Laserfiche WebLink
CITY OF SANTA ANA <br />2022 Single -Family Residential Mandatory Requirements Summary <br />Energy Storage System (ESS) Ready. Al single-family residences must meet all of the following: Either ESS-ready interconnection <br />§ 150.0(s) <br />equipment with backed up capacity of60 amps or more and four or more ESS supplied branch circuits, Lr a dedicated raceway from the <br />main service to a subpanel that supplies the branch circuits in § 150.0(s); at least four branch circuits must be identified and have their <br />source collocated at a single panelboard suitable to be supplied by the ESS, with one circuit supplying the refrigerator, one lighting circuit <br />near the primaryexit, and one circuit supplying a sleeping room receptacle outlet, main panelboard crust have a minimum busbar rating of <br />225 amps,- sufficient space must be reserved to allow future installation of system isolation equipment/transfer switch within 3' of the main <br />panelboard, with raceways installed between the panelboard and the switch location to allow the connection of backup power source. <br />§ 150.0(tj <br />Heat Pump Space Heater Ready. Systems using gas or propane furnaces to serve individual dwelling units must include: A dedicated <br />unobstructed 240V branch circuit wiring installed within 3' of the furnace with circuit conductors rated at least 30 amps with the blank cover <br />identified as "240V ready, and a reserved main electrical service panel space to allow for the installation of a double pole circuit breaker <br />permanently marked as "For Future 240V use" <br />Electric Cooktop Ready. Systems using gas or propane cooktop to serve individual dwelling units must include: A dedicated unobstructed <br />§ 150.0(u) <br />240V branch circuit wiring installed within 3' of the cooktop with circuit conductors rated at least 50 amps with the blank cover identified as <br />'240V ready; and a reserved main electrical service panel space to allow for the installation of a double pole circuit breaker permanently <br />marked as "For Future 240V use." <br />Electric Clothes Dryer Ready. Clothes dryer locations with as or propane plumbing to serve individual dwelling units must include: A <br />ry Y Y 9 P P p 9 9 <br />§ 150.0(v) <br />dedicated unobstructed 240V branch circuit wiring installed within 3' of the dryer location with circuit conductors rated at least 30 arms with <br />the blank cover identified as "240V ready;' and a reserved main electrical service panel space to allow for the installation of a double pole <br />circuit breaker permanently marked as "For Future 240V use" <br />*Exceptions may apply. <br />i,1c�yxa <br />2022 Single -Family Residential Mandatory Requirements Summary <br />Space Conditioning System Airfl ow Rate and Fan Efficacy. S pace conditioning systems that use ducts to supply coo ling must have <br />a hole for the placement of a static pressure probe, or a permanently installed static pressure probe in the supply plenum. Airflow must <br />7 G <br />be - 350 CFM per ton of nominal cooling capacity, and an air -handling unit fan efficac - 0.45 waits per CFM for as furnace air <br />150.0 m 13: <br />§ () P 9 P Y. g Y P 9 <br />handlers and <0.58 watts per CFM for all others. Small duct high velocity systems must provide an airflow2t 250 CFM per ton of nominal <br />cooling capacity, and an air -handling unit fan efficacys 0.62 watts per CFM. Field verification testing is required in accordance with <br />Reference Residential Appendix RA3.3 " <br />Ventilation and Indoor Air OLiality- <br />Requirements for Ventilation and Indoor Air Quality. All dwelling units must meet the requirements of ASHRAE Standard 62.2, <br />§ 150.0(o)1: <br />Ventilation and Acceptable Indoor Air Quality in Residential Buildings subject to the amendments specified in§ 150.0(o)1. * <br />Central Fan Integrated CFI Ventilation Systems. Continuous operation of CFI air handlers is not allowed to provide the whole- <br />g (CFI)Y P <br />§ 150.0(0)1B: <br />dwelling unit ventilation airflow required per §150.0(o)1C. A motorized damper(s) must be installed on the ventilation duct(s) that <br />prevents all airflow through the space conditioning duct system when the damper(s) is closed andcontrolled per §150.0(o)18iii&jv. CFI <br />ventilation systems must have controls that track outdoor air venti lation run time, and either open or close the motorized damper(s) for <br />compliance with 150.0 0 1C. <br />Whole -Dwelling Unit Mechanical Ventilation for Single -Family Detached and townhouses. Single-family detached dwelling units, <br />§ 150.0(o)1C: <br />and attached dwelling units not sharing ceilings or floors with other dwelling units, occupiable spaces, public garages, or commercial <br />spaces must have mechanical ventilation airflow specified in § 150.0(0)10-iii. <br />§ 150.0(o)IG: <br />Local Mechanical Exhaust. Kitchens and bathrooms must have local mechanical exhaust; nonenclosed kitchens must have demand - <br />controlled exhaust system meeting requirements of§150.0(o)1Giii,enclosed kitchens and bathrooms can use demand -controlled or <br />continuous exhaust meeting §150.0(o)lGiii-iv. Airflow must be measured by the installer per §150.0(o) 1Gv, and rated for sound per <br />150.0 0 1Gvi.' <br />§ 150.0(o)1H&l: <br />Airflow Measurement and Sound Ratings of Whole -Dwelling Unit Ventilation Systems. The airflow required per § 150.0(o)1C must <br />be measured by using a flow hood, flow grid, or other airflow measuring device at the fan's inlet or outlet terminals/grilles per Reference <br />Residential Appendix RA3.7 Whole -Dwelling unit ventilation systems must be rated for sound per ASHRAE 62.2 §7.2 at no less than the <br />minimum airflow rate required bv 150.0 0 1C. <br />Field Verification and Diagnostic Testing. Whole -Dwelling Unit ventilation airflow, vented range hood airflow and sound rating, <br />§ 150.0(o)2: <br />and HRV and ERV fan efficacy must be verified in accordance with Reference Residential Appendix RA3.7. Vented range hoods <br />must be verified per Reference Residential Appendix RA3.7.4.3 to confirm if it is rated by HVI or ARAM to comply with the airflow <br />rates and sound requirements per §150.0(o) I G <br />Pool and Soa Svstems and Eautoment: <br />Certification by Manufacturers. Any pool or spa heating system or equipment must be certified to have all of the followin g: compliance <br />§ 110.4(a): <br />with the Appliance Efficiency Regulations and listing in MAEDbS, an on -off switch mounted outside of the heater that allows shutting off <br />the heater without adjusting the thermostat setting, a permanent weatherproof plate or card with operating instructions; and must not <br />use electric resistanceheatin . <br />Piping. Any pool or spa healing system or equipment must be installed with at least 36 inches of pipe between the filter and the heater, or <br />§ 110.4(b)1: <br />dedicated suction and return lines, or built-in or built-up connections to allow for future solar heating. <br />§ 110.4(b)2: <br />Covers. Outdoor pools or spas that have a heat pump or gas heater must have a cover. <br />Directional Inlets and Time Switches for Pools. Pools must have directional inlets that adequately mix the pool water, and a time <br />§ 110.4(1b)3: <br />switch that will allow all pumps 10 be set or programmed to run only during off peak electric demand periods. <br />§ 110.5: <br />Pilot Light. Natural gas pool and spa heaters must not have a continuously burning pilot light. <br />Pool Systems and Equipment Installation. Residential pool systems or equipment must meet the specified requirements for pump <br />§ 150.0(p). <br />sizing, flow rate, piping, filters, and valves. <br />Liahtina- <br />Lighting Controls and Components. Al lighting control devices and systems, ballasts, and luminaires must meet the applicable <br />§ 110.9: <br />re uirements of 110.0 x <br />§ 150.0(k)1A: <br />Luminaire Efficacy. All installed luminaires must meet the requirements in Table 150.0-A, except lighting integral to exhaust fans, kitchen <br />range hoods, bath vanity mirrors, and garage door openers, navigation light ng less than 5 watts, and lighting internal to drawers, cabinets, and linen <br />closets with an efficacy of at least 45 lumens per watt. <br />150.0(k)1 B: <br />Screw based luminaires. Screw based luminaires must contain lamps that comply with Reference Joint Appendix JAB,* <br />§ 150.0(k) IC: <br />Recessed Dowd ight Luminaires 1n Ceilings. Luminaires recessed into ceilings must not contain screw based sockets, must be airtight, <br />and must be sealed with a gasket or caulk. California Electrical Code § 410.116 must also be met. <br />Light Sources in Enclosed or Recessed Luminaires. Lamps and other separable light sources that are not compliant with the JAB <br />§ 150.0(k)1D: <br />elevated temperature requirements, including marking requirements, must not be installed in enclosed or recessed luminaires. <br />§ 150.0(k)1E: <br />Blank Electrical Boxes. The number of electrical boxes that are more than five feel above the finished floor and do not contain a <br />Luminaire or other device shall be no more than the number of bedrooms. These boxes must be served by a dimmer, vacancy sensor <br />control, low volla e wiring, or fanspeed control. <br />Lighting Integral to Exhaust Fans. Lighting integral to exhaust fans (except when installed by the manufacturer in kitchen exhaust <br />§ 150.0(k) lE <br />hoods) must meet the applicable requirements of § 150.0 k . x <br />516/22 <br />2022 Single -Family Residential Mandatory Requirements Summary <br />§ 1:50.Qk'j1G: Screwy based luminaires _:_iewnsad lumrares misi conlan lamps t-ral corr'irlywrth RaierenceJoint Appendix,J.A6.' <br />Light Sources in Enclosed or Recessed Luminaires. Lamps and ct-ier separable light sourm that are not compliant with the JAB <br />§ 15Cr.Qk)1H.elevated lempe-aluie iii-quiierrent:.. mr: uJmg ma•krig requrements, Nnust not be rn5talled'n enclosed or recessed luminaires. <br />Light Sourcers in Drawers, Catwnets, and Linen Closets, tight source interval todrawers. cabinetvy or linen ckmts are not required <br />150.Cn;k)1 I: to comply watt 1 able 1:50.0-A or be controlled by vacancy sensors provided that they are rated to consume no more than 5 waits of <br />power. emit no more than 1.50 lumens, and are equipped with co'ntrds that automatically tirn t've lighting off when the drawer. cabinet or <br />Inert doset is closed. <br />1a0.0(k)2A Interior Switches and Controls. All forward phaise cart dirniers used with LED light sources must comply with HEMA, SSL 7f'c <br />1 l]:f1(kj2tl: Interior Switches and Controls. Waist fans mud be canti'dled separately from lighting syskmrs. t <br />Accessible Controls. _igh.ing must have readily accessible wall -mounted controls that allow the lighting to be manually turned <br />§ 1.50.1(k)2A an and off. . <br />Multiple controls. cor'lirals must not bypass a r wnmer. oGtu pant sensor, or vacancy sensor unction 9 the dimmer or senso7 s metalled <br />6130.t1r(k)2B: to com 'v writfi 1511.OIk1. <br />5150:0(k)2C: Mandatory Requirements. Lghting controls must comply with the applicable requirernants of § 110.9. <br />Energy Management Control Systems. An a ergy managgerivenl cinbred system (FMCS) may be used Dry crornply with dimming. <br />150_0(k)2D_ occupari y. and cantirdi requirements 0 it provides be functionality of the spenfied control per § 110.9 and the physical controls specilfiad <br />in 150.01'k12A <br />Automabc Shutoff Controls. In batrinx: -rrs, garages, laundry rooms, utility{ rooms and wakAn closets, at least erne vrrslallEJ Iuinrrra re <br />§ 1.511.4i;kj2E: roust be conbclled by an occupancy or vacancy sensor providing automatic -off functionality. Lighting inside drawors and cabinets wth <br />o ue fronds or dccfs roust have controls that turn the light off when the drawer or door is dosed. <br />mmer5. Lighting in habitable spaces (e.g-, living rooms, dining rooms. b1chms, and bedrooms) must have readily accssstde wall- <br />§ 150 r3r;k)r"F: rnourdad dimming contrite dual allow the lighting to be manually adjusted up and down. Forward phase art dimmers mi-drdling LED hghd <br />sources in these spaces moist com ty vidth NEWSSL 7A <br />§ 150_i3(k j<: Independent controls. Inbigraied lighting col exhaust fans shall be controlled independently from the fans. Lghitrig under cabnets or <br />sheMes. lightnig in di cat>erWs, and swekited ovtlais must be contr'dled separately from cxdrn rislalle ligtdlTlg. <br />Residentiial Outdoor UgM ling. For "a -family residential buildings. outdoor bighting permanently nlourite%J 1D a resdenival Luildng. or to <br />15O g3g;k)3A: other buddings an the same Ict, must have a manual Dii'cM width and ether a olocell ,and matron sensoe or aulDrnabc time sw1c:h <br />rc.nlroll or an astronomical tare dodo. An energy management control system that provides the specified ied coitld iuncirmal:ty and meals all <br />a zhcable r_ u rernenis Tiay be used to Meet these requirements. <br />Internally illuminated address signs. Internally duminated address signs rn,sl ether comply wit•i § 1413.8 cr consume -io more than 5 <br />15Lr-r3g;k;r4. watts ail ptm-_r. <br />Residential Garages for Eightor More Vehicles. LiOt rgg for residenhal paduag garages for 9ghl cv mcxe vehi,"Jes must c mvply wtlr tie <br />§ 150.0g;k'v5_ ap; licable regiire,ne•its jar rcmesdentral garages n §51113.9. 130.0.130.1.1VA, 140.16, and 141.4.. <br />Solar Readinesr.- <br />ingle- amily Residences. Single4armly residences located in subd �l outs -Arth10 or more sngle- ,arndy residences and where the <br />110_10Qai1: <br />appl{ olio for a tentat� a si."ivnsron m.Vkx the residainces has been deemed-wri,lele and approved by the enforcement agency. <br />whorl do not'vane a hUt!VC.Aagc Syslaxm installed, must comply with t`ie re iirame-its Di 110.10ilti Ie). <br />Minimum Solar Tune Area. 7 he soar zone must have a mnimum bct<al area as descrized be4ow- "he solo- zDne rn rst comply v,rt*i <br />access, pathway. smoke verddabD i. and spading mquremerts as spec Aed in Tithe 24, Pail 9 or other pails of Title 24 cY in any <br />irequvemerds adopted by a local jurisdiction- The solar zow total area roust be comprised of areas that have no dimension less titan 5 <br />feet and are no isle than 90 square feel each kw buildings with roof areas less than or equal to 10,000 square feet or no less vian 160 <br />§ 110.1 C Ib)1 A= <br />square feet each for buldingis with roof areas greater titan 10,D30 square feet. IFor single-famity mWences, tie solar zone must be <br />tocaled on the roof or Overharing of the buidirx3 and have a total area no less than 250 Square feet. * <br />110_10: ;2. <br />Azimuth. All sections of the solar zone located on sleep -sloped worts mist have an azimuth belwvom 90-300* of true norits <br />Shading. The solar zone must not c5oritain array obsbuchons, including bout riot I m led bo_ vents, chwmey& archtev tural features, and roof <br />110-101WA: <br />ne mlad equprnenL <br />Shading Any ontistudion locaried an the rood or any other part of the building that projects above a solar zone muss be located at Isast t#Ace the <br />G.i i343: <br />horizontal distance of the height differerice betweeen the h ghesi pant of the obstruction acid the horizontal prpje ton of the nearest pant od the <br />solar zone, measured in the vertical plane.' <br />truct.ur Design Loads on Construction Documents. Fcr areas of the desig-iated as a solo! = e. the structural design loads far <br />11 CI.11}Iti <br />roof dead load acid roof live bad must be dearly irdic-ated on the c D istruction docurneds. <br />Intarir onnecMn Pathways. The construct�,n documents must indicate: a /oration reserved to-, mirarters and melairig eq.vrpme;it acid a <br />§ 110L101ck <br />palmy resurrect inn routing of conduit from the solar zone to the point of riterconnedion with the electrical service; and for srigle-fa* <br />residences and central water-heatirig systems, a pathway resewed for rouling pluriting from the solar zone In the warlm-heafting system. <br />ocumentatiou. A crpy ru the c:Drislruchon docume-its Dr a c;Drnparafrfe docurrnent indicating the slarmaticiri tram § 1 .1 bXc must be <br />§ 110.101d): <br />provided to the cxz ipanl- <br />110_101e)1: <br />Main Electrical Service Parmit The main electrical service panel must have a minrnurn bulbar rating of 2W amps. <br />Main Electrical Service Parcel. The main electrical ser`rrick panel must hm a reserved space lo' allow for the Installation of a double pole <br />11 Ci_1(fIe 2: <br />erw t breaker for a tulwe solar electric installation- The reserved mace roust be pemuwndy marked as `For future Solar Electric_ - <br />Electric and Energy Storage Ready: <br />5,'6,'22 <br />2022 Single -Family Residential Mandatory Requirements Summary Planning Emd E <br />NOTE: Single-family residentiaI buildings sub/•ect to the Energy Codes must comply with all applicable mandatory measures, regardless of the ompli ance approach <br />used. Review the respective section for more information. <br />(04M) <br />Building Envelope: <br />Air Leakage. Manufactured fenestration, exterior doors, and exterior pet doors muss limit air leakage to 0.3 CFM pe, square fool or A r <br />§ 110.6(a)l: less when tested per NFRC-400, ASTM E283, or AAMAtWDMA/CSA 101/I.S.2/A440-2011. x <br />§ 110.6(a)5: Labeling. Fenestration products and exterior doors must have a label meeting the requirements of § 10-111(a).F 0 'PE I <br />Field fabricated exterior doors and fenestration products must use U-factors and solar heat gain coefficient (SH C) values from <br />§ 110.6(b): Tables 110.E-A, 110.E-B, or JA4.5 for exterior doors. They must be caulked and/or weather- stri pped. <br />Air Leakage. All joints, penetrations, and other openings in the building envelope that are potential sources of air le 11kage must be <br />§ 110.7: caulked, gasketed, or weather stripped. <br />Insulation Certification by Manufacturers. Insulation must be certified by the Department of Consumer Affairs, B reau of Household <br />§ 110.8(a): Goods and Services BHGS <br />§ 110.8(g): Insulation Requirements for Heated Slab Floors. Heated slab floors must be insulated per the requirements of § 1OMaStpr I D <br />Roofing Products Solar Reflectance and Thermal Emittance. The thermal emittance and aged solar reflectance values of the <br />§ 110.8(1): roofing material must meet the requirements of § 110.8() and be labeled per §10-113 when the installation of a coo rogFi,, e fi is <br />on the CF1R ��,,JJ l`�� <br />§ 110.60): Radiant Barrier. When required, radiant barriers must have an emiflance of0.05 or less and be certified to the Dep rtment of Consumer <br />Affairs. <br />Roof Deck, Ceiling and Rafter Roof Insulation. Roof decks in newly constructed attics in climate zones 4 and 8-16 <br />average U -factor not exceeding U-0.184. Ceiling and rafter roofs mini mu m R-22 i nsulation in wood -frame ceiling- or area -weighted average <br />§ 150.0(a): U-factor must not exceed 0.043. Rafler roof alterations minimum R-19 or area -weighted average U-factor of 6.054 or less. Attic access <br />doors must have permanently attached insulation using adhesive or mechanical fasteners. The attic access must be gasketed to <br />prevent air leakage. Insulation must be installed in direct contact with a roof or ceiling which is sealed to limit infiltration and exfiltrationx <br />asspecified in§ 110.7 including but not limited to placing insulation either above or below the roof deck or on top of a drywall ceiling. <br />§ 150.0(b): Loose -fill Insulation. Loose fill insulation must meet the manufacturer's required density for the labeled R-value. <br />Wall Insulation. Minimum R-13 insulation in 2x4 inch wood framing wall or have a U-factor of0.102 or less, or R 20 in 2x6 inch wood <br />§ 150.0(c): framing or have a U-factor of0.071 or less. Opaque non -framed assemblies must have an overall assembly U-factor not exceeding 0.102. <br />Masonry walls must meet Tables 150.1-A or B. x <br />§ 150.0(d): <br />Raised -floor Insulation. Minimum R-19 insulation in raised wood framed floor or 0.037 maximum U-factor.' <br />Slab Edge Insulation. Slab edge insulation must meet all of the following: have a water absorption rate, for the insulation material alone <br />§ 150.0(fj: <br />without facings, no greater than 0.3 percent; have a water vapor permeance no greater than 2.0 perm per inch; be protected from <br />physical damage and UV light deterioration,- and, when installed as part of a heated slab floor, meet the requirements of § 110.8(g). <br />Vapor Retarder. In climate zones 1 through 16, the earth floor of unvented crawl space must be covered with a Class I or Class II <br />§ 150.0(g)1: <br />vapor retarder. This requirement also applies to controlled ventilation crawl space for buildings complying with the exception to <br />§150.0(d). <br />Vapor Retarder. In climate zones 14 and 16, a Class I or Class II vapor retarder must be install ed on the conditioned space side of <br />§ 150.0(g)Z <br />all insulation in all exterior walls, vented attics, and unvented attics with air -permeable insulation. <br />Fenestration Products. Fenestration, including skylights, separating conditioned space from unconditioned space or outdoors must have <br />x <br />§ 150 0(q) <br />a maximum U-factor of 0.45, or area -weighted average U-factor of all fenestration must not exceed 0.45. <br />Firanlaras f)ararativa(iasAnnlianras and Sae I nn- <br />§ 110.5(e) <br />Pilot Light. Continuously burning pilot lights are not allowed for indoor and outdoor fireplaces. <br />§ 150.0(e) I <br />Closable Doors. Masonry or factory -built fireplaces must have a closable metal or glass door covering the entire opening of the firebox. <br />§ 150.0(e)Z <br />Combustion Intake. Masonry or factory -built fireplaces must have a combustion outside air intake, which is at least six square inches in <br />area and is equipped with a readily accessible, operable, and tight-fittingtight-ftting damper or combustion -air control device. <br />§ 150.0(e)3: <br />Flue Damper. Masonry or factory -built fireplaces must have a flue damper with a readily accessible control." <br />Snare Cnnditinninn liWatPr Haatinn and Plumhinn SVStPm• <br />Certification. Heating, ventilation, and air conditioning (HVAC) equipment, wafer heaters, showerheads, faucets, and all other <br />§ 110.0-§ 110.3 <br />regulated appliances must be certified by the manufacturer to the California Energy Commission. <br />§ 110.2(a): <br />HVAC Efficiency. Equipment must meet the applicable efficiency requirements in Table 110.2-A through Table 110.2-N_ <br />Controls for Heat Pumps with Supplementary Electric Resistance Heaters. Heat pumps with supplementary electric resistance <br />§ 110.2(b): <br />heaters must have controls that prevent supplementary heater operation when the heating load can be met by the heat pump alone; <br />and in which the cut -on temperature for compression heating is higher than the cut -on temperature for supplementary heating, and <br />x <br />the cut-off temperature for compression heating is higher than the cut-off temperature for supplementary heating. <br />Thermostats. All heating or cooling systems not controlled by a central energy management control system (FMCS) must have a <br />§ 110.2(c) <br />setback thermostat. x <br />Insulation. Unfired service water heater storage tanks and solar water -heating backup tanks must have adequate insulation, or tank <br />110.3 c 3: <br />surface heat loss rating. <br />Isolation Valves. Instantaneous water heaters with an input rating greater than 6.6 kBtu per hour (2 kW) must have isolation valves with <br />§ 110.3(c)6: <br />hose bibbs or other fittings on both cold and hot water lines to allowfor flushing the water heater when the valves are closed. <br />5/6/22 <br />2022 Single -Family Residential Mandatory Requirements Summary <br />Pilot Lights. Continuously burning pilot lights are prohibited for natural gas: fan -type central furnaces- household cooking appliances <br />110 5 <br />(except appliances without an electrical supply voltage connection with pilot lights that consume less than 150 Btu per hour) - and pool and <br />spa heaters. <br />Building Cooling and Heating Loads. Heating andlor cooling loads are calculated in accordance with the ASHRAE Handbook, <br />§ 150.00)1: <br />Equipment Volume, Applications Volume, and Fundamentals Volume; the SMACNA Residential Comfort System Installation <br />Standards Manual,- or the ACCA Manual J using design conditions specified in § 150.0(h)2. <br />§ 150.0(h)3A: <br />Clearances. Air conditioner and heat pump outdoor condensing units must have a clearance of at least five feet from the outlet of any <br />dryer. <br />Liquid Line Drier. Air conditioners and heat pump systems must be equipped with liquid line filter driers if required, as specified by the <br />§ 150.0(h)3B: <br />manufacturer's instructions. <br />Water Piping, Solar Water -heating System Piping, and Space Conditioning System Line Insulation. All domestic hot water <br />150.0 011: <br />i in must be insulated asspecified in § 609.11 of the California Plumbing Code. * <br />Insulation Protection. Piping insulation must be protected from damage, including that due to sunlight, moisture, equipmenf <br />§ 150 0WZ <br />maintenance, and wind as required by §120.3(b). Insulation exposed to weather must be water retardant and protected from UV light (no <br />adhesive tapes). Insulation covering chilled water piping and refrigerant suction piping located outside theconditioned space must <br />include, or be protected by, a Class I or Class II vapor retarder. Pipe insulation buried below grade must be installed in a waterproof and <br />non -crushable casing or sleeve. <br />Gas or Propane Water Heating Systems. Systems using gas or propane water heaters to serve individual dwelling units must <br />designate a space at least 2.5' x2.5' x 7' suitable for the future installation of a heat pump water heater, and meet electrical and <br />§ 150.0(n)1: <br />plumbing requirements, based on the distance between this designated space and the water heater location; and a condensate drain no <br />more than 2' higher than the base of the water heater <br />Solar Water -heating Systems. Solar water -heating systems and collectors must be certified and rated by the Solar Rating and <br />§ 150.0(n)3: <br />Certification Corporation (SRCC), the International Association of Plumbing and Mechanical Officials, Research and Testing (IAPMO <br />R&T), or by a listing agency that is approved by the executive director. <br />Nick and Fans• <br />Ducts. Insulation installed on an existing space -conditioning duct must comply with § 604.0 of the California Mechanical Code (CMC). If a <br />§ 110.6(d)3: <br />contractor installs the insulation, the contractor must certify to the customer, in writing, that the insulation meets this requirement. <br />CMC Compliance. All air -distribution system ducts and plenums must meet CMC §§ 601.0-605.0 and ANSIISMACNA 006-2006 HVAC <br />Duct Construction Standards Metal and Flexible 3rd Edition. Portions of supply -air and return -air ducts and plenums must be insulated to <br />R-6.0 or higher; ducts located entirely in conditioned space as confirmed through field verification and diagnostic testing (RA3.1.4.3.8) <br />do not require insulation. Connections of metal ducts and inner core of flexible ducts must be mechanically fastened. Openings must be <br />sealed with mastic, tape, or other duct -closure system that meets the applicable UL requirements, or aerosol sealant that meets UL723. <br />§ 150.0(m)1: <br />The combination of mastic and either mesh or tape must be used to seal openings greater than'/4 , If mastic or tape is used. Building <br />cavities, air handler support platforms, and plenums designed or constructed with materials other than sealed sheet metal, duct board or <br />flexible duct must not be used to convey conditioned air. Building cavities and support platforms maycontain ducts,- ducts installed in <br />these spaces must not becompressed. * <br />Factory -Fabricated Duct Systems. Factory -fabricated duct systems must comply with applicable requirements for duct construction, <br />§ 150.0(m)2: <br />connections, and closures, joints and seams of duct systems and their components must not be sealed with cloth back rubber adhesive <br />duct tapes unless such toe is used in combination with mastic and draw bands. <br />Field -Fabricated Duct Systems. Field -fabricated duct systems must comply with applicable requirements for: pressure -sensitive tapes, <br />§ 150.0(m)3: <br />mastics, sealants, and other requirements specified for duct construction. <br />§ 150.0(m)7: <br />Backdraft Damper. Fan systems that exchange air between the conditioned space and outdoors must have backdrafl or automatic <br />dampers. <br />Gravity Ventilation Dampers. Gravity ventilating systems serving conditioned space must have either automatic or readily accessible, <br />§ 150.0(m)6: <br />manually operated dampers in all openings to the outside, except combustion inlet and outlet air openings and elevator shaft vents. <br />Protection of Insulation. Insulation must be protected from damage due tosunlight, moisture, equipment maintenance, and wind. <br />§ 150.0(m)a <br />Insulation exposed to weather must be suitable for outdoor service (e.g., protected by aluminum, sheet metal, painted canvas, or plastic <br />cover). Cellular foam insulation must be protected as above or painted with a water retardant and solar radiation -resistant coating. <br />§ 150.0(m)10: <br />Porous Inner Core Flex Duct. Porous inner cores of flex ducts must have a non -porous layer or air barrier between the innercore and <br />outer vapor barrier. <br />Duct System Sealing and Leakage Test. When space conditioning systems use forked air duct systems to supply conditioned air to an <br />§ 150.0(m)11: <br />occupiable space, the ducts must be sealed and duct leakage tested, as confirmed through field verification and diagnostic testing, in <br />accordance with Reference Residential Appendix RA3.1. <br />Air Filtration. Space conditioning systems with ducts exceeding 10 feet and the supply side of ventilation systems must have N1ERV 13 <br />§ 150.0(m)12: <br />or equivalent filters. Filters for space conditioning systems must have a two inch depth or can be one inch if sized per Equation 150.0-A. <br />Clean -filter pressure drop and labeling must meet the requirements in §150.0(m)12. Filters must be accessible for regular service. Filter <br />racks or grilles must use gaskets, sealing, or other means to close gaps around the inserted filters to and prevents air from bypassing the <br />filt"r " <br />516/2 2 <br />aiIdM <br />A <br />(? <br />PC 11-20-25 <br />PC2 02-10-26 <br />10 <br />ve <br />ISS <br />l� 0 <br />�o & <br />Q <br />CD <br />V V. <br />Ell�3:5 <br />H¢[rW <br />LLJ <br />U <br />L �J <br />O <br />U _J CY) cc� <br />J_ N_ <br />°o <br />U <br />M N <br />W w z w <br />co O <br />CT) a- U rz <br />C <br />DL <br />J <br />tit C 9131 <br />_31_2027� <br />OF <br />CFI. <br />LIJ <br />W <br />U <br />z <br />_Q <br />J <br />0 <br />U <br />N <br />CV <br />r- <br />z O <br />z r-- <br />CV <br />t_,_i M <br />> Q <br />Q U <br />Q <br />Q <br />Li <br />U <br />� Q <br />Q <br />DATE: 12-27-2022 <br />SCALE: AS SHOWN <br />DRAWN: <br />SL <br />JOB: 22-01-10 <br />DRAWING TITLE: <br />k6aT24 <br />:y � <br />