HomeMy WebLinkAbout1646 E Washington Ave - PlanExpedited Permit Process for PV Systems1 Expedited Permit Process for PV Systems Standard String System The Solar America Board for Codes and Standards (Solar ABCs) Expedited Permit Pro- cess provides a means to differentiate systems that can be permitted quickly and easily due to their similarity with the majority of small-scale PV systems. Those systems with unique characteristics may be handled with small additions to this Expedited Permit Process or may require much more information, depending on the uniqueness of the installation. The following pages contain forms for the Standard String System to use with the Expe- dited Permit Process. The Micro-Inverter, AC Module, and Supply-Side Connection forms are also available as interactive PDF files at www.solarabcs.org/permitting. In jurisdic- tions that have adopted the Expedited Permit Process for PV Systems, these forms can be filled out electronically and submitted in either printed form and via email. An elec- tronic format is used so that the supplied information is standardized and legible for the local jurisdiction. 1646 E Washington Ave03/28/23 Expedited Permit Process for PV Systems2 Expedited Permit Process for Small-Scale PV Systems Standard String System The information in this guideline is intended to help local jurisdictions and contractors identify when PV system installations are simple, needing only a basic review, and when an installation is more complex. It is likely that 50%-75% of all residential systems will comply with these simple criteria. For projects that fail to meet the simple criteria, resolution steps have been suggested to provide as a path to permit approval. Required Information for Permit: 1. Site plan showing location of major components on the property. This drawing need not be exactly to scale, but it should represent relative location of components at site (see supplied example site plan). PV arrays on dwellings with a 3’ perimeter space at ridge and sides may not need separate fire service review. 2. Electrical diagram showing PV array configuration, wiring system, overcurrent protection, inverter, disconnects, required signs, and ac connection to building (see supplied standard electrical diagram). 3. Specification sheets and installation manuals (if available) for all manufactured components including, but not limited to, PV modules, inverter(s), combiner box, disconnects, and mounting system. Step 1: Structural Review of PV Array Mounting System Is the array to be mounted on a defined, permitted roof structure? l Yes l No If No due to non-compliant roof or a ground mount, submit completed worksheet for the structure WKS1. Roof Information: 1. Is the roofing type lightweight (Yes = composition, lightweight masonry, metal, etc…)__________________________ ____________________________________________________________________________________________________ If No, submit completed worksheet for roof structure WKS1 (No = heavy masonry, slate, etc…). 2. Does the roof have a single roof covering? l Yes l No If No, submit completed worksheet for roof structure WKS1. 3. Provide method and type of weatherproofing roof penetrations (e.g. flashing, caulk).____________________________ Mounting System Information: 1. Is the mounting structure an engineered product designed to mount PV modules with no more than an 18” gap beneath the module frames? l Yes l No If No, provide details of structural attachment certified by a design professional. 2. For manufactured mounting systems, fill out information on the mounting system below: a. Mounting System Manufacturer ___________Product Name and Model#________________________________ b. Total Weight of PV Modules and Rails ___________lbs c. Total Number of Attachment Points____________ d. Weight per Attachment Point (b÷c)_________________lbs (if greater than 45 lbs, see WKS1) e. Maximum Spacing Between Attachment Points on a Rail ______________inches (see product manual for maximum spacing allowed based on maximum design wind speed) f. Total Surface Area of PV Modules (square feet)_________________ ft 2 g. Distributed Weight of PV Module on Roof (b÷f)_______________ lbs/ft2 If distributed weight of the PV system is greater than 5 lbs/ft2, see WKS1. Step 2: Electrical Review of PV System (Calculations for Electrical Diagram) In order for a PV system to be considered for an expedited permit process, the following must apply: 1. PV modules, utility-interactive inverters, and combiner boxes are identified for use in PV systems. 2. The PV array is composed of 4 series strings or less per inverter. 3. The total inverter capacity has a continuous ac power output 13,440 Watts or less 4. The ac interconnection point is on the load side of service disconnecting means (690.64(B)). 5. One of the standard electrical diagrams (E1.1, E1.1a, E1.1b, or E1.1c) can be used to accurately represent the PV system. Interactive PDF diagrams are available at www.solarabcs.org/permitting. Fill out the standard electrical diagram completely. A guide to the electrical diagram is provided to help the applicant understand each blank to fill in. If the electrical system is more complex than the standard electrical diagram can effectively communicate, provide an alternative diagram with appropriate detail. 1646 E Washington Ave03/28/23 Ex p e d i t e d P e r m i t P r o c e s s f o r P V S y s t e m s 3 Standard String System Site Plan                                                           8 PV CIRCUIT 1: 8 MODULES/PARALLEL ROOF TO P GROU ND LEV EL - USE E X TERIO HO R 20A 20A N 15A 2 7 (N) 15 SOLARIA POWER X-390R (390W) MODULES WITH AN ENPHASE IQ8M-72-2-US MICRO-INVERTER ATTACHED TO THE BACK OF EVERY MODULE. PV CIRCUIT 2: 7 MODULES/PARALLEL 1 2 12 1 1 (N)N) JUNCTION WITH IRREVERSIBLE GROUND SPLICE (N) 125A/240V AC COMBINER BOX WITH ENPHASE IQ ENVOY COMM. GATEWAY EN P H A S E I Q EN V O Y CO M M U N I C A T I O N S GA T E W A Y NOTE: IN BETWEEN EACH ARRAY THE EMT IS USED AS THE GROUNDING / BONDING, GROUND CLAMPS ARE AT EACH END OF THE EMT CONDUIT WITH THE WIRE THEN FREE AIR'D TO THE GROUND CLAMP ON THE RACKING RAIL 2A M POINT OF DELIVERY AND INTERCONNECTION 30A 100A N 3 (E) GROUNDING ELECTRODE OR (UFER) BACKFEED BREAKER (N)N) VISI LOCKABLE 2 POLE 30A 'KNIFE' AC DISCONNECT 3 AC DISCONNECT TO BE LOCATED WITHIN 10' OF METER EXISTING 240V/125A MAIN SERVICE PANEL SINGLE PHASE MAIN SERVICE PANEL 240/120V 1Ø, 3W MAIN BUSS: 125A MAX BREAKER SIZE: (125A X 1.2) - 100A = 50.0A Inverter Ratings Inverter Make/Model ENPHASE IQ8M-72-2-US Max DC Volt Rating 60V Max Continuous Output Power 325W Max Nominal Voltage 240V Max AC Current 1.35A Max OCPD Rating 20A DESIGN TEMPERATURES ASHRAE EXTREME LOW 2°C ASHRAE 2% HIGH 28°C PV Module Ratings @ STC Module Make/Model SOLARIA POWER X-390R (390W) [BLK] Max Power-Point Current (Imp)12.73A Max Power-Point Voltage (Vmp)30.6V Open-Circuit Voltage (Voc)36.9V Short-Circuit Current (Isc)13.52A Max Series Fuse (OCPD)25A Nominal Maximum Power at STC (Pmax)390W Maximum System Voltage 1000V Voc Temperature Coefficient -0.28%/°C METER # 222013430961 Conduit and Conductor Schedule Tag Description Wire Gauge # of Conductors Conduit Type Conduit Size 1 Enphase Q cable - THWN-2 10 AWG 2 N/A - Free Air N/A - Free Air 1 Bare Copper Ground (EGC/GEC) 6 AWG 1 N/A - Free Air N/A - Free Air 2 THWN-2 10 AWG 4 EMT 3/4" 2 THWN-2 - Ground 10 AWG 1 EMT 3/4" 2A THWN-2 10 AWG 3 N/A - Free Air N/A - Free Air 3 THWN-2 10 AWG 3 EMT 3/4" 3 THWN-2 - Ground 10 AWG 1 EMT 3/4" SYSTEM SUMMARY BRANCH #1 BRANCH #2 INVERTERS PER BRANCH 8 7 MAX AC CURRENT 10.80A 9.45A MAX AC OUTPUT POWER 2600W 2275W ARRAY STC POWER 5850W ARRAY PTC POWER 5391.0W MAX AC CURRENT 20.25A MAX AC POWER 4875W DERATED (CEC) AC POWER 5229.27W Complete Solar Inc 3000 Executive pkwy ste 504 1646 Washington Ave, Santa Ana, CA 92701 San Ramon, CA 94583 1646 Washington Ave, Santa Ana, CA 92701877-299-4943 4.875 AC kw 1646 E Washington Ave03/28/23 Ex p e d i t e d P e r m i t P r o c e s s f o r P V S y s t e m s 4 Standard String System Electrical Diagram                                                                                                                                                                                                                                                   Complete Solar Inc 3000 Executive pkwy ste 504 1646 Washington Ave, Santa Ana, CA 92701 San Ramon, CA 94583 1646 Washington Ave, Santa Ana, CA 92701 877-299-4943 4.875 AC kw 1646 E Washington Ave03/28/23 Ex p e d i t e d P e r m i t P r o c e s s f o r P V S y s t e m s 5 Notes for Standard String System Electrical Diagram Contractor Name, Address and Phone: _________________ _________________ _________________ _________________ Notes for One-Line Standard Electrical Diagram for Single-Phase PV Systems Site Name: __________________________ Site Address: ________________________ System AC Size: ______________________ SIZE FSCM NO DWG NO REV SCALE NTS Date:SHEET Drawn By: Checked By: MAX POWER-POINT CURRENT (IMP) MAX POWER-POINT VOLTAGE (VMP) OPEN-CIRCUIT VOLTAGE (VOC) SHORT-CIRCUIT CURRENT (ISC) MAX SERIES FUSE (OCPD) MAXIMUM POWER (PMAX) MAX VOLTAGE (TYP 600VDC) VOC TEMP COEFF (mV/oC or %/oC ) IF COEFF SUPPLIED, CIRCLE UNITS A V V A A W V MODULE MAKE MODULE MODEL PV MODULE RATINGS @ STC (Guide Section 5) MAX DC VOLT RATING MAX POWER @ 40oC NOMINAL AC VOLTAGE MAX AC CURRENT MAX OCPD RATING V W V A A INVERTER MAKE INVERTER MODEL INVERTER RATINGS (Guide Section 4) 1) IF UTILITY REQUIRES A VISIBLE-BREAK SWITCH, DOES THIS SWITCH MEET THE REQUIREMENT? YES NO N/A 2) IF GENERATION METER REQUIRED, DOES THIS METER SOCKET MEET THE REQUIREMENT? YES NO N/A 3) SIZE PHOTOVOLTAIC POWER SOURCE (DC) CONDUCTORS BASED ON MAX CURRENT ON NEC 690.53 SIGN OR OCPD RATING AT DISCONNECT 4) SIZE INVERTER OUTPUT CIRCUIT (AC) CONDUCTORS ACCORDING TO INVERTER OCPD AMPERE RATING. (See Guide Section 9) 5) TOTAL OF ______ INVERTER OCPD(s), ONE FOR EACH INVERTER. DOES TOTAL SUPPLY BREAKERS COMPLY WITH 120% BUSBAR EXCEPTION IN 690.64(B)(2)(a)? YES NO NOTES FOR INVERTER CIRCUITS (Guide Section 8 and 9): 1.) LOWEST EXPECT AMBIENT TEMPERATURE BASED ON ASHRAE MINIMUM MEAN EXTREME DRY BULB TEMPERATURE FOR ASHRAE LOCATION MOST SIMILAR TO INSTALLATION LOCATION. LOWEST EXPECTED AMBIENT TEMP ______oC 2.) HIGHEST CONTINUOUS AMBIENT TEMPERATURE BASED ON ASHRAE HIGHEST MONTH 2% DRY BULB TEMPERATURE FOR ASHRAE LOCATION MOST SIMILAR TO INSTALLATION LOCATION. HIGHEST CONTINUOUS TEMPERATURE _____oC 2.) 2005 ASHRAE FUNDEMENTALS 2% DESIGN TEMPERATURES DO NOT EXCEED 47oC IN THE UNITED STATES (PALM SPRINGS, CA IS 44.1 oC). FOR LESS THAN 9 CURRENT-CARRYING CONDUCTORS IN ROOF-MOUNTED SUNLIT CONDUIT AT LEAST 0.5" ABOVE ROOF AND USING THE OUTDOOR DESIGN TEMPERATURE OF 47oC OR LESS (ALL OF UNITED STATES), a)12 AWG, 90oC CONDUCTORS ARE GENERALLY ACCEPTABLE FOR MODULES WITH Isc OF 7.68 AMPS OR LESS WHEN PROTECTED BY A 12-AMP OR SMALLER FUSE. b)10 AWG, 90oC CONDUCTORS ARE GENERALLY ACCEPTABLE FOR MODULES WITH Isc OF 9.6 AMPS OR LESS WHEN PROTECTED BY A 15-AMP OR SMALLER FUSE. NOTES FOR ARRAY CIRCUIT WIRING (Guide Section 6 and 8 and Appendix D): OCPD = OVERCURRENT PROTECTION DEVICE NATIONAL ELECTRICAL CODE ® REFERENCES SHOWN AS (NEC XXX.XX) NOTES FOR ALL DRAWINGS: SIGNS–SEE GUIDE SECTION 7 SIGN FOR DC DISCONNECT SIGN FOR INVERTER OCPD AND AC DISCONNECT (IF USED) RATED MPP CURRENT RATED MPP VOLTAGE MAX SYSTEM VOLTAGE MAX CIRCUIT CURRENT A V V A PHOTOVOLTAIC POWER SOURCE WARNING: ELECTRICAL SHOCK HAZARD–LINE AND LOAD MAY BE ENERGIZED IN OPEN POSITION AC OUTPUT CURRENT NOMINAL AC VOLTAGE A V SOLAR PV SYSTEM AC POINT OF CONNECTION THIS PANEL FED BY MULTIPLE SOURCES (UTILITY AND SOLAR) Complete Solar Inc 3000 Executive pkwy ste 504 1646 Washington Ave, Santa Ana, CA 92701 San Ramon, CA 94583 1646 Washington Ave, Santa Ana, CA 92701 877-299-4943 4.875 AC kw 1646 E Washington Ave03/28/23 V V S U L T I N G | 76 North M eadowbrook Drive Scott E . Wyssling, PE Alpine, UT 84004 C o l e m a n D. L a r s e n , S E , P E off i c e (2 0 1 ) 8 7 4 - 3 4 8 3 G r e g o r y T. E l v es t ad , P E s w y s s l i n g @ w y s s l i n g c o n s u l t i n g . c o m March 2, 2023 Current Insight 2852 W . Amini W a y South Jordan, UT 8 409 5 Re: Engineering Services Sianc as Tao Residence 1646 East Was hi ngton Avenue, Santa An a, C A 5.850 kW System T o W h o m It May Concern: W e h a v e r e c e i v e d i n f o r m a t i o n r e g a r d i n g s o l a r p a n e l i n s tal l ati on o n t h e r o o f o f t h e a b o v e r e f e r e n c e d s tr u c tu re. O u r e v a l u a t i o n o f t h e s t r u c t u r e is t o v e r i f y t h e ex i s t i n g c a p a c i t y o f t h e r o o f s y s t e m a n d its abi l i ty t o s u p p o r t t h e addi t i o n al l o a d s i m p o s e d by t h e p r o p o s e d s o l a r s y s t e m . A. Site A s s e s s m e n t i n f o r m a t i o n 1. Site visit documentation identifying attic information Including size and spacing of framing for the existing roof structure. 2. D e s i g n d r a w i n g s o f t h e p r o p o s e d s y s t e m i n c l u d i n g a s ite p l an , r o o f p l a n a n d c o n n e c t i o n det ai l s f o r t h e s ol ar p a n e l s . T h i s i n f o r m a t i o n w i l l b e u til i z ed f o r a p p r o v a l a n d c o n s t r u c t i o n o f t h e p r o p o s e d s y s t e m . B. D e s c r i p t i o n o f S t r u c t u r e : R o o f F r am i n g : 2x6 dimensional l u m ber at 24" on center. R o o f M aterial : Composite Asphalt Shingles R o o f S t o p e : 8 d e g r e e s A tt i c A c c e s s : Accessible F o u n d a t i o n : ? Permanent C. L o a d i n g Cri teria U s ed « D ead L oad o Existing Roofing and framing = 7 psf o N ew Sol ar Panets and Racking = 3 psf o T O T A L = 10 PSF « Live L oad = 20 psf (reducible) ? 0 psf at locations of solar panels * G r o u n d S n o w L o ad = 0 psf « W i n d L oad based on ASCE 7-16 © Ultimate Wi n d Speed = 95 mph {based on Risk C atag ory II} o Exposure Category C A n a l y s i s p e r f o r m e d o f t h e ex i s t i n g r o o f s t r u c t u r e u t i l i z i n g t h e a b o v e l o a d i n g c r i t er i a is i n a c c o r d a n c e w i t h t h e 2 0 2 2 C a l i f o r n i a B u i l d i n g C o d e , i n c l u d i n g p r o v i s i o n s a l l o w i n g e x i s t i n g s t r u c t u r e s to n o t r e q u i r e s t r e n g t h e n i n g if t h e n e w l o a d s d o n o t e x c e e d e x i s t i n g d e s i g n l o a d s b y 1 0 5 % f o r g r a v i t y e l e m e n t s a n d 1 1 0 % f o r s e i s m i c e l e m e n t s . T h i s a n a l y s i s i n d i c a t e s t h a t t h e e x i s t i n g f r a m i n g wil l s u p p o r t t h e a d d i t i o n a l p a n e l l o a d i n g w i t h o u t d a m a g e , i f i n s t al l ed c o rrec tl y . 1646 E Washington Ave03/28/23 P a g e 2 o f 2 D. S o l a r P an el A n c h o r a g e 1. T h e s o l a r p a n e l s s h a l l b e m o u n t e d in a c c o r d a n c e w i t h t h e m o s t r e c e n t U n i r a c i n s tal l ati on m a n u a l . If d u r i n g s o l a r p an el i n s tal l ati on , t h e r o o f f r a m i n g m e m b e r s a p p e a r u n s t a b l e or d e f l e c t n o n - u n i f orm l y , o u r o f f i c e s h o u l d be n oti fi ed b e f o r e p r o c e e d i n g w i t h t h e i n s tal l ati on . 2. T h e m a x i m u m a l l o w a b l e w i t h d r a w a l f o r c e f o r a 5/16? l ag s c r e w is 2 9 8 I bs p er i n c h o f p e n e t r a t i o n a s iden ti fied in t h e N a t i on al D e s i g n S t a n d a r d s ( N D S ) o f t i m b e r c o n s t r u c t i o n s p e c i f i c a t i o n s . B a s e d o n a m i n i m u m p e n e t r a t i o n d e p t h o f 2 4 " , t h e a l l o w a b l e c a p a c i t y p er c o n n e c t i o n i s g r e a t e r t h a n t h e d e s i g n w i t h d r a w a l f o r c e ( d e m a n d ) . C o n s i d e r i n g t h e v a r i a b l e f a c t o r s f o r t h e e x i s t i n g r o o f f r a m i n g a n d i n s tal l ati on t o l e r a n c e s , t h e c o n n e c t i o n u s i n g o n e °/:6" d i a m e t e r lag s c r e w w i t h a m i n i m u m o f 2 % " e m b e d m e n t w i l l b e a d e q u a t e a n d will i n c l u d e a s u f f i c i e n t f a c t o r o f s af et y . 3. C o n s i d e r i n g t h e w i n d s p e e d , r oo f s l op es , s i z e a n d s p a c i n g o f f r a m i n g m e m b e r s , a n d c o n d i t i o n o f t h e roof, t h e p a n e l s u p p o r t s s h a l l b e p l a c e d n o g r e a t e r t h a n 7 2 " o n c e n t e r . B a s e d o n t h e a b o v e ev a l u at i o n , th i s of fi c e c erti fies t h a t w i th the r a c k i n g a n d m o u n t i n g s p ec i fied, t h e ex is ti n g r oo f s y s t e m wil l a d e q u a t e l y s u p p o r t the addi tion al l o adi n g i m p o s e d by t h e s o l a r s y s tem . T h i s ev al u at i on is i n c o n f o r m a n c e w i th the 2 0 2 2 C al i f or n i a B u i l d i n g C o d e , c u r r en t i n d u s t r y s t an d ar d s , a n d is b a s e d on i n f o r m at i on s u p p l i ed t o u s a t t h e t i m e of th is report. S h o u l d y o u h a v e a n y q u e s t i o n s r e g a r d i n g t h e a b o v e o r if y ou r eq u i r e f u rth er i n f or m a t i on d o n o t h es i tate t o c o n t a c t me. Vf truly yours, 7 2 4 3 0 . Scott E. Wyssiig§, PE. Califomia License N Signed 3/2/2023 1646 E Washington Ave03/28/23 W y s s l i n g C o n s u l t i n g 76 N. Meadowbrook Drive {201} 874-3483 Alpine, UT 84004 swyssling@wysslingconsulting.comG r a v i t y L o a d s E x i s t i n g SiancasTao Residence Roof Dead Load 1646 East Washington Avenue 2.0 psf Composite Shingle Santa Ana, CA 1.6 psf 1/2" Plywood Sheathing 1.3 psf 2x6 @ 24 in. o.c. 1.0 psf Ceiling, Mechanical, Electrical L.1 psf Miscellaneous 7.0 psf TOTAL Second Floor Dead Load 0 p s f F l oor Finishes Opsf ?_1 1/8" Subfloor Sheathing Opsf Joists @ I6' oc. O p s f Partitions 0 p s f C ei l i n g , M ec h an ic al , El ectrical 0 psf Miscellaneous O pst.TOTAL Roof Live Load Floor Live Load Signed 20 psf 0 psf janed 3/2/2023 R o o f S n o w L o a d G rou n d S n o w L oad= _ 0 p s f (to be di v i ded by cosine o f r o o f an g l e fo r h ori z on tal proj ec tion A S C E 7 Sec. 7.4) pr= 7 C C Ip, O p s t C , - 1 , - 1 . 1 Flat Reof Snow Load (ASCE 7-16 Eq. 7.3-1) G = 1.00 ASCE 7-16 Figure 7.4-1 A d d i t i o n a l Roof Dead Load - New Solar Panels 3 psf Roof Live Load at Solar Panels 0 psf Roof Snow Load at Solar Panels O psf Sloped Roof Snow Load (ASCE 7-16 Eq. 7.4-1) T o t a l Total Existing Roof Load = (DLaoor + Max(LLgoor oF $)) Areagqor 77517 tbs Total NewRoof Load = (DLgnar + DL apn + Max(LLgoor of $)) Areaguor 72028 Ibs Change in D em an d = (T otal N ew Roof L oad - E x is tin g R o o f L o ad ) / E x i s t i n g R o o f L oad - 7 . 0 8 % T o t a l N e w G r a v i t y L eads are less th an E x i s t i n g L o ads . O K 2021 I E B C Section 805.2 states: ?Any existing gravity load-carrying structural efement for which an alteration causes an increase in design gravity load of more than 5 percent shall be strengthened, supplemented, replaced or otherwise altered as needed to carry the increased gravity load required by this code for new structures.? 1646 E Washington Ave03/28/23 1646 E Washington Ave03/28/23 Rev: 7/15/2021 RESIDENTIAL PHOTOVOLTAIC CHECKLIST SOL-01 CBC 2019 Solar Photovoltaic (PV) Checklist for Detached SINGLE FAMILY RESIDENCES Only Instructions: The licensed contractor of record shall complete all sections, answer the ten questions and sign the certification section below. A copy of this form shall be attached to each of TWO sets of plans, of minimum 11” x 17” size. If answering NO to any of the questions, plan check shall be required. Project Address: Contractor Company Name: Contractor License Number: YES NO Are the following applicable to the proposed project? 1.   Will the PV system layout provide the required three-foot wide clear access pathways per Section 605.11 of the California Fire Code, and is this shown on the roof plan? 2.   Will the PV system be installed on a roof having only one roofing layer with no overlays? 3.   Will the PV array be flush mounted to the existing roof so that the plane of the modules (panels) are parallel to the plane of the roof? 4. Will the PV system weigh maximum 4 pounds per square feet or less? 5. Will the PV system be installed where the modules do not overhang any roof edges (such as eaves, gabled ends, ridges and hips)? 6.   Will the PV system be installed with a space of 2” minimum to 10” maximum between the underside of modules and the surface of the roof? 7.   Will the PV system be installed without using any ballast system or counter-weight system? 8.   Will the anchors be installed with a maximum horizontal anchor spacing of 6 feet and is this maximum horizontal spacing shown on the plans? 9.   Will the minimum 5/16” lag screws be installed with a minimum of 2-1/2 inch embedment into roof rafters (with pre-drilled holes) and is this minimum embedment shown on the plans? 10.   Are ALL the structural pages of the plans stamped and signed by a California licensed professional engineer? (including project specific site plan, PV layout, anchorage spacing, anchorage details and manufacturer’s PV support information.) I certify under penalty of perjury under the laws of the State of California that the above is true: Print Name: Signature: Phone Number: Date: Email Address: Planning & Building Agency Building Safety Division 20 Civic Center Plaza P.O. Box 1988 (M-19) Santa Ana, CA 92702 (714) 647-5800 www.santa-ana.org 1646 E Washington Ave03/28/23 Certificate Of Completion Envelope Id: 0182A9F47D694211AC068ACFF450E3BA Status: Completed Subject: Complete with DocuSign: Need Homeowner Signature Source Envelope: Document Pages: 1 Signatures: 1 Envelope Originator: Certificate Pages: 5 Initials: 0 Project Coordinators AutoNav: Enabled EnvelopeId Stamping: Enabled Time Zone: (UTC-08:00) Pacific Time (US & Canada) 144 Anacapa Avenue 144 Anacapa Avenue Oxnard, CA 93035 help@completesolar.com IP Address: 190.143.253.184 Record Tracking Status: Original 3/8/2023 12:13:58 PM Holder: Project Coordinators help@completesolar.com Location: DocuSign Signer Events Signature Timestamp Juan Siancas Tao jrsian@hotmail.com Security Level: Email, Account Authentication (None) Signature Adoption: Pre-selected Style Using IP Address: 76.169.131.71 Sent: 3/8/2023 12:15:47 PM Viewed: 3/8/2023 12:34:44 PM Signed: 3/8/2023 12:35:09 PM Electronic Record and Signature Disclosure: Accepted: 3/8/2023 12:34:44 PM ID: 1f1c2b0e-7178-4fb3-acd8-d972f06f986a In Person Signer Events Signature Timestamp Editor Delivery Events Status Timestamp Agent Delivery Events Status Timestamp Intermediary Delivery Events Status Timestamp Certified Delivery Events Status Timestamp Carbon Copy Events Status Timestamp Project Coordinators help@completesolar.com Complete Solar, Inc Security Level: Email, Account Authentication (None) Sent: 3/8/2023 12:15:47 PM Resent: 3/8/2023 12:35:10 PM Viewed: 3/8/2023 12:35:49 PM Electronic Record and Signature Disclosure: Not Offered via DocuSign Witness Events Signature Timestamp Notary Events Signature Timestamp Envelope Summary Events Status Timestamps Envelope Sent Hashed/Encrypted 3/8/2023 12:15:47 PM Certified Delivered Security Checked 3/8/2023 12:34:44 PM Signing Complete Security Checked 3/8/2023 12:35:09 PM Completed Security Checked 3/8/2023 12:35:09 PM 1646 E Washington Ave03/28/23 Payment Events Status Timestamps Electronic Record and Signature Disclosure 1646 E Washington Ave03/28/23 ELECTRONIC RECORD AND SIGNATURE DISCLOSURE From time to time, Complete Solar (we, us or Company) may be required by law to provide to you certain written notices or disclosures. Described below are the terms and conditions for providing to you such notices and disclosures electronically through the DocuSign system. Please read the information below carefully and thoroughly, and if you can access this information electronically to your satisfaction and agree to this Electronic Record and Signature Disclosure (ERSD), please confirm your agreement by selecting the check-box next to ‘I agree to use electronic records and signatures’ before clicking ‘CONTINUE’ within the DocuSign system. Getting paper copies At any time, you may request from us a paper copy of any record provided or made available electronically to you by us. You will have the ability to download and print documents we send to you through the DocuSign system during and immediately after the signing session and, if you elect to create a DocuSign account, you may access the documents for a limited period of time (usually 30 days) after such documents are first sent to you. After such time, if you wish for us to send you paper copies of any such documents from our office to you, you will be charged a $0.00 per-page fee. You may request delivery of such paper copies from us by following the procedure described below. Withdrawing your consent If you decide to receive notices and disclosures from us electronically, you may at any time change your mind and tell us that thereafter you want to receive required notices and disclosures only in paper format. How you must inform us of your decision to receive future notices and disclosure in paper format and withdraw your consent to receive notices and disclosures electronically is described below. Consequences of changing your mind If you elect to receive required notices and disclosures only in paper format, it will slow the speed at which we can complete certain steps in transactions with you and delivering services to you because we will need first to send the required notices or disclosures to you in paper format, and then wait until we receive back from you your acknowledgment of your receipt of such paper notices or disclosures. Further, you will no longer be able to use the DocuSign system to receive required notices and consents electronically from us or to sign electronically documents from us. All notices and disclosures will be sent to you electronically Electronic Record and Signature Disclosure created on: 3/2/2020 9:22:02 AM Parties agreed to: Juan Siancas Tao 1646 E Washington Ave03/28/23 Unless you tell us otherwise in accordance with the procedures described herein, we will provide electronically to you through the DocuSign system all required notices, disclosures, authorizations, acknowledgements, and other documents that are required to be provided or made available to you during the course of our relationship with you. To reduce the chance of you inadvertently not receiving any notice or disclosure, we prefer to provide all of the required notices and disclosures to you by the same method and to the same address that you have given us. Thus, you can receive all the disclosures and notices electronically or in paper format through the paper mail delivery system. If you do not agree with this process, please let us know as described below. Please also see the paragraph immediately above that describes the consequences of your electing not to receive delivery of the notices and disclosures electronically from us. How to contact Complete Solar: You may contact us to let us know of your changes as to how we may contact you electronically, to request paper copies of certain information from us, and to withdraw your prior consent to receive notices and disclosures electronically as follows: To contact us by email send messages to: csmith@completesolar.com To advise Complete Solar of your new email address To let us know of a change in your email address where we should send notices and disclosures electronically to you, you must send an email message to us at csmith@completesolar.com and in the body of such request you must state: your previous email address, your new email address. We do not require any other information from you to change your email address. If you created a DocuSign account, you may update it with your new email address through your account preferences. To request paper copies from Complete Solar To request delivery from us of paper copies of the notices and disclosures previously provided by us to you electronically, you must send us an email to csmith@completesolar.com and in the body of such request you must state your email address, full name, mailing address, and telephone number. We will bill you for any fees at that time, if any. To withdraw your consent with Complete Solar To inform us that you no longer wish to receive future notices and disclosures in electronic format you may: 1646 E Washington Ave03/28/23 i. decline to sign a document from within your signing session, and on the subsequent page, select the check-box indicating you wish to withdraw your consent, or you may; ii. send us an email to csmith@completesolar.com and in the body of such request you must state your email, full name, mailing address, and telephone number. We do not need any other information from you to withdraw consent.. The consequences of your withdrawing consent for online documents will be that transactions may take a longer time to process.. Required hardware and software The minimum system requirements for using the DocuSign system may change over time. The current system requirements are found here: https://support.docusign.com/guides/signer-guide- signing-system-requirements. Acknowledging your access and consent to receive and sign documents electronically To confirm to us that you can access this information electronically, which will be similar to other electronic notices and disclosures that we will provide to you, please confirm that you have read this ERSD, and (i) that you are able to print on paper or electronically save this ERSD for your future reference and access; or (ii) that you are able to email this ERSD to an email address where you will be able to print on paper or save it for your future reference and access. Further, if you consent to receiving notices and disclosures exclusively in electronic format as described herein, then select the check-box next to ‘I agree to use electronic records and signatures’ before clicking ‘CONTINUE’ within the DocuSign system. By selecting the check-box next to ‘I agree to use electronic records and signatures’, you confirm that: You can access and read this Electronic Record and Signature Disclosure; and You can print on paper this Electronic Record and Signature Disclosure, or save or send this Electronic Record and Disclosure to a location where you can print it, for future reference and access; and  Until or unless you notify Complete Solar as described above, you consent to receive exclusively through electronic means all notices, disclosures, authorizations, acknowledgements, and other documents that are required to be provided or made available to you by Complete Solar during the course of your relationship with Complete Solar. 1646 E Washington Ave03/28/23 I, ________________________ The homeowner at (____________________________________________________________), a m writing this letter to inform you that we would like to install solar panels with Complete Solar as my Solar Contractor. Regards, __________________ __________________ 10/28/2022 *Sign: Juan Siancas Tao 1646 Washington Ave Santa Ana, CA 92701 3/5/23 Juan Siancas Tao DocuSign Envelope ID: 0182A9F4-7D69-4211-AC06-8ACFF450E3BA 1646 E Washington Ave03/28/23 PV M o d u l e R a t i n g s @ S T C S Y S T E M S U M M A R Y Inverter Ratings BRANCH #1]BRANCH #2 ENPHASE! C o m p lInverter Make/Model e e m p l e t e S o l a r IModute Make/Model 3 0 0 8 GOO) BLK] INVERTERS PER BRANCH 8 7|18M-72-2-US}P nemtne v y MAX AC CURRENT 10.80A 945A Max DC Volt Rating S o v " Max Power-Point Current (Imp)12.73A|MAX AC OUTPUT POWER 2600W 2275W|Max Continuous Output Power 325) IMax Power-Point Voltage (Vmp)30,6V| ARRAY STC POWER 5850W [Max Norunal Vallage 240V| 3900 EXECUTIVE PKWY, [Open-Circuit Voltage (Voo)36.9V/ ARRAY PTC POWER 5391.0W|Max AC Current 135A] STE 504 SAN RAMON, [Short-Circuit Current (Isc)13.52A/MAX AG CURRENT 20.250 Max OCPD Rating 208) CA 94583 Max Series Fuse (OCPD)25A|MAX AG POWER 48750 D E S I G N T E M P E R A T U R E S LICENSE TYPE C10 Nominal Maximum Power at STC (Pmax)s90w|JASHRAE EXTREME LOW 2 ¢| PHONE #(eT?) 299-4943 DERATED (CEC) AC POWER 5229.27W IASHRAE 2% HIGH ° C ] Maximum System Voltage 1000V j Voc Temperature Coefficient -0 .2 8 %C Sg Conduit and Conductor Schedule Tap Descrpton ire Gauge [Pot conductors] _Condut Type | Gonduk Size 1 [erohase @ cable-THWN2 TANG 2 NA-Froe Ar | NA- row Ar 1 [Bare Comper Ground (EGCIGEC)| AWG 1 NA-FreeAr | NIA-Free Ar 2 [r a w 10 AWG 4 EMT ae 2 frawn.2- Ground TOAWG 1 EMT ee 2a [rwm-2 10.ANG 3 NA: Free Ar | NIA-FreeAr 3 [rene 10.00 3 EMT ae METER # 222013430961 3 [ T H W . 2-Ground 10.806 ?eur aut MAIN SERVICE PANEL 240/120V 12, 3W MAIN BUSS: 125A MAX BREAKER SIZE: (N) 1254/240VAC.(125A X 1.2) - 100A = 50.04 ?COMBINER BOX WITH ENPHASE 10 ENVOY POINT OF DESIGNER: ORV 6%COMM. GATEWAY DELIVERY AND B e INTERCONNECTION {N) 15 SOLARIA POWER X-390R (390W) MODULES B o e {N) VISIBLE J U A N S I A N C A S T A OWITH AN ENPHASE [08M-72-2-US MICRO-INVERTER S A S LOCKABLE ?ATTACHED TO THE BACK OF EVERY MODULE.a o e 2POLE 30A R E S I D E N C E S S >?KNIFE?AC. PV CIRCUIT 2: 7 MODULES/PARALLEL ,DISCOUNT o y |** l o | o z ?EXISTING 1646 E WASHINGTON AVE S o =MAIN SERVICE PANEL SANTA ANA PV CIRCUIT4: 8 MODULES/PARALLEL 1 SINGLE PHASE cagz2701 o o ) |o 3o - Z | . . . .|O+Z 2 1 APN:40028711 - a t ;=DATE:2/23/2023 |NOTE: IN BETWEEN EACH ARRAY THE EMT IS USED AS THE|AC ]GROUNDING / BONDING, GROUND CLAMPS ARE AT EACH.(N) JUNCTION BOX DISCONNECT = |END OF THE EMT CONOUIT WITH THE WIRE THEN FREE WITH IRREVERSIOLE TO BE LOCATED E e e AIR? TO THE GROUND CLAMP ON THE RACKING RAIL GROUND SPLICE WITHIN 10°OF (UFER) SHEET METER E-1 ELECTRICAL DIAGRAM 1646 E Washington Ave03/28/23 ELECTRICAL SHOCK HAZARD TERMINALS ON LINE AND LOAD ?SIDES MAY BE ENERGIZED IN THE OPEN POSITION LABEL LOCATION: INVERTER(S). AC DISCONNECT(S}, AC COMBINER PANEL {IF APPLICABLE), PER CODEIS) CEG 2022:690.138) LABEL LOCATION: OTILITY SERVICE ENTRANCE:/METER, INVERTERIDG. DISCONNECT IF REQUIRED BY LOCAL AHJ, OR ?OTHER LOCATIONS AS REQUIRED BY LOCAL AHJ. PER CODE(S): CEC 2022: 690 56(C)(2, OFC 2022: 1204.6.3 POWER SOURCE OUTPUT CONNECTION DO NOT RELOCATE THIS OVERGURRENT DEVICE LABEL LOCATION: ADJACENT TO PV BREAKER (IF APPLICABLE), PER CODE(S): CEC 2022: 708.12(8)243Kb) PHOTOVOLTAIC SYSTEM C e ] NOT ADD LOADS LABEL LOCATION PHOTOVOLTAIC AC COMBINER (IF APPLICABLE) PHOTOVOLTAIC AC DISCONNECT DO t e a s e e l c e e e l y NOMINAL OPERATING AG VOLTAGE: 240.0 VAC LABEL LOCATION AC DISCONNECT(S), PHOTOVOLTAIC SYSTEM POINT OF INTERCONNECTION, PER CODE(S) GEG 2022: 690.54 S O L A R PV SYSTEM EQUIPPED WITH RAPID S H U T D O W N SWITCH TO THE "OFF" POSITION TO SHUT DOWN PV SYSTEM AND REDUCE ?SHOCK HAZARD IN THE ARRAY, LABEL LOCATION, ?ON OR NO MORE THAT 3 M(10 FT) FROM THE SERVICE DISCONNECTING MEANS TO WHICH THE PY SYSTEMS. ARE CONNECTED C A U T I O N : POWER TO T H I S B U I L D I N G IS A L S O SUPPLIED FROM THE F O L L O W I N G SOURCES W I T H D I S C O N N E C T S AS S H O W N (N) SOLAR PANELS AND ?Pp _ MICRO-INVERTERS ON [ I l [ 1646 E W A S H I N G T O N A V E ROOF P V I N T E R C O N N E C T I O N P O I N T . ?~ LOCATION OF METER MAIN COMBO, AC DISCONNECT & COMBINER BOX. PERMANENT SIGNAGE NOTES. NOTALL PLACARDSSHOWNMAY BE REGURED BY LOCALAMS.C O N T R A C T O R TO VERIFY PLACARD REQUIREMENTS WITH LOCAL AKU BEFORE INSTALLATION ALLPLAQUES AND SIGNAGE REQUIRED BY THE LATEST ED/TON OF THE CAUFORNIA ELECTRICA. CODE ALTERNATE POWER SOURCE PLACARD SHALL BE METALLIC OR PLASTIC. ENGRAVED OR MACHINE PRINTED LETTERS IN A CONTRASTING COLOR TO THE PLAQUE. THIS PLAQUE WILL BEATTCHED BY POP RIVETS OR SCREWS OR OTHER APPROVED METHOD DIRECTORY PLACARD MARKING CONTENT AND FORMAT RED BACKGROUND WHITE LETTERING, MINKA 33 LETER WIEGHT ALL CAPITAL LETTERS ARIAL OR SMILAR FONT, HOM BOLD REPLECTIVE WEATHER RESISTANT MATERIAL SUITABLE FOR THE ENVIRONMENT C o m p l e t e S o l a r ?ABrghtorWay, 3000 EXECUTIVE PKWY, STE 504 SAN RAMON, CA 94583 LICENSE TYPE C10 LICENSE # 961988 PHONE # (877) 299-4943 i a ) D E S I G N E R : O R V JUAN SIANCASTAO RESIDENCE 11646 E WASHI NGTON AVE SANTA A N A C A 92701 APN:40028711 DATE:2/23/2023 SHEET E -2 WARNING LABELS 1646 E Washington Ave03/28/23 1646 E WAS H I N G T O N AVE METER MAN COMBO. ?COMAINER BOX ?AG OXSCONNECT 62. LOCATED AT STRONG POINTS OF CONSTRUCTION IN LOGATION OF METER MAIN COMBO ?AG OISCONNECT & COMBINER BOX MOUNTED ON EXTERIOR WALL OF A SINGLE FAKALY RESIDENCE PV SYSTEM SIZE: 5.85 kw DC ROPERTY LINE PROPERTY LINE - - ? - ? _ - ? - ? ? - - -- _ ?- ?- ? - ? -? - . _ DRIVEWAY ' v c | °' ° ° ' 2 3 0 | °' w y | pncoxour Ru ?| (erseRnce ono by.| ?, CALeIRE ROOF LADDER CALFIRE ROOF LADDER secessPont ?ROCESS PONT ! LEGEND PROPERTY LINE loot Section 1 scouns vanes a EROPERTY LINE Z EW SOLAR PANELS t a e iran eNeHASe a r e aS MCROMVERTENSEZ LOGATION OF RAPIDSHUTDOWN MouniTen 10 THE BACK OF EACH MODULE FIRE SETBACKS:PV INTERCONNECTION POINT MOUNTED ON COMP SHINGLE ROOF C O N S T R U C T I O N N O T E S C o m p l e t e S o l a r ABoginerWay ?SOLAR PHOTOVOLTAIC SYSTEM TO BE INSTALLED ON RESIDENTIAL STRUCTURE. THIS PROJECT HAS BEEN DESIGNED IN COMPLIANCE, WITH THE CBC SECTION 1609 TO WITHSTAND A BASIC. WIND EXPOSURE C. THE ROOF MEMBERS ARE 2 "X 6" TRUSSES AT 24? ON CENTER. CONNECTION TO STRUCTURE SHALL NOT BE WITHIN 11? OF NAILING PLATES. 3 0 0 0 E X E C U T I V E P K W Y , S T E 5 0 4 S A N R A M O N , THE SOLAR PHOTOVOLTAIC INSTALLATION SHALL NOT C A 94583 OBSTRUCT ANY PLUMBING, MECHANICAL, OR BUILDING L I C E N S E T Y P E C10 a o connue LICENSE # 9 61 9 8 8 ALL CONDUCTORS AND CONDUITS MOUNTED ON ROOF SHALL BE MINIMUM 718" ABOVE ROOF SURFACE PHONE # (877) 299-4943 (INCLUDING CABLES UNDERNEATH MODULES AND RACKING). ROOF ACCESS POINTS SHALL BE PROVIDED PER THE FOLLOWING (CRC R324.7.1, CBC 3111.21} LOCATED IN AREAS NOT REQUIRING PLACEMENT OF GROUND LADDERS OVER OPENINGS SUCH AS DOORS OR WINDOWS. LOCATIONS WHERE ACCESS POINT DOES NOT CONFLICT WITH OVERHEAD OBSTRUCTIONS SUCH AS: TREES, WIRES, OR SIGNS. S E T B A C K S A T R I D G E S C A N B E R E D U C E D T O 1 8 I N C H E S IN C O M P L I A N C E W I T H 2 0 1 9 C F C / 2 0 1 8 I F C 1 2 0 4 .2 .1 .2 TOTAL PLAN VIEW AREA = 3108 SQFT TOTAL PY AREA = 15(678 INJ(447 INY(144 IN*2) = 316.69 SQFT (415.89 S Q F T / 3 1 0 8 S Q F T } 1 0 0 = 10.16% T O T A L P V AREA POPULATES 10 16% OF TOTAL PLAN VIEW AREA AND IS WITHIN THE 33% REQUIREMENT. DESIGNER: ORV JUAN SIANCASTAO RESIDENCE 1646 E WASHI NGTON AVE SANTA AN A C A9 2 7 0 1 APN:40028711 DATE:2/23/2023 P V S Y S T E M S I T E P L A N SCALE: 3/32" = 1646 E Washington Ave03/28/23 C o m p l e t e S o l a r ABoginerWay 3 0 0 0 E X E C U T I V E P K W Y , S T E 5 0 4 S A N R A M O N , C A 94583 UNIRAC FLASHKIT PRO FOR COMP ?L I C E N S E T Y P E C10 ? S H I N G L E @ 7 2 °0.C,MAX L I C E N S E# 9 6 1 9 8 8 EXISTING COMP SHINGLE ROOF PHONE # (877) 299-4943 EXISTING 2°X 6° ROOF RAFTERS @ 24°0.C ? 6 ' ? _ , ? 6 . _ + ?6" 6 ? ? 6 s ?- DESIGNER: ORV R o o f Sect i on 1Roof Azimuth:180°S N P Roof Tilt: 8° ' ? PROPOSED UNIRAC SOLAR MOUNT PROPOSED SOLARIA POWER (E) SERVICE DROP.X-390R (3900) [BLK]PVSOLARRACKING.ES JUAN SIANCASTAO RESIDENCE 1646 E WASHI NGTON AVE SANTA A N A C A 9 2 7 0 1 APN:40028711 DATE:2/23/2023 PV SYSTEM MOUNTING DETAILS SHEET SCALE: 3/16" = 1'-0"P V -2 ATTACHMENT DETAILS 1646 E Washington Ave03/28/23 @ RACKING DETAIL (TRANSVERSE) NOTTOSCALE ® ® RACKING DETAIL (TOP) NOTTOSCALE NOTTO SCALE L a y 0 , a o e ! @ D2 RACKING DETAIL (LONGITUDINAL} DETAIL (TRANSVERSE)DS DETAIL (LONGITUDINAL) NOTTO SCALE ROOF MATERIAL: COMP SHINGLE ROOF STRUCTURE: RAFTERS ATTACHMENT TYPE: UNIRAG FLASHKIT PRO MODULE MANUFACTURER: SOLARIA MODULE MODEL: POWER X-200R (300%) [BLK] MODULE LENGTH: 67.8° MODULE WIDTH: 44.7" MODULE WEIGHT: 48,7 LBS. SEE SHEET S-1 FOR DIMENSION(S) MIN. FIRE OFFSET: 18° RAFTERS SPACING: 24°0.¢. RAFTERS SIZE: 2 "X 6° NOMINAL LAG BOLT DIAMETER: 5/16 IN LAG BOLT EMBEDMENT: 251N. TOTAL # OF ATTACHMENTS: 28 TOTAL AREA: 315.89 SO. FT. T O T AL WEIGHT: 1363.60 LBS. WEIGHT PER ATTACHMENT: 26.09 LAS. DISTRIBUTED LOAD:231 PSF |.MAX. HORIZONTAL STANDOFF: 72 0N. |.MAX. VERTICAL STANDOFF: LANDSCAPE: 26 IN. PORTRAIT: 39 IN. STANDOFF STAGGERING. YES 3.RAIL MANUFACTURER AND MODEL (OR EQUIV. -UNIRAC SOLAR MOUNT RAIL WEIGHT: 0.436 PLF. MAX. RAFTERS SPAN: 12 FT. MODULE CLEARANCE: 3 IN. M I N .6IN. MAX. C o m p l e t e S o l a r 3 0 0 0 E X E C U T I V E P K W Y , S T E 5 0 4 S A N R A M O N , C A 9 4 5 8 3 L I C E N S E T Y P E C 1 0 L I C E N S E # 9 6 1 9 8 8 P H O N E# ( 8 7 7 ) 2 9 9 - 4 9 4 3 DESIGNER: ORV JUAN SIANCASTAO RESIDENCE 1646 E WASHI NGTON A V E SANTA ANA C A 92701 APN:40028711 DATE:2/23/2023 SHEET P Y - 3 MOUNTING DETAILS 1646 E Washington Ave03/28/23 SOLARIA High Efficiency, High Power High Quality and Retiability All Black Aesthetics Best Syste Value Imptoved Shading Tolerance Low Light Performance Solaria PowrerX | YC Panel SOLARIA P R E e e ) Solaria PowerX 403R C C S ) r r rr M o e :oy WS 40D membrane e a s nl m7 08 VID}E r Yen wrvorage ys Mw B 1 3 Meant 221g 48 bs ShowCo Coen ie tal 13601368 Glass pe.Menness AR Coated Tempeee Xam Mar Pseer ws oge1 Ww woh 310 Hse pe BuschKnog Jee atu nue MaePower Caserta ial 1821726 CAB Tepe vest WARN er 1208Pom aes i Der 64k Connector toe cadctanBos1oes Frow 108d 1apsh Rea toa pale ner al Il 7380 cee Maes ane Caer oh is 9070 197 Crit ators wen doen 0 feelape a %Pe]2 e a Rabon Bsyeanst won:Cae of Bau s e oe Teep Cortot Vs 078 aeons se fee Cont ot ue e Staraag Merce versa Pallwsed Patet Dorsit x eam ooo a y asa 1 80m 111m 1283 Pave: wenn rasag ina ms Panels 40 Contamer 2 Panes HON Comranee oe f o C o m p l e t e S o l a r Way, 3 0 0 0 E X E C U T I V E P K W Y , S T E 5 0 4 S A N R A M O N , C A 9 4 5 8 3 L I C E N S E T Y P E C 1 0 L I C E N S E # 9 6 1 9 8 3 P H O N E # ( 8 7 7 ) 2 9 9 - 4 9 4 3 | D E S I G N E R : O R V JUAN SIANCASTAO RESIDENCE 1646 E WASHI NGTON AVE SANTA A N A C A 92701 APN:40028711 DATE:2/23/2023 SHEET S P E C S H E E T 1646 E Washington Ave03/28/23 Enphase IQ Combiner 4/4C aor wo Feptane Netweth st o m i t Tre Eaphase IQ Combiner aEnphase 1Q C o m b i n e r 4 / 4 C X-1Q-AM1-240-4 X%-1Q-AM1-240-4C tha + TARE REAL SPUCIEATIONS s i a8 @ ca LUSTER To learn more aboul Enphase alfenings sit anphase.com S E N P H A S ESS ENPHASE T o l e m n i a r e shou Eronau oes vaere c r n C o m p l e t e S o l a r ABnghter ?Way. 3000 EXECUTIVE PKWY, STE 504 SAN RAMON, CA 94583 LICENSE TYPE C10 LICENSE # 961988 PHONE # (877) 299-4943 | D E S I G N E R : O R V J U A N SIANCASTAO RESIDENCE 11646 E WASHI NGTON AVE SANTA A N A C A 92701 A P N : 4 0 0 2 8 7 11 DATE:2/23/2023 SHEET S-3 SPEC SHEET 1646 E Washington Ave03/28/23 SOLARMOUNT BUNIRAC SOLARMOUNT defined ihe standard in solar racking. Features are designed to get instatiers off the roof faster. Our grounding & Bonding process eliminates capper wite and grounding straps to reduce casts. Systems can be configured with standard of light rail to meet yout design requirements at the lowest cost possible. The supenor aesthetics package provides a streamed clean edge for enhanced curb appeal. with 0 special brackels required for installation Now Featuring: THE NEW FACE OF SOLAR RACKING Superior Aesthetics Package oo ( e ] e n p h a s e LOSE ALL OF THE COPPER & LUGS SMALL IS THE HEXT NEW BIG THING ~~ » q " a y r 4 C o m p l e t e S o l a r ABnghtorWay. 3 0 0 0 E X E C U T I V E P K W Y , ?STE 5 0 4 S A N R A M O N , C A 9 4 5 8 3 L I C E N S E T Y P E C 1 0 L I C E N S E # 9 6 1 9 8 3 P H O N E # ( 8 7 7 ) 2 9 9 - 4 9 4 3 peed D E S I G N E R : O R V JUAN SIANCASTAO RESIDENCE 1646 E WASHI NGTON AVE SANTA A N A C A 92701 A P N : 4 0 0 2 8 7 11 DATE:2/23/2023 SHEET $ 4 SPEC SHEET 1646 E Washington Ave03/28/23 FUNIRAC scones SHED &SEAL soanonecs FLASHKIT PRO FLASHKIT PRO 1s the complete attachment solulan for composition shingle coals Featuring Uniracs patented SHED & SEAL technology. a weather proof system which proves the ullumale plotectin apainst ?oot leaks Kitted in 10 packs for maximum convemence.flastings and hardware are available an W.. us ark horghes With FLASHKIT pro. you have everyting you need tora quick, professional wslallaton wyTRUSTED WATER SEAL FLASHINGS YOUR COMPLETE SOLUTION CONVENIENT 19 PACKS e n e SHED?SEAL vownecs ??dgs las colonssh Lert andhatnare Packaged spend andease ol handing UNIRAC HOSED:SEAL emer FLASHKIT PRO IMSTALLATION GUIDE FLASHEIT PRD 1S THE COMPLETE FLASHING AND ATTACHMENT SOLUTION FOR C a r 7 EAPES, eth BRASH Vs fot pect tar e o PRE-NSTALL f o e t u sSTEP1 INSTALL FLASHKIT PRO FLASHING S E E STEP A T T A C HFOOTTORAIL C o m p l e t e S o l a r ABnghtorWay. 3000 EXECUTIVE PKWY, STE 504 SAN RAMON, CA 94583 LICENSE TYPE C10 LICENSE # 961988 PHONE # (877) 299-4943 | D E S I G N E R : O R V JUAN SIANCASTAO RESIDENCE 1646 E WASHI NGTON AVE SANTA A N A C A 92701 A P N : 4 0 0 2 8 7 11 DATE:2/23/2023 SHEET S-5 SPEC SHEET 1646 E Washington Ave03/28/23 orosccrnroruanon JUAN SIANCASTAO RESIDENCE PROPERTY OWNER NAME: PHONE: CONTRACTOR NAME: PHONE: DESIGN SPECIFICATIONS OCCUPANCY: CONSTRUCTION TYPE: ZONING: WIND EXPOSURE: SHEET # T-1 N E W P H OT OVOLT A I C S Y S T E M P R O J E C T - 5.850 kW D C/ COMPLETE SOAR 4.875 kW AC R3 SINGLE FAMILY RESIDENCE RESIDENTIAL c JUAN SIANCASTAO APPLICABLE CODES & STANDARDS 2022 CALIFORNIA RESIDENTIAL CODE {CRC}. 2022 CALIFORNIA BUILDING CODE (CBC)C O O R D I N A T E S : 2022 CALIFORNIA MECHANI 2022 CALIFORNIA ELECTRICAL CODE (CEC) 2022 CALIFORNIA PLUMBING CODE {CPC} 2022 CALIFORNIA ENERGY 2022 CALIFORNIA GREEN BUILDING CODE (CALGREEN) 2020 NATIONAL ELECTRICAL CODE (NEC) 2022 CALIFORNIA FIRE CODE (CFC) T Y P E O F I N T E R C O N N E C T I O N : S C O P E O F W O R K S Y S T E M S I Z E : M S P U P G R A D E : M A I N B R E A K E R D E R A T E : N O R A C K I N G & M O U N T I N G P V A T T A C H M E N T T Y P E : U N I R A C F L A S H K I T P R O F O R C O M P S H I N G L E R O O F R A C K I N G T Y P E : ICAL CODE (CMC)33.756384, -117.844124 CODE (ENERGY) B A C K F E E D B R E A K E R IN T H E M S P S T C : 1 5 X 3 9 0 W = 5 . 8 5 0 k W P T C : 1 5 X 3 5 9 . 4 W = 6.39 1 k W (1 5 ) S O L A R I A P O W E R X - 3 9 0 R ( 3 9 0 W ) [ B LK ] M O D U LE S . (15) E N P H A S E 1 Q 8 M -7 2 -2 -U S M I C R O I N V E R T E R S (1) 4 2 5 A E N P H A S E IQ C O M B I N E R 4 / 4 C B O X (1) 3 0 A K N I F E A C D I S C O N N E C T N O UNIRAC SOLAR MOUNT- ROOF MOUNT RACKING HARDWARE T-2 Pv-1 PV-2 PV-3 E14 E-2 S-1 $ 2 $ 3 S 4 $ 5 A E R I A L VI E W SHEET N A M E C OVE R SHEET PLAN NOTES SITE PLAN LAYOUT A T T A C H M E N T DETAILS MOUNTING DETAILS ELECTRICAL DIAGRAM WA RNI NG LABELS SPEC SHEET SPEC SHEET SPEC SHEET SPEC SHEET SPEC SHEET C o m p l e t e S o l a r 3000 EXECUTIVE PKWY, STE 504 SAN RAMON, CA 94583 LICENSE TYPE C10 LICENSE # 961988 PHONE # (877) 299-4943 DESIGNER: ORV JUAN SIANCASTAO RESIDENCE 1646 E WASHI NGTON AVE SANTA ANA C A 92701 APN:40028711 DATE:2/23/2023 SHEET T-4 COVER SHEET BLDG# 101114436 ISS. 03/27/23 ELEC# 20179158 ISS. 03/27/23 The scope of the plans is for the installation of the solar photovoltaic system only and the approval is subject to compliance with all applicable city and state codes and regulations regarding construction. The approval of the plans does not constitute any certification of the accuracy, completeness, or building permit status of the existing buildings and structures as shown. 1646 E Washington Ave03/28/23 14, 13, 14, 15, 16, 47. 18, 19. 1.10, 10. 127. 128. 1.29, -ROJECT NOTES: THIS PHOTOVOLTAIC (PV) SYSTEM SHALL COMPLY WITH THE 2022 CALIFORNIA ELECTRICAL CODE (CEC) ARTICLE 690, ALL MANUFACTURER'S LISTING AND INSTALLATION INSTRUCTIONS. AND THE RELEVANT CODES AS SPECIFIED BY THE AUTHORITY HAVING JURISDICTION'S (AHJ) APPLICABLE CODES. THE UTILITY INTERCONNECTION APPLICATION MUST BE APPROVED ANO PV SYSTEM INSPECTED PRIOR TO PARALLEL OPERATION ?GROUND FAULT DETECTION AND INTERRUPTION {GFDI} DEVICE IS INTEGRATED WITH THE MICROINVERTER IN ACCORDANCE WITH 2022 CEG 890 418) ALL PV SYSTEM COMPONENTS: MODULES, UTILITY-INTERACTIVE INVERTERS, AND SOURCE CIRGUIT COMBINER BOXES ARE IDENTIFIED AND LISTED FOR USE IN PHOTOVOLTAIC SYSTEMS AS REQUIRED BY 2022 CEC 690.4 PV MODULES: UL1703, 1E.C61730, AND IEC61215, AND NFPA 70 CLAGS C FIRE INVERTERS: UL 1741 CERTIFIED, IEEE 1547, 929, 519 COMBINER BOX(ES) UL 1703 OR UL 1741 ACCESSORY, MAX DC VOLTAGE CALCULATED USING MANUFACTURER PROVIDED TEMP COEFFICIENT FOR VOC. IF UNAVAILABLE, MAX OC VOLTAGE CALCULATEO. ACCORDING TO 2022 CEC 690 7. ALL INVERTERS, PHOTOVOLTAIC MODULES, PHOTOVOLTAIC PANELS. AND SOURCE CIRCUIT COMBINERS INTENDED FOR USE IN A PHOTOVOLTAIC POWER SYSTEM WILL BE IDENTIFIED AND LISTED FOR THE APPLICATION PER 690.4 (0). SHALL BE INSTALLED ACCORDING TO ANY INSTRUCTIONS, FROM LISTING OR LABELING [2022 CEC 110.3} ALL SIGNAGE TO BE PLACED IN ACCORDANCE WITH LOCAL BUILDING CODE. IF EXPOSED TO SUNLIGHT, IT SHALL BE UV RESISTANT. ALL PLAQUES AND SIGNAGE WILL BE INSTALLED AS REQUIRED BY THE CEC AND AHJ. SCOPE OF WOR! PRIME CONTRACTOR IS RESPONSIBLE FOR THE DESIGN AND ?SPECIFICATIONS OF THE GRID-TIED PHOTOVOLTAIC SYSTEM RETROFIT. PRIME CONTRACTOR WILL BE RESPONSIBLE FOR COLLECTING EXISTING ONSITE REQUIREMENTS TO DESIGN, SPECIFY. AND INSTALL THE EXTERIOR ROOF-MOUNTEO PORTION OF THE PHOTOVOLTAIC SYSTEMS DETAILED IN THIS DOCUMENT. ?WORK INCLUDES: BV ROOF ATTACHMENTS - UNIRAC FLASHKIT PRO FOR COMP SHINGLE ROOF BV RACKING SYSTEM INSTALLATION - UNIRAC SOLAR MOUNT ROOF MOUNT RACKING HARDWARE PV MODULE AND INVERTER I N S T A L L A T I O N -SOLARIA POWER X-390R (390) [BLK] MODULES / ENPHASE 108M-72-2-US MICROINVERTERS BV EQUIPMENT GROUNDING PV SYSTEM WIRING TO A ROOF-MOUNTEO JUNCTION BOX PV LOAD CENTERS (IF INCLUDED) PV METERING:MONITORING (FF INCLUDED) PV DISCONNECTS PV GROUNDING ELECTRODE & BONDING TO (E) GEC. PV FINAL COMMISSIONING. (E) ELECTRICAL EQUIPMENT RETROFIT FOR PV SIGNAGE PLACED IN ACCORDANCE WITH LOCAL BUILDING CODE \.SITE NOTES: ALLADDER WILL BE IN PLACE FOR INSPECTION IN COMPLIANCE WITH OSHA, REGULATIONS. ?THE PY MODULES ARE CONSIDERED NON.COMBUSTIBLE AND THIS SYSTEM IS A UTILITY INTERACTIVE SYSTEM WITH NO STORAGE BATTERIES. ?THE SOLAR PV INSTALLATION WILL NOT OBSTRUCT ANY PLUMBING, MECHANICAL. OR BUILDING ROOF VENTS. PROPER ACCESS AND WORKING CLEARANGE AROUND EXISTING AND. PROPOSED ELECTRICAL EQUIPMENT WILL BE PROVIDED AS PER SECTION 2022 CEC 110.28. ROOF COVERINGS SHALL BE DESIGNED, INSTALLED, AND MAINTAINED IN ACCORDANCE WITH THIS CODE AND THE APPROVED MANUFACTURER'S INSTRUCTIONS SUCH THAT THE ROOF COVERING SERVES TO PROTECT ?THE BUILDING OR STRUCTURE. 1.30, 3 432, 1.33) 4.34, 1.35, 1.38, 4a. +30) 1.40, 1A 1.42, 1.431 1a, 148, 148 1.47, 148. 1.48, 150, 1st. 321 183) 154, 158. EQUIPMENT LOCATIONS: ALL EQUIPMENT SHALL MEET MINIMUM SETBACKS AS REQUIRED @Y 2022 CEC 110.28 WIRING SYSTEMS INSTALLED IN DIRECT SUNLIGHT MUST BE RATED FOR EXPECTED OPERATING TEMPERATURE AS SPECIFIED BY 2022 CEC 690.31 (AKC) AND CEG TABLES 310.15 (B)2MA) AND 20.15 (813) JUNCTION AND PULL BOXES PERMITTED INSTALLED UNDERPV MODULES ACCORDING TO 2022 CEC 690 34 ADDITIONAL AC DISCONNECT(S) SHALL BE PROVIDED WHERE THE INVERTER IS NOT WITHIN SIGHT OF THE AC SERVICING DISCONNECT ALL EQUIPMENT SHALL BE INSTALLED ACCESSIBLE TO QUALIFIED. PERSONNEL ACCORDING TO 2022 CEG APPLICABLE CODES. ?ALL COMPONENTS ARE LISTED FOR THEIR PURPOSE AND RATED FOR, ?OUTDOOR USAGE WHEN APPROPRIATE, ?STRUCTURAL NOTE! RACKING SYSTEM PV ARRAY WiLL BE INSTALLED ACCORDING TO CODE-COMPLIANT INSTALLATION MANUAL TOP CLAMPS REQUIRE & DESIGNATED SPACE BETWEEN MODULES, AND RAILS MUST ALSO EXTEND. AMINIMUM DISTANCE BEYOND EITHER EDGE OF THE ARRAY/SUBARRAY. ?ACCORDING TO RAIL MANUFACTURER'S INSTRUCTIONS. JUNCTION BOX WILL BE INSTALLED PER MANUFACTURER'S SPECIFICATIONS. IF ROOF-PENETRATING TYPE, IT SHALL BE FLASHEO SEALED PER LOCAL REQUIREMENTS. ROOFTOP PENETRATIONS FOR PV RACEWAY WILL BE COMPLETED AND SEALED WITH APPROVED CHEMICAL SEALANT PER CODE BY A LICENSED CONTRACTOR, ALL PV RELATED ROOF ATTACHMENTS TO BE SPACED NO GREATER THAN ?THE SPAN DISTANCE SPECIFIED BY THE RACKING MANUFACTURER. WHENPOSSIBLE, ALL PV RELATED RACKING ATTACHMENTS WILL BE STAGGERED AMONGST THE ROOF FRAMING MEMBERS. WARING & CONDUIT NOTES: ALL CONDUIT AND WIRE WILL BE LISTED AND APPROVED FOR THEIR PURPOSE C O N D U I T ANDWIRE SPECIFICATIONS ARE BASED ON MINIMUM CODE REQUIREMENTS AND ARE NOT MEANT TO LIMIT UP-SIZING CONDUCTORS SIZEO ACCORDING TO 2022 CEC 690 8. 2022 CEC 690.7, VOLTAGE DROP LIMITED TO 1 5%. OC WIRING LIMITED TO MODULE FOOTPRINT. MICROINVERTER WIRING ?SYSTEMS SHALL BE LOCATED AND SECURED UNDER THE ARRAY WITH ?SUITABLE WIRING CLIPS. AG CONDUCTORS COLORED OR MARKED AS FOLLOWS: PHASE A OR L1- BLACK PHASE BOR L2- REO, OR OTHER CONVENTION IF THREE PHASE PHASEC OR L3- BLUE, YELLOW, ORANGE?, OR OTHER CONVENTION. NEUTRAL. WHITE OR GREY IN 4:WIRE DELTA CONNECTED SYSTEMS THE PHASE WITH HIGHER VOLTAGE TO BE MARKED ORANGE [2022 CEC 110.15, ING NOTE GROUNDING SYSTEM COMPONENTS SHALL BE LISTED FOR THEIR PURPOSE, AND GROUNDING DEVISES EXPOSED TO THE ELEMENTS SHALL BE RATED FOR SUCH USE. PY EQUIPMENT SHALL BE GROUNDED ACCORDING TO 2022 CEC 690.43 AND MINIMUM 2022 CEC TABLE 250.122. METAL PARTS OF MODULE FRAMES, MODULE RACKING, AND ENCLOSURES CONSIDERED GROUNDED IN ACCORDING WITH 2022 CEG 250.134 AND 2022 250 12644) EQUIPMENT GROUNDING CONDUCTORS SHALL BE SIZED ACCORDING TO CEC 690-45 AND MICROINVERTER MANUFACTURER'S INSTRUCTIONS. 156. 187 188. 159 180 181. 183 184. 185 166 187. 1.58. 1.70. ca 173. 1.74, EACH MODULE WILL BE GROUNDED USING WEEB GROUNDING CUPS AS SHOWN IN MANUFACTURER DOCUMENTATION AND APPROVED BY THE AK) (F WEBS ARE NOT USED MODULE GROUNDING LUGS MUST BE, INSTALLED AT THE SPECIFIED GROUNDING LUG HOLES PER THE MANUFACTURERS? INSTALLATION REQUIREMENTS THE GROUNDING CONNECTION TO A MODULE SHALL BE ARRANGED SUCH THAT THE REMOVAL OF A MODULE DOES NOT I N T E R R U P TA GROUNDING. CONDUCTOR TO ANOTHER MODULE. GROUNDING AND BONDING CONDUCTORS, IF INSULATED, SHALL BE COLORED GREEN OF MARKED GREEN IF #4 AWG OR LARGER [2022 CEC. 250 119] THE GROUNDING ELECTRODE SYSTEM COMPLIES WITH CEC 690 47 AND ?CEC 250 50 THROUGH 250.108 iF EXISTING SYSTEM IS INACCESSBLE. OR. INADEQUATE. A GROUNDING ELECTRODE SYSTEM PROVIDED ACCORDING TO ?CEC 250, CEC 690.47 AND AHI GROUND-FAULT DETECTION SHALL COMPLY WITH CEC 690.41 IN GENERAL AND CEC 690.41 {A\1) SPECIFICALLY. DISCONNECTION AND OVER-CURRENT PROTECTION NOTES: DISCONNECTING SWITCHES SHALL BE WIRED SUCH THAT WHEN THE SWITCH IS OPENED THE CONDUCTORS REMAINING ENERGIZED ARE. CONNECTED TO THE TERMINALS MARKED ?LINE SIDE? (TYPICALLY THE UPPER TERMINALS) DISCONNECTS TO BE ACCESSIBLE TO QUALIFIED UTILITY PERSONNEL. BE LOCKABLE, AND BE A VISIBLE-GREAK SWITCH RAPID SHUTDOWN OF ENERGIZED CONDUCTORS BEYOND 1FTOF PV ARRAY OR 5 FT INSIDE A BUILDING WITHIN 10 SECONDS. CONTROLLED CONDUCTORS S30V AND <240VA [CEG 690.12(6)} LOCATION OF LABEL ACCOROING TO AHS ALL OCPD RATINGS AND TYPES SPECIFIED ACCORDING TO CEC 690.8, 8909 AND 240 EQUIPMENT THAT IS LISTED, LABELED. OR BOTH SHALL BE INSTALLEDAND ?USED IN ACCORDANCE WITH ANY INSTRUCTIONS INCLUDED IN THE LISTING ?OR LABELING. CEC 110.318) IF REQUIRED 6Y AHJ, SYSTEM WILL INCLUDE ARC-FAULT CIRCUIT PROTECTION ACCORDING TO CEC 690.11 AND UL16998. SSTERCONNECTION NOTES: LOAD-SIDE INTERCONNECTION SHALL BE IN ACCORDANCE WITH i2022 CEC 705 121BV2K3nalt THE SUM OF THE UTILITY OCPD AND INVERTER CONTINUOUS INPUT MAY NOT EXCEED 120% OF BUSQAR RATING [2022 CEC 705 12(BKSN2i] [ene CEG 705 1218%2) WHEN SUM OF THEPV SOURCES EQUALS >100% OF BUSBAR RATING. PV CEDICATED BACKFEED BREAKERS MUST 8E LOCATED OPPOSITE END OF THE BUS FROM THE UTILITY SOURCE OCPD {2022 CEC 705 12(B}23Nell AT MULTIPLE PV OUTPUT COMBINER PANEL. TOTAL RATING OF ALL QVERCURRENT DE. "''< SHALL NOT EXCEED AMPACITY OF BUSBAR HOWEVER THE: -ERGURRENT DEVICE MAY BE EXCLUDED ACCORDING 10 duc. 2 ?U5 121893) SUPPLY SIDE TAP INTERCONNECTION ACCORDING TO 2022 CEC 706.11 HTH SERVICE ENTRANCE CONDUCTORS IN ACCORDANCE WITH 2022 CEC 290.42 GACKFEEDING BREAKER FOR UTILTY-NTERACTIVE INVERTER OUTPUT (S EXEMPT FROM ADOITIONAL FASTENING [2022 CEC 705.12(E)I- C o m p l e t e S o l a r ABogtter Way 3 0 0 0 E X E C U T I V E P K W Y , S T E 5 0 4 S A N R A M O N , C A 9 4 5 8 3 L I C E N S E T Y P E C 1 0 L I C E N S E # 9 6 1 9 8 8 P H O N E # (8 7 7 ) 2 9 9 - 4 9 4 3 DESIGNER: ORV JUAN SIANCASTAO RESIDENCE 1646 E WASHI NGTON AVE SANTA A N A C A 9 2 7 0 1 APN:40028711 DATE:2/23/2023 1646 E Washington Ave03/28/23