Laserfiche WebLink
M-020 <br />MECHANICAL SPECIFICATIONS <br />MECHANICAL SPECIFICATIONS (cont.) <br />13.Replace damaged insulation which cannot be repaired satisfactorily, including units with vapor barrier damage and moisture <br />saturated units. <br />D. Plumbing Insulation (as manufactured by Owens Corning, Knauf or Schuller) <br />1.Insulate all above-grade hot water, hot water return and cold water piping with 1” thick molded fiberglass having an all <br />service jacket. <br />2.Insulate all above-grade, horizontal air conditioning condensate floor drains and waste lines, with 1” thick molded fiberglass <br />having an all service jacket. <br />3.Include insulation of fittings and valves. Keep vapor barriers intact. Apply per manufacturer's recommendations. <br />4.Insulate all exposed waste and water supply piping under lavatory with safety covers per ADA requirements (as <br />manufactured by Plumberex Specialty Products, McGuire or Truebro). <br />E. HVAC Insulation (as manufactured by Owens Corning, Knauf) <br />1.All insulation to be applied in full accordance with the manufacturer's recommendations and comply with 25/50 flame and <br />smoke hazard ratings per ASTM E-84, NFPA 255 and UL 723. <br />2.Insulate all supply, return, outside and exhaust air ducts with 3/4" thick lined insulation or less to none with 1-1/2" thick, 1.5 <br />pcf, R-6, foil faced reinforced kraft jacket fiberglass duct wrap fully secured to duct. Lap and tape seams and secure tightly <br />to the ducts with wire or stick pins. Exposed ductwork in conditioned spaces without ceilings shall not be insulated, unless <br />otherwise noted to be insulated. Ductwork in ceiling plenum space shall be insulated. <br />3.Insulate all supply, return, outside and exhaust air ducts lined or not lined located in the attic space with 3” thick, 0.75 pcf <br />nominal density, R-10, foil faced reinforced Kraft jacket, fiberglass duct wrap fully secured to duct. Lap and tape seams and <br />secure tightly to the ducts with wire or stick pins. <br />4.Insulate all supply, return, outside and exhaust air ducts lined or not lined exposed to weather outside with 3” thick <br />mineral-fiber board, 3 pcf nominal density, R-13. Provide a venture clad insulation jacketing, color as selected by architect, <br />field-applied jacket. <br />5.Insulate all air conditioning condensate drain piping with 1" thick molded fiberglass insulation, C = 0.22. <br />6.Insulate all refrigerant suction and hot gas lines with 1" elastomeric foam insulation, C = 0.24 with joints and seams sealed <br />vapor tight. Insulation outside shall be painted with two coats of protective coatings per manufacturer for protection to <br />weather (as manufactured by Aeroflex, Armocell, or K-Flex). <br />Section 211000 - Fire Protection Systems <br />A. General <br />1.Furnish all labor, materials and equipment as required to install a complete fire protection system for <br />project. <br />2.Field-verify sizes and location of existing sprinkler piping before fabrication of new. <br />3.This contractor shall be responsible for the removal and reinstallation of existing ceiling tiles, as <br />required, for the installation of work shown in areas where existing ceilings are to remain. See <br />architectural drawings for areas where existing ceilings are to remain. <br />4.This removal and reinstallation of existing lay-in ceiling tiles shall be the responsibility of the fire <br />protection contractor (under the supervision of the general contractor) as required to perform his work. <br />Any damage to existing ceiling tiles or supports shall be the responsibility of the general contractor. <br />Ceiling tiles may be left out of the ceiling areas under construction only if stored in areas as directed <br />by the owner so as not to hinder the daily operations of the building's occupations. <br />5.This contractor shall modify and relocate sprinkler piping and provide new sprinkler piping and heads, <br />as required, to accommodate new mechanical work in full compliance with NFPA 13. This contractor <br />shall also perform hydraulic calculations for sprinkler piping in the remodeled areas in accordance with <br />NFPA 13. <br />B. Design Basis <br />1.Design basis for system shall be per NFPA 13 (latest edition) building code requirements, local water <br />department, local fire department, state fire marshal, local code, and owner and owner's fire insurance <br />underwriter requirements. <br />2.System shall be hydraulically calculated as required by code. <br />3.Pipe sizes indicated on drawing are approximate and shall be verified per the contractor's hydraulic <br />calculations. <br />C. Drawings and Calculations <br />1.Contractor shall prepare submittal drawings and hydraulic calculations with a 10% factor of safety for <br />building in accordance with owner's insurance company building department, and local fire authority <br />requirements, tenant's requirements for design density, whichever is most stringent. <br />2.Contractor shall perform a flow test data on water main and submit data with calculations. <br />3.It is the fire protection contractor's responsibility to verify each tenant's design density with agreed <br /> upon lease documentation and that tenant's prototype or insurance underwriters requirements. <br />4.Provide wet standpipe system for project in accordance with NFPA 14 requirements. <br />5.Contractor and designer shall be state certified. <br />6.Coordinate layout and installation of sprinklers with ductwork and equipment above ceilings and other <br />construction that penetrates ceilings, including but not limited to light fixtures, speakers, HVAC <br />equipment, doors and partition assemblies. No sprinkler piping shall be routed beneath equipment <br />above any ceilings that must be dropped directly down for service, repair, or replacement. <br />7.Examine areas and conditions under which fire protection materials and products are to be installed. <br />Do not proceed with work until unsatisfactory conditions have been corrected in manner acceptable to <br />installer. Schedule rough-in installations with installations of other building components. <br />8.Shop drawings review does not relieve fire protection contractor from responsibility to meet each <br />tenant's requirements for sprinkler coverage. <br />9.Fire protection contractor is responsible for verifying any high pile storage requirements of future <br />tenants and providing an incoming sprinkler service size and risers to meet the requirements for <br />adequate sprinkler coverage. <br />D. Piping <br />1.All piping shall be installed in accordance with NFPA 13, 14 (latest edition) and local code <br />requirements. <br />2.Fire protection piping shall be as follows: <br />a. Below-grade outside building - ductile iron, cement lined. Class of pipe as directed by local water <br />purveyor with mechanical or push-on type joints. <br />b. Inside building - pipe and tubing shall be steel or copper in accordance with NFPA requirements. <br />c. Piping shall match existing building standards. <br />d. Contractor shall arrange with owner and insurance underwriter prior to shut down of existing <br /> systems. <br />e. Flush all piping upon completion of project and test per NFPA requirements. <br />f. No piping shall be installed at locations subject to freezing. <br />3.Excavation and backfill - see Section 200510, Basic Materials and Methods. <br />E. Sprinkler Heads <br />1.Sprinkler heads shall be UL listed, match existing building standards and be manufactured by Central, <br />Star or Viking. <br />2.Sprinkler heads shall be as follows: <br />a. Areas with exposed structure <br />3.Upright - rough brass. <br />a. Areas with ceilings <br />4.Recessed Pendent - chrome plated with matching two (2) piece, flush escutcheon. <br />5.Concealed - brass finish with off-white ceiling cover plate. <br />6.Sidewall - chrome plated with off-white, two (2) piece, semi-recessed escutcheon. <br />7.Install concealed heads with white flush mounted cover plate in (sales area). <br />8.Install higher temperature sprinkler heads where required by code or application. <br />9.Sprinkler heads shall be located in the center of ceiling tiles or the center of an area of a 24” x 24” tile <br /> section. See architectural reflected ceiling plans. <br />10.Submit samples of sprinkler heads to architect prior to fabrication of any piping. <br />11.Install inspector's test connection with valve and terminate drain through exterior wall with text fitting <br />and splash block. <br />F. Valves <br />1.Install all valves as required by NFPA 13, UL or FM listed and as manufactured by Grinnell, Hammond <br />or Milwaukee. <br />2.All shut-off valves shall be fitted with tamper switches by fire protection contractor and wired by <br />electrical contractor. Tamper switches shall be as manufactured by Notifier, Potter or Viking. <br />3.Install flow switch in riser as manufactured by Notifier, Potter or Viking and wired by electrical <br />contractor. <br />4.Install UL listed alarm check valve with all required trim, including water motor alarm bell and drains as <br /> manufactured by Central Star or Viking. <br />5.Install wall mounted indicator valve as manufactured by Potter Roemer, Croker or Elkhart and <br />approved by local authorities. <br />6.Install double check detector assembly backflow preventer, as required by local water purveyor and as <br /> manufactured by Watts, Zurn or Conbraco. <br />Section 211000 (cont.) <br />G. Extra Materials <br />1.Valve wrenches: Furnish to owner, 2 valve wrenches for each type of sprinkler head installed. <br />2.Sprinkler heads and cabinets: Furnish 2 extra sprinkler heads of each style included in the project. <br />Furnish each style with its own sprinkler head cabinet and special wrenches. <br />3.Obtain receipt from owner that extra stock has been received and give architect a copy of this receipt. <br />Section 224000 - Plumbing Fixtures and Equipment <br />A. General <br />1.Furnish all fixtures and equipment indicated and scheduled on drawings, complete with all accessories, controls, etc., as <br />required. <br />2.Provide factory-fabricated fixtures of type, style and material indicated. For each type fixture, provide fixture manufacturer's <br />standard trim, carrier, seats and valves as shown by their published product information and indicated in the plumbing <br />fixtures schedule; either as designed and constructed or as recommended by manufacturer and as required for complete <br />installation. Where more than one type is indicated, selection is Installer's option, but all fixtures of same type must be <br />furnished by single manufacturer. Where type is not otherwise indicated, provide fixtures complying with governing <br />regulations. <br />3.Where fittings, trim and accessories are exposed or semi-exposed, provide bright chrome-plated or polished stainless steel <br />units. Provide copper or brass where not exposed. <br />4.Water Outlets: At locations where water is supplied (by manual, automatic or remote control), provide commercial quality <br />faucets, valves or dispensing devices of type and size indicated and as required to operate as indicated. Include manual <br />shut-off valves and connecting stem pipes to permit outlet servicing without shut-down of water supply piping systems. <br />5.Water Hammer Arrestors: Provide water hammer arrestors where shown on the drawings and as required to prevent water <br />hammer and excessive vibration in the domestic water system. Arrestors to be of size indicated or as recommended by the <br />manufacturer. <br />6.P-Traps: Include removable P-traps (with clean out plug) where drains are indicated for direct connection to drainage system. <br />7.Carriers: Provide cast iron supports for fixtures of either graphitic gray iron, ductile iron or malleable iron as indicated. <br />8.Escutcheons: Where fixture supplies and drains penetrate walls in exposed locations, provide chrome-plated sheet steel <br />escutcheons with friction slips. <br />9.Aerators: Provide aerators of types approved by Health Department having jurisdiction. <br />10.Comply with additional fixture requirements contained in fixture schedule on drawings. <br />B. Backflow Preventer <br />1.Provide reduced pressure backflow preventer consisting of assembly including abutting shutoff valves on inlet and outlet, and <br />discharge funnel. Backflow preventer shall include a minimum of four (4) test cocks and pressure-differential relief valve <br />located between two (2) positive seating check valves. Backflow preventer and shutoff valves shall be the same size as the <br />upstream pipe. <br />2.Backflow preventers sizes 2” and smaller shall have NPT connections, be of bronze body construction with bronze ball type <br />shut-off valves as specified in Section 200523 and test cock and bronze body relief valves with stainless steel trim. <br />3.Complete backflow preventer assembly shall be rated to 150 psi working pressure and water temperature range from 32º F <br />to 140º F. <br />4.Provide each backflow preventer with a drain funnel furnished by the manufacturer. Extend drain from funnel to nearest floor <br /> drain. <br />5.Backflow devices must meet ASSE Standards 1013, 1015 and 1020 and shall be tested at the time of installation by a person <br />certified by the Ohio Department of Health. The plumbing contractor shall pay for all costs associated with this test. <br />6.Manufacturer: Subject to compliance with requirements, provide backflow preventers of one of the following: <br />a. Cla-Val Company <br />b. Conbraco Industries, Inc. <br />c. Febco Sales, Inc., Sub. Of Charles M. Bailey Co., Inc. <br />d. Hersey Products, Inc. <br />e. Watts Regulator Company <br />Section 230900 - Instrumentation and Controls <br />C. General <br />1.Furnish and install complete temperature control for all HVAC systems. <br />2.Provide new control devices including thermostats, humidistats, damper operators, motors, temperature sensors, staging <br /> relays, and other related devices for a complete operational system per the operating sequence and industry standards. <br />3.Mount all controls furnished as accessories to equipment and provide all control wiring required for proper operation. All <br />wiring shall be in conduit per N.E.C. and local code requirements. <br />4.Mechanical contractor shall install all duct-mounted smoke detectors. Electrical contractor shall furnish and wire <br />photo-electric duct smoke detectors at each unit to shut down fan upon activation. Detector shall be located in the <br />supply/return air duct downstream/upstream of the unit connection. Detector will have manual reset and will activate a <br />local alarm panel. <br />G. Exhaust Fans <br />1.Toilet Room Exhaust Fan (EF-1) <br />a. Interlock fan with light switch to operate when lights are turned on (interlocking wiring) by electrical contractor. <br />H. Rooftop Units <br />1.Gas Fired Rooftop Unit (RTU-1(E)) <br />a. Wall mounted thermostat shall sequence heating and cooling. Provide with sub-base to manually select heating, <br />cooling, fan on-off, auto operation. <br />b. Unit shall operate in occupied or unoccupied modes based upon time clock sequence as determined by owner. <br />c. Unoccupied mode - The supply fan will be off, the outdoor air damper will go to 100% closed position and unit will <br />cycle on with a call for heating or cooling. <br />d. Occupied mode - The supply fan shall run continuously, the outdoor air damper will open to the minimum air <br />position and the unit will go into the heating or cooling mode, based upon room thermostat setpoint temperature. <br />e. Upon a call for cooling, and the outdoor air temperature is 55 degrees F. (adjustable) or cooler, the unit shall go <br />into economizer mode. If the outdoor air temperature is greater than 55 degrees F. (adjustable), the outside air <br />damper shall go to minimum position, and the compressors will be energized. <br />f. Upon a call for heating, the gas burner shall fire. <br />g. A low temperature thermostat will de-energize the supply fan and close the outside air damper if the mixed air <br />temperature is sensed at 40 degrees F or colder. <br />h. A duct mounted, photoelectric smoke detector (furnished by electrical contractor and installed by mechanical <br />contractor) shall shut down the unit, close the outside air damper and send a signal to the fire alarm panel when <br />activated. Both safeties will require manual reset, and will activate an alarm at the local control panel. <br />Section 233000 - Air Distribution Systems <br />A. General <br />1.Furnish all materials, labor, equipment and accessories required to install complete air distribution <br />systems. <br />2.Contractors bidding this project shall visit this site and familiarize themselves with all condition <br />affecting their work. Submission of a bid on this project shall be construed as having such knowledge. <br />3.Verify exact conditions in field and coordinate with these drawings and other trades before beginning <br />new work. <br />4.Determine exact locations for all new and relocated ductwork and accessories in field. <br />5.Coordinate work of this contract with other trades. <br />6.Any discrepancies between what is shown on drawings or specified and the actual conditions in the <br />field shall immediately be brought to the attention of the architect before proceeding. <br />7.Building and surfaces damaged during installation shall be repaired, replaced, and/or restored to <br />original condition after completion of work and before acceptance by owner. <br />8.This contractor is also referred to the appropriate mechanical and plumbing specification sections the <br />items of equipment to be bid as a part of this project. <br />B. Ductwork <br />1.Fabricate and erect all ductwork to ASHRAE and SMACNA standards from galvanized steel. Comply <br />with NFPA 90A requirements. <br />2.Ductwork shall be SMACNA low pressure construction 2" static pressure rating with Seal Class B <br />seams and joints, unless otherwise noted. <br />3.Include all acoustic, airfoil shaped perforated aluminum turning vanes, manual dampers, flexible <br />connectors, grilles and diffusers, acoustic lining, and other sheet metal accessories for the project. <br />4.Changes in direction, in low velocity supply air rectangular ductwork, shall be made with full radius <br />elbows with radius equal to 1 1/2 times the horizontal width of the duct, or with square elbows with <br />turning vanes. Turning vanes shall be constructed of the same material as the surrounding ductwork <br />and two (2) gauge numbers heavier. <br />5.Furnish and install all manual balancing dampers, splitter dampers, extractors, and deflectors required <br />to properly distribute the air. All dampers, extractors and deflectors shall be constructed of the same <br />material as the surrounding ductwork, unless noted otherwise on the drawings. All manual balancing <br />dampers shall be the opposed blade type. <br />6.Furnish and install all automatic control dampers unless noted otherwise on the drawings, all control <br />dampers shall be opposed blade type and shall have leakage of less than 1 percent when closing <br />against 4" water column static pressure and when sized for 2000 fpm velocity. <br />7.All manual balancing dampers, splitter dampers, extractors and deflectors shall be controlled by <br />Young No. 1 or Ventlock No. 688 regulators. If ductwork is accessible, mount the regulator on the <br />ductwork. If ductwork will be inaccessible after the installation of the ceiling or walls, mount the <br />regulator in a steel, flush mounted box specifically designed for this purpose. Provide all linkage, top <br />bearings and/or gear drives required for the remote installation of the regulator. <br />8.All branch connection fittings in rectangular ductwork shall be 45 degree transition type, conical fittings <br /> or spin-in fittings with integral air scoops. Butt fittings are not acceptable. <br />Section 233000 (cont.) <br />9.Exhaust duct outlets shall be installed a minimum of 10'-0" from all outside air intakes. <br />10.Kitchen hood exhaust duct shall be minimum thickness .060” black steel with liquid-tight welded joints, <br />where concealed, and of 18-Ga. minimum stainless steel where exposed. Install per local code and <br />NFPA 96 requirements. Maintain 18" clearance from duct to combustibles. <br />11.Alternative design: Furnish double wall, zero clearance to combustibles, factory built grease duct for <br />use with Type 1 kitchen hoods, which conform to the requirements of NFPA-96. Products shall be ETL <br />listed to UL-1978 and UL-2221 for venting air and grease vapors from commercial cooking operation. <br />The duct sections shall be constructed of an inner duct wall and an outer duct wall with insulation <br />between. Duct shall be CaptiveAire DW-2R or approved equal. Install per manufacturers instructions. <br />12.All exposed round ductwork shall be spiral seam ductwork and painted a color as selected by the <br />architect. <br />C. Drain Pans <br />1.Install 2” deep secondary drain pan below all furnaces and domestic water heaters. Pipe 3/4” drain to <br />floor drain independently off all the other drains. <br />D. Duct Liner <br />1.Acoustic line all rectangular ducts indicated on drawings with 1” thick non-flaking, coated medium <br />density liner, apply to manufacturer's recommendations. <br />2.Duct dimensions indicated on drawings are clear inside dimensions (free area). <br />3.Duct liner shall comply with NFPA 90A and 90B (latest edition) requirements. <br />E. Duct Accessories <br />1.Flexible ductwork (as manufactured by Clevaflex, Flexmaster or Wiremold). <br />a. Flexible ducts shall be independently supported from the structure and connected with plastic <br />draw bands and tightened. Flexible ducts shall be limited to 48" maximum straight length. <br />Flexible ducts shall be constructed of 1 1/2" insulation with vinyl vapor barrier jacket and rated at <br />10" W.C. for sizes though 12", UL listed, and meet 25/50 flame and smoke test. Flexible ducts <br />are not permitted in rooms without ceiling. <br />2.Dampers (as manufactured by Ruskin, Nailor or Safe-Air) <br />a. Fabricate in accordance with SMACNA Standards. Provide end bearings and locking, indicating <br />quadrant regulators. Blade to be single thickness with continuous hinge or rod. <br />3.Backdraft Dampers (as manufactured by Ruskin, Nailor or Safe-Air) <br />a. Multiple blade, parallel type damper constructed of galvanized steel with felt or flexible vinyl <br />sealed edges, ball bearings, pivot pin and adjustment device for varying pressures. <br />4.Access Doors (as manufactured by Ruskin, Nailor or Safe-Air) <br />a. Fabricate in accordance with SMACNA standards. Doors to be fabricated of galvanized steel with <br />sealing gasket and quick locking device. <br />b. For insulated ductwork, doors shall have minimum 1” insulation with sheet metal cover. <br />F. High efficient boilers and domestic water heaters shall have stainless steel or PVC combustion air intakes <br />and flue gas outlets as recommended by the equipment manufacturer. <br />G. Domestic water heater flues shall conform to the specification for low pressure ductwork. <br />H. All grilles, registers, diffusers and louvers shall be of the sizes, type, etc., as shown on the plan and <br /> schedules. <br />I. Grilles, registers, louvers and diffusers as manufactured by Krueger, Anemostat or Titus Company will be <br />considered provided dimensions, capacities, construction and sound characteristics are compatible and so <br />shown by shop drawings and performance specifications. All grilles, registers and diffusers shall be <br />finished a color as selected by the architect. <br />J. Furnish and install all hoods and hood exhaust ductwork. The construction of the hoods and hood exhaust <br />ductwork shall be as indicated on the drawings. <br />K. Centrifugal roof exhaust fans, intake, and relief vents as manufactured by Loren Cook or Greenheck will be <br />considered provided size, performance ratings and dimensions are compatible and so shown by shop <br />drawings and performance specifications. <br />L. Roof mounted equipment shall be supported using Pate curbs. <br />M. Louvers (as manufactured by American Warming, Arrow or Ruskin) <br />1.Extruded aluminum, storm-proof, drainable type, with a 6" deep frame, channel frame, 1/2" birdscreen <br />mounted on the interior face and prime coat finish. Final color selected by architect. Weather-proof all <br />joints around louver. <br />Section 235000 - Heat Generation Equipment <br />A. General <br />1.Furnish all material, labor, equipment, and accessories as required to install equipment as indicated on mechanical <br />drawings. <br />2.Install in full accordance with local code requirements, other specification section requirements, and manufacturer <br />recommendations. <br />B. See equipment schedules on mechanical drawings. <br />Section 236000 - Refrigeration Equipment <br />A. General <br />1.Furnish all material, labor, equipment, and accessories as required to install equipment as indicated on mechanical drawings. <br />2.Install in full accordance with local code requirements, other specification section requirements, and manufacturer <br />recommendations. <br />B. See equipment schedules on mechanical drawings. <br />Section 237000 - HVAC Systems and Equipment <br />A. General <br />1.Furnish all equipment, material, labor, tools, etc., for the complete HVAC system. Install complete and place in operation. <br />2.Contractors bidding this project shall visit this site and familiarize themselves with all conditions affecting their work. <br />Submission of a bid on this project shall be construed as having such knowledge. <br />3.Verify exact conditions in field and coordinate with these drawings and other trades before beginning new work. <br />4.Determine exact locations for all new and relocated equipment, piping, conduits and ductwork in field. <br />5.Coordinate work of this contract with other trades. Conflicts shall immediately be brought to the attention of the architect. <br />Architect's resolution to conflicts shall be final. <br />6.Any discrepancies between what is shown on drawings or specified and the actual conditions in the field shall immediately be <br />brought to the attention of the architect before proceeding. <br />7.Building and surfaces damaged during installation shall be repaired, replaced, and/or restored to original condition after <br />completion of work and before acceptance by owner. <br />B. Equipment <br />1.Mechanical contractor to furnish all HVAC equipment indicated and/or scheduled on the drawings complete with bases, <br />isolators, supports and other required accessories. <br />2.Install complete and place in proper operation per manufacturer's recommendations, lubricate and adjust as required. <br />Furnish and install clean set of filters prior to balancing. <br />3.Equipment to be make and model as scheduled unless alternate equipment of equivalent quality and performance is <br />submitted as a substitution prior to bidding. All substitutions are subject to acceptance without qualification by owner, <br />engineer and architect. <br />4.Contractor shall perform routine service inspection of all existing HVAC equipment to remain. Lubricate bearing, service <br />control systems, replace fan belts and install new filters in each rooftop unit. <br />5.Contractor shall field verify refrigerant charge and add refrigerant if the charge is less than manufacturer's specifications. <br />6.Submit service report to any major component failures or malfunctions. Report shall include cost to service all malfunctioning <br />or damaged items listed. Cost shall include parts and labor. Equipment shall be placed in full operation with controls <br />calibrated upon completion of project. <br />C. See equipment schedules on mechanical drawings. <br />79 <br />6 <br /> <br />M <br />e <br />r <br />u <br />s <br /> <br />C <br />o <br />u <br />r <br />t <br />St <br />. <br /> <br />L <br />o <br />u <br />i <br />s <br />, <br /> <br />M <br />O <br /> <br />6 <br />3 <br />0 <br />2 <br />6 <br />T <br />6 <br />3 <br />6 <br />. <br />3 <br />4 <br />9 <br />. <br />1 <br />6 <br />0 <br />0 <br />F <br />6 <br />3 <br />6 <br />. <br />3 <br />4 <br />9 <br />. <br />1 <br />7 <br />3 <br />0 <br />16842136571210911141315 <br />84213657 1210911 1413 15 16 <br />a <br />b <br />c <br />d <br />e <br />f <br />g <br />h <br />j <br />k <br />l <br />m <br />n <br />p <br />r <br />s <br />a <br />b <br />c <br />d <br />e <br />f <br />g <br />h <br />j <br />k <br />l <br />m <br />n <br />p <br />r <br />s <br />Checked by <br />Drawn by <br />Issue Date <br />Project # <br />Scale <br />Client Approval <br />TI <br /> <br />T <br />E <br />M <br />P <br />L <br />A <br />T <br />E <br /> <br />V <br />1 <br />. <br />0 <br />, <br />10 <br />- <br />1 <br />1 <br />- <br />2 <br />0 <br />1 <br />1 <br />SANTA ANA - SOUTH <br />(#0972) <br />3313 S. BRISTOL ST. <br />SANTA ANA, CA 92704 <br />AS INDICATED <br />07/09/2025 <br />69325-CA03 <br />ISSUED FOR <br />PERMIT <br /># Description Date <br />These drawings/specifications are the property of Oculus Inc. They are <br />furnished as contract documents only. The seal(s) and signature(s) apply <br />only to the document to which they are affixed, and expressly disclaim <br />any responsibility for all other plans, specifications, estimates, reports or <br />other documents or instruments relating to or intended to be used for any <br />part or parts of the architectural or engineering project. Additionally these <br />drawings and seal(s) shall in no way convey or imply any type of warranty <br />or certification relating to the performance of products and materials <br />beyond those provided by their respective manufacturer. <br />© 2025 Oculus Inc. <br />03/10/2026 <br />Matthew R. Case, Engineer <br />CA # M41121