HomeMy WebLinkAbout515 E Dyer - PlanUTILITY-DLX8
Utility Company -
SystemNominalVoltage 480.0 V
SC Contribution 3P 9021.0 Amps
SC Contribution SLG 5638.0 Amps
SWBD MSA
57.6 Cal/cm^2
16.135 kA
203 inches
480.0 V
CBL-SWBD MSA
500 kcmil
105.0 ft
3 per phase
F-PNL HA
GOULD SHAWMUT
A6T
Sensor/Trip 400.0 A
InterruptingRating 200.0 kA
CBL-PNL HA
3/0 AWG
505.0 ft
1 per phase
PNL HA
8.67 Cal/cm^2
4.473 kA
62 inches
480.0 V
F-PNL HH
GOULD SHAWMUT
A6T
Sensor/Trip 225.0 A
InterruptingRating 200.0 kA
CBL-PNL HH
4/0 AWG
966.0 ft
1 per phase
PNL HH
2.14 Cal/cm^2
3.002 kA
26 inches
480.0 V
F-PNL HJ
GOULD SHAWMUT
A6T
Sensor/Trip 225.0 A
InterruptingRating 200.0 kA
CBL-PNL HJ
4/0 AWG
840.0 ft
1 per phase
PNL HJ
1.49 Cal/cm^2
3.372 kA
21 inches
480.0 V
S
P
T-PNL LA
112.5 kVA
5.6000 %
480 V
208 V
CBL-PNL LA
500 kcmil
12.0 ft
1 per phase
CB-T-PNL LA
SQUARE D
JJ
Sensor/Trip 175.0 A
Plug 175.0 A
Settings
Thermal Curve
INST (5-10 x Trip) 10 (1750A)
InterruptingRating 65.0 kA
CBL-T-PNL LA
3/0 AWG
12.0 ft
1 per phase
MCB-PNL LA
SQUARE D
LA
Sensor/Trip 400.0 A
Plug 400.0 A
Settings
Thermal Curve
INST 10 (4000A)
InterruptingRating 42.0 kA
PNL LA
6.59 Cal/cm^2
3.639 kA
52 inches
208.0 V
S
P
T-PNL LH
75 kVA
5.0000 %
480 V
208 V
CBL-PNL LH
4/0 AWG
12.0 ft
1 per phase
CB-T-PNL LH
SQUARE D
ED
Sensor/Trip 100.0 A
Plug 100.0 A
Settings
Fixed
InterruptingRating 18.0 kA
CBL-T-PNL LH
2 AWG
15.0 ft
1 per phase
S
P
T-PNL LJ
75 kVA
5.0000 %
480 V
208 V
CBL-PNL LJ
4/0 AWG
12.0 ft
1 per phase
CB-T-PNL LJ
SQUARE D
ED
Sensor/Trip 100.0 A
Plug 100.0 A
Settings
Fixed
InterruptingRating 18.0 kA
CBL-T-PNL LJ
2 AWG
15.0 ft
1 per phase
MCB-PNL LJ
SQUARE D
QB
Sensor/Trip 225.0 A
Plug 225.0 A
Settings
Fixed
InterruptingRating 10.0 kA
PNL LJ
4.69 Cal/cm^2
2.702 kA
42 inches
208.0 V
CBL-PNL LA1
500 kcmil
10.0 ft
1 per phase
PNL LA1
6.47 Cal/cm^2
3.579 kA
52 inches
208.0 V
CB-PNL LA2
SQUARE D
QB
Sensor/Trip 200.0 A
Plug 200.0 A
Settings
Fixed
InterruptingRating 10.0 kA
CBL-PNL LA2
4/0 AWG
10.0 ft
1 per phase
PNL LA2
6.31 Cal/cm^2
3.502 kA
51 inches
208.0 V
CB-T-PNL MDF
SQUARE D
ED
Sensor/Trip 70.0 A
Plug 70.0 A
Settings
Fixed
InterruptingRating 18.0 kA
CBL-T-PNL MDF
4 AWG
85.0 ft
1 per phase
S
P
T-PNL MDF
45 kVA
4.2000 %
480 V
208 V
CBL-PNL MDF
2/0 AWG
12.0 ft
1 per phase
MCB-PNL MDF
SQUARE D
HD
Sensor/Trip 150.0 A
Plug 150.0 A
Settings
Fixed
InterruptingRating 18.0 kA
PNL MDF
3.64 Cal/cm^2
2.167 kA
36 inches
208.0 V
CB-HJ-DS-SF-2
SQUARE D
ED
Sensor/Trip 15.0 A
Plug 15.0 A
Settings
Fixed
InterruptingRating 18.0 kA
CBL-HJ-DS-SF-2
10 AWG
280.0 ft
1 per phase
HJ-DS-SF-2
0.12 Cal/cm^2
0.698 kA
4 inches
480.0 V
CB-HH-DS-SF-5
SQUARE D
ED
Sensor/Trip 15.0 A
Plug 15.0 A
Settings
Fixed
InterruptingRating 18.0 kA
CBL-HH-DS-SF-5
10 AWG
290.0 ft
1 per phase
HH-DS-SF-5
0.13 Cal/cm^2
0.663 kA
4 inches
480.0 V
CB-DS-CU-1
SQUARE D
ED
Sensor/Trip 60.0 A
Plug 60.0 A
Settings
Fixed
InterruptingRating 18.0 kA
CBL-DS-CU-1
6 AWG
90.0 ft
1 per phase
DS-CU-1
0.07 Cal/cm^2
2.690 kA
3 inches
480.0 V
CB-DS-CU-2
SQUARE D
ED
Sensor/Trip 60.0 A
Plug 60.0 A
Settings
Fixed
InterruptingRating 18.0 kA
CBL-DS-CU-2
6 AWG
65.0 ft
1 per phase
DS-CU-2
0.08 Cal/cm^2
3.041 kA
3 inches
480.0 V
CB-DS-CF-D26
SQUARE D
ED
Sensor/Trip 15.0 A
Plug 15.0 A
Settings
Fixed
InterruptingRating 18.0 kA
CBL-DS-CF-D26
10 AWG
230.0 ft
1 per phase
DS-CF-D26
0.1 Cal/cm^2
0.797 kA
4 inches
480.0 V
CB-DS-CF-B27
SQUARE D
ED
Sensor/Trip 15.0 A
Plug 15.0 A
Settings
Fixed
InterruptingRating 18.0 kA
CBL-DS-CF-B27
10 AWG
245.0 ft
1 per phase
DS-CF-B27
0.11 Cal/cm^2
0.759 kA
4 inches
480.0 V
MCB-PNL LH
SQUARE D
QB
Sensor/Trip 225.0 A
Plug 225.0 A
Settings
Fixed
InterruptingRating 10.0 kA
PNL LH
4.48 Cal/cm^2
2.599 kA
41 inches
208.0 V
E.601.AF
Uninterruptible
Power Supply (UPS)
Bus - Panel (PNL), Switchboard
(SWBD), Disconnect Switch (DS),
or Control Panel (CP)
Auto/Manual Transfer Switch
(ATS/MTS)
Utility
Motor (M)
Fuse (F)
E N
Receptacle (R)
Transformer (T)
Generator
(GEN)
(Main) Circuit Breaker
(MCB, CB)
Capacitor Bank (C)
Utility MeterWH
Bus Duct (BD)
Battery (BAT)
Rectifier (REC)
Switch (SW)
Fuse Switch (FS)
1. NOT TO BE USED FOR CONSTRUCTION PURPOSES
2. THIS DRAWING WAS CREATED FROM FIELD
NOTES TAKEN FROM THE SITE SURVEY ON
THE DATE SHOWN IN THE DESCRIPTION BOX
BELOW
3. ELECTRICAL DETAILS HAVE BEEN
DOCUMENTED WHERE INFORMATION
HAS BEEN VERIFIED WITH A SURVEY AND MAY BE A
COMBINATION OF THE FOLLOWING:
• EQUIPMENT NAMEPLATES
• EXISTING EQUIPMENT LABELING
• EXISTING ELECTRICAL SITE DRAWINGS
Legend
Load (L)
(Main) Medium Voltage Circuit
Breaker (MCB, CB)
Relay (RLY)
C:\Users\Jeff Lunsford\Desktop\arc_flash_report\amazonlogo.jpg
***NO PLAN CHECK REQ'D per M. Smith***
Planning approved by F. Arias
Elect permit #20177149
Permit issued on 8/25/22
515 E Dyer Rd -
2017714908/25/22
TO E.603.AF
UTILITY-DLX8
Utility Company -
SystemNominalVoltage 480.0 V
SC Contribution 3P 9021.0 Amps
SC Contribution SLG 5638.0 Amps
CBL-SWBD MSB
500 kcmil
85.0 ft
5 per phase
MF-SWBD MSB
BUSSMANN
KTU
Sensor/Trip 2000.0 A
InterruptingRating 200.0 kA
SWBD MSB
61.1 Cal/cm^2
17.066 kA
211 inches
480.0 V
F-PNL HC
BUSSMANN
JKS
Sensor/Trip 200.0 A
InterruptingRating 200.0 kA
CBL-PNL HC
4/0 AWG
435.0 ft
1 per phase
S
P
T-PNL LC
75 kVA
5.0000 %
480 V
208 V
CBL-PNL LC
4/0 AWG
15.0 ft
1 per phase
PNL HC
0.09 Cal/cm^2
5.672 kA
4 inches
480.0 V
CB-T-PNL LC
SQUARE D
ED
Sensor/Trip 100.0 A
Plug 100.0 A
Settings
Fixed
InterruptingRating 18.0 kA
CBL-T-PNL LC
2 AWG
15.0 ft
1 per phase
MCB-PNL LC
SQUARE D
QB
Sensor/Trip 225.0 A
Plug 225.0 A
Settings
Fixed
InterruptingRating 10.0 kA
PNL LC
5.45 Cal/cm^2
3.084 kA
46 inches
208.0 V
F-PNL HK
BUSSMANN
JKS
Sensor/Trip 200.0 A
InterruptingRating 200.0 kA
F-PNL HL
BUSSMANN
JKS
Sensor/Trip 200.0 A
InterruptingRating 200.0 kA
F-PNL HM
BUSSMANN
JKS
Sensor/Trip 200.0 A
InterruptingRating 200.0 kA
CBL-PNL HM
3/0 AWG
45.0 ft
1 per phase
PNL HM
0.11 Cal/cm^2
14.183 kA
4 inches
480.0 V
F-PNL DISTRIBUTION
BUSSMANN
KLU
Sensor/Trip 1200.0 A
InterruptingRating 200.0 kA
S
P
T-PNL LM
75 kVA
5.0000 %
480 V
208 V
CBL-PNL LM
4/0 AWG
15.0 ft
1 per phase
CB-T-PNL LM
SQUARE D
ED
Sensor/Trip 100.0 A
Plug 100.0 A
Settings
Fixed
InterruptingRating 18.0 kA
CBL-T-PNL LM
2 AWG
15.0 ft
1 per phase
MCB-PNL LM
SQUARE D
QB
Sensor/Trip 225.0 A
Plug 225.0 A
Settings
Fixed
InterruptingRating 10.0 kA
PNL LM
6.4 Cal/cm^2
3.546 kA
51 inches
208.0 V
CB-TERM-EF11/12
SQUARE D
ED
Sensor/Trip 20.0 A
Plug 20.0 A
Settings
Fixed
InterruptingRating 18.0 kA
CBL-TERM-EF11/12
10 AWG
190.0 ft
1 per phase
CBL-DS-EF-11
10 AWG
31.0 ft
1 per phase
DS-EF-11
0.02 Cal/cm^2
1.025 kA
2 inches
480.0 V
CBL-DS-EF-12
10 AWG
2.0 ft
1 per phase
DS-EF-12
0.03 Cal/cm^2
1.173 kA
2 inches
480.0 V
CB-TERM-EF15
SQUARE D
ED
Sensor/Trip 15.0 A
Plug 15.0 A
Settings
Fixed
InterruptingRating 18.0 kA
CBL-DS-EF-15
12 AWG
216.0 ft
1 per phase
DS-EF-15
0.12 Cal/cm^2
0.671 kA
4 inches
480.0 V
CBL-PNL HK
4/0 AWG
694.0 ft
1 per phase
PNL HK
0.16 Cal/cm^2
3.987 kA
5 inches
480.0 V
CBL-PNL HL
3/0 AWG
349.0 ft
1 per phase
PNL HL
0.09 Cal/cm^2
5.973 kA
3 inches
480.0 V
S
P
T-PNL LK
75 kVA
5.0000 %
480 V
208 V
CBL-PNL LK
4/0 AWG
15.0 ft
1 per phase
CB-T-PNL LK
SQUARE D
ED
Sensor/Trip 100.0 A
Plug 100.0 A
Settings
Fixed
InterruptingRating 18.0 kA
CBL-T-PNL LK
2 AWG
15.0 ft
1 per phase
MCB-PNL LK
SQUARE D
QB
Sensor/Trip 225.0 A
Plug 225.0 A
Settings
Fixed
InterruptingRating 10.0 kA
PNL LK
4.94 Cal/cm^2
2.828 kA
44 inches
208.0 V
S
P
T-PNL LL
75 kVA
5.0000 %
480 V
208 V
CBL-PNL LL
4/0 AWG
15.0 ft
1 per phase
CB-T-PNL LL
SQUARE D
ED
Sensor/Trip 100.0 A
Plug 100.0 A
Settings
Fixed
InterruptingRating 18.0 kA
CBL-T-PNL LL
2 AWG
15.0 ft
1 per phase
MCB-PNL LL
SQUARE D
QB
Sensor/Trip 225.0 A
Plug 225.0 A
Settings
Fixed
InterruptingRating 10.0 kA
PNL LL
5.55 Cal/cm^2
3.130 kA
47 inches
208.0 V
CB-DS-CF 11
SQUARE D
ED
Sensor/Trip 15.0 A
Plug 15.0 A
Settings
Fixed
InterruptingRating 18.0 kA
CBL-DS-CF 11
10 AWG
75.0 ft
1 per phase
DS-CF 11
0.05 Cal/cm^2
1.876 kA
2 inches
480.0 V
CB-DS-CF 12
SQUARE D
ED
Sensor/Trip 15.0 A
Plug 15.0 A
Settings
Fixed
InterruptingRating 18.0 kA
CBL-DS-CF 12
10 AWG
65.0 ft
1 per phase
DS-CF 12
0.05 Cal/cm^2
2.029 kA
2 inches
480.0 V
CB-DS-CF 15
SQUARE D
ED
Sensor/Trip 15.0 A
Plug 15.0 A
Settings
Fixed
InterruptingRating 18.0 kA
CBL-DS-CF 15
10 AWG
65.0 ft
1 per phase
DS-CF 15
0.06 Cal/cm^2
2.404 kA
3 inches
480.0 V
CB-HL-DS-SF-2
SQUARE D
ED
Sensor/Trip 15.0 A
Plug 15.0 A
Settings
Fixed
InterruptingRating 18.0 kA
CBL-HL-DS-SF-2
10 AWG
180.0 ft
1 per phase
HL-DS-SF-2
0.03 Cal/cm^2
1.113 kA
2 inches
480.0 V
CB-HK-DS-SF-2
SQUARE D
ED
Sensor/Trip 15.0 A
Plug 15.0 A
Settings
Fixed
InterruptingRating 18.0 kA
CBL-HK-DS-SF-2
10 AWG
148.0 ft
1 per phase
HK-DS-SF-2
0.03 Cal/cm^2
1.198 kA
2 inches
480.0 V
CB-DS-CF-G23
SQUARE D
ED
Sensor/Trip 15.0 A
Plug 15.0 A
Settings
Fixed
InterruptingRating 18.0 kA
CBL-DS-CF-G23
10 AWG
117.0 ft
1 per phase
DS-CF-G23
0.03 Cal/cm^2
1.417 kA
2 inches
480.0 V
CB-DS-CF-G27
SQUARE D
ED
Sensor/Trip 15.0 A
Plug 15.0 A
Settings
Fixed
InterruptingRating 18.0 kA
CBL-DS-CF-G27
10 AWG
203.0 ft
1 per phase
DS-CF-G27
0.09 Cal/cm^2
0.938 kA
4 inches
480.0 V
CB-DS-CF-E23
SQUARE D
ED
Sensor/Trip 15.0 A
Plug 15.0 A
Settings
Fixed
InterruptingRating 18.0 kA
CBL-DS-CF-E23
10 AWG
218.0 ft
1 per phase
DS-CF-E23
0.09 Cal/cm^2
0.886 kA
4 inches
480.0 V
CB-DS-CF-H19.5
SQUARE D
ED
Sensor/Trip 15.0 A
Plug 15.0 A
Settings
Fixed
InterruptingRating 18.0 kA
CBL-DS-CF-H19.5
10 AWG
145.0 ft
1 per phase
DS-CF-H19.5
0.03 Cal/cm^2
1.333 kA
2 inches
480.0 V
CBL-PNL DISTRIBUTION
600 kcmil
53.0 ft
3 per phase
E.602.AF
Uninterruptible
Power Supply (UPS)
Bus - Panel (PNL), Switchboard
(SWBD), Disconnect Switch (DS),
or Control Panel (CP)
Auto/Manual Transfer Switch
(ATS/MTS)
Utility
Motor (M)
Fuse (F)
E N
Receptacle (R)
Transformer (T)
Generator
(GEN)
(Main) Circuit Breaker
(MCB, CB)
Capacitor Bank (C)
Utility MeterWH
Bus Duct (BD)
Battery (BAT)
Rectifier (REC)
Switch (SW)
Fuse Switch (FS)
1. NOT TO BE USED FOR CONSTRUCTION PURPOSES
2. THIS DRAWING WAS CREATED FROM FIELD
NOTES TAKEN FROM THE SITE SURVEY ON
THE DATE SHOWN IN THE DESCRIPTION BOX
BELOW
3. ELECTRICAL DETAILS HAVE BEEN
DOCUMENTED WHERE INFORMATION
HAS BEEN VERIFIED WITH A SURVEY AND MAY BE A
COMBINATION OF THE FOLLOWING:
• EQUIPMENT NAMEPLATES
• EXISTING EQUIPMENT LABELING
• EXISTING ELECTRICAL SITE DRAWINGS
Legend
Load (L)
(Main) Medium Voltage Circuit
Breaker (MCB, CB)
Relay (RLY)
C:\Users\Jeff Lunsford\Desktop\arc_flash_report\amazonlogo.jpg
515 E Dyer Rd -
2017714908/25/22
TO E.604.AF
FROM E.602.AF
F-PNL HB
BUSSMANN
JKS
Sensor/Trip 200.0 A
InterruptingRating 200.0 kA
F-PNL HE
BUSSMANN
JKS
Sensor/Trip 200.0 A
InterruptingRating 200.0 kA
F-PNL HF
BUSSMANN
JKS
Sensor/Trip 200.0 A
InterruptingRating 200.0 kA
F-PNL HG
BUSSMANN
JKS
Sensor/Trip 200.0 A
InterruptingRating 200.0 kA
F-PNL HN
BUSSMANN
JKS
Sensor/Trip 100.0 A
InterruptingRating 200.0 kA
F-PNL HQ
BUSSMANN
JKS
Sensor/Trip 100.0 A
InterruptingRating 200.0 kA
F-PNL HR
BUSSMANN
JKS
Sensor/Trip 100.0 A
InterruptingRating 200.0 kA
F-PNL HT
BUSSMANN
JKS
Sensor/Trip 100.0 A
InterruptingRating 200.0 kA
CB-T-PNL EV
GOULD SHAWMUT
A4J
Sensor/Trip 175.0 A
InterruptingRating 200.0 kA
CBL-T-PNL EV
2/0 AWG
85.0 ft
1 per phase
S
P
T-PNL EV
112.5 kVA
5.6000 %
480 V
208 V
CBL-PNL EV
500 kcmil
15.0 ft
1 per phase
MCB-PNL EV
SQUARE D
LA
Sensor/Trip 400.0 A
Plug 400.0 A
Settings
Thermal Curve
INST 10 (4000A)
InterruptingRating 30.0 kA
PNL EV
7.43 Cal/cm^2
4.472 kA
56 inches
208.0 V
PNL DISTRIBUTION
28.83 Cal/cm^2
16.171 kA
132 inches
480.0 V
CBL-PNL DISTRIBUTION
600 kcmil
53.0 ft
3 per phase
CBL-PNL HN
1/0 AWG
546.0 ft
1 per phase
PNL HN
0.04 Cal/cm^2
3.182 kA
2 inches
480.0 V
CBL-PNL HQ
1/0 AWG
430.0 ft
1 per phase
PNL HQ
0.05 Cal/cm^2
3.891 kA
2 inches
480.0 V
CBL-PNL HR
3/0 AWG
760.0 ft
1 per phase
PNL HR
0.04 Cal/cm^2
3.223 kA
2 inches
480.0 V
CBL-PNL HT
3/0 AWG
980.0 ft
1 per phase
PNL HT
0.06 Cal/cm^2
2.593 kA
3 inches
480.0 V
S
P
T-PNL LN
15 kVA
4.9000 %
480 V
208 V
CBL-PNL LN
6 AWG
15.0 ft
1 per phase
CB-T-PNL LN
SQUARE D
ED
Sensor/Trip 25.0 A
Plug 25.0 A
Settings
Fixed
InterruptingRating 18.0 kA
CBL-T-PNL LN
10 AWG
15.0 ft
1 per phase
MCB-PNL LN
SQUARE D
QOB
Sensor/Trip 60.0 A
Plug 60.0 A
Settings
Fixed (730-6, 60A)
InterruptingRating 10.0 kA
PNL LN
1.09 Cal/cm^2
0.746 kA
17 inches
208.0 V
S
P
T-PNL LQ
15 kVA
4.9000 %
480 V
208 V
CBL-PNL LQ
6 AWG
15.0 ft
1 per phase
CB-T-PNL LQ
SQUARE D
ED
Sensor/Trip 25.0 A
Plug 25.0 A
Settings
Fixed
InterruptingRating 18.0 kA
CBL-T-PNL LQ
10 AWG
15.0 ft
1 per phase
MCB-PNL LQ
SQUARE D
QOB
Sensor/Trip 60.0 A
Plug 60.0 A
Settings
Fixed (730-6, 60A)
InterruptingRating 10.0 kA
PNL LQ
1.11 Cal/cm^2
0.757 kA
17 inches
208.0 V
S
P
T-PNL LR
15 kVA
4.9000 %
480 V
208 V
CBL-PNL LR
6 AWG
15.0 ft
1 per phase
CB-T-PNL LR
SQUARE D
ED
Sensor/Trip 25.0 A
Plug 25.0 A
Settings
Fixed
InterruptingRating 18.0 kA
CBL-T-PNL LR
10 AWG
15.0 ft
1 per phase
MCB-PNL LR
SQUARE D
QOB
Sensor/Trip 60.0 A
Plug 60.0 A
Settings
Fixed (730-6, 60A)
InterruptingRating 10.0 kA
PNL LR
1.08 Cal/cm^2
0.742 kA
17 inches
208.0 V
S
P
T-PNL LT
15 kVA
4.9000 %
480 V
208 V
CBL-PNL LT
6 AWG
15.0 ft
1 per phase
CB-T-PNL LT
SQUARE D
ED
Sensor/Trip 25.0 A
Plug 25.0 A
Settings
Fixed
InterruptingRating 18.0 kA
CBL-T-PNL LT
10 AWG
15.0 ft
1 per phase
MCB-PNL LT
SQUARE D
QOB
Sensor/Trip 60.0 A
Plug 60.0 A
Settings
Fixed (730-6, 60A)
InterruptingRating 10.0 kA
PNL LT
1.06 Cal/cm^2
0.726 kA
17 inches
208.0 V
CB-DS-CP-DD WEST 1
SQUARE D
ED
Sensor/Trip 15.0 A
Plug 15.0 A
Settings
Fixed
InterruptingRating 18.0 kA
CBL-DS-CP-DD WEST 1
10 AWG
60.0 ft
1 per phase
DS-CP-DD WEST 1
0.04 Cal/cm^2
1.630 kA
2 inches
480.0 V
CBL-CP-DD WEST 1
10 AWG
15.0 ft
1 per phase
CP-DD WEST 1
0.02 Cal/cm^2
1.485 kA
1 inches
480.0 V
F-DS-CP-DD WEST 1
BUSSMANN
FRS-R
Sensor/Trip 15.0 A
InterruptingRating 200.0 kA
CB-DS-CP-DD WEST 2
SQUARE D
ED
Sensor/Trip 15.0 A
Plug 15.0 A
Settings
Fixed
InterruptingRating 18.0 kA
CBL-DS-CP-DD WEST 2
10 AWG
80.0 ft
1 per phase
DS-CP-DD WEST 2
0.03 Cal/cm^2
1.442 kA
2 inches
480.0 V
CBL-CP-DD WEST 2
10 AWG
15.0 ft
1 per phase
CP-DD WEST 2
0.02 Cal/cm^2
1.325 kA
1 inches
480.0 V
F-DS-CP-DD WEST 2
BUSSMANN
FRS-R
Sensor/Trip 15.0 A
InterruptingRating 200.0 kA
CB-TERM-EF1/2
SQUARE D
ED
Sensor/Trip 25.0 A
Plug 25.0 A
Settings
Fixed
InterruptingRating 18.0 kA
CBL-TERM-EF1/2
10 AWG
180.0 ft
1 per phase
CBL-DS-EF-1
10 AWG
8.0 ft
1 per phase
DS-EF-1
0.21 Cal/cm^2
0.936 kA
6 inches
480.0 V
CBL-DS-EF-2
10 AWG
47.0 ft
1 per phase
DS-EF-2
0.24 Cal/cm^2
0.812 kA
7 inches
480.0 V
CB-TERM-EF3/4
SQUARE D
ED
Sensor/Trip 25.0 A
Plug 25.0 A
Settings
Fixed
InterruptingRating 18.0 kA
CBL-TERM-EF3/4
10 AWG
200.0 ft
1 per phase
CBL-DS-EF-3
10 AWG
30.0 ft
1 per phase
DS-EF-3
0.26 Cal/cm^2
0.760 kA
7 inches
480.0 V
CBL-DS-EF-4
10 AWG
60.0 ft
1 per phase
DS-EF-4
0.28 Cal/cm^2
0.693 kA
7 inches
480.0 V
CB-TERM-EF5/6
SQUARE D
ED
Sensor/Trip 25.0 A
Plug 25.0 A
Settings
Fixed
InterruptingRating 18.0 kA
CBL-TERM-EF5/6
10 AWG
220.0 ft
1 per phase
CBL-DS-EF-5
10 AWG
77.0 ft
1 per phase
DS-EF-5
0.3 Cal/cm^2
0.644 kA
8 inches
480.0 V
CBL-DS-EF-6
10 AWG
27.0 ft
1 per phase
DS-EF-6
0.26 Cal/cm^2
0.746 kA
7 inches
480.0 V
CB-TERM-EF7/8
SQUARE D
ED
Sensor/Trip 30.0 A
Plug 30.0 A
Settings
Fixed
InterruptingRating 18.0 kA
CBL-TERM-EF7/8
10 AWG
200.0 ft
1 per phase
CBL-DS-EF-7
10 AWG
35.0 ft
1 per phase
DS-EF-7
0.34 Cal/cm^2
0.811 kA
8 inches
480.0 V
CBL-DS-EF-8
10 AWG
46.0 ft
1 per phase
DS-EF-8
0.36 Cal/cm^2
0.782 kA
8 inches
480.0 V
CBL-PNL HB
3/0 AWG
145.0 ft
1 per phase
CBL-PNL HE
3/0 AWG
388.0 ft
1 per phase
CBL-PNL HF
2/0 AWG
606.0 ft
2 per phase
CBL-PNL HG
2/0 AWG
831.0 ft
2 per phase
TO E.604.AF TO E.604.AF TO E.604.AF
E.603.AF
Uninterruptible
Power Supply (UPS)
Bus - Panel (PNL), Switchboard
(SWBD), Disconnect Switch (DS),
or Control Panel (CP)
Auto/Manual Transfer Switch
(ATS/MTS)
Utility
Motor (M)
Fuse (F)
E N
Receptacle (R)
Transformer (T)
Generator
(GEN)
(Main) Circuit Breaker
(MCB, CB)
Capacitor Bank (C)
Utility MeterWH
Bus Duct (BD)
Battery (BAT)
Rectifier (REC)
Switch (SW)
Fuse Switch (FS)
1. NOT TO BE USED FOR CONSTRUCTION PURPOSES
2. THIS DRAWING WAS CREATED FROM FIELD
NOTES TAKEN FROM THE SITE SURVEY ON
THE DATE SHOWN IN THE DESCRIPTION BOX
BELOW
3. ELECTRICAL DETAILS HAVE BEEN
DOCUMENTED WHERE INFORMATION
HAS BEEN VERIFIED WITH A SURVEY AND MAY BE A
COMBINATION OF THE FOLLOWING:
• EQUIPMENT NAMEPLATES
• EXISTING EQUIPMENT LABELING
• EXISTING ELECTRICAL SITE DRAWINGS
Legend
Load (L)
(Main) Medium Voltage Circuit
Breaker (MCB, CB)
Relay (RLY)
C:\Users\Jeff Lunsford\Desktop\arc_flash_report\amazonlogo.jpg
515 E Dyer Rd -
2017714908/25/22
FROM E.603.AF
CBL-PNL HB
3/0 AWG
145.0 ft
1 per phase
PNL HB
0.12 Cal/cm^2
9.619 kA
4 inches
480.0 V
CBL-PNL HE
3/0 AWG
388.0 ft
1 per phase
PNL HE
0.1 Cal/cm^2
5.441 kA
4 inches
480.0 V
CBL-PNL HF
2/0 AWG
606.0 ft
2 per phase
PNL HF
0.09 Cal/cm^2
5.787 kA
4 inches
480.0 V
CBL-PNL HG
2/0 AWG
831.0 ft
2 per phase
PNL HG
0.13 Cal/cm^2
4.584 kA
4 inches
480.0 V
S
P
T-PNL LB
75 kVA
5.0000 %
480 V
208 V
CBL-PNL LB
4/0 AWG
15.0 ft
1 per phase
CB-T-PNL LB
SQUARE D
ED
Sensor/Trip 100.0 A
Plug 100.0 A
Settings
Fixed
InterruptingRating 18.0 kA
CBL-T-PNL LB
2 AWG
15.0 ft
1 per phase
MCB-PNL LB
SQUARE D
QB
Sensor/Trip 225.0 A
Plug 225.0 A
Settings
Fixed
InterruptingRating 10.0 kA
PNL LB
6.07 Cal/cm^2
3.384 kA
50 inches
208.0 V
S
P
T-PNL LE
75 kVA
5.0000 %
480 V
208 V
CBL-PNL LE
4/0 AWG
15.0 ft
1 per phase
CB-T-PNL LE
SQUARE D
ED
Sensor/Trip 100.0 A
Plug 100.0 A
Settings
Fixed
InterruptingRating 18.0 kA
CBL-T-PNL LE
2 AWG
15.0 ft
1 per phase
MCB-PNL LE
SQUARE D
QB
Sensor/Trip 225.0 A
Plug 225.0 A
Settings
Fixed
InterruptingRating 10.0 kA
PNL LE
5.42 Cal/cm^2
3.069 kA
46 inches
208.0 V
S
P
T-PNL LF
75 kVA
5.0000 %
480 V
208 V
CBL-PNL LF
4/0 AWG
15.0 ft
1 per phase
CB-T-PNL LF
SQUARE D
ED
Sensor/Trip 100.0 A
Plug 100.0 A
Settings
Fixed
InterruptingRating 18.0 kA
CBL-T-PNL LF
2 AWG
15.0 ft
1 per phase
MCB-PNL LF
SQUARE D
QB
Sensor/Trip 225.0 A
Plug 225.0 A
Settings
Fixed
InterruptingRating 10.0 kA
PNL LF
5.54 Cal/cm^2
3.125 kA
47 inches
208.0 V
S
P
T-PNL LG
75 kVA
5.0000 %
480 V
208 V
CBL-PNL LG
4/0 AWG
15.0 ft
1 per phase
CB-T-PNL LG
SQUARE D
ED
Sensor/Trip 100.0 A
Plug 100.0 A
Settings
Fixed
InterruptingRating 18.0 kA
CBL-T-PNL LG
2 AWG
15.0 ft
1 per phase
MCB-PNL LG
SQUARE D
QB
Sensor/Trip 225.0 A
Plug 225.0 A
Settings
Fixed
InterruptingRating 10.0 kA
PNL LG
5.23 Cal/cm^2
2.972 kA
45 inches
208.0 V
CB-PNL LB1
SQUARE D
QOB
Sensor/Trip 100.0 A
Plug 100.0 A
Settings
Fixed (730-7, 100A)
InterruptingRating 10.0 kA
CBL-PNL LB1
2 AWG
8.0 ft
1 per phase
PNL LB1
4.67 Cal/cm^2
3.286 kA
42 inches
208.0 V
CB-DS-CP-DD NORTH 1
SQUARE D
ED
Sensor/Trip 15.0 A
Plug 15.0 A
Settings
Fixed
InterruptingRating 18.0 kA
CBL-DS-CP-DD NORTH 1
10 AWG
86.0 ft
1 per phase
DS-CP-DD NORTH 1
0.05 Cal/cm^2
1.950 kA
2 inches
480.0 V
CBL-CP-DD NORTH 1
10 AWG
15.0 ft
1 per phase
CP-DD NORTH 1
0.02 Cal/cm^2
1.737 kA
1 inches
480.0 V
F-DS-CP-DD NORTH 1
BUSSMANN
FRS-R
Sensor/Trip 15.0 A
InterruptingRating 200.0 kA
CB-DS-CP-DD NORTH 2
SQUARE D
ED
Sensor/Trip 15.0 A
Plug 15.0 A
Settings
Fixed
InterruptingRating 18.0 kA
CBL-DS-CP-DD NORTH 2
10 AWG
110.0 ft
1 per phase
DS-CP-DD NORTH 2
0.04 Cal/cm^2
1.630 kA
2 inches
480.0 V
CBL-CP-DD NORTH 2
10 AWG
15.0 ft
1 per phase
CP-DD NORTH 2
0.02 Cal/cm^2
1.478 kA
1 inches
480.0 V
F-DS-CP-DD NORTH 2
BUSSMANN
FRS-R
Sensor/Trip 15.0 A
InterruptingRating 200.0 kA
CB-DS-CP-DD NORTH 3
SQUARE D
ED
Sensor/Trip 15.0 A
Plug 15.0 A
Settings
Fixed
InterruptingRating 18.0 kA
CBL-DS-CP-DD NORTH 3
10 AWG
97.0 ft
1 per phase
DS-CP-DD NORTH 3
0.04 Cal/cm^2
1.654 kA
2 inches
480.0 V
CBL-CP-DD NORTH 3
10 AWG
15.0 ft
1 per phase
CP-DD NORTH 3
0.02 Cal/cm^2
1.498 kA
1 inches
480.0 V
F-DS-CP-DD NORTH 3
BUSSMANN
FRS-R
Sensor/Trip 15.0 A
InterruptingRating 200.0 kA
CB-DS-CP-DD NORTH 4
SQUARE D
ED
Sensor/Trip 15.0 A
Plug 15.0 A
Settings
Fixed
InterruptingRating 18.0 kA
CBL-DS-CP-DD NORTH 4
10 AWG
120.0 ft
1 per phase
DS-CP-DD NORTH 4
0.03 Cal/cm^2
1.427 kA
2 inches
480.0 V
CBL-CP-DD NORTH 4
10 AWG
15.0 ft
1 per phase
CP-DD NORTH 4
0.02 Cal/cm^2
1.309 kA
1 inches
480.0 V
F-DS-CP-DD NORTH 4
BUSSMANN
FRS-R
Sensor/Trip 15.0 A
InterruptingRating 200.0 kA
CB-TERM-EF9/10
SQUARE D
ED
Sensor/Trip 20.0 A
Plug 20.0 A
Settings
Fixed
InterruptingRating 18.0 kA
CBL-TERM-EF9/10
10 AWG
170.0 ft
1 per phase
CBL-DS-EF-9
10 AWG
2.0 ft
1 per phase
DS-EF-9
0.03 Cal/cm^2
1.248 kA
2 inches
480.0 V
CBL-DS-EF-10
10 AWG
52.0 ft
1 per phase
DS-EF-10
0.15 Cal/cm^2
0.986 kA
5 inches
480.0 V
CB-TERM-EF13/14
SQUARE D
ED
Sensor/Trip 15.0 A
Plug 15.0 A
Settings
Fixed
InterruptingRating 18.0 kA
CBL-TERM-EF13/14
10 AWG
260.0 ft
1 per phase
CBL-DS-EF-13
10 AWG
125.0 ft
1 per phase
DS-EF-13
0.15 Cal/cm^2
0.560 kA
5 inches
480.0 V
CBL-DS-EF-14
10 AWG
10.0 ft
1 per phase
DS-EF-14
0.11 Cal/cm^2
0.772 kA
4 inches
480.0 V
CB-HG-DS-SF-3
SQUARE D
ED
Sensor/Trip 15.0 A
Plug 15.0 A
Settings
Fixed
InterruptingRating 18.0 kA
CBL-HG-DS-SF-3
10 AWG
280.0 ft
1 per phase
HG-DS-SF-3
0.11 Cal/cm^2
0.726 kA
4 inches
480.0 V
CB-HF-DS-SF-1
SQUARE D
ED
Sensor/Trip 15.0 A
Plug 15.0 A
Settings
Fixed
InterruptingRating 18.0 kA
CBL-HF-DS-SF-1
10 AWG
280.0 ft
1 per phase
HF-DS-SF-1
0.11 Cal/cm^2
0.750 kA
4 inches
480.0 V
CB-DS-CF-D20
SQUARE D
ED
Sensor/Trip 15.0 A
Plug 15.0 A
Settings
Fixed
InterruptingRating 18.0 kA
CBL-DS-CF-D20
10 AWG
265.0 ft
1 per phase
DS-CF-D20
0.11 Cal/cm^2
0.787 kA
4 inches
480.0 V
CB-DS-CF-B20
SQUARE D
ED
Sensor/Trip 15.0 A
Plug 15.0 A
Settings
Fixed
InterruptingRating 18.0 kA
CBL-DS-CF-B20
10 AWG
200.0 ft
1 per phase
DS-CF-B20
0.08 Cal/cm^2
1.006 kA
3 inches
480.0 V
CB-DS-CF-B17
SQUARE D
ED
Sensor/Trip 15.0 A
Plug 15.0 A
Settings
Fixed
InterruptingRating 18.0 kA
CBL-DS-CF-B17
10 AWG
135.0 ft
1 per phase
DS-CF-B17
0.03 Cal/cm^2
1.391 kA
2 inches
480.0 V
CB-DS-CF-B24
SQUARE D
ED
Sensor/Trip 15.0 A
Plug 15.0 A
Settings
Fixed
InterruptingRating 18.0 kA
CBL-DS-CF-B24
10 AWG
210.0 ft
1 per phase
DS-CF-B24
0.09 Cal/cm^2
0.925 kA
4 inches
480.0 V
FROM E.603.AF
FROM E.603.AF FROM E.603.AF
E.604.AF
Uninterruptible
Power Supply (UPS)
Bus - Panel (PNL), Switchboard
(SWBD), Disconnect Switch (DS),
or Control Panel (CP)
Auto/Manual Transfer Switch
(ATS/MTS)
Utility
Motor (M)
Fuse (F)
E N
Receptacle (R)
Transformer (T)
Generator
(GEN)
(Main) Circuit Breaker
(MCB, CB)
Capacitor Bank (C)
Utility MeterWH
Bus Duct (BD)
Battery (BAT)
Rectifier (REC)
Switch (SW)
Fuse Switch (FS)
1. NOT TO BE USED FOR CONSTRUCTION PURPOSES
2. THIS DRAWING WAS CREATED FROM FIELD
NOTES TAKEN FROM THE SITE SURVEY ON
THE DATE SHOWN IN THE DESCRIPTION BOX
BELOW
3. ELECTRICAL DETAILS HAVE BEEN
DOCUMENTED WHERE INFORMATION
HAS BEEN VERIFIED WITH A SURVEY AND MAY BE A
COMBINATION OF THE FOLLOWING:
• EQUIPMENT NAMEPLATES
• EXISTING EQUIPMENT LABELING
• EXISTING ELECTRICAL SITE DRAWINGS
Legend
Load (L)
(Main) Medium Voltage Circuit
Breaker (MCB, CB)
Relay (RLY)
C:\Users\Jeff Lunsford\Desktop\arc_flash_report\amazonlogo.jpg
515 E Dyer Rd -
2017714908/25/22
SOW
SHUT DOWN POWER TO BUILDING WITH
UTILITY COMPANY
INSTALLATION OF ARC FLASH
RELAYS/CONNECT RELAY
REMOVE PANELS TO SWITCH GEAR
DUST AND VACUUM SWITCH GEAR
REMOVE UNWANTED DEBRIS
LOOP FIBRE INSIDE OF THE GEAR
INSTALL IR SCANNING WINDOWS PER FLUKE
SPECS INTO SWITCH GEAR COVERS
TEST BUS AND BREAKERS (MEGGER AND LOW
VOLTAGE INJECTION TESTING)
CHECK TORQUE ON BOLTS
REINSTALL COVERS
REENERGIZE BUILDING AND SWITCH GEAR
515 E Dyer Rd -
2017714908/25/22