Loading...
HomeMy WebLinkAbout1210 E Avalon Ave Unit# 2- Solar - PlanPage RE V I S I O N S : Pr o j e c t N a m e 3. 5 2 0 k W ( D C ) / 3 . 2 0 2 k W ( C E C - A C ) PH O T O V O L T A I C S Y S T E M 12 1 0 E A V A L O N A V E U N I T 2 - AD U 12 1 0 E A V A L O N A V E U N I T 2 , SA N T A A N A , C A 9 2 7 0 5 AP N : 3 9 6 1 9 1 0 7 DA T E : 06 / 1 1 / 2 0 2 4 DR A W N B Y : RD Co n t r a c t o r s S i g n a t u r e : PR E M I E R B U I L D E R S & H A R D S C A P E I N C 88 3 2 L A G R A N D A V E GA R D E N G R O V E , C A 9 2 8 4 1 PH O N E : ( 7 1 4 ) 4 6 7 - 9 0 1 8 LI C E N S E : # 9 9 5 0 6 8 / B , C 5 3 R1 0 6 . 1 3 . 2 4 ( T Y ) CO V E R P A G E 1A OF 11 PHOTOVOLTAIC GENERAL NOTES · ALL MATERIALS, EQUIPMENT, INSTALLATION AND WORK PERFORMED SHALL BE IN ACCORDANCE WITH THE FOLLOWING CODES: - 2022 CBC / 2021 IBC - 2022 CRC / 2021 IRC - 2022 CEC / 2020 NEC - 2022 CMC / 2021 IMC - 2022 CPC / 2021 IPC - 2022 CFC / 2021 IFC - 2022 BUILDING ENERGY EFFICIENCY STANDARDS · ALL EQUIPMENT SHALL BE LISTED AND LABELED BY A RECOGNIZED ELECTRICAL TESTING LABORATORY AND L.A. TEST LAB. EQUIPMENT INSTALLED SHALL BE PER ITS LISTING REQUIREMENTS AND THE MANUFACTURER'S INSTRUCTIONS. NEC 110.2, 110.3, 690.4(B), 690.12(D). · ALL OUTDOOR EQUIPMENT SHALL BE NEMA 3R RATED, INCLUDING ALL ROOF MOUNTED TRANSITION BOXES AND SWITCHES. · ALL EQUIPMENT SHALL BE PROPERLY GROUNDED AND BONDED IN ACCORDANCE WITH NEC ARTICLE 250. · PV SYSTEM DC CIRCUIT AND INVERTER OUTPUT CONDUCTORS AND EQUIPMENT SHALL BE PROTECTED AGAINST OVERCURRENT. CIRCUITS SIZED IN ACCORDANCE WITH 690.8(A)(2) ARE REQUIRED TO BE PROTECTED AGAINST OVERCURRENT PROTECTIVE DEVICES. EACH CIRCUIT SHALL BE PROTECTED FROM OVERCURRENT IN ACCORDANCE WITH 690.9(A)(1), (A)(2), OR (A)(3). [NEC 690.9(A)] · DISCONNECTING MEANS OF THE PV SYSTEM (INCLUDING RAPID SHUTDOWN INITIATION) SHALL BE LOCATED IN A READILY ACCESSIBLE LOCATION WITHIN THE EQUIPMENT, WITHIN SIGHT OF THE EQUIPMENT, OR REMOTELY WHERE THE EQUIPMENT DISCONNECTING MEANS. [NEC 690.13(A), 690.15] · RAPID SHUTDOWN EQUIPMENT TO COMPLY WITH NEC 690.12. · ENERGY STORAGE SYSTEM DISCONNECTING MEANS SHALL BE PROVIDED FOR ALL UNGROUNDED CONDUCTORS AND SHALL BE READILY ACCESSIBLE AND WITHIN LINE OF SIGHT; WHERE PARTITIONED, AN ADDITIONAL DISCONNECT SHALL BE PROVIDED WITHIN SIGHT OF THE ESS COMPONENT. OVERCURRENT PROTECTION SHALL BE PROVIDED. [706.15, 706.31] · UPON LOSS OF PRIMARY SOURCE, THE OUTPUT OF ELECTRIC POWER PRODUCTION EQUIPMENT SHALL BE AUTOMATICALLY DISCONNECTED FROM ALL UNGROUNDED CONDUCTORS OF THE INTERCONNECTED SYSTEMS. THE ELECTRIC POWER PRODUCTION EQUIPMENT SHALL NOT BE RECONNCETED UNTIL ALL PHASES OF THE PRIMARY SOURCE IS RESTORED. [NEC 705.40] · ALL CONDUCTORS IN EXPOSED OUTDOOR LOCATIONS SHALL BE LISTED AND IDENTIFIED FOR USE IN DIRECT SUNLIGHT AND FOR THE APPLICATION. [NEC 690.31(C) THROUGH (F), 310.10(D)] · EXPOSED CONDUCTORS WITHIN THE PV ARRAY SHALL BE PV WIRE/CABLE, OR TYPE USE-2, OR TYPE RHW-2 (UL 4703 & 854 LISTED) [NEC 690.31(C)(1)] · FINE-STRANDED CABLE CONNECTIONS MUST BE MADE IN LUGS AND TERMINALS TO ENSURE A THOROUGHLY GOOD CONNECTION WITHOUT DAMAGING THE CONDUCTORS. [NEC 110.14(A)] · FLEXIBLE, FINE-STRANDED CABLES SHALL BE TERMINATED ONLY WITH TERMINALS, LUGS, DEVICES, OR CONNECTORS THAT ARE IDENTIFIED AND LISTED FOR SUCH USE. [NEC 690.31(C)(5), 110.14] · ALL PV CIRCUIT CONDUCTORS SHALL BE MARKED ON EACH END AND GROUPED FOR UNIQUE IDENTIFICATION. [NEC 690.31(B)] · ALL EXTERIOR CONDUIT, FITTINGS, AND BOXES SHALL BE RAIN TIGHT AND APPROVED FOR USE IN WET LOCATIONS. (NEC 314.15) · ALL GROUNDED, (NEUTRAL), CONDUCTORS' INSULATION SHALL BE SOLID WHITE, GRAY, OR WITH 3-WHITE STRIPES. [NEC 200.6, 200.7, 400.22]; ALL GROUNDING CONDUCTORS SHALL BE OF BARE WIRE WITHOUT COVERING, OR WITH INSULATION OF GREEN OR GREEN WITH YELLOW STRIPES, NEC 250.119 & 400.23. THE COLOR OF UNGROUNDED CONDUCTORS SHALL BE OTHER THAN FOR GROUNDED, (NEUTRAL), AND GROUNDING CONDUCTORS. [NEC 310.110(C)] · MAXIMUM CONDUCTOR LENGTH BETWEEN SUPPLY SIDE CONNECTION AND OVERCURRENT PROTECTION IS 10FT IN DWELLING UNITS AND 16.5FT IN OTHER THAN DWELLING UNITS FROM THE POINT OF CONNECTION TO THE SERVICE. [NEC 705.11(C)] · CONNECTIONS ON THE LOAD SIDE OF THE SERVICE DISCONNECTING MEANS OF THE OTHER SOURCE(S) AT ANY DISTRIBUTION EQUIPMENT ON THE PREMISES SHALL BE IN ACCORDANCE WITH NEC 705.12(B). · DC WIRING INSIDE A BUILDING MUST BE IN METAL RACEWAYS, METAL-CLAD CABLE, OR METAL ENCLOSURES. [NEC 690.31(D)] · METALLIC TYPE RACEWAYS, CONDUITS, ENCLOSURES, AND CABLE SHEATHS CONTAINING CIRCUITS OVER 250-VOLTS TO GROUND MUST BE BONDED IN ACCORDANCE WITH NEC 250.97. · CONNECTORS SHALL BE OF LATCHING OR LOCKING TYPE. CONNECTORS THAT ARE READILY ACCESSIBLE AND OPERATING AT OVER 30-VOLTS SHALL REQUIRE A TOOL TO OPEN AND MARKED "DO NOT DISCONNECT UNDER LOAD" OR "NOT FOR CURRENT INTERRUPTING." [NEC 690.33(C) & (D)(2)] · EQUIPMENT GROUNDING CONDUCTOR (EGC) SMALLER THAN #6-AWG SHALL BE PROTECTED FROM PHYSICAL DAMAGE BY AN IDENTIFIED RACEWAY OR CABLE ARMOR, UNLESS INSTALLED WITHIN HOLLOW SPACES OF THE FRAMING MEMBERS OF BUILDINGS OR STRUCTURES AND WHERE NOT SUBJECT TO PHYSICAL DAMAGE. [NEC 250.120(C)] · THE INTERCONNECTION POINT SHALL BE ON THE SUPPLY SIDE OF ALL GROUND-FAULT PROTECTION EQUIPMENT. [NEC 705.32] · CABLES/WIRES THAT ARE SUBJECT TO PHYSICAL DAMAGE, SUCH AS THOSE NOT LOCATED UNDER THE MODULES, MUST BE PROTECTED. [NEC 300.4] · FOR ELECTRICAL SERVICE REPLACEMENTS, BONDING TO THE METAL PIPES OF NATURAL GAS, HOT WATER, AND COLD WATER MUST BE PROVIDED. [NEC 250.104] · GROUNDING ROD ELECTRODES SHALL BE INSTALLED 8-FT MINIMUM IN CONTACT WITH SOIL AND MINIMUM 5/8-INCH DIAMETER. [NEC 250.52(A)(5), 250.53(G)] · THE MARKINGS, "PHOTOVOLTAIC POWER SOURCE", FOR DC RACEWAYS AND CABLE ASSEMBLIES MUST BE NO MORE THAN 10-FT O.C.; AND IS SEPARATED BY ENCLOSURES, WALLS, PARTITIONS, CEILINGS, FLOORS, OR BENDS ABOVE OR BELOW PENETRATIONS. [NEC 690.31(D)(2)] · WORKING CLEARANCES TO BE PROVIDED AT NEW AND EXISTING ELECTRICAL EQUIPMENT. [NEC 110.26] · POWER PRODUCTION SYSTEMS, AND ALL ASSOCIATED WIRING AND INTERCONNECTIONS OPERATING IN PARALLEL WITH A PRIMARY POWER SOURCE SHALL BE PERFORMED ONLY BY QUALIFIED PERSONS. [NEC 690.4(C), 705.8] · LABELS SHALL BE REFLECTIVE, AND ALL LETTERS SHALL BE CAPITALIZED AND SHALL BE A MINIMUM HEIGHT OF 3/8" IN WHITE ON A RED BACKGROUND. [NEC 690.31(G)(4)] · IDENTIFICATION OF POWER SOURCE RAPID SHUTDOWN AND LABELING SHALL BE IN ACCORDANCE WITH NEC 690.56(C). · SMOKE ALARMS AND CARBON MONOXIDE ALARMS ARE REQUIRED TO BE RETROFITTED ONTO THE EXISTING DWELLING AS PER THE 2019 CRC. THESE SMOKE ALARMS ARE REQUIRED TO BE IN ALL BEDROOMS, OUTSIDE EACH BEDROOM, AND AT LEAST ONE ON EACH FLOOR OF THE HOUSE. CARBON MONOXIDE ALARMS ARE REQUIRED TO BE RETROFITTED OUTSIDE EACH BEDROOM AND AT LEAST ONE ON EACH FLOOR OF THE HOUSE. (CRC 314,315) · SMOKE ALARMS AND CARBON MONOXIDE ALARMS ARE REQUIRED PER CRC SECTIONS 314 AND 315 TO BE VERIFIED AND INSPECTED BY THE INSPECTOR IN THE FIELD. · A LADDER MUST BE PROVIDED FOR INSPECTIONS IN ACCORDANCE WITH Cal-OSHA REGULATIONS, SECURED AND EXTENDING 3-FT ABOVE THE ROOF. · ALL OF THE REQUIRED MARKINGS, SIGNS, AND LABELS MUST BE INSTALLED ON ALL EQUIPMENT PRIOR TO ANY INSPECTIONS. PHOTOVOLTAIC MODULES AND PANEL SYSTEMS INSTALLED ON OR INTEGRAL WITH BUILDINGS, OR TO BE FREESTANDING (NOT ATTACHED TO BUILDINGS) SHALL BE TESTED, LISTED, AND IDENTIFIED WITH A FIRE CLASSIFICATION (CLASS C MINIMUM) IN ACCORDANCE WITH UL1703. WHERE CLASS A OR B ROOFING IS REQUIRED, THE PV SOLAR SYSTEM (PV PANEL & RACK) SHALL HAVE THE SAME CLASS/TYPE RATING OR BETTER. COUNTY ELECTRONIC STAMP Bldg# 101119921 Elec# 20183310 The scope of the plans is for the installation of the solar photovoltaic system only and the approval is subject to compliance with all applicable city and state codes and regulations regarding construction. The approval of the plans does not constitute any certification of the accuracy, completeness, or building permit status of the existing buildings and structures as shown. 1210 E Avalon Ave Unit# 2- Solar7/11/2024 CONTRACTOR INFORMATION CONTRACTOR:PREMIER BUILDERS & HARDSCAPE INC ADDRESS:8832 LA GRAND AVE, GARDEN GROVE, CA 92841 PHONE:(714) 467-9018 LICENSE #/TYPE:#995068/B,C53 TABLE OF CONTENTS PAGE 1 COVER PAGE PAGE 2 SITE PLAN PAGE 3 PLOT PLAN PAGE 4 SINGLE LINE DIAGRAM PAGE 5 STRUCTURAL ATTACHMENT DETAIL PAGE 6 LABELS AND WARNING SIGNAGE PAGE 7 PV MODULE SPEC SHEET PAGE 8 INVERTER SPEC SHEET PAGE 9 UL LISTING PAGE 10 GROUNDING PAGE 11 RAPID SHUTDOWN SYSTEM INFORMATION SIZE(kw):3.520 MODULE TYPE:8 URE SOLAR FAM440E8G-BB INVERTERS(S):8 ENPHASE IQ8PLUS-72-2-US INVERTER TYPE:MICRO-INVERTER SCOPE OF WORK: INSTALL (8) ROOF MOUNTED PV SOLAR MODULES, (8) ENPHASE IQ8PLUS-72-2-US INVERTER(S)(240V). (DC) / 3.202 (CEC-AC) Page RE V I S I O N S : Pr o j e c t N a m e 3. 5 2 0 k W ( D C ) / 3. 2 0 2 k W ( C E C - A C ) PH O T O V O L T A I C S Y S T E M 12 1 0 E A V A L O N A V E U N I T 2 - AD U 12 1 0 E A V A L O N A V E U N I T 2 , SA N T A A N A , CA 92 7 0 5 AP N : 39 6 1 9 1 0 7 DA T E : 06 / 1 1 / 2 0 2 4 DR A W N B Y : RD Co n t r a c t o r s S i g n a t u r e : PR E M I E R B U I L D E R S & H A R D S C A P E I N C 88 3 2 L A G R A N D A V E GA R D E N G R O V E , C A 9 2 8 4 1 PH O N E : (7 1 4 ) 4 6 7 - 9 0 1 8 LI C E N S E : #9 9 5 0 6 8 / B , C 5 3 R1 0 6 . 1 3 . 2 4 ( T Y ) CO V E R P A G E 1B OF 11 PROJECT INFORMATION NAME:1210 E AVALON AVE UNIT 2 - ADU ADDRESS:1210 E AVALON AVE UNIT 2, SANTA ANA, CA 92705 APN:39619107 JURISDICTION:SANTA ANA OCCUPANCY GROUP: R3 CONSTRUCTION TYPE: V-B COUNTY ELECTRONIC STAMP 1210 E Avalon Ave Unit# 2- Solar7/11/2024 Page RE V I S I O N S : Pr o j e c t N a m e 3. 5 2 0 k W ( D C ) / 3. 2 0 2 k W ( C E C - A C ) PH O T O V O L T A I C S Y S T E M 12 1 0 E A V A L O N A V E U N I T 2 - AD U 12 1 0 E A V A L O N A V E U N I T 2 , SA N T A A N A , CA 92 7 0 5 AP N : 39 6 1 9 1 0 7 DA T E : 06 / 1 1 / 2 0 2 4 DR A W N B Y : RD Co n t r a c t o r s S i g n a t u r e : PR E M I E R B U I L D E R S & H A R D S C A P E I N C 88 3 2 L A G R A N D A V E GA R D E N G R O V E , C A 9 2 8 4 1 PH O N E : (7 1 4 ) 4 6 7 - 9 0 1 8 LI C E N S E : #9 9 5 0 6 8 / B , C 5 3 R1 0 6 . 1 3 . 2 4 ( T Y ) CO V E R P A G E 1C OF 11 NOTE: 1. IN CASE OF EMERGENCY, CALL ______________________ AT WORK PHONE #___________________ OR HOME PHONE#__________________. 2. SEDIMENT FROM AREAS DISTURBED BY CONSTRUCTION SHALL BE RETAINED ON SITE USING STRUCTURAL CONTROLS TO THE MAXIMUM EXTENT PRACTICABLE. 3. STOCKPILES OF SOIL SHALL BE PROPERLY CONTAINED TO MINIMIZE SEDIMENT TRANSPORT FROM THE SITE TO STREETS, DRAINAGE FACILITIES OR ADJACENT PROPERTIES VIA RUNOFF, VEHICLE TACKING, OR WIND. 4. APPROPRIATE BMP'S FOR CONSTRUCTION-RELATED MATERIALS, WASTES, SPILLS SHALL BE IMPLEMENTED TO MINIMIZE TRANSPORT FROM THE SITE TO STREETS, DRAINAGE FACILITIES, OR ADJOINING PROPERTIES BY WIND OR RUNOFF. 5. RUNOFF FROM EQUIPMENT AND VEHICLE WASHING SHALL BE CONTAINED AT CONSTRUCTION SITES UNLESS TREATED TO REDUCE OR REMOVE SEDIMENT AND OTHER POLLUTANTS. 6. ALL CONSTRUCTION CONTRACTOR AND SUBCONTRACTOR PERSONNEL ARE TO BE MADE AWARE OR THE REQUIRED BEST MANAGEMENT PRACTICES AND GOOD HOUSEKEEPING MEASURES FOR THE PROJECT SITE AND ANY ASSOCIATED CONSTRUCTION STAGING AREAS. 7. AT THE END OF EACH DAY OF CONSTRUCTION ACTIVITY ALL CONSTRUCTION DEBRIS AND WASTE MATERIALS SHALL BE COLLECTED AND PROPERLY DISPOSED IN TRASH OR RECYCLE BINS. 8. CONSTRUCTION SITES SHALL BE MAINTAINED IN SUCH A CONDITION THAT AN ANTICIPATED STORM DOES NOT CARRY WASTES OR POLLUTANTS OFF THE SITE. DISCHARGES OF MATERIAL OTHER THAN STORMWATER ONLY WHEN NECESSARY FOR PERFORMANCE AND COMPLETION OF CONSTRUCTION PRACTICES AND WHERE THEY DO NOT: CAUSE OR CONTRIBUTE TO A VIOLATION OF ANY WATER QUALITY STANDARD; CAUSE OR THREATEN TO CAUSE POLLUTION, CONTAMINATION, OR NUISANCE; OR CONTAIN A HAZARDOUS SUBSTANCE IN A QUANTITY REPORTABLE UNDER FEDERAL REGULATIONS 40 CFR PARTS 117 AND 302. 9. POTENTIAL POLLUTANTS INCLUDE BUT ARE NOT LIMITED TO: SOLID OR LIQUID CHEMICAL SPILLS; WASTES FROM PAINTS, STAINS, SEALANTS, GLUES, LIMES, PESTICIDES, HERBICIDES, WOOD PRESERVATIVES AND SOLVENTS; ASBESTOS FIBERS, PAINT FLAKES OR STUCCO FRAGMENTS; FUELS, OILS, LUBRICANTS, AND HYDRAULIC, RADIATOR OR BATTERY FLUIDS; FERTILIZERS, VEHICLE/EQUIPMENT WASH WATER AND CONCRETE WASH WATER; CONCRETE, DETERGENT OR FLOATABLE WASTES; WASTES FROM ANY ENGINE/EQUIPMENT STEAM CLEANING OR CHEMICAL DEGREASING AND SUPERCHLORINATED POTABLE WATER LINE FLUSHING. DURING CONSTRUCTION, PERMITTEE SHALL DISPOSE OF SUCH MATERIALS IN A SPECIFIED AND CONTROLLED TEMPORARY AREA ON-SITE, PHYSICALLY SEPARATED FROM POTENTIAL STORMWATER RUNOFF, WITH ULTIMATE DISPOSAL IN ACCORDANCE WITH LOCAL, STATE AND FEDERAL REQUIREMENTS. 10. DEWATERING OF CONTAMINATED GROUNDWATER, OR DISCHARGING CONTAMINATED SOILS VIA SURFACE EROSION IS PROHIBITED. DEWATERING OF NON-CONTAMINATED GROUNDWATER REQUIRES A NATIONAL POLLUTANT DISCHARGE ELIMINATION SYSTEM PERMIT FROM THE RESPECTIVE STATE REGIONAL WATER QUALITY CONTROL BOARD. 11. GRADED AREAS ON THE PERMITTED AREA PERIMETER MUST DRAIN AWAY FROM THE FACE OF SLOPES AT THE CONCLUSION OF EACH WORKING DAY. DRAINAGE IS TO BE DIRECTED TOWARD DESILTING FACILITIES. 12. THE PERMITTEE AND CONTRACTOR SHALL BE RESPONSIBLE AND SHALL TAKE NECESSARY PRECAUTIONS TO PREVENT PUBLIC TRESPASS ONTO AREAS WHERE IMPOUNDED WATER CREATES A HAZARDOUS CONDITION. 13. THE PERMITTEE AND CONTRACTOR SHALL INSPECT THE EROSION CONTROL WORK AND INSURE THAT THE WORK IS IN ACCORDANCE WITH THE APPROVED PLANS. 14. THE PERMITTEE SHALL NOTIFY ALL GENERAL CONTRACTORS, SUBCONTRACTORS, MATERIAL SUPPLIERS, LESSEES, AND PROPERTY OWNERS: THAT DUMPING OF CHEMICALS INTO THE STORM DRAIN SYSTEM OR THE WATERSHED IS PROHIBITED. 15. EQUIPMENT AND WORKERS FOR EMERGENCY WORK SHALL BE MADE AVAILABLE AT ALL TIMES DURING THE RAINY SEASON. NECESSARY MATERIALS SHALL BE AVAILABLE ON SITE AND STOCKPILED AT CONVENIENT LOCATIONS TO FACILITATE RAPID CONSTRUCTION OF TEMPORARY DEVICES WHEN RAIN IS IMMINENT. 16. ALL REMOVABLE EROSION PROTECTIVE DEVICES SHALL BE IN PLACE AT THE END OF EACH WORKING DAY WHEN THE 5-DAY RAIN PROBABILITY FORECAST EXCEEDS 40%. 17. SEDIMENTS FROM AREAS DISTURBED BY CONSTRUCTION SHALL BE RETAINED ON SITE USING AN EFFECTIVE COMBINATION OF EROSION AND SEDIMENT CONTROLS TO THE MAXIMUM EXTENT PRACTICABLE, AND STOCKPILES OF SOIL SHALL BE PROPERLY CONTAINED TO MINIMIZE SEDIMENT TRANSPORT FROM THE SITE TO STREETS, DRAINAGE FACILITIES OR ADJACENT PROPERTIES VIA RUNOFF, VEHICLE TRACKING, OR WIND. 18. APPROPRIATE BMPS FOR CONSTRUCTION-RELATED MATERIALS, WASTES, SPILLS OR RESIDUES SHALL BE IMPLEMENTED AND RETAINED ON SITE TO MINIMIZE TRANSPORT FROM THE SITE TO STREETS, DRAINAGE FACILITIES, OR ADJOINING PROPERTY BY WIND OR RUNOFF. COUNTY ELECTRONIC STAMP 1210 E Avalon Ave Unit# 2- Solar7/11/2024 Page RE V I S I O N S : Pr o j e c t N a m e 3. 5 2 0 k W ( D C ) / 3. 2 0 2 k W ( C E C - A C ) PH O T O V O L T A I C S Y S T E M 12 1 0 E A V A L O N A V E U N I T 2 - AD U 12 1 0 E A V A L O N A V E U N I T 2 , SA N T A A N A , CA 92 7 0 5 AP N : 39 6 1 9 1 0 7 DA T E : 06 / 1 1 / 2 0 2 4 DR A W N B Y : RD Co n t r a c t o r s S i g n a t u r e : PR E M I E R B U I L D E R S & H A R D S C A P E I N C 88 3 2 L A G R A N D A V E GA R D E N G R O V E , C A 9 2 8 4 1 PH O N E : (7 1 4 ) 4 6 7 - 9 0 1 8 LI C E N S E : #9 9 5 0 6 8 / B , C 5 3 R1 0 6 . 1 3 . 2 4 ( T Y ) SI T E P L A N 02 OF 11 MSP A/C D.PVLC SP comp shingle roofing material ROOF FRAMING 2"X6" ROOF RAFTER @ 24" O.C Ridge 24" EXTERIOR WALL load bearing wall INTERIOR WALL load bearing wall STRUT PURLIN CELLING JOIST 6'-0" MAX SPAN ROOF SECTION PLAN SCALE: NTS N S EW Scale: 1/8" = 1'-0" (For 24x36 Print) COUNTY ELECTRONIC STAMP 1210 E AVALON AVE UNIT 2 (E) DRIVEWAY FRONT OF RESIDENCE MAIN RESIDENCE REAR OF RESIDENCE PR O P E R T Y L I N E PR O P E R T Y L I N E PROPERTY LINE (E) ADU 10' 17'-2"14'-8" 113'-5" (E) 200A SUB PANEL 120/240VAC SINGLE PHASE (E) 300A MAIN SERVICE PANEL 120/240VAC SINGLE PHASE 1210 E Avalon Ave Unit# 2- Solar7/11/2024 Page RE V I S I O N S : Pr o j e c t N a m e 3. 5 2 0 k W ( D C ) / 3. 2 0 2 k W ( C E C - A C ) PH O T O V O L T A I C S Y S T E M 12 1 0 E A V A L O N A V E U N I T 2 - AD U 12 1 0 E A V A L O N A V E U N I T 2 , SA N T A A N A , CA 92 7 0 5 AP N : 39 6 1 9 1 0 7 DA T E : 06 / 1 1 / 2 0 2 4 DR A W N B Y : RD Co n t r a c t o r s S i g n a t u r e : PR E M I E R B U I L D E R S & H A R D S C A P E I N C 88 3 2 L A G R A N D A V E GA R D E N G R O V E , C A 9 2 8 4 1 PH O N E : (7 1 4 ) 4 6 7 - 9 0 1 8 LI C E N S E : #9 9 5 0 6 8 / B , C 5 3 R1 0 6 . 1 3 . 2 4 ( T Y ) PL O T P L A N BUILDING SPECIFICATIONS TYPE:ADU STORIES:1 BUILDING HEIGHT(FT.):12 BUILDING(SQ.FT):800 ROOF SLOPES(°):4/12 ROOF FRAME MEMBER:2X6 RAFTER O.C. SPACING(IN.):24 MAX SPAN:6'-0" IN BETWEEN SUPPORTS MIN LAG BOLT EMBEDMENT(IN.):2-1/2 MOUNTING AND STANDOFF SPECIFICATIONS ROOFING MATERIAL:SINGLE LAYER COMP RACKING SYSTEM:IRONRIDGE STANDOFF DISTANCE(IN.):48 MOUNTING TYPE:FLUSH MOUNT TILT LEG HEIGHT (IN.):N/A HEIGHT OF PV MODULE ABOVE ROOF SURFACE:3" TO 5" MAX CANTILEVER (IN.):24 SYSTEM SPECIFICATIONS SIZE(kW):3.520 MODULE:(8) URE SOLAR FAM440E8G-BB INVERTER(S):(8) ENPHASE IQ8PLUS-72-2-US INVERTER TYPE:MICRO-INVERTER STRING SCHEDULE:1 CIRCUIT(S) OF 8 MODULES SYSTEM WEIGHT(LBS):470.32 ARRAY AREA(SQ.FT):190.23 ARRAY AZIMUTH(°):180 LBS/SQ.FT:2.47 03 OF 11 ROOF MOUNTED NOTES: ADDITIONAL BUILDING DATA TOTAL ARRAY AREA (SQ. FT.):190.23 TOTAL PLAN VIEW ROOF AREA (SQ. FT.):800 OCCUPYING PV PERCENTAGE:23.78% SPRINKLER SYSTEM INSTALLED (IFC 903.3.1.3)NO - SOLAR PHOTOVOLTAIC SYSTEM TO BE INSTALLED ON RESIDENTIAL STRUCTURE (GROUP R3 BUILDINGS). -THIS SYSTEM WILL NOT BE INTERCONNECTED UNTIL APPROVAL FROM THE LOCAL JURISDICTION AND THE UTILITY IS OBTAINED. -A 36-INCH WIDE PATHWAY SHALL BE PROVIDED TO THE EMERGENCY ESCAPE AND RESCUE OPENING(S). -IF THE EXISTING MAIN SERVICE PANEL DOES NOT HAVE A VERIFIABLE GROUNDING ELECTRODE, IT IS THE CONTRACTOR'S RESPONSIBILITY TO INSTALL A SUPPLEMENTAL GROUNDING ELECTRODE. R324.6.1 Pathways R324.6.2 Setback at ridge R324.6.2.1 Alternative setback at ridge Exceptions: 1. These requirements shall not apply to structures designed and constructed in accordance with the International Residential Code. 2. These requirements shall not apply to roofs with slopes of 2 units vertical in 12 units horizontal or less. ROOF ACCESS POINTS PER 2022 CRC, R324 (IFC 1204) MSP A/C D.PVLC JB N S EW Scale: 1/4" = 1'-0" (For 24x36 Print) COUNTY ELECTRONIC STAMP 3FT WIDTH FIRE PATHWAY NEMA 3R JUNCTION BOX (N) ENPHASE AC COMBINER BOX 240VAC, NEMA 3R (N) 30A AC DISCONNECT 2P - NON FUSIBLE (E) 300A MAIN SERVICE PANEL 120/240VAC SINGLE PHASE (N) SUPPORT RAILS (TYP.) (E) ROOF FRAMING CENTERLINE (N) TYP. ATTACHMENT POINT (16) IN TOTAL3' 3' 3' ROOF ACCESS POINT (STREET-SIDE) 4'2' ROMEX RUN IN-ATTIC 1210 E Avalon Ave Unit# 2- Solar7/11/2024 Page RE V I S I O N S : Pr o j e c t N a m e 3. 5 2 0 k W ( D C ) / 3. 2 0 2 k W ( C E C - A C ) PH O T O V O L T A I C S Y S T E M 12 1 0 E A V A L O N A V E U N I T 2 - AD U 12 1 0 E A V A L O N A V E U N I T 2 , SA N T A A N A , CA 92 7 0 5 AP N : 39 6 1 9 1 0 7 DA T E : 06 / 1 1 / 2 0 2 4 DR A W N B Y : RD Co n t r a c t o r s S i g n a t u r e : PR E M I E R B U I L D E R S & H A R D S C A P E I N C 88 3 2 L A G R A N D A V E GA R D E N G R O V E , C A 9 2 8 4 1 PH O N E : (7 1 4 ) 4 6 7 - 9 0 1 8 LI C E N S E : #9 9 5 0 6 8 / B , C 5 3 R1 0 6 . 1 3 . 2 4 ( T Y ) ST R U C T U R A L AT T A C H M E N T 05 OF 11 pv module comp shingle roofing material roof framing comp shingle roofing material flashing roof framing l-foot (1) 5/16" x 3" lag screw 2-1/2" min. embedment 3" to 5" pv modul e rail COUNTY ELECTRONIC STAMP 1210 E Avalon Ave Unit# 2- Solar7/11/2024 Page RE V I S I O N S : Pr o j e c t N a m e 3. 5 2 0 k W ( D C ) / 3. 2 0 2 k W ( C E C - A C ) PH O T O V O L T A I C S Y S T E M 12 1 0 E A V A L O N A V E U N I T 2 - AD U 12 1 0 E A V A L O N A V E U N I T 2 , SA N T A A N A , CA 92 7 0 5 AP N : 39 6 1 9 1 0 7 DA T E : 06 / 1 1 / 2 0 2 4 DR A W N B Y : RD Co n t r a c t o r s S i g n a t u r e : PR E M I E R B U I L D E R S & H A R D S C A P E I N C 88 3 2 L A G R A N D A V E GA R D E N G R O V E , C A 9 2 8 4 1 PH O N E : (7 1 4 ) 4 6 7 - 9 0 1 8 LI C E N S E : #9 9 5 0 6 8 / B , C 5 3 R1 0 6 . 1 3 . 2 4 ( T Y ) SI N G L E L I N E DI A G R A M INVERTER VALUES: BRAND AND MODEL: ENPHASE IQ8PLUS-72-2-US INVERTER TYPE:MICRO-INVERTER MAX INPUT VOLTAGE (V):60 MAX INPUT CURRENT (A):15 NOMINAL OUTPUT VOLTAGE (V):240 MAX CONT. OUTPUT CURRENT (A):1.21 INVERTER OCPD (A):15 MAX POWER AT 25ºC (W):290 AMBIENT TEMPERATURE ºF:-40 PV MODULE RATINGS BRAND AND MODEL: URE SOLAR FAM440E8G-BB MAX POWER [Pmax] (w):440 MAX POWER-POINT VOLTAGE [Vmp] (V):41 OPEN CIRCUIT VOLTAGE [Voc] (V):49.6 MAX POWER-POINT CURRENT [Imp] (A):10.74 SHORT CIRCUIT CURRENT [Isc] (A):11.34 MAX SERIES FUSE [OCPD] (A):20 MAX SYSTEM VOLTAGE (V):600 NOTES: 1- ALL METALLIC RACEWAYS AND EQUIPMENT SHALL BE BONDED AND ELECTRICALLY CONTINUOUS (NEC 250.90, 250.96). 2- GROUNDING BUSHINGS ARE REQUIRED AROUND PREPUNCHED CONCENTRIC KNOCKOUTS ON THE DC SIDE OF THE SYSTEM (NEC 250.97) 3- THE GROUNDING ELECTRODE CONDUCTOR WILL BE CONTINUOUS, EXCEPT FOR SPLICES OR JOINTS AT BUSBARS WITHIN LISTED EQUIPMENT. (NEC 250.64) 4- THE EQUIPMENT GROUNDING CONDUCTOR MAY BE USED AS A GROUNDING ELECTRODE CONDUCTOR. (NEC 250.121 EXCEPTION, INSTALLED PER 250.6(A), II, III, VI.) 5- INSTALLER TO IDENTIFY THE EXISTING GROUNDING ELECTRODE TYPE (I.E. DRIVEN ROD, UFER, WATER PIPE, OR COMBINATION OF SOME OR ALL OF THE PREVIOUSLY MENTIONED). IN EXISTING ELECTRICAL SYSTEMS THAT USE ONLY A WATER PIPING GROUNDING ELECTRODE SYSTEM, AN ADDITIONAL GROUNDING ELECTRODE (I.E DRIVEN ROD) SHALL BE PROVIDED. (NEC 250.50) -PER NEC 250.53(2), A SINGLE ROD, PIPE OR PLATE ELECTRODE SHALL BE SUPPLEMENTED BY AN ADDITIONAL ELECTRODE OF TYPE SPECIFIED IN 250.52(A)(2) THROUGH (A)(8) SPACED NO LESS THAN 6FT APART. EXCEPTION, IF A SINGLE ROD, PIPE OR PLATE GROUNDING ELECTRODE HAS A RESISTANCE TO EARTH OF 25 OHMS OR LESS, THE SUPPLEMENTAL ELECTRODE SHALL NOT BE REQUIRED. -#4 AWG CU TO UNDERGROUND METAL WATER PIPE THAT IS A MINIMUM 10 FOOT BURIAL IN PIPE LENGTH. CONNECT GROUNDING ELECTRODE CONDUCTOR WITHIN FIVE FEET OF WHERE IT ENTERS BUILDING. 250.52(A)(1), 250.68(C). -ADDITIONAL #4 AWG CONNECTION TO UFER IF AVAILABLE PER 250.66. IF UFER NOT AVAILABLE THEN TWO #6 AWG CU CONNECTIONS TO GROUND RODS SEPARATED BY AT LEAST 6 FT IS NEEDED 250.33. MICROINVERTER TO JBOX ITEM NUMBER OF MODULES IN CIRCUIT ADJUSTED TEMP. ADJUSTMENT (7/8"+ ABOVE ROOF) CORRECTED Ifc (A) FOR WIRE SIZING AWG NEEDED NUMBER OF CONDUCTORS EGC SIZE CONDUIT 1.1 8 12.10 0.91 13.30 #12 THWN-2 L1, L2, G #6 ENPHASE Q CABLE MICRO INVERTER INPUT (DC SIDE) POWER: 440W < MAX INPUT POWER OK VOLTAGE: 49.6 x 1.14 x 1 = 56.54V < 60V OK SHORT CIRCUIT: 11.34 = 11.34A < 15A OK WIRE CHECK FROM ABOVE TABLE ENPHASE Q CABLE CONTAINS (2) #12 THWN-2 AWG WIRES: 13.30A < 30A OK 04 OF 11 MAXIMUM VOLTAGE & VOLTAGE CORRECTION FACTOR (DC SIDE) MICRO-INVERTER INPUT [CEC 690.7] LOWEST EXPECTED AMBIENT TEMPERATURE (ºC):-7 ºC VOLTAGE CORRECTION FACTOR:1.14 MODULE OPEN CIRCUIT VOLTAGE:49.6 MODULE PER MICRO-INVERTER 1 ADJUSTED VOLTAGE:56.54 MAXIMUM VOLTAGE:60 V LOAD CENTER TO MSP CALCULATION ITEM TOTAL INVERTER OUTPUT (A) CONTINUOUS RESULT (A)TEMPERATURE CORRECTION CORRECTED (A)AWG NEEDED NUMBER OF CONDUCTORS EGC/GEC CONDUIT 3.1 9.68 1.25 12.10 0.91 13.30 #10 THWN-2 L1, L2, N, G #8 3/4" EMT J-BOX TO LOAD CENTER CALCULATION ITEM ADJUSTED (A) TEMP. ADJUSTMENT (IN ATTIC)ADJUSTED (A) Ifc # ENERGIZED CONDUCTORS IN RACEWAY RACEWAY ADJUSTMENT FACTOR ADJUSTED (A)AWG NEEDED NUMBER OF CONDUCTORS EGC SIZE CONDUIT 2.1 12.10 0.91 13.30 2 1.00 13.30 10/2 ROMEX (1)L1, (1)L2, G #10 N/A (N) 20A PV BREAKER 8 TOTAL MODULES 8 TOTAL INVERTERS EQUIPMENT LEGEND ITEM DESCRIPTION A (N) URE SOLAR FAM440E8G-BB MODULE B (N) NEMA 3R JUNCTION BOX (1) TOTAL. SEE LAYOUT. C (N) ENPHASE AC COMBINER BOX 240VAC, NEMA 3R, 10KAIC D (N) NEMA 3R 30A AC DISCONNECT 240VAC 10,000AIC RATING, NON-FUSIBLE, BLADE TYPE VISIBLE & LOCKABLE INV #1:(N) ENPHASE IQ8PLUS-72-2-US INVERTER SYSTEM RATINGS NOMINAL SYSTEM VOLTAGE (V):240Vac AC INVERTER OUTPUT (A):9.68 BUS BAR: 200A x 120% = 240.00A TOTAL BUS LOAD: = 212.10A ≤ 240.00A 705.12(B)(3)(2), BUSBAR END-FED PV SOLAR BREAKER TO BE MOUNTED ON THE OPPOSITE END OF THE BUSBAR FARTHEST FROM THE MAIN BREAKER OR INPUT FEEDER #6 BARE COPPER GROUND - EQUIPMENT CIRCUIT 1 - 8 MODULES INV# 1 (TYP.) A 1.1 G B G 20A PV SOLAR 15A ENVOY. C 2.1 3.1 LINE M M (E) GROUND ELECTRODE CONDUCTOR #4 SEE NOTE 5 N G (N) 20A PV BREAKER (E) 300A MAIN SERVICE METER/PANEL 120/240VAC, 1PH, 3W, 10KAIC TERMINALS SUITABLE FOR USE WITH 60°C/75°C CU/Al WIRE (E) 200A/2P MAIN BREAKER (E) 200A SUBPANEL 120/240VAC, 1PH, 3W,10KAIC TERMINALS SUITABLE FOR USE WITH 60°C/75°C CU/Al WIRE MAIN LUG ONLY ON OFF D PER NEC 250.122, 250.166, 690.47(C)(3), 250.64(E) SEE NOTES EGC/GEC 3.1 ADU MAIN HOUSE (E) WIRES (3) 3/0 AWG Cu (1) #6 AWG Cu 2" EMT (E) 100A/2P MAIN BREAKER COUNTY ELECTRONIC STAMP 1210 E Avalon Ave Unit# 2- Solar7/11/2024 Page RE V I S I O N S : Pr o j e c t N a m e 3. 5 2 0 k W ( D C ) / 3. 2 0 2 k W ( C E C - A C ) PH O T O V O L T A I C S Y S T E M 12 1 0 E A V A L O N A V E U N I T 2 - AD U 12 1 0 E A V A L O N A V E U N I T 2 , SA N T A A N A , CA 92 7 0 5 AP N : 39 6 1 9 1 0 7 DA T E : 06 / 1 1 / 2 0 2 4 DR A W N B Y : RD Co n t r a c t o r s S i g n a t u r e : PR E M I E R B U I L D E R S & H A R D S C A P E I N C 88 3 2 L A G R A N D A V E GA R D E N G R O V E , C A 9 2 8 4 1 PH O N E : (7 1 4 ) 4 6 7 - 9 0 1 8 LI C E N S E : #9 9 5 0 6 8 / B , C 5 3 R1 0 6 . 1 3 . 2 4 ( T Y ) SI G N A G E 06 OF 11 NEC 705.10 - ON MAIN SERVICE PANEL: CAUTION 1210 E AVALON AVE UNIT 2, SANTA ANA, CA 92705 WARNING ELECTRIC SHOCK HAZARD TERMINALS ON BOTH THE LINE AND LOAD SIDES MAY BE ENERGIZED IN THE OPEN POSITION AC PHOTOVOLTAIC DISCONNECT NEC 690.13, 690.15 - AT J-BOXES, ENCLOSURES, DISTRIBUTION EQUIPMENT, AND AC/DC DISCONNECTS WARNING ELECTRICAL SHOCK HAZARD TERMINALS ON BOTH THE LINE AND LOAD SIDE MAY BE ENERGIZED IN THE OPEN POSITION NEC 690.56 - WITHIN 3FT OF SERVICE DISCONNECT: RAPID SHUTDOWN SWITCH FOR SOLAR PV SYSTEM (690.56(C) RED WITH WHITE LETTERING) WARNING POWER SOURCE OUTPUT CONNECTION DO NOT RELOCATE THIS OVERCURRENT DEVICE TURN RAPID SHUTDOWN SWITCH TO THE "OFF" POSITION TO SHUT DOWN PV SYSTEM AND REDUCE SHOCK HAZARD IN ARRAY SOLAR ELECTRIC PV PANELS SOLAR PV SYSTEM EQUIPPED WITH RAPID SHUTDOWN (690.56(C)(1)(a) YELLOW WITH BLACK LETTERING) NEC 690.56 - ON RAPID SHUTDOWN DISCONNECT: OUTPUT CURRENT: OPERATING VOLTAGE:240V 9.7A NEC 690.54 - ON AC DISCONNECT: WARNING THIS EQUIPMENT FED BY MULTIPLE SOURCES. TOTAL RATING OF ALL OVERCURRENT DEVICES, EXCLUDING MAIN SUPPLY OVERCURRENT DEVICE, SHALL NOT EXCEED AMPACITY OF BUSBAR ALL PLAQUES AND SIGNAGE REQUIRED BY THE LATEST EDITION OF CALIFORNIA ELECTRICAL CODE WILL BE INSTALLED AS REQUIRED. ALTERNATE POWER SOURCE PLACARD SHALL BE METALLIC OR PLASTIC, ENGRAVED, OR MACHINE PRINTED LETTERS IN A CONTRASTING COLOR TO THE PLAQUE. THIS PLAQUE WILL BE ATTACHED BY POP RIVETS OR SCREWS OR OTHER APPROVED METHOD. IF EXPOSED TO SUNLIGHT, IT SHALL BE UV RESISTANT. PHOTOVOLTAIC DC CONDUCTORS SHALL BE LABELED, "WARNING PHOTOVOLTAIC DC POWER SOURCE" OR EQUIVALENT EVERY 10 FT AND KEPT MINIMUM 18" BELOW THE ROOF SURFACE. PV DC CIRCUIT LABELS SHALL APPEAR ON EVERY SECTION OF THE WIRING SYSTEM THAT IS SEPARTED BY ENCLOSURES, WALLS, PARTITIONS, CEILINGS, OR FLOORS. PV DC LABELS SHALL BE REFLECTIVE, SUITABLE FOR SURROUNDING ENVIRONMENT, AND WHITE LETTERING ON A RED BACKGROUND. [690.31(G)] EXPOSED NON-CURRENT CARRYING METAL PARTS OF MODULE FRAMES, EQUIPMENTS, AND CONDUCTOR ENCLOSURES SHALL BE GROUNDED IN ACCORDANCE WITH 250.134 OR 250.136(A) REGARDLESS OF VOLTAGE. EACH MODULE SHALL BE GROUNDED USING THE SUPPLIED CONNECTION POINT IDENTIFIED ON THE MODULE AND THE MANUFACTURER'S INSTRUCTIONS. IF THE EXISTING GROUNDING ELECTRODE SYSTEM CANNOT BE VERIFIED OR IS ONLY METALLIC WATER PIPING, IT IS THE CONTRACTOR'S RESPONSIBILITY TO INSTALL A SUPPLEMENTAL GROUNDING ELECTRODE. EQUIPMENT COMPLIES WITH RAPID SHUTDOWN REQUIREMENTS. [690.12] PLAQUES SHALL BE PLASTIC ENGRAVED IN A CONTRASTING COLOR TO THE PLAQUE. NEC 705.10(C) - AT EACH SERVICE EQUIPMENT: CAUTION MULTIPLE SOURCES OF POWER SOURCES INCLUDE: UTILITY, PV SOLAR MULTIPLE SOURCES OF POWER DISCONNECTS LOCATED AS SHOWN NEC 705.12(B)(3)(2) - BY BREAKER AT DISTRIBUTION EQUIPMENT: NEC 705.12(B)(3)(3) - BY BREAKER AT DISTRIBUTION EQUIPMENT: MSP A/CD.PVLC SP N COUNTY ELECTRONIC STAMP ENPHASE AC COMBINER BOX PV SYSTEM DISCONNECT FOR UTILITY OPERATION SUB PANEL MAIN ELECTRIC SERVICE DISCONNECT 1210 E Avalon Ave Unit# 2- Solar7/11/2024 Page RE V I S I O N S : Pr o j e c t N a m e 3. 5 2 0 k W ( D C ) / 3. 2 0 2 k W ( C E C - A C ) PH O T O V O L T A I C S Y S T E M 12 1 0 E A V A L O N A V E U N I T 2 - AD U 12 1 0 E A V A L O N A V E U N I T 2 , SA N T A A N A , CA 92 7 0 5 AP N : 39 6 1 9 1 0 7 DA T E : 06 / 1 1 / 2 0 2 4 DR A W N B Y : RD Co n t r a c t o r s S i g n a t u r e : PR E M I E R B U I L D E R S & H A R D S C A P E I N C 88 3 2 L A G R A N D A V E GA R D E N G R O V E , C A 9 2 8 4 1 PH O N E : (7 1 4 ) 4 6 7 - 9 0 1 8 LI C E N S E : #9 9 5 0 6 8 / B , C 5 3 R1 0 6 . 1 3 . 2 4 ( T Y ) MO D U L E SP E C I F I C A T I O N S 07 OF 11 COUNTY ELECTRONIC STAMP 1210 E Avalon Ave Unit# 2- Solar7/11/2024 Page RE V I S I O N S : Pr o j e c t N a m e 3. 5 2 0 k W ( D C ) / 3. 2 0 2 k W ( C E C - A C ) PH O T O V O L T A I C S Y S T E M 12 1 0 E A V A L O N A V E U N I T 2 - AD U 12 1 0 E A V A L O N A V E U N I T 2 , SA N T A A N A , CA 92 7 0 5 AP N : 39 6 1 9 1 0 7 DA T E : 06 / 1 1 / 2 0 2 4 DR A W N B Y : RD Co n t r a c t o r s S i g n a t u r e : PR E M I E R B U I L D E R S & H A R D S C A P E I N C 88 3 2 L A G R A N D A V E GA R D E N G R O V E , C A 9 2 8 4 1 PH O N E : (7 1 4 ) 4 6 7 - 9 0 1 8 LI C E N S E : #9 9 5 0 6 8 / B , C 5 3 R1 0 6 . 1 3 . 2 4 ( T Y ) IN V E R T E R SP E C I F I C A T I O N S 08 OF 11 COUNTY ELECTRONIC STAMP 1210 E Avalon Ave Unit# 2- Solar7/11/2024 Page RE V I S I O N S : Pr o j e c t N a m e 3. 5 2 0 k W ( D C ) / 3. 2 0 2 k W ( C E C - A C ) PH O T O V O L T A I C S Y S T E M 12 1 0 E A V A L O N A V E U N I T 2 - AD U 12 1 0 E A V A L O N A V E U N I T 2 , SA N T A A N A , CA 92 7 0 5 AP N : 39 6 1 9 1 0 7 DA T E : 06 / 1 1 / 2 0 2 4 DR A W N B Y : RD Co n t r a c t o r s S i g n a t u r e : PR E M I E R B U I L D E R S & H A R D S C A P E I N C 88 3 2 L A G R A N D A V E GA R D E N G R O V E , C A 9 2 8 4 1 PH O N E : (7 1 4 ) 4 6 7 - 9 0 1 8 LI C E N S E : #9 9 5 0 6 8 / B , C 5 3 R1 0 6 . 1 3 . 2 4 ( T Y ) UL L I S T I N G 09 OF 11 COUNTY ELECTRONIC STAMP 1210 E Avalon Ave Unit# 2- Solar7/11/2024 Page RE V I S I O N S : Pr o j e c t N a m e 3. 5 2 0 k W ( D C ) / 3. 2 0 2 k W ( C E C - A C ) PH O T O V O L T A I C S Y S T E M 12 1 0 E A V A L O N A V E U N I T 2 - AD U 12 1 0 E A V A L O N A V E U N I T 2 , SA N T A A N A , CA 92 7 0 5 AP N : 39 6 1 9 1 0 7 DA T E : 06 / 1 1 / 2 0 2 4 DR A W N B Y : RD Co n t r a c t o r s S i g n a t u r e : PR E M I E R B U I L D E R S & H A R D S C A P E I N C 88 3 2 L A G R A N D A V E GA R D E N G R O V E , C A 9 2 8 4 1 PH O N E : (7 1 4 ) 4 6 7 - 9 0 1 8 LI C E N S E : #9 9 5 0 6 8 / B , C 5 3 R1 0 6 . 1 3 . 2 4 ( T Y ) GR O U N D I N G 10 OF 11 RAIL TO RAIL BONDING #6 BARE COPPER WIRE INV (IF USED) MSP CONTINUOUS GROUND PER SLD JBOX GROUND BUSHINGS REQ. MODULE RAIL SOLAR METER (IF REQ) (A) (1) BOND STRIP GROUNDS RAIL TO RAIL SPLICES - STAR WASHERS USED TO BOND RAIL TO BONDING STRIP (2) SPLICE BAR, SELF-TAP SCREWS JOIN RAILS. BONDING STRIPS USED ON RAILS WITH GROUND LUGS. (1)(2) (3) IF SPLICE BAR HAS INTEGRATED GROUND, BONDING STRIP IS NOT NECESSARY. (3) WHERE NEITHER BONDING STRIP, INTEGRATED GROUNDING SPLICE BAR, OR INTEGRATED GROUNDING MIDCLAMP ARE USED, UL 2703 APPROVED GROUND LUG WITH #6 BARE COPPER SHALL BE USED TO GROUND SPLICED RAILS. USE METHOD (2) (1) (C) RAIL SPLICE GROUNDING (C) #6 BARE COPPER RAIL 1 RAIL 2 EITHER METHOD 1-3 PER MANUFACTURERS INSTALL INSTRUCTIONS CONDUIT COMPRESSION FITTING LOCK NUT GROUNDING BUSHING WITH LAY-IN LUG ENCLOSURE CONTINUOUS GROUND STRIP INSULATION CONDUIT GROUNDING DETAIL EQUIPMENT GROUND BUSHINGS REQ. FOR SYSTEMS OVER 250V A GROUNDING MID CLAMP EACH GROUNDING MID CLAMP PIERCES THROUGH THE ANODIZED COATINGS OF BOTH THE MODULE FRAME AND THE MOUNTING RAIL TO FORM SECURE ELECTRICAL BONDS, WHICH ARE REPEATED THROUGHOUT THE ARRAY. MIDCLAMP TEETH MODULE PENETRATION SERRATED T-BOLT BONDS CLAMP TO RAIL COUNTY ELECTRONIC STAMP 1210 E Avalon Ave Unit# 2- Solar7/11/2024 Page RE V I S I O N S : Pr o j e c t N a m e 3. 5 2 0 k W ( D C ) / 3. 2 0 2 k W ( C E C - A C ) PH O T O V O L T A I C S Y S T E M 12 1 0 E A V A L O N A V E U N I T 2 - AD U 12 1 0 E A V A L O N A V E U N I T 2 , SA N T A A N A , CA 92 7 0 5 AP N : 39 6 1 9 1 0 7 DA T E : 06 / 1 1 / 2 0 2 4 DR A W N B Y : RD Co n t r a c t o r s S i g n a t u r e : PR E M I E R B U I L D E R S & H A R D S C A P E I N C 88 3 2 L A G R A N D A V E GA R D E N G R O V E , C A 9 2 8 4 1 PH O N E : (7 1 4 ) 4 6 7 - 9 0 1 8 LI C E N S E : #9 9 5 0 6 8 / B , C 5 3 R1 0 6 . 1 3 . 2 4 ( T Y ) RA P I D SH U T D O W N 11 OF 11 COUNTY ELECTRONIC STAMP 1210 E Avalon Ave Unit# 2- Solar7/11/2024 1210 E. AVALON AVE. UNIT 2 - ADU SANTA ANA, CA 92705 1210 E. AVALON AVE. UNIT 2 - ADU Design Criteria 1- Code: CALIFORNIA BLDG CODE 2022 / ASCE 7-16 2 - Wind: 95 MPH, Exposure: C 3 - Wood Species: DF-L No. 2 (SG = 0.5 ) Notice: Use restrictions of these calculations. The attached Calculations are valid only when bearing original signature hereon. Contractor/Client to verify existing dimensions/conditions prior to construction & solar racking is installed per manufacturer span requirements. The use of these calculations is solely intended for the above mentioned project. 6/11/2024 Structural Calculations for SOLAR POWER SYSTEM CONNECTION CHECK AT: Job: 1-844-PV ELITE | info@yoursolarplans.com 3000 E. Birch Street Suite 201 | Brea CA 92821 1210 E Avalon Ave Unit# 2- Solar7/11/2024                                    !"##$      %&'()*+,-.(/'01.,6#67 8 8  #9 9:#!7;9<5 >>!?;;@?;9"66!@;>#67?6!! #7#F"7?"666;G7@G7!@:!H5 L??U!6U!!U @6US @:USS :;USSS 67#USW 67?U 2%=AMNOXQRS67"T  !#UQRS#;"T  !:UQRS;7"T  @;UQRS677"T  :6UR V S 677UR V SS 667UR V SSS"SW 66;U 2%=AMNXY !"7;L @;U dbefa\d[\]\ghihZ]\j`\eafck^afa\l]`lef`fm\cdm\ca^ala[\nf`_\^l]fckd\`bc\fablc`bc\^mfd\d_]bcoa[\p_b`dbcoeld\fdlqablcq]le\^^rs^\]^^[l_`delcjb]mfck\dj]lma[b^all`tba[a[\`lef`u_a[l]bakvfnbcow_]b^dbeablcp\jl]\q]le\\dbcotba[d\^bocra[faa[\uZyvfzf]d^pk{lefablct\p^ba\tb``clap\_qdfa\dal^_qql]au|y}~€€r bcdl_at[kr     U  8  !          V   !9                              ƒ U  9     „               9 8     V V …† G  "     V    9    V U    8   VU            "     9V V 9   U   9   V    „U       U           8     9      U              U                       U   „U  8      9       V                 U        ˆVU    U      98V „     V                 ‡        V V          8    <     U   UU      V U <             U  8   V 8 V V         V   8       V        ‰ V          Š‹‹Œ Ž ‘ ’ “”•”–—˜˜™š›œšžŸ—š › ˜¡’ ¢ ›¡¡˜¡ 1210 E Avalon Ave Unit# 2- Solar7/11/2024 ASCE 29.4.4 Rooftop Solar Panels Parallel to the Roof Surface on Buildings of All Heights and Roof Slopes. Roof Slope =18.43 ° Roof Shape Gable Tributary Width s =4.00 ft Tributary Length l =3.46 ft Effective Area Ae =13.83 f 2 Height of Structure h =15 ft Wind Speed V =95 mph Exposure Categor C Building Width B =15 ft Building Length L =45 ft Zone Width a =3 ft Elevation Height zg =177 ft Wind Directionality Kd =0.85 Topography Factor Kt =1.00 Ground Elevation Factor Ke =0.99 Velocity Pressure Exposure Coefficient Kz =0.85 Velocity Pressure qz = 0.00256KzKztKdKeV2 =16.56 psf Solar Array Pressure Equalization a =0.78 Array Edge Factor E =1.50 Zone GCp p = qz(GCp)(E)(a) 3 - - 3r 3.52 -68.54 3e 2.97 -57.74 2 - - 2r 2.97 -57.74 2e - - 2n 2.97 -57.74 1 - - 1' - - 1210 E Avalon Ave Unit# 2- Solar7/11/2024 LAG SCREW ANALYSIS Loads Wind Pressures qz =-57.74 psf Solar Panel Load QD =3 psf Panel Length l =6.916 ft Panel Width b 3.4383 ft Attachment Spacing s =4 ft Portrait Tributary Area At =13.83 ft2 Wind Load PW = qz * At =-799 lbs Dead Load PD = QD * At =41.495 lbs Uplift Pa = 0.6 PD + 0.6 Pw =-454 lbs Landscape Tributary Area At = b * s =6.8767 ft2 Wind Load PW = qz * At =-397 lbs Dead Load PD = QD * At =20.63 lbs Uplift Pa = 0.6 PD + 0.6 Pw =-226 lbs Lag Screw Specific Gravity of Lumber SG =0.50 (Douglas Fir-Larch) Diameter of Lag Screw D =5/16 in Withdraw Design /in 1800*SG3/2*D3/4 =266 lbs/in Depth of Embedment lp =2.50 in Total Nominal Withdrawal Value W = W * l p =665 lbs Load Duration Factor CD =1.6 Withdrawal Design Value W' = W * C D =1064 lbs Demand Capacity Ratio DCR = Pa / W'=0.43 < 1 OK 1210 E Avalon Ave Unit# 2- Solar7/11/2024 ASCE 30.3.2 Design Wind Pressure Beam/ Top Chord Check Roof Slope =18.43 ° Roof Shape Gable Tributary Width s =2.00 ft Tributary Length L =9.50 ft Effective Area A = L ( MAX [ s , L/3] )=30 f 2 Height of Structure h =15 ft Wind Speed V =95 mph Exposure Categor C Building Width B =15 ft Building Length L =45 ft Zone Width a =3 ft Elevation Height zg =177 ft Wind Directionality Kd =0.85 Topography Factor Kt =1.00 Ground Elevation Factor Ke =0.99 Velocity Pressure Exposure Coefficient Kz =0.85 Velocity Pressure qz = 0.00256KzKztKdKeV2 =16.56 psf Internal Pressure Coefficient (GCpi)=-0.18 Zone GCp p = qz [(GCp) - (Gcpi)] 3 - - 3r 3.20 -55.96 3e 2.83 -49.90 2 - - 2r 2.83 -49.90 2e - - 2n 2.83 -49.90 1 - - 1' - - 1210 E Avalon Ave Unit# 2- Solar7/11/2024 Beam/ Top Chord Check Lumber: Moment Demand # of Attachment per Rafter NA =Span :Orientation Lenght (ft) : Dead Load Roof Material:QD =psf Live Load QLr =psf Wind Load p = psf Snow Load QS =psf Rafter Spacing s = in Wind Load, Portrait Portrait UL = Wind Load, Landscape Landscape UW = Linear Dead Load wd =plf Live Load wLr = plf Start ft Start ft End ft End ft Snow Load ws = plf Start ft Start ft End ft End ft Ma, Moment D lb-ft D+Lr lb-ft D+S lb-ft 0.6D+0.6W lb-ft D+0.45W+0.75Lr lb-ft D+0.45W+0.75S lb-ft Moment Capacity Framing Member Size Lumber Grade : DF-L No. 2 CM = 1 Ct = 1 Cr= CF = fb =psi Cfu =Ci = Breadth b = in Depth d = in Section Modulus Sx = bd2 / 6 =in3 Bending Stress Capacity Fb = CM * Ct * Cr * CF * fb =psi Table 4.3.1 NDS 2015 Deflection Limit E = ksi I =in4 Transient Deflection in Transient Deflection Allowed > [OKAY] Total Deflection in Total Deflection Allowed > [OKAY] 1.0 1 20 0.00 24 Comp 0.212 482 180 1.6 2153 psi D+0.45W+0.75S 626 psi 0.29 OKAY 1.6 2153 psi D+0.45W+0.75L 626 psi 0.29 OKAY 1.6 2153 psi 0.243 419 120 1600 20.80 0.6D+0.6W 1098 psi 0.51 OKAY 1.15 1547 psi D+S 393 psi 0.25 OKAY OKAY 1.25 1682 psi D+Lr 406 psi 0.24 OKAY DCR 0.9 1211 psi D 393 psi 0.32 7.56 1346 CD Fb' = CD * Fb ASD Load Ma / Sx 2x6 1.15 1.3 9.50 8.42 9.50 900 1.50 5.50 247 256 247 692 394 394 0 0.0 0 1.5 0 0 0.0 Portrait 1.5 0.0Portrait0 0.0 0.0 AT (ft2) 13.832 6.8767 pd (lbs) 41.495 -690 pw (lbs) ps (lbs) 0 8.4240 0.0 0.0 0.0 0.0 0 0.0Portrait0 0.020.63 -343 0 0 0.0Portrait0 0.0 0.0 0 0.0 20 1 2 3 4 Eave 2 0.0 0.0 0.0 0.0 0.0 0 0.0 0.0 0.0 0.0 0 0.0 0.0 0.0 0.0 0 0.0 0.0 0.0 8.50 0.00 0.00 0.00 1.00 Portrait 0 0.0 0.0 10.00 -49.90 DF-L No. 2 2 j lj (ft)pd,j (lbs) pw,j (lbs) ps,j (lbs) Portrait 1 2.4 41.5 -690 0.0 7.5 41.5 -690 0 0.0 0 0.0 0.0 0 0.0 𝑴𝒙 𝑹𝒊𝒙 𝑳𝒊 𝑷𝒋𝒙 𝒍𝒋 𝒘𝒅𝒙𝟐 𝟐 ‐200.0 0.0 200.0 400.0 600.0 800.0 0.000 2.000 4.000 6.000 8.000 10.000 1210 E Avalon Ave Unit# 2- Solar7/11/2024 EISMIC WEIGHT COMPARISON / ANALYSIS - (PER CEBC 2022 Part 10 Chapter 5 Section 502.5) PV System Weight Module Model URE Panel Weight W panel = 53.79 lbs Number of Panels NPV = 8 Total PV System Weight W PV = W panel * NPV =430.3 lbs Existing Roof Weight Roof Weight QD =10.0 psf Building Length Lbuild =45 ft Building Width W build =15 ft Roof Area Abuild =675 ft2 Building Perimeter Pbuild =120 ft Wall Height ht =8 ft Wall weight Qwall =15 psf Interior wall weight Qint =10 psf Roof Load W floor = Abuild * QD =6750 lbs Wall Load wall = ht /2 * Qwall * Pbuild + Abuild * Qint /=10575 lbs Total Story Weight W build = W floor + W wall =17325 lbs Percentage Weight Increas WPV / Wbuild = 2.48% < 10% OKAY 1210 E Avalon Ave Unit# 2- Solar7/11/2024 Expedited Permit Process for PV Systems 1 Expedited Permit Process for PV Systems Standard String System The Solar America Board for Codes and Standards (Solar ABCs) Expedited Permit Pro- cess provides a means to differentiate systems that can be permitted quickly and easily due to their similarity with the majority of small-scale PV systems. Those systems with unique characteristics may be handled with small additions to this Expedited Permit Process or may require much more information, depending on the uniqueness of the installation. The following pages contain forms for the Standard String System to use with the Expe- dited Permit Process. The Micro-Inverter, AC Module, and Supply-Side Connection forms are also available as interactive PDF files at www.solarabcs.org/permitting. In jurisdic- tions that have adopted the Expedited Permit Process for PV Systems, these forms can be filled out electronically and submitted in either printed form and via email. An elec- tronic format is used so that the supplied information is standardized and legible for the local jurisdiction. 1210 E Avalon Ave Unit# 2- Solar7/11/2024 Expedited Permit Process for PV Systems 2 Expedited Permit Process for Small-Scale PV Systems Standard String System The information in this guideline is intended to help local jurisdictions and contractors identify when PV system installations are simple, needing only a basic review, and when an installation is more complex. It is likely that 50%-75% of all residential systems will comply with these simple criteria. For projects that fail to meet the simple criteria, resolution steps have been suggested to provide as a path to permit approval. Required Information for Permit: 1. Site plan showing location of major components on the property. This drawing need not be exactly to scale, but it should represent relative location of components at site (see supplied example site plan). PV arrays on dwellings with a 3’ perimeter space at ridge and sides may not need separate fire service review. 2. Electrical diagram showing PV array configuration, wiring system, overcurrent protection, inverter, disconnects, required signs, and ac connection to building (see supplied standard electrical diagram). 3. Specification sheets and installation manuals (if available) for all manufactured components including, but not limited to, PV modules, inverter(s), combiner box, disconnects, and mounting system. Step 1: Structural Review of PV Array Mounting System Is the array to be mounted on a defined, permitted roof structure? l Yes l No If No due to non-compliant roof or a ground mount, submit completed worksheet for the structure WKS1. Roof Information: 1. Is the roofing type lightweight (Yes = composition, lightweight masonry, metal, etc…)__________________________ ____________________________________________________________________________________________________ If No, submit completed worksheet for roof structure WKS1 (No = heavy masonry, slate, etc…). 2. Does the roof have a single roof covering? l Yes l No If No, submit completed worksheet for roof structure WKS1. 3. Provide method and type of weatherproofing roof penetrations (e.g. flashing, caulk).____________________________ Mounting System Information: 1. Is the mounting structure an engineered product designed to mount PV modules with no more than an 18” gap beneath the module frames? l Yes l No If No, provide details of structural attachment certified by a design professional. 2. For manufactured mounting systems, fill out information on the mounting system below: a. Mounting System Manufacturer ___________Product Name and Model#________________________________ b. Total Weight of PV Modules and Rails ___________lbs c. Total Number of Attachment Points____________ d. Weight per Attachment Point (b÷c)_________________lbs (if greater than 45 lbs, see WKS1) e. Maximum Spacing Between Attachment Points on a Rail ______________inches (see product manual for maximum spacing allowed based on maximum design wind speed) f. Total Surface Area of PV Modules (square feet)_________________ ft2 g. Distributed Weight of PV Module on Roof (b÷f)_______________ lbs/ft2 If distributed weight of the PV system is greater than 5 lbs/ft2, see WKS1. Step 2: Electrical Review of PV System (Calculations for Electrical Diagram) In order for a PV system to be considered for an expedited permit process, the following must apply: 1. PV modules, utility-interactive inverters, and combiner boxes are identified for use in PV systems. 2. The PV array is composed of 4 series strings or less per inverter. 3. The total inverter capacity has a continuous ac power output 13,440 Watts or less 4. The ac interconnection point is on the load side of service disconnecting means (690.64(B)). 5. One of the standard electrical diagrams (E1.1, E1.1a, E1.1b, or E1.1c) can be used to accurately represent the PV system. Interactive PDF diagrams are available at www.solarabcs.org/permitting. Fill out the standard electrical diagram completely. A guide to the electrical diagram is provided to help the applicant understand each blank to fill in. If the electrical system is more complex than the standard electrical diagram can effectively communicate, provide an alternative diagram with appropriate detail. 1210 E Avalon Ave Unit# 2- Solar7/11/2024 E x p e d i t e d P e r m i t P r o c e s s f o r P V S y s t e m s 3 Standard String System Site Plan               1210 E Avalon Ave Unit# 2- Solar7/11/2024 E x p e d i t e d P e r m i t P r o c e s s f o r P V S y s t e m s 4 Standard String System Electrical Diagram                                                                                                            1210 E Avalon Ave Unit# 2- Solar7/11/2024 E x p e d i t e d P e r m i t P r o c e s s f o r P V S y s t e m s 5 Notes for Standard String System Electrical Diagram Contractor Name, Address and Phone: _________________ _________________ _________________ _________________ Notes for One-Line Standard Electrical Diagram for Single-Phase PV Systems Site Name: __________________________ Site Address: ________________________ System AC Size: ______________________ SIZE FSCM NO DWG NO REV SCALE NTS Date:SHEET Drawn By: Checked By: MAX POWER-POINT CURRENT (IMP) MAX POWER-POINT VOLTAGE (VMP) OPEN-CIRCUIT VOLTAGE (VOC) SHORT-CIRCUIT CURRENT (ISC) MAX SERIES FUSE (OCPD) MAXIMUM POWER (PMAX) MAX VOLTAGE (TYP 600VDC) VOC TEMP COEFF (mV/oC or %/oC ) IF COEFF SUPPLIED, CIRCLE UNITS A V V A A W V MODULE MAKE MODULE MODEL PV MODULE RATINGS @ STC (Guide Section 5) MAX DC VOLT RATING MAX POWER @ 40oC NOMINAL AC VOLTAGE MAX AC CURRENT MAX OCPD RATING V W V A A INVERTER MAKE INVERTER MODEL INVERTER RATINGS (Guide Section 4) 1) IF UTILITY REQUIRES A VISIBLE-BREAK SWITCH, DOES THIS SWITCH MEET THEREQUIREMENT? YES NO N/A 2) IF GENERATION METER REQUIRED, DOES THIS METER SOCKET MEET THEREQUIREMENT? YES NO N/A 3) SIZE PHOTOVOLTAIC POWER SOURCE (DC) CONDUCTORS BASED ON MAXCURRENT ON NEC 690.53 SIGN OR OCPD RATING AT DISCONNECT 4) SIZE INVERTER OUTPUT CIRCUIT (AC) CONDUCTORS ACCORDING TO INVERTEROCPD AMPERE RATING. (See Guide Section 9) 5) TOTAL OF ______ INVERTER OCPD(s), ONE FOR EACH INVERTER. DOES TOTALSUPPLY BREAKERS COMPLY WITH 120% BUSBAR EXCEPTION IN 690.64(B)(2)(a)?YES NO NOTES FOR INVERTER CIRCUITS (Guide Section 8 and 9): 1.) LOWEST EXPECT AMBIENT TEMPERATURE BASED ON ASHRAE MINIMUM MEANEXTREME DRY BULB TEMPERATURE FOR ASHRAE LOCATION MOST SIMILAR TOINSTALLATION LOCATION. LOWEST EXPECTED AMBIENT TEMP ______oC 2.) HIGHEST CONTINUOUS AMBIENT TEMPERATURE BASED ON ASHRAE HIGHESTMONTH 2% DRY BULB TEMPERATURE FOR ASHRAE LOCATION MOST SIMILAR TOINSTALLATION LOCATION. HIGHEST CONTINUOUS TEMPERATURE _____oC 2.) 2005 ASHRAE FUNDEMENTALS 2% DESIGN TEMPERATURES DO NOT EXCEED47oC IN THE UNITED STATES (PALM SPRINGS, CA IS 44.1oC). FOR LESS THAN 9CURRENT-CARRYING CONDUCTORS IN ROOF-MOUNTED SUNLIT CONDUIT ATLEAST 0.5" ABOVE ROOF AND USING THE OUTDOOR DESIGN TEMPERATURE OF47oC OR LESS (ALL OF UNITED STATES), a)12 AWG, 90oC CONDUCTORS ARE GENERALLY ACCEPTABLE FOR MODULESWITH Isc OF 7.68 AMPS OR LESS WHEN PROTECTED BY A 12-AMP OR SMALLERFUSE.b)10 AWG, 90oC CONDUCTORS ARE GENERALLY ACCEPTABLE FOR MODULESWITH Isc OF 9.6 AMPS OR LESS WHEN PROTECTED BY A 15-AMP OR SMALLERFUSE. NOTES FOR ARRAY CIRCUIT WIRING (Guide Section 6 and 8 and Appendix D): OCPD = OVERCURRENT PROTECTION DEVICE NATIONAL ELECTRICAL CODE® REFERENCES SHOWN AS (NEC XXX.XX) NOTES FOR ALL DRAWINGS: SIGNS–SEE GUIDE SECTION 7 SIGN FOR DC DISCONNECT SIGN FOR INVERTER OCPD AND AC DISCONNECT (IF USED) RATED MPP CURRENT RATED MPP VOLTAGE MAX SYSTEM VOLTAGE MAX CIRCUIT CURRENT A V V A PHOTOVOLTAIC POWER SOURCE WARNING: ELECTRICAL SHOCK HAZARD–LINE AND LOAD MAY BE ENERGIZED IN OPEN POSITION AC OUTPUT CURRENT NOMINAL AC VOLTAGE A V SOLAR PV SYSTEM AC POINT OF CONNECTION THIS PANEL FED BY MULTIPLE SOURCES (UTILITY AND SOLAR) 1210 E Avalon Ave Unit# 2- Solar7/11/2024 Rev: 7/15/2021 RESIDENTIAL PHOTOVOLTAIC CHECKLIST SOL-01 CBC 2019 Solar Photovoltaic (PV) Checklist for Detached SINGLE FAMILY RESIDENCES Only Instructions: The licensed contractor of record shall complete all sections, answer the ten questions and sign the certification section below. A copy of this form shall be attached to each of TWO sets of plans, of minimum 11” x 17” size. If answering NO to any of the questions, plan check shall be required. Project Address: Contractor Company Name: Contractor License Number: YES NO Are the following applicable to the proposed project? 1.   Will the PV system layout provide the required three-foot wide clear access pathways per Section 605.11 of the California Fire Code, and is this shown on the roof plan? 2.   Will the PV system be installed on a roof having only one roofing layer with no overlays? 3.   Will the PV array be flush mounted to the existing roof so that the plane of the modules (panels) are parallel to the plane of the roof? 4.   Will the PV system weigh maximum 4 pounds per square feet or less? 5.   Will the PV system be installed where the modules do not overhang any roof edges (such as eaves, gabled ends, ridges and hips)? 6.   Will the PV system be installed with a space of 2” minimum to 10” maximum between the underside of modules and the surface of the roof? 7.   Will the PV system be installed without using any ballast system or counter-weight system? 8.   Will the anchors be installed with a maximum horizontal anchor spacing of 6 feet and is this maximum horizontal spacing shown on the plans? 9.   Will the minimum 5/16” lag screws be installed with a minimum of 2-1/2 inch embedment into roof rafters (with pre-drilled holes) and is this minimum embedment shown on the plans? 10.   Are ALL the structural pages of the plans stamped and signed by a California licensed professional engineer? (including project specific site plan, PV layout, anchorage spacing, anchorage details and manufacturer’s PV support information.) I certify under penalty of perjury under the laws of the State of California that the above is true: Print Name: Signature: Phone Number: Date: Email Address: Planning & Building Agency Building Safety Division 20 Civic Center Plaza P.O. Box 1988 (M-19) Santa Ana, CA 92702 (714) 647-5800 www.santa-ana.org 849 E MCFADDEN AVE UNIT 2, SANTA ANA, CA 92707 PREMIER BUILDERS & HARDSCAPE INC #995068 BRYAN HA (714) 653-8019 OCPREMIERBUILDERS@GMAIL.COM 3/26/2024 1210 E AVALON UNIT 2, SANTA ANA, CA 06/13/2024 1210 E Avalon Ave Unit# 2- Solar7/11/2024 Owner Consent Form – Solar Permits I certify that I am the owner of the subject property and that the authorized agent noted in this application has my consent to represent me with respect to this permit. Should any of the information or representations submitted in connection with this permit application be incorrect or untrue, I understand that Eagle Mountain City may rescind any approval, or take any other legal or appropriate action. Additionally, I acknowledge that I have reviewed and understand that there are fees associated with the review of this permit application and its contents. Owner Signature: ____________________________ Printed Name: _______________________________ Date: ____________________ PREMIER BUILDERS & HARDSCAPE INC., Bryan Ha SANG PHAM 1210 E AVALON UNIT 2 SANTA ANA CA SANG PHAM I, _____________________________________________ (property owners), do hereby grant permission for the following agent, ______________________________________________, to apply and receive a building permit in my name for the installation of photovoltaic panels to be located at __________________________________________________________________. Sang pham (Jun 13, 2024 12:21 PDT) Jun 13, 2024 1210 E Avalon Ave Unit# 2- Solar7/11/2024 SolarOwnerConsentForm Final Audit Report 2024-06-13 Created:2024-06-13 By:Hoa Nguyen (hknguyen217@gmail.com) Status:Signed Transaction ID:CBJCHBCAABAAmhKOq2E8OGoJnG0gLlKKIX7fN2zr2eKE "SolarOwnerConsentForm" History Document created by Hoa Nguyen (hknguyen217@gmail.com) 2024-06-13 - 7:16:03 PM GMT- IP address: 98.149.46.17 Document emailed to sanginvestmentproperties@gmail.com for signature 2024-06-13 - 7:16:38 PM GMT Email viewed by sanginvestmentproperties@gmail.com 2024-06-13 - 7:20:21 PM GMT- IP address: 104.28.85.120 Signer sanginvestmentproperties@gmail.com entered name at signing as Sang pham 2024-06-13 - 7:21:39 PM GMT- IP address: 23.241.87.85 Document e-signed by Sang pham (sanginvestmentproperties@gmail.com) Signature Date: 2024-06-13 - 7:21:41 PM GMT - Time Source: server- IP address: 23.241.87.85 Agreement completed. 2024-06-13 - 7:21:41 PM GMT 1210 E Avalon Ave Unit# 2- Solar7/11/2024