppercase letter “I”. §11B-703.2.5
<br />f. Stroke thickness of the uppercase letter “I”shall be 15 percent maximum of the height of
<br />the character. §11B-703.2.6
<br />g. Character spacing shall be measured between the two closest points of adjacent raised
<br />characters within a message, excluding word spaces. Where characters have rectangular
<br />cross sections, spacing between individual raised characters shall be 1/8”minimum and 4
<br />times the raised characters stroke width maximum. Where characters have other cross
<br />sections, spacing between individual raised characters shall be 1/16”minimum and 4 times
<br />the raised characters stroke width maximum at the base of the cross section, and 1/8”inch
<br />minimum and 4 times the raised character stroke width maximum at the top of the cross
<br />sections. Characters shall be separated from raised borders and decorative elements 3/8”
<br />minimum.§11B-703.2.7
<br />h. Spacing between the baselines of separate lines of raised characters within a message
<br />shall be 135 percent minim and 170 percent maximum of the raised character height. §
<br />11B-703.2.8
<br />i. Text shall be in a horizontal format.§11B-703.2.9
<br />2. Braille shall be contracted (Grade 2) and shall comply with 11B-703.3 Braille and 11B-703.4
<br />Installation Height and Location.§11B-703.3
<br />a. Braille dots shall have a domed or rounded shape and shall comply with Table
<br />11B-703.3.1 The indication of an uppercase letter or letters shall only be used before the first
<br />word of sentences, proper nouns and names, individual letters of the alphabet, initials, and
<br />acronyms.§11B-703.3.1
<br />b. Braille shall be positioned below the corresponding text in a horizontal format, flush left or
<br />centered. If text is multi-lined, Braille shall be placed below the entire text. Braille shall be
<br />separated 3/8”minimum and ½”maximum from any other tactile characters and 3/8”
<br />minimum from raised borders and decorative elements.§11B-703.3.2
<br />3. Signs with tactile characters shall comply with 11B-703.4 Installation Height and Location.§
<br />11B-703.4
<br />a. Tactile characters on signs shall be located 48 inches minimum above finish floor or
<br />ground surface, measured from baseline of the lowest tactile character Braille cells and 60
<br />inches maximum above finish floor or ground surface, measured from the baseline of the
<br />highest tactile character line of raised characters.§11B703.4.1 (See exception)
<br />b. Where a tactile sign is provided at a door, the sign shall be located alongside the door at
<br />the latch side. Where a tactile sign is provided at double doors with one active leaf, the sign
<br />shall be located on the inactive leaf. Where a tactile sign is provided at double doors with two
<br />active leafs, the sign shall be located to the right of the right hand door Where there is no
<br />wall space at the latch side of a single door or at the right side of double doors, signs shall be
<br />located on the nearest adjacent wall. Signs containing tactile characters shall be located so
<br />that a clear floor space of 18 inches minimum by 18 inches minimum, centered on the tactile
<br />character, is provided beyond the arc of any door swing between the closed position and 45
<br />degree open position. Where permanent identification signage is provided for rooms and
<br />spaces they shall be located on the approach side of the door as one enters the room or
<br />space. Signs that identify exits shall be located on the approach side of the door as one exits
<br />the room or space. 11B-703.4.2 (See exception)
<br />4. Visual characters shall comply with the following, except where visual characters comply with
<br />11B-703.2 Raised Characters and are accompanied by Braille complying with 11B-703.3 Braille, they
<br />shall not be required to comply with 11B-703.5.2 through 11B-703.5.6, 11B-703.5.8 and 11B-703.5.9:
<br />a. Characters and their background shall have a non-glare finish. Characters shall contrast
<br />with their background with either light characters on a dark background or dark characters on
<br />a light background. §11B-703.5.1
<br />b. Characters shall be uppercase or lowercase or a combination of both. §11B-703.5.2
<br />c. Characters shall be conventional in form. Characters shall not be italic, oblique, script,
<br />highly decorative, or of other unusual forms. §11B-703.5.3
<br />d. Characters shall be selected from fonts where the width of the uppercase letter “O”is 55
<br />60 percent minimum and 110 percent maximum of the height of the uppercase letter “I”. §
<br />11B-703.5.4
<br />e. Minimum character height shall comply with Table 11B-703.5.5 Viewing distance shall be
<br />measured as the horizontal distance between the character and an obstruction preventing
<br />further approach towards the sign. Character height shall be based on the uppercase letter
<br />“I”. §11B-703.5.5 (See exception)
<br />f. Visual characters shall be 40 inches minimum above the finish floor or ground. §
<br />11B-703.5.6 (See exceptions)
<br />g. Stroke thickness of the uppercase letter “I”shall be 10 percent minimum and 20 percent
<br />maximum of the height of the character. §11b-703.5.7
<br />h. Character spacing shall be measured between the two closest points of adjacent
<br />characters, excluding word spaces. Spacing between individual characters shall be 10
<br />percent minimum and 35 percent maximum of character height. §11B-703.5.8
<br />i. Spacing between the baselines of separate lines of characters within a message shall
<br />be135 percent minimum and 170 percent maximum of the character height. §11B-703.5.9
<br />j. Text shall be in a horizontal format. §11B-703.5.10
<br />5. Pictograms shall comply with the following:
<br />a. Pictograms shall have a field height of 6 inches minimum. Characters and Braille shall not
<br />be located in the pictogram field. §11B-703.6.1
<br />b. Pictograms and their fields shall have a non-glare finish. Pictograms shall contrast with
<br />their field with either a light pictogram on a dark field or a dark pictogram on a light field. §
<br />11B-703.6.2
<br />c. Pictograms shall have text descriptors located directly below the pictogram field. Text
<br />descriptors shall comply with 11B-703.2 Raised Characters, 11B-703.3 Braille and
<br />11B-703.4 Installation Height and Location. §11B-703.6.3
<br />6. Symbols of accessibility and their background shall have a non-glare finish. Symbols of
<br />Accessibility shall contrast with their background with either a light symbol on a dark
<br />background or a dark symbol on a light background. §11B-703.7.1
<br />7. Symbols shall comply with the following:
<br />a. The International Symbol of Accessibility shall comply with Figure 11B-703.7.2.1 ISA. The
<br />symbol shall consist of a white figure on a blue background. The blue shall be Color No.
<br />15090 in Federal Standard 595B. §11B-703.7.2.1 (See exception)
<br />b. The International Symbol of TTY shall comply with Figure 11B-703.7.2.2.
<br />c. Telephones with a volume control shall be identified by a pictogram of a telephone
<br />handset with radiating sound waves on a square field such as shown in figure 11B-703.7.2.3.
<br />d. Assistive listening systems shall be identified by the International Symbol of Access for
<br />Hearing Loss complying with Figure 11B-703.7.2.4.
<br />e. Edges of signs shall be rounded chamfered or erased. Corners of signs shall have a
<br />minimum radius of 1/8 inch. §11B-703.7.2.6.4
<br />E. SPECIAL ROOMS, SPACES, AND ELEMENTS
<br />F. BUILT-IN ELEMENTS
<br />DINING SURFACES AND WORK SURFACES
<br />(Note or show on the plans)
<br />1.The tops of dining surfaces and work surfaces shall be 28 inches minimum and 34 inches
<br />maximum above the finish floor or ground. §11B-902.3
<br />2.2. Where food or drink is served for consumption at a counter exceeding 34 inches in height,
<br />a portion of the main counter 60 inches minimum in length shall be provided in compliance with
<br />11B-902.3. §11B-226.3
<br />DIVISION 3 – BUILDING BLOCKS
<br />FLOOR OR GROUND SURFACE
<br />1. Floor and ground surfaces shall be stable, firm, and slip resistant. §11B-302.1
<br />2. Carpet or carpet tile shall be securely attached and shall have a firm cushion, pad, or backing or
<br />no cushion or pad. Carpet or carpet tile shall have a level loop,
<br />textured loop, level cut pile, or level cut/uncut pile texture. Pile height shall be ½ inch maximum. §
<br />11B- 302.2, Figure 11B-302.2
<br />3. Exposed edges of carpet shall be fastened to floor surfaces and shall have trim on the entire
<br />length of the exposed edge. Carpet edge trim shall comply with 11B-303 changes in level. Per
<br />11B-302.2
<br />CHANGES IN LEVEL
<br />4. Vertical changes in level for floor or ground surfaces may be 1/4" high max. and without edge
<br />treatment. Changes in level greater than 1/4" and not exceeding 1/2" in height shall be beveled with a
<br />slope not steeper than 1:2. Per 11B-303, Figures 11B-303.2 & 11B-303.3
<br />5. Changes in level greater than ½" in height shall be ramped and shall comply with the requirements
<br />of 11B-405 Ramps or 11B-406 Curb Ramps as applicable.
<br />§11B-303
<br />TURNING SPACE
<br />1. Floor or ground surfaces of a turning space shall be level with slopes not steeper than 1:48.
<br />[11B-304.2]
<br />2. Circular turning space shall be a space of 60 inches diameter minimum with knee and toe
<br />clearance complying with Section 11B-306. [11B-304.3.1] 3. T-Shaped turning space shall be a
<br />space within 60 inch square minimum with arms and base 36 inches wide minimum. Each arm of the
<br />T shall be clear of obstructions 12 inches minimum in each direction and the base shall be clear of
<br />obstructions 24 inches minimum. [11B-304.3.2]
<br />CLEAR FLOOR OR GROUND SPACE
<br />1. Clear floor or ground spaces shall meet the requirements of 11B-302 Floor or Ground Surfaces
<br />and shall not have changes in level except for slopes not steeper than 1:48 (2.083%). §11B-305
<br />2. Clear floor or ground space shall be 30" minimum by 48" minimum. §11B-305.3, Figure 11B-305.3
<br />3. Clear floor or ground spaces shall be positioned for either forward or parallel approach to an
<br />element unless otherwise specified. One full unobstructed side of the clear floor or ground space
<br />shall adjoin an accessible route or adjoin another clear floor or ground space. §11B-305.5, §
<br />11B-305.6, Figure §11B-305.5
<br />4. Clear floor or ground space may include knee and toe clearance complying with 11B-306 knee
<br />and Toe Clearance unless otherwise specified. §11B-305.4
<br />KNEE AND TOE CLEARANCE
<br />10. For built-in dining required to be accessible, toe clearance shall be provided that is 30 inches in
<br />width and 9 inches in height above the finish floor or ground for a depth of 19 inches minimum. §
<br />11B-306.2.1
<br />11. Space extending greater than 6" beyond the available knee clearance at 9" above the finish floor
<br />or ground shall not be considered toe clearance. §11B-306.2.4
<br />12. Toe clearance shall extend 19 inches maximum under lavatories for toilet and bathing facilities
<br />and 25 inches maximum under other elements. §11B-306.2.2
<br />13. At lavatories in toilet and bathing facilities, knee clearance shall be provided that is 30 inches in
<br />width for a depth of 11 inches at 9 inches above the finish floor or ground and for a depth of 8 inches
<br />at 27 inches above the finish floor or ground increasing to 29 inches high minimum above the finish
<br />floor or ground at the front edge of a counter with a built-in lavatory or at the front edge of a wall-
<br />mounted lavatory fixture. §11B-306.3.3, Figure 11B-306.3(c)
<br />14. At dining and work surfaces required to be accessible, knee clearance shall be provided that is
<br />30 inches in width at 27 inches above the finish floor or ground for a
<br />depth of at least 19 inches. §11B-306.3
<br />15. Knee clearance shall extend 25" maximum under an element at 9" above the finish floor or
<br />ground. §11B-306.3.2
<br />PROTRUDING OBJECTS
<br />16. Except for handrails, objects with leading edges more than 27 inches and less than 80 inches
<br />above the finish floor or ground shall protrude no more than 4 inches
<br />horizontally into the circulation path. Handrails may protrude 4½ inches maximum. §11B-307.2,
<br />Figure 11B-307.2
<br />17. Freestanding objects mounted on posts or pylons shall overhang circulation paths no more than
<br />12 inches when located from 27 to 80 inches above the finish
<br />floor or ground. §11B-307.3, Figure 11B-307.3(a)
<br />18. Protruding objects shall not reduce the clear width required for accessible routes. §11B-307.5
<br />19. Lowest edge of a sign or other obstruction, when mounted between posts or pylons separated
<br />with a clear distance greater than 12 inches, shall be less than
<br />27 inches or more than 80 inches above the finish floor or ground. §11B-307.3, Figure 11B-307.3(b)
<br />20. Edge of signs or other objects, when mounted on posts or pylons with their bottom edges less
<br />than 80" above the floor or ground surface, shall be rounded or eased and the corners shall have a
<br />minimum radius of 1/8". §11B-307.3.1
<br />21. Vertical clearance shall be at least 80 inches high on circulation paths except at door closer's
<br />and door stops, which may be 78 inches minimum abov e the finish floor or ground. §11B-307.4
<br />REACH RANGES
<br />22. Electrical controls and switches intended to be used by the occupant of a room or area to control
<br />lighting and receptacle outlets, appliances or cooling, heating and
<br />ventilating equipment shall be located within allowable reach ranges. Low reach shall be measured to
<br />the bottom of the outlet box and high reach shall be measured to the top of the outlet box. §
<br />11B-308.1.1
<br />23. Electrical receptacle outlets on branch circuits of 30 amperes or less and communication system
<br />receptacles shall be located within allowable reach
<br />ranges. Low reach shall be measured to the bottom of the outlet box and high reach shall be
<br />measured to the top of the outlet box. §11B-308.1.2.
<br />24. High forward reach that is unobstructed shall be 48 inches maximum and the low forward reach
<br />shall be 15 inches minimum above the finish floor or ground. §11B-308.2.1, Figure 11B-308.2.1
<br />25. High forward reach shall be 48 inches maximum where the reach depth is 20 inches or less and
<br />44 inches maximum where the reach depth exceeds 20 inches.
<br />High forward reach shall not exceed 25 inches in depth. §11B-308.2.2, Figure 11B-308.2.2
<br />26. Where a high forward reach is over an obstruction, the clear floor space shall extend beneath the
<br />element for a distance not less than the required reach depth over the obstruction. §11B-308.2.2
<br />27. High side reach shall be 48 inches maximum and the low side reach shall be 15 inches minimum
<br />above the finish floor where the side reach is unobstructed or the depth of any obstruction does not
<br />exceed 10 inches. §11B-308.3.1, Figure 11B-308.3.1
<br />28. High side reach shall be 46 inches maximum above the finish floor or ground where the high side
<br />reach is over an obstruction more than 10 inches but not more than 24 inches in depth. §
<br />11B-308.3.2, Figure 11B-308.3.2
<br />29. Obstructions for high side reach shall not exceed 34 inches in height and 24 inches in depth. §
<br />11B-308.3.2, Figure 11B-308.3.2
<br />30. Operable parts on accessible elements, accessible routes, and in accessible rooms and spaces
<br />shall be provided a clear floor or ground space complying with 11B-305 Clear Floor or Ground Space
<br />and be placed within one or more of the reach ranges specified in 11B-308 Reach Ranges. §
<br />11B-309.2
<br />31. Operable parts shall be operable with one hand and shall not require tight grasping, pinching, or
<br />twisting of the wrist. Force required to activate operable parts shall be 5 pounds maximum. §
<br />11B-309.4
<br />32. Not Used.
<br />33. Elements that are exempt from all requirements for operable parts requirements include electrical
<br />or communication receptacles serving a dedicated use; floor electrical receptacles; HVAC diffusers,
<br />exercise machines and exercise equipment and those operable parts intended for use only by service
<br />or maintenance personnel. §11B-205.1
<br />34. Except for light switches, where redundant controls are provided for a single element, one control
<br />in each space shall not be required to comply with Section 11B-309 Operable Parts. §11B-205.1
<br />DIVISION OPERABLE PARTS
<br />1. Operable parts shall be placed within one or more of the reach ranges and the clear floor or ground
<br />space 30 inches by 48 inches minimum. [11B-309.2 and 11B-309.3]
<br />2. Operable parts shall be operable with one hand and shall not require tight grasping, pinching, or
<br />twisting of the wrist. The force required to activate operable parts shall be 5 pounds maximum,
<br />except gas pump nozzles. [11B-309.4]
<br />DIVISION 4 - ACCESSIBLE ROUTES
<br />DOORS, DOORWAYS, AND GATES
<br />1. There shall be no projections into the required clear opening width lower than 34" above the finish
<br />floor or ground. Projections into the clear opening width between 34" and 80" above the finish floor or
<br />ground shall not exceed 4". §11B-404.2.3
<br />2. Not used.
<br />3. Handles, pulls, latches, locks, and other operable parts on doors and gates shall comply with
<br />11B-309.4 Operation. Operable parts of such hardware shall be 34 inches minimum and 44 inches
<br />maximum above the finish floor or ground. Where sliding doors are in the fully open position,
<br />operating hardware shall be
<br />exposed and usable from both sides. §11B-404.2.7
<br />4. Door and gate closing speed shall comply with the following:
<br />a. Door closer and gate closer shall be adjusted so that from an open position of 90
<br />degrees, the time required to move the door to a position 12 degrees from the latch is 5
<br />seconds minimum. §11B-404.2.8.1
<br />b. Door and gate spring hinges shall be adjusted so that from the open position of 70
<br />degrees, the door or gate shall move to the closed position in 1.5 seconds minimum. §
<br />11B-404.2.8.2
<br />5. The force for pushing or pulling open a door or gate other than fire doors shall be as follows: §
<br />11B-404.2.9
<br />a. Interior hinged doors and gates: 5 pounds maximum.
<br />b. Sliding or folding doors: 5 pounds maximum.
<br />c. Required fire doors: the minimum opening force allowable by the appropriate
<br />administrative authority, not to exceed 15 pounds.
<br />d. Exterior hinged doors: 5 pounds maximum.
<br />6. Swinging door and gate surfaces within 10 inches of the finish floor or ground measured vertically
<br />shall have a smooth surface on the push side extending the full width of the door or gate. Parts
<br />creating horizontal or vertical joints in these surfaces shall be within 1/16 inch of the same plane as
<br />the other and be free of sharp or abrasive edges. Cavities created by added kick plates shall be
<br />capped. §11B-404.2.10
<br />7. Doors and side lights adjacent to doors and gates, containing one or more glazing panels that
<br />permit viewing through the panels shall have the bottom of at least one glazed panel located 43"
<br />maximum above the finish floor. §11B-404.2.11
<br />DIVISION 6 – PLUMBING ELEMENTS AND FACILITIES
<br />TOILET AND BATHING ROOMS
<br />1. Turning space shall be provided with the room and shall comply with Section 11B-304.
<br />[11B-603.2.1]
<br />2. Required clear floor spaces, clearance at fixtures, and turning space shall be permitted to overlap.
<br />[11B-603.2.2]
<br />3. Doors shall not swing into the clear floor space or clearance required for any fixture. Other than the
<br />door to the accessible water closet compartment, a door in any position may encroach into the
<br />turning space by 12 inches maximum. [ 11B-603.2.3]
<br />4. Mirrors located above lavatories or countertops shall be installed with the bottom edge of the
<br />reflecting surface 40 inches maximum above the finish floor or ground. Mirrors not located above
<br />lavatories or countertops shall be installed with the bottom edge of the reflecting surface 35 inches
<br />maximum above the finish floor or ground. [11B-603.3]
<br />5. Coat hooks shall be located within one of the reach ranges specified in Section 11B-308. Shelves
<br />shall be located 40 inches minimum and 48 inches maximum above the finish floor. Medicine
<br />cabinets shall be located with a usable shelf no higher than 44 inches maximum above the finish
<br />floor. [11B-603.4]
<br />WATER CLOSETS AND TOILET COMPARTMENTS
<br />1. The water closet shall be positioned with a wall or partition to the rear and to one side. The
<br />centerline of the water closet shall be 17 inches minimum to 18 inches maximum from the side wall or
<br />partition, except that water closet shall be 17 inches minimum and 19 inches maximum from the side
<br />wall or partition in the ambulatory accessible toilet compartment specified in Section 11B-604.8.2.
<br />Water closets shall be arranged for a left-hand or right-hand approach. [11B-604.2]
<br />2. Clearance around a water closet shall be 60 inches minimum measured perpendicular from the
<br />side wall and 56 inches minimum measured perpendicular front he rear wall. A minimum 60 inches
<br />wide and 48 inches deep maneuvering space shall be provided in front of the water closet.
<br />[11B-604.3.1]
<br />3. The required clearance around the water closet shall be permitted to overlap the water closet,
<br />associated grab bars, dispensers, sanitary napkin disposal units, coat hooks, shelves, accessible
<br />routes, clear floor space and clearances required at other fixtures, and the turning space. No other
<br />fixtures or obstructions shall be located within the required water closet clearance. [11B-604.3.2]
<br />4. The seat height of a water closet above the finish floor shall be 17 inches minimum and 19 inches
<br />maximum measured to the top of the seat. Seats shall not be sprung to return to a lifted position.
<br />Seats shall be 2 inches high maximum. [11B-604.4]
<br />5. Grab bars shall be provided on the side wall closet to the water closet and on the rear wall.
<br />[11B-604.5]
<br />6. The side wall grab bar shall be 42 inches long minimum, located 12 inches maximum from the rear
<br />wall and extending 54 inches minimum from the rear wall with the front end positioned 24 inches
<br />minimum in front of the water closet. [11B-604.5.1]
<br />7. The rear wall grab bar shall be 36 inches long minimum and extend from the centerline of the water
<br />closet 112 inches minimum on one side and 24 inches minimum on the other side. [11B-604.5.2]
<br />8. Toilet paper dispenser shall comply with Section 11B-309.4 and shall be 7 inches minimum and 9
<br />inches maximum in front of the water closet measured to the centerline of the dispenser. The outlet
<br />of the dispenser shall be below the grab bar, 19 inches minimum above the finish floor and shall not
<br />be located behind grab bars.
<br />9. Wheelchair accessible compartments shall be 60 inches wide minimum measured perpendicular to
<br />the side wall, and 56 inches deep minimum for wall hung water closets and 59 inches deep minimum
<br />for floor mounted water closets measured perpendicular to the rear wall. [11B-604.8.1.1]
<br />10. In a wheelchair accessible compartment with an end-opening door, either in-swinging or out-
<br />swinging, a minimum 60 inches wide and 48 inches deep maneuvering space shall be provided in
<br />front of the water closet. [11B-604.8.1.1.3]
<br />11. Doors shall be located in the front partition or in the side wall or partition farthest from the water
<br />closet. Where located in the front partition, the door opening shall be 4 inches maximum from the side
<br />wall or partition farthest from the water closet. Where located in the side wall or partition, the door
<br />opening shall be 4 inches maximum from the front partition. The door shall be self-closing. Doors
<br />shall not swing into the clear floor space or clearance required for any fixture.
<br />12. A side-wall grab bar complying with Section 11B-604.5.1 shall be provided and shall be located
<br />on the wall closet to the water closet. In addition, a rear-wall grab bar shall be provided.
<br />[11B-604.8.1.5]
<br />13. Coat hooks shall be located within one of the reach ranges specified in Section 11B-308. Shelves
<br />shall be located 40 inches minimum and 48 inches maximum above the finish floor. [11B-604.8.3]
<br />URINALS
<br />1. Urinals shall be the stall-type or the wall-hung type with the rim 17 inches maximum above the
<br />finish floor or ground. Urinals shall be 13½ inches deep minimum measured from the outer-face of
<br />the urinal rim to the back of the fixture. [11B-605.2]
<br />2. A clear floor or ground space complying with Section 11B-305 positioned for forward approach
<br />shall be provide. [11B-605.3]
<br />LAVATORIES AND SINKS
<br />1. A clear floor space complying with Section 11B-305, positioned for a forward approach, and knee
<br />and toe clearance complying with Section 11B-306 shall be provided. [11B-606.2]
<br />2. A parallel approach complying with Section 11B-305 shall be permitted to a kitchen sink in a space
<br />where a cook top or conventional range is not provided and to wet bars. [11B-606.2 Exception 1]
<br />3. Lavatories and sinks shall be installed with the front of the higher of the rim or counter surface 34
<br />inches maximum above the finish floor or ground. [11B-606.3]
<br />4. Controls of faucets shall comply with Section 11B-309.
<br />5. Water supply and drain pipes under lavatories and sinks shall be insulated or otherwise configured
<br />to protect against contact. There shall be no sharp or abrasive surfaces under lavatories and sinks.
<br />[11B-606.5]
<br />6. Lavatories, when located adjacent to a side wall or partition, shall be a minimum of 18 inches to the
<br />centerline of the fixture. [11B-606.6]
<br />7. Sinks shall be 6½ inches deep maximum. [11B-606.7] Knee clearance at lavatories shall comply
<br />with 11B-306.3.
<br />#10 GA EXPANDED
<br />MESH MATCH
<br />EXISTING
<br />STRUCTURE
<br />PLASTER
<br />L 1 1/4" X 3/4" X 1/8"
<br />3/4" X 3/4" X1/16"
<br />CHANNEL WIRE
<br />TIED TO MET LATH
<br />2X BLOCKING @
<br />2'-0" O.C. WHERE
<br />RAFTERS ARE
<br />PARALLEL TO
<br />HEAD
<br />2 1/4
<br />"
<br />2 1/4
<br />"
<br />5"
<br />5"
<br />1'
<br />-
<br />4"
<br />
<br />2"
<br />1/4" STEEL TYPICAL
<br />1 1/2"
<br />1 1/2"
<br />1/4" HOLES FOR SCREEN FRAME
<br />9/16 Ø HOLE FOR 1/2" Ø
<br />ANCHOR BOLT TYP.
<br />9/16 Ø HOLE FOR 1/2" Ø
<br />ANCHOR BOLT TYP.
<br />5"
<br />
<br />
<br />2 1/4"
<br />10
<br />"
<br />
<br />
<br />2 1/2"
<br />1 1/2"1/4" HOLES FOR
<br />SCREEN FRAME
<br />9/16 Ø HOLE FOR 1/2" Ø
<br />ANCHOR BOLT TYP.
<br />L 1/4" X 3/4" X 1/8"
<br />STEEL BEAM &
<br />POST
<br />2"
<br />2 1/4"
<br />#10 GA EXPANDED
<br />MESH MATCH
<br />EXISTING
<br />A5.0
<br />4
<br />#10 GA EXPANDED
<br />MESH MATCH
<br />EXISTING
<br />8" CMU WALL
<br />6"X 2" X 1/4"
<br />CHANNEL
<br />L 1 1/4"X 3/4" X 1/8"
<br />STEEL BEAM &
<br />POST A5.0
<br />4
<br />DOOR
<br />INTERIOREXTERIOR
<br />FLOORING PER
<br />SCHEDULECONCRETE
<br />
<br />
<br />1
<br />/
<br />4
<br />"
<br />10
<br />"
<br />
<br />A
<br />L
<br />U
<br />M
<br />I
<br />N
<br />U
<br />M
<br />
<br />K
<br />I
<br />C
<br />K
<br />
<br />P
<br />L
<br />A
<br />T
<br />E
<br />
<br />T
<br />Y
<br />P
<br />.
<br />PS-25-2401
<br />CITY OF SANTA ANA
<br />PUBLIC WORKS AGENCY
<br />REVISIONS REFERENCES
<br />CONSTRUCTION COMPLETED:
<br />BENCHMARK NO.: SA-253-70 ELEV.: 176.00 (2010)
<br />PREPARED UNDER THE
<br />SUPERVISION OF:
<br />SHEET OF
<br />1511 Cota Ave. Long Beach,
<br />CA 90813 Tel. 562-912-7900
<br />Architecture
<br />Government Services
<br />Edward
<br />Lok Ng
<br />C-16840
<br />REN.11/30/25
<br />LICENSED A RCHITECT
<br />STATE OF C ALIFORNIA
<br />DRAWNDESIGNED:CHECKED:
<br />UNDERGROUND SERVICE ALERT OF SOUTHERN CALIFORNIA
<br />811
<br />ATTENTION IS DIRECTED TO THE POSSIBLE EXISTENCE OF
<br />UNDERGROUND FACILITIES NOT KNOWN OR IN A LOCATION
<br />DIFFERENT FROM THAT WHICH IS SHOWN ON THE PLANS OR IN
<br />THE SPECIAL PROVISIONS. THE CONTRACTOR SHALL TAKE
<br />STEPS TO ASCERTAIN THE EXACT LOCATION OF ALL
<br />UNDERGROUND FACILITIES PRIOR TO DOING WORK THAT MAY
<br />DAMAGE SUCH FACILITIES OR INTERFERE WITH THEIR SERVICE
<br />BEFORE EXCAVATING. THE CONTRACTOR SHALL VERIFY THE
<br />LOCATION OF UNDERGROUND UTILITIES BY CONTRACTING
<br />UNDERGROUND SERVICES ALERT. DIAL 811
<br />LOK NG:
<br />REVIEWED FOR
<br />CONSTRUCTABLITY:
<br />RECOMMENDED FOR
<br />CONSTRUCTION:
<br />ARCHITECT
<br />INSTALLED
<br />1700 E. SANTA CLARA AVENUE, SANTA ANA, CA 92705
<br />FILE NO:
<br />PRINCIPAL CIVIL ENGINEER RCE NO.:
<br />PRINCIPAL CIVIL ENGINEER RCE NO.:G:
<br />\
<br />P
<br />r
<br />o
<br />j
<br />e
<br />c
<br />t
<br />
<br />F
<br />i
<br />l
<br />e
<br />s
<br />\
<br />3
<br />1
<br />3
<br />9
<br />
<br />S
<br />a
<br />n
<br />t
<br />a
<br />
<br />A
<br />n
<br />a
<br />
<br />P
<br />o
<br />r
<br />t
<br />o
<br />l
<br />a
<br />
<br />P
<br />a
<br />r
<br />k
<br />
<br />R
<br />e
<br />s
<br />t
<br />o
<br />o
<br />m
<br />R
<br />e
<br />n
<br />o
<br />v
<br />
<br />&
<br />
<br />A
<br />d
<br />d
<br />
<br />f
<br />o
<br />r
<br />
<br />D
<br />V
<br />D
<br />\
<br />0
<br />1
<br />-
<br />D
<br />r
<br />a
<br />w
<br />i
<br />n
<br />g
<br />s
<br />\
<br />0
<br />1
<br />-
<br />R
<br />e
<br />v
<br />i
<br />t
<br />\
<br />3
<br />-
<br />C
<br />D
<br />\
<br />3
<br />1
<br />3
<br />9
<br />S
<br />a
<br />n
<br />t
<br />a
<br />
<br />A
<br />n
<br />a
<br />
<br />P
<br />o
<br />r
<br />t
<br />o
<br />l
<br />a
<br />
<br />P
<br />a
<br />r
<br />k
<br />
<br />R
<br />e
<br />s
<br />t
<br />r
<br />o
<br />o
<br />m
<br />
<br />R
<br />e
<br />n
<br />o
<br />
<br />&
<br />
<br />A
<br />d
<br />d
<br />
<br />C
<br />D
<br />.
<br />r
<br />v
<br />t
<br />A5.0
<br />PORTOLA PARK
<br />SPLASH PAD
<br />ACCESSIBLE DETAILS
<br />JSAF LN
<br />PO
<br />R
<br />T
<br />O
<br />L
<br />A
<br />
<br />P
<br />A
<br />R
<br />K
<br />
<br />S
<br />P
<br />L
<br />A
<br />S
<br />H
<br />
<br />P
<br />A
<br />D
<br />
<br />P
<br />R
<br />O
<br />J
<br />E
<br />C
<br />T
<br />
<br />N
<br />O
<br />.
<br />
<br />2
<br />5
<br />-24
<br />0
<br />1
<br />GENERAL ACCESSIBILITY.
<br />1HEAD METAL SCREEN
<br />4JAMB AT SCREEN ISO
<br />3JAMB METAL SCREEN
<br />2SILL METAL SCREEN
<br />5THRESHOLD
<br />NUMBER DATE INITALS DESCRIPTION APPROVED
<br />SHEET 34 OF 57
|