HomeMy WebLinkAbout2634 N Oakmont Ave - PlanNEW GEN ENERGY
CORPORATION
P.O. Box 143, Placentia,
CA 92871-0143
Phone: (909) 215-5291
CSLB Lic# 949365 (C-10)
X:_____________________
_
Solar Photovoltaic System
BENJAMIN FERENC
2634 OAKMONT AVE
SANTA ANA, CA 92705
(626)367-3951
0.0-Cover
Sheet
0.0 PROJECT INFORMATION
0.1 SITE PLAN, HOUSE PHOTO
S1.0
S1.1
E1.0
E1.1
PV0.0
PV.01
-
ROOF PLAN
ATTACHMENT DETAILS
ELECTRICAL LINE DIAGRAM
ELECTRICAL NOTES, LOAD CALCS
REQUIRED SIGNAGE
PV EQUIPMENT SHEETS
PROJECT INFORMATION VICINITY MAPPLAN SET LEGEND
SUB SERVICE PANEL
AC DISCONNECT
DC DISCONNECT
SOLAR LOAD CENTER
INVERTER
SUB
AC
DC
SLC
INV
JUNCTION BOXJB
COMBINER BOXCB
ABBREVIATIONS
EXTERIOR
INTERIOR
EXT
INT
NEW(N)
EXISTING(E)
ELECTRICAL METALLIC TUBINGEMT
RIGID METALLIC TUBINGRMT
VOLTAGE OPEN CIRCUITVOC
VOLTAGE AT MAX. POWERVMP
SHORT CIRCUIT CURRENTISC
CURRENT AT MAX. POWERIMP
MONITORING METERM
NOT TO SCALENTS
OCCUPANCY: R-3
CONSTRUCTION TYPE: VB
UNSPRINKLERED
MAIN SERVICE PANEL MSP
DEVICERSRAPID SHUTDOWN
DATE:
PROJECT
INFORMATION
N
PROJECT
SITE
AHJ NOTES SHEET INDEXAPPLICABLE CODES
ALL WORK TO COMPLY WITH
THE FOLLOWING CODES:
2019 CA BUILDING CODE
2019 CA RESIDENTIAL CODE
2019 CA MECHANICAL CODE
2019 CA ELECTRICAL CODE
2019 CA GREEN CODE
2019 CA PLUMBING CODE
2019 CA ENERGY CODE
2019 CA FIRE CODE
PROJECT INFO
22 X 395 W
22 X 401 W
ROOF MOUNTED SOLAR
PHOTOVOLTAIC MODULES
1 X 7600 W
HANWHA/QCELL Q.PEAK
DUO ML-G10.A+ 395W
P-401
SE7600H-USSNBBL14 (240V)
(SI1-JUN20)
SYSTEM SIZE: 8.096 kW AC STC
SYSTEM SIZE: 8.690 kW DC STC
ARRAY AREA: 465 SF
PANEL UPGRADE: 200/200 A
AHJ: CITY OF SANTA ANA
APN: 396-402-06
BENJAMIN FERENC
2634 OAKMONT AVE
SANTA ANA, CA 92705
PER SECTION R314 AND R315 OF CRC 2019, IT'S REQUIRED THAT
SMOKE ALARM AND CARBON MONOXIDE DETECTORS ARE
RETROFITTED INTO THE EXISTING DWELLING FOR A PERMIT WITH
REPAIRS OR ADDITIONS EXCEEDING $1,000.
ALL NEW UTILITY CONNECTIONS ARE REQUIRED TO BE INSTALLED
BELOW GRADE BY SANTA ANA MUNICOPAL CODE 41-626(B). THERE IS
A STANDING EXCEPTION FOR EXISTING ONE AND TWO FAMILY
DWELLINGS. THIS EXCEPTION APPLIES ONLY WHEN THE NEW
ELECTRICAL SERVICE IS DESIGNATED TO BE FED FROM BELOW
GRADE AS WELL AS OVERHEAD.
ONLY LISTED COMBINATION OVERHEAD AND UNDERGROUND FEED
SERVICE BOXES MAY BE USED TO CONNECT TO AN OVERHEAD
UTILITY DROP. THIS EXCEPTION TO AN UNDERGROUND FED SERVICE
APPLIES ONLY TO EXISTING SINGLE FAMILY AND TWO FAMILY
RESIDENCES.
4/27/2022
SOLAREDGE INVERTERS ARE
EQUIPPED WITH RAPID SHUTDOWN
REQUIREMENTS PER NEC 2017
SECTION 690.12
ALL CONDUIT TO RUN ON EXTERIOR
OF HOUSE UNLESS OTHERWISE NOTED
9-23
Bldg permit#101110511
Elect permit# 20176238
Issued on 5/24/22
2634 N Oakmont
Ave05/24/22
Solar Photovoltaic System
BENJAMIN FERENC
2634 OAKMONT AVE
SANTA ANA, CA 92705
(626)367-3951
NEW GEN ENERGY
CORPORATION
P.O. Box 143, Placentia,
CA 92871-0143
Phone: (909) 215-5291
CSLB Lic# 949365 (C-10)
X:_____________________
_
MSP SIZE IS AN
TOTAL # OF PANELS
(E)POOL DRIVEWAY
0.1-Site
Plan
HOUSE PHOTO
DATE:
SITE PLAN, HOUSE
PHOTO
SCALE: N.T.S.
ARRAY LOCATION
SCALE: 1":15'-0" SITE PLAN
N
(N)200 A
22
OA
KMONT
AVE
22 SOLAR MODULES
FIRE ACCESS POINT
4/27/2022
(E)ONE-STORY
HOUSE
3FT ACCESS PATHWAY
LEGEND
ALL SETBACK CONFORM TO
R324.6.1 THROUGH R324.6.2.1
TOTAL ARRAY AREA: 465
TOTAL ROOF AREA: 2107
ARRAYS OCCUPANCY: 22%
LOCATED AT EACH
PANEL
OPTIMIZER
PL
PL
PL
PL
5'-0"
FIRE ACCESS POINT
21
21
21
21
21
21
21
21
21
21
21
9-23
2634 N Oakmont
Ave05/24/22
NEW GEN ENERGY
CORPORATION
P.O. Box 143, Placentia,
CA 92871-0143
Phone: (909) 215-5291
CSLB Lic# 949365 (C-10)
X:_____________________
_
Solar Photovoltaic System
BENJAMIN FERENC
2634 OAKMONT AVE
SANTA ANA, CA 92705
(626)367-3951
PV-1
PV-1 PROJECT INFORMATION
PV-1A SITE PLAN, HOUSE PHOTO
PV-2 ROOF PLAN
PV-2A ATTACHMENT DETAILS
PV-3 ELECTRICAL LINE DIAGRAM
PV-3A ELECTRICAL NOTES, LOAD CALCS
PV-4 REQUIRED SIGNAGE
PROJECT INFORMATION VICINITY MAPPLAN SET LEGEND
SUB SERVICE PANEL
AC DISCONNECT
DC DISCONNECT
SOLAR LOAD CENTER
INVERTER
SUB
AC
DC
SLC
INV
JUNCTION BOXJB
COMBINER BOXCB
ABBREVIATIONS
EXTERIOR
INTERIOR
EXT
INT
NEW(N)
EXISTING(E)
ELECTRICAL METALLIC TUBINGEMT
RIGID METALLIC TUBINGRMT
VOLTAGE OPEN CIRCUITVOC
VOLTAGE AT MAX. POWERVMP
SHORT CIRCUIT CURRENTISC
CURRENT AT MAX. POWERIMP
MONITORING METERM
NOT TO SCALENTS
OCCUPANCY: R-3
CONSTRUCTION TYPE: VB
UNSPRINKLERED
MAIN SERVICE PANEL MSP
DEVICERSRAPID SHUTDOWN
DATE:
PROJECT
INFORMATION
N
PROJECT
SITE
AHJ NOTES SHEET INDEXAPPLICABLE CODES
ALL WORK TO COMPLY WITH
THE FOLLOWING CODES:
2019 CA BUILDING CODE
2019 CA RESIDENTIAL CODE
2019 CA MECHANICAL CODE
2019 CA ELECTRICAL CODE
2019 CA GREEN CODE
2019 CA PLUMBING CODE
2019 CA ENERGY CODE
2019 CA FIRE CODE
PROJECT INFO
22 X 395 W
22 X 401 W
ROOF MOUNTED SOLAR
PHOTOVOLTAIC MODULES
1 X 7600 W
HANWHA/QCELL Q.PEAK
DUO ML-G10.A+ 395W
P-401
SE7600H-USSNBBL14 (240V)
(SI1-JUN20)
SYSTEM SIZE: 8.096 kW AC STC
SYSTEM SIZE: 8.690 kW DC STC
ARRAY AREA: 465 SF
PANEL UPGRADE: 200/200 A
AHJ: CITY OF SANTA ANA
APN: 396-402-06
BENJAMIN FERENC
2634 OAKMONT AVE
SANTA ANA, CA 92705
PER SECTION R314 AND R315 OF CRC 2019, IT'S REQUIRED THAT
SMOKE ALARM AND CARBON MONOXIDE DETECTORS ARE
RETROFITTED INTO THE EXISTING DWELLING FOR A PERMIT WITH
REPAIRS OR ADDITIONS EXCEEDING $1,000.
ALL NEW UTILITY CONNECTIONS ARE REQUIRED TO BE INSTALLED
BELOW GRADE BY SANTA ANA MUNICOPAL CODE 41-626(B). THERE IS
A STANDING EXCEPTION FOR EXISTING ONE AND TWO FAMILY
DWELLINGS. THIS EXCEPTION APPLIES ONLY WHEN THE NEW
ELECTRICAL SERVICE IS DESIGNATED TO BE FED FROM BELOW
GRADE AS WELL AS OVERHEAD.
ONLY LISTED COMBINATION OVERHEAD AND UNDERGROUND FEED
SERVICE BOXES MAY BE USED TO CONNECT TO AN OVERHEAD
UTILITY DROP. THIS EXCEPTION TO AN UNDERGROUND FED SERVICE
APPLIES ONLY TO EXISTING SINGLE FAMILY AND TWO FAMILY
RESIDENCES.
4/27/2022
SOLAREDGE INVERTERS ARE
EQUIPPED WITH RAPID SHUTDOWN
REQUIREMENTS PER NEC 2017
SECTION 690.12
ALL CONDUIT TO RUN ON EXTERIOR
OF HOUSE UNLESS OTHERWISE NOTED
9-23
2634 N Oakmont
Ave05/24/22
Solar Photovoltaic System
BENJAMIN FERENC
2634 OAKMONT AVE
SANTA ANA, CA 92705
(626)367-3951
NEW GEN ENERGY
CORPORATION
P.O. Box 143, Placentia,
CA 92871-0143
Phone: (909) 215-5291
CSLB Lic# 949365 (C-10)
X:_____________________
_
MSP SIZE IS AN
TOTAL # OF PANELS
(E)POOL DRIVEWAY
PV-1A
HOUSE PHOTO
DATE:
SITE PLAN, HOUSE
PHOTO
SCALE: N.T.S.
ARRAY LOCATION
SCALE: 1":15'-0" SITE PLAN
N
(N)200 A
22
OAKMONT AVE
22 SOLAR MODULES
FIRE ACCESS POINT
4/27/2022
(E)ONE-STORY
HOUSE
3FT ACCESS PATHWAY
LEGEND
ALL SETBACK CONFORM TO
R324.6.1 THROUGH R324.6.2.1
TOTAL ARRAY AREA: 465
TOTAL ROOF AREA: 2107
ARRAYS OCCUPANCY: 22%
LOCATED AT EACH
PANEL
OPTIMIZER
PL
PL
PL
PL
5'-0"
FIRE ACCESS POINT
21
21
21
21
21
21
21
21
21
21
21
9-23
2634 N Oakmont
Ave05/24/22
Solar Photovoltaic System
BENJAMIN FERENC
2634 OAKMONT AVE
SANTA ANA, CA 92705
(626)367-3951
SCALE: 1":10'-0" ROOF PLAN
MSP SIZE IS AN
ATTACHMENT POINTS:
R1
ARRAY 1
22 SOLAR MODULES
26 ATTACHMENTS
@ 72" O.C. MAX.
3/4" EMT CONDUIT,
TO RUN ON ROOF
AND UNDER EAVES
WITH MC-4 CONNECTORS
INTERIOR RAFTER
SUPPORT, TYP.
EXT. WALL
(E)ROOF
FRAMING, SEE
ROOF INFO
LOCATED AT EACH
PANEL
OPTIMIZER
PV-2
ARRAY AND ROOF INFO
DATE:
ROOF PLAN
N
MODULE TYPE, DIMENSIONS & WEIGHT
(N)200 A
" O.C. MAX72
(E)PLUMBING VENT
(E)ROOF VENT
(E)CHIMNEY
FIRE ACCESS POINT
(E)PATIO COVER
ACCESSES IDENTIFIED ARE AT STRONG POINTS OF ROOF WHICH DO NOT HAVE OPENINGS BELOW LADDER ACCESSES.
PER CRC R331.4.1.
PANEL TYPE:HANWHA/QCELL Q.PEAK DUO ML-G10.A+ 395W
PANEL WEIGHT:48.5 lb
PANEL DIMENSIONS:74 " X 41.14 "
PANEL AREA:21.14 SF
UNIT WEIGHT OF PANELS:48.5/21.14 = 2.29 PSF
INVERTER & RACKING:0.19 PSF
AREA PER ATTACHMENT:6'X2.48 = 14.9 SF
WEIGHT PER ATTACHMENT:14.9X2.7 = 40.23 LB
4/27/2022
SINGLE LAYER OF ROOFING
PITCH AZIMUTH MATERIAL SP SQ.FT ARRAY SQ.FT RAFTER SPECS
ROOF
AREA %
R #1 270 COMP. SHINGLE 1182 465.08 2X6@24"39.3%
SOLAREDGE INVERTERS ARE
EQUIPPED WITH RAPID SHUTDOWN
REQUIREMENTS PER NEC 2017
SECTION 690.12
FIRE ACCESS POINT
NEW GEN ENERGY
CORPORATION
P.O. Box 143, Placentia,
CA 92871-0143
Phone: (909) 215-5291
CSLB Lic# 949365 (C-10)
X:______________________
9-23
2634 N Oakmont
Ave05/24/22
MIN. 2.5"PENETRATION SEALED W/
SIKAFLEX 1A
(E)ROOF FRAMING, SEE ROOF INFO
MATCH (E) ROOF SLOPE
PV MODULES
IRONRIDGE XR-10 RAIL
IRONRIDGE FLASHVUE
Solar Photovoltaic System
BENJAMIN FERENC
2634 OAKMONT AVE
SANTA ANA, CA 92705
(626)367-3951
NEW GEN ENERGY
CORPORATION
P.O. Box 143, Placentia,
CA 92871-0143
Phone: (909) 215-5291
CSLB Lic# 949365 (C-10)
X:______________________
SCALE: 1/2" = 1'-0"ATTACHMENT DETAIL
PV-2A
DATE:
ATTACHMENT
DETAILS
4/27/2022
1'-6" 9'-3" 9'-3"
RAFTER SECTION DETAIL
9-23
5/16" x 3.5" STAINLESS STEEL LAG BOLT
2634 N Oakmont
Ave05/24/22
Solar Photovoltaic System
BENJAMIN FERENC
2634 OAKMONT AVE
SANTA ANA, CA 92705
(626)367-3951
NEW GEN ENERGY
CORPORATION
P.O. Box 143, Placentia,
CA 92871-0143
Phone: (909) 215-5291
CSLB Lic# 949365 (C-10)
X:______________________
PV-3
DATE:
ELECTRICAL LINE
DIAGRAM
ELECTRICAL SINGLE LINE DIAGRAM
LOW MEAN TEMP
PER ASHRAE
HANDBOOK
MFR VOLTAGE TEMP
COEFFICIENT (oC)
VOLTAGE LOW
TEMP. CORR. (oC)
HIGH AMBIENT
TEMP (oC)
CONDUIT
HEIGHT (in)
ROOF TOP ADDED
TEMP PER Table ADJUSTED
TEMP
ROOF 2
-0.34 1.08
44 0.875 15.55 59.55
WALL 2 44 N/A 0 44
ATTIC 2 56 N/A 0 56
A
B
ELECTRICAL EQUIPMENT CALLOUTS
7.6kW INVERTER
SOLAREDGE SE7600H-USSNBBL14 (240V) (SI1-JUN20)
INVERTER 240 VAC, 32A NEMA 3R, UL LISTED,
(WITH INTEGRATED DC DISCONNECT)
AC DISCONNECT FUSED
240 VAC, 60A NEMA 3R, UL LISTED
PV BREAKER IS TO BE LOCATED AT
THE OPPOSITE END OF THE BUS BAR
FROM THE MAIN BREAKER.
4/27/2022
SOLAREDGE INVERTERS ARE
EQUIPPED WITH RAPID SHUTDOWN
REQUIREMENTS PER NEC 2017
SECTION 690.12
MAX PV VOLTAGE & CURRENT CALCS:
-2
TEMP COEFFICIENT (Voc) PER MANUFACTURER: -0.34 %/C
VOLTAGE CORRECTION:1.08
Vcorrection X Voptm
1.08 *400 = 432 V
OUTPUT FROM POWER OPTIMIZER PER STRING: 10.86 ADC
1.00 X Iopt
1.00 * 10.86 = 10.86 ADC
WIRE TAG # CONDUIT WIRE QTY
(CARRY
CURRENT)
WIRE
GAUGE
(AWG)
WIRE TYPE WIRE
LENGTH
(FEET)
TEMP
RATING:
WIRE
LOCATION
ADJUSTED
WIRE TEMP
WIRE
AMP
TEMP
CORRECTION
PER TABLE
310.15(B)(2)(a):
CONDUIT FILL
PER Table
310.15(B)(3)(a):
WIRE OCP: TERMINAL
75oC
RATING
STRINGS PER SET OF
WIRES (DC) OR # 0F
INVERTERS:
SHORT CIRCUIT
CURRENT (DC) OR
AC OUTPUT
NEC
690.8(A)
NEC
690.8(B)
STRING
AMPS
GROUND
SIZE
GROUND
TYPE
OCPD CHECK
1 3/4" EMT 4 10 60 ROOF 59.55 40 X 0.71 X 0.8 = 22.72 35 1 X 10.86 X 1.00 X 1 = 10.86 #8 THWN-2 NONE
2 3/4" EMT 3 8 THWN-2 5 WALL 44 55 X 0.87 X 1 = 47.85 50 1 X 32.00 X 1.25 X 1 = 40 #8 THWN-2 40A 2P
(N)200 A MAIN SERVICE
DISCONNECT
STRING 2
STRING 111 OPTIMIZERS/MODULES IN SERIES
W/ INTEGRATED RAPID SHUTDOWN
11 OPTIMIZERS/MODULES IN SERIES
W/ INTEGRATED RAPID SHUTDOWN
TO UTILITY GRID
BOND TO
EXISTING UFER
1PH, 120/240V,
3W
BI-DIRECTIONAL
UTILITY METER
(N)200 A MAIN
SERVICE
PANEL
NO CENTER
MAIN BREAKER
2-POLE 40A PV BREAKER,
BACKFED
AB
EXISTING AC
GROUNDING
ELECTRODE
8.690kW SOLAR ARRAY
22 HANWHA/QCELL 395W MODULES TOTAL
120%RULE
BUS BAR MAIN BREAKER ALLOWED MAX
PV OCPD
200 200 40
STRINGS CONNECTED IN PARALLEL
HANWHA/QCELL Q.PEAK DUO ML-G10.A+395W
Vmp= 36.88V Voc= 45.27V
Isc= 11.1A Imp= 10.71A
CEC PTC POWER=371.73W
SOLAREDGE SE7600H-USSNBBL14 (240V)
(SI1-JUN20)INVERTER
MAX DC VOLTAGE: 480V
DC VOLTAGE INPUT RANGE: 400-480V @ 240V
PEAK POWER TRACKING VOLTAGE: 400-480V @ 240V
AC NOMINAL VOLTAGE/RANGE: 211-264V @ 240V
MAX AC OUTPUT CURRENT: 32A
CEC WEIGHTED EFFICIENCY: 99% @ 240V
SOLAREDGE POWER OPTIMIZER P401 (240V)MAX
DC VOLTAGE: 60V
DC VOLTAGE INPUT RANGE: 8-60V @ 240V PEAK
POWER TRACKING VOLTAGE: 8-80V @ 240V DC
NOMINAL VOLTAGE/RANGE: 5-60 @ 240V MAX DC
OUTPUT CURRENT: 15ADC
CEC WEIGHTED EFFICIENCY: 98.8% @ 240V
PER 2019 CEC, 690.64 (B)(7): LOCATE INVERTER OUTPUT AS FAR AS POSSIBLE FROM NORMAL POWER SUPPLY AT SERVICE
PANEL. RELOCATION OF EXISTING CIRCUITS MAY BE NEEDED. DO NOT CHANGE PHASING OF MULTI-WIRE CIRCUITS.
PERMANENT SIGNAGE AT PV SUPPLY CIRCUIT BREAKERS MUST SAY: WARNING! INVERTER OUTPUT CONNECTION. DO NOT
RELOCATE THIS OVERCURRENT DEVICE. SIGNAGE TO BE LOCATED ADJACENT TO BACKFED BREAKER.
SECOND #4 AWG TO UNDERGROUND
WATER SERVICE LESS THAN 5' FROM
WHERE IT ENTERS THE BUILDING
2634 N Oakmont
Ave05/24/22
Solar Photovoltaic System
BENJAMIN FERENC
2634 OAKMONT AVE
SANTA ANA, CA 92705
(626)367-3951
NEW GEN ENERGY
CORPORATION
P.O. Box 143, Placentia,
CA 92871-0143
Phone: (909) 215-5291
CSLB Lic# 949365 (C-10)
X:_____________________
_
ALL EQUIPMENT SHALL BE PROPERLY GROUNDED AND BONDED IN ACCORDANCE WITH ARTICLE 250. ALL
CIRCUITS CONNECTED TO MORE THAN ONE SOURCE SHALL HAVE OVERCURRENT DEVICES LOCATED SO
AS TO PROVIDE OVERCURRENT PROTECTION FROM ALL SOURCES 690.9 (A)
PV ARRAYS ARE PER SINGLE LINE.
PV ARRAY WIRING TO JUNCTION IS #10 AWG PV WIRE W/ FIELD INSTALLED MC CONNECTORS TO INTERFACE W/ MODULES.
PV POWER SOURCE DISCONNECT (INTEGRATED) RATED AT 36 AMPS, 600Vdc, NEMA 3R RAINPROOF.
USE UFER GROUND ELECTRODE SYSTEM FROM INVERTER TO EXISTING MAIN SERVICE GROUND ELECTRODE PER N.E.C.
250.58.
WHEN REQUIRED, GROUND ELECTRODE CONDUCTOR FROM INVERTER TO GROUND ELECTRODE TO BE MINIMUM PROTECTION
OF BARE ARMOR SHEATHED CABLE FOR ALL CONDUCTOR SIZES.
ALL GROUND CONNECTED TO MAIN SERVICE GROUND IN MAIN SERVICE PANEL.
INVERTER SHALL BE PER ATTACHED CUT SHEET.
AC DISCONNECT SHALL BE PER SINGLE LINE.
EQUIPMENT GROUNDING CONDUCTORS ON AC AND DC SIDE SIZED ACCORDING TO NEC 690.
POLE OF PV ARRAY REFERENCED TO GROUND AT THE INVERTER IN SINGLE LINE.
ALL CONDUCTORS SHALL BE 600V, 90C STANDARD COPPER. ALL CONDUCTORS IN CONDUIT SHALL BE THWN-2.
MAXIMUM DC VOLTAGE DROP SHALL BE 1.5%
ALL CONDUCTORS SHALL BE IN CONDUIT UNLESS OTHERWISE NOTED.
ALL WORK TO COMPLY WITH 2019 CALIFORNIA ELECTRIC CODE, 2019 CALIFORNIA BUILDING CODE
EXACT CONDUIT RUN LOCATIONS SUBJECT TO CHANGE.
3.0 PSF MAX (.5 PSF FROM RACKING, 2.5 PSF FROM MODULES) DEAD LOAD CONTRIBUTED FROM SOLAR ARRAY.
CONDUCTORS ON ROOF ARE TO BE 0.875" OFF OF THE ROOF SURFACE.
GEC TO BE CONNECTED TO EXISTING UFER. F UFER IS NOT PRESENT THEN A NEW GROUND ROD WILL BE ADDED FOR
GROUNDNG PURPOSES.
PV WIRES UTILIZED IN SYSTEM ARE UL-4703 COMPLIANT.
ON RESIDENTIAL ROOF INSTALLATIONS ALL RACKING AND MODULES ARE UL2703 COMPLIANT
PV-3A
DATE:
ELECTRICAL NOTES,
LOAD CALCS
ELECTRICAL NOTES
4/27/2022
GROUNDING:
IRONRIDGE INTEGRATED
CLAMP
MODEL: UFO
UL LISTED #2703
"PV SYSTEM TO BE IRREVERSIBLY CONNECTED TO UFER, IF UFER IS NOT PRESENT IT IS THE RESPONSIBILITY OF THE
CONTRACTOR TO BRING GROUNDING UP TO CODE."
2634 N Oakmont
Ave05/24/22
Solar Photovoltaic System
BENJAMIN FERENC
2634 OAKMONT AVE
SANTA ANA, CA 92705
(626)367-3951
NEW GEN ENERGY
CORPORATION
P.O. Box 143, Placentia,
CA 92871-0143
Phone: (909) 215-5291
CSLB Lic# 949365 (C-10)
X:______________________
PV-4
DATE:
REQUIRED SIGNAGE
4/27/2022
ELECTRICAL SHOCK HAZARD
TERMINALS ON THE LINE AND
LOAD SIDES MAY BE ENERGIZED
IN THE OPEN POSITION
WARNING
INSTALL LABEL ON: INVERTER(S), AC DISCONNECT(S), AC
COMBINER PANEL(IF APPLICABLE) PER CODE NEC-2017 690.13(B)
INSTALL LABEL ON: ADJACENT TO PV BREAKER (IF APPLICABLE)
PER CODE NEC2017 705.12(B)(2)(3)(b)
INSTALL LABEL ON INTERIOR AND EXTERIOR DC CONDUIT EVERY
10FT, AT EACH TURN, ABOVE AND BELOW PENETRATIONS, ON
EVERY JB/PULL BOX CONTAINING DC CIRCUITS.
PER CODE NEC2017 690.31(G)(3), 690.31(G)(4)
INSTALL LABEL ON: AC DISCONNECT(S), PHOTOVOLTAIC SYSTEM
POINT OF INTERCONNECTION. PER CODE NEC-2017 690.54
TURN RAPID SHUTDOWN
SWITCH TO THE "OFF"
POSITION TO
SHUTDOWN PV SYSTEM
AND REDUCE
SHOCK HAZARD
IN ARRAY
SOLAR ELECTRIC
PV PANELS
6"
SOLAR PV SYSTEM EQUIPPED
WITH RAPID SHUTDOWN
INSTALL LABEL ON: UTILITY SERVICE ENTRANCE / METER,
INVERTER/ DC DISCONNECT IF REQUIRED BY LOCAL AHJ OR OTHER
LOCATIONS AS REQUIRED BY LOCAL AHJ. PER CODE NEC2017
690.12
CAUTION
POWER TO THIS BUILDING IS ALSO SUPPLIED
FROM THE FOLLOWING SOURCES WITH
DISCONNECTS AS SHOWN
LABEL TO BE INSTALLED ON THE FACE OF THE SERVICE
METER PANEL:
OAKMONT AVE
METER AND MAIN
SERVICE
AC DISCONNECT
EQUIPMENT AT
DC DISCONNECT
INVERTER
2 1
1
2
3
EQUIPMENT AT
EACH MODULE
OPTIMIZER3
INVERTER OUTPUT CONNECTION
WARNING
DO NOT RELOCATE THIS
OVERCURRENT DEVICE
RAPID SHUTDOWN SWITCH
FOR SOLAR PV SYSTEM
WARNING: PHOTOVOLTAIC POWER SOURCE
PHOTOVOLTAIC AC DISCONNECT
RATED AC OUTPUT CURRENT:
NOMINAL OPERATING AC VOLTAGE:V
A
240
2634 N Oakmont
Ave05/24/22
2634 N Oakmont
Ave05/24/22
2634 N Oakmont
Ave05/24/22
2634 N Oakmont
Ave05/24/22
2634 N Oakmont
Ave05/24/22
9-23
2634 N Oakmont
Ave05/24/22
9-23
2634 N Oakmont
Ave05/24/22
9-23
2634 N Oakmont
Ave05/24/22
2634 N Oakmont
Ave05/24/22
9-23
2634 N Oakmont
Ave05/24/22
9-23
2634 N Oakmont
Ave05/24/22
Solar Photovoltaic System
BENJAMIN FERENC
2634 OAKMONT AVE
SANTA ANA, CA 92705
(626)367-3951
NEW GEN ENERGY
CORPORATION
P.O. Box 143, Placentia,
CA 92871-0143
Phone: (909) 215-5291
CSLB Lic# 949365 (C-10)
X:______________________
E1.0
DATE:
ELECTRICAL LINE
DIAGRAM
ELECTRICAL SINGLE LINE DIAGRAM
LOW MEAN TEMP
PER ASHRAE
HANDBOOK
MFR VOLTAGE TEMP
COEFFICIENT (oC)
VOLTAGE LOW
TEMP. CORR. (oC)
HIGH AMBIENT
TEMP (oC)
CONDUIT
HEIGHT (in)
ROOF TOP ADDED
TEMP PER Table ADJUSTED
TEMP
ROOF 2
-0.34 1.08
44 0.875 15.55 59.55
WALL 2 44 N/A 0 44
ATTIC 2 56 N/A 0 56
A
B
ELECTRICAL EQUIPMENT CALLOUTS
7.6kW INVERTER
SOLAREDGE SE7600H-USSNBBL14 (240V) (SI1-JUN20)
INVERTER 240 VAC, 32A NEMA 3R, UL LISTED,
(WITH INTEGRATED DC DISCONNECT)
AC DISCONNECT FUSED
240 VAC, 60A NEMA 3R, UL LISTED
PV BREAKER IS TO BE LOCATED AT
THE OPPOSITE END OF THE BUS BAR
FROM THE MAIN BREAKER.
4/27/2022
SOLAREDGE INVERTERS ARE
EQUIPPED WITH RAPID SHUTDOWN
REQUIREMENTS PER NEC 2017
SECTION 690.12
MAX PV VOLTAGE & CURRENT CALCS:
-2
TEMP COEFFICIENT (Voc) PER MANUFACTURER: -0.34 %/C
VOLTAGE CORRECTION:1.08
Vcorrection X Voptm
1.08 *400 = 432 V
OUTPUT FROM POWER OPTIMIZER PER STRING: 10.86 ADC
1.00 X Iopt
1.00 * 10.86 = 10.86 ADC
WIRE TAG # CONDUIT WIRE QTY
(CARRY
CURRENT)
WIRE
GAUGE
(AWG)
WIRE TYPE WIRE
LENGTH
(FEET)
TEMP
RATING:
WIRE
LOCATION
ADJUSTED
WIRE TEMP
WIRE
AMP
TEMP
CORRECTION
PER TABLE
310.15(B)(2)(a):
CONDUIT FILL
PER Table
310.15(B)(3)(a):
WIRE OCP: TERMINAL
75oC
RATING
STRINGS PER SET OF
WIRES (DC) OR # 0F
INVERTERS:
SHORT CIRCUIT
CURRENT (DC) OR
AC OUTPUT
NEC
690.8(A)
NEC
690.8(B)
STRING
AMPS
GROUND
SIZE
GROUND
TYPE
OCPD CHECK
1 3/4" EMT 4 10 60 ROOF 59.55 40 X 0.71 X 0.8 = 22.72 35 1 X 10.86 X 1.00 X 1 = 10.86 #8 THWN-2 NONE
2 3/4" EMT 3 8 THWN-2 5 WALL 44 55 X 0.87 X 1 = 47.85 50 1 X 32.00 X 1.25 X 1 = 40 #8 THWN-2 40A 2P
(N)200 A MAIN SERVICE
DISCONNECT
STRING 2
STRING 111 OPTIMIZERS/MODULES IN SERIES
W/ INTEGRATED RAPID SHUTDOWN
11 OPTIMIZERS/MODULES IN SERIES
W/ INTEGRATED RAPID SHUTDOWN
TO UTILITY GRID
BOND TO
EXISTING UFER
1PH, 120/240V,
3W
BI-DIRECTIONAL
UTILITY METER
(N)200 A MAIN
SERVICE
PANEL
NO CENTER
MAIN BREAKER
2-POLE 40A PV BREAKER,
BACKFED
AB
EXISTING AC
GROUNDING
ELECTRODE
8.690kW SOLAR ARRAY
22 HANWHA/QCELL 395W MODULES TOTAL
120%RULE
BUS BAR MAIN BREAKER ALLOWED MAX
PV OCPD
200 200 40
STRINGS CONNECTED IN PARALLEL
HANWHA/QCELL Q.PEAK DUO ML-G10.A+395W
Vmp= 36.88V Voc= 45.27V
Isc= 11.1A Imp= 10.71A
CEC PTC POWER=371.73W
SOLAREDGE SE7600H-USSNBBL14 (240V)
(SI1-JUN20)INVERTER
MAX DC VOLTAGE: 480V
DC VOLTAGE INPUT RANGE: 400-480V @ 240V
PEAK POWER TRACKING VOLTAGE: 400-480V @ 240V
AC NOMINAL VOLTAGE/RANGE: 211-264V @ 240V
MAX AC OUTPUT CURRENT: 32A
CEC WEIGHTED EFFICIENCY: 99% @ 240V
SOLAREDGE POWER OPTIMIZER P401 (240V)MAX
DC VOLTAGE: 60V
DC VOLTAGE INPUT RANGE: 8-60V @ 240V PEAK
POWER TRACKING VOLTAGE: 8-80V @ 240V DC
NOMINAL VOLTAGE/RANGE: 5-60 @ 240V MAX DC
OUTPUT CURRENT: 15ADC
CEC WEIGHTED EFFICIENCY: 98.8% @ 240V
PER 2019 CEC, 690.64 (B)(7): LOCATE INVERTER OUTPUT AS FAR AS POSSIBLE FROM NORMAL POWER SUPPLY AT SERVICE
PANEL. RELOCATION OF EXISTING CIRCUITS MAY BE NEEDED. DO NOT CHANGE PHASING OF MULTI-WIRE CIRCUITS.
PERMANENT SIGNAGE AT PV SUPPLY CIRCUIT BREAKERS MUST SAY: WARNING! INVERTER OUTPUT CONNECTION. DO NOT
RELOCATE THIS OVERCURRENT DEVICE. SIGNAGE TO BE LOCATED ADJACENT TO BACKFED BREAKER.
SECOND #4 AWG TO UNDERGROUND
WATER SERVICE LESS THAN 5' FROM
WHERE IT ENTERS THE BUILDING
2634 N Oakmont
Ave05/24/22
Solar Photovoltaic System
BENJAMIN FERENC
2634 OAKMONT AVE
SANTA ANA, CA 92705
(626)367-3951
ALL EQUIPMENT SHALL BE PROPERLY GROUNDED AND BONDED IN ACCORDANCE WITH ARTICLE 250.
ALL CIRCUITS CONNECTED TO MORE THAN ONE SOURCE SHALL HAVE OVERCURRENT DEVICES LOCATED
SO AS TO PROVIDE OVERCURRENT PROTECTION FROM ALL SOURCES 690.9 (A)
1. PV ARRAYS ARE PER SINGLE LINE.
2. PV ARRAY WIRING TO JUNCTION IS #10 AWG PV WIRE W/ FIELD INSTALLED MC CONNECTORS TO INTERFACE W/ MODULES.
3. CONTINUOUS PV WIRE FROM ARRAY TO INVERTER VIA CONDUIT. USE HEYCO CORD GRIPS TO TRANSITION FROM CONDUIT.
4. PV POWER SOURCE DISCONNECT (INTEGRATED) RATED AT 6 0 AMPS, 600Vdc, NEMA 3R RAINPROOF.
5. USE UFER GROUND ELECTRODE SYSTEM FROM INVERTER TO EXISTING MAIN SERVICE GROUND ELECTRODE PER N.E.C.
250.58.
6. WHEN REQUIRED, GROUND ELECTRODE CONDUCTOR FROM INVERTER TO GROUND ELECTRODE TO BE MINIMUM
PROTECTION OF BARE ARMOR SHEATHED CABLE FOR ALL CONDUCTOR SIZES.
7. ALL GROUND CONNECTED TO MAIN SERVICE GROUND IN MAIN SERVICE PANEL.
8. CONNECTORS SHALL BE MC-4.
9. INVERTER SHALL BE PER ATTACHED CUT SHEET.
10. AC DISCONNECT SHALL BE PER SINGLE LINE.
11. EQUIPMENT GROUNDING CONDUCTORS ON AC AND DC SIDE SIZED ACCORDING TO NEC 690.
12. POLE OF PV ARRAY REFERENCED TO GROUND AT THE INVERTER IN SINGLE LINE.
13. ALL CONDUCTORS SHALL BE 600V, 90C STANDARD COPPER. ALL CONDUCTORS IN CONDUIT SHALL BE THWN-2.
14. MAXIMUM DC VOLTAGE DROP SHALL BE 1.5%
15. ALL CONDUCTORS SHALL BE IN CONDUIT UNLESS OTHERWISE NOTED.
16. ALL WORK TO COMPLY WITH 2019 CALIFORNIA ELECTRIC CODE, 2019 CALIFORNIA BUILDING CODE
17. NOT USED.
18. EXACT CONDUIT RUN LOCATIONS SUBJECT TO CHANGE.
19. 3.0 PSF MAX (.5 PSF FROM RACKING, 2.5 PSF FROM MODULES) DEAD LOAD CONTRIBUTED FROM SOLAR ARRAY.
20. CONDUCTORS ON ROOF ARE TO BE 0.875" OFF OF THE ROOF SURFACE.
21. GEC TO BE CONNECTED TO EXISTING UFER. iF UFER IS NOT PRESENT THEN A NEW GROUND ROD WILL BE ADDED FOR
GROUNDNG PURPOSES.
22. PV WIRES UTILIZED IN SYSTEM ARE UL-4703 COMPLIANT.
23. ON RESIDENTIAL ROOF INSTALLATIONS ALL RACKING AND MODULES ARE UL2703 COMPLIANT
RACKING & MODULES ARE GROUNDED VIA A CONTINUOUS #6AWG COPPER CONDUCTOR CONNECTED W/
IRONRIDGE INTEGRATED GROUNDING.
E1.1
DATE:
ELECTRICAL NOTES,
LOAD CALCS
ELECTRICAL NOTES
4/27/2022
GROUNDING:
IRONRIDGE INTEGRADED
CLAMP
MODEL: UFO
UL LISTED #2703
"PV SYSTEM TO BE IRREVERSIBLY CONNECTED TO UFER, IF UFER IS NOT PRESENT IT IS THE RESPONSIBILITY OF THE
CONTRACTOR TO BRING GROUNDING UP TO CODE."
NEW GEN ENERGY
CORPORATION
P.O. Box 143, Placentia,
CA 92871-0143
Phone: (909) 215-5291
CSLB Lic# 949365 (C-10)
X:_____________________
_
2634 N Oakmont
Ave05/24/22
Expedited Permit Process for PV Systems1
Expedited Permit Process for PV Systems
Standard String System
The Solar America Board for Codes and Standards (Solar ABCs) Expedited Permit Pro-
cess provides a means to differentiate systems that can be permitted quickly and easily
due to their similarity with the majority of small-scale PV systems. Those systems with
unique characteristics may be handled with small additions to this Expedited Permit
Process or may require much more information, depending on the uniqueness of the
installation.
The following pages contain forms for the Standard String System to use with the Expe-
dited Permit Process. The Micro-Inverter, AC Module, and Supply-Side Connection forms
are also available as interactive PDF files at www.solarabcs.org/permitting. In jurisdic-
tions that have adopted the Expedited Permit Process for PV Systems, these forms can
be filled out electronically and submitted in either printed form and via email. An elec-
tronic format is used so that the supplied information is standardized and legible for the
local jurisdiction.
2634 N Oakmont
Ave05/24/22
Expedited Permit Process for PV Systems2
Expedited Permit Process for Small-Scale PV Systems
Standard String System
The information in this guideline is intended to help local jurisdictions and contractors identify when PV system installations
are simple, needing only a basic review, and when an installation is more complex. It is likely that 50%-75% of all residential
systems will comply with these simple criteria. For projects that fail to meet the simple criteria, resolution steps have been
suggested to provide as a path to permit approval.
Required Information for Permit:
1. Site plan showing location of major components on the property. This drawing need not be exactly to scale, but it
should represent relative location of components at site (see supplied example site plan). PV arrays on dwellings
with a 3’ perimeter space at ridge and sides may not need separate fire service review.
2. Electrical diagram showing PV array configuration, wiring system, overcurrent protection, inverter, disconnects,
required signs, and ac connection to building (see supplied standard electrical diagram).
3. Specification sheets and installation manuals (if available) for all manufactured components including, but not
limited to, PV modules, inverter(s), combiner box, disconnects, and mounting system.
Step 1: Structural Review of PV Array Mounting System
Is the array to be mounted on a defined, permitted roof structure? l Yes l No
If No due to non-compliant roof or a ground mount, submit completed worksheet for the structure WKS1.
Roof Information:
1. Is the roofing type lightweight (Yes = composition, lightweight masonry, metal, etc…)__________________________
____________________________________________________________________________________________________
If No, submit completed worksheet for roof structure WKS1 (No = heavy masonry, slate, etc…).
2. Does the roof have a single roof covering? l Yes l No
If No, submit completed worksheet for roof structure WKS1.
3. Provide method and type of weatherproofing roof penetrations (e.g. flashing, caulk).____________________________
Mounting System Information:
1. Is the mounting structure an engineered product designed to mount PV modules with no more than an 18” gap
beneath the module frames? l Yes l No
If No, provide details of structural attachment certified by a design professional.
2. For manufactured mounting systems, fill out information on the mounting system below:
a. Mounting System Manufacturer ___________Product Name and Model#________________________________
b. Total Weight of PV Modules and Rails ___________lbs
c. Total Number of Attachment Points____________
d. Weight per Attachment Point (b÷c)_________________lbs (if greater than 45 lbs, see WKS1)
e. Maximum Spacing Between Attachment Points on a Rail ______________inches (see product manual for
maximum spacing allowed based on maximum design wind speed)
f. Total Surface Area of PV Modules (square feet)_________________ ft 2
g. Distributed Weight of PV Module on Roof (b÷f)_______________ lbs/ft2
If distributed weight of the PV system is greater than 5 lbs/ft2, see WKS1.
Step 2: Electrical Review of PV System (Calculations for Electrical Diagram)
In order for a PV system to be considered for an expedited permit process, the following must apply:
1. PV modules, utility-interactive inverters, and combiner boxes are identified for use in PV systems.
2. The PV array is composed of 4 series strings or less per inverter.
3. The total inverter capacity has a continuous ac power output 13,440 Watts or less
4. The ac interconnection point is on the load side of service disconnecting means (690.64(B)).
5. One of the standard electrical diagrams (E1.1, E1.1a, E1.1b, or E1.1c) can be used to accurately represent the PV
system. Interactive PDF diagrams are available at www.solarabcs.org/permitting.
Fill out the standard electrical diagram completely. A guide to the electrical diagram is provided to help the applicant
understand each blank to fill in. If the electrical system is more complex than the standard electrical diagram can effectively
communicate, provide an alternative diagram with appropriate detail.
2634 N Oakmont
Ave05/24/22
Ex
p
e
d
i
t
e
d
P
e
r
m
i
t
P
r
o
c
e
s
s
f
o
r
P
V
S
y
s
t
e
m
s
3
Standard String System Site Plan
New Gen Energy Corporation
PO Box 143 BENJAMIN FERENC
Placentia, CA 92870
2634 OAKMONT AVE SANTA ANA, CA 92705
909-215-5291
8.096 kW AC
2634 N Oakmont
Ave05/24/22
Ex
p
e
d
i
t
e
d
P
e
r
m
i
t
P
r
o
c
e
s
s
f
o
r
P
V
S
y
s
t
e
m
s
4
Standard String System Electrical Diagram
New Gen Energy Corporation
PO Box 143 BENJAMIN FERENC
Placentia, CA 92870
2634 OAKMONT AVE SANTA ANA, CA 92705
909-215-5291
8.096 kW AC
2634 N Oakmont
Ave05/24/22
Ex
p
e
d
i
t
e
d
P
e
r
m
i
t
P
r
o
c
e
s
s
f
o
r
P
V
S
y
s
t
e
m
s
5
Notes for Standard String System Electrical Diagram
Contractor Name,
Address and Phone:
_________________
_________________
_________________
_________________
Notes for One-Line Standard Electrical
Diagram for Single-Phase PV Systems
Site Name: __________________________
Site Address: ________________________
System AC Size: ______________________
SIZE FSCM NO DWG NO REV
SCALE NTS Date:SHEET
Drawn By:
Checked By:
MAX POWER-POINT CURRENT (IMP)
MAX POWER-POINT VOLTAGE (VMP)
OPEN-CIRCUIT VOLTAGE (VOC)
SHORT-CIRCUIT CURRENT (ISC)
MAX SERIES FUSE (OCPD)
MAXIMUM POWER (PMAX)
MAX VOLTAGE (TYP 600VDC)
VOC TEMP COEFF (mV/oC or %/oC )
IF COEFF SUPPLIED, CIRCLE UNITS
A
V
V
A
A
W
V
MODULE MAKE
MODULE MODEL
PV MODULE RATINGS @ STC (Guide Section 5)
MAX DC VOLT RATING
MAX POWER @ 40oC
NOMINAL AC VOLTAGE
MAX AC CURRENT
MAX OCPD RATING
V
W
V
A
A
INVERTER MAKE
INVERTER MODEL
INVERTER RATINGS (Guide Section 4)
1) IF UTILITY REQUIRES A VISIBLE-BREAK SWITCH, DOES THIS SWITCH MEET THE
REQUIREMENT? YES NO N/A
2) IF GENERATION METER REQUIRED, DOES THIS METER SOCKET MEET THE
REQUIREMENT? YES NO N/A
3) SIZE PHOTOVOLTAIC POWER SOURCE (DC) CONDUCTORS BASED ON MAX
CURRENT ON NEC 690.53 SIGN OR OCPD RATING AT DISCONNECT
4) SIZE INVERTER OUTPUT CIRCUIT (AC) CONDUCTORS ACCORDING TO INVERTER
OCPD AMPERE RATING. (See Guide Section 9)
5) TOTAL OF ______ INVERTER OCPD(s), ONE FOR EACH INVERTER. DOES TOTAL
SUPPLY BREAKERS COMPLY WITH 120% BUSBAR EXCEPTION IN 690.64(B)(2)(a)?
YES NO
NOTES FOR INVERTER CIRCUITS (Guide Section 8 and 9):
1.) LOWEST EXPECT AMBIENT TEMPERATURE BASED ON ASHRAE MINIMUM MEAN
EXTREME DRY BULB TEMPERATURE FOR ASHRAE LOCATION MOST SIMILAR TO
INSTALLATION LOCATION. LOWEST EXPECTED AMBIENT TEMP ______oC
2.) HIGHEST CONTINUOUS AMBIENT TEMPERATURE BASED ON ASHRAE HIGHEST
MONTH 2% DRY BULB TEMPERATURE FOR ASHRAE LOCATION MOST SIMILAR TO
INSTALLATION LOCATION. HIGHEST CONTINUOUS TEMPERATURE _____oC
2.) 2005 ASHRAE FUNDEMENTALS 2% DESIGN TEMPERATURES DO NOT EXCEED
47oC IN THE UNITED STATES (PALM SPRINGS, CA IS 44.1 oC). FOR LESS THAN 9
CURRENT-CARRYING CONDUCTORS IN ROOF-MOUNTED SUNLIT CONDUIT AT
LEAST 0.5" ABOVE ROOF AND USING THE OUTDOOR DESIGN TEMPERATURE OF
47oC OR LESS (ALL OF UNITED STATES),
a) 12 AWG, 90oC CONDUCTORS ARE GENERALLY ACCEPTABLE FOR MODULES
WITH Isc OF 7.68 AMPS OR LESS WHEN PROTECTED BY A 12-AMP OR SMALLER
FUSE.
b) 10 AWG, 90oC CONDUCTORS ARE GENERALLY ACCEPTABLE FOR MODULES
WITH Isc OF 9.6 AMPS OR LESS WHEN PROTECTED BY A 15-AMP OR SMALLER
FUSE.
NOTES FOR ARRAY CIRCUIT WIRING (Guide Section 6 and 8 and Appendix D):
OCPD = OVERCURRENT PROTECTION DEVICE
NATIONAL ELECTRICAL CODE ® REFERENCES
SHOWN AS (NEC XXX.XX)
NOTES FOR ALL DRAWINGS:
SIGNSSEE GUIDE SECTION 7
SIGN FOR DC DISCONNECT
SIGN FOR INVERTER OCPD AND
AC DISCONNECT (IF USED)
RATED MPP CURRENT
RATED MPP VOLTAGE
MAX SYSTEM VOLTAGE
MAX CIRCUIT CURRENT
A
V
V
A
PHOTOVOLTAIC POWER SOURCE
WARNING: ELECTRICAL SHOCK
HAZARDLINE AND LOAD MAY BE
ENERGIZED IN OPEN POSITION
AC OUTPUT CURRENT
NOMINAL AC VOLTAGE
A
V
SOLAR PV SYSTEM
AC POINT OF CONNECTION
THIS PANEL FED BY MULTIPLE
SOURCES (UTILITY AND SOLAR)
New Gen Energy Corporation
PO Box 143 BENJAMIN FERENC
Placentia, CA 92870
2634 OAKMONT AVE SANTA ANA, CA 92705
909-215-5291
8.096 kW AC
2634 N Oakmont
Ave05/24/22
Solar Photovoltaic System
BENJAMIN FERENC
2634 OAKMONT AVE
SANTA ANA, CA 92705
(626)367-3951
NEW GEN ENERGY
CORPORATION
P.O. Box 143, Placentia,
CA 92871-0143
Phone: (909) 215-5291
CSLB Lic# 949365 (C-10)
X:______________________
PV-0.0
DATE:
REQUIRED SIGNAGE
4/27/2022
ELECTRICAL SHOCK HAZARD
TERMINALS ON THE LINE AND
LOAD SIDES MAY BE ENERGIZED
IN THE OPEN POSITION
WARNING
INSTALL LABEL ON: INVERTER(S), AC DISCONNECT(S), AC
COMBINER PANEL(IF APPLICABLE) PER CODE NEC-2017 690.13(B)
INSTALL LABEL ON: ADJACENT TO PV BREAKER (IF APPLICABLE)
PER CODE NEC2017 705.12(B)(2)(3)(b)
INSTALL LABEL ON INTERIOR AND EXTERIOR DC CONDUIT EVERY
10FT, AT EACH TURN, ABOVE AND BELOW PENETRATIONS, ON
EVERY JB/PULL BOX CONTAINING DC CIRCUITS.
PER CODE NEC2017 690.31(G)(3), 690.31(G)(4)
INSTALL LABEL ON: AC DISCONNECT(S), PHOTOVOLTAIC SYSTEM
POINT OF INTERCONNECTION. PER CODE NEC-2017 690.54
TURN RAPID SHUTDOWN
SWITCH TO THE "OFF"
POSITION TO
SHUTDOWN PV SYSTEM
AND REDUCE
SHOCK HAZARD
IN ARRAY
SOLAR ELECTRIC
PV PANELS
6"
SOLAR PV SYSTEM EQUIPPED
WITH RAPID SHUTDOWN
INSTALL LABEL ON: UTILITY SERVICE ENTRANCE / METER,
INVERTER/ DC DISCONNECT IF REQUIRED BY LOCAL AHJ OR OTHER
LOCATIONS AS REQUIRED BY LOCAL AHJ. PER CODE NEC2017
690.12
CAUTION
POWER TO THIS BUILDING IS ALSO SUPPLIED
FROM THE FOLLOWING SOURCES WITH
DISCONNECTS AS SHOWN
LABEL TO BE INSTALLED ON THE FACE OF THE SERVICE
METER PANEL:
OAKMONT AVE
METER AND MAIN
SERVICE
AC DISCONNECT
EQUIPMENT AT
DC DISCONNECT
INVERTER
2 1
1
2
3
EQUIPMENT AT
EACH MODULE
OPTIMIZER3
INVERTER OUTPUT CONNECTION
WARNING
DO NOT RELOCATE THIS
OVERCURRENT DEVICE
RAPID SHUTDOWN SWITCH
FOR SOLAR PV SYSTEM
WARNING: PHOTOVOLTAIC POWER SOURCE
PHOTOVOLTAIC AC DISCONNECT
RATED AC OUTPUT CURRENT:
NOMINAL OPERATING AC VOLTAGE:V
A
240
2634 N Oakmont
Ave05/24/22
PV 1.0
2634 N Oakmont
Ave05/24/22
PV 2.0
2634 N Oakmont
Ave05/24/22
PV 2.1
2634 N Oakmont
Ave05/24/22
PV 3.0
2634 N Oakmont
Ave05/24/22
9-23
PV 4.0
2634 N Oakmont
Ave05/24/22
9-23
PV 4.1
2634 N Oakmont
Ave05/24/22
9-23
PV 4.2
2634 N Oakmont
Ave05/24/22
9-23
PV 4.3
2634 N Oakmont
Ave05/24/22
9-23
PV 4.4
2634 N Oakmont
Ave05/24/22
PV 5.0
2634 N Oakmont
Ave05/24/22
Solar Photovoltaic System
BENJAMIN FERENC
2634 OAKMONT AVE
SANTA ANA, CA 92705
(626)367-3951
SCALE: 1":10'-0" ROOF PLAN
MSP SIZE IS AN
ATTACHMENT POINTS:
R1
ARRAY 1
22 SOLAR MODULES
26 ATTACHMENTS
@ 72" O.C. MAX.
3/4" EMT CONDUIT,
TO RUN ON ROOF
AND UNDER EAVES
WITH MC-4 CONNECTORS
INTERIOR RAFTER
SUPPORT, TYP.
EXT. WALL
(E)ROOF
FRAMING, SEE
ROOF INFO
LOCATED AT EACH
PANEL
OPTIMIZER
S1.0
ARRAY AND ROOF INFO
DATE:
ROOF PLAN
N
MODULE TYPE, DIMENSIONS & WEIGHT
(N)200 A
" O.C. MAX72
(E)PLUMBING VENT
(E)ROOF VENT
(E)CHIMNEY
FIRE ACCESS POINT
(E)PATIO COVER
ACCESSES IDENTIFIED ARE AT STRONG POINTS OF ROOF WHICH DO NOT HAVE OPENINGS BELOW LADDER ACCESSES.
PER CRC R331.4.1.
PANEL TYPE:HANWHA/QCELL Q.PEAK DUO ML-G10.A+ 395W
PANEL WEIGHT:48.5 lb
PANEL DIMENSIONS:74 " X 41.14 "
PANEL AREA:21.14 SF
UNIT WEIGHT OF PANELS:48.5/21.14 = 2.29 PSF
INVERTER & RACKING:0.19 PSF
AREA PER ATTACHMENT:6'X2.48 = 14.9 SF
WEIGHT PER ATTACHMENT:14.9X2.7 = 40.23 LB
4/27/2022
SINGLE LAYER OF ROOFING
PITCH AZIMUTH MATERIAL SP SQ.FT ARRAY SQ.FT RAFTER SPECS
ROOF
AREA %
R #1 270 COMP. SHINGLE 1182 465.08 2X6@24"39.3%
SOLAREDGE INVERTERS ARE
EQUIPPED WITH RAPID SHUTDOWN
REQUIREMENTS PER NEC 2017
SECTION 690.12
FIRE ACCESS POINT
NEW GEN ENERGY
CORPORATION
P.O. Box 143, Placentia,
CA 92871-0143
Phone: (909) 215-5291
CSLB Lic# 949365 (C-10)
X:______________________
9-23
2634 N Oakmont
Ave05/24/22
MIN. 2.5"PENETRATION SEALED W/
SIKAFLEX 1A
(E)ROOF FRAMING, SEE ROOF INFO
MATCH (E) ROOF SLOPE
PV MODULES
IRONRIDGE XR-10 RAIL
IRONRIDGE FLASHVUE
Solar Photovoltaic System
BENJAMIN FERENC
2634 OAKMONT AVE
SANTA ANA, CA 92705
(626)367-3951
NEW GEN ENERGY
CORPORATION
P.O. Box 143, Placentia,
CA 92871-0143
Phone: (909) 215-5291
CSLB Lic# 949365 (C-10)
X:______________________
SCALE: 1/2" = 1'-0"ATTACHMENT DETAIL
S1.1
DATE:
ATTACHMENT
DETAILS
4/27/2022
1'-6" 9'-3" 9'-3"
RAFTER SECTION DETAIL
9-23
5/16" x 3.5" STAINLESS STEEL LAG BOLT
2634 N Oakmont
Ave05/24/22
2634 N Oakmont
Ave05/24/22
Rev: 7/15/2021
RESIDENTIAL
PHOTOVOLTAIC
CHECKLIST
SOL-01 CBC 2019
Solar Photovoltaic (PV) Checklist for Detached SINGLE FAMILY RESIDENCES Only
Instructions: The licensed contractor of record shall complete all sections, answer the ten questions and
sign the certification section below. A copy of this form shall be attached to each of TWO sets of plans, of
minimum 11” x 17” size. If answering NO to any of the questions, plan check shall be required.
Project Address:
Contractor Company Name:
Contractor License Number:
YES NO Are the following applicable to the proposed project?
1. Will the PV system layout provide the required three-foot wide clear access pathways
per Section 605.11 of the California Fire Code, and is this shown on the roof plan?
2. Will the PV system be installed on a roof having only one roofing layer with no
overlays?
3. Will the PV array be flush mounted to the existing roof so that the plane of the
modules (panels) are parallel to the plane of the roof?
4. Will the PV system weigh maximum 4 pounds per square feet or less?
5. Will the PV system be installed where the modules do not overhang any roof edges
(such as eaves, gabled ends, ridges and hips)?
6. Will the PV system be installed with a space of 2” minimum to 10” maximum between
the underside of modules and the surface of the roof?
7. Will the PV system be installed without using any ballast system or counter-weight
system?
8. Will the anchors be installed with a maximum horizontal anchor spacing of 6 feet
and is this maximum horizontal spacing shown on the plans?
9. Will the minimum 5/16” lag screws be installed with a minimum of 2-1/2 inch
embedment into roof rafters (with pre-drilled holes) and is this minimum embedment
shown on the plans?
10. Are ALL the structural pages of the plans stamped and signed by a California
licensed professional engineer? (including project specific site plan, PV layout,
anchorage spacing, anchorage details and manufacturer’s PV support information.)
I certify under penalty of perjury under the laws of the State of California that the above is true:
Print Name: Signature:
Phone Number: Date:
Email Address:
Planning & Building Agency
Building Safety Division
20 Civic Center Plaza
P.O. Box 1988 (M-19)
Santa Ana, CA 92702
(714) 647-5800
www.santa-ana.org
2634 Oakmont Ave, Santa Ana CA 92705
New Gen Enrgy Corporation
949365
X
X
X
X
X
X
X
X
X
X
Jennifer Pickering Kronick
909-215-5291
jennifer@newgensolar.net
05-10-2022
2634 N Oakmont
Ave05/24/22
Structural Calculations for a Roof Mounted Solar Photovoltaic System for:
Benjamin Ferenc Residence
2634 Oakmont Ave.,
Santa Ana, CA 92705
Applicable Codes:
2019 California Building Code, 2019 California Electric Code,
2019 California Mechanical Code, American Society of Civil Engineers
Standard ASCE 7-16 Minimum Design Loads for Buildings and Other
Structures, American Wood Council 2018 National Design Specification
for Wood Construction, Local Municipal Code, and all other codes which
are adopted by reference or enacted by law.
Assumed Design Parameters:
The existing structure has been built under a building permit and is in its
original condition. The existing roof structure is capable of its code
required live load and the ability of the roof structure to support live loads
has not been substantially reduced by the age of the structure, termites or
mold, or unauthorized modifications to the existing structure. Solar Energy
Contractor shall make inspection of the existing roof framing system prior
to installation of the roof mounted solar energy system to verify that the
existing roof is capable of supporting minimum roof live loads.
Assumed Design Parameters:
All 2x members are grade Douglas Fir #2 or better
All 4x members are grade Douglas Fir #1 or better
All Roof Connectors are Simpsons Strong-Tie or Equal
All Concrete Foundations are f'c = 2500 psi or stronger
Original Structure was built to the Type-V Wood Framed Standards
of the Applicable Building Code at the time of Construction.
Loyd W. Martin Professional Engineer, Inc.
9924 Universal Boulevard #224-406 Orlando, FL 32819 Tel:1.310.464.1804
Email: loydwmartin@gmail.com www.loydwmartin.com
2022-2018 New Gen Solar Benjamin Ferenc Residence
Sht # 1 of 7
Date: May 09, 2022
Exp. 3-31-19
No. C58724
NITRAMW.DYO
REGISTEREDPROFESSIONALENGINEER
C
V
L
FOETATS
ALIFORNIAICIL
-23
2634 N Oakmont
Ave05/24/22
w DL + LL
R1 R2
w = 30 psf x 2 ft. = 60 plf
11.8'
= 60 plf x 11.8 ft. = 708 lbs
Note to Building Official:
Based upon a review of the proposed plans I am confident that the
existing roof framing system is capable of safely supporting the additional
loads caused by the solar photovoltaic energy system. The contractor
shall field verify that the existing roof structure is in its original permitted
condition and verify that it can support the normal code required roof live
loads. Attached in this package are several calculations showing that the
roof members can support the additional weight of the solar array.
Furthermore, an analysis of the solar array's support for wind forces and a
seismic analysis of the existing structure are also included.
Check 2x6 Rafters @ 24" O.C.*:
Total load on rafter
*Note: Contractor to Field Verify Framing
Loyd W. Martin Professional Engineer, Inc.
9924 Universal Boulevard #224- 406 Orlando, FL 32819 Tel:1.310.464.1804
Email: loydwmartin@gmail.com www.loydwmartin.com
Sht # 2 of 7
2021-417 Solar Deployed Francisco Pelayo Residence Date: February 05, 20212021-417 Solar Deployed Fransisco Pelayo Residence2021-419 Better Earth Erlinda San Jose Residence Date: February 05, 2021
Exp. 3-31-19
No. C58724
NITRAMW.DYO
REGISTEREDPROFESSIONALENGINEER
C
V
L
FOETATS
ALIFORNIAICIL
-23
Date: June 04, 20212021-2029 Better Earth Emily Golding Residence Date: July 26, 20212021-2938 Better Earth Gary Richardson Residence Date: July 26, 20212021-2941 Better Earth Heather Kelly Residence Date: July 30, 20212021-3015 Better Earth Sally West Residence Date: December 13, 20212021-5468 Better Earth Kimberly Adams Residence2022-044 Divine Power Michael Teal Residence Date: January 6, 2022
( Assume max rafter span = 11.8 ft. )
Date: February 1, 20222022-367 Connect Solar Joshua Georgopoulos Residence Date: May 09, 20222022-2018 New Gen Solar Benjamin Ferenc Residence
2634 N Oakmont
Ave05/24/22
w DL + LL = 30 psf x 2 ft. = 60 plf
= 60 plf x 4.2 + 28 plf x 7.6 ft. + ( 6' x 2.75' x 3 psf x 3 )
= 613 lbs < 708 lbs OK
Check attachment of Support to Existing Structure for Wind Uplift
CHECK SOLAR STRUCTURE ATTACHMENTS PER ASCE 7-16 WIND LOADS ON BUILDING
APPURTENANCES AND OTHER STRUCTURES Section 29.4.4 THEREFORE CHECK
ATTACHMENT FOR TYPICAL CRITICAL LOAD WHICH IS THE EDGE ZONE - ZONE 2.
NOTE: PER DEFINITION ON SHEETS 246 & 247 OF ASCE 7-16 EFFECTIVE WIND AREA:
"FOR ROOFTOP SOLAR ARRAYS, THE EFFECTIVE WIND AREA IN FIG. 29.4-7 IS
EQUAL TO THE TRIBUTARY AREA FOR THE STRUCTURAL ELEMENT BEING
CONSIDERED, EXCEPT THAT THE WIDTH OF THE EFFECTIVE WIND AREA NEED NOT
BE LESS THAN ONE-THIRD ITS LENGTH."
EFFECTIVE AREA = 15 SQ FT
w DL + LLreduced = 22 psf x 2 ft. = 44 plf
Check 2x6 Rafters @ 24" O.C.:
Total load on rafter
Loyd W. Martin Professional Engineer, Inc.
9924 Universal Boulevard #224- 406 Orlando, FL 32819 Tel:1.310.464.1804
Email: loydwmartin@gmail.com www.loydwmartin.com
Sht # 3 of 7
2021-417 Solar Deployed Francisco Pelayo Residence Date: February 05, 20212021-417 Solar Deployed Fransisco Pelayo Residence
R1 R2
11.8'
P
w LLw DL
2021-419 Better Earth Erlinda San Jose Residence Date: February 05, 2021
Exp. 3-31-19
No. C58724
NITRAMW.DYO
REGISTEREDPROFESSIONALENGINEER
C
V
L
FOETATS
ALIFORNIAICIL
-23
Date: June 04, 20212021-2029 Better Earth Emily Golding Residence Date: July 26, 20212021-2938 Better Earth Gary Richardson Residence Date: July 26, 20212021-2941 Better Earth Heather Kelly Residence
P
Date: July 30, 20212021-3015 Better Earth Sally West Residence Date: December 13, 20212021-5468 Better Earth Kimberly Adams Residence2022-044 Divine Power Michael Teal Residence Date: January 6, 2022
P
4.2'7.6'
Date: February 1, 20222022-367 Connect Solar Joshua Georgopoulos Residence Date: May 09, 20222022-2018 New Gen Solar Benjamin Ferenc Residence
2634 N Oakmont
Ave05/24/22
Loyd W. Martin Professional Engineer, Inc.
9924 Universal Boulevard #224-406 Orlando, FL 32819 Tel:1.310.464.1804
Email: loydwmartin@gmail.com www.loydwmartin.com
p =qh ðGCp ÞðγEÞðγa Þ
Kz = 0.9 (Exposure C, Height = 20 ft or less)
Kz = velocity pressure coefficient,
q h =0.00256Kz KztKdKeV 2
Check attachment of Support to Existing Structure for Wind Uplift - Cont'd
Exp. 3-31-19
No. C58724
NITRAMW.DYO
REGISTEREDPROFESSIONALENGINEER
C
V
L
FOETATS
ALIFORNIAICIL
12
Tributary Area to Each Solar Mount = 6 ft. x 2.75 ft. = 16.5 sq. ft. ( Max )
Calculate Design Wind Pressure at each support (Wind Speed 130 mph Exposure C):
Eq'n 29.4-7 ASCE 7-16
Section 26.10.1 ASCE 7-16
Kzt = Topographical Factor = 1.0
Ke = Ground Elevation Factor = 1.0
V = 130 mph ; VASD = 101 mph Table 1609.3.1 2019 CBC
qh =0.00256 (0.9) (1.0) (0.85) (1.0) (101)2
qh =20 psf
p 20 psf (-2.0) (1.5) (0.7) = -42 psf
= -2.0 (Zone 2 ; Effective Area = 15 sq. ft. )
= Exposure Factor = 1.5
GCp = Solar Array Pressure Equalization Factor = 0.7 Fig. 29.4-8 ASCE 7-16
Design (Factored) Uplift at each support = 0.6 x 693 lbs = 416 lbs
Nominal (Unfactored) Uplift at each support = 42 psf x 16.5 sq. ft. = 693 lbs
Note: Section 2.4.1 of ASCE 7-16, Basic Load Combinations for Allowable Stress
Load per lag screw = 416 lbs / 1 = 416 lbs
Design. Note: Applicable Load Combination #5 (D + 0.6W)
p =qh ðGCp ÞðγEÞðγa Þ
Eq'n 26.10-1 ASCE 7-16
Note:
Kd = Wind Directionality Factor = 0.85
GCp )
γE
γa
=
Sht # 4 of 7
2021-417 Solar Deployed Francisco Pelayo Residence Date: February 05, 20212021-417 Solar Deployed Fransisco Pelayo Residence2021-419 Better Earth Erlinda San Jose Residence Date: February 05, 2021
Exp. 3-31-19
No. C58724
NITRAMW.DYO
REGISTEREDPROFESSIONALENGINEER
C
V
L
FOETATS
ALIFORNIAICIL
-23
Date: June 04, 20212021-2029 Better Earth Emily Golding Residence Date: July 26, 20212021-2938 Better Earth Gary Richardson Residence Date: July 26, 20212021-2941 Better Earth Heather Kelly Residence Date: July 30, 20212021-3015 Better Earth Sally West Residence Date: December 13, 20212021-5468 Better Earth Kimberly Adams Residence2022-044 Divine Power Michael Teal Residence Date: January 6, 2022 Date: February 1, 20222022-367 Connect Solar Joshua Georgopoulos Residence Date: May 09, 20222022-2018 New Gen Solar Benjamin Ferenc Residence
2634 N Oakmont
Ave05/24/22
Loyd W. Martin Professional Engineer, Inc.
9924 Universal Boulevard #224-406 Orlando, FL 32819 Tel:1.310.464.1804
Email: loydwmartin@gmail.com www.loydwmartin.com
Check attachment of Support to Existing Structure for Wind Uplift - Cont'd
Use Support connected to 2x Min. Roof Member
w/ (1) 5/16" x 3.5" lag screw per connection minimum.
Determine allowable load per 5/16" lag screw w/ 2.5" embedment into wood below
according to the 2018 NDS.
W ' = W x Cd x Ct Table 10.3.1 2018 NDS
where:
W = 266 lbs / in. of embedment per Table 12.2A
Cd = 1.6 per Table 2.3.2 of 2018 NDS
Ct = 1.0 per Table 10.3.4 of 2018 NDS
W ' = 266 lbs/ in. x 2.5 in. x 1.6 x 1.0 = 1,064 lbs > 416 lbs OK
Sht # 5 of 7
2021-417 Solar Deployed Francisco Pelayo Residence Date: February 05, 20212021-417 Solar Deployed Fransisco Pelayo Residence2021-419 Better Earth Erlinda San Jose Residence Date: February 05, 2021
Exp. 3-31-19
No. C58724
NITRAMW.DYO
REGISTEREDPROFESSIONALENGINEER
C
V
L
FOETATS
ALIFORNIAICIL
-23
Date: June 04, 20212021-2029 Better Earth Emily Golding Residence Date: July 26, 20212021-2938 Better Earth Gary Richardson Residence Date: July 26, 20212021-2941 Better Earth Heather Kelly Residence Date: July 30, 20212021-3015 Better Earth Sally West Residence Date: December 13, 20212021-5468 Better Earth Kimberly Adams Residence2022-044 Divine Power Michael Teal Residence Date: January 6, 2022 Date: February 1, 20222022-367 Connect Solar Joshua Georgopoulos Residence Date: May 09, 20222022-2018 New Gen Solar Benjamin Ferenc Residence
2634 N Oakmont
Ave05/24/22
Check Seismic load due to added dead load of photovoltaic system.
Determine Seismic Weight of Existing Building:
Effective Existing Seismic Weight
Area of (E) Building = Approximately 2,200 sq. ft.
Approximate
Effective
Seismic Weight
= 2,200 sq. ft. x 30 psf ave. = 66,000 LBS
DETERMINE BASE SHEAR
V = Cs W EQ'N 12.8-1 ASCE 7-16
Cs =
SDS
R
l e
EQ'N 12.8-2 ASCE 7-16
R = THE RESPONSE MODIFICATION FACTOR IN TABLE 12.2-1
R = 6.5 WOOD SHEAR WALL
e l = 1.0 IMPORTANCE FACTOR
SDS = 2/3 x S MS EQ'N 11.4-3 ASCE 7-16
SMS = FA x SS EQ'N 11.4-1 ASCE 7-16
SMS = 1.2 x 1.5 = 1.8
SDS = 2/3 x 1.8 = 1.2
Cs =
1.2
6.5
1
= 0.185 EQ'N 12.8-2 ASCE 7-16
Loyd W. Martin Professional Engineer, Inc.
9924 Universal Boulevard #224- 406 Orlando, FL 32819 Tel:1.310.464.1804
Email: loydwmartin@gmail.com www.loydwmartin.com
Sht # 6 of 7
2021-417 Solar Deployed Francisco Pelayo Residence Date: February 05, 20212021-417 Solar Deployed Fransisco Pelayo Residence2021-419 Better Earth Erlinda San Jose Residence Date: February 05, 2021
Exp. 3-31-19
No. C58724
NITRAMW.DYO
REGISTEREDPROFESSIONALENGINEER
C
V
L
FOETATS
ALIFORNIAICIL
-23
Date: June 04, 20212021-2029 Better Earth Emily Golding Residence Date: July 26, 20212021-2938 Better Earth Gary Richardson Residence Date: July 26, 20212021-2941 Better Earth Heather Kelly Residence Date: July 30, 20212021-3015 Better Earth Sally West Residence Date: December 13, 20212021-5468 Better Earth Kimberly Adams Residence2022-044 Divine Power Michael Teal Residence Date: January 6, 2022 Date: February 1, 20222022-367 Connect Solar Joshua Georgopoulos Residence Date: May 09, 20222022-2018 New Gen Solar Benjamin Ferenc Residence
2634 N Oakmont
Ave05/24/22
V = 0.185 x 66,000 LBS = 12,210 LBS EQ'N 12.8-1 ASCE 7-16
DETERMINE NEW BASE SHEAR
Determine Seismic Weight of Building with Solar Array:
EXISTING
SEISMIC
WEIGHT
= 66,000 LBS
NEW SOLAR
ARRAY 3 PSF x 22 PANELS x 3.3' x 5.5' = 1,198 LBS=
NEW
SEISMIC
WEIGHT
= 66,000 LBS + 1,198 LBS = 67,198 LBS
THEREFORE NEW BASE SHEAR:
V = 0.185 x 67,198 = 12,432 LBS EQ'N 12.8-1 ASCE 7-16
% CHANGE = 12,432 LBS - 12,210 LBS
12,210 LBS x 100 = 1.8 % < 10% OK
OK. PER ASCE 7-16 SECTION 11.B.3 ALTERATIONS
EXISTING LATERAL FORCE RESISTING SYSTEM IS EXEMPT
FROM ANALYSIS SINCE NEW SEISMIC FORCE IS
LESS THAN 10% GREATER THAN EXISTING SEISMIC FORCE.
"Alterations are permitted to be made to any structure without requiring the
existing structure to comply with this standard provided the alterations comply
with the requirements for a new structure. Alterations that increase the
seismic force in any existing structural element by more than 10 percent or
decrease the design strength of any existing structural element to resist
seismic forces by more than 10 percent shall not be permitted unless the
entire seismic force-resisting system is determined to comply with this
standard for a new structure."
End of Calculations
EXISTING BASE SHEAR
Loyd W. Martin Professional Engineer, Inc.
9924 Universal Boulevard #224- 406 Orlando, FL 32819 Tel:1.310.464.1804
Email: loydwmartin@gmail.com www.loydwmartin.com
Sht # 7 of 7
2021-417 Solar Deployed Francisco Pelayo Residence Date: February 05, 20212021-417 Solar Deployed Fransisco Pelayo Residence2021-419 Better Earth Erlinda San Jose Residence Date: February 05, 2021
Exp. 3-31-19
No. C58724
NITRAMW.DYO
REGISTEREDPROFESSIONALENGINEER
C
V
L
FOETATS
ALIFORNIAICIL
-23
Date: June 04, 20212021-2029 Better Earth Emily Golding Residence Date: July 26, 20212021-2938 Better Earth Gary Richardson Residence Date: July 26, 20212021-2941 Better Earth Heather Kelly Residence Date: July 30, 20212021-3015 Better Earth Sally West Residence Date: December 13, 20212021-5468 Better Earth Kimberly Adams Residence2022-044 Divine Power Michael Teal Residence Date: January 6, 2022 Date: February 1, 20222022-367 Connect Solar Joshua Georgopoulos Residence Date: May 09, 20222022-2018 New Gen Solar Benjamin Ferenc Residence