HomeMy WebLinkAbout1028 S Maxine St - PlanSHEET NAME SHEET NUMBER PV-4 PROJECT NAME TH I E N A N V A N 1 0 2 8 S M A X I N E S T , SA N T A A N A , C A , 9 2 7 0 4 U S A AP N # 1 0 8 5 9 1 8 7 UT I L I T Y : S C E AH J : C I T Y O F S A N T A A N A SHEET SIZE ANSI B 11" X 17" DEL MAR, CA 92014, USA REVDATE DESCRIPTION VERSION UR05/16/2023 INITIAL RELEASE DESIGN SUPPORT DAY OF INSTALL: CHAT.POWUR.COM ELECTRICAL LINE DIAGRAM WITH CALCULATION ELECTRICAL LINE DIAGRAM WITH CALCULATION SCALE: NTS1 AMBIENT TEMPERTURE SPECIFICATIONS RECORD LOW TEMP AMBIENT TEMP (HIGH TEMP 2%) CONDUCTOR TEMPERATURE RATE (ON ROOF) CONDUCTOR TEMPERATURE RATE (OFF ROOF) 2° 31°90°75° INVERTER SPECIFICATIONS MANUFACTURER / MODEL # QUANTITY NOMINAL OUTPUT VOLTAGE NOMINAL OUTPUT CURRENT ENPHASE ENERGY IQ8A-72-2-US 15 240 VAC 1.45A EXISTING GROUNDING SYSTEM (N) 50A FEEDER BREAKER 200A 50A L BI-DIRECTIONAL UTILITY METER 1-PHASE, 3-W, 120V/240V, 60Hz (E) 225A MAIN SERVICE PANEL WITH (E) 200A MAIN BREAKER (BOTTOM FED) INTERCONNECTION 120% RULE - CEC 705.12(b)(3)(2) UTILITY FEED + SOLAR CURRENT 200A + 40A = 240A BUSS RATING x 120% 225A x 120% = 270A TERMINATOR CAP ON LAST CABLE CONNECTOR Q CABLE (TYP) 07 MICRO-INVERTERS IN BRANCH CIRCUIT #2 G (N)JUNCTION BOX G ENPHASE ENERGY IQ8A-72-2-US, 240V, MICRO-INVERTERS 20A 10A/15A A B 20A 08 MICRO-INVERTERS IN BRANCH CIRCUIT #1 (N)ENPHASE IQ COMBINER BOX 4 X2-IQ-AM1-240-4 (IEEE 1547:2018) IQ GATEWAY UTILITY PROVIDER: MAIN SERVICE VOLTAGE: MAIN PANEL BRAND: MAIN SERVICE PANEL: MAIN CIRCUIT BREAKER RATING: MAIN SERVICE LOCATION: SERVICE FEED SOURCE: SCE 240V EATON (E) 225A (E) 200 A SOUTH SERVICE INFO. UNDERGROUND NOTE: 3/4" OR GREATER EMT CONDUIT RUN (7/8" ABOVE ROOF) SOLAR MODULE SPECIFICATIONS MANUFACTURER / MODEL # VMP IMP VOC ISC TEMPERATURE COEFFICIENT OF Voc # OF MODULES REC SOLAR REC400AA PURE (400W)42.1 9.51 48.8 10.28 -0.24%/°C 15 MODULE DIMENSION 71.7" L x 40" W x 1.2"D TOTAL SYSTEM SIZE:- (NEW) (15 x 400W) = 6.000 KWDC (15 X 381W X 97.0)= 5.544 CEC KWAC WIRE TAG CONDUIT WIRE QTY WIRE GAUGE WIRE TYPE TEMP. RATING WIRE AMPACI TY (A) TEMP. DERATE CONDUIT FILL DERATE DERATED AMPACITY (A) INVERTER QTY. DESIGN CURRENT (A) GROUND SIZE GROUND WIRE TYPE A OPEN AIR 2 12 AWG Q-CABLES 90°C 30 0.96 N/A 28.80 08 11.60 06 AWG BARE CU GND B 3/4" EMT 4 2 10 AWG 12 AWG THWN-2 NM-B CABLES WHERE RUN INDOORS 90°C 40 30 0.96 0.8 30.72 23.04 08 11.60 10 AWG THWN-2 C 3/4" EMT 3 10 AWG THWN-2 75°C 35 0.94 1.0 32.90 15 21.75 10 AWG THWN-2 D 3/4" EMT 3 8 AWG THWN-2 75°C 50 0.94 1.0 47.00 ------ 10 AWG THWN-2 NOTE: PV BREAKER CALCULATION: (15 X 1.45)X 1.25) = 27.18) ~30A 08 SUNPOWER SPR-X20-250-BLK (250) MODULES G (E)JUNCTION BOX (E)INTEGRATED MICROINVERTERS, 240V EXISTING WIRES (N) 30A PV BREAKER 30A 20A G (E) AC DISCONNECT 30A NON-FUSED, 240 VAC EXISTING WIRES (N) 100A LOAD CENTER, 240 VAC C D (E) 20A PV BREAKER 1028 S Maxine St 07/28/23 Expedited Permit Process for PV Systems - Micro-Inverter1 Expedited Permit Process for PV Systems Micro-Inverter The Solar America Board for Codes and Standards (Solar ABCs) Expedited Permit Pro- cess provides a means to differentiate systems that can be permitted quickly and easily due to their similarity with the majority of small-scale PV systems. Those systems with unique characteristics may be handled with small additions to this Expedited Permit Process or may require much more information, depending on the uniqueness of the installation. The following pages contain forms for the Micro-Inverter to use with the Expedited Per- mit Process. The Standard String, AC Module, and Supply-Side Connection forms are also available as interactive PDF files at www.solarabcs.org/permitting. In jurisdic- tions that have adopted the Expedited Permit Process for PV Systems, these forms can be filled out electronically and submitted in either printed form and via email. An elec- tronic format is used so that the supplied information is standardized and legible for the local jurisdiction. 1028 S Maxine St 07/28/23 Expedited Permit Process for PV Systems — Micro-Inverter2 Expedited Permit Process for Small-Scale PV Systems Micro-Inverter The information in this guideline is intended to help local jurisdictions and contractors identify when PV system installations are simple, needing only a basic review, and when an installation is more complex. It is likely that 50%-75% of all residential systems will comply with these simple criteria. For projects that fail to meet the simple criteria, resolution steps have been suggested to provide as a path to permit approval. Required Information for Permit: 1. Site plan showing location of major components on the property. This drawing need not be exactly to scale, but it should represent relative location of components at site (see supplied example site plan). PV arrays on dwellings with a 3’ perimeter space at ridge and sides may not need separate fire service review. 2. Electrical diagram showing PV array configuration, wiring system, overcurrent protection, inverter, disconnects, required signs, and ac connection to building (see supplied standard electrical diagram). 3. Specification sheets and installation manuals (if available) for all manufactured components including, but not limited to, PV modules, inverter(s), combiner box, disconnects, and mounting system. Step 1: Structural Review of PV Array Mounting System Is the array to be mounted on a defined, permitted roof structure? l Yes l No If No due to non-compliant roof or a ground mount, submit completed worksheet for the structure WKS1. Roof Information: 1. Is the roofing type lightweight (Yes = composition, lightweight masonry, metal, etc…)__________________________ ____________________________________________________________________________________________________ If No, submit completed worksheet for roof structure WKS1 (No = heavy masonry, slate, etc…). 2. Does the roof have a single roof covering? l Yes l No If No, submit completed worksheet for roof structure WKS1. 3. Provide method and type of weatherproofing roof penetrations (e.g. flashing, caulk).____________________________ Mounting System Information: 1. Is the mounting structure an engineered product designed to mount PV modules with no more than an 18” gap beneath the module frames? l Yes l No If No, provide details of structural attachment certified by a design professional. 2. For manufactured mounting systems, fill out information on the mounting system below: a. Mounting System Manufacturer ___________Product Name and Model#________________________________ b. Total Weight of PV Modules and Rails ___________lbs c. Total Number of Attachment Points____________ d. Weight per Attachment Point (b÷c)_________________lbs (if greater than 45 lbs, see WKS1) e. Maximum Spacing Between Attachment Points on a Rail ______________inches (see product manual for maximum spacing allowed based on maximum design wind speed) f. Total Surface Area of PV Modules (square feet)_________________ ft 2 g. Distributed Weight of PV Module on Roof (b÷f)_______________ lbs/ft2 If distributed weight of the PV system is greater than 5 lbs/ft2, see WKS1. Step 2: Electrical Review of PV System (Calculations for Electrical Diagram) In order for a PV system to be considered for an expedited permit process, the following must apply: 1. PV modules, utility-interactive inverters, and combiner boxes are identified for use in PV systems. 2. The PV array is composed of 4 series strings or less per inverter. 3. The total inverter capacity has a continuous ac power output 13,440 Watts or less 4. The ac interconnection point is on the load side of service disconnecting means (690.64(B)). 5. One of the standard electrical diagrams (E1.1, E1.1a, E1.1b, or E1.1c) can be used to accurately represent the PV system. Interactive PDF diagrams are available at www.solarabcs.org/permitting. Fill out the standard electrical diagram completely. A guide to the electrical diagram is provided to help the applicant understand each blank to fill in. If the electrical system is more complex than the standard electrical diagram can effectively communicate, provide an alternative diagram with appropriate detail. 1028 S Maxine St 07/28/23 E x p e d i t e d P e r m i t P r o c e s s f o r P V S y s t e m s 3 Micro-Inverter Site Plan 1028 S Maxine St 07/28/23 E x p e d i t e d P e r m i t P r o c e s s f o r P V S y s t e m s 4 Micro-Inverter Electrical Diagram Contractor Name, Address and Phone: One-Line Standard Electrical Diagram for Micro-Inverter PV Systems Site Name: Site Address: System AC Size: SIZE FSCM NO DWG NO REV E1.1a SCALE NTS Date: SHEET Drawn By: Checked By: DESCRIPTION OR CONDUCTOR TYPE USE-2 or PV WIRE GEC EGC X ALL THAT APPLY EXTERIOR CABLE LISTED W/ INV. THWN-2 or XHHW-2 or RHW-2 GEC EGC X ALL THAT APPLY NO DC GEC IF 690.35 SYSTEM THWN-2 or XHHW-2 or RHW-2 GEC EGC X ALL THAT APPLY TAG 1 2 3 4 5 CONDUIT AND CONDUCTOR SCHEDULE COND. GAUGE MFG MFG NUMBER OF CONDUCTORS MFG Cable MFG Cable CONDUIT TYPE N/A N/A N/A SAME SAME CONDUIT SIZE N/A N/A N/A SAME SAME DESCRIPTION PV DC or AC MODULE DC/AC INVERTER (MICRO) J-BOX (IF USED) PV ARRAY AC COMB. PANEL (IF USED) GEN METER (IF USED) AC DISCONNECT (IF USED) SERVICE PANEL TAG 1 2 3 4 5 6 7 8 PART NUMBER NOTES FOR UNUSED MODULES PUT "N/A” in BLANK ABOVE 1 1 3 2 3 EQUIPMENT SCHEDULE 2 _____ MICRO-INVERTERS IN BRANCH- CIRCUIT MOD ____ DC AC MOD ____ DC AC MOD ____ DC AC MOD ____ DC AC MOD ____ DC AC MOD ____ DC AC J-BOX 4 AC DISCO M BUILDING GROUNDING ELECTRODE G M UTILITY SERVICE MAIN SERVICE PANEL MAIN OCPD INVERTER OCPD 6 7 8 5 4 5 G SEE GUIDE APPENDIX D FOR INFORMATION ON MODULE AND ARRAY GROUNDING AC COMBINER PANEL G ____ MICRO-INVERTERS IN BRANCH- CIRCUIT 1028 S Maxine St 07/28/23 E x p e d i t e d P e r m i t P r o c e s s f o r P V S y s t e m s 5 Contractor Name, Address and Phone: Notes for One-Line Standard Electrical Diagram for Single-Phase PV Systems Site Name: Site Address: System AC Size: SIZE FSCM NO DWG NO REV E1.2a SCALE NTS Date: SHEET Drawn By: Checked By: MAX POWER-POINT CURRENT (IMP) MAX POWER-POINT VOLTAGE (VMP) OPEN-CIRCUIT VOLTAGE (VOC) SHORT-CIRCUIT CURRENT (I SC) MAX SERIES FUSE (OCPD) MAXIMUM POWER (P MAX) MAX VOLTAGE (TYP 600VDC) VOC TEMP COEFF (mV/oC or %/oC ) IF COEFF SUPPLIED, CIRCLE UNITS MODULE MAKE MODULE MODEL PV MODULE RATINGS @ STC (Guide Section 5) MAX DC VOLT RATING MAX POWER @ 40oC NOMINAL AC VOLTAGE MAX AC CURRENT MAX OCPD RATING INVERTER MAKE INVERTER MODEL INVERTER RATINGS (Guide Section 4) 1) IF UTILITY REQUIRES A VISIBLE-BREAK SWITCH, DOES THIS SWITCH MEET THE REQUIREMENT? YES NO N/A 2) IF GENERATION METER REQUIRED, DOES THIS METER SOCKET MEET THE REQUIREMENT? YES NO N/A 3) SIZE PHOTOVOLTAIC POWER SOURCE (DC) CONDUCTORS BASED ON MAX CURRENT ON NEC 690.53 SIGN OR OCPD RATING AT DISCONNECT 4) SIZE INVERTER OUTPUT CIRCUIT (AC) CONDUCTORS ACCORDING TO INVERTER OCPD AMPERE RATING. (See Guide Section 9) 5) TOTAL OF ______ INVERTER OUTPUT CIRCUIT OCPD(s), ONE FOR EACH MICRO- INVERTER CIRCUIT. DOES TOTAL SUPPLY BREAKERS COMPLY WITH 120% BUSBAR EXCEPTION IN 690.64(B)(2)(a)? YES NO NOTES FOR INVERTER CIRCUITS (Guide Section 8 and 9): 1.) LOWEST EXPECT AMBIENT TEMPERATURE BASED ON ASHRAE MINIMUM MEAN EXTREME DRY BULB TEMPERATURE FOR ASHRAE LOCATION MOST SIMILAR TO INSTALLATION LOCATION. LOWEST EXPECTED AMBIENT TEMP ____oC 2.) HIGHEST CONTINUOUS AMBIENT TEMPERATURE BASED ON ASHRAE HIGHEST MONTH 2% DRY BULB TEMPERATURE FOR ASHRAE LOCATION MOST SIMILAR TO INSTALLATION LOCATION. HIGHEST CONTINUOUS TEMPERATURE ____oC 2.) 2009 ASHRAE FUNDAMENTALS 2% DESIGN TEMPERATURES DO NOT EXCEED 47oC IN THE UNITED STATES (PALM SPRINGS, CA IS 44.1 oC). FOR LESS THAN 9 CURRENT-CARRYING CONDUCTORS IN ROOF-MOUNTED SUNLIT CONDUIT AT LEAST 0.5" ABOVE ROOF AND USING THE OUTDOOR DESIGN TEMPERATURE OF 47oC OR LESS (ALL OF UNITED STATES), a) 12 AWG, 90 oC CONDUCTORS ARE GENERALLY ACCEPTABLE FOR MODULES WITH Isc OF 7.68 AMPS OR LESS WHEN PROTECTED BY A 12-AMP OR SMALLER FUSE. b) 10 AWG, 90oC CONDUCTORS ARE GENERALLY ACCEPTABLE FOR MODULES WITH Isc OF 9.6 AMPS OR LESS WHEN PROTECTED BY A 15-AMP OR SMALLER FUSE. NOTES FOR ARRAY CIRCUIT WIRING (Guide Section 6 and 8 and Appendix E): OCPD = OVERCURRENT PROTECTION DEVICE NATIONAL ELECTRICAL CODE ® REFERENCES SHOWN AS (NEC XXX.XX) NOTES FOR ALL DRAWINGS: SIGNS–SEE GUIDE SECTION 7 SIGN FOR DC DISCONNECT SIGN FOR INVERTER OCPD AND AC DISCONNECT (IF USED) No sign necessary since 690.51 marking on PV module covers needed information AC OUTPUT CURRENT NOMINAL AC VOLTAGE SOLAR PV SYSTEM AC POINT OF CONNECTION THIS PANEL FED BY MULTIPLE SOURCES (UTILITY AND SOLAR) Notes for Micro-Inverter Electrical Diagram 1028 S Maxine St 07/28/23 COVER SHEET PHOTOVOLTAIC ROOF MOUNT SYSTEM 1028 S MAXINE ST , SANTA ANA, CA, 92704 USA SHEET NAME SHEET NUMBER PV-0 PROJECT NAME TH I E N A N V A N 1 0 2 8 S M A X I N E S T , SA N T A A N A , C A , 9 2 7 0 4 U S A AP N # 1 0 8 5 9 1 8 7 UT I L I T Y : S C E AH J : C I T Y O F S A N T A A N A SHEET SIZE ANSI B 11" X 17" DEL MAR, CA 92014, USA REVDATE DESCRIPTION VERSION UR05/16/2023 INITIAL RELEASE DESIGN SUPPORT DAY OF INSTALL: CHAT.POWUR.COM 2 VICINITY MAP SCALE: NTSPV-0 1 AERIAL PHOTO SCALE: NTSPV-0 GENERAL NOTES · THE CONTRACTOR/INSTALLER OF THE SOLAR PV SYSTEM OVER EXISTING ROOF SHALL CONFORM TO OSHA REQUIREMENTS DURING THE CONSTRUCTION PHASE. JOB SAFETY AND CONSTRUCTION PROCEDURES ARE THE SOLE RESPONSIBILITY OF THE CONTRACTOR/INSTALLER. · REFER TO ELECTRICAL DRAWING PV-4 FOR PANEL DETAILED INFORMATION. · IN CASE OF CONFLICT BETWEEN STRUCTURAL DRAWINGS AND ELECTRICAL DRAWINGS, THE MOST RIGID REQUIREMENTS SHALL GOVERN. · THE CONTRACTOR/INSTALLER SHALL VERIFY ALL EXISTING BUILDING INFORMATION SHOWN (DIMENSIONS, ROOF TOP PROJECTIONS, ETC.) AND NOTIFY THE ENGINEER OF ANY DISCREPANCIES PRIOR TO INSTALLATIONS OF PV SYSTEM. · THE CONTRACTOR/INSTALLER SHALL VERIFY AND COORDINATE EXISTING OPENINGS, ROOF TOP UNITS, VENT PIPES, ETC. SHOWN ON DRAWINGS. IF THERE IS A DISCREPANCY BETWEEN DRAWINGS, IT IS THE CONTRACTORS/INSTALLER'S RESPONSIBILITY TO NOTIFY ENGINEER PRIOR TO PERFORMING THE WORK. · ALL CONSTRUCTION IS TO BE PERFORMED IN STRICT CONFORMANCE WITH ALL APPLICABLE TOWN, COUNTY & STATE REGULATIONS AND/OR ANY OTHER GOVERNING BODIES. · DO NOT SCALE THESE DRAWINGS, USE DIMENSIONS. CONTRACTOR MUST CONDUCT ROOF SURVEY TO VERIFY DIMENSIONS SHOWN ON PLAN PRIOR TO INSTALLATION. IF THERE IS A DISCREPANCY IT IS CONTRACTOR/INSTALLER'S RESPONSIBILITY TO NOTIFY THE ENGINEER IMMEDIATELY. · LOCATED IN AREAS NOT REQUIRING PLACEMENT OF GROUND LADDERS OVER OPENINGS SUCH AS DOORS OR WINDOWS. · LOCATED AT STRONG POINTS OF BUILDING CONSTRUCTION IN LOCATIONS WHERE ACCESS POINT DOES NOT CONFLICT WITH OVERHEAD OBSTRUCTIONS SUCH AS TREE LIMBS, WIRES, OR SIGNS. · DISCONNECT MEANS MUST HAVE DEDICATED CLEAR UNOBSTRUCTED WORKING SPACE NOT LESS THAN 3' DEEP BY 2.5' WIDE TO NOT LESS THAN 6.5' ABOVE WALKABLE SURFACES IN FRONT OF DISTRIBUTION PANEL. ·ALL SOLAR MODULES, EQUIPMENT, AND METALLIC COMPONENTS TO BE BONDED. ·PV ARRAY NOT TO EXCEED HIGHEST POINT OF THE ROOF. ·RAPID SHUTDOWN IS ACTIVED AT THE INVERTER BY THE AC DISCONNECT. ELECTRICAL NOTES · ALL EQUIPMENT TO BE LISTED BY UL OR OTHER NRTL, AND LABELED FOR ITS APPLICATION. ·ALL CONDUCTORS SHALL BE COPPER, RATED FOR 600 V AND 90 & 75 DEGREE C WET ENVIRONMENT. ·WIRING, CONDUIT, AND RACEWAYS MOUNTED ON ROOFTOPS SHALL BE ROUTED DIRECTLY TO, AND LOCATED AS CLOSE AS POSSIBLE TO THE NEAREST RIDGE, HIP, OR VALLEY. · WORKING CLEARANCES AROUND ALL NEW AND EXISTING ELECTRICAL EQUIPMENT SHALL COMPLY WITH CEC 110.26. ·DRAWINGS INDICATE THE GENERAL ARRANGEMENT OF SYSTEMS. CONTRACTOR SHALL FURNISH ALL NECESSARY OUTLETS, SUPPORTS, FITTINGS AND ACCESSORIES TO FULFILL APPLICABLE CODES AND STANDARDS. ·WHERE SIZES OF JUNCTION BOXES, RACEWAYS, AND CONDUITS ARE NOT SPECIFIED, THE CONTRACTOR SHALL SIZE THEM ACCORDINGLY. ·ALL WIRE TERMINATIONS SHALL BE APPROPRIATELY LABELED AND READILY VISIBLE. ·MODULE GROUNDING CLIPS TO BE INSTALLED BETWEEN MODULE FRAME AND MODULE SUPPORT RAIL, PER THE GROUNDING CLIP MANUFACTURER'S INSTRUCTION. ·MODULE SUPPORT RAIL TO BE BONDED TO CONTINUOUS COPPER E.G.C. VIA WEEB LUG OR ILSCO GBL-4DBT LAY-IN LUG. ·THE POLARITY OF THE GROUNDED CONDUCTORS IS NEGATIVE INTERCONNECTION METHOD : BACKFEED BREAKER ROOF TYPE: - FLAT-TILE ROOF FRAME: - 2"X4" TRUSSES @ 24" O.C. STORY: - TWO STORY SNOW LOAD : - 0 PSF WIND SPEED :- 95 MPH WIND EXPOSURE:- C RISK CATEGORY:- II COORDINATE:- 33.733703, -117.939228 DESIGN CRITERIA: 15 MODULES-ROOF MOUNTED - 6.000 kWDC, 5.544 CEC kWAC SHEET INDEX PV-0 COVER SHEET PV-1 SITE PLAN WITH ROOF PLAN PV-2 ROOF PLAN WITH MODULES PV-3 ATTACHMENT DETAILS PV-4 ELECTRICAL LINE DIAGRAM WITH CALCULATION PV-5 WARNING LABELS & PLACARD PV-6+ EQUIPMENT SPEC SHEETS 2022 CALIFORNIA ELECTRICAL CODE (CEC) 2022 CALIFORNIA BUILDING CODE (CBC) 2022 CALIFORNIA RESIDENTIAL CODE (CRC) 2022 CALIFORNIA EXISTING BUILDING CODE (CEBC) 2022 CALIFORNIA PLUMBING CODE (CPC) 2022 CALIFORNIA MECHANICAL CODE (CMC) 2022 CALIFORNIA GREEN BUILDING CODE (CGBC) 2022 CALIFORNIA ENERGY CODE (CEC) 2022 CALIFORNIA FIRE CODE TITLE 24 SUPPLEMENT ANY OTHER LOCAL AMENDMENTS GOVERNING CODES: SYSTEM SUMMARY: (N) 15 - REC SOLAR REC400AA PURE (400W) MODULES (N) 15 - ENPHASE ENERGY IQ8A-72-2-US MICRO-INVERTERS (N)JUNCTION BOX (E) 225A MAIN SERVICE PANEL WITH (E) 200A MAIN BREAKER (N)100A LOAD CENTER (N)ENPHASE IQ COMBINER BOX 4 X2-IQ-AM1-240-4 (IEEE 1547:2018) NOTE: INSTALLER TO DETERMINE OPTIMAL CONDUIT RUN ON SITE. ATTIC RUN IS OPTIONAL UNLESS REQUIRED BELOW. ATTIC RUN: OPTIONAL EXISTING SYSTEM SUMMARY: (E) 08 - SUNPOWER SPR-X20-250-BLK (250) MODULES (E)08 - MICRO-INVERTERS (E)JUNCTION BOX (E)30A NON-FUSED AC DISCONNECT 6/30/2024 STAMPED 07/06/2023 2.000 Kw The scope of the plans is for the installation of the solar photovoltaic system only and the approval is subject to compliance with all applicable city and state codes and regulations regarding construction. The approval of the plans does not constitute any certification of the accuracy, completeness, or building permit status of the existing buildings and structures as shown. Bldg# 101115963 Elec# 20180398 Issued 07/27/23 1028 S Maxine St 07/28/23 ~123.85' ~5 1 . 4 6 ' ~116.29' 4' - 1 " 18'-3" 3' - 1 0 " 34'-0" ~5 4 . 5 3 ' MSP LC ACD JB UM CB MSP LC ACDUM CB JB SITE PLAN WITH ROOF PLAN SHEET NAME SHEET NUMBER PV-1 PROJECT NAME TH I E N A N V A N 1 0 2 8 S M A X I N E S T , SA N T A A N A , C A , 9 2 7 0 4 U S A AP N# 1 0 8 5 9 1 8 7 UT I L I T Y : S C E AH J : C I T Y O F S A N T A A N A SHEET SIZE ANSI B 11" X 17" DEL MAR, CA 92014, USA REVDATE DESCRIPTION VERSION UR05/16/2023 INITIAL RELEASE DESIGN SUPPORT DAY OF INSTALL: CHAT.POWUR.COM SITE PLAN WITH ROOF PLAN 1 SCALE: 3/32" = 1'-0" NOTE: A. ALL ELECTRICAL EQUIPMENT, INVERTERS/COMBINER, DISCONNECTS, MAIN SERVICE PANELS, ETC. SHALL NOT BE INSTALLED WITHIN 3’ OF THE GAS METERS’ SUPPLY OR DEMAND PIPING. ROOF ACCESS POINT SHALL BE LOCATED IN AREAS THAT DO NOT REQUIRE THE PLACEMENT OF GROUND LADDERS OVER OPENINGS SUCH AS WINDOWS OR DOORS, AND LOCATED AT STRONG POINTS OF BUILDING CONSTRUCTION IN LOCATIONS WHERE THE ACCESS POINT DOES NOT CONFLICT WITH OVERHEAD OBSTRUCTIONS SUCH AS TREE LIMBS, WIRES OR SIGNS. NOTE: 3/4" OR GREATER EMT CONDUIT RUN (7/8" ABOVE ROOF) LEGEND AC DISCONNECT JUNCTION BOX ACD JB MSP MAIN SERVICE PANEL GATE FENCE TREES ENPHASE IQ COMBINER 4 X2-IQ-AM1-240-4 (IEEE 1547:2018)CB UTILITY METERUM VENT, ATTIC FAN (ROOF OBSTRUCTION) PROPERTY LINE EXISTING DRIVEWAY (E) SHED S M A X I N E S T TWO- STORY HOUSE ROOF ACCESS POINT ROOF ACCESS POINT (E)08 - SUNPOWER SPR-X20-250-BLK (250)MODULES LC LOAD CENTER 6/30/2024 STAMPED 07/06/2023 STRUCTURAL NOTES : 1. THESE PLANS ARE STAMPED FOR STRUCTURAL CODE COMPLIANCE OF THE ROOF FRAMING SUPPORTING THE PROPOSED PV INSTALLATION ONLY. 2. THESE PLANS ARE NOT STAMPED FOR WATER LEAKAGE. 3. PV MODULES, RACKING, AND ATTACHMENT COMPONENTS MUST FOLLOW MANUFACTURER GUIDELINES AND REQUIREMENTS. 4. PLEASE SEE THE ACCOMPANYING STRUCTURAL CALCULATIONS REPORT FOR ADDITIONAL INFORMATION. 5. PRIOR TO COMMENCEMENT OF WORK, THE SOLAR INSTALLER SHALL VERIFY THE ROOF FRAMING INFO BEFORE INSTALLATION AND NOTIFY THE E.O.R. IF THERE IS ANY INCONSISTENCY BETWEEN SITE VERIFICATION AND FOLLOWING: 2x4 TRUSSES @ 24" OC SPACING WITH MAX UNSUPPORTED SPAN EQUAL OR LESS THAN 8 FT. 1028 S Maxine St 07/28/23 1 0 ' - 0 " 35'-2"10'-11" 10'-1"5'-10" 8' - 0 " 9' - 5 " 8'-10" 6" 1 1 ' - 6 " 7' - 1 0 " MSP LC ACD JB UM CB SHEET NAME SHEET NUMBER PV-2 PROJECT NAME TH I E N A N V A N 1 0 2 8 S M A X I N E S T , SA N T A A N A , C A , 9 2 7 0 4 U S A AP N# 1 0 8 5 9 1 8 7 UT I L I T Y : S C E AH J : C I T Y O F S A N T A A N A SHEET SIZE ANSI B 11" X 17" DEL MAR, CA 92014, USA REVDATE DESCRIPTION VERSION UR05/16/2023 INITIAL RELEASE DESIGN SUPPORT DAY OF INSTALL: CHAT.POWUR.COM ROOF PLAN WITH MODULES ROOF PLAN WITH MODULES SCALE: 1/8" = 1'-0"1 MODULE TYPE, DIMENSIONS & WEIGHT NUMBER OF MODULES = 15 MODULES MODULE TYPE = REC SOLAR REC400AA PURE (400W) MODULE WEIGHT = 45 LBS / 20.5 KG. MODULE DIMENSIONS = 71.7"X 40" = 19.92 SF UNIT WEIGHT OF ARRAY = 2.26 PSF · PLUMBING VENTS, SKYLIGHTS AND MECHANICAL VENTS SHALL NOT BE COVERED, MOVED, RE-ROUTED OR RE-LOCATED. NOTE: ACTUAL ROOF CONDITIONS AND TRUSSES (OR SEAM) LOCATIONS MAY VARY. INSTALL PER MANUFACTURER(S) INSTALLATION GUIDELINES AND ENGINEERED SPANS FOR ATTACHMENTS DISTRIBUTED DEAD LOAD = 3.16 PSF AVERAGE ROOF POINT DEAD LOAD = 23.00 LBS TOTAL SYSTEM WEIGHT: 942.90 LBS NOTE: 3/4" OR GREATER EMT CONDUIT RUN (7/8" ABOVE ROOF) ARRAY AREA & ROOF AREA CALC'S ROOF # OF MODULES ARRAY AREA (Sq. Ft.) ROOF AREA (Sq. Ft.) ROOF AREA COVERED BY ARRAY (%) #1 12 239.00 672.45 35.54 #2 3 59.75 341.41 17.50 ROOF DESCRIPTION ROOF TYPE FLAT-TILE ROOF ROOF ROOF TILT AZIMUTH TRUSSES SIZE TRUSSES SPACING #1 15°180° 2"X4" 24" O.C. #2 15°270° 2"X4" 24" O.C. LEGEND VENT, ATTIC FAN (ROOF OBSTRUCTION) ROOF ATTACHMENT UNIRAC SOLARHOOK AT1 @ 48" O.C. TRUSSES AC DISCONNECT JUNCTION BOX ACD JB MSP MAIN SERVICE PANEL FIRE PATHWAY UNIRAC SM LIGHT RAIL ENPHASE ENERGY IQ8A-72-2-US MICRO-INVERTERS ENPHASE IQ COMBINER 4 X2-IQ-AM1-240-4 (IEEE 1547:2018)CB UTILITY METERUM ROOF #1 ROOF #2 36" FIR E PATH W A Y 18" FIRE PATHWAY 18" FIRE PATHWAY 18" F IRE P ATH W A Y 18" F IRE P ATH WAY 18" FI R E PATHWAY 18" F IRE P ATHWAY RE A R Y A R D FR O N T Y A R D BILL OF MATERIALS EQUIPMENT QTY DESCRIPTION RAIL 8 UNIRAC SM LIGHT RAIL 168" MILL SPLICE 2 BND SPLICE BAR PRO SERIES MILL MID CLAMP 17 UNIVERSAL AF SERIES MID CLAMP END CLAMP 25 UNIVERSAL AF SERIES END CLAMP ATTACHMENT 41 UNIRAC SOLARHOOK AT1 ATTACHMENT GROUNDING LUG 07 GROUND LUG MICROINVERTER MOUNTING 15 MICRO MNT BND T-BOLT 1/4IN X 3/4IN SS HARDWARE 41 BND T-BOLT&NUT 3/8" X 1" SS S M A X I N E S T 36 " F I R E P AT H W A Y ARRAY AREA & ROOF AREA CALC'S AREA OF NEW ARRAY (Sq. Ft.) AREA OF EXISTING ARRAY (Sq. Ft.) AREA OF NEW & EXISTING ARRAY (Sq. Ft.) AREA OF ROOF(PLAN VIEW) (Sq. Ft.) TOTAL ROOF AREA COVERED BY ARRAY % 298.75 105.13 403.88 2607.39 15.49% LC LOAD CENTER (E)08 - SUNPOWER SPR-X20-250-BLK (250)MODULES 6/30/2024 STAMPED 07/06/2023 1028 S Maxine St 07/28/23 SHEET NAME SHEET NUMBER PV-3 PROJECT NAME TH I E N A N V A N 1 0 2 8 S M A X I N E S T , SA N T A A N A , C A , 9 2 7 0 4 U S A AP N # 1 0 8 5 9 1 8 7 UT I L I T Y : S C E AH J : C I T Y O F S A N T A A N A SHEET SIZE ANSI B 11" X 17" DEL MAR, CA 92014, USA REVDATE DESCRIPTION VERSION UR05/16/2023 INITIAL RELEASE DESIGN SUPPORT DAY OF INSTALL: CHAT.POWUR.COM ATTACHMENT DETAIL ATTACHMENT DETAIL SCALE: NTS1 ATTACHMENT DETAIL (ENLARGED VIEW) SCALE: NTS2 NOTE: ACTUAL ROOF CONDITIONS AND TRUSSES (OR SEAM) LOCATIONS MAY VARY. INSTALL PER MANUFACTURER(S) INSTALLATION GUIDELINES AND ENGINEERED SPANS FOR ATTACHMENTS (N) PV MODULES (N) SM LIGHT RAIL ROOF / DECK MEMBRANE UNIRAC SOLARHOOK AT1 2.5" MIN. EMBEDMENT (2) 1/4” STAINLESS STEEL LAG BOLT AND SS EPDM WASHER; 2.5” MINIMUM EMBEDMENT REQUIRED ENLARGE VIEW (N) PV MODULES (E) 2"X4" TRUSSE S @ 24" O.C ~4 " ~4 " (E) FLAT-TILE ROOF SS SERRATED FLANGE NUT 1. 2" 1 . 2 " 6/30/2024 STAMPED 07/06/2023 1028 S Maxine St 07/28/23 SHEET NAME SHEET NUMBER PV-5 PROJECT NAME TH I E N A N V A N 1 0 2 8 S M A X I N E S T , SA N T A A N A , C A , 9 2 7 0 4 U S A AP N # 1 0 8 5 9 1 8 7 UT I L I T Y : S C E AH J : C I T Y O F S A N T A A N A SHEET SIZE ANSI B 11" X 17" DEL MAR, CA 92014, USA REVDATE DESCRIPTION VERSION UR05/16/2023 INITIAL RELEASE DESIGN SUPPORT DAY OF INSTALL: CHAT.POWUR.COM WARNING LABELS & PLACARD WARNING DUAL POWER SOURCE SECOND SOURCE IS PHOTOVOLTAIC SYSTEM LABEL LOCATION: EMT/CONDUIT RACEWAYS (PER CODE: CEC690.31(D)(2) PHOTOVOLTAIC POWER SOURCE LABEL LOCATION: POINT OF INTERCONNECTION PRODUCTION METER CEC 705.12(B)(3)(3) & CEC 690.59) NOTES AND SPECIFICATIONS: ·SIGNS AND LABELS SHALL MEET THE REQUIREMENTS OF THE 2022 ARTICLE 110.21(B), UNLESS SPECIFIC INSTRUCTIONS ARE REQUIRED BY SECTION 690, OR IF REQUESTED BY THE LOCAL AHJ. ·SIGNS AND LABELS SHALL ADEQUATELY WARN OF HAZARDS USING EFFECTIVE WORDS, COLORS AND SYMBOLS. ·LABELS SHALL BE PERMANENTLY AFFIXED TO THE EQUIPMENT OR WIRING METHOD AND SHALL NOT BE HAND WRITTEN. ·LABEL SHALL BE OF SUFFICIENT DURABILITY TO WITHSTAND THE ENVIRONMENT INVOLVED. ·SIGNS AND LABELS SHALL COMPLY WITH ANSI Z535.4-2011, PRODUCT SAFETY SIGNS AND LABELS, UNLESS OTHERWISE SPECIFIED. ·DO NOT COVER EXISTING MANUFACTURER LABELS. ELECTRICAL SHOCK HAZARD WARNING TERMINALS ON LINE AND LOAD SIDES MAY BE ENERGIZED IN THE OPEN POSITION LABEL LOCATION: AC DISCONNECT(S), COMBINER PANEL (IF APPLICABLE). PER CODE(S): CEC 2022: CEC 706.15 (C)(4) & CEC 690.13(B) MAXIMUM AC OPERATING CURRENT: NOMINAL OPERATING AC VOLTAGE: 21.75 AMPS 240 VAC LABEL LOCATION: AC DISCONNECT(S), PHOTOVOLTAIC SYSTEM POINT OF INTERCONNECTION. PER CODE(S): CEC 2022: 690.54 SOLAR PV SYSTEM EQUIPPED WITH RAPID SHUTDOWN SOLAR ELECTRIC PV PANELS TURN RAPID SHUTDOWN SWITCH TO THE "OFF" POSITION TO SHUT DOWN PV SYSTEM AND REDUCE SHOCK HAZARD IN THE ARRAY. LABEL LOCATION: ON OR NO MORE THAT 1 M (3 FT) FROM THE SERVICE DISCONNECTING MEANS TO WHICH THE PV SYSTEMS ARE CONNECTED. PER CODE(S): 2022 CEC 690.56(C) 2022 CFC 1205.4.1 ! 4" 3" PHOTOVOLTAIC AC DISCONNECT MAIN PHOTOVOLTAIC SYSTEM DISCONNECT LABEL LOCATION: MAIN SERVICE DISCONNECT / UTILITY METER (PER CODE: CEC 690.13(B)) LABEL LOCATION: UTILITY SERVICE ENTRANCE/METER, INVERTER/DC DISCONNECT IF REQUIRED BY LOCAL AHJ, OR OTHER LOCATIONS AS REQUIRED BY LOCAL AHJ. PER CODE(S): CEC 2022: 690.56(C)(2) RAPID SHUTDOWN FOR SOLAR PV SYSTEM ! WARNING THE DISCONNECTION OF THE GROUNDED CONDUCTOR(S) MAY RESULT IN OVERVOLTAGE ON THE EQUIPMENT ! LABEL LOCATION: COMBINER PER CODE: CEC 690.31(E) POWER TO THIS BUILDING IS ALSO SUPPLIED FROM THE FOLLOWING SOURCES WITH DISCONNECTS LOCATED AS SHOWN 1 0 2 8 S M A X I N E S T (E)MAIN SERVICE PANEL (E)UTILITY METER CAUTION ! MULTIPLE SOURCES OF POWER THIS EQUIPMENT FED BY MULTIPLE SOURCES: TOTAL RATING OF ALL OVERCURRENT DEVICES EXCLUDING MAIN POWER SUPPLY SHALL NOT EXCEED AMPACITY OF BUSBAR WARNING LABEL LOCATION: POINTS OF CONNECTION/BREAKER CODE: CEC 705.12(b)(3)(2) WARNING POWER SOURCE OUTPUT CONNECTION DO NOT RELOCATE THIS OVERCURRENT DEVICE ! LABEL LOCATION: SERVICE PANEL IF SUM OF BREAKERS EXCEEDS PANEL RATING CEC 705.12 (b)(3)(2) ! LABEL LOCATION: MSP (PER CODE: CEC 705.12(D) & CEC 690.59 CAUTION PHOTOVOLTAIC SYSTEM CIRCUIT IS BACKFED ! (N)LOAD CENTER (N)COMBINER BOX (E)AC DISCONNECT (N)PV ARRAY (E)PV ARRAY 1028 S Maxine St 07/28/23 Rev: 7/15/2021 RESIDENTIAL PHOTOVOLTAIC CHECKLIST SOL-01 CBC 2019 Solar Photovoltaic (PV) Checklist for Detached SINGLE FAMILY RESIDENCES Only Instructions: The licensed contractor of record shall complete all sections, answer the ten questions and sign the certification section below. A copy of this form shall be attached to each of TWO sets of plans, of minimum 11” x 17” size. If answering NO to any of the questions, plan check shall be required. Project Address: Contractor Company Name: Contractor License Number: YES NO Are the following applicable to the proposed project? 1.Will the PV system layout provide the required three-foot wide clear access pathways per Section 605.11 of the California Fire Code, and is this shown on the roof plan? 2.Will the PV system be installed on a roof having only one roofing layer with no overlays? 3.Will the PV array be flush mounted to the existing roof so that the plane of the modules (panels) are parallel to the plane of the roof? 4.Will the PV system weigh maximum 4 pounds per square feet or less? 5.Will the PV system be installed where the modules do not overhang any roof edges (such as eaves, gabled ends, ridges and hips)? 6.Will the PV system be installed with a space of 2” minimum to 10” maximum between the underside of modules and the surface of the roof? 7.Will the PV system be installed without using any ballast system or counter-weight system? 8.Will the anchors be installed with a maximum horizontal anchor spacing of 6 feet and is this maximum horizontal spacing shown on the plans? 9.Will the minimum 5/16” lag screws be installed with a minimum of 2-1/2 inch embedment into roof rafters (with pre-drilled holes) and is this minimum embedment shown on the plans? 10. Are ALL the structural pages of the plans stamped and signed by a California licensed professional engineer? (including project specific site plan, PV layout, anchorage spacing, anchorage details and manufacturer’s PV support information.) I certify under penalty of perjury under the laws of the State of California that the above is true: Print Name: Signature: Phone Number: Date: Email Address: Planning & Building Agency Building Safety Division 20 Civic Center Plaza P.O. Box 1988 (M-19) Santa Ana, CA 92702 (714) 647-5800 www.santa-ana.org 1028 S Maxine St Santa Ana, CA 92704 POWUR PBC 1060243 TRAVIS CAMPBELL 866 467 6987 permitting@powur.com 7/20/23 1028 S Maxine St 07/28/23 POWUR PBC 2683 Via della Valle, Suite 321G Del Mar, CA 92014 (760) 658-9450 I ______________________, grant permission for the company Powur PBC and their subcontractors to install solar panels on my residence located at _______________________________. _________________________ Owner Printed Name _________________________ ______________ Owner Signature Date Signed Thienan Van 1028 S Maxine St ,Santa Ana, CA 92704 Thienan Van DocuSign Envelope ID: 913833D3-1AB0-405D-948C-1A940B307C41 7/19/2023 1028 S Maxine St 07/28/23 Certificate Of Completion Envelope Id: 913833D31AB0405D948C1A940B307C41 Status: Completed Subject: Complete with DocuSign: SantaAnaCity_HomeownerAuthorizationLetter-Thienan Van (286705).pdf Source Envelope: Document Pages: 1 Signatures: 1 Envelope Originator: Certificate Pages: 1 Initials: 0 Permitting Team AutoNav: Enabled EnvelopeId Stamping: Enabled Time Zone: (UTC-08:00) Pacific Time (US & Canada) 2683 Via De La Valle #G321 Del Mar, CA 92014 permitting@powur.com IP Address: 104.173.34.168 Record Tracking Status: Original 7/13/2023 4:17:06 PM Holder: Permitting Team permitting@powur.com Location: DocuSign Signer Events Signature Timestamp Thienan Van vanbuithienan@gmail.com Security Level: Email, Account Authentication (None) Signature Adoption: Drawn on Device Using IP Address: 172.56.120.243 Signed using mobile Sent: 7/13/2023 4:17:07 PM Viewed: 7/18/2023 11:05:51 PM Signed: 7/19/2023 6:05:32 AM Electronic Record and Signature Disclosure: Not Offered via DocuSign In Person Signer Events Signature Timestamp Editor Delivery Events Status Timestamp Agent Delivery Events Status Timestamp Intermediary Delivery Events Status Timestamp Certified Delivery Events Status Timestamp Carbon Copy Events Status Timestamp Travis Campbell travis.campbell@powur.com Security Level: Email, Account Authentication (None) Sent: 7/13/2023 4:17:06 PM Viewed: 7/13/2023 4:17:06 PM Signed: 7/13/2023 4:17:06 PM Electronic Record and Signature Disclosure: Not Offered via DocuSign Witness Events Signature Timestamp Notary Events Signature Timestamp Envelope Summary Events Status Timestamps Envelope Sent Hashed/Encrypted 7/13/2023 4:17:07 PM Certified Delivered Security Checked 7/18/2023 11:05:51 PM Signing Complete Security Checked 7/19/2023 6:05:32 AM Completed Security Checked 7/19/2023 6:05:32 AM Payment Events Status Timestamps 1028 S Maxine St 07/28/23 SHEET NAME SHEET NUMBER PV-6 PROJECT NAME TH I E N A N V A N 1 0 2 8 S M A X I N E S T , SA N T A A N A , C A , 9 2 7 0 4 U S A AP N # 1 0 8 5 9 1 8 7 UT I L I T Y : S C E AH J : C I T Y O F S A N T A A N A SHEET SIZE ANSI B 11" X 17" DEL MAR, CA 92014, USA REVDATE DESCRIPTION VERSION UR05/16/2023 INITIAL RELEASE DESIGN SUPPORT DAY OF INSTALL: CHAT.POWUR.COM SPEC SHEETS 1028 S Maxine St 07/28/23 SHEET NAME SHEET NUMBER PV-7 PROJECT NAME TH I E N A N V A N 1 0 2 8 S M A X I N E S T , SA N T A A N A , C A , 9 2 7 0 4 U S A AP N # 1 0 8 5 9 1 8 7 UT I L I T Y : S C E AH J : C I T Y O F S A N T A A N A SHEET SIZE ANSI B 11" X 17" DEL MAR, CA 92014, USA REVDATE DESCRIPTION VERSION UR05/16/2023 INITIAL RELEASE DESIGN SUPPORT DAY OF INSTALL: CHAT.POWUR.COM SPEC SHEETS 1028 S Maxine St 07/28/23 SHEET NAME SHEET NUMBER PV-8 PROJECT NAME TH I E N A N V A N 1 0 2 8 S M A X I N E S T , SA N T A A N A , C A , 9 2 7 0 4 U S A AP N # 1 0 8 5 9 1 8 7 UT I L I T Y : S C E AH J : C I T Y O F S A N T A A N A SHEET SIZE ANSI B 11" X 17" DEL MAR, CA 92014, USA REVDATE DESCRIPTION VERSION UR05/16/2023 INITIAL RELEASE DESIGN SUPPORT DAY OF INSTALL: CHAT.POWUR.COM SPEC SHEETS 1028 S Maxine St 07/28/23 SHEET NAME SHEET NUMBER PV-9 PROJECT NAME TH I E N A N V A N 1 0 2 8 S M A X I N E S T , SA N T A A N A , C A , 9 2 7 0 4 U S A AP N # 1 0 8 5 9 1 8 7 UT I L I T Y : S C E AH J : C I T Y O F S A N T A A N A SHEET SIZE ANSI B 11" X 17" DEL MAR, CA 92014, USA REVDATE DESCRIPTION VERSION UR05/16/2023 INITIAL RELEASE DESIGN SUPPORT DAY OF INSTALL: CHAT.POWUR.COM SPEC SHEETS 1028 S Maxine St 07/28/23 SHEET NAME SHEET NUMBER PV-10 PROJECT NAME TH I E N A N V A N 1 0 2 8 S M A X I N E S T , SA N T A A N A , C A , 9 2 7 0 4 U S A AP N # 1 0 8 5 9 1 8 7 UT I L I T Y : S C E AH J : C I T Y O F S A N T A A N A SHEET SIZE ANSI B 11" X 17" DEL MAR, CA 92014, USA REVDATE DESCRIPTION VERSION UR05/16/2023 INITIAL RELEASE DESIGN SUPPORT DAY OF INSTALL: CHAT.POWUR.COM SPEC SHEETS 1028 S Maxine St 07/28/23 SHEET NAME SHEET NUMBER PV-11 PROJECT NAME TH I E N A N V A N 1 0 2 8 S M A X I N E S T , SA N T A A N A , C A , 9 2 7 0 4 U S A AP N # 1 0 8 5 9 1 8 7 UT I L I T Y : S C E AH J : C I T Y O F S A N T A A N A SHEET SIZE ANSI B 11" X 17" DEL MAR, CA 92014, USA REVDATE DESCRIPTION VERSION UR05/16/2023 INITIAL RELEASE DESIGN SUPPORT DAY OF INSTALL: CHAT.POWUR.COM SPEC SHEETS 1028 S Maxine St 07/28/23 SHEET NAME SHEET NUMBER PV-12 PROJECT NAME TH I E N A N V A N 1 0 2 8 S M A X I N E S T , SA N T A A N A , C A , 9 2 7 0 4 U S A AP N # 1 0 8 5 9 1 8 7 UT I L I T Y : S C E AH J : C I T Y O F S A N T A A N A SHEET SIZE ANSI B 11" X 17" DEL MAR, CA 92014, USA REVDATE DESCRIPTION VERSION UR05/16/2023 INITIAL RELEASE DESIGN SUPPORT DAY OF INSTALL: CHAT.POWUR.COM SPEC SHEETS 1028 S Maxine St 07/28/23 SHEET NAME SHEET NUMBER PV-13 PROJECT NAME TH I E N A N V A N 1 0 2 8 S M A X I N E S T , SA N T A A N A , C A , 9 2 7 0 4 U S A AP N # 1 0 8 5 9 1 8 7 UT I L I T Y : S C E AH J : C I T Y O F S A N T A A N A SHEET SIZE ANSI B 11" X 17" DEL MAR, CA 92014, USA REVDATE DESCRIPTION VERSION UR05/16/2023 INITIAL RELEASE DESIGN SUPPORT DAY OF INSTALL: CHAT.POWUR.COM SPEC SHEETS 1028 S Maxine St 07/28/23 SHEET NAME SHEET NUMBER PV-14 PROJECT NAME TH I E N A N V A N 1 0 2 8 S M A X I N E S T , SA N T A A N A , C A , 9 2 7 0 4 U S A AP N # 1 0 8 5 9 1 8 7 UT I L I T Y : S C E AH J : C I T Y O F S A N T A A N A SHEET SIZE ANSI B 11" X 17" DEL MAR, CA 92014, USA REVDATE DESCRIPTION VERSION UR05/16/2023 INITIAL RELEASE DESIGN SUPPORT DAY OF INSTALL: CHAT.POWUR.COM SPEC SHEETS 1028 S Maxine St 07/28/23 Page 1 of 8 1760 Chicago Ave Ste J13, Riverside, CA 92507 (951) 405-1733 info@currentrenewableseng.com Signed on:07/05/2023 07/05/2023 Powur PBC 2683 Via De La Valle #321G,Del Mar,CA,92014 To Whom It May ConcernAttn.: Job:Thienan Van (286705) , , , Project Address:1028 Maxine Street Santa Ana CA 92704 The following calculations are for the structural engineering design of the photovoltaic panels and are valid only for the structural info referenced in the stamped plan set. I Allcertify that the roof structure has sufficient structural capacity for the applied PV loads. mounting equipment shall be designed and installed per manufacturer's approved installation specifications. Design Criteria Code: 2022 CBC,IBC 2021,IEBC 2021,ASCE 7-16 20 psfLive Load: mphUlt Wind Speed:95.0 Exposure Cat:C psfGround Snow:0.0 N/AMin Snow Roof: Current Renewables Engineering Inc. Professional Engineer info@currentrenewableseng.com 1028 S Maxine St 07/28/23 Page 2 of 8 1760 Chicago Ave Ste J13, Riverside, CA 92507 (951) 405-1733 info@currentrenewableseng.com Roof Properties: Roof 1 Roof Type:Tile Roof Pitch (deg):15 Mean Roof Height (ft):23.00 Attachment Trib Width (ft):3.25 Attachment Spacing (ft):4.00 Framing Type:Truss Framing Size:2x4 Framing OC Spacing (in):24.00 Section Thickness, b (in):1.50 Section Depth, d (in):3.50 Section Modulus, Sx (in ):3 3.062 Moment of Inertia, Ix (in ):4 5.359 Unsupported Span (ft):8.00 Upper Chord Length (ft):24.00 Deflection Limit D+L (in):4.800 Deflection Limit S or W (in):3.200 Framing Upgrade:No Sister Size:N/A Wood Species:DF Wood Fb (psi):900.00 Wood Fv (psi):180.00 Wood E (psi):1,600,000.00 C (Wind):D 1.60 C (Snow):D 1.15 C :LS 1.00 C = C = C = C :M t L i 1.00 C :F 1.50 C :fu 1.00 C :r 1.15 F'b Wind (psi):2,484.00 F'b Snow (psi):1,785.37 F'v Wind (psi):288.00 F'v Snow (psi):207.00 Moment Allowable Wind (lb-ft):633.94 Moment Allowable Snow (lb-ft):455.64 V Allowable Wind (lbs):1,008.00 V Allowable Snow (lbs):724.50 E' (psi): 1,600,000 1028 S Maxine St 07/28/23 Page 3 of 8 1760 Chicago Ave Ste J13, Riverside, CA 92507 (951) 405-1733 info@currentrenewableseng.com Load Calculations: Dead Load Calculations: Roof 1 Panel Dead Load (psf):3.00 Roofing Weight (psf):9.00 Decking Weight (psf):2.00 Framing Weight (psf):0.60 Misc. Additional Weight (psf):1.00 Existing Dead Load (psf):12.60 Total Dead Load (psf):15.60 Wind Load Calculations: Roof 1 Ultimate Wind Speed (mph):95.00 Directionality Factor, kd:0.85 Topographic Factor, kzt:1.00 Velocity Press Exp Factor, kz:0.93 Velocity Pressure, qz (psf):18.21 External Pressure Up, GCp :1 -2.00 External Pressure Up, GCp :2 -2.57 External Pressure Up, GCp :3 -3.06 External Pressure Down, GCp:0.46 Design Pressure Up, p (psf):1 -25.13 Design Pressure Up, p (psf):2 -32.28 Design Pressure Up, p (psf):3 -38.42 Design Pressure Down, p (psf):16.00 Snow Load Calculations: Roof 1 Ground Snow Load, pg (psf):0.00 Min Flat Snow, pf_min (psf):0.00 Min Sloped Snow, ps_min (psf):0.00 Snow Importance Factor, Ic:1.00 Exposure Factor, Ce:0.90 Thermal Factor, Ct:1.10 Flat Roof Snow, pf (psf):0.00 Slope Factor, Cs:1.00 Sloped Roof Snow, ps (psf):0.00 1028 S Maxine St 07/28/23 Page 4 of 8 1760 Chicago Ave Ste J13, Riverside, CA 92507 (951) 405-1733 info@currentrenewableseng.com Hardware Checks: Attachment Check: Roof 1 Attachment Type: Unirac Tile Hook (004AT1) Allowable Up Force (lbs): 218.00 Allowable Down Force (lbs): 218.00 Allowable Side Force (lbs): 120.00 Applied Uplift Force (lbs): -195.16 Uplift DCR: 0.895 Applied Down Force (lbs): 134.82 Down DCR: 0.618 Applied Lateral Force (lbs): 10.09 Lateral DCR: 0.084 1028 S Maxine St 07/28/23 Page 5 of 8 1760 Chicago Ave Ste J13, Riverside, CA 92507 (951) 405-1733 info@currentrenewableseng.com Roof Framing Checks: Force Checks LC1: D+S Roof 1 Applied Moment (lb-ft):199.7 Applied Shear (lbs):148.5 Allowable Moment (lb-ft):455.6 Allowable Shear (lbs):724.5 Moment DCR:0.438 Shear DCR:0.205 LC2: D+0.6W Roof 1 Applied Moment (lb-ft):322.5 Applied Shear (lbs):239.8 Allowable Moment (lb-ft):633.9 Allowable Shear (lbs):1,008.0 Moment DCR:0.509 Shear DCR:0.238 LC3: D+0.75(S+0.6W) Roof 1 Applied Moment (lb-ft):291.8 Applied Shear (lbs):217.0 Allowable Moment (lb-ft):633.9 Allowable Shear (lbs):1,008.0 Moment DCR:0.460 Shear DCR:0.215 LC4: 0.6D+0.6W Roof 1 Applied Moment (lb-ft):242.7 Applied Shear (lbs):180.4 Allowable Moment (lb-ft):633.9 Allowable Shear (lbs):1,008.0 Moment DCR:0.383 Shear DCR:0.179 1028 S Maxine St 07/28/23 Page 6 of 8 1760 Chicago Ave Ste J13, Riverside, CA 92507 (951) 405-1733 info@currentrenewableseng.com Deflection Checks (Service Level): LC1: D+L Roof 1 Deflection (in.):0.556 Deflection Limit (in.):4.800 Deflection DCR:0.116 LC2: S Roof 1 Deflection (in.):0.000 Deflection Limit (in.):3.200 Deflection DCR:0.000 LC3: W (Down) Roof 1 Deflection (in.):0.076 Deflection Limit (in.):3.200 Deflection DCR:0.024 LC4: W (Up) Roof 1 Deflection (in.):0.120 Deflection Limit (in.):3.200 Deflection DCR:0.037 1028 S Maxine St 07/28/23 Page 7 of 8 1760 Chicago Ave Ste J13, Riverside, CA 92507 (951) 405-1733 info@currentrenewableseng.com Seismic Check: Existing Weight: Wall Weight (psf):17.00 Tributary Wall Area (ft ): 2 3,060.00 Total Wall Weight (lbs):52,020.00 Roof Weight (psf):12.60 Roof Area (ft ):2 2,537.00 Total Roof Weight (lbs):31,970.16 Total Existing Weight (lbs):83,990.16 Additional PV Weight: PV Panel Weight (lbs):64.35 Number of Panels:23 Total Additional PV Weight (lbs):1,480.05 Weight Increase: (Existing W + Additional W) ÷ (Existing W) = 101.76% The increase in weight as a result of the solar system is less than 10% of the existing structure. Therefore, no further seismic analysis is required. 1028 S Maxine St 07/28/23 Page 8 of 8 1760 Chicago Ave Ste J13, Riverside, CA 92507 (951) 405-1733 info@currentrenewableseng.com Limits of Scope of Work and Liability: Existing structure is assumed to have been designed and constructed following appropriate codes at time of erection, and assumed to have appropriate permits. The calculations produced are only for the roof framing supporting the proposed PV installation referenced in the stamped planset and were completed according to generally recognized structural analysis standards and procedures, professional engineering and design experience, opinions and judgements. Existing deficiencies which are unknown or were not observable during time of inspection are not included in this scope of work. All PV modules, racking, and mounting equipment shall be designed and installed per manufacturer's approved installation specifications. The Engineer of Record and the engineering consulting firm assume no responsibility for misuse or improper installation. This analysis is not stamped for water leakage. Framing was determined based on information in provided plans and/or photos, along with engineering judgement. Prior to commencement of work, the contractor shall verify the framing sizes, spacings, and spans noted in the stamped plans, calculations, and cert letter (where applicable) and notify the Engineer of Record of any discrepancies prior to starting construction. Contractor shall also verify that there is no damaged framing that was not addressed in stamped plans, calculations, and cert letter (where applicable) and notify the Engineer of Record of any concerns prior to starting construction. 1028 S Maxine St 07/28/23 Page 1 of 2 1760 Chicago Ave Ste J13, Riverside, CA 92507 (951) 405-1733 info@currentrenewableseng.com Signed on:07/05/2023 07/05/2023 Powur PBC 2683 Via De La Valle #321G,Del Mar,CA, 92014 Structural Certification for Installation of Residential SolarSubject: Job:Thienan Van (286705) , , ,Project Address:1028 Maxine Street Santa Ana CA 92704 To Whom It May ConcernAttn.: Observation of the condition of the existing framing system was performed by an audit team of Powur PBC. After review of the field observation data, structural capacity calculations were performed in accordance with applicable building codes to determine adequacy of the existing roof framing supporting the proposed panel layout. Please see full Structural Calculations report for details regarding calculations performed and limits of scope of work and liability. The design criteria and structural adequacy are summarized below: Design Criteria Code: 2022 CBC,IBC 2021,IEBC 2021,ASCE 7-16 mphUlt Wind Speed:95.0 psfGround Snow:0.0 psfMin Snow Roof:0.0 Current Renewables Engineering Inc. Professional Engineer info@currentrenewableseng.com 1028 S Maxine St 07/28/23 Page 2 of 2 1760 Chicago Ave Ste J13, Riverside, CA 92507 (951) 405-1733 info@currentrenewableseng.com Summaries: : roofing supported by @ in. OC spacing. The roof is sloped atRoof 1 Tile 2x4 Truss 24 approximately degrees and has a max beam span of ft between supports. 15 8.0 Roof is adequate to support the imposed loads. Therefore, no structural upgrades are required.1028 S Maxine St 07/28/23