ESR-5175 Page 4 of 8 <br /> <br /> <br /> <br />4.3.6 Sealer (Required for Systems B and C): The sealer must be one of the following: <br />• Two coats of Dex-O-Tex Aero-Flor 100 Sealer, or two coats of Dex-O-Tex Clear Sealer HD 50 sealer roller- <br />applied over the top coat at a rate of 1 gallon per 400 square feet (1 L/9.8 m2), for a minimum wet-film <br />thickness of 0.0053 inch [5.3 mils (0.13 mm)] for each coat. The first coat must be allowed to dry for a <br />minimum of 30 minutes before application of the second coat. <br />• Two coats of Dex-O-Tex Weatherseal XL Sealer, roller-applied over the protection coat at a rate of 1 gallon <br />per 400 square feet (1 L/9.8 m2), for a minimum wet-film thickness of 0.011 inch [11 mils (0.28 mm)] for each <br />coat. The first coat must be allowed to dry for a minimum of 30 minutes before application of the second <br />coat. <br />• As an additional option for System C, two coats of Dex-O-Tex AJ-44 XL must be roller-applied over the <br />protection coat at a rate of 1 gallon per 300 square feet (1 L/7.4 m2), for a minimum wet-film thickness of <br />0.011 inch [11 mils (0.28 mm)] for each coat. The first coat must be allowed to dry for approximately one <br />hour before application of the second coat. <br />For all sealers, after application of the second coat, the coating must be allowed to dry for 12 to 24 hours <br />before traffic is allowed on the coating. <br />4.4 Systems D, E and F (Installation over Concrete – See Table 2): Application of the waterproofing layer <br />and protection coat, must be as described in Sections 4.3.3 and 4.3.4, respectively. <br />For Systems D and E application of the topcoat must be as described in Section 4.3.5. <br />For Systems D and F application of the sealer must be as described in Section 4.3.6. <br />4.5 System G (Installation over Concrete–See Table 2): <br />Application of the waterproofing layer and sealer must be as described in Sections 4.3.3 and 4.3.6, <br />respectively. <br />For application of the protection coat, one gallon (3.8 L) of Dex-O-Tex Stamp-Cote Liquid must be mixed with <br />a 45-pound (20.5 kg) bag of Dex-O-Tex Stamp-Cote Powder and applied with a spreader rake and closed with <br />a float trowel over the waterproofing layer at a rate per batch of 18 square feet(1.7 m2) for the minimum 1/4- <br />inch (6.4 mm) thickness, 13.5 square feet (1.3 m2) for the 3/8-inch (9.5 mm) thickness, or 9 square feet (0.83 <br />m2) for a thickness of 1/2 inch (12.7 mm). The coating is processed and stamped and allowed to cure for a <br />minimum of 12 hours. <br />4.6 Method of Repair: <br />The damaged area must be removed and replaced as required for a new installation, as described in Section <br />4.3, 4.4, or 4.5. When substrate damage occurs, the retention of the fire-resistance rating and strength <br />properties must be investigated, and the results submitted to the code official. <br />4.7 Wind Resistance: <br />Under the 2021 and 2018 IBC, the Dex-O-Tex Dex-Flex Decking system may be used in areas subject to a <br />basic wind speed (V) of 130 mph (209 km/h) on structures with a maximum height of 40 feet (12,192 mm) in <br />Exposure B areas. <br />Under the 2021 IRC, 2018 IRC, 2015 IBC, 2015 IRC, and 2012 IBC, the Dex-O-Tex Dex-Flex Decking system <br />may be used in areas subject to an ultimate design wind speed (Vult) of 130 mph (209 km/h) on structures with <br />a maximum height of 40 feet (12,192 mm) in Exposure B areas. <br />Installation must be limited to areas where the maximum basic wind speed, building height and exposure <br />comply with Tables 3 and 4 of this report, as applicable. <br />4.8 Class A Roof Covering Construction: <br />When Dex-O-Tex Dex-Flex Decking systems are applied over concrete or 5/8-inch-thick (15.9 mm) exterior- <br />grade plywood substrates with all edges blocked, the systems have a Class A roof classification, provided the <br />maximum slope does not exceed 1/2 inch per foot (4% slope). <br />4.9 One-hour Fire-resistance-rated Construction: <br />The deck system described in Section 4.3 of this report, when applied over 5/8-inch-thick (15.9 mm) exterior- <br />grade plywood, with nominally 2-by-10 (51 by 254 mm) joists spaced at 16 inches (406 mm) on center, and all <br />plywood joints blocked, can be recognized as a substitute for the double wood floor described in Assembly 13 <br />of Table 721.1(3) of the 2021, 2018, 2015 and 2012 IBC (Table 720.1(3) of the 2019 IBC and 2006 IBC). <br /> <br />