HomeMy WebLinkAbout1406 W 12th St - PlanExpedited Permit Process for PV Systems - Micro-Inverter1 Expedited Permit Process for PV Systems Micro-Inverter The Solar America Board for Codes and Standards (Solar ABCs) Expedited Permit Pro- cess provides a means to differentiate systems that can be permitted quickly and easily due to their similarity with the majority of small-scale PV systems. Those systems with unique characteristics may be handled with small additions to this Expedited Permit Process or may require much more information, depending on the uniqueness of the installation. The following pages contain forms for the Micro-Inverter to use with the Expedited Per- mit Process. The Standard String, AC Module, and Supply-Side Connection forms are also available as interactive PDF files at www.solarabcs.org/permitting. In jurisdic- tions that have adopted the Expedited Permit Process for PV Systems, these forms can be filled out electronically and submitted in either printed form and via email. An elec- tronic format is used so that the supplied information is standardized and legible for the local jurisdiction. 1406 W 12th St 05/19/23 Expedited Permit Process for PV Systems — Micro-Inverter2 Expedited Permit Process for Small-Scale PV Systems Micro-Inverter The information in this guideline is intended to help local jurisdictions and contractors identify when PV system installations are simple, needing only a basic review, and when an installation is more complex. It is likely that 50%-75% of all residential systems will comply with these simple criteria. For projects that fail to meet the simple criteria, resolution steps have been suggested to provide as a path to permit approval. Required Information for Permit: 1. Site plan showing location of major components on the property. This drawing need not be exactly to scale, but it should represent relative location of components at site (see supplied example site plan). PV arrays on dwellings with a 3’ perimeter space at ridge and sides may not need separate fire service review. 2. Electrical diagram showing PV array configuration, wiring system, overcurrent protection, inverter, disconnects, required signs, and ac connection to building (see supplied standard electrical diagram). 3. Specification sheets and installation manuals (if available) for all manufactured components including, but not limited to, PV modules, inverter(s), combiner box, disconnects, and mounting system. Step 1: Structural Review of PV Array Mounting System Is the array to be mounted on a defined, permitted roof structure? l Yes l No If No due to non-compliant roof or a ground mount, submit completed worksheet for the structure WKS1. Roof Information: 1. Is the roofing type lightweight (Yes = composition, lightweight masonry, metal, etc…)__________________________ ____________________________________________________________________________________________________ If No, submit completed worksheet for roof structure WKS1 (No = heavy masonry, slate, etc…). 2. Does the roof have a single roof covering? l Yes l No If No, submit completed worksheet for roof structure WKS1. 3. Provide method and type of weatherproofing roof penetrations (e.g. flashing, caulk).____________________________ Mounting System Information: 1. Is the mounting structure an engineered product designed to mount PV modules with no more than an 18” gap beneath the module frames? l Yes l No If No, provide details of structural attachment certified by a design professional. 2. For manufactured mounting systems, fill out information on the mounting system below: a. Mounting System Manufacturer ___________Product Name and Model#________________________________ b. Total Weight of PV Modules and Rails ___________lbs c. Total Number of Attachment Points____________ d. Weight per Attachment Point (b÷c)_________________lbs (if greater than 45 lbs, see WKS1) e. Maximum Spacing Between Attachment Points on a Rail ______________inches (see product manual for maximum spacing allowed based on maximum design wind speed) f. Total Surface Area of PV Modules (square feet)_________________ ft 2 g. Distributed Weight of PV Module on Roof (b÷f)_______________ lbs/ft2 If distributed weight of the PV system is greater than 5 lbs/ft2, see WKS1. Step 2: Electrical Review of PV System (Calculations for Electrical Diagram) In order for a PV system to be considered for an expedited permit process, the following must apply: 1. PV modules, utility-interactive inverters, and combiner boxes are identified for use in PV systems. 2. The PV array is composed of 4 series strings or less per inverter. 3. The total inverter capacity has a continuous ac power output 13,440 Watts or less 4. The ac interconnection point is on the load side of service disconnecting means (690.64(B)). 5. One of the standard electrical diagrams (E1.1, E1.1a, E1.1b, or E1.1c) can be used to accurately represent the PV system. Interactive PDF diagrams are available at www.solarabcs.org/permitting. Fill out the standard electrical diagram completely. A guide to the electrical diagram is provided to help the applicant understand each blank to fill in. If the electrical system is more complex than the standard electrical diagram can effectively communicate, provide an alternative diagram with appropriate detail. 1406 W 12th St 05/19/23 Ex p e d i t e d P e r m i t P r o c e s s f o r P V S y s t e m s 3 Micro-Inverter Site Plan                                                        EMpower Solar 1406 W 12th St Santa Ana, California - 92703 5.65 1406 W 12th St 05/19/23 Ex p e d i t e d P e r m i t P r o c e s s f o r P V S y s t e m s 4 Micro-Inverter Electrical Diagram Contractor Name, Address and Phone: One-Line Standard Electrical Diagram for Micro-Inverter PV Systems Site Name: Site Address: System AC Size: SIZE FSCM NO DWG NO REV E1.1a SCALE NTS Date: SHEET Drawn By: Checked By: DESCRIPTION OR CONDUCTOR TYPE USE-2 or PV WIRE GEC EGC X ALL THAT APPLY EXTERIOR CABLE LISTED W/ INV. THWN-2 or XHHW-2 or RHW-2 GEC EGC X ALL THAT APPLY NO DC GEC IF 690.35 SYSTEM THWN-2 or XHHW-2 or RHW-2 GEC EGC X ALL THAT APPLY TAG 1 2 3 4 5 CONDUIT AND CONDUCTOR SCHEDULE COND. GAUGE MFG MFG NUMBER OF CONDUCTORS MFG Cable MFG Cable CONDUIT TYPE N/A N/A N/A SAME SAME CONDUIT SIZE N/A N/A N/A SAME SAME DESCRIPTION PV DC or AC MODULE DC/AC INVERTER (MICRO) J-BOX (IF USED) PV ARRAY AC COMB. PANEL (IF USED) GEN METER (IF USED) AC DISCONNECT (IF USED) SERVICE PANEL TAG 1 2 3 4 5 6 7 8 PART NUMBER NOTES FOR UNUSED MODULES PUT "N/A” in BLANK ABOVE 1 1 3 2 3 EQUIPMENT SCHEDULE 2 _____ MICRO-INVERTERS IN BRANCH- CIRCUIT MOD ____ DC AC MOD ____ DC AC MOD ____ DC AC MOD ____ DC AC MOD ____ DC AC MOD ____ DC AC J-BOX 4 AC DISCO M BUILDING GROUNDING ELECTRODE G M UTILITY SERVICE MAIN SERVICE PANEL MAIN OCPD INVERTER OCPD 6 7 8 5 4 5 G SEE GUIDE APPENDIX D FOR INFORMATION ON MODULE AND ARRAY GROUNDING AC COMBINER PANEL G ____ MICRO-INVERTERS IN BRANCH- CIRCUIT EMpower Solar 5.65 1406 W 12th St Santa Ana, California - 92703 1406 W 12th St 05/19/23 Ex p e d i t e d P e r m i t P r o c e s s f o r P V S y s t e m s 5 Contractor Name, Address and Phone: Notes for One-Line Standard Electrical Diagram for Single-Phase PV Systems Site Name: Site Address: System AC Size: SIZE FSCM NO DWG NO REV E1.2a SCALE NTS Date: SHEET Drawn By: Checked By: MAX POWER-POINT CURRENT (IMP) MAX POWER-POINT VOLTAGE (VMP) OPEN-CIRCUIT VOLTAGE (VOC) SHORT-CIRCUIT CURRENT (ISC) MAX SERIES FUSE (OCPD) MAXIMUM POWER (PMAX) MAX VOLTAGE (TYP 600VDC) VOC TEMP COEFF (mV/oC or %/oC ) IF COEFF SUPPLIED, CIRCLE UNITS MODULE MAKE MODULE MODEL PV MODULE RATINGS @ STC (Guide Section 5) MAX DC VOLT RATING MAX POWER @ 40oC NOMINAL AC VOLTAGE MAX AC CURRENT MAX OCPD RATING INVERTER MAKE INVERTER MODEL INVERTER RATINGS (Guide Section 4) 1) IF UTILITY REQUIRES A VISIBLE-BREAK SWITCH, DOES THIS SWITCH MEET THE REQUIREMENT? YES NO N/A 2) IF GENERATION METER REQUIRED, DOES THIS METER SOCKET MEET THE REQUIREMENT? YES NO N/A 3) SIZE PHOTOVOLTAIC POWER SOURCE (DC) CONDUCTORS BASED ON MAX CURRENT ON NEC 690.53 SIGN OR OCPD RATING AT DISCONNECT 4) SIZE INVERTER OUTPUT CIRCUIT (AC) CONDUCTORS ACCORDING TO INVERTER OCPD AMPERE RATING. (See Guide Section 9) 5) TOTAL OF ______ INVERTER OUTPUT CIRCUIT OCPD(s), ONE FOR EACH MICRO- INVERTER CIRCUIT. DOES TOTAL SUPPLY BREAKERS COMPLY WITH 120% BUSBAR EXCEPTION IN 690.64(B)(2)(a)? YES NO NOTES FOR INVERTER CIRCUITS (Guide Section 8 and 9): 1.) LOWEST EXPECT AMBIENT TEMPERATURE BASED ON ASHRAE MINIMUM MEAN EXTREME DRY BULB TEMPERATURE FOR ASHRAE LOCATION MOST SIMILAR TO INSTALLATION LOCATION. LOWEST EXPECTED AMBIENT TEMP ____oC 2.) HIGHEST CONTINUOUS AMBIENT TEMPERATURE BASED ON ASHRAE HIGHEST MONTH 2% DRY BULB TEMPERATURE FOR ASHRAE LOCATION MOST SIMILAR TO INSTALLATION LOCATION. HIGHEST CONTINUOUS TEMPERATURE ____oC 2.) 2009 ASHRAE FUNDAMENTALS 2% DESIGN TEMPERATURES DO NOT EXCEED 47oC IN THE UNITED STATES (PALM SPRINGS, CA IS 44.1 oC). FOR LESS THAN 9 CURRENT-CARRYING CONDUCTORS IN ROOF-MOUNTED SUNLIT CONDUIT AT LEAST 0.5" ABOVE ROOF AND USING THE OUTDOOR DESIGN TEMPERATURE OF 47oC OR LESS (ALL OF UNITED STATES), a) 12 AWG, 90 oC CONDUCTORS ARE GENERALLY ACCEPTABLE FOR MODULES WITH Isc OF 7.68 AMPS OR LESS WHEN PROTECTED BY A 12-AMP OR SMALLER FUSE. b) 10 AWG, 90oC CONDUCTORS ARE GENERALLY ACCEPTABLE FOR MODULES WITH Isc OF 9.6 AMPS OR LESS WHEN PROTECTED BY A 15-AMP OR SMALLER FUSE. NOTES FOR ARRAY CIRCUIT WIRING (Guide Section 6 and 8 and Appendix E): OCPD = OVERCURRENT PROTECTION DEVICE NATIONAL ELECTRICAL CODE®REFERENCES SHOWN AS (NEC XXX.XX) NOTES FOR ALL DRAWINGS: SIGNS–SEE GUIDE SECTION 7 SIGN FOR DC DISCONNECT SIGN FOR INVERTER OCPD AND AC DISCONNECT (IF USED) No sign necessary since 690.51 marking on PV module covers needed information AC OUTPUT CURRENT NOMINAL AC VOLTAGE SOLAR PV SYSTEM AC POINT OF CONNECTION THIS PANEL FED BY MULTIPLE SOURCES (UTILITY AND SOLAR) Notes for Micro-Inverter Electrical Diagram EMpower Solar 1406 W 12th St Santa Ana, California - 92703 5.65 1406 W 12th St 05/19/23 Project : Project Number: By : Date : UNIRAC 1411 Broadway Blvd, NE Albuquerque, NM 87102 RE: Solar Array Installation at 1406 W 12th St, Santa Ana, CA 92703, USA To Whom it May Concern, CODE REFERENCES: BUILDING CODE: 2022 CALIFORNIA BUILDING CODE 2021 INTERNATIONAL BUILDING CODE ASCE 7-16 SCOPE OF WORK: DESIGN PARAMETERS RISK CATEGORY : DESIGN WIND SPEED :mph WIND EXPOSURE : GROUND SNOW LOAD :psf SEISMIC DESIGN CATEGORY : EXISTING ROOF STRUCTURE ROOF : 2x4 Rafters @ 28" O.C. ROOF MATERIAL : Asphalt Shingles CONNECTION TO ROOF STRUCTURE MOUNTING CONNECTION : Abel Gonzalez Chavez PE 18-03-2023 Roof structural framing plan has been reviewed for additional loading due to installation of the roof mounted solar PV addition. The structural review that follows, including plans and calculations, only apply to the section of the roof that is directly supporting the solar PV system and its supporting elements. 18 March 2023 Per your request, we have reviewed the existing structure at the above referenced site. The purpose of our review was to determine the adequacy of the existing structure to support the proposed installation of solar panels on the roof per layout plan. (1) 5/16" SS LAG BOLT w/ MIN. 2.5" EMBEDMENT INTO (E) 2x FRAMING MEMBER @ MAX. 56" o.c. ALONG RAILS (2) RAILS PER ROW OF PANELS, EVENLY SPACED. PANEL LENGTH PERPENDICULAR TO RAIL NOT TO EXCEED 67.79" II 95 C 0 *null 1406 W 12th St 05/19/23 OBSERVED CONDITIONS: CONCLUSIONS: LIMITATIONS: Praneet R Erusu, P.E. Principal Engineer Erusu Consultants US Inc. The observed roof framing is described below. If field conditions differ, the contractor shall notify the engineer prior to starting construction. The roof framing is supported by 2x4 Rafters @ 28" O.C are spanning between load bearing walls. The maximum allowed clear span of rafter is 6.5ft, to be verified in field by the contractor. Based upon our review, we conclude that the existing structure is adequate to support the proposed solar panel installation. In the area of the solar array, other live loads will not be present or will be greatly reduced (2022 CBC, Section 1607.14.4). The gravity loads and the stresses of the structural elements, in the area of the solar array are either decreased or increased by no more than 5%. Therefore, the requirements of Section 503.3 of the 2022 CEBC are met and the structure is permitted to remain unaltered. The solar array will be flush-mounted (no more than 6" above the roof surface) and parallel to the roof surface. Thus, we conclude that any additional wind loading on the structure related to the addition of the proposed solar array is negligible. The attached calculations verify the capacity of the connections of the solar array to the existing roof against wind (uplift), the governing load case. Regarding seismic loads, we conclude that any additional forces will be small. Conservatively neglecting the weight of existing wall materials, the installation of the solar panels represents an increase in the total weight (and resulting seismic load) of 4.2%. Because the increase in lateral forces is less than 10%, this addition meets the requirements of the exception in Section 503.4 of the 2022 CEBC. Thus the existing lateral force resisting system is permitted to remain unaltered. Installation of the solar panels must be performed in accordance with manufacturer recommendations. All work performed must be in accordance with accepted industry-wide methods and applicable safety standards. Existing Roof and structural members are assumed to be in good and serviceable condition. The contractor must notify Erusu Consultants US Inc. should any damage, deterioration or discrepancies between the as-built condition of the structure and the condition described in this letter be found. The use of solar panel support span tables provided by others are allowed only where the building type, site conditions, site-specific design parameters, and solar panel configuration match the description of the span tables. The design of the solar panel racking (mounts, rails, etc.) and electrical engineering is the responsibility of others. Waterproofing around the roof penetrations is the responsibility of others. Erusu Consultants US Inc. assumes no responsibility for improper installation of the solar array. 18 Mar 2023 EXP : 30 Sep 2023 1406 W 12th St 05/19/23 Project : Project Number: By : Date : Address : Site Plan: Abel Gonzalez Chavez PE 18-03-2023 1406 W 12th St, Santa Ana, CA 92703, USA 1406 W 12th St 05/19/23 Project : Project Number: By : Date : Roof Dead Load Roof Slope =: Angle = Roof Live Load Roof Live Load = psf (Refer ASCE 7-16, Table 4.3-1) Roof Live Load with PV Array = psf 2022 CBC, Section 1607.14.4 (Ceiling load and MEP is assumed to be not supported by rafter) 3.16 1/2" Gypsum Ceiling Abel Gonzalez Chavez PE 18-03-2023 DL = Increase due to Roof Slope Plan Projected Material Weight (psf) 4.22 1.16 3.16 0.53Insulation0.5 1.05 2.32 1.50 12.88 1/2" Plywood 1.1 1.05 Framing 3 1.05 Asphalt Shingles 4 1.05 4 12 18 Material Material Weight (psf) PV Array 3 1.05 2.2 1.05 MEP & Misc.1.5 20 0 1406 W 12th St 05/19/23 Project : Project Number: By : Date : Abel Gonzalez Chavez PE 18-03-2023 Summary of Gravity Loads Dead Load, D =psf Roof Live Load, Lr =psf Gravity Load Comparison (D + Lr)/Cd =psf (Cd = 0.9 for D, 1.15 for S, 1.25 for Lr) Max Loading =psf Proposed to Current Loading Ratio = Existing With PV Array 12.88 16.05 30.32 17.83 20.00 0.00 Existing With PV Array O.K. Gravity Loading with PV Array is not stressing the current framing system by more that 5% of the original configuration. Per Section 503.3 of 2022 California Existing Building Code the structure is allowed to remain unaltered for gravity loading 30.32 17.83 59% < 105% 1406 W 12th St 05/19/23 Wood Beam LIC# : KW-06014559, Build:20.23.2.14 ERUSU CONSULTANTS US (c) ENERCALC INC 1983-2022 DESCRIPTION: 2x4 Rafters @ 28" o.c. (Wind Condition_Downward) (Strength Check) Project File: 2x4 Joist @ 28 O.C.ec6 Project Title: Engineer: Project ID: Printed: 15 MAR 2023, 4:40PM Project Descr: CODE REFERENCES Calculations per NDS 2018, IBC 2021, ASCE 7-16 Load Combination Set : ASCE 7-16 Material Properties Beam Bracing : Beam is Fully Braced against lateral-torsional buckling Repetitive Member Stress Increase Allowable Stress Design Douglas Fir-Larch No.2 900.0 900.0 1,350.0 625.0 1,600.0 580.0 180.0 575.0 31.210 Analysis Method : Eminbend - xx ksi Wood Species : Wood Grade : Fb + psi psi Fv psi Fb - Ft psi Fc - Prll psi psiFc - Perp E : Modulus of Elasticity Ebend- xx ksi Density pcf Load Combination :ASCE 7-16 . Applied Loads Service loads entered. Load Factors will be applied for calculations. Beam self weight NOT internally calculated and added Load for Span Number 1 Uniform Load : D = 0.00810, Lr = 0.020, W = 0.0160 ksf, Tributary Width = 2.330 ft, (Existing Roof Load) Load for Span Number 2 Uniform Load : D = 0.00810 ksf, Tributary Width = 2.330 ft, (Existing Roof Dead Load) Point Load : D = 0.040, W = 0.2110 k @ 2.30 ft, (Solar Panel Load) Point Load : D = 0.040, W = 0.2110 k @ 5.80 ft, (Solar Panel Load) Uniform Load : Lr = 0.020, W = 0.0160 ksf, Extent = 0.0 -->> 1.30 ft, Tributary Width = 2.330 ft, (Existing Wind & Roof Live Load) .DESIGN SUMMARY Design OK Maximum Bending Stress Ratio 0.534: 1 Load Combination +D+0.60W+H Span # where maximum occurs Span # 2 Location of maximum on span 2.324 ft 72.48 psi= = 2,484.00 psi 2x4 Section used for this span Span # where maximum occurs Location of maximum on span Span # 2= Load Combination +D+0.60W+H = = = 288.00 psi== Section used for this span 2x4 Maximum Shear Stress Ratio 0.252 : 1 6.209 ft= = 1,326.79 psi Maximum Deflection 206 >=180 271 Ratio =200 >=120 Max Downward Transient Deflection 0.271 in 287 Ratio =>=180 Max Upward Transient Deflection -0.231 in Ratio = Max Downward Total Deflection 0.288 in Ratio =>=120 Max Upward Total Deflection -0.240 in fb: Actual F'b fv: Actual F'v Span: 2 : W Only Span: 2 : Lr Only Span: 2 : +D+0.60W+H Span: 1 : +D+0.60W+H .Maximum Forces & Stresses for Load Combinations Span # Moment ValuesLoad Combination C i CLx CCCM C F r t Shear ValuesMax Stress Ratios M CD V fb M fv F'b V F'v Segment Length Cfu +D+H 0.0 0.00 0.00.0 1.00 Length = 2.0 ft 1 0.106 0.162 0.90 1.500 1.15 1.00 1.00 0.04 147.9 1,397.3 0.09 162.01.00 26.2 1.00 1.00 Length = 6.50 ft 2 0.396 0.176 0.90 1.500 1.15 1.00 1.00 0.14 553.4 1,397.3 0.10 162.01.00 28.5 1.00 1.00 +D+L+H 1.500 1.15 1.00 1.00 0.0 0.00 0.01.00 0.0 1.00 1.00 Length = 2.0 ft 1 0.095 0.146 1.00 1.500 1.15 1.00 1.00 0.04 147.9 1,552.5 0.09 180.01.00 26.2 1.00 1406 W 12th St 05/19/23 Wood Beam LIC# : KW-06014559, Build:20.23.2.14 ERUSU CONSULTANTS US (c) ENERCALC INC 1983-2022 DESCRIPTION: 2x4 Rafters @ 28" o.c. (Wind Condition_Downward) (Strength Check) Project File: 2x4 Joist @ 28 O.C.ec6 Project Title: Engineer: Project ID: Printed: 15 MAR 2023, 4:40PM Project Descr: Maximum Forces & Stresses for Load Combinations Span # Moment ValuesLoad Combination C iCLx CCCM C F r t Shear ValuesMax Stress Ratios M CD V fb M fv F'b V F'vSegment Length Cfu 1.00 Length = 6.50 ft 2 0.356 0.159 1.00 1.500 1.15 1.00 1.00 0.14 553.4 1,552.5 0.10 180.01.00 28.5 1.00 1.00 +D+Lr+H 1.500 1.15 1.00 1.00 0.0 0.00 0.01.00 0.0 1.00 1.00 Length = 2.0 ft 1 0.264 0.187 1.25 1.500 1.15 1.00 1.00 0.13 513.1 1,940.6 0.15 225.01.00 42.0 1.00 1.00 Length = 6.50 ft 2 0.264 0.187 1.25 1.500 1.15 1.00 1.00 0.13 513.1 1,940.6 0.15 225.01.00 42.0 1.00 1.00 +D+S+H 1.500 1.15 1.00 1.00 0.0 0.00 0.01.00 0.0 1.00 1.00 Length = 2.0 ft 1 0.083 0.127 1.15 1.500 1.15 1.00 1.00 0.04 147.9 1,785.4 0.09 207.01.00 26.2 1.00 1.00 Length = 6.50 ft 2 0.310 0.138 1.15 1.500 1.15 1.00 1.00 0.14 553.4 1,785.4 0.10 207.01.00 28.5 1.00 1.00 +D+0.750Lr+0.750L+H 1.500 1.15 1.00 1.00 0.0 0.00 0.01.00 0.0 1.00 1.00 Length = 2.0 ft 1 0.217 0.169 1.25 1.500 1.15 1.00 1.00 0.11 421.8 1,940.6 0.13 225.01.00 38.1 1.00 1.00 Length = 6.50 ft 2 0.244 0.169 1.25 1.500 1.15 1.00 1.00 0.12 473.1 1,940.6 0.13 225.01.00 38.1 1.00 1.00 +D+0.750L+0.750S+H 1.500 1.15 1.00 1.00 0.0 0.00 0.01.00 0.0 1.00 1.00 Length = 2.0 ft 1 0.083 0.127 1.15 1.500 1.15 1.00 1.00 0.04 147.9 1,785.4 0.09 207.01.00 26.2 1.00 1.00 Length = 6.50 ft 2 0.310 0.138 1.15 1.500 1.15 1.00 1.00 0.14 553.4 1,785.4 0.10 207.01.00 28.5 1.00 1.00 +D+0.60W+H 1.500 1.15 1.00 1.00 0.0 0.00 0.01.00 0.0 1.00 1.00 Length = 2.0 ft 1 0.130 0.212 1.60 1.500 1.15 1.00 1.00 0.08 323.2 2,484.0 0.21 288.01.00 61.1 1.00 1.00 Length = 6.50 ft 2 0.534 0.252 1.60 1.500 1.15 1.00 1.00 0.34 1,326.8 2,484.0 0.25 288.01.00 72.5 1.00 1.00 +D+0.750Lr+0.750L+0.450W+H 1.500 1.15 1.00 1.00 0.0 0.00 0.01.00 0.0 1.00 1.00 Length = 2.0 ft 1 0.223 0.223 1.60 1.500 1.15 1.00 1.00 0.14 553.3 2,484.0 0.22 288.01.00 64.2 1.00 1.00 Length = 6.50 ft 2 0.414 0.223 1.60 1.500 1.15 1.00 1.00 0.26 1,027.1 2,484.0 0.22 288.01.00 64.2 1.00 1.00 +D+0.750L+0.750S+0.450W+H 1.500 1.15 1.00 1.00 0.0 0.00 0.01.00 0.0 1.00 1.00 Length = 2.0 ft 1 0.112 0.182 1.60 1.500 1.15 1.00 1.00 0.07 279.4 2,484.0 0.18 288.01.00 52.4 1.00 1.00 Length = 6.50 ft 2 0.454 0.214 1.60 1.500 1.15 1.00 1.00 0.29 1,128.8 2,484.0 0.22 288.01.00 61.5 1.00 1.00 +0.60D+0.60W+0.60H 1.500 1.15 1.00 1.00 0.0 0.00 0.01.00 0.0 1.00 1.00 Length = 2.0 ft 1 0.106 0.176 1.60 1.500 1.15 1.00 1.00 0.07 264.0 2,484.0 0.18 288.01.00 50.6 1.00 1.00 Length = 6.50 ft 2 0.448 0.212 1.60 1.500 1.15 1.00 1.00 0.28 1,112.9 2,484.0 0.21 288.01.00 61.1 1.00 1.00 +D+0.70E+0.60H 1.500 1.15 1.00 1.00 0.0 0.00 0.01.00 0.0 1.00 1.00 Length = 2.0 ft 1 0.060 0.091 1.60 1.500 1.15 1.00 1.00 0.04 147.9 2,484.0 0.09 288.01.00 26.2 1.00 1.00 Length = 6.50 ft 2 0.223 0.099 1.60 1.500 1.15 1.00 1.00 0.14 553.4 2,484.0 0.10 288.01.00 28.5 1.00 1.00 +D+0.750L+0.750S+0.5250E+H 1.500 1.15 1.00 1.00 0.0 0.00 0.01.00 0.0 1.00 1.00 Length = 2.0 ft 1 0.060 0.091 1.60 1.500 1.15 1.00 1.00 0.04 147.9 2,484.0 0.09 288.01.00 26.2 1.00 1.00 Length = 6.50 ft 2 0.223 0.099 1.60 1.500 1.15 1.00 1.00 0.14 553.4 2,484.0 0.10 288.01.00 28.5 1.00 1.00 +0.60D+0.70E+H 1.500 1.15 1.00 1.00 0.0 0.00 0.01.00 0.0 1.00 1.00 Length = 2.0 ft 1 0.036 0.055 1.60 1.500 1.15 1.00 1.00 0.02 88.7 2,484.0 0.06 288.01.00 15.7 1.00 1.00 Length = 6.50 ft 2 0.134 0.059 1.60 1.500 1.15 1.00 1.00 0.08 332.0 2,484.0 0.06 288.01.00 17.1 1.00 . Location in SpanLoad CombinationMax. "-" Defl Location in Span Load Combination Span Max. "+" Defl Overall Maximum Deflections +D+0.60W+H 1 0.0000 0.000 -0.2400 0.000 +D+0.60W+H 2 0.2876 3.268 0.0000 0.000 . Load Combination Support 1 Support 2 Support 3 Vertical Reactions Support notation : Far left is #1 Values in KIPS Max Upward from all Load Conditions 0.387 0.259 Max Upward from Load Combinations 0.387 0.259 Max Upward from Load Cases 0.289 0.256 Max Downward from all Load Conditio -0.008 Max Downward from Load Cases (Resis -0.008 +D+H 0.135 0.105 +D+L+H 0.135 0.105 +D+Lr+H 0.297 0.097 +D+S+H 0.135 0.105 1406 W 12th St 05/19/23 Wood Beam LIC# : KW-06014559, Build:20.23.2.14 ERUSU CONSULTANTS US (c) ENERCALC INC 1983-2022 DESCRIPTION: 2x4 Rafters @ 28" o.c. (Wind Condition_Downward) (Strength Check) Project File: 2x4 Joist @ 28 O.C.ec6 Project Title: Engineer: Project ID: Printed: 15 MAR 2023, 4:40PM Project Descr: Load Combination Support 1 Support 2 Support 3 Vertical Reactions Support notation : Far left is #1 Values in KIPS +D+0.750Lr+0.750L+H 0.257 0.099 +D+0.750L+0.750S+H 0.135 0.105 +D+0.60W+H 0.308 0.259 +D+0.750Lr+0.750L+0.450W+H 0.387 0.215 +D+0.750L+0.750S+0.450W+H 0.265 0.221 +0.60D+0.60W+0.60H 0.254 0.217 +D+0.70E+0.60H 0.135 0.105 +D+0.750L+0.750S+0.5250E+H 0.135 0.105 +0.60D+0.70E+H 0.081 0.063 D Only 0.135 0.105 Lr Only 0.162 -0.008 W Only 0.289 0.256 H Only 1406 W 12th St 05/19/23 Wood Beam LIC# : KW-06014559, Build:20.23.2.14 ERUSU CONSULTANTS US (c) ENERCALC INC 1983-2022 DESCRIPTION: 2x4 Rafters @ 28" o.c. (Wind Condition_Uplift) (Strength Check) Project File: 2x4 Joist @ 28 O.C.ec6 Project Title: Engineer: Project ID: Printed: 15 MAR 2023, 4:40PM Project Descr: CODE REFERENCES Calculations per NDS 2018, IBC 2021, ASCE 7-16 Load Combination Set : ASCE 7-16 Material Properties Beam Bracing : Beam is Fully Braced against lateral-torsional buckling Repetitive Member Stress Increase Allowable Stress Design Douglas Fir-Larch No.2 900.0 900.0 1,350.0 625.0 1,600.0 580.0 180.0 575.0 31.210 Analysis Method : Eminbend - xx ksi Wood Species : Wood Grade : Fb + psi psi Fv psi Fb - Ft psi Fc - Prll psi psiFc - Perp E : Modulus of Elasticity Ebend- xx ksi Density pcf Load Combination :ASCE 7-16 . Applied Loads Service loads entered. Load Factors will be applied for calculations. Beam self weight NOT internally calculated and added Load for Span Number 1 Uniform Load : D = 0.00810, Lr = 0.020, W = -0.0520 ksf, Tributary Width = 2.330 ft, (Existing Roof Load) Load for Span Number 2 Uniform Load : D = 0.00810 ksf, Tributary Width = 2.330 ft, (Existing Roof Dead Load) Point Load : D = 0.040, W = -0.6860 k @ 2.30 ft, (Solar Panel Load) Point Load : D = 0.040, W = -0.6860 k @ 5.80 ft, (Solar Panel Load) Uniform Load : Lr = 0.020, W = -0.0520 ksf, Extent = 0.0 -->> 1.30 ft, Tributary Width = 2.330 ft, (Existing Wind & Roof Live Load) . DESIGN SUMMARY Design OK Maximum Bending Stress Ratio 0.908: 1 Load Combination +0.60D+0.60W+0.60H Span # where maximum occurs Span # 2 Location of maximum on span 2.324 ft 127.02 psi= = 2,484.00 psi 2x4 Section used for this span Span # where maximum occurs Location of maximum on span Span # 2= Load Combination +0.60D+0.60W+0.60H = = = 288.00 psi== Section used for this span 2x4 Maximum Shear Stress Ratio 0.441 : 1 5.810 ft= = 2,254.65 psi Maximum Deflection 88 >=62 122 Ratio =171 >=120 Max Downward Transient Deflection 0.752 in 62 Ratio =>=62 Max Upward Transient Deflection -0.883 in Ratio = Max Downward Total Deflection 0.390 in Ratio =>=120 Max Upward Total Deflection -0.455 in fb: Actual F'b fv: Actual F'v Span: 1 : W Only Span: 2 : W Only Span: 2 : +D+H Span: 2 : +0.60D+0.60W+0.60H .Maximum Forces & Stresses for Load Combinations Span # Moment ValuesLoad Combination C i CLx CCCM C F rt Shear ValuesMax Stress Ratios M CD V fb M fv F'b V F'v Segment Length Cfu +D+H 0.0 0.00 0.00.0 1.00 Length = 2.0 ft 1 0.106 0.162 0.90 1.500 1.15 1.00 1.00 0.04 147.9 1,397.3 0.09 162.01.00 26.2 1.00 1.00 Length = 6.50 ft 2 0.396 0.176 0.90 1.500 1.15 1.00 1.00 0.14 553.4 1,397.3 0.10 162.01.00 28.5 1.00 1.00 +D+L+H 1.500 1.15 1.00 1.00 0.0 0.00 0.01.00 0.0 1.00 1.00 Length = 2.0 ft 1 0.095 0.146 1.00 1.500 1.15 1.00 1.00 0.04 147.9 1,552.5 0.09 180.01.00 26.2 1.00 1406 W 12th St 05/19/23 Wood Beam LIC# : KW-06014559, Build:20.23.2.14 ERUSU CONSULTANTS US (c) ENERCALC INC 1983-2022 DESCRIPTION: 2x4 Rafters @ 28" o.c. (Wind Condition_Uplift) (Strength Check) Project File: 2x4 Joist @ 28 O.C.ec6 Project Title: Engineer: Project ID: Printed: 15 MAR 2023, 4:40PM Project Descr: Maximum Forces & Stresses for Load Combinations Span # Moment ValuesLoad Combination C iCLx CCCM C F r t Shear ValuesMax Stress Ratios M CD V fb M fv F'b V F'vSegment Length Cfu 1.00 Length = 6.50 ft 2 0.356 0.159 1.00 1.500 1.15 1.00 1.00 0.14 553.4 1,552.5 0.10 180.01.00 28.5 1.00 1.00 +D+Lr+H 1.500 1.15 1.00 1.00 0.0 0.00 0.01.00 0.0 1.00 1.00 Length = 2.0 ft 1 0.264 0.187 1.25 1.500 1.15 1.00 1.00 0.13 513.1 1,940.6 0.15 225.01.00 42.0 1.00 1.00 Length = 6.50 ft 2 0.264 0.187 1.25 1.500 1.15 1.00 1.00 0.13 513.1 1,940.6 0.15 225.01.00 42.0 1.00 1.00 +D+S+H 1.500 1.15 1.00 1.00 0.0 0.00 0.01.00 0.0 1.00 1.00 Length = 2.0 ft 1 0.083 0.127 1.15 1.500 1.15 1.00 1.00 0.04 147.9 1,785.4 0.09 207.01.00 26.2 1.00 1.00 Length = 6.50 ft 2 0.310 0.138 1.15 1.500 1.15 1.00 1.00 0.14 553.4 1,785.4 0.10 207.01.00 28.5 1.00 1.00 +D+0.750Lr+0.750L+H 1.500 1.15 1.00 1.00 0.0 0.00 0.01.00 0.0 1.00 1.00 Length = 2.0 ft 1 0.217 0.169 1.25 1.500 1.15 1.00 1.00 0.11 421.8 1,940.6 0.13 225.01.00 38.1 1.00 1.00 Length = 6.50 ft 2 0.244 0.169 1.25 1.500 1.15 1.00 1.00 0.12 473.1 1,940.6 0.13 225.01.00 38.1 1.00 1.00 +D+0.750L+0.750S+H 1.500 1.15 1.00 1.00 0.0 0.00 0.01.00 0.0 1.00 1.00 Length = 2.0 ft 1 0.083 0.127 1.15 1.500 1.15 1.00 1.00 0.04 147.9 1,785.4 0.09 207.01.00 26.2 1.00 1.00 Length = 6.50 ft 2 0.310 0.138 1.15 1.500 1.15 1.00 1.00 0.14 553.4 1,785.4 0.10 207.01.00 28.5 1.00 1.00 +D+0.60W+H 1.500 1.15 1.00 1.00 0.0 0.00 0.01.00 0.0 1.00 1.00 Length = 2.0 ft 1 0.170 0.302 1.60 1.500 1.15 1.00 1.00 0.11 421.8 2,484.0 0.30 288.01.00 87.1 1.00 1.00 Length = 6.50 ft 2 0.822 0.404 1.60 1.500 1.15 1.00 1.00 0.52 2,040.8 2,484.0 0.41 288.01.00 116.5 1.00 1.00 +D+0.750Lr+0.750L+0.450W+H 1.500 1.15 1.00 1.00 0.0 0.00 0.01.00 0.0 1.00 1.00 Length = 2.0 ft 1 0.002 0.163 1.60 1.500 1.15 1.00 1.00 0.00 5.5 2,484.0 0.16 288.01.00 46.9 1.00 1.00 Length = 6.50 ft 2 0.603 0.287 1.60 1.500 1.15 1.00 1.00 0.38 1,498.5 2,484.0 0.29 288.01.00 82.5 1.00 1.00 +D+0.750L+0.750S+0.450W+H 1.500 1.15 1.00 1.00 0.0 0.00 0.01.00 0.0 1.00 1.00 Length = 2.0 ft 1 0.112 0.204 1.60 1.500 1.15 1.00 1.00 0.07 279.4 2,484.0 0.21 288.01.00 58.7 1.00 1.00 Length = 6.50 ft 2 0.562 0.280 1.60 1.500 1.15 1.00 1.00 0.36 1,396.9 2,484.0 0.28 288.01.00 80.8 1.00 1.00 +0.60D+0.60W+0.60H 1.500 1.15 1.00 1.00 0.0 0.00 0.01.00 0.0 1.00 1.00 Length = 2.0 ft 1 0.194 0.339 1.60 1.500 1.15 1.00 1.00 0.12 481.0 2,484.0 0.34 288.01.00 97.6 1.00 1.00 Length = 6.50 ft 2 0.908 0.441 1.60 1.500 1.15 1.00 1.00 0.58 2,254.6 2,484.0 0.44 288.01.00 127.0 1.00 1.00 +D+0.70E+0.60H 1.500 1.15 1.00 1.00 0.0 0.00 0.01.00 0.0 1.00 1.00 Length = 2.0 ft 1 0.060 0.091 1.60 1.500 1.15 1.00 1.00 0.04 147.9 2,484.0 0.09 288.01.00 26.2 1.00 1.00 Length = 6.50 ft 2 0.223 0.099 1.60 1.500 1.15 1.00 1.00 0.14 553.4 2,484.0 0.10 288.01.00 28.5 1.00 1.00 +D+0.750L+0.750S+0.5250E+H 1.500 1.15 1.00 1.00 0.0 0.00 0.01.00 0.0 1.00 1.00 Length = 2.0 ft 1 0.060 0.091 1.60 1.500 1.15 1.00 1.00 0.04 147.9 2,484.0 0.09 288.01.00 26.2 1.00 1.00 Length = 6.50 ft 2 0.223 0.099 1.60 1.500 1.15 1.00 1.00 0.14 553.4 2,484.0 0.10 288.01.00 28.5 1.00 1.00 +0.60D+0.70E+H 1.500 1.15 1.00 1.00 0.0 0.00 0.01.00 0.0 1.00 1.00 Length = 2.0 ft 1 0.036 0.055 1.60 1.500 1.15 1.00 1.00 0.02 88.7 2,484.0 0.06 288.01.00 15.7 1.00 1.00 Length = 6.50 ft 2 0.134 0.059 1.60 1.500 1.15 1.00 1.00 0.08 332.0 2,484.0 0.06 288.01.00 17.1 1.00 . Location in SpanLoad CombinationMax. "-" Defl Location in Span Load Combination Span Max. "+" Defl Overall Maximum Deflections W Only 1 0.7518 0.000 0.0000 0.000 W Only20.0000 0.000 -0.8827 3.232 . Load Combination Support 1 Support 2 Support 3 Vertical Reactions Support notation : Far left is #1 Values in KIPS Max Upward from all Load Conditions 0.297 0.105 Max Upward from Load Combinations 0.297 0.105 Max Upward from Load Cases 0.162 0.105 Max Downward from all Load Conditio -0.938 -0.833 Max Downward from Load Combinations -0.482 -0.437 Max Downward from Load Cases (Resis -0.938 -0.833 +D+H 0.135 0.105 +D+L+H 0.135 0.105 +D+Lr+H 0.297 0.097 1406 W 12th St 05/19/23 Wood Beam LIC# : KW-06014559, Build:20.23.2.14 ERUSU CONSULTANTS US (c) ENERCALC INC 1983-2022 DESCRIPTION: 2x4 Rafters @ 28" o.c. (Wind Condition_Uplift) (Strength Check) Project File: 2x4 Joist @ 28 O.C.ec6 Project Title: Engineer: Project ID: Printed: 15 MAR 2023, 4:40PM Project Descr: Load Combination Support 1 Support 2 Support 3 Vertical Reactions Support notation : Far left is #1 Values in KIPS +D+S+H 0.135 0.105 +D+0.750Lr+0.750L+H 0.257 0.099 +D+0.750L+0.750S+H 0.135 0.105 +D+0.60W+H -0.428 -0.395 +D+0.750Lr+0.750L+0.450W+H -0.166 -0.276 +D+0.750L+0.750S+0.450W+H -0.287 -0.270 +0.60D+0.60W+0.60H -0.482 -0.437 +D+0.70E+0.60H 0.135 0.105 +D+0.750L+0.750S+0.5250E+H 0.135 0.105 +0.60D+0.70E+H 0.081 0.063 D Only 0.135 0.105 Lr Only 0.162 -0.008 W Only -0.938 -0.833 H Only 1406 W 12th St 05/19/23 Project : Project Number: By : Date : Wind Load Calculation Wind Loads - ASCE 7-16 Chapter 26 & 29 Width of the Building, B = ft (Approximate) V = mph Exposure = Average height of building, z = ft - avg (Approximate) ft (Refer ASCE 7-16, Table 26.10-1) α = Zg = ft (Refer ASCE 7-16, Table 26.11-1) Kh & Kz = 2.01(z/Zg)^(2/α) = Kzt =(Refer ASCE 7-16, Equation 26.8-1) Kd =(Refer ASCE 7-16, Table 26.6.1) Ke =(Refer ASCE 7-16, Table 26.9-1) qh ='.00256 KzKztKdKeV² =psf (Refer ASCE 7-16, Section 26.10-1) Building Classification = Solar Panel Components and Cladding p C&C = qh(GCp)(ϒe)(ϒa) ASCE 7-16 Chaper 29.4.4 Module Length = in Module Width = in Area of Module = ft2 Roof Pitch =: Slope = degrees Gable Roof = ϒe= ϒa=(Refer ASCE 7-16, Figure 29.4-8) Abel Gonzalez Chavez PE 18-03-2023 900 zmin = 15 9.5 1 47.2 1 0.85 16.67 4.0 44.64 95 C 15 0.85 Enclosed 0.8 21.0 67.79 7° < θ ≤ 20° 1.5 12 18 1406 W 12th St 05/19/23 Project : Project Number: By : Date : Abel Gonzalez Chavez PE 18-03-2023 Zone 1 Uplift External Wind pressure coefficient GCp = External Wind pressure, qGCp = psf Zone 2 Uplift External Wind pressure coefficient GCp = External Wind pressure, qGCp = psf All Zone Downward External Wind pressure coefficient GCp = External Wind pressure, qGCp = psf Maximum Uplift Wind Pressure, p = psf Minimum Downward Wind Pressure ,p = psf Lag Screw / Bolt Connection Check (ASD) Tributary Width = in (Max Spacing of fasteners along Rails) Tributary Length = in (Half Panel Length) Tributary Area = ft2 Lag Screw/Bolt Size = Cd =(Refer NDS Table 2.3.2) Embedment = in Grade of Wood = #2 ( or better) G = Capacity = lb/in (Refer NDS Table 12.2A) Number of Screws in Tension = Prying Coefficient = Capacity of Fasteners = lb Demand -2.6 (Measured from top of the framing member to tapered tip of lag screw, embedment in sheathing and tapered tip of screw is not included) DF -52.01 -2 -40.01 -52.01 16.0 33.895 13.2 5/16 1.6 2.5 56 0.5 10.0 Uplift (lb) Zone 0.5 266 1 1.4 760 Zone 1 Zone 2 0.54 Pressure ASD (0.6W)(psf) -24.0 -31.2 13.2 411.4 760 DCR 13.2 316.4 760 0.42 Capacity (lb)Tributary Area (ft2) 1406 W 12th St 05/19/23 Project : Project Number: By : Date : Seismic Ground Motion Values Abel Gonzalez Chavez PE 18-03-2023 1406 W 12th St 05/19/23 Project : Project Number: By : Date : Seismic Design Force Seismic Loads - ASCE 7-16 Chapter 13 Seismic Force Component Amplification Factor, ap= (Refer ASCE 7-16, Table 13.6 -1) Overstrength Factor, Ωo =(Refer ASCE 7-16, Table 13.6 -1) Component Importance Factor, Ip= SDS = Average roof height of structure,h = ft z/h = z/h should not exceed 1 Frame Weight Wp = psf Seismic Design Force on Solar framing structure Max Fp =1.6 x SDS x Ip X Wp = psf Min Fp =0.3 x SDS x Ip X Wp = psf Seismic Design Load Fp = psf Vertical Seismic Design Load Fp = psf Seismic Coefficients for Mechanical and Electrical components = Component Response Modification Factor, Rp= 1.50 Abel Gonzalez Chavez PE 18-03-2023 12 Other mechanical or electrical components. (Refer ASCE 7-16, Table 13.6 -1) Height in structure at point of attachment, z = 15 ft 1.00 1.50 1.05 1.00 F P = ((0.4 x ap x SDS x Wp)/ (Rp / Ip)) x ((1+2(z/h)) =2.65 psf 15 1 2.65 5.29 0.99 3.16 0.66 1406 W 12th St 05/19/23 Project : Project Number: By : Date : Abel Gonzalez Chavez PE 18-03-2023 Check for Increase in overall seismic loads Array Area = ft2 Number of Arrays = Total Array Area = ft2 Array Load = psf Number of Existing Arrays = Exisitng Area = ft2 Total Array Wt. = lb Total Roof Area = ft2 DL of Roof = psf Total Wt of Roof = lb Increase in Seismic Wt = < 10% Conservatively the Wt. of the Walls tributary to the roof is not included. Seismic weight increase is less than 10% and no seismic retrofit or evaluation of existing lateral system is required per Section 503.4 of 2022 CEBC. 21.0 16 336.24 1878.3 3.00 1008.7 0 0.00 12.88 24200 4.2% 1406 W 12th St 05/19/23 Rev: 7/15/2021 RESIDENTIAL PHOTOVOLTAIC CHECKLIST SOL-01 CBC 2019 Solar Photovoltaic (PV) Checklist for Detached SINGLE FAMILY RESIDENCES Only Instructions: The licensed contractor of record shall complete all sections, answer the ten questions and sign the certification section below. A copy of this form shall be attached to each of TWO sets of plans, of minimum 11” x 17” size. If answering NO to any of the questions, plan check shall be required. Project Address: Contractor Company Name: Contractor License Number: YES NO Are the following applicable to the proposed project? 1.   Will the PV system layout provide the required three-foot wide clear access pathways per Section 605.11 of the California Fire Code, and is this shown on the roof plan? 2.   Will the PV system be installed on a roof having only one roofing layer with no overlays? 3.   Will the PV array be flush mounted to the existing roof so that the plane of the modules (panels) are parallel to the plane of the roof? 4.   Will the PV system weigh maximum 4 pounds per square feet or less? 5.   Will the PV system be installed where the modules do not overhang any roof edges (such as eaves, gabled ends, ridges and hips)? 6.   Will the PV system be installed with a space of 2” minimum to 10” maximum between the underside of modules and the surface of the roof? 7.   Will the PV system be installed without using any ballast system or counter-weight system? 8.   Will the anchors be installed with a maximum horizontal anchor spacing of 6 feet and is this maximum horizontal spacing shown on the plans? 9.   Will the minimum 5/16” lag screws be installed with a minimum of 2-1/2 inch embedment into roof rafters (with pre-drilled holes) and is this minimum embedment shown on the plans? 10.   Are ALL the structural pages of the plans stamped and signed by a California licensed professional engineer? (including project specific site plan, PV layout, anchorage spacing, anchorage details and manufacturer’s PV support information.) I certify under penalty of perjury under the laws of the State of California that the above is true: Print Name: Signature: Phone Number: Date: Email Address: Planning & Building Agency Building Safety Division 20 Civic Center Plaza P.O. Box 1988 (M-19) Santa Ana, CA 92702 (714) 647-5800 www.santa-ana.org 1406 W 12th St 05/19/23 Abel Gonzalez Chavez 1406 W 12th St 03/07/2023 1406 W 12th St 05/19/23 Envelope Report ID 8aa24f9f-488d-4ddf-9992-c2d87861614c Created 2023-03-08T03:16:00.488Z Document Signer Signer ID IP Address Timestamp California Consumer Protection Guide (CCPG) Empower Abel Gonzalez Chavez abel9954@sbcglobal.net 52a3012c11fa84276386974667bdcfd787562922bd69bae07b56c05693f1699d 99.8.0.253 2023-03- 08T03:19:27.182Z Empower Solar Home Improvement Contract Abel Gonzalez Chavez abel9954@sbcglobal.net 52a3012c11fa84276386974667bdcfd787562922bd69bae07b56c05693f1699d 99.8.0.253 2023-03- 08T03:20:49.822Z Empower Solar California - (CA) - Santa Ana - HO Authorization Abel Gonzalez Chavez abel9954@sbcglobal.net 52a3012c11fa84276386974667bdcfd787562922bd69bae07b56c05693f1699d 99.8.0.253 2023-03- 08T03:21:01.687Z California Consumer Protection Guide (CCPG) Empower Treven Hansen treven+sales@usrenewable.org 0f5a6e1e2bc4cc2553e42c48ae46d52d8307bd7545a8b567da2755c33a5947e2 0.0.0.0 2023-03- 08T03:15:58.458Z Empower Solar Home Improvement Contract Treven Hansen treven+sales@usrenewable.org 0f5a6e1e2bc4cc2553e42c48ae46d52d8307bd7545a8b567da2755c33a5947e2 0.0.0.0 2023-03- 08T03:15:58.453Z Empower Solar Home Improvement Contract Landon Wimmer ae3001dc49e584501eb993f2f3894e444d63e2a8b44421d739e62c6939dc9182 0.0.0.0 2023-03- 08T03:15:58.453Z 1406 W 12th St 05/19/23 COVER SHEET PHOTOVOLTAIC ROOF MOUNT SYSTEM 1406 W 12TH ST, SANTA ANA, CA 92703 USA REV SHEET NAME SHEET NUMBER DATE DESCRIPTION VERSION PV-0 PROJECT NAME UR03/14/2023 INITIAL RELEASE AB E L G O N Z A L E Z C H A V E Z 1 4 0 6 W 1 2 T H S T , SA N T A A N A , C A 9 2 7 0 3 U S A UT I L I T Y : S C E AH J : C I T Y O F S A N T A A N A SHEET SIZE ANSI B 11" X 17" EMPOWER ELECTRIC SOLAR 1300 E SHAW AVE,173 FRESNO, CA 93710 TEL: (559) 360-9292 CSLB: 1057693 Email : permits@mpwrsolar.com AP N : 0 0 4 1 1 2 0 7 SYSTEM SUMMARY: DESIGN CRITERIA: GOVERNING CODES: 2022 CALIFORNIA ELECTRICAL CODE (CEC) 2022 CALIFORNIA BUILDING CODE (CBC) 2022 CALIFORNIA EXISTING BUILDING CODE (CEBC) 2022 CALIFORNIA RESIDENTIAL CODE (CRC) 2022 CALIFORNIA GREEN CODE (CGC) 2022 CALIFORNIA MECHANICAL CODE (CMC) 2022 CALIFORNIA PLUMBING CODE (CPC) 2022 CA FIRE CODE TITLE 24 SUPPLEMENT ANY OTHER LOCAL AMENDMENTS 16 MODULES-ROOF MOUNTED - 6.24 kWDC, 5.65 CEC kWAC ROOF TYPE: - ASPHALT SHINGLE NUMBER OF LAYERS: - 01 ROOF FRAME: - 2"X4" RAFTERS @28" O.C. STORY: - ONE STORY SNOW LOAD : - 0 PSF WIND SPEED :- 95 MPH WIND EXPOSURE:- C RISK CATEGORY:- II COORDINATE:- 33.754764, -117.887156 2 VICINITY MAP SCALE: NTSPV-0 1 AERIAL PHOTO SCALE: NTSPV-0 GENERAL NOTES · THE CONTRACTOR/INSTALLER OF THE SOLAR PV SYSTEM OVER EXISTING ROOF SHALL CONFORM TO OSHA REQUIREMENTS DURING THE CONSTRUCTION PHASE. JOB SAFETY AND CONSTRUCTION PROCEDURES ARE THE SOLE RESPONSIBILITY OF THE CONTRACTOR/INSTALLER. · REFER TO ELECTRICAL DRAWING PV-4 FOR PANEL DETAILED INFORMATION. · IN CASE OF CONFLICT BETWEEN STRUCTURAL DRAWINGS AND ELECTRICAL DRAWINGS, THE MOST RIGID REQUIREMENTS SHALL GOVERN. · THE CONTRACTOR/INSTALLER SHALL VERIFY ALL EXISTING BUILDING INFORMATION SHOWN (DIMENSIONS, ROOF TOP PROJECTIONS, ETC.) AND NOTIFY THE ENGINEER OF ANY DISCREPANCIES PRIOR TO INSTALLATIONS OF PV SYSTEM. · THE CONTRACTOR/INSTALLER SHALL VERIFY AND COORDINATE EXISTING OPENINGS, ROOF TOP UNITS, VENT PIPES, ETC. SHOWN ON DRAWINGS. IF THERE IS A DISCREPANCY BETWEEN DRAWINGS, IT IS THE CONTRACTORS/INSTALLER'S RESPONSIBILITY TO NOTIFY ENGINEER PRIOR TO PERFORMING THE WORK. · ALL CONSTRUCTION IS TO BE PERFORMED IN STRICT CONFORMANCE WITH ALL APPLICABLE TOWN, COUNTY & STATE REGULATIONS AND/OR ANY OTHER GOVERNING BODIES. · DO NOT SCALE THESE DRAWINGS, USE DIMENSIONS. CONTRACTOR MUST CONDUCT ROOF SURVEY TO VERIFY DIMENSIONS SHOWN ON PLAN PRIOR TO INSTALLATION. IF THERE IS A DISCREPANCY IT IS CONTRACTOR/INSTALLER'S RESPONSIBILITY TO NOTIFY THE ENGINEER IMMEDIATELY. · LOCATED IN AREAS NOT REQUIRING PLACEMENT OF GROUND LADDERS OVER OPENINGS SUCH AS DOORS OR WINDOWS. · LOCATED AT STRONG POINTS OF BUILDING CONSTRUCTION IN LOCATIONS WHERE ACCESS POINT DOES NOT CONFLICT WITH OVERHEAD OBSTRUCTIONS SUCH AS TREE LIMBS, WIRES, OR SIGNS. · DISCONNECT MEANS MUST HAVE DEDICATED CLEAR UNOBSTRUCTED WORKING SPACE NOT LESS THAN 3' DEEP BY 2.5' WIDE TO NOT LESS THAN 6.5' ABOVE WALKABLE SURFACES IN FRONT OF DISTRIBUTION PANEL. · ALL SOLAR MODULES, EQUIPMENT, AND METALLIC COMPONENTS TO BE BONDED. · PV ARRAY NOT TO EXCEED HIGHEST POINT OF THE ROOF. · RAPID SHUTDOWN IS ACTIVED AT THE INVERTER BY THE AC DISCONNECT. ELECTRICAL NOTES · ALL EQUIPMENT TO BE LISTED BY UL OR OTHER NRTL, AND LABELED FOR ITS APPLICATION. · ALL CONDUCTORS SHALL BE COPPER, RATED FOR 600 V AND 90 DEGREE C WET ENVIRONMENT. ·WIRING, CONDUIT, AND RACEWAYS MOUNTED ON ROOFTOPS SHALL BE ROUTED DIRECTLY TO, AND LOCATED AS CLOSE AS POSSIBLE TO THE NEAREST RIDGE, HIP, OR VALLEY. · WORKING CLEARANCES AROUND ALL NEW AND EXISTING ELECTRICAL EQUIPMENT SHALL COMPLY WITH CEC 110.26. ·DRAWINGS INDICATE THE GENERAL ARRANGEMENT OF SYSTEMS. CONTRACTOR SHALL FURNISH ALL NECESSARY OUTLETS, SUPPORTS, FITTINGS AND ACCESSORIES TO FULFILL APPLICABLE CODES AND STANDARDS. ·WHERE SIZES OF JUNCTION BOXES, RACEWAYS, AND CONDUITS ARE NOT SPECIFIED, THE CONTRACTOR SHALL SIZE THEM ACCORDINGLY. ·ALL WIRE TERMINATIONS SHALL BE APPROPRIATELY LABELED AND READILY VISIBLE. ·MODULE GROUNDING CLIPS TO BE INSTALLED BETWEEN MODULE FRAME AND MODULE SUPPORT RAIL, PER THE GROUNDING CLIP MANUFACTURER'S INSTRUCTION. ·MODULE SUPPORT RAIL TO BE BONDED TO CONTINUOUS COPPER E.G.C. VIA WEEB LUG OR ILSCO GBL-4DBT LAY-IN LUG. ·THE POLARITY OF THE GROUNDED CONDUCTORS IS NEGATIVE SHEET INDEX PV-0 COVER SHEET PV-1 SITE PLAN WITH ROOF PLAN PV-2 ROOF PLAN WITH MODULES PV-3 ATTACHMENT DETAILS PV-4 ELECTRICAL LINE DIAGRAM WITH CALCULATION PV-5 PLACARDS & WARNING LABELS PV-6+ EQUIPMENT SPEC SHEETS (N) 16 - JA SOLAR JAM54S31-390/MR (390W) MODULES (N) 16 - ENPHASE ENERGY IQ7-60-2-US MICRO-INVERTERS (N) JUNCTION BOX (E) 200A MAIN SERVICE PANEL WITH (E) 200A MAIN BREAKER (N) 30A NON FUSED AC DISCONNECT (N) ENPHASE IQ COMBINER BOX 3 STRUCTURAL ONLY 18 Mar 2023 EXP : 30 Sep 2023 BLDG# 101115144 ISS. 05/19/2023 ELEC# 20179684 ISS. 05/19/2023 The scope of the plans is for the installation of the solar photovoltaic system only and the approval is subject to compliance with all applicable city and state codes and regulations regarding construction. The approval of the plans does not constitute any certification of the accuracy, completeness, or building permit status of the existing buildings and structures as shown. 1406 W 12th St 05/19/23 ~1 1 1 .48 ' ~56.00' ~1 1 1 . 38 ' 54 ' - 2 " ~56.00' 24 ' - 8 " 3'-9" 3'-3" CBACD MSP UM JB CBACDMSP UM SITE PLAN WITH ROOF PLAN REV SHEET NAME SHEET NUMBER DATE DESCRIPTION VERSION PV-1 PROJECT NAME UR03/14/2023 INITIAL RELEASE AB E L G O N Z A L E Z C H A V E Z 14 0 6 W 1 2 T H S T , SA N T A A N A , C A 9 2 7 0 3 U S A UT I L I T Y : S C E AH J : C I T Y O F S A N T A A N A SHEET SIZE ANSI B 11" X 17" EMPOWER ELECTRIC SOLAR 1300 E SHAW AVE,173 FRESNO, CA 93710 TEL: (559) 360-9292 CSLB: 1057693 Email : permits@mpwrsolar.com AP N : 0 0 4 1 1 2 0 7 SITE PLAN WITH ROOF PLAN 1 SCALE: 1/16" = 1'-0" ROOF ACCESS POINT SHALL BE LOCATED IN AREAS THAT DO NOT REQUIRE THE PLACEMENT OF GROUND LADDERS OVER OPENINGS SUCH AS WINDOWS OR DOORS, AND LOCATED AT STRONG POINTS OF BUILDING CONSTRUCTION IN LOCATIONS WHERE THE ACCESS POINT DOES NOT CONFLICT WITH OVERHEAD OBSTRUCTIONS SUCH AS TREE LIMBS, WIRES OR SIGNS. NOTE: A. ALL ELECTRICAL EQUIPMENT, INVERTERS, DISCONNECTS, MAIN SERVICE PANELS, ETC. SHALL NOT BE INSTALLED WITHIN 3’ OF THE GAS METERS’ SUPPLY OR DEMAND PIPING. NOTE: * 3/4" OR GREATER IMC, RMC, FMC, LFMC, PVC, HDPE, NUCC, RTRC, LFNC, FMT, ENT OREMT CONDUIT RUN EXPOSED CONDUIT RUN SHALL BE MIN. 7/8" ABOVE ROOF. * ROMEX RUN INSIDE ATTIC 67.79" 44 . 6 4 " PHOTOVOLTAIC MODULES JA SOLAR JAM54S31-390/MR (390W) LEGEND UTILITY METER AC DISCONNECT JUNCTION BOX UM ACD JB MSP MAIN SERVICE PANEL ENPHASE IQ COMBINER 3CB GATE FENCE CONDUIT PROPERTY TREES PROPERTY LINE PR O P E R T Y LI NE PROPERTY LINE PR O P E R T Y L I N E W 12TH ST ONE- STORY HOUSE EXISTING DRIVEWAY (N) 3/4" OR GREATER EMT CONDUIT RUN (7/8 INCHES ABOVE ROOF) (E) STRUCTURE VENT, ATTIC FAN (ROOFOBSTRUCTION) ROOF ACCESS POINT STRUCTURAL ONLY 18 Mar 2023 EXP : 30 Sep 2023 1406 W 12th St 05/19/23 REV SHEET NAME SHEET NUMBER DATE DESCRIPTION VERSION PV-10 PROJECT NAME UR03/14/2023 INITIAL RELEASE AB E L G O N Z A L E Z C H A V E Z 14 0 6 W 1 2 T H S T , SA N T A A N A , C A 9 2 7 0 3 U S A UT I L I T Y : S C E AH J : C I T Y O F S A N T A A N A SHEET SIZE ANSI B 11" X 17" EMPOWER ELECTRIC SOLAR 1300 E SHAW AVE,173 FRESNO, CA 93710 TEL: (559) 360-9292 CSLB: 1057693 Email : permits@mpwrsolar.com AP N : 0 0 4 1 1 2 0 7 SPEC SHEETS 1406 W 12th St 05/19/23 REV SHEET NAME SHEET NUMBER DATE DESCRIPTION VERSION PV-11 PROJECT NAME UR03/14/2023 INITIAL RELEASE AB E L G O N Z A L E Z C H A V E Z 14 0 6 W 1 2 T H S T , SA N T A A N A , C A 9 2 7 0 3 U S A UT I L I T Y : S C E AH J : C I T Y O F S A N T A A N A SHEET SIZE ANSI B 11" X 17" EMPOWER ELECTRIC SOLAR 1300 E SHAW AVE,173 FRESNO, CA 93710 TEL: (559) 360-9292 CSLB: 1057693 Email : permits@mpwrsolar.com AP N : 0 0 4 1 1 2 0 7 SPEC SHEETS 1406 W 12th St 05/19/23 REV SHEET NAME SHEET NUMBER DATE DESCRIPTION VERSION PV-12 PROJECT NAME UR03/14/2023 INITIAL RELEASE AB E L G O N Z A L E Z C H A V E Z 14 0 6 W 1 2 T H S T , SA N T A A N A , C A 9 2 7 0 3 U S A UT I L I T Y : S C E AH J : C I T Y O F S A N T A A N A SHEET SIZE ANSI B 11" X 17" EMPOWER ELECTRIC SOLAR 1300 E SHAW AVE,173 FRESNO, CA 93710 TEL: (559) 360-9292 CSLB: 1057693 Email : permits@mpwrsolar.com AP N : 0 0 4 1 1 2 0 7 SPEC SHEETS 1406 W 12th St 05/19/23 REV SHEET NAME SHEET NUMBER DATE DESCRIPTION VERSION PV-13 PROJECT NAME UR03/14/2023 INITIAL RELEASE AB E L G O N Z A L E Z C H A V E Z 14 0 6 W 1 2 T H S T , SA N T A A N A , C A 9 2 7 0 3 U S A UT I L I T Y : S C E AH J : C I T Y O F S A N T A A N A SHEET SIZE ANSI B 11" X 17" EMPOWER ELECTRIC SOLAR 1300 E SHAW AVE,173 FRESNO, CA 93710 TEL: (559) 360-9292 CSLB: 1057693 Email : permits@mpwrsolar.com AP N : 0 0 4 1 1 2 0 7 SPEC SHEETS 1406 W 12th St 05/19/23 REV SHEET NAME SHEET NUMBER DATE DESCRIPTION VERSION PV-14 PROJECT NAME UR03/14/2023 INITIAL RELEASE AB E L G O N Z A L E Z C H A V E Z 14 0 6 W 1 2 T H S T , SA N T A A N A , C A 9 2 7 0 3 U S A UT I L I T Y : S C E AH J : C I T Y O F S A N T A A N A SHEET SIZE ANSI B 11" X 17" EMPOWER ELECTRIC SOLAR 1300 E SHAW AVE,173 FRESNO, CA 93710 TEL: (559) 360-9292 CSLB: 1057693 Email : permits@mpwrsolar.com AP N : 0 0 4 1 1 2 0 7 SPEC SHEETS 1406 W 12th St 05/19/23 REV SHEET NAME SHEET NUMBER DATE DESCRIPTION VERSION PV-15 PROJECT NAME UR03/14/2023 INITIAL RELEASE AB E L G O N Z A L E Z C H A V E Z 14 0 6 W 1 2 T H S T , SA N T A A N A , C A 9 2 7 0 3 U S A UT I L I T Y : S C E AH J : C I T Y O F S A N T A A N A SHEET SIZE ANSI B 11" X 17" EMPOWER ELECTRIC SOLAR 1300 E SHAW AVE,173 FRESNO, CA 93710 TEL: (559) 360-9292 CSLB: 1057693 Email : permits@mpwrsolar.com AP N : 0 0 4 1 1 2 0 7 SPEC SHEETS 1406 W 12th St 05/19/23 REV SHEET NAME SHEET NUMBER DATE DESCRIPTION VERSION PV-16 PROJECT NAME UR03/14/2023 INITIAL RELEASE AB E L G O N Z A L E Z C H A V E Z 14 0 6 W 1 2 T H S T , SA N T A A N A , C A 9 2 7 0 3 U S A UT I L I T Y : S C E AH J : C I T Y O F S A N T A A N A SHEET SIZE ANSI B 11" X 17" EMPOWER ELECTRIC SOLAR 1300 E SHAW AVE,173 FRESNO, CA 93710 TEL: (559) 360-9292 CSLB: 1057693 Email : permits@mpwrsolar.com AP N : 0 0 4 1 1 2 0 7 SPEC SHEETS 1406 W 12th St 05/19/23 REV SHEET NAME SHEET NUMBER DATE DESCRIPTION VERSION PV-17 PROJECT NAME UR03/14/2023 INITIAL RELEASE AB E L G O N Z A L E Z C H A V E Z 14 0 6 W 1 2 T H S T , SA N T A A N A , C A 9 2 7 0 3 U S A UT I L I T Y : S C E AH J : C I T Y O F S A N T A A N A SHEET SIZE ANSI B 11" X 17" EMPOWER ELECTRIC SOLAR 1300 E SHAW AVE,173 FRESNO, CA 93710 TEL: (559) 360-9292 CSLB: 1057693 Email : permits@mpwrsolar.com AP N : 0 0 4 1 1 2 0 7 SPEC SHEETS 1406 W 12th St 05/19/23 2'-0" 23'-7" 1'-7" 7' - 6 " 1 5 ' - 2 " 1 ' - 8 " CBACD MSPUM JB 1'-8" 5'-5" 4'-1"5'-5" 3'-5"2'-4" REV SHEET NAME SHEET NUMBER DATE DESCRIPTION VERSION PV-2 PROJECT NAME UR03/14/2023 INITIAL RELEASE AB E L G O N Z A L E Z C H A V E Z 1 4 0 6 W 1 2 T H S T , SA N T A A N A , C A 9 2 7 0 3 U S A UT I L I T Y : S C E AH J : C I T Y O F S A N T A A N A SHEET SIZE ANSI B 11" X 17" EMPOWER ELECTRIC SOLAR 1300 E SHAW AVE,173 FRESNO, CA 93710 TEL: (559) 360-9292 CSLB: 1057693 Email : permits@mpwrsolar.com AP N : 0 0 4 1 1 2 0 7 ROOF PLAN WITH MODULES ROOF PLAN WITH MODULES SCALE: 1/8" = 1'-0"1 67.79" 44 . 6 4 " PHOTOVOLTAIC MODULES JA SOLAR JAM54S31-390/MR (390W) MODULE TYPE, DIMENSIONS & WEIGHT NUMBER OF MODULES = 16 MODULES MODULE TYPE = JA SOLAR JAM54S31-390/MR (390W) MODULES MODULE WEIGHT = 47.39 LBS / 21.5 KG. MODULE DIMENSIONS = 67.79"X 44.64" = 21.01 SF UNIT WEIGHT OF ARRAY = 2.26 PSF · PLUMBING VENTS, SKYLIGHTS AND MECHANICAL VENTS SHALL NOT BE COVERED, MOVED, RE-ROUTED OR RE-LOCATED. NOTE: ACTUAL ROOF CONDITIONS AND RAFTERS (OR SEAM) LOCATIONS MAY VARY. INSTALL PER MANUFACTURER(S) INSTALLATION GUIDELINES AND ENGINEERED SPANS FOR ATTACHMENTS ARRAY AREA & ROOF AREA CALC'S AREA OF NEW ARRAY (Sq. Ft.) AREA OF ROOF(PLAN VIEW) (Sq. Ft.) TOTAL ROOF AREA COVERED BY ARRAY % 336.24 1878.30 18% 18% ROOF AREA (ARRAY <33% OF ROOF AREA) 3' - 0 " 36" FIRE PATHWAY 1 8 " 18" FIRE PATHWAY BILL OF MATERIALS EQUIPMENT QTY DESCRIPTION RAIL 10 UNIRAC NXT HORIZON RAIL 168" DRK RAIL SPLICE 06 NXT HORIZON RAIL SPLICE UNIVERSAL CLAMP 40 NXT HORIZON COMBO CLAMP -DRK ROOF ATTACHMENTS 36 UNIRAC STRONGHOLD ACCESSORIES 16 NXT HORIZON RL & CLMP CAP KIT MLPE & GROUNDING 04 NXT HORIZON MLPE & LUG CLAMP ARRAY AREA & ROOF AREA CALC'S ROOF # OF MODULES ARRAY AREA (Sq. Ft.) ROOF AREA (Sq. Ft.) ROOF AREA COVERED BY ARRAY (%) #1 04 84.06 218.21 38.52 #2 04 84.06 217.33 38.68 #3 08 168.12 563.50 29.83 ROOF DESCRIPTION ROOF TYPE ASPHALT SHINGLE ROOF ROOF ROOF TILT AZIMUTH RAFTERS SIZE RAFTERS SPACING #1 18°90°2"x4" 28" O.C. #2 18°270°2"x4" 28" O.C. #3 18°180°2"x4" 28" O.C. LEGEND UTILITY METER AC DISCONNECT JUNCTION BOX UM ACD JB MSP MAIN SERVICE PANEL ENPHASE IQ COMBINER 3CB CONDUIT VENT, ATTIC FAN (ROOFOBSTRUCTION) ROOF ATTACHMENT @ 56" O.C. RAIL RAFTERS MICRO-INVERTER NOTE: * 3/4" OR GREATER IMC, RMC, FMC, LFMC, PVC, HDPE, NUCC, RTRC, LFNC, FMT, ENT OREMT CONDUIT RUN EXPOSED CONDUIT RUN SHALL BE MIN. 7/8" ABOVE ROOF. * ROMEX RUN INSIDE ATTIC W 12TH ST FRONT YARD REAR YARD 18" FIRE PATHWAY 18" FIRE PATHWAY 1 8 " F I R E P A T H W A Y 1 8 " F I R E P A T H W A Y 36" F I R E P A T H W A Y 36" F I RE PAT H W A Y 36" F I R E P A T H W A Y 18" FIRE PATHWAY 18" FIRE PATHWAY ROOF #1ROOF #2 ROOF #3 (N) 3/4" OR GREATER EMT CONDUIT RUN (7/8 INCHES ABOVE ROOF)1 8 " F I R E P A T H W A Y 1 8 " F I R E P A T H W A Y 28"56" 56 " 28 " STRUCTURAL ONLY 18 Mar 2023 EXP : 30 Sep 2023 NOTE:CONTRACTOR TO VERIFY EXISTING FRAMING AND STRUCTURAL LETTER NOTIFY EOR INCASE OF DISCRIPENCIES 1406 W 12th St 05/19/23 REV SHEET NAME SHEET NUMBER DATE DESCRIPTION VERSION PV-3 PROJECT NAME UR03/14/2023 INITIAL RELEASE AB E L G O N Z A L E Z C H A V E Z 14 0 6 W 1 2 T H S T , SA N T A A N A , C A 9 2 7 0 3 U S A UT I L I T Y : S C E AH J : C I T Y O F S A N T A A N A SHEET SIZE ANSI B 11" X 17" EMPOWER ELECTRIC SOLAR 1300 E SHAW AVE,173 FRESNO, CA 93710 TEL: (559) 360-9292 CSLB: 1057693 Email : permits@mpwrsolar.com AP N : 0 0 4 1 1 2 0 7 ATTACHMENT DETAIL ATTACHMENT DETAIL1 ATTACHMENT DETAIL (ENLARGED VIEW)2 NOTE: ACTUAL ROOF CONDITIONS AND RAFTERS (OR SEAM) LOCATIONS MAY VARY. INSTALL PER MANUFACTURER(S) INSTALLATION GUIDELINES AND ENGINEERED SPANS FOR ATTACHMENTS SCALE: NTS NXT HORIZON RAIL ROOF / DECK MEMBRANE 5/16" x 4" STAINLESS STEEL LAG BOLT W/ SS EPDM BONDED WASHER NXT HORIZON COMBO CLAMP 2.5" MIN. EMBEDMENT 2"X4" RAFTE R S @ 28" O.CENLARGE VIEW PV MODULES ASPHALT SHINGLE ROOF PV MODULES STRONGHOLD RAIL CLAMP STRONGHOLD ATTACHMENT 4 3 16" TO 3 7 16 HEIGHT ADJUSTMENT 5/16"-18 x 2" SERRATED FLANGE HEX SCREW 4316" TO 3 7 16 HE I G HT ADJ U S T M E N T 1.18 " 1. 1 8 " SCALE: NTS STRUCTURAL ONLY 18 Mar 2023 EXP : 30 Sep 2023 NOTE TO INSTALLER: VERIFY THE ROOF FRAMING INFO BEFORE INSTALLATION AND NOTIFY EOR IF THERE IS ANY INCONSISTENCY BETWEEN SITE VERIFICATION AND THE FOLLOWING: 2X4 RAFTERS @28" O.C. WITH MAX UNSUPPORTED SPAN EQUAL OR LESS THAN 6.5 FT. 1406 W 12th St 05/19/23 REV SHEET NAME SHEET NUMBER DATE DESCRIPTION VERSION PV-4 PROJECT NAME UR03/14/2023 INITIAL RELEASE AB E L G O N Z A L E Z C H A V E Z 14 0 6 W 1 2 T H S T , SA N T A A N A , C A 9 2 7 0 3 U S A UT I L I T Y : S C E AH J : C I T Y O F S A N T A A N A SHEET SIZE ANSI B 11" X 17" EMPOWER ELECTRIC SOLAR 1300 E SHAW AVE,173 FRESNO, CA 93710 TEL: (559) 360-9292 CSLB: 1057693 Email : permits@mpwrsolar.com AP N : 0 0 4 1 1 2 0 7 ELECTRICAL LINE DIAGRAM WITH CALCULATION ELECTRICAL LINE DIAGRAM SCALE: NTS1 (E) 200A MAIN SERVICE PANEL WITH (E) 200A MAIN BREAKER (TOP FED) L EXISTING GROUNDING SYSTEM (N) 20A PV BREAKER 200A 20A BI-DIRECTIONAL UTILITY METER 1-PHASE, 3-W, 120V/240V, 60Hz TERMINATOR CAP ON LAST CABLE CONNECTOR AC TRUNK CABLE (TYP) 16 MICRO-INVERTERS IN BRANCH CIRCUIT #1 G (N) JUNCTION BOX G IQ ENVOY ENPHASE ENERGY IQ7-60-2-US, 240V, MICRO-INVERTERS 20A 15A (N) ENPHASE IQ COMBINER BOX 3 A G (N) AC DISCONNECT 30A NON FUSED, 240 VAC SOLAR MODULE SPECIFICATIONS MANUFACTURER / MODEL # VMP IMP VOC ISC TEMPERATURE COEFFICIENT OF Voc JA SOLAR JAM54S31-390/MR (390W)30.64 12.73 36.85 13.61 -0.275%/°C MODULE DIMENSION 67.79" L x 44.64" W x 1.18" D INVERTER SPECIFICATIONS MANUFACTURER / MODEL # QUANTITY NOMINAL OUTPUT VOLTAGE NOMINAL OUTPUT CURRENT ENPHASE ENERGY IQ7-60-2-US 16 240 VAC 1.00A INTERCONNECTION 120% RULE - CEC 705.12(b)(3)(2) UTILITY FEED + SOLAR BACKFEED 200A + 20A = 220A BUSS RATING x 120% 200A x 120% = 240A B Wire Tag Conduit Wire Qty Wire Gauge Wire Type Temp. Rating Wire Ampacity (A) Temp. Derate Conduit Fill Derate Derated Ampacity (A) Inverter Qty NOC (A)CEC Correction Design Current (A) Ground Size Ground Wire Type A 3/4" EMT 2 10 AWG THWN-2 90°C 40 0.96 1.0 38.40 16 1.00 1.25 20.00 08 AWG THWN-2 B 3/4" EMT 3 + G 10 AWG THWN-2 90°C 40 0.96 1.0 38.40 16 1.00 1.25 20.00 08 AWG THWN-2 AMBIENT TEMPERTURE SPECIFICATIONS RECORD LOW TEMP AMBIENT TEMP (HIGH TEMP 2%) CONDUIT HEIGHT CONDUCTOR TEMPERATURE RATE (ON ROOF) CONDUCTOR TEMPERATURE RATE (OFF ROOF) 2° 31° 7/8"90°90° NOTE: * 3/4" OR GREATER IMC, RMC, FMC, LFMC, PVC, HDPE, NUCC, RTRC, LFNC, FMT, ENT OREMT CONDUIT RUN EXPOSED CONDUIT RUN SHALL BE MIN. 7/8" ABOVE ROOF. * ROMEX RUN INSIDE ATTIC SERVICE FEED: OVERHEAD (1) Q-CABLE (1) PV #6 BARE CU GND 1406 W 12th St 05/19/23 REV SHEET NAME SHEET NUMBER DATE DESCRIPTION VERSION PV-5 PROJECT NAME UR03/14/2023 INITIAL RELEASE AB E L G O N Z A L E Z C H A V E Z 14 0 6 W 1 2 T H S T , SA N T A A N A , C A 9 2 7 0 3 U S A UT I L I T Y : S C E AH J : C I T Y O F S A N T A A N A SHEET SIZE ANSI B 11" X 17" EMPOWER ELECTRIC SOLAR 1300 E SHAW AVE,173 FRESNO, CA 93710 TEL: (559) 360-9292 CSLB: 1057693 Email : permits@mpwrsolar.com AP N : 0 0 4 1 1 2 0 7 WARNING LABELS & PLACARD WARNING POWER SOURCE OUTPUT CONNECTION DO NOT RELOCATE THIS OVERCURRENT DEVICE ! WARNING DUAL POWER SOURCE SECOND SOURCE IS PHOTOVOLTAIC SYSTEM LABEL LOCATION: EMT/CONDUIT RACEWAYS (PER CODE: CEC690.31(D)(2) PHOTOVOLTAIC POWER SOURCE LABEL LOCATION: POINT OF INTERCONNECTION PRODUCTION METER CEC 705.12(B)(3)(3) & CEC 690.59) ELECTRICAL SHOCK HAZARD WARNING TERMINALS ON LINE AND LOAD SIDES MAY BE ENERGIZED IN THE OPEN POSITION LABEL LOCATION: INVERTER(S), AC DISCONNECT(S), AC COMBINER PANEL (IF APPLICABLE). PER CODE(S): CEC 2022: CEC 706.15 (C)(4) & CEC 690.13(B) MAXIMUM AC OPERATING CURRENT: NOMINAL OPERATING AC VOLTAGE: 16.00 AMPS 240 VAC LABEL LOCATION: AC DISCONNECT(S), PHOTOVOLTAIC SYSTEM POINT OF INTERCONNECTION. PER CODE(S): CEC 2022: 690.54 SOLAR PV SYSTEM EQUIPPED WITH RAPID SHUTDOWN SOLAR ELECTRIC PV PANELS TURN RAPID SHUTDOWN SWITCH TO THE "OFF" POSITION TO SHUT DOWN PV SYSTEM AND REDUCE SHOCK HAZARD IN THE ARRAY. LABEL LOCATION: ON OR NO MORE THAT 1 M (3 FT) FROM THE SERVICE DISCONNECTING MEANS TO WHICH THE PV SYSTEMS ARE CONNECTED. PER CODE(S): 2022 CEC 690.56(C) & 2022 CFC 1205.4.1 ! 4" 3" PHOTOVOLTAIC AC DISCONNECT MAIN PHOTOVOLTAIC SYSTEM DISCONNECT LABEL LOCATION: MAIN SERVICE DISCONNECT / UTILITY METER (PER CODE: CEC 690.13(B)) THIS EQUIPMENT FED BY MULTIPLE SOURCES TOTAL RATING OF ALL OVERCURRENT DEVICES EXCLUDING MAIN POWER SUPPLY SHALL NOT EXCEED AMPACITY OF BUSBAR WARNING LABEL LOCATION: POINTS OF CONNECTION/BREAKER CODE: CEC 705.12(B)(3)(3) PHOTOVOLTAIC AC DISCONNECT LABEL LOCATION: AC DISCONNECT CEC 690.13(B) LABEL LOCATION: MSP (PER CODE: CEC 705.12(D) & CEC 690.59 CAUTION PHOTOVOLTAIC SYSTEM CIRCUIT IS BACKFED ! LABEL LOCATION: SERVICE PANEL IF SUM OF BREAKERS EXCEEDS PANEL RATING CEC 705.12 (B)(3)(2) LABEL LOCATION: UTILITY SERVICE ENTRANCE/METER, INVERTER/DC DISCONNECT IF REQUIRED BY LOCAL AHJ, OR OTHER LOCATIONS AS REQUIRED BY LOCAL AHJ. PER CODE(S): CEC 2022: 690.56(C)(2) RAPID SHUTDOWN FOR SOLAR PV SYSTEM ! ! WARNING THE DISCONNECTION OF THE GROUNDED CONDUCTOR(S) MAY RESULT IN OVERVOLTAGE ON THE EQUIPMENT ! LABEL LOCATION: INVERTER PER CODE: CEC 690.31(E) POWER TO THIS BUILDING IS ALSO SUPPLIED FROM THE FOLLOWING SOURCES WITH DISCONNECTS LOCATED AS SHOWN 1406 W 12TH ST UTILITY METER COMBINER BOX PV MODULES MAIN SERVICE PANEL WITH MAIN BREAKER AC DISCONNECT CAUTION ! MULTIPLE SOURCES OF POWER 1406 W 12th St 05/19/23 REV SHEET NAME SHEET NUMBER DATE DESCRIPTION VERSION PV-6 PROJECT NAME UR03/14/2023 INITIAL RELEASE AB E L G O N Z A L E Z C H A V E Z 14 0 6 W 1 2 T H S T , SA N T A A N A , C A 9 2 7 0 3 U S A UT I L I T Y : S C E AH J : C I T Y O F S A N T A A N A SHEET SIZE ANSI B 11" X 17" EMPOWER ELECTRIC SOLAR 1300 E SHAW AVE,173 FRESNO, CA 93710 TEL: (559) 360-9292 CSLB: 1057693 Email : permits@mpwrsolar.com AP N : 0 0 4 1 1 2 0 7 SPEC SHEETS 1406 W 12th St 05/19/23 REV SHEET NAME SHEET NUMBER DATE DESCRIPTION VERSION PV-7 PROJECT NAME UR03/14/2023 INITIAL RELEASE AB E L G O N Z A L E Z C H A V E Z 14 0 6 W 1 2 T H S T , SA N T A A N A , C A 9 2 7 0 3 U S A UT I L I T Y : S C E AH J : C I T Y O F S A N T A A N A SHEET SIZE ANSI B 11" X 17" EMPOWER ELECTRIC SOLAR 1300 E SHAW AVE,173 FRESNO, CA 93710 TEL: (559) 360-9292 CSLB: 1057693 Email : permits@mpwrsolar.com AP N : 0 0 4 1 1 2 0 7 SPEC SHEETS 1406 W 12th St 05/19/23 REV SHEET NAME SHEET NUMBER DATE DESCRIPTION VERSION PV-8 PROJECT NAME UR03/14/2023 INITIAL RELEASE AB E L G O N Z A L E Z C H A V E Z 14 0 6 W 1 2 T H S T , SA N T A A N A , C A 9 2 7 0 3 U S A UT I L I T Y : S C E AH J : C I T Y O F S A N T A A N A SHEET SIZE ANSI B 11" X 17" EMPOWER ELECTRIC SOLAR 1300 E SHAW AVE,173 FRESNO, CA 93710 TEL: (559) 360-9292 CSLB: 1057693 Email : permits@mpwrsolar.com AP N : 0 0 4 1 1 2 0 7 SPEC SHEETS 1406 W 12th St 05/19/23 REV SHEET NAME SHEET NUMBER DATE DESCRIPTION VERSION PV-9 PROJECT NAME UR03/14/2023 INITIAL RELEASE AB E L G O N Z A L E Z C H A V E Z 14 0 6 W 1 2 T H S T , SA N T A A N A , C A 9 2 7 0 3 U S A UT I L I T Y : S C E AH J : C I T Y O F S A N T A A N A SHEET SIZE ANSI B 11" X 17" EMPOWER ELECTRIC SOLAR 1300 E SHAW AVE,173 FRESNO, CA 93710 TEL: (559) 360-9292 CSLB: 1057693 Email : permits@mpwrsolar.com AP N : 0 0 4 1 1 2 0 7 SPEC SHEETS 1406 W 12th St 05/19/23