HomeMy WebLinkAbout610 E Santa Clara Ave - PlanExpedited Permit Process for PV Systems 1 Expedited Permit Process for PV Systems Standard String System The Solar America Board for Codes and Standards (Solar ABCs) Expedited Permit Pro- cess provides a means to differentiate systems that can be permitted quickly and easily due to their similarity with the majority of small-scale PV systems. Those systems with unique characteristics may be handled with small additions to this Expedited Permit Process or may require much more information, depending on the uniqueness of the installation. The following pages contain forms for the Standard String System to use with the Expe- dited Permit Process. The Micro-Inverter, AC Module, and Supply-Side Connection forms are also available as interactive PDF files at www.solarabcs.org/permitting. In jurisdic- tions that have adopted the Expedited Permit Process for PV Systems, these forms can be filled out electronically and submitted in either printed form and via email. An elec- tronic format is used so that the supplied information is standardized and legible for the local jurisdiction. 610 E Santa Clara Ave11/21/2023 Expedited Permit Process for PV Systems 2 Expedited Permit Process for Small-Scale PV Systems Standard String System The information in this guideline is intended to help local jurisdictions and contractors identify when PV system installations are simple, needing only a basic review, and when an installation is more complex. It is likely that 50%-75% of all residential systems will comply with these simple criteria. For projects that fail to meet the simple criteria, resolution steps have been suggested to provide as a path to permit approval. Required Information for Permit: 1. Site plan showing location of major components on the property. This drawing need not be exactly to scale, but it should represent relative location of components at site (see supplied example site plan). PV arrays on dwellings with a 3’ perimeter space at ridge and sides may not need separate fire service review. 2. Electrical diagram showing PV array configuration, wiring system, overcurrent protection, inverter, disconnects, required signs, and ac connection to building (see supplied standard electrical diagram). 3. Specification sheets and installation manuals (if available) for all manufactured components including, but not limited to, PV modules, inverter(s), combiner box, disconnects, and mounting system. Step 1: Structural Review of PV Array Mounting System Is the array to be mounted on a defined, permitted roof structure? l Yes l No If No due to non-compliant roof or a ground mount, submit completed worksheet for the structure WKS1. Roof Information: 1. Is the roofing type lightweight (Yes = composition, lightweight masonry, metal, etc…)__________________________ ____________________________________________________________________________________________________ If No, submit completed worksheet for roof structure WKS1 (No = heavy masonry, slate, etc…). 2. Does the roof have a single roof covering? l Yes l No If No, submit completed worksheet for roof structure WKS1. 3. Provide method and type of weatherproofing roof penetrations (e.g. flashing, caulk).____________________________ Mounting System Information: 1. Is the mounting structure an engineered product designed to mount PV modules with no more than an 18” gap beneath the module frames? l Yes l No If No, provide details of structural attachment certified by a design professional. 2. For manufactured mounting systems, fill out information on the mounting system below: a. Mounting System Manufacturer ___________Product Name and Model#________________________________ b. Total Weight of PV Modules and Rails ___________lbs c. Total Number of Attachment Points____________ d. Weight per Attachment Point (b÷c)_________________lbs (if greater than 45 lbs, see WKS1) e. Maximum Spacing Between Attachment Points on a Rail ______________inches (see product manual for maximum spacing allowed based on maximum design wind speed) f. Total Surface Area of PV Modules (square feet)_________________ ft2 g. Distributed Weight of PV Module on Roof (b÷f)_______________ lbs/ft2 If distributed weight of the PV system is greater than 5 lbs/ft2, see WKS1. Step 2: Electrical Review of PV System (Calculations for Electrical Diagram) In order for a PV system to be considered for an expedited permit process, the following must apply: 1. PV modules, utility-interactive inverters, and combiner boxes are identified for use in PV systems. 2. The PV array is composed of 4 series strings or less per inverter. 3. The total inverter capacity has a continuous ac power output 13,440 Watts or less 4. The ac interconnection point is on the load side of service disconnecting means (690.64(B)). 5. One of the standard electrical diagrams (E1.1, E1.1a, E1.1b, or E1.1c) can be used to accurately represent the PV system. Interactive PDF diagrams are available at www.solarabcs.org/permitting. Fill out the standard electrical diagram completely. A guide to the electrical diagram is provided to help the applicant understand each blank to fill in. If the electrical system is more complex than the standard electrical diagram can effectively communicate, provide an alternative diagram with appropriate detail. 610 E Santa Clara Ave11/21/2023 E x p e d i t e d P e r m i t P r o c e s s f o r P V S y s t e m s 3 Standard String System Site Plan               610 E Santa Clara Ave11/21/2023 E x p e d i t e d P e r m i t P r o c e s s f o r P V S y s t e m s 4 Standard String System Electrical Diagram                                                                                                            610 E Santa Clara Ave11/21/2023 E x p e d i t e d P e r m i t P r o c e s s f o r P V S y s t e m s 5 Notes for Standard String System Electrical Diagram Contractor Name, Address and Phone: _________________ _________________ _________________ _________________ Notes for One-Line Standard Electrical Diagram for Single-Phase PV Systems Site Name: __________________________ Site Address: ________________________ System AC Size: ______________________ SIZE FSCM NO DWG NO REV SCALE NTS Date:SHEET Drawn By: Checked By: MAX POWER-POINT CURRENT (IMP) MAX POWER-POINT VOLTAGE (VMP) OPEN-CIRCUIT VOLTAGE (VOC) SHORT-CIRCUIT CURRENT (ISC) MAX SERIES FUSE (OCPD) MAXIMUM POWER (PMAX) MAX VOLTAGE (TYP 600VDC) VOC TEMP COEFF (mV/oC or %/oC ) IF COEFF SUPPLIED, CIRCLE UNITS A V V A A W V MODULE MAKE MODULE MODEL PV MODULE RATINGS @ STC (Guide Section 5) MAX DC VOLT RATING MAX POWER @ 40oC NOMINAL AC VOLTAGE MAX AC CURRENT MAX OCPD RATING V W V A A INVERTER MAKE INVERTER MODEL INVERTER RATINGS (Guide Section 4) 1) IF UTILITY REQUIRES A VISIBLE-BREAK SWITCH, DOES THIS SWITCH MEET THEREQUIREMENT? YES NO N/A 2) IF GENERATION METER REQUIRED, DOES THIS METER SOCKET MEET THEREQUIREMENT? YES NO N/A 3) SIZE PHOTOVOLTAIC POWER SOURCE (DC) CONDUCTORS BASED ON MAXCURRENT ON NEC 690.53 SIGN OR OCPD RATING AT DISCONNECT 4) SIZE INVERTER OUTPUT CIRCUIT (AC) CONDUCTORS ACCORDING TO INVERTEROCPD AMPERE RATING. (See Guide Section 9) 5) TOTAL OF ______ INVERTER OCPD(s), ONE FOR EACH INVERTER. DOES TOTALSUPPLY BREAKERS COMPLY WITH 120% BUSBAR EXCEPTION IN 690.64(B)(2)(a)?YES NO NOTES FOR INVERTER CIRCUITS (Guide Section 8 and 9): 1.) LOWEST EXPECT AMBIENT TEMPERATURE BASED ON ASHRAE MINIMUM MEANEXTREME DRY BULB TEMPERATURE FOR ASHRAE LOCATION MOST SIMILAR TOINSTALLATION LOCATION. LOWEST EXPECTED AMBIENT TEMP ______oC 2.) HIGHEST CONTINUOUS AMBIENT TEMPERATURE BASED ON ASHRAE HIGHESTMONTH 2% DRY BULB TEMPERATURE FOR ASHRAE LOCATION MOST SIMILAR TOINSTALLATION LOCATION. HIGHEST CONTINUOUS TEMPERATURE _____oC 2.) 2005 ASHRAE FUNDEMENTALS 2% DESIGN TEMPERATURES DO NOT EXCEED47oC IN THE UNITED STATES (PALM SPRINGS, CA IS 44.1oC). FOR LESS THAN 9CURRENT-CARRYING CONDUCTORS IN ROOF-MOUNTED SUNLIT CONDUIT ATLEAST 0.5" ABOVE ROOF AND USING THE OUTDOOR DESIGN TEMPERATURE OF47oC OR LESS (ALL OF UNITED STATES), a) 12 AWG, 90oC CONDUCTORS ARE GENERALLY ACCEPTABLE FOR MODULESWITH Isc OF 7.68 AMPS OR LESS WHEN PROTECTED BY A 12-AMP OR SMALLERFUSE. b) 10 AWG, 90oC CONDUCTORS ARE GENERALLY ACCEPTABLE FOR MODULESWITH Isc OF 9.6 AMPS OR LESS WHEN PROTECTED BY A 15-AMP OR SMALLERFUSE. NOTES FOR ARRAY CIRCUIT WIRING (Guide Section 6 and 8 and Appendix D): OCPD = OVERCURRENT PROTECTION DEVICE NATIONAL ELECTRICAL CODE® REFERENCES SHOWN AS (NEC XXX.XX) NOTES FOR ALL DRAWINGS: SIGNS–SEE GUIDE SECTION 7 SIGN FOR DC DISCONNECT SIGN FOR INVERTER OCPD AND AC DISCONNECT (IF USED) RATED MPP CURRENT RATED MPP VOLTAGE MAX SYSTEM VOLTAGE MAX CIRCUIT CURRENT A V V A PHOTOVOLTAIC POWER SOURCE WARNING: ELECTRICAL SHOCK HAZARD–LINE AND LOAD MAY BE ENERGIZED IN OPEN POSITION AC OUTPUT CURRENT NOMINAL AC VOLTAGE A V SOLAR PV SYSTEM AC POINT OF CONNECTION THIS PANEL FED BY MULTIPLE SOURCES (UTILITY AND SOLAR) 610 E Santa Clara Ave11/21/2023 REV SHEET NAME SHEET SIZE SHEET NUMBER DO U G R I S K 61 0 E S A N T A C L A R A A V E , SA N T A A N A , C A 9 2 7 0 6 , U S A ANSI B 11" X 17" DATE DESCRIPTION REVISIONS Signature with Seal PROJECT NAME & ADDRESS PV-1 CONTRACTOR NAME CONTRACTOR INFORMATION 8001 CANOGA AVE #B CANOGA PARK, CA 91304 PHONE: 1(818) 564-4820 COASTAL BUILDERS 610 E. SANTA CLARA AVE. SANTA ANA, CA 92706 (714) 234-9160 CALIFORNIA LIC# 623480- B COVER SHEET SCOPE OF WORK SYSTEM SIZE: 7.04KW CEC AC: 6.53KW MODULES: (22) HANWHA Q.CELLS: Q.PEAK DUO BLK-G5 320W MODULES MODULE MAX POWER (P/MAX): 320W INVERTER: (1) SOLAREDGE SE7600H-US000BNU4 INVERTER OPTIMIZER: (22) SOLAREDGE POWER OPTIMIZER P320 RACKING: IRONRIDGE XR10 RAIL ATTACHMENT: UNIRAC UNIVERSAL TILE HOOK VICINITY MAP BUILDING INFORMATION: TWO STORY HOUSE TYPE OF CONSTRUCTION: V-B OCCUPANCY: RESIDENTIAL GROUP R - 3 APN# 00313203 ROOF TYPE: S-TILE RAFTERS: 2"X4" @ 24" O.C. ELECTRICAL INFORMATION UTILITY COMPANY: SCE MAIN SERVICE AMPERAGE: 200A ARRAY TILT UP: #1 - 27° ARRAY AZIMUTH: #1 - 90° TABLE OF CONTENTS PAGE #DESCRIPTION PV 1 COVER SHEET PV 2 SITE PLAN PV 3 ARRAY DETAIL PV 4 STRING LAYOUT PV 5-6 ATTACHMENT DETAIL PV 7 ELECTRICAL DIAGRAM PV 8 ELECTRICAL CALCULATION PV 9 PLACARD PV 10 OPTIMIZER CHART PV 11+SPEC SHEETS THIS PROJECT SHALL COMPLY WITH THE FOLLOWING CODE 2019 CALIFORNIA ELECTRICAL CODE 2019 CALIFORNIA RESIDENTIAL CODE 2019 CALIFORNIA BUILDING CODE 2019 CALIFORNIA GREEN BUILDING STANDARDS CODE 2019 CALIFORNIA ENERGY CODE 2019 CALIFORNIA PLUMBING CODE 2019 CALIFORNIA MECHANICAL CODE 2019 NATIONAL ELECTRICAL CODE ALL OTHER ORDINANCES ADOPTED BY THE LOCAL GOVERNING AGENCIES. CODE SUMMARY GENERAL NOTES: · LOCAL UTILITY PROVIDER SHALL BE NOTIFIED PRIOR TO USE AND ACTIVATION OF ANY SOLAR PHOTOVOLTAIC INSTALLATION. ·THIS PROJECT SHALL COMPLY WITH LOCAL ORDINANCES ·PROPER ACCESS AND WORKING CLEARANCE WILL BE PROVIDED ·ALL ELECTRICAL WORK SHOWN ON THESE PLANS WILL BE COMPLETED BY THE UNDERSIGNED ·ALL APPLICABLE PV EQUIPMENT LISTED AND COMPLIANT WITH UL2703, UL1741 AND UL1703 ·ALL ROOF PENETRATIONS TO BE SEALED WITH A HIGH PERFORMANCE ROOF SEALANT SUCH AS GeoCel 2300 CLEAR SEALANT ·THE SYSTEM WILL NOT BE INTERCONNECTED UNTIL APPROVAL FROM THE LOCAL JURISDICTION AND THE UTILITY IS OBTAINED ·THE SOLAR PHOTOVOLTAIC INSTALLATION SHALL NOT OBSTRUCT ANY PLUMBING, MECHANICAL, OR BUILDING ROOF VENTS ·IF THE EXISTING MAIN PANEL DOES NOT HAVE VERIFIABLE GROUNDING ELECTRODE, IT IS THE NECESSARY TO INSTALL A SUPPLEMENTAL GROUNDING ELECTRODE ·EACH MODULE WILL BE GROUNDED UL 2703 OR UL 1703 APPROVED USING THE SUPPLIED CONNECTION POINTS IDENTIFIED ON THE MODULE AND THE MANUFACTURER'S INSTALLATION INSTRUCTIONS" ·A LADDER SHALL BE IN PLACE FOR THE INSPECTION IN COMPLIANCE WITH CAL-OSHA REGULATIONS ·PHOTOVOLTAIC SYSTEM INVERTER IS UNGROUNDED. NO CONDUCTORS ARE SOLIDLY GROUNDED IN THE INVERTER, AND SYSTEM COMPLIES WITH 690.35. ·MODULES CONFORM TO AND ARE LISTED UNDER UL 1703. ·INVERTER CONFORMS TO AND IS LISTED UNDER UL 1741. ·ELECTRICAL EQUIPMENT AND MATERIAL TO BE LISTED, LABELED, AND INSTALLED PER THE NEC, THE INSTALLATION STANDARDS/MANUFACTURER'S RECOMMENDATIONS AND IF REQUIRED A RECOGNIZED ELECTRICAL TESTING LABORATORY. ·CONDUITS EXPOSED TO SUNLIGHT ON ROOF SHALL BE LOCATED NOT LESS THAN 7/8" ABOVE ROOF SURFACE. NEC 310.15(B)(3)(c) ·THIS PROJECT HAS BEEN DESIGNED IN COMPLIANCE WITH THE CBC SECTION 1609 TO WITHSTAND A MINIMUM 110 MPH WIND LOAD. Permit # 101108446 & 20174666 Issued 11/02/2021 610 E Santa Clara Ave11/09/21 IN V MS P UM AC D REV SHEET NAME SHEET SIZE SHEET NUMBER DO U G R I S K 61 0 E S A N T A C L A R A A V E , SA N T A A N A , C A 9 2 7 0 6 , U S A ANSI B 11" X 17" DATE DESCRIPTION REVISIONS Signature with Seal PROJECT NAME & ADDRESS PV-10 CONTRACTOR NAME CONTRACTOR INFORMATION 8001 CANOGA AVE #B CANOGA PARK, CA 91304 PHONE: 1(818) 564-4820 COASTAL BUILDERS 610 E. SANTA CLARA AVE. SANTA ANA, CA 92706 (714) 234-9160 CALIFORNIA LIC# 623480- B OPTIMIZER CHART 610 E Santa Clara Ave11/09/21 REV SHEET NAME SHEET SIZE SHEET NUMBER DO U G R I S K 61 0 E S A N T A C L A R A A V E , SA N T A A N A , C A 9 2 7 0 6 , U S A ANSI B 11" X 17" DATE DESCRIPTION REVISIONS Signature with Seal PROJECT NAME & ADDRESS PV-11 CONTRACTOR NAME CONTRACTOR INFORMATION 8001 CANOGA AVE #B CANOGA PARK, CA 91304 PHONE: 1(818) 564-4820 COASTAL BUILDERS 610 E. SANTA CLARA AVE. SANTA ANA, CA 92706 (714) 234-9160 CALIFORNIA LIC# 623480- B SPECS SHEET 610 E Santa Clara Ave11/09/21 REV SHEET NAME SHEET SIZE SHEET NUMBER DO U G R I S K 61 0 E S A N T A C L A R A A V E , SA N T A A N A , C A 9 2 7 0 6 , U S A ANSI B 11" X 17" DATE DESCRIPTION REVISIONS Signature with Seal PROJECT NAME & ADDRESS PV-12 CONTRACTOR NAME CONTRACTOR INFORMATION 8001 CANOGA AVE #B CANOGA PARK, CA 91304 PHONE: 1(818) 564-4820 COASTAL BUILDERS 610 E. SANTA CLARA AVE. SANTA ANA, CA 92706 (714) 234-9160 CALIFORNIA LIC# 623480- B SPECS SHEET 610 E Santa Clara Ave11/09/21 REV SHEET NAME SHEET SIZE SHEET NUMBER DO U G R I S K 61 0 E S A N T A C L A R A A V E , SA N T A A N A , C A 9 2 7 0 6 , U S A ANSI B 11" X 17" DATE DESCRIPTION REVISIONS Signature with Seal PROJECT NAME & ADDRESS PV-13 CONTRACTOR NAME CONTRACTOR INFORMATION 8001 CANOGA AVE #B CANOGA PARK, CA 91304 PHONE: 1(818) 564-4820 COASTAL BUILDERS 610 E. SANTA CLARA AVE. SANTA ANA, CA 92706 (714) 234-9160 CALIFORNIA LIC# 623480- B SPECS SHEET 610 E Santa Clara Ave11/09/21 REV SHEET NAME SHEET SIZE SHEET NUMBER DO U G R I S K 61 0 E S A N T A C L A R A A V E , SA N T A A N A , C A 9 2 7 0 6 , U S A ANSI B 11" X 17" DATE DESCRIPTION REVISIONS Signature with Seal PROJECT NAME & ADDRESS PV-14 CONTRACTOR NAME CONTRACTOR INFORMATION 8001 CANOGA AVE #B CANOGA PARK, CA 91304 PHONE: 1(818) 564-4820 COASTAL BUILDERS 610 E. SANTA CLARA AVE. SANTA ANA, CA 92706 (714) 234-9160 CALIFORNIA LIC# 623480- B SPECS SHEET 610 E Santa Clara Ave11/09/21 REV SHEET NAME SHEET SIZE SHEET NUMBER DO U G R I S K 61 0 E S A N T A C L A R A A V E , SA N T A A N A , C A 9 2 7 0 6 , U S A ANSI B 11" X 17" DATE DESCRIPTION REVISIONS Signature with Seal PROJECT NAME & ADDRESS PV-15 CONTRACTOR NAME CONTRACTOR INFORMATION 8001 CANOGA AVE #B CANOGA PARK, CA 91304 PHONE: 1(818) 564-4820 COASTAL BUILDERS 610 E. SANTA CLARA AVE. SANTA ANA, CA 92706 (714) 234-9160 CALIFORNIA LIC# 623480- B SPECS SHEET 610 E Santa Clara Ave11/09/21 REV SHEET NAME SHEET SIZE SHEET NUMBER DO U G R I S K 61 0 E S A N T A C L A R A A V E , SA N T A A N A , C A 9 2 7 0 6 , U S A ANSI B 11" X 17" DATE DESCRIPTION REVISIONS Signature with Seal PROJECT NAME & ADDRESS PV-16 CONTRACTOR NAME CONTRACTOR INFORMATION 8001 CANOGA AVE #B CANOGA PARK, CA 91304 PHONE: 1(818) 564-4820 COASTAL BUILDERS 610 E. SANTA CLARA AVE. SANTA ANA, CA 92706 (714) 234-9160 CALIFORNIA LIC# 623480- B SPECS SHEET 610 E Santa Clara Ave11/09/21 REV SHEET NAME SHEET SIZE SHEET NUMBER DO U G R I S K 61 0 E S A N T A C L A R A A V E , SA N T A A N A , C A 9 2 7 0 6 , U S A ANSI B 11" X 17" DATE DESCRIPTION REVISIONS Signature with Seal PROJECT NAME & ADDRESS PV-17 CONTRACTOR NAME CONTRACTOR INFORMATION 8001 CANOGA AVE #B CANOGA PARK, CA 91304 PHONE: 1(818) 564-4820 COASTAL BUILDERS 610 E. SANTA CLARA AVE. SANTA ANA, CA 92706 (714) 234-9160 CALIFORNIA LIC# 623480- B SPECS SHEET 610 E Santa Clara Ave11/09/21 REV SHEET NAME SHEET SIZE SHEET NUMBER DO U G R I S K 61 0 E S A N T A C L A R A A V E , SA N T A A N A , C A 9 2 7 0 6 , U S A ANSI B 11" X 17" DATE DESCRIPTION REVISIONS Signature with Seal PROJECT NAME & ADDRESS PV-18 CONTRACTOR NAME CONTRACTOR INFORMATION 8001 CANOGA AVE #B CANOGA PARK, CA 91304 PHONE: 1(818) 564-4820 COASTAL BUILDERS 610 E. SANTA CLARA AVE. SANTA ANA, CA 92706 (714) 234-9160 CALIFORNIA LIC# 623480- B SPECS SHEET 610 E Santa Clara Ave11/09/21 REV SHEET NAME SHEET SIZE SHEET NUMBER DO U G R I S K 61 0 E S A N T A C L A R A A V E , SA N T A A N A , C A 9 2 7 0 6 , U S A ANSI B 11" X 17" DATE DESCRIPTION REVISIONS Signature with Seal PROJECT NAME & ADDRESS PV-19 CONTRACTOR NAME CONTRACTOR INFORMATION 8001 CANOGA AVE #B CANOGA PARK, CA 91304 PHONE: 1(818) 564-4820 COASTAL BUILDERS 610 E. SANTA CLARA AVE. SANTA ANA, CA 92706 (714) 234-9160 CALIFORNIA LIC# 623480- B SPECS SHEET 610 E Santa Clara Ave11/09/21 INV MSP UM ACD JB 52 ' - 0 " 52 ' - 0 " 121'-9" 121'-9" SITE PLAN REV SHEET NAME SHEET SIZE SHEET NUMBER DO U G R I S K 61 0 E S A N T A C L A R A A V E , SA N T A A N A , C A 9 2 7 0 6 , U S A ANSI B 11" X 17" DATE DESCRIPTION REVISIONS Signature with Seal PROJECT NAME & ADDRESS PV-2 CONTRACTOR NAME CONTRACTOR INFORMATION 8001 CANOGA AVE #B CANOGA PARK, CA 91304 PHONE: 1(818) 564-4820 COASTAL BUILDERS 610 E. SANTA CLARA AVE. SANTA ANA, CA 92706 (714) 234-9160 CALIFORNIA LIC# 623480- B SITE PLAN: SCALE:- 3/32" = 1'-0" LEGEND MAIN SERVICE PANEL METER JUNCTION BOX AC DISCONNECT ARRAY ARRAY TILT UP AZIMUTH SOLAR AREA (SQFT) SOLAR LOAD (LBS) ROOF AREA (SQFT) ROOF AREA COVERED BY SOLAR # MODULES #1 27°90° 399.08 906.4 969.50 41.16% 22 ROOF ACCESS POINT (E) MAIN SERVICE PANEL, 200A RATED, 240V (N) JUNCTION BOX ON ROOF (E) UTILITY METER (N) 60A PV SYSTEM AC DISCONNECT (N) SOLAREDGE SE7600H-US000BNU4 INVERTER FIRE SETBACK (36" TYP.) UM MSP ACD JB INV INVERTER 3/4" EMT CONDUIT RUN MIN. 7/8" ABOVE ROOF MODULE TYPE, DIMENSIONS & WEIGHT NUMBER OF MODULES = 22 MODULES MODULE TYPE = HANWHA Q.CELLS Q.PEAK DUO BLK-G5 320W MODULES MODULE WEIGHT = 41.2 LBS / 18.7 KG. MODULE DIMENSIONS = 66.3"x 39.4" = 18.14 SF UNIT WEIGHT OF ARRAY = 2.27 PSF (E) 2-STORY RESIDENCEE S A N T A C L A R A A V E EXISTING DRIVEWAY ARRAY #1 (22) HANWHA Q.CELLS Q.PEAK DUO BLK-G5 320W MODULES (E) POOL PROPERTY LINE PR O P E R T Y L I N E PROPERTY LINE PR O P E R T Y L I N E STRUCTURE 610 E Santa Clara Ave11/09/21 REV SHEET NAME SHEET SIZE SHEET NUMBER DO U G R I S K 61 0 E S A N T A C L A R A A V E , SA N T A A N A , C A 9 2 7 0 6 , U S A ANSI B 11" X 17" DATE DESCRIPTION REVISIONS Signature with Seal PROJECT NAME & ADDRESS PV-3 CONTRACTOR NAME CONTRACTOR INFORMATION 8001 CANOGA AVE #B CANOGA PARK, CA 91304 PHONE: 1(818) 564-4820 COASTAL BUILDERS 610 E. SANTA CLARA AVE. SANTA ANA, CA 92706 (714) 234-9160 CALIFORNIA LIC# 623480- B ARRAY DETAIL # MODULES PER ARRAY ROOF TYPE ATTACHMENT ROOF HEIGHT FRAME MATERIAL FRAME TYPE FRAME SIZE OC SPACING AR-01 22 S-TILE UNIRAC UNIVERSAL TILE HOOK 2 STORY WOOD RAFTERS 2" X 4" 24"O.C. AR-01 - SCALE:3/16" = 1'-0" PITCH: 27° AZIMUTH: 90° LOAD CALCULATION ITEM #OR LIN FT WEIGHT PER (lbs) TOTAL WEIGHT (lbs) MODULES 22 41.2 906.40 RAILS 228.05 0.4 99.4 ATTACHMENTS 44 0.65 28.60 TILT LEGS 0 3.5 0 OPTIMIZER 22 1.4 30.4 TOTAL WEIGHT 1064.8 WEIGHT PER MOUNT 1064.8 / 44 = 24.2 lbs/Mount lbs MODULES: 22 MAX DISTRIBUTED LOAD: 3 PSF SNOW LOAD: 0 PSF WIND SPEED: 110 MPH 3-SEC GUST. LAG SCREWS: 5/16"x 2.5" MIN EMBEDMENT NOTE: INSTALLERS TO VERIFY RAFTER SIZE, SPACING AND SLOPED SPANS, AND NOTIFY E.O.R. OF ANY DISCREPANCIES BEFORE PROCEEDING. DESIGN CRITERIA (N) IRONRIDGE XR10 RAIL RACKING SYSTEM UNIRAC UNIVERSAL TILE HOOK ATTACHMENT @ 48" O.C. (N) 22-SOLAREDGE POWER OPTIMIZER P320 3' 3' 29'-11" 3' 16'-9" 2"x4" RAFTERS @ 24" OC 4' MAX. 3'-11" 610 E Santa Clara Ave11/09/21 INV MSP UM ACD JB REV SHEET NAME SHEET SIZE SHEET NUMBER DO U G R I S K 61 0 E S A N T A C L A R A A V E , SA N T A A N A , C A 9 2 7 0 6 , U S A ANSI B 11" X 17" DATE DESCRIPTION REVISIONS Signature with Seal PROJECT NAME & ADDRESS PV-4 CONTRACTOR NAME CONTRACTOR INFORMATION 8001 CANOGA AVE #B CANOGA PARK, CA 91304 PHONE: 1(818) 564-4820 COASTAL BUILDERS 610 E. SANTA CLARA AVE. SANTA ANA, CA 92706 (714) 234-9160 CALIFORNIA LIC# 623480- B STRING LAYOUT STRING LAYOUT : SCALE:- 3/16" = 1' (22) HANWHA Q.CELLS Q.PEAK DUO BLK-G5 320W MODULES (2) STRINGS OF 11 MODULES CONNECTED IN SERIES. BILL OF MATERIALS EQUIPMENT QTY DESCRIPTION SOLAR PV MODULE 22 HANWHA Q.CELLS Q.PEAK DUO BLK-G5 320W MODULES INVERTER 1 SOLAREDGE SE7600H-US000BNU4 INVERTER AC DISCONNECT 1 AC DISCONNECT: 240V, 60AMP NON-FUSED NEMA 3R, UL LISTED OPTIMIZER 22 SOLAREDGE POWER OPTIMIZER P320 ATTACHMENT 44 UNIRAC UNIVERSAL TILE HOOK ATTACHMENT ATTACHMENT RAILS 11 IRONRIDGE XR10 RAIL RACKING 168" RAIL SPLICE 6 SPLICE KIT MID CLAMPS 38 MID CLAMP END CLAMPS 12 END CLAMP GROUNDING LUG 3 E S A N T A C L A R A A V E AA A A A A A AA A AB B B BB B BB B B B 610 E Santa Clara Ave11/09/21 REV SHEET NAME SHEET SIZE SHEET NUMBER DO U G R I S K 61 0 E S A N T A C L A R A A V E , SA N T A A N A , C A 9 2 7 0 6 , U S A ANSI B 11" X 17" DATEDESCRIPTION REVISIONS Signature with Seal PROJECT NAME & ADDRESS PV-5 CONTRACTOR NAME CONTRACTOR INFORMATION 8001 CANOGA AVE #B CANOGA PARK, CA 91304 PHONE: 1(818) 564-4820 COASTAL BUILDERS 610 E. SANTA CLARA AVE. SANTA ANA, CA 92706 (714) 234-9160 CALIFORNIA LIC# 623480- B ATTACHMENT DETAIL REV SHEET NAME SHEET SIZE SHEET NUMBER DO U G R I S K 61 0 E S A N T A C L A R A A V E , SA N T A A N A , C A 9 2 7 0 6 , U S A ANSI B 11" X 17" DATE DESCRIPTION REVISIONS Signature with Seal PROJECT NAME & ADDRESS PV-5 CONTRACTOR NAME CONTRACTOR INFORMATION 8001 CANOGA AVE #B CANOGA PARK, CA 91304 PHONE: 1(818) 564-4820 COASTAL BUILDERS 610 E. SANTA CLARA AVE. SANTA ANA, CA 92706 (714) 234-9160 CALIFORNIA LIC# 623480- B 2 ATTACHMENT DETAIL (enlarged section view) PV-5 SCALE: NTS 2"x4" RAFTE R S @ 2 4 " O C PV MODULE IRONRIDGE INTEGRATED GROUNDING & END/MID CLAMP ALUMN. "L" BRACKET W/3/8" SS BOLT & NUT PV MODULES IRONRIDGE XR-10 RACKING SYSTEM (E) S-TILE ROOF 2"x4" RAFTERS @ 24" OC UNIRAC UNIVERSAL TILE HOOK ATTACHMENTS SEE (2/PV-5) FOR ENLARGED VIEW 5/16"x3" SS LAG BOLT WITH MIN 2-1/2" THREAD EMBEDMENT, SEALED PENETRATION FLASHING (E) S-TILE ROOF 1 ATTACHMENT DETAIL PV-5 SCALE: 1" = 1'-0" 7" 610 E Santa Clara Ave11/09/21 REV SHEET NAME SHEET SIZE SHEET NUMBER DO U G R I S K 61 0 E S A N T A C L A R A A V E , SA N T A A N A , C A 9 2 7 0 6 , U S A ANSI B 11" X 17" DATE DESCRIPTION REVISIONS Signature with Seal PROJECT NAME & ADDRESS PV-6 CONTRACTOR NAME CONTRACTOR INFORMATION 8001 CANOGA AVE #B CANOGA PARK, CA 91304 PHONE: 1(818) 564-4820 COASTAL BUILDERS 610 E. SANTA CLARA AVE. SANTA ANA, CA 92706 (714) 234-9160 CALIFORNIA LIC# 623480- B ATTACHMENT DETAIL EAST WALL (E) MAIN SERVICE PANEL WITH UTILITY METER 2 ELECTRICAL EQUIPMENT ELEVATION SCALE: NTSPV-6 CONDUIT PV ARRAY (N) SOLAREDGE SE7600H-US000BNU4 INVERTER (N) 60A AC DISCONNECT STRAIN RELIEF J-BOX RAIN TIGHT, STEEL EMT CONNECTOR CONDUIT ABOVE ROOF TO LOAD CENTER/MAIN SERVICE STRUT STRAP APPROVED LONG LASTING BLOCK EMT CONDUIT 1 CONDUIT DETAILS SCALE: NTSPV-6 3 SECURE FIRST END SCALE: NTSPV-6 4 GROUNDING DETAIL SCALE: NTSPV-6 UFO (80 IN LBS) STOPPER SLEEVE1" FROM RAIL END UFO GROUNDING LUG FAULT CURRENT GROUND PATH MINIMUM 10 AWG COPPER WIRE BOUDED SPLICE (RAIL CONNECTION) 610 E Santa Clara Ave11/09/21 REV SHEET NAME SHEET SIZE SHEET NUMBER DO U G R I S K 61 0 E S A N T A C L A R A A V E , SA N T A A N A , C A 9 2 7 0 6 , U S A ANSI B 11" X 17" DATE DESCRIPTION REVISIONS Signature with Seal PROJECT NAME & ADDRESS PV-7 CONTRACTOR NAME CONTRACTOR INFORMATION 8001 CANOGA AVE #B CANOGA PARK, CA 91304 PHONE: 1(818) 564-4820 COASTAL BUILDERS 610 E. SANTA CLARA AVE. SANTA ANA, CA 92706 (714) 234-9160 CALIFORNIA LIC# 623480- B ELECTRICAL SERVICE INFO UTILITY PROVIDER: MAIN SERVICE VOLTAGE: MAIN PANEL BRAND: MAIN SERVICE PANEL: MAIN CIRCUIT BREAKER RATING: MAIN SERVICE LOCATION: SERVICE FEED SOURCE: SCE 240V CUTLER HAMMER 200A EAST WALL UNDERGROUND 200A INTERCONNECTION 120% RULE - NEC 705.12(B)(2)(3)(b) UTILITY FEED + SOLAR BACKFEED 200A + 40A = 240A BUSS RATING x 120% 200A x 120% = 240A (N) 40A BACK FED BREAKER AT THE OPPOSITE END OF THE MAIN SERVICE BUSBAR FROM THE MAIN OVER CURRENT DEVICE. AC DISCONNECT: 240V, 60AMP NON-FUSED NEMA 3R, UL LISTED SOLAREDGE SE7600H-US000BNU4 INVERTER OUTPUT: 240 VAC, 32A NEMA 3R, UL LISTED GROUNDING ELECTRODE SYSTEM G BI-DIRECTIONAL UTILITY METER 1-PHASE, 3-W, 120V/240V, 60Hz (E) MAIN BREAKER TO HOUSE 240 V, 200A/2P (TOP FED) (E) MAIN SERVICE PANEL, 200A RATED, 240V 40A M TO UTILITY GRID CONDUCTORS EXPOSED TO FREE AIR: (2) #10 AWG PV WIRE + RED (2) #10 AWG PV WIRE - BLACK (1) #6 AWG BARE COPPER 3/4" EMT CONDUIT (2) #10 AWG THWN-2 + Red (2) #10 AWG THWN-2 - Black (1) #8 AWG THWN-2 GND 3/4" EMT CONDUIT (3) #8 AWG THWN-2 (1) #8 AWG THWN-2 GND JUNCTION BOX 600 V, NEMA 3 UL LISTED 1 STRING A == 11 1 STRING B == 11 == == HANWHA Q.CELLS Q.PEAK DUO BLK-G5 320W MODULES (11) POWER OPTIMIZER P320 (1) STRING OF (11) MODULES HANWHA Q.CELLS Q.PEAK DUO BLK-G5 320W MODULES (11) POWER OPTIMIZER P320 (1) STRING OF (11) MODULES GEC WIL BE CONNECTED DIRECTLY TO THE PREMISE WIRING ELECTRODE ALL ELECTRICAL EQUIPMENT SHALL BE LABELED, LISTED, OR CERTIFIED BY NATIONALLY RECOGNIZED TESTING LABORATORY ACCREDITED BY THE UNITED STATES OCCUPATIONAL SAFETY HEALTH ADMINISTRATION. TERMINATION POINTS FOR ELECTRICAL EQUIPMENT ARE RATED FOR 60/75 DEGREES CELSIUS THE BACKFEED BREAKER SHALL BE LOCATED AT THE OPPOSITE END OF THE MAIN BREAKER OR INPUT FEEDER. 610 E Santa Clara Ave11/09/21 REV SHEET NAME SHEET SIZE SHEET NUMBER DO U G R I S K 61 0 E S A N T A C L A R A A V E , SA N T A A N A , C A 9 2 7 0 6 , U S A ANSI B 11" X 17" DATE DESCRIPTION REVISIONS Signature with Seal PROJECT NAME & ADDRESS PV-8 CONTRACTOR NAME CONTRACTOR INFORMATION 8001 CANOGA AVE #B CANOGA PARK, CA 91304 PHONE: 1(818) 564-4820 COASTAL BUILDERS 610 E. SANTA CLARA AVE. SANTA ANA, CA 92706 (714) 234-9160 CALIFORNIA LIC# 623480- B WIRING CALCULATIONS ELECTRICAL NOTES DC CONDUCTOR AMPACITY CALCULATIONS: ARRAY TO JUNCTION BOX: DC CONDUCTOR AMPACITY CALCULATIONS: FROM JUNCTION BOX TO INVERTER: AC CONDUCTOR AMPACITY CALCULATIONS: INVERTER TO MAIN PANEL 1.) ALL EQUIPMENT TO BE LISTED BY UL OR OTHER NRTL, AND LABELED FOR ITS APPLICATION. 2.) ALL CONDUCTORS SHALL BE COPPER, RATED FOR 600 V AND 90 DEGREE C WET ENVIRONMENT. 3.) WIRING, CONDUIT, AND RACEWAYS MOUNTED ON ROOFTOPS SHALL BE ROUTED DIRECTLY TO, AND LOCATED AS CLOSE AS POSSIBLE TO THE NEAREST RIDGE, HIP, OR VALLEY. 4.) WORKING CLEARANCES AROUND ALL NEW AND EXISTING ELECTRICAL EQUIPMENT SHALL COMPLY WITH NEC 110.26. 5.) DRAWINGS INDICATE THE GENERAL ARRANGEMENT OF SYSTEMS. CONTRACTOR SHALL FURNISH ALL NECESSARY OUTLETS, SUPPORTS, FITTINGS AND ACCESSORIES TO FULFILL APPLICABLE CODES AND STANDARDS. 6.) WHERE SIZES OF JUNCTION BOXES, RACEWAYS, AND CONDUITS ARE NOT SPECIFIED, THE CONTRACTOR SHALL SIZE THEM ACCORDINGLY. 7.) ALL WIRE TERMINATIONS SHALL BE APPROPRIATELY LABELED AND READILY VISIBLE. 8.) MODULE GROUNDING CLIPS TO BE INSTALLED BETWEEN MODULE FRAME AND MODULE SUPPORT RAIL, PER THE GROUNDING CLIP MANUFACTURER'S INSTRUCTION. 9.) MODULE SUPPORT RAIL TO BE BONDED TO CONTINUOUS COPPER G.E.C. VIA WEEB LUG OR ILSCO GBL-4DBT LAY-IN LUG. 10.) THE POLARITY OF THE GROUNDED CONDUCTORS IS NEGATIVE INVERTER SPECIFICATIONS MANUFACTURER / MODEL # NOMINAL AC POWER NOMINAL OUTPUT VOLTAGE MAX. CONTINUOUS OUTPUT CURRENT NUMBER OF CURRENT CARRYING CONDUCTORS IN EMT 4-6 7-9 10-20 PERCENT OF VALUES .80 .70 .50 SOLAREDGE SE7600H-US000BNU4 7.6 KW 240 VAC 32A OPTIMIZERS SPECIFICATIONS MANUFACTURER / MODEL # MAX. OUTPUT CURRENT MAX. INPUT CURRENT MAX. INPUT VOLTAGE SOLAREDGE POWER OPTIMIZER P320 15A 8.8A 48Vdc SOLAR MODULE SPECIFICATIONS MANUFACTURER / MODEL # VMP IMP VOC ISC HANWHA Q.CELLS Q.PEAK DUO BLK-G5 320W MODULE DIMENSION MODULE TEMPERATURE COEFFICIENT OF Voc 33.32V 9.60A 40.13V 10.09A 66.3"L x 39.4"W x 1.26"D (In Inch) -0.28%/°C EXPECTED WIRE TEMP (In Celsius)31° TEMP. CORRECTION PER TABLE (310.16)0.96 NO. OF CURRENT CARRYING CONDUCTORS 4 CONDUIT FILL CORRECTION PER NEC 310.15(B)(2)(a)0.80 CIRCUIT CONDUCTOR SIZE 10 AWG CIRCUIT CONDUCTOR AMPACITY 40A REQUIRED CIRCUIT CONDUCTOR AMPACITY PER NEC 690.8(A&B) 18.75A 1.25 X OPTIMIZER OUTPUT DERATED AMPACITY OF CIRCUIT CONDUCTOR PER NEC TABLE 310.16 30.72ATEMP. CORRECTION PER TABLE (310.16) X CONDUIT FILL CORRECTION PER NEC 310.15(B)(2)(a) X CIRCUIT CONDUCTOR AMPACITY Result should be greater than (18.75A) otherwise less the entry for circuit conductor size and ampacity EXPECTED WIRE TEMP (In Celsius)31° TEMP. CORRECTION PER TABLE (310.16)0.96 NO. OF CURRENT CARRYING CONDUCTORS 4 CONDUIT FILL CORRECTION PER NEC 310.15(B)(2)(a)0.80 CIRCUIT CONDUCTOR SIZE 10AWG CIRCUIT CONDUCTOR AMPACITY 40A REQUIRED CIRCUIT CONDUCTOR AMPACITY PER NEC 690.8(A&B) 18.75A 1.25 X OPTIMIZER OUTPUT DERATED AMPACITY OF CIRCUIT CONDUCTOR PER NEC TABLE 310.16 30.72ATEMP. CORRECTION PER TABLE (310.16) X CONDUIT FILL CORRECTION PER NEC 310.15(B)(2)(a) X CIRCUIT CONDUCTOR AMPACITY Result should be greater than (18.75A) otherwise less the entry for circuit conductor size and ampacity No. OF INVERTER 1 EXPECTED WIRE TEMP (In Celsius)31° TEMP. CORRECTION PER TABLE (310.16)0.96 NO. OF CURRENT CARRYING CONDUCTORS 3 CONDUIT FILL CORRECTION PER NEC 310.15(B)(2)(a)1 CIRCUIT CONDUCTOR SIZE 8AWG CIRCUIT CONDUCTOR AMPACITY 50A REQUIRED CIRCUIT CONDUCTOR AMPACITY PER NEC 690.8(B) 40A 1.25 X MAX INVERTER OUTPUT CURRENT DERATED AMPACITY OF CIRCUIT CONDUCTOR PER NEC TABLE 310.16 44ATEMP. CORRECTION PER TABLE (310.16) X CONDUIT FILL CORRECTION PER NEC 310.15(B)(2)(a) X CIRCUIT CONDUCTOR AMPACITY Result should be greater than (40.00A) otherwise less the entry for circuit conductor size and ampacity AMBIENT TEMPERATURE SPECS RECORD LOW TEMP 2° AMBIENT TEMP (HIGH TEMP 2%)31° CONDUIT HEIGHT 7/8" ROOF TOP TEMP 53° CONDUCTOR TEMPERATURE RATE 90°75°/ 610 E Santa Clara Ave11/09/21 INVMSP UM ACD REV SHEET NAME SHEET SIZE SHEET NUMBER DO U G R I S K 61 0 E S A N T A C L A R A A V E , SA N T A A N A , C A 9 2 7 0 6 , U S A ANSI B 11" X 17" DATE DESCRIPTION REVISIONS Signature with Seal PROJECT NAME & ADDRESS PV-9 CONTRACTOR NAME CONTRACTOR INFORMATION 8001 CANOGA AVE #B CANOGA PARK, CA 91304 PHONE: 1(818) 564-4820 COASTAL BUILDERS 610 E. SANTA CLARA AVE. SANTA ANA, CA 92706 (714) 234-9160 CALIFORNIA LIC# 623480- B PLACARDS CAUTION POWER TO THIS BUILDING IS ALSO SUPPLIED FROM THE FOLLOWING SOURCES WITH DISCONNECTS LOCATED AS SHOWN PV ARRAY AC DISCONNECT ADHESIVE FASTENED SIGNS: ·THE LABEL SHALL BE SUITABLE FOR THE ENVIRONMENT WHERE IT IS INSTALLED. ·WHERE REQUIRED ELSEWHERE IN THIS CODE, ALL FIELD APPLIED LABELS, WARNINGS, AND MARKINGS SHOULD COMPLY WITH ANSI Z535.4 [NEC 110.21(B) FIELD MARKING]. ·ADHESIVE FASTENED SIGNS MAY BE ACCEPTABLE IF PROPERLY ADHERED. VINYL SIGNS SHALL BE WEATHER RESISTANT [IFC 605.11.1.3] SIGNAGE FORMAT: ALL LETTERS SHALL BE CAPITALIZED, 3/8" WHITE LETTERING ON RED BACKGROUND, ARIAL OR SIMILAR FONT, NON-BOLD; REFLECTIVE, ON WEATHER- RESISTANT MATERIAL SUITABLE FOR THE ENVIRONMENT (USE UL-969 AS STANDARD FOR WEATHER RATING) WILL BE USED; DURABLE ADHESIVE MATERIALS MEET THIS REQUIREMENT. LABEL LOCATION: AC DISCONNECT, POINT OF INTERCONNECTION (PER CODE: CEC690.54) LABEL LOCATION: CONDUIT, COMBINER BOX (PER CODE: CEC690.31(G)(3)(4) & CEC 690.13(G)(4) WARNING: PHOTOVOLTAIC POWER SOURCE WARNING ELECTRIC SHOCK HAZARD LABEL LOCATION: AC DISCONNECT, POINT OF INTERCONNECTION PER CODE: CEC 690.17(E), CB DO NOT TOUCH TERMINALS TERMINALS ON BOTH LINE AND LOAD SIDES MAY BE ENERGIZED IN THE OPEN POSITION ELECTRIC SHOCK HAZARD IF A GROUND FAULT IS INDICATED NORMALLY GROUNDED CONDUCTORS MAY BE UNGROUNDED AND ENERGIZED LABEL LOCATION: DC DISCONNECT, INVERTER (PER CODE: CEC 690.35(F)) [To be used when inverter is ungrounded] WARNING WARNING ELECTRIC SHOCK HAZARD THE DC CONDUCTORS OF THIS PHOTOVOLTAIC SYSTEM ARE UNGROUNDED AND MAY BE ENERGIZED LABEL LOCATION: DC DISCONNECT, INVERTER (PER CODE: CEC 690.35(F)) [To be used when inverter is ungrounded] PHOTOVOLTAIC SYSTEM AC DISCONNECT RATED AC OPERATING CURRENT 32 AMPS AC NOMINAL OPERATING VOLTAGE 240 VOLTS ! PHOTOVOLTAIC SYSTEM EQUIPPED WITH RAPID SHUTDOWN DISCONNECT LABEL LOCATION: SERVICE DISCONNECTING (PER CODE: NEC 690.56(C)) SOLAR ELECTRIC PV PANELS LABEL LOCATION: AC DISCONNECT, POINT OF INTERCONNECTION (PER CODE: NEC690.56(C)(1)(A)) SOLAR PV SYSTEM EQUIPPED WITH RAPID SHUTDOWN LABEL LOCATION: UTILITY SERVICE METER AND MAIN SERVICE PANEL. PER CODE(S): CEC 2019: 705.12(B)(2)(3)(b) WARNING POWER SOURCE OUTPUT CONNECTION DO NOT RELOCATE THIS OVERCURRENT DEVICE LABEL LOCATION: POINT OF INTERCONNECTION (PER CODE: CEC 705.12(B)(2)(3)(b)) [Not required if panelboard is rated not less than sum of ampere ratings of all overcurrent devices supplying it] ! LABEL LOCATION: POINT OF INTERCONNECTION (PER CODE: CEC 705.12(B)(2)(3)(b)) WARNING DUAL POWER SOURCE SECOND SOURCE IS PHOTOVOLTAIC SYSTEM TURN RAPID SHUTDOWN SWITCH TO THE "OFF" POSITION TO SHUT DOWN PV SYSTEM AND REDUCE SHOCK HAZARD IN THE ARRAY SOURCES: UTILITY GRID AND PV SOLAR ELECTRIC SYSTEM DUAL POWER SUPPLY WARNING! ! ! MAIN SERVICE PANEL INVERTER LABEL LOCATION: INVERTER(S), DC DISCONNECT(S). PER CODE(S): CEC 2019, NEC 2019 (PER CODE 690.53) INVERTER ADC 45 30 480 MAXIMUM VOLTAGE: MAXIMUM CIRCUIT CURRENT: MAXIMUM RATED OUTPUT CURRENT OF THE CHARGE CONTROLLER OR DC-TO-DC CONVERTER: ADC VDC RAPID SHUTDOWN SWITCH FOR SOLAR PV SYSTEM LABEL LOCATION: PV SOLAR SHUTDOWN SWITCH (NO MORE THAN 3F FROM THE SWITCH) (PER CODE: NEC690.56(C)(3) E S A N T A C L A R A A V E 610 E Santa Clara Ave11/09/21 Rahman Engineering A Civil / Structural & Environmental Engineering Services Company (Professional Engineer License # C69263, QSD/QSP # 22406) Rahman Engineering Inc. 13611 12th St., Suite-B, Chino, CA 91710 STRUCTURAL Project Name & Address DOUG RISK 610 E SANTA CLARA AVE, Rahman Engineering Inc. tructural & Environmental Engineering Services Company (Professional Engineer License # C69263, QSD/QSP # 22406) E-mail: moksud.rahman@gmail.com STRUCTURAL CALCULATIONS Project Name & Address DOUG RISK SOLAR PROJECT 610 E SANTA CLARA AVE, SANTA ANA, CA 92706 Date: 05-Oct-21 by - Moksud Rahman, PE Tel: (213) 400-8078 moksud.rahman@gmail.com CALCULATIONS 610 E Santa Clara Ave11/09/21 PROJECT : PAGE : CLIENT : DESIGN BY : JOB NO. : DATE : REVIEW BY : INPUT DATA Exposure category (B, C or D)C Importance factor, pg 77, (0.87, 1.0 or 1.15)I = 1.00 Category II Basic wind speed (IBC Tab 1609.3.1V3S)V = 110 mph Topographic factor (Sec.6.5.7.2, pg 26 & 45)Kzt = 1 Flat Building height to eave he = 18 ft Building height to ridge hr = 25 ft Building length L = 38 ft Building width B = 22 ft Effective area of components A = 11 ft2 DESIGN SUMMARY Max horizontal force normal to building length, L, face = 20.15 kips Max horizontal force normal to building length, B, face = 8.84 kips Max total horizontal torsional load = 91.46 ft-kips Max total upward force = 15.73 kips ANALYSIS Velocity pressure qh = 0.00256 Kh Kzt Kd V2 I = 24.01 psf where: qh = velocity pressure at mean roof height, h. (Eq. 6-15, page 27) Kh = velocity pressure exposure coefficient evaluated at height, h, (Tab. 6-3, Case 1,pg 79)= 0.91 Kd = wind directionality factor. (Tab. 6-4, for building, page 80)= 0.85 h = mean roof height = 21.50 ft < 60 ft, [Satisfactory] < Min (L, B), [Satisfactory] Design pressures for MWFRS p = qh [(G Cpf )-(G Cpi )] where: p = pressure in appropriate zone. (Eq. 6-18, page 28). pmin = 10 psf (Sec. 6.1.4.1 & 6.1.4.2) G Cp f = product of gust effect factor and external pressure coefficient, see table below. (Fig. 6-10, page 53 & 54) G C = product of gust effect factor and internal pressure coefficient.(Fig. 6-5, Enclosed Building, page 47) DOUG RISK RES G Cp i = product of gust effect factor and internal pressure coefficient.(Fig. 6-5, Enclosed Building, page 47) = 0.18 or -0.18 a = width of edge strips, Fig 6-10, note 9, page 54, MAX[ MIN(0.1B, 0.4h), 0.04B,3] = 3.00 ft Net Pressures (psf), Basic Load Cases Net Pressures (psf), Torsional Load Cases 32.47 0.00 32.47 (+GCp i ) (-GCp i ) (+GCp i ) (-GCp i )(+GCp i ) (-GCp i ) 1 0.56 9.12 17.77 0.40 5.28 13.93 1T 0.56 2.28 4.44 2 0.21 0.72 9.36 -0.69 -20.89 -12.25 2T 0.21 0.18 2.34 3 -0.43 -14.65 -6.00 -0.37 -13.21 -4.56 3T -0.43 -3.66 -1.50 4 -0.37 -13.21 -4.56 -0.29 -11.29 -2.64 4T -0.37 -3.30 -1.14 1E 0.69 12.25 20.89 0.61 10.33 18.97 0.00 2E 0.27 2.16 10.81 -1.07 -30.02 -21.37 3E -0.53 -17.05 -8.40 -0.53 -17.05 -8.40 (+GCp i ) (-GCp i ) 4E -0.48 -15.85 -7.20 -0.43 -14.65 -6.00 1T 0.40 1.32 3.48 5 -0.45 -15.13 -6.48 -0.45 -15.13 -6.48 2T -0.69 -5.22 -3.06 6 -0.45 -15.13 -6.48 -0.45 -15.13 -6.48 3T -0.37 -3.30 -1.14 4T -0.29 -2.82 -0.66 Surface Roof angle q = Surface Roof angle q = G Cp f Net Pressure with Surface Roof angle q = G Cp f Net Pressure with Roof angle q = G Cp f Net Pressure withNet Pressure with G Cp f Wind Analysis for Low-rise Building, Based on ASCE 7-16 / IBC 2018 / CBC 2019 610 E Santa Clara Ave11/09/21 DOUG RISK RES 610 E SANTA CLARA AVE, SANTA ANA, CA 92706 LOAD CRITERIA WEIGHT OF MODULE 41.88 LB MODULE LENGTH 5.44 FT MODULE WIDTH 3.25 FT MODULE AREA 17.68 FT^2 UNIT WT OF MODULE 2.37 PSF AVG RACKING WT 0.3 PSF TOTAL AVG WT (MODULE+RACKING)2.67 PSF NO OF MODULE 22 CONNECTION POINT TRIB LENGTH 2.75 FT CONNECTION POINT TRIB WIDTH 4 FT MAX. SPACING CONN POINT TRIB. AREA 11 FT^2 LOAD PER CONN PT LOAD 29 LB ROOF SLOPE 27.00 DEGREE SLIING FORCE 13.33 LB LOAD*SIN(ROOF SLOPE ) LOAD ON EXISTING ROOF 1) ROOFING 10.00 PSF 2) 5/8" PLYWOOD 1.8 PSF 3) ROOF RAFTER 3.1 PSF 4) INSULATION 1.5 PSF 5) MISC 1.5 PSF TOTAL DL 17.90 PSF ROOF AREA 836 SF TOTAL ROOF WT 14.96 KIP WALL WT 1.44 KIP TOTAL BUILDING DL 16.40 KIP EACH MODULE AREA 17.68 TOTAL AREA OF MODULE 388.96 SF TOTAL MODULE WT 1.56 KIP ADDITIONAL DL ADDED TO EXISTING BUILDING 9.48 % LATERAL LOAD ANALYSIS COMMENTS SINCE TOTAL ADDED DL TO THE BUILDING IS LESS THAN 10%, PER CBC 2019 EXISTING LATERAL RESISTING ELEMENTS WILL NOT BE AFFECTED VERTICAL LOAD ANALYSIS COMMENTS PER CBC SECTION 1607.9.1.1 EXCEPTION 2, THE ROOF LL CAN BE PERMITTED TO BE RATIONALLY REDUCED TO 10 PSF AT THE AREA OCCUPIED BY THE SOLAR MODULES THEREFORE, DESIGN LOAD BY ADDING SOLAR MODULE OF 2.75 PSF IS LESS THAN WITHOUT MODULES AND HENCE EXISTING FRAMING WILL THEREFORE BE OK. 610 E Santa Clara Ave11/09/21 DOUG RISK RES 610 E SANTA CLARA AVE, SANTA ANA, CA 92706 CONNECTION DESIGN VELOCITY PRESSURE, qh 24.01 PSF (SEE WIND LOAD CALC) A) LATERAL FORCE Fh FOR ROOFTOP STRUCTURES (FOR ONE CONN POINT) (ONE SCREW PER CONN POINT) HORIZONTAL WIND FORCE, Fh = qh * Gcr * Af ASCE 7-16, Eq. 29.4.4 WIDTH OF BUILDING, B 22 FT MEAN HEIGHT OF BLDG, H 25 FT CONNECTION POINT TRIB LENGTH, l 4 FT MAX. SPACING CONNECTION POINT PROJECTED HEIGHT, h1.25 FT [2.75' SIN(ROOF SLOPE)] VERTICAL PROJECTED AREA, Af 4.99 FT^2 Gcr 1.9 IF(B*H*0.1>Af,1.9) ASCE 7-16, Eq. 29.4.4 WIND LATERAL FORCE, Fh 227.8 LB SLIDING FORCE 13.33 DESIGN LATERAL FORCE 241.10 B) VERTICAL FORCE Fv FOR ROOFTOP STRUCTURES ( (FOR ONE CONN POINT) VERTICAL WIND FORCE, Fv = qh * Gcr * Ar ASCE 7-16, Eq. 29.4.4 WIDTH OF BUILDING, B 22 FT LENGTH OF BLDG, L 38 FT CONNECTION POINT TRIB LENGTH, l 4 FT CONNECTION POINT TRIB WIDTH, w 2.45 FT [2.75' COS(ROOF SLOPE)] HORIZONTAL PROJECTED AREA, Ar 9.80 FT^2 Gcr 1.4 IF(B*L*0.1>Ar,1.5) ASCE 7-16, Eq. 29.4.4 WIND VERTICAL FORCE, Fv 329.5 LB DESIGN WITHDRAWL FORCE 329.5 610 E Santa Clara Ave11/09/21 DOUG RISK RES 610 E SANTA CLARA AVE, SANTA ANA, CA 92706 CONNECTION DESIGN DESIGN LATERAL FORCE 241.102 USE LAG SCREW 5/16" INCH CAPACITY PER ONE SCREW, ZII 320 LB (NDS 2018 REFERENCE DESIGN VALUE, SEE ATTACHED) DESIGN CAPACITY, Z II '425.6 LB DESIGN IS GOOD DESIGN WITHDRAWL FORCE 329.468 USE LAG SCREW 5/16" INCH WITHDRAWL CAPACITY 227 LB (NDS 2018 REFERENCE DESIGN VALUE, SEE ATTACHED) DESIGN WITHDRAWL CAPACITY 1056.69 LB DESIGN IS GOOD COMBINED WIND SHEAR/UPLIFT 0.10 0.321 0.42 < 1.0 DESIGN IS GOOD (UPLIFT)(SHEAR) USE 5/16" DIA X 3 1/2" (EMBEDMENT) LAG SCREW PER CONNECTION POINT 610 E Santa Clara Ave11/09/21 610 E Santa Clara Ave11/09/21 Expedited Permit Process for PV Systems1 Expedited Permit Process for PV Systems Standard String System The Solar America Board for Codes and Standards (Solar ABCs) Expedited Permit Pro- cess provides a means to differentiate systems that can be permitted quickly and easily due to their similarity with the majority of small-scale PV systems. Those systems with unique characteristics may be handled with small additions to this Expedited Permit Process or may require much more information, depending on the uniqueness of the installation. The following pages contain forms for the Standard String System to use with the Expe- dited Permit Process. The Micro-Inverter, AC Module, and Supply-Side Connection forms are also available as interactive PDF files at www.solarabcs.org/permitting. In jurisdic- tions that have adopted the Expedited Permit Process for PV Systems, these forms can be filled out electronically and submitted in either printed form and via email. An elec- tronic format is used so that the supplied information is standardized and legible for the local jurisdiction. 610 E Santa Clara Ave11/09/21 Expedited Permit Process for PV Systems2 Expedited Permit Process for Small-Scale PV Systems Standard String System The information in this guideline is intended to help local jurisdictions and contractors identify when PV system installations are simple, needing only a basic review, and when an installation is more complex. It is likely that 50%-75% of all residential systems will comply with these simple criteria. For projects that fail to meet the simple criteria, resolution steps have been suggested to provide as a path to permit approval. Required Information for Permit: 1. Site plan showing location of major components on the property. This drawing need not be exactly to scale, but it should represent relative location of components at site (see supplied example site plan). PV arrays on dwellings with a 3’ perimeter space at ridge and sides may not need separate fire service review. 2. Electrical diagram showing PV array configuration, wiring system, overcurrent protection, inverter, disconnects, required signs, and ac connection to building (see supplied standard electrical diagram). 3. Specification sheets and installation manuals (if available) for all manufactured components including, but not limited to, PV modules, inverter(s), combiner box, disconnects, and mounting system. Step 1: Structural Review of PV Array Mounting System Is the array to be mounted on a defined, permitted roof structure? l Yes l No If No due to non-compliant roof or a ground mount, submit completed worksheet for the structure WKS1. Roof Information: 1. Is the roofing type lightweight (Yes = composition, lightweight masonry, metal, etc…)__________________________ ____________________________________________________________________________________________________ If No, submit completed worksheet for roof structure WKS1 (No = heavy masonry, slate, etc…). 2. Does the roof have a single roof covering? l Yes l No If No, submit completed worksheet for roof structure WKS1. 3. Provide method and type of weatherproofing roof penetrations (e.g. flashing, caulk).____________________________ Mounting System Information: 1. Is the mounting structure an engineered product designed to mount PV modules with no more than an 18” gap beneath the module frames? l Yes l No If No, provide details of structural attachment certified by a design professional. 2. For manufactured mounting systems, fill out information on the mounting system below: a. Mounting System Manufacturer ___________Product Name and Model#________________________________ b. Total Weight of PV Modules and Rails ___________lbs c. Total Number of Attachment Points____________ d. Weight per Attachment Point (b÷c)_________________lbs (if greater than 45 lbs, see WKS1) e. Maximum Spacing Between Attachment Points on a Rail ______________inches (see product manual for maximum spacing allowed based on maximum design wind speed) f. Total Surface Area of PV Modules (square feet)_________________ ft2 g. Distributed Weight of PV Module on Roof (b÷f)_______________ lbs/ft2 If distributed weight of the PV system is greater than 5 lbs/ft2, see WKS1. Step 2: Electrical Review of PV System (Calculations for Electrical Diagram) In order for a PV system to be considered for an expedited permit process, the following must apply: 1. PV modules, utility-interactive inverters, and combiner boxes are identified for use in PV systems. 2. The PV array is composed of 4 series strings or less per inverter. 3. The total inverter capacity has a continuous ac power output 13,440 Watts or less 4. The ac interconnection point is on the load side of service disconnecting means (690.64(B)). 5. One of the standard electrical diagrams (E1.1, E1.1a, E1.1b, or E1.1c) can be used to accurately represent the PV system. Interactive PDF diagrams are available at www.solarabcs.org/permitting. Fill out the standard electrical diagram completely. A guide to the electrical diagram is provided to help the applicant understand each blank to fill in. If the electrical system is more complex than the standard electrical diagram can effectively communicate, provide an alternative diagram with appropriate detail. 610 E Santa Clara Ave11/09/21 Ex p e d i t e d P e r m i t P r o c e s s f o r P V S y s t e m s 3 Standard String System Site Plan                                                        COASTAL BUILDERS Risk 610 E. SANTA CLARA AVE. SANTA ANA, CA 92706 (714) 234-9160 610 E Santa Clara Ave. Santa Ana CA 92706 CEC AC: 6.53KW 610 E Santa Clara Ave11/09/21 Ex p e d i t e d P e r m i t P r o c e s s f o r P V S y s t e m s 4 Standard String System Electrical Diagram                                                                                                                                                                                                                                                  COASTAL BUILDERS Risk 610 E. SANTA CLARA AVE. SANTA ANA, CA 92706 (714) 234-9160 610 E Santa Clara Ave. Santa Ana CA 92706 CEC AC: 6.53KW 610 E Santa Clara Ave11/09/21 Ex p e d i t e d P e r m i t P r o c e s s f o r P V S y s t e m s 5 Notes for Standard String System Electrical Diagram Contractor Name, Address and Phone: _________________ _________________ _________________ _________________ Notes for One-Line Standard Electrical Diagram for Single-Phase PV Systems Site Name: __________________________ Site Address: ________________________ System AC Size: ______________________ SIZE FSCM NO DWG NO REV SCALE NTS Date: SHEET Drawn By: Checked By: MAX POWER-POINT CURRENT (IMP) MAX POWER-POINT VOLTAGE (VMP) OPEN-CIRCUIT VOLTAGE (VOC) SHORT-CIRCUIT CURRENT (ISC) MAX SERIES FUSE (OCPD) MAXIMUM POWER (PMAX) MAX VOLTAGE (TYP 600VDC) VOC TEMP COEFF (mV/oC or %/oC ) IF COEFF SUPPLIED, CIRCLE UNITS A V V A A W V MODULE MAKE MODULE MODEL PV MODULE RATINGS @ STC (Guide Section 5) MAX DC VOLT RATING MAX POWER @ 40oC NOMINAL AC VOLTAGE MAX AC CURRENT MAX OCPD RATING V W V A A INVERTER MAKE INVERTER MODEL INVERTER RATINGS (Guide Section 4) 1) IF UTILITY REQUIRES A VISIBLE-BREAK SWITCH, DOES THIS SWITCH MEET THE REQUIREMENT? YES NO N/A 2) IF GENERATION METER REQUIRED, DOES THIS METER SOCKET MEET THE REQUIREMENT? YES NO N/A 3) SIZE PHOTOVOLTAIC POWER SOURCE (DC) CONDUCTORS BASED ON MAX CURRENT ON NEC 690.53 SIGN OR OCPD RATING AT DISCONNECT 4) SIZE INVERTER OUTPUT CIRCUIT (AC) CONDUCTORS ACCORDING TO INVERTER OCPD AMPERE RATING. (See Guide Section 9) 5) TOTAL OF ______ INVERTER OCPD(s), ONE FOR EACH INVERTER. DOES TOTAL SUPPLY BREAKERS COMPLY WITH 120% BUSBAR EXCEPTION IN 690.64(B)(2)(a)? YES NO NOTES FOR INVERTER CIRCUITS (Guide Section 8 and 9): 1.) LOWEST EXPECT AMBIENT TEMPERATURE BASED ON ASHRAE MINIMUM MEAN EXTREME DRY BULB TEMPERATURE FOR ASHRAE LOCATION MOST SIMILAR TO INSTALLATION LOCATION. LOWEST EXPECTED AMBIENT TEMP ______oC 2.) HIGHEST CONTINUOUS AMBIENT TEMPERATURE BASED ON ASHRAE HIGHEST MONTH 2% DRY BULB TEMPERATURE FOR ASHRAE LOCATION MOST SIMILAR TO INSTALLATION LOCATION. HIGHEST CONTINUOUS TEMPERATURE _____oC 2.) 2005 ASHRAE FUNDEMENTALS 2% DESIGN TEMPERATURES DO NOT EXCEED 47oC IN THE UNITED STATES (PALM SPRINGS, CA IS 44.1 oC). FOR LESS THAN 9 CURRENT-CARRYING CONDUCTORS IN ROOF-MOUNTED SUNLIT CONDUIT AT LEAST 0.5" ABOVE ROOF AND USING THE OUTDOOR DESIGN TEMPERATURE OF 47oC OR LESS (ALL OF UNITED STATES), a) 12 AWG, 90oC CONDUCTORS ARE GENERALLY ACCEPTABLE FOR MODULES WITH Isc OF 7.68 AMPS OR LESS WHEN PROTECTED BY A 12-AMP OR SMALLER FUSE. b) 10 AWG, 90oC CONDUCTORS ARE GENERALLY ACCEPTABLE FOR MODULES WITH Isc OF 9.6 AMPS OR LESS WHEN PROTECTED BY A 15-AMP OR SMALLER FUSE. NOTES FOR ARRAY CIRCUIT WIRING (Guide Section 6 and 8 and Appendix D): OCPD = OVERCURRENT PROTECTION DEVICE NATIONAL ELECTRICAL CODE ® REFERENCES SHOWN AS (NEC XXX.XX) NOTES FOR ALL DRAWINGS: SIGNS–SEE GUIDE SECTION 7 SIGN FOR DC DISCONNECT SIGN FOR INVERTER OCPD AND AC DISCONNECT (IF USED) RATED MPP CURRENT RATED MPP VOLTAGE MAX SYSTEM VOLTAGE MAX CIRCUIT CURRENT A V V A PHOTOVOLTAIC POWER SOURCE WARNING: ELECTRICAL SHOCK HAZARD–LINE AND LOAD MAY BE ENERGIZED IN OPEN POSITION AC OUTPUT CURRENT NOMINAL AC VOLTAGE A V SOLAR PV SYSTEM AC POINT OF CONNECTION THIS PANEL FED BY MULTIPLE SOURCES (UTILITY AND SOLAR) COASTAL BUILDERS Risk 610 E. SANTA CLARA AVE. SANTA ANA, CA 92706 (714) 234-9160 610 E Santa Clara Ave. Santa Ana CA 92706 CEC AC: 6.53KW 610 E Santa Clara Ave11/09/21 Rev: 7/15/2021 RESIDENTIAL PHOTOVOLTAIC CHECKLIST SOL-01 CBC 2019 Solar Photovoltaic (PV) Checklist for Detached SINGLE FAMILY RESIDENCES Only Instructions: The licensed contractor of record shall complete all sections, answer the ten questions and sign the certification section below. A copy of this form shall be attached to each of TWO sets of plans, of minimum 11” x 17” size. If answering NO to any of the questions, plan check shall be required. Project Address: Contractor Company Name: Contractor License Number: YES NO Are the following applicable to the proposed project? 1.   Will the PV system layout provide the required three-foot wide clear access pathways per Section 605.11 of the California Fire Code, and is this shown on the roof plan? 2.  Will the PV system be installed on a roof having only one roofing layer with no overlays? 3.  Will the PV array be flush mounted to the existing roof so that the plane of the modules (panels) are parallel to the plane of the roof? 4.  Will the PV system weigh maximum 4 pounds per square feet or less? 5.  Will the PV system be installed where the modules do not overhang any roof edges (such as eaves, gabled ends, ridges and hips)? 6.   Will the PV system be installed with a space of 2” minimum to 10” maximum between the underside of modules and the surface of the roof? 7.   Will the PV system be installed without using any ballast system or counter-weight system? 8.   Will the anchors be installed with a maximum horizontal anchor spacing of 6 feet and is this maximum horizontal spacing shown on the plans? 9.   Will the minimum 5/16” lag screws be installed with a minimum of 2-1/2 inch embedment into roof rafters (with pre-drilled holes) and is this minimum embedment shown on the plans? 10.   Are ALL the structural pages of the plans stamped and signed by a California licensed professional engineer? (including project specific site plan, PV layout, anchorage spacing, anchorage details and manufacturer’s PV support information.) I certify under penalty of perjury under the laws of the State of California that the above is true: Print Name: Signature: Phone Number: Date: Email Address: Planning & Building Agency Building Safety Division 20 Civic Center Plaza P.O. Box 1988 (M-19) Santa Ana, CA 92702 (714) 647-5800 www.santa-ana.org X X X X X X X X X X FEDERICO MECIAS 10/05/21 5102892494 RICOSASHA16@GMAIL.COM SASHHA INTERNATIONAL 610 E SANTA CLARA AVE 623480 610 E Santa Clara Ave11/09/21