HomeMy WebLinkAbout1238 S Cypress - Plan1238 S Cypress -
2017784102/16/23
SPEC SHEET
ADDRESS:1238 CYPRESS AVENUE,
SANTA ANA, CA 92707
33.732077, -117.866857
APN:014-01-116
CUSTOMER INFORMATION
NAME:VICTOR BALLINAS
DATE:10/4/2022
SCALE:AS NOTED REV:A
AHJ:CA - CITY OF SANTA ANA
UTILITY:SCE
PRN NUMBER:MAS-64171
DRAFTED BY:
M.SAILESH
QC'ED BY:H.RAJ
PAPER SIZE:17"X11"
SOLARPLEX LLC
Dba MARAVILLA CONSTRUCTION
License#:1056065
5902 FIRESTONE BLVD
SOUTH GATE, CA 90280
TEL:(562) 806-6000
FAX:(562) 806-4006
RAIL SPEC SHEET
SS-05
1238 S Cypress -
2017784102/16/23
MSP CBAC PM CB AC
WARNING PLACARD
ADDRESS:1238 CYPRESS AVENUE,
SANTA ANA, CA 92707
33.732077, -117.866857
APN:014-01-116
CUSTOMER INFORMATION
NAME:VICTOR BALLINAS
DATE:10/4/2022
SCALE:AS NOTED REV:A
AHJ:CA - CITY OF SANTA ANA
UTILITY:SCE
PRN NUMBER:MAS-64171
DRAFTED BY:
M.SAILESH
QC'ED BY:H.RAJ
PAPER SIZE:17"X11"
SOLARPLEX LLC
Dba MARAVILLA CONSTRUCTION
License#:1056065
5902 FIRESTONE BLVD
SOUTH GATE, CA 90280
TEL:(562) 806-6000
FAX:(562) 806-4006
WARNING PLACARDS -1
PL-01
POWER TO THIS BUILDING IS ALSO
SUPPLIED FROM THE FOLLOWING
SOURCES WITH DISCONNECTS LOCATED
AS SHOWN
!
ELECTRIC SHOCK HAZARD
THE DC CONDUCTORS OF THIS PHOTOVOLTAIC
SYSTEM ARE UNGROUNDED AND MAY BE
ENERGIZED
LABEL LOCATION
DC DISCONNECT,INVERTER
[To be used when inverter is
ungrounded]
WARNING!
ELECTRIC SHOCK HAZARD
DO NOT TOUCH TERMINALS
TERMINALS ON BOTH LINE AND LOAD SIDES
MAY BE ENERGIZED IN THE OPEN POSITION
WARNING
LABEL LOCATION
AC DISCONNECT,
POINT OF INTERCONNECTION
PER CODE: CEC 690.13(B)
!
WARNING-ELECTRIC SHOCK HAZARD
NO USER SERVICEABLE PARTS INSIDE
CONTACT AUTHORIZED SERVICE
PROVIDE FOR ASSISTANCE
LABEL LOCATION
INVERTER, JUNCTION BOXES(ROOF),
AC DISCONNECT
WARNING:PHOTOVOLTAIC
POWER SOURCE
LABEL LOCATION
CONDUIT, COMBINER BOX
PER CODE: CEC690.31(G)(3)
LABEL LOCATION
AC DISCONNECT, POINT OF INTERCONNECTION
PER CODE: CEC 690.54
RATED AC OPERATING CURRENT
AC NOMINAL OPERATING VOLTAGE
18.15
240
AMPS AC
VAC
PHOTOVOLTAIC SYSTEM AC DISCONNECT SWITCH
LABEL LOCATION
POINT OF INTERCONNECTION
PER CODE: CEC 705.12(B)(2)(3)(b)
WARNING
POWER SOURCE OUTPUT
CONNECTION
DO NOT RELOCATE THIS
OVER-CURRENT DEVICE
CAUTION: SOLAR CIRCUIT
LABEL LOCATION
MARKINGS PLACED ON ALL INTERIOR AND EXTERIOR
DC CONDUIT, RACEWAYS, ENCLOSURES AND CABLE
ASSEMBLES AT LEAST EVERY 10 FT, AT TURNS AND
ABOVE/BELOW PENETRATIONS AND ALL
COMBINER/JUNCTION BOXES.
PER CODE: CEC690.31(G)(3)
SOLAR DISCONNECT
LABEL LOCATION
DISCONNECT, POINT OF INTERCONNECTION
PER CODE: CEC690.31(B)
CAUTION: SOLAR ELECTRIC
SYSTEM CONNECTED
LABEL LOCATION
PLACED WITHIN THE MAIN SERVICE
DISCONNECT,
PLACED ON THE OUTSIDE OF THE COVER
WHEN DISCONNECT IS OPERATED WITH THE
SERVICE PANEL CLOSED.
PER CODE: CEC690.15 ,690.13(B)
TURN RAPID SHUTDOWN
SWITCH TO THE
"OFF" POSITION TO
SHUT DOWN PV SYSTEM
AND REDUCE
SHOCK HAZARD
IN THE ARRAY
SOLAR ELECTRIC
PV PANELS
SOLAR PV SYSTEM EQUIPPED
WITH RAPID SHUTDOWN
LABEL LOCATION
AC DISCONNECT, DC DISCONNECT,
POINT OF INTERCONNECTION
PER CODE: CEC690.56(C)(1)(a)
!!CAUTION:MULTIPLE SOURCES
OF POWER
NOTES:
ALL PLACARDS SHALL BE OF WEATHER PROOF CONSTRUCTION, BACKGROUND ON ALL PLACARDS SHALL BE
RED WITH WHITE LETTERING U.O.N.
PLACARD SHALL BE MOUNTED DIRECTLY ON THE EXISTING UTILITY ELECTRICAL SERVICE.
FASTENERS APPROVED BY THE LOCAL JURISDICTION
LABEL LOCATION
SERVICE PANEL
PER CODE: CEC 705.10
1238 CYPRESS AVENUE, SANTA ANA, CA 92707
SYSTEM UTILIZES MICRO-INVERTERS LOCATED UNDER EACH SOLAR MODULE
LABEL LOCATION
POINT OF INTERCONNECTION
PER CODE: CEC705.12(B)(3-4) AND 690.59
WARNING
DUAL POWER SOURCE SECOND
SOURCE IS PHOTOVOLTAIC
SYSTEM
!
RAPID SHUTDOWN
SWITCH FOR SOLAR PV
SYSTEM
LABEL LOCATION
INVERTER
PER CODE: CEC 690.56(C)(3)
(N)SOLAR PHOTOVOLTAIC
ARRAYS ON ROOF
(E)SOLAR PHOTOVOLTAIC
ARRAYS ON ROOF(E)UTILITY METER WITH
(E) MAIN SERVICE PANEL
(N) AC DISCONNECT
(N) ENPHASE COMBINER 4
(E) LOAD COMBINER
(E) PRODUCTION METER
(E) AC DISCONNECT
1238 S Cypress -
2017784102/16/23
SPEC SHEET
ADDRESS:1238 CYPRESS AVENUE,
SANTA ANA, CA 92707
33.732077, -117.866857
APN:014-01-116
CUSTOMER INFORMATION
NAME:VICTOR BALLINAS
DATE:10/4/2022
SCALE:AS NOTED REV:A
AHJ:CA - CITY OF SANTA ANA
UTILITY:SCE
PRN NUMBER:MAS-64171
DRAFTED BY:
M.SAILESH
QC'ED BY:H.RAJ
PAPER SIZE:17"X11"
SOLARPLEX LLC
Dba MARAVILLA CONSTRUCTION
License#:1056065
5902 FIRESTONE BLVD
SOUTH GATE, CA 90280
TEL:(562) 806-6000
FAX:(562) 806-4006
MODULE SPEC SHEET
SS-01
1238 S Cypress -
2017784102/16/23
SPEC SHEET
ADDRESS:1238 CYPRESS AVENUE,
SANTA ANA, CA 92707
33.732077, -117.866857
APN:014-01-116
CUSTOMER INFORMATION
NAME:VICTOR BALLINAS
DATE:10/4/2022
SCALE:AS NOTED REV:A
AHJ:CA - CITY OF SANTA ANA
UTILITY:SCE
PRN NUMBER:MAS-64171
DRAFTED BY:
M.SAILESH
QC'ED BY:H.RAJ
PAPER SIZE:17"X11"
SOLARPLEX LLC
Dba MARAVILLA CONSTRUCTION
License#:1056065
5902 FIRESTONE BLVD
SOUTH GATE, CA 90280
TEL:(562) 806-6000
FAX:(562) 806-4006
INVERTER SPEC SHEET
SS-02
1238 S Cypress -
2017784102/16/23
SPEC SHEET
ADDRESS:1238 CYPRESS AVENUE,
SANTA ANA, CA 92707
33.732077, -117.866857
APN:014-01-116
CUSTOMER INFORMATION
NAME:VICTOR BALLINAS
DATE:10/4/2022
SCALE:AS NOTED REV:A
AHJ:CA - CITY OF SANTA ANA
UTILITY:SCE
PRN NUMBER:MAS-64171
DRAFTED BY:
M.SAILESH
QC'ED BY:H.RAJ
PAPER SIZE:17"X11"
SOLARPLEX LLC
Dba MARAVILLA CONSTRUCTION
License#:1056065
5902 FIRESTONE BLVD
SOUTH GATE, CA 90280
TEL:(562) 806-6000
FAX:(562) 806-4006
COMBINER SPEC SHEET
SS-03
1238 S Cypress -
2017784102/16/23
SPEC SHEET
ADDRESS:1238 CYPRESS AVENUE,
SANTA ANA, CA 92707
33.732077, -117.866857
APN:014-01-116
CUSTOMER INFORMATION
NAME:VICTOR BALLINAS
DATE:10/4/2022
SCALE:AS NOTED REV:A
AHJ:CA - CITY OF SANTA ANA
UTILITY:SCE
PRN NUMBER:MAS-64171
DRAFTED BY:
M.SAILESH
QC'ED BY:H.RAJ
PAPER SIZE:17"X11"
SOLARPLEX LLC
Dba MARAVILLA CONSTRUCTION
License#:1056065
5902 FIRESTONE BLVD
SOUTH GATE, CA 90280
TEL:(562) 806-6000
FAX:(562) 806-4006
MOUNT SPEC SHEET
SS-04
1238 S Cypress -
2017784102/16/23
(1) BRANCH OF (8) MICRO-INVERTERS
(1) BRANCH OF (7) MICRO-INVERTERS
1
(N)(15)HANWHA Q CELL QPEAK DUO BLK ML-G10+ 400W
MODULES WITH
(15)ENPAHSE IQ8PLUS-72-2-US(240V)(SI-1)
(N)JUNCTION
BOX
2
ENPHASE Q CABLE
DC CONDUCTORS
AC CONDUCTORS
3
(N)30A AC
DISCONNECT
AC DISCONNECT
NON FUSED 30A,
120/240V, 2P
(N)ENPHASE IQ
COMBINER 4
20A
20A
ENPHASE COMBINER BOX
X-IQ-AM1-240-4 120/240
NEMA 3R INSTALL
(2)20A PV 2P BREAKERS
(ONLY FOR SOLAR, NO
LOADS TO BE ADDED)
(E)(20)HYUNDAI HIS-S260RG 260W MODULES WITH
(E)(20)ENPHASE M215-60-2LL-S22/23-IG(240V)
(E)JUNCTION
BOX
E E
ENPHASE Q CABLE
DC CONDUCTORS
AC CONDUCTORS
E
(E)30A AC
DISCONNECT
AC DISCONNECT
NON FUSED 60A,
120/240V, 2P
(E)LOAD COMBINER
30A
3
INSTALL (1)30A PV 2P
BREAKERS
(ONLY FOR SOLAR, NO
LOADS TO BE ADDED)
EXISTING PV SYSTEM
(E)PV METER
M
PV PRODUCTION
METER 120/240V
E
E
4
(N)30A
INSTALL (2)30A 2P
BREAKERS
(ONLY FOR SOLAR, NO
LOADS TO BE ADDED)
(N)100A LOAD CENTER
(E)30A
(E)200A END FED
MAIN PANEL
UTILITY
GRID
(E
)
2
0
0
A
M
A
I
N
BR
E
A
K
E
R
(E) GROUND
ELECTRODE
60A SUB FEEDER
BREAKER
(N)100A SUB
PANEL
60A PV BREAKER
AT OPPOSITE END
OF THE BUS BAR
4
EXISTING 120/240V 1PH 60HZ
METER#:SCE
222013-519809M
MODULE SPECIFICATION
MODEL
HANWHA Q CELL
QPEAK DUO BLK
ML-G10+ 400W
MODULE POWER @ STC 400W
OPEN CIRCUIT VOLTAGE:Voc 45.30V
MAX POWER VOLTAGE:Vmp 37.13V
SHORT CIRCUIT CURRENT:Isc 11.14A
MAX POWER CURRENT:Imp 10.77A
ADDRESS:1238 CYPRESS AVENUE,
SANTA ANA, CA 92707
33.732077, -117.866857
APN:014-01-116
CUSTOMER INFORMATION
NAME:VICTOR BALLINAS
DATE:11/12/2022
SCALE:AS NOTED REV:D
AHJ:CA - CITY OF SANTA ANA
UTILITY:SCE
PRN NUMBER:MAS-64171
DRAFTED BY:
M.SAILESH
QC'ED BY:H.RAJ
PAPER SIZE:17"X11"
SOLARPLEX LLC
Dba MARAVILLA CONSTRUCTION
License#:1056065
5902 FIRESTONE BLVD
SOUTH GATE, CA 90280
TEL:(562) 806-6000
FAX:(562) 806-4006
SINGLE LINE DIAGRAM
E-01
1. CONDUCTORS EXPOSED TO SUNLIGHT
SHALL BE LISTED AS SUNLIGHT
RESISTANT PER CEC 310.10(D).
2. CONDUCTORS EXPOSED TO WET
LOCATIONS SHALL BE SUITABLE FOR
USE IN WET LOCATIONS PER CEC
310.10(C).
3. MAXIMUM DC/AC VOLTAGE DROP SHALL
BE NO MORE THAN 2%.
4. ALL CONDUCTORS SHALL BE IN
CONDUIT UNLESS OTHERWISE NOTED.
5. BREAKER/FUSE SIZES CONFORMS TO
CEC 240.6 CODE SECTION.
6. AC GROUNDING ELECTRODE
CONDUCTOR SIZED PER CEC 250.66.
7. AMBIENT TEMPERATURE CORRECTION
FACTOR IS BASED ON CEC 690.31(A).
8. AMBIENT TEMPERATURE ADJUSTMENT
FACTOR IS BASED ON CEC 310.15(B)(2).
9. MAX. SYSTEM VOLTAGE CORRECTION IS
PER CEC 690.7.
10. CONDUCTORS ARE SIZED PER WIRE
AMPACITY TABLE CEC 310.15(B)(16).
ELECTRICAL NOTESSINGLE LINE DIAGRAM: DC SYSTEM SIZE - 6000W, AC SYSTEM SIZE - 4350W, CEC AC RATING:5405W
AC WIRE SIZING CALCULATIONS BASED OF FOLLOWING EQUATIONS >>
· REQUIRED CONDUCTOR AMPACITY: INVERTER OUTPUT CURRENT X #OF
INVERTERS = MAX CURRENT PER 690.8(A)(3) X 125% = MAX CURRENT PER
690.8(B)(1)
· CORRECTED AMPACITY CALCULATIONS: AMPACITY X TEMPERATURE DERATE
FACTOR X CONDUIT FILL DERATE = DERATED CONDUCTOR AMPACITY PER
690.8(B)(2)
· DERATED CONDUCTOR AMPACITY CHECK: MAX CURRENT PER 690.8(A)(3)
<DERATED CONDUCTOR AMPACITY
AC WIRE CALCULATIONS:- MATERIAL:COPPER & TEMPERATURE RATING:90°C
TAG ID REQUIRED CONDUCTOR AMPACITY CORRECTED AMPACITY CALCULATION DERATED CONDUCTOR AMPACITY CHECK
1 1.21 X 8 = 9.68 X 1.25 = 12.10A 30 X 0.87 X 1 =26.10A 12.10A <26.10A
2 1.21 X 8 = 9.68 X 1.25 = 12.10A 40 X 0.87 X 0.8 =27.84A 12.10A <27.84A
3 1.21 X 15 = 18.15 X 1.25 = 22.69A 40 X 0.87 X 1 =34.80A 22.69A <34.80A
4 (E)18A+(N)18.15 = 36.15 X 1.25 = 45.19A 75 X 0.87 X 1 =65.25A 45.19A <65.25A
CONDUIT SCHEDULE
TAG ID CONDUIT SIZE CONDUCTOR NEUTRAL GROUND
1 NONE (2) 12AWG ENPHASE Q CABLE
PER BRANCH CIRCUIT NONE (1) 6AWG BARE COPPER
2 3/4"EMT (4) 10AWG THHN/THWN-2 NONE (1) 8AWG THHN/THWN-2
3 3/4"EMT (2) 10AWG THHN/THWN-2 (1) 10AWG THHN/THWN-2 (1) 8AWG THHN/THWN-2
4 3/4"EMT (2) 6AWG THHN/THWN-2 (1) 6AWG THHN/THWN-2 (1) 8AWG THHN/THWN-2
NOTE:
SUB PANEL RATING:100A, SUB FEEDER RATING RATING:60A
120% RULE: (100AX1.2)-60A=60A =>ALLOWABLE BACKFEED IS 60A
OCPD CALCULATIONS:
INVERTER OVERCURRENT PROTECTION=
INVERTER O/P I X CONTINUOUS LOAD(1.25)X #OF INVERTERS
=1.21x15x1.25=22.69 A =>REQUIRED BREAKER =30A
=(N)30A+(E)30A =>PV BREAKER=60A
ALLOWABLE BACKFEED 60A =>60A PV BREAKER
THE DESIGNED INTERCONNECTION MEETS THE 705.12(B)(2) REQUIREMENTS.
ELECTRICAL CALCULATION
MICRO INVERTER SPECIFICATIONS
MODEL
ENPAHSE
IQ8PLUS-72-2-US(240V)(SI-
1)
POWER RATING 290W
MAX OUTPUT CURRENT 1.21A
CEC WEIGHTED EFFICIENCY 97%
MAX NO OF MICRO
INVERTERS/BRANCH 13
MAX DC VOLTAGE 60V
NOTE:
1. EACH MICRO INVERTER IS RAPID SHUTDOWN COMPLIANT.
D
Service meter was replaced without inspections.
A new Service Meter permit is required.
Inspector to examine and determine approval or
corrections.
Existing PV system was never inspected nor
approved.
A new permit for the existing PV system is
required.
Inspector to verify system and determine approval
or corrections.
1238 S Cypress -
2017784102/16/23
LC CBAC PM CB AC SP MSP
WARNING PLACARD
ADDRESS:1238 CYPRESS AVENUE,
SANTA ANA, CA 92707
33.732077, -117.866857
APN:014-01-116
CUSTOMER INFORMATION
NAME:VICTOR BALLINAS
DATE:11/12/2022
SCALE:AS NOTED REV:D
AHJ:CA - CITY OF SANTA ANA
UTILITY:SCE
PRN NUMBER:MAS-64171
DRAFTED BY:
M.SAILESH
QC'ED BY:H.RAJ
PAPER SIZE:17"X11"
SOLARPLEX LLC
Dba MARAVILLA CONSTRUCTION
License#:1056065
5902 FIRESTONE BLVD
SOUTH GATE, CA 90280
TEL:(562) 806-6000
FAX:(562) 806-4006
WARNING PLACARDS -1
PL-01
POWER TO THIS BUILDING IS ALSO
SUPPLIED FROM THE FOLLOWING
SOURCES WITH DISCONNECTS LOCATED
AS SHOWN
!
ELECTRIC SHOCK HAZARD
THE DC CONDUCTORS OF THIS PHOTOVOLTAIC
SYSTEM ARE UNGROUNDED AND MAY BE
ENERGIZED
LABEL LOCATION
DC DISCONNECT,INVERTER
[To be used when inverter is
ungrounded]
WARNING!
ELECTRIC SHOCK HAZARD
DO NOT TOUCH TERMINALS
TERMINALS ON BOTH LINE AND LOAD SIDES
MAY BE ENERGIZED IN THE OPEN POSITION
WARNING
LABEL LOCATION
AC DISCONNECT,
POINT OF INTERCONNECTION
PER CODE: CEC 690.13(B)
!
WARNING-ELECTRIC SHOCK HAZARD
NO USER SERVICEABLE PARTS INSIDE
CONTACT AUTHORIZED SERVICE
PROVIDE FOR ASSISTANCE
LABEL LOCATION
INVERTER, JUNCTION BOXES(ROOF),
AC DISCONNECT
WARNING:PHOTOVOLTAIC
POWER SOURCE
LABEL LOCATION
CONDUIT, COMBINER BOX
PER CODE: CEC690.31(G)(3)
LABEL LOCATION
AC DISCONNECT, POINT OF INTERCONNECTION
PER CODE: CEC 690.54
RATED AC OPERATING CURRENT
AC NOMINAL OPERATING VOLTAGE
18.15
240
AMPS AC
VAC
PHOTOVOLTAIC SYSTEM AC DISCONNECT SWITCH
LABEL LOCATION
POINT OF INTERCONNECTION
PER CODE: CEC 705.12(B)(2)(3)(b)
WARNING
POWER SOURCE OUTPUT
CONNECTION
DO NOT RELOCATE THIS
OVER-CURRENT DEVICE
CAUTION: SOLAR CIRCUIT
LABEL LOCATION
MARKINGS PLACED ON ALL INTERIOR AND EXTERIOR
DC CONDUIT, RACEWAYS, ENCLOSURES AND CABLE
ASSEMBLES AT LEAST EVERY 10 FT, AT TURNS AND
ABOVE/BELOW PENETRATIONS AND ALL
COMBINER/JUNCTION BOXES.
PER CODE: CEC690.31(G)(3)
SOLAR DISCONNECT
LABEL LOCATION
DISCONNECT, POINT OF INTERCONNECTION
PER CODE: CEC690.31(B)
CAUTION: SOLAR ELECTRIC
SYSTEM CONNECTED
LABEL LOCATION
PLACED WITHIN THE MAIN SERVICE
DISCONNECT,
PLACED ON THE OUTSIDE OF THE COVER
WHEN DISCONNECT IS OPERATED WITH THE
SERVICE PANEL CLOSED.
PER CODE: CEC690.15 ,690.13(B)
TURN RAPID SHUTDOWN
SWITCH TO THE
"OFF" POSITION TO
SHUT DOWN PV SYSTEM
AND REDUCE
SHOCK HAZARD
IN THE ARRAY
SOLAR ELECTRIC
PV PANELS
SOLAR PV SYSTEM EQUIPPED
WITH RAPID SHUTDOWN
LABEL LOCATION
AC DISCONNECT, DC DISCONNECT,
POINT OF INTERCONNECTION
PER CODE: CEC690.56(C)(1)(a)
!!CAUTION:MULTIPLE SOURCES
OF POWER
NOTES:
ALL PLACARDS SHALL BE OF WEATHER PROOF CONSTRUCTION, BACKGROUND ON ALL PLACARDS SHALL BE
RED WITH WHITE LETTERING U.O.N.
PLACARD SHALL BE MOUNTED DIRECTLY ON THE EXISTING UTILITY ELECTRICAL SERVICE.
FASTENERS APPROVED BY THE LOCAL JURISDICTION
LABEL LOCATION
SERVICE PANEL
PER CODE: CEC 705.10
1238 CYPRESS AVENUE, SANTA ANA, CA 92707
SYSTEM UTILIZES MICRO-INVERTERS LOCATED UNDER EACH SOLAR MODULE
LABEL LOCATION
POINT OF INTERCONNECTION
PER CODE: CEC705.12(B)(3-4) AND 690.59
WARNING
DUAL POWER SOURCE SECOND
SOURCE IS PHOTOVOLTAIC
SYSTEM
!
RAPID SHUTDOWN
SWITCH FOR SOLAR PV
SYSTEM
LABEL LOCATION
INVERTER
PER CODE: CEC 690.56(C)(2)
(N)SOLAR PHOTOVOLTAIC
ARRAYS ON ROOF
(E)SOLAR PHOTOVOLTAIC ARRAYS ON ROOF
(DOES NOT SUPPORT RAPID SHUTDOWN)
(E) MAIN SERVICE PANEL
(N) AC DISCONNECT
(N) ENPHASE COMBINER 4
(E) LOAD COMBINER
(E) PRODUCTION METER
(E) AC DISCONNECT
(N)LOAD CENTER
D
(N)SUB PANEL
1238 S Cypress -
2017784102/16/23
10/26/2022
Design Criteria
Code 2019 California Building Code (ASCE 7‐16)
Risk category II Wind Load (component and Cladding)
Roof Dead Load Dr 10 psf V 95 mph
PV Dead Load DPV 3 psf Exposure C
Roof Live Load Lr 20 psf
Ground Snow S 0 psf
If you have any questions on the above, please do not hesitate to call.
Sincerely,
Eugene Munyanziza, P.E.
EV Engineering, LLC
projects@evengineersnet.com
http://www.evengineersnet.com
Exp: 06/30/2024
RE: Structural Certification for Installation of Residential Solar
VICTOR BALLINAS:1238 CYPRESS AVENUE, SANTA ANA, CA, 92707
Attn: To Whom It May Concern
This Letter is for the existing roof framing which supports the new PV modules as well as the attachment of
the PV system to existing roof framing. From the field observation report, the roof is made of Composition
shingle roofing over roof plywood supported by 2X4 Rafters at 24 inches. The slope of the roof was
approximated to be 23 degrees and the allowable maximum rafter span is 6 feet between supports.
After review of the field observation data and based on our structural capacity calculation, the existing roof
framing has been determined to be adequate to support the imposed loads without structural upgrades.
Contractor shall verify that existing framing is consistent with the described above before install. Should they
find any discrepancies, a written approval from SEOR is mandatory before proceeding with install. Capacity
calculations were done in accordance with applicable building codes.
projects@evengineersnet.com
http://www.evengineersnet.com
1238 S Cypress -
2017784102/16/23
Structural Letter for PV Installation
Date: 10/26/2022
Job Address: 1238 CYPRESS AVENUE
SANTA ANA, CA, 92707
Job Name: VICTOR BALLINAS
Job Number: 221026VB
Scope of Work
Table of Content
Sheet
1 Cover
2 Attachment Uplift checks
3 Roof Framing Check
4 Seismic Check and Scope of work
Engineering Calculations Summary
Code 2019 California Building Code (ASCE 7‐16)
Risk category II
Roof Dead Load Dr 10 psf
PV Dead Load DPV 3 psf
Roof Live Load Lr 20 psf
Ground Snow S 0 psf
Wind Load (component and Cladding)
V 95 mph
Exposure C
References
NDS for Wood Construction
Sincerely,
Eugene Munyanziza, P.E.
EV Engineering, LLC
projects@evengineersnet.com
http://www.evengineersnet.com Exp: 06/30/2024
This Letter is for the existing roof framing which supports the new PV modules as well as the attachment of
the PV system to existing roof framing. All PV mounting equipment shall be designed and installed per
manufacturer's approved installation specifications.
projects@evengineersnet.com
http://www.evengineersnet.com
1238 S Cypress -
2017784102/16/23
Wind Load Cont.
95 mph ASCE 7‐16 Figure 26.5‐1B
C
1.0 ASCE 7‐16 Sec 26.8.2
0.85 ASCE 7‐16 Table 26.10‐1
0.85 ASCE 7‐16 Table 26.6‐1
1.00 ASCE 7‐16 Table 26.9‐1
16.64 psf
23.0 Degrees
1.5 Conservatively assuming all exposed
0.8 conservatively assuming 10 ft2 effective area
Uplift (W)Zone(1) Zone(2r) Zone(2e)Zone(3)
Fig. 30‐3‐2 GCp=‐1.8 ‐2.2 ‐2.2 ‐2.1
Eq. 29.4‐7 P=qh(GCp)(γE)(γa)=‐35.94 ‐43.92 ‐43.92 ‐41.93
GCp=0.7 Figure 30.3‐2
P=qh(GCp)(γE)(γa)=10.48 Equation 29.4‐7
Rafter Attachments: 0.6D+0.6W (CD=1.6)
Connection Check
Attachment max. spacing= 6 ft
5/16"X4.75"Lag Screw Withdrawal Value= 266 lbs/in Table 12.2A ‐ NDS
2.5 in DFL Assumed
Prying Coefficient 1.4
Allowable Capacity= 760 lbs
Zone Trib Width Area (ft) Uplift (lbs) Down (lbs)
Zone(1) 6 16.5 289.1 222.4
Zone(2r) 6 16.5 348.4 222.4
Zone(2e) 6 16.5 348.4 222.4
Zone(3) 6 16.5 333.6 222.4
Conservative Max= 348.4 < 760
CONNECTION IS OK
2.Embedment is measured from the top of the framing member to the tapered tip of a lag screw.
Embedment in sheading or other material does not count.
II
V=
Exposure =
1.Pv seismic dead weight is negligible to result in significant seismic uplift, therefore the wind uplift
governs
γE=
γa=
KZt =
q h= 0.00256KzKztKdKeV2=
Pitch =
Lag Screw Penetration
Risk Category =
KZ =
Kd =
Ke =
projects@evengineersnet.com
http://www.evengineersnet.com
1238 S Cypress -
2017784102/16/23
Vertical Load Resisting System Design
Roof Framing Rafters
Snow Load Fully Exposed
pg= 0 psf Ct = 1.1
Ce = 0.9 Is = 1.0
pf = 0 psf
pfmin. = 0.0 psf
ps = 0 psf Conservatively (Cs=1) 0 plf
Max Length, L = 6.0 ft (Rafter maximum Allowable Horizontal Span)
Tributary Width, WT = 24 in
Dr = 10 psf 20 plf
PvDL = 3 psf 18 plf
Load Case: DL+0.75(0.6W+S)
0.75(Pnet+Ps)+ Ppvcos(θ)+PDL= 47 plf
Mdown= 213 lb‐ft
Mallowable = Sx x Fb' (wind)= 456 lb‐ft > 213 lb‐ft OK
Load Case: DL+S
Ps+ Ppvcos(θ)+PDL= 38 plf
Mdown= 171 lb‐ft
Mallowable = Sx x Fb' (wind)= 456 lb‐ft > 171 lb‐ft OK
Load Case: DL+0.6W
Pnet+ Ppvcos(θ)+PDL= 50.6 plf
Max Moment, Mu= 228 lb‐ft
Mallowable = Sx x Fb' (wind)= 634 lb‐ft > 228 lb‐ft OK
Pv max Shear= 222.4 lbs
Shear, Vu=wL/2+Pv Point Load = 336 lbs
Max Shear, Vu=wL/2+Pv Point Load = 336 lb
Member Capacity
DF‐L No.2
2X4 CL CF Ci Cr KF φ λ
Fb = 900 psi 1.0 1.5 1.0 1.15 2.54 0.85 0.8 1553 psi
Fv = 180 psi N/A N/A 1.0 N/A 2.88 0.75 0.8 180 psi
E = 1600000 psi N/A N/A 1.0 N/A N/A N/A N/A 1600000 psi
Emin = 580000 psi N/A N/A 1.0 N/A 1.76 0.85 N/A 580000 psi
Depth, d = 3.5 in
Width, b = 1.5 in
Cross‐Sectonal Area, A = 5.25 in2
Moment of Inertia, Ixx = 5.35938 in4
Section Modulus, Sxx = 3.0625 in
Allowable Moment, Mall = Fb'Sxx = 396.2 lb‐ft DCR=Mu/Mall = 0.47 < 1 Satisfactory
Allowable Shear, Vall = 2/3Fv'A = 630.0 lb DCR=Vu/Vall = 0.53 < 1 Satisfactory
Design Value Adjusted Value
projects@evengineersnet.com
http://www.evengineersnet.com
1238 S Cypress -
2017784102/16/23
Siesmic Loads Check
Roof Dead Load 10 psf
% or Roof with Pv 28%
Dpv and Racking 3 psf
Average Total Dead Load 10.8 psf
Increase in Dead Load 3.4%OK
The increase in seismic Dead weight as a result of the solar system is less than 10% of the existing structure and
therefore no further seismic analysis is required.
Limits of Scope of Work and Liability
We have based our structural capacity determination on information in pictures and a drawing set titled PV plans
‐VICTOR BALLINAS. The analysis was according to applicable building codes, professional engineering and design
experience, opinions and judgments. The calculations produced for this dwelling's assessment are only for the
proposed solar panel installation referenced in the stamped plan set and were made according to generally
recognized structural analysis standards and procedures.
projects@evengineersnet.com
http://www.evengineersnet.com
1238 S Cypress -
2017784102/16/23
1238 S Cypress -
2017784102/16/23
(1) BRANCH OF (8) MICRO-INVERTERS
(1) BRANCH OF (7) MICRO-INVERTERS
1
(15)HANWHA Q CELL QPEAK DUO BLK ML-G10
400W MODULES WITH (15)ENPAHSE
IQ8PLUS-72-2-US(240V)(SI-1)
(N)JUNCTION
BOX
2
ENPHASE Q CABLE
DC CONDUCTORS
AC CONDUCTORS
3
(E)200A END FED
MAIN PANEL
UTILITY
GRID
(E
)
2
0
0
A
M
A
I
N
BR
E
A
K
E
R
PV BREAKER AT THE
OPPOSITE END OF
BUSBAR
(N)30A 2P
PV BREAKER
EXISTING 120/240V 1PH 60HZ
METER#:SCE
222013-519809M
N
G
(E) GROUND
ELECTRODE
LOADS
(N)30A AC
DISCONNECT
AC DISCONNECT
NON FUSED 30A,
120/240V, 2P
10A
(N)ENPHASE IQ
COMBINER 4
20A
20A
AC COMBINER BOX
X-IQ-AM1-240-4 120/240
NEMA 3R INSTALL
(2)20A PV 2P BREAKERS
(ONLY FOR SOLAR, NO
LOADS TO BE ADDED)
(E)(20)HYUNDAI HIS-S260RG 260W MODULES WITH
(E)(20)ENPHASE M215-60-2LL-S22/23-IG(240V)
(E)JUNCTION
BOX
E E
ENPHASE Q CABLE
DC CONDUCTORS
AC CONDUCTORS
E
(E)30A AC
DISCONNECT
AC DISCONNECT
NON FUSED 60A,
120/240V, 2P
(E)LOAD COMBINER
20A
3
INSTALL (2)30A PV 2P
BREAKERS
(ONLY FOR SOLAR, NO
LOADS TO BE ADDED)
EXISTING PV SYSTEM
(E)30A 2P
PV
BREAKER
(E)PV METER
M
PV PRODUCTION
METER 120/240V
E
E
MODULE SPECIFICATION
MODEL
HANWHA Q CELL
QPEAK DUO BLK
ML-G10 400W
MODULE POWER @ STC 400W
OPEN CIRCUIT VOLTAGE:Voc 45.30V
MAX POWER VOLTAGE:Vmp 37.13V
SHORT CIRCUIT CURRENT:Isc 11.14A
MAX POWER CURRENT:Imp 10.77A
ADDRESS:1238 CYPRESS AVENUE,
SANTA ANA, CA 92707
33.732077, -117.866857
APN:014-01-116
CUSTOMER INFORMATION
NAME:VICTOR BALLINAS
DATE:10/4/2022
SCALE:AS NOTED REV:A
AHJ:CA - CITY OF SANTA ANA
UTILITY:SCE
PRN NUMBER:MAS-64171
DRAFTED BY:
M.SAILESH
QC'ED BY:H.RAJ
PAPER SIZE:17"X11"
SOLARPLEX LLC
Dba MARAVILLA CONSTRUCTION
License#:1056065
5902 FIRESTONE BLVD
SOUTH GATE, CA 90280
TEL:(562) 806-6000
FAX:(562) 806-4006
SINGLE LINE DIAGRAM
E-01
1. CONDUCTORS EXPOSED TO SUNLIGHT
SHALL BE LISTED AS SUNLIGHT
RESISTANT PER CEC 310.10(D).
2. CONDUCTORS EXPOSED TO WET
LOCATIONS SHALL BE SUITABLE FOR
USE IN WET LOCATIONS PER CEC
310.10(C).
3. MAXIMUM DC/AC VOLTAGE DROP SHALL
BE NO MORE THAN 2%.
4. ALL CONDUCTORS SHALL BE IN
CONDUIT UNLESS OTHERWISE NOTED.
5. BREAKER/FUSE SIZES CONFORMS TO
CEC 240.6 CODE SECTION.
6. AC GROUNDING ELECTRODE
CONDUCTOR SIZED PER CEC 250.66.
7. AMBIENT TEMPERATURE CORRECTION
FACTOR IS BASED ON CEC 690.31(A).
8. AMBIENT TEMPERATURE ADJUSTMENT
FACTOR IS BASED ON CEC 310.15(B)(2).
9. MAX. SYSTEM VOLTAGE CORRECTION IS
PER CEC 690.7.
10. CONDUCTORS ARE SIZED PER WIRE
AMPACITY TABLE CEC 310.15(B)(16).
ELECTRICAL NOTESSINGLE LINE DIAGRAM: DC SYSTEM SIZE - 6000W, AC SYSTEM SIZE - 4350W, CEC AC RATING:5405W
AC WIRE SIZING CALCULATIONS BASED OF FOLLOWING EQUATIONS >>
· REQUIRED CONDUCTOR AMPACITY: INVERTER OUTPUT CURRENT X #OF
INVERTERS = MAX CURRENT PER 690.8(A)(3) X 125% = MAX CURRENT PER
690.8(B)(1)
· CORRECTED AMPACITY CALCULATIONS: AMPACITY X TEMPERATURE DERATE
FACTOR X CONDUIT FILL DERATE = DERATED CONDUCTOR AMPACITY PER
690.8(B)(2)
· DERATED CONDUCTOR AMPACITY CHECK: MAX CURRENT PER 690.8(A)(3)
<DERATED CONDUCTOR AMPACITY
AC WIRE CALCULATIONS:- MATERIAL:COPPER & TEMPERATURE RATING:90°C
TAG ID REQUIRED CONDUCTOR AMPACITY CORRECTED AMPACITY CALCULATION DERATED CONDUCTOR AMPACITY CHECK
1 1.21 X 8 = 9.68 X 1.25 = 12.10A 30 X 0.87 X 1 =26.10A 12.10A <26.10A
2 1.21 X 8 = 9.68 X 1.25 = 12.10A 40 X 0.87 X 0.8 =27.84A 12.10A <27.84A
3 1.21 X 15 = 18.15 X 1.25 = 22.69A 40 X 0.87 X 1 =34.80A 22.69A <34.80A
CONDUIT SCHEDULE
TAG ID CONDUIT SIZE CONDUCTOR NEUTRAL GROUND
1 NONE (2) 12AWG ENPHASE Q CABLE
PER BRANCH CIRCUIT NONE (1) 6AWG BARE COPPER
2 3/4"EMT (4) 10AWG THHN/THWN-2 NONE (1) 8AWG THHN/THWN-2
3 3/4"EMT (2) 10AWG THHN/THWN-2 (1) 10AWG THHN/THWN-2 (1) 8AWG THHN/THWN-2
NOTE:
MAIN PANEL RATING:200A, MAIN BREAKER RATING:200A
120% RULE: (200AX1.2)-200A=40A =>ALLOWABLE BACKFEED IS 40A
OCPD CALCULATIONS:
INVERTER OVERCURRENT PROTECTION=
INVERTER O/P I X CONTINUOUS LOAD(1.25)X #OF INVERTERS
=1.21x15x1.25=22.69 A =>PV BREAKER = 30A
ALLOWABLE BACKFEED 40A =>30A PV BREAKER
THE DESIGNED INTERCONNECTION MEETS THE 705.12(B)(2) REQUIREMENTS.
ELECTRICAL CALCULATION
MICRO INVERTER SPECIFICATIONS
MODEL
ENPAHSE
IQ8PLUS-72-2-US(240V)(SI-
1)
POWER RATING 290W
MAX OUTPUT CURRENT 1.21A
CEC WEIGHTED EFFICIENCY 97%
MAX NO OF MICRO
INVERTERS/BRANCH 13
MAX DC VOLTAGE 60V
NOTE:
1. EACH MICRO INVERTER IS RAPID SHUTDOWN COMPLIANT.
1238 S Cypress -
2017784102/16/23
A A A A A A A A B B B
BB B B
MOUNTING DETAIL
S-01SCALE:1"=10'-0"
NOTE:PENETRATIONS ARE STAGGERED
ADDRESS:1238 CYPRESS AVENUE,
SANTA ANA, CA 92707
33.732077, -117.866857
APN:014-01-116
CUSTOMER INFORMATION
NAME:VICTOR BALLINAS
DATE:10/4/2022
SCALE:AS NOTED REV:A
AHJ:CA - CITY OF SANTA ANA
UTILITY:SCE
PRN NUMBER:MAS-64171
DRAFTED BY:
M.SAILESH
QC'ED BY:H.RAJ
PAPER SIZE:17"X11"
SOLARPLEX LLC
Dba MARAVILLA CONSTRUCTION
License#:1056065
5902 FIRESTONE BLVD
SOUTH GATE, CA 90280
TEL:(562) 806-6000
FAX:(562) 806-4006
INSTALLATION NOTES
1. STRUCTURAL ROOF MEMBER LOCATIONS ARE
ESTIMATED AND SHOULD BE LOCATED AND
VERIFIED BY THE CONTRACTOR WHEN LAG BOLT
PENETRATION OR MECHANICAL ATTACHMENT TO
THE STRUCTURE IS REQUIRED.
2. ROOFTOP PENETRATIONS FOR SOLAR RACKING
WILL BE COMPLETED AND SEALED WITH APPROVED
SEALANT PER CODE BY A LICENSED CONTRACTOR.
3. LAGS MUST HAVE A MINIMUM 2.5" THREAD
EMBEDMENT INTO THE STRUCTURAL MEMBER.
4. ALL PV RACKING ATTACHMENTS SHALL BE
STAGGERED BY ROW BETWEEN THE ROOF FRAMING
MEMBERS AS NECESSARY.
5. ROOF MOUNTED STANDARD RAIL REQUIRES ONE
THERMAL EXPANSION GAP FOR EVERY RUN OF RAIL
GREATER THAN 40'.
6. ALL CONDUCTORS AND CONDUITS ON THE ROOF
SHALL BE MINIMUM 7/8" ABOVE THE ROOF
SURFACE (INCLUDING CABLES UNDERNEATH
MODULES AND RACKING).
7. THE PV INSTALLATION SHALL NOT OBSTRUCT ANY
PLUMBING, MECHANICAL OR BUILDING ROOF
VENTS.
ROOF ACCESS PATHWAYS AND SETBACKS:
1204.2.1 SOLAR PHOTOVOLTAIC SYSTEMS FOR GROUP
R-3 BUILDINGS.SOLAR PHOTOVOLTAIC SYSTEMS FOR
GROUP R-3 BUILDINGS SHALL COMPLY WITH SECTIONS
1204.2.1.1 THROUGH 1204.2.1.3.
EXCEPTIONS:
1. THESE REQUIREMENTS SHALL NOT APPLY TO
STRUCTURES DESIGNED AND CONSTRUCTED IN
ACCORDANCE WITH THE CALIFORNIA RESIDENTIAL
CODE.
2. THESE REQUIREMENTS SHALL NOT APPLY TO ROOFS
WITH SLOPES OF 2 UNITS VERTICAL IN 12 UNITS
HORIZONTAL OR LESS.
1204.2.1.1 PATHWAYS TO RIDGE. NOT FEWER THAN
TWO 36-INCH-WIDE (914 MM) PATHWAYS ON SEPARATE
ROOF PLANES,FROM LOWEST ROOF EDGE TO RIDGE,
SHALL BE PROVIDED ON ALL BUILDINGS. NOT FEWER
THAN ONE PATHWAY SHALL BE PROVIDED ON THE
STREET OR DRIVEWAY SIDE OF THE ROOF. FOR EACH
ROOF PLANE WITH A PHOTOVOLTAIC ARRAY, NOT FEWER
THAN ONE 36-INCH-WIDE (914 MM) PATHWAY FROM
LOWEST ROOF EDGE TO RIDGE SHALL BE PROVIDED ON
THE SAME ROOF PLANE AS THE PHOTOVOLTAIC ARRAY,
ON AN ADJACENT ROOF PLANE OR STRADDLING THE
SAME AND ADJACENT ROOF PLANES
1204.2.1.2 SETBACKS AT RIDGE.FOR PHOTOVOLTAIC
ARRAYS OCCUPYING 33 PERCENT OR LESS OF THE PLAN
VIEW TOTAL ROOF AREA,
A SETBACK OF NOT LESS THAN 18 INCHES (457
MM)WIDE IS REQUIRED ON BOTH SIDES OF A
HORIZONTAL RIDGE. FOR PHOTOVOLTAIC ARRAYS
OCCUPYING MORE THAN 33 PERCENT OF THE PLAN VIEW
TOTAL ROOF AREA, A SETBACK OF NOT LESS THAN 36
INCHES (457 MM) WIDE IS REQUIRED ON BOTH SIDES
OF A HORIZONTAL RIDGE.
1204.2.2 EMERGENCY ESCAPE AND RESCUE OPENINGS.
PANELS AND MODULES INSTALLED ON GROUP R-3
BUILDINGS SHALL NOT BE PLACED ON THE PORTION OF
A ROOF THAT IS BELOW AN EMERGENCY ESCAPE AND
RESCUE OPENING. A PATHWAY OF NOT LESS THAN 36
INCHES (914 MM) WIDE SHALL BE PROVIDED TO THE
EMERGENCY ESCAPE AND RESCUE OPENING
1204.2.1.3 ALTERNATIVE SETBACKS AT RIDGE.
WHERE AN AUTOMATIC SPRINKLER SYSTEM IS
INSTALLED WITHIN THE DWELLING IN ACCORDANCE
WITH SECTION 903.3.1.3, SETBACKS AT THE RIDGE
SHALL CONFORM TO ONE OF THE FOLLOWING:
1. FOR PHOTOVOLTAIC ARRAYS OCCUPYING 66 PERCENT
OR LESS OF THE PLAN VIEW TOTAL ROOF AREA, A
SETBACK OF NOT LESS THAN 18 INCHES (457 MM) WIDE
IS REQUIRED ON BOTH SIDES OF A HORIZONTAL RIDGE.
2.FOR PHOTOVOLTAIC ARRAYS OCCUPYING MORE THAN
66 PERCENT OF THE PLAN VIEW TOTAL ROOF AREA, A
SETBACK OF NOT LESS THAN 36 INCHES (914 MM) WIDE
IS REQUIRED ON BOTH SIDES OF A HORIZONTAL RIDGE
ALUMINIUM RAILS
2 X 4 RAFTERS@
2'-0"SPACING
ARRAY MP-01
SITE INFORMATION - WIND SPEED: 95 MPH AND SNOW LOAD: 0 PSF
SR.
NO AZIMUTH PITCH NO. OF
MODULES
ARRAY AREA
(SQ. FT.)ROOF TYPE ATTACHMENT ROOF
EXPOSURE FRAME TYPE FRAME
SIZE
FRAME
SPACING
MAX RAIL
SPAN
OVER
HANG
MP-01 360° 23° 15 317.0 COMPOSITION
SHINGLE
IRONRIDGE
FLASHFOOT2 ATTIC RAFTERS 2 X 4 2'-0" 6'-0" 2'-0"
AERIAL VIEW
STRING CONFIGURATION
BRANCH DETAILS
A 8 MODULES
B 7 MODULES
6'
3'
3'
Structural
Only
1238 S Cypress -
2017784102/16/23
MODULE
END CLAMPMID CLAMPMODULE
ADDRESS:1238 CYPRESS AVENUE,
SANTA ANA, CA 92707
33.732077, -117.866857
APN:014-01-116
CUSTOMER INFORMATION
NAME:VICTOR BALLINAS
DATE:10/4/2022
SCALE:AS NOTED REV:A
AHJ:CA - CITY OF SANTA ANA
UTILITY:SCE
PRN NUMBER:MAS-64171
DRAFTED BY:
M.SAILESH
QC'ED BY:H.RAJ
PAPER SIZE:17"X11"
SOLARPLEX LLC
Dba MARAVILLA CONSTRUCTION
License#:1056065
5902 FIRESTONE BLVD
SOUTH GATE, CA 90280
TEL:(562) 806-6000
FAX:(562) 806-4006
STRUCTURAL DETAIL
S-02
MID-CLAMP AND END-CLAMP ANATOMY
GROUNDING LUG
MID CLAMP
ASSEMBLY
MODULE
FRAME
RAIL
MODULE TO MODULE & MODULE TO RAIL
GROUNDING MID-CLAMP
SCALE: NTS
GROUNDING DETAILS
IRONRIDGE RAIL
IRONRIDGE INTERNAL SPLICE
SELF-DRILLING SCREW
SCALE: NTS
RAIL TO RAIL
T-BOLT
DEAD LOAD CALCULATIONS
BOM QUANTITY LBS/UNIT TOTAL WEIGHT
(LBS)
MODULES 15 48.50 727.50
MID-CLAMP 24 0.170 4.08
END-CLAMP 12 0.300 3.60
RAIL LENGTH 118 0.790 93.22
SPLICE BAR 4 0.650 2.60
IRONRIDGE
FLASHFOOT2 27 1.88 50.76
MICRO-INVERTER 15 2.38 35.70
TOTAL WEIGHT OF THE SYSTEM (LBS)881.76
TOTAL ARRAY AREA ON THE ROOF (SQ. FT.)316.99
WEIGHT PER SQ. FT.(LBS)2.78
WEIGHT PER PENETRATION (LBS)20.99
MODULES DATA
HANWHA Q CELL QPEAK DUO BLK ML-G10
400W
MODULE DIMS 73.97"x41.14"x1.25"
LAG SCREWS 5/16"x4.75":2.5"MIN
EMBEDMENT
2 X 4 RAFTERS
@2'-0" SPACING
COMPOSITION SHINGLE ROOF
MODULE
5/16" X 4.75" LAG SCREW
1 BOLT PER PENETRATION
LOAD BEARING WALL SCALE:NTS
ROOF FRAMING DETAILS
ATTACHMENT DETAIL- IRONRIDGE FLASHFOOT2
FLASHFOOT2SOLAR MODULE
STAINLESS STEEL 5/16" X 4.75" LAG SCREW 2.5"
EMBEDMENT PILOT HOLE REQUIRED
RAIL
FLASHING
6" MAX
Structural
Only
1238 S Cypress -
2017784102/16/23
A
MSP CBAC PM CB AC
A A A A A A A B B B
BB B B
VICINITY MAP
ADDRESS:1238 CYPRESS AVENUE,
SANTA ANA, CA 92707
33.732077, -117.866857
APN:014-01-116
CUSTOMER INFORMATION
NAME:VICTOR BALLINAS
DATE:10/4/2022
SCALE:AS NOTED REV:A
AHJ:CA - CITY OF SANTA ANA
UTILITY:SCE
PRN NUMBER:MAS-64171
DRAFTED BY:
M.SAILESH
QC'ED BY:H.RAJ
PAPER SIZE:17"X11"
SOLARPLEX LLC
Dba MARAVILLA CONSTRUCTION
License#:1056065
5902 FIRESTONE BLVD
SOUTH GATE, CA 90280
TEL:(562) 806-6000
FAX:(562) 806-4006
APPLICABLE CODES
COVER PAGE
T-01
SCALE:1"=20'-0"
1.MODULES ARE LISTED UNDER UL 61730 AND
CONFORM TO THE STANDARDS.
2.INVERTERS ARE LISTED UNDER UL 1741 AND
CONFORM TO THE STANDARDS.
3.DRAWINGS ARE DIAGRAMMATIC, INDICATING
GENERAL ARRANGEMENT OF THE PV SYSTEM AND
THE ACTUAL SITE CONDITION MIGHT VARY.
4.WORKING CLEARANCES AROUND THE NEW PV
ELECTRICAL EQUIPMENT WILL BE MAINTAINED IN
ACCORDANCE WITH CEC 110.26.
5.ALL GROUND WIRING CONNECTED TO THE MAIN
SERVICE GROUNDING IN MAIN SERVICE PANEL/
SERVICE EQUIPMENT.
6.ALL CONDUCTORS SHALL BE 600V, 75°C
STANDARD COPPER UNLESS OTHERWISE NOTED.
7.WHEN REQUIRED, A LADDER SHALL BE IN PLACE
FOR INSPECTION IN COMPLIANCE WITH OSHA
REGULATIONS.
8.THE SYSTEM WILL NOT BE INTERCONNECTED BY
THE CONTRACTOR UNTIL APPROVAL FROM THE
LOCAL JURISDICTION AND/OR THE UTILITY.
9.ROOF ACCESS POINT SHALL BE LOCATED IN
AREAS THAT DO NOT REQUIRE THE PLACEMENT
OF GROUND LADDERS OVER OPENINGS SUCH AS
WINDOWS OR DOORS, AND LOCATED AT STRONG
POINTS OF BUILDING CONSTRUCTION WHERE THE
ACCESS POINT DOES NOT CONFLICT WITH
OVERHEAD OBSTRUCTIONS SUCH AS TREES,
WIRES OR SIGNS.
10.PV ARRAY COMBINER/JUNCTION BOX
PROVIDES TRANSITION FROM ARRAY WIRING TO
CONDUIT WIRING
GENERAL NOTES
SHEET CATALOG
INDEX NO. DESCRIPTION
T-01 COVER PAGE
S-01 MOUNTING DETAIL
S-02 STRUCTURAL DETAIL
E-01 SINGLE LINE DIAGRAM
PL-01 WARNING PLACARDS
SS SPEC SHEET(S)
SITE PLAN LAYOUT
VICTOR BALLINAS - 6.000kW DC, 4.350kW AC, CEC AC RATING:5.405kW
ENGINEERING SCOPE OF WORK
1.ILLUMINE INDUSTRIES INC. HAS ONLY PROVIDED DRAFTING SERVICES FOR THE PERMIT DRAWINGS. NO ACTUAL ENGINEERING WORK, ENGINEERING REVIEW OR ENGINEERING
APPROVAL HAS BEEN CONDUCTED BY ILLUMINE INDUSTRIES INC UNLESS NOTED OTHERWISE.
2.WHEN A PROFESSIONAL ENGINEER APPROVES AND SEALS THE DESIGN FOR COMPONENTS OF THEIR RESPECTIVE DISCIPLINE (STRUCTURAL/ELECTRICAL) SHOWN ON THESE PERMIT
DRAWINGS, HE/SHE:
a. TAKES FULL DIRECT CONTROL OF THE ENGINEERED DESIGN
b.IS GIVEN ACCESS TO PERSONALLY SUPERVISE AND RECTIFY ANY ASPECT OF THE ENGINEERED DESIGN
c.HAS FULLY ACCEPTED RESPONSIBILITY FOR THE ENGINEERED DESIGN
GENERAL SYSTEM INFORMATION:
SYSTEM SIZE:
6000W DC, 4350W AC,CEC RATING: 5405W
MODULES:
(15)HANWHA Q CELL QPEAK DUO BLK ML-G10
400W
INVERTER:
(15)ENPAHSE IQ8PLUS-72-2-US(240V)(SI-1)
BRANCH DETAILS:
1X8, 1X7 ENPHASE BRANCH
EXISTING SYSTEM SIZE:
(20) HYUNDAI HIS-S260RG
(20) ENPHASE M215-60-2LL/23-IG(240V)
SCOPE OF WORK
(E)UTILITY METER WITH
(E) MAIN SERVICE PANEL
CONDUIT RUN
(N)PHOTOVOLTAIC ARRAY ON THE ROOF
STRING CONFIGURATION
BRANCH DETAILS
A 8 MODULES
B 7 MODULES
(N) AC DISCONNECT
(N) ENPHASE COMBINER 4
DETACHED STRUCTURE
PROPERTY LINE
DRIVE WAY
CY
P
R
E
S
S
A
V
E
·ELECTRIC CODE:CEC 2019
·FIRE CODE:CFC 2019
·BUILDING CODE:CBC 2019
·RESIDENTIAL CODE:CRC 2019
3' FIRE SETBACK
(E) LOAD COMBINER
(E) PRODUCTION METER
(E) AC DISCONNECT
158'-4"
55'
158'-4"
10'
84'
11'
18'
(E)PHOTOVOLTAIC ARRAY ON THE ROOF
Structural
Only
BLDG# 101112622 ISS. 12/20/2022
ELEC# 20177841 ISS. 12/20/2022
The scope of the plans is for the installation of the solar photovoltaic system only and the approval is subject to compliance with all
applicable city and state codes and regulations regarding construction. The approval of the plans does not constitute any
certification of the accuracy, completeness, or building permit status of the existing buildings and structures as shown.
1238 S Cypress -
2017784102/16/23