<br />a — Conversion factor calculated as a weighted average of the load I
<br />load combination. In addition, a must include all applicable
<br />nonductile failure modes and required over -strength.
<br />The requirements for member thickness, edge distance and spacing, described in this
<br />Approved
<br />+_)I.(bR PERMIT, ISSUANCE
<br />6terID:
<br />4.2.2 Interaction of Tensile and Shear Forces: The interaction must be calculated all late
<br />318-19 17.8 as follows:
<br />For shear loads Vapplled < 0.2Vallowable.AW, the full allowable load in tension is permitted.
<br />For tension loads Tappled <— 0.2Tallowable,ASD, the full allowable load in shear is permitted.
<br />For all other cases:
<br />Tapplied + 11applied
<br />Tallo,vable.ASD valla,vable,ASD C 1.2 (Eq-4)
<br />4.2.3 Installation:
<br />Installation parameters are provided in Table 1 and Figure 2, Figure 5A, Figure 5B, Figure 5C and Figure 5D.
<br />Anchor locations must comply with this report and plans and specifications approved by the code official. The
<br />Hilti KB-TZ2 must be installed in accordance with manufacturer's published instructions and this report. In case
<br />of conflict, this report governs. Anchors must be installed in holes drilled into the concrete using carbide -tipped
<br />masonry drill bits complying with ANSI B212.15-1994, using the Hilti SafeSet System" with Hilti TE-YD or
<br />TE-CD Hollow Drill Bits complying with ANSI B212.15-1994 with a Hilti vacuum in accordance with Figure 6
<br />and Figure 7, or using Hilti SPX-T core bits in accordance with Figure 7. The Hollow Drill Bits are not permitted
<br />for use with the'/4-inch and 3/8-inch diameter KB-TZ2 anchors. The Hilti SPX-T core bits are not permitted for
<br />use with the 1/4-inch and 1-inch diameter KB-TZ2 anchors. The minimum drilled hole depth, ho, is given in
<br />Table 1. If dust and debris is removed from the drilled hole with the Hilti TE-YD or TE-CD Hollow Drill Bits, the
<br />DRS attachment system, or compressed air or a manual pump, hnan, is achieved at the specified value of
<br />ho noted in Table 1. The anchor must be hammered into the predrilled hole until tenon, is achieved. The nut must
<br />be tightened against the washer until the torque values specified in Table 1 are achieved, or the anchors may
<br />be installed using the appropriate Hilti Impact Wrench and corresponding Hilti AT Module in accordance with
<br />Figure 7. The Hilti AT Tool system is not permitted for use with the 1/4-inch and 1-inch diameter KB-TZ2
<br />anchors. For installation in the soffit of concrete on steel deck assemblies, the hole diameter in the steel deck
<br />must not exceed the diameter of the hole in the concrete by more than inch (3.2 mm). For member thickness
<br />and edge distance restrictions for installations into the soffit of concrete on steel deck assemblies, Figure 5A,
<br />Figure 5B and Figure 5C.
<br />4.3 Special Inspection:
<br />Periodic special inspection is required in accordance with Section 1705.1.1 and Table 1705.3 of the 2024 IBC,
<br />as applicable. The special inspector must make periodic inspections during anchor installation to verify anchor
<br />type, anchor dimensions, concrete type, concrete compressive strength, anchor spacing, edge distances,
<br />concrete member thickness, tightening torque, hole dimensions, anchor embedment and adherence to the
<br />manufacturer's printed installation instructions. The special inspector must be present as often as required in
<br />accordance with the "statement of special inspection." Under the IBC, additional requirements as set forth in
<br />Sections 1705, 1706 and 1707 must be observed, where applicable.
<br />5.0 CONDITIONS OF USE:
<br />The Hilti KB-TZ2 anchors described in this report comply with the codes listed in Section 1.0 of this repot I, subject
<br />to the folinwing conditions:
<br />5.1 Ancho; sizes, di+iuonsion:-., i-.601nlUn+ cic�plhs t:md other installation paromelem as sal forth in
<br />this report.
<br />2 The: l,cs installed it+;:,:.:- r :u c: v,iih I!u: manufacturer's pulAshc:d it7struc6011s anit this rcpori.
<br />In case of conflict, this report governs.
<br />5.3 Anchors must be limited to use in cracked and uncracked normal -weight concrete and lightweight concrete
<br />having a specified compressive strength, fc, of 2,500 psi to 8,500 psi (17.2 MPa to 58.6 MPa), and cracked
<br />and uncracked normal -weight or sand -lightweight concrete over metal deck having a specified compressive
<br />strength, Pc, of 3,000 psi to 8,500 psi (20.7 MPa to 58.6 MPa).
<br />5.4 The values of fc used for calculation purposes must not exceed 8,000 psi (55.1 MPa).
<br />5.5 The concrete shall have attained its minimum design strength prior to installation of the anchors.
<br />5.6 Strength design values must be established in accordance with Section 4.1 of this report.