Loading...
HomeMy WebLinkAbout801 E Borchard Ave - PlanPage RE V I S I O N S : Pr o j e c t N a m e 2. 8 0 0 k W ( D C ) / 2 . 5 3 0 k W ( C E C - A C ) PH O T O V O L T A I C S Y S T E M OV I E D O , B L A N C A 80 1 E B O R C H A R D A V E , SA N T A A N A , C A 9 2 7 0 7 AP N : 0 1 4 4 0 3 0 5 DA T E : 09 / 1 4 / 2 0 2 1 DR A W N B Y : ZM Co n t r a c t o r s S i g n a t u r e : SO L A R P L E X L L C 59 0 2 F I R E S T O N E B L V D SO U T H G A T E , C A 9 0 2 8 0 PH O N E : ( 5 6 2 ) 8 0 6 - 6 0 0 0 LI C E N S E : # 1 0 5 6 0 6 5 / B , C 1 0 R1 0 9 . 1 5 . 2 1 ( Z M ) CO V E R P A G E PHOTOVOLTAIC GENERAL NOTES · ALL MATERIALS, EQUIPMENT, INSTALLATION AND WORK PERFORMED SHALL BE IN ACCORDANCE WITH THE FOLLOWING CODES: - 2019 CBC / 2018 IBC - 2019 CRC / 2018 IRC - 2019 CEC / 2017 NEC - 2019 CMC / 2018 IMC - 2019 CPC / 2018 IPC - 2019 CFC / 2018 IFC - 2019 BUILDING ENERGY EFFICIENCY STANDARDS · ALL EQUIPMENT SHALL BE LISTED AND LABELED BY A RECOGNIZED ELECTRICAL TESTING LABORATORY AND L.A. TEST LAB. EQUIPMENT INSTALLED SHALL BE PER ITS LISTING REQUIREMENTS AND THE MANUFACTURER'S INSTRUCTIONS. [NEC 110.2, 110.3, 690.4(B), 690.12(D)] · ALL OUTDOOR EQUIPMENT SHALL BE NEMA 3R RATED, INCLUDING ALL ROOF MOUNTED TRANSITION BOXES AND SWITCHES. · ALL EQUIPMENT SHALL BE PROPERLY GROUNDED AND BONDED IN ACCORDANCE WITH NEC ARTICLE 250. · ALL PV CIRCUITS CONNECTED AND EQUIPMENT SHALL BE PROTECTED AGAINST OVERCURRENT. OVERCURRENT DEVICES SHALL BE LISTED FOR USE IN PV SYSTEMS. OVERCURRENT PROTECTIVE DEVICES SHALL NOT BE REQUIRED FOR CIRCUITS WITH SUFFICIENT AMPACITY FOR THE HIGHEST AVAILABLE CURRENT. CIRCUITS CONNECTED TO CURRENT LIMITED SUPPLIES AND ALSO CONNECTED TO SOURCES HAVING HIGHER CURRENT AVAILABILITY SHALL BE PROTECTED AT THE HIGHER CURRENT SOURCE CONNECTION. [NEC 690.9] · DISCONNECTING MEANS OF THE PV SYSTEM (INCLUDING RAPID SHUTDOWN INITIATION) SHALL BE LOCATED IN A READILY ACCESSIBLE LOCATION NEAR THE EQUIPMENT. [NEC 690.13,690.15] · RAPID SHUTDOWN EQUIPMENT TO COMPLY WITH NEC 690.12. · ENERGY STORAGE SYSTEM TERMINALS LOCATED MORE THAN 5 FEET AWAY OR ON OPPOSITE SIDE OF WALL FROM CONNECTED EQUIPMENT MUST HAVE DISCONNECTING MEANS IN ACCORDANCE WITH NEC 706.7(E) AND LABELED PER 706.7(D). A SECOND DISCONNECTING MEANS LOCATED AT THE CONNECTED EQUIPMENT SHALL BE INSTALLED WHERE THE DISCONNECTING MEANS AT THE ESS END OF THE CIRCUIT IS NOT WITHIN SIGHT. · THE UTILITY-INTERACTIVE INVERTERS SHALL AUTOMATICALLY DE-ENERGIZE ITS OUTPUT TO THE CONNECTED ELECTRICAL PRODUCTION AND DISTRIBUTION NETWORK VOLTAGE HAS BEEN RESTORED. [NEC 705.40] · ALL CONDUCTORS IN EXPOSED OUTDOOR LOCATIONS SHALL BE LISTED AND IDENTIFIED FOR USE IN DIRECT SUNLIGHT AND FOR THE APPLICATION. [NEC 690.31(C) THROUGH (F), 310.10(D)] · INSULATION OF EXPOSED CONDUCTORS UNDER THE MODULES SHALL BE USE-2 OR PV-WIRE TYPE FOR PV SYSTEMS (UL 4703 & 854 LISTED) [NEC 690.31(C)] · FINE-STRANDED CABLE CONNECTIONS MUST BE MADE IN LUGS AND TERMINALS TO ENSURE A THOROUGHLY GOOD CONNECTION WITHOUT DAMAGING THE CONDUCTORS. [NEC 110.14(A)] · FLEXIBLE, FINE-STRANDED CABLES SHALL BE TERMINATED ONLY WITH TERMINALS, LUGS, DEVICES, OR CONNECTORS THAT ARE IDENTIFIED AND LISTED FOR SUCH USE. [NEC 690.31(H), 110.14] · ALL PV CIRCUIT CONDUCTORS SHALL BE MARKED ON EACH END AND GROUPED FOR UNIQUE IDENTIFICATION. [NEC 690.31(B)] · ALL EXTERIOR CONDUIT, FITTINGS, AND BOXES SHALL BE RAIN TIGHT AND APPROVED FOR USE IN WET LOCATIONS. [NEC 314.15] · ALL GROUNDED, (NEUTRAL), CONDUCTORS' INSULATION SHALL BE SOLID WHITE, GRAY, OR WITH 3-WHITE STRIPES. [NEC 200.6, 200.7, 400.22]; ALL GROUNDING CONDUCTORS SHALL BE OF BARE WIRE WITHOUT COVERING, OR WITH INSULATION OF GREEN OR GREEN WITH YELLOW STRIPES, NEC 250.119 & 400.23. THE COLOR OF UNGROUNDED CONDUCTORS SHALL BE OTHER THAN FOR GROUNDED, (NEUTRAL), AND GROUNDING CONDUCTORS. [NEC 310.110(C)] · MAXIMUM CONDUCTOR LENGTH BETWEEN SUPPLY SIDE CONNECTION AND OVERCURRENT PROTECTION IS 10FT. [NEC 705.31] · CONNECTIONS ON THE LOAD SIDE OF THE SERVICE DISCONNECTING MEANS OF THE OTHER SOURCE(S) AT ANY DISTRIBUTION EQUIPMENT ON THE PREMISES SHALL BE IN ACCORDANCE WITH NEC 705.12(B). · DC WIRING INSIDE A BUILDING MUST BE IN METALLIC TYPE RACEWAYS, CONDUITS, ENCLOSURES, OR CABLE SHEATHINGS. [NEC 690.31(G)] · METALLIC TYPE RACEWAYS, CONDUITS, ENCLOSURES, AND CABLE SHEATHS CONTAINING CIRCUITS OVER 250-VOLTS TO GROUND MUST BE BONDED IN ACCORDANCE WITH NEC 250.97. · CONNECTORS SHALL BE OF LATCHING OR LOCKING TYPE. CONNECTORS THAT ARE READILY ACCESSIBLE AND OPERATING AT OVER 30-VOLTS SHALL REQUIRE A TOOL TO OPEN AND MARKED "DO NOT DISCONNECT UNDER LOAD" OR "NOT FOR CURRENT INTERRUPTING." [NEC 690.33(C) & (E)(2)] · FOR PV MODULES, EQUIPMENT GROUNDING CONDUCTOR (EGC) SMALLER THAN #6-AWG SHALL BE PROTECTED FROM PHYSICAL DAMAGE BY AN IDENTIFIED RACEWAY OR CABLE ARMOR, UNLESS INSTALLED WITHIN HOLLOW SPACES OF THE FRAMING MEMBERS OF BUILDINGS OR STRUCTURES AND WHERE NOT SUBJECT TO PHYSICAL DAMAGE. [NEC 690.46, 250.120(C)] · THE INTERCONNECTION POINT SHALL BE ON THE SUPPLY SIDE OF ALL GROUND-FAULT PROTECTION EQUIPMENT. [NEC 705.32] · CABLES/WIRES THAT ARE SUBJECT TO PHYSICAL DAMAGE, SUCH AS THOSE NOT LOCATED UNDER THE MODULES, MUST BE PROTECTED. [NEC 300.4] · FOR ELECTRICAL SERVICE REPLACEMENTS, BONDING TO THE METAL PIPES OF NATURAL GAS, HOT WATER, AND COLD WATER MUST BE PROVIDED. [NEC 250.104] · GROUNDING ROD ELECTRODES SHALL BE INSTALLED 8-FT MINIMUM IN CONTACT WITH SOIL AND MINIMUM 5/8-INCH DIAMETER. [NEC 250.52(A)(5), 250.53(G)] · THE MARKINGS, "WARNING: PHOTOVOLTAIC POWER SOURCE", FOR DC RACEWAYS AND CABLE ASSEMBLIES MUST BE NO MORE THAN 10-FT O.C.; AND IS SEPARATED BY ENCLOSURES, WALLS, PARTITIONS, CEILINGS, FLOORS, OR BENDS ABOVE OR BELOW PENETRATIONS. [NEC 690.31(G)(3)&(4)] · WORKING CLEARANCES TO BE PROVIDED AT NEW AND EXISTING ELECTRICAL EQUIPMENT. [NEC 110.26] · POWER PRODUCTION SYSTEMS, AND ALL ASSOCIATED WIRING AND INTERCONNECTIONS OPERATING IN PARALLEL WITH A PRIMARY POWER SOURCE SHALL BE PERFORMED ONLY BY QUALIFIED PERSONS. [NEC 690.4(C), 705.8] · LABELS SHALL BE REFLECTIVE, AND ALL LETTERS SHALL BE CAPITALIZED AND SHALL BE A MINIMUM HEIGHT OF 3/8" IN WHITE ON A RED BACKGROUND. [NEC 690.31(G)(4)] · IDENTIFICATION OF POWER SOURCE RAPID SHUTDOWN AND LABELING SHALL BE IN ACCORDANCE WITH NEC 690.56(C). · SMOKE ALARMS AND CARBON MONOXIDE ALARMS ARE REQUIRED TO BE RETROFITTED ONTO THE EXISTING DWELLING AS PER THE 2019 CRC. THESE SMOKE ALARMS ARE REQUIRED TO BE IN ALL BEDROOMS, OUTSIDE EACH BEDROOM, AND AT LEAST ONE ON EACH FLOOR OF THE HOUSE. CARBON MONOXIDE ALARMS ARE REQUIRED TO BE RETROFITTED OUTSIDE EACH BEDROOM AND AT LEAST ONE ON EACH FLOOR OF THE HOUSE. (CRC 314,315) · SMOKE ALARMS AND CARBON MONOXIDE ALARMS ARE REQUIRED PER CRC SECTIONS 314 AND 315 TO BE VERIFIED AND INSPECTED BY THE INSPECTOR IN THE FIELD. · A LADDER MUST BE PROVIDED FOR INSPECTIONS IN ACCORDANCE WITH Cal-OSHA REGULATIONS, SECURED AND EXTENDING 3-FT ABOVE THE ROOF. · ALL OF THE REQUIRED MARKINGS, SIGNS, AND LABELS MUST BE INSTALLED ON ALL EQUIPMENT PRIOR TO ANY INSPECTIONS. 1A OF 11 COUNTY ELECTRONIC STAMP Bldg permit#101109184 Elect permit#20175177 Issued on 2/16/22 801 E Borchard Ave 02/17/22 Page RE V I S I O N S : Pr o j e c t N a m e 2. 8 0 0 k W ( D C ) / 2 . 5 3 0 k W ( C E C - A C ) PH O T O V O L T A I C S Y S T E M OV I E D O , B L A N C A 80 1 E B O R C H A R D A V E , SA N T A A N A , C A 9 2 7 0 7 AP N : 0 1 4 4 0 3 0 5 DA T E : 09 / 1 4 / 2 0 2 1 DR A W N B Y : ZM Co n t r a c t o r s S i g n a t u r e : SO L A R P L E X L L C 59 0 2 F I R E S T O N E B L V D SO U T H G A T E , C A 9 0 2 8 0 PH O N E : ( 5 6 2 ) 8 0 6 - 6 0 0 0 LI C E N S E : # 1 0 5 6 0 6 5 / B , C 1 0 R1 0 9 . 1 5 . 2 1 ( Z M ) IN V E R T E R SP E C I F I C A T I O N S 08 OF 11 COUNTY ELECTRONIC STAMP 801 E Borchard Ave02/17/22 Page RE V I S I O N S : Pr o j e c t N a m e 2. 8 0 0 k W ( D C ) / 2 . 5 3 0 k W ( C E C - A C ) PH O T O V O L T A I C S Y S T E M OV I E D O , B L A N C A 80 1 E B O R C H A R D A V E , SA N T A A N A , C A 9 2 7 0 7 AP N : 0 1 4 4 0 3 0 5 DA T E : 09 / 1 4 / 2 0 2 1 DR A W N B Y : ZM Co n t r a c t o r s S i g n a t u r e : SO L A R P L E X L L C 59 0 2 F I R E S T O N E B L V D SO U T H G A T E , C A 9 0 2 8 0 PH O N E : ( 5 6 2 ) 8 0 6 - 6 0 0 0 LI C E N S E : # 1 0 5 6 0 6 5 / B , C 1 0 R1 0 9 . 1 5 . 2 1 ( Z M ) UL L I S T I N G 09 OF 11 COUNTY ELECTRONIC STAMP 801 E Borchard Ave02/17/22 Page RE V I S I O N S : Pr o j e c t N a m e 2. 8 0 0 k W ( D C ) / 2 . 5 3 0 k W ( C E C - A C ) PH O T O V O L T A I C S Y S T E M OV I E D O , B L A N C A 80 1 E B O R C H A R D A V E , SA N T A A N A , C A 9 2 7 0 7 AP N : 0 1 4 4 0 3 0 5 DA T E : 09 / 1 4 / 2 0 2 1 DR A W N B Y : ZM Co n t r a c t o r s S i g n a t u r e : SO L A R P L E X L L C 59 0 2 F I R E S T O N E B L V D SO U T H G A T E , C A 9 0 2 8 0 PH O N E : ( 5 6 2 ) 8 0 6 - 6 0 0 0 LI C E N S E : # 1 0 5 6 0 6 5 / B , C 1 0 R1 0 9 . 1 5 . 2 1 ( Z M ) GR O U N D I N G 10 OF 11 RAIL TO RAIL BONDING #6 BARE COPPER WIRE INV (IF USED) MSP CONTINUOUS GROUND PER SLD JBOX GROUND BUSHINGS REQ. MODULE RAIL SOLAR METER (IF REQ) (A) (1) BOND STRIP GROUNDS RAIL TO RAIL SPLICES - STAR WASHERS USED TO BOND RAIL TO BONDING STRIP (2) SPLICE BAR, SELF-TAP SCREWS JOIN RAILS. BONDING STRIPS USED ON RAILS WITH GROUND LUGS. (1) (2) (3) IF SPLICE BAR HAS INTEGRATED GROUND, BONDING STRIP IS NOT NECESSARY. (3) WHERE NEITHER BONDING STRIP, INTEGRATED GROUNDING SPLICE BAR, OR INTEGRATED GROUNDING MIDCLAMP ARE USED, UL 2703 APPROVED GROUND LUG WITH #6 BARE COPPER SHALL BE USED TO GROUND SPLICED RAILS. USE METHOD (2) (1) (C) RAIL SPLICE GROUNDING (C) #6 BARE COPPER RAIL 1 RAIL 2 EITHER METHOD 1-3 PER MANUFACTURERS INSTALL INSTRUCTIONS CONDUIT COMPRESSION FITTING LOCK NUT GROUNDING BUSHING WITH LAY-IN LUG ENCLOSURE CONTINUOUS GROUND STRIP INSULATION CONDUIT GROUNDING DETAIL EQUIPMENT GROUND BUSHINGS REQ. FOR SYSTEMS OVER 250V A GROUNDING MID CLAMP EACH GROUNDING MID CLAMP PIERCES THROUGH THE ANODIZED COATINGS OF BOTH THE MODULE FRAME AND THE MOUNTING RAIL TO FORM SECURE ELECTRICAL BONDS, WHICH ARE REPEATED THROUGHOUT THE ARRAY AND AT LEAST TWICE PER PANEL. MODULE SHALL BE GROUNDED AT LEAST TWICE OVER WITH A MINIMUM OF TWO MIDCLAMPS. -UNIRAC GROUNDING MID CLAMP WITH SERRATED TEETH MIDCLAMP TEETH MODULE PENETRATION MAX. UTILIZATION OF RAIL WITH 1/4" SPACING SERRATED T-BOLT BONDS CLAMP TO RAIL COUNTY ELECTRONIC STAMP 801 E Borchard Ave02/17/22 Page RE V I S I O N S : Pr o j e c t N a m e 2. 8 0 0 k W ( D C ) / 2 . 5 3 0 k W ( C E C - A C ) PH O T O V O L T A I C S Y S T E M OV I E D O , B L A N C A 80 1 E B O R C H A R D A V E , SA N T A A N A , C A 9 2 7 0 7 AP N : 0 1 4 4 0 3 0 5 DA T E : 09 / 1 4 / 2 0 2 1 DR A W N B Y : ZM Co n t r a c t o r s S i g n a t u r e : SO L A R P L E X L L C 59 0 2 F I R E S T O N E B L V D SO U T H G A T E , C A 9 0 2 8 0 PH O N E : ( 5 6 2 ) 8 0 6 - 6 0 0 0 LI C E N S E : # 1 0 5 6 0 6 5 / B , C 1 0 R1 0 9 . 1 5 . 2 1 ( Z M ) RA P I D SH U T D O W N 11 OF 11 COUNTY ELECTRONIC STAMP 801 E Borchard Ave02/17/22 CONTRACTOR INFORMATION CONTRACTOR: SOLARPLEX LLC ADDRESS: 5902 FIRESTONE BLVD, SOUTH GATE, CA 90280 PHONE: (562) 806-6000 LICENSE #/TYPE: #1056065/B,C10 TABLE OF CONTENTS PAGE 1 COVER PAGE PAGE 2 SITE PLAN PAGE 3 PLOT PLAN PAGE 4 SINGLE LINE DIAGRAM PAGE 5 STRUCTURAL ATTACHMENT DETAIL PAGE 6 LABELS AND WARNING SIGNAGE PAGE 7 PV MODULE SPEC SHEET PAGE 8 INVERTER SPEC SHEET PAGE 9 UL LISTING PAGE 10 GROUNDING PAGE 11 RAPID SHUTDOWN PROJECT INFORMATION NAME:OVIEDO, BLANCA ADDRESS:801 E BORCHARD AVE, SANTA ANA, CA 92707 APN:01440305 JURISDICTION:SANTA ANA SYSTEM INFORMATION SIZE(kw): 2.800 MODULE TYPE: 8 LONGI LR4-60HPB-350M INVERTERS(S): 8 ENPHASE IQ7-60-2-US INVERTER TYPE: MICRO-INVERTER SCOPE OF WORK: INSTALL (8) ROOF MOUNTED PV SOLAR MODULES, (8) ENPHASE IQ7-60-2-US INVERTER(S)(240V). (1) 125A ELECTRICAL SUB PANEL (240V), 1PH, 3W. (DC) / 2.530 (CEC-AC) PHOTOVOLTAIC MODULES AND PANEL SYSTEMS INSTALLED ON OR INTEGRAL WITH BUILDINGS, OR TO BE FREESTANDING (NOT ATTACHED TO BUILDINGS) SHALL BE TESTED, LISTED, AND IDENTIFIED WITH A FIRE CLASSIFICATION (CLASS C MINIMUM) IN ACCORDANCE WITH UL1703. WHERE CLASS A OR B ROOFING IS REQUIRED, THE PV SOLAR SYSTEM (PV PANEL & RACK) SHALL HAVE THE SAME CLASS/TYPE RATING OR BETTER. OCCUPANCY GROUP: R3 CONSTRUCTION TYPE: V-B Page RE V I S I O N S : Pr o j e c t N a m e 2. 8 0 0 k W ( D C ) / 2 . 5 3 0 k W ( C E C - A C ) PH O T O V O L T A I C S Y S T E M OV I E D O , B L A N C A 80 1 E B O R C H A R D A V E , SA N T A A N A , C A 9 2 7 0 7 AP N : 0 1 4 4 0 3 0 5 DA T E : 09 / 1 4 / 2 0 2 1 DR A W N B Y : ZM Co n t r a c t o r s S i g n a t u r e : SO L A R P L E X L L C 59 0 2 F I R E S T O N E B L V D SO U T H G A T E , C A 9 0 2 8 0 PH O N E : ( 5 6 2 ) 8 0 6 - 6 0 0 0 LI C E N S E : # 1 0 5 6 0 6 5 / B , C 1 0 R1 0 9 . 1 5 . 2 1 ( Z M ) CO V E R P A G E 1B OF 11 COUNTY ELECTRONIC STAMP 801 E Borchard Ave02/17/22 Page RE V I S I O N S : Pr o j e c t N a m e 2. 8 0 0 k W ( D C ) / 2 . 5 3 0 k W ( C E C - A C ) PH O T O V O L T A I C S Y S T E M OV I E D O , B L A N C A 80 1 E B O R C H A R D A V E , SA N T A A N A , C A 9 2 7 0 7 AP N : 0 1 4 4 0 3 0 5 DA T E : 09 / 1 4 / 2 0 2 1 DR A W N B Y : ZM Co n t r a c t o r s S i g n a t u r e : SO L A R P L E X L L C 59 0 2 F I R E S T O N E B L V D SO U T H G A T E , C A 9 0 2 8 0 PH O N E : ( 5 6 2 ) 8 0 6 - 6 0 0 0 LI C E N S E : # 1 0 5 6 0 6 5 / B , C 1 0 R1 0 9 . 1 5 . 2 1 ( Z M ) CO V E R P A G E 1C OF 11 NOTE: 1. IN CASE OF EMERGENCY, CALL ______________________ AT WORK PHONE #___________________ OR HOME PHONE#__________________. 2. SEDIMENT FROM AREAS DISTURBED BY CONSTRUCTION SHALL BE RETAINED ON SITE USING STRUCTURAL CONTROLS TO THE MAXIMUM EXTENT PRACTICABLE. 3. STOCKPILES OF SOIL SHALL BE PROPERLY CONTAINED TO MINIMIZE SEDIMENT TRANSPORT FROM THE SITE TO STREETS, DRAINAGE FACILITIES OR ADJACENT PROPERTIES VIA RUNOFF, VEHICLE TACKING, OR WIND. 4. APPROPRIATE BMP'S FOR CONSTRUCTION-RELATED MATERIALS, WASTES, SPILLS SHALL BE IMPLEMENTED TO MINIMIZE TRANSPORT FROM THE SITE TO STREETS, DRAINAGE FACILITIES, OR ADJOINING PROPERTIES BY WIND OR RUNOFF. 5. RUNOFF FROM EQUIPMENT AND VEHICLE WASHING SHALL BE CONTAINED AT CONSTRUCTION SITES UNLESS TREATED TO REDUCE OR REMOVE SEDIMENT AND OTHER POLLUTANTS. 6. ALL CONSTRUCTION CONTRACTOR AND SUBCONTRACTOR PERSONNEL ARE TO BE MADE AWARE OR THE REQUIRED BEST MANAGEMENT PRACTICES AND GOOD HOUSEKEEPING MEASURES FOR THE PROJECT SITE AND ANY ASSOCIATED CONSTRUCTION STAGING AREAS. 7. AT THE END OF EACH DAY OF CONSTRUCTION ACTIVITY ALL CONSTRUCTION DEBRIS AND WASTE MATERIALS SHALL BE COLLECTED AND PROPERLY DISPOSED IN TRASH OR RECYCLE BINS. 8. CONSTRUCTION SITES SHALL BE MAINTAINED IN SUCH A CONDITION THAT AN ANTICIPATED STORM DOES NOT CARRY WASTES OR POLLUTANTS OFF THE SITE. DISCHARGES OF MATERIAL OTHER THAN STORMWATER ONLY WHEN NECESSARY FOR PERFORMANCE AND COMPLETION OF CONSTRUCTION PRACTICES AND WHERE THEY DO NOT: CAUSE OR CONTRIBUTE TO A VIOLATION OF ANY WATER QUALITY STANDARD; CAUSE OR THREATEN TO CAUSE POLLUTION, CONTAMINATION, OR NUISANCE; OR CONTAIN A HAZARDOUS SUBSTANCE IN A QUANTITY REPORTABLE UNDER FEDERAL REGULATIONS 40 CFR PARTS 117 AND 302. 9. POTENTIAL POLLUTANTS INCLUDE BUT ARE NOT LIMITED TO: SOLID OR LIQUID CHEMICAL SPILLS; WASTES FROM PAINTS, STAINS, SEALANTS, GLUES, LIMES, PESTICIDES, HERBICIDES, WOOD PRESERVATIVES AND SOLVENTS; ASBESTOS FIBERS, PAINT FLAKES OR STUCCO FRAGMENTS; FUELS, OILS, LUBRICANTS, AND HYDRAULIC, RADIATOR OR BATTERY FLUIDS; FERTILIZERS, VEHICLE/EQUIPMENT WASH WATER AND CONCRETE WASH WATER; CONCRETE, DETERGENT OR FLOATABLE WASTES; WASTES FROM ANY ENGINE/EQUIPMENT STEAM CLEANING OR CHEMICAL DEGREASING AND SUPERCHLORINATED POTABLE WATER LINE FLUSHING. DURING CONSTRUCTION, PERMITTEE SHALL DISPOSE OF SUCH MATERIALS IN A SPECIFIED AND CONTROLLED TEMPORARY AREA ON-SITE, PHYSICALLY SEPARATED FROM POTENTIAL STORMWATER RUNOFF, WITH ULTIMATE DISPOSAL IN ACCORDANCE WITH LOCAL, STATE AND FEDERAL REQUIREMENTS. 10. DEWATERING OF CONTAMINATED GROUNDWATER, OR DISCHARGING CONTAMINATED SOILS VIA SURFACE EROSION IS PROHIBITED. DEWATERING OF NON-CONTAMINATED GROUNDWATER REQUIRES A NATIONAL POLLUTANT DISCHARGE ELIMINATION SYSTEM PERMIT FROM THE RESPECTIVE STATE REGIONAL WATER QUALITY CONTROL BOARD. 11. GRADED AREAS ON THE PERMITTED AREA PERIMETER MUST DRAIN AWAY FROM THE FACE OF SLOPES AT THE CONCLUSION OF EACH WORKING DAY. DRAINAGE IS TO BE DIRECTED TOWARD DESILTING FACILITIES. 12. THE PERMITTEE AND CONTRACTOR SHALL BE RESPONSIBLE AND SHALL TAKE NECESSARY PRECAUTIONS TO PREVENT PUBLIC TRESPASS ONTO AREAS WHERE IMPOUNDED WATER CREATES A HAZARDOUS CONDITION. 13. THE PERMITTEE AND CONTRACTOR SHALL INSPECT THE EROSION CONTROL WORK AND INSURE THAT THE WORK IS IN ACCORDANCE WITH THE APPROVED PLANS. 14. THE PERMITTEE SHALL NOTIFY ALL GENERAL CONTRACTORS, SUBCONTRACTORS, MATERIAL SUPPLIERS, LESSEES, AND PROPERTY OWNERS: THAT DUMPING OF CHEMICALS INTO THE STORM DRAIN SYSTEM OR THE WATERSHED IS PROHIBITED. 15. EQUIPMENT AND WORKERS FOR EMERGENCY WORK SHALL BE MADE AVAILABLE AT ALL TIMES DURING THE RAINY SEASON. NECESSARY MATERIALS SHALL BE AVAILABLE ON SITE AND STOCKPILED AT CONVENIENT LOCATIONS TO FACILITATE RAPID CONSTRUCTION OF TEMPORARY DEVICES WHEN RAIN IS IMMINENT. 16. ALL REMOVABLE EROSION PROTECTIVE DEVICES SHALL BE IN PLACE AT THE END OF EACH WORKING DAY WHEN THE 5-DAY RAIN PROBABILITY FORECAST EXCEEDS 40%. 17. SEDIMENTS FROM AREAS DISTURBED BY CONSTRUCTION SHALL BE RETAINED ON SITE USING AN EFFECTIVE COMBINATION OF EROSION AND SEDIMENT CONTROLS TO THE MAXIMUM EXTENT PRACTICABLE, AND STOCKPILES OF SOIL SHALL BE PROPERLY CONTAINED TO MINIMIZE SEDIMENT TRANSPORT FROM THE SITE TO STREETS, DRAINAGE FACILITIES OR ADJACENT PROPERTIES VIA RUNOFF, VEHICLE TRACKING, OR WIND. 18. APPROPRIATE BMPS FOR CONSTRUCTION-RELATED MATERIALS, WASTES, SPILLS OR RESIDUES SHALL BE IMPLEMENTED AND RETAINED ON SITE TO MINIMIZE TRANSPORT FROM THE SITE TO STREETS, DRAINAGE FACILITIES, OR ADJOINING PROPERTY BY WIND OR RUNOFF. COUNTY ELECTRONIC STAMP 801 E Borchard Ave02/17/22 Page RE V I S I O N S : Pr o j e c t N a m e 2. 8 0 0 k W ( D C ) / 2 . 5 3 0 k W ( C E C - A C ) PH O T O V O L T A I C S Y S T E M OV I E D O , B L A N C A 80 1 E B O R C H A R D A V E , SA N T A A N A , C A 9 2 7 0 7 AP N : 0 1 4 4 0 3 0 5 DA T E : 09 / 1 4 / 2 0 2 1 DR A W N B Y : ZM Co n t r a c t o r s S i g n a t u r e : SO L A R P L E X L L C 59 0 2 F I R E S T O N E B L V D SO U T H G A T E , C A 9 0 2 8 0 PH O N E : ( 5 6 2 ) 8 0 6 - 6 0 0 0 LI C E N S E : # 1 0 5 6 0 6 5 / B , C 1 0 R1 0 9 . 1 5 . 2 1 ( Z M ) SI T E P L A N 02 OF 11 MS P A/ CD. IN V A/ CD. PV L C PV L C SU B ROOF SECTION PLAN SCALE: NTS PV MODULE COMP SHINGLE ROOFING MATERIAL 2"X4" ROOF TRUSS @ 24" O.C 24"LOAD BEARING WALL RIDGE 40" MAX SPAN N S EW Scale: 3/16" = 1'-0" (For 24x36 Print) COUNTY ELECTRONIC STAMP 801 E BORC H A R D A V E PROPERTY L I N E PR O P E R T Y LI N E PR O P E R T Y L I NE MAIN RESIDENCE FRONT OF RESIDENCE REAR OF RESIDENCE (E) DRIVEWAY (E) PATIO (E) PATIO (E) PV ARRAY 26'-6" 20'-5" 20'-11" 58'-9" 801 E Borchard Ave02/17/22 Page RE V I S I O N S : Pr o j e c t N a m e 2. 8 0 0 k W ( D C ) / 2 . 5 3 0 k W ( C E C - A C ) PH O T O V O L T A I C S Y S T E M OV I E D O , B L A N C A 80 1 E B O R C H A R D A V E , SA N T A A N A , C A 9 2 7 0 7 AP N : 0 1 4 4 0 3 0 5 DA T E : 09 / 1 4 / 2 0 2 1 DR A W N B Y : ZM Co n t r a c t o r s S i g n a t u r e : SO L A R P L E X L L C 59 0 2 F I R E S T O N E B L V D SO U T H G A T E , C A 9 0 2 8 0 PH O N E : ( 5 6 2 ) 8 0 6 - 6 0 0 0 LI C E N S E : # 1 0 5 6 0 6 5 / B , C 1 0 R1 0 9 . 1 5 . 2 1 ( Z M ) PL O T P L A N BUILDING SPECIFICATIONS TYPE:S.F.D STORIES:1 BUILDING HEIGHT(FT.): 12 BUILDING(SQ.FT):1548 ROOF SLOPES(°):20 ROOF FRAME MEMBER: 2X4 TRUSS O.C. SPACING(IN.):24 MAX SPAN:40'-0" IN BETWEEN SUPPORTS MIN LAG BOLT EMBEDMENT(IN.):2-1/2 MOUNTING AND STANDOFF SPECIFICATIONS ROOFING MATERIAL:SINGLE LAYER COMP RACKING SYSTEM:UNIRAC STANDOFF DISTANCE(IN.): 72 MOUNTING TYPE: FLUSH MOUNT TILT LEG HEIGHT (IN.): N/A HEIGHT OF PV MODULE ABOVE ROOF SURFACE:3" TO 5" MAX CANTILEVER (IN.): 24 SYSTEM SPECIFICATIONS SIZE(kW):2.800 MODULE:(8) LONGI LR4-60HPB-350M INVERTER(S):(8) ENPHASE IQ7-60-2-US INVERTER TYPE:MICRO-INVERTER STRING SCHEDULE:1 CIRCUIT(S) OF 8 MODULES SYSTEM WEIGHT(LBS): 383.92 ARRAY AREA(SQ.FT):156.87 ARRAY AZIMUTH(°):278 LBS/SQ.FT:2.45 03 OF 11 ROOF MOUNTED NOTES: ADDITIONAL BUILDING DATA TOTAL ARRAY AREA (SQ. FT.):362.87 TOTAL PLAN VIEW ROOF AREA (SQ. FT.):1548 OCCUPYING PV PERCENTAGE:23.44% SPRINKLER SYSTEM INSTALLED (IFC 903.3.1.3)NO - SOLAR PHOTOVOLTAIC SYSTEM TO BE INSTALLED ON RESIDENTIAL STRUCTURE (GROUP R3 BUILDINGS). -THIS SYSTEM WILL NOT BE INTERCONNECTED UNTIL APPROVAL FROM THE LOCAL JURISDICTION AND THE UTILITY IS OBTAINED. -A 36-INCH WIDE PATHWAY SHALL BE PROVIDED TO THE EMERGENCY ESCAPE AND RESCUE OPENING(S). -IF THE EXISTING MAIN SERVICE PANEL DOES NOT HAVE A VERIFIABLE GROUNDING ELECTRODE, IT IS THE CONTRACTOR'S RESPONSIBILITY TO INSTALL A SUPPLEMENTAL GROUNDING ELECTRODE. R324.6.1 Pathways R324.6.2 Setback at ridge R324.6.2.1 Alternative setback at ridge Exceptions: 1. These requirements shall not apply to structures designed and constructed in accordance with the International Residential Code. 2. These requirements shall not apply to roofs with slopes of 2 units vertical in 12 units horizontal or less. ROOF ACCESS POINTS PER 2019 CRC, R324 (IFC 1204) MS P A/ CD. INV A/ CD. PV L C PV L C JB SU B N S EW Scale: 3/16" = 1'-0" (For 24x36 Print) (E) PV ARRAY COUNTY ELECTRONIC STAMP (E) 30A AC DISCONNECT 2P - NON FUSIBLE (E) 100A MAIN SERVICE PANEL 120/240VAC SINGLE PHASE (N) ENPHASE AC COMBINER BOX 240VAC, NEMA 3R (E) SOLAREDGE SE3800H-US INVERTER (N) 30A AC DISCONNECT 2P - NON FUSIBLE (N)125A AC LOAD CENTER NO OTHER LOADS ATTACHED EXTERIOR CONDUIT (7/8"+ ABOVE ROOF) NEMA 3R JUNCTION BOX 3' ROOF ACCESS POINT (STREET-SIDE) 3FT FIRE PATHWAY 3' 3' 3' (N) 125A SUB PANEL 120/240VAC SINGLE PHASE 801 E Borchard Ave02/17/22 Page RE V I S I O N S : Pr o j e c t N a m e 2. 8 0 0 k W ( D C ) / 2 . 5 3 0 k W ( C E C - A C ) PH O T O V O L T A I C S Y S T E M OV I E D O , B L A N C A 80 1 E B O R C H A R D A V E , SA N T A A N A , C A 9 2 7 0 7 AP N : 0 1 4 4 0 3 0 5 DA T E : 09 / 1 4 / 2 0 2 1 DR A W N B Y : ZM Co n t r a c t o r s S i g n a t u r e : SO L A R P L E X L L C 59 0 2 F I R E S T O N E B L V D SO U T H G A T E , C A 9 0 2 8 0 PH O N E : ( 5 6 2 ) 8 0 6 - 6 0 0 0 LI C E N S E : # 1 0 5 6 0 6 5 / B , C 1 0 R1 0 9 . 1 5 . 2 1 ( Z M ) SI N G L E L I N E DI A G R A M INVERTER VALUES: BRAND AND MODEL: ENPHASE IQ7-60-2-US INVERTER TYPE: MICRO-INVERTER MAX INPUT VOLTAGE (V): 48 MAX INPUT CURRENT (A): 15 NOMINAL OUTPUT VOLTAGE (V): 240 MAX CONT. OUTPUT CURRENT (A): 1 INVERTER OCPD (A): 15 MAX POWER AT 25ºC (W): 240 AMBIENT TEMPERATURE ºF: -40 PV MODULE RATINGS BRAND AND MODEL: LONGI LR4-60HPB-350M MAX POWER [Pmax] (w): 350 MAX POWER-POINT VOLTAGE [Vmp] (V): 34.4 OPEN CIRCUIT VOLTAGE [Voc] (V):40.4 MAX POWER-POINT CURRENT [Imp] (A):10.18 SHORT CIRCUIT CURRENT [Isc] (A):11.16 MAX SERIES FUSE [OCPD] (A): 20 MAX SYSTEM VOLTAGE (V): 600 SYSTEM RATINGS NOMINAL SYSTEM VOLTAGE (V):240Vac AC INVERTER OUTPUT (A):8.00 OPERATING TEMP (ºC)ͲϳǑdK39Ǒ NOTES: 1- ALL METALLIC RACEWAYS AND EQUIPMENT SHALL BE BONDED AND ELECTRICALLY CONTINUOUS (NEC 250.90, 250.96). 2- GROUNDING BUSHINGS ARE REQUIRED AROUND PREPUNCHED CONCENTRIC KNOCKOUTS ON THE DC SIDE OF THE SYSTEM (NEC 250.97) 3- THE GROUNDING ELECTRODE CONDUCTOR WILL BE CONTINUOUS, EXCEPT FOR SPLICES OR JOINTS AT BUSBARS WITHIN LISTED EQUIPMENT. (NEC 250.64) 4- THE EQUIPMENT GROUNDING CONDUCTOR MAY BE USED AS A GROUNDING ELECTRODE CONDUCTOR. (NEC 250.121 EXCEPTION, INSTALLED PER 250.6(A), II, III, VI.) 5- INSTALLER TO IDENTIFY THE EXISTING GROUNDING ELECTRODE TYPE (I.E. DRIVEN ROD, UFER, WATER PIPE, OR COMBINATION OF SOME OR ALL OF THE PREVIOUSLY MENTIONED). IN EXISTING ELECTRICAL SYSTEMS THAT USE ONLY A WATER PIPING GROUNDING ELECTRODE SYSTEM, AN ADDITIONAL GROUNDING ELECTRODE (I.E DRIVEN ROD) SHALL BE PROVIDED. (NEC 250.50) -PER NEC 250.53(2), A SINGLE ROD, PIPE OR PLATE ELECTRODE SHALL BE SUPPLEMENTED BY AN ADDITIONAL ELECTRODE OF TYPE SPECIFIED IN 250.52(A)(2) THROUGH (A)(8) SPACED NO LESS THAN 6FT APART. EXCEPTION, IF A SINGLE ROD, PIPE OR PLATE GROUNDING ELECTRODE HAS A RESISTANCE TO EARTH OF 25 OHMS OR LESS, THE SUPPLEMENTAL ELECTRODE SHALL NOT BE REQUIRED. -#4 AWG CU TO UNDERGROUND METAL WATER PIPE THAT IS A MINIMUM 10 FOOT BURIAL IN PIPE LENGTH. CONNECT GROUNDING ELECTRODE CONDUCTOR WITHIN FIVE FEET OF WHERE IT ENTERS BUILDING. 250.52(A)(1), 250.68(C). -ADDITIONAL #4 AWG CONNECTION TO UFER IF AVAILABLE PER 250.66. IF UFER NOT AVAILABLE THEN TWO #6 AWG CU CONNECTIONS TO GROUND RODS SEPARATED BY AT LEAST 6 FT IS NEEDED 250.33. MICROINVERTER TO JBOX ITEM NUMBER OF MODULES IN CIRCUIT ADJUSTED TEMP. ADJUSTMENT (7/8"+ ABOVE ROOF) CORRECTED Ifc (A) FOR WIRE SIZING AWG NEEDED NUMBER OF CONDUCTORS EGC SIZE CONDUIT 1.1 8 10.00 0.91 10.99 #12 THWN-2 L1, L2, G #6 ENPHASE Q CABLE MICRO INVERTER INPUT (DC SIDE) POWER: 350W < MAX INPUT POWER OK VOLTAGE: 40.4 x 1.14 x 1 = 46.06V < 48V OK SHORT CIRCUIT: 11.16 x 1.25 = 13.95A < 15A OK WIRE CHECK FROM ABOVE TABLE ENPHASE Q CABLE CONTAINS (2) #12 THWN-2 AWG WIRES: 10.99A < 30A OK 04 OF 11 MAXIMUM VOLTAGE & VOLTAGE CORRECTION FACTOR (DC SIDE) MICRO-INVERTER INPUT [CEC 690.7] LOWEST EXPECTED AMBIENT TEMPERATURE (ºC):-7 Ǒ VOLTAGE CORRECTION FACTOR:1.14 MODULE OPEN CIRCUIT VOLTAGE:40.4 MODULE PER MICRO-INVERTER 1 ADJUSTED VOLTAGE:46.06 MAXIMUM VOLTAGE:48 V SOLAR PV CIRCUIT BREAKER AIC RATING = 10kA SUB PANEL BUS RATING PER NEC 705.12(B)(2)(3)(b) 125A x 120% = 150.00A TOTAL BUS LOAD = 130.00A ≤ 150.00A LOAD CENTER TO MSP CALCULATION ITEM TOTAL INVERTER OUTPUT (A) CONTINUOUS RESULT (A)TEMPERATURE CORRECTION CORRECTED (A)AWG NEEDED NUMBER OF CONDUCTORS EGC/GEC CONDUIT 3.1 8.00 1.25 10.00 0.91 10.99 #10 THWN-2 L1, L2, N, G #8 3/4" EMT 4.1 24 1.25 30.00 0.91 32.97 #10 THWN-2 L1, L2, N, G #8 3/4" EMT J-BOX TO LOAD CENTER CALCULATION ITEM ADJUSTED (A) TEMP. ADJUSTMENT (7/8"+ ABOVE ROOF)ADJUSTED (A) Ifc # ENERGIZED CONDUCTORS IN RACEWAY RACEWAY ADJUSTMENT FACTOR ADJUSTED (A) AWG NEEDED NUMBER OF CONDUCTORS EGC SIZE CONDUIT 2.1 10.00 0.91 10.99 2 1.00 10.99 #10 THWN-2 (1)L1, (1)L2, G #8 3/4" EMT (N) 30A PV BREAKER 8 TOTAL MODULES 8 TOTAL INVERTERS EQUIPMENT LEGEND ITEM DESCRIPTION A (N) LONGI LR4-60HPB-350M MODULE B (N) NEMA 3R JUNCTION BOX (1) TOTAL. SEE LAYOUT. C (N) ENPHASE AC COMBINER BOX 240VAC, NEMA 3R, 10KAIC D (N) NEMA 3R 30A AC DISCONNECT 240VAC 10,000AIC RATING, NON-FUSIBLE, BLADE TYPE VISIBLE & LOCKABLE INV #1: (N) ENPHASE IQ7-60-2-US INVERTER PV SOLAR BREAKER TO BE MOUNTED ON THE OPPOSITE END OF THE BUSBAR FARTHEST FROM THE MAIN BREAKER OR INPUT FEEDER, AND NOT TO BE AT BOTH ENDS IF IT IS A CENTER-FED PANELBOARD. 705.12 (B)(2)(3)(b) or (d) #6 BARE COPPER GROUND - EQUIPMENT CIRCUIT 1 - 8 MODULES INV# 1 (TYP.) A 1.1 4.1 ON OFF G D 4.1 G 20A PV SOLAR 10A ENVOY. C (N) 20A PV BREAKER (N) 20A PV BREAKER G (N) PV LOAD ONLY COMBINER BOX 125A, 10KAIC, 240V (12) MODULES (E) SOLAREDGE SE3800H-US INVERTER (E) 30A AC DISCONNECT (E) PV SYSTEM NOT IN SCOPE OF WORK G B 2.1 3.1 PER NEC 250.122, 250.166, 690.47(C)(3), 250.64(E) SEE NOTES EGC/GEC SEE NOTE 5 M N (E) 100A MAIN BREAKER END-FED G LINELOAD (E) 100A MAIN SERVICE METER/PANEL 120/240VAC, 1-PHASE, 3-WIRE, 10KAIC RATING, MSP SUITABLE FOR USE WITH 60°C/75°C Cu/Al WIRE N (N) 125A SUB PANEL 120/240VAC, 1-PHASE, 3-WIRE, 10KAIC RATING, MSP SUITABLE FOR USE WITH 60°C/75°C Cu/Al WIRE (N) 30A PV BREAKER (N) 100A MAIN BREAKER ALL RELOCATED BREAKERS ARE WITHIN 6' OF ORIGINAL LOCATION ADJACENT TO MAIN SERVICE PANEL. [210.12(D)] LUG ONLY (3) #3 AWG Cu (1) #8 AWG Cu 1" EMT COUNTY ELECTRONIC STAMP 801 E Borchard Ave02/17/22 Page RE V I S I O N S : Pr o j e c t N a m e 2. 8 0 0 k W ( D C ) / 2 . 5 3 0 k W ( C E C - A C ) PH O T O V O L T A I C S Y S T E M OV I E D O , B L A N C A 80 1 E B O R C H A R D A V E , SA N T A A N A , C A 9 2 7 0 7 AP N : 0 1 4 4 0 3 0 5 DA T E : 09 / 1 4 / 2 0 2 1 DR A W N B Y : ZM Co n t r a c t o r s S i g n a t u r e : SO L A R P L E X L L C 59 0 2 F I R E S T O N E B L V D SO U T H G A T E , C A 9 0 2 8 0 PH O N E : ( 5 6 2 ) 8 0 6 - 6 0 0 0 LI C E N S E : # 1 0 5 6 0 6 5 / B , C 1 0 R1 0 9 . 1 5 . 2 1 ( Z M ) ST R U C T U R A L AT T A C H M E N T 05 OF 11 (1) 5/16"x 3.5" lag screw minimum 2-1/2" embedment Unirac Rail L-Foot w/ hardware flashing pv module (1) 5/16"x 3.5" lag screw minimum 2-1/2" embedment flashing pv module Unirac Rail, L-Foot comp shingle roofing materialroof framing 3" TO 5" COUNTY ELECTRONIC STAMP 801 E Borchard Ave02/17/22 Page RE V I S I O N S : Pr o j e c t N a m e 2. 8 0 0 k W ( D C ) / 2 . 5 3 0 k W ( C E C - A C ) PH O T O V O L T A I C S Y S T E M OV I E D O , B L A N C A 80 1 E B O R C H A R D A V E , SA N T A A N A , C A 9 2 7 0 7 AP N : 0 1 4 4 0 3 0 5 DA T E : 09 / 1 4 / 2 0 2 1 DR A W N B Y : ZM Co n t r a c t o r s S i g n a t u r e : SO L A R P L E X L L C 59 0 2 F I R E S T O N E B L V D SO U T H G A T E , C A 9 0 2 8 0 PH O N E : ( 5 6 2 ) 8 0 6 - 6 0 0 0 LI C E N S E : # 1 0 5 6 0 6 5 / B , C 1 0 R1 0 9 . 1 5 . 2 1 ( Z M ) SI G N A G E 06 OF 11 NEC 705.10 - ON MAIN SERVICE PANEL: CAUTION POWER TO THIS BUILDING IS ALSO SUPPLIED FROM THE FOLLOWING SOURCES WITH DISCONNECTS LOCATED AS SHOWN. 801 E BORCHARD AVE, SANTA ANA, CA 92707 WARNING ELECTRIC SHOCK HAZARD TERMINALS ON BOTH THE LINE AND LOAD SIDES MAY BE ENERGIZED IN THE OPEN POSITION NEC 690.13, 690.15 - ON AC/DC DISCONNECT NEC 690.53, 690.54 - ON AC/DC DISCONNECT AC PHOTOVOLTAIC DISCONNECT NEC 690.13, 690.15 - AT J-BOXES, ENCLOSURES, DISTRIBUTION EQUIPMENT, AND AC/DC DISCONNECTS WARNING ELECTRICAL SHOCK HAZARD TERMINALS ON BOTH THE LINE AND LOAD SIDE MAY BE ENERGIZED IN THE OPEN POSITION NEC 690.56 - WITHIN 3FT OF SERVICE DISCONNECT: RAPID SHUTDOWN SWITCH FOR SOLAR PV SYSTEM (690.56(C) RED WITH WHITE LETTERING) WARNING POWER SOURCE OUTPUT CONNECTION DO NOT RELOCATE THIS OVERCURRENT DEVICE NEC 705.12(B)(2)(3)(b) - BY BREAKER AT DISTRIBUTION EQUIPMENT: NEC 705.12(B)(3) - AT DISTRIBUTION EQUIPMENT: AC PHOTOVOLTAIC DISCONNECT WARNING MULTI - POWER SUPPLY SOURCES INCLUDE: UTILITY GRID, PV SOLAR TURN RAPID SHUTDOWN SWITCH TO THE "OFF" POSITION TO SHUT DOWN PV SYSTEM AND REDUCE SHOCK HAZARD IN ARRAY SOLAR ELECTRIC PV PANELS SOLAR PV SYSTEM EQUIPPED WITH RAPID SHUTDOWN (690.56(C)(1)(a) YELLOW WITH BLACK LETTERING) NEC 690.56 - ON RAPID SHUTDOWN DISCONNECT: OUTPUT CURRENT: OPERATING VOLTAGE: 240V 24.0A NEC 690.54 - ON AC DISCONNECT: NEC 705.12(B)(2)(3)(c) - BY BREAKER AT DISTRIBUTION EQUIPMENT: WARNING THIS EQUIPMENT FED BY MULTIPLE SOURCES. TOTAL RATING OF ALL OVERCURRENT DEVICES, EXCLUDING MAIN SUPPLY OVERCURRENT DEVICE, SHALL NOT EXCEED AMPACITY OF BUSBAR ALL PLAQUES AND SIGNAGE REQUIRED BY THE LATEST EDITION OF CALIFORNIA ELECTRICAL CODE WILL BE INSTALLED AS REQUIRED. ALTERNATE POWER SOURCE PLACARD SHALL BE METALLIC OR PLASTIC, ENGRAVED, OR MACHINE PRINTED LETTERS IN A CONTRASTING COLOR TO THE PLAQUE. THIS PLAQUE WILL BE ATTACHED BY POP RIVETS OR SCREWS OR OTHER APPROVED METHOD. IF EXPOSED TO SUNLIGHT, IT SHALL BE UV RESISTANT. PHOTOVOLTAIC DC CONDUCTORS SHALL BE LABELED, "WARNING PHOTOVOLTAIC DC POWER SOURCE" OR EQUIVALENT EVERY 10 FT AND KEPT MINIMUM 18" BELOW THE ROOF SURFACE. PV DC CIRCUIT LABELS SHALL APPEAR ON EVERY SECTION OF THE WIRING SYSTEM THAT IS SEPARTED BY ENCLOSURES, WALLS, PARTITIONS, CEILINGS, OR FLOORS. PV DC LABELS SHALL BE REFLECTIVE, SUITABLE FOR SURROUNDING ENVIRONMENT, AND WHITE LETTERING ON A RED BACKGROUND. [690.31(G)] EXPOSED NON-CURRENT CARRYING METAL PARTS OF MODULE FRAMES, EQUIPMENTS, AND CONDUCTOR ENCLOSURES SHALL BE GROUNDED IN ACCORDANCE WITH 250.134 OR 250.136(A) REGARDLESS OF VOLTAGE. EACH MODULE SHALL BE GROUNDED USING THE SUPPLIED CONNECTION POINT IDENTIFIED ON THE MODULE AND THE MANUFACTURER'S INSTRUCTIONS. IF THE EXISTING GROUNDING ELECTRODE SYSTEM CANNOT BE VERIFIED OR IS ONLY METALLIC WATER PIPING, IT IS THE CONTRACTOR'S RESPONSIBILITY TO INSTALL A SUPPLEMENTAL GROUNDING ELECTRODE. EQUIPMENT COMPLIES WITH RAPID SHUTDOWN REQUIREMENTS. [690.12] PLAQUES SHALL BE PLASTIC ENGRAVED IN A CONTRASTING COLOR TO THE PLAQUE. MSP A/C D.INV A/C D.PVLC PVLCSUB N COUNTY ELECTRONIC STAMP ENPHASE AC COMBINER BOX PV SYSTEM DISCONNECT FOR UTILITY OPERATION MAIN ELECTRIC SERVICE DISCONNECT PV LOAD CENTER (E ) P V S Y S T E M SUB PANEL 801 E Borchard Ave02/17/22 Page RE V I S I O N S : Pr o j e c t N a m e 2. 8 0 0 k W ( D C ) / 2 . 5 3 0 k W ( C E C - A C ) PH O T O V O L T A I C S Y S T E M OV I E D O , B L A N C A 80 1 E B O R C H A R D A V E , SA N T A A N A , C A 9 2 7 0 7 AP N : 0 1 4 4 0 3 0 5 DA T E : 09 / 1 4 / 2 0 2 1 DR A W N B Y : ZM Co n t r a c t o r s S i g n a t u r e : SO L A R P L E X L L C 59 0 2 F I R E S T O N E B L V D SO U T H G A T E , C A 9 0 2 8 0 PH O N E : ( 5 6 2 ) 8 0 6 - 6 0 0 0 LI C E N S E : # 1 0 5 6 0 6 5 / B , C 1 0 R1 0 9 . 1 5 . 2 1 ( Z M ) MO D U L E SP E C I F I C A T I O N S 07 OF 11 COUNTY ELECTRONIC STAMP 801 E Borchard Ave02/17/22 SOLARPLEX LLC 5902 FIRESTONE BLVD, SOUTH GATE, CA 90280 I (562) 806-6000 I #1056065/B,C10 Project Name: OVIEDO, BLANCA I 801 E BORCHARD AVE, SANTA ANA, CA 92707 Date: April 6, 2022 Dear Plan Checker, We have completed the plan corrections, here are the details: Revised wall equipment according to as-built information. Added warning label per installation on site. Corrections are clouded and noted with Delta 1. Sincerely, Leon Zhu YourSolarPlans 3000 E. Birch Street, Suite 201 I Brea, CA 92821 p: 844.PV-ELITE I e: Leora,yoursolarplans.com I s: yoursolarplans.com 801 E Borchard Ave04/13/22 PHOTOVOLTAIC GENERAL NOTES · ALL MATERIALS, EQUIPMENT. INSTALLATION AND WORK · ALL GROUNDED (NEUTRAL) CONDUCTORS INSULATION SHALL BE SOLID WHITE, GRAY PERFORMED SHALL BE IN ACCORDANCE WITH THE FOLLOWING OR WITH 3-WHITE STRIPES (NEC 2000 200 7 400 22], ALL GROUNDING CONDUCTORS COUNT/ ELECTRONIC STAMP CODES SHALL BE OF BARE WIRE WITHOUT COVERING OR WITH INSULATION OF GREEN OR - 2019 CRC /2018 IBC GREEN WITH YELLOW STRIPES NEC 250 119 & 400 23 THE COLOR OF UNGROUNDED .2019 CRC 12018 IRC CONDUCTORS SHALL BE OTHER THAN FOR GROUNDED. (NEUTRAL) AND GROUNDING -2019 CEC /2017 NEC CONDUCTORS [NEC 310 110(0)) · 2019 CMC /2018 IMC 2019 CPC /2019 PC MAXIMUM CONDUCTOR LENGTH BETWEEN SUPPLY SIDE CONNECTION AND OVERCURRENT PROTECTION IS 10FT [NEC 705 31]2019 CFC /2010 IFC -2019 BUILDING ENERGY EFFICIENCY STANDARDS CONNECTIONS ON THE LOAD SIDE OF THE SERVICE DISCONNECTING MEANS OF THE OTHER SOURCE(S) AT ANY DISTRIBUTION EQUIPMENT ON THE PREMISES SHALL BE IN · ALL EQUIPMENT SHALL BE LISTED AND LABELED BY A RECOGNIZED ACCORDANCE WITH NEC 705 12(B) ELECTRICAL TESTING LABORATORY AND L.A. TEST LAB EQUIPMENT INSTALLED SHALL BE PER ITS LISTING REQUIREMENTS DC WIRING INSIDE A BUILDING MUST BE IN METALLIC TYPE RACEWAYS CONDUITS_ AND THE MANUFACTURERS INSTRUCTIONS (NEC 110.2. 110.3,ENCLOSURES OR CABLE SHEATHINGS [NEC 690 3110)] 6904(B/.690 12(D)) METALLIC TYPE RACEWAYS CONDUITS.ENCLOSURES, AND CABLE SHEATHS ALL OUTDOOR EQUIPMENT SHALL BE NEMA 3R RATED. INCLUDING CONTAINING CIRCUITS OVER 250-VOLTS TO GROUND MUST BE BONDED IN ALL ROOF MOUNTED TRANSITION BOXES AND SWITCHES ACCORDANCE WITH NEC 250 97. ALL EQUIPMENT SHALL BE PROPERLY GROUNDED AND BONDED IN CONNECTORS SHALL BE OF LATCHING OR LOCKING TYPE CONNECTORS THAT ARE READILY ACCESSIBLE AND OPERATING AT OVER .30 -VOLTS SHALL REQUIRE A TOOL TOACCORDANCE WITH NEC ARTICLE 250.OPEN AND MARKED "DO NOT DISCONNECT UNDER LOAD" OR NOT FOR CURRENT INTERRUPTING " (NEC 690 331C18 (E)(2)1 ALL PV CIRCUITS CONNECTED AND EQUIPMENT SHALL BE PROTECTED AGAINST OVERCURRENT, OVERCURRENT DEVICES · FOR PV MODULES EQUIPMENT GROUNDING CONDUCTOR (EGC) SMALLER THAN46.AWG SHALL BE LISTED FOR USE IN PV SYSTEMS OVERCURRENT SHALL BE PROTECTED FROM PHYSICAL DAMAGE BY AN IDENTIFIED RACEWAY OR CABLE PROTECTIVE DEVICES SHALL NOT BE REQUIRED FOR CIRCUITS ARMOR UNLESS INSTALLED WITHIN HOLLOW SPACES OF THE FRAMING MEMBERS OF WITH SUFFICIENT AMPACITY FOR THE HIGHEST AVAILABLE BUILDINGS OR STRUCTURES AND WHERE NOT SUBJECT TO PHYSICAL DAMAGE [NEC CURRENT CIRCUITS CONNECTED TO CURRENT LIMITED SUPPLIES 69046 250_120(C)] AND ALSO CONNECTED TO SOURCES HAVING HIGHER CURRENT AVAILABILITY SHALL BE PROTECTED AT THE HIGHER CURRENT · THE INTERCONNECTION POINT SHALL BE ON THE SUPPLY SIDE OF ALL GROUND-FAULT SOURCE CONNECTION [NEC 690 91 PROTECTION EQUIPMENT [NEC 705321 DISCONNECTING MEANS OF THE PV SYSTEM (INCLUDING RAPID · CABLES/WIRES THAT ARE SUBJECT TO PHYSICAL DAMAGE, SUCH AS THOSE NOT LOCATED UNDER THE MODULES MUST BE PROTECTED [NEC 3004]SHUTDOWN INITIATION) SHALL BE LOCATED IN A READILY ACCESSIBLE LOCATION NEAR THE EQUIPMENT [NEC 690 13 690 15] · FOR ELECTRICAL SERVICE REPLAC,EMENTS, BONDING TO THE METAL PIPES OF NATURAL GAS HOT WATER AND COLD WATER MUST BE PROVIDED [NEC 250 104] · RAPID SHUTDOWN EQUIPMENT TO COMPLY WITH NEC 690 12 GROUNDING ROD ELECTRODES SI IALL BE INSTALLED a-FT MINIMUM IN CONTACT WITt I ENERGY STORAGE SYSTEM TERMINALS LOCATED MORE THAN 5 SOIL AND MINIMUM 5/8 -INCH DIAMETER (NEC 250 52(A)(5) 250.53(G)] FEET AWAY OR ON OPPOSITE SIDE OF WALL FROM CONNECTED EQUIPMENT MUST HAVE DISCONNECTING MEANS IN ACCORDANCE THE MARKINGS 'WARNING PITOTOVOL TAIC POWER SOURCE' FOR DC RACEWAYS AND WITH NEC 706.7(E) AND LABELED PER 706 7I0) A SECOND CABLE ASSEMBLIES MUST BE NO MORE THAN /0-FT 00 AND IS SEPARATED BY DISCONNECTING MEANS LOCATED AT THE CONNECTED ENCLOSURES WALLS PARTITIONS CEILINGS FLOORS, OR BENDS ABOVE OR BELOW EQUIPMENT SHALL BE INSTALLED WHERE THE DISCONNECTING PENETRATIONS. [NEC 690 31(G)(318(411 MEANS AT THE ESS END OF THE CIRCUIT IS NOT WITHIN SIGHT WORKING CLEARANCES TOOT PROVIDED AT NEW AND EXISTING ELECTRICAL EQUIPMENT [NEC 11026]· THE UTILITY-INTERACTIVE INVERTERS SHALL AUTOMATICALLY DE-ENERGIZE ITS OUTPUT TO THE CONNECTED ELECTRICAL · POWER PRODUCTION SYSTEMS AND At L ASSOCIATED WIRING AND PRODUCTION AND DISTRIBUTION NETWORK VOLTAGE HAS BEEN INTERCONNECTIONS OPERATING IN PARALLEL WITH A PRIMARY POWER SOURCE SHALL RESTORED (NEC 705 40]BE PERFORMED ONLY BY QUALIFIED PERSONS [NEC 690 41C) 7058) ALL CONDUCTORS IN EXPOSED OUTDOOR LOCATIONS SHALL BE LABELS SHALL BE REFLECTIVE AND ALL LETTERS SHALL BE CAPITALIZED AND SHALL BE LISTED AND IDENTIFIED FOR USE IN DIRECT SUNLIGHT AND FOR A MINIMUM HEIGHT OF 3'8 IN WHITE ON A RED BACKGROUND [NEC 690.31(G1(4)] THE APPLICATION [NEC 690 31(C) THROUGH (F). 310 10(D)] IDENTIFICATION OF POWER SOURCE RAPID SHUTDOWN AND LABELING SHALL BE IN INSULATION OF EXPOSED CONDUCTORS UNDER THE MODULES ACCORDANCE WITH NEC 690 56(C) SHALL BE USE 2 OR PV.WIRE TYPE FOR PV SYSTEMS (UL 4703 854 LISTED) [NEC 690 31(C))· SMOKE ALARMS AND CARBON mONOxIDE ALARMS ARE REQUIRED 10 BE RE ['ROE! ! I ED ONTO THE EXISTING DWELLING AS PER THE 2019 CRC THESE SMOKE ALARMS ARE REQUIRED TO BE IN ALL BEDROOMS OUTSIDE EACH BEDROOM AT LEAST ONE ONFINE STRANDED CABLE CONNECTIONS MUST BE MADE IN LUGS .AND EACi I FLOOR OF THE HOUSE. CARBON MONOXIDE ALARMS ARE REQUPED TO BE AND TERMINALS TO ENSURE A THOROUGHLY GOOD CONNECTION RETROFITTED OUTSIDE EACH BEDROOM AND AT LEAST ONE ON EACH FLOOR OF THE WITHOUT DAMAGING THE CONDUCTORS [NEC 110 14(A)]HOUSE .(CRC 314 315) FLEXIBLE, FINE-STRANDED CABLES SHALL BE TERMINATED ONLY SMOKE ALARMS AND CARBON MONOXIDE ALARMS ARE REQUIRED PER CRC SECTIONS WITH TERMINALS LUGS DEVICES, OR CONNECTORS THAT ARE 314 AND 315 TO BE VERIFIED AND INSPECTED BY THE INSPECTOR IN THE FIELD IDENTIFIED AND LISTED FOR SUCH USE [NEC 690 3111-1). 110 14] · A LADDER MUST BE PROVIDED FOR INSPECTIONS IN ACCORDANCE WITH Cal-OSHA ALL PV CIRCUIT CONDUCTORS SHALL BE MARKED ON EACH END REGULATIONS, SECURED AND EXTENDING 3-FT ABOVE THE ROOF AND GROUPED FOR UNIQUE IDENTIFICATION [NEC 690 3163)1 · ALL OF THE REQUIRED MARKINGS, SIGNS AND LABELS MUST BE INSTALLED ON ALL ALL EXTERIOR CONDUIT FITTINGS, AND BOXES SHALL BE RAIN EQUIPMENT PRIOR TO ANY INSPECTIONS TIGHT AND APPROVED FOR USE IN WET LOCATIONS [NEC 314.15] — · 2 I—(/) cnc0 — OD < C·i 7-1, - · > O 0 0 c'n 0 2cs1 · g C O V E R PA G E ;PI 1AOF 11 801 E Borchard Ave04/13/22 TAth· Enphase IQ 7 and IQ 7+ Mrcromverters enphase Tom with foe Once) OndlI old ready . S U . and I .sses. rt) +. 4.1:sn in f t nOv s.itoo,ty tilt' 4,Oallanor Dreg!, 1S ,10:53 ini, ving the !·lalla,,sh. 5ystern etfwCry 'art Of to Enphase ig ti, g :0 7 and Microtnvertets integrate th toe Loohase LIvSy" Lf vhaw .() thltiory 3,35!In Lrpho'- In 011t0t n'Ig and analyst' Set t.are ro-nverters erring the 'eliagdity ,4 0negreS Set 0,01 fly egr.nr.g.r3n, !c10 ',Or a rIlEMH, ', OLDS of 00. , co C.] ngt ling li rrO,a er(mge Ind5:50 x31133114 of up to v." IstrisitP · .········11·····.-- ···· ······ · w · · · .··· · ····· A ...S.., I ·T···· ..1,·····064.1 1..1. —.7.41 God Sposio 4110 PI I if kal ...op J. ,.· ...· EN PHASE Enphase IQ 7 and IQ 7+ Microinverters ,Spur DATA (DC1 C·rAmonIv Lam, n·······1 ps·Angs· Mextmum wout DC. WSW Opet.····· tans, Car cw ·ge .fact.shott·tr·········.1 At, OC t,·IN,Itf·ved AAA,. 100 SCADS t se Us 107O. uS 122 USi 1079-L05 72 BUS 236W 350W+2TiiW 4·10 W · 00 :gli .0 ,1····· ASV ASV 1M1 ·vt AR V 16 v ttA 1,1 ·· 15 A to 00 OUTPUT DATA (AC) autpAl Dcw, 1001 /A t · vaSase· ·He.' Na·wevi tr.vv·v · ,······ 10 · Microltwerter /0E. Alecromverter 3503,ICC Inoon Cr2. 1112640 011 00.? 1632290 ··· ·v "O T t nO&V 1 070 ED Tv SE ,It 5 MA,5 a AT, P EFFICIENCY ,.,2411 V (1. V WittO V HMIS An, MECHANICAL DATA Ar········· Incr.,.· AM' A·Ac. ··al·siocAt M "DAV TO,MA 1, tat · to, Any,···· m NT MA Type 6 couT, MIA DAC, IV( T AdmA.0 ACORES COrt.,1/11Cht:0,Dow, · ot CHAtn .Alon tHt C· .1··· :nowt T 4·4,1 T 0 10 ENPHASE COUNTY waRoNicvrom, 801 E Borchard Ave04/13/22 .,401·11. CSA Group 1101110e. Certificate of Compliance Certificate; 2462554 Master Contract: 254141 Project: 2692509 Issued to: Hanwha Q.CELLS GmbH 17-21 Sonnenallee Bitterfeld-Wolfen, Saxony-Anhalt 06766 Germany Date Issued. January 28, 2014 The products listed below are eligible to bear the CSA Mark shown with adjacent indicators 'C' and 'US' for Canada and US or with adjacent indicator 'US' for US only Or without either indicator for Canada only. c US rq Awictrwca, Issued by: BriJ Aggarwal. P.Ene PRODUCTS CLASS 5311 10 - POWER SUPPLIES - Photovoltaic Modules and Panels CLASS 5311 90 - POWER SUPPI.IES - Photovoltaic Modules and Panels - Certified to US Standards PhOlOVOItaic Modules with maximum system voltage of 600 V dc or 1000 V de. and Class C fire class rating, Model Series Q.BASE (3Y XXX; Q.PRO GY XXX, Q.PLUS-G3 XXX. Q.PRO BER-03 XXX, Q.PRO RIK- 03 XXX where XXX is the power output front 205 W to 280W, Q PEAK XXX, Q PF.AK - GY XXX and Q PEAK BLK XXX, Q PEAK BLK - GY XXX where XXX is the power output from 245 W to 295 Wand Q.PRO 1 XXX where XXX is the power output from 280 W to 335 W (in steps of 5 W) with the following electrical ratings typical at 230W for Q.BASE./Q PRO, 270W for Q.PLUS-03, 240W for QPRO BFR-03 Q PRO BLK, 249W for Q PEAK and 100W for Q PRO I respectively 2 Standard Test Condition (STC). Open Circuit Voltage t Voct: 36.69 36.79138 73'36 641655145 4 V Short Circuit Current Ilse) 8 58/8.63/9 44/8.24/8 998.82 A Operating Voltage (Vpmax) 28 96,29 07/30 62/30 73129.55/35 8 V Current at Operating Voltage (lpmax): 7 99/8 04i8 82/7 818 298.38 A Lams RtA, 2012.5-22 1,0 I Test Verification of Conformity [...In Ike basis NI fro 1441astalissabirn the samasiti el in* ware product Mee been foend la tirtitplgaihK at Ow searanadvansersainset awl am be rats a era anwir en. Product Dataptiore Ratings & Peinitiple Characteristic* Morals, Rand warns: Relevant Standerd6 Verdlcation issuing OM. Date of rens. Tenillerserl Falareetitt_ ISavwdlontat h retlew imply redact arelleallan. COneldead by, call Gaga Technical, 4. firegarstence *ware, taw 43.101204s POnII.6e. 145.5 kneser Ave. Kiverted, CA 94544 USA RR Reels wen Integrated Cir °unary/. rg Vass Reatante Ram +four Mount (Svnenetual) CASS A Fire Rated for IRVIStpcm apotrations when dung,rwe 1.2 and 3, fsted Prettovoltalc rnoddes Chas A Fre Rated for SteapSrepe taphatt.s.th TY9Par 2 and A lista pnostwoltalc moat es tested wdo a 3" gapLdtstento between Me bottom the nalltdell66. 9nd 4..ol not&641. per the standard ths astern an Overacted at alre gee *lowed by.the Manufacturers instal Neon instructions. No peracterguardingrs reooired 5131 GO 005. 51-616041158, S1 5000-601 end 51-4S-061 ho *Wet Roof Mount UL 001 Mar. ISL and IS 3l Standard for Safety MounalgGesienu...untnit 6a.tes· .aarrapinejleteYition El.lit2P-s, and Ground Lugs be U. WWI Plat.Plate Photowita,caSodides and.Partels, Pad Edam dated law 211, 10t5 lafarencin1410763 Third Steam dated Nov la MU, aection 31.2) Standard for Saletyfor Rat-Pleb- Photostilac Snail. and Panes. Interva Testing Services NA, Inc. 6431 lewdly Orive fdiddletern, Vol 53561 larrlitail 113/ MIMS 10911490160 466 t 1415413411:140401e tpt0I5b1Ibill 4 IIIIN1911911.1111061a r il l 1.111 Mika( 4 and &addled eadamatildanInewelPiewer. Illiteepert aleveull earlowteaare 0noI.w.db, Gregor/Allen Ode faeneeeng Tarn IkeResistance %IVORY( 0: DIrt 0;;30/2616:- o Fqg 8E5,2gaz, 880011 re UL LI S T I N G C o ,0 CO 0 0 oi> 0 co s to en 0 to- 0 uj —8 co wc 0 xLu CO < Lo, - W , 0 a. ix — ·wceEi.cn 05 "2 8 ° *- Page 09 OF 11 801 E Borchard Ave04/13/22 (C) RAIL SPLICE GROUNDING EITHER METHOD 1.3 PER MANUFACTURERS INSTALL INSTRUCTIONS (1) BOND STRIP GROUNDS RAIL TO RAIL SPLICES -STAR WASHERS USED g liitOTO BOND RAIL TO BONDING STRIP , \ -- _ ,I RAIL RAIL .. 2 ,.. , ---- 2AC- I- #6 BARE (3) COPPER (3) WHERE NEITHER BONDING STRIP, INTEGRATED GROUNDING SPLICE BAR OR INTEGRATED GROUNDING MIDCLAMP ARE USED, 01 2703 APPROVED GROUND LUG WITH #6 BARE COPPER SHALL BE USED TO GROUND SPLICED RAILS. USE METHOD (2) RAIL TO RAIL BONDING #6 BARE COPPER WIRE -, JBOX GROUND BUSHINGS REQ. , \— CONDUIT- COMPRESSION- -- FITTING (2) SPLICE BAR SELF-TAP SCREWS JOIN RAILS BONDING STRIPS USED ON RAILS WITH GROUND LUGS IF SPLICE BAR HAS INTEGRATED GROUND BONDING STRIP IS NOT NECESSARY T ir c no nuoo LOCK /- 1- - LI GROUNDING BUSHING WITH LAY-IN LUG ),, \ / -ENCLOSURE CONTINUOUS GROUND STRIP INSULATION CONDUIT GROUNDING DETAIL EQUIPMENT GROUND BUSHINGS REQ. FOR SYSTEMS OVER 250V \ (C)/ (A) A CONTINUOUS s\". GROUND PER SLD_--- _ _INV (IF USED) - SOLAR METER (IF REQ) MIDCLAMP TEETH MODULE PENETRATION_ \ MODULE RAIL SERRATED T-BOL I BONDS CLAMP TO RAIL GROUNDING MID CLAMP EACH GROUNDING MID CLAMP PIERCES THROUGH THE ANODIZED COATINGS OF BOTH THE MODULE FRAME AND THE MOUNTING RAIL TO FORM SECURE ELECTRICAL BONDS WHICH ARE REPEATED THROUGHOUT THE ARRAY MSP Ad\ IRONRIDGE =111 UFO Family of Components —0121 -M -11111111CMOIMIt ut. -Se,- · G R O U N D I N G 801 E Borchard Ave04/13/22 Enphase·Energy // Rapid Shutdown Rapid shutdown is built-in The 2014 edition of the National Electrical Code (NEC 2014) added new rapid shutdown requirements for PV systems installed on buildings. Enphase Microinverters fully meet rapid shutdown requirements in the new code without the need to install any additional electrical equipment. What's new in NEC 2014? · ! roo! o„,· String inverters require work arounds for rapid shutdown fhisicientwi Siring Inernwt Commercial String Inverter Enphase comes standard with rapid shutdown capability — — To learn more, visit Commeiclal Microinverter [el enphase 7,0,2010 01.1W E.1185 ape Snutlown Syslom Ego (9 ONLINE crarincloritilltalaatilaaT___ QUW.E341165 Photovoltaic Rapid Shutdown System Equipment Photovoltaic Rapid Shutdown System Equipment .1.111110. aleggN rag L. coma, Eusanotic PAW n1 E2a, mann. Inao M1-olvo< ,Aint .1. -vive al., 17 „ 6,04:11 .l01 wwwoaco,0,1,'" 1.1. .11 coma. 0 atelJoE,,,, halAEO, ,anonaoe--0iLv. E3411653....10,1 , ...olnuca -ZEF7.7.!,;a7 > J..C.) N Lc) Ez0 ° °ta < < Z < <OcrZ0 2 0 0 < z< 5 ui H OD 0 E< II 0 801 E Borchard Ave04/13/22 PROJECT INFORMATION NAME:OVIEDO, BLANCA ADDRESS: 801 E BORCHARD AVE, SANTA ANA, CA 92707 APN:01440305 JURISDICTION:SANTA ANA _ CONTRACTOR INFORMATION CONTRACTOR: SOLARPLEX LLC ADDRESS: 5902 FIRESTONE BLVD, SOUTH GATE, CA 90280 PHONE: (562) 806-6000 LICENSE #/TYPE: #1056065/13,C10 SIZE(kw): MODULE TYPE: INVERTERS(S): SYSTEM INFORMATION 3.200 (DC) / 2.883 (CEC-AC) 8 HANWHA Q CELLS Q.PEAK DUO BLK ML-G10.A+ 400 8 ENPHASE1Q7PLUS-72-2·US INVERTER TYPE: MICRO-INV- ERTER SCOPE OF WORK: INSTALL I (8) ROOF MOUNTED PV SOLAR MODULES, (8) ENPHASE IQ7PLUS-72-2-US INVERTER(S)(240V). (1) 125A AC LOAD CENTER (240V), 1PH, 3W. — TABLE OF CONTENTS PAGE 1 I COVER PAGE [PAGE 2 1SITE PLAN ' PAGE 3 PLOT PLAN— ! PAGE 4 SINGLE LINE DIAGRAM 1PAGE 5 STRUCTURAL ATTACHMENT DETAIL PAGE 6 LABELS AND WARNING SIGNAGE [PAGE 7 PV MODULE SPEC SHEET , PAGE 8 _NVERTER SPEC SHEET— PAGE 9 UL LISTING 1PAGE 10 GROUNDING [PAGE 11 1 RAPID SHUTDOWN PHOTOVOLTAIC MODULES AND PANEL SYSTEMS INSTALLED ON OR INTEGRAL WITH BUILDINGS. OR TO BE FREESTANDING (NOT ATTACHED TO BUILDINGS) SHALL BE TESTED. LISTED AND IDENTIFIED WITH A FRE CLASSIFICATION (CLASS C MINIMUM) IN ACCORDANCE WITH UL1703 WHERE CLASS A OR B ROOFING IS REQUIRED THE PV SOLAR SYSTEM (PV PANEL 8. RACK) SHALL HAVE THE SAME CLASS/TYPE RATING OR BETTER OCCUPANCY GROUP R3 CONSTRUCTION TYPE V-B - mum aecntame STAMP LU t7tC.) I—(/) .) CI) c0 -<1co c‘i O > O 0'—' · ON O. CO V E R PA G E 0 S Z3 ip: > co CO C p cf)x — uicr <Z Z .j " 4 00WO 0 0CI) CO a- I j Page 1B OF 11 ***PLANS REVISED TO REFLECT REVISED WALL EQUIPMENT (PREVIOUS WAS DISCONTINUED). AZ. 4/13/22*** 801 E Borchard Ave 04/13/22 NOTE. 1 IN CASE OF EMERGENCY CALL AT WORK PHONE 4 OR HOME PHONE4 2 SEDIMENT FROM AREAS DISTURBED BY CONSTRUCTION SHALL BE RETAINED ON SITE USING STRUCTURAL CONTROLS TO THE MAXIMUM EXTENT PRACTICABLE 3 STOCKPILES OF SOIL SHALL BE PROPERLY CONTAINED TO MINIMIZE SEDIMENT TRANSPORT FROM THE SITE TO STREETS DRAINAGE FACILITIES OR ADJACENT PROPERTIES VIA RUNOFF, VEHICLE TACKING OR WIND 4 APPROPRIATE BMPS FOR CONSTRUCTION-RELATED MATERIALS. WASTES, SPILLS SHALL BE IMPLEMENTED TO MINIMIZE TRANSPORT FROM THE SITE TO STREETS DRAINAGE FACILITIES OR ADJOINING PROPERTIES BY WIND OR RUNOFF 5 RUNOFF FROM EQUIPMENT AND VEHICLE WASHING SHALL BE CONTAINED AT CONSTRUCTION SITES UNLESS TREATED TO REDUCE OR REMOVE SEDIMENT AND OTHER POLLUTANTS 6 ALL CONSTRUCTION CONTRACTOR AND SUBCONTRACTOR PERSONNEL ARE TO BE MADE AWARE OR THE REQUIRED BEST MANAGEMENT PRACTICES AND GOOD HOUSEKEEPING MEASURES FOR THE PROJECT SITE AND ANY ASSOCIATED CONSTRUCTION STAGING AREAS 7 AT THE END OF EACH DAY OF CONSTRUCTION ACTIVITY ALL CONSTRUCTION DEBRIS AND WASTE MATERIALS SHALL BE COLLECTED AND PROPERLY DISPOSED IN TRASH OR RECYCLE BINS 8 CONSTRUCTION SITES SHALL BE MAINTAINED IN SUCH A CONDITION THAT AN ANTICIPATED STORM DOES NOT CARRY WASTES OR POLLUTANTS OFF THE SITE DISCHARGES OF MATERIAL OTHER THAN STORMWATER ONLY WHEN NECESSARY FOR PERFORMANCE AND COMPLETION OF CONSTRUCTION PRACTICES AND WHERE THEY DO NOT CAUSE OR CONTRIBUTE TO A VIOLATION OF ANY WATER QUALITY STANDARD CAUSE OR THREATEN TO CAUSE POLLUTION CONTAMINATION. OR NUISANCE OR CONTAIN A HAZARDOUS SUBSTANCE IN A QUANTITY REPORTABLE UNDER FEDERAL REGULATIONS 40 CFR PARTS 117 AND 302 9 POTENTIAL POLLUTANTS INCLUDE BUT ARE NOT LIMITED TO SOLID OR LIQUID CHEMICAL SPILLS WASTES FROM PAINTS, STAINS SEALANTS GLUES LIMES PESTICIDES HERBICIDES WOOD PRESERVATIVES AND SOLVENTS ASBESTOS FIBERS PAINT FLAKES OR STUCCO FRAGMENTS FUELS OILS. LUBRICANTS.AND HYDRAULIC RADIATOR OR BATTERY FLUIDS FERTILIZERS, VEHICLE/EQUIPMENT WASH WATER AND CONCRETE WASH WATER. CONCRETE, DETERGENT OR FLOATABLE WASTES. WASTES FROM ANY ENGINE/EQUIPMENT STEAM CLEANING OR CHEMICAL DEGREASING AND SUPERCHLORINATED POTABLE WATER LINE FLUSHING. DURING CONSTRUCTION. PERMITTEE SHALL DISPOSE OF SUCH MATERIALS IN A SPECIFIED AND CONTROLLED TEMPORARY AREA ON -SITE, PHYSICALLY SEPARATED FROM POTENTIAL STORMVVATER RUNOFF WITH ULTIMATE DISPOSAL IN ACCORDANCE WIT' I LOCAL. STATE AND FEDERAL REQUIREMENTS 10 DEWATERING OF CONTAMINATED GROUNDWATER. OR DISCHARGING CONTAMINATED SOILS VIA SURFACE EROSION IS PROHIBITED DEWATERING OF NON-CONTAMINATED GROUNDWATER REQUIRES A NATIONAL POLLUTANT DISCHARGE ELIMINATION SYSTEM PERMIT FROM THE RESPECTIVE STATE REGIONAL WATER QUALITY CONTROL BOARD Ti GRADED AREAS ON THE PERMITTED AREA PERIMETER MUST DRAIN AWAY FROM THE FACE OF SLOPES AT THE CONCLUSION OF EACH WORKING DAY DRAINAGE IS TO BE DIRECTED TOWARD DESILTING FACILITIES 12 IHE PERMITTEE AND CONTRACTOR SHALL BE RESPONSIBLE AND SHALL TAKE NECESSARY PRECAUTIONS TO PREVENT PUE,LIC TRESPASS ONTO AREAS WHERE IMPOUNDED WATER CREATES A HAZARDOUS CONDITION 13 THE PERMITTEE AND CONTRACTOR SHALL INSPECT THE EROSION CONTROL WORK AND INSURE THAT THE WORK IS IN ACCORDANCE WITH THE APPROVED PLANS 14 THE PERMITTEE SHALL NOTIFY ALL GENERAL CONTRACTORS. SUBCONTRACTORS MATERIAL SUPPLIERS LESSEES AND PROPERTY OWNERS THAT DUMPING OF CHEMICALS INTO THE STORM DRAIN SYSTEM OR THE WATERSHED IS PROHIBITED 15 EQUIPMENT AND WORKERS FOR EMERGENCY WORK SHALL BE MADE AVAILABLE AT ALL TIMES DURING THE RAINY SEASON NECESSARY MATERIALS SHALL BE AVAILABLE ON SITE AND STOCKPILED AT CONVENIENT LOCATIONS TO FACILITATE RAPID CONSTRUCTION OF TEMPORARY DEVICES 'NHEN RAIN IS IMMINENT 16 ALL REMOVABLE EROSION PROTECTIVE DEVICES SHALL BE IN PLACE AT THE END OF EACH WORKING DAY WHEN THE 6 -DAY RAIN PROBABILITY FORECAST EXCEEDS 40% 17 SEDIMENTS FROM AREAS DISTURBED BY CONSTRUCTION SHALL BE RETAINED ON SITE USING AN EFFECTIVE COMBINATION OF EROSION AND SEDIMENT CONTROLS TO THE MAXIMUM EXTENT PRACTICABLE . AND STOCKPILES OF SOIL SHALL BE PROPERLY CONTAINED TO MINIMI7E SEDIMENT TRANSPORT FROM THE SITE TO STREETS DRAINAGE FACILI TIES OR ADJACENT PROPERTIES VIA RUNOFF VEHICLE TRACKING, OR WIND 18 APPROPRIATE BMPS FOR CONSTRUCTION-RELATED MATERIALS, WASTES SPILLS OR RESIDUES SHALL BE IMPLEMENTED AND RETAINED ON SITE TO MINIMIZE TRANSPORT FROM THE SITE TO STREETS DRAINAGE FACILITIES OR ADJOINING PROPERTY BY WIND OR RUNOFF COUNTY B.ECIRONK STAMP C O V E R P A G E 801 E Borchard Ave04/13/22 A V 8 8 V Ad ( 3 SOLARPLEX LLC o 5902 FIRESTONE BLVDN.) 0 -oco SOUTH GATE, CA 90280 co PHONE (562) 806-6000 --,LICENSE #1056065/B,C10L— Contractors Signature: Dikran Komalian - _ _P____ROPfRTy LINE 10 II172 PPop-E- Ty Lame _ 3.200 kW (DC) / 2.883 kW (CEC-AC) PHOTOVOLTAIC SYSTEM LDRP././N CY SITE PLAN DATE 04/05/2022 Project Name OVIEDO, BLANCA 801 E BORCHARD AVE. SANTA ANA, CA 92707 APNI01440305 REVISIONSRI 00 15 21(ZIN)0 10 15 21(21,1)RI 02 21 22(ni,04 040122(0)1)L,RS 04 06 22(710,Rena 06.22(CV) 801 E Borchard Ave04/13/22 SIZE(kW) MODULE: SYSTEM SPECIFICATIONS 3.200 7 (8) HANWHA 0 CELLS 0 PEAK DUO BLK ML-G10.114- 400 INVERTER(S):(8) ENPHASE IQ7PLUS-72-2-US INVERTER TYPE: STRING SCHEDULE MICRO-INVERT ER 1 CIRCUIT(S) OF 8 MODULES SYSTEM WEIGHT(LBS)428 00 ARRAY AREA(SQ FT)168 97 ARRAY AZIMUTHC)/ 188. 278 LBS/SQ FT 1 253 BUILDING SPECIFICATIONS TYPE SFD STORIES: TIHJILDING HEIGHT(FT ): BUILDING(S0 FT) ROOF SLOPES("): 12 1548 1 18 ROOF FRAME MEMBER O C SPACING(IN) MAX SPAN MIN LAG BOLT EMBEDMENT(IN ) 2X4 TRUSS 24 40 -GIN BETWEEN SUPPORTS , 2-1/2 MOUNTING AND STANDOFF SPECIFICATIONS SINGLE LAYER COMP iRONRIDGE · 72 FLUSH MOUNT , N/A ROOFING MATERIAL RACKING SYSTEM TANDOFF DISTANCE(IN ) MOUNTING TYPE ' TILT LEG HEIGHT (IN.): HEIGHT OF PV MODULE ABOVE ROOF SURFACE MAX CANTILEVER (IN)I 24 3" TO 5" ROOF MOUNTED NOTES: -SOLAR PHOTOVOLTAIC SYSTEM TO BE INSTALLED ON RESIDENTIAL STRUCTURE (GROUP R3 BUILDINGS) -THIS SYSTEM WILL NOT BE INTERCONNECTED UNTIL APPROVAL FROM THE LOCAL JURISDICTION AND THE UTILITY IS OBTAINED -A 36-INCH WIDE PATHWAY SHALL BE PROVIDED TO THE EMERGENCY ESCAPE AND RESCUE OPENING(SI 'IF THE EXISTING MAIN SERVICE PANEL DOES NOT HAVE A VERIFIABLE GROUNDING ELECTRODE. IT IS ICE CONTRACTOR S RESPONSIBILITY TO INSTALL A SUPPLEMENTAL GROUNDING ELECTRODE AGOMONAL BUILDING DATA TOTAL ARRAY AREA 150. FT I TOTAL PLAN VIEW ROOF AREA (SQ. FT OCCUPYING PT PERCENTAGE SPRINKLER SYSTEM INSTALLED (IFC 903 3 1 3) 374 97 1548 24.22% NO TILT 18' AZIMUTH 273° · ROOF ACCESS POINTS PER 2019 CRC R324 (iFC 1204) ' Exceptions. 1 These requirements shall not apply to structures designed and constructed in accordance with the International Residential Code 2 These requirements shall not g/kr i to roofs with slopes of 2 unRs vertical in 12 units honzontal or less R324 6.1 Pathways R324.6.2 Setback at ridge R324.6 2 1 Alternative setback at ridge · - MINN ELECTRONIC STAMP (N) ENPHASE AC COMBINER BOX 240VAC NEMA 3R ' (N) 30A AC DISCONNECT 2P - NON FUSIBLE (N)125A AC LOAD CENTER NO OTHER LOADS ATTACHED (E) 125A MAIN SERVICE PANEL 120/240VAC SINGLE PHASE · — (E) 30A AC DISCONNECT 2P . NON FUSIBLE (E) SOLAREDGE SE3800H.US INVERTER A 7 ' EXTERIOR CONDUIT (7/8"-i- ABOVE ROO.) I NEMA 3R JUNCTION BOX TILT 18'' AZIMUTH 188° TX, POINT (E) PV ARRAY 3FT FIRE PATHWAY Scale: 3/16" = (For 24x36 Print) 0 :2:2,7;238 it5 0.90 0 020000UIre A P L O T P L A N Page 03 OF 11 801 E Borchard Ave04/13/22 MiCROiNvENTER TO J001 DEM "M"'""WthI" ITL.8'.':011'.1TRMOEONFT) CORRECTED 11=IN CIRCUIT NUMBER OfAWG NEEDED LONDULTORS ECIC SIZE CONDuir - - - - - -_ - ·_ - - -_ ---1 1 .8 12 10 t 0 91 13 30 2'2 TH.NN-1 i L 1 12 0 d lk ENPHASE 0 CABLE· LSO% To L OAD cENTER ADJUSTED TEMP ADJUSTMENT DENEROITED RACEWAY IA) (ID. ABOVE GDIU'I ADJUSTED (AID CONDUCTORS ADJUSTMENT ADJUSTED 101 IN RACEWAY FACTOR 2 1 12 10 0 91 1530 2 c- I ToTAL INvERTER CoNTINUOUSOuTPLEE EA) 3T 9 68 1.25 12 10 091 13 30 210 111W0.2 i TV 25.08 I - 1.25 32 10 0.91 35.27 ' T INO THWN·2 LT 1.2 NV RI E T (N) 40A PV BREAKER (12) MODULES P rin nL:L n j - (E) SOLAREDGE (E) 30A SE3800H-US INVERTER AC DISCONNECT (E) PV SYSTEM NOT IN SCOPE OF WORK MICRO INVERTER INPUT (DC SIDE) POWER 400W < MAX INPUT POWER OK VOLTAGE 45.3o (.140 1 = 51 6V S 600 OK SHORT CIRCUIT 11.14 x 1 25 = 13 5300 15A OK WIRE CHECK FROM ABOVE TABLE ENPHASE C) CABLE CONTAINS (2) #12 TOWN-2 AWG WIRES 13 30A < 30A OK 18 TOTAL MODULES 8 TOTAL INVERTERS CIRCUIT 1 -8 MODULES I 1 , #6 BARE DWG NEEDED I : 0I:' Ictr.,Z,s EGG SIZE TOCI 1330 810 500N.1 - i (1)L2 G 8.9 _ LOAD CENTER TO MSP CALCULATION RESULT IA)TEmPERATBRE CORRECTED (Al ATNG NEEDED NUMBeR OF T -r- CORFEC,ON COC,GFC CONDUIT OC.NDLAT 3.4TEMT ·j, I 7' 1 Li_ 1 ·! COPPER GROUND - EQUIPMENT (TYP 16B,n, 1 PV MODULE RATINGS BRAND AND MODEL: MAX POWER [Pmax] (w): MAX POWER-POINT VOLTAGE (Vmp] (V): OPEN CIRCUIT VOLTAGE [Voc] (V): MAX POWER-POINT CURRENT [Imp] (A):_ SHORT CIRCUIT CURRENT Ilsc] (A): MAX SERIES FUSE [OCPD] (A): MAX SYSTEM VOLTAGE (V): HANWHA Q CELLS Q.PEAK DUO BLK ML-G10 A+ 400 400 37.13 45.3 1077 11,14 20 600 .1 10A ENVOY 31 200 PV SOLAR _ !O r-- _ INVERTER VALUES: _ ENPHASE BRAND AND MODEL:, IQ7PLUS-72-2-US INVERTER TYPE: , MAX INPUT VOLTAGE (V) MAX INPUT CURRENT (A) 'NOMINAL OUTPUT VOLTAGE (V): MICRO-INVERTER 60 15 1 t2_4 MAX CONT. OUTPUT CURRENT (A):11.21 INVERTER OCPD (A): 115 MAX POWER AT 252C (W): ; 290 AMBIENT TEMPERATURE 2F: -40 -1 (N) PV LOAD 01417 COMBINER BOX 125A, 106AI5 240V 1_1 1 -'_ J (N) 20070 BREAKER (N) 20A PV BREAKER H 1 .1 1 1 TI EC/GEC PER NEC 250 122 250 166 690 47(C)1.3) 250 64(E) SEE NOTES SYSTEM RATINGS NOMINAL SYSTEM VOLTAGE (V): L_HAC INVERTER OUTPUT (A): OPERATING TEMP (BC) COUNTVELECTRONIC sum, -,-- --....-.--,,..---.-...---- (E) 125A MAIN SERVICE ·· ----- -- -.--· r .-- EQUIPMENT LEGEND METER/PANEL 1201240VAC (PHASE. t 3-WIRE. 10KAIC RATING MSP SUITABLE 1 DESCRIP HON 3 3 OR USE WITH 60'C/75'C Cu/Al WIRE 1 ITEM7 F I " A 3,0 HANwHA o CELLS 0 PEAK DUOr LOAD I-T, LINE I B , (N) NEMA 3R JUNCTION BOX ·1; 13LK ML-GIOA- 400 MODULE -- ‘T. -.. -, ! : I' ,r-i -: 11'7 1 i TOTAL AYE t ATOBT . I C 4_04) ENPHASE AC COMBINER 130% 2405AC. NEMA Ilt IONAK 1-1.(n . 111) NEMA 3R 30A AC DISCONNECT 210000 10 000010 RATING 1 I NON FUSIBLE BLADE. TYPE VISIBLE 1 !,- · (El 100W MAIN BRsAFHE ! ! END-FED L, PO 40070 BREAKER 240 Vac 9.68 SEE NOTE 5 A LOCKABLE NV SI INEESPHASEIOIPLUS 72·24.1s L INVERTER rpl -SoLAFIBRfAKER 000E MOUNTED 73 I ON THE OPPOSITE ENO OF THE BUSBAR FARINES( FROM THE MAIN BREAKER OR INPUT FEEDER AND NOT TORE AT I BOTH ENDS (FIT IS A CENTER-FED PANELBOARD 700 12 (B)(2)0)(h).109 SOLAR PV CIRCUIT BREAKER AID RATING 70(,4 SUB PANEL BUS RATING 1 PER NEC 705 12(131i2)13)(01 125A x 120%- 150 00A TOTAL BUS LOAD - 132 ICA 5 150 00A HORS I. 41 ME I AI (IC RACEWAYS IZNE, rISUIPMeNt SHALL HT BONDED AND FI EC TRICA1 I CONTINUOUS MEC 250 90 250 961 _I 1 GROUNDING BUSHINGS ARE REOUIRCO AROUND PREPUNCHED CONCENTRIC KNOCKOUTS ON THE DC SIDE OF THE SYSTEM (NEC 250 971 3 THE GROuNDING ELECTRODE coNaucToR wiLL BE CONTINUOUS EXCEPT FOR SPLICES OR JOINTS AT BUSISARS WITHIN LISTED EQUIPMENT (NEC 250 041 4-THE ECUIPNENT GROUNDING CONDLIGTOR MAY BE USED AS A GROUNDING _ ELECTRODE CONDUCTOR NEC 250 121 EXCEPTION INSTALLED PER 250 61A1 II III VI, -79C TO 39C 5-INSTALLER TO IDENTIFY THE EXISTING GROUNDING ELECTRODE TYPE (LE DRIVEN ROD UFER WATER PIPE OR COMBINATION OF SOME MAXIMUM VOLTAGE & VOLTAGE CORRECTION FACTOR (DC si ) 010,, Fi ALLi.,, OF ‘, WATER TTEHE P R RVPIPINGEI0 GROUNDING US LY MENTIONED)ELEc,R i N E xl S OCE TSYSTEMKGELECTRICALAN ADDITIONAL SY SI EMS H AT U GROUNDING S E MICRO-INVERTER INPUT [CEC 690.71 ELECTRODE (I E DRIVEN ROD) SHALL BE PROVIDED (NEC 250 50, 1 LOWEST EXPECTED AMBIENT TEMPERATURE (20: VOLTAGE CORRECTION FACTOR: MODULE OPEN CIRCUIT VOLTAGE: MODULE PER MICRO-INVERTER -7 °C -4- 1.14 45.3- - - - -I-[I ADJUSTED VOLTAGE: _1 51.6 MAXIMUM VOLTAGE:60 v 1 · PER NEC 250 53121 A SINGLE ROD PIPE OR PLATE ELECTRODE SHALL BE SUPPLEMENTED ES AN ADDITIONAL ELECTRODE OF TYPE SPECIFIED IN 250 510/121 THROUGH (AK8) SPACED NO LESS THAN HER APART EXCEPTION IF A SINGLE ROD PIPE OR PLATE GROUNDING ELECTRODE HAS A . RUSTS, ANCE TO EARTH OF 25 OHMS OR I ESS THE SUPPI L MENTAL F1 FCTRODE SHALL 1 NOT BE REQUIRED 44 AUG CU To UNDERGROUND METAL WA- ER PIPE THAT IS A MINIMUM 10 FOOT BURIAL IN PIPE LENGTH CONNECT GROUNDING ELECTRODE CONDUCTOR WITHIN FIVE FEET OF :MERE IT EN FERS HUI/ DING 250 51120E11 250681C) -ADDITIONAL BA AWG CONNECTION TO UFER IF AVAILABLE PER 250 64 IF UFER NOT AVAILABLE THEN TWO 56 2400 CU CONNECTIONS TO GROUND RODS SEPARATED BO AT LEAST AFT IS NEEDED 250.33 2 akkid 4'40;s96 7/57.B223g W Page 04 OF 11 801 E Borchard Ave04/13/22 pv module roof framing 111=11 XR Rail Family The SR Rail Family otters the Rrength of a caved rail in three targeted sues Each wee supports speak: design :Dads while inmonizmg material costs Clegendog on roof locator, there tS an Xin Rail to match %Ma S dropa ior opens you awe or Po ono II wrapper ssenr up ro reer vole rep., Eger anew-non -oar XR100 onto® ..001,14 www,easpr ammo mover, ea Parana's; odd er e 64...64.64616 u zoarrop capon. Nalwaleba0 capallIVI ,a, 053 calsibrOr Clew. a arradavorroh crew 6.0 anodrea trror aver. sorreserwarde inlamei e01.4. wade. Rail Selection SCialt rnoreddreris ire 01110,4r , e !2 snood worearry Lorene 66 cattatery = = The table below was prepared in eatomplence waft applicable eng.neerong codes and SlandatOIS · Values are based on the following craeno ASCE 7 16 Gable Rool Flush MM.. Roo. Zone.s t & 2e Exposure B Roof Sloped 8 to 20 degrees and Mean Building Height of TOIl Vise IronRidge com for detailed certificallon letters flashing rail, l-foot comp shingle roofing material (1)5/16" x 4-3/4" lag screw 2-1/2" min. embedment Installation flashing Tools Required tape meawan thalk line stud finder fooling bar caulking gun driver with We nit and 7116 hex socket El 4 0--Rand I ocale rafters and snap vertical and hon2onlal lines o mat* trashing locations Drill 101- 71101 halts then till with roofing manufacturer s approved sealant 1 .6. up ;VIM hole with Hashing 1101E and (naiad lag boll wah bonded washer through Hashing. Tighten lag bolt until fully sealed Attach teas Is either side ol lie open sld using bondevg hardWare eVel meat desired iteght then lOrque 10250 0·1145 (21 11-1b6r ena cotinle e pow. Slide flashing between lot and 2nci COurSe so lye op 6 al lean 3/4 above i he edge 01 1110 3rd course and the bottom 6 above the edge of the 1st course Flare Cap onto 0.111111) in drwared Ortenbstinn Or EM Or NG rails and /wale 180 degrees FlashE ool 2 is now irtsta1641 and ready tor Ironnidge SR Halls 911.1.1.1Carelltallan Deanne. Co Cenral in Canwarzooto tieimam:mom Burldnq Grrie PSCESEI I seer Sewnalinga Wow serorps Tee. to rd. no ardor 27 ER0 rest and iz51.25 Wed Odor Rad 'era tro Owner sawipaeaah eesson wean meh nwno shoe. treforan 2 12.0 1212 LIL2e03 Comoros to UL knownror sol BorOdp Repairer.. See Iron., RAI Aro.n1liestallefele Manuel for eel rat, 0 2015 Pon marred .1 wt.' oN11 1400-221 ter mere ...era. 3" to 5" roof framing cowry toicroatorSTAMP comp shingle roofing material nummiemonemis lots Insert Framire.Kili boa in 106101.1 Place star washer over TOO, allow, lift rest on top or Orr Se.re module cramps w·th a her nut and UW091080 ln/lbs Tasted or evaluated mod. clamp,. · swoon. view or Week 20018) Oa and Sr. IITEC-200(131 end Sanwa. ·11vre or beck mel awl*. amp. %MP....eye, ',peeper. aa an, · wooed.. Si,.Sr Plac..1. oil Mel end damps ale, pall nerd«. r Russo-ow, more w a or ir or -Yr we or ono 0 raise model* manulacerre. rnerelletlan rnanereuone er mewl! did moduIe dere., I. frames.. rnedule. require inlep · Groundlep Lep on wary rell ce, yoduaer on,. n ...in. to use ewe praranuan narewerre we Module.. Prerentleri Addendum IVeralen I 10, 1110011.1 01:11101:1111111.11N The lush Mount SW. rody blasadlo ground andtro noun' a PV modure omprong wen UL 1705 Orly When tI40 sped, moeure has heel evaluated ter proundalg andror mounting In complorre all Ito 'outrided ostrootirros rldess elnervose nolod err relers to he module eerier ;Ong and both WWII and siher hones are ouluded in the cerldration IM!MI11111·1111111·MaINII IIIIII 1,11,5 WI, 3, 4C aro SOrom err az arrd .100 clenPre,,, y4,2 , uet, _dr ue 44 Er 027 Pr 0101 or P30 Ertl Z ran toetaant Soup rid,. Rue 35 40 010461, Parlez ala rode, olerdder a2606242P, nor une - 2.1 ca , or A 0 Pe, Ow rat, r0 no 42 aro,. car oe bra. 0603F r et 6 wavers , odree 0 · eauer rrerntrlor 6.2.16O1011.00.ir ama 210.0244, Oro vanes and OWE. ut.nuller Orllmrtoneina rdere. (ca , Co 10 11 or 12 and /11- 01111,.. er Moor, Yarn 1, pro 40ron earns, or or. iclan., K.y/aa · · moo ni r a, car be 1200 1,6 and r, can Or 546 605 0 , 25 shorn. we ati wr lee.. 46 an. 424-aw· 10 nue., · aor Wral.iez.ri can or r1 e 0500i ler.r .7 10: 000 P 05 01 54-20 P-An POD 06-AP ;5E40 ·k4:=Cl F redress modules voth model oentda 05b4 or, node 5 ran to 3 0 z Z 6 0 0 a anc 2 can be 01-, 0 0510 PT, 1.02-06 cr0006 ...ore 35 asp ·Ornin 2 woes ann.,. radAblo CTwx43,06, enere _so Ar = , ·ran be 000, IC Ii II sor 1,0 0' 02 or 03 Mures 2011 35 arra 40mm frames and mode V 2,00 Oleo ·=1- o 00orr 451 bers 60 5 121' 4 dank Pr, 0 0.4 10 a brard BE 062 oe go, 64664.4.6 35 40 00 SIVom traces aro draw ,ero.en001aslr.15 WI where 1,0 50, S T "Zr.r.artter12e,15. ·A P 50.04 4150 o ra Aro, can be torer o trodurea *alb 35 40 or 50m0 tomes ar, moael dlnidlor ET 3 6620.6 area 4 ce 1, 0 701 . 000 or 72 and -46 0 nre 1001 145r WWG 6 PAC NESPO WVICAD MVO,: Or SE. (3 NNt4Nrc41 z 0 to geVaSZ r7 ,7 ` 71k? L I:[1 < 801 E Borchard Ave04/13/22 ALL PLAQUES AND SIGNAGE REQUIRED BY THE LATEST EDITION OF CALIFORNIA ELECTRICAL CODE WILL BE INSTALLED AS REQUIRED ALTERNATE POWER SOURCE PLACARD SHALL BE METALLIC OR PLASTIC, ENGRAVED, OR MACHINE PRINTED LETTERS IN A CONTRASTING COLOR TO THE PLAQUE THIS PLAQUE WILL BE ATTACHED BY POP RIVETS OR SCREWS OR OTHER APPROVED METHOD IF EXPOSED TO SUNLIGHT, IT SHALL BE UV RESISTANT PHOTOVOLTAIC DC CONDUCTORS SHALL BE LABELED."WARNING PHOTOVOLTAIC DC POWER SOURCE" OR EQUIVALENT EVERY 10 FT AND KEPT MINIMUM 18 BELOW THE ROOF SURFACE. PV DC CIRCUIT LABELS SHALL APPEAR ON EVERY SECTION OF THE WIRING SYSTEM THAT IS SEPARTED BY ENCLOSURES. WALLS, PARTITIONS, CEILINGS, OR FLOORS PV DC LABELS SHALL BE REFLECTIVE. SUITABLE FOR SURROUNDING ENVIRONMENT, AND WHITE LETTERING ON A RED BACKGROUND [690 31(G)] EXPOSED NON-CURRENT CARRYING METAL PARTS OF MODULE FRAMES, EQUIPMENTS, AND CONDUCTOR ENCLOSURES SHALL BE GROUNDED IN ACCORDANCE WITH 250.134 OR 250 136(A) REGARDLESS OF VOLTAGE. EACH MODULE SHALL BE GROUNDED USING THE SUPPLIED CONNECTION POINT IDENTIFIED ON THE MODULE AND THE MANUFACTURER'S INSTRUCTIONS. IF THE EXISTING GROUNDING ELECTRODE SYSTEM CANNOT BE VERIFIED OR IS ONLY METALLIC WATER PIPING. IT IS THE CONTRACTOR'S RESPONSIBILITY TO INSTALL A SUPPLEMENTAL GROUNDING ELECTRODE EQUIPMENT COMPLIES WITH RAPID SHUTDOWN REQUIREMENTS [690 12] PLAQUES SHALL BE PLASTIC ENGRAVED IN A CONTRASTING COLOR TO THE PLAQUE. NEC 705.10- ON MAIN SERVICE PANEL CAUTION POWER TO THIS BUILDING IS ALSO SUPPLIED FROM THE FOLLOWING SOURCES WITH DISCONNECTS LOCATED AS SHOWN MAI C , , p IC J .0,,EXTEP N8 T N8,81, 88, 801 E EIONSITANO AVE SANTA ANA CA 92707 ,IWARNINGELECTRIC SHOCK HAZARDTERMINALS ON BOTH THE LINE AND LOAD SIDES MAYBE ENERGIZED IN THE OPEN POSITION NEC 690-13, 690.15- AT J-BOXES, ENCLOSURES, DISTRIBUTION EQUIPMENT, AND AC/DC DISCONNECTS WARNING ELECTRICAL SHOCK HAZARD TERMINALS ON BOTH THE LINE ANDLOAD SIDE MAY BE ENERGIZED IN THEOPEN POSITION NEC 705,12(B)(2)(3)(b) - BY BREAKER AT DISTRIBUTION EQUIPMENT: WARNING POWER SOURCE OUTPUT CONNECTION DO NOT RELOCATE THISOVERCURRENT DEVICE NEC 705.12(B)(2)(3)(c) - BY BREAKER AT DISTRIBUTION EQUIPMENT: WARNING THIS EQUIPMENT FED BY MULTIPI F SOURCES TOTAL RATING OF ALL OVERCURRENT DEVICES. EXCLUDING MAIN SUPPLY OVERCURRENT DEVICE.SHALL NOT EXCEED AMPACITY OF BUSBAR NEC 705.12(6)(3) - AT DISTRIBUTION EQUIPMENT k WARNING k MULTI - POWER SUPPLY SOURCES INCLUDE UTILITY GRID, PV SOLAR NEC 690.56 - WITHIN 3FT OF SERVICE DISCONNECT. 1690 961C1)1101 YELLOW WITH BLACK LETTERING' SOLAR PV SYSTEM EQUIPPED WITH RAPID SHUTDOWN TJRN RAPID SHUTDOWNSWITCH TO THE "OFF'POSITION TO SHUT DOWN PVSYSTEM AND REDUCE-SHOCKHAZARD IN ARRAY NEC 690.56- ON RAPID SHUTDOWN DISCONNECT (690 5610 RED WITH WHITE LETTERING) i RAPID SHUTDOWN SWITCH FOR SOLAR PV SYSTEM cotonytucmotoormw 1 LOCATION; MAIN PANEL NEC 705.12.6.3 WARNING DUAL POWER SOURCE SECOND SOURCE IS PHOTOVOLTAIC SYSTEM RATED AC OUTPUT CURRENT:15.83 AMPS ACNORMAL OPERATING VOLTAGE·240 VOILS _k WARNING k TURN OFF PHOTOVOLTAIC i AC DISCONNECT PRIOR TO WORKING INSIE PANEL PHOTOVOLTAIC SYSTEM EQUIPPED WITH RAPID SHUTDOWN NEC 690.13, 690.15 - ON AC/DC DISCONNECT NEC 690.53, 690 54 -ON AC/DC DISCONNECT AC PHOTOVOLTAIC DISCONNECT NEC 690.54 -ON AC DISCONNECT AC PHOTOVOLTAIC DISCONNECT_ OUTPUT CURRENT 25.7A OPERATING VOLTAGE 240V · 1 W wu · V) co co < Al: 0 (7) O > O 0-- 0 oa. c>o z (N Page 06 OF 11 ;27 801 E Borchard Ave04/13/22 SOLARPLEX LLC 0 5902 FIRESTONE BLVD--.1 0 -A?SOUTH GATE, CA 90280 11 ugCD PHONE (562) 806-6000 —,LICENSE #1056065/B,C10 Contractors Signature: Doyen Konlahan 5 3.200 kW (DC) / 2.883 kW (CEC-AC) PHOTOVOLTAIC SYSTEM DRAWN BY MODULE DATE ZM SPECIFICATIONS 04/05/2022 Project Name OVIEDO, BLANCA 801 E BORCHARD AVE SANTA ANA CA 92707 APN: 01440305 REVISIONS 01 00 15 21(210112 10 15 21(2M)03 02 21 22(ZN1)04 03 01 22(Z111,AR.1) 04 06 02(71.4 )R6 09 00 22(CV, * 801 E Borchard Ave04/13/22 Page RE V I S I O N S : Pr o j e c t N a m e 3. 2 0 0 k W ( D C ) / 2 . 8 8 3 k W ( C E C - A C ) PH O T O V O L T A I C S Y S T E M OV I E D O , B L A N C A 80 1 E B O R C H A R D A V E , SA N T A A N A , C A 9 2 7 0 7 AP N : 0 1 4 4 0 3 0 5 DA T E : 04 / 0 5 / 2 0 2 2 DR A W N B Y : ZM Co n t r a c t o r s S i g n a t u r e : SO L A R P L E X L L C 59 0 2 F I R E S T O N E B L V D SO U T H G A T E , C A 9 0 2 8 0 PH O N E : ( 5 6 2 ) 8 0 6 - 6 0 0 0 LI C E N S E : # 1 0 5 6 0 6 5 / B , C 1 0 R1 0 9 . 1 5 . 2 1 ( Z M ) R2 1 0 . 1 5 . 2 1 ( Z M ) R3 0 2 . 2 1 . 2 2 ( Z M ) R4 0 3 . 0 1 . 2 2 ( Z M ) R5 0 4 . 0 6 . 2 2 ( Z M ) 1 R6 0 4 . 0 6 . 2 2 ( C V ) Di k r a n K o n i a l i a n ST R U C T U R A L AT T A C H M E N T 05 OF 11 flashing pv module rail, l-foot comp shingle roofing material roof framing comp shingle roofing material flashing roof framing rail, l-foot (1)5/16" x 4-3/4" lag screw 2-1/2" min. embedment 3" to 5" COUNTY ELECTRONIC STAMP R E G I S T E R E D P R O F E S S I O N A L E N G I N E E R C I V I L No. C70784 Exp. 06/30/2023 S T A T E O F C A L I F O R N I A PHONG TRUONG 801 E Borchard Ave04/13/22 801 E. BORCHARD AVE. SANTA ANA, CA 92707 OVIEDO, BLANCA Prepared For: SOLARPLEX, LLC. 5902 FIRESTONE BLVD. SOUTH GATE, CA 90280 (562) 806-6000 Design Criteria 1- Code: CALIFORNIA BLDG CODE 2019 / ASCE 7-16 2 - Wind: 95 MPH, Exposure: C 3 - Wood Species: DF-L No. 1 (SG = 0.5 ) Notice: Use restrictions of these calculations. The attached Calculations are valid only when bearing original signature hereon. Contractor/Client to verify existing dimensions/conditions prior to construction & solar racking is installed per manufacturer span requirements. The use of these calculations is solely intended for the above mentioned project. 1-844-PV ELITE | info@yoursolarplans.com 3000 E. Birch Street Suite 201 | Brea CA 92821 2/21/2022 Structural Calculations for SOLAR POWER SYSTEM CONNECTION CHECK AT: Job: R E G I S T E R E D P R O F E S S I O N A L E N G I N E E R C I V I L No. C70784 Exp. 06/30/2023 S T A T E O F C A L I F O R N I A PHONG TRUONG 801 E Borchard Ave04/13/22 0102133467089 9  711 !1"1#$ %&&83'&(60) !%*008'+23(03),%'20-.9/,03 1903  96382803 219 013  3456789:;<6=5>?<: @AA64BBC '20-.9/,4194 9638284 219 D<<6A?:5>4BC &&83'&(604*008'+23(03 EF4G5>?<:C '+H I?=4B>5=JC 3233*20*02 0870873688+K L5M56AINJ4C O @3DEPQR S TU02*V,++W TU3X*V,80W TUX2*V,88 W TU022*V,'0W TY ,!U '6 W TY ,!UU 6X W TY ,!UUU 023W TY ,!UZ 02+W @3DEPQR [ TU02*V,83W TU3X*V,86 W TUX2*V,'X W TU022*V,60W TY ,!U 022 W TY ,!UU 002 W TY ,!UUU*UZ 00X W @3DEPQ[\ 91 -8*2XO1,,'X W ]^_`_abcdaefgehid_g^_`_jklk]`_mc_hdifnadid_o`cohicip_fgp_fdadod^_qicb_ao`ifng_cef_ideofcef_apig_gb`efrd^_sbecgefr hog_igotdeoft`oh_aauva_`aa^obcghofme`pifnobdtbdosdief_gm`opd^eadoocwed^d^_cohicxbd^o`ednyiqefrzb`eagehdeofs_mo`_ t`oh__gefrwed^g_aerfu {?B7F5?=46  ,, ,HW/,91 -8,,,,# ,,!,|,91 -84  ,,,  ,, #,,H, ,}W,,4#,,# ,~ , , #,,,,H,4/,#,, ! !,€ -7‚,,,#*,,,! ,4,, !,,W,/,!#WHH,#,,,,,##*, ,,! ,4!!,4,W,4, #,! ,,~W,H # O ,,HW,,,#,,, ,/,,,49 W,,    H ,W, ,,,,, ,,, ,H,H # W,,,~W/,HH4   ,!,,, ,,H, 9 , ,,,HHW, ,,ƒ!W,HW,,H, 4/!,~,,,Y# ,!, ,H, H,4,H,H,,‚,HH, ,,! !,, H, ,/,#,,2,H,HWHW#,,W,   !HW,2,H,H #,,,W / ,!/,! !,,, ,H !,/ ,,H, „…†‡ ˆ‰Š‹ŒŽŽŠ‰ŒŒ‹ŒŽŠ‘ŽŽ’“”““•‹‹–—‰˜™š›•™ 801 E Borchard Ave04/13/22 ASCE 29.4.4 Rooftop Solar Panels Parallel to the Roof Surface on Buildings of All Heights and Roof Slopes. Roof Slope  = 18 ° Roof Shape Gable Tributary Width s = 6.00 ft Tributary Length l = 3.08 ft Effective Area A e = 18.50 ft2 Height of Structure h = 15 ft Wind Speed V = 95 mph Exposure Category C Building Width B = 25 ft Building Length L = 50 ft Zone Width a = 3 ft Elevation Height zg = 86 ft Wind Directionality Kd = 0.85 Topography Factor Kt = 1.00 Ground Elevation Factor Ke = 1.00 Velocity Pressure Exposure Coefficient Kz = 0.85 Velocity Pressure q z = 0.00256KzKztKdKeV2 = 16.62 psf Solar Array Pressure Equalization a = 0.76 Array Edge Factor E = 1.50 Zone GCp p = qz(GCp)(E)(a) 3 - - 3r 3.43 -65.17 3e 2.93 -55.66 2 - - 2r 2.93 -55.66 2e - - 2n 2.93 -55.66 1 - - 1' - - 801 E Borchard Ave04/13/22 LAG SCREW ANALYSIS Loads Wind Pressures qz = -55.66 psf Solar Panel Load QD = 3 psf Panel Length l = 6.167 ft Panel Width b 3.425 ft Attachment Spacing s = 6 ft Portrait Tributary Area At = 18.50 ft2 Wind Load P W = qz * At = -1030 lbs Dead Load P D = Q D * At = 55.5 lbs Uplift Pa = 0.6 P D + 0.6 Pw = -584 lbs Landscape Tributary Area At = b * s = 10.275 ft2 Wind Load P W = qz * At = -572 lbs Dead Load P D = Q D * At = 30.825 lbs Uplift Pa = 0.6 P D + 0.6 Pw = -325 lbs Lag Screw 5/16" x 3" Specific Gravity of Lumber SG = 0.50 (Douglas Fir-Larch) Diameter of Lag Screw D = 5/16 in Withdraw Design /in 1800*SG 3/2 *D 3/4 = 266 lbs/in Depth of Embedment lp = 2.50 in Total Nominal Withdrawal Value W = W * l p = 665 lbs Load Duration Factor CD = 1.6 Withdrawal Design Value W' = W * C D = 1064 lbs Demand Capacity Ratio DCR = Pa / W' = 0.55 < 1 OK 801 E Borchard Ave04/13/22 ASCE 30.3.2 Design Wind Pressure Beam/ Top Chord Check Roof Slope  = 18 ° Roof Shape Gable Tributary Width s = 2.00 ft Tributary Length L = 14.00 ft Effective Area A = L ( MAX [ s , L/3] ) = 65 ft2 Height of Structure h = 15 ft Wind Speed V = 95 mph Exposure Category C Building Width B = 25 ft Building Length L = 50 ft Zone Width a = 3 ft Elevation Height zg = 86 ft Wind Directionality Kd = 0.85 Topography Factor Kt = 1.00 Ground Elevation Factor Ke = 1.00 Velocity Pressure Exposure Coefficient Kz = 0.85 Velocity Pressure q z = 0.00256KzKztKdKeV 2 = 16.62 psf Internal Pressure Coefficient (GCpi) = -0.18 Zone GCp p = q z [(GCp) - (Gcpi)] 3 - - 3r 2.49 -44.43 3e 2.54 -45.18 2 - - 2r 2.54 -45.18 2e - - 2n 2.54 -45.18 1 - - 1' - - 801 E Borchard Ave04/13/22 Beam/ Top Chord Check Lumber: Moment Demand # of Attachment per Rafter N A = Span : Orientation Lenght (ft) : Dead Load Roof Material: Q D = psf Live Load QLr = psf Wind Load p = psf Snow Load QS = psf Rafter Spacing s = in Wind Load, Portrait Portrait UL = Wind Load, Landscape Landscape U W = Linear Dead Load wd = plf Live Load wLr = plf Start ft Start ft End ft End ft Snow Load ws = plf Start ft Start ft End ft End ft Ma, Moment D lb-ft D+Lr lb-ft D+S lb-ft 0.6D+0.6W lb-ft D+0.45W+0.75Lr lb-ft D+0.45W+0.75S lb-ft Moment Capacity Framing Member Size Lumber Grade : DF-L No. 1 C M = 1 Ct = 1 Cr= CF = fb = psi Cfu =C i = Breadth b = in Depth d = in Section Modulus Sx = bd 2 / 6 = in3 Bending Stress Capacity Fb = CM * C t * Cr * C F * fb = psi Table 4.3.1 NDS 2015 Deflection Limit E = ksi I = in4 Transient Deflection in Transient Deflection Allowed > [OKAY] Total Deflection in Total Deflection Allowed > [OKAY] -45.18 DF-L No. 1 4 j lj (ft) pd,j  (lbs) pw,j  (lbs) ps,j  (lbs) Portrait 1 2.3 55.5 -836 0.0 6.9 55.5 -836 -836 0.0 4 13.0 55.5 -836 0.0 0.0 6.50 6.50 0.00 0.00 1.00 Portrait 3 8.5 55.5 14.00 1 2 3 4 Eave 2 0.0 0.0 0.0 0.0 0.0 0 0.0 0.0 0.0 0.0 0 0.0 0.0 0.0 0.0 0 0.0 0.0 0 0.0 Portrait 0 0.0 0.0 0 0.0 28 40 0.0 0.0 0.0 0.0 0 0.0 Portrait 0 0.0 30.825 -464 0 0 0.0 0 1.5 0 0 0.0 Portrait 1.5 0.0 Portrait 0 0.0 0.0 AT (ft2) 18.5 10.275 pd (lbs) 55.5 -836 p w (lbs) ps (lbs) 0 13.83 2x4 1.15 1.5 14.00 13.83 14.00 1000 1.50 3.50 213 217 213 495 255 255 DCR 0.9 1553 psi D 833 psi 0.54 3.06 1725 CD Fb' = C D * F b ASD Load Ma * S x 1.15 1984 psi D+S 833 psi 0.42 OKAY OKAY 1.25 2156 psi D+Lr 852 psi 0.39 OKAY 1.6 2760 psi 0.167 468 120 1700 5.36 0.6D+0.6W 1941 psi 0.70 OKAY 1.0 1 20 0.00 24 Comp 0.144 542 180 1.6 2760 psi D+0.45W+0.75S 997 psi 0.36 OKAY 1.6 2760 psi D+0.45W+0.75Lr 997 psi 0.36 OKAY ൌ ሺ െ ሻ െ െ െ ‐600.0 ‐400.0 ‐200.0 0.0 200.0 400.0 600.0 0.000 2.000 4.000 6.000 8.000 10.000 12.000 14.000 16.000 801 E Borchard Ave04/13/22 EISMIC WEIGHT COMPARISON / ANALYSIS - (PER CEBC 2019 Part 10 Chapter 5 Section 502.5) PV System Weight Module Model Hanwha Panel Weight Wpanel = 48.5 lbs Number of Panels NPV = 8 Total PV System Weight W PV = Wpanel * NPV = 388 lbs Existing Roof Weight Roof Weight QD =14.0 psf Building Length Lbuild =50 ft Building Width W build =25 ft Roof Area Abuild =1250 ft2 Building Perimeter Pbuild = 150 ft Wall Height ht = 8 ft Wall weight Qwall = 15 psf Interior wall weight Qint = 10 psf Roof Load Wfloor = Abuild * QD = 17500 lbs Wall LoadWwall = ht /2 * Qwall * Pbuild + Abuild * Qint /2 = 15250 lbs Total Story Weight Wbuild = Wfloor + Wwall = 32750 lbs Percentage Weight Increase WPV / Wbuild = 1.18%< 10% OKAY 801 E Borchard Ave04/13/22 1 801 E Borchard Ave02/17/22 801 E Borchard Ave04/13/22 2 Step 1: Structural Review of PV Array Mounting System . Step 2: Electrical Review of PV System (Calculations for Electrical Diagram) 801 E Borchard Ave02/17/22 801 E Borchard Ave04/13/22 3 801 E Borchard Ave02/17/22 801 E Borchard Ave04/13/22 4 Co n t r a c t o r N a m e , Ad d r e s s a n d P h o n e : On e - L i n e S t a n d a r d E l e c t r i c a l D i a g r a m fo r M i c r o - I n v e r t e r P V S y s t e m s Si t e N a m e : Si t e A d d r e s s : Sy s t e m A C S i z e : SI Z E FS C M N O DW G N O RE V E1 . 1 a SC A L E NT S Da t e : SH E E T Dr a w n B y : Ch e c k e d B y : DE S C R I P T I O N O R C O N D U C T O R T Y P E US E - 2 or P V W I R E GE C EG C X A L L T H A T A P P L Y EX T E R I O R C A B L E L I S T E D W / I N V . TH W N - 2 or X H H W - 2 or R H W - 2 GE C EG C X A L L T H A T A P P L Y NO D C G E C I F 6 9 0 . 3 5 S Y S T E M TH W N - 2 or X H H W - 2 or R H W - 2 GE C EG C X A L L T H A T A P P L Y TA G 1 2 3 4 5 CO N D U I T A N D C O N D U C T O R S C H E D U L E CO N D . GA U G E MF G MF G NU M B E R O F CO N D U C T O R S MF G C a b l e MF G C a b l e CO N D U I T TY P E N/ A N/ A N/ A SA M E SA M E CO N D U I T SI Z E N/ A N/ A N/ A SA M E SA M E DE S C R I P T I O N PV D C o r A C M O D U L E DC / A C I N V E R T E R ( M I C R O ) J- B O X ( I F U S E D ) PV A R R A Y AC C O M B . P A N E L ( I F U S E D ) GE N M E T E R ( I F U S E D ) AC D I S C O N N E C T ( I F U S E D ) SE R V I C E P A N E L TA G 1 2 3 4 5 6 7 8 PA R T N U M B E R NO T E S FO R U N U S E D M O D U L E S PU T " N / A ” i n B L A N K A B O V E EQ U I P M E N T S C H E D U L E __ _ _ _ MI C R O - I N V E R T E R S IN B R A N C H - CI R C U I T MO D __ _ _ DC AC MO D __ _ _ DC AC MO D __ _ _ DC AC MO D __ _ _ DC AC MO D __ _ _ DC AC MO D __ _ _ DC AC J- B O X AC D I S C O M BU I L D I N G GR O U N D I N G EL E C T R O D E G M UT I L I T Y SE R V IC E MA I N S E R V I C E P A N E L MA I N OC P D IN V ER T E R OC P D G SE E G U I D E A P P E N D I X D F O R IN F O R M A T I O N O N M O D U L E A N D AR R A Y G R O U N D I N G AC C O M B I N E R PA N E L G __ _ _ MI C R O - I N V E R T E R S IN B R A N C H - CI R C U I T 801 E Borchard Ave02/17/22 801 E Borchard Ave04/13/22 5 Co n t r a c t o r N a m e , Ad d r e s s a n d P h o n e : No t e s f o r O n e - L i n e S t a n d a r d E l e c t r i c a l Di a g r a m f o r S i n g l e - P h a s e P V S y s t e m s Si t e N a m e : Si t e A d d r e s s : Sy s t e m A C S i z e : SI Z E FS C M N O DW G N O RE V E1 . 2 a SC A L E NT S Da t e : SH E E T Dr a w n B y : Ch e c k e d B y : MA X P O W E R - P O I N T C U R R E N T ( I MP ) MA X P O W E R - P O I N T V O L T A G E ( V MP ) OP E N - C I R C U I T V O L T A G E ( V OC ) SH O R T - C I R C U I T C U R R E N T ( I SC ) MA X S E R I E S F U S E ( O C P D ) MA X I M U M P O W E R ( P MA X ) MA X V O L T A G E ( T Y P 6 0 0 V DC ) VO C T E M P C O E F F ( m V / oC or % / oC ) IF C O E F F S U P P L I E D , C I R C L E U N I T S MO D U L E M A K E MO D U L E M O D E L PV M O D U L E R A T I N G S @ S T C ( G u i d e S e c t i o n 5 ) MA X D C V O L T R A T I N G MA X P O W E R @ 4 0 oC NO M I N A L A C V O L T A G E MA X A C C U R R E N T MA X O C P D R A T I N G IN V E R T E R M A K E IN V E R T E R M O D E L IN V E R T E R R A T I N G S ( G u i d e S e c t i o n 4 ) 1 ) I F U T I L I T Y R E Q U I R E S A V I S I B L E - B R E A K S W I T C H , D O E S T H I S S W I T C H M E E T T H E RE Q U I R E M E N T ? Y E S N O N / A 2) I F G E N E R A T I O N M E T E R R E Q U I R E D , D O E S T H I S M E T E R S O C K E T M E E T T H E RE Q U I R E M E N T ? Y E S N O N / A 3) S I Z E P H O T O V O L T A I C P O W E R S O U R C E ( D C ) C O N D U C T O R S B A S E D O N M A X CU R R E N T O N N E C 6 9 0 . 5 3 S I G N O R O C P D R A T I N G A T D I S C O N N E C T 4) S I Z E I N V E R T E R O U T P U T C I R C U I T ( A C ) C O N D U C T O R S A C C O R D I N G T O I N V E R T E R OC P D A M P E R E R A T I N G . ( S e e G u i d e S e c t i o n 9 ) 5) T O T A L O F _ _ _ _ _ _ I N V E R T E R O U T P U T C I R C U I T O C P D ( s ) , O N E F O R E A C H M I C R O - IN V E R T E R C I R C U I T . D O E S T O T A L S U P P L Y B R E A K E R S C O M P L Y W I T H 1 2 0 % B U S B A R EX C E P T I O N I N 6 9 0 . 6 4 ( B ) ( 2 ) ( a ) ? Y E S N O NO T E S F O R I N V E R T E R C I R C U I T S ( G u i d e S e c t i o n 8 a n d 9 ) : 1 . ) L O W E S T E X P E C T A M B I E N T T E M P E R A T U R E B A S E D O N A S H R A E M I N I M U M M E A N EX T R E M E D R Y B U L B T E M P E R A T U R E F O R A S H R A E L O C A T I O N M O S T S I M I L A R T O IN S T A L L A T I O N L O C A T I O N . L O W E S T E X P E C T E D A M B I E N T T E M P _ _ _ _ oC 2. ) H I G H E S T C O N T I N U O U S A M B I E N T T E M P E R A T U R E B A S E D O N A S H R A E H I G H E S T MO N T H 2 % D R Y B U L B T E M P E R A T U R E F O R A S H R A E L O C A T I O N M O S T S I M I L A R T O IN S T A L L A T I O N L O C A T I O N . H I G H E S T C O N T I N U O U S T E M P E R A T U R E _ _ _ _ oC 2. ) 2 0 0 9 A S H R A E F U N D A M E N T A L S 2 % D E S I G N T E M P E R A T U R E S D O N O T E X C E E D 47 oC I N T H E U N I T E D S T A T E S ( P A L M S P R I N G S , C A I S 4 4 . 1 oC) . F O R L E S S T H A N 9 CU R R E N T - C A R R Y I N G C O N D U C T O R S I N R O O F - M O U N T E D S U N L I T C O N D U I T A T LE A S T 0 . 5 " A B O V E R O O F A N D U S I N G T H E O U T D O O R D E S I G N T E M P E R A T U R E O F 47 oC O R L E S S ( A L L O F U N I T E D S T A T E S ) , a) 1 2 A W G , 9 0 oC C O N D U C T O R S A R E G E N E R A L L Y A C C E P T A B L E F O R M O D U L E S WI T H I s c O F 7 . 6 8 A M P S O R L E S S W H E N P R O T E C T E D B Y A 1 2 - A M P O R S M A L L E R FU S E . b) 1 0 A W G , 9 0 oC C O N D U C T O R S A R E G E N E R A L L Y A C C E P T A B L E F O R M O D U L E S WI T H I s c O F 9 . 6 A M P S O R L E S S W H E N P R O T E C T E D B Y A 1 5 - A M P O R S M A L L E R FU S E . NO T E S F O R A R R A Y C I R C U I T W I R I N G ( G u i d e S e c t i o n 6 a n d 8 a n d A p p e n d i x E ) : OC P D = O V E R C U R R E N T P R O T E C T I O N D E V I C E NA T I O N A L E L E C T R I C A L C O D E ® RE F E R E N C E S SH O W N A S (N E C X X X . X X ) NO T E S F O R A L L D R A W I N G S : SI G N S – S E E G U I D E S E C T I O N 7 SI G N F O R D C D I S C O N N E C T SI G N F O R I N V E R T E R O C P D A N D A C DI S C O N N E C T ( I F U S E D ) No s i g n n e c e s s a r y s i n c e 6 9 0 . 5 1 ma r k i n g o n P V m o d u l e c o v e r s ne e d e d i n f o r m a t i o n AC O U T P U T C U R R E N T NO M I N A L A C V OL T A G E SO L A R P V S Y S T E M AC P O I N T O F C O N N E C T I O N TH I S P A N E L F E D B Y M U L T I P L E SO U R C E S ( U T I L I T Y A N D S O L A R ) 801 E Borchard Ave02/17/22 801 E Borchard Ave04/13/22 1 801 E Borchard Ave02/17/22 2 Step 1: Structural Review of PV Array Mounting System . Step 2: Electrical Review of PV System (Calculations for Electrical Diagram) 801 E Borchard Ave02/17/22 3 801 E Borchard Ave02/17/22 4 Co n t r a c t o r N a m e , Ad d r e s s a n d P h o n e : On e - L i n e S t a n d a r d E l e c t r i c a l D i a g r a m fo r M i c r o - I n v e r t e r P V S y s t e m s Si t e N a m e : Si t e A d d r e s s : Sy s t e m A C S i z e : SI Z E FS C M N O DW G N O RE V E1 . 1 a SC A L E NT S Da t e : SH E E T Dr a w n B y : Ch e c k e d B y : DE S C R I P T I O N O R C O N D U C T O R T Y P E US E - 2 or P V W I R E GE C EG C X A L L T H A T A P P L Y EX T E R I O R C A B L E L I S T E D W / I N V . TH W N - 2 or X H H W - 2 or R H W - 2 GE C EG C X A L L T H A T A P P L Y NO D C G E C I F 6 9 0 . 3 5 S Y S T E M TH W N - 2 or X H H W - 2 or R H W - 2 GE C EG C X A L L T H A T A P P L Y TA G 1 2 3 4 5 CO N D U I T A N D C O N D U C T O R S C H E D U L E CO N D . GA U G E MF G MF G NU M B E R O F CO N D U C T O R S MF G C a b l e MF G C a b l e CO N D U I T TY P E N/ A N/ A N/ A SA M E SA M E CO N D U I T SI Z E N/ A N/ A N/ A SA M E SA M E DE S C R I P T I O N PV D C o r A C M O D U L E DC / A C I N V E R T E R ( M I C R O ) J- B O X ( I F U S E D ) PV A R R A Y AC C O M B . P A N E L ( I F U S E D ) GE N M E T E R ( I F U S E D ) AC D I S C O N N E C T ( I F U S E D ) SE R V I C E P A N E L TA G 1 2 3 4 5 6 7 8 PA R T N U M B E R NO T E S FO R U N U S E D M O D U L E S PU T " N / A ” i n B L A N K A B O V E EQ U I P M E N T S C H E D U L E __ _ _ _ MI C R O - I N V E R T E R S IN B R A N C H - CI R C U I T MO D __ _ _ DC AC MO D __ _ _ DC AC MO D __ _ _ DC AC MO D __ _ _ DC AC MO D __ _ _ DC AC MO D __ _ _ DC AC J- B O X AC D I S C O M BU I L D I N G GR O U N D I N G EL E C T R O D E G M UT I L I T Y SE R V I C E MA I N S E R V I C E P A N E L MA I N OC P D IN V E R T E R OC P D G SE E G U I D E A P P E N D I X D F O R IN F O R M A T I O N O N M O D U L E A N D AR R A Y G R O U N D I N G AC C O M B I N E R PA N E L G __ _ _ MI C R O - I N V E R T E R S IN B R A N C H - CI R C U I T 801 E Borchard Ave02/17/22 5 Co n t r a c t o r N a m e , Ad d r e s s a n d P h o n e : No t e s f o r O n e - L i n e S t a n d a r d E l e c t r i c a l Di a g r a m f o r S i n g l e - P h a s e P V S y s t e m s Si t e N a m e : Si t e A d d r e s s : Sy s t e m A C S i z e : SI Z E FS C M N O DW G N O RE V E1 . 2 a SC A L E NT S Da t e : SH E E T Dr a w n B y : Ch e c k e d B y : MA X P O W E R - P O I N T C U R R E N T ( I MP ) MA X P O W E R - P O I N T V O L T A G E ( V MP ) OP E N - C I R C U I T V O L T A G E ( V OC ) SH O R T - C I R C U I T C U R R E N T ( I SC ) MA X S E R I E S F U S E ( O C P D ) MA X I M U M P O W E R ( P MA X ) MA X V O L T A G E ( T Y P 6 0 0 V DC ) VO C T E M P C O E F F ( m V / oC or % / oC ) IF C O E F F S U P P L I E D , C I R C L E U N I T S MO D U L E M A K E MO D U L E M O D E L PV M O D U L E R A T I N G S @ S T C ( G u i d e S e c t i o n 5 ) MA X D C V O L T R A T I N G MA X P O W E R @ 4 0 oC NO M I N A L A C V O L T A G E MA X A C C U R R E N T MA X O C P D R A T I N G IN V E R T E R M A K E IN V E R T E R M O D E L IN V E R T E R R A T I N G S ( G u i d e S e c t i o n 4 ) 1 ) I F U T I L I T Y R E Q U I R E S A V I S I B L E - B R E A K S W I T C H , D O E S T H I S S W I T C H M E E T T H E RE Q U I R E M E N T ? Y E S N O N / A 2) I F G E N E R A T I O N M E T E R R E Q U I R E D , D O E S T H I S M E T E R S O C K E T M E E T T H E RE Q U I R E M E N T ? Y E S N O N / A 3) S I Z E P H O T O V O L T A I C P O W E R S O U R C E ( D C ) C O N D U C T O R S B A S E D O N M A X CU R R E N T O N N E C 6 9 0 . 5 3 S I G N O R O C P D R A T I N G A T D I S C O N N E C T 4) S I Z E I N V E R T E R O U T P U T C I R C U I T ( A C ) C O N D U C T O R S A C C O R D I N G T O I N V E R T E R OC P D A M P E R E R A T I N G . ( S e e G u i d e S e c t i o n 9 ) 5) T O T A L O F _ _ _ _ _ _ I N V E R T E R O U T P U T C I R C U I T O C P D ( s ) , O N E F O R E A C H M I C R O - IN V E R T E R C I R C U I T . D O E S T O T A L S U P P L Y B R E A K E R S C O M P L Y W I T H 1 2 0 % B U S B A R EX C E P T I O N I N 6 9 0 . 6 4 ( B ) ( 2 ) ( a ) ? Y E S N O NO T E S F O R I N V E R T E R C I R C U I T S ( G u i d e S e c t i o n 8 a n d 9 ) : 1 . ) L O W E S T E X P E C T A M B I E N T T E M P E R A T U R E B A S E D O N A S H R A E M I N I M U M M E A N EX T R E M E D R Y B U L B T E M P E R A T U R E F O R A S H R A E L O C A T I O N M O S T S I M I L A R T O IN S T A L L A T I O N L O C A T I O N . L O W E S T E X P E C T E D A M B I E N T T E M P _ _ _ _ oC 2. ) H I G H E S T C O N T I N U O U S A M B I E N T T E M P E R A T U R E B A S E D O N A S H R A E H I G H E S T MO N T H 2 % D R Y B U L B T E M P E R A T U R E F O R A S H R A E L O C A T I O N M O S T S I M I L A R T O IN S T A L L A T I O N L O C A T I O N . H I G H E S T C O N T I N U O U S T E M P E R A T U R E _ _ _ _ oC 2. ) 2 0 0 9 A S H R A E F U N D A M E N T A L S 2 % D E S I G N T E M P E R A T U R E S D O N O T E X C E E D 47 oC I N T H E U N I T E D S T A T E S ( P A L M S P R I N G S , C A I S 4 4 . 1 oC) . F O R L E S S T H A N 9 CU R R E N T - C A R R Y I N G C O N D U C T O R S I N R O O F - M O U N T E D S U N L I T C O N D U I T A T LE A S T 0 . 5 " A B O V E R O O F A N D U S I N G T H E O U T D O O R D E S I G N T E M P E R A T U R E O F 47 oC O R L E S S ( A L L O F U N I T E D S T A T E S ) , a) 1 2 A W G , 9 0 oC C O N D U C T O R S A R E G E N E R A L L Y A C C E P T A B L E F O R M O D U L E S WI T H I s c O F 7 . 6 8 A M P S O R L E S S W H E N P R O T E C T E D B Y A 1 2 - A M P O R S M A L L E R FU S E . b) 1 0 A W G , 9 0 oC C O N D U C T O R S A R E G E N E R A L L Y A C C E P T A B L E F O R M O D U L E S WI T H I s c O F 9 . 6 A M P S O R L E S S W H E N P R O T E C T E D B Y A 1 5 - A M P O R S M A L L E R FU S E . NO T E S F O R A R R A Y C I R C U I T W I R I N G ( G u i d e S e c t i o n 6 a n d 8 a n d A p p e n d i x E ) : OC P D = O V E R C U R R E N T P R O T E C T I O N D E V I C E NA T I O N A L E L E C T R I C A L C O D E ® RE F E R E N C E S SH O W N A S (N E C X X X . X X ) NO T E S F O R A L L D R A W I N G S : SI G N S – S E E G U I D E S E C T I O N 7 SI G N F O R D C D I S C O N N E C T SI G N F O R I N V E R T E R O C P D A N D A C DI S C O N N E C T ( I F U S E D ) No s i g n n e c e s s a r y s i n c e 6 9 0 . 5 1 ma r k i n g o n P V m o d u l e c o v e r s ne e d e d i n f o r m a t i o n AC O U T P U T C U R R E N T NO M I N A L A C V O L T A G E SO L A R P V S Y S T E M AC P O I N T O F C O N N E C T I O N TH I S P A N E L F E D B Y M U L T I P L E SO U R C E S ( U T I L I T Y A N D S O L A R ) 801 E Borchard Ave02/17/22 801 E Borchard Ave02/17/22 801 E Borchard Ave04/13/22 801 E Borchard Ave02/17/22 801 E. BORCHARD AVE. SANTA ANA, CA 92707 OVIEDO, BLANCA Prepared For: SOLARPLEX, LLC. 5902 FIRESTONE BLVD. SOUTH GATE, CA 90280 (562) 806-6000 Design Criteria 1- Code: CALIFORNIA BLDG CODE 2019 / ASCE 7-16 2 - Wind: 95 MPH, Exposure: C 3 - Wood Species: DF-L No. 1 (SG = 0.5 ) Notice: Use restrictions of these calculations. The attached Calculations are valid only when bearing original signature hereon. Contractor/Client to verify existing dimensions/conditions prior to construction & solar racking is installed per manufacturer span requirements. The use of these calculations is solely intended for the above mentioned project. 1-844-PV ELITE | info@yoursolarplans.com 3000 E. Birch Street Suite 201 | Brea CA 92821 1/10/2022 Structural Calculations for SOLAR POWER SYSTEM CONNECTION CHECK AT: Job: R E G I S T E R E D P R O F E S S I O N A L E N G I N E E R C I V I L No. C70784 Exp. 06/30/2023 S T A T E O F C A L I F O R N I A PHONG TRUONG 801 E Borchard Ave02/17/22 0102133467089 9  711 !1"1#$ %&&83'&(60) !%*008'+23(03),%'20-.9/,03 1903  96382803 219 013  3456789:;<6=5>?<: @AA64BBC '20-.9/,4194 9638284 219 D<<6A?:5>4BC &&83'&(604*008'+23(03 EF4G5>?<:C '+H I?=4B>5=JC 3233*20*02 0870873688+K L5M56AINJ4C O @3DEPQR S TU02*V,++W TU3X*V,80W TUX2*V,88 W TU022*V,'0W TY ,!U '6 W TY ,!UU 6X W TY ,!UUU 023W TY ,!UZ 02+W @3DEPQR [ TU02*V,83W TU3X*V,86 W TUX2*V,'X W TU022*V,60W TY ,!U 022 W TY ,!UU 002 W TY ,!UUU*UZ 00X W @3DEPQ[\ 91 -8*2XO1,,'X W ]^_`_abcdaefgehid_g^_`_jklk]`_mc_hdifnadid_o`cohicip_fgp_fdadod^_qicb_ao`ifng_cef_ideofcef_apig_gb`efrd^_sbecgefr hog_igotdeoft`oh_aauva_`aa^obcghofme`pifnobdtbdosdief_gm`opd^eadoocwed^d^_cohicxbd^o`ednyiqefrzb`eagehdeofs_mo`_ t`oh__gefrwed^g_aerfu {?B7F5?=46  ,, ,HW/,91 -8,,,,# ,,!,|,91 -84  ,,,  ,, #,,H, ,}W,,4#,,# ,~ , , #,,,,H,4/,#,, ! !,€ -7‚,,,#*,,,! ,4,, !,,W,/,!#WHH,#,,,,,##*, ,,! ,4!!,4,W,4, #,! ,,~W,H # O ,,HW,,,#,,, ,/,,,49 W,,    H ,W, ,,,,, ,,, ,H,H # W,,,~W/,HH4   ,!,,, ,,H, 9 , ,,,HHW, ,,ƒ!W,HW,,H, 4/!,~,,,Y# ,!, ,H, H,4,H,H,,‚,HH, ,,! !,, H, ,/,#,,2,H,HWHW#,,W,   !HW,2,H,H #,,,W / ,!/,! !,,, ,H !,/ ,,H, „…†‡ ˆ‰Š‹ŒŽŽŠ‰ŒŒ‹ŒŽŠ‘ŽŽ’“”““•‹‹–—‰˜™š›•™ 801 E Borchard Ave02/17/22 ASCE 29.4.4 Rooftop Solar Panels Parallel to the Roof Surface on Buildings of All Heights and Roof Slopes. Roof Slope  = 20 ° Roof Shape Gable Tributary Width s = 6.00 ft Tributary Length l = 2.88 ft Effective Area A e = 17.27 ft2 Height of Structure h = 15 ft Wind Speed V = 95 mph Exposure Category C Building Width B = 25 ft Building Length L = 50 ft Zone Width a = 3 ft Elevation Height zg = 86 ft Wind Directionality Kd = 0.85 Topography Factor Kt = 1.00 Ground Elevation Factor Ke = 1.00 Velocity Pressure Exposure Coefficient Kz = 0.85 Velocity Pressure q z = 0.00256KzKztKdKeV2 = 16.62 psf Solar Array Pressure Equalization a = 0.77 Array Edge Factor E = 1.50 Zone GCp p = qz(GCp)(E)(a) 3 - - 3r 3.45 -66.11 3e 2.94 -56.25 2 - - 2r 2.94 -56.25 2e - - 2n 2.94 -56.25 1 - - 1' - - 801 E Borchard Ave02/17/22 LAG SCREW ANALYSIS Loads Wind Pressures qz = -56.25 psf Solar Panel Load QD = 3 psf Panel Length l = 5.758 ft Panel Width b 3.4055 ft Attachment Spacing s = 6 ft Portrait Tributary Area At = 17.27 ft2 Wind Load P W = qz * At = -972 lbs Dead Load P D = Q D * At = 51.821 lbs Uplift Pa = 0.6 P D + 0.6 Pw = -552 lbs Landscape Tributary Area At = b * s = 10.217 ft2 Wind Load P W = qz * At = -575 lbs Dead Load P D = Q D * At = 30.65 lbs Uplift Pa = 0.6 P D + 0.6 Pw = -326 lbs Lag Screw 5/16" x 3" Specific Gravity of Lumber SG = 0.50 (Douglas Fir-Larch) Diameter of Lag Screw D = 5/16 in Withdraw Design /in 1800*SG 3/2 *D 3/4 = 266 lbs/in Depth of Embedment lp = 2.50 in Total Nominal Withdrawal Value W = W * l p = 665 lbs Load Duration Factor CD = 1.6 Withdrawal Design Value W' = W * C D = 1064 lbs Demand Capacity Ratio DCR = Pa / W' = 0.52 < 1 OK 801 E Borchard Ave02/17/22 ASCE 30.3.2 Design Wind Pressure Beam/ Top Chord Check Roof Slope  = 20 ° Roof Shape Gable Tributary Width s = 2.00 ft Tributary Length L = 13.25 ft Effective Area A = L ( MAX [ s , L/3] ) = 59 ft2 Height of Structure h = 15 ft Wind Speed V = 95 mph Exposure Category C Building Width B = 25 ft Building Length L = 50 ft Zone Width a = 3 ft Elevation Height zg = 86 ft Wind Directionality Kd = 0.85 Topography Factor Kt = 1.00 Ground Elevation Factor Ke = 1.00 Velocity Pressure Exposure Coefficient Kz = 0.85 Velocity Pressure q z = 0.00256KzKztKdKeV 2 = 16.62 psf Internal Pressure Coefficient (GCpi) = -0.18 Zone GCp p = q z [(GCp) - (Gcpi)] 3 - - 3r 2.63 -46.69 3e 2.60 -46.13 2 - - 2r 2.60 -46.13 2e - - 2n 2.60 -46.13 1 - - 1' - - 801 E Borchard Ave02/17/22 Beam/ Top Chord Check Lumber: Moment Demand # of Attachment per Rafter N A = Span : Orientation Lenght (ft) : Dead Load Roof Material: Q D = psf Live Load QLr = psf Wind Load p = psf Snow Load QS = psf Rafter Spacing s = in Wind Load, Portrait Portrait UL = Wind Load, Landscape Landscape U W = Linear Dead Load wd = plf Live Load wLr = plf Start ft Start ft End ft End ft Snow Load ws = plf Start ft Start ft End ft End ft Ma, Moment D lb-ft D+Lr lb-ft D+S lb-ft 0.6D+0.6W lb-ft D+0.45W+0.75Lr lb-ft D+0.45W+0.75S lb-ft Moment Capacity Framing Member Size Lumber Grade : DF-L No. 1 C M = 1 Ct = 1 Cr= CF = fb = psi Cfu =C i = Breadth b = in Depth d = in Section Modulus Sx = bd 2 / 6 = in3 Bending Stress Capacity Fb = CM * C t * Cr * C F * fb = psi Table 4.3.1 NDS 2015 Deflection Limit E = ksi I = in4 Transient Deflection in Transient Deflection Allowed > [OKAY] Total Deflection in Total Deflection Allowed > [OKAY] -46.13 DF-L No. 1 4 j lj (ft) pd,j  (lbs) pw,j  (lbs) ps,j  (lbs) Portrait 1 2.2 51.8 -797 0.0 6.5 51.8 -797 -797 0.0 4 12.3 51.8 -797 0.0 0.0 6.00 6.00 0.00 0.00 1.25 Portrait 3 8.0 51.8 14.00 1 2 3 4 Eave 2 0.0 0.0 0.0 0.0 0.0 0 0.0 0.0 0.0 0.0 0 0.0 0.0 0.0 0.0 0 0.0 0.0 0 0.0 Portrait 0 0.0 0.0 0 0.0 28 40 0.0 0.0 0.0 0.0 0 0.0 Portrait 0 0.0 30.65 -471 0 0 0.0 0 1.5 0 0 0.0 Portrait 1.5 0.0 Portrait 0 0.0 0.0 AT (ft2) 17.274 10.217 pd (lbs) 51.821 -797 p w (lbs) ps (lbs) 0 13.02 2x4 1.15 1.5 13.25 13.02 13.25 1000 1.50 3.50 182 187 182 462 246 246 DCR 0.9 1553 psi D 715 psi 0.46 3.06 1725 CD Fb' = C D * F b ASD Load Ma * S x 1.15 1984 psi D+S 715 psi 0.36 OKAY OKAY 1.25 2156 psi D+Lr 731 psi 0.34 OKAY 1.6 2760 psi 0.129 558 120 1700 5.36 0.6D+0.6W 1810 psi 0.66 OKAY 1.0 1 20 0.00 24 Comp 0.109 663 180 1.6 2760 psi D+0.45W+0.75S 965 psi 0.35 OKAY 1.6 2760 psi D+0.45W+0.75Lr 965 psi 0.35 OKAY ൌ ሺ െ ሻ െ െ െ ‐600.0 ‐400.0 ‐200.0 0.0 200.0 400.0 600.0 0.000 2.000 4.000 6.000 8.000 10.000 12.000 14.000 801 E Borchard Ave02/17/22 EISMIC WEIGHT COMPARISON / ANALYSIS - (PER CEBC 2019 Part 10 Chapter 5 Section 502.5) PV System Weight Module Model Longi Panel Weight Wpanel = 43 lbs Number of Panels NPV = 8 Total PV System Weight W PV = Wpanel * NPV = 344 lbs Existing Roof Weight Roof Weight QD =14.0 psf Building Length Lbuild =50 ft Building Width W build =25 ft Roof Area Abuild =1250 ft2 Building Perimeter Pbuild = 150 ft Wall Height ht = 8 ft Wall weight Qwall = 15 psf Interior wall weight Qint = 10 psf Roof Load Wfloor = Abuild * QD = 17500 lbs Wall LoadWwall = ht /2 * Qwall * Pbuild + Abuild * Qint /2 = 15250 lbs Total Story Weight Wbuild = Wfloor + Wwall = 32750 lbs Percentage Weight Increase WPV / Wbuild = 1.05%< 10% OKAY 801 E Borchard Ave02/17/22