HomeMy WebLinkAbout4410 W Celeste St - Plan0
PV SYSTEM
AS INDICATED
SEPTEMBER 30, 2021
NAM NGUYEN
4410 CELESTE ST,
SANTA ANA, CA 92703
CONTRACTOR
True Power Solar
Address:
201 Clark Ave
Pomona, CA 91767
Phone Number:
(714)676-8888
Lic type: C-46
Lic# 970591
Drawn By : Narek A.
COVER PAGE
1. ALL ELECTRICAL MATERIALS SHALL BE NEW AND LISTED BY RECOGNIZED ELECTRICAL TESTING LABORATORY CUSTOM MADE EQUIPMENT SHALL HAVE
COMPLETE TEST DATA SUBMITTED BY THE MANUFACTURER ATTESTING TO ITS SAFETY
2. OUTDOOR EQUIPMENT SHALL BE AT LEAST NEMA 3R RATED
3. ALL METALLIC EQUIPMENT SHALL BE GROUNDED
4. ALL SPECIFIC WIRING IS BASED ON THE USE OF COPPER.
5.CONTRACTOR SHALL OBTAIN ELECTRICAL PERMITS PRIOR TO INSTALLATION AND SHALL COORDINATE ALL INSPECTIONS, TESTING
COMMISSIONING AND ACCEPTANCE WITH THE CLIENT, UTILITY CO. AND CITY INSPECTORS AS NEEDED.
6.THE ELECTRICAL CONTRACTOR SHALL VERIFY THE EXACT LOCATIONS OF SERVICE POINTS AND SERVICE SIZES WITH THE SERVING UTILITY COMPANY
AND COMPLY WITH ALL UTILITY COMPANIES REQUIREMENTS. IF THE SOLAR BACK FED BREAKER IS OVER THE BUSS SIZE 20% LIMIT, CONTRACTOR SHALL
INCLUDE THE COST TO REPLACE MAIN BREAKER OR ENLARGE MAIN CAPACITY.
7. DRAWINGS ARE DIAGRAMMATIC ONLY, ROUTING OF RACEWAYS SHALL BE OPTION OF THE CONTRACTOR UNLESS OTHERWISE NOTED AND SHALL BE
COORDINATED WITH OTHER TRADES.
8. IF THE ROOF MATERIAL OR ROOF STRUCTURE NOT ADEQUATE FOR PV INSTALLATION, CALL ENGINEER PRIOR TO INSTALL. THE CONTRACTOR IS
RESPONSIBLE TO VERIFY THAT THE ROOF IS CAPABLE OF WITHSTANDING THE EXTRA WEIGHT.
9. IF THE DISTANCES FOR CABLE RUNS ARE DIFFERENT THAN SHOWN, THE CONTRACTOR SHALL NOTIFY THE ELECTRICAL ENGINEER TO VALIDATE THE
WIRE SIZE. FINAL DRAWINGS WILL BE RED-LINED AND UPDATED AS APPROPRIATE.
10. WHENEVER A DISCREPANCY IN QUALITY OF EQUIPMENT ARISES ON THE DRAWING OR SPECIFICATIONS, THE CONTRACTOR SHALL BE RESPONSIBLE FOR
PROVIDING AND INSTALLING ALL MATERIAL AND SERVICES REQUIRED BY THE STRICTEST CONDITIONS NOTED ON THE DRAWINGS OR IN THE
SPECIFICATIONS TO ENSURE COMPLETE COMPLIANCE AND LONGEVITY OF THE OPERABLE SYSTEM REQUIRED BY THE ARCHITECT/ENGINEERS.
11. ALL BROCHURES, OPERATION MANUALS, CATALOGS, SHOP DRAWINGS, ETC. SHALL BE HANDED OVER TO OWNER'S REPRESENTATIVE AT THE
COMPLETION OF WORK
OWNER
SCOPE
PROJECT
ADDRESS
PROJECT DATA GENERAL NOTES VICINITY MAP
SHEET INDEX
0 COVER PAGE
PHOTOVOLTAIC NOTES
SATELLITE VIEW
BUILDING
INFORMATION:
SINGLE LINE DIAGRAM
CODE REQUIRED SIGNAGE
3
4
ATTACHMENT LAYOUT5
6
7
INVERTER DATA SHEET
D1 MODULE DATA SHEET
RACKING DATA SHEET
RACKING CERTIFICATE
ATTACHMENT DATA SHEET
ELECTRICAL
INFORMATION
MAIN SERVICE PANEL
BUSBAR RATING
MAIN SERVICE
BREAKER RATING
ROOF PLAN
MODULE MAP
RACKING
INFORMATION
Main Service Panel
Solar Module
Micro Inverter /
Optimizer
EMT / FMT / PVC
/ RMC type conduit/
Romex NM Cable/
FNMT (Fluid non-metalic tube)
36'' SetbackInverter
Utility Meter
Production Meter
PV Load Center
IQ Combiner Box
Junction Box
Sunpower PV Supervisor
18'' Setback
EV Outlet
CONSTRUCTION TYPE: V-B
ROOF
TYPE
AHJ
APN
LOT AREA
LIVING AREA
MSP
UM
PM
INV
PV
PVS6
IQ
J/B
EV
NAM NGUYEN
46 HANWHA 430W
Q.PEAK DUO L-G8 430
46 ENPHASE
IQ7PLUS-72-2-US
4410 CELESTE ST,
SANTA ANA, CA 92703
AC DisconnectACD
SSP Service Sub Panel
COMPOSITION SHINGLE
4,044 SQFT
19832426
CITY OF SANTA ANA
WIRE SIZE CALCULATIONS
INVERTER MAP
D2
D3
D4
D5
D6
ROOF MOUNT INSTALLATION OF
DC PHOTOVOLTAIC SYSTEM
19.78 KW DC
19.78 KW
18.02 KW AC
EXISTING
1. ROOFTOP MOUNTED PHOTOVOLTAIC PANELS AND MODULES SHALL BE TESTED, LISTED AND IDENTIFIED UL 1703.
2. SOLAR SYSTEM SHALL NOT COVER ANY PLUMBING OR MECHANICAL VENTS
3. MODULES AND SUPPORT STRUCTURES SHALL BE GROUNDED.
4. SOLAR INVERTER MUST HAVE A MANUFACTURE INSTALLED DISCONNECTING MEANS THAT PREVENTS PARALLEL FEEDING UTILITY LINES DURING POWER
OUTAGE.
5. REMOVAL OF AN INTERACTIVE INVERTER OR OTHER EQUIPMENT SHALL NOT DISCONNECT THE BONDING CONNECTION BETWEEN THE GROUNDING
ELECTRODE CONDUCTOR AND THE PHOTOVOLTAIC SOURCE AND/OR OUTPUT CIRCUIT GROUNDED CONDUCTORS.
6. ALL PV MODULES AND ASSOCIATED EQUIPMENT AND WIRING SHALL BE PROTECTED FROM ANY PHYSICAL DAMAGE.
7. LIVE PARTS OF PV SOURCE CIRCUITS AND PV OUTPUT CIRCUITS OVER 150V TO GROUND SHALL NOT BE
ACCESSIBLE TO OTHER THAN QUALIFIED PERSONS WHILE ENERGIZED.
8 .INVERTER IS EQUIPPED W/ INTEGRATED GFDI, THUS PROVIDING GROUND FAULT PROTECTION
9. ALL CONDUCTORS SHALL BE COPPER AND 90 DEG RATED
10. ALL ELECTRICAL EQUIPMENT SHALL BE LISTED BY A RECOGNIZED ELECTRICAL TESTING LABORATORY OR APPROVED BY THE DEPARTMENT.
11. CONDUITS SHOULD BE PAINTED TO MATCH EXISTING ROOF AND WALL COLORS
12. THE OUTPUT OF A UTILITY INTERACTIVE-INVERTER SHALL BE PERMITTED TO BE CONNECTED TO THE SUPPLY SIDE OF THE SERVICE DISCONNECTING
MEANS AS PER 230.82(6)
13. A SINGLE CONDUCTOR SHALL BE PERMITTED TO BE USED TO PERFORM THE MULTIPLE FUNCTIONS OF DC GROUNDING, AC GROUNDING
AND BONDING BETWEEN AC AND DC SYSTEMS SIZED AS PER SEC 250.122
14. EQUIPMENT GROUND CONDUCTOR REQUIRED IN RACEWAYS SIZED PER CEC 250-122.
15. PER ART 250.92. NON-CURRENT CARRYING METAL PARTS OF EQUIPMENT SHALL BE EFFECTIVELY BONDED TOGETHER. BOND BOTH ENDS OF RACEWAYS
ALL OTHER ORDINANCE ADOPTED BY THE
LOCAL GOVERNING AGENCIES
THE INSTALLATION OF SOLAR ARRAYS AND
PHOTOVOLTAIC POWER SYSTEMS SHALL COMPLY
WITH THE FOLLOWING CODES:
2019 CALIFORNIA ELECTRICAL CODE
2019 CALIFORNIA BUILDING CODE
2019 CALIFORNIA GREEN BUILDING STANDARDS
CODE
2019 CALIFORNIA ENERGY CODE
2019 CALIFORNIA MECHANICAL CODE
2019 CALIFORNIA PLUMBING CODE
2019 INTERNATIONAL RESIDENTIAL CODE
2019 INTERNATIONAL FIRE CODE
1
2 0.64 ACRES
LG Chem Battery BackupLGB
Solar Edge Auto TransformerAT
Solar Edge Meter EnclosureSEM
Distribution PanelDP
Rapid Shutdown Controller RSC
Rapid Shutdown Box RSB
Itron MeterIM
UNIT INDEX
CODE REFERENCES
SOLAR WAREHOUSE RACKING
RAFTERS 2"X6" @ 16" O.C
OCCUPANCY: R
ONE STORY BUILDING
200A
225A
Coordinates: 33.752833, -117.928242
IQ COMBINER BOX DATA SHEET
Bldg permit #101108385
Elect permit #20174618
Issued on 12/23/2021
4410 W Celeste St
12/23/21
4410 CELESTE ST.
SANTA ANA, CA 92703
NGUYEN, NAM
Prepared For:
TRUE POWER SOLAR
201 CLARK AVE.
POMONA, CA 91767
(714) 676-8888
Design Criteria
1- Code: CALIFORNIA BLDG CODE 2019 / ASCE 7-16
2 - Wind: 95 MPH, Exposure: C
3 - Wood Species: DF-L No. 2 (SG = 0.5 )
Notice: Use restrictions of these calculations.
The attached Calculations are valid only when bearing original signature hereon.
Contractor/Client to verify existing dimensions/conditions prior to construction
& solar racking is installed per manufacturer span requirements.
The use of these calculations is solely intended for the above mentioned project.
1-844-PV ELITE | info@yoursolarplans.com
3000 E. Birch Street Suite 201 | Brea CA 92821
10/4/2021
Structural Calculations for
SOLAR POWER SYSTEM CONNECTION CHECK AT:
Job:
4410 W Celeste St
12/23/21
0123240537089
722 !"2#2$%!&''()4(()0 *******+!"&,00 (*48408'+-&3301-!--./4./4*4(1'/40. 024
123456789:4;3<=:8
>??42@@A 3301-!--.5.5*4(1'50.
B::4?=83<2@A ''()4(()0 *******5,00 (*48408'
CD2E3<=:8A (3F
G=;2@<3;HA 4140 ,01,13
4'70870 '3I8J
K3L34?GMH2A N
>1BCOPQ R
ST01,U-II V
ST4),U-(0 V
ST)1,U-(I V
ST011,U-80 V
SW-"T 8*V
SW-"TT *)V
SW-"TTT 014 V
SW-"TX 01I V
>1BCOPQ Y
ST01,U-(4 V
ST4),U-(*V
ST)1,U-8)V
ST011,U-*0 V
SW-"T 011V
SW-"TT 001V
SW-"TTT,TX 00 )V
>1BCOPYZ
.[(,1)N.--8)V
\]^_^`abc`defdghc^f]^_^ijkj\_^lb^gchem`chc^n_bnghbho^efo^ec`cnc]^phba^`n_hemf^bde^hcdnebde^`ohf^fa_deqc]^radbfdeq
gnf^hfnscdnes_ng^``tu`^_``]nabfgneld_ohemnacsacnrchde^fl_noc]d`cnnbvdc]c]^bnghbwac]n_dcmxhpdeqya_d`fdgcdner^ln_^
s_ng^^fdeqvdc]f^`dqet
z=@5D3=;24
!--!-FV{-.[( - ---$!--"-9-.[(5!!
- --! ! --!$-- F-!-|V--5$--$!!-}!-
-!$-- --F-5{-$--!"!"-~
[7 ---$,---"
-5-- !"--V-{- "$VFF-$-----$$,-
--"
-5""-5-V-5-!$-"!!--}V-F !$
N!--FV---$---!-{---5
V--!
!!F
-V-!----- !- --!- F-F!$
V---}V{-FF 5 !!!-"---!--F-!
-
-- -FFV-!-- "V-F V--F-!5{"-}---W$!-"-
-F-!F-5 -F-F-- -F F-!--"!"-- !F-
-{-$--0-F-FVFV$-- V-!!!!"FV -0-F- F
$---V!{!-"{-" !"---!-F !"-{!--F-
4410 W Celeste St
12/23/21
ASCE 29.4.4 Rooftop Solar Panels Parallel to the Roof Surface on Buildings of All Heights and Roof Slopes.
Roof Slope = 21 °
Roof Shape Hip
Tributary Width s = 4.00 ft
Tributary Length l = 3.41 ft
Effective Area A e = 6.77 ft2
Height of Structure h = 15 ft
Wind Speed V = 95 mph
Exposure Category C
Building Width B = 40 ft
Building Length L = 55 ft
Zone Width a = 4 ft
Elevation Height zg = 74 ft
Wind Directionality Kd = 0.85
Topography Factor Kt = 1.00
Ground Elevation Factor Ke = 1.00
Velocity Pressure Exposure Coefficient Kz = 0.85
Velocity Pressure q z = 0.00256KzKztKdKeV 2 = 16.63 psf
Solar Array Pressure Equalization a = 0.80
Array Edge Factor E = 1.50
Zone GCp p = qz(GCp)(E)(a)
3 2.00 -39.90
3r - -
3e - -
2 - -
2r 2.00 -39.90
2e 2.00 -39.90
2n - -
1 1.40 -27.93
1'- -
4410 W Celeste St
12/23/21
LAG SCREW ANALYSIS
Loads
Wind Pressures qz = -39.90 psf
Solar Panel Load QD = 3 psf
Panel Length l = 6.825 ft
Panel Width b 3.3833 ft
Attachment Spacing s = 4 ft
Portrait
Tributary Area At = 13.65 ft2
Wind Load P W = qz * At = -545 lbs
Dead Load P D = Q D * At = 40.95 lbs
Uplift Pa = 0.6 P D + 0.6 Pw = -302 lbs
Landscape
Tributary Area At = b * s = 6.7667 ft2
Wind Load P W = qz * At = -270 lbs
Dead Load P D = Q D * At = 20.3 lbs
Uplift Pa = 0.6 P D + 0.6 Pw = -150 lbs
Lag Screw 5/16" x 5"
Specific Gravity of Lumber SG = 0.50 (Douglas Fir-Larch)
Diameter of Lag Screw D = 5/16 in
Withdraw Design /in 1800*SG 3/2 *D 3/4 = 266 lbs/in
Depth of Embedment lp = 2.50 in
Total Nominal Withdrawal Value W = W * l p = 665 lbs
Load Duration Factor CD = 1.6
Withdrawal Design Value W' = W * C D = 1064 lbs
Demand Capacity Ratio DCR = Pa / W' = 0.28 < 1 OK
4410 W Celeste St
12/23/21
ASCE 30.3.2 Design Wind Pressure Beam/ Top Chord Check
Roof Slope = 21 °
Roof Shape Hip
Tributary Width s = 1.33 ft
Tributary Length L = 14.65 ft
Effective Area A = L ( MAX [ s , L/3] ) = 72 ft2
Height of Structure h = 15 ft
Wind Speed V = 95 mph
Exposure Category C
Building Width B = 40 ft
Building Length L = 55 ft
Zone Width a = 4 ft
Elevation Height zg = 74 ft
Wind Directionality Kd = 0.85
Topography Factor Kt = 1.00
Ground Elevation Factor Ke = 1.00
Velocity Pressure Exposure Coefficient Kz = 0.85
Velocity Pressure q z = 0.00256KzKztKdKeV 2 = 16.63 psf
Internal Pressure Coefficient (GCpi) = -0.18
Zone GCp p = q z [(GCp) - (Gcpi)]
3 1.68 -30.86
3r - -
3e - -
2 - -
2r 1.68 -30.86
2e 1.68 -30.86
2n - -
1 0.99 -19.45
1' - -
4410 W Celeste St
12/23/21
Beam/ Top Chord Check Lumber:
Moment Demand
# of Attachment per Rafter N A = Span : Orientation
Lenght (ft) :
Dead Load Roof Material: Q D = psf
Live Load QLr = psf
Wind Load p = psf
Snow Load QS = psf
Rafter Spacing s = in
Wind Load, Portrait Portrait UL =
Wind Load, Landscape Landscape U W =
Linear Dead Load wd = plf
Live Load wLr = plf Start ft Start ft
End ft End ft
Snow Load ws = plf Start ft Start ft
End ft End ft
Ma, Moment
D lb-ft
D+Lr lb-ft
D+S lb-ft
0.6D+0.6W lb-ft
D+0.45W+0.75Lr lb-ft
D+0.45W+0.75S lb-ft
Moment Capacity Framing Member Size Lumber Grade : DF-L No. 2
C M = 1 Ct = 1 Cr= CF = fb = psi Cfu =C i =
Breadth b = in
Depth d = in
Section Modulus Sx = bd 2 / 6 = in3
Bending Stress Capacity Fb = CM * C t * Cr * C F * fb = psi Table 4.3.1 NDS 2015
Deflection Limit E = ksi I = in4
Transient Deflection in
Transient Deflection Allowed > [OKAY]
Total Deflection in
Total Deflection Allowed > [OKAY]
-30.86
DF-L No. 2
6 j lj (ft) pd,j (lbs) pw,j (lbs) ps,j (lbs)
Landscape
1 3.6 20.3 -209 0.0
5.7 20.3 -209
-209 0.0
4 9.1 20.3 -209 0.0
0.0
12.65 0.00 0.00 0.00 2.00
Landscape
3 7.0 20.3
10.00
1 2 3 4 Eave
2
0.0
0.0 0.0 0.0
0.0
0 0.0 0.0 0.0 0.0
0 0.0 0.0 0.0
0.0
6 12.5 20.3 -209 0.0
Landscape
5 10.4 20.3 -209
0.0
13.3
26.7
0.0 0.0 0.0 0.0
0 0.0
Portrait
0
0.0 20.3 -209 0
0
0.0
0
3
0
0
0.0
Portrait
3
0.0
Portrait
0 0.0 0.0
AT (ft 2)
13.65
6.7667
pd (lbs)
40.95 -421
p w (lbs) ps (lbs)
0
13.15
2x6
1.15 1.3
14.65
13.15
14.65
900
1.50
5.50
466
495
466
1047
530
530
DCR
0.9 1211 psi D 739 psi 0.61
7.56
1346
CD Fb' = C D * F b ASD Load Ma * S x
1.15 1547 psi D+S 739 psi 0.48 OKAY
OKAY
1.25 1682 psi D+Lr 785 psi 0.47 OKAY
1.6 2153 psi
0.869
175 120
1600 20.80
0.6D+0.6W 1661 psi 0.77 OKAY
1.0 1
20
0.00
16
Comp.
0.775
196 180
1.6 2153 psi D+0.45W+0.75S 841 psi 0.39 OKAY
1.6 2153 psi D+0.45W+0.75Lr 841 psi 0.39 OKAY
ൌ ሺ െ ሻ െ െ െ
‐200.0
0.0
200.0
400.0
600.0
800.0
1000.0
1200.0
0.000 2.000 4.000 6.000 8.000 10.000 12.000 14.000 16.000
4410 W Celeste St
12/23/21
EISMIC WEIGHT COMPARISON / ANALYSIS - (PER CEBC 2019 Part 10 Chapter 5 Section 502.5)
PV System Weight
Module Model Hanwha
Panel Weight Wpanel = 54 lbs
Number of Panels NPV = 46
Total PV System Weight W PV = Wpanel * NPV = 2484 lbs
Existing Roof Weight
Roof Weight QD =10.0 psf
Building Length Lbuild =55 ft
Building Width W build =40 ft
Roof Area Abuild =2200 ft2
Building Perimeter Pbuild = 190 ft
Wall Height ht = 8 ft
Wall weight Qwall = 15 psf
Interior wall weight Qint = 10 psf
Roof Load Wfloor = Abuild * QD = 22000 lbs
Wall LoadWwall = ht /2 * Qwall * Pbuild + Abuild * Qint /2 = 22400 lbs
Total Story Weight Wbuild = Wfloor + Wwall = 44400 lbs
Percentage Weight Increase WPV / Wbuild = 5.59%< 10% OKAY
4410 W Celeste St
12/23/21
1
ROOF PLAN
PV SYSTEM
AS INDICATED
SEPTEMBER 30, 2021
NAM NGUYEN
4410 CELESTE ST,
SANTA ANA, CA 92703
CONTRACTOR
True Power Solar
Address:
201 Clark Ave
Pomona, CA 91767
Phone Number:
(714)676-8888
Lic type: C-46
Lic# 970591
Drawn By : Narek A.
N
0
S
180
E
90
W
270
SCALE
0 5 10
PHOTOVOLTAIC SYSTEM
46 Hanwha 430W Modules (Q.PEAK DUO L-G8 430)
46 Enphase Energy Microinverters
(IQ7PLUS-72-2-US)
FROM JUNCTION BOX TO ROOF EAVE EMT TYPE CONDUIT WILL RUN OVER
THE ROOF AT 3 1/2" HEIGHT, THEN UNDER THE EAVE TO PV EQUIPMENT19.78 KW DC
MSP
ACD
IQ
Solar Array 3
5 Hanwha Q.Cell 430W
5 IQ7+ Microinverters
Pitch: 21 Deg
Orientation: 135 Deg
J/B
Solar Array 5
10 Hanwha Q.Cell 430W
10 IQ7+ Microinverters
Pitch: 21 Deg
Orientation: 135 Deg
Solar Array 2
13 Hanwha Q.Cell 430W
13 IQ7+ Microinverters
Pitch: 21 Deg
Orientation: 180 Deg
Celeste St
Gate
Solar Array 6
4 Hanwha Q.Cell 430W
4 IQ7+ Microinverters
Pitch: 21 Deg
Orientation: 315 Deg
Solar Array 4
3 Hanwha Q.Cell 430W
3 IQ7+ Microinverters
Pitch: 21 Deg
Orientation: 315 Deg
Solar Array 1
11 Hanwha Q.Cell 430W
11 IQ7+ Microinverters
Pitch: 21 Deg
Orientation: 0 Deg
15ft
b
aa
aa a a a a a a a
bb b b b
bb
b b
b
c c c
c
c
c
c
c
c
c
c
c
d
d
d
d
d
d
d
d
d
d
d
d
E
V
No. C70784
Exp. 06/30/2023
4410 W Celeste St
12/23/21
2
SINGLE LINE
DIAGRAM
PV SYSTEM
AS INDICATED
SEPTEMBER 30, 2021
NAM NGUYEN
4410 CELESTE ST,
SANTA ANA, CA 92703
CONTRACTOR
True Power Solar
Address:
201 Clark Ave
Pomona, CA 91767
Phone Number:
(714)676-8888
Lic type: C-46
Lic# 970591
Drawn By : Narek A.
ITEM DESCRIPTION QTY#
PV MODULE
MAIN SERVICE PANEL
MAIN SERVICE PANEL
& UTILITY METER
BUSBAR RATING
BREAKER RATING
1
ITEM DESCRIPTION QTY#
PVC JUNCTION BOX 4"x4"x2" UL LISTED WATER TIGHT NEMA TYPE 3
1
1
1
4
3
1
8
10A 6
M
MAIN
SERVICE
PANEL
120/240V
1P,3W
2
EXISTING
GROUNDING SYSTEM
UTILITY
46
HANWHA 430W
Q.PEAK DUO L-G8 430
Voc = 49.33V
Vmp = 41.70V
Isc = 10.83A
Imp = 10.31A
2
3
INVERTER
PEAK PWR TRACKING VOLTAGE
CEC EFFICIENCY
PROTECTION RATING:
MAXIMUM INPUT CURRENT
MAXIMUM OUTPUT CURRENT
MAXIMUM INPUT POWER
PEAK OUTPUT POWER
4 46
Enphase Energy Microinverters (IQ7PLUS-72-2-US)
27-45 V
97.0 %
NEMA 6
15.0 A
1.21 A
235-440 W
295 W
IQ COMBINER
ENPHASE IQ COMBINER BOX WITH ENPHASE ENVOY IQ
120/240V, NEMA 3R MODEL# X-IQ-AM1-240-3
INSTALL 15A PV 2-POLE C/B
INSTALL 20A PV 2-POLE C/B
0
4
8 1
10A PV 2-POLE C/B
(2)#14 AWG THWN-2 (L1+L2)
(1)#14 AWG-NEUTRAL
ENVOY
INFORMATION
100A AC DISCONNECT NON FUSED AC DISCONNECT LOCKABLE,
BLADE TYPE, NEMA 3R, 120/240V 16
EXISTING
2
1
3
200A
3
200A
225A
225A
FOR WIRE SIZE CALCULATIONS PLEASE SEE PAGE #3
INSTALL 2P
70A CB(PV) AT
OPPOSITE END
OF BUS FROM
MAIN FEEDER CB
Branches a,b: (11) Modules, (11) Microinverters
Branches c,d: (12) Modules, (12) Microinverters
20A
20A
20A
20A
4410 W Celeste St
12/23/21
46
46
430W
*430
403.9W
*403.9 *
Q.PEAK DUO L-G8 430
IQ7PLUS-72-2-US (CEC)97%
0.97
1.21
1.21
46
FROM JBOX TO IQ COMBINER BOX
FROM IQ COMBINER BOX TO MAIN SERVICE PANEL
3 1/2''
0.71 TEMP. DERATE FACTOR (TEMP - 39 + 17 = 56C)
RACEWAY HEIGHT FROM ROOF
PV SYSTEM
AS INDICATED
SEPTEMBER 30, 2021
NAM NGUYEN
4410 CELESTE ST,
SANTA ANA, CA 92703
CONTRACTOR
True Power Solar
Address:
201 Clark Ave
Pomona, CA 91767
Phone Number:
(714)676-8888
Lic type: C-46
Lic# 970591
Drawn By : Narek A.
3
WIRE SIZE
CALCULATIONSFROM PV MODULES TO JBOX
#12 AWG ENPHASE TRUNK CABLE, PV WIRE(8) 1
(1) #6 AWG BARE CU EGC
2
#8 AWG CU EGC,
(3)
3
(1) #8 AWG CU EGC,
MAXIMUM INVERTER OUTPUT CURRENT
WALL TEMPERATURE FACTOR
OUTPUT CALCULATIONS
PV SYSTEM MAX DC OUTPUT
PV SYSTEM MAX AC OUTPUT
1.25
0.91
(8)
(1)
46
Pmax (PTC Rating)
3/4'' EMT TYPE CONDUIT
1'' EMT TYPE CONDUIT
#10 AWG THWN-2
WIRE CHART WIRE CHART
a b c d
4 BRANCH CIRCUITS
INVERTER OUTPUT MAX CURRENT
COEFFICIENT 1.25
11
BRANCH CIRCUIT CURRENT a,b:11 BREAKER SIZE PER BRANCH CRCT
20A
ADJST. FACTOR (7 thru 9 WIRES)0.7
**1.25111.21 16.6A
ADJUSTED CONDUCTOR AMPACITY
/ / 18.2 0.71 0.7 36.6A
NUMBER OF MICROINVERTERS
19.78KW
18.02KW
MAIN SERVICE PANEL RATING
BUSBAR RATING
MAIN BREAKER
PV BACKFEED BREAKER SIZE
120% RULE:
MAX ALLOWED FEED
70A
200A
225A
270A
200A''MB'' + 70A "SOLAR" = 270A 270A MAX
WIRE CHART
QTY
CONSIDER CONTINUOUS COEFFICIENT
CONSIDER CONTINUOUS (A)1.25**46 1.21 69.6
*1.25 / 0.91*46 1.21 76.5
#4 AWG THWN-2
TEMPERATURE ADJUSTMENT (A)
46
Attention!!!!!!!
Need Calculation
(don't delete this note)
11 12 12
BRANCH CIRCUIT CURRENT c,d:12 BREAKER SIZE PER BRANCH CRCT
20A**1.25121.21 18.2A
4410 W Celeste St
12/23/21
CODE REQUIRED
SIGNAGE
4
PV SYSTEM
AS INDICATED
SEPTEMBER 30, 2021
NAM NGUYEN
4410 CELESTE ST,
SANTA ANA, CA 92703
CONTRACTOR
True Power Solar
Address:
201 Clark Ave
Pomona, CA 91767
Phone Number:
(714)676-8888
Lic type: C-46
Lic# 970591
Drawn By : Narek A.
WARNING
ELECTRICAL SHOCK HAZARD
TERMINALS ON THE LINE AND
LOAD SIDES MAY BE ENERGIZED
IN THE OPEN POSITION
NEC 690.13(B)
TURN OFF PHOTOVOLTAIC
AC DISCONNECT PRIOR TO
WORKING INSIDE PANEL
NEC 110.27(C) & OSHA 1910.145(f)(7)
ELECTRICAL SHOCK HAZARD
TERMINALS ON THE LINE AND
LOAD SIDES MAY BE ENERGIZED
IN THE OPEN POSITION
NEC 690.13(B)
DC VOLTAGE IS ALWAYS PRESENT
WHEN SOLAR MODULES
ARE EXPOSED TO SUNLIGHT NEC 690.53 FOR MARKING DC BACKUP SYSTEMS
NEC 690.13(B)
WARNING
THE DISCONNECTION OF THE
GROUNDING CONDUCTOR(S)
MAY RESULT IN OVERVOLTAGE
ON THE EQUIPMENT
NEC 690.31(I)
NEC 690.54
NEC 690.54
NEC 690.52
WARNING
ELECTRICAL SHOCK HAZARD
TERMINALS ON THE LINE AND
LOAD SIDES MAY BE ENERGIZED
IN THE OPEN POSITION
NEC 690.13(B)
NEC 705.12(D)(3) & NEC 690.59
NEC 690.54
NEC 690.13 (F), NEC 705.12(B)(3-4) & NEC 690.59
NEC 705.12(D)(3) & NEC 690.59
NEC 690.15 (C) & NEC 690.33(E)(2)
NEC 690.13(B)
SINGLE 120-VOLT SUPPLY
DO NOT CONNECT
MULTIWIRE BRANCH CIRCUIT
NEC 710.15(C) & 692.9 (C)
TURN OFF PHOTOVOLTAIC
AC DISCONNECT PRIOR TO
WORKING INSIDE PANEL
NEC 110.27(C) & OSHA 1910.145(f)(7)
WARNING
ELECTRICAL SHOCK HAZARD
TERMINALS ON THE LINE AND
LOAD SIDES MAY BE ENERGIZED
IN THE OPEN POSITION
NEC 690.13(B)
NEC 705.12 (B)(2)(c)
CAUTION
POWER TO THIS BUILDING IS ALSO SUPPLIED
FROM THE FOLLOWING SOURCES WITH
DISCONNECTS LOCATED AS SHOWN:
NEC 705.10(B) & NEC 690.56(B)
LABELING REQUIREMENTS FOR ARTICLE 690
NEC 690.13(B) Each PV system disconnecting means shall plainly indicate whether
the specific system configuration. For PV system disconnecting means where the
line and load terminals may be energized in the open position, the device shall be
marked with the following words or equivalent.
NEC 690.13(F) Type of Disconnect. A dc PV system disconnecting means shall be
marked for use in PV systems or be suitable for backfeed operation.
NEC 690.15(C) An isolating device shall be rated to open the maximum circuit
NEC 690.31(B)(1) PV system circuit conductors shall be identified at all accessible
points of termination, connection and splices. The means of identification shall be
permitted by separate color coding, marking tape, tagging or other approved means.
NEC 690.31(G)(1) Where circuits are embedded in build up, laminate or membrane
roofing materials not covered by PV modules and associated equipment, the location
of the circuits shall be clearly marked.
NEC 690.31(G)(4) PV dc system circuit labels shall appear on every section of the wiring
system that is separated by enclosures, walls, partitions, ceilings, or floors. Spacing between
labels or markings, or between a label and a marking, shall not be more than 3 m (10 ft).
Labels required in this section shall be suitable for the environment where they are installed.
NEC 690.31(I) Solidly-grounded bipolar PV systems shall be clearly marked with a permanent,
legible warning notice indicating that the disconnection of the grounded conductor(s) may
result in overvoltage on the equipment.
NEC 690.33(E)(2) Interruption of Circuit. Connectors shall be a type that requires the use of a
NEC 690.52 Alternating-current modules shall be marked with identification of terminals or
leads and with identification of the following ratings.
NEC 690.53A permanent label for the dc PV power source indicating items (1) through (3)
shall be provided by the installer at dc PV system disconnecting means and at each dc
equipment disconnecting means required by 690.15. Where a disconnecting means has more
than one dc PV power source, the values in 690.53 (1) through (3) shall be specified for each
source.
NEC 690.54 All interactive system(s) points of interconnection with other
sources shall be marked as an accessible location at the disconnecting
means as a power source and with the rated ac output current and the
nominal operating ac voltage.
NEC 690.55 The PV system output circuit conductors shall be marked to
indicate polarity where connected to energy storage systems.
NEC 690.56(B)Plaques or directories shall be installed in accordance with
705.10.
NEC 690.56(C)(3) A rapid shutdown switch shall have a label located on
or no more than 1 meter (3 ft) from the switch that includes the following
wording.
NEC 690.56(C)(1)(a-b) The type of PV system shall be labeled as described
in a) or b):
NEC 690.59 PV systems connected to other sources shall be installed in
accordance with Parts I and II of Article 705.
Permanent directory or plaque providing location of service disconnecting means and
photovoltaic system disconnecting means, if not located at the same location. (Plaques
shall be metal or plastic, with engraved or machine printed letters, or electro-photo plating, in a
contrasting color to the plaque. Plaques shall be permanently attached to the equipmenq or in
the required location using an approved method that is suitable to withstand the environment to
which it is exposed. Plaques and signage shall meet legibility, defacemet, exposure and
adhesion requirements of Underwriters Laboratories marking and labeling system 969(UL969).
Plaques will have red background & white lettering.
Only present if required by either the AHJ and/or utility company
SOLAR ELECTRIC
PV PANELS
SOLAR PV SYSTEM EQUIPPED
WITH RAPID SHUTDOWN
TURN RAPID SHUTDOWN
SWITCH ON THE
"OFF" POSITION TO
SHUTDOWN PV SYSTEM
AND REDUCE
SHOCK HAZARD
IN ARRAY
IFC 605.11.3.1(1) & 690.56(C)(1)(a)
NEC 690.56(C)(3)
NEC 690.31(G)(3)(4)
NEC 690.31(G)(1)
RATED AC OUTPUT CURRENT:
NOMINAL OPERATING AC VOLTAGE:
PHOTOVOLTAIC AC DISCONNECT
MAXIMUM VOLTAGE
MAXIMUM CIRCUIT CURRENT
MAX RATED OUTPUT CURRENT OF
THE CHARGE CONTROLLER
OR DC-TO-DC CONVERTER
(IF INSTALLED)
RATED AC OPERATING CURRENT
MAX RATED AC OPERATING CURRENT
RATED AC OPERATING VOLTAGE
MAX RATED AC OPERATING VOLTAGE
RATED SHORT CIRCUIT CURRENT
MAXIMUM SYSTEM VOLTAGE
DC DISCONNECT
PHOTOVOLTAIC
WARNING WARNING DUAL POWER SOURCE
SECOND SOURCE IS PHOTOVOLTAIC SYSTEM
RATED AC OUTPUT CURRENT:
NOMINAL OPERATING AC VOLTAGE:
PHOTOVOLTAIC AC DISCONNECT NOMINAL OPERATING AC VOLTAGE
NOMINAL OPERATING AC FREQUENCY
MAXIMUM AC POWER
MAXIMUM AC CURRENT
MAX OVERCURRENT DEVICE RATING
FOR AC MODULE PROTECTION
RATED AC OUTPUT CURRENT:
NOMINAL OPERATING AC VOLTAGE:
PHOTOVOLTAIC AC DISCONNECT WARNING DUAL POWER SOURCE
SECOND SOURCE IS PHOTOVOLTAIC SYSTEM
MAIN PHOTOVOLTAIC
SYSTEM DISCONNECT WARNING
CAUTION
PHOTOVOLTAIC SYSTEM CIRCUIT IS BACKFED
WARNING
POWER SOURCE OUTPUT
CONNECTION. DO NOT
RELOCATE THIS
OVERCURRENT DEVICE.
WARNING
DO NOT DISCONNECT
UNDER LOAD
RAPID SHUT DOWN SWITCH
FOR SOLAR PV SYSTEM
WARNING: PHOTOVOLTAIC
POWER SOURCE
WARNING
PHOTOVOLTAIC POWER SOURCE
DO NOT REMOVE UNLESS REPLACED IN EXACT LOCATION - PV POWER CIRCUIT DIRECTLY BELOW
WARNING
FOR PV SYSTEMS THAT SHUT DOWN THE ARRAY
AND CONDUCTORS LEAVING THE ARRAY: SIGH TO
BE LOCATED ON OR NO MORE THAN 3 FT AWAY
FROM SERVICE DISCONNECTING MEANS TO WHICH
THE PV SYSTEMS ARE CONNECTED AND SHALL
INDICATE THE LOCATION OF ALL IDENTIFIED RAPID
SHUTDOWN SWITCHES IF NOT AT THE SAME
LOCATION. [CEC 690.56(C)(1)(A)]
N/A
240 Vac
N/A
240 Vac
N/A
N/A
240 Vac
N/A
N/A
N/A
NEC 690.13(B)
AC DISCONNECT
PHOTOVOLTAIC
70 A
10.83 A
55.2 V
N 4410 Celeste Street, Santa Ana, CA 92703
Celeste St
SOLAR ARRAY
ON THE ROOF
SOLAR ARRAY
ON THE ROOF
SOLAR ARRAY
ON THE ROOF
PV SYSTEM DISCONNECT
FOR UTILITY OPERATION
IQ COMBINER BOX
SERVICE POINT &
UTILITY METERING
55.66 A
55.66 A
55.66 A
55.66 A
295 W
60 Hz
240 Vac
4410 W Celeste St
12/23/21
ATTACHMENT
LAYOUT
5
PV SYSTEM
AS INDICATED
SEPTEMBER 30, 2021
NAM NGUYEN
4410 CELESTE ST,
SANTA ANA, CA 92703
CONTRACTOR
True Power Solar
Address:
201 Clark Ave
Pomona, CA 91767
Phone Number:
(714)676-8888
Lic type: C-46
Lic# 970591
Drawn By : Narek A.
STRUCTURAL STAMPROOF
PITCH
ROOFING
TYPE
ATTACHMENT
TYPE
FRAMING
TYPE
FRAMING
SIZE
PENETRATION
PATTERN
21
RACKING
TYPE
MAX
PENETRATION
SPACING
ROOFING
LAYERS
WIND SPEED MPH
SNOW LOAD 0 PSF
EXPOSURE C
LAG BOLTS MOUNTS AND MOUNTING HARDWARE WILL BE
SEALED WITH CHEM LINK SEALANT OR EQUIVALENT.
MODULE WEIGHT (LBS)
# OF MODULES
TOTAL MODULE WEIGHT (LBS)
RACK WEIGHT (LBS)
TOTAL SYSTEM WEIGHT (LBS)
# OF STANDOFFS
LOADING PER STANDOFF (LBS)
TOTAL MODULE AREA (SQ.FT.)
LOADING (PSF)
WEIGHT LOAD CALCULATION INDEX
ROOF SHEATHED WITH 1/2" PLYWOOD AND UPPER
SURFACE IS FACED WITH FELT PAPER
TOTAL ROOF AREA (Sq. FT)
% OF COVERED AREA
PV MODULE MODEL #
54.0
Q.PEAK DUO L-G8 430
MICROINVERTER WEIGHT (LBS)
46
Roof 1 Layer Comp Shingle SWH Rafter Stacked 48"2"X6" @ 16" O.C
MIN 2.5" EMBEDMENT
RACKING RAIL
ATTACHMENT
ROOF FRAMING
SWH L-Feet
5/16" X 5"
L Foot
Flat Flashing
ATTACHMENT DETAILS
5/16" X 5" Lag Bolt with 2.5"
Min. embedment into the Rafter
128
1058
5775
2484
497
109
3090
24.1
2.92
18.3
2''X6'' Blocking
OPEN CEILING
SOLAR MODULE
ROOF
ASCE 7-16
Max 6''
DF #2 2" BY 6" RAFTERS @ 16" O.C.
48'' 16''
E
V
No. C70784
Exp. 06/30/2023
4410 W Celeste St
12/23/21
6
MODULE
MAP
PV SYSTEM
AS INDICATED
SEPTEMBER 30, 2021
NAM NGUYEN
4410 CELESTE ST,
SANTA ANA, CA 92703
CONTRACTOR
True Power Solar
Address:
201 Clark Ave
Pomona, CA 91767
Phone Number:
(714)676-8888
Lic type: C-46
Lic# 970591
Drawn By : Narek A.
[FOR INSTALLER USE ONLY]
PHOTOVOLTAIC SYSTEM
46 Hanwha 430W Modules (Q.PEAK DUO L-G8 430)
46 Enphase Energy Microinverters
(IQ7PLUS-72-2-US)
19.78 KW DC
Solar Array 3
5 Hanwha Q.Cell 430W
5 IQ7+ Microinverters
Pitch: 21 Deg
Orientation: 135 Deg
Solar Array 5
10 Hanwha Q.Cell 430W
10 IQ7+ Microinverters
Pitch: 21 Deg
Orientation: 135 Deg
Solar Array 2
13 Hanwha Q.Cell 430W
13 IQ7+ Microinverters
Pitch: 21 Deg
Orientation: 180 Deg
Solar Array 6
4 Hanwha Q.Cell 430W
4 IQ7+ Microinverters
Pitch: 21 Deg
Orientation: 315 Deg
Solar Array 4
3 Hanwha Q.Cell 430W
3 IQ7+ Microinverters
Pitch: 21 Deg
Orientation: 315 Deg
Solar Array 1
11 Hanwha Q.Cell 430W
11 IQ7+ Microinverters
Pitch: 21 Deg
Orientation: 0 Deg
4410 W Celeste St
12/23/21
7
PV SYSTEM
AS INDICATED
SEPTEMBER 30, 2021
NAM NGUYEN
4410 CELESTE ST,
SANTA ANA, CA 92703
CONTRACTOR
True Power Solar
Address:
201 Clark Ave
Pomona, CA 91767
Phone Number:
(714)676-8888
Lic type: C-46
Lic# 970591
Drawn By : Narek A.
INVERTER
MAP
INVERTERPHOTOVOLTAIC SYSTEM
46 Hanwha 430W Modules (Q.PEAK DUO L-G8 430)
46
ENVOY SERIAL #:
ENVOY LOCATION:
COMMUNICATION LEVEL:
ETHERNET BRIDGE INSTALLED:
NOTES:
Enphase Energy Microinverters
(IQ7PLUS-72-2-US)
19.78 KW DC
[FOR INSTALLER USE ONLY]
Solar Array 3
5 Hanwha Q.Cell 430W
5 IQ7+ Microinverters
Pitch: 21 Deg
Orientation: 135 Deg
Solar Array 5
10 Hanwha Q.Cell 430W
10 IQ7+ Microinverters
Pitch: 21 Deg
Orientation: 135 Deg
Solar Array 2
13 Hanwha Q.Cell 430W
13 IQ7+ Microinverters
Pitch: 21 Deg
Orientation: 180 Deg
Solar Array 6
4 Hanwha Q.Cell 430W
4 IQ7+ Microinverters
Pitch: 21 Deg
Orientation: 315 Deg
Solar Array 4
3 Hanwha Q.Cell 430W
3 IQ7+ Microinverters
Pitch: 21 Deg
Orientation: 315 Deg
Solar Array 1
11 Hanwha Q.Cell 430W
11 IQ7+ Microinverters
Pitch: 21 Deg
Orientation: 0 Deg
4410 W Celeste St
12/23/21
D1
MODULE
DATA SHEET
PV SYSTEM
AS INDICATED
SEPTEMBER 30, 2021
NAM NGUYEN
4410 CELESTE ST,
SANTA ANA, CA 92703
CONTRACTOR
True Power Solar
Address:
201 Clark Ave
Pomona, CA 91767
Phone Number:
(714)676-8888
Lic type: C-46
Lic# 970591
Drawn By : Narek A.
4410 W Celeste St
12/23/21
INVERTER
DATA SHEET
PV SYSTEM
AS INDICATED
SEPTEMBER 30, 2021
NAM NGUYEN
4410 CELESTE ST,
SANTA ANA, CA 92703
CONTRACTOR
True Power Solar
Address:
201 Clark Ave
Pomona, CA 91767
Phone Number:
(714)676-8888
Lic type: C-46
Lic# 970591
Drawn By : Narek A.
D2
4410 W Celeste St
12/23/21
PV SYSTEM
AS INDICATED
SEPTEMBER 30, 2021
NAM NGUYEN
4410 CELESTE ST,
SANTA ANA, CA 92703
CONTRACTOR
True Power Solar
Address:
201 Clark Ave
Pomona, CA 91767
Phone Number:
(714)676-8888
Lic type: C-46
Lic# 970591
Drawn By : Narek A.
IQ COMBINER
BOX DATA SHEET
D3
4410 W Celeste St
12/23/21
PV SYSTEM
AS INDICATED
SEPTEMBER 30, 2021
NAM NGUYEN
4410 CELESTE ST,
SANTA ANA, CA 92703
CONTRACTOR
True Power Solar
Address:
201 Clark Ave
Pomona, CA 91767
Phone Number:
(714)676-8888
Lic type: C-46
Lic# 970591
Drawn By : Narek A.
D4
RACKING
DATA SHEET
4410 W Celeste St
12/23/21
PV SYSTEM
AS INDICATED
SEPTEMBER 30, 2021
NAM NGUYEN
4410 CELESTE ST,
SANTA ANA, CA 92703
CONTRACTOR
True Power Solar
Address:
201 Clark Ave
Pomona, CA 91767
Phone Number:
(714)676-8888
Lic type: C-46
Lic# 970591
Drawn By : Narek A.
ATTACHMENT
DATA SHEET
D5
4410 W Celeste St
12/23/21
PV SYSTEM
AS INDICATED
SEPTEMBER 30, 2021
NAM NGUYEN
4410 CELESTE ST,
SANTA ANA, CA 92703
CONTRACTOR
True Power Solar
Address:
201 Clark Ave
Pomona, CA 91767
Phone Number:
(714)676-8888
Lic type: C-46
Lic# 970591
Drawn By : Narek A.
D6
RACKING
CERTIFICATION
4410 W Celeste St
12/23/21
Rev: 11/19/2015
RESIDENTIAL
PHOTOVOLTAIC
CHECKLIST
SOL-01 CBC 2013
Solar Photovoltaic (PV) Checklist for Detached SINGLE FAMILY RESIDENCES Only
Instructions: The licensed contractor of record shall complete all sections, answer the ten questions and
sign the certification section below. A copy of this form shall be attached to each of TWO sets of plans, of
minimum 11” x 17” size. If answering NO to any of the questions, plan check shall be required.
Project Address:
Contractor Company Name:
Contractor License Number:
YES NO Are the following applicable to the proposed project?
1. Will the PV system layout provide the required three-foot wide clear access pathways
per Section 605.11 of the California Fire Code, and is this shown on the roof plan?
2. Will the PV system be installed on a roof having only one roofing layer with no
overlays?
3.Will the PV array be flush mounted to the existing roof so that the plane of the
modules (panels) are parallel to the plane of the roof?
4.Will the PV system weigh maximum 4 pounds per square feet or less?
5.Will the PV system be installed where the modules do not overhang any roof edges
(such as eaves, gabled ends, ridges and hips)?
6.Will the PV system be installed with a space of 2” minimum to 10” maximum between
the underside of modules and the surface of the roof?
7.Will the PV system be installed without using any ballast system or counter-weight
system?
8.Will the anchors be installed with a maximum horizontal anchor spacing of 6 feet
and is this maximum horizontal spacing shown on the plans?
9.Will the minimum 5/16” lag screws be installed with a minimum of 2-1/2 inch
embedment into roof rafters (with pre-drilled holes) and is this minimum embedment
shown on the plans?
10.Are ALL the structural pages of the plans stamped and signed by a California
licensed professional engineer? (including project specific site plan, PV layout,
anchorage spacing, anchorage details and manufacturer’s PV support information.)
I certify under penalty of perjury under the laws of the State of California that the above is true:
Print Name: Signature:
Phone Number: Date:
Email Address:
Planning & Building Agency
Building Safety Division
20 Civic Center Plaza
P.O. Box 1988 (M-19)
Santa Ana, CA 92702
(714) 647-5800
www.santa-ana.org
4410 Celeste Street, Santa Ana, CA 92703
True Power Solar
970591
X
X
X
X
X
X
X
X
X
X
Maochen Chang
(909)753-3178 10/12/2021
operations@truepowersolar.com
Maochen Chang
4410 W Celeste St
12/23/21