HomeMy WebLinkAbout1225 S Rosewood Ave - PlanExpedited Permit Process for PV Systems - Micro-Inverter1 Expedited Permit Process for PV Systems Micro-Inverter The Solar America Board for Codes and Standards (Solar ABCs) Expedited Permit Pro- cess provides a means to differentiate systems that can be permitted quickly and easily due to their similarity with the majority of small-scale PV systems. Those systems with unique characteristics may be handled with small additions to this Expedited Permit Process or may require much more information, depending on the uniqueness of the installation. The following pages contain forms for the Micro-Inverter to use with the Expedited Per- mit Process. The Standard String, AC Module, and Supply-Side Connection forms are also available as interactive PDF files at www.solarabcs.org/permitting. In jurisdic- tions that have adopted the Expedited Permit Process for PV Systems, these forms can be filled out electronically and submitted in either printed form and via email. An elec- tronic format is used so that the supplied information is standardized and legible for the local jurisdiction. 1225 S Rosewood Ave03/14/23 Expedited Permit Process for PV Systems — Micro-Inverter2 Expedited Permit Process for Small-Scale PV Systems Micro-Inverter The information in this guideline is intended to help local jurisdictions and contractors identify when PV system installations are simple, needing only a basic review, and when an installation is more complex. It is likely that 50%-75% of all residential systems will comply with these simple criteria. For projects that fail to meet the simple criteria, resolution steps have been suggested to provide as a path to permit approval. Required Information for Permit: 1. Site plan showing location of major components on the property. This drawing need not be exactly to scale, but it should represent relative location of components at site (see supplied example site plan). PV arrays on dwellings with a 3’ perimeter space at ridge and sides may not need separate fire service review. 2. Electrical diagram showing PV array configuration, wiring system, overcurrent protection, inverter, disconnects, required signs, and ac connection to building (see supplied standard electrical diagram). 3. Specification sheets and installation manuals (if available) for all manufactured components including, but not limited to, PV modules, inverter(s), combiner box, disconnects, and mounting system. Step 1: Structural Review of PV Array Mounting System Is the array to be mounted on a defined, permitted roof structure? l Yes l No If No due to non-compliant roof or a ground mount, submit completed worksheet for the structure WKS1. Roof Information: 1. Is the roofing type lightweight (Yes = composition, lightweight masonry, metal, etc…)__________________________ ____________________________________________________________________________________________________ If No, submit completed worksheet for roof structure WKS1 (No = heavy masonry, slate, etc…). 2. Does the roof have a single roof covering? l Yes l No If No, submit completed worksheet for roof structure WKS1. 3. Provide method and type of weatherproofing roof penetrations (e.g. flashing, caulk).____________________________ Mounting System Information: 1. Is the mounting structure an engineered product designed to mount PV modules with no more than an 18” gap beneath the module frames? l Yes l No If No, provide details of structural attachment certified by a design professional. 2. For manufactured mounting systems, fill out information on the mounting system below: a. Mounting System Manufacturer ___________Product Name and Model#________________________________ b. Total Weight of PV Modules and Rails ___________lbs c. Total Number of Attachment Points____________ d. Weight per Attachment Point (b÷c)_________________lbs (if greater than 45 lbs, see WKS1) e. Maximum Spacing Between Attachment Points on a Rail ______________inches (see product manual for maximum spacing allowed based on maximum design wind speed) f. Total Surface Area of PV Modules (square feet)_________________ ft 2 g. Distributed Weight of PV Module on Roof (b÷f)_______________ lbs/ft2 If distributed weight of the PV system is greater than 5 lbs/ft2, see WKS1. Step 2: Electrical Review of PV System (Calculations for Electrical Diagram) In order for a PV system to be considered for an expedited permit process, the following must apply: 1. PV modules, utility-interactive inverters, and combiner boxes are identified for use in PV systems. 2. The PV array is composed of 4 series strings or less per inverter. 3. The total inverter capacity has a continuous ac power output 13,440 Watts or less 4. The ac interconnection point is on the load side of service disconnecting means (690.64(B)). 5. One of the standard electrical diagrams (E1.1, E1.1a, E1.1b, or E1.1c) can be used to accurately represent the PV system. Interactive PDF diagrams are available at www.solarabcs.org/permitting. Fill out the standard electrical diagram completely. A guide to the electrical diagram is provided to help the applicant understand each blank to fill in. If the electrical system is more complex than the standard electrical diagram can effectively communicate, provide an alternative diagram with appropriate detail. 1225 S Rosewood Ave03/14/23 Ex p e d i t e d P e r m i t P r o c e s s f o r P V S y s t e m s 3 Micro-Inverter Site Plan                                                       18271 MCDURMOTT W SUITE E, EVERARDO ALDAPAIRVINE, CA 92614. TEL.NO: 949-309-2453 1225 S ROSEWOOD AVE, SANTA AVA, CA 92707. LIC:#B/C10 - 1037212 6380W 1225 S Rosewood Ave03/14/23 Ex p e d i t e d P e r m i t P r o c e s s f o r P V S y s t e m s 4 Micro-Inverter Electrical Diagram Contractor Name, Address and Phone: One-Line Standard Electrical Diagram for Micro-Inverter PV Systems Site Name: Site Address: System AC Size: SIZE FSCM NO DWG NO REV E1.1a SCALE NTS Date: SHEET Drawn By: Checked By: DESCRIPTION OR CONDUCTOR TYPE USE-2 or PV WIRE GEC EGC X ALL THAT APPLY EXTERIOR CABLE LISTED W/ INV. THWN-2 or XHHW-2 or RHW-2 GEC EGC X ALL THAT APPLY NO DC GEC IF 690.35 SYSTEM THWN-2 or XHHW-2 or RHW-2 GEC EGC X ALL THAT APPLY TAG 1 2 3 4 5 CONDUIT AND CONDUCTOR SCHEDULE COND. GAUGE MFG MFG NUMBER OF CONDUCTORS MFG Cable MFG Cable CONDUIT TYPE N/A N/A N/A SAME SAME CONDUIT SIZE N/A N/A N/A SAME SAME DESCRIPTION PV DC or AC MODULE DC/AC INVERTER (MICRO) J-BOX (IF USED) PV ARRAY AC COMB. PANEL (IF USED) GEN METER (IF USED) AC DISCONNECT (IF USED) SERVICE PANEL TAG 1 2 3 4 5 6 7 8 PART NUMBER NOTES FOR UNUSED MODULES PUT "N/A” in BLANK ABOVE 1 1 3 2 3 EQUIPMENT SCHEDULE 2 _____ MICRO-INVERTERS IN BRANCH- CIRCUIT MOD ____ DC AC MOD ____ DC AC MOD ____ DC AC MOD ____ DC AC MOD ____ DC AC MOD ____ DC AC J-BOX 4 AC DISCO M BUILDING GROUNDING ELECTRODE G M UTILITY SERVICE MAIN SERVICE PANEL MAIN OCPD INVERTER OCPD 6 7 8 5 4 5 G SEE GUIDE APPENDIX D FOR INFORMATION ON MODULE AND ARRAY GROUNDING AC COMBINER PANEL G ____ MICRO-INVERTERS IN BRANCH- CIRCUIT 18271 MCDURMOTT W SUITE E, IRVINE, CA 92614. TEL.NO: 949-309-2453 EVERARDO ALDAPA 6380W 1225 S ROSEWOOD AVE, SANTA AVA, CA 92707. LIC:#B/C10 - 1037212 1225 S Rosewood Ave03/14/23 Ex p e d i t e d P e r m i t P r o c e s s f o r P V S y s t e m s 5 Contractor Name, Address and Phone: Notes for One-Line Standard Electrical Diagram for Single-Phase PV Systems Site Name: Site Address: System AC Size: SIZE FSCM NO DWG NO REV E1.2a SCALE NTS Date: SHEET Drawn By: Checked By: MAX POWER-POINT CURRENT (IMP) MAX POWER-POINT VOLTAGE (VMP) OPEN-CIRCUIT VOLTAGE (VOC) SHORT-CIRCUIT CURRENT (ISC) MAX SERIES FUSE (OCPD) MAXIMUM POWER (PMAX) MAX VOLTAGE (TYP 600VDC) VOC TEMP COEFF (mV/oC or %/oC ) IF COEFF SUPPLIED, CIRCLE UNITS MODULE MAKE MODULE MODEL PV MODULE RATINGS @ STC (Guide Section 5) MAX DC VOLT RATING MAX POWER @ 40oC NOMINAL AC VOLTAGE MAX AC CURRENT MAX OCPD RATING INVERTER MAKE INVERTER MODEL INVERTER RATINGS (Guide Section 4) 1) IF UTILITY REQUIRES A VISIBLE-BREAK SWITCH, DOES THIS SWITCH MEET THE REQUIREMENT? YES NO N/A 2) IF GENERATION METER REQUIRED, DOES THIS METER SOCKET MEET THE REQUIREMENT? YES NO N/A 3) SIZE PHOTOVOLTAIC POWER SOURCE (DC) CONDUCTORS BASED ON MAX CURRENT ON NEC 690.53 SIGN OR OCPD RATING AT DISCONNECT 4) SIZE INVERTER OUTPUT CIRCUIT (AC) CONDUCTORS ACCORDING TO INVERTER OCPD AMPERE RATING. (See Guide Section 9) 5) TOTAL OF ______ INVERTER OUTPUT CIRCUIT OCPD(s), ONE FOR EACH MICRO- INVERTER CIRCUIT. DOES TOTAL SUPPLY BREAKERS COMPLY WITH 120% BUSBAR EXCEPTION IN 690.64(B)(2)(a)? YES NO NOTES FOR INVERTER CIRCUITS (Guide Section 8 and 9): 1.) LOWEST EXPECT AMBIENT TEMPERATURE BASED ON ASHRAE MINIMUM MEAN EXTREME DRY BULB TEMPERATURE FOR ASHRAE LOCATION MOST SIMILAR TO INSTALLATION LOCATION. LOWEST EXPECTED AMBIENT TEMP ____oC 2.) HIGHEST CONTINUOUS AMBIENT TEMPERATURE BASED ON ASHRAE HIGHEST MONTH 2% DRY BULB TEMPERATURE FOR ASHRAE LOCATION MOST SIMILAR TO INSTALLATION LOCATION. HIGHEST CONTINUOUS TEMPERATURE ____oC 2.) 2009 ASHRAE FUNDAMENTALS 2% DESIGN TEMPERATURES DO NOT EXCEED 47oC IN THE UNITED STATES (PALM SPRINGS, CA IS 44.1 oC). FOR LESS THAN 9 CURRENT-CARRYING CONDUCTORS IN ROOF-MOUNTED SUNLIT CONDUIT AT LEAST 0.5" ABOVE ROOF AND USING THE OUTDOOR DESIGN TEMPERATURE OF 47oC OR LESS (ALL OF UNITED STATES), a) 12 AWG, 90 oC CONDUCTORS ARE GENERALLY ACCEPTABLE FOR MODULES WITH Isc OF 7.68 AMPS OR LESS WHEN PROTECTED BY A 12-AMP OR SMALLER FUSE. b) 10 AWG, 90oC CONDUCTORS ARE GENERALLY ACCEPTABLE FOR MODULES WITH Isc OF 9.6 AMPS OR LESS WHEN PROTECTED BY A 15-AMP OR SMALLER FUSE. NOTES FOR ARRAY CIRCUIT WIRING (Guide Section 6 and 8 and Appendix E): OCPD = OVERCURRENT PROTECTION DEVICE NATIONAL ELECTRICAL CODE®REFERENCES SHOWN AS (NEC XXX.XX) NOTES FOR ALL DRAWINGS: SIGNS–SEE GUIDE SECTION 7 SIGN FOR DC DISCONNECT SIGN FOR INVERTER OCPD AND AC DISCONNECT (IF USED) No sign necessary since 690.51 marking on PV module covers needed information AC OUTPUT CURRENT NOMINAL AC VOLTAGE SOLAR PV SYSTEM AC POINT OF CONNECTION THIS PANEL FED BY MULTIPLE SOURCES (UTILITY AND SOLAR) Notes for Micro-Inverter Electrical Diagram 18271 MCDURMOTT W SUITE E, IRVINE, CA 92614. TEL.NO: 949-309-2453 LIC:#B/C10 - 1037212 EVERARDO ALDAPA 1225 S ROSEWOOD AVE, SANTA AVA, CA 92707. 6380W 1225 S Rosewood Ave03/14/23 1225 S Rosewood Ave03/14/23 MSPAC LC SITE PLAN-1 PV-1.0 EVERARDO ALDAPA - 8.800kW DC, 6.380kW AC, 8.013kW CEC AC SITE PLAN-1 PV-1.0 A SITE PLAN-1 SCALE: 1"=10'-0" ELECTRIC CODE CEC 2022 FIRE CODE CFC 2022 RESIDENTIAL CODE CRC 2022 BUILDING CODE CBC 2022 WIND SPEED 96 MPH SNOW LOAD 0 PSF GENERAL INFORMATION PV-1.0 A1 VICINITY MAP SCALE: NTS CUSTOMER INFORMATION NAME&ADDRESS: 33°43'54.17"N 117°52'53.71"W APN:013-024-23 AHJ:CA-CITY OF SANTA ANA UTILITY:SCE SYSTEM INFORMATION DESIGNER/CHECKED BY: SB/MR PROJECT NUMBER:GOSG-007806 SCALE:AS NOTED PAPER SIZE:17"x11" EVERARDO ALDAPA 1225 S ROSEWOOD AVE, SANTA ANA, CA 92707. ENGINEER OF RECORD DATE:02/16/2023 REV:A DC SYSTEM SIZE: 8800W AC SYSTEM SIZE: 6380W CEC AC SYSTEM SIZE: 8013W MODULES: (22)URECO FBM400MFG-BB INVERTER: (22)ENPHASE IQ8PLUS-72-2-US(240V,1PH) BRANCH DETAILS: 2 BRANCH OF 11 MICRO INVERTERS (11 MODULES) CONTRACTOR INFORMATION 18271 MCDURMOTT W SUITE E, IRVINE, CA 92614. TEL.NO: 949-309-2453 LIC:#B/C10 - 1037212 INDEX INDEX NO.DESCRIPTION SITE PLAN-1 SITE PLAN-2 MICRO SERIAL MAP GENERAL NOTES MOUNTING DETAILS STRUCTURAL DETAILS SINGLE LINE DIAGRAM WARNING PLACARDS SPEC SHEETS PV-1.0 PV-1.1 PV-1.2 PV-2.0 PV-3.0 PV-3.1 PV-4.0 PV-5.0 SS 29 ' 25' 19' 13' 5' 7' 3' FIRE SETBACK PHOTOVOLTAIC ARRAY ON THE ROOF (N) ENPHASE IQ COMBINER 4 (EXTERIOR) (N) AC DISCONNECT (EXTERIOR) (N) MAIN SERVICE PANEL (EXTERIOR) CONDUIT RUN 31 ' - 8 " Signed: 3/8/2023 Structural Only BLDG # 101114252 ISS. 3/12/2023 ELEC # 20179008 ISS. 03/12/2023 The scope of the plans is for the installation of the solar photovoltaic system only and the approval is subject to compliance with all applicable city and state codes and regulations regarding construction. The approval of the plans does not constitute any certification of the accuracy, completeness, or building permit status of the existing buildings and structures as shown. 1225 S Rosewood Ave03/14/23 MSPAC LC SITE PLAN-2 PV-1.1 EVERARDO ALDAPA - 8.800kW DC, 6.380kW AC, 8.013kW CEC AC SITE PLAN-2 PV-1.1 A SITE PLAN-2 SCALE: 1/16" = 1'-0" CUSTOMER INFORMATION NAME&ADDRESS: 33°43'54.17"N 117°52'53.71"W APN:013-024-23 AHJ:CA-CITY OF SANTA ANA UTILITY:SCE SYSTEM INFORMATION DESIGNER/CHECKED BY: SB/MR PROJECT NUMBER:GOSG-007806 SCALE:AS NOTED PAPER SIZE:17"x11" EVERARDO ALDAPA 1225 S ROSEWOOD AVE, SANTA ANA, CA 92707. ENGINEER OF RECORD DATE:02/16/2023 REV:A DC SYSTEM SIZE: 8800W AC SYSTEM SIZE: 6380W CEC AC SYSTEM SIZE: 8013W MODULES: (22)URECO FBM400MFG-BB INVERTER: (22)ENPHASE IQ8PLUS-72-2-US(240V,1PH) BRANCH DETAILS: 2 BRANCH OF 11 MICRO INVERTERS (11 MODULES) CONTRACTOR INFORMATION 18271 MCDURMOTT W SUITE E, IRVINE, CA 92614. TEL.NO: 949-309-2453 LIC:#B/C10 - 1037212 PHOTOVOLTAIC ARRAY ON THE ROOF GATE-1 POOL PROPERTY LINE DETACHED STRUCTURE GATE-2 DRIVE WAY WALK WAY S RO S E W O O D AV E 133'-11" 54 ' - 9 " 133'-11" 2'-10" 35'-7" 1'-10" 19'-10" Structural Only 1225 S Rosewood Ave03/14/23 MICRO SERIAL MAP PV-1.2 EVERARDO ALDAPA - 8.800kW DC, 6.380kW AC, 8.013kW CEC AC MICRO SERIAL MAP PV-1.2 A MICRO SERIAL MAP SCALE: NTS CUSTOMER INFORMATION NAME&ADDRESS: 33°43'54.17"N 117°52'53.71"W APN:013-024-23 AHJ:CA-CITY OF SANTA ANA UTILITY:SCE SYSTEM INFORMATION DESIGNER/CHECKED BY: SB/MR PROJECT NUMBER:GOSG-007806 SCALE:AS NOTED PAPER SIZE:17"x11" EVERARDO ALDAPA 1225 S ROSEWOOD AVE, SANTA ANA, CA 92707. ENGINEER OF RECORD DATE:02/16/2023 REV:A DC SYSTEM SIZE: 8800W AC SYSTEM SIZE: 6380W CEC AC SYSTEM SIZE: 8013W MODULES: (22)URECO FBM400MFG-BB INVERTER: (22)ENPHASE IQ8PLUS-72-2-US(240V,1PH) BRANCH DETAILS: 2 BRANCH OF 11 MICRO INVERTERS (11 MODULES) CONTRACTOR INFORMATION 18271 MCDURMOTT W SUITE E, IRVINE, CA 92614. TEL.NO: 949-309-2453 LIC:#B/C10 - 1037212 PHOTOVOLTAIC ARRAY ON THE ROOF 1225 S Rosewood Ave03/14/23 GENERAL NOTES PV-2.0 CUSTOMER INFORMATION NAME&ADDRESS: 33°43'54.17"N 117°52'53.71"W APN:013-024-23 AHJ:CA-CITY OF SANTA ANA UTILITY:SCE SYSTEM INFORMATION DESIGNER/CHECKED BY: SB/MR PROJECT NUMBER:GOSG-007806 SCALE:AS NOTED PAPER SIZE:17"x11" EVERARDO ALDAPA 1225 S ROSEWOOD AVE, SANTA ANA, CA 92707. ENGINEER OF RECORD DATE:02/16/2023 REV:A DC SYSTEM SIZE: 8800W AC SYSTEM SIZE: 6380W CEC AC SYSTEM SIZE: 8013W MODULES: (22)URECO FBM400MFG-BB INVERTER: (22)ENPHASE IQ8PLUS-72-2-US(240V,1PH) BRANCH DETAILS: 2 BRANCH OF 11 MICRO INVERTERS (11 MODULES) CONTRACTOR INFORMATION 18271 MCDURMOTT W SUITE E, IRVINE, CA 92614. TEL.NO: 949-309-2453 LIC:#B/C10 - 1037212 GENERAL NOTES GENERAL NOTES 1. MODULES ARE LISTED UNDER UL 1703 AND CONFORM TO THE STANDARDS. 2. INVERTERS ARE LISTED UNDER UL 1741 AND CONFORM TO THE STANDARDS. 3. DRAWINGS ARE DIAGRAMMATIC, INDICATING GENERAL ARRANGEMENT OF THE PV SYSTEM AND THE ACTUAL SITE CONDITION MIGHT VARY. 4. WORKING CLEARANCES AROUND THE NEW PV ELECTRICAL EQUIPMENT WILL BE MAINTAINED IN ACCORDANCE WITH CEC CODE. 5. ALL GROUND WIRING CONNECTED TO THE MAIN SERVICE GROUNDING IN MAIN SERVICE PANEL/ SERVICE EQUIPMENT. 6. ALL CONDUCTORS SHALL BE 600V, 75°C STANDARD COPPER UNLESS OTHERWISE NOTED. 7. WHEN REQUIRED, A LADDER SHALL BE IN PLACE FOR INSPECTION IN COMPLIANCE WITH OSHA REGULATIONS. 8. THE SYSTEM WILL NOT BE INTERCONNECTED BY THE CONTRACTOR UNTIL APPROVAL FROM THE LOCAL JURISDICTION AND/OR THE UTILITY. 9. ROOF ACCESS POINT SHALL BE LOCATED IN AREAS THAT DO NOT REQUIRE THE PLACEMENT OF GROUND LADDERS OVER OPENINGS SUCH AS WINDOWS OR DOORS, AND LOCATED AT STRONG POINTS OF BUILDING CONSTRUCTION WHERE THE ACCESS POINT DOES NOT CONFLICT WITH OVERHEAD OBSTRUCTIONS SUCH AS TREES, WIRES OR SIGNS. 10. PV ARRAY COMBINER/JUNCTION BOX PROVIDES TRANSITION FROM ARRAY WIRING TO CONDUIT WIRING EQUIPMENT LOCATION: 11. ALL EQUIPMENT SHALL MEET MINIMUM SETBACKS AS REQUIRED BY CEC CODE. 12. WIRING SYSTEMS INSTALLED IN DIRECT SUNLIGHT MUST BE RATED FOR EXPECTED OPERATING TEMPERATURE AS SPECIFIED BY CEC CODE AND CEC TABLES. 13. JUNCTION AND PULL BOXES PERMITTED INSTALLED UNDER PV MODULES ACCORDING TO CEC CODE. 14. ADDITIONAL AC DISCONNECT(S) SHALL BE PROVIDED WHERE THE INVERTER IS NOT WITHIN SIGHT OF THE AC SERVICING DISCONNECT. 15. ALL EQUIPMENT SHALL BE INSTALLED ACCESSIBLE TO QUALIFIED PERSONNEL ACCORDING TO CEC APPLICABLE CODES. 16. ALL COMPONENTS ARE LISTED FOR THEIR PURPOSE AND RATED FOR OUTDOOR USAGE WHEN APPROPRIATE . STRUCTURAL NOTES: 17. RACKING SYSTEM & PV ARRAY WILL BE INSTALLED ACCORDING TO CODE-COMPLIANT INSTALLATION MANUAL. TOP CLAMPS REQUIRE A DESIGNATED SPACE BETWEEN MODULES, AND RAILS MUST ALSO EXTEND A MINIMUM DISTANCE BEYOND EITHER EDGE OF THE ARRAY/SUBARRAY, ACCORDING TO RAIL MANUFACTURER’S INSTRUCTIONS. 18. JUNCTION BOX WILL BE INSTALLED PER MANUFACTURER'S SPECIFICATIONS. IF ROOF-PENETRATING TYPE, IT SHALL BE FLASHED & SEALED PER LOCAL REQUIREMENTS. 19. ROOFTOP PENETRATIONS FOR PV RACEWAY WILL BE COMPLETED AND SEALED WITH APPROVED CHEMICAL SEALANT PER CODE BY A LICENSED CONTRACTOR. 20. ALL PV RELATED ROOF ATTACHMENTS TO BE SPACED NO GREATER THAN THE SPAN DISTANCE SPECIFIED BY THE RACKING MANUFACTURER. 21. WHEN POSSIBLE, ALL PV RELATED RACKING ATTACHMENTS WILL BE STAGGERED AMONGST THE ROOF FRAMING MEMBERS. WIRING & CONDUIT NOTES: 22. ALL CONDUIT AND WIRE WILL BE LISTED AND APPROVED FOR THEIR PURPOSE. CONDUIT AND WIRE SPECIFICATIONS ARE BASED ON MINIMUM CODE REQUIREMENTS AND ARE NOT MEANT TO LIMIT UP-SIZING. 23. CONDUCTORS SIZED ACCORDING TO CEC CODE. 24. DC WIRING LIMITED TO MODULE FOOTPRINT. MICRO INVERTER WIRING SYSTEMS SHALL BE LOCATED AND SECURED UNDER THE ARRAY WITH SUITABLE WIRING CLIPS. 25. AC CONDUCTORS COLORED OR MARKED AS FOLLOWS: PHASE A OR L1- BLACK PHASE B OR L2- RED, OR OTHER CONVENTION IF THREE PHASE PHASE C OR L3- BLUE, YELLOW, ORANGE**, OR OTHER CONVENTION NEUTRAL- WHITE OR GREY IN 4-WIRE DELTA CONNECTED SYSTEMS THE PHASE WITH HIGHER VOLTAGE TO BE MARKED ORANGE [CEC CODE]. INTERCONNECTION NOTES: 26. LOAD-SIDE INTERCONNECTION SHALL BE IN ACCORDANCE WITH [CEC CODE] 27. THE SUM OF THE UTILITY OCPD AND INVERTER CONTINUOUS INPUT MAY NOT EXCEED 120% OF BUSBAR RATING [CEC CODE]. 28. WHEN SUM OF THE PV SOURCES EQUALS >100% OF BUSBAR RATING, PV DEDICATED BACKFED BREAKERS MUST BE LOCATED OPPOSITE END OF THE BUS FROM THE UTILITY SOURCE OCPD [CEC CODE]. 29. AT MULTIPLE PV OUTPUT COMBINER PANEL, TOTAL RATING OF ALL OVER CURRENT DEVICES SHALL NOT EXCEED AMPACITY OF BUSBAR. HOWEVER, THE COMBINED OVER CURRENT DEVICE MAY BE EXCLUDED ACCORDING TO CEC CODE. 30. FEEDER TAP INTER CONNECTION (LOAD SIDE) ACCORDING TO CEC CODE. 31. SUPPLY SIDE TAP INTERCONNECTION ACCORDING TO CEC CODE WITH SERVICE ENTRANCE CONDUCTORS IN ACCORDANCE WITH CEC CODE. 32. BACK FEEDING BREAKER FOR UTILITY-INTERACTIVE INVERTER OUTPUT IS EXEMPT FROM ADDITIONAL FASTENING [CEC CODE]. GROUNDING NOTES: 33. GROUNDING SYSTEM COMPONENTS SHALL BE LISTED FOR THEIR PURPOSE, AND GROUNDING DEVISES EXPOSED TO THE ELEMENTS SHALL BE RATED FOR SUCH USE. 34. PV EQUIPMENT SHALL BE GROUNDED ACCORDING TO CEC CODE AND MINIMUM CEC TABLE. 35. METAL PARTS OF MODULE FRAMES, MODULE RACKING, AND ENCLOSURES CONSIDERED GROUNDED IN ACCORD. 36. EQUIPMENT GROUNDING CONDUCTORS SHALL BE SIZED ACCORDING TO CEC CODE AND MICRO INVERTER MANUFACTURER'S INSTRUCTIONS. 37. EACH MODULE WILL BE GROUNDED USING WEEB GROUNDING CLIPS AS SHOWN IN MANUFACTURER DOCUMENTATION AND APPROVED BY THE AHJ. IF WEEBS ARE NOT USED, MODULE GROUNDING LUGS MUST BE INSTALLED AT THE SPECIFIED GROUNDING LUG HOLES PER THE MANUFACTURERS' INSTALLATION REQUIREMENTS. 38. THE GROUNDING CONNECTION TO A MODULE SHALL BE ARRANGED SUCH THAT THE REMOVAL OF A MODULE DOES NOT INTERRUPT A GROUNDING CONDUCTOR TO ANOTHER MODULE. 39. GROUNDING AND BONDING CONDUCTORS, IF INSULATED, SHALL BE COLORED GREEN OR MARKED GREEN IF #4 AWG OR LARGER [CEC CODE] 40. THE GROUNDING ELECTRODE SYSTEM COMPLIES WITH CEC CODE AND NEC CODE THROUGH . IF EXISTING SYSTEM IS INACCESSIBLE, OR INADEQUATE, A GROUNDING ELECTRODE SYSTEM PROVIDED ACCORDING TO CEC CODE AND AHJ. 41. GROUND-FAULT DETECTION SHALL COMPLY WITH CEC CODE IN GENERAL AND CEC CODE SPECIFICALLY. 42. DISCONNECTION AND OVER-CURRENT PROTECTION NOTES. 43. DISCONNECTING SWITCHES SHALL BE WIRED SUCH THAT WHEN THE SWITCH IS OPENED THE CONDUCTORS REMAINING ENERGIZED ARE CONNECTED TO THE TERMINALS MARKED “LINE SIDE” (TYPICALLY THE UPPER TERMINALS). 44. DISCONNECTS TO BE ACCESSIBLE TO QUALIFIED UTILITY PERSONNEL, BE LOCKABLE, AND BE A VISIBLE-BREAK SWITCH 45. RAPID SHUTDOWN OF ENERGIZED CONDUCTORS BEYOND 10 FT OF PV ARRAY OR 5 FT INSIDE A BUILDING WITHIN 10 SECONDS. CONTROLLED CONDUCTORS ≤30V AND ≤240VA [CEC CODE]. LOCATION OF LABEL ACCORDING TO AHJ. 46. ALL OCPD RATINGS AND TYPES SPECIFIED ACCORDING TO CEC CODE. 47. MICRO INVERTER BRANCHES CONNECTED TO A SINGLE BREAKER OR GROUPED FUSES IN ACCORDANCE WITH CEC CODE. IF REQUIRED BY AHJ, SYSTEM WILL INCLUDE ARC-FAULT CIRCUIT PROTECTION ACCORDING TO CEC CODE AND UL1699B. Structural Only 1225 S Rosewood Ave03/14/23 MOUNTING DETAILS PV-3.0 CUSTOMER INFORMATION NAME&ADDRESS: 33°43'54.17"N 117°52'53.71"W APN:013-024-23 AHJ:CA-CITY OF SANTA ANA UTILITY:SCE SYSTEM INFORMATION DESIGNER/CHECKED BY: SB/MR PROJECT NUMBER:GOSG-007806 SCALE:AS NOTED PAPER SIZE:17"x11" EVERARDO ALDAPA 1225 S ROSEWOOD AVE, SANTA ANA, CA 92707. ENGINEER OF RECORD DATE:02/16/2023 REV:A DC SYSTEM SIZE: 8800W AC SYSTEM SIZE: 6380W CEC AC SYSTEM SIZE: 8013W MODULES: (22)URECO FBM400MFG-BB INVERTER: (22)ENPHASE IQ8PLUS-72-2-US(240V,1PH) BRANCH DETAILS: 2 BRANCH OF 11 MICRO INVERTERS (11 MODULES) CONTRACTOR INFORMATION 18271 MCDURMOTT W SUITE E, IRVINE, CA 92614. TEL.NO: 949-309-2453 LIC:#B/C10 - 1037212 PV-3.0 B MOUNTING DETAILS SCALE: 3/32" = 1'-0" UPLIFT CALCULATIONS UPLIFT 13868.7 LBS PULL OUT STRENGTH 30750 LBS POINT LOADING 21 LBS MODULES DATA URECO FBM400MFG-BB MODULE DIMS 67.83"x44.61"x1.38" LAG SCREWS 5/16"x3":2.5"MIN EMBEDMENT AERIAL VIEW SITE INFORMATION SR.NO AZIMUTH PITCH NO. OF MODULES ARRAY AREA (SQ. FT.)ROOF TYPE ATTACHMENT ROOF EXPOSURE FRAME TYPE FRAME SIZE FRAME SPACING MAX RAIL SPAN OVER HANG MP-01 270° 20° 7 147.1 COMPOSITION SHINGLE FLASH FOOT ATTIC RAFTERS 2 X 4 2'-0"6'-0" 2'-0" MP-02 180° 20° 4 84.1 COMPOSITION SHINGLE FLASHFOOT ATTIC RAFTERS 2 X 4 2'-0"6'-0" 2'-0" MP-03 180° 20° 7 147.1 COMPOSITION SHINGLE FLASHFOOT ATTIC RAFTERS 2 X 4 2'-0"6'-0" 2'-0" MP-04 90° 20° 4 84.1 COMPOSITION SHINGLE FLASHFOOT ATTIC RAFTERS 2 X 4 2'-0"6'-0" 2'-0" MINIMUM FIRE ACCESS PATHWAYS PER CFC 2022 RIDGE TO ARRAY: 3'-0" EAVE TO ARRAY : 3'-0" HIP/VALLEY W/ ADJACENT ARRAY: 1'-6" EACH SIDE HIP/VALLEY W/O ADJACENT ARRAY: 0'-0" NOTE: INSTALLER TO VERIFY RAFTER SIZE, SPACING AND SLOPED SPANS, AND NOTIFY ANY DISCREPANCIES BEFORE PROCEEDING. FIRE SETBACK DEAD LOAD CALCULATIONS BOM QUANTITY LBS/UNIT TOTAL WEIGHT (LBS) MODULES 22 47.84 1052.48 MID-CLAMP 24 0.050 1.20 END-CLAMP 40 0.050 2.00 RAIL LENGTH 174 0.680 118.32 SPLICE BAR 2 0.360 0.72 FLASHFOOT 50 1.35 67.50 MICRO-INVERTER 22 2.38 52.36 TOTAL WEIGHT OF THE SYSTEM (LBS)1294.58 TOTAL ARRAY AREA ON THE ROOF (SQ. FT.)462.29 WEIGHT PER SQ. FT.(LBS)2.80 WEIGHT PER PENETRATION (LBS)25.89 ARRAY MP-02 ALUMINIUM RAILS 2 X 4 RAFTERS@ 2'-0" SPACING ARRAY MP-01 ARRAY MP-03 ARRAY MP-04 1'-6 " 6' 3' Structural Only 1225 S Rosewood Ave03/14/23 STRUCTURAL DETAILS PV-3.1 CUSTOMER INFORMATION NAME&ADDRESS: 33°43'54.17"N 117°52'53.71"W APN:013-024-23 AHJ:CA-CITY OF SANTA ANA UTILITY:SCE SYSTEM INFORMATION DESIGNER/CHECKED BY: SB/MR PROJECT NUMBER:GOSG-007806 SCALE:AS NOTED PAPER SIZE:17"x11" EVERARDO ALDAPA 1225 S ROSEWOOD AVE, SANTA ANA, CA 92707. ENGINEER OF RECORD DATE:02/16/2023 REV:A DC SYSTEM SIZE: 8800W AC SYSTEM SIZE: 6380W CEC AC SYSTEM SIZE: 8013W MODULES: (22)URECO FBM400MFG-BB INVERTER: (22)ENPHASE IQ8PLUS-72-2-US(240V,1PH) BRANCH DETAILS: 2 BRANCH OF 11 MICRO INVERTERS (11 MODULES) CONTRACTOR INFORMATION 18271 MCDURMOTT W SUITE E, IRVINE, CA 92614. TEL.NO: 949-309-2453 LIC:#B/C10 - 1037212 MID-CLAMP & END CLAMP DETAIL GROUNDING DETAILS MID CLAMP ASSEMBLY MODULE FRAME RAIL GROUNDING MID-CLAMP SCALE: NTS MODULE TO MODULE & MODULE TO RAIL GROUNDING RAIL TO RAIL IRON RIDGE RAIL INTERNAL SPLICE SELF-DRILLING SCREW SCALE: NTS T BOLT SCALE: NTS SCALE: NTS SCALE: NTS 2 X 4 RAFTERS@2'-0" SPACING LOAD BEARING WALL PV MODULE IRONRIDGE RAIL IRONRIDGE STOPPER SLEEVE END CLAMP PV MODULE IRONRIDGE RAIL MID CLAMP SCALE: NTS FLASHFOOT SOLAR MODULE RAIL 6" MAX 5/16 HEX-BOLT STAINLESS STEEL 5/16" HANGER BOLT 2.5" EMBEDMENT PILOT HOLE REQUIRED (E)COMPOSITION SHINGLE ROOF IRONRIDGE FLASHFOOT IRONRIDGE RAIL PV MODULE (E) BUILDING STRUCTURE ATTACHMENT DETAIL- FLASH FOOT ROOF FRAMING DETAIL Structural Only 1225 S Rosewood Ave03/14/23 (N)JUNCTION BOX OR EQUIV 2 33 (N)ENPHASE IQ COMBINER 4 AC COMBINER WITH ENPHASE ENVOY-S X-IQ-AM1-240-4 120/240 NEMA 3R INSTALL (2)20A PV 2P BREAKERS(ONLY FOR SOLAR NO LOAD TO BE ADDED) 20A 20A 15A (N)200A MAIN BREAKER M PV BREAKER AT THE OPPOSITE END OF BUSBAR 40A 2P PV BREAKER EXISTING 120/240V 1PH 60HZ UT I L I T Y GR I D (E)GROUND ELECTRODE (N)200A END FED MAIN PANEL UTILITY:SCE 222013-161748 (N)(22)ENPHASE IQ8PLUS-72-2-US(240V,1PH) WITH (22)URECO FBM400MFG-BB MODULES 1 (1) BRANCH OF (11) MICRO-INVERTERS(11 MODULES) (1) BRANCH OF (11) MICRO-INVERTERS(11 MODULES) (N)URECO FBM400MFG-BB, 400W MODULES (N)60A AC DISCONNECT SQUARE D DU222RB AC DISCONNECT NON FUSED 60A, 120/240V, 2P SINGLE LINE DIAGRAM PV-4.0 SINGLE LINE DIAGRAM: DC SYSTEM SIZE - 8800W, AC SYSTEM SIZE - 6380W, CEC AC SYSTEM SIZE - 8013W CUSTOMER INFORMATION NAME&ADDRESS: 33°43'54.17"N 117°52'53.71"W APN:013-024-23 AHJ:CA-CITY OF SANTA ANA UTILITY:SCE SYSTEM INFORMATION DESIGNER/CHECKED BY: SB/MR PROJECT NUMBER:GOSG-007806 SCALE:AS NOTED PAPER SIZE:17"x11" EVERARDO ALDAPA 1225 S ROSEWOOD AVE, SANTA ANA, CA 92707. ENGINEER OF RECORD DATE:02/16/2023 REV:A DC SYSTEM SIZE: 8800W AC SYSTEM SIZE: 6380W CEC AC SYSTEM SIZE: 8013W MODULES: (22)URECO FBM400MFG-BB INVERTER: (22)ENPHASE IQ8PLUS-72-2-US(240V,1PH) BRANCH DETAILS: 2 BRANCH OF 11 MICRO INVERTERS (11 MODULES) CONTRACTOR INFORMATION 18271 MCDURMOTT W SUITE E, IRVINE, CA 92614. TEL.NO: 949-309-2453 LIC:#B/C10 - 1037212 MAIN PANEL UPGRADE:REPLACE EXISTING MAIN SERVICE PANEL WITH NEW 200/200A MAIN PANEL ELECTRICAL NOTES: 1. MAXIMUM DC/AC VOLTAGE DROP SHALL BE NO MORE THAN 2%. 2. BREAKER/FUSE SIZES CONFORMS TO CEC 240.6 CODE SECTION. 3. AC GROUNDING ELECTRODE CONDUCTOR SIZED PER CEC 250.66. 4. AMBIENT TEMPERATURE CORRECTION FACTOR IS BASED ON CEC 690.31(A). 5. AMBIENT TEMPERATURE ADJUSTMENT FACTOR IS BASED ON CEC 310.15(B)(2). 6. MAX. SYSTEM VOLTAGE CORRECTION IS PER CEC 690.7. 7. CONDUCTORS ARE SIZED PER WIRE AMPACITY TABLE CEC 310.15(B)(16). 8. CONDUCTORS EXPOSED TO SUNLIGHT SHALL BE LISTED AS SUNLIGHT RESISTANT PER CEC 310.10(D). 9. CONDUCTORS EXPOSED TO WET LOCATIONS SHALL BE SUITABLE FOR USE IN WET LOCATIONS PER CEC 310.10(C). NOTE: 1. MICRO INVERTERS ARE UL1741 RATED 2. EACH MICRO INVERTER IS RAPID SHUTDOWN COMPLIANT OCPD CALCULATIONS: SUB PANEL RATING:200A, SUB MAIN BREAKER RATING:200A 120% RULE: (200AX1.2)-200A=40A =>ALLOWABLE BACKFEED IS 40A INVERTER OVERCURRENT PROTECTION= INVERTER O/P I X CONTINUOUS LOAD(1.25)X #OF INVERTERS =1.21x1.25x22=33.28 A =>PV BREAKER = 40A ALLOWABLE BACKFEED 40A =>40A PV BREAKER THE DESIGNED INTERCONNECTION MEETS THE 705.12(B)(2) REQUIREMENTS MODULE SPECIFICATION MODEL URECO FBM400MFG-BB MODULE POWER @ STC 400W OPEN CIRCUIT VOLTAGE:Voc 37.2V MAX POWER VOLTAGE:Vmp 31.17V SHORT CIRCUIT CURRENT:Isc 13.68A MAX POWER CURRENT:Imp 12.84A MICRO INVERTER SPECIFICATIONS MODEL ENPHASE IQ8PLUS-72-2-US(240V,1PH) POWER RATING 290W MAX OUTPUT CURRENT 1.21A CEC WEIGHTED EFFICIENCY 97% MAX NO OF MICRO INVERTERS/BRANCH 13 MAX DC VOLTAGE 60V CONDUIT SCHEDULE TAG ID CONDUIT SIZE CONDUCTOR NEUTRAL GROUND 1 NONE (4) 12 AWG ENPHASE Q CABLE PER BRANCH CIRCUIT NONE (1) 6 AWG BARE COPPER 2 3/4"EMT OR EQUIV (4) 10 AWG THHN/THWN-2 NONE (1) 10 AWG THHN/THWN-2 3 3/4"EMT OR EQUIV (2) 8 AWG THHN/THWN-2 (1) 8 AWG THHN/THWN-2 (1) 10 AWG THHN/THWN-2 AC WIRE CALCULATIONS:- MATERIAL:COPPER & TEMPERATURE RATING:90°C TAG ID REQUIRED CONDUCTOR AMPACITY CORRECTED AMPACITY CALCULATION TERMINAL RATING CHECK DERATED CONDUCTOR AMPACITY CHECK 1 1.21 X 11 = 13.31 X 1.25 = 16.64A 30 X 0.96 X 1 =28.80A 16.64A <25A 16.64A <28.80A 2 1.21 X 11 = 13.31 X 1.25 = 16.64A 40 X 0.96 X 0.8 =30.72A 16.64A <35A 16.64A <30.72A 3 1.21 X 22 = 26.62 X 1.25 = 33.28A 55 X 0.96 X 1 =52.80A 33.28A <50A 33.28A <52.80A ELECTRICAL CALCULATION NOTE: 1.NEW SERVICE PANEL MUST BE COMBINATION/ALL-IN-ONE, AND METER AND MAIN CANNOT BE SEPARATE. 2.LISTED COMBINATION OVERHEAD AND UNDERGROUND FEED SERVICE BOXES REQUIRED.2. EACH OPTIMIZER IS RAPID SHUTDOWN COMPLIANT 3.200A SERVICE REQUIRES A MINIMUM 4 AWG CONDUCTOR TO 10' OF UNDERGROUND METAL WATER PIPE ELECTRODE. BOND ON THE INSIDE/OUTSIDE WITHIN FIRST 5' OF WHERE THE WATER ENTERS THE BUILDING. AN ADDITIONAL CONNECTION UFER OR 2 NEW RODS IS NEEDED - LOCATED 6' FROM OTHER ELECTRODES. WATER PIPE MAY NOT BE USED TO BOND ANY ELECTRODES UNLESS BURIED OR ENCASED, ELECTRODE CONNECTIONS MUST BE ACCESSIBLE. 1225 S Rosewood Ave03/14/23 MSPAC LC PV-5.0 CUSTOMER INFORMATION NAME&ADDRESS: 33°43'54.17"N 117°52'53.71"W APN:013-024-23 AHJ:CA-CITY OF SANTA ANA UTILITY:SCE SYSTEM INFORMATION DESIGNER/CHECKED BY: SB/MR PROJECT NUMBER:GOSG-007806 SCALE:AS NOTED PAPER SIZE:17"x11" EVERARDO ALDAPA 1225 S ROSEWOOD AVE, SANTA ANA, CA 92707. ENGINEER OF RECORD DATE:02/16/2023 REV:A DC SYSTEM SIZE: 8800W AC SYSTEM SIZE: 6380W CEC AC SYSTEM SIZE: 8013W MODULES: (22)URECO FBM400MFG-BB INVERTER: (22)ENPHASE IQ8PLUS-72-2-US(240V,1PH) BRANCH DETAILS: 2 BRANCH OF 11 MICRO INVERTERS (11 MODULES) CONTRACTOR INFORMATION 18271 MCDURMOTT W SUITE E, IRVINE, CA 92614. TEL.NO: 949-309-2453 LIC:#B/C10 - 1037212 ALL PLACARDS SHALL BE OF WEATHER PROOF CONSTRUCTION, BACKGROUND ON ALL PLACARDS SHALL BE RED WITH WHITE LETTERING U.O.N. PLACARD SHALL BE MOUNTED DIRECTLY ON THE EXISTING UTILITY ELECTRICAL SERVICE.FASTENERS APPROVED BY THE LOCAL JURISDICTION NOTE:ALL SIGNAGE CANNOT BE HAND WRITTEN CEC 110.21 WARNING PLACARDS WARNING PLACARDS WARNING CAUTION: SOLAR CIRCUIT LABEL LOCATION POINT OF INTERCONNECTION (PER CODE: CEC 705.12(B)(3)(2) [ NOT REQUIRED IF PANEL BOARD IS RATED NOT LESS THAN SUM OF AMPERE RATINGS OF ALL OVERCURRENT DEVICES SUPPLYING IT] WARNING INVERTER OUTPUT CONNECTION DO NOT RELOCATE THIS OVER-CURRENT DEVICE WARNING:PHOTOVOLTAIC POWER SOURCE LABEL LOCATION CONDUIT, COMBINER BOX [PER CODE: CEC 390.31(D)(2)] WARNING-Electric Shock Hazard No User Serviceable Parts inside Contact authorized service provide for assistance LABEL LOCATION INVERTER, JUNCTION BOXES(ROOF), AC DISCONNECT [PER CODE: CEC 690.13] LABEL LOCATION DISCONNECT, POINT OF INTERCONNECTION [PER CODE: CEC 690.13(B)] LABEL LOCATION AC DISCONNECT , POINT OF INTERCONNECTION [PER CODE: CEC 690.54] LABEL LOCATION MARKINGS PLACED ON ALL INTERIOR AND EXTERIOR DC CONDUIT, RACEWAYS, ENCLOSURES AND CABLE ASSEMBLES AT LEAST EVERY 10 FT, AT TURNS AND ABOVE/BELOW PENETRATIONS AND ALL COMBINER/JUNCTION BOXES. (PER CODE: CFC605.11.1.4) LABEL LOCATION POINT OF INTERCONNECTION [PER CODE: CEC705.12(D)(4)] ELECTRIC SHOCK HAZARD TERMINALS ON BOTH LINE AND LOAD SIDES MAY BE ENERGIZED IN THE OPEN POSITION LABEL LOCATION AC DISCONNECT,POINT OF INTERCONNECTION [PER CODE: CEC 690.13(B)] DC VOLTAGE IS ALWAYS PRESENT WHEN SOLAR MODULES ARE EXPOSED TO SUNLIGHT ELECTRIC SHOCK HAZARD TERMINALS ON BOTH LINE AND LOAD SIDES MAY BE ENERGIZED IN THE OPEN POSITION WARNING LABEL LOCATION AC DISCONNECT,POINT OF INTERCONNECTION [PER CODE: CEC 690.13(B)] LABEL LOCATION WEATHER RESISTANT MATERIAL, DURABLE ADHESDIVE, UL969 AS STANDARD TO WEATHER RATING (UL LISTING OF MARKINGS NOT REQUIRED), MIN 3 8" LETTER HEIGHT ARIAL OR SIMILAR FONT NON-BOLD,PLACED WITHIN THE MAIN SERVICE DISCONNECT,PLACED ON THE OUTSIDE OF THE COVER WHEN DISCONNECT IS OPERATED WITH THE SERVICE PANEL CLOSED. (PWER CODE: CEC690.15 ,690.13(B)) WARNING DUAL POWER SOURCE SECOND SOURCE IS PHOTOVOLTAIC SYSTEM SOLAR DISCONNECT RATED AC OPERATING CURRENT AC NOMINAL OPERATING VOLTAGE 26.62 240 AMPS AC VAC PHOTOVOLTAIC SYSTEM AC DISCONNECT SWITCH CAUTION: SOLAR ELECTRIC SYSTEM CONNECTED TURN RAPID SHUTDOWN SWITCH TO THE "OFF" POSITION TO SHUT DOWN PV SYSTEM AND REDUCE SHOCK HAZARD IN THE ARRAY SOLAR ELECTRIC PV PANELS SOLAR PV SYSTEM EQUIPPED WITH RAPID SHUTDOWN LABEL LOCATION AC DISCONNECT, DC DISCONNECT, POINT OF INTERCONNECTION (PER CODE: CEC690.56(C)(1) LABEL LOCATION INVERTER,POINT OF INTERCONNECTION [PER CODE: CEC 690.56(C)(3)] RAPID SHUTDOWN SWITCH FOR SOLAR SYSTEM PHOTOVOLTAIC ARRAY ON THE ROOF (N) ENPHASE IQ COMBINER 4 (EXTERIOR) (N) AC DISCONNECT (EXTERIOR) (N) MAIN SERVICE PANEL (EXTERIOR) 1225 S ROSEWOOD AVE, SANTA ANA, CA 92707. SYSTEM UTILIZES MICRO-INVERTERS LOCATED UNDER SOLAR MODULE POWER TO THIS BUILDING IS ALSO SUPPLIED FROM THE FOLLOWING SOURCES WITH DISCONNECTS LOCATED AS SHOWN WARNING: ! 1225 S Rosewood Ave03/14/23 PV-6.0 CUSTOMER INFORMATION NAME&ADDRESS: 33°43'54.17"N 117°52'53.71"W APN:013-024-23 AHJ:CA-CITY OF SANTA ANA UTILITY:SCE SYSTEM INFORMATION DESIGNER/CHECKED BY: SB/MR PROJECT NUMBER:GOSG-007806 SCALE:AS NOTED PAPER SIZE:17"x11" EVERARDO ALDAPA 1225 S ROSEWOOD AVE, SANTA ANA, CA 92707. ENGINEER OF RECORD DATE:02/16/2023 REV:A DC SYSTEM SIZE: 8800W AC SYSTEM SIZE: 6380W CEC AC SYSTEM SIZE: 8013W MODULES: (22)URECO FBM400MFG-BB INVERTER: (22)ENPHASE IQ8PLUS-72-2-US(240V,1PH) BRANCH DETAILS: 2 BRANCH OF 11 MICRO INVERTERS (11 MODULES) CONTRACTOR INFORMATION 18271 MCDURMOTT W SUITE E, IRVINE, CA 92614. TEL.NO: 949-309-2453 LIC:#B/C10 - 1037212 MODULE SPECSHEET 1225 S Rosewood Ave03/14/23 PV-6.1 CUSTOMER INFORMATION NAME&ADDRESS: 33°43'54.17"N 117°52'53.71"W APN:013-024-23 AHJ:CA-CITY OF SANTA ANA UTILITY:SCE SYSTEM INFORMATION DESIGNER/CHECKED BY: SB/MR PROJECT NUMBER:GOSG-007806 SCALE:AS NOTED PAPER SIZE:17"x11" EVERARDO ALDAPA 1225 S ROSEWOOD AVE, SANTA ANA, CA 92707. ENGINEER OF RECORD DATE:02/16/2023 REV:A DC SYSTEM SIZE: 8800W AC SYSTEM SIZE: 6380W CEC AC SYSTEM SIZE: 8013W MODULES: (22)URECO FBM400MFG-BB INVERTER: (22)ENPHASE IQ8PLUS-72-2-US(240V,1PH) BRANCH DETAILS: 2 BRANCH OF 11 MICRO INVERTERS (11 MODULES) CONTRACTOR INFORMATION 18271 MCDURMOTT W SUITE E, IRVINE, CA 92614. TEL.NO: 949-309-2453 LIC:#B/C10 - 1037212 INVERTER SPECSHEET 1225 S Rosewood Ave03/14/23 PV-6.2 CUSTOMER INFORMATION NAME&ADDRESS: 33°43'54.17"N 117°52'53.71"W APN:013-024-23 AHJ:CA-CITY OF SANTA ANA UTILITY:SCE SYSTEM INFORMATION DESIGNER/CHECKED BY: SB/MR PROJECT NUMBER:GOSG-007806 SCALE:AS NOTED PAPER SIZE:17"x11" EVERARDO ALDAPA 1225 S ROSEWOOD AVE, SANTA ANA, CA 92707. ENGINEER OF RECORD DATE:02/16/2023 REV:A DC SYSTEM SIZE: 8800W AC SYSTEM SIZE: 6380W CEC AC SYSTEM SIZE: 8013W MODULES: (22)URECO FBM400MFG-BB INVERTER: (22)ENPHASE IQ8PLUS-72-2-US(240V,1PH) BRANCH DETAILS: 2 BRANCH OF 11 MICRO INVERTERS (11 MODULES) CONTRACTOR INFORMATION 18271 MCDURMOTT W SUITE E, IRVINE, CA 92614. TEL.NO: 949-309-2453 LIC:#B/C10 - 1037212 COMBINER SPECSHEET 1225 S Rosewood Ave03/14/23 PV-6.3 CUSTOMER INFORMATION NAME&ADDRESS: 33°43'54.17"N 117°52'53.71"W APN:013-024-23 AHJ:CA-CITY OF SANTA ANA UTILITY:SCE SYSTEM INFORMATION DESIGNER/CHECKED BY: SB/MR PROJECT NUMBER:GOSG-007806 SCALE:AS NOTED PAPER SIZE:17"x11" EVERARDO ALDAPA 1225 S ROSEWOOD AVE, SANTA ANA, CA 92707. ENGINEER OF RECORD DATE:02/16/2023 REV:A DC SYSTEM SIZE: 8800W AC SYSTEM SIZE: 6380W CEC AC SYSTEM SIZE: 8013W MODULES: (22)URECO FBM400MFG-BB INVERTER: (22)ENPHASE IQ8PLUS-72-2-US(240V,1PH) BRANCH DETAILS: 2 BRANCH OF 11 MICRO INVERTERS (11 MODULES) CONTRACTOR INFORMATION 18271 MCDURMOTT W SUITE E, IRVINE, CA 92614. TEL.NO: 949-309-2453 LIC:#B/C10 - 1037212 RACKING SPECSHEET 1225 S Rosewood Ave03/14/23 PV-6.4 CUSTOMER INFORMATION NAME&ADDRESS: 33°43'54.17"N 117°52'53.71"W APN:013-024-23 AHJ:CA-CITY OF SANTA ANA UTILITY:SCE SYSTEM INFORMATION DESIGNER/CHECKED BY: SB/MR PROJECT NUMBER:GOSG-007806 SCALE:AS NOTED PAPER SIZE:17"x11" EVERARDO ALDAPA 1225 S ROSEWOOD AVE, SANTA ANA, CA 92707. ENGINEER OF RECORD DATE:02/16/2023 REV:A DC SYSTEM SIZE: 8800W AC SYSTEM SIZE: 6380W CEC AC SYSTEM SIZE: 8013W MODULES: (22)URECO FBM400MFG-BB INVERTER: (22)ENPHASE IQ8PLUS-72-2-US(240V,1PH) BRANCH DETAILS: 2 BRANCH OF 11 MICRO INVERTERS (11 MODULES) CONTRACTOR INFORMATION 18271 MCDURMOTT W SUITE E, IRVINE, CA 92614. TEL.NO: 949-309-2453 LIC:#B/C10 - 1037212 MOUNT SPECSHEET 1225 S Rosewood Ave03/14/23 PV-6.5 CUSTOMER INFORMATION NAME&ADDRESS: 33°43'54.17"N 117°52'53.71"W APN:013-024-23 AHJ:CA-CITY OF SANTA ANA UTILITY:SCE SYSTEM INFORMATION DESIGNER/CHECKED BY: SB/MR PROJECT NUMBER:GOSG-007806 SCALE:AS NOTED PAPER SIZE:17"x11" EVERARDO ALDAPA 1225 S ROSEWOOD AVE, SANTA ANA, CA 92707. ENGINEER OF RECORD DATE:02/16/2023 REV:A DC SYSTEM SIZE: 8800W AC SYSTEM SIZE: 6380W CEC AC SYSTEM SIZE: 8013W MODULES: (22)URECO FBM400MFG-BB INVERTER: (22)ENPHASE IQ8PLUS-72-2-US(240V,1PH) BRANCH DETAILS: 2 BRANCH OF 11 MICRO INVERTERS (11 MODULES) CONTRACTOR INFORMATION 18271 MCDURMOTT W SUITE E, IRVINE, CA 92614. TEL.NO: 949-309-2453 LIC:#B/C10 - 1037212 GROUNDING SPECSHEET 1225 S Rosewood Ave03/14/23 PV-6.6 CUSTOMER INFORMATION NAME&ADDRESS: 33°43'54.17"N 117°52'53.71"W APN:013-024-23 AHJ:CA-CITY OF SANTA ANA UTILITY:SCE SYSTEM INFORMATION DESIGNER/CHECKED BY: SB/MR PROJECT NUMBER:GOSG-007806 SCALE:AS NOTED PAPER SIZE:17"x11" EVERARDO ALDAPA 1225 S ROSEWOOD AVE, SANTA ANA, CA 92707. ENGINEER OF RECORD DATE:02/16/2023 REV:A DC SYSTEM SIZE: 8800W AC SYSTEM SIZE: 6380W CEC AC SYSTEM SIZE: 8013W MODULES: (22)URECO FBM400MFG-BB INVERTER: (22)ENPHASE IQ8PLUS-72-2-US(240V,1PH) BRANCH DETAILS: 2 BRANCH OF 11 MICRO INVERTERS (11 MODULES) CONTRACTOR INFORMATION 18271 MCDURMOTT W SUITE E, IRVINE, CA 92614. TEL.NO: 949-309-2453 LIC:#B/C10 - 1037212 INTEGRATED GROUNDING SPECSHEET 1225 S Rosewood Ave03/14/23 PV-6.7 CUSTOMER INFORMATION NAME&ADDRESS: 33°43'54.17"N 117°52'53.71"W APN:013-024-23 AHJ:CA-CITY OF SANTA ANA UTILITY:SCE SYSTEM INFORMATION DESIGNER/CHECKED BY: SB/MR PROJECT NUMBER:GOSG-007806 SCALE:AS NOTED PAPER SIZE:17"x11" EVERARDO ALDAPA 1225 S ROSEWOOD AVE, SANTA ANA, CA 92707. ENGINEER OF RECORD DATE:02/16/2023 REV:A DC SYSTEM SIZE: 8800W AC SYSTEM SIZE: 6380W CEC AC SYSTEM SIZE: 8013W MODULES: (22)URECO FBM400MFG-BB INVERTER: (22)ENPHASE IQ8PLUS-72-2-US(240V,1PH) BRANCH DETAILS: 2 BRANCH OF 11 MICRO INVERTERS (11 MODULES) CONTRACTOR INFORMATION 18271 MCDURMOTT W SUITE E, IRVINE, CA 92614. TEL.NO: 949-309-2453 LIC:#B/C10 - 1037212 FIRE RATING CERTIFICATE 1225 S Rosewood Ave03/14/23 Rev: 7/15/2021 RESIDENTIAL PHOTOVOLTAIC CHECKLIST SOL-01 CBC 2019 Solar Photovoltaic (PV) Checklist for Detached SINGLE FAMILY RESIDENCES Only Instructions: The licensed contractor of record shall complete all sections, answer the ten questions and sign the certification section below. A copy of this form shall be attached to each of TWO sets of plans, of minimum 11” x 17” size. If answering NO to any of the questions, plan check shall be required. Project Address: Contractor Company Name: Contractor License Number: YES NO Are the following applicable to the proposed project? 1. ‰ ‰ Will the PV system layout provide the required three-foot wide clear access pathways per Section 605.11 of the California Fire Code, and is this shown on the roof plan? 2. ‰ ‰ Will the PV system be installed on a roof having only one roofing layer with no overlays? 3. ‰ ‰ Will the PV array be flush mounted to the existing roof so that the plane of the modules (panels) are parallel to the plane of the roof? 4. ‰ ‰ Will the PV system weigh maximum 4 pounds per square feet or less? 5. ‰ ‰ Will the PV system be installed where the modules do not overhang any roof edges (such as eaves, gabled ends, ridges and hips)? 6. ‰ ‰ Will the PV system be installed with a space of 2” minimum to 10” maximum between the underside of modules and the surface of the roof? 7. ‰ ‰ Will the PV system be installed without using any ballast system or counter-weight system? 8. ‰ ‰ Will the anchors be installed with a maximum horizontal anchor spacing of 6 feet and is this maximum horizontal spacing shown on the plans? 9. ‰ ‰ Will the minimum 5/16” lag screws be installed with a minimum of 2-1/2 inch embedment into roof rafters (with pre-drilled holes) and is this minimum embedment shown on the plans? 10. ‰ ‰ Are ALL the structural pages of the plans stamped and signed by a California licensed professional engineer? (including project specific site plan, PV layout, anchorage spacing, anchorage details and manufacturer’s PV support information.) I certify under penalty of perjury under the laws of the State of California that the above is true: Print Name: Signature: Phone Number: Date: Email Address: Planning & Building Agency Building Safety Division 20 Civic Center Plaza P.O. Box 1988 (M-19) Santa Ana, CA 92702 (714) 647-5800 www.santa-ana.org 1225 S Rosewood Ave03/14/23 12/10/2022 RE: Structural Certification for Installation of Residential Solar EVERARDO ALDAPA:1225 S ROSEWOOD AVE, SANTA ANA, CA 92707 2019 California Building Code (ASCE 7-16) Risk category II Wind Load (component and Cladding) Roof Dead Load Dr 10 psf V 96 mph PV Dead Load DPV 3 psf Exposure C Roof Live Load Lr 20 psf Ground Snow S 0 psf If you have any questions on the above, please do not hesitate to call. Sincerely, Eugene Munyanziza, P.E.Signed: 12/10/2022 EV Engineering, LLC projects@evengineersnet.com http://www.evengineersnet.com Exp: 06/30/2024 Attn: To Whom It May Concern This Letter is for the existing roof framing which supports the new PV modules as well as the attachment of the PV system to existing roof framing. From the field observation report, the roof is made of Composition shingle roofing over roof plywood supported by 2X4 Rafters at 24 inches and 2X6 Rafters at 16 inches. The slopes of the roof were approximated to be 20 and 1 degrees and the allowable maximum rafter span is 6 feet between supports. After review of the field observation data and based on our structural capacity calculation, the existing roof framing has been determined to be adequate to support the imposed loads without structural upgrades. Contractor shall verify that existing framing is consistent with the described above before install. Should they find any discrepancies, a written approval from SEOR is mandatory before proceeding with install. Capacity calculations were done in accordance with applicable building codes. Design Criteria projects@evengineersnet.com http://www.evengineersnet.com Code 1225 S Rosewood Ave03/14/23 Structural Letter for PV Installation Date: 12/10/2022 Job Address: 1225 S ROSEWOOD AVE SANTA ANA, CA 92707 Job Name: EVERARDO ALDAPA Job Number: 221210EA Scope of Work Table of Content Sheet 1 Cover 2 Attachment Uplift checks 3 Roof Framing Check 4 Seismic Check and Scope of work Engineering Calculations Summary Code 2019 California Building Code (ASCE 7-16) Risk category II Roof Dead Load Dr 10 psf PV Dead Load DPV 3 psf Roof Live Load Lr 20 psf Ground Snow S 0 psf Wind Load (component and Cladding) V 96 mph Exposure C References NDS for Wood Construction Sincerely, Signed: 12/10/2022 Eugene Munyanziza, P.E. EV Engineering, LLC projects@evengineersnet.com http://www.evengineersnet.com Exp: 06/30/2024 This Letter is for the existing roof framing which supports the new PV modules as well as the attachment of the PV system to existing roof framing. All PV mounting equipment shall be designed and installed per manufacturer's approved installation specifications. projects@evengineersnet.com http://www.evengineersnet.com 1225 S Rosewood Ave03/14/23 Wind Load Cont. 96 mph ASCE 7-16 Figure 26.5-1B C 1.0 ASCE 7-16 Sec 26.8.2 0.85 ASCE 7-16 Table 26.10-1 0.85 ASCE 7-16 Table 26.6-1 1.00 ASCE 7-16 Table 26.9-1 16.65 psf 20.0 Degrees 1.5 Conservatively assuming all exposed 0.8 conservatively assuming 10 ft2 effective area Uplift (W)Zone(1) Zone(2r) Zone(2e)Zone(3) Fig. 30-3-2 GCp=-2.1 -2.6 -2.7 -2.7 Eq. 29.4-7 P=qh(GCp)(γE)(γa)=-41.95 -51.94 -53.94 -53.94 GCp=0.3 Figure 30.3-2 P=qh(GCp)(γE)(γa)=4.50 Equation 29.4-7 Rafter Attachments: 0.6D+0.6W (CD=1.6) Connection Check Attachment max. spacing= 6 ft 5/16" Lag Screw Withdrawal Value= 266 lbs/in Table 12.2A - NDS 2.5 in DFL Assumed Prying Coefficient 1.4 Allowable Capacity= 760 lbs Zone Trib Width Area (ft) Uplift (lbs) Down (lbs) Zone(1) 6 16.5 333.8 123.7 Zone(2r) 6 16.5 408.0 123.7 Zone(2e) 6 16.5 422.8 123.7 Zone(3) 6 16.5 422.8 123.7 Conservative Max= 422.8 < 760 CONNECTION IS OK 2. Embedment is measured from the top of the framing member to the tapered tip of a lag screw. Embedment in sheading or other material does not count. II V= Exposure = 1. Pv seismic dead weight is negligible to result in significant seismic uplift, therefore the wind uplift governs γE= γa= KZt = qh= 0.00256KzKztKdKeV2= Pitch = Lag Screw Penetration Risk Category = KZ = Kd = Ke = projects@evengineersnet.com http://www.evengineersnet.com 1225 S Rosewood Ave03/14/23 Vertical Load Resisting System Design Roof Framing Rafters Snow Load Fully Exposed pg= 0 psf Ct =1.1 Ce = 0.9 Is =1.0 pf = 0 psf pfmin. = 0.0 psf ps =0 psf Conservatively (Cs=1) 0 plf Max Length, L = 6.0 ft (Rafter maximum Allowable Horizontal Span) Tributary Width, WT = 24in Dr = 10 psf 20 plf PvDL = 3 psf 18 plf Load Case: DL+0.75(0.6W+S) 0.75(Pnet+Ps)+ Ppvcos(θ)+PDL= 42 plf Mdown= 189 lb-ft Mallowable = Sx x Fb' (wind)= 456 lb-ft > 189 lb-ft OK Load Case: DL+S Ps+ Ppvcos(θ)+PDL= 38 plf Mdown= 171 lb-ft Mallowable = Sx x Fb' (wind)= 456 lb-ft > 171 lb-ft OK Load Case: DL+0.6W Pnet+ Ppvcos(θ)+PDL= 43.4 plf Max Moment, Mu= 195 lb-ft Mallowable = Sx x Fb' (wind)= 634 lb-ft > 195 lb-ft OK Pv max Shear= 123.7 lbs Shear, Vu=wL/2+Pv Point Load = 238 lbs Max Shear, Vu=wL/2+Pv Point Load = 238 lb Member Capacity DF-L No.2 2X4 CL CF Ci Cr KF φ λ Fb = 900 psi 1.0 1.5 1.0 1.15 2.54 0.85 0.8 1553 psi Fv = 180 psi N/A N/A 1.0 N/A 2.88 0.75 0.8 180 psi E = 1600000 psi N/A N/A 1.0 N/A N/A N/A N/A 1600000 psi Emin = 580000 psi N/A N/A 1.0 N/A 1.76 0.85 N/A 580000 psi Depth, d = 3.5 in Width, b = 1.5 in Cross-Sectonal Area, A = 5.25 in2 Moment of Inertia, Ixx = 5.35938 in4 Section Modulus, Sxx = 3.0625 in Allowable Moment, Mall = Fb'Sxx = 396.2 lb-ft DCR=Mu/Mall = 0.42 < 1 Satisfactory Allowable Shear, Vall = 2/3Fv'A = 630.0 lb DCR=Vu/Vall = 0.38 < 1 Satisfactory Design Value Adjusted Value projects@evengineersnet.com http://www.evengineersnet.com 1225 S Rosewood Ave03/14/23 Siesmic Loads Check Roof Dead Load 10psf % or Roof with Pv 30% Dpv and Racking 3 psf Average Total Dead Load 10.9 psf Increase in Dead Load 3.6%OK The increase in seismic Dead weight as a result of the solar system is less than 10% of the existing structure and therefore no further seismic analysis is required. Limits of Scope of Work and Liability We have based our structural capacity determination on information in pictures and a drawing set titled PV plans - EVERARDO ALDAPA. The analysis was according to applicable building codes, professional engineering and design experience, opinions and judgments. The calculations produced for this dwelling's assessment are only for the proposed solar panel installation referenced in the stamped plan set and were made according to generally recognized structural analysis standards and procedures. projects@evengineersnet.com http://www.evengineersnet.com 1225 S Rosewood Ave03/14/23 1225 S Rosewood Ave03/14/23