Text:
Floor pressure loads are at each base plate under vertical columns and distributed evenly to the floor pads per page 4 (2600 lbs per plate) Horizontal loads are at 2nd floor and distributed evenly tot he horizontal braces per page 1 (750 lbs per braces)
Line
ID:
1
Creator:
Import Agent
Created:
5/8/2026 5:00 AM
Modified:
5/7/2026 5:31 PM
ID:
2
Creator:
Import Agent
Created:
5/8/2026 5:00 AM
Modified:
5/7/2026 5:31 PM
Document management portal powered by Laserfiche WebLink 9 © 1998-2015
Laserfiche.
All rights reserved.
/
31
PDF
Print
Pages to print
Enter page numbers and/or page ranges separated by commas. For example, 1,3,5-12.
After downloading, print the document using a PDF reader (e.g. Adobe Reader).
Show annotations
View images
View plain text
PURPOSE OF THIS DRAWING <br />THE PURPOSE OF THIS DRAWING IS TO PROVIDE NECESSARY INFORMATION ABOUT THE EQUIPMENT SO THAT THE ARCHITECT OR INSTALLER CAN <br />MAKE A FINAL CONSTRUCTION DRAWING FOR THE SPECIFIC JOB SITE. <br /> <br />INSTALLATION DETAILS SUCH AS CONCRETE THICKNESS, REINFORCING, PIPING DIRECTION, CONDUIT SIZE, POWER UNIT LOCATION, ADJACENT <br />STRUCTURES, ETC CANNOT ECONOMICALLY BE INCORPORATED IN THE MANUFACTURER'S DRAWINGS. <br /> APPROVAL DRAWING <br /> APPROVAL OF THIS DRAWING IS AN APPROVAL OF THE EQUIPMENT ONLY. ANY REQUIRED CHANGES SHOULD ONLY INCLUDE ITEMS PERTINENT TO THE EQUIPMENT ITSELF. <br />PLEASE CHECK AND RETURN ONE SIGNED COPY IMMEDIATELY. THE FINAL DESIGN WILL NOT PROCEED UNTIL APPROVAL DRAWING IS RECEIVED BY AUTOQUIP. <br /> APPROVED WITH NO CHANGES REVISE AND RESUBMIT <br />FIRM________________________________________ <br /> BY__________________________________ DATE_________________ <br />NOTES: <br />ALL AXLES, ROLLERS, AND PIVOT POINTS ARE EQUIPPED WITH LIFE TIME LUBRICATED BEARINGS.1. <br />ELECTRICAL DISCONNECT: BY OTHERS2. <br />GATES, ENCLOSURES AND INTERLOCKS ARE REQUIRED.WHEN GATES, ENCLOSURES OR INTERLOCKS ARE SUPPLIED BY 3.OTHERS. IT IS THE RESPONSIBILITY OF THE BUYER OF THE VRC TO BE COMPLIANT WITH REQUIREMENTS SET FORTH IN ASME B20.1 <br />(2) SOLENOID INTERLOCK KITS FOR CUSTOMER SUPPLIED BI-PARTING SWING DOORS, SHIPPED LOOSE.4. <br />(2) GREEN LIFT PRESENT LIGHTS, SHIPPED LOOSE.5. <br />LIFT TO MEET CODES FOR THE STATE OF CALIFORNIA, TO INCLUDE:6.UL LISTED MOTOR CONTROL PANEL•"LIFT OPERATING INSTRUCTIONS" SIGNAGE• <br />0 <br />0 <br />ADDITIONAL SPECIFICATIONS <br />LIFT INFORMATION <br />MODEL:FMS-168-0030 <br />FINISH:POLYURETHANE PAINT - AQ BLUE, RAL 5000 (VIOLET BLUE) <br />CAPACITY:3,000 LBS MAX LIFTINGEDGE LOAD:1,950 LBSPLATFORM SURFACE:SMOOTH STEELFLOOR PRESSURE:5,200 PSFBRACE REACTION:1,500 LBS <br />LIFT COMPONENTS NEMA:MEETS OR EXCEEDS NEMA 1 <br />POWER UNIT INFORMATION <br />TYPE:ELECTRO-MECHANICAL <br />HP:7.5 HP <br />CURRENT:11 AMPS <br />NEMA:MEETS OR EXCEEDS NEMA 1RAISE SPEED:30 FPMLOWER SPEED:30 FPM <br />VOLTAGES <br />PRIMARY:460 VAC / 3 PH / 60 HZ <br />CONTROL:24 VDC <br />CONTROL PANEL INFORMATION <br />CONTROL TYPE:PRESS AND RELEASELOCATION:SHIPPED LOOSENEMA:MEETS OR EXCEEDS NEMA 4 <br />CONTROL SIGNAL INFORMATION <br />TYPE / QTY:(2) MOUNTABLE PUSHBUTTONOPERATORS:UP/DOWN/ESTOP (ILLUMINATED)WIRED TO:SHIPPED LOOSENEMA:MEETS OR EXCEEDS NEMA 12 <br />JOB NAME: <br />DRAWN BY:DATE:REV.SIZE: <br />DRAWING TITLE: <br />DRAWING NUMBER:PAGE: <br />REFERENCE DRAWING: <br />APPROXIMATE WEIGHT: <br />5 OF 5 <br />9FMS-89603-1 5 OF 5 <br />12/01/256,250 LBS RMS <br />IRVINE, CA - COLLECTORST O L E R A N C E S <br /> ALL DIMENSIONS ARE IN INCHES <br />0SLK <br />CHECKED: <br />UNLESS OTHERWISE SPECIFIED: <br />FRACTIONS: +/- 1/4 9FMS-89603-1B <br />APPROVAL DRAWING© COPYRIGHT AUTOQUIP <br /> ALL RIGHTS RESERVED. <br /> Year of copyright is first yearindicated on this document. <br />ASME B20.1 CODE COMPLIANCE <br />THE FREIGHTLIFT IS A VERTICAL RECIPROCATING CONVEYOR GOVERNED BY ASME B20.1 TO BE USED FOR THE MOVEMENT OF MATERIAL <br />ONLY - NO RIDERS! GATES, INTERLOCKS AND SAFETY ENCLOSURES ARE MANDATORY PER ASME AND OSHA. INSTALLATION INSTRUCTIONS IN <br />THE OWNERS MANUAL INCLUDE IMPORTANT INFORMATION SUCH AS ASSEMBLY HARDWARE REQUIREMENTS, TORQUE SPECS, HYDRAULIC AND <br />ELECTRICAL CONNECTIONS, WARNING SIGNS AND DECALS. THESE MUST BE FOLLOWED TO ASSURE PROPER PERFORMANCE OF THE LIFT. IN <br />ORDER TO ASSURE THAT THE INSTALLATION IS IN ACCORDANCE WITH ASME B20.1, ALL DETAILS OF THIS DRAWING AND THE INSTALLATION <br />INSTRUCTIONS IN THE OWNERS MANUAL MUST BE MET AND VERIFIED AFTER INSTALLATION BY SIGNING AND RETURNING THE WARRANT <br />REGISTRATION FORM TO AUTOQUIP. <br />STATE, LOCAL & IBC CODE COMPLIANCES <br />AUTOQUIP VERTICAL RECIPROCATING CONVEYORS (VRCs) MEET ALL DESIGN AND SAFETY REQUIREMENTS SET <br />FORTH IN ASME B20.1. AUTOQUIP GUARANTEES ASSISTANCE IN SECURING CODE COMPLIANCE IN ALL 50 <br />STATES. ULTIMATE RESPONSIBILITY FOR GAINING STATE AND LOCAL CODE APPROVAL IS THE RESPONSIBILITY <br />OF THE BUYER OF THE VRC. PLEASE ACQUAINT YOURSELF WITH THE PERMITTING AND/OR LICENSING EXPENSES <br />AND REQUIREMENTS OF THE LOCAL REGULATORY AGENCIES IN THE INSTALLATION AREA. <br /> <br />ADOPTION OF THE INTERNATIONAL BUILDING CODE (IBC) BY MANY STATE AND LOCAL BUILDING OFFICIALS <br />HAS INCLUDED - BY REFERENCE IN CHAPTER 30 OF THE IBC - THE RECOGNITION OF VRC's AND THEIR <br />JURISDICTION UNDER ASME B20.1. BE AWARE THAT SPECIAL PERMITTING AND TESTING OF YOUR VRC MAY BE <br />REQUIRED BY STATE OR LOCAL BUILDING CODE OFFICIALS TO PROVIDE BUILDING INSPECTORS A MEANS TO <br />VERIFY THE COMPLIANCE OF THE EQUIPMENT WITH THE GENERAL SAFETY REQUIREMENTS SET FORTH IN ASME <br />B20.1. IT IS ULTIMATELY THE RESPONSIBILITY OF THE CUSTOMER TO VERIFY THE NEED FOR, AND ASSUME THE <br />ADDED COSTS OF, ANY SUCH SPECIAL PERMITTING AND/OR TESTING. <br />SITE REQUIREMENTS <br />UPPER AND LOWER PUSH-BUTTON CONTROLS <br />MUST BE INSTALLED OR LOCATED SO THEY <br />CANNOT BE ACTUATED BY A PERSON ON THE LIFT <br />CARRIAGE. <br /> <br />FIRST LEVEL FLOOR MUST SUPPORT MAST FOOT <br />PRESSURES AS INDICATED. MOUNTING HOLES <br />PROVIDED ARE 11/16" DIA. ANCHORS WITH 750 <br />LBS. MIN PULL OUT STRENGTH, EACH BOLT. <br />SECOND LEVEL FLOOR MUST SUPPORT REACTION <br />LOAD AS INDICATED. HOLES IN EACH BRACE <br />PLATE ARE 9/16" DIA. LAG BOLTS AND ANCHORS <br />ARE BY OTHERS. <br />ORDER NUMBER: <br />174348