Loading...
HomeMy WebLinkAbout624 E 3rd St - PlanGENERAL 1. All electrical work to be installed by a qualified licensed electrician and apprentices working under the direct supervision of the licensed contractor. 2. All solar modules shall be listed 1703 & CEC approved. All inverters shall be UL listed 1741 certified & CEC approved. All electrical components and materials shall be listed for its purpose and installed in a workman-like manner. All customer equipment shall meet appropriate NEMA standards. 3. All fabrication and manufacturing shall be performed by certified individuals in approved assembly and fabrication shops. 4. Prior to commencement of any work, the contractor shall notify the engineer of any discrepancies noted among site conditions, manufacturer recommendations or authority having jurisdiction (AHJ). 5. Contractor-initiated changes shall be submitted in writing to the engineer in the form of a "RFI" (Request for Information), prior to making any changes. Approved changes shall require a drawing revision to maintain control over the engineer approved design. 6. The electrical contractor is advised that all drawings and component manuals are to be understood prior to installation. The contractor is advised to have all switches in "off "position and the fuses removed prior to the installation of fuse-bearing components. 7. This proposed solar electric system is intended to operate in parallel with power received from the utility service provider. 8. Anti-islanding protection is requirement of UL 1741 and is intended to prevent the operation of the PV System when the utility grid is not operational. 9. Permission to operate the system is not authorized until final inspections and approvals are obtained from the local authority having jurisdiction and the local utility service provider. ELECTRICAL 1. PV installation shall comply with article 690 of 2017 NEC. 2. The inverter for the proposed solar electric system shall be identified for use in solar photovoltaic systems. All equipment shall be UL approved. 3. This system is intended to connect to the existing facility power system at one point. The point of common coupling (POCC). This connection shall be in compliance with the NEC article 690.64 "POINT OF CONNECTION". 4. All circuits shall have individual source circuit protection for testing and isolation. All combiner boxes shall have disconnecting means near the combiner for isolation and testing. 5. All disconnects and combiners shall be secured from unauthorized / unqualified personnel by locking location. 6.All disconnects, combiners, pull/ splice boxes and enclosures shall be listed for its purpose. 7. Equipment shall be installed in a secure area. Inverter performance may be affected if installed in direct sunlight. 8. DC array conductors are to remain outside of building prior to fused combiner box or fused DC disconnecting means. 9. Raceway for grounding electrode conductor shall be bonded at each end. 10.The DC grounding electrode conductor shall be bonded to the AC grounding electrode conductor to make a grounding electrode system according to CEC 250.52 and 250.53. The bonding conductor shall be no smaller than the largest grounding electrode conductor, either DC or AC, 690.47(c)(1) 11.Grounding electrode conductor from inverter to grounding electrode shall be a minimum of bare copper armor sheathed cable and sized for the largest conductor supplied by the system. CEC 250.64(b), 250.166(b). 12. The PV connection in the panel board shall be positioned at the opposite load end from the input feeder location or main circuit location: CEC 690.64(b)(7). RACKING 1. All fasteners shall be corrosion resistant appropiate for site conditions. Connectors shall be torqued per device specifications or engineering recommendations. 2. The method of attachment creates a unified structure to meet dead / wind load and seismic requirements. Solar modules will be secured to the existing roof as specified on the structural sheets. Existing roof equipment will not be affected by the PV system. 3. All roofing repair must maintain existing class and type of roof and all work shall be in accordance with the roofing manufacturer installation requirements. .. ..EPB ECO PLANET BUILDERS 7127 Laurel Canyon Blvd., N.Hollywood, CA 91605 (818)427-4249 C0 PL.ANET BI.IJLCeRs License Number: 1031107 Contractor Signature: PHOTOVOLTAIC GENERAL NOTES WIRING 1. All wiring methods and installation practices shall conform to the N.E.C., local state codes and other local codes. 2. Exposed PV solar panel wiring will be USE-2 / RHW-2, 90 °C, wet rated, and UV resistant. All exposed cables, such module leads, shall be secured with mechanical or other sunlight resistant means. 3. All grounded conductors are white and equipment grounding conductors are green or bare. (NEC 200-6). 4. Flexible metal conduit is generally suitable for installation in dry locations (NEC 348.12) should it be employed, supports will be no more than 12 inches from boxes (junction box, cabinets, or conduit fittings and no more than 54 inches apart (NEC 348.30). 5. Liquid tight flexible metal conduit is generally suitable for installation in wet and dry locations , should it be employed, supports will be no more than 12 inches from boxes (junction box, cabinets, or conduit fitting) and no more than 54" apart (NEC 530.30). 6. Liquid tight flexible metal conduit is generally suitable for installation in wet and dry locations, should it be employed, supports will be no more than 12 inches from boxes (junction box, cabinets, or conduit fitting) and no more than 36" apart (NEC 356.30). 7. Unless marked as UV resistant, PVC is not approved for installation in locations subjected to direct sunlight and shall not be employed in any such location. 8. Long straight conduit runs, 100 feet or more, shall have expansion fittings. 9 If used, all wire nuts are to be suitable for theirs intended application. Where installed in a moisture prone environment, wire nuts shall be equivalent ideal blue, and shall be installed per manufactures specifications by a qualified / certified person. 10. Fuses and wires subject to transformer inrush current shall be sized accordingly. 11.All DC materials shall be listed for 600V DC. 12. The Photovoltaic Source Circuits and Photovoltaic Output Circuits of this proposed solar system shall not be contained in the same raceway, cable tray, cable outlet box, junction box, or other similar fitting as feeders or branch circuits of other systems unless the conductors of the different systems are separated by a partition or are connected together. 13. Connectors to be torqued per devise listing or manufactures specifications. 14. Split bolts/ splices/ connectors shall be insulated with approved means. UL listed electrical tape alone is not suitable as the only insulation means. Follow manufactures instructions for application of insulating product. 15. AC wiring shall be cu. wire rated for 600V. 16. Use listed bridgeport raintight connectors as available. Like product may be substituted so long as it is listed for its intended purpose. Seal all other electrical connections with water resistant caulking or silicone. 17. Protect USE-2 / RHW-2 from sharp or other suitable means. 18. Label combiner box wiring red for positive, white for negative, and green for grounded conductor. 19. A field wiring larger than 6 AWG that is not color coded shall be tagged at both ends with permanent wire markers to identified polarity and ground. (See Electrical diagram and electrical detail for more grounding information). 20. Only one connection to DC circuits and one connection to AC circuits will be used for system grounding (NEC 250.21) both the AC and DC ground will be referenced to the same point. 21. Equipment grounding conductors and sys. grounding conductors will have as short a distance to ground as possible and a minimum number of turns. 22. Non-current carrying metal parts shall be checked for proper grounding, noting that terminal lugs bolted on an enclosures' finished surface may be insulated because of the paint/finish, pain/finish at point of contact shall be properly removed and repaired when necessary. 23. Modules shall be grounded with equipment grounding conductors bonded to a location approved by the manufacturer with a mean of bonding listed for this purpose. 24. The connection to the module or panel of this proposed solar electric system shall be arranged so that the removal of a module or a panel from the photovoltaic source circuit does not interrupt a grounded conductor to another photovoltaic source circuit, sets of modules interconnected as systems rated at S0V or less with or without blocking diodes, and having a single overcurrent protection device shall be labeled as a single source circuit. 25. Grounding system components shall be listed for their purpose, included but not limited to ground rods, grounding lugs, grounding clamps, etc. Grounding devices exposed to the environment shall be rated for direct burial or listed for their intended purpose. PROJECT NAME CARLOS/LUZ GUILLEN 624 E 3 RD ST, SAN TA AN A, CA 92701 PROTECTION 1. Photovoltaic inverters shall be equipped with DC ground fault protection to reduce fire hazards. Inverters are also equipped with anti-islanding circuitry. 2. Circuits, over current devices, and blocking diodes shall be permitted on the photovoltaic side of the photovoltaic disconnection means. 3. Means shall be provided to disconnect equipment such as inverters, batteries, charge controllers, and the like from all ungrounded conductors of all sources, if the equipment is energized from more than one source, the disconnecting means shall be grouped and identified. 4. A simple disconnecting means shall be permitted for the combined ac output of one or more inverters in an interactive system. 5. Disconnecting means shall be provided to disconnect a fuse from all sources of supply if the fuse is energized from both direction and is accessible to other than qualified persons. Such a fuse in a photovoltaic source circuit shall be capable of being disconnected independently of fuses in other photovoltaic source circuits. 6. Means shall be provided to disconnect all current carrying conductors of the photovoltaic power source from all other conductors in the building. 7. Where a circuit grounding connection is not designed to be automatically interrupted as part of the ground fault protection system required by 690.5, a switch or circuit breaker used as a disconnecting means shall not have a pole in the grounded conductor. 8. The grounded conductor may have a bolted or terminal disconnecting means to allow maintenance or troubleshooting by qualified personnel. 9. The disconnecting means shall not be required to be suitable as service equipment and shall be rated in accordance with section 690. LABELS 1. Required safety signs and labels shall be permanently attached by adhesive or other mechanical means. Labels shall comply with Article 690 of the NEC or other applicable state and local codes. See labels and marking page for more information. 2. Any switch, fuses, or circuit breakers that can be energized in either direction shall be labeled as follows: WARNING: ELECTRICAL SHOCK HAZARD. DO NOT TOUCH THE TERMINALS. TERMINALS ON BOTH THE LINE AND LOAD SIDE MAY BE ENERGIZED IN THE OPEN POSITION. 3. This photovoltaic system will be equipped with a DC disconnect which will be labeled as follows: PHOTOVOLTAIC DISCONNECT MEANS DC DISCONNECT 4. This photovoltaic system will be equipped with an AC disconnect which will be labeled as follows: PHOTOVOLTAIC DISCONNECTING MEANS AC DISCONNECT 5. A marking specifying the photovoltaic power source rated as follows shall be proved at an accessible location at the disconnecting means for the power source. 6. Permanent labels shall be provided. No sharpie marking will be allowed within any main service panel or Sub-Panel. 7. Marking shall have red background. 8. White lettering minimum 3/8" letter height and all capital letters "Arial" or similar font. 9. Reflective weather resistant material suitable for the environment (durable adhesive) materials must meet this requirements. 10. Marking is required in all interior and exterior DC conduit, raceways, enclosures, cable assemblies, and junction boxes to alert the fire service to avoid cutting them. 11. Marking shall be placed every 10 feet, at turns and above and/ or penetrations, and at all DC combiner and junction boxes. PV installation shall comply with 2019 CEC, 2019 CFC, 2019 CRC (or CBC where applicable), 2019 CGBSC, 2019 CEnC and local jurisdiction code requirements. PROJECT INFORMATION NAME: CARLOS/LUZ GUILLEN ADDRESS: 624 E 3RD ST, SANTA ANA, CA 92701 APN / AHJ: 39848209 CONTRACTOR INFORMATION CONTRACTOR: ECO PLANET BUILDERS ADDRESS: 7127 Laurel Canyon Blvd., N.Hollywood, CA 91605 PHONE: (818)427-4249 LICENSE#: 1 031107 SYSTEM SPECIFICATIONS SIZE (kW): MODULE: INVERTER: 13 13 4.485 Mission Solar MSE345SX5T Enphase IQ7Plus-72-2-US SCOPE OF WORK INSTALL 13 ROOF MOU NTE D PV SOLAR MODULES, 13 Enphase IQ7Plus-72-2-US Inverter TITLE A SHEETS E SHEETS S SHEETS MAIN PANE L UPG RADE TABLE OF CONTENTS GEN ERAL NOTES & PROJ ECT INFO ARCHITECHURAL ELECTRICAL STRUCTURAL 4.485 kW-DC 4.053 kW-AC Photovoltaic System Page: TITLE Drawn By: VS. COVER PAGE Date: 5/26/22 Revision: O BLDG # 101111693 ELECT # 20177150 ISSUED: 10/12/2022 624 E 3rd St 10/12/22 624 E 3rd St 10/12/22 624 E 3rd St 10/12/22 Expedited Permit Process for PV Systems - Micro-Inverter1 Expedited Permit Process for PV Systems Micro-Inverter The Solar America Board for Codes and Standards (Solar ABCs) Expedited Permit Pro- cess provides a means to differentiate systems that can be permitted quickly and easily due to their similarity with the majority of small-scale PV systems. Those systems with unique characteristics may be handled with small additions to this Expedited Permit Process or may require much more information, depending on the uniqueness of the installation. The following pages contain forms for the Micro-Inverter to use with the Expedited Per- mit Process. The Standard String, AC Module, and Supply-Side Connection forms are also available as interactive PDF files at www.solarabcs.org/permitting. In jurisdic- tions that have adopted the Expedited Permit Process for PV Systems, these forms can be filled out electronically and submitted in either printed form and via email. An elec- tronic format is used so that the supplied information is standardized and legible for the local jurisdiction. 624 E 3rd St 10/12/22 Expedited Permit Process for PV Systems — Micro-Inverter2 Expedited Permit Process for Small-Scale PV Systems Micro-Inverter The information in this guideline is intended to help local jurisdictions and contractors identify when PV system installations are simple, needing only a basic review, and when an installation is more complex. It is likely that 50%-75% of all residential systems will comply with these simple criteria. For projects that fail to meet the simple criteria, resolution steps have been suggested to provide as a path to permit approval. Required Information for Permit: 1. Site plan showing location of major components on the property. This drawing need not be exactly to scale, but it should represent relative location of components at site (see supplied example site plan). PV arrays on dwellings with a 3’ perimeter space at ridge and sides may not need separate fire service review. 2. Electrical diagram showing PV array configuration, wiring system, overcurrent protection, inverter, disconnects, required signs, and ac connection to building (see supplied standard electrical diagram). 3. Specification sheets and installation manuals (if available) for all manufactured components including, but not limited to, PV modules, inverter(s), combiner box, disconnects, and mounting system. Step 1: Structural Review of PV Array Mounting System Is the array to be mounted on a defined, permitted roof structure? l Yes l No If No due to non-compliant roof or a ground mount, submit completed worksheet for the structure WKS1. Roof Information: 1. Is the roofing type lightweight (Yes = composition, lightweight masonry, metal, etc…)__________________________ ____________________________________________________________________________________________________ If No, submit completed worksheet for roof structure WKS1 (No = heavy masonry, slate, etc…). 2. Does the roof have a single roof covering? l Yes l No If No, submit completed worksheet for roof structure WKS1. 3. Provide method and type of weatherproofing roof penetrations (e.g. flashing, caulk).____________________________ Mounting System Information: 1. Is the mounting structure an engineered product designed to mount PV modules with no more than an 18” gap beneath the module frames? l Yes l No If No, provide details of structural attachment certified by a design professional. 2. For manufactured mounting systems, fill out information on the mounting system below: a. Mounting System Manufacturer ___________Product Name and Model#________________________________ b. Total Weight of PV Modules and Rails ___________lbs c. Total Number of Attachment Points____________ d. Weight per Attachment Point (b÷c)_________________lbs (if greater than 45 lbs, see WKS1) e. Maximum Spacing Between Attachment Points on a Rail ______________inches (see product manual for maximum spacing allowed based on maximum design wind speed) f. Total Surface Area of PV Modules (square feet)_________________ ft 2 g. Distributed Weight of PV Module on Roof (b÷f)_______________ lbs/ft2 If distributed weight of the PV system is greater than 5 lbs/ft2, see WKS1. Step 2: Electrical Review of PV System (Calculations for Electrical Diagram) In order for a PV system to be considered for an expedited permit process, the following must apply: 1. PV modules, utility-interactive inverters, and combiner boxes are identified for use in PV systems. 2. The PV array is composed of 4 series strings or less per inverter. 3. The total inverter capacity has a continuous ac power output 13,440 Watts or less 4. The ac interconnection point is on the load side of service disconnecting means (690.64(B)). 5. One of the standard electrical diagrams (E1.1, E1.1a, E1.1b, or E1.1c) can be used to accurately represent the PV system. Interactive PDF diagrams are available at www.solarabcs.org/permitting. Fill out the standard electrical diagram completely. A guide to the electrical diagram is provided to help the applicant understand each blank to fill in. If the electrical system is more complex than the standard electrical diagram can effectively communicate, provide an alternative diagram with appropriate detail. 624 E 3rd St 10/12/22 Ex p e d i t e d P e r m i t P r o c e s s f o r P V S y s t e m s 3 Micro-Inverter Site Plan                                                         ECO PLANET BUILDERS INC. CARLOS/LUZ GUILLEN7127 LAUREL CANYON BLVD. NORTH HOLLYWOOD, CA. 91605 624 E 3RD ST. SANTA ANA 92701 818-962-5874 4.053 624 E 3rd St 10/12/22 Ex p e d i t e d P e r m i t P r o c e s s f o r P V S y s t e m s 4 Micro-Inverter Electrical Diagram Contractor Name, Address and Phone: One-Line Standard Electrical Diagram for Micro-Inverter PV Systems Site Name: Site Address: System AC Size: SIZE FSCM NO DWG NO REV E1.1a SCALE NTS Date: SHEET Drawn By: Checked By: DESCRIPTION OR CONDUCTOR TYPE USE-2 or PV WIRE GEC EGC X ALL THAT APPLY EXTERIOR CABLE LISTED W/ INV. THWN-2 or XHHW-2 or RHW-2 GEC EGC X ALL THAT APPLY NO DC GEC IF 690.35 SYSTEM THWN-2 or XHHW-2 or RHW-2 GEC EGC X ALL THAT APPLY TAG 1 2 3 4 5 CONDUIT AND CONDUCTOR SCHEDULE COND. GAUGE MFG MFG NUMBER OF CONDUCTORS MFG Cable MFG Cable CONDUIT TYPE N/A N/A N/A SAME SAME CONDUIT SIZE N/A N/A N/A SAME SAME DESCRIPTION PV DC or AC MODULE DC/AC INVERTER (MICRO) J-BOX (IF USED) PV ARRAY AC COMB. PANEL (IF USED) GEN METER (IF USED) AC DISCONNECT (IF USED) SERVICE PANEL TAG 1 2 3 4 5 6 7 8 PART NUMBER NOTES FOR UNUSED MODULES PUT "N/A” in BLANK ABOVE 1 1 3 2 3 EQUIPMENT SCHEDULE 2 _____ MICRO-INVERTERS IN BRANCH- CIRCUIT MOD ____ DC AC MOD ____ DC AC MOD ____ DC AC MOD ____ DC AC MOD ____ DC AC MOD ____ DC AC J-BOX 4 AC DISCO M BUILDING GROUNDING ELECTRODE G M UTILITY SERVICE MAIN SERVICE PANEL MAIN OCPD INVERTER OCPD 6 7 8 5 4 5 G SEE GUIDE APPENDIX D FOR INFORMATION ON MODULE AND ARRAY GROUNDING AC COMBINER PANEL G ____ MICRO-INVERTERS IN BRANCH- CIRCUIT ECO PLANET BUILDERS INC. 7127 LAUREL CANYON BLVD. NORTH HOLLYWOOD, CA. 91605 CARLOS/LUZ GUILLEN 4.053 624 E 3RD ST. SANTA ANA 92701 818-962-5874 624 E 3rd St 10/12/22 Ex p e d i t e d P e r m i t P r o c e s s f o r P V S y s t e m s 5 Contractor Name, Address and Phone: Notes for One-Line Standard Electrical Diagram for Single-Phase PV Systems Site Name: Site Address: System AC Size: SIZE FSCM NO DWG NO REV E1.2a SCALE NTS Date: SHEET Drawn By: Checked By: MAX POWER-POINT CURRENT (IMP) MAX POWER-POINT VOLTAGE (VMP) OPEN-CIRCUIT VOLTAGE (VOC) SHORT-CIRCUIT CURRENT (ISC) MAX SERIES FUSE (OCPD) MAXIMUM POWER (PMAX) MAX VOLTAGE (TYP 600VDC) VOC TEMP COEFF (mV/oC or %/oC ) IF COEFF SUPPLIED, CIRCLE UNITS MODULE MAKE MODULE MODEL PV MODULE RATINGS @ STC (Guide Section 5) MAX DC VOLT RATING MAX POWER @ 40oC NOMINAL AC VOLTAGE MAX AC CURRENT MAX OCPD RATING INVERTER MAKE INVERTER MODEL INVERTER RATINGS (Guide Section 4) 1) IF UTILITY REQUIRES A VISIBLE-BREAK SWITCH, DOES THIS SWITCH MEET THE REQUIREMENT? YES NO N/A 2) IF GENERATION METER REQUIRED, DOES THIS METER SOCKET MEET THE REQUIREMENT? YES NO N/A 3) SIZE PHOTOVOLTAIC POWER SOURCE (DC) CONDUCTORS BASED ON MAX CURRENT ON NEC 690.53 SIGN OR OCPD RATING AT DISCONNECT 4) SIZE INVERTER OUTPUT CIRCUIT (AC) CONDUCTORS ACCORDING TO INVERTER OCPD AMPERE RATING. (See Guide Section 9) 5) TOTAL OF ______ INVERTER OUTPUT CIRCUIT OCPD(s), ONE FOR EACH MICRO- INVERTER CIRCUIT. DOES TOTAL SUPPLY BREAKERS COMPLY WITH 120% BUSBAR EXCEPTION IN 690.64(B)(2)(a)? YES NO NOTES FOR INVERTER CIRCUITS (Guide Section 8 and 9): 1.) LOWEST EXPECT AMBIENT TEMPERATURE BASED ON ASHRAE MINIMUM MEAN EXTREME DRY BULB TEMPERATURE FOR ASHRAE LOCATION MOST SIMILAR TO INSTALLATION LOCATION. LOWEST EXPECTED AMBIENT TEMP ____oC 2.) HIGHEST CONTINUOUS AMBIENT TEMPERATURE BASED ON ASHRAE HIGHEST MONTH 2% DRY BULB TEMPERATURE FOR ASHRAE LOCATION MOST SIMILAR TO INSTALLATION LOCATION. HIGHEST CONTINUOUS TEMPERATURE ____oC 2.) 2009 ASHRAE FUNDAMENTALS 2% DESIGN TEMPERATURES DO NOT EXCEED 47oC IN THE UNITED STATES (PALM SPRINGS, CA IS 44.1 oC). FOR LESS THAN 9 CURRENT-CARRYING CONDUCTORS IN ROOF-MOUNTED SUNLIT CONDUIT AT LEAST 0.5" ABOVE ROOF AND USING THE OUTDOOR DESIGN TEMPERATURE OF 47oC OR LESS (ALL OF UNITED STATES), a) 12 AWG, 90 oC CONDUCTORS ARE GENERALLY ACCEPTABLE FOR MODULES WITH Isc OF 7.68 AMPS OR LESS WHEN PROTECTED BY A 12-AMP OR SMALLER FUSE. b) 10 AWG, 90oC CONDUCTORS ARE GENERALLY ACCEPTABLE FOR MODULES WITH Isc OF 9.6 AMPS OR LESS WHEN PROTECTED BY A 15-AMP OR SMALLER FUSE. NOTES FOR ARRAY CIRCUIT WIRING (Guide Section 6 and 8 and Appendix E): OCPD = OVERCURRENT PROTECTION DEVICE NATIONAL ELECTRICAL CODE®REFERENCES SHOWN AS (NEC XXX.XX) NOTES FOR ALL DRAWINGS: SIGNS–SEE GUIDE SECTION 7 SIGN FOR DC DISCONNECT SIGN FOR INVERTER OCPD AND AC DISCONNECT (IF USED) No sign necessary since 690.51 marking on PV module covers needed information AC OUTPUT CURRENT NOMINAL AC VOLTAGE SOLAR PV SYSTEM AC POINT OF CONNECTION THIS PANEL FED BY MULTIPLE SOURCES (UTILITY AND SOLAR) Notes for Micro-Inverter Electrical Diagram ECO PLANET BUILDERS INC. 7127 LAUREL CANYON BLVD. NORTH HOLLYWOOD, CA. 91605 818-962-5874 CARLOS/LUZ GUILLEN 624 E 3RD ST. SANTA ANA 92701 4.053 624 E 3rd St 10/12/22 624 E. 3RD ST. SANTA ANA, CA 92701 GUILLEN, CARLOS Prepared For: ECO PLANET BUILDERS, INC. 7127 LAUREL CANYON BLVD. N. HOLLYWOOD, CA 91605 (818) 427-4249 Design Criteria 1- Code: CALIFORNIA BLDG CODE 2019 / ASCE 7-16 2 - Wind: 95 MPH, Exposure: B 3 - Wood Species: DF-L No. 2 (SG = 0.5 ) Notice: Use restrictions of these calculations. The attached Calculations are valid only when bearing original signature hereon. Contractor/Client to verify existing dimensions/conditions prior to construction & solar racking is installed per manufacturer span requirements. The use of these calculations is solely intended for the above mentioned project. 1-844-PV ELITE | info@yoursolarplans.com 3000 E. Birch Street Suite 201 | Brea CA 92821 6/13/2022 Structural Calculations for SOLAR POWER SYSTEM CONNECTION CHECK AT: Job: 624 E 3rd St 10/12/22 01231445227289 9  711 !1"1#$ %33&80'33&( !%)22 &*02 +34'(,%048-3./4 .9/4  9'4&02 /4 1.9 214  23456789:;5<4=>;9 ?@@53AAB 048-3.5.95 9'4&02 51.9 C;;5@>94=3AB 33&80'33&5)22 &*02 +34' DE3F4=>;9B 24&G H><3A=4<IB 4044)00)23 2 *72874&*&'J K4L45@HMI3B N ?2CDOPQ R ST2 0)U,00V ST4+)U,&2 V ST+0)U,&&V ST2 00)U,*2 V SW ,!T *'V SW ,!TT '+V SW ,!TTT 2 04V SW ,!TX 2 00V ?2CDOPQ Y ST2 0)U,&4V ST4+)U,&'V ST+0)U,*+V ST2 00)U,'2 V SW ,!T 2 00 V SW ,!TT 22 0 V SW ,!TTT)TX 22 +V ?2CDOPYZ 9. -&)0+N.,,*+V [\]^]_`ab_cdecfgb]e\]^]hiji[^]ka]fbgdl_bgb]m^amfgagn]den]db_bmb\]oga`]_m^gdle]acd]gbcmdacd]_nge]e`^cdpb\]q`caecdp fme]gemrbcmdr^mf]__st_]^__\m`aefmdkc^ngdlm`br`bmqbgcd]ek^mnb\c_bmmaucb\b\]amfgav`b\m^cblwgocdpx`^c_ecfbcmdq]km^] r^mf]]ecdpucb\e]_cpds y>A6E4><35  ,, ,GVz,9. -&,,,,# ,,!,{,9. -&5  ,,,  ,, #,,G, ,|V,,5#,,# ,} , , #,,,,G,5z,#,, ! !,~ -7€,,,#),,,! ,5,, !,,V,z,!#VGG,#,,,,,##), ,,! ,5!!,5,V,5, #,! ,,}V,G # N ,,GV,,,#,,, ,z,,,59 V,,    G ,V, ,,,,, ,,, ,G,G # V,,,}Vz,GG5   ,!,,, ,,G, 9 , ,,,GGV, ,,‚!V,GV,,G, 5z!,},,,W# ,!, ,G, G,5,G,G,,,GG, ,,! !,, G, ,z,#,,1,G,GVGV#,,V,   !GV,1,G,G #,,,V z ,!z,! !,,, ,G !,z ,,G, ƒ„…†‡ ˆ‰Š‹ŒŽŽŠ‰ŒŒ‹ŒŽŠ‘ŽŽ’“”““•‹‹–—‰˜™š›•™ 624 E 3rd St 10/12/22 ASCE 29.4.4 Rooftop Solar Panels Parallel to the Roof Surface on Buildings of All Heights and Roof Slopes. Roof Slope  = 17 ° Roof Shape Gable Tributary Width s = 4.00 ft Tributary Length l = 2.87 ft Effective Area A e = 6.92 ft2 Height of Structure h = 15 ft Wind Speed V = 95 mph Exposure Category B Building Width B = 30 ft Building Length L = 60 ft Zone Width a = 3 ft Elevation Height zg = 127 ft Wind Directionality Kd = 0.85 Topography Factor Kt = 1.00 Ground Elevation Factor Ke = 1.00 Velocity Pressure Exposure Coefficient Kz = 0.70 Velocity Pressure q z = 0.00256KzKztKdKeV2 = 13.70 psf Solar Array Pressure Equalization a = 0.80 Array Edge Factor E = 1.50 Zone GCp p = qz(GCp)(E)(a) 3 - - 3r 3.60 -59.16 3e 3.00 -49.30 2 - - 2r 3.00 -49.30 2e - - 2n 3.00 -49.30 1 - - 1' - - 624 E 3rd St 10/12/22 LAG SCREW ANALYSIS Loads Wind Pressures qz = -49.30 psf Solar Panel Load QD = 3 psf Panel Length l = 5.735 ft Panel Width b 3.458 ft Attachment Spacing s = 4 ft Portrait Tributary Area At = 11.47 ft2 Wind Load P W = qz * At = -566 lbs Dead Load P D = Q D * At = 34.409 lbs Uplift Pa = 0.6 P D + 0.6 Pw = -319 lbs Landscape Tributary Area At = b * s = 6.916 ft2 Wind Load P W = qz * At = -341 lbs Dead Load P D = Q D * At = 20.748 lbs Uplift Pa = 0.6 P D + 0.6 Pw = -192 lbs Lag Screw 5/16" x 5" Specific Gravity of Lumber SG = 0.50 (Douglas Fir-Larch) Diameter of Lag Screw D = 5/16 in Withdraw Design /in 1800*SG 3/2 *D 3/4 = 266 lbs/in Depth of Embedment lp = 2.50 in Total Nominal Withdrawal Value W = W * l p = 665 lbs Load Duration Factor CD = 1.6 Withdrawal Design Value W' = W * C D = 1064 lbs Demand Capacity Ratio DCR = Pa / W' = 0.30 < 1 OK 624 E 3rd St 10/12/22 ASCE 30.3.2 Design Wind Pressure Beam/ Top Chord Check Roof Slope  = 17 ° Roof Shape Gable Tributary Width s = 2.00 ft Tributary Length L = 11.19 ft Effective Area A = L ( MAX [ s , L/3] ) = 42 ft2 Height of Structure h = 15 ft Wind Speed V = 95 mph Exposure Category B Building Width B = 30 ft Building Length L = 60 ft Zone Width a = 3 ft Elevation Height zg = 127 ft Wind Directionality Kd = 0.85 Topography Factor Kt = 1.00 Ground Elevation Factor Ke = 1.00 Velocity Pressure Exposure Coefficient Kz = 0.70 Velocity Pressure q z = 0.00256KzKztKdKeV 2 = 13.70 psf Internal Pressure Coefficient (GCpi) = -0.18 Zone GCp p = q z [(GCp) - (Gcpi)] 3 - - 3r 2.97 -43.08 3e 2.74 -39.93 2 - - 2r 2.74 -39.93 2e - - 2n 2.74 -39.93 1 - - 1' - - 624 E 3rd St 10/12/22 Beam/ Top Chord Check Lumber: Moment Demand # of Attachment per Rafter N A = Span : Orientation Lenght (ft) : Dead Load Roof Material: Q D = psf Live Load QLr = psf Wind Load p = psf Snow Load QS = psf Rafter Spacing s = in Wind Load, Portrait Portrait UL = Wind Load, Landscape Landscape U W = Linear Dead Load wd = plf Live Load wLr = plf Start ft Start ft End ft End ft Snow Load ws = plf Start ft Start ft End ft End ft Ma, Moment D lb-ft D+Lr lb-ft D+S lb-ft 0.6D+0.6W lb-ft D+0.45W+0.75Lr lb-ft D+0.45W+0.75S lb-ft Moment Capacity Framing Member Size Lumber Grade : DF-L No. 2 C M = 1 Ct = 1 Cr= CF = fb = psi C fu =C i = Breadth b = in Depth d = in Section Modulus Sx = bd 2 / 6 = in3 Bending Stress Capacity Fb = CM * C t * Cr * C F * fb = psi Table 4.3.1 NDS 2015 Deflection Limit E = ksi I = in4 Transient Deflection in Transient Deflection Allowed > [OKAY] Total Deflection in Total Deflection Allowed > [OKAY] -39.93 DF-L No. 2 4 j lj (ft) pd,j  (lbs) pw,j  (lbs) ps,j  (lbs) Landscape 1 0.7 20.7 -276 0.0 2.8 20.7 -276 -458 0.0 4 8.4 34.4 -458 0.0 0.0 2.19 8.00 0.00 0.00 1.00 Portrait 3 4.2 34.4 10.00 1 2 3 4 Eave 2 0.0 0.0 0.0 0.0 0.0 0 0.0 0.0 0.0 0.0 0 0.0 0.0 0.0 0.0 0 0.0 0.0 0 0.0 Portrait 0 0.0 0.0 0 0.0 20 40 0.0 0.0 0.0 0.0 0 0.0 Portrait 0 0.0 20.748 -276 0 0 0.0 0 0 0 0 0.0 Portrait 0 0.0 Portrait 0 0.0 0.0 AT (ft 2) 11.47 6.916 pd (lbs) 34.409 -458 p w (lbs) ps (lbs) 0 9.19 2x4 1.15 1.5 11.19 9.19 11.19 900 1.50 3.50 191 191 191 426 214 214 DCR 0.9 1397 psi D 748 psi 0.54 3.06 1553 CD Fb' = C D * F b ASD Load Ma * S x 1.15 1785 psi D+S 748 psi 0.42 OKAY OKAY 1.25 1941 psi D+Lr 747 psi 0.39 OKAY 1.6 2484 psi 0.322 298 120 1600 5.36 0.6D+0.6W 1668 psi 0.67 OKAY 1.0 1 20 0.00 24 Comp 0.293 328 180 1.6 2484 psi D+0.45W+0.75S 840 psi 0.34 OKAY 1.6 2484 psi D+0.45W+0.75Lr 840 psi 0.34 OKAY ൌ ሺ െ ሻ െ െ െ ‐600.0 ‐400.0 ‐200.0 0.0 200.0 400.0 0.000 2.000 4.000 6.000 8.000 10.000 12.000 624 E 3rd St 10/12/22 EISMIC WEIGHT COMPARISON / ANALYSIS - (PER CEBC 2019 Part 10 Chapter 5 Section 502.5) PV System Weight Module Model Mission Solar Panel Weight Wpanel = 44.8 lbs Number of Panels NPV = 13 Total PV System Weight W PV = Wpanel * NPV = 582.4 lbs Existing Roof Weight Roof Weight QD =10.0 psf Building Length Lbuild =60 ft Building Width W build =30 ft Roof Area Abuild =1800 ft2 Building Perimeter Pbuild = 180 ft Wall Height ht = 8 ft Wall weight Qwall = 15 psf Interior wall weight Qint = 10 psf Roof Load Wfloor = Abuild * QD = 18000 lbs Wall LoadWwall = ht /2 * Qwall * Pbuild + Abuild * Qint /2 = 19800 lbs Total Story Weight Wbuild = Wfloor + Wwall = 37800 lbs Percentage Weight Increase WPV / Wbuild = 1.54%< 10% OKAY 624 E 3rd St 10/12/22 624 E 3rd St 10/12/22 624 E 3rd St 10/12/22 624 E 3rd St 10/12/22 624 E 3rd St 10/12/22 624 E 3rd St 10/12/22 624 E 3rd St 10/12/22 To whom it may concern As the homeowner of the property at: 624 East 3rd St Santa Ana CA 92701, I hereby confirm that the solar installer company Eco Planet Builders Inc. has closed a contract with myself to complete the work and permitting of a roof mounted solar system for me. I give them permission to pull permits and conduct the install at my above-mentioned residence. Thank you Carlos & Luz Guillen Date ignature Date Signature 624 E 3rd St 10/12/22 624 E 3rd St 10/12/22 624 E 3rd St 10/12/22 624 E 3rd St 10/12/22 624 E 3rd St 10/12/22 624 E 3rd St 10/12/22 624 E 3rd St 10/12/22 624 E 3rd St 10/12/22 624 E 3rd St 10/12/22 624 E 3rd St 10/12/22 624 E 3rd St 10/12/22 624 E 3rd St 10/12/22 624 E 3rd St 10/12/22 624 E 3rd St 10/12/22 624 E 3rd St 10/12/22 624 E 3rd St 10/12/22 624 E 3rd St 10/12/22 624 E 3rd St 10/12/22 624 E 3rd St 10/12/22 Rev: 7/15/2021 RESIDENTIAL PHOTOVOLTAIC CHECKLIST SOL-01 CBC 2019 Solar Photovoltaic (PV) Checklist for Detached SINGLE FAMILY RESIDENCES Only Instructions: The licensed contractor of record shall complete all sections, answer the ten questions and sign the certification section below. A copy of this form shall be attached to each of TWO sets of plans, of minimum 11” x 17” size. If answering NO to any of the questions, plan check shall be required. Project Address: Contractor Company Name: Contractor License Number: YES NO Are the following applicable to the proposed project? 1.   Will the PV system layout provide the required three-foot wide clear access pathways per Section 605.11 of the California Fire Code, and is this shown on the roof plan? 2.   Will the PV system be installed on a roof having only one roofing layer with no overlays? 3.   Will the PV array be flush mounted to the existing roof so that the plane of the modules (panels) are parallel to the plane of the roof? 4.   Will the PV system weigh maximum 4 pounds per square feet or less? 5.   Will the PV system be installed where the modules do not overhang any roof edges (such as eaves, gabled ends, ridges and hips)? 6.   Will the PV system be installed with a space of 2” minimum to 10” maximum between the underside of modules and the surface of the roof? 7.   Will the PV system be installed without using any ballast system or counter-weight system? 8.   Will the anchors be installed with a maximum horizontal anchor spacing of 6 feet and is this maximum horizontal spacing shown on the plans? 9.   Will the minimum 5/16” lag screws be installed with a minimum of 2-1/2 inch embedment into roof rafters (with pre-drilled holes) and is this minimum embedment shown on the plans? 10.   Are ALL the structural pages of the plans stamped and signed by a California licensed professional engineer? (including project specific site plan, PV layout, anchorage spacing, anchorage details and manufacturer’s PV support information.) I certify under penalty of perjury under the laws of the State of California that the above is true: Print Name: Signature: Phone Number: Date: Email Address: Planning & Building Agency Building Safety Division 20 Civic Center Plaza P.O. Box 1988 (M-19) Santa Ana, CA 92702 (714) 647-5800 www.santa-ana.org 624 E 3RD ST. SANTA ANA CA 92701 ECO PLANET BUILDERS INC. 1031107 NIR LEVI 818-427-4249 INFO@ECOPLANETBUILDERS.COM 6/1/22 624 E 3rd St 10/12/22