Tomasetti <br />PROJECT 888 N Main St Santa Ana <br />SUBJECT ASCE41-13 Alternative Methods Summary <br />PROJECT NO.S18003.00 <br />REVIEWER LJICSMP <br />DATE 6/28/2018 <br />CODE REFERENCE TOPIC RESPONSE <br />2.2 <br />2.2.3 <br />From Table C2-2, Target Building Perofrmance Levels 'c' and 'd' apply to the tower concrete <br />Performance Objective frame building structure. These levels correspond to Limited Objectives of Life Safety and <br />Collapse Prevention at the 50%/50 year Seismic Hazard Level. <br />The code lists four stipulations when achieving the Limited Performance Objective. The first three <br />Limited Performance Objectives of which are satisfied and the final will be confirmed during the on-going connection design. <br />2.3 Target Building Performance <br />Levels <br />At the 50%/50year mean recurrence interval (MRI) event, the Collapse Prevention (S-5) and Life <br />Safety (S-3) Levels will be achieved. See Table C2-4 for Concrete frames. <br />2.4.2.2 <br />3.2.1 <br />3.2.2 <br />Ground Motion Acceleration <br />Histories <br />Building Type <br />Building Configuration <br />Evaluation of the existing structure is being conducted with three separate acceleration histories <br />(each with two horizontal components) scaled to match a 100yr (39%/50yr) MRI Response <br />Spectrum. Ultimately we will use a suite of 72yr (50%/50yr) time histories as provided by the <br />geotechnical engineer. <br />Cl Classification - Concrete Moment Frames <br />The tower floor geometry is regular at all levels. Continuous concrete diaphragms are integrated <br />with perimeter moment frames with few obstructions or irregularities. <br />4.4 Tier 1 Checklist <br />Referencing the checklist for Cl Concrete Moment frames in 16.9LS in high seismicity, certain <br />applicable items are addressed below: <br />Redundancy: entire perimeter moment frame system contributes to lateral resistance. <br />Column Axial Stress Check: Under the Tier 3 Nonlinear Time History Analysis, moment frame <br />columns will be assessed under axial and fiexural combined stresses to determine adequacy. <br />Likwise, column shear stress will be evaluated. <br />Captive Columns: All perimeter columns are captured to an extent by a perimeter concrete infill <br />panel. No irregularly captured columns are present. <br />Column/Beam Bar Splices: Field testing is on-going to confirm splice extents. <br />Column Tie Spacing: With application of Fiber-Reinforced Polymer (FRP) wrap, additional column <br />confinement, shear capacity, and ductility will be provided for all columns extending from the <br />ground floor to L3. <br />Diaphragm Continuity: Visibly satisfied as mentioned above. <br />The Tier 1 checklist is used to help identify structural deficiencies in existing buildings. <br />Considering this structure's limited performance objective, the primary components of interest are <br />the tower moment frame columns: MF beams will be checked to not control due to much greater <br />effective depth. Therefore this building performance will be evaluated at a Tier 3 level for <br />Once deficiencies are identified in a Tier 1 screening, they are specifically addressed in Tier 2. In <br />the case of this project, the design team recognizes that the following potential deficiencies are to <br />5.4 Tier 2 Deficiency-Based Evaluation be evaluated within the eventual Tier 3 analysis: tower perimeter Ll -L3 column moment and <br />shear capacity, tower perimeter L3 through roof column moment and shear capacity. <br />5.4.2.2 Soft Story Irregularity <br />The nearly-double height moment frame columns extending from the ground floor the Level 3 <br />introduce a stiffness discontinuity which tends to form a soft story. The primary retrofit measure of <br />introducing strategically-positioned viscous diagonal dampers aims to mitigate this primary <br />deficiency. As mentioned above, no significant irregularities are present in this predominantly <br />symmetric, continuous structure. <br />5.5.2.1 <br />General checks to be carried out for moment frames include drifts and axial stress (in conjunction <br />with flexural). Deep perimeter moment frame beams combined with a thinner concrete infill panel <br />General Moment Frame Checks preclude this system from obeying the traditional strong column-weak beam framing proportions. <br />Thus, as noted in C5.5.2.1.5, additional column shear capacity studies will be performed via the <br />Tier 3 Nonlinear time history analyses. <br />5.5.2.3 <br />Specific checks pertaining to Concrete moment frames: No Shear Failures - per C5.5.2.3.4, <br />members that cannot develop the flexural capacity in shear shall be checked for adequacy <br />against calculated shear demands. For columns, the shear capacity is dependent upon the level <br />Concrete Moment Frame Checks of axial stress and therefore will be evaluated for all pertinent load combinations to determine the <br />most critical. Bar splices - not considered critical as 50%/50yr demand/capacity is typically well <br />below 1.0 and likely bar splice locations are at the elevations of infill panels 'capturing' columns.