Laserfiche WebLink
M-000 <br />MECHANICAL SPECIFICATIONS <br />MECHANICAL SPECIFICATIONS <br />Section 200500 - General Requirements <br />A. General <br />1. Specifications are applicable to all contractors and/or subcontractors for all mechanical systems in <br />Divisions 01, 20, 21, 22, and 23. <br />2. This contractor is also referred to the architectural, structural, electrical and all other drawings and <br />specifications pertinent to this project and fully coordinate with all other trades, owner and architect <br />requirements. All of the above mentioned drawings and specifications are considered a part of the <br />contract documents. <br />3. Conform to all Instructions to Bidders, general and special conditions of contract as specified by <br />architect and/or owner. <br />4. Refer to “Alternate Proposals” for possible changes affecting the extent of this section of work. <br />5. Before submitting a bid, each contractor is requested to visit the job site to familiarize themselves with <br />construction condition, check facilities and conditions and make all necessary observations and <br />measurements. Note conditions under which work is to be performed and take all items into <br />consideration in bid. No consideration will be given for his failure to do so. <br />6. Systems are to be complete and workable in all respects, placed in operation and properly adjusted. <br />7. Each contractor shall provide for his own clean-up, removal and legal disposal of all rubbish daily. <br />8. Each contractor shall protect his work, his existing and adjacent property against weather. <br />9. Each contractor shall protect his work, materials, apparatus and fixtures from damage. Any work <br />damaged by failure to provide protection required, shall be removed and replaced with new material at <br />the contractor's expense. <br />10. Each contractor must confirm all utility company requirements and connection points in field, prior to <br />starting work. Each contractor shall include cost of utility companies work in their bid. <br />11. Each contractor must confirm size, location and materials at point of tie in connections in the field prior <br />to rough-in of new work. <br />12. Arrange for and obtain owner's and insurance representative's permission for any service shutdowns. <br />13. Each contractor shall be solely responsible for construction means, methods, sequences of <br />construction and the safety of workmen. <br />14. No piping, ductwork, wiring, etc., shall be installed or routed above or below electrical panels and <br />equipment, through elevator equipment rooms or elevator shafts or stairways unless these items serve <br />these areas only. <br />15. All contractors shall coordinate with the electrical contractor and obtain a written approval identifying <br />the electrical characteristics of all mechanical equipment prior to ordering of equipment. No additional <br />payment will be made for lack of contractor coordination of electrical characteristics. <br />16. Each contractor shall include modifying existing conditions to complete the project. During <br />construction the contractors may uncover an existing condition that will have to be modified. Any such <br />work which comes under the jurisdiction of this contractor shall be done by this contractor without extra <br />cost to the owner and project. <br />17. Work related to the existing building shall be coordinated to minimize interference or interruption of <br />normal building use by the owner. Refer to architectural plans for phasing requirements. <br />18. Ceiling grid systems shall not be supported from ductwork, heating or plumbing lines or any other <br />utility lines, and vice versa. Each utility and the ceiling grid system shall be a separate installation and <br />each shall be independently supported from the building structure - concrete, steel or masonry. <br />Where interferences occur, in order to support ductwork, piping, ceiling grid systems, etc., trapeze <br />type hangers or supports shall be employed which shall be located so as not to interfere with access <br />to such mechanical equipment as valves, regulators, mixing boxes, fire dampers, etc. <br />B. Work Coordination and Scope <br />1. Each contractor under this division shall familiarize himself with the work to be done under other <br />divisions of this specification and their related drawings and shall so coordinate and schedule his work <br />as not to cause delays or interference with the work of others. Such coordination and scheduling shall <br />accomplish the installation of mechanical and plumbing equipment and piping with a minimum of <br />cutting through masonry and other adjustments. <br />2. Work included under this division shall consist of furnishing all materials, supplies, equipment, tools, <br />transportation and facilities and performing all labor and services necessary for the complete <br />installation of the mechanical systems of plumbing, fire protection, heating, ventilating, air conditioning, <br />and specialty systems. <br />3. The contractor under this division shall report discrepancies in the work of others which affect his work. <br />Any changes made necessary by failure or neglect to report such discrepancies shall be made by and <br />at the expense of the contractor of this division. Obtain written instructions for changes necessary to <br />accommodate work of others. <br />4. The contractor under this division shall be responsible for proper size and location of anchors, chases, <br />recesses, opening, etc., required for the proper installation of his work. <br />5. The division of responsibility under separate mechanical, fire protection and plumbing contracts for <br />tie-in points shall be as follows: <br />a.The plumbing contractor shall provide domestic water and gas to within five feet (5'-0”) of <br />equipment connection furnished by the mechanical or electrical contractor, final connection by <br />mechanical or electrical contractor. On the water lines, the plumbing contractor shall provide the <br />shut-off valve, check valve, backflow preventor and pressure regulator. On the gas lines, the <br />plumbing contractor shall provide the shut-off valve and pressure regulator. <br />b. Plumbing contractor shall run the gas, water and sanitary to 5'-0” outside the building or to points <br />as noted on the drawings. <br />c. Fire protection, plumbing and mechanical contractor shall provide sleeves to the general <br />contractor for placement in floors, walls, etc. and coordinate such location. The plumbing <br />contractor shall be responsible for flashing at vent roof terminals. <br />d. The fire protection, plumbing and mechanical contractor shall check with the architectural <br />drawings concerning the test borings to determine areas of rock which should be included in his <br />excavation work. Failure to adjust for rock conditions shall not warrant cause for additional <br />compensation. <br />e. The plumbing contractor shall rough-in and connect all other fixtures and equipment where shown <br />on the drawings but not previously mentioned. Provide with shut-off valves and p-traps with <br />clean-out plug. <br />f. All motors 1/3 HP and smaller shall be single phase motors, 1/2 HP and larger, shall be three <br />phase motors except where otherwise specified. Thermal overload protection for all motors shall <br />be provided. Combination fused disconnect and magnetic line starters with auto-off-test switch <br />shall be provided for all three-phase motors. Thermal overload relays shall be sized for 115 <br />percent of full load motor current. For motors with VFD; motors shall be inverter duty motors that <br />meets current “MG 1 Part 31” specifications. Motors to have a minimum of 20:1 turn down ratio. <br />Motors over 20 Hp shall have shaft ground rings. The installation of all motors, starters and other <br />electrical work under this mechanical division shall be done so as to conform with the National <br />Electric Code. Each motor shall be of squirrel cage type, open-drip proof, normal starting torque, <br />having ball bearings unless otherwise specified. For manufacturers that use PMAC motors, this <br />contractor shall supply VFD's to operate motor. <br />6. Each contractor shall provide OSHA approved handrail (Guard) system for all roof mounted equipment <br />within 10'- 0” of roof edge where the roof edge does not have a 42” high parapet or higher. <br />C. Codes, Permits, Standards and Regulations <br />1. Contractors shall install work in full accordance with rules and regulations of all applicable codes (local, <br />city, county, state, national codes, NFPA, OSHA, etc.), government regulations, utility company <br />requirements, and applicable standards having jurisdiction over premises. This shall include safety <br />requirements of the state department. Do not construe this as relieving contractor from compliance <br />with any requirements of specifications which are in excess of code requirements and not in conflict <br />therewith. <br />2. Contractors shall secure and pay for all fees, permits, and certificates of inspection incidental to this <br />work required by foregoing authorities. Arrange for all required inspections and approvals. <br />3. Contractor shall be responsible for payments to all public utilities for work performed by them in <br />connection with provision of service connections required under this division of specifications. <br />4. Deliver all permits and certificates to architect in duplicate. <br />D. Design Drawings <br />1. The design drawings, as submitted, are diagrammatic and are not intended to show exact location of <br />equipment, piping and ductwork unless dimensions are given. Piping and ductwork are to be installed <br />along the general plans shown on the drawings while conforming to actual building conditions. Each <br />contractor shall confirm all dimensions by field measurement. <br />2. Before entering into a contract, the successful bidder may be required to submit satisfactory evidence <br />to show that the manufacturer of all parts of the equipment offered have been regularly engaged in the <br />manufacture of such equipment for three (3) years and have not less than three (3) installations of a <br />similar type which have been in successful operation under conditions similar to those specified for not <br />less than two (2) years. <br />3. All equipment, piping and material specified herein after as shown on the drawings shall be furnished <br />and installed by the contractor, unless specifically indicated to the contrary. Installation shall comply <br />with all required “Building Codes” and “Reference Standards.” <br />4. If this contractor proposes to install equipment requiring space conditions other than those as specified <br />and/or shown on the design drawings, or to rearrange the equipment, he shall assume full <br />responsibility and submit drawings for the rearrangement of the space and shall obtain the full <br />approval of the architect prior to start of any work. <br />5. The exact locations for fixtures, equipment and piping which is not covered by drawings shall be <br />obtained from the architect or his representative in the field and the work shall be laid out accordingly.The design drawings, as <br />submitted, are diagrammatic and are not intended to show exact location of <br />equipment, piping and ductwork unless dimensions are given. Piping and ductwork are to be installed <br />along the general plans shown on the drawings while conforming to actual building conditions. Each <br />contractor shall confirm all dimensions by field measurement. <br />Section 200500 (cont.) <br />6. Drawings and specifications are intended to supplement one another. Any materials or labor called for <br />in one but not the other shall be furnished as if both were mentioned in the specifications and shown <br />on the drawings. <br />E. Base Bid Equipment, Materials and Substitutions <br />1. All equipment and materials shall be new, free of defects and UL labeled. <br />2. Base bid manufacturers are included in the specification or listed in schedules on the drawings. All <br />other manufacturers are considered substitution. <br />3. The name or make of any article, device, material, form of construction, fixture, etc., stated in this <br />specification, whether or not the words "or approved equal" are used, shall be known as a "standard". <br />4. All cost shall be based on "standards" specified. <br />5. The equipment schedules on the drawings indicate manufacturer and their equipment model numbers <br />that this design has been based on. Each contractor is required to bid upon the basis of design and <br />furnish the makes specified. <br />6. Where more than one make or name is mentioned as being acceptable, it shall be understood that <br />only the name or make referring to the manufacturers model numbers or sizes shall be considered the <br />“Specified Standards.” It shall be further understood that other makes and names, even though <br />mentioned, have not been checked for detail and that their size and arrangement are the contractor's <br />responsibility the same as a proposed substitute item. The use of other manufacturer's equipment that <br />is listed as acceptable alternates that entails general trades, structural, mechanical, electrical, etc., <br />revisions is this contractor's responsibility to provide revisions. Any additional cost of such changes <br />shall be paid by the contractor submitting the acceptable alternates which necessitates changes in <br />installing such submitted alternate equipment, even though such costs may be part of another division <br />of work. <br />7. Bids concerning the use of substitute products must be accompanied by complete specifications and <br />performance characteristic covering these products. Contractor shall provide all available test data and <br />experience records which may be helpful to the architect in evaluating the quality and/or suitability of <br />alternate products. <br />8. Contractor is also invited to bid on any other similar products the contractor desires to propose as <br />substitutions, stating any difference in cost (add or deduct from base bid cost) for each proposed <br />substitution on the substitution sheet. If the architect decides to accept any of the proposed <br />substitutions, proper notations thereof shall be made in the written contract. Where several makes are <br />mentioned in the specifications and the contractor fails to state that he prefers a particular make in his <br />bid, the owner shall have the right to choose any of the makes mentioned without change in price. No <br />consideration will be given to proposals for alternative products unless submitted with the original bids. <br />9. Substitutions are subject to the approval of the owner. If a substitution is submitted, it is the <br />contractor's responsibility to evaluate it and certify that the substitution is equivalent in all respects to <br />the base specifications. <br />10. If substitutions are approved, notify all other contractors, subcontractors, etc., affected by the <br />substitution and fully coordinate with them. Any costs resulting from substitution, whether by this <br />contractor or others, shall be the responsibility of and paid for by the substituting contractor. Approved <br />shop drawings do not absolve this contractor from this responsibility. <br />11. All equipment shall be installed in full accordance with the manufacturer's data and installation <br />instructions and service clearances. It is this contractor's responsibility to check and confirm these <br />requirements prior to starting of any work. <br />F. Warranty <br />1. Fully warrant all materials, equipment and workmanship and the successful operation of all equipment <br />and apparatus installed by this contractor for one (1) year from date of final acceptance. <br />2. Extend all manufacturers' warranties to owner; including five (5) year compressor and ten (10) year <br />heat exchanger extended warranty on HVAC equipment to include material and labor. <br />3. Repair or replace without material and labor charge to the owner all items found defective during the <br />warranty periods. In the case of replacement or repair due to failure within the warranty period, the <br />warranty on that portion of the work shall be extended for a minimum period of one (1) year from the <br />date of such replacement or repair. <br />G. Shop Drawing Submittals <br />1. Submit shop drawings for mechanical, plumbing, fire protection, and control systems; including but not <br />limited to sheetmetal, plumbing fixtures and equipment with adequate details and scales to clearly <br />show construction. Indicate the operating characteristics for each required item. Clearly identify each <br />item on the submittal as to mark, location and use, using the same identification as provided on the <br />construction documents. <br />2. Sheet metal and fire protection shop drawings shall be fully dimensioned and coordinated based on <br />field verified building dimensions and clearances and architectural ceiling layouts. Indicate structural <br />systems, lighting, ductwork and piping at all critical locations. <br />3. Contractor shall review and indicate his approval of each shop drawing prior to submittal for review. <br />Shop drawings will not be reviewed by the engineer unless the contractor's approval is noted. Do not <br />start work or fabrication until shop drawings have been reviewed by the engineer and returned to the <br />contractor. <br />4. Submittals will be reviewed only for general compliance with the contract documents and not for <br />dimensions or quantities. The architect and engineer will make every effort to detect and correct <br />errors, omissions, and inaccuracies in such drawings, but the failure to detect errors, omissions, and <br />inaccuracies shall not relieve the contractor of responsibility for the proper and complete installation in <br />accordance with the intent of the contract documents. The submittal review shall not relieve the <br />contractor of responsibility for purchase of any item in full compliance with the contract documents or <br />its complete and proper installation. <br />5. Where submittals vary from the contract requirements, the contractor shall clearly indicate on submittal <br />or accompanying documents the nature and reason for the variations. <br />6. Each manufacturer or his representative must check the application of his equipment and certify at <br />time of shop drawing submittal that the equipment specified has been properly applied and can be <br />installed, serviced and maintained where indicated on the drawings. Advise engineer in writing with <br />submittal drawings of any potential problems. The manufacturer shall be responsible for any changes <br />that might be necessary because of physical characteristics of equipment that have not been called to <br />the engineer's attention at the time of submittal. <br />7. Submit a minimum of one (1) print and an electronic “pdf” of shop drawings to the architect. The <br />architect and engineer shall review and return a pdf. The contractor shall distribute copies as required <br />to properly conduct the work, including requirements of the operating manual. <br />H. Record Drawings <br />1. Each contractor or subcontractor shall keep one (1) complete set of the contract drawings and <br />equipment submittals on the job site on which he shall regularly record any deviations or changes from <br />such contract drawings made during construction. All recording shall be done in color ink. <br />2. These drawings shall record the installed location of all concealed equipment, piping, electric service, <br />sewers, wastes, vents, ducts, conduit, etc., by measure dimensions to each such item from column <br />centerlines or readily identifiable and accessible walls or corners of the building. Plans also shall show <br />invert elevation of sewers and top elevation of all other below-grade lines. <br />3. Record drawings shall be kept clean and undamaged and shall not be used for any purpose other than <br />recording deviations from working drawings and exact locations of concealed work. <br />4. After the project is completed, these drawings shall be scanned to an electronic “pdf” format and pdf <br />and hard drawings shall be delivered to the architect in good condition, as a permanent record of the <br />installation as actually constructed. <br />I. Supervision <br />1. The contractor shall have in charge of work at all times during construction a competent foreman or <br />superintendent whose experience and background shall qualify him for the work to be performed <br />under this division. Once assigned, the foreman or superintendent shall be retained until completion of <br />the project and any consideration as to his removal on grounds of incompetence shall either be <br />initiated by or referred to the architect for decision. <br />Section 200510 - Basic Materials and Methods <br />A. General <br />1. Provide all materials, labor, equipment, and accessories required to furnish and install the mechanical <br />items identified in this section. <br />2. This section includes basic mechanical materials and methods to complement other division sections <br />in this specification and requirements indicated on the mechanical drawings. <br />B. Interferences <br />1. Before installing any work, contractor shall see that it does not interfere with clearance required for <br />finish on beams, columns, pilasters, walls, or other structural or architectural members, as shown on <br />architectural drawings. If any work is so installed and it later develops that architectural design cannot <br />be followed, contractor shall, at his own expense, make such changes in his work as architect may <br />direct to permit completion of architectural work in accordance with plans and specifications. <br />2. Install additional offsets on piping or ductwork where required to obtain maximum headroom or to <br />avoid conflict with other work without additional cost to owner. <br />3. Report any interferences between work under this division and that of any other contractors to <br />architect as soon as they are discovered. Architect will determine which equipment shall be relocated, <br />regardless of which was first installed, and his decision shall be final. <br />Section 200510 (cont.) <br />C. Protection of Work and Property <br />1. The contractor shall be responsible for safeguarding work, property, and facilities against damage, <br />both his own as well as others with which he may come into contact in the performance of his work. <br />2. Stored materials shall be protected against damage from weather. Pipe, and duct openings shall be <br />closed with caps or plugs during installation. All fixtures and equipment shall be covered and protected <br />against damage. Any materials or equipment damaged at any stage in the construction shall be <br />replaced or repaired. Final completion, all work shall be in a clean and unblemished condition. <br />3. During construction, all return air ductwork and transfer air openings serving new and existing air <br />handling equipment and/or adjacent tenant spaces shall be protected. Openings which need to <br />remain active shall be covered and protected with MERV 8 filtration media; openings which can remain <br />inactive during construction shall be covered with plastic sheathing and sealed air tight. Filter media <br />shall be replaced regularly as required during construction in order to ensure adequate airflow through <br />all required active openings. In addition, at the end of each phase of construction and at the end of <br />the construction project, all filtration media within each piece of equipment serving the space shall be <br />replaced. <br />D. Excavation and Backfill <br />1. Perform all excavation and backfill required for installation of below-grade piping and ductwork. <br />2. Excavate as required to install piping at required depth and pitch. Pipe to be laid on sand bedding to <br />give uniform bearing along length of pipe (sand inside building and interlocking aggregate outside <br />building). <br />3. Backfill with bedding material to a minimum of 12” above top of pipe and compact. Balance of backfill <br />in outdoor grass areas shall be clean earth up to 6” above surrounding grades. Backfill below finished <br />floors shall be sand. Backfill outdoors under paving shall be interlocking aggregate and shall be <br />compacted in maximum 10” layers. <br />4. All other excavations shall be backfilled with clean earth, excluding rubbish and boulders. Backfill shall <br />be thoroughly tamped and puddled. <br />5. Patch floor and paving to match existing adjacent surfaces. <br />6. Backfilling shall not be done until pipe lines are properly tested in the presence of the architect and/or <br />inspection of the government agency having jurisdiction. <br />7. Control trench soil compaction during construction for compliance with the maximum density specified <br />for the following areas: <br />a. Building slabs, walkways, roadways, or public thorough-fares; compact top 12” of subgrade and <br />each layer of backfill for fill material at 95 percent density for cohesionless soils, and 90 percent <br />density for cohesive soil material. Tests to be performed by an independent testing service, with <br />the compliance report submitted to the architect. <br />8. Pipe shall not be laid in water. Furnish all pumping equipment, power, temporary connections, etc., <br />and do all pumping necessary to remove ground or casual water. <br />9. Where trenches cross roads, walks, or public thoroughfares, provide suitable barricades and bridges <br />adequately protected by signs or red flags during day and lights as night. <br />10. Repave all streets or sidewalks disturbed at this contractor's expense to recommendations, <br />procedures and satisfaction of architect and authorities having jurisdiction. <br />E. Supports and Hangers <br />1. Hangers and supports are to be provided to properly support, secure and align piping and to meet field <br />conditions and as manufactured by Grinnell, Michigan Hanger or Caddy. <br />2. All hangers, brackets, clamps, etc., shall be of standard weight steel. Perforated strap hangers shall <br />not be used in any work. When two or more pipes are run parallel, they may be supported on <br />unistrut-type trapeze hangers. Other hangers for pipe 3” in size and smaller shall be clevis. For pipe <br />transporting medium above 150 degrees F and 4” in size and above, use pipe roll. Each hanger is to <br />be sized to include pipe insulation saddle for protection. <br />3. Where building service lines enter or leave building such as water, sewer, gas, etc., and are installed <br />on filled earth, provide continuous support on a reinforced concrete beam furnished and installed <br />under this division. Support beam on building and with vertical support down to foundation footing and <br />on undisturbed earth at other end. Gas main shall enter building above grade. <br />4. All vertical piping passing through floors shall be supported at the floor by a riser clamp. <br />5. Isolate all copper lines form ferrous hangers or supports by using foil filler or vinyl tape. <br />6. Spacing to comply with ASHRAE standards and code requirements. <br />F. Pipe Sleeves, Floor and Ceiling Plates <br />1. All pipes passing through floors or masonry walls shall be provided with machine-cut schedule 40 pipe <br />steel sleeves. The sleeves shall be so sized to allow at least 1/4" clearance between the inside sleeve <br />wall and the pipe or insulation surface. Sheet metal sleeves shall not be used in this work. Pipe <br />sleeves are to extend 2” above finished floor and sealed. Pipe sleeves are to be full wall thickness and <br />sealed. <br />2. Unused sleeves shall be plugged and finished to match adjoining surface. <br />G. Escutcheons <br />1. Fit all pipe passing through walls, floors or ceilings in finished rooms with steel or brass escutcheons. <br />Where surface is to receive a paint finish, make escutcheons prime painted; otherwise, make <br />escutcheons nickel or chrome plated. Where piping is insulated, fit escutcheons outside insulation. <br />H. Pipe Identification and Tags <br />1. Identify each pipe, valve and controls in equipment rooms, above accessible ceilings and in accessible <br />shafts. <br />2. Color code identification bands or marker backgrounds to identify contents of pipe with initials and <br />direction of flow located near each valve and fitting, on both sides of pipe passing through walls and on <br />long runs at not over 20'-0” intervals. <br />3. At place where pipe is to have marking, covered pipe shall be properly primed with clear lacquer. After <br />marking is applied, coat with lacquer. Apply marking adjacent to valves and equipment at major <br />changes in directions, where pipes pass through walls or floors. <br />4. Each piece of equipment shall be identified by a number, together with a brief description of its <br />purpose, e.g. “Air Handling Unit - East Lobby.” Identification shall be embossed or engraved plastic or <br />stamped brass strips firmly attached to the equipment or adjacent wall at the obvious location. The <br />lettering for such strips shall be not less than 1/2" high. <br />5. All valves shall be provided with brass numbered tags attached to handle with a brass chain or ring. <br />Wiring of tags will not be acceptable. At the completion of the work, a reproducible valve schedule <br />shall be provided. Three (3) copies of this shall be mounted in metal, glass covered frames where <br />requested by the architect. The schedule shall give a description of the line or equipment controlled; <br />the normal position, emergency and/or shutdown position and location given either by description or <br />diagram. <br />6. All controls, starters, switches, etc, shall be identified by embossed stencil or engraved plate as to <br />purpose and/or equipment controlled. Control wiring shall be identified with program number and <br />device it services. <br />I. Access Panels <br />1. Each contractor shall be responsible for providing all required access panels necessary for his work. <br />This includes any access panels required for HVAC, plumbing and fire protection. Each contractor <br />shall also provide access panels for any existing conditions as required. <br />2. Refer to architectural drawings and specifications for type of access panel and coordinate locations <br />prior to any work. <br />3. Contractor shall mark lay-in ceiling tiles, in a method approved by the architect, where access is <br />required to such mechanical, plumbing, and fire protection equipment, valves, regulators, mixing <br />boxes, fire damper, etc. <br />J. Noise and Vibration Isolation <br />1. Furnish and install vibration isolating mountings to isolate from the structure, by means of resilient <br />vibration and noise isolators, all mechanical equipment over 1 HP having rotating or reciprocating <br />a. Isolators shall be supplied by a single source, and shall be guaranteed by the manufacturer to <br />provide isolation efficiencies in accordance with this specification. Selection shall be based on <br />equipment purposed, power dissipated, frequency, weight distribution and nature of the building <br />structure. Mountings shall be designed to permit attachment to the equipment base or pad and to the <br />structure and shall be selected for uniform deflection allowing for unequal weight distribution. <br />2. Selection shall be made by the manufacturer of the mountings to provide a transmissibility not <br />exceeding 10 percent. This contractor shall provide inertia pads for equipment where called for on <br />drawings or recommended by the manufacturer of the mountings. These shall consist of reinforced <br />concrete pads of suitable shape, of weight 1-1/2 times the weight of the equipment and provided with <br />weld plates or channels at the corners to which the mountings may be secured. <br />3. Vibration or noise created in any part of the building by the operation of any equipment furnished <br />and/or installed under this contract will be prohibited, and this contractor shall take all precautions by <br />isolating the various items of equipment, pipe and sheet metal work form the building structure. The <br />major items of equipment shall be isolated as called for on the plans and specified herein. The minor <br />items shall be held the responsibility of this contractor. <br />Section 200510 (cont.) <br />1. Mechanical equipment not internally isolated by the manufacturer shall be isolated as follows: <br />a. Connections from pump outlet and discharge nozzles to piping shall be made with flexible <br />connectors. <br />b. Isolate each base mounted pump from the piping systems by use of appropriate size corrugated <br />bellows, type 347 stainless steel couplings with control rods as manufactured by Keflex Mfg. or <br />flexonics for 300 psig design pressure at 800 degrees F. Design temperature. <br />c. Centrifugal fans, air conditioning and/or heating and ventilating units up to 3”static pressure on <br />grade shall be mounted on precompressed molded fiberglass, rubber-in-shear, or steel spring <br />isolators. If the drive motor is not supported directly on the fan, both units shall be mounted on an <br />integral structural steel base supplied by the isolator manufacturer, or sufficient rigidity to maintain <br />alignment between the fan and the drive motor. The base shall, in turn be mounted on <br />precompressed molded fiberglass, rubber-in-shear, or steel spring isolators. <br />The fans' isolators shall provide isolation efficiencies as follows: <br />Fan speed over 700 RPM 95 percent <br />Fan speed between 450 and 700 RPM 90 percent <br />Fan speed below 450 RPM, fan <br />wheel over 48” diameter 80 percent <br />Fan speed below 450 RPM, fan <br />wheel under 48” diameter Noise isolation only <br />d. Centrifugal fans, air conditioning and/or heating and ventilating units up to 3” static pressure <br />above grade shall be mounted on steel spring vibration isolators in combination with <br />precompressed molded fiberglass noise isolation pads. If the drive motor is not supported directly <br />on the fan, both units shall be mounted on an integral concrete inertia base, supplied by the <br />isolator manufacturer, of sufficient rigidity to maintain alignment between the fan and isolators in <br />combination with precompressed molded fiberglass noise isolation pads. See “C” above for <br />isolation efficiencies. <br />e. Centrifugal fans, air conditioning and/or heating and ventilating units up to 3” static pressure <br />ceiling suspended shall be mounted on a suitable platform and the platform in turn, suspended by <br />threaded rods from the overhead structure. Resilient hangers incorporating steel springs and <br />precompressed molded inserts shall be incorporated into each supporting rod. See “C” above for <br />isolation efficiencies. <br />2. Piping and ductwork shall be supported independently of the mechanical equipment and shall be <br />isolated as follows: <br />a. All suspended piping in the mechanical equipment and air handling rooms shall be supported <br />from the overhead structure by threaded rods incorporating resilient hangers. The resilient <br />hangers shall contain steel springs and precompressed molded fiberglass inserts, designed for <br />static deflections of between 1” and 1-3/4” under operating conditions. <br />b. All floor supported piping and pipe hangers in the mechanical equipment rooms shall be mounted <br />on steel spring vibration isolators in combination with precompressed molded fiberglass noise <br />isolators, designed for minimum static deflections of 1”. <br />c. Suspended piping entering or leaving mechanical or air handling equipment outside the <br />equipment rooms shall be supported for the first three hangers away from the equipment by <br />threaded rods incorporating resilient hangers from the overhead structure. The resilient hangers <br />shall contain steel springs and precompressed molded fiberglass inserts, designed for static <br />deflections between 1” and 1-3/4” under operating conditions. <br />d. Floor supported piping entering or leaving mechanical equipment outside the equipment room <br />shall be mounted on steel spring vibration isolators in combination with precompressed molded <br />fiberglass noise isolators, designed for minimum static deflections of 1” for the first three supports. <br />e. Flexible connections shall be used between air handling equipment and ductwork. <br />f. All ductwork within the mechanical equipment and air handling rooms shall be suspended with rod <br />and rubber-in-shear hangers. <br />3. Isolation efficiency shall be based on the lowest operating speed of the supported equipment. The <br />isolator manufacturer shall provide, as a part of his submittal data, and isolating efficiencies for the <br />isolators supporting each piece of equipment. Isolators shall be manufactured by Consolidated <br />Kinetics Corp., 401 Dublin Avenue, Columbus, Ohio, or Mason Industries, Inc., Hollis, New York. <br />K. Expansion Joints <br />1. Expansion joints in piping for heating and domestic water system 2-1/2” and below shall be Flexicraft <br />ML loop stainless steel for steel and copper pipe or Flexonics model H, stainless steel bellows, internal <br />guides, anti-torque device for steel pipe and model HB, bronze bellows, internal guides, anti-torque <br />device for copper pipe; end connections to match corresponding pipe construction. <br />2. Pipe alignment guide to be steel spider (copper clad for copper pipe) housed in a steel sleeve with feet <br />for attachment to structure. <br />3. Expansion loops shall be provided on all pipe runs over 100 ft in length. Size loop per manufacturer's <br />recommendations or as scheduled. <br />L. Thermometers and Gauges <br />1. Pressure gauges shall be provided in pipe lines and at inlets and outlets to equipment as called for or <br />specified. These shall be installed to indicate pressure changes across equipment only. This means <br />that they must have connections installed as close as possible to equipment flanges. These shall be <br />bourdon tube type with 3” minimum dial 1/4 male NPT connection, steel cages with pressure ranges <br />suitable for indicating the normal operating pressure at the two-third point of the scale range. Ashcroft, <br />3M or Taylor. Connections shall be made with shut-off cock and surge snubber. <br />2. Thermometers shall be a red mercury in glass-type with adjustable angle feature, 7” minimum scale <br />length with range and bulb length suitable for the application and insertion well. These shall be located <br />where they sense a true temperature and where they can be easily read and be installed with heat <br />transfer grease. <br />M. Miscellaneous Steel <br />1. Furnish and install all miscellaneous steel required for supports, hangers, anchors, guides, etc., <br />required for installation of equipment and materials furnished and installed under this division. <br />N. Painting <br />1. This contractor shall perform all painting incidental to this work. <br />2. All insulation shall be painted at the time of installation with one coat of Benjamin Foster “Lagtone” <br />water base paint. At the completion of the work, all such insulation shall be given an additional coat of <br />alkyd resin paint of a color to match existing building structure or as selected by the architect. <br />3. All uncovered black iron pipe, fittings, iron portions of valves, hangers, structural steel, expansion <br />tanks, cooling tower sumps and all other black iron work shall be thoroughly cleaned and given two <br />coats of alkyd resin paint of a color to match existing building structure or as selected by the architect. <br />4. All uncovered exposed sheet metal shall be thoroughly cleaned and neutralized and given two (2) <br />coats of alkyd resin paint of a color to match existing building structure or as selected by the architect. <br />5. All painting shall be done with a brush or roller. Spray painting will be prohibited. <br />6. All finishing materials, thinners, etc., shall be the best quality, first line materials as manufactured by: <br />a. E.I. Dupont De Nemours and Company <br />b. Pratt and Lambert, Inc. <br />c. The Glidden Company <br />d. The Sherwin-Williams Company <br />e. The Pittsburgh Plate Glass Company <br />7. All paint materials shall be delivered to the job in the manufacturer's original unopened and labeled <br />containers, and they shall be used strictly in accordance with the manufacturer's directions. <br />8. This contractor shall submit a list of materials to the architect. The list shall state the branch names of <br />the materials that the contractor intends to use. This list shall be secured from the paint manufacturer <br />and shall be on his stationery. <br />9. The architect's approval must be secured before any painting work is started. <br />O. Clean-Up <br />1. Insofar as this contract is concerned, at all times keep premises and building in a neat and orderly <br />condition: Follow explicitly any instructions of architect in regard to storing of materials, protective <br />measures, cleaning-up of debris, etc. <br />2. Upon completion of work, this contractor shall thoroughly clean all apparatus furnished by him, pack all <br />valves and thoroughly clean piping, fixtures and equipment removing all dirt, grease and oil. <br />3. Air systems shall not be operated without filters. Upon completion of work, replace all filters. <br />79 <br />6 <br /> <br />M <br />e <br />r <br />u <br />s <br /> <br />C <br />o <br />u <br />r <br />t <br />St <br />. <br /> <br />L <br />o <br />u <br />i <br />s <br />, <br /> <br />M <br />O <br /> <br />6 <br />3 <br />0 <br />2 <br />6 <br />T <br />6 <br />3 <br />6 <br />. <br />3 <br />4 <br />9 <br />. <br />1 <br />6 <br />0 <br />0 <br />F <br />6 <br />3 <br />6 <br />. <br />3 <br />4 <br />9 <br />. <br />1 <br />7 <br />3 <br />0 <br />16842136571210911141315 <br />84213657 1210911 1413 15 16 <br />a <br />b <br />c <br />d <br />e <br />f <br />g <br />h <br />j <br />k <br />l <br />m <br />n <br />p <br />r <br />s <br />a <br />b <br />c <br />d <br />e <br />f <br />g <br />h <br />j <br />k <br />l <br />m <br />n <br />p <br />r <br />s <br />Checked by <br />Drawn by <br />Issue Date <br />Project # <br />Scale <br />Client Approval <br />TI <br /> <br />T <br />E <br />M <br />P <br />L <br />A <br />T <br />E <br /> <br />V <br />1 <br />. <br />0 <br />, <br />10 <br />- <br />1 <br />1 <br />- <br />2 <br />0 <br />1 <br />1 <br />SANTA ANA - SOUTH <br />(#0972) <br />3313 S. BRISTOL ST. <br />SANTA ANA, CA 92704 <br />AS INDICATED <br />07/09/2025 <br />69325-CA03 <br />ISSUED FOR <br />PERMIT <br /># Description Date <br />These drawings/specifications are the property of Oculus Inc. They are <br />furnished as contract documents only. The seal(s) and signature(s) apply <br />only to the document to which they are affixed, and expressly disclaim <br />any responsibility for all other plans, specifications, estimates, reports or <br />other documents or instruments relating to or intended to be used for any <br />part or parts of the architectural or engineering project. Additionally these <br />drawings and seal(s) shall in no way convey or imply any type of warranty <br />or certification relating to the performance of products and materials <br />beyond those provided by their respective manufacturer. <br />© 2025 Oculus Inc. <br />03/10/2026 <br />Matthew R. Case, Engineer <br />CA # M41121