HomeMy WebLinkAbout624 E 3rd St - PlanGENERAL
1. All electrical work to be installed by a qualified licensed electrician and apprentices
working under the direct supervision of the licensed contractor.
2. All solar modules shall be listed 1703 & CEC approved. All inverters shall be UL listed
1741 certified & CEC approved. All electrical components and materials shall be listed
for
its purpose and installed in a workman-like manner. All customer equipment shall
meet
appropriate NEMA standards.
3. All fabrication and manufacturing shall be performed by certified individuals in
approved
assembly and fabrication shops.
4. Prior to commencement of any work, the contractor shall notify the engineer of any
discrepancies noted among site conditions, manufacturer recommendations or
authority
having jurisdiction (AHJ).
5. Contractor-initiated changes shall be submitted in writing to the engineer in the
form of a "RFI" (Request for Information), prior to making any changes. Approved
changes shall require a drawing revision to maintain control over the engineer
approved
design.
6. The electrical contractor is advised that all drawings and component manuals are to
be
understood prior to installation. The contractor is advised to have all switches in
"off "position and the fuses removed prior to the installation of fuse-bearing
components.
7. This proposed solar electric system is intended to operate in parallel with power
received
from the utility service provider.
8. Anti-islanding protection is requirement of UL 1741 and is intended to prevent the
operation of the PV System when the utility grid is not operational.
9. Permission to operate the system is not authorized until final inspections and
approvals are obtained from the local authority having jurisdiction and the local
utility service provider.
ELECTRICAL
1. PV installation shall comply with article 690 of 2017 NEC.
2. The inverter for the proposed solar electric system shall be identified for use in solar
photovoltaic systems. All equipment shall be UL approved.
3. This system is intended to connect to the existing facility power system at one point.
The point of common coupling (POCC). This connection shall be in compliance
with the NEC article 690.64 "POINT OF CONNECTION".
4. All circuits shall have individual source circuit protection for testing and isolation.
All combiner boxes shall have disconnecting means near the combiner
for isolation and testing.
5. All disconnects and combiners shall be secured from unauthorized / unqualified
personnel by locking location.
6.All disconnects, combiners, pull/ splice boxes and enclosures shall be listed for its
purpose.
7. Equipment shall be installed in a secure area. Inverter performance may be affected
if installed in direct sunlight.
8. DC array conductors are to remain outside of building prior to fused combiner box or
fused DC disconnecting means.
9. Raceway for grounding electrode conductor shall be bonded at each end.
10.The DC grounding electrode conductor shall be bonded to the AC grounding
electrode conductor to make a grounding electrode system according to CEC 250.52
and 250.53. The bonding conductor shall be no smaller than the largest grounding
electrode conductor, either DC or AC, 690.47(c)(1)
11.Grounding electrode conductor from inverter to grounding electrode shall be a
minimum of bare copper armor sheathed cable and sized for the largest conductor
supplied by the system. CEC 250.64(b), 250.166(b).
12. The PV connection in the panel board shall be positioned at the opposite load end
from
the input feeder location or main circuit location: CEC 690.64(b)(7).
RACKING
1. All fasteners shall be corrosion resistant appropiate for site conditions. Connectors
shall be torqued per device specifications or engineering recommendations.
2. The method of attachment creates a unified structure to meet dead / wind load and
seismic requirements. Solar modules will be secured to the existing roof as specified
on the structural sheets. Existing roof equipment will not be affected by the PV
system.
3. All roofing repair must maintain existing class and type of roof and all work shall be
in accordance with the roofing manufacturer installation requirements.
..
..EPB
ECO PLANET BUILDERS
7127 Laurel Canyon Blvd., N.Hollywood, CA 91605
(818)427-4249
C0 PL.ANET BI.IJLCeRs License Number: 1031107
Contractor Signature:
PHOTOVOLTAIC GENERAL NOTES
WIRING
1. All wiring methods and installation practices shall conform to the N.E.C.,
local state codes and other local codes.
2. Exposed PV solar panel wiring will be USE-2 / RHW-2, 90 °C, wet rated, and
UV resistant. All exposed cables, such module leads, shall be secured with
mechanical or other sunlight resistant means.
3. All grounded conductors are white and equipment grounding conductors are
green or bare. (NEC 200-6).
4. Flexible metal conduit is generally suitable for installation in dry locations
(NEC 348.12) should it be employed, supports will be no more than 12 inches
from boxes (junction box, cabinets, or conduit fittings and no more than
54 inches apart (NEC 348.30).
5. Liquid tight flexible metal conduit is generally suitable for installation in wet
and dry locations , should it be employed, supports will be no more
than 12 inches from boxes (junction box, cabinets, or conduit fitting) and no more
than 54" apart (NEC 530.30).
6. Liquid tight flexible metal conduit is generally suitable for installation in wet
and dry locations, should it be employed, supports will be no more
than 12 inches from boxes (junction box, cabinets, or conduit fitting) and no more
than 36" apart (NEC 356.30).
7. Unless marked as UV resistant, PVC is not approved for installation in locations
subjected to direct sunlight and shall not be employed in any such location.
8. Long straight conduit runs, 100 feet or more, shall have expansion fittings.
9 If used, all wire nuts are to be suitable for theirs intended application. Where
installed in a moisture prone environment, wire nuts shall be
equivalent ideal blue, and shall be installed per manufactures
specifications by a qualified / certified person.
10. Fuses and wires subject to transformer inrush current shall be sized accordingly.
11.All DC materials shall be listed for 600V DC.
12. The Photovoltaic Source Circuits and Photovoltaic Output Circuits of this
proposed solar system shall not be contained in the same raceway, cable tray, cable
outlet box, junction box, or other similar fitting as feeders or branch circuits of
other systems unless the conductors of the different systems are separated by
a partition or are connected together.
13. Connectors to be torqued per devise listing or manufactures specifications.
14. Split bolts/ splices/ connectors shall be insulated with approved means. UL
listed electrical tape alone is not suitable as the only insulation means.
Follow manufactures instructions for application of insulating product.
15. AC wiring shall be cu. wire rated for 600V.
16. Use listed bridgeport raintight connectors as available. Like product may be
substituted so long as it is listed for its intended purpose. Seal all other electrical
connections with water resistant caulking or silicone.
17. Protect USE-2 / RHW-2 from sharp or other suitable means.
18. Label combiner box wiring red for positive, white for negative, and green for
grounded
conductor.
19. A field wiring larger than 6 AWG that is not color coded shall be tagged at both
ends with permanent wire markers to identified polarity and ground.
(See Electrical diagram and electrical detail for more grounding information).
20. Only one connection to DC circuits and one connection to AC circuits will be used for
system grounding (NEC 250.21) both the AC and DC ground will be referenced to the
same point.
21. Equipment grounding conductors and sys. grounding conductors will have as short a
distance to ground as possible and a minimum number of turns.
22. Non-current carrying metal parts shall be checked for proper grounding, noting that
terminal lugs bolted on an enclosures' finished surface may be insulated
because of the paint/finish, pain/finish at point of contact shall be properly removed
and repaired when necessary.
23. Modules shall be grounded with equipment grounding conductors bonded
to a location approved by the manufacturer with a mean of bonding
listed for this purpose.
24. The connection to the module or panel of this proposed solar electric system shall
be arranged so that the removal of a module or a panel from the photovoltaic
source circuit does not interrupt a grounded conductor to another
photovoltaic source circuit, sets of modules interconnected as systems rated
at S0V or less with or without blocking diodes, and having a single overcurrent
protection device shall be labeled as a single source circuit.
25. Grounding system components shall be listed for their purpose, included but not
limited to ground rods, grounding lugs, grounding clamps, etc. Grounding
devices exposed to the environment shall be rated for direct burial or listed for their
intended purpose.
PROJECT NAME
CARLOS/LUZ GUILLEN
624 E 3 RD ST, SAN TA AN A, CA 92701
PROTECTION
1. Photovoltaic inverters shall be equipped with DC ground fault protection to reduce fire
hazards. Inverters are also equipped with anti-islanding circuitry.
2. Circuits, over current devices, and blocking diodes shall be permitted on the
photovoltaic side of the photovoltaic disconnection means.
3. Means shall be provided to disconnect equipment such as inverters, batteries,
charge controllers, and the like from all ungrounded conductors of all sources, if the
equipment is energized from more than one source, the disconnecting means shall be
grouped and identified.
4. A simple disconnecting means shall be permitted for the combined ac output of one
or more inverters in an interactive system.
5. Disconnecting means shall be provided to disconnect a fuse from all sources of
supply if the fuse is energized from both direction and is accessible to other than
qualified persons. Such a fuse in a photovoltaic source circuit shall be capable
of being disconnected independently of fuses in other photovoltaic source circuits.
6. Means shall be provided to disconnect all current carrying conductors of the
photovoltaic power source from all other conductors in the building.
7. Where a circuit grounding connection is not designed to be automatically interrupted
as
part of the ground fault protection system required by 690.5, a switch or circuit
breaker used as a disconnecting means shall not have a pole in the grounded
conductor.
8. The grounded conductor may have a bolted or terminal disconnecting means to allow
maintenance or troubleshooting by qualified personnel.
9. The disconnecting means shall not be required to be suitable as service
equipment and shall be rated in accordance with section 690.
LABELS
1. Required safety signs and labels shall be permanently attached by adhesive or other
mechanical means. Labels shall comply with Article 690 of the NEC or other applicable
state and local codes. See labels and marking page for more information.
2. Any switch, fuses, or circuit breakers that can be energized in either direction shall be
labeled as follows:
WARNING:
ELECTRICAL SHOCK HAZARD. DO NOT
TOUCH THE TERMINALS.
TERMINALS ON BOTH THE LINE AND
LOAD SIDE MAY BE
ENERGIZED IN THE OPEN POSITION.
3. This photovoltaic system will be equipped with a DC disconnect which will be labeled
as follows:
PHOTOVOLTAIC DISCONNECT MEANS
DC DISCONNECT
4. This photovoltaic system will be equipped with an AC disconnect which will be labeled
as follows:
PHOTOVOLTAIC DISCONNECTING MEANS
AC DISCONNECT
5. A marking specifying the photovoltaic power source rated as follows shall be proved
at
an accessible location at the disconnecting means for the power source.
6. Permanent labels shall be provided. No sharpie marking will be allowed within any
main service panel or Sub-Panel.
7. Marking shall have red background.
8. White lettering minimum 3/8" letter height and all capital letters "Arial" or similar font.
9. Reflective weather resistant material suitable for the environment (durable adhesive)
materials must meet this requirements.
10. Marking is required in all interior and exterior DC conduit, raceways, enclosures, cable
assemblies, and junction boxes to alert the fire service to avoid cutting them.
11. Marking shall be placed every 10 feet, at turns and above and/ or penetrations,
and at all DC combiner and junction boxes.
PV installation shall comply with 2019 CEC, 2019 CFC, 2019 CRC (or CBC where
applicable), 2019 CGBSC, 2019 CEnC and local jurisdiction code requirements.
PROJECT INFORMATION
NAME: CARLOS/LUZ GUILLEN
ADDRESS: 624 E 3RD ST, SANTA ANA, CA 92701
APN / AHJ: 39848209
CONTRACTOR INFORMATION
CONTRACTOR: ECO PLANET BUILDERS
ADDRESS: 7127 Laurel Canyon Blvd., N.Hollywood, CA 91605
PHONE: (818)427-4249
LICENSE#: 1 031107
SYSTEM SPECIFICATIONS
SIZE (kW):
MODULE:
INVERTER:
13
13
4.485
Mission Solar MSE345SX5T
Enphase IQ7Plus-72-2-US
SCOPE OF WORK
INSTALL
13 ROOF MOU NTE D PV SOLAR MODULES,
13 Enphase IQ7Plus-72-2-US Inverter
TITLE
A SHEETS
E SHEETS
S SHEETS
MAIN PANE L UPG RADE
TABLE OF CONTENTS
GEN ERAL NOTES & PROJ ECT INFO
ARCHITECHURAL
ELECTRICAL
STRUCTURAL
4.485 kW-DC 4.053 kW-AC Photovoltaic System Page: TITLE
Drawn By: VS. COVER PAGE Date: 5/26/22 Revision: O
BLDG # 101111693
ELECT # 20177150
ISSUED: 10/12/2022
624 E 3rd St
10/12/22
624 E 3rd St
10/12/22
624 E 3rd St
10/12/22
Expedited Permit Process for PV Systems - Micro-Inverter1
Expedited Permit Process for PV Systems
Micro-Inverter
The Solar America Board for Codes and Standards (Solar ABCs) Expedited Permit Pro-
cess provides a means to differentiate systems that can be permitted quickly and easily
due to their similarity with the majority of small-scale PV systems. Those systems with
unique characteristics may be handled with small additions to this Expedited Permit
Process or may require much more information, depending on the uniqueness of the
installation.
The following pages contain forms for the Micro-Inverter to use with the Expedited Per-
mit Process. The Standard String, AC Module, and Supply-Side Connection forms
are also available as interactive PDF files at www.solarabcs.org/permitting. In jurisdic-
tions that have adopted the Expedited Permit Process for PV Systems, these forms can
be filled out electronically and submitted in either printed form and via email. An elec-
tronic format is used so that the supplied information is standardized and legible for the
local jurisdiction.
624 E 3rd St
10/12/22
Expedited Permit Process for PV Systems — Micro-Inverter2
Expedited Permit Process for Small-Scale PV Systems
Micro-Inverter
The information in this guideline is intended to help local jurisdictions and contractors identify when PV system installations
are simple, needing only a basic review, and when an installation is more complex. It is likely that 50%-75% of all residential
systems will comply with these simple criteria. For projects that fail to meet the simple criteria, resolution steps have been
suggested to provide as a path to permit approval.
Required Information for Permit:
1. Site plan showing location of major components on the property. This drawing need not be exactly to scale, but it
should represent relative location of components at site (see supplied example site plan). PV arrays on dwellings
with a 3’ perimeter space at ridge and sides may not need separate fire service review.
2. Electrical diagram showing PV array configuration, wiring system, overcurrent protection, inverter, disconnects,
required signs, and ac connection to building (see supplied standard electrical diagram).
3. Specification sheets and installation manuals (if available) for all manufactured components including, but not
limited to, PV modules, inverter(s), combiner box, disconnects, and mounting system.
Step 1: Structural Review of PV Array Mounting System
Is the array to be mounted on a defined, permitted roof structure? l Yes l No
If No due to non-compliant roof or a ground mount, submit completed worksheet for the structure WKS1.
Roof Information:
1. Is the roofing type lightweight (Yes = composition, lightweight masonry, metal, etc…)__________________________
____________________________________________________________________________________________________
If No, submit completed worksheet for roof structure WKS1 (No = heavy masonry, slate, etc…).
2. Does the roof have a single roof covering? l Yes l No
If No, submit completed worksheet for roof structure WKS1.
3. Provide method and type of weatherproofing roof penetrations (e.g. flashing, caulk).____________________________
Mounting System Information:
1. Is the mounting structure an engineered product designed to mount PV modules with no more than an 18” gap
beneath the module frames? l Yes l No
If No, provide details of structural attachment certified by a design professional.
2. For manufactured mounting systems, fill out information on the mounting system below:
a. Mounting System Manufacturer ___________Product Name and Model#________________________________
b. Total Weight of PV Modules and Rails ___________lbs
c. Total Number of Attachment Points____________
d. Weight per Attachment Point (b÷c)_________________lbs (if greater than 45 lbs, see WKS1)
e. Maximum Spacing Between Attachment Points on a Rail ______________inches (see product manual for
maximum spacing allowed based on maximum design wind speed)
f. Total Surface Area of PV Modules (square feet)_________________ ft 2
g. Distributed Weight of PV Module on Roof (b÷f)_______________ lbs/ft2
If distributed weight of the PV system is greater than 5 lbs/ft2, see WKS1.
Step 2: Electrical Review of PV System (Calculations for Electrical Diagram)
In order for a PV system to be considered for an expedited permit process, the following must apply:
1. PV modules, utility-interactive inverters, and combiner boxes are identified for use in PV systems.
2. The PV array is composed of 4 series strings or less per inverter.
3. The total inverter capacity has a continuous ac power output 13,440 Watts or less
4. The ac interconnection point is on the load side of service disconnecting means (690.64(B)).
5. One of the standard electrical diagrams (E1.1, E1.1a, E1.1b, or E1.1c) can be used to accurately represent the PV
system. Interactive PDF diagrams are available at www.solarabcs.org/permitting.
Fill out the standard electrical diagram completely. A guide to the electrical diagram is provided to help the applicant
understand each blank to fill in. If the electrical system is more complex than the standard electrical diagram can effectively
communicate, provide an alternative diagram with appropriate detail.
624 E 3rd St
10/12/22
Ex
p
e
d
i
t
e
d
P
e
r
m
i
t
P
r
o
c
e
s
s
f
o
r
P
V
S
y
s
t
e
m
s
3
Micro-Inverter Site Plan
ECO PLANET BUILDERS INC.
CARLOS/LUZ GUILLEN7127 LAUREL CANYON BLVD.
NORTH HOLLYWOOD, CA. 91605 624 E 3RD ST. SANTA ANA 92701
818-962-5874 4.053
624 E 3rd St
10/12/22
Ex
p
e
d
i
t
e
d
P
e
r
m
i
t
P
r
o
c
e
s
s
f
o
r
P
V
S
y
s
t
e
m
s
4
Micro-Inverter Electrical Diagram
Contractor Name,
Address and Phone:
One-Line Standard Electrical Diagram
for Micro-Inverter PV Systems
Site Name:
Site Address:
System AC Size:
SIZE FSCM NO DWG NO REV
E1.1a
SCALE NTS Date: SHEET
Drawn By:
Checked By:
DESCRIPTION OR CONDUCTOR TYPE
USE-2 or PV WIRE
GEC EGC X ALL THAT APPLY
EXTERIOR CABLE LISTED W/ INV.
THWN-2 or XHHW-2 or RHW-2
GEC EGC X ALL THAT APPLY
NO DC GEC IF 690.35 SYSTEM
THWN-2 or XHHW-2 or RHW-2
GEC EGC X ALL THAT APPLY
TAG
1
2
3
4
5
CONDUIT AND CONDUCTOR SCHEDULE
COND.
GAUGE
MFG
MFG
NUMBER OF
CONDUCTORS
MFG Cable
MFG Cable
CONDUIT
TYPE
N/A
N/A
N/A
SAME
SAME
CONDUIT
SIZE
N/A
N/A
N/A
SAME
SAME
DESCRIPTION
PV DC or AC MODULE
DC/AC INVERTER (MICRO)
J-BOX (IF USED)
PV ARRAY
AC COMB. PANEL (IF USED)
GEN METER (IF USED)
AC DISCONNECT (IF USED)
SERVICE PANEL
TAG
1
2
3
4
5
6
7
8
PART NUMBER NOTES
FOR UNUSED MODULES
PUT "N/A in BLANK ABOVE
1
1
3
2
3
EQUIPMENT SCHEDULE
2
_____
MICRO-INVERTERS
IN BRANCH-
CIRCUIT
MOD
____
DC
AC
MOD
____
DC
AC
MOD
____
DC
AC
MOD
____
DC
AC
MOD
____
DC
AC
MOD
____
DC
AC
J-BOX
4
AC DISCO
M
BUILDING
GROUNDING
ELECTRODE
G
M
UTILITY
SERVICE
MAIN SERVICE PANEL
MAIN
OCPD
INVERTER
OCPD
6
7
8
5
4
5
G
SEE GUIDE APPENDIX D FOR
INFORMATION ON MODULE AND
ARRAY GROUNDING
AC COMBINER
PANEL
G
____
MICRO-INVERTERS
IN BRANCH-
CIRCUIT
ECO PLANET BUILDERS INC.
7127 LAUREL CANYON BLVD.
NORTH HOLLYWOOD, CA. 91605
CARLOS/LUZ GUILLEN
4.053
624 E 3RD ST. SANTA ANA 92701
818-962-5874
624 E 3rd St
10/12/22
Ex
p
e
d
i
t
e
d
P
e
r
m
i
t
P
r
o
c
e
s
s
f
o
r
P
V
S
y
s
t
e
m
s
5
Contractor Name,
Address and Phone:
Notes for One-Line Standard Electrical
Diagram for Single-Phase PV Systems
Site Name:
Site Address:
System AC Size:
SIZE FSCM NO DWG NO REV
E1.2a
SCALE NTS Date: SHEET
Drawn By:
Checked By:
MAX POWER-POINT CURRENT (IMP)
MAX POWER-POINT VOLTAGE (VMP)
OPEN-CIRCUIT VOLTAGE (VOC)
SHORT-CIRCUIT CURRENT (ISC)
MAX SERIES FUSE (OCPD)
MAXIMUM POWER (PMAX)
MAX VOLTAGE (TYP 600VDC)
VOC TEMP COEFF (mV/oC or %/oC )
IF COEFF SUPPLIED, CIRCLE UNITS
MODULE MAKE
MODULE MODEL
PV MODULE RATINGS @ STC (Guide Section 5)
MAX DC VOLT RATING
MAX POWER @ 40oC
NOMINAL AC VOLTAGE
MAX AC CURRENT
MAX OCPD RATING
INVERTER MAKE
INVERTER MODEL
INVERTER RATINGS (Guide Section 4)
1) IF UTILITY REQUIRES A VISIBLE-BREAK SWITCH, DOES THIS SWITCH MEET THE
REQUIREMENT? YES NO N/A
2) IF GENERATION METER REQUIRED, DOES THIS METER SOCKET MEET THE
REQUIREMENT? YES NO N/A
3) SIZE PHOTOVOLTAIC POWER SOURCE (DC) CONDUCTORS BASED ON MAX
CURRENT ON NEC 690.53 SIGN OR OCPD RATING AT DISCONNECT
4) SIZE INVERTER OUTPUT CIRCUIT (AC) CONDUCTORS ACCORDING TO INVERTER
OCPD AMPERE RATING. (See Guide Section 9)
5) TOTAL OF ______ INVERTER OUTPUT CIRCUIT OCPD(s), ONE FOR EACH MICRO-
INVERTER CIRCUIT. DOES TOTAL SUPPLY BREAKERS COMPLY WITH 120% BUSBAR
EXCEPTION IN 690.64(B)(2)(a)? YES NO
NOTES FOR INVERTER CIRCUITS (Guide Section 8 and 9):
1.) LOWEST EXPECT AMBIENT TEMPERATURE BASED ON ASHRAE MINIMUM MEAN
EXTREME DRY BULB TEMPERATURE FOR ASHRAE LOCATION MOST SIMILAR TO
INSTALLATION LOCATION. LOWEST EXPECTED AMBIENT TEMP ____oC
2.) HIGHEST CONTINUOUS AMBIENT TEMPERATURE BASED ON ASHRAE HIGHEST
MONTH 2% DRY BULB TEMPERATURE FOR ASHRAE LOCATION MOST SIMILAR TO
INSTALLATION LOCATION. HIGHEST CONTINUOUS TEMPERATURE ____oC
2.) 2009 ASHRAE FUNDAMENTALS 2% DESIGN TEMPERATURES DO NOT EXCEED
47oC IN THE UNITED STATES (PALM SPRINGS, CA IS 44.1 oC). FOR LESS THAN 9
CURRENT-CARRYING CONDUCTORS IN ROOF-MOUNTED SUNLIT CONDUIT AT
LEAST 0.5" ABOVE ROOF AND USING THE OUTDOOR DESIGN TEMPERATURE OF
47oC OR LESS (ALL OF UNITED STATES),
a) 12 AWG, 90 oC CONDUCTORS ARE GENERALLY ACCEPTABLE FOR MODULES
WITH Isc OF 7.68 AMPS OR LESS WHEN PROTECTED BY A 12-AMP OR SMALLER
FUSE.
b) 10 AWG, 90oC CONDUCTORS ARE GENERALLY ACCEPTABLE FOR MODULES
WITH Isc OF 9.6 AMPS OR LESS WHEN PROTECTED BY A 15-AMP OR SMALLER
FUSE.
NOTES FOR ARRAY CIRCUIT WIRING (Guide Section 6 and 8 and Appendix E):
OCPD = OVERCURRENT PROTECTION DEVICE
NATIONAL ELECTRICAL CODE®REFERENCES
SHOWN AS (NEC XXX.XX)
NOTES FOR ALL DRAWINGS:
SIGNSSEE GUIDE SECTION 7
SIGN FOR DC DISCONNECT
SIGN FOR INVERTER OCPD AND AC
DISCONNECT (IF USED)
No sign necessary since 690.51
marking on PV module covers
needed information
AC OUTPUT CURRENT
NOMINAL AC VOLTAGE
SOLAR PV SYSTEM
AC POINT OF CONNECTION
THIS PANEL FED BY MULTIPLE
SOURCES (UTILITY AND SOLAR)
Notes for Micro-Inverter Electrical Diagram
ECO PLANET BUILDERS INC.
7127 LAUREL CANYON BLVD.
NORTH HOLLYWOOD, CA. 91605
818-962-5874
CARLOS/LUZ GUILLEN
624 E 3RD ST. SANTA ANA 92701
4.053
624 E 3rd St
10/12/22
624 E. 3RD ST.
SANTA ANA, CA 92701
GUILLEN, CARLOS
Prepared For:
ECO PLANET BUILDERS, INC.
7127 LAUREL CANYON BLVD.
N. HOLLYWOOD, CA 91605
(818) 427-4249
Design Criteria
1- Code: CALIFORNIA BLDG CODE 2019 / ASCE 7-16
2 - Wind: 95 MPH, Exposure: B
3 - Wood Species: DF-L No. 2 (SG = 0.5 )
Notice: Use restrictions of these calculations.
The attached Calculations are valid only when bearing original signature hereon.
Contractor/Client to verify existing dimensions/conditions prior to construction
& solar racking is installed per manufacturer span requirements.
The use of these calculations is solely intended for the above mentioned project.
1-844-PV ELITE | info@yoursolarplans.com
3000 E. Birch Street Suite 201 | Brea CA 92821
6/13/2022
Structural Calculations for
SOLAR POWER SYSTEM CONNECTION CHECK AT:
Job:
624 E 3rd St
10/12/22
012314452272899
711 !1"1#$ %33&80'33&( !%)22 &*02 +34'(,%048-3./4
.9/4
9'4&02 /4
1.9 214
23456789:;5<4=>;9
?@@53AAB 048-3.5.95
9'4&02 51.9
C;;5@>94=3AB 33&80'33&5)22 &*02 +34'
DE3F4=>;9B 24&G
H><3A=4<IB 4044)00)232 *72874&*&'J
K4L45@HMI3B N
?2CDOPQ R
ST2 0)U,00V
ST4+)U,&2 V
ST+0)U,&&V
ST2 00)U,*2 V
SW
,!T *'V
SW
,!TT '+V
SW
,!TTT 2 04V
SW
,!TX 2 00V
?2CDOPQ Y
ST2 0)U,&4V
ST4+)U,&'V
ST+0)U,*+V
ST2 00)U,'2 V
SW
,!T 2 00 V
SW
,!TT 22 0 V
SW
,!TTT)TX 22 +V
?2CDOPYZ
9.
-&)0+N.,,*+V
[\]^]_`ab_cdecfgb]e\]^]hiji[^]ka]fbgdl_bgb]m^amfgagn]den]db_bmb\]oga`]_m^gdle]acd]gbcmdacd]_nge]e`^cdpb\]q`caecdp
fme]gemrbcmdr^mf]__st_]^__\m`aefmdkc^ngdlm`br`bmqbgcd]ek^mnb\c_bmmaucb\b\]amfgav`b\m^cblwgocdpx`^c_ecfbcmdq]km^]
r^mf]]ecdpucb\e]_cpds
y>A6E4><35
,, ,GVz,9.
-&,,,,# ,,!,{,9.
-&5
,,, ,, #,,G, ,|V,,5#,,# ,} ,
, #,,,,G,5z,#,, ! !,~-7,,,#),,,!
,5,, !,,V,z,!#VGG,#,,,,,##),
,,!
,5!!,5,V,5, #,! ,,}V,G #
N ,,GV,,,#,,, ,z,,,59
V,,
G,V, ,,,,, ,,, ,G,G #
V,,,}Vz,GG5 ,!,,, ,,G, 9
,
,,,GGV, ,,!V,GV,,G, 5z!,},,,W# ,!,
,G, G,5,G,G,,,GG, ,,! !,, G,
,z,#,,1,G,GVGV#,,V, !GV,1,G,G
#,,,V z ,!z,! !,,, ,G !,z ,,G,
624 E 3rd St
10/12/22
ASCE 29.4.4 Rooftop Solar Panels Parallel to the Roof Surface on Buildings of All Heights and Roof Slopes.
Roof Slope = 17 °
Roof Shape Gable
Tributary Width s = 4.00 ft
Tributary Length l = 2.87 ft
Effective Area A e = 6.92 ft2
Height of Structure h = 15 ft
Wind Speed V = 95 mph
Exposure Category B
Building Width B = 30 ft
Building Length L = 60 ft
Zone Width a = 3 ft
Elevation Height zg = 127 ft
Wind Directionality Kd = 0.85
Topography Factor Kt = 1.00
Ground Elevation Factor Ke = 1.00
Velocity Pressure Exposure Coefficient Kz = 0.70
Velocity Pressure q z = 0.00256KzKztKdKeV2 = 13.70 psf
Solar Array Pressure Equalization a = 0.80
Array Edge Factor E = 1.50
Zone GCp p = qz(GCp)(E)(a)
3 - -
3r 3.60 -59.16
3e 3.00 -49.30
2 - -
2r 3.00 -49.30
2e - -
2n 3.00 -49.30
1 - -
1' - -
624 E 3rd St
10/12/22
LAG SCREW ANALYSIS
Loads
Wind Pressures qz = -49.30 psf
Solar Panel Load QD = 3 psf
Panel Length l = 5.735 ft
Panel Width b 3.458 ft
Attachment Spacing s = 4 ft
Portrait
Tributary Area At = 11.47 ft2
Wind Load P W = qz * At = -566 lbs
Dead Load P D = Q D * At = 34.409 lbs
Uplift Pa = 0.6 P D + 0.6 Pw = -319 lbs
Landscape
Tributary Area At = b * s = 6.916 ft2
Wind Load P W = qz * At = -341 lbs
Dead Load P D = Q D * At = 20.748 lbs
Uplift Pa = 0.6 P D + 0.6 Pw = -192 lbs
Lag Screw 5/16" x 5"
Specific Gravity of Lumber SG = 0.50 (Douglas Fir-Larch)
Diameter of Lag Screw D = 5/16 in
Withdraw Design /in 1800*SG 3/2 *D 3/4 = 266 lbs/in
Depth of Embedment lp = 2.50 in
Total Nominal Withdrawal Value W = W * l p = 665 lbs
Load Duration Factor CD = 1.6
Withdrawal Design Value W' = W * C D = 1064 lbs
Demand Capacity Ratio DCR = Pa / W' = 0.30 < 1 OK
624 E 3rd St
10/12/22
ASCE 30.3.2 Design Wind Pressure Beam/ Top Chord Check
Roof Slope = 17 °
Roof Shape Gable
Tributary Width s = 2.00 ft
Tributary Length L = 11.19 ft
Effective Area A = L ( MAX [ s , L/3] ) = 42 ft2
Height of Structure h = 15 ft
Wind Speed V = 95 mph
Exposure Category B
Building Width B = 30 ft
Building Length L = 60 ft
Zone Width a = 3 ft
Elevation Height zg = 127 ft
Wind Directionality Kd = 0.85
Topography Factor Kt = 1.00
Ground Elevation Factor Ke = 1.00
Velocity Pressure Exposure Coefficient Kz = 0.70
Velocity Pressure q z = 0.00256KzKztKdKeV 2 = 13.70 psf
Internal Pressure Coefficient (GCpi) = -0.18
Zone GCp p = q z [(GCp) - (Gcpi)]
3 - -
3r 2.97 -43.08
3e 2.74 -39.93
2 - -
2r 2.74 -39.93
2e - -
2n 2.74 -39.93
1 - -
1' - -
624 E 3rd St
10/12/22
Beam/ Top Chord Check Lumber:
Moment Demand
# of Attachment per Rafter N A = Span : Orientation
Lenght (ft) :
Dead Load Roof Material: Q D = psf
Live Load QLr = psf
Wind Load p = psf
Snow Load QS = psf
Rafter Spacing s = in
Wind Load, Portrait Portrait UL =
Wind Load, Landscape Landscape U W =
Linear Dead Load wd = plf
Live Load wLr = plf Start ft Start ft
End ft End ft
Snow Load ws = plf Start ft Start ft
End ft End ft
Ma, Moment
D lb-ft
D+Lr lb-ft
D+S lb-ft
0.6D+0.6W lb-ft
D+0.45W+0.75Lr lb-ft
D+0.45W+0.75S lb-ft
Moment Capacity Framing Member Size Lumber Grade : DF-L No. 2
C M = 1 Ct = 1 Cr= CF = fb = psi C fu =C i =
Breadth b = in
Depth d = in
Section Modulus Sx = bd 2 / 6 = in3
Bending Stress Capacity Fb = CM * C t * Cr * C F * fb = psi Table 4.3.1 NDS 2015
Deflection Limit E = ksi I = in4
Transient Deflection in
Transient Deflection Allowed > [OKAY]
Total Deflection in
Total Deflection Allowed > [OKAY]
-39.93
DF-L No. 2
4 j lj (ft) pd,j (lbs) pw,j (lbs) ps,j (lbs)
Landscape
1 0.7 20.7 -276 0.0
2.8 20.7 -276
-458 0.0
4 8.4 34.4 -458 0.0
0.0
2.19 8.00 0.00 0.00 1.00
Portrait
3 4.2 34.4
10.00
1 2 3 4 Eave
2
0.0
0.0 0.0 0.0
0.0
0 0.0 0.0 0.0 0.0
0 0.0 0.0 0.0
0.0
0 0.0 0.0 0 0.0
Portrait
0 0.0 0.0 0
0.0
20
40
0.0 0.0 0.0 0.0
0 0.0
Portrait
0
0.0 20.748 -276 0
0
0.0
0
0
0
0
0.0
Portrait
0
0.0
Portrait
0 0.0 0.0
AT (ft 2)
11.47
6.916
pd (lbs)
34.409 -458
p w (lbs) ps (lbs)
0
9.19
2x4
1.15 1.5
11.19
9.19
11.19
900
1.50
3.50
191
191
191
426
214
214
DCR
0.9 1397 psi D 748 psi 0.54
3.06
1553
CD Fb' = C D * F b ASD Load Ma * S x
1.15 1785 psi D+S 748 psi 0.42 OKAY
OKAY
1.25 1941 psi D+Lr 747 psi 0.39 OKAY
1.6 2484 psi
0.322
298 120
1600 5.36
0.6D+0.6W 1668 psi 0.67 OKAY
1.0 1
20
0.00
24
Comp
0.293
328 180
1.6 2484 psi D+0.45W+0.75S 840 psi 0.34 OKAY
1.6 2484 psi D+0.45W+0.75Lr 840 psi 0.34 OKAY
ൌ ሺ െ ሻ െ െ െ
‐600.0
‐400.0
‐200.0
0.0
200.0
400.0
0.000 2.000 4.000 6.000 8.000 10.000 12.000
624 E 3rd St
10/12/22
EISMIC WEIGHT COMPARISON / ANALYSIS - (PER CEBC 2019 Part 10 Chapter 5 Section 502.5)
PV System Weight
Module Model Mission Solar
Panel Weight Wpanel = 44.8 lbs
Number of Panels NPV = 13
Total PV System Weight W PV = Wpanel * NPV = 582.4 lbs
Existing Roof Weight
Roof Weight QD =10.0 psf
Building Length Lbuild =60 ft
Building Width W build =30 ft
Roof Area Abuild =1800 ft2
Building Perimeter Pbuild = 180 ft
Wall Height ht = 8 ft
Wall weight Qwall = 15 psf
Interior wall weight Qint = 10 psf
Roof Load Wfloor = Abuild * QD = 18000 lbs
Wall LoadWwall = ht /2 * Qwall * Pbuild + Abuild * Qint /2 = 19800 lbs
Total Story Weight Wbuild = Wfloor + Wwall = 37800 lbs
Percentage Weight Increase WPV / Wbuild = 1.54%< 10% OKAY
624 E 3rd St
10/12/22
624 E 3rd St
10/12/22
624 E 3rd St
10/12/22
624 E 3rd St
10/12/22
624 E 3rd St
10/12/22
624 E 3rd St
10/12/22
624 E 3rd St
10/12/22
To whom it may concern
As the homeowner of the property at: 624 East 3rd St Santa Ana CA 92701, I hereby confirm that the
solar installer company Eco Planet Builders Inc. has closed a contract with myself to complete the work
and permitting of a roof mounted solar system for me. I give them permission to pull permits and
conduct the install at my above-mentioned residence. Thank you
Carlos & Luz Guillen
Date ignature
Date Signature
624 E 3rd St
10/12/22
624 E 3rd St
10/12/22
624 E 3rd St
10/12/22
624 E 3rd St
10/12/22
624 E 3rd St
10/12/22
624 E 3rd St
10/12/22
624 E 3rd St
10/12/22
624 E 3rd St
10/12/22
624 E 3rd St
10/12/22
624 E 3rd St
10/12/22
624 E 3rd St
10/12/22
624 E 3rd St
10/12/22
624 E 3rd St
10/12/22
624 E 3rd St
10/12/22
624 E 3rd St
10/12/22
624 E 3rd St
10/12/22
624 E 3rd St
10/12/22
624 E 3rd St
10/12/22
624 E 3rd St
10/12/22
Rev: 7/15/2021
RESIDENTIAL
PHOTOVOLTAIC
CHECKLIST
SOL-01 CBC 2019
Solar Photovoltaic (PV) Checklist for Detached SINGLE FAMILY RESIDENCES Only
Instructions: The licensed contractor of record shall complete all sections, answer the ten questions and
sign the certification section below. A copy of this form shall be attached to each of TWO sets of plans, of
minimum 11” x 17” size. If answering NO to any of the questions, plan check shall be required.
Project Address:
Contractor Company Name:
Contractor License Number:
YES NO Are the following applicable to the proposed project?
1. Will the PV system layout provide the required three-foot wide clear access pathways
per Section 605.11 of the California Fire Code, and is this shown on the roof plan?
2. Will the PV system be installed on a roof having only one roofing layer with no
overlays?
3. Will the PV array be flush mounted to the existing roof so that the plane of the
modules (panels) are parallel to the plane of the roof?
4. Will the PV system weigh maximum 4 pounds per square feet or less?
5. Will the PV system be installed where the modules do not overhang any roof edges
(such as eaves, gabled ends, ridges and hips)?
6. Will the PV system be installed with a space of 2” minimum to 10” maximum between
the underside of modules and the surface of the roof?
7. Will the PV system be installed without using any ballast system or counter-weight
system?
8. Will the anchors be installed with a maximum horizontal anchor spacing of 6 feet
and is this maximum horizontal spacing shown on the plans?
9. Will the minimum 5/16” lag screws be installed with a minimum of 2-1/2 inch
embedment into roof rafters (with pre-drilled holes) and is this minimum embedment
shown on the plans?
10. Are ALL the structural pages of the plans stamped and signed by a California
licensed professional engineer? (including project specific site plan, PV layout,
anchorage spacing, anchorage details and manufacturer’s PV support information.)
I certify under penalty of perjury under the laws of the State of California that the above is true:
Print Name: Signature:
Phone Number: Date:
Email Address:
Planning & Building Agency
Building Safety Division
20 Civic Center Plaza
P.O. Box 1988 (M-19)
Santa Ana, CA 92702
(714) 647-5800
www.santa-ana.org
624 E 3RD ST. SANTA ANA CA 92701
ECO PLANET BUILDERS INC.
1031107
NIR LEVI
818-427-4249
INFO@ECOPLANETBUILDERS.COM
6/1/22
624 E 3rd St
10/12/22