HomeMy WebLinkAbout1505 W 11th St - PlanPHOTOVOLTAIC ROOF MOUNT SYSTEM 13 MODULES - SYSTEM SIZE STC (5.200 kW DC / 3.770 kW AC, 4.707kW AC CEC) 1505 WEST 11TH STREET, SANTA ANA, CA 92703, USA (33.7544133, -117.8888065) SYSTEM SUMMARY STC (5.200 kW DC / 3.770 kW AC, 4.707kW AC CEC) STC DC: (13) 400W = 5.200 kW STC AC: (13) 290W = 3.770 kW, 4.707kW AC CEC ● (13) AXITEC AC-400MBT108V MODULES ● (13) ENPHASE ENERGY INC. IQ8PLUS-72-2-US 240V MICROINVERTERS ● 1x BRANCH OF 13 CONNECTED IN PARALLEL GOVERNING CODES ● 2022 CALIFORNIA FIRE CODE ● 2022 CALIFORNIA BUILDING CODE ● 2022 CALIFORNIA RESIDENTIAL CODE ● 2022 CALIFORNIA ELECTRICAL CODE GENERAL NOTES 1) ALL PANELS, SWITCHES, ETC. SHALL HAVE SUFFICIENT GUTTER SPACE AND LUGS IN COMPLIANCE WITH UL REQUIREMENTS TO ACCOMMODATE CONDUCTORS SHOWN. 2) THIS SYSTEM WILL NOT BE INTERCONNECTED UNTIL APPROVAL FROM THE LOCAL JURISDICTION AND UTILITY IS OBTAINED. 3) ALL EXTERIOR ELECTRICAL DEVICES AND EQUIPMENT INCLUDING THOSE THAT ARE EXPOSED TO OUTSIDE ENVIRONMENT SHALL BE WEATHERPROOF AND SHALL BE LISTED BY 'UL' FOR THE TYPE OF APPLICATION AND 'UL' LABEL SHALL APPEAR ON ALL ELECTRICAL EQUIPMENT. 4) WIRING METHOD SHALL BE EMT ABOVE GROUND MOUNTED IN CONCEALED SPACES (UNLESS APPROVED OTHERWISE) AND SCHEDULE-40 PVC FOR BELOW GROUND INSTALLATIONS UNLESS NOTED OTHERWISE. 5) AN OSHA APPROVED LADDER PROVIDING ACCESS TO ALL PORTIONS OF THE ARRAY SHALL BE SECURED IN PRIOR TO REQUESTING INSPECTION. 6) IT IS THE CONTRACTOR'S RESPONSIBILITY TO INSTALL A SUPPLEMENTAL GROUNDING ELECTRODE CONDUCTOR IF NECESSARY. 7) OCCUPANCY TYPE: R-3 8) CONSTRUCTION TYPE: VB ARRAY LOCATION PROJECT SITE 1 1 2 ' - 5 " 1 1 2 ' - 5 " 53'-11" 28 ' - 2 " 53'-11" 22'-4" 27 ' - 2 " 4'-1" MS P UM AC D CB SHEET NAME SHEET SIZE SHEET NUMBER ANSI B REVISIONS PV-1 HOMEOWNER INFO 11" X 17" SIGNATURE & SEAL LU I S O L I V A R E S 1 5 0 5 W E S T 1 1 T H S T R E E T , SA N T A A N A , C A 9 2 7 0 3 , U S A APN: 405-152-27 EMAIL: N/A PHONE: N/A REVDATE DESCRIPTION CONTRACTOR: NERD POWER DESIGNER: ABHISHEK MAHESH ADDRESS: 2065 W OBISPO AVE #102 GILBERT, AZ 85233 USA PHONE: 8665722637 LICENSE #: CA-1019100 FRESH08/24/2023 ORIGINAL PLAN COVER PAGE SCALE: 1/16" = 1'-0" SITE PLAN & SAFETY PLAN HOUSE PHOTO SCALE: NTS VICINITY MAP SCALE: NTS MSP MAIN SERVICE PANEL (EXISTING, 100A) UM UTILITY METER (EXISTING) PM PRODUCTION METER (N/A) BAT BATTERY (N/A) INV (0) INVERTER (N/A) CB LOAD CENTER (COMBINER BOX) (NEW) SM SOLAREDGE METER (N/A) BLP BACKUP LOAD PANEL (N/A) ACD AC DISCONNECT (NEW) ACF AC DISCONNECT FUSED (N/A) JB JUNCTION BOX (NEW) AT AUTO TRANSFORMER (N/A) SUB SUBPANEL (N/A) DCD DC DISCONNECT (N/A) DCC DC COMBINER (N/A) EE EXISTING EQUIPMENT LE G E N D PV MODULE DIMENSIONS PROPERTY LINE FENCE GATE DRIVEWAY AHJ - SANTA ANA UTILITY - SCE ACCOUNT # - CA-R-206916 SHEET INDEX PV-1 COVER PAGE PV-2 ROOF PLAN WITH MODULES PV-3 ATTACHMENT DETAIL PV-4 THREE LINE DIAGRAM PV-5 WIRING CALCULATION PV-6 PLACARDS PV-6.1 EQUIPMENT ELEVATION PV-7-15 EQUIPMENT SPECIFICATION PV-16 PROPOSED EQUIPMENT PLACEMENTS AHJ: SANTA ANA (CITY OF), CALIFORNIA UTILITY: SOUTHERN CALIFORNIA EDISON CO 1 505 WEST 1 1 TH STREET (E)MAIN SERVICE PANEL, 100A RATED, 240V (FLUSH MOUNT) (N)ENPHASE COMBINER BOX (N)AC DISCONNECT (E)UTILITY METER ROOF #01 (13)AXITEC AC-400MBT108V 400W MODULES ROOF ACCESS POINT (E)FENCE PROPERTY LINE PROPERTY LINE PR O P E R T Y L I N E PR O P E R T Y L I N E EX I S T I N G DR I V E W A Y 1-STORY HOUSE (E)DETACHED STRUCTURE (E)GATE (TYP.) (E)SHED SIGNED ON: 11 /30/2023 Structural Only Bldg# 101117593 Elec# 20181627 Issued 12/04/23 The scope of the plans is for the installation of the solar photovoltaic system only and the approval is subject to compliance with all applicable city and state codes and regulations regarding construction. The approval of the plans does not constitute any certification of the accuracy, completeness, or building permit status of the existing buildings and structures as shown. 1505 W 11th St 12/4/2023 PV-10 SHEET NAME SHEET SIZE SHEET NUMBER ANSI B REVISIONS PV-10 HOMEOWNER INFO 11" X 17" SIGNATURE & SEAL LU I S O L I V A R E S 15 0 5 W E S T 1 1 T H S T R E E T , SA N T A A N A , C A 9 2 7 0 3 , U S A APN: 405-152-27 EMAIL: N/A PHONE: N/A REVDATEDESCRIPTION CONTRACTOR: NERD POWER DESIGNER: ABHISHEK MAHESH ADDRESS: 2065 W OBISPO AVE #102 GILBERT, AZ 85233 USA PHONE: 8665722637 LICENSE #: CA-1019100 FRESH08/24/2023ORIGINAL PLAN EQUIPMENT SPECIFICATION SIGNED ON: 11/30/2023 Structural Only 1505 W 11th St 12/4/2023 PV-11 SHEET NAME SHEET SIZE SHEET NUMBER ANSI B REVISIONS PV-11 HOMEOWNER INFO 11" X 17" SIGNATURE & SEAL LU I S O L I V A R E S 15 0 5 W E S T 1 1 T H S T R E E T , SA N T A A N A , C A 9 2 7 0 3 , U S A APN: 405-152-27 EMAIL: N/A PHONE: N/A REVDATEDESCRIPTION CONTRACTOR: NERD POWER DESIGNER: ABHISHEK MAHESH ADDRESS: 2065 W OBISPO AVE #102 GILBERT, AZ 85233 USA PHONE: 8665722637 LICENSE #: CA-1019100 FRESH08/24/2023ORIGINAL PLAN EQUIPMENT SPECIFICATION SIGNED ON: 11/30/2023 Structural Only 1505 W 11th St 12/4/2023 PV-12 SHEET NAME SHEET SIZE SHEET NUMBER ANSI B REVISIONS PV-12 HOMEOWNER INFO 11" X 17" SIGNATURE & SEAL LU I S O L I V A R E S 15 0 5 W E S T 1 1 T H S T R E E T , SA N T A A N A , C A 9 2 7 0 3 , U S A APN: 405-152-27 EMAIL: N/A PHONE: N/A REVDATEDESCRIPTION CONTRACTOR: NERD POWER DESIGNER: ABHISHEK MAHESH ADDRESS: 2065 W OBISPO AVE #102 GILBERT, AZ 85233 USA PHONE: 8665722637 LICENSE #: CA-1019100 FRESH08/24/2023ORIGINAL PLAN EQUIPMENT SPECIFICATION SIGNED ON: 11/30/2023 Structural Only 1505 W 11th St 12/4/2023 PV-13 SHEET NAME SHEET SIZE SHEET NUMBER ANSI B REVISIONS PV-13 HOMEOWNER INFO 11" X 17" SIGNATURE & SEAL LU I S O L I V A R E S 15 0 5 W E S T 1 1 T H S T R E E T , SA N T A A N A , C A 9 2 7 0 3 , U S A APN: 405-152-27 EMAIL: N/A PHONE: N/A REVDATEDESCRIPTION CONTRACTOR: NERD POWER DESIGNER: ABHISHEK MAHESH ADDRESS: 2065 W OBISPO AVE #102 GILBERT, AZ 85233 USA PHONE: 8665722637 LICENSE #: CA-1019100 FRESH08/24/2023ORIGINAL PLAN EQUIPMENT SPECIFICATION SIGNED ON: 11/30/2023 Structural Only 1505 W 11th St 12/4/2023 PV-14 SHEET NAME SHEET SIZE SHEET NUMBER ANSI B REVISIONS PV-14 HOMEOWNER INFO 11" X 17" SIGNATURE & SEAL LU I S O L I V A R E S 15 0 5 W E S T 1 1 T H S T R E E T , SA N T A A N A , C A 9 2 7 0 3 , U S A APN: 405-152-27 EMAIL: N/A PHONE: N/A REVDATEDESCRIPTION CONTRACTOR: NERD POWER DESIGNER: ABHISHEK MAHESH ADDRESS: 2065 W OBISPO AVE #102 GILBERT, AZ 85233 USA PHONE: 8665722637 LICENSE #: CA-1019100 FRESH08/24/2023ORIGINAL PLAN EQUIPMENT SPECIFICATION SIGNED ON: 11/30/2023 Structural Only 1505 W 11th St 12/4/2023 MODULE AREA & WEIGHT CALCULATIONS PANEL TYPES (COUNT, AREA, WEIGHT): ● (13x) AXITEC AC-400MBT108V (67.8" x 44.6", 47.4 LB) MICRO-INVERTER TYPES (COUNT, WEIGHT): ● (13x) ENPHASE ENERGY INC. IQ8PLUS-72-2-US 240V (2.38 LB) ATTACHMENT COUNT: 46 MOUNTING SYSTEM WEIGHT/MODULE: 1.5 LB TOTAL ROOF AREA: 2061 SF NEW PANELS: ● TOTAL AREA: (13) 67.8" x 44.6" = 273 SF ● TOTAL WEIGHT: (13) 47.4 + (13) 2.4 + (13) 1.5 = 667 LB ● WEIGHT PER CONNECTION: 667 LB / 46 = 14.50 LB ● DISTRIBUTED LOAD: 667 LB / 273 SF = 2.44 PSF ● ROOF AREA COVERED: 273 SF / 2061 SF = 13.3% BILL OF MATERIALS EQUIPMENT QTY DESCRIPTION SOLAR PV MODULES 13 AXITEC AC-400MBT108V MICRO INVERTERS 13 ENPHASE ENERGY INC. IQ8PLUS-72-2-US 240V JUNCTION BOX (AC)1 JUNCTION BOX 600V, NEMA 3R UL LISTED COMBINER BOX 1 125A ENPHASE 4C X-IQ-AM1-240-4C COMBINER BOX AC DISCONNECT 1 AC DISCONNECT EATON#DG221URB 30A, 2P,240VAC NEMA 3R ATTACHMENTS 46 CHIKOUSA COMPOSITION L-FOOT ATTACHMENT RAIL 13 CHIKOUSA ASPHALT ROOF RACKING 134" RAIL 0 CHIKOUSA ASPHALT ROOF RACKING 166" RAIL SPLICES 8 RAIL SPLICES MID CLAMPS 18 MID CLAMPS END CLAMPS 16 END CLAMPS GROUNDING LUG 4 GROUNDING LUG ROOF DESCRIPTION TABLE ROOF PLANE ROOF PITCH ROOF AZIMUTH RAFTER SIZE RAFTER SPACING ATTACHMENT SPACING MODULES (PITCH) #1 23° 180°2" x 4"24" O.C. 48" O.C.13 (23°) ROOF ACCESS POINT ● SHALL BE LOCATED IN AREAS THAT DO NOT REQUIRE THE PLACEMENT OF GROUND LADDERS OVER OPENINGS SUCH AS WINDOWS OR DOORS, AND LOCATED AT STRONG POINTS OF BUILDING CONSTRUCTION IN LOCATIONS WHERETHE ACCESS POINT DOES NOT CONFLICT WITH OVERHEAD OBSTRUCTIONS SUCH AS TREE LIMBS, WIRES OR SIGNS. 36 " F I R E S E T B A C K 18 " F I R E S E T B A C K 36" FIRE SETBACK 18" FIRE SETBACK 18 " F I R E S E T B A C K 18" FIRE SETBACK 1'-6"28'-7"3'-6" 2' - 4 " 10 ' - 5 " 2' - 8 " MS P UM AC D CB JB SHEET NAME SHEET SIZE SHEET NUMBER ANSI B REVISIONS PV-2 HOMEOWNER INFO 11" X 17" SIGNATURE & SEAL LU I S O L I V A R E S 15 0 5 W E S T 1 1 T H S T R E E T , SA N T A A N A , C A 9 2 7 0 3 , U S A APN: 405-152-27 EMAIL: N/A PHONE: N/A REVDATEDESCRIPTION CONTRACTOR: NERD POWER DESIGNER: ABHISHEK MAHESH ADDRESS: 2065 W OBISPO AVE #102 GILBERT, AZ 85233 USA PHONE: 8665722637 LICENSE #: CA-1019100 FRESH08/24/2023ORIGINAL PLAN ROOF PLAN WITH MODULES SCALE: 1/8" = 1'-0" ROOF PLAN WITH MODULES MSP MAIN SERVICE PANEL (EXISTING, 100A) UM UTILITY METER (EXISTING) PM PRODUCTION METER (N/A) BAT BATTERY (N/A) INV (0) INVERTER (N/A) CB LOAD CENTER (COMBINER BOX (NEW) SM SOLAREDGE METER (N/A) BLP BACKUP LOAD PANEL (N/A) ACF AC DISCONNECT FUSED (N/A) JB JUNCTION BOX (NEW) AT AUTO TRANSFORMER (N/A) SUB SUBPANEL (N/A) DCD DC DISCONNECT (N/A) DCC DC COMBINER (N/A) EE EXISTING EQUIPMENT LE G E N D PV MODULE ROOF ATTACHMENT DIMENSIONS ROOF CONNECTION RAFTERS RAIL OBSTRUCTION CONDUIT MICRO-INVERTER ACD AC DISCONNECT (NEW) (E) MAIN SERVICE PANEL, 100A RATED, 240V (FLUSH MOUNT) (N) ENPHASE COMBINER BOX (N) AC DISCONNECT (E) UTILITY METER ROOF #01 (13) AXITEC AC-400MBT108V 400W MODULES ROOF ACCESS POINT (N) CHIKO ASPHALT ROOF RACKING SYSTEM (46) CHIKOUSA COMPOSITION L-FOOT ATTACHMENTS @48" O.C. (13) ENPHASE : IQ8PLUS-72-2-US MICRO INVERTERS CIRCUIT 1 (E) FRONT OF HOUSE 1505 WEST 11TH STREET (E) BACK OF RESIDENCE (N) JUNCTION BOX 3/4" EMT CONDUIT RUN ON ROOF ROOF 01 PITCH 23° AZIMUTH 180° (E) DETACHED STRUCTURE (E) MAIN HOUSE CONDUIT (N) 18"D x 12"W (~7') TRENCH (N) 2" PVC CONDUIT RUN UNDERGROUND SIGNED ON: 11/30/2023 Structural Only 1505 W 11th St 12/4/2023 SHEET NAME SHEET SIZE SHEET NUMBER ANSI B REVISIONS PV-3 HOMEOWNER INFO 11" X 17" SIGNATURE & SEAL LU I S O L I V A R E S 15 0 5 W E S T 1 1 T H S T R E E T , SA N T A A N A , C A 9 2 7 0 3 , U S A APN: 405-152-27 EMAIL: N/A PHONE: N/A REVDATEDESCRIPTION CONTRACTOR: NERD POWER DESIGNER: ABHISHEK MAHESH ADDRESS: 2065 W OBISPO AVE #102 GILBERT, AZ 85233 USA PHONE: 8665722637 LICENSE #: CA-1019100 FRESH08/24/2023ORIGINAL PLAN ATTACHMENT DETAIL SCALE: NTS ATTACHMENT DETAIL SCALE: NTS ATTACHMENT DETAIL (ENLARGED SECTION VIEW) PV MODULE SEE (2/PV-3) FOR ENLARGED VIEW (E) SINGLE LAYER OF COMP SHINGLE PV MODULE CHIKOUSA FLASHING COMPOSITION L-FOOT ATTACHMENT (E) SINGLE LAYER OF COMP SHINGLE GROUNDING & END/MID CLAMP CHIKO ASPHALT RACKING SYSTE 2"x4" RAFTERS @ 24" O.C. 6" M I N . 2"X4" R A F T E R S @ 2 4 O . C . 5/16" x 3 1/2" SS LAG BOLT INTO RAFTER(S) 2 1/2" MIN. PENETRATION SEALED W/ GEOCEL. CHIKOUSA CHANNEL NUT SIGNED ON: 11/30/2023 Structural Only 1505 W 11th St 12/4/2023 SYSTEM SUMMARY STC (5.200 kW DC / 3.770 kW AC, 4.707kW AC CEC) STC DC: (13) 400W = 5.200 kW STC AC: (13) 290W = 3.770 kW, 4.707kW AC CEC ● (13) AXITEC AC-400MBT108V MODULES ● (13) ENPHASE ENERGY INC. IQ8PLUS-72-2-US 240V MICROINVERTERS ● 1x BRANCH OF 13 CONNECTED IN PARALLEL 1 1 2 G 21 1 2 G 13 MOD: AXITEC AC-400MBT108V INV: ENPHASE ENERGY INC. IQ8PLUS-72-2-US 240V (1 BRANCH X 13 MICRO-INV) 1 2 G N JUNCTION BOX 600V, NEMA 3R UL LISTED G N GATEWAY - - - 20A(N) 15A IQ COMBINER 4C G N 1 2 1 2 ON OFF AC DISCONNECT EATON#DG221URB 30A, 2P,240VAC NEMA 3R G N TO UTILITY GRID M 20A(N) 100A(E) MAIN SERVICE PANEL (EXISTING, CENTER-FED) (FLUSH MOUNTED) BUS RATING: 100A MAIN BREAKER: 100A (E) BI-DIRECTIONAL UTILITY METER METER NO: 222013-571864 UTILITY: SOUTHERN CALIFORNIA EDISON CO SERVICE: 240V 60HZ 1PH 12 AWG Q-CABLE 06 AWG Cu BARE G (BOND RACKING) GROUND ROD MS-01 MCB-01 LC-01 LC-01 AC wire details Wire Min Ampacity Live Neutral Ground Min EMT Min PVC Min RMC MS-01 19.66A 12 AWG (Q-Cable)-06 AWG BARE (NOT IN CONDUIT)--- MCB-01 19.66A (2) 10 AWG THWN-2 10 AWG THWN-2 10 AWG THWN-2 - 2 in - LC-01 19.66A (2) 10 AWG THWN-2 10 AWG THWN-2 10 AWG THWN-2 3/4 in 3/4 in 3/4 in UTILITY FEED + TOTAL BACKFEED 100A + 20A = 120A LESS OR EQUAL TO BUS RATING x 120% 100A x 120% = 120A INTERCONNECTION 120% RULE (MAIN PANEL) CALCULATION ENSURES BUS IS SAFE REGARDLESS OF LOADS Isc(25°C) = 13.79A, Tisc = 0.045%/°C Isc(T) = Isc(25°C) x [1 + Tisc x (T-25°C)] Isc(2°C) = 13.65A, Isc(31°C) = 13.83A Voc(25°C) = 37.07V, Tvoc = -0.280%/°C Voc(T) = Voc(25°C) x [1 + Tvoc x (T-25°C)] Voc(2°C) = 39.46V, Voc(31°C) = 36.45V EXTREME CASE MODULE OUTPUT (AXITEC AC-400MBT108V)ELECTRICAL NOTES 1) ALL GROUNDING TO COMPLY WITH NEC 690.47. 2) ROOFTOP CONDUIT SHALL BE LOCATED MIN. 7/8" ABOVE ROOF SURFACE. 3) ALL TERMINALS SHALL BE MIN. 75°C RATED. 4) IQ GATEWAY BREAKER DETERMINED AT FACTORY BY MANUFACTURER (10A or 15A). 5) FOR IQ GATEWAY: USE SINGLE CT FOR PV PRODUCTION (L1 FROM ALL PV BRANCH CIRCUITS). USE DOUBLE CTs FOR CONSUMPTION (L1 AND L2 FEEDING MSP MAIN BREAKER, SERVICE SIDE). (N) SURGE PROTECTOR PER CEC 2022 - 230.67 (N) 2" PVC CONDUIT RUN (N) 18"D x 12"W (~7') TRENCH IN MAIN PANEL REPLACE (4) 20A 1P BREAKERS WITH (2) NEW 20/20A 1-1P TWIN BREAKERS. SHEET NAME SHEET SIZE SHEET NUMBER ANSI B REVISIONS PV-4 HOMEOWNER INFO 11" X 17" SIGNATURE & SEAL LU I S O L I V A R E S 15 0 5 W E S T 1 1 T H S T R E E T , SA N T A A N A , C A 9 2 7 0 3 , U S A APN: 405-152-27 EMAIL: N/A PHONE: N/A REVDATEDESCRIPTION CONTRACTOR: NERD POWER DESIGNER: ABHISHEK MAHESH ADDRESS: 2065 W OBISPO AVE #102 GILBERT, AZ 85233 USA PHONE: 8665722637 LICENSE #: CA-1019100 FRESH08/24/2023ORIGINAL PLAN THREE LINE DIAGRAM SCALE: NTS ELECTRICAL THREE LINE DIAGRAM 1505 W 11th St 12/4/2023 AC wire details WireID #Modules Nominal Voltage Backfeed *1.25 /cond. set Min OCPD Total Power Conductor sets ccConductors /conduit Expected max temp Adjusted ampacity (ampacity x temp derate x conduit fill derate) Conductor & neutral size EGC size (Cu) Conductor metal Max length V drop Min EMT size Min PVC size Min RMC size MS-01 13 240 V 19.66 A 20 A 3.8 kW 1 2 31 25 x 0.94 x - = 23.50 A 12 AWG (Q-Cable)06 AWG BARE (NOT IN CONDUIT)Cu 50 ft 1.12 %--- MCB-01 13 240 V 19.66 A 20 A 3.8 kW 1 2 31 35 x 0.94 x 1.00 = 32.90 A 10 AWG THWN-2 10 AWG THWN-2 Cu 50 ft 0.67 %-2 in - LC-01 13 240 V 19.66 A 20 A 3.8 kW 1 2 31 35 x 0.94 x 1.00 = 32.90 A 10 AWG THWN-2 10 AWG THWN-2 Cu 10 ft 0.13 %3/4 in 3/4 in 3/4 in UTILITY FEED + TOTAL BACKFEED 100A + 20A = 120A LESS OR EQUAL TO BUS RATING x 120% 100A x 120% = 120A INTERCONNECTION 120% RULE (MAIN PANEL) CALCULATION ENSURES BUS IS SAFE REGARDLESS OF LOADS Isc(25°C) = 13.79A, Tisc = 0.045%/°C Isc(T) = Isc(25°C) x [1 + Tisc x (T-25°C)] Isc(2°C) = 13.65A, Isc(31°C) = 13.83A Voc(25°C) = 37.07V, Tvoc = -0.280%/°C Voc(T) = Voc(25°C) x [1 + Tvoc x (T-25°C)] Voc(2°C) = 39.46V, Voc(31°C) = 36.45V EXTREME CASE MODULE OUTPUT (AXITEC AC-400MBT108V) ELECTRICAL NOTES 1)ALL EQUIPMENT TO BE LISTED BY UL OR OTHER NRTL, AND LABELED FOR ITS APPLICATION. 2)ALL CONDUCTORS SHALL BE COPPER, RATED FOR 600V AND 90°C WET ENVIRONMENT. 3)WIRING, CONDUIT, AND RACEWAYS MOUNTED ON ROOFTOPS SHALL BE ROUTED DIRECTLY TO, AND LOCATED AS CLOSE AS POSSIBLE TO THE NEAREST RIDGE, HIP, OR VALLEY. 4)WORKING CLEARANCES AROUND ALL NEW AND EXISTING ELECTRICAL EQUIPMENT SHALL COMPLY WITH NEC 110.26. 5)DRAWINGS INDICATE THE GENERAL ARRANGEMENT OF SYSTEMS. CONTRACTOR SHALL FURNISH ALL NECESSARY OUTLETS, SUPPORTS, FITTINGS AND ACCESSORIES TO FULFILL APPLICABLE CODES AND STANDARDS. 6)WHERE SIZES OF JUNCTION BOXES, RACEWAYS, AND CONDUITS ARE NOT SPECIFIED, THE CONTRACTOR SHALL SIZE THEM ACCORDINGLY. 7)ALL WIRE TERMINATIONS SHALL BE APPROPRIATELY LABELED AND READILY VISIBLE. 8)MODULE GROUNDING CLIPS TO BE INSTALLED BETWEEN MODULE FRAME AND MODULE SUPPORT RAIL, PER THE GROUNDING CLIP MANUFACTURER'S INSTRUCTION. 9)MODULE SUPPORT RAIL TO BE BONDED TO CONTINUOUS COPPER G.E.C.VIA WEEB LUG OR ILSCO GBL-4DBT LAY-IN LUG. 10)PV EQUIPMENT SHALL BE DESIGNED AND INSTALLED IN ACCORDANCE WITH NEC 690. 11)EXACT LOCATION OF AUXILIARY GROUNDING TO BE DETERMINED AT TIME OF INSTALL. 12)EXISTING WIRES MUST BE REPLACED IF SMALLER THAN LISTED MINIMUM SIZES PER NEC 310.15(B)(16). 13)IQ GATEWAY BREAKER DETERMINED AT FACTORY BY MANUFACTURER (10A or 15A). 14)FOR IQ GATEWAY: USE SINGLE CT FOR PV PRODUCTION (L1 FROM ALL PV BRANCH CIRCUITS). USE DOUBLE CTs FOR CONSUMPTION (L1 AND L2 FEEDING MSP MAIN BREAKER, SERVICE SIDE). SYSTEM SUMMARY STC (5.200 kW DC / 3.770 kW AC, 4.707kW AC CEC) STC DC: (13) 400W = 5.200 kW STC AC: (13) 290W = 3.770 kW, 4.707kW AC CEC ●(13) AXITEC AC-400MBT108V MODULES ●(13) ENPHASE ENERGY INC. IQ8PLUS-72-2-US 240V MICROINVERTERS ●1x BRANCH OF 13 CONNECTED IN PARALLEL SHEET NAME SHEET SIZE SHEET NUMBER ANSI B REVISIONS PV-5 HOMEOWNER INFO 11" X 17" SIGNATURE & SEAL LU I S O L I V A R E S 15 0 5 W E S T 1 1 T H S T R E E T , SA N T A A N A , C A 9 2 7 0 3 , U S A APN: 405-152-27 EMAIL: N/A PHONE: N/A REVDATEDESCRIPTION CONTRACTOR: NERD POWER DESIGNER: ABHISHEK MAHESH ADDRESS: 2065 W OBISPO AVE #102 GILBERT, AZ 85233 USA PHONE: 8665722637 LICENSE #: CA-1019100 FRESH08/24/2023ORIGINAL PLAN WIRING CALCULATIONS SCALE: NTS WIRING CALCULATIONS 1505 W 11th St 12/4/2023 PV-6ELECTRICAL SHOCK HAZARD WARNING! TERMINALS ON LINE AND LOAD SIDES MAY BE ENERGIZED IN THE OPEN POSITION LABEL LOCATION: INVERTERS, AC DISCONNECTS, AC COMBINER BOXES CODE REF: NEC 2020 - 690.13(B) RAPID SHUTDOWN SWITCH FOR SOLAR PV SYSTEM LABEL LOCATION: UTILITY SERVICE ENTRANCE (MSP OR AC DISCONNECT IF LINE SIDE TAP), AND WHEREVER REQUIRED BY AHJ (INVERTERS, DC DISCONNECTS, OTHER) CODE REF: NEC 2020 - 690.56(C)(2) MAXIMUM AC OPERATING CURRENT: NOMINAL OPERATING AC VOLTAGE: AMPS VAC PV SYSTEM DISCONNECT 240.0 15.73 LABEL LOCATION: INTERCONNECTION Placard (MSP BACKFEED BREAKER OR TAP BOX IF LINE SIDE TAP), AC DISCONNECTS CODE REF: NEC 2020 - 690.54 PHOTOVOLTAIC AC DISCONNECT LABEL LOCATION: INTERCONNECTION Placard (MSP BACKFEED BREAKER OR TAP BOX IF LINE SIDE TAP), AC DISCONNECTS CODE REF: NEC 2020 - 690.13(B) MAIN PHOTOVOLTAIC SYSTEM DISCONNECT LABEL LOCATION: AC DISCONNECTS FOR UTILITY ACCESS CODE REF: NEC 2020 - 690.13(B) WARNING! DO NOT RELOCATE THIS OVERCURRENT DEVICE POWER SOURCE OUTPUT CONNECTION LABEL LOCATION: FIRST BACKFEED BREAKER (MSP/SUBPANEL) IF NO LINE SIDE TAP CODE REF: NEC 2020 - 705.12(B)(3)(2), CEC 2019 - 705.12(B)(2)(3)(b), CEC 2019 - 705.12(B)(3) CAUTION: MULTIPLE POWER SOURCES LABEL LOCATION: N/A CODE REF: NEC 2020 - 690.56(B), NEC 2020 - 705.10 SOLAR PV SYSTEM EQUIPPED WITH RAPID SHUTDOWN SOLAR ELECTRIC PV PANELS TURN RAPID SHUTDOWN SWITCH TO THE "OFF" POSITION TO SHUT DOWN PV SYSTEM AND REDUCE SHOCK HAZARD IN THE ARRAY. LABEL LOCATION: INTERCONNECTION POINT (MSP OR AC DISCONNECT IF LINE SIDE TAP) CODE REF: NEC 2020 - 690.56(C) WARNING SOLAR SYSTEM CONNECTED AND ENERGISED LABEL LOCATION: UTILITY METER CODE REF: NEC 2020 - 690.13(B) WARNING TURN OFF PHOTOVOLTAIC AC DISCONNECT PRIOR TO WORKING INSIDE PANEL ! LABEL LOCATION: MSP CODE REF: NEC 2020 - 110.27(C) CAUTION: MULTIPLE SOURCES OF POWER LABEL LOCATION: MSP CODE REF: NEC 2020 - 705.10, NEC 2020 - 710.10 MSP UM ACD CB SHEET NAME SHEET SIZE SHEET NUMBER ANSI B REVISIONS PV-6 HOMEOWNER INFO 11" X 17" SIGNATURE & SEAL LU I S O L I V A R E S 15 0 5 W E S T 1 1 T H S T R E E T , SA N T A A N A , C A 9 2 7 0 3 , U S A APN: 405-152-27 EMAIL: N/A PHONE: N/A REVDATEDESCRIPTION CONTRACTOR: NERD POWER DESIGNER: ABHISHEK MAHESH ADDRESS: 2065 W OBISPO AVE #102 GILBERT, AZ 85233 USA PHONE: 8665722637 LICENSE #: CA-1019100 FRESH08/24/2023ORIGINAL PLAN PLACARDS (E) MAIN SERVICE PANEL (FLUSH MOUNTED) (E) UTILITY METER (N) AC DISCONNECT (N) ENPHASE COMBINER BOX 15 0 5 W E S T 1 1 T H S T R E E T , SA N T A A N A , C A 9 2 7 0 3 , U S A 1505 W 11th St 12/4/2023 10 ' - 0 " SHEET NAME SHEET SIZE SHEET NUMBER ANSI B REVISIONS PV-6.1 HOMEOWNER INFO 11" X 17" SIGNATURE & SEAL LU I S O L I V A R E S 15 0 5 W E S T 1 1 T H S T R E E T , SA N T A A N A , C A 9 2 7 0 3 , U S A APN: 405-152-27 EMAIL: N/A PHONE: N/A REVDATEDESCRIPTION CONTRACTOR: NERD POWER DESIGNER: ABHISHEK MAHESH ADDRESS: 2065 W OBISPO AVE #102 GILBERT, AZ 85233 USA PHONE: 8665722637 LICENSE #: CA-1019100 FRESH08/24/2023ORIGINAL PLAN EQUIPMENTS ELEVATION SCALE: NTS EQUIPMENTS ELEVATION (N) ENPHASE COMBINER BOX (N) AC DISCONNECT (E) MAIN SERVICE PANEL, 100A RATED, 240V (FLUSH MOUNTED) (E) UTILITY METER (N) CONDUIT RUN FROM MICRO INVERTERS 1505 W 11th St 12/4/2023 PV-7 SHEET NAME SHEET SIZE SHEET NUMBER ANSI B REVISIONS PV-7 HOMEOWNER INFO 11" X 17" SIGNATURE & SEAL LU I S O L I V A R E S 15 0 5 W E S T 1 1 T H S T R E E T , SA N T A A N A , C A 9 2 7 0 3 , U S A APN: 405-152-27 EMAIL: N/A PHONE: N/A REVDATEDESCRIPTION CONTRACTOR: NERD POWER DESIGNER: ABHISHEK MAHESH ADDRESS: 2065 W OBISPO AVE #102 GILBERT, AZ 85233 USA PHONE: 8665722637 LICENSE #: CA-1019100 FRESH08/24/2023ORIGINAL PLAN EQUIPMENT SPECIFICATION 1505 W 11th St 12/4/2023 PV-8 SHEET NAME SHEET SIZE SHEET NUMBER ANSI B REVISIONS PV-8 HOMEOWNER INFO 11" X 17" SIGNATURE & SEAL LU I S O L I V A R E S 15 0 5 W E S T 1 1 T H S T R E E T , SA N T A A N A , C A 9 2 7 0 3 , U S A APN: 405-152-27 EMAIL: N/A PHONE: N/A REVDATEDESCRIPTION CONTRACTOR: NERD POWER DESIGNER: ABHISHEK MAHESH ADDRESS: 2065 W OBISPO AVE #102 GILBERT, AZ 85233 USA PHONE: 8665722637 LICENSE #: CA-1019100 FRESH08/24/2023ORIGINAL PLAN EQUIPMENT SPECIFICATION 1505 W 11th St 12/4/2023 Expedited Permit Process for PV Systems - Micro-Inverter1 Expedited Permit Process for PV Systems Micro-Inverter The Solar America Board for Codes and Standards (Solar ABCs) Expedited Permit Pro- cess provides a means to differentiate systems that can be permitted quickly and easily due to their similarity with the majority of small-scale PV systems. Those systems with unique characteristics may be handled with small additions to this Expedited Permit Process or may require much more information, depending on the uniqueness of the installation. The following pages contain forms for the Micro-Inverter to use with the Expedited Per- mit Process. The Standard String, AC Module, and Supply-Side Connection forms are also available as interactive PDF files at www.solarabcs.org/permitting. In jurisdic- tions that have adopted the Expedited Permit Process for PV Systems, these forms can be filled out electronically and submitted in either printed form and via email. An elec- tronic format is used so that the supplied information is standardized and legible for the local jurisdiction. 1505 W 11th St 12/4/2023 Expedited Permit Process for PV Systems — Micro-Inverter 2 Expedited Permit Process for Small-Scale PV Systems Micro-Inverter The information in this guideline is intended to help local jurisdictions and contractors identify when PV system installations are simple, needing only a basic review, and when an installation is more complex. It is likely that 50%-75% of all residential systems will comply with these simple criteria. For projects that fail to meet the simple criteria, resolution steps have been suggested to provide as a path to permit approval. Required Information for Permit: 1. Site plan showing location of major components on the property. This drawing need not be exactly to scale, but it should represent relative location of components at site (see supplied example site plan). PV arrays on dwellings with a 3’ perimeter space at ridge and sides may not need separate fire service review. 2. Electrical diagram showing PV array configuration, wiring system, overcurrent protection, inverter, disconnects, required signs, and ac connection to building (see supplied standard electrical diagram). 3. Specification sheets and installation manuals (if available) for all manufactured components including, but not limited to, PV modules, inverter(s), combiner box, disconnects, and mounting system. Step 1: Structural Review of PV Array Mounting System Is the array to be mounted on a defined, permitted roof structure? l Yes l No If No due to non-compliant roof or a ground mount, submit completed worksheet for the structure WKS1. Roof Information: 1. Is the roofing type lightweight (Yes = composition, lightweight masonry, metal, etc…)__________________________ ____________________________________________________________________________________________________ If No, submit completed worksheet for roof structure WKS1 (No = heavy masonry, slate, etc…). 2. Does the roof have a single roof covering? l Yes l No If No, submit completed worksheet for roof structure WKS1. 3. Provide method and type of weatherproofing roof penetrations (e.g. flashing, caulk).____________________________ Mounting System Information: 1. Is the mounting structure an engineered product designed to mount PV modules with no more than an 18” gap beneath the module frames? l Yes l No If No, provide details of structural attachment certified by a design professional. 2. For manufactured mounting systems, fill out information on the mounting system below: a. Mounting System Manufacturer ___________Product Name and Model#________________________________ b. Total Weight of PV Modules and Rails ___________lbs c. Total Number of Attachment Points____________ d. Weight per Attachment Point (b÷c)_________________lbs (if greater than 45 lbs, see WKS1) e. Maximum Spacing Between Attachment Points on a Rail ______________inches (see product manual for maximum spacing allowed based on maximum design wind speed) f. Total Surface Area of PV Modules (square feet)_________________ ft2 g. Distributed Weight of PV Module on Roof (b÷f)_______________ lbs/ft2 If distributed weight of the PV system is greater than 5 lbs/ft2, see WKS1. Step 2: Electrical Review of PV System (Calculations for Electrical Diagram) In order for a PV system to be considered for an expedited permit process, the following must apply: 1. PV modules, utility-interactive inverters, and combiner boxes are identified for use in PV systems. 2. The PV array is composed of 4 series strings or less per inverter. 3. The total inverter capacity has a continuous ac power output 13,440 Watts or less 4. The ac interconnection point is on the load side of service disconnecting means (690.64(B)). 5. One of the standard electrical diagrams (E1.1, E1.1a, E1.1b, or E1.1c) can be used to accurately represent the PV system. Interactive PDF diagrams are available at www.solarabcs.org/permitting. Fill out the standard electrical diagram completely. A guide to the electrical diagram is provided to help the applicant understand each blank to fill in. If the electrical system is more complex than the standard electrical diagram can effectively communicate, provide an alternative diagram with appropriate detail. 1505 W 11th St 12/4/2023 E x p e d i t e d P e r m i t P r o c e s s f o r P V S y s t e m s 3 Micro-Inverter Site Plan             1505 W 11th St 12/4/2023 E x p e d i t e d P e r m i t P r o c e s s f o r P V S y s t e m s 4 Micro-Inverter Electrical Diagram Contractor Name, Address and Phone:One-Line Standard Electrical Diagram for Micro-Inverter PV Systems Site Name: Site Address: System AC Size: SIZE FSCM NO DWG NO REV E1.1a SCALE NTS Date: SHEET Drawn By: Checked By: DESCRIPTION OR CONDUCTOR TYPE USE-2 or PV WIRE GEC EGC X ALL THAT APPLY EXTERIOR CABLE LISTED W/ INV. THWN-2 or XHHW-2 or RHW-2 GEC EGC X ALL THAT APPLY NO DC GEC IF 690.35 SYSTEM THWN-2 or XHHW-2 or RHW-2 GEC EGC X ALL THAT APPLY TAG 1 2 3 4 5 CONDUIT AND CONDUCTOR SCHEDULE COND. GAUGE MFG MFG NUMBER OF CONDUCTORS MFG Cable MFG Cable CONDUIT TYPE N/A N/A N/A SAME SAME CONDUIT SIZE N/A N/A N/A SAME SAME DESCRIPTION PV DC or AC MODULE DC/AC INVERTER (MICRO) J-BOX (IF USED) PV ARRAY AC COMB. PANEL (IF USED) GEN METER (IF USED) AC DISCONNECT (IF USED) SERVICE PANEL TAG 1 2 3 4 5 6 7 8 PART NUMBER NOTES FOR UNUSED MODULES PUT "N/A” in BLANK ABOVE 1 1 3 2 3 EQUIPMENT SCHEDULE 2 _____ MICRO-INVERTERS IN BRANCH- CIRCUIT MOD ____ DC AC MOD ____ DC AC MOD ____ DC AC MOD ____ DC AC MOD ____ DC AC MOD ____ DC AC J-BOX 4 AC DISCO M BUILDING GROUNDING ELECTRODE G M UTILITY SERVICE MAIN SERVICE PANEL MAIN OCPD INVERTER OCPD 6 7 8 5 4 5 G SEE GUIDE APPENDIX D FOR INFORMATION ON MODULE AND ARRAY GROUNDING AC COMBINER PANEL G ____ MICRO-INVERTERS IN BRANCH- CIRCUIT 1505 W 11th St 12/4/2023 E x p e d i t e d P e r m i t P r o c e s s f o r P V S y s t e m s 5 Contractor Name, Address and Phone:Notes for One-Line Standard Electrical Diagram for Single-Phase PV Systems Site Name: Site Address: System AC Size: SIZE FSCM NO DWG NO REV E1.2a SCALE NTS Date: SHEET Drawn By: Checked By: MAX POWER-POINT CURRENT (IMP) MAX POWER-POINT VOLTAGE (VMP) OPEN-CIRCUIT VOLTAGE (VOC) SHORT-CIRCUIT CURRENT (ISC) MAX SERIES FUSE (OCPD) MAXIMUM POWER (PMAX) MAX VOLTAGE (TYP 600VDC) VOC TEMP COEFF (mV/oC or %/oC ) IF COEFF SUPPLIED, CIRCLE UNITS MODULE MAKE MODULE MODEL PV MODULE RATINGS @ STC (Guide Section 5) MAX DC VOLT RATING MAX POWER @ 40oC NOMINAL AC VOLTAGE MAX AC CURRENT MAX OCPD RATING INVERTER MAKE INVERTER MODEL INVERTER RATINGS (Guide Section 4) 1) IF UTILITY REQUIRES A VISIBLE-BREAK SWITCH, DOES THIS SWITCH MEET THE REQUIREMENT? YES NO N/A 2) IF GENERATION METER REQUIRED, DOES THIS METER SOCKET MEET THE REQUIREMENT? YES NO N/A 3) SIZE PHOTOVOLTAIC POWER SOURCE (DC) CONDUCTORS BASED ON MAX CURRENT ON NEC 690.53 SIGN OR OCPD RATING AT DISCONNECT 4) SIZE INVERTER OUTPUT CIRCUIT (AC) CONDUCTORS ACCORDING TO INVERTER OCPD AMPERE RATING. (See Guide Section 9) 5) TOTAL OF ______ INVERTER OUTPUT CIRCUIT OCPD(s), ONE FOR EACH MICRO-INVERTER CIRCUIT. DOES TOTAL SUPPLY BREAKERS COMPLY WITH 120% BUSBAR EXCEPTION IN 690.64(B)(2)(a)? YES NO NOTES FOR INVERTER CIRCUITS (Guide Section 8 and 9): 1.) LOWEST EXPECT AMBIENT TEMPERATURE BASED ON ASHRAE MINIMUM MEAN EXTREME DRY BULB TEMPERATURE FOR ASHRAE LOCATION MOST SIMILAR TO INSTALLATION LOCATION. LOWEST EXPECTED AMBIENT TEMP ____oC 2.) HIGHEST CONTINUOUS AMBIENT TEMPERATURE BASED ON ASHRAE HIGHEST MONTH 2% DRY BULB TEMPERATURE FOR ASHRAE LOCATION MOST SIMILAR TO INSTALLATION LOCATION. HIGHEST CONTINUOUS TEMPERATURE ____oC 2.) 2009 ASHRAE FUNDAMENTALS 2% DESIGN TEMPERATURES DO NOT EXCEED 47oC IN THE UNITED STATES (PALM SPRINGS, CA IS 44.1oC). FOR LESS THAN 9 CURRENT-CARRYING CONDUCTORS IN ROOF-MOUNTED SUNLIT CONDUIT AT LEAST 0.5" ABOVE ROOF AND USING THE OUTDOOR DESIGN TEMPERATURE OF 47oC OR LESS (ALL OF UNITED STATES), a) 12 AWG, 90oC CONDUCTORS ARE GENERALLY ACCEPTABLE FOR MODULES WITH Isc OF 7.68 AMPS OR LESS WHEN PROTECTED BY A 12-AMP OR SMALLER FUSE.b) 10 AWG, 90oC CONDUCTORS ARE GENERALLY ACCEPTABLE FOR MODULES WITH Isc OF 9.6 AMPS OR LESS WHEN PROTECTED BY A 15-AMP OR SMALLER FUSE. NOTES FOR ARRAY CIRCUIT WIRING (Guide Section 6 and 8 and Appendix E): OCPD = OVERCURRENT PROTECTION DEVICE NATIONAL ELECTRICAL CODE®REFERENCES SHOWN AS (NEC XXX.XX) NOTES FOR ALL DRAWINGS: SIGNS–SEE GUIDE SECTION 7 SIGN FOR DC DISCONNECT SIGN FOR INVERTER OCPD AND AC DISCONNECT (IF USED) No sign necessary since 690.51 marking on PV module covers needed information AC OUTPUT CURRENT NOMINAL AC VOLTAGE SOLAR PV SYSTEM AC POINT OF CONNECTION THIS PANEL FED BY MULTIPLE SOURCES (UTILITY AND SOLAR) Notes for Micro-Inverter Electrical Diagram 1505 W 11th St 12/4/2023 Certificate Of Completion Envelope Id: C70B567821F94CC39EA06BA574A46394 Status: Completed Subject: Complete with DocuSign: Santa Ana Letter of Authorization.pdf Source Envelope: Document Pages: 1 Signatures: 1 Envelope Originator: Certificate Pages: 5 Initials: 0 NERD Power AutoNav: Enabled EnvelopeId Stamping: Enabled Time Zone: (UTC-08:00) Pacific Time (US & Canada) 13614 Carolina Hill Court Draper, UT 84020 info@gonerdpower.com IP Address: 24.56.55.135 Record Tracking Status: Original 10/26/2023 1:53:19 PM Holder: NERD Power info@gonerdpower.com Location: DocuSign Signer Events Signature Timestamp Luis Olivares luisrolivares@att.net Security Level: Email, Account Authentication (None) Signature Adoption: Drawn on Device Using IP Address: 172.58.208.136 Signed using mobile Sent: 10/26/2023 1:54:54 PM Viewed: 10/26/2023 3:59:12 PM Signed: 10/26/2023 3:59:57 PM Electronic Record and Signature Disclosure: Accepted: 10/26/2023 3:59:12 PM ID: 1a6d0778-8fa6-496d-b5d7-f5182eb98359 In Person Signer Events Signature Timestamp Editor Delivery Events Status Timestamp Agent Delivery Events Status Timestamp Intermediary Delivery Events Status Timestamp Certified Delivery Events Status Timestamp Carbon Copy Events Status Timestamp Ashley Rivas caprocessing@nerdpower.energy Security Level: Email, Account Authentication (None) Sent: 10/26/2023 1:54:54 PM Viewed: 10/26/2023 1:55:16 PM Electronic Record and Signature Disclosure: Accepted: 10/26/2023 2:03:38 PM ID: 61acf6a0-34a3-48d5-80a7-c71ea0aa001f Witness Events Signature Timestamp Notary Events Signature Timestamp Envelope Summary Events Status Timestamps Envelope Sent Hashed/Encrypted 10/26/2023 1:54:54 PM Certified Delivered Security Checked 10/26/2023 3:59:12 PM Signing Complete Security Checked 10/26/2023 3:59:57 PM Completed Security Checked 10/26/2023 3:59:57 PM 1505 W 11th St 12/4/2023 Payment Events Status Timestamps Electronic Record and Signature Disclosure 1505 W 11th St 12/4/2023 ELECTRONIC RECORD AND SIGNATURE DISCLOSURE From time to time, Nerd Power LLC (we, us or Company) may be required by law to provide to you certain written notices or disclosures. Described below are the terms and conditions for providing to you such notices and disclosures electronically through the DocuSign, Inc. (DocuSign) electronic signing system. Please read the information below carefully and thoroughly, and if you can access this information electronically to your satisfaction and agree to these terms and conditions, please confirm your agreement by clicking the ‘I agree’ button at the bottom of this document. Getting paper copies At any time, you may request from us a paper copy of any record provided or made available electronically to you by us. You will have the ability to download and print documents we send to you through the DocuSign system during and immediately after signing session and, if you elect to create a DocuSign signer account, you may access them for a limited period of time (usually 30 days) after such documents are first sent to you. After such time, if you wish for us to send you paper copies of any such documents from our office to you, you will be charged a $0.00 per-page fee. You may request delivery of such paper copies from us by following the procedure described below. Withdrawing your consent If you decide to receive notices and disclosures from us electronically, you may at any time change your mind and tell us that thereafter you want to receive required notices and disclosures only in paper format. How you must inform us of your decision to receive future notices and disclosure in paper format and withdraw your consent to receive notices and disclosures electronically is described below. Consequences of changing your mind If you elect to receive required notices and disclosures only in paper format, it will slow the speed at which we can complete certain steps in transactions with you and delivering services to you because we will need first to send the required notices or disclosures to you in paper format, and then wait until we receive back from you your acknowledgment of your receipt of such paper notices or disclosures. To indicate to us that you are changing your mind, you must withdraw your consent using the DocuSign ‘Withdraw Consent’ form on the signing page of a DocuSign envelope instead of signing it. This will indicate to us that you have withdrawn your consent to receive required notices and disclosures electronically from us and you will no longer be able to use the DocuSign system to receive required notices and consents electronically from us or to sign electronically documents from us. All notices and disclosures will be sent to you electronically Unless you tell us otherwise in accordance with the procedures described herein, we will provide electronically to you through the DocuSign system all required notices, disclosures, authorizations, acknowledgements, and other documents that are required to be provided or made available to you during the course of our relationship with you. To reduce the chance of you inadvertently not receiving any notice or disclosure, we prefer to provide all of the required notices and disclosures to you by the same method and to the same address that you have given us. Thus, you can receive all the disclosures and notices electronically or in paper format through the paper mail delivery system. If you do not agree with this process, please let us know as described below. Please also see the paragraph immediately above that describes the consequences of your electing not to receive delivery of the notices and disclosures Electronic Record and Signature Disclosure created on: 6/23/2017 2:07:56 PM Parties agreed to: Luis Olivares, Ashley Rivas 1505 W 11th St 12/4/2023 electronically from us. How to contact Nerd Power LLC: You may contact us to let us know of your changes as to how we may contact you electronically, to request paper copies of certain information from us, and to withdraw your prior consent to receive notices and disclosures electronically as follows: To contact us by email send messages to: info@gonerdpower.com To advise Nerd Power LLC of your new e-mail address To let us know of a change in your e-mail address where we should send notices and disclosures electronically to you, you must send an email message to us at info@gonerdpower.com and in the body of such request you must state: your previous e-mail address, your new e-mail address. We do not require any other information from you to change your email address.. In addition, you must notify DocuSign, Inc. to arrange for your new email address to be reflected in your DocuSign account by following the process for changing e-mail in the DocuSign system. To request paper copies from Nerd Power LLC To request delivery from us of paper copies of the notices and disclosures previously provided by us to you electronically, you must send us an e-mail to info@gonerdpower.com and in the body of such request you must state your e-mail address, full name, US Postal address, and telephone number. We will bill you for any fees at that time, if any. To withdraw your consent with Nerd Power LLC To inform us that you no longer want to receive future notices and disclosures in electronic format you may: i. decline to sign a document from within your DocuSign session, and on the subsequent page, select the check-box indicating you wish to withdraw your consent, or you may; ii. send us an e-mail to info@gonerdpower.com and in the body of such request you must state your e-mail, full name, US Postal Address, and telephone number. We do not need any other information from you to withdraw consent.. The consequences of your withdrawing consent for online documents will be that transactions may take a longer time to process.. Required hardware and software Operating Systems: Windows® 2000, Windows® XP, Windows Vista®; Mac OS® X Browsers: Final release versions of Internet Explorer® 6.0 or above (Windows only); Mozilla Firefox 2.0 or above (Windows and Mac); Safari™ 3.0 or above (Mac only) PDF Reader: Acrobat® or similar software may be required to view and print PDF files Screen Resolution: 800 x 600 minimum Enabled Security Settings: Allow per session cookies ** These minimum requirements are subject to change. If these requirements change, you will be asked to re-accept the disclosure. Pre-release (e.g. beta) versions of operating systems and browsers are not supported. Acknowledging your access and consent to receive materials electronically 1505 W 11th St 12/4/2023 To confirm to us that you can access this information electronically, which will be similar to other electronic notices and disclosures that we will provide to you, please verify that you were able to read this electronic disclosure and that you also were able to print on paper or electronically save this page for your future reference and access or that you were able to e-mail this disclosure and consent to an address where you will be able to print on paper or save it for your future reference and access. Further, if you consent to receiving notices and disclosures exclusively in electronic format on the terms and conditions described above, please let us know by clicking the ‘I agree’ button below. By checking the ‘I agree’ box, I confirm that: • I can access and read this Electronic CONSENT TO ELECTRONIC RECEIPT OF ELECTRONIC RECORD AND SIGNATURE DISCLOSURES document; and • I can print on paper the disclosure or save or send the disclosure to a place where I can print it, for future reference and access; and • Until or unless I notify Nerd Power LLC as described above, I consent to receive from exclusively through electronic means all notices, disclosures, authorizations, acknowledgements, and other documents that are required to be provided or made available to me by Nerd Power LLC during the course of my relationship with you. 1505 W 11th St 12/4/2023 Date: _______________________________________________________________________ Name: ______________________________________________________________________ Address: ____________________________________________________________________ To whom it may concern; I hereby grant permission to Nerd Power LLC and it’s employees to obtain permits and install a roof-mounted solar system on my home. Thank you, ______________________________________________________________________ (signature) DocuSign Envelope ID: C70B5678-21F9-4CC3-9EA0-6BA574A46394 Luis Olivares 10/26/2023 1505 West 11th Street Santa Ana CA 92703 1505 W 11th St 12/4/2023 Rev: 7/15/2021 RESIDENTIAL PHOTOVOLTAIC SOL-01 CBC 2019 Solar Photovoltaic (PV) Checklist for Detached SINGLE FAMILY RESIDENCES Only Instructions: The licensed contractor of record shall complete all sections, answer the ten questions and sign the certification section below. A copy of this form shall be attached to each of TWO sets of plans, of minimum 11” x 17” size. If answering NO to any of the questions, plan check shall be required. Project Address: Contractor Company Name: Contractor License Number: YES NO Are the following applicable to the proposed project? 1.   Will the PV system layout provide the required three-foot wide clear access pathways per Section 605.11 of the California Fire Code, and is this shown on the roof plan? 2.   Will the PV system be installed on a roof having only one roofing layer with no overlays? 3.   Will the PV array be flush mounted to the existing roof so that the plane of the modules (panels) are parallel to the plane of the roof? 4.   Will the PV system weigh maximum 4 pounds per square feet or less? 5.   Will the PV system be installed where the modules do not overhang any roof edges (such as eaves, gabled ends, ridges and hips)? 6.   Will the PV system be installed with a space of 2” minimum to 10” maximum between the underside of modules and the surface of the roof? 7.   Will the PV system be installed without using any ballast system or counter-weight system? 8.   Will the anchors be installed with a maximum horizontal anchor spacing of 6 feet and is this maximum horizontal spacing shown on the plans? 9.   Will the minimum 5/16” lag screws be installed with a minimum of 2-1/2 inch embedment into roof rafters (with pre-drilled holes) and is this minimum embedment shown on the plans? 10.   Are ALL the structural pages of the plans stamped and signed by a California licensed professional engineer? (including project specific site plan, PV layout, anchorage spacing, anchorage details and manufacturer’s PV support information.) I certify under penalty of perjury under the laws of the State of California that the above is true: Print Name: Signature: Phone Number: Date: Email Address: Planning & Building Agency Building Safety Division 20 Civic Center Plaza P.O. Box 1988 (M-19) Santa Ana, CA 92702 (714) 647-5800 www.santa-ana.org DocuSign Envelope ID: 031D91FE-C2D5-455E-8BA9-175702953039 1505 West 11th Street Santa Ana CA 92703 X 10/26/2023 X X X X X X X 310-598-2412 Ashley Rivas X Nerd Power CA LLC caprocessing@nerdpower.energy X 1019100 1505 W 11th St 12/4/2023 10/27/2023 RE: Structural Certification for Installation of Residential Solar LUIS OLIVARES:1505 WEST 11TH STREET, SANTA ANA, CA 92703 Attn: To Whom It May Concern Design Criteria Code 2022 California Building Code (ASCE 7-16) Risk category II Wind Load (component and Cladding) Roof Dead Load Dr 10 psf V 96 mph PV Dead Load DPV 3 psf Exposure C Roof Live Load Lr 20 psf Ground Snow S 0 psf If you have any questions on the above, please do not hesitate to call. Sincerely, Eugene Munyanziza, P.E. Signed 10/27/2023 EV Engineering, LLC projects@evengineersnet.com http://www.evengineersnet.com Exp: 06/30/2024 This Letter is for the existing roof framing which supports the new PV modules as well as the attachment of the PV system to existing roof framing. From the field observation report, the roof is made of Composition shingle roofing over roof plywood supported by 2X4 Rafters at 24 inches. The slope of the roof was approximated to be 23 degrees. After review of the field observation data and based on our structural capacity calculation, the existing roof framing has been determined to be adequate to support the imposed loads without structural upgrades. Contractor shall verify that existing framing is consistent with the described above before install. Should they find any discrepancies, a written approval from SEOR is mandatory before proceeding with install. Capacity calculations were done in accordance with applicable building codes. projects@evengineersnet.com http://www.evengineersnet.com 1505 W 11th St 12/4/2023 Structural Letter for PV Installation Date: 10/27/2023 Job Address:1505 WEST 11TH STREET SANTA ANA, CA 92703 Job Name:LUIS OLIVARES Job Number:102723LO Scope of Work Table of Content Sheet 2 Cover 3 Attachment Uplift checks 4 Roof Framing Check 5 Seismic Check and Scope of work Engineering Calculations Summary Code 2022 California Building Code (ASCE 7-16) Risk category II Roof Dead Load Dr 10 psf PV Dead Load DPV 3 psf Roof Live Load Lr 20 psf Ground Snow S 0 psf Wind Load (component and Cladding) V 96 mph Exposure C References NDS for Wood Construction Sincerely, Signed 10/27/2023 Eugene Munyanziza, P.E. EV Engineering, LLC projects@evengineersnet.com http://www.evengineersnet.com Exp: 06/30/2024 This Letter is for the existing roof framing which supports the new PV modules as well as the attachment of the PV system to existing roof framing. All PV mounting equipment shall be designed and installed per manufacturer's approved installation specifications. projects@evengineersnet.com http://www.evengineersnet.com 1505 W 11th St 12/4/2023 Wind Load Cont. 96 mph ASCE 7-16 Figure 26.5-1B C 1.0 ASCE 7-16 Sec 26.8.2 0.85 ASCE 7-16 Table 26.10-1 0.85 ASCE 7-16 Table 26.6-1 1.00 ASCE 7-16 Table 26.9-1 16.98 psf 23.0 Degrees 1.5 Conservatively assuming all exposed 0.8 conservatively assuming 10 ft2 effective area Uplift (W)Zone(1,2e) Zone(2r, 2n) Zone(3e) Zone(3r) Fig. 30-3-2 GCp=-1.3 -1.7 -1.7 -1.8 Eq. 29.4-7 P=qh(GCp)(γE)(γa)=-26.50 -34.65 -34.65 -36.69 GCp=0.6 Figure 30.3-2 P=qh(GCp)(γE)(γa)=6.59 Equation 29.4-7 Rafter Attachments: 0.6D+0.6W (CD=1.6) Connection Check Attachment max. spacing=4 ft 5/16" Lag Screw Withdrawal Value=266 lbs/in Table 12.2A - NDS 2.5 in DFL Assumed Prying Coefficient 1.4 Allowable Capacity= 760 lbs Zone Trib Width Area (ft) Uplift (lbs) Down (lbs) Zone(1,2e)4 11.0 104.9 105.5 Zone(2r, 2n)4 11.0 133.8 105.5 Zone(3e)4 11.0 133.8 105.5 Zone(3r)4 11.0 141.1 105.5 Conservative Max=141.1 <760 CONNECTION IS OK Risk Category = KZ = Kd = Ke = 2. Embedment is measured from the top of the framing member to the tapered tip of a lag screw. Embedment in sheading or other material does not count. II V= Exposure = 1. Pv seismic dead weight is negligible to result in significant seismic uplift, therefore the wind uplift governs γE= γa= KZt = qh= 0.00256KzKztKdKeV2= Pitch = Lag Screw Penetration projects@evengineersnet.com http://www.evengineersnet.com 1505 W 11th St 12/4/2023 Vertical Load Resisting System Design Roof Framing Rafters Snow Load Fully Exposed pg= 0 psf Ct =1.1 Ce =0.9 Is =1.0 pf = 0 psf pfmin. = 0.0 psf ps = 0 psf Conservatively (Cs=1) 0 plf Max Length, L =8.0 ft (Rafter maximum Allowable Horizontal Span) Tributary Width, WT =24 in Dr =10 psf 20 plf PvDL =3 psf 12 plf Load Case: DL+0.75(0.6W+S) 0.75(Pnet+Ps)+ Ppvcos(θ)+PDL=38 plf Mdown=303 lb-ft Mallowable = Sx x Fb' (wind)=456 lb-ft >303 lb-ft OK Load Case: DL+S Ps+ Ppvcos(θ)+PDL=32 plf Mdown=256 lb-ft Mallowable = Sx x Fb' (wind)=456 lb-ft >256 lb-ft OK Load Case: DL+0.6W Pnet+ Ppvcos(θ)+PDL=39.9 plf Max Moment, Mu=319 lb-ft Mallowable = Sx x Fb' (wind)=634 lb-ft >319 lb-ft OK Pv max Shear=105.5 lbs Shear, Vu=wL/2+Pv Point Load =233 lbs Max Shear, Vu=wL/2+Pv Point Load =233 lb Member Capacity DF-L No.2 2X4 CL CF Ci Cr KF φ λ Fb =900 psi 1.0 1.5 1.0 1.15 2.54 0.85 0.8 1553 psi Fv =180 psi N/A N/A 1.0 N/A 2.88 0.75 0.8 180 psi E =1600000 psi N/A N/A 1.0 N/A N/A N/A N/A 1600000 psi Emin =580000 psi N/A N/A 1.0 N/A 1.76 0.85 N/A 580000 psi Depth, d =3.5 in Width, b =1.5 in Cross-Sectonal Area, A =5.25 in2 Moment of Inertia, Ixx =5.35938 in4 Section Modulus, Sxx =3.0625 in3 Allowable Moment, Mall = Fb'Sxx =396.2 lb-ft DCR=Mu/Mall =0.67 < 1 Satisfactory Allowable Shear, Vall = 2/3Fv'A =630.0 lb DCR=Vu/Vall =0.37 < 1 Satisfactory Design Value Adjusted Value projects@evengineersnet.com http://www.evengineersnet.com 1505 W 11th St 12/4/2023 Siesmic Loads Check Roof Dead Load 10 psf % or Roof with Pv 13% Dpv and Racking 3 psf Average Total Dead Load 10.4 psf Increase in Dead Load 1.6%OK Limits of Scope of Work and Liability The increase in seismic Dead weight as a result of the solar system is less than 10% of the existing structure and therefore no further seismic analysis is required. We have based our structural capacity determination on information in pictures and a drawing set titled PV plans - LUIS OLIVARES. The analysis was according to applicable building codes, professional engineering and design experience, opinions and judgments. The calculations produced for this Structure's assessment are only for the proposed solar panel installation referenced in the stamped plan set and were made according to generally recognized structural analysis standards and procedures. projects@evengineersnet.com http://www.evengineersnet.com 1505 W 11th St 12/4/2023