HomeMy WebLinkAbout1036 W Highland St - Plan1036 W Highland
St - 2017628306/30/23
1036 W. HIGHLAND ST.
SANTA ANA, CA 92703
PHAN, CHIEU
Prepared For:
LARA SYSTEMATIC ELECTRICAL
13210 HARBOR BLVD., #215
GARDEN GROVE, CA 92843
Design Criteria
1- Code: CALIFORNIA BLDG CODE 2019 / ASCE 7-16
2 - Wind: 95 MPH, Exposure: C
3 - Wood Species: DF-L No. 2 (SG = 0.5 )
Notice: Use restrictions of these calculations.
The attached Calculations are valid only when bearing original signature hereon.
Contractor/Client to verify existing dimensions/conditions prior to construction
& solar racking is installed per manufacturer span requirements.
The use of these calculations is solely intended for the above mentioned project.
1-844-PV ELITE | info@yoursolarplans.com
3000 E. Birch Street Suite 201 | Brea CA 92821
5/12/2022
Structural Calculations for
SOLAR POWER SYSTEM CONNECTION CHECK AT:
Job:
1036 W Highland
St - 2017628306/30/23
012313342676289 8
711 1!1"#$%%&%'(2 ') $*22 &++66'20),$26%'-
./3 .8/38(3&6%/3 0.8 213
123456789:4;3<=:8
>??42@@A 26%'-
.4 .848(3&6%4
0.8
B::4?=83<2@A %%&%'(2 '4*22 &++66'20
CD2E3<=:8A &(F
G=;2@<3;HA 3633*60*232 &76270&(+IJ
K3L34? GMH2A -
>1BCNOP Q
9RS26*T,'' U
9RS30*T,&2 U
9RS06*T,&& U
9RS266*T,+2 U
RV, S +( U
RV, SS (0 U
RV, SSS 263 U
RV, SW 26' U
>1BCNOP X
9RS26*T,&3 U
9RS30*T,&( U
9RS06*T,+0 U
9RS266*T,(2 U
RV, S 266 U
RV, SS 226 U
RV, SSS*SW 220 U
>1BCNOXY
8.Z&*60- .,,+0 U
[\]^]_`ab_cdecfgb]e \]^] hiji[^]ka]fbgdl_bgb] m^amfga gn]den]db_bmb\] oga`]_ m^ gdl e]acd]gbcmdacd]_nge] e`^cdpb\]q`caecdp
fme]gemrbcmd r^mf]__st_]^__\m`aefmdkc^n gdl m`br`b mqbgcd]ek^mnb\c_bmmau cb\b\]amfga v`b\m^cblwgocdpx`^c_ecfbcmdq]km^]
r^mf]]ecdpu cb\ e]_cpds
y=@5D3=;24
,,,FUz,8.Z&,,,, ",, , {,8.Z&4
,,,,, ",,F,, |U,,4 ",, ",},
, ",,,,F,4z, ",, , ~Z7 ,,, "*,,,
,4,, ,,U,z, "UFF, ",,,,, " "*,
,,
9,4 ,4,U,4, ", ,,}U,F "
-,,FU,,, ",,,,z,,,48U,,
F,U,,,,,,,,,,F,F "
U,,,}Uz,FF4, ,,,,,F,8,
,,,FFU,,, U,FU,,F,4z ,},,,V", ,
,F,F,4,F,F,,,FF,,, ,,F,
,z, ",, 0,F,FUFU ",,U, FU, 0,F,F
",,,Uz, z, ,,,,F ,z,,F,
1036 W Highland
St - 2017628306/30/23
ASCE 29.4.4 Rooftop Solar Panels Parallel to the Roof Surface on Buildings of All Heights and Roof Slopes.
Roof Slope = 10 °
Roof Shape Gable
Tributary Width s = 4.00 ft
Tributary Length l = 2.99 ft
Effective Area A e = 11.95 ft2
Height of Structure h = 25 ft
Wind Speed V = 95 mph
Exposure Category C
Building Width B = 30 ft
Building Length L = 50 ft
Zone Width a = 3 ft
Elevation Height zg = 79 ft
Wind Directionality Kd = 0.85
Topography Factor K t = 1.00
Ground Elevation Factor Ke = 1.00
Velocity Pressure Exposure Coefficient Kz = 0.95
Velocity Pressure q z = 0.00256KzKztKdKeV 2 = 18.51 psf
Solar Array Pressure Equalization a = 0.79
Array Edge Factor E = 1.50
Zone GCp p = qz(GCp)( E)( a)
3 - -
3r 3.56 -78.24
3e 2.98 -65.56
2 - -
2r 2.98 -65.56
2e - -
2n 2.98 -65.56
1 --
1'--
1036 W Highland
St - 2017628306/30/23
LAG SCREW ANALYSIS
Loads
Wind Pressures qz = -65.56 psf
Solar Panel Load QD = 3 psf
Panel Length l = 5.975 ft
Panel Width b 3.3333 ft
Attachment Spacing s = 4 ft
Portrait
Tributary Area At = 11.95 ft2
Wind Load P W = qz * At = -783 lbs
Dead Load P D = Q D * At = 35.85 lbs
Uplift Pa = 0.6 P D + 0.6 Pw = -449 lbs
Landscape
Tributary Area At = b * s = 6.6667 ft2
Wind Load P W = qz * At = -437 lbs
Dead Load P D = Q D * At = 20 lbs
Uplift Pa = 0.6 P D + 0.6 Pw = -250 lbs
Lag Screw
Specific Gravity of Lumber SG = 0.50 (Douglas Fir-Larch)
Diameter of Lag Screw D = 5/16 in
Withdraw Design /in 1800*SG 3/2*D 3/4 = 266 lbs/in
Depth of Embedment lp = 2.50 in
Total Nominal Withdrawal Value W = W * l p = 665 lbs
Load Duration Factor CD = 1.6
Withdrawal Design Value W' = W * C D = 1064 lbs
Demand Capacity Ratio DCR = Pa / W' = 0.42 < 1 OK
1036 W Highland
St - 2017628306/30/23
ASCE 30.3.2 Design Wind Pressure Beam/ Top Chord Check
Roof Slope = 10 °
Roof Shape Gable
Tributary Width s = 2.00 ft
Tributary Length L = 17.00 ft
Effective Area A = L ( MAX [ s , L/3] ) = 96 ft2
Height of Structure h = 25 ft
Wind Speed V = 95 mph
Exposure Category C
Building Width B = 30 ft
Building Length L = 50 ft
Zone Width a = 3 ft
Elevation Height zg = 79 ft
Wind Directionality Kd = 0.85
Topography Factor Kt = 1.00
Ground Elevation Factor Ke = 1.00
Velocity Pressure Exposure Coefficient Kz = 0.95
Velocity Pressure q z = 0.00256KzKztKdKeV2 = 18.51 psf
Internal Pressure Coefficient (GCpi) = -0.18
Zone GCp p = q z [(GCp) - (Gcpi)]
3 - -
3r 1.87 -38.01
3e 2.28 -45.55
2 - -
2r 2.28 -45.55
2e - -
2n 2.28 -45.55
1 --
1'--
1036 W Highland
St - 2017628306/30/23
Beam/ Top Chord Check Lumber:
Moment Demand
# of Attachment per Rafter N A = Span : Orientation
Lenght (ft) :
Dead Load Roof Material: Q D = psf
Live Load QLr = psf
Wind Load p = psf
Snow Load QS = psf
Rafter Spacing s = in
Wind Load, Portrait Portrait UL =
Wind Load, Landscape Landscape U W =
Linear Dead Load wd = plf
Live Load wLr = plf Start ft Start ft
End ft End ft
Snow Load ws = plf Start ft Start ft
End ft End ft
Ma, Moment
D lb-ft
D+Lr lb-ft
D+S lb-ft
0.6D+0.6W lb-ft
D+0.45W+0.75Lr lb-ft
D+0.45W+0.75S lb-ft
Moment Capacity Framing Member Size Lumber Grade : DF-L No. 2
C M = 1 Ct = 1 Cr= CF = fb = psi C fu =C i =
Breadth b = in
Depth d = in
Section Modulus Sx = bd 2 / 6 = in3
Bending Stress Capacity Fb = CM * C t * Cr * C F * fb = psi Table 4.3.1 NDS 2015
Deflection Limit E = ksi I = in4
Transient Deflection in
Transient Deflection Allowed > [OKAY]
Total Deflection in
Total Deflection Allowed > [OKAY]
-45.55
DF-L No. 2
4 j lj (ft) pd,j (lbs) pw,j (lbs) ps,j (lbs)
Portrait
1 3.8 35.9 -544 0.0
8.2 35.9 -544
-544 0.0
4 14.2 35.9 -544 0.0
0.0
8.00 8.00 0.00 0.00 1.00
Portrait
3 9.8 35.9
10.00
1 2 3 4 Eave
2
0.0
0.0 0.0 0.0
0.0
0 0.0 0.0 0.0 0.0
0 0.0 0.0 0.0
0.0
0 0.0 0.0 0 0.0
Portrait
0 0.0 0.0 0
0.0
20
40
0.0 0.0 0.0 0.0
0 0.0
Portrait
0
0.0 20 -304 0
0
0.0
0
3
0
0
0.0
Portrait
3
0.0
Portrait
0 0.0 0.0
A T (ft 2)
11.95
6.6667
pd (lbs)
35.85 -544
p w (lbs) ps (lbs)
0
14.95
2x4
1.15 1.5
17.00
14.95
17.00
900
1.50
3.50
222
243
222
473
233
233
DCR
0.9 1397 psi D 871 psi 0.62
3.06
1553
CD Fb' = C D * F b ASD Load Ma / S x
1.15 1785 psi D+S 871 psi 0.49 OKAY
OKAY
1.25 1941 psi D+Lr 952 psi 0.49 OKAY
1.6 2484 psi
0.370
260 120
1600 5.36
0.6D+0.6W 1855 psi 0.75 OKAY
1.0 1
20
0.00
24
Comp
0.315
305 180
1.6 2484 psi D+0.45W+0.75S 912 psi 0.37 OKAY
1.6 2484 psi D+0.45W+0.75Lr 912 psi 0.37 OKAY
ൌ ሺ െ ሻ െ െ െ
‐600.0
‐400.0
‐200.0
0.0
200.0
400.0
600.0
0.000 5.000 10.000 15.000 20.000
1036 W Highland
St - 2017628306/30/23
EISMIC WEIGHT COMPARISON / ANALYSIS - (PER CEBC 2019 Part 10 Chapter 5 Section 502.5)
PV System Weight
Module Model REC
Panel Weight Wpanel = 45 lbs
Number of Panels NPV = 30
Total PV System Weight W PV = Wpanel * NPV = 1350 lbs
Existing Roof Weight
Roof Weight QD =10.0 psf
Building Length Lbuild =50 ft
Building Width W build =30 ft
Roof Area Abuild =1500 ft2
Building Perimeter Pbuild = 160 ft
Wall Height ht = 8 ft
Wall weight Qwall = 15 psf
Interior wall weight Qint = 10 psf
Roof Load Wfloor = Abuild * QD = 15000 lbs
Wall LoadWwall = ht /2 * Qwall * Pbuild + Abuild * Qint /2 = 17100 lbs
Total Story Weight Wbuild = Wfloor + Wwall = 32100 lbs
Percentage Weight Increase WPV / Wbuild = 4.21% < 10% OKAY
1036 W Highland
St - 2017628306/30/23
1036 W Highland
St - 2017628306/30/23
The scope of the plans is for the
installation of the solar photovoltaic
system only and the approval is subject to
compliance with all applicable city and
state codes and regulations regarding
construction. The approval of the plans
does not constitute any certification of the
accuracy, completeness, or building
permit status of the existing buildings and
structures as shown.
Bldg# 101110586
Elec# 20176283
Approved MSmith
Issued 07/01/22
1036 W Highland St
- 2017628306/30/23
1036 W Highland
St - 2017628306/30/23
1036 W Highland
St - 2017628306/30/23
1036 W Highland
St - 2017628306/30/23
1036 W Highland
St - 2017628306/30/23
1036 W Highland
St - 2017628306/30/23
1036 W Highland
St - 2017628306/30/23
1036 W Highland
St - 2017628306/30/23