HomeMy WebLinkAbout2002 S Artesia St - 20181492 - PlanBETTER EARTH ELECTRIC INC.
16720 MARQUARDT AVE CERRITOS
CERRITOS, CA 90703
PHONE #: (888) 373-9379
LIC #: C10-1024460
DESIGNER: TAYLOR BICKFORD
NEW PV SYSTEM: 7290 DC / 6000 AC
Francisco Rodriguez
2002 S Artesia St, Santa Ana, CA 92704
APN: 40836410
11/10/2023DATE:
TIME: 03:39 pm
REVISION:DATE:DESCRIPTION:
DRAWING TITLE:
DRAWING PAGE:
SCALE:
DESIGNER SIGNATURE:
COVER SHEET
P1
TABLE OF CONTENTS
PAGE NUMBER: PAGE TITLE:
P1 COVER SHEET
P2 NOTES SHEET
P3 SITE PLAN
P4 ROOF PLAN
P5 RACKING & FRAMING
P6 LINE DIAGRAM &
DESIGN TABLES
P7 PLACARDS & PLACARD
MAP
P8 OPTIMIZER MAP
P9 JOB HAZARD ANALYSIS
SS00 SPECIFICATION PAGES
JURISDICTION STAMPS: Francisco Rodriguez
2002 S Artesia St, Santa Ana, CA 92704
APN: 40836410
SYSTEM SIZE: 7290 DC
SYSTEM SIZE 6000 AC
CEC POWER OUTPUT: 6773.4 CEC
PROPERTY INFORMATION
OWNER:Francisco Rodriguez
PHONE:1714-495-6452
EMAIL:luzrodriguez010667@gmail.com
CONTRACTOR:BETTER EARTH
ELECTRIC INC.
PHONE: (888) 373-9379
AUTHORITIES HAVING JURISDICTION
BUILDING: SANTA ANA (CA)
UTILITY: SOUTHERN CALIFORNIA EDISON
DESIGN SPECIFICATIONS
OCCUPANCY: R-3/U
CONSTRUCTION: V-B
NAME: RESIDENTIAL
SNOW LOAD: 0 PSF
WIND EXPOSURE: C
WIND SPEED: 130 MPH
ROOF SURFACE: 2881 SQ.FT.
PV SQ FOOTAGE: 380.18 SQ.FT.
PV COVERAGE: 13.20 %
WEIGHT OF EQUIPMENT: 858.42 LBS
WEIGHT PER ATTACHMENT: 20.44 LBS
DISTRIBUTED WEIGHT: 2.26 PSF
NO. OF STORIES: 1
FIRE SPRINKLERS: NO
LOT INFORMATION
APN: 40836410
LOT AREA: 6100
LIVING AREA: 1775
MODULE INFORMATION
MODULE QTY:
MODULE MFG:
MODULE TYPE:
INVERTER INFORMATION
INVERTER QTY: 1 INVERTER MFG: SOLAREDGE
INVERTER TYPE:
POWER OPTIMIZER INFORMATION
OPTIMIZER QTY: 18
OPTIMIZER MFG: SOLAREDGE
OPTIMIZER TYPE: S440
RAILING INFORMATION
RAILING MFG: UNIRAC
RAILING TYPE: UNIRAC SM LIGHT
MOUNTING INFORMATION
MOUNT FLASHING QTY:
MOUNT FLASHING MFG: UNIRAC
MOUNT FLASHING TYPE:
42
UNIRAC FLASHLOC - MILL
6000H-US (ENERGY HUB) RGM
18
HANWHA Q CELLS
Q.PEAK DUO BLK ML-G10+ 405
ENERGY STORAGE SYSTEM INFORMATION
BATTERY QTY:
BATTERY MFG:
BATTERY TYPE:
1
SOLAREDGE
ENERGY BANK 10kWh BAT-10K1P
EXISTING SOLAR INFORMATION - N/A
PROJECT DETAILS
ADDITIONAL SCOPE OF WORK
MAIN PANEL UPGRADE: (E) 100A/100A TO (N) 225A/200A
DERATE MAIN BREAKER: N/A
EV CHARGER: N/A
ESS: OUTDOORS ON EXTERIOR WALL - (1) SOLAREDGE ENERGY BANK AT 10kWh EACH
BATTERY TO BE INSTALLED AT LEAST 3' FROM EDGES, WINDOWS, DOORS, VENTS,
GAS, AND OTHER EQUIPMENT.
DISCONNECTS
MINIMUM NUMBER OF DISCONNECTS REQUIRED TO TURN OFF POWER SOURCES FEEDING
THE HOME
1. UTILITY AC DISCONNECT
2. PV RAPID SHUTDOWN INTEGRATED WITH INVERTER
3. DC DISCONNECT
ALL WORK SHALL COMPLY WITH THE MOST CURRENT LOS ANGELES COUNTY FIRE CODE
AND ITS SECTIONS.
PROJECT SHALL COMPLY WITH THE CURRENT VERSION OF THE LOS ANGELES COUNTY FIRE
DEPARTMENT ELECTRICAL POWER SOURCE DISCONNECT PLACARDING SYSTEM.
UPSIZE MAIN BREAKER: N/A
This item has been digitally signed
and sealed on Nov 14, 2023
Revision to
ELEC# 20180711
Issued 09/12/2023
ELEC# 20181492
Issues 01/10/2024
Approved
ELEC- MSmith
The scope of the plans is for the installation of
the solar photovoltaic system only and the
approval is subject to compliance with all
applicable city and state codes and regulations
regarding construction. The approval of the
plans does not constitute any certification of the
accuracy, completeness, or building permit
status of the existing buildings and structures
as shown.
2002 S Artesia St -
201814921/10/2024
IN
V
B
MS
P
DC
SITE PLAN
N
(N) BATTERY
ROOF ACCESS POINT
PER CRC 2022 (R324.6)
ARRAY 1 -
(N) 18 HANWHA Q CELLS
MODULES
TILT: 12°
AZIMUTH: 295°
P3
DESIGNER: TAYLOR BICKFORD
NEW PV SYSTEM: 7290 DC / 6000 AC
Francisco Rodriguez
2002 S Artesia St, Santa Ana, CA 92704
APN: 40836410
11/10/2023DATE:
TIME:03:39 pm
REVISION:DATE:DESCRIPTION:
DRAWING TITLE:
DRAWING PAGE:
SCALE:
DESIGNER SIGNATURE:
(N) 225A MAIN
SERVICE PANEL
(N) SOLAREDGE
6000H-US (ENERGY HUB)
RGM INVERTER
1" = 15'
JURISDICTION STAMPS:
NOTES:
BETTER EARTH ELECTRIC INC.
16720 MARQUARDT AVE CERRITOS
CERRITOS, CA 90703
PHONE #: (888) 373-9379
LIC #: C10-1024460
DRIVEWAY
PROP
E
R
T
Y
L
I
N
E
(N) 30A DC DISCONNECT
This item has been digitally signed
and sealed on Nov 14, 2023
2002 S Artesia St -
201814921/10/2024
POWER SOURCE DISCONNECT SCHEDULE
DISCONNECT NUMBER
1 OF 3
2 OF 3
3 OF 3
TYPE OF DISCONNECT
UTILITY
PV RAPID SHUTDOWN
DC DISCONNECT
14'
INVERTER
METER/MSP 14'
15'
GAS METER
ENERGY BANK
1 OF 3
2 OF 3 3 OF 3
DC DISCONNECT
WINDOW
DESIGNER: TAYLOR BICKFORD
NEW PV SYSTEM: 7290 DC / 6000 AC
Francisco Rodriguez
2002 S Artesia St, Santa Ana, CA 92704
APN: 40836410
11/10/2023DATE:
TIME:03:39 pm
REVISION:DATE:DESCRIPTION:
DRAWING TITLE:
DRAWING PAGE:
SCALE:
DESIGNER SIGNATURE:ELEVATION DETAIL
P5.1
ELEVATION DETAIL JURISDICTION STAMPS:
BETTER EARTH ELECTRIC INC.
16720 MARQUARDT AVE CERRITOS
CERRITOS, CA 90703
PHONE #: (888) 373-9379
LIC #: C10-1024460
This item has been digitally signed
and sealed on Nov 14, 2023
2002 S Artesia St -
201814921/10/2024
STRING 1: (9x) Hanwha Q CELLS Q.PEAK DUO
BLK ML-G10+ 405 PV MODULES
WITH 9 S440 SE POWER OPTIMIZERS
1
1
JUNCTION BOX
- NEMA 3R
AS REQUIRED
2
3+-
+-
+-
+-
+-
+-
+-
+-
+-
+-
+-
+-
STRING 2: (9x) Hanwha Q CELLS Q.PEAK DUO
BLK ML-G10+ 405 PV MODULES
WITH 9 S440 SE POWER OPTIMIZERS
921
921
(N) INVERTER
SOLAREDGE
SE6000H-US (ENERGY HUB)
RGM (240V) [SL1]
DC AC
4
MAIN (N) 200A
(N) 40A
M
BI-DIRECTIONAL
UTILITY METER
1PH/240V
MAIN BONDING JUMPER
TO UTILITY GRID
(OVERHEAD)
SOLAR BREAKER LOCATED
AT THE FURTHEST END OF
BUS BAR FROM THE MAIN
BREAKER
MAX BREAKER CALC.:
225A X 1.2 - 200A = 70A
(N) 225A/200A MAIN
SERVICE PANEL
240/120v 1-PH, 3-W
POINT OF INTERCONNECTION
LOAD SIDE 705.12(B)(3)(2)
(E) GROUNDING
ELECTRODE
(COPPER)
GROUND
ROD
METER NUMBER: 222013-510057
(1) (N)
SOLAREDGE
ENERGY BANK
BAT-10K1P
5.0kW, 9.7kWh
30A,600V DC
DISCONNECT
CONDUCTOR AND CONDUIT SCHEDULE W/ELECTRICAL CALCULATIONS
ID CONDUCTOR (CU)CONDUIT CONDUCTORS IN CONDUIT EGC TEMP. CORR. FACTOR CONT. CURRENT MAX. CURRENT (125%)BASE AMP.DERATED AMP.TERM. TEMP. RATING
2 3/4" EMT 4 & (1)G #8 0.91 15 18.75 40 36.4 90#10 THWN-2, in conduit
1 #10 PV Wire, in open air N/A N/A #6 0.91 15 18.75 40 36.4 90
#8 THWN-2, in conduit 3/4" EMT #8 0.91 32 40 55 50.05 903 & (1)G
#10 THWN-2, in conduit 3/4" EMT #8 0.91 21 26 40 36.4 903 & (1)G4
3
DESIGN TEMPERATURES
ASHRAE 2% HIGH
30°C
2°C
ASHRAE EXTREME LOW
INVERTER 1 SPECS
SE6000H-US (ENERGY HUB)_RGM
AC VOLTAGE
240V
GROUND
MAX OCPD
35A
RATED POWER
6000W
MAX OUTPUT
25A
MAX INPUT
17A
MAX INPUT
480V
EFFICIENCY
CEC
POWERBOX MAX OUTPUT CURRENT
OPTIMIZERS IN SERIES
NOMINAL STRING VOLTAGE
ARRAY OPERATING CURRENT
STRING DETAILS
STRING CALCULATIONS - INVERTER 1
STRING 1 STRING 2
15A
9
380V
25A
15A
9
380V
25A
TOTAL SYSTEM SUMMARY
ARRAY STC POWER
7290W
ARRAY PTC POWER
6773.4W
MAX AC CURRENT
25A
MAX AC POWER
6000W
MODULE SPECS
HANWHA Q CELLS
Q.PEAK DUO BLK ML-G10+ 405
PMAX
405W
PTC
376.3W
ISC
11.17A
IMP
10.83A
VOC
45.34V
VMP
37.39V
TEMP. COEFF. OF VOC
-0.122
POWER
OPTIMIZERS
RATED INPUT
MAX ISC
WEIGHTED EFFICIENCY
MAX OUTPUT
MAX DC
SOLAREDGE
S440 OPTIMIZER
440W
15A
98.6
15A
60V
AHJ/UTILITY NOTES:
SOLAREDGE INVERTER EQUIPPED WITH RSD PER 690.12
INSTALLER NOTES:
DESIGNER: TAYLOR BICKFORD
NEW PV SYSTEM: 7290 DC / 6000 AC
Francisco Rodriguez
2002 S Artesia St, Santa Ana, CA 92704
APN: 40836410
11/10/2023DATE:
TIME:03:39 pm
REVISION:DATE:DESCRIPTION:
DRAWING TITLE:
DRAWING PAGE:
SCALE:
DESIGNER SIGNATURE:
LINE DIAGRAM &
DESIGN TABLES
P6
JURISDICTION STAMPS:
EQUIPMENT SPECS
BETTER EARTH ELECTRIC INC.
16720 MARQUARDT AVE CERRITOS
CERRITOS, CA 90703
PHONE #: (888) 373-9379
LIC #: C10-1024460
This item has been digitally signed
and sealed on Nov 14, 2023
2002 S Artesia St -
201814921/10/2024