PROJECT NOTES:
THIS PHOTOVOLTAIC (PV) SYSTEM SHALL COMPLY WITH THE LOCAL
ELECTRIC CODE ( ) ARTICLE 690, ALL MANUFACTURERS
LISTING AND INSTALLATION INSTRUCTIONS, AND THE RELEVANT
CODES AS SPECIFIED BY THE AUTHORITY HAVING JURISDICTIONS
(AHJ) APPLICABLE CODES.
THE UTILITY INTERCONNECTION APPLICATION MUST BE APPROVED
AND PV SYSTEM INSPECTED PRIOR TO PARALLEL OPERATION.
GROUND FAULT DETECTION AND INTERRUPTION (GFDI) DEVICE IS
INTEGRATED WITH THE MICRO INVERTER IN ACCORDANCE WITH
690.41(B).
ALL PV SYSTEM COMPONENTS, MODULES, UTILITY-INTERACTIVE
INVERTERS, AND SOURCE CIRCUIT COMBINER BOXES ARE
IDENTIFIED AND LISTED FOR USE IN PHOTOVOLTAIC SYSTEMS AS
REQUIRED BY 690.4:
PV MODULES: UL1703, IEC61730, AND IEC61215, AND NFPA 70 CLASS
C FIRE.
INVERTERS UL1741 CERTIFIED, IEEE 1547, 929, 519.
COMBINER BOX(ES): UL 1703 OR UL 1741 ACCESSORY.
MAX DC VOLTAGE CALCULATED USING MANUFACTURER PROVIDED
TEMP COEFFICIENT FOR VOC. IF UNAVAILABLE, MAX DC VOLTAGE
CALCULATED ACCORDING TO 690.7.
ALL INVERTERS, PHOTOVOLTAIC MODULES, PHOTOVOLTAIC PANELS,
AND SOURCE CIRCUIT COMBINERS INTENDED FOR USE IN A
PHOTOVOLTAIC POWER SYSTEM WILL BE IDENTIFIED AND LISTED
FOR THE APPLICATION PER 690.4 ((D). SHALL BE INSTALLED
ACCORDING TO ANY INSTRUCTIONS FROM LISTING OR LABELING
110.3.
ALL SIGNAGE WILL BE INSTALLED AS REQUIRED BY THE AND
AHJ.
WORK INCLUDED:
PV ROOF ATTACHMENTS
PV RACKING SYSTEM INSTALL ATION - EVEREST CROSSRAIL 44-X
PV MODULE AND INVERTER INSTALLATION
PV EQUIPMENT GROUNDING.
PV SYSTEM WIREING TO A ROOF-MOUNTED JUNCTION BOX.
PV LOAD CENTERS (IF INCLUDED).
PV METERING/MONITORING (IF INCLUDED).
PV DISCONNECTS.
PV FINAL COMMISSIONING.
(E) ELECTRICAL EQUIPMENT RETROFIT FOR PV
SIGNAGE PLACED IN ACCORDANCE WITH LOCAL BUILDING CODE.
PLANSET-1
SITE INFORMATION
drawn by:
sheet name:
REVISION:
sheet number:
VICTOR LARA
123 EAST ANAHURST PLACE
SANTA ANA
CALIFORNIA
92707
9/14/2022
MJ
3
COVER SHEET PS-1
TABLE OF CONTENTS:
PS-1 - COVER SHEET
PS-2 - SITE NOTES
PS-3 - SITE PLAN
PS-4 -FIRE ACCESS
PS-5 - MODULE AREA
PS-6 - RACKING DETAIL
PS-7 - ELECTRICAL LINE
PS-8 - PLACARDS
FM-1 FIELD MARKINGS
RS-1 - RS-6 - RESOURCE
DOCUMENT
SCOPE OF WORK: INSTALLATION OF UTILITY INTERACTIVE PHOTOVOLTAIC SYSTEM
4.44kW AC PHOTOVOLTAIC SOLAR ARRAY
PV MODULES: SILFAB - 370 NX
INVERTER(S): SE3800-US
ROOF TYPE: Composition Shingle
PV MOUNTING HARDWARE: QUICK BOLT (QB2) 17662 (COMP SHINGLE)
AHJ:SANTA ANA
BUILDING CODE:2019 CBC
ELECTRICAL CODE:2019 CEC
FIRE CODE:2019 CBC
RESIDENTIAL
CODE:2019 CRC
CONFIDENTIAL - THE INFORMATION
HEREIN CONTAINED SHALL NOT BE
USED FOR THE BENEFIT OF ANYONE
EXCEPT SOLID STATE ELECTRIC LLC,
NOR SHALL IT BE DISCLOSED IN
WHOLE OR IN PART TO OTHERS
OUTSIDE RECIPIENT
ORGANIZATIONS, EXCEPT IN
CONNECTION WITH THE SALE AND
USE OF THE RESPECTIVE
EQUIPMENT, WITHOUT THE WRITTEN
PERMISSION OF SOLID STATE
ELECTRIC LLC.
SOLID STATE ELECTRIC
LLC
7787 EASTGATE RD #100
HENDERSON, NV 89011
USA
CEC
CEC
CEC
CEC
CEC
CEC
MODULE QUANTITY: 12
09/19/2022
VSE Project Number: U4879.0061.221
Vector Structural Engineering has reviewed the existing
structure with loading from the solar array and screw
connections to the existing framing. The design of the
racking system, racking connections, and all other
structural is by others. Mechanical, architectural, and all
other nonstructural aspects of the design are by others.
Electrical is by others, unless stamped by Dean Levorsen.
BLDG # 101112676
ISSUED: 11/08/2022
ELECT # 20177888
ISSUED: 11/10/2022
123 E. Anahurst Pl
11/10/22
Rev: 7/15/2021
RESIDENTIAL
PHOTOVOLTAIC
CHECKLIST
SOL-01 CBC 2019
Solar Photovoltaic (PV) Checklist for Detached SINGLE FAMILY RESIDENCES Only
Instructions: The licensed contractor of record shall complete all sections, answer the ten questions and
sign the certification section below. A copy of this form shall be attached to each of TWO sets of plans, of
minimum 11” x 17” size. If answering NO to any of the questions, plan check shall be required.
Project Address:
Contractor Company Name:
Contractor License Number:
YES NO Are the following applicable to the proposed project?
1. Will the PV system layout provide the required three-foot wide clear access pathways
per Section 605.11 of the California Fire Code, and is this shown on the roof plan?
2. Will the PV system be installed on a roof having only one roofing layer with no
overlays?
3. Will the PV array be flush mounted to the existing roof so that the plane of the
modules (panels) are parallel to the plane of the roof?
4. Will the PV system weigh maximum 4 pounds per square feet or less?
5. Will the PV system be installed where the modules do not overhang any roof edges
(such as eaves, gabled ends, ridges and hips)?
6. Will the PV system be installed with a space of 2” minimum to 10” maximum between
the underside of modules and the surface of the roof?
7. Will the PV system be installed without using any ballast system or counter-weight
system?
8. Will the anchors be installed with a maximum horizontal anchor spacing of 6 feet
and is this maximum horizontal spacing shown on the plans?
9. Will the minimum 5/16” lag screws be installed with a minimum of 2-1/2 inch
embedment into roof rafters (with pre-drilled holes) and is this minimum embedment
shown on the plans?
10. Are ALL the structural pages of the plans stamped and signed by a California
licensed professional engineer? (including project specific site plan, PV layout,
anchorage spacing, anchorage details and manufacturer’s PV support information.)
I certify under penalty of perjury under the laws of the State of California that the above is true:
Print Name: Signature:
Phone Number: Date:
Email Address:
Planning & Building Agency
Building Safety Division
20 Civic Center Plaza
P.O. Box 1988 (M-19)
Santa Ana, CA 92702
(714) 647-5800
www.santa-ana.org
Solid State Electric LLC
1081695
123 E Anahurst Pl. Santa Ana, CA 92707
Isaac Thompson
435-773-0279 11/08/2022
isaac.thompson@flexenergysolar.com
123 E. Anahurst Pl
11/10/22
120/240 VAC
60HZ
SINGLE PHASE
UTILITY
SERVICE
LL
L L
N
EQUIPPED WITH RAPID
SHUTDOWN, INTEGRATED
DC DISCONNECT & ARC
FAULT PROTECTION
EGC
L2
L1
EGC
L2
L1
L2
L1
EGC
AA B
JUNCTION BOX
(OPTIONAL - FOR
CONDUCTOR SPLICE)
JUNCTION BOX
(OPTIONAL - FOR
CONDUCTOR SPLICE)
(1)
STRING
OF 12
MODULES
GN
D
N
INVERTER 1 (240V)
SOLAREDGE SE 3800H-US MODULE TYPE: SILFAB - 370 NX UL 1703
INVERTER TYPE: SE3800-US UL 1741VISIBLE LOCKABLE LABELED
PV AC DISCONNECT
30A, 240V, 2P, NON- FUSED
LOCKABLE, VISIBLE OPEN
EGC
N
L2
L1
N
N
C
GN
D
N
L2
L1
C
GEC
N
EGC
C
(N) SECONDARY POWER
SOURCE (PV OCPD) TO
BE LOCATED AT
OPPOSITE END OF
BUSBAR FROM PRIMARY
SOURCE (MAIN OCPD)
(NEC 705.12)
(E) GROUNDING
ELECTRODE
SYSTEM
LOAD-SIDE SOURCE CONNECTION
SUBPANEL BUSBAR PLUG-IN TYPE BREAKER
(NEC 705.12)
(E)LOADS
(E)LOADS
GN
D
N
L2
L1
N
EGC
(E)125A/2P
(N)20A/2P
(E)125A SUBPANEL
(E)125A MAIN SERVICE PANEL
(E)125A/2P MAIN DISCONNECT
1081695
CONTRACTOR LICENSE
NUMBER
PLANSET-7
SITE INFORMATION
drawn by:
sheet name:
REVISION:
sheet number:
9/14/2022
MJ
3
ELECTRICAL
LINE DIAGRAM
PS-7CONFIDENTIAL - THE INFORMATION
HEREIN CONTAINED SHALL NOT BE
USED FOR THE BENEFIT OF ANYONE
EXCEPT SOLID STATE ELECTRIC LLC,
NOR SHALL IT BE DISCLOSED IN
WHOLE OR IN PART TO OTHERS
OUTSIDE RECIPIENT
ORGANIZATIONS, EXCEPT IN
CONNECTION WITH THE SALE AND
USE OF THE RESPECTIVE
EQUIPMENT, WITHOUT THE WRITTEN
PERMISSION OF SOLID STATE
ELECTRIC LLC.
SOLID STATE ELECTRIC
LLC
7787 EASTGATE RD #100
HENDERSON, NV 89011
USA
MPU REQUIRED: NO
TAG CONDUCTOR TYPE
MINIMUM WIRE
SIZE # OF CONDUCTORS
RACEWAY/ CABLE
TYPE
MINIMUM CONDUIT
SIZE
A CABLE (USE-2)12 2 USE-2 / FREE AIR
FREE AIRBARE COPPER (EGC)6 1 BARE / FREE AIR
B CU THHN OR NM-B CABLE *10 4 EMT OR EQUIVALENT /
NM-B CABLE OR UF-B /
FLEX 3/4" INTERIOR USECU THHN OR NM-B CALBE (EGC)*10 2
C CU THHN/THWN-2 10 3
EMT OR EQUIVALENT 3/4"CU THHN/THWN-2 (EGC)10 1
AHJ:SANTA ANA
BUILDING CODE:2019 CBC
ELECTRICAL CODE:2019 CEC
FIRE CODE:2019 CBC
RESIDENTIAL
CODE:2019 CRC
VICTOR LARA
123 EAST ANAHURST PLACE
SANTA ANA
CALIFORNIA
92707
123 E. Anahurst Pl
11/10/22
123 E. Anahurst Pl
11/10/22
RS1
123 EAST ANAHURST PLACE
FRONT OF HOME
1081695
CONTRACTOR LICENSE
NUMBER
(E) MAIN SERVICE PANEL
(E) UTILITY METER /
MAIN SERVICE PANEL
(E) SUBPANEL
(N) PV LOAD CENTER
(N) PV PRODUCTION
METER
FIRE SETBACK
(N) AC DISCONNECT
(VISIBLE LOCKABLE
LABELED DISCONNECT)
(N) PV MODULE
SYSTEM LEGEND
(N) PV COMBINER PANEL
(N) JUNCTION BOX
(N) DC-DC / STRING
INVERTER
(N) MICROINVERTER
(N) DC DISCONNECT
ROOF SECTION
CRITERIA AND
SPECIFICATIONS
PLANSET-4
SITE INFORMATION
drawn by:
sheet name:
REVISION:
sheet number:
9/14/2022
MJ
3
(IRE ACCESS AND
ROO( IN(ORMATION
PS-4
all modules will be installed in compliance with fire code.2019
CBC
CONFIDENTIAL - THE INFORMATION
HEREIN CONTAINED SHALL NOT BE
USED FOR THE BENEFIT OF ANYONE
EXCEPT SOLID STATE ELECTRIC LLC,
NOR SHALL IT BE DISCLOSED IN
WHOLE OR IN PART TO OTHERS
OUTSIDE RECIPIENT
ORGANIZATIONS, EXCEPT IN
CONNECTION WITH THE SALE AND
USE OF THE RESPECTIVE
EQUIPMENT, WITHOUT THE WRITTEN
PERMISSION OF SOLID STATE
ELECTRIC LLC.
SOLID STATE ELECTRIC
LLC
7787 EASTGATE RD #100
HENDERSON, NV 89011
USA
AHJ:SANTA ANA
BUILDING CODE:2019 CBC
ELECTRICAL CODE:2019 CEC
FIRE CODE:2019 CBC
RESIDENTIAL
CODE:2019 CRC
VICTOR LARA
123 EAST ANAHURST PLACE
SANTA ANA
CALIFORNIA
92707
ROOF SECTION QUANTITY KILOWATTAGE ROOF PITCH AZIMUTH TSRF
RS1 12 4.44kW 20° 181 94%
RS2 0kW
RS3 0kW
RS4 0kW
RS5 0kW
3'-0"
3'-0"
1'-6"
1'-6"
09/19/2022
VSE Project Number: U4879.0061.221
Vector Structural Engineering has reviewed the existing
structure with loading from the solar array and screw
connections to the existing framing. The design of the
racking system, racking connections, and all other
structural is by others. Mechanical, architectural, and all
other nonstructural aspects of the design are by others.
Electrical is by others, unless stamped by Dean Levorsen.
123 E. Anahurst Pl
11/10/22
RS1
123 EAST ANAHURST PLACE
FRONT OF HOME
1081695
CONTRACTOR LICENSE
NUMBER
(E) MAIN SERVICE PANEL
(E) UTILITY METER /
MAIN SERVICE PANEL
(E) SUBPANEL
(N) PV LOAD CENTER
(N) PV PRODUCTION
METER
FIRE SETBACK
(N) AC DISCONNECT
(VISIBLE LOCKABLE
LABELED DISCONNECT)
(N) PV MODULE
SYSTEM LEGEND
(N) PV COMBINER PANEL
(N) JUNCTION BOX
(N) DC-DC / STRING
INVERTER
(N) MICROINVERTER
(N) DC DISCONNECT
PLANSET-5
SITE INFORMATION
drawn by:
sheet name:
REVISION:
sheet number:
9/14/2022
MJ
3
MODULE AREA AND
RAFTER INFORMATION
PS-5
ROOF MEMBERS
CONFIDENTIAL - THE INFORMATION
HEREIN CONTAINED SHALL NOT BE
USED FOR THE BENEFIT OF ANYONE
EXCEPT SOLID STATE ELECTRIC LLC,
NOR SHALL IT BE DISCLOSED IN
WHOLE OR IN PART TO OTHERS
OUTSIDE RECIPIENT
ORGANIZATIONS, EXCEPT IN
CONNECTION WITH THE SALE AND
USE OF THE RESPECTIVE
EQUIPMENT, WITHOUT THE WRITTEN
PERMISSION OF SOLID STATE
ELECTRIC LLC.
SOLID STATE ELECTRIC
LLC
7787 EASTGATE RD #100
HENDERSON, NV 89011
USA
AHJ:SANTA ANA
BUILDING CODE:2019 CBC
ELECTRICAL CODE:2019 CEC
FIRE CODE:2019 CBC
RESIDENTIAL
CODE:2019 CRC
FRAMING TYPE: Manufactured Wood Truss
RAFTER SIZE: 2x4
RAFTER SPACING: 24
RAFTER SPAN: 72
ROOF TYPE: Composition Shingle
SHEATHING TYPE: 7/16" OSB
STRUCTURE TYPE:Inhabited - Gable / Flat Roof
WIND EXPOSURE CATEGORY:B
NUMBER OF PV ARRAYS:1
TOTAL ROOF AREA (SQ. FT):2200
VICTOR LARA
123 EAST ANAHURST PLACE
SANTA ANA
CALIFORNIA
92707
09/19/2022
VSE Project Number: U4879.0061.221
Vector Structural Engineering has reviewed the existing
structure with loading from the solar array and screw
connections to the existing framing. The design of the
racking system, racking connections, and all other
structural is by others. Mechanical, architectural, and all
other nonstructural aspects of the design are by others.
Electrical is by others, unless stamped by Dean Levorsen.
123 E. Anahurst Pl
11/10/22
3'-9"
5'-9"
(aptos 370 watt)
dna-120-mf26-370w
1081695
CONTRACTOR LICENSE
NUMBER
*NOT TO SCALE*NOT TO SCALE
*NOT TO SCALE
LAG BOLT
EMBEDMENT: 3"
LAG BOLT
DIAMETER: 5/16"
PLANSET-6
SITE INFORMATION
drawn by:
sheet name:
REVISION:
sheet number:
VICTOR LARA
123 EAST ANAHURST PLACE
SANTA ANA
CALIFORNIA
92707
6/28/2022
MJ
1
RAC -IN) AN&
ASSEMBL; &ETAIL
PS-6
structural information:
HOME IS FRAMED WITH 2X4 TRUSSES AT 24" ON CENTER.
construction notes:
1. solar photovoltaic system to be installed on residential
structure.
2. this project has been designed in compliance with cbc section
1609 to withstand a basic wind speed of 110 mph (3 second gust),
3. connection to structure shall not be within 6" of nailing plates.
4. the solar PV installation shall not obstruct any plumbing,
mechanical or building roof vents.
5. all conductors and conduits mounted on roof shall be minimum 3
3
4" above roof surface (including cables underneath modules and
racking).
6. roof access points shall be provided per the following (cec
r324.6, cvc 3111.2.1):
located in areas not requiring placement of ground ladders over
openings such as doors or windows.
located at strong points of building construction in locations
where access point does not conflict with overhead obstructions such
as: tree limbs, wires or signs.
CONFIDENTIAL - THE INFORMATION
HEREIN CONTAINED SHALL NOT BE
USED FOR THE BENEFIT OF ANYONE
EXCEPT SOLID STATE ELECTRIC LLC,
NOR SHALL IT BE DISCLOSED IN
WHOLE OR IN PART TO OTHERS
OUTSIDE RECIPIENT
ORGANIZATIONS, EXCEPT IN
CONNECTION WITH THE SALE AND
USE OF THE RESPECTIVE
EQUIPMENT, WITHOUT THE WRITTEN
PERMISSION OF SOLID STATE
ELECTRIC LLC.
SOLID STATE ELECTRIC
LLC
7787 EASTGATE RD #100
HENDERSON, NV 89011
USA
AHJ:
BUILDING CODE:2019 CBC
ELECTRICAL CODE:2019 CEC
FIRE CODE:2019 CBC
RESIDENTIAL
CODE:2019 CRC07/07/2022
VSE Project Number: U4879.0027.221
Vector Structural Engineering has reviewed the existing
structure with loading from the solar array and screw
connections to the existing framing. The design of the
racking system, racking connections, and all other structural
is by others. Mechanical, architectural, and all other
nonstructural aspects of the design are by others. Electrical
is by others, unless stamped by Dean Levorsen.
123 E. Anahurst Pl
11/10/22
RS1
123 EAST ANAHURST PLACE
FRONT OF HOME
1081695
CONTRACTOR LICENSE
NUMBER
PLANSET-3
SITE INFORMATION
drawn by:
sheet name:
REVISION:
sheet number:
9/14/2022
MJ
3
sKte RNan
PS-3CONFIDENTIAL - THE INFORMATION
HEREIN CONTAINED SHALL NOT BE
USED FOR THE BENEFIT OF ANYONE
EXCEPT SOLID STATE ELECTRIC LLC,
NOR SHALL IT BE DISCLOSED IN
WHOLE OR IN PART TO OTHERS
OUTSIDE RECIPIENT
ORGANIZATIONS, EXCEPT IN
CONNECTION WITH THE SALE AND
USE OF THE RESPECTIVE
EQUIPMENT, WITHOUT THE WRITTEN
PERMISSION OF SOLID STATE
ELECTRIC LLC.
SOLID STATE ELECTRIC
LLC
7787 EASTGATE RD #100
HENDERSON, NV 89011
USA
AHJ:SANTA ANA
BUILDING CODE:2019 CBC
ELECTRICAL CODE:2019 CEC
FIRE CODE:2019 CBC
RESIDENTIAL
CODE:2019 CRC
VICTOR LARA
123 EAST ANAHURST PLACE
SANTA ANA
CALIFORNIA
92707
31'-6"
11'-2"
16'-8"
16'-4"
09/19/2022
VSE Project Number: U4879.0061.221
Vector Structural Engineering has reviewed the existing
structure with loading from the solar array and screw
connections to the existing framing. The design of the
racking system, racking connections, and all other
structural is by others. Mechanical, architectural, and all
other nonstructural aspects of the design are by others.
Electrical is by others, unless stamped by Dean Levorsen.
123 E. Anahurst Pl
11/10/22
1081695
CONTRACTOR LICENSE
NUMBER
RESOURCE -1
SITE INFORMATION
drawn by:
sheet name:
REVISION:
sheet number:
9/14/2022
MJ
3
MO&ULE S2EC
S*EET
RS-1CONFIDENTIAL - THE INFORMATION
HEREIN CONTAINED SHALL NOT BE
USED FOR THE BENEFIT OF ANYONE
EXCEPT SOLID STATE ELECTRIC LLC,
NOR SHALL IT BE DISCLOSED IN
WHOLE OR IN PART TO OTHERS
OUTSIDE RECIPIENT
ORGANIZATIONS, EXCEPT IN
CONNECTION WITH THE SALE AND
USE OF THE RESPECTIVE
EQUIPMENT, WITHOUT THE WRITTEN
PERMISSION OF SOLID STATE
ELECTRIC LLC.
SOLID STATE ELECTRIC
LLC
7787 EASTGATE RD #100
HENDERSON, NV 89011
USA
VICTOR LARA
123 EAST ANAHURST PLACE
SANTA ANA
CALIFORNIA
92707
123 E. Anahurst Pl
11/10/22
1081695
CONTRACTOR LICENSE
NUMBER
RESOURCE - 2
SITE INFORMATION
drawn by:
sheet name:
REVISION:
sheet number:
9/14/2022
MJ
3
INVERTER S2EC
S*EET
RS-2CONFIDENTIAL - THE INFORMATION
HEREIN CONTAINED SHALL NOT BE
USED FOR THE BENEFIT OF ANYONE
EXCEPT SOLID STATE ELECTRIC LLC,
NOR SHALL IT BE DISCLOSED IN
WHOLE OR IN PART TO OTHERS
OUTSIDE RECIPIENT
ORGANIZATIONS, EXCEPT IN
CONNECTION WITH THE SALE AND
USE OF THE RESPECTIVE
EQUIPMENT, WITHOUT THE WRITTEN
PERMISSION OF SOLID STATE
ELECTRIC LLC.
SOLID STATE ELECTRIC
LLC
7787 EASTGATE RD #100
HENDERSON, NV 89011
USA
VICTOR LARA
123 EAST ANAHURST PLACE
SANTA ANA
CALIFORNIA
92707
123 E. Anahurst Pl
11/10/22
1081695
CONTRACTOR LICENSE
NUMBER
RESOURCE - 3
SITE INFORMATION
drawn by:
sheet name:
REVISION:
sheet number:
9/14/2022
MJ
3
COMBINER BO:
S2EC S*EET
RS-3CONFIDENTIAL - THE INFORMATION
HEREIN CONTAINED SHALL NOT BE
USED FOR THE BENEFIT OF ANYONE
EXCEPT SOLID STATE ELECTRIC LLC,
NOR SHALL IT BE DISCLOSED IN
WHOLE OR IN PART TO OTHERS
OUTSIDE RECIPIENT
ORGANIZATIONS, EXCEPT IN
CONNECTION WITH THE SALE AND
USE OF THE RESPECTIVE
EQUIPMENT, WITHOUT THE WRITTEN
PERMISSION OF SOLID STATE
ELECTRIC LLC.
SOLID STATE ELECTRIC
LLC
7787 EASTGATE RD #100
HENDERSON, NV 89011
USA
VICTOR LARA
123 EAST ANAHURST PLACE
SANTA ANA
CALIFORNIA
92707
123 E. Anahurst Pl
11/10/22
1081695
CONTRACTOR LICENSE
NUMBER
RESOURCE - 4
SITE INFORMATION
drawn by:
sheet name:
REVISION:
sheet number:
9/14/2022
MJ
3
RAILIN) S2EC
S*EET
RS-4CONFIDENTIAL - THE INFORMATION
HEREIN CONTAINED SHALL NOT BE
USED FOR THE BENEFIT OF ANYONE
EXCEPT SOLID STATE ELECTRIC LLC,
NOR SHALL IT BE DISCLOSED IN
WHOLE OR IN PART TO OTHERS
OUTSIDE RECIPIENT
ORGANIZATIONS, EXCEPT IN
CONNECTION WITH THE SALE AND
USE OF THE RESPECTIVE
EQUIPMENT, WITHOUT THE WRITTEN
PERMISSION OF SOLID STATE
ELECTRIC LLC.
SOLID STATE ELECTRIC
LLC
7787 EASTGATE RD #100
HENDERSON, NV 89011
USA
VICTOR LARA
123 EAST ANAHURST PLACE
SANTA ANA
CALIFORNIA
92707
123 E. Anahurst Pl
11/10/22
1081695
CONTRACTOR LICENSE
NUMBER
RESOURCE -5
SITE INFORMATION
drawn by:
sheet name:
REVISION:
sheet number:
9/14/2022
MJ
3
ANC*OR S2EC
S*EET
RS-5CONFIDENTIAL - THE INFORMATION
HEREIN CONTAINED SHALL NOT BE
USED FOR THE BENEFIT OF ANYONE
EXCEPT SOLID STATE ELECTRIC LLC,
NOR SHALL IT BE DISCLOSED IN
WHOLE OR IN PART TO OTHERS
OUTSIDE RECIPIENT
ORGANIZATIONS, EXCEPT IN
CONNECTION WITH THE SALE AND
USE OF THE RESPECTIVE
EQUIPMENT, WITHOUT THE WRITTEN
PERMISSION OF SOLID STATE
ELECTRIC LLC.
SOLID STATE ELECTRIC
LLC
7787 EASTGATE RD #100
HENDERSON, NV 89011
USA
VICTOR LARA
123 EAST ANAHURST PLACE
SANTA ANA
CALIFORNIA
92707
123 E. Anahurst Pl
11/10/22
Expedited Permit Process for PV Systems1
Expedited Permit Process for PV Systems
Standard String System
The Solar America Board for Codes and Standards (Solar ABCs) Expedited Permit Pro-
cess provides a means to differentiate systems that can be permitted quickly and easily
due to their similarity with the majority of small-scale PV systems. Those systems with
unique characteristics may be handled with small additions to this Expedited Permit
Process or may require much more information, depending on the uniqueness of the
installation.
The following pages contain forms for the Standard String System to use with the Expe-
dited Permit Process. The Micro-Inverter, AC Module, and Supply-Side Connection forms
are also available as interactive PDF files at www.solarabcs.org/permitting. In jurisdic-
tions that have adopted the Expedited Permit Process for PV Systems, these forms can
be filled out electronically and submitted in either printed form and via email. An elec-
tronic format is used so that the supplied information is standardized and legible for the
local jurisdiction.
123 E. Anahurst Pl
11/10/22
Expedited Permit Process for PV Systems2
Expedited Permit Process for Small-Scale PV Systems
Standard String System
The information in this guideline is intended to help local jurisdictions and contractors identify when PV system installations
are simple, needing only a basic review, and when an installation is more complex. It is likely that 50%-75% of all residential
systems will comply with these simple criteria. For projects that fail to meet the simple criteria, resolution steps have been
suggested to provide as a path to permit approval.
Required Information for Permit:
1. Site plan showing location of major components on the property. This drawing need not be exactly to scale, but it
should represent relative location of components at site (see supplied example site plan). PV arrays on dwellings
with a 3’ perimeter space at ridge and sides may not need separate fire service review.
2. Electrical diagram showing PV array configuration, wiring system, overcurrent protection, inverter, disconnects,
required signs, and ac connection to building (see supplied standard electrical diagram).
3. Specification sheets and installation manuals (if available) for all manufactured components including, but not
limited to, PV modules, inverter(s), combiner box, disconnects, and mounting system.
Step 1: Structural Review of PV Array Mounting System
Is the array to be mounted on a defined, permitted roof structure? l Yes l No
If No due to non-compliant roof or a ground mount, submit completed worksheet for the structure WKS1.
Roof Information:
1. Is the roofing type lightweight (Yes = composition, lightweight masonry, metal, etc…)__________________________
____________________________________________________________________________________________________
If No, submit completed worksheet for roof structure WKS1 (No = heavy masonry, slate, etc…).
2. Does the roof have a single roof covering? l Yes l No
If No, submit completed worksheet for roof structure WKS1.
3. Provide method and type of weatherproofing roof penetrations (e.g. flashing, caulk).____________________________
Mounting System Information:
1. Is the mounting structure an engineered product designed to mount PV modules with no more than an 18” gap
beneath the module frames? l Yes l No
If No, provide details of structural attachment certified by a design professional.
2. For manufactured mounting systems, fill out information on the mounting system below:
a. Mounting System Manufacturer ___________Product Name and Model#________________________________
b. Total Weight of PV Modules and Rails ___________lbs
c. Total Number of Attachment Points____________
d. Weight per Attachment Point (b÷c)_________________lbs (if greater than 45 lbs, see WKS1)
e. Maximum Spacing Between Attachment Points on a Rail ______________inches (see product manual for
maximum spacing allowed based on maximum design wind speed)
f. Total Surface Area of PV Modules (square feet)_________________ ft 2
g. Distributed Weight of PV Module on Roof (b÷f)_______________ lbs/ft2
If distributed weight of the PV system is greater than 5 lbs/ft2, see WKS1.
Step 2: Electrical Review of PV System (Calculations for Electrical Diagram)
In order for a PV system to be considered for an expedited permit process, the following must apply:
1. PV modules, utility-interactive inverters, and combiner boxes are identified for use in PV systems.
2. The PV array is composed of 4 series strings or less per inverter.
3. The total inverter capacity has a continuous ac power output 13,440 Watts or less
4. The ac interconnection point is on the load side of service disconnecting means (690.64(B)).
5. One of the standard electrical diagrams (E1.1, E1.1a, E1.1b, or E1.1c) can be used to accurately represent the PV
system. Interactive PDF diagrams are available at www.solarabcs.org/permitting.
Fill out the standard electrical diagram completely. A guide to the electrical diagram is provided to help the applicant
understand each blank to fill in. If the electrical system is more complex than the standard electrical diagram can effectively
communicate, provide an alternative diagram with appropriate detail.
4
Yes
4
flashing
4
K2 CrossRail 44-X
563
27
21
6
485
5
123 E. Anahurst Pl
11/10/22
RS1
123 EAST ANAHURST PLACE
FRONT OF HOME
STANDARD STRING SYSTEM SITE PLAN
EX
P
E
D
I
T
E
D
P
E
R
M
I
T
P
R
O
C
E
S
S
F
O
R
P
V
S
Y
S
T
E
M
S
CONTRACTOR NAME.
ADDRESS AND PHONE: SITE PLAN FOR SMALL-SCALE, SINGLE-PHASE PV
SYSTEMS
SITE NAME: VICTOR LARA
SITE ADDRESS: 123 EAST ANAHURST PLACE
SYSTEM AC
SIZE:3.48
DRAWN BY: MJ SIZE 3.48 FSCM NO:
DWG NO:
1 REV: 3
CHECKED BY: MJ SCALE DATE: 44818 SHEET: 1
123 E. Anahurst Pl
11/10/22
CONTRACTOR NAME.
ADDRESS AND PHONE:
SITE PLAN FOR SMALL-SCALE, SINGLE-PHASE PV
SYSTEMS
SITE NAME:VICTOR LARA
SITE ADDRESS:123 EAST ANAHURST PLACE
SYSTEM AC SIZE:3.48
DRAWN BY: MJ SIZE 3.48 FSCM NO:DWG NO: 1 REV:3
CHECKED BY: MJ SCALE DATE:44818 SHEET:1
STANDARD STRING SYSTEM SITE PLAN
EX
P
E
D
I
T
E
D
P
E
R
M
I
T
P
R
O
C
E
S
S
F
O
R
P
V
S
Y
S
T
E
M
S
CONDUIT AND CONDUCTOR SCHEDULE
TAG DESCRIPTION OR CONDUCTOR TYPE COND. NUMBER OF CONDUIT CONDUIT
GAUGE CONDUCTOR TYPE SIZE
1 USE-2 √ OR PV WIRE 12 2 N/A N/A
BARE COPPER EQ. GRD. COND. (EGC)6 1 N/A N/A
2 THWN-2 √ OR XHHW-2 OR RHW-2 10 4
EMT OR EQUIVALENT / NM-B
CABLE OR UF-B / FLEX
3 THWN-2 √ OR XHHW-2 OR RHW-2 10 2 0
3/4"
INTERIOR USE
INSULATED EGC 10 3 0
4 DC GROUNDING ELECTRODE COND.10 10 EMT OR EQUIVALENT 3/4"
5 THWN-2 √ OR XHHW-2 OR RHW-2 10 1 0 0
INSULATED EGC
EQUIPMENT SCHEDULE
TAG DESCRIPTION PART NUMBER NOTES
1 SOLAR PV MODULE SILFAB - 370 NX
2 PV ARRAY 1
3 J-BOX (IF USED) 2IH5-2
4 COMBINER (IF USED) X-IQ-AM1-240-4
5 DC DICSONNECT
6 DC/AC INVERTER SE3800-US
7 GEN METER (IF USED)
8
AC DISCONNECT (IF
USED) DG222URB
9 SERVICE PANEL EATON 240 VAC, 125 A MAIN, 125 A BUS, A INVERTER OCPD
(SEE NOTE 5 FOR INVERTER OCPDs, ALSO SEE GUEID SECTION 9)
INVERTER
OCPD
BUILDING
GROUDING
ELECTRODE
DISREGARD IF
PROVIDED
WITH
INVERTER
FOR UNUSED SERIES STRINGS
PUT "N/A" IN BLANK ABOVE
SEE GUIDE APPENDIX C FOR
INFORMATION ON MODULE
AND ARRAY GROUNDING
12MODULES IN
SERIES SOURCE-CIRCUIT
----MODULES IN
SERIES SOURCE-CIRCUIT
----MODULES IN
SERIES SOURCE-CIRCUIT
----MODULES IN
SERIES SOURCE-CIRCUIT
AC
DC
1 2 3 4 5 6 7 8 9
M
1 2 3
4
5
M
COMBINERJ-BOX
DC DISCO
INVERTER
AC DISCO
MAIN
OCPD
123 E. Anahurst Pl
11/10/22
STANDARD STRING SYSTEM SITE PLAN
EX
P
E
D
I
T
E
D
P
E
R
M
I
T
P
R
O
C
E
S
S
F
O
R
P
V
S
Y
S
T
E
M
S
NOTES FOR ALL DRAWINGS:
OCPD = OVERCURRENT PROTECTION DEVICE
NATIONAL ELECTRICAL CODE REFERENCES
SHOWN AS (NEC XXX.XX)
1.) LOWEST EXPECT AMBIENT TEMPERATURE BASED ON ASHRAE MINIMUM MEAN
EXTREME DRY BULB TEMPERATURE FOR ASHRAE LOCATION MOST SIMILAR TO
INSTALLATION LOCATION. LOWEST EXPECTED AMBIENT TEMP 8.3°C
2.) highest continuous ambient temperature based on ashrae highest moth 2% dry bulb
temperature for ashrae location most similar to installation location. highest
continuous temperature 27°C
3.) 2005 ASHRAE FUNDAMENTALS 2% DESIGN TEMPERATURE DO NOT EXCEED 47%°C
IN THE UNITED STATES (PAL SPRINGS, CA IS 44.1°C) FOR LESS THAN 9
CURRENT-CARRYING CONDUCTORS IN ROOF-MOUNTED SUNLIT CONDUIT AT LEAST .05"
ABOVE ROOF AND USING THE OUTDOOR DESIGN TEMPERATURE FO 47°C OR LESS (ALL
OF THE UNITED STATES
A) 12 AWG, 90°C CONDUCTORS ARE GENERALLY ACCEPTABLE FOR MODULES WITH
ISC OF 7.68 AMPS OR LESS WHEN PROTECTED BY A 12-AMP OR SMALLER FUSE.
B) 10 AWG, 90°C CONDUCTORS ARE GENERALLY ACCEPTABLE FOR MODULES WITH
ISC OF 9.6 AMPS OR LESS WHEN PROTECTED BY A 15-AMP OR SMALLER FUSE.
NOTES FOR ARRAY CIRCUIT WIRING (GUIDE SECTION 6 AND 8 AND APPENDIX D):
1) IF UTILITY REQUIRES A VISIBLE-BREAK SWITCH, DOES THIS SWITCH MEET
THE REQUIREMENTS? YES NO N/A√
2) IF GENERATION METER REQUIRED, DOES THIS METER SOCKET MEET THE
REQUIREMENT? YES NO N/A √
3) SIZE PHOTOVOLTAIC POWER SOURCE (DC) CONDUCTORS BASED ON MAX
CURRENT ON NEC 690.53 SIGN OR OCPD RATING AT DISCONNECT
4) SIZE INVERTER OUTPUT CIRCUIT (AC) CONDUCTORS ACCORDING TO
INVERTER OCPD AMPERE RATING. (SEE GUIDE SECTION 9)
5) TOTAL OF 1 INVERTER OCPD(S), ONE FOR EACH INVERTER. DOES TOTAL
SUPPLY BREAKERS COMPLY WITH 120% BUSBAR EXCEPTION IN
690.64(B)(2)(A)? YES √ NO
NOTES FOR INVERTER CIRCUITS (GUIDE SECTION 8 AND 9):
PHOTOVOLTAIC POWER
SOURCE
RATED IMPP
CURRENT A
RATED IMPP
VOLTAGE V
MAX SYSTEM
VOLTAGE V
MAX CIRCUIT
CURRENT A
WARNING: ELECTRICAL SHOT
HAZARD-LINE AND LOAD MAY BE
ENERGIZED IN OPEN POSITION
SOLAR PV SYSTEM AC POINT
OF CONNECTION
AC OUTPUT
CURRENT 60A
NOMINAL AC
VOLTAGE 240V
THIS PANEL FED BY MULTIPLE
SOURCES (UTILITY AND SOLAR)
SIGN FOR INVERTER OCPD AND AC
DISCONNECT (IF USED)
SIGN FOR DC DISCONNECT
SIGNS-SEE GUIDE SECTION 7
CONTRACTOR NAME.
ADDRESS AND PHONE: SITE PLAN FOR SMALL-SCALE, SINGLE-PHASE PV
SYSTEMS
SITE NAME: VICTOR LARA
SITE ADDRESS: 123 EAST ANAHURST PLACE
SYSTEM AC
SIZE:3.48
DRAWN BY: MJ SIZE 3.48 FSCM NO:
DWG NO:
1 REV: 3
CHECKED BY: MJ SCALE DATE: 44818 SHEET: 1
PV MODULE RATING @ STC (GUIDE SECTION 5)
MODULE MAKE SILFAB - 370 NX
MODULE MODEL SILFAB - 370 NX
MAX PWER-POINT CURRENT (IMP) 20A
MAX POWER-POINT VOLTAGE (VMP) 1000V
OPEN-CIRCUIT CURRENT (VOC) 40.8V
SHORT-CIRCUIT CURRENT (ISC) 11.51A
MAX SERIES FUSE (ISC) 25A
MAXIMUM POWER (PMAX) 370
MAX VOLTAGE (TYP 600VDC) 34.06V
VOC TEMP COEFF (mV/°C OR %/°C√) -0.29
INVERTER RATING (GUIDE SECTION 4)
INVERTER MAKE SE3800-US
INVERTER MODEL SE3800-US
MAX DC VOLT RATING 480V
MAX POWER @ 40°C 93000W
NOMINAL AC VOLTAGE 240V
MAX AC CURRENT 25A
MAX OCPD RATING 25A