Loading...
HomeMy WebLinkAbout2007 S Main St - PlanSCOPE OF WORK SYSTEM SIZE: STC: 87 X 450W = 39.150KW PTC: 87 X 426.6W = 37.114KW (87) YOTTA YSM-B450-1 (22) YOTTA DPI-208 ATTACHMENT TYPE: UNIRAC BALLASTED MOUNT RM10 EVO MSP UPGRADE: NO OWNER NAME: AZ-3320 PROJECT MANAGER NAME: ANTHONY BARO PHONE: CONTRACTOR NAME:E2SOL PHONE:401-489-2273 AUTHORITIES HAVING JURISDICTION BUILDING: SANTA ANA CITY ZONING: SANTA ANA CITY UTILITY: DESIGN SPECIFICATIONS OCCUPANCY: MERCANTILE GROUP M CONSTRUCTION TYPE: V-B CONSTRUCTION: TRUSS 2'-0" O.C. TOTAL BUILDING AREA: 5516 SQ. FT. ZONNING: COMMERCIAL GROUND SNOW LOAD: 0 PSF WIND EXPOSURE: B WIND SPEED: 95 MPH APPLICABLE CODES & STANDARDS BUILDING: CBC 2022 ELECTRICAL: CEC 2022 FIRE: CFC 2022 PROJECT INFORMATION NEW PV SYSTEM: 39.150 kWp AZ-3320 2007 S MAIN ST, SANTA ANA, CA 92707 ASSESSOR'S #: 403-164-31 C2019G 2.1.1 SITE NOTES: 2.1.2 A LADDER WILL BE IN PLACE FOR INSPECTION IN COMPLIANCE WITH OSHA REGULATIONS. 2.1.3 THE PV MODULES ARE CONSIDERED NON-COMBUSTIBLE AND THIS SYSTEM IS A UTILITY INTERACTIVE SYSTEM WITH NO STORAGE BATTERIES. 2.1.4 THE SOLAR PV INSTALLATION WILL NOT OBSTRUCT ANY PLUMBING, MECHANICAL, OR BUILDING ROOF VENTS. 2.1.5 PROPER ACCESS AND WORKING CLEARANCE AROUND EXISTING AND PROPOSED ELECTRICAL EQUIPMENT WILL BE PROVIDED AS PER SECTION CEC 110.26. 2.1.6 ROOF COVERINGS SHALL BE DESIGNED, INSTALLED, AND MAINTAINED IN ACCORDANCE WITH THIS CODE AND THE APPROVED MANUFACTURER'S INSTRUCTIONS SUCH THAT THE ROOF COVERING SERVES TO PROTECT THE BUILDING OR STRUCTURE. 2.2.1 EQUIPMENT LOCATIONS: 2.2.2 ALL EQUIPMENT SHALL MEET MINIMUM SETBACKS AS REQUIRED BY CEC 110.26. 2.2.3 WIRING SYSTEMS INSTALLED IN DIRECT SUNLIGHT MUST BE RATED FOR EXPECTED OPERATING TEMPERATURE AS SPECIFIED BY CEC 690.31 (A),(C) AND CEC TABLE 310.15 (B)(1). 2.2.4 JUNCTION AND PULL BOXES PERMITTED INSTALLED UNDER PV MODULES ACCORDING TO CEC 690.34. 2.2.5 ADDITIONAL AC DISCONNECT(S) SHALL BE PROVIDED WHERE THE INVERTER IS NOT WITHIN SIGHT OF THE AC SERVICING DISCONNECT. 2.2.6 ALL EQUIPMENT SHALL BE INSTALLED ACCESSIBLE TO QUALIFIED PERSONNEL ACCORDING TO CEC APPLICABLE CODES. 2.2.7 ALL COMPONENTS ARE LISTED FOR THEIR PURPOSE AND RATED FOR OUTDOOR USAGE WHEN APPROPRIATE. 2.3.1 STRUCTURAL NOTES: 2.3.2 RACKING SYSTEM & PV ARRAY WILL BE INSTALLED ACCORDING TO CODE-COMPLIANT INSTALLATION MANUAL. TOP CLAMPS REQUIRE A DESIGNATED SPACE BETWEEN MODULES, AND RAILS MUST ALSO EXTEND A MINIMUM DISTANCE BEYOND EITHER EDGE OF THE ARRAY/SUBARRAY, ACCORDING TO RAIL MANUFACTURER’S INSTRUCTIONS. 2.3.3 JUNCTION BOX WILL BE INSTALLED PER MANUFACTURERS' SPECIFICATIONS. IF ROOF-PENETRATING TYPE, IT SHALL BE FLASHED & SEALED PER LOCAL REQUIREMENTS. 2.3.4 ROOFTOP PENETRATIONS FOR PV RACEWAY WILL BE COMPLETED AND SEALED W/ APPROVED CHEMICAL SEALANT PER CODE BY A LICENSED CONTRACTOR. 2.3.5 ALL PV RELATED ROOF ATTACHMENTS TO BE SPACED NO GREATER THAN THE SPAN DISTANCE SPECIFIED BY THE RACKING MANUFACTURER. 2.3.6 WHEN POSSIBLE, ALL PV RELATED RACKING ATTACHMENTS WILL BE STAGGERED AMONGST THE ROOF FRAMING MEMBERS. 2.4.1 WIRING & CONDUIT NOTES: 2.4.2 ALL CONDUIT AND WIRE WILL BE LISTED AND APPROVED FOR THEIR PURPOSE. CONDUIT AND WIRE SPECIFICATIONS ARE BASED ON MINIMUM CODE REQUIREMENTS AND ARE NOT MEANT TO LIMIT UP-SIZING. 2.4.3 CONDUCTORS SIZED ACCORDING TO CEC 690.8, CEC 690.7. 2.4.4 VOLTAGE DROP LIMITED TO 1.5%. 2.4.5 DC WIRING LIMITED TO MODULE FOOTPRINT. MICROINVERTER WIRING SYSTEMS SHALL BE LOCATED AND SECURED UNDER THE ARRAY W/ SUITABLE WIRING CLIPS. 2.4.6 AC CONDUCTORS COLORED OR MARKED AS FOLLOWS: PHASE A OR L1- BLACK PHASE B OR L2- RED, OR OTHER CONVENTION IF THREE PHASE PHASE C OR L3- BLUE, YELLOW, ORANGE**, OR OTHER CONVENTION NEUTRAL- WHITE OR GRAY IN 4-WIRE DELTA CONNECTED SYSTEMS THE PHASE WITH HIGHER VOLTAGE TO BE MARKED ORANGE [CEC 110.15]. 2.5.1 GROUNDING NOTES: 2.5.2 GROUNDING SYSTEM COMPONENTS SHALL BE LISTED FOR THEIR PURPOSE, AND GROUNDING DEVICES EXPOSED TO THE ELEMENTS SHALL BE RATED FOR SUCH USE. 2.5.3 PV EQUIPMENT SHALL BE GROUNDED ACCORDING TO CEC 690.43 AND MINIMUM CEC TABLE 250.122. 2.5.4 METAL PARTS OF MODULE FRAMES, MODULE RACKING, AND ENCLOSURES CONSIDERED GROUNDED IN ACCORD WITH 250.134 AND 250.136(A). 2.5.5 EQUIPMENT GROUNDING CONDUCTORS SHALL BE SIZED ACCORDING TO CEC 690.45 AND MICROINVERTER MANUFACTURERS' INSTRUCTIONS. 2.5.6 EACH MODULE WILL BE GROUNDED USING WEEB GROUNDING CLIPS AS SHOWN IN MANUFACTURER DOCUMENTATION AND APPROVED BY THE AHJ. IF WEEBS ARE NOT USED, MODULE GROUNDING LUGS MUST BE INSTALLED AT THE SPECIFIED GROUNDING LUG HOLES PER THE MANUFACTURERS' INSTALLATION REQUIREMENTS. 2.5.7 THE GROUNDING CONNECTION TO A MODULE SHALL BE ARRANGED SUCH THAT THE REMOVAL OF A MODULE DOES NOT INTERRUPT A GROUNDING CONDUCTOR TO ANOTHER MODULE. 2.5.8 GROUNDING AND BONDING CONDUCTORS, IF INSULATED, SHALL BE COLORED GREEN OR MARKED GREEN IF #4 AWG OR LARGER [CEC 250.119] 2.5.9 THE GROUNDING ELECTRODE SYSTEM COMPLIES WITH CEC 690.47 AND CEC 250.50 THROUGH 250.106. IF EXISTING SYSTEM IS INACCESSIBLE, OR INADEQUATE, A GROUNDING ELECTRODE SYSTEM PROVIDED ACCORDING TO CEC 250, CEC 690.47 AND AHJ. 2.5.10 GROUND-FAULT DETECTION SHALL COMPLY WITH CEC 690.41(B)(1) THROUGH (3) TO REDUCE FIRE HAZARDS 2.6.1 DISCONNECTION AND OVER-CURRENT PROTECTION NOTES: 2.6.2 DISCONNECTING SWITCHES SHALL BE WIRED SUCH THAT WHEN THE SWITCH IS OPENED THE CONDUCTORS REMAINING ENERGIZED ARE CONNECTED TO THE TERMINALS MARKED “LINE SIDE” (TYPICALLY THE UPPER TERMINALS). 2.6.3 DISCONNECTS TO BE ACCESSIBLE TO QUALIFIED UTILITY PERSONNEL, BE LOCKABLE, AND BE A VISIBLE-BREAK SWITCH 2.6.4 PV SYSTEM CIRCUITS INSTALLED ON OR IN BUILDINGS SHALL INCLUDE A RAPID SHUTDOWN FUNCTION TO REDUCE SHOCK HAZARD FOR EMERGENCY RESPONDERS IN ACCORDANCE WITH 690.12(A) THROUGH (D). 2.6.5 ALL OCPD RATINGS AND TYPES SPECIFIED ACCORDING TO CEC 690.8, 690.9, AND 240. 2.6.6 MICROINVERTER BRANCHES CONNECTED TO A SINGLE BREAKER OR GROUPED FUSES IN ACCORDANCE WITH CEC 110.3(B). 2.6.7 IF REQUIRED BY AHJ, SYSTEM WILL INCLUDE ARC-FAULT CIRCUIT PROTECTION ACCORDING TO CEC 690.11 AND UL1699B. 2.7.1 INTERCONNECTION NOTES: 2.7.2 LOAD-SIDE INTERCONNECTION SHALL BE IN ACCORDANCE WITH CEC 705.12 2.7.3 THE SUM OF 125 PERCENT OF THE POWER SOURCE(S) OUTPUT CIRCUIT CURRENT AND THE RATING OF THE OVERCURRENT DEVICE PROTECTING THE BUSBAR SHALL NOT EXCEED 120 PERCENT OF THE AMPACITY OF THE BUSBAR, PV DEDICATED BACKFEED BREAKERS MUST BE LOCATED OPPOSITE END OF THE BUS FROM THE UTILITY SOURCE OCPD [CEC 705.12(B)(3)(2)]. 2.7.4 AT MULTIPLE ELECTRIC POWER SOURCES OUTPUT COMBINER PANEL, TOTAL RATING OF ALL OVERCURRENT DEVICES SHALL NOT EXCEED AMPACITY OF BUSBAR. HOWEVER, THE COMBINED OVERCURRENT DEVICE MAY BE EXCLUDED ACCORDING TO CEC 705.12 (B)(3)(3). 2.7.5 FEEDER TAP INTERCONNECTION (LOAD SIDE) ACCORDING TO CEC 705.12 (B)(1) AND (2) 2.7.6 SUPPLY SIDE TAP INTERCONNECTION ACCORDING TO CEC 705.11 WITH SERVICE ENTRANCE CONDUCTORS IN ACCORDANCE WITH CEC 230.42 2.7.7 BACKFEEDING BREAKER FOR ELECTRIC POWER SOURCES OUTPUT IS EXEMPT FROM ADDITIONAL FASTENING [CEC 705.12 (E)]. *CEC2022M *CEC2022M GENERAL NOTES A-201 01 E MAIN ENTRANCE DOOR PROPERTY LINE SOLAR (PV) MODULE EQUIPMENT GROUND CONDUIT FIRE CLEARANCE (E) UTILITY METERM S PNL V MEP AC DISCONNECT AC PANELBOARD PV REVENUE METERMAIN ELECTRICAL PANEL DC/AC INVERTER DC DISCONNECT COMBINER BOX JUNCTION BOX INV DCSW CBR JB U UTILITY POLE TB RSD TAP BOX RAPID SHUTDOWN SUB (AC) PANEL METER/MAIN SUB M/M CBR MODULE STRINGING (DC) COMBINER BOX MODULE STRINGING MODULE STRINGING ATTACHMENTS RAILS ROOF RAFTERS N EW S S-501 D1 26 SYMBOL LEGEND MODULE STRINGING MODULE STRINGING SHEET KEYNOTE INDICATOR DETAIL INDICATOR ELEVATION INDICATOR NORTH INDICATOR DISCLAIMER: PLEASE NOTE THAT THE ABBREVIATIONS, ANNOTATIONS, AND SYMBOLS LISTED ARE INTENDED TO ILLUSTRATE THOSE THAT ARE COMMONLY USED; NOT ALL ARE NECESSARILY UTILIZED WITHIN THIS SET OF DRAWINGS. A B C D A B C D SETBACK G-1 COVER PAGE 01 AERIAL PHOTO NOT TO SCALE N EW S 02 PLOT MAP NOT TO SCALE N EW S ENGINEER OF RECORD DATE: 8.21.2023 DESIGN BY: V.D. CHECKED BY: D.A. AZ-3320 2007 S MAIN ST, SANTA ANA, CA 92707 PAPER SIZE: 36" x 24" (ARCH D) A B C D E F G H I J K L M N O 1 2 3 4 5 6 7 8 9 10 11 12 A B C D E F G H I J K L M N O CONTRACTOR E2SOL PHONE: LIC. NO.: UNAUTHORIZED USE OF THIS DRAWING SET WITHOUT WRITTEN PERMISSION FROM CONTRACTOR IS IN VIOLATION OF U.S. COPYRIGHT LAWS AND WILL BE SUBJECT TO CIVIL DAMAGES AND PROSECUTIONS. P P NO. DESCRIPTION DATE PROJECT REVISION / RELEASE SHEET NUMBER: SHEET TITLE: 401-489-2273 APN: 403-164-31 REPC-134 NEW PV SYSTEM: 39.150 kWp 1 REVISION 1 01.10.2024 SHEET LIST TABLE SHEET NUMBER SHEET TITLE G-1 COVER PAGE PV-1 SITE PLAN PV-2 ELECTRICAL ROOF PLAN PV-3 ARRAY PLAN PV-4 THREE LINE DIAGRAM PV-5 PLACARDS PV-6 RESOURCE DOCUMENTS PV-7 RESOURCE DOCUMENTS S M A I N S T REVISION 1: 01.10.2024 - SHEET G-1: VERIFIED BUILDING SPECS - SHEET PV-1: PROPERTY LINE TAG ADDED -SHEET PV-3: LAYOUT AND CALCULATIONS UPDATED WITH SEISMIC ATTACHMENTS 1 Signed 1/10/2024 Bldg#: 101117244 Elec#: 20181345 Approvals: Planning: FArias Bldg: JLo Elec: MSmith The scope of the plans is for the installation of the solar photovoltaic system only and the approval is subject to compliance with all applicable city and state codes and regulations regarding construction. The approval of the plans does not constitute any certification of the accuracy, completeness, or building permit status of the existing buildings and structures as shown. 2007 S Main St - 101117244 & 20181345 3/20/2024 1. FIELD VERIFY ALL MEASUREMENTS 2. SEE SHEET G-1 FOR LEGEND OF SYMBOLS 3. SEE PV-2 FOR DETAILS 4. RELOCATE DRAIN PVC PIPES IF NEEDED. GAS LINES TO REMAIN GENERAL NOTES PROPERTY LINE PV-1 SITE PLAN ENGINEER OF RECORD DATE:8.21.2023 DESIGN BY:V.D. CHECKED BY:D.A. AZ-3320 2007 S MAIN ST, SANTA ANA, CA 92707 PAPER SIZE: 36" x 24" (ARCH D) A B C D E F G H I J K L M N O 1 2 3 4 5 6 7 8 9 10 11 12 A B C D E F G H I J K L M N O CONTRACTOR E2SOL PHONE: LIC. NO.: UNAUTHORIZED USE OF THIS DRAWING SET WITHOUT WRITTEN PERMISSION FROM CONTRACTOR IS IN VIOLATION OF U.S. COPYRIGHT LAWS AND WILL BE SUBJECT TO CIVIL DAMAGES AND PROSECUTIONS. P P NO. DESCRIPTION DATE PROJECT REVISION / RELEASE SHEET NUMBER: SHEET TITLE: 401-489-2273 APN: 403-164-31 REPC-134 NEW PV SYSTEM: 39.150 kWp 1 REVISION 1 01.10.2024 CONSTRUCTION NOTES 1. SOLAR PHOTOVOLTAIC SYSTEM TO BE INSTALLED ON ROOF. 2. THIS PROJECT HAS BEEN DESIGNED IN COMPLIANCE WITH THE CBC SECTION 1609 TO WITHSTAND A BASIC WIND SPEED OF 95 MPH (3 SECOND GUST), WIND EXPOSURE B. N EW S 03/32" = 1'-0" SITE PLAN01 5'-4" 10'-8" AREA OF WORK (E) (1) MAIN SERVICE SWITCHBOARD (N) (1) AC COMBINER BOX (N) (1) AC DISCONNECT (N) (1) PV METER EXTERIOR PV EQUIPMENT S M A I N S T 14'-3" 63'-1" 19'-2" 78'-0" PROPERTY LINE 1 Signed 1/10/2024 2007 S Main St - 101117244 & 20181345 3/20/2024 X 1 1 1 1 1 X 1 1 1 1 1 1 1 X 1 1 1 1 1 1 1 1 1 2 1 1 X 1 1 1 1 1 1 1 1 1 1 X 1 2 1 X 1 1 1 11 X 1 1 1 1 1 1 1 1 1 1 1 1 1 X 1 1 1 1 1 1 1 1 X 1 X 1 X 1 1 1 1 1 1 1 1 1 1 1 1 1 1 X 1 X 1 2 1 1 1 1 1 11 1 1 1 X 1 1 1 1 1 1 1 1 1 1 1 1 1 X 1 1 X 1 1 X MODULE: YOTTA YSM-B450-1 450 WATTS 40.87'' 82.44'' SHEET KEYNOTES 1. ROOF MATERIAL: TPO 2. ROOF STRUCTURE: TRUSS 2'-0" O.C. 3. ATTACHMENT TYPE: UNIRAC BALLASTED MOUNT RM10 EVO 4. MODULE MANUFACTURER: YOTTA 5. MODULE MODEL: YSM-B450-1 6. MODULE LENGTH: 82.44'' 7. MODULE WIDTH: 40.87'' 8. MODULE WEIGHT: 61.73 LBS. 9. SEE SHEET PV-3 FOR DIMENSION(S) 10. MIN. FIRE OFFSET: 4' FROME EDGE ONLY 11. TOTAL AREA: 2801 SQ. FT. 12. TOTAL WEIGHT: 9318 LBS. 13. AVERAGE PSF: 3.33 PSF 14. MAX. VERTICAL STANDOFF: IN ACCORDANCE WITH MODULE MANUFACTURER'S INSTRUCTIONS. 15. STANDOFF STAGGERING: NO 16. RAIL MANUFACTURER (OR EQUIV.): UNIRAC 17. RAIL MODEL (OR EQUIVALENT): RM10 EVO 18. MAX. RAFTER SPAN: N/A 19. ARRAY MAX HEIGHT: 16 IN. 20. RACKING WEIGHT: 309 LBS 21. MODULE WEIGHT: 5371 LBS 22. BALLAST WEIGHT: 3584 LBS 23. MAX BAY LOAD (DEAD): 128 LBS 24. 310771 RM10 ATTACHMENT KIT 25. 3/8-16 STRUT NUT x2 26. ATTACHMENT TYPE: U-ANCHOR U-2400 27. #15 X 4" ANCHOR SCREW: 8 PER ATTACHMENT 28. SEISMIC ATTACHMENTS COUNT: 17 29. ATTACHMENT KIT WEIGHT: 55.25 LBS PV-3 ARRAY PLAN ENGINEER OF RECORD DATE: 8.21.2023 DESIGN BY: V.D. CHECKED BY: D.A. AZ-3320 2007 S MAIN ST, SANTA ANA, CA 92707 PAPER SIZE: 36" x 24" (ARCH D) A B C D E F G H I J K L M N O 1 2 3 4 5 6 7 8 9 10 11 12 A B C D E F G H I J K L M N O CONTRACTOR E2SOL PHONE: LIC. NO.: UNAUTHORIZED USE OF THIS DRAWING SET WITHOUT WRITTEN PERMISSION FROM CONTRACTOR IS IN VIOLATION OF U.S. COPYRIGHT LAWS AND WILL BE SUBJECT TO CIVIL DAMAGES AND PROSECUTIONS. P P NO. DESCRIPTION DATE PROJECT REVISION / RELEASE SHEET NUMBER: SHEET TITLE: 401-489-2273 APN: 403-164-31 REPC-134 NEW PV SYSTEM: 39.150 kWp 1 REVISION 1 01.10.2024 N EW S 0 1/8" = 1'-0" ARRAY PLAN01 4' 8' BALLAST MOUNTED SOLAR MODULES BAY WITH MICROINVERTER (INVERTER WEIGHT: 12 LBS.) 1. FIELD VERIFY ALL MEASUREMENTS 2. SEE SHEET G-1 FOR LEGEND OF SYMBOLS 3. RELOCATE DRAIN PVC PIPES IF NEEDED. GAS LINES TO REMAIN GENERAL NOTES 48'-3" 89'-5" 60'-7" 75'-0" BAY WITH BALLASTS 4 3 19 5 6 7 8 D1 RACKING DETAIL (TRANSVERSE) NOT TO SCALE D3 DETAIL (TRANSVERSE) NOT TO SCALED2RACKING DETAIL (TOP) NOT TO SCALE 7 6 9 D4 DETAIL (TRANSVERSE) NOT TO SCALE D5 DETAIL (TRANSVERSE) NOT TO SCALE 24 25 24 MODULE CLIP W/BOLT MODULE CLIP PIN BOLT ATTACHMENT KIT BAY ASSEMBLY ROOF PAD U-ANCHOR D6 DETAIL (BAY WITH ATTACHEMENT) NOT TO SCALE 26 24 24 27 28 29 BAY WITH ATTACHMENTX 1 1 Signed 1/10/2024 2007 S Main St - 101117244 & 20181345 3/20/2024 MODULE STRINGING FIRE CLEARANCE MODULE: YOTTA YSM-B450-1 450 WATTS 40.87'' 82.44'' PV-2 ELECTRICAL ROOF PLAN ENGINEER OF RECORD DATE:8.21.2023 DESIGN BY:V.D. CHECKED BY:D.A. AZ-3320 2007 S MAIN ST, SANTA ANA, CA 92707 PAPER SIZE: 36" x 24" (ARCH D) A B C D E F G H I J K L M N O 1 2 3 4 5 6 7 8 9 10 11 12 A B C D E F G H I J K L M N O CONTRACTOR E2SOL PHONE: LIC. NO.: UNAUTHORIZED USE OF THIS DRAWING SET WITHOUT WRITTEN PERMISSION FROM CONTRACTOR IS IN VIOLATION OF U.S. COPYRIGHT LAWS AND WILL BE SUBJECT TO CIVIL DAMAGES AND PROSECUTIONS. P P NO. DESCRIPTION DATE PROJECT REVISION / RELEASE SHEET NUMBER: SHEET TITLE: 401-489-2273 APN: 403-164-31 REPC-134 NEW PV SYSTEM: 39.150 kWp EA 03/16" = 1'-0" ELECTRICAL ROOF PLAN012'-8" 5'-4" N EW S ARRAY 1 - 39.150 KW [x87] (N) MODULES FLAT ROOF TILT: 10 DEGREES AZIMUTH: 181 DEGREES 1. FIELD VERIFY ALL MEASUREMENTS 2. SEE SHEET G-1 FOR LEGEND OF SYMBOLS 3. FIELD VERIFY LOCATION OF EQUIPMENT AND PROVIDE WORKING CLEARANCE AS REQUIRED BY CODE. GENERAL NOTES (N) (1) AC COMBINER BOX (N) (1) AC DISCONNECT (N) (1) PV METER EXTERIOR PV EQUIPMENT (N) JUNCTION BOX А (E) (1) MAIN SERVICE SWITCHBOARD 4'-0" FIRE ACCESS PATH (ALL HATCHED AREA) А В ВС С D D E E Signed 1/10/2024 2007 S Main St - 101117244 & 20181345 3/20/2024 30A/3P CB1 (87) YOTTA YSM-B450-1 450 WATT (22) YOTTA DPI-208 240V MICROINVERTER 20 MODULES IN BRANCH A 3 (N) AC DISCONNECT 240 VAC, 200A, 3/P NEMA 3R, 42 KAIC G 5EQUIPMENT ABOVE LINE IS (N) NEW EQUIPMENT BELOW LINE IS (E) EXISTING UNLESS OTHERWISE NOTED. G L1 L2 L3 N (N) AC LOAD CENTER 200A, 120/240V, 3Ø NEMA 3R, 42 KAIC 1 BARE #6 CU 1 BARE #6 CU 1 BARE #6 CU 1 BARE #6 CU 1 BARE #6 CU 20 MODULES IN BRANCH В 20 MODULES IN BRANCH С 20 MODULES IN BRANCH D 7 MODULES IN BRANCH E 30A/3P CB2 30A/3P CB3 30A/3P CB4 30A/3P CB5 ROUTER GATEWAY 20A/2P СВ6 4 NOTE: RAPID SHUTDOWN INITIATION DEVICE (RSID) CONFORMING WITH 690.12. THE RAPID SHUTDOWN CAN ALSO BE INITIATED BY ONE OF THE FOLLOWING METHODS: · AC BREAKER IS TURNED OFF. · AC TO THE INVERTER IS DISCONNECTED BY ANOTHER METHOD (INTENTIONALLY OR AS RESULT OF A FAULT) · INVERTER ON/OFF SWITCH IS TURNED OFF. · ALL THE ABOVE SHUTS DOWN MICROINVERTERS OR TRANSMITTER WHENEVER SUNSPEC SIGNAL IS INTERRUPTED. VV(N) PV METER NEMA 3R, SCCR = 42 KA (N) JUNCTION BOX NEMA 3R 2 TO (E) GROUNDING ELECTRODE (Е) MAIN SERVICE SWITCHBOARD 120/240 V 3Ø, 4W MAIN BUSS: 600A (E) UTILITY METER TO UTILITY GRID 120/240V, 3Ø MAIN (E) 600A G N L2 L1 L3 PV SYSTEM EQUIPPED WITH RAPID SHUTDOWN DISCONNECT PER CEC 690.12 SYSTEM COMPLIANT WITH CEC 690.13 СВ7 2 TO (E) MDP A TO (E) MDP В TO (E) MDP С 150A/3P 705.13 PCS CONTROL SYSTEM. SYSTEM TO BE LIMITED TO 100A CONTINUOUS VIA INVERTER SETTINGS. SEE PV-7 FOR DETAILS. CONDUCTOR AND CONDUIT SCHEDULE W/ELECTRICAL CALCULATIONS ID CONDUCTOR RUN CONDUCTOR CONDUIT CURRENT-CARRYING CONDUCTORS IN CONDUIT OCPD EGC TEMP. CORR. FACTOR CONDUIT FILL FACTOR CONT. CURRENT MAX. CURRENT (125%) BASE AMP.DERATED AMP.TERM. TEMP. RATING AMP. @ TERMINAL LENGTH VOLTAGE VOLTAGE DROP, V VOLTAGE DROP, % 1 INVERTER TO JUNCTION BOX 10 AWG THWN-2 COPPER, Y3 BUS CABLE FREE AIR -N/A 6 AWG BARE, COPPER 0.96 (32.6 °C)1 24A 30A 40A 38.4A 75°C 25A 45 FT.240V 1.94V 0.81% 2 JUNCTION BOX TO AC LOAD CENTER 8 AWG THWN-2, COPPER 1'' DIA EMT 9 30A 10 AWG THWN-2, COPPER 0.96 (32.6 °C)0.8 24A 30A 55A 42.24A 75°C 50A 30 FT.240V 0.86V 0.36% 3 AC LOAD CENTER TO SMART METER 1/O AWG THWN-2, COPPER 1.5'' DIA EMT 3 N/A 6 AWG THWN-2, COPPER 0.96 (32.6 °C)1 105.6A 132A 170A 163.2A 75°C 150A 10 FT.240V 0.24V 0.10% 4 SMART METER TO AC DISCONNECT 1/O AWG THWN-2, COPPER 1.5'' DIA EMT 3 N/A 6 AWG THWN-2, COPPER 0.96 (32.6 °C)1 105.6A 132A 170A 163.2A 75°C 150A 10 FT.240V 0.24V 0.10% 5 AC DISCONNECT TO TAP 1/O AWG THWN-2, COPPER 1.5'' DIA EMT 3 150A 6 AWG THWN-2, COPPER 0.96 (32.6 °C)1 105.6A 132A 170A 163.2A 75°C 150A 10 FT.240V 0.24V 0.10% PV-4 THREE LINE DIAGRAM ENGINEER OF RECORD DATE: 8.21.2023 DESIGN BY: V.D. CHECKED BY: D.A. AZ-3320 2007 S MAIN ST, SANTA ANA, CA 92707 PAPER SIZE: 36" x 24" (ARCH D) A B C D E F G H I J K L M N O 1 2 3 4 5 6 7 8 9 10 11 12 A B C D E F G H I J K L M N O CONTRACTOR E2SOL PHONE: LIC. NO.: UNAUTHORIZED USE OF THIS DRAWING SET WITHOUT WRITTEN PERMISSION FROM CONTRACTOR IS IN VIOLATION OF U.S. COPYRIGHT LAWS AND WILL BE SUBJECT TO CIVIL DAMAGES AND PROSECUTIONS. P P NO. DESCRIPTION DATE PROJECT REVISION / RELEASE SHEET NUMBER: SHEET TITLE: 401-489-2273 APN: 403-164-31 REPC-134 NEW PV SYSTEM: 39.150 kWp Signed 1/10/2024 INSPECTOR: Please verify that Inverters are set to limit current as stated. 2007 S Main St - 101117244 & 20181345 3/20/2024 SYSTEM SUMMARY BRANCH А BRANCH В BRANCH С BRANCH D BRANCH E INVERTERS PER BRANCH 5 5 5 5 2 MAX AC CURRENT 24A 24A 24A 24A 9.6A MAX AC OUTPUT POWER 8,640W 8,640W 8,640W 8,640W 3,456W ARRAY STC POWER 39,150W ARRAY PTC POWER 37,114W MAX AC CURRENT 105.6A MAX AC POWER 38,016W DERATED (CEC) AC POWER 35,815W DISCONNECTS INVERTERS OCPDS MODULES ASHRAE EXTREME LOW 0.5°C (32.9°F), SOURCE: EL TORO MCAS (33.68°; -117.73°) ASHRAE 2% HIGH 32.6°C (90.7°F), SOURCE: EL TORO MCAS (33.68°; -117.73°) REF.QTY.RATED CURRENT MAX VOLTAGE CB1-5 5 30A 240VAC CB6 1 20A 240VAC CB7 1 150A 240VAC REF.QTY.MAKE AND MODEL RATED CURRENT MAX RATED VOLTAGE SW1 1 SQUARE D DU324RB OR EQUIV.200A 240VAC REF.QTY.MAKE AND MODEL PMAX PTC ISC IMP VOC VMP TEMP. COEFF. OF VOC FUSE RATING PM1-87 87 YOTTA YSM-B450-1 450W 426.6W 11.36A 10.72A 50.4V 42V -0.131V/°C (-0.26%/°C)25A REF.QTY.MAKE AND MODEL AC VOLTAGE GROUND OCPD RATING RATED POWER MAX OUTPUT CURRENT MAX INPUT CURRENT MAX INPUT VOLTAGE CEC WEIGHTED EFFICIENCY I1-22 22 YOTTA DPI-208 240V FLOATING 30A 1728W 4.8A 4x25A 60V 96.5% ELECTRICAL SHOCK HAZARD TERMINALS ON THE LINE AND LOAD SIDES MAY BE ENERGIZED IN THE OPEN POSITION WARNING LABEL 1 AT EACH DISCONNECTING MEANS FOR PHOTOVOLTAIC EQUIPMENT (2" X 4"). [СEC 690.13]. POWER SOURCE OUTPUT CONNECTION DO NOT RELOCATE THIS OVERCURRENT DEVICE WARNING LABEL 2 AT POINT OF INTERCONNECTION OVERCURRENT DEVICE (2" X 4"). [СEC 705.12(B)(3)(2)]. WARNING: PHOTOVOLTAIC POWER SOURCE LABEL 4 AT EXPOSED RACEWAYS, CABLE TRAYS, AND OTHER WIRING METHODS; SPACED AT MAXIMUM 10 FT SECTION OR WHERE SEPARATED BY ENCLOSURES, WALLS, PARTITIONS, CEILINGS, OR FLOORS (5 3/4" X 1 1/8"). [CEC 690.31(D)(2)]] LABEL 5 AT RAPID SHUTDOWN DISCONNECT SWITCH (5 1/4" X 2"). [СEC 690.56(C)(3)]. LABEL 9 AT EACH AC DISCONNECTING MEANS (4" X 1"). [СEC 690.13(B)]. SOLAR PV SYSTEM EQUIPPED WITH RAPID SHUTDOWN TURN RAPID SHUTDOWN SWITCH TO THE "OFF" POSITION TO SHUT DOWN PV SYSTEM AND REDUCE SHOCK HAZARD IN ARRAY LABEL 3 AT RAPID SHUTDOWN SYSTEM (3 3/4" X 5 1/4"). [СEC 690.56(C)(1)(A)]. INTERACTIVE PHOTOVOLTAIC SYSTEM CONNECTED PHOTOVOLTAIC SYSTEM DISCONNECT LOCATED EAST SIDE OF THE BUILDING PERMANENT PLAQUE OR DIRECTORY PROVIDING THE LOCATION OF THE SERVICE DISCONNECTING MEANS AND THE PHOTOVOLTAIC SYSTEM DISCONNECTING MEANS IF NOT IN THE SAME LOCATION (5 3/4" X 1 1/8"). [СEC 690.56(B)] WHERE THE PV SYSTEMS ARE REMOTELY LOCATED FROM EACH OTHER, A DIRECTORY IN ACCORDANCE WITH 705.10 SHALL BE PROVIDED AT EACH PV SYSTEM DISCONNECTING MEANS. PV SYSTEM EQUIPMENT AND DISCONNECTING MEANS SHALL NOT BE INSTALLED IN BATHROOMS [СEC 690.4(D),(E)] CAUTION MULTIPLE SOURCE OF POWER LABEL 6 AT UTILITY METER (5 3/4" X 1 1/8") [СEC 690.56(B)] WARNING DUAL POWER SUPPLY SOURCES: UTILITY GRID AND PV SOLAR ELECTRIC SYSTEM LABEL 7 AT POINT OF INTERCONNECTION (2 3/4" X 1 5/8"). [СEC 705.12(B)(3)] WARNING SOLAR ELECTRIC CIRCUIT BREAKER IS BACKFED LABEL 8 AT POINT OF INTERCONNECTION (2" X 1"). [СEC 705.12(B)(3)] SOLAR ELECTRIC PV PANELS DIRECTORY LABELING NOTES 1.1 LABELING REQUIREMENTS BASED ON THE 2022 CALIFORNIA ELECTRICAL CODE, CALIFORNIA FIRE CODE, OSHA STANDARD 1910.145, ANSI Z535 1.2 MATERIAL BASED ON THE REQUIREMENTS OF THE AUTHORITY HAVING JURISDICTION. 1.3 LABELS TO BE OF SUFFICIENT DURABILITY TO WITHSTAND THE ENVIRONMENT INVOLVED. 1.4 LABELS TO BE A MINIMUM LETTER HEIGHT OF 3/8” AND PERMANENTLY AFFIXED. 1.5 ALERTING WORDS TO BE COLOR CODED. “DANGER” WILL HAVE RED BACKGROUND; “WARNING” WILL HAVE ORANGE BACKGROUND; “CAUTION” WILL HAVE YELLOW BACKGROUND. [ANSI Z535] 1.6 ALL SIGNAGE MUST BE PERMANENTLY ATTACHED AND BE WEATHER RESISTANT/SUNLIGHT RESISTANT AND CANNOT BE HAND-WRITTEN PER СEC 110.21(B) RAPID SHUTDOWN SWITCH FOR SOLAR PV SYSTEM AMPS VOLTS LABEL 10 AT POINT OF INTERCONNECTION, MARKED AT DISCONNECTING MEANS (4" X 2"). [СEC 690.54] AC DISCONNECT PHOTOVOLTAIC SYSTEM POWER SOURCE RATED AC OUTPUT CURRENT NOMINAL OPERATING AC VOLTAGE AMPS VOLTS 105.6 240 RACEWAY IS ENERGIZED WHEN DISCONNECT IS IN THE OPEN POSITION. DO NOT RELOCATE OR CUT WARNING LABEL 11 AT EACH DISCONNECTING MEANS FOR PHOTOVOLTAIC EQUIPMENT (2" X 4"). [СEC 690.13]. PHOTOVOLTAIC SYSTEM DISCONNECT BILL OF MATERIALS CATEGORY MAKE MODEL NUMBER REF QTY UNIT QTY/UNIT DESCRIPTION MODULE YOTTA YSM-B450-1 PM1-87 87 PIECES 1 YOTTA YSM-B450-1 450W 0 INVERTER YOTTA DPI-208 I1-22 22 PIECES 1 YOTTA DPI-208 1728W INVERTER DISCONNECT SQUARE D DU324RB SW1 1 PIECE 1 SQUARE D DU324RB, NONFUSED, 3-POLE, 200A, 240VAC OR EQUIVALENT PRODUCTION METER GENERIC MANUFACTURER GEN-METER-200A M1 1 PIECE 1 ELECTRICAL METER, OWNER APPROVED AC COMBINER PANEL GEN-AC-PANEL EP1 1 PIECE 1 AC LOAD CENTER, 200A, 120/240V, 3Ø WIRING GEN-10-AWG-THWN-2-CU-Y3-BUS-CABLE WR1 990 FEET 1 10 AWG THWN-2 COPPER, Y3 BUS CABLE (LINE 1,2,3) WIRING GEN-6-AWG-BARE-CU-GR WR1 990 FEET 1 6 AWG BARE COPPER, GREEN (GROUND) WIRING GEN-10-AWG-THWN-2-CU-GR WR2 60 FEET 1 10 AWG THWN-2, COPPER, GREEN (GROUND) WIRING GEN-8-AWG-THWN-2-CU-RD WR2 240 FEET 1 8 AWG THWN-2, COPPER, RED (LINE 1) WIRING GEN-8-AWG-THWN-2-CU-BLK WR2 240 FEET 1 8 AWG THWN-2, COPPER, BLACK (LINE 2) WIRING GEN-8-AWG-THWN-2-CU-BLU WR2 240 FEET 1 8 AWG THWN-2, COPPER, BLUE (LINE 3) WIRING GEN-6-AWG-THWN-2-CU-GR WR3-5 30 FEET 1 6 AWG THWN-2, COPPER, GREEN (GROUND) WIRING GEN-1/0-AWG-THWN-2-CU-RD WR3-5 30 FEET 1 1/0 AWG THWN-2, COPPER, RED (LINE 1) WIRING GEN-1/0-AWG-THWN-2-CU-BLK WR3-5 30 FEET 1 1/0 AWG THWN-2, COPPER, BLACK (LINE 2) WIRING GEN-1/0-AWG-THWN-2-CU-BLU WR3-5 30 FEET 1 1/0 AWG THWN-2, COPPER, BLUE (LINE 3) WIREWAY GEN-EMT-1'' DIA WW2 60 FEET 1 EMT CONDUIT, 1'' DIA WIREWAY GEN-EMT-1.5'' DIA WW3-5 30 FEET 1 EMT CONDUIT, 1.5'' DIA OCPD GENERIC MANUFACTURER GEN-CB-30A-240VAC CB1-5 5 PIECES 1 CIRCUIT BREAKER, 30A, 240VAC OCPD GENERIC MANUFACTURER GEN-CB-20A-240VAC CB6 1 PIECE 1 CIRCUIT BREAKER, 20A, 240VAC OCPD GENERIC MANUFACTURER GEN-CB-150A-240VAC CB7 1 PIECE 1 CIRCUIT BREAKER, 150A, 240VAC TRANSITION BOX GENERIC MANUFACTURER GEN-AWB-TB-4-4X JB1-2 2 PIECE 1 TRANSITION/PASS-THROUGH BOX, WITH 4 TERMINAL BLOCKS PV-5 PLACARDS ENGINEER OF RECORD DATE:8.21.2023 DESIGN BY:V.D. CHECKED BY:D.A. AZ-3320 2007 S MAIN ST, SANTA ANA, CA 92707 PAPER SIZE: 36" x 24" (ARCH D) A B C D E F G H I J K L M N O 1 2 3 4 5 6 7 8 9 10 11 12 A B C D E F G H I J K L M N O CONTRACTOR E2SOL PHONE: LIC. NO.: UNAUTHORIZED USE OF THIS DRAWING SET WITHOUT WRITTEN PERMISSION FROM CONTRACTOR IS IN VIOLATION OF U.S. COPYRIGHT LAWS AND WILL BE SUBJECT TO CIVIL DAMAGES AND PROSECUTIONS. P P NO. DESCRIPTION DATE PROJECT REVISION / RELEASE SHEET NUMBER: SHEET TITLE: 401-489-2273 APN: 403-164-31 REPC-134 NEW PV SYSTEM: 39.150 kWp MAIN DISTRIBUTION UTILITY DISCONNECT FRONT BACK N EW S !CAUTION! MULTIPLE SOURCES OF POWER SAFETY DISCONNECTS AS SHOWN: AC DISCONNECT PV ARRAY Signed 1/10/2024 2007 S Main St - 101117244 & 20181345 3/20/2024 PV-6 RESOURCE DOCUMENTS ENGINEER OF RECORD DATE:8.21.2023 DESIGN BY:V.D. CHECKED BY:D.A. AZ-3320 2007 S MAIN ST, SANTA ANA, CA 92707 PAPER SIZE: 36" x 24" (ARCH D) A B C D E F G H I J K L M N O 1 2 3 4 5 6 7 8 9 10 11 12 A B C D E F G H I J K L M N O CONTRACTOR E2SOL PHONE: LIC. NO.: UNAUTHORIZED USE OF THIS DRAWING SET WITHOUT WRITTEN PERMISSION FROM CONTRACTOR IS IN VIOLATION OF U.S. COPYRIGHT LAWS AND WILL BE SUBJECT TO CIVIL DAMAGES AND PROSECUTIONS. P P NO. DESCRIPTION DATE PROJECT REVISION / RELEASE SHEET NUMBER: SHEET TITLE: 401-489-2273 APN: 403-164-31 REPC-134 NEW PV SYSTEM: 39.150 kWp 2007 S Main St - 101117244 & 20181345 3/20/2024 PV-7 RESOURCE DOCUMENTS ENGINEER OF RECORD DATE:8.21.2023 DESIGN BY:V.D. CHECKED BY:D.A. AZ-3320 2007 S MAIN ST, SANTA ANA, CA 92707 PAPER SIZE: 36" x 24" (ARCH D) A B C D E F G H I J K L M N O 1 2 3 4 5 6 7 8 9 10 11 12 A B C D E F G H I J K L M N O CONTRACTOR E2SOL PHONE: LIC. NO.: UNAUTHORIZED USE OF THIS DRAWING SET WITHOUT WRITTEN PERMISSION FROM CONTRACTOR IS IN VIOLATION OF U.S. COPYRIGHT LAWS AND WILL BE SUBJECT TO CIVIL DAMAGES AND PROSECUTIONS. P P NO. DESCRIPTION DATE PROJECT REVISION / RELEASE SHEET NUMBER: SHEET TITLE: 401-489-2273 APN: 403-164-31 REPC-134 NEW PV SYSTEM: 39.150 kWp 2007 S Main St - 101117244 & 20181345 3/20/2024 2007 S Main St - 101117244 & 20181345 3/20/2024 2007 S Main St - 101117244 & 20181345 3/20/2024 2007 S Main St - 101117244 & 20181345 3/20/2024 2007 S Main St - 101117244 & 20181345 3/20/2024 2007 S Main St - 101117244 & 20181345 3/20/2024 2007 S Main St - 101117244 & 20181345 3/20/2024 2007 S Main St - 101117244 & 20181345 3/20/2024 2007 S Main St - 101117244 & 20181345 3/20/2024 2007 S Main St - 101117244 & 20181345 3/20/2024 2007 S Main St - 101117244 & 20181345 3/20/2024 2007 S Main St - 101117244 & 20181345 3/20/2024 2007 S Main St - 101117244 & 20181345 3/20/2024 2007 S Main St - 101117244 & 20181345 3/20/2024 2007 S Main St - 101117244 & 20181345 3/20/2024 2007 S Main St - 101117244 & 20181345 3/20/2024 2007 S Main St - 101117244 & 20181345 3/20/2024 2007 S Main St - 101117244 & 20181345 3/20/2024 2007 S Main St - 101117244 & 20181345 3/20/2024 2007 S Main St - 101117244 & 20181345 3/20/2024 2007 S Main St - 101117244 & 20181345 3/20/2024 2007 S Main St - 101117244 & 20181345 3/20/2024 2007 S Main St - 101117244 & 20181345 3/20/2024 2007 S Main St - 101117244 & 20181345 3/20/2024 2007 S Main St - 101117244 & 20181345 3/20/2024 2007 S Main St - 101117244 & 20181345 3/20/2024 2007 S Main St - 101117244 & 20181345 3/20/2024 2007 S Main St - 101117244 & 20181345 3/20/2024