Article 220 - Service Feeder calculation for (address):Job Code <br />2325 W Flora St Santa Ana CA USA 92704 109R-325SHAN2 <br />Section 220.83 Existing Dwelling Unit <br />Part #1 - Section 220.83(A)(1) Generatl Lighting/Receptacles @ 3 VA per sq ft: <br />Building Square Footage VA (watts)Amps <br />House 2100 6300 26.25 <br />Amps Box A (VA) <br />26.25 6300Total for Part #1: <br />Part #2 - Section 220.83(A)(2),(4) Appliances and Dedicated Circuits: <br />Dedicated Circuit Size in VA Dedicated Circuit Size in VA <br />Dishwasher 1000 N/A <br />Dryer 5760 N/A <br />Laundry 1500 N/A <br />Appliance Circuit 1 1500 N/A <br />Appliance Circuit 2 1500 N/A <br />Range 9600 N/A <br />N/A N/A <br />N/A N/A <br />N/A N/A <br />N/A Amps Box B (VA) <br />N/A 86.92 20860Total for Part #2: <br />Total VA from Parts #1 and #2 combined:Box A + Box B = 27160 <br />Total VA 27160 <br />First 8000 VA @ 100% 8000 Remaining VA @ 40% <br />Remaining VA = 19160 19160 x 40% = 7664 VA <br />Adding First 8,000 VA 8000 VA <br />15664 VA <br />65.27 Amps <br />Total VA for Gen. Lights/Recep, Appliances & Dedicated circuits: <br />Total AMP for Gen. Lights/Recep, Appliances & Dedicated circuits: <br />Part #3 - Section 220.83(A) Heating and A/C Loads: <br />100% of all the Heating or A/C loads in VA: 7320 VA <br />100% of all the Heating or A/C loads in Amps: 30.5 A <br />*Combine the larger loads of either the Heating or the A/C loads togther <br />Totals from all Parts#EStamp <br />VA Volts Amps <br />Parts #1 & #2 15664 240 65.27 <br />Part #3 7320 240 30.5 <br />Total VA for all Parts: 22984 <br />Totals Service/Feeder Load 95.77