Loading...
HomeMy WebLinkAbout2026 N Olive St - PlanACD INV MSP UM INVCB 140'-2" 70 ' - 1 1 " 70 ' - 1 1 " 140'-2" 39 ' - 1 0 " 19'-3" 38'-1" 3'-0" 1 PROJECT DESCRIPTION: PLOT PLAN & VICINITY MAP SCALE: 1/16" = 1'PV-1 SCALE: NTS PV-1 PLOT PLAN & VICINITY MAP 52X355 LONGI SOLAR:LR4-60HPB 355M 355W MODULE ROOF MOUNTED SOLAR PHOTOVOLTAIC MODULES SYSTEM SIZE: 18.46KW DC STC,7.60 kW AC CEC REV SHEET NAME SHEET SIZE SHEET NUMBER ANSI B 11" X 17" DATE DESCRIPTION REVISIONS Signature with Seal PROJECT NAME & ADDRESS PV-1 PROJECT ID DA N I E L S C H E I N B E R G 20 2 6 N O L I V E S T , SA N T A A N A , C A 9 2 7 0 6 , U S A FRESH10/26/2022 ORIGINAL PLAN 2065 W OBISPO AVE #102 GILBERT, AZ 85233 USA 866-572-2637 LIC # CA-1019100 ABHISHEK MAHESH ROOF ACCESS POINT ROOF ACCESS POINT SHALL NOT BE LOCATED IN AREAS THAT DO NOT REQUIRE THE PLACEMENT OF GROUND LADDERS OVER OPENINGS SUCH AS WINDOWS OR DOORS, AND LOCATED AT STRONG POINTS OF BUILDING CONSTRUCTION IN LOCATIONS WHERE THE ACCESS POINT DOES NOT CONFLICT WITH OVERHEAD OBSTRUCTIONS SUCH AS TREE LIMBS, WIRES OR SIGNS. ARRAY LOCATIONS VICINITY MAP SCALE: NTSPV-1 2 HOUSE PHOTO EQUIPMENT SUMMARY 52 - LONGI SOLAR:LR4-60HPB 355M 355W MODULES 02 - SOLAREDGE TECHNOLOGY:SE7600H-US (240V) INVERTER 52 - SOLAREDGE POWER OPTIMIZERS S-440 PROJECT SITE SHEET INDEX PV-1 PLOT PLAN & VICINITY MAP PV-2 ROOF PLAN & MODULES PV-3 STRING LAYOUT PV-4 ATTACHMENT DETAIL PV-5 ELECTRICAL LINE DIAGRAM PV-6 WIRING CALCULATIONS PV-7 PLACARDS PV-8 OPTIMIZER CHART PV-9 EQUIPMENT ELEVATION PV-10-17 EQUIPMENT SPECIFICATIONS PV-18 PROPOSED EQUIPMENT PLACEMENTS 3 PAGE 1 OF 18 NOTES 1. NOTIFY SERVING UTILITY BEFORE ACTIVATION OF PV SYSTEM. 2. MANUFACTURERS PRODUCT INSTALLATION INSTRUCTIONS SHALL BE AVAILABLE AT THE TIME OF INSPECTION. 3. ALL SUBMITTALS WILL COMPLY WITH 2019 CEC, CBC, AND CFC. 4. SMOKE ALARMS AND CARBON MONOXIDE DETECTOR EQUIPMENT SHALL BE IN PLACE AT RESIDENCE ACCORDING TO THE CRC, CBC R314-315 REQUIREMENT. AHJ - SANTA ANA UTILITY - SCE ACCOUNT # - CA-R-195106 GOVERNING CODES THIS PROJECT SHALL COMPLY WITH THE FOLLOWING CODE 2019 CALIFORNIA ELECTRICAL CODE 2019 CALIFORNIA RESIDENTIAL CODE 2019 CALIFORNIA BUILDING CODE 2019 CALIFORNIA FIRE CODE 2019 CALIFORNIA GREEN BUILDING STANDARDS CODE 2019 CALIFORNIA ENERGY CODE 2019 CALIFORNIA PLUMBING CODE 2020 NATIONAL ELECTRICAL CODE ALL OTHER ORDINANCES ADOPTED BY THE LOCAL GOVERNING AGENCIES. 1-STORY HOUSE EXISTING DRIVEWAY ROOF #01 (03) LONGI SOLAR LR4-60HPB 355M 355W MODULES ROOF ACCESS POINT N O L I V E S T PR O P E R T Y L I N E PROPERTY LINE (E) POOL ROOF #03 (02) LONGI SOLAR LR4-60HPB 355M 355W MODULES ROOF #04 (20) LONGI SOLAR LR4-60HPB 355M 355W MODULES (E) GATE (E) FENCE PROPERTY LINE PR O P E R T Y L I N E (N) MAIN SERVICE PANEL, 200A RATED, 240V,SOLAR READY (SURFACE MOUNT) (E) UTILITY METER (N) AC DISCONNECT (N) SOLAREDGE TECHNOLOGY : SE7600H-US INVERTER-2 INTEGRATED RAPID SHUTDOWN (N) SOLAREDGE TECHNOLOGY : SE7600H-US INVERTER-1 INTEGRATED RAPID SHUTDOWN (N) COMBINER BOX ROOF #02 (06) LONGI SOLAR LR4-60HPB 355M 355W MODULES ROOF #05 (21) LONGI SOLAR LR4-60HPB 355M 355W MODULES Structural Only Signed 11/10/2022 Bldg permit #101113264 Elect permit #20178298- Approved by M. Smith on 3/7/23 Issued on 3/10/23 ***The scope of the plans is for the installation of the solar photovoltaic system only and the approval is subject to compliance with all applicable city and state codes and regulations regarding construction. The approval of the plans does not constitute any certification of the accuracy, completeness, or building permit status of the existing buildings and structures as shown.*** 2026 N Olive St - 2017829803/10/23 REV SHEET NAME SHEET SIZE SHEET NUMBER ANSI B 11" X 17" DATE DESCRIPTION REVISIONS Signature with Seal PROJECT NAME & ADDRESS PV-5 PROJECT ID DA N I E L S C H E I N B E R G 20 2 6 N O L I V E S T , SA N T A A N A , C A 9 2 7 0 6 , U S A FRESH10/26/2022 ORIGINAL PLAN 2065 W OBISPO AVE #102 GILBERT, AZ 85233 USA 866-572-2637 LIC # CA-1019100 ABHISHEK MAHESH A12/30/2022 REV ELECTRICAL LINE DIAGRAM MAIN SERVICE VOLTAGE: MAIN PANEL BRAND: MAIN SERVICE PANEL: MAIN BREAKER RATING: MAIN SERVICE LOCATION: SERVICE FEED SOURCE: 240V 200 A (NEW) NORTH 200 A (NEW) PAGE 5 OF 18 SERVICE INFO UTILITY PROVIDER: SCE OVERHEAD (SIEMENS MC4040S1200SC) SCALE: NTSPV-5 1 ELECTRICAL THREE LINE DIAGRAM Tag # THWN-2 - Ground Conduit Conductor Schedule (ALL CONDUCTORS MUST BE COPPER) THWN-2 1 1 2 2 3 Bare Copper Ground (EGC/GEC) THWN-2 PV WIRE 10 AWG 8 AWG THWN-2 - Ground Description Wire Gauge # of Conductors/Color 10 AWG 6 AWG 8 AWG 8 AWG 4 (2V+, 2V-) 1 BARE 4 (2V+, 2V-) B/R 1 (GRN) 3 (1L1, 1L2, 1N) B/R/W 1 (GRN) Conduit Type Conduit Size EMT 3/4" 3/4" 3/4" 3/4" EMT EMT EMT INSIDE EMT-ON ROOF INSIDE EMT-ON ROOF 3/4" 3/4" 1A 1A 2A 2A 3A THWN-2 - Ground THWN-2 Bare Copper Ground (EGC/GEC) THWN-2 PV WIRE 10 AWG 8 AWG 10 AWG 6 AWG 8 AWG 4 (2V+, 2V-) 1 BARE 4 (2V+, 2V-) B/R 1 (GRN) 3 (1L1, 1L2, 1N) B/R/W EMT 3/4" 3/4" 3/4" EMT EMT INSIDE EMT-ON ROOF INSIDE EMT-ON ROOF 3/4" 3/4" 3 3A THWN-2 - Ground 8 AWG 1 (GRN) 3/4"EMT THWN-2 3 AWG 3 (1L1, 1L2, 1N) B/R/W EMT THWN-2 - Ground 6 AWG 1 (GRN) EMT L1 L2 N G = AC DC JUNCTION BOX-2 600 V, NEMA 3 UL LISTED - + - + + - + + + +- - - 2 - + - 1 3 = = = = = = = = = = 2A 1A - + - + + - + + + +- - - 2 - + - 1 3 = = = = = = = = = = SolarEdge Power Optimizer S S-440 Rated DC Input Power - S-440 watts Maximum Input Voltage - 60 Vdc MPPT Range - 8 to 60 Vdc Maximum Input Current - 14.50 Adc Maximum Output Current - 15 Adc String Limitations - 8 to 25 Optimizers, 5700 watts STC per string maximum LONGI SOLAR LR4-60HPB 355M 355W MODULES G N 3A (N) 125A COMBINER PANEL 120/240V 40A 40A L1 L2 N G = ACDC JUNCTION BOX-1 600 V, NEMA 3 UL LISTED - + - + + - + + + + - - - 2 - + - 1 3 = = = = = = = = = = 2 1 - + - + + - + + + +- - - 2 - + - 1 3 = = = = = = = = = = 12 13 3 1-1/4" 4 L1 L2 L1 L2 N G N G 4 SYSTEM SIZE: TOTAL DC SYSTEM SIZE: 18.46 kW DC TOTAL AC SYSTEM SIZE: 15.20 kW AC (52) LONGI SOLAR LR4-60HPB 355M 355W MODULES (4) STRINGS OF 13 MODULES CONNECTED IN SERIES. 4 4 SOLAREDGE TECHNOLOGY: SE7600H-US INVERTER-2 OUTPUT: 240 VAC, 32A 99% CEC WEIGHTED EFFICIENCY NEMA 3R, UL LISTED, INTERNAL GFDI WITH INTEGRATED DC DISCONNECT & INTEGRATED RAPID SHUTDOWN SOLAREDGE TECHNOLOGY: SE7600H-US INVERTER-1 OUTPUT: 240 VAC, 32A 99% CEC WEIGHTED EFFICIENCY NEMA 3R, UL LISTED, INTERNAL GFDI WITH INTEGRATED DC DISCONNECT & INTEGRATED RAPID SHUTDOWN GROUNDING ELECTRODE SYSTEM GEC G N NL2L1 M TO UTILITY GRID 80A (N) 80A PV BREAKER IN SOLAR READY SLOT (N) MAIN BREAKER TO HOUSE 240V, 200A/2P, (TOP FED) 200A 1-1/4" (N) MAIN SERVICE PANEL, 200A RATED, 240V (SOLAR READY) (SIEMENS MC4040S1200SC) BI-DIRECTIONAL UTILITY METER 1-PHASE, 3-W, 120V/240V UTILITY PROVIDER :- SCE UTILITY METER # :- 222013-614152 AC DISCONNECT EATON#DG223URB 100A, 2P,240VAC NEMA 3R 12 13 12 13 12 13 · APPROVED MAIN SERVICE PANEL TO BE INSTALLED AT SITE Exp. Date: 09/30/24 2/3/23 2026 N Olive St - 2017829803/10/23 REV SHEET NAME SHEET SIZE SHEET NUMBER ANSI B 11" X 17" DATEDESCRIPTION REVISIONS Signature with Seal PROJECT NAME & ADDRESS PV-7 PROJECT ID DA N I E L S C H E I N B E R G 20 2 6 N O L I V E S T , SA N T A A N A , C A 9 2 7 0 6 , U S A FRESH10/26/2022ORIGINAL PLAN 2065 W OBISPO AVE #102 GILBERT, AZ 85233 USA 866-572-2637 LIC # CA-1019100 ABHISHEK MAHESH PLACARDS NOTES AND SPECIFICATIONS: SIGNS AND LABELS SHALL MEET THE REQUIREMENTS OF THE NEC 2017 ARTICLE 110.21(B), UNLESS SPECIFIC INSTRUCTIONS ARE REQUIRED BY SECTION 690, OR IF REQUESTED BY THE LOCAL AHJ. SIGNS AND LABELS SHALL ADEQUATELY WARN OF HAZARDS USING EFFECTIVE WORDS, COLORS AND SYMBOLS. LABELS SHALL BE PERMANENTLY AFFIXED TO THE EQUIPMENT OR WIRING METHOD AND SHALL NOT BE HAND WRITTEN. LABEL SHALL BE OF SUFFICIENT DURABILITY TO WITHSTAND THE ENVIRONMENT INVOLVED. SIGNS AND LABELS SHALL COMPLY WITH ANSI Z535.4-2011, PRODUCT SAFETY SIGNS AND LABELS, UNLESS OTHERWISE SPECIFIED. DO NOT COVER EXISTING MANUFACTURER LABELS. REV SHEET NAME SHEET SIZE SHEET NUMBER ANSI B 11" X 17" DATE DESCRIPTION REVISIONS Signature with Seal PROJECT NAME & ADDRESS PV-7 PROJECT ID DA N I E L S C H E I N B E R G 20 2 6 N O L I V E S T , SA N T A A N A , C A 9 2 7 0 6 , U S A FRESH10/26/2022 ORIGINAL PLAN 2065 W OBISPO AVE #102 GILBERT, AZ 85233 USA 866-572-2637 LIC # CA-1019100 ABHISHEK MAHESH SOURCES: UTILITY GRID AND PV SOLAR ELECTRIC SYSTEM DUAL POWER SUPPLY LABEL LOCATION: UTILITY SERVICE METER AND MAIN SERVICE PANEL. PER CODE(S): CEC 2019: 705.12(D)(3), NEC 2017: 705.12(D)(3), NEC 2011: 705.12(D)(4) DO NOT ADD LOADS PHOTOVOLTAIC SYSTEM COMBINER PANEL LABEL LOCATION: PHOTOVOLTAIC AC COMBINER (IF APPLICABLE). PER CODE(S): CEC 2019: 705.12(D)(2)(3)(c), NEC 2017: 705.12(D)(2)(3)(c), NEC 2011: 705.12(D)(4) LABEL LOCATION: INTERIOR AND EXTERIOR DC CONDUIT EVERY 1O FT, AT EACH TURN, ABOVE AND BELOW PENETRATIONS, ON EVERY JB/PULL BOX CONTAINING DC CIRCUITS. PER CODE(S): CEC 2019: 690.31(G)(3), 690.31(G)(4), NEC 2017: 690.31(G)(3), 690.31(G)(4), NEC 2011: 690.31(E)(3), 690.31(E)(4), IFC 2012: 605.11.1.4 ELECTRICAL SHOCK HAZARD LABEL LOCATION: INVERTER(S), ENPHASE ENVOY ENCLOSURE (IF APPLICABLE). PER CODE(S): CEC 2019: 690.5(C), NEC 2017: 690.5(C), NEC 2011: 690.5(C) PHOTOVOLTAIC AC DISCONNECT LABEL LOCATION: AC DISCONNECT(S), PHOTOVOLTAIC SYSTEM POINT OF INTERCONNECTION. PER CODE(S): CEC 2019: 690.54, NEC 2017: 690.54, NEC 2011: 690.54 THE DC CONDUCTORS OF THIS PHOTOVOLTAIC SYSTEM ARE UNGROUNDED AND MAY BE ENERGIZED ELECTRICAL SHOCK HAZARD WARNING ! LABEL LOCATION: INVERTER(S), DC DISCONNECTS. PER CODE(S): CEC 2019: 690.35(F), NEC 2017: 690.35(F), NEC 2011: 690.35(F) ELECTRICAL SHOCK HAZARD WARNING! LABEL LOCATION: INVERTER(S), AC DISCONNECT(S), AC COMBINER PANEL (IF APPLICABLE). PER CODE(S): CEC 2019: 690.17(E), NEC 2017: 690.17(E), NEC 2011: 690.17(4) WARNING! WARNING! WARNING! TURN RAPID SHUTDOWN SWITCH TO THE "OFF" POSITION TO SHUT DOWN PV SYSTEM AND REDUCE SHOCK HAZARD IN THE ARRAY SOLAR PV SYSTEM EQUIPPED WITH RAPID SHUTDOWN SOLAR ELECTRIC PV PANELS LABEL LOCATION: AC DISCONNECT, POINT OF INTERCONNECTION (PER CODE: NEC 690.56(C)(1)(a), IFC 605.11.3.1(1) LABEL LOCATION: INVERTER(S), DC DISCONNECT(S). PER CODE(S): CEC 2019: 690.53, NEC 2017: 690.53, NEC 2011: 690.53 INVERTER #1 SOLAREDGE MAXIMUM VOLTAGE MAXIMUM CIRCUIT CURRENT MAX. RATED OUTPUT CURRENT OF THE CHARGE CONTROLLER OR DC-TO-DC- CONVERTER (IF INSTALLED) 480VDC 30.0ADC 23.08ADC PAGE 7 OF 18 DO NOT RELOCATE THIS OVERCURRENT DEVICE LABEL LOCATION: ADJACENT TO PV BREAKER (IF APPLICABLE). PER CODE(S): CEC 2019: 705.12(B)(2)(3)(b), NEC 2017: 705.12(B)(2)(3)(b), NEC 2011: 705.12(D)(7) WARNING ! CAUTION: POWER TO THIS BUILDING IS ALSO SUPPLIED FROM THE FOLLOWING SOURCES WITH DISCONNECTS LOCATED AS SHOWN UTILITY METER & MAIN SERVICE PANEL AC DISCONNECT INVERTER (N) INVERTER-1 (N) AC DSCONNECT (E) UTILITY METER (N) MAIN SERVICE PANEL, SOLAR READY (SURFACE MOUNT) (N) INVERTER-2 (N) COMBINER BOX 20 2 6 N O L I V E S T LABEL LOCATION: INVERTER(S), DC DISCONNECT(S). PER CODE(S): CEC 2019: 690.53, NEC 2017: 690.53, NEC 2011: 690.53 INVERTER #2 SOLAREDGE MAXIMUM VOLTAGE MAXIMUM CIRCUIT CURRENT MAX. RATED OUTPUT CURRENT OF THE CHARGE CONTROLLER OR DC-TO-DC- CONVERTER (IF INSTALLED) 480VDC 30.0ADC 23.08ADC NOTICE PV SYSTEM COMBINER PANEL DO NOT ADD LOADS TO THIS PANEL signed 11/9/2022 2026 N Olive St - 2017829803/10/23 REV SHEET NAME SHEET SIZE SHEET NUMBER ANSI B 11" X 17" DATE DESCRIPTION REVISIONS Signature with Seal PROJECT NAME & ADDRESS PV-18 PROJECT ID DA N I E L S C H E I N B E R G 20 2 6 N O L I V E S T , SA N T A A N A , C A 9 2 7 0 6 , U S A FRESH10/26/2022 ORIGINAL PLAN 2065 W OBISPO AVE #102 GILBERT, AZ 85233 USA 866-572-2637 LIC # CA-1019100 ABHISHEK MAHESH PAGE 18 OF 18 PROPOSED EQUIPMENT PLACEMENTS NOTE:- GAS AND WATER LINE 2026 N Olive St - 2017829803/10/23 Certificate Of Completion Envelope Id: DAB538C6C31F4430B680CF31A7F70EBE Status: Completed Subject: Complete with DocuSign: Santa Ana Letter of Authorization Source Envelope: Document Pages: 1 Signatures: 1 Envelope Originator: Certificate Pages: 5 Initials: 0 NERD Power AutoNav: Enabled EnvelopeId Stamping: Enabled Time Zone: (UTC-08:00) Pacific Time (US & Canada) 13614 Carolina Hill Court Draper, UT 84020 info@gonerdpower.com IP Address: 184.191.133.199 Record Tracking Status: Original 12/16/2022 12:56:31 PM Holder: NERD Power info@gonerdpower.com Location: DocuSign Signer Events Signature Timestamp Daniel Scheinberg Danielscheinberg@gmail.com Security Level: Email, Account Authentication (None) Signature Adoption: Drawn on Device Using IP Address: 104.58.250.107 Signed using mobile Sent: 12/16/2022 12:59:16 PM Viewed: 12/16/2022 1:16:06 PM Signed: 12/16/2022 1:17:04 PM Electronic Record and Signature Disclosure: Accepted: 9/21/2022 3:51:19 PM ID: d9fdb813-f174-4089-93c7-c321cdff8d6e In Person Signer Events Signature Timestamp Editor Delivery Events Status Timestamp Agent Delivery Events Status Timestamp Intermediary Delivery Events Status Timestamp Certified Delivery Events Status Timestamp Carbon Copy Events Status Timestamp NERD Power caprocessing@nerdpower.energy Security Level: Email, Account Authentication (None) Sent: 12/16/2022 1:17:06 PM Viewed: 12/16/2022 1:17:26 PM Electronic Record and Signature Disclosure: Accepted: 7/28/2022 12:48:28 PM ID: 8b726499-6bac-4ee7-a42c-673efa97b5b8 Witness Events Signature Timestamp Notary Events Signature Timestamp Envelope Summary Events Status Timestamps Envelope Sent Hashed/Encrypted 12/16/2022 12:59:16 PM Certified Delivered Security Checked 12/16/2022 1:16:06 PM Signing Complete Security Checked 12/16/2022 1:17:04 PM Completed Security Checked 12/16/2022 1:17:06 PM 2026 N Olive St - 2017829803/10/23 Payment Events Status Timestamps Electronic Record and Signature Disclosure 2026 N Olive St - 2017829803/10/23 ELECTRONIC RECORD AND SIGNATURE DISCLOSURE From time to time, Nerd Power LLC (we, us or Company) may be required by law to provide to you certain written notices or disclosures. Described below are the terms and conditions for providing to you such notices and disclosures electronically through the DocuSign, Inc. (DocuSign) electronic signing system. Please read the information below carefully and thoroughly, and if you can access this information electronically to your satisfaction and agree to these terms and conditions, please confirm your agreement by clicking the ‘I agree’ button at the bottom of this document. Getting paper copies At any time, you may request from us a paper copy of any record provided or made available electronically to you by us. You will have the ability to download and print documents we send to you through the DocuSign system during and immediately after signing session and, if you elect to create a DocuSign signer account, you may access them for a limited period of time (usually 30 days) after such documents are first sent to you. After such time, if you wish for us to send you paper copies of any such documents from our office to you, you will be charged a $0.00 per-page fee. You may request delivery of such paper copies from us by following the procedure described below. Withdrawing your consent If you decide to receive notices and disclosures from us electronically, you may at any time change your mind and tell us that thereafter you want to receive required notices and disclosures only in paper format. How you must inform us of your decision to receive future notices and disclosure in paper format and withdraw your consent to receive notices and disclosures electronically is described below. Consequences of changing your mind If you elect to receive required notices and disclosures only in paper format, it will slow the speed at which we can complete certain steps in transactions with you and delivering services to you because we will need first to send the required notices or disclosures to you in paper format, and then wait until we receive back from you your acknowledgment of your receipt of such paper notices or disclosures. To indicate to us that you are changing your mind, you must withdraw your consent using the DocuSign ‘Withdraw Consent’ form on the signing page of a DocuSign envelope instead of signing it. This will indicate to us that you have withdrawn your consent to receive required notices and disclosures electronically from us and you will no longer be able to use the DocuSign system to receive required notices and consents electronically from us or to sign electronically documents from us. All notices and disclosures will be sent to you electronically Unless you tell us otherwise in accordance with the procedures described herein, we will provide electronically to you through the DocuSign system all required notices, disclosures, authorizations, acknowledgements, and other documents that are required to be provided or made available to you during the course of our relationship with you. To reduce the chance of you inadvertently not receiving any notice or disclosure, we prefer to provide all of the required notices and disclosures to you by the same method and to the same address that you have given us. Thus, you can receive all the disclosures and notices electronically or in paper format through the paper mail delivery system. If you do not agree with this process, please let us know as described below. Please also see the paragraph immediately above that describes the consequences of your electing not to receive delivery of the notices and disclosures Electronic Record and Signature Disclosure created on: 6/23/2017 2:07:56 PM Parties agreed to: Daniel Scheinberg, NERD Power 2026 N Olive St - 2017829803/10/23 electronically from us. How to contact Nerd Power LLC: You may contact us to let us know of your changes as to how we may contact you electronically, to request paper copies of certain information from us, and to withdraw your prior consent to receive notices and disclosures electronically as follows: To contact us by email send messages to: info@gonerdpower.com To advise Nerd Power LLC of your new e-mail address To let us know of a change in your e-mail address where we should send notices and disclosures electronically to you, you must send an email message to us at info@gonerdpower.com and in the body of such request you must state: your previous e-mail address, your new e-mail address. We do not require any other information from you to change your email address.. In addition, you must notify DocuSign, Inc. to arrange for your new email address to be reflected in your DocuSign account by following the process for changing e-mail in the DocuSign system. To request paper copies from Nerd Power LLC To request delivery from us of paper copies of the notices and disclosures previously provided by us to you electronically, you must send us an e-mail to info@gonerdpower.com and in the body of such request you must state your e-mail address, full name, US Postal address, and telephone number. We will bill you for any fees at that time, if any. To withdraw your consent with Nerd Power LLC To inform us that you no longer want to receive future notices and disclosures in electronic format you may: i. decline to sign a document from within your DocuSign session, and on the subsequent page, select the check-box indicating you wish to withdraw your consent, or you may; ii. send us an e-mail to info@gonerdpower.com and in the body of such request you must state your e-mail, full name, US Postal Address, and telephone number. We do not need any other information from you to withdraw consent.. The consequences of your withdrawing consent for online documents will be that transactions may take a longer time to process.. Required hardware and software Operating Systems:Windows® 2000, Windows® XP, Windows Vista®; Mac OS® X Browsers:Final release versions of Internet Explorer® 6.0 or above (Windows only); Mozilla Firefox 2.0 or above (Windows and Mac); Safari™ 3.0 or above (Mac only) PDF Reader:Acrobat® or similar software may be required to view and print PDF files Screen Resolution:800 x 600 minimum Enabled Security Settings:Allow per session cookies ** These minimum requirements are subject to change. If these requirements change, you will be asked to re-accept the disclosure. Pre-release (e.g. beta) versions of operating systems and browsers are not supported. Acknowledging your access and consent to receive materials electronically 2026 N Olive St - 2017829803/10/23 To confirm to us that you can access this information electronically, which will be similar to other electronic notices and disclosures that we will provide to you, please verify that you were able to read this electronic disclosure and that you also were able to print on paper or electronically save this page for your future reference and access or that you were able to e-mail this disclosure and consent to an address where you will be able to print on paper or save it for your future reference and access. Further, if you consent to receiving notices and disclosures exclusively in electronic format on the terms and conditions described above, please let us know by clicking the ‘I agree’ button below. By checking the ‘I agree’ box, I confirm that: • I can access and read this Electronic CONSENT TO ELECTRONIC RECEIPT OF ELECTRONIC RECORD AND SIGNATURE DISCLOSURES document; and • I can print on paper the disclosure or save or send the disclosure to a place where I can print it, for future reference and access; and • Until or unless I notify Nerd Power LLC as described above, I consent to receive from exclusively through electronic means all notices, disclosures, authorizations, acknowledgements, and other documents that are required to be provided or made available to me by Nerd Power LLC during the course of my relationship with you. 2026 N Olive St - 2017829803/10/23 ACD INV MSP UM INVCB JB JB REV SHEET NAME SHEET SIZE SHEET NUMBER ANSI B 11" X 17" DATE DESCRIPTION REVISIONS Signature with Seal PROJECT NAME & ADDRESS PV-3 PROJECT ID DA N I E L S C H E I N B E R G 20 2 6 N O L I V E S T , SA N T A A N A , C A 9 2 7 0 6 , U S A FRESH10/26/2022 ORIGINAL PLAN 2065 W OBISPO AVE #102 GILBERT, AZ 85233 USA 866-572-2637 LIC # CA-1019100 ABHISHEK MAHESH STRING LAYOUT 1 STRING LAYOUT PV-3 SCALE: 3/32" = 1'-0" PAGE 3 OF 18 STRING 1 STRING 2 BILL OF MATERIALS EQUIPMENT QTY DESCRIPTION SOLAR PV MODULE 52 LONGI SOLAR LR4-60HPB 355M 355W MODULES INVERTER 02 SOLAREDGE TECHNOLOGY: SE7600H-US (240V) INVERTER OPTIMIZER 52 SOLAREDGE POWER OPTIMIZERS S-440 COMBINER BOX 1 125A COMBINER BOX 120/240V AC DISCONNECT 1 AC DISCONNECT EATON#DG223URB 100A, 2P,240VAC NEMA 3R ATTACHMENT 139 CHIKOUSA L FOOT ATTACHMENTS RAILS 10 CHIKOUSA 7 RAIL SYSTEM 134" RAILS 27 CHIKOUSA 7 RAIL SYSTEM 166" RAIL SPLICE 16 SPLICE KIT MID CLAMPS 78 MID CLAMPS END CLAMPS 52 END CLAMPS / STOPPER SLEEVE GROUNDING LUG 13 GROUNDING LUG (E ) B A C K O F R E S I D E N C E (E ) F R O N T O F R E S I D E N C E N O L I V E S T STRING 1A STRING 2A Structural Only Signed 11/10/2022 2026 N Olive St - 2017829803/10/23 REV SHEET NAME SHEET SIZE SHEET NUMBER ANSI B 11" X 17" DATE DESCRIPTION REVISIONS Signature with Seal PROJECT NAME & ADDRESS PV-6 PROJECT ID DA N I E L S C H E I N B E R G 20 2 6 N O L I V E S T , SA N T A A N A , C A 9 2 7 0 6 , U S A FRESH10/26/2022 ORIGINAL PLAN 2065 W OBISPO AVE #102 GILBERT, AZ 85233 USA 866-572-2637 LIC # CA-1019100 ABHISHEK MAHESH WIRING CALCULATIONS PAGE 6 OF 18 ELECTRICAL NOTES 1.) ALL EQUIPMENT TO BE LISTED BY UL OR OTHER NRTL, AND LABELED FOR ITS APPLICATION. 2.) ALL CONDUCTORS SHALL BE COPPER, RATED FOR 600 V AND 90 DEGREE C WET ENVIRONMENT. 3.) WIRING, CONDUIT, AND RACEWAYS MOUNTED ON ROOFTOPS SHALL BE ROUTED DIRECTLY TO, AND LOCATED AS CLOSE AS POSSIBLE TO THE NEAREST RIDGE, HIP, OR VALLEY. 4.) WORKING CLEARANCES AROUND ALL NEW AND EXISTING ELECTRICAL EQUIPMENT SHALL COMPLY WITH NEC 110.26. 5.) DRAWINGS INDICATE THE GENERAL ARRANGEMENT OF SYSTEMS. CONTRACTOR SHALL FURNISH ALL NECESSARY OUTLETS, SUPPORTS, FITTINGS AND ACCESSORIES TO FULFILL APPLICABLE CODES AND STANDARDS. 6.) WHERE SIZES OF JUNCTION BOXES, RACEWAYS, AND CONDUITS ARE NOT SPECIFIED, THE CONTRACTOR SHALL SIZE THEM ACCORDINGLY. 7.) ALL WIRE TERMINATIONS SHALL BE APPROPRIATELY LABELED AND READILY VISIBLE. 8.) MODULE GROUNDING CLIPS TO BE INSTALLED BETWEEN MODULE FRAME AND MODULE SUPPORT RAIL, PER THE GROUNDING CLIP MANUFACTURER'S INSTRUCTION. 9.) MODULE SUPPORT RAIL TO BE BONDED TO CONTINUOUS COPPER G.E.C. VIA WEEB LUG OR ILSCO GBL-4DBT LAY-IN LUG. 10.) THE POLARITY OF THE GROUNDED CONDUCTORS IS NEGATIVE NUMBER OF CURRENT CARRYING CONDUCTORS IN EMT 4-6 7-9 10-20 PERCENT OF VALUES .80 .70 .50 DC CONDUCTOR AMPACITY CALCULATIONS: ARRAY TO JUNCTION BOX 1&2: SOLAR MODULE SPECIFICATIONS MANUFACTURER / MODEL # LONGI SOLAR LR4-60HPB 355M 355 (355W)MODULES VMP 34.6 IMP 10.27 VOC 40.6 ISC 11.25 MODULE DIMENSION 69.09"L x 40.87"W x 1.38"D (In Inch) INVERTER SPECIFICATIONS 1&2 MANUFACTURER / MODEL #SOLAREDGE TECHNOLOGY SE7600H-US NOMINAL AC POWER 7.60KW NOMINAL OUTPUT VOLTAGE 240 VAC NOMINAL OUTPUT CURRENT 32A AMBIENT TEMPERATURE SPECS RECORD LOW TEMP AMBIENT TEMP (HIGH TEMP 2%) CONDUIT HEIGHT 0.5" ROOF TOP TEMP CONDUCTOR TEMPERATURE RATE MODULE TEMPERATURE COEFFICIENT OF Voc EXPECTED WIRE TEMP (In Celsius) TEMP. CORRECTION PER TABLE (310.16)0.96 NO. OF CURRENT CARRYING CONDUCTORS 4 CONDUIT FILL CORRECTION PER NEC 310.15(B)(2)(a)0.80 CIRCUIT CONDUCTOR SIZE 10 AWG CIRCUIT CONDUCTOR AMPACITY 40A REQUIRED CIRCUIT CONDUCTOR AMPACITY PER NEC 690.8(A&B) 17.58A 1.25 X 1.25 X MODULE ISC DERATED AMPACITY OF CIRCUIT CONDUCTOR PER NEC TABLE 310.16 30.72ATEMP. CORRECTION PER TABLE (310.16) X CONDUIT FILL CORRECTION PER NEC 310.15(B)(2)(a) X CIRCUIT CONDUCTOR AMPACITY Result should be greater than (17.58A) otherwise less the entry for circuit conductor size and ampacity DC CONDUCTOR AMPACITY CALCULATIONS: FROM JUNCTION BOX 1&2 TO INVERTER 1&2: AMBIENT TEMPERATURE ADJUSTMENT FOR EXPOSED CONDUIT PER NEC 310.15(B)(2)(c) EXPECTED WIRE TEMP (In Celsius)31 +22 = 53 TEMP. CORRECTION PER TABLE (310.16)0.76 NO. OF CURRENT CARRYING CONDUCTORS 4 CONDUIT FILL CORRECTION PER NEC 310.15(B)(2)(a)0.80 CIRCUIT CONDUCTOR SIZE 10AWG CIRCUIT CONDUCTOR AMPACITY 40A REQUIRED CIRCUIT CONDUCTOR AMPACITY PER NEC 690.8(A&B) 18.75A 1.25 X OPTIMIZER OUTPUT CURRENT DERATED AMPACITY OF CIRCUIT CONDUCTOR PER NEC TABLE 310.16 24.32ATEMP. CORRECTION PER TABLE (310.16) X CONDUIT FILL CORRECTION PER NEC 310.15(B)(2)(a) X CIRCUIT CONDUCTOR AMPACITY Result should be greater than (18.75A) otherwise less the entry for circuit conductor size and ampacity AC CONDUCTOR AMPACITY CALCULATIONS: FROM INVERTER 1&2 TO COMBINER BOX: No. OF INVERTER 1 EXPECTED WIRE TEMP (In Celsius) TEMP. CORRECTION PER TABLE (310.16)0.96 NO. OF CURRENT CARRYING CONDUCTORS 3 CONDUIT FILL CORRECTION PER NEC 310.15(B)(2)(a)1 CIRCUIT CONDUCTOR SIZE 8AWG CIRCUIT CONDUCTOR AMPACITY 55A REQUIRED CIRCUIT CONDUCTOR AMPACITY PER NEC 690.8(B) 40.00A 1.25 X MAX INVERTER OUTPUT CURRENT DERATED AMPACITY OF CIRCUIT CONDUCTOR PER NEC TABLE 310.16 52.80A TEMP. CORRECTION PER TABLE (310.16) X CONDUIT FILL CORRECTION PER NEC 310.15(B)(2)(a) X CIRCUIT CONDUCTOR AMPACITY Result should be greater than (40.00A) otherwise less the entry for circuit conductor size and ampacity AC CONDUCTOR AMPACITY CALCULATIONS: FROM COMBINER BOX TO MAIN SERVICE PANEL: No. OF INVERTER 1 EXPECTED WIRE TEMP (In Celsius) TEMP. CORRECTION PER TABLE (310.16)0.96 NO. OF CURRENT CARRYING CONDUCTORS 3 CONDUIT FILL CORRECTION PER NEC 310.15(B)(2)(a)1 CIRCUIT CONDUCTOR SIZE 3AWG CIRCUIT CONDUCTOR AMPACITY 115A REQUIRED CIRCUIT CONDUCTOR AMPACITY PER NEC 690.8(B) 80.00A 1.25 X MAX INVERTER OUTPUT CURRENT DERATED AMPACITY OF CIRCUIT CONDUCTOR PER NEC TABLE 310.16 110.40ATEMP. CORRECTION PER TABLE (310.16) X CONDUIT FILL CORRECTION PER NEC 310.15(B)(2)(a) X CIRCUIT CONDUCTOR AMPACITY Result should be greater than (80.00A) otherwise less the entry for circuit conductor size and ampacity signed 11/9/2022 2026 N Olive St - 2017829803/10/23 REV SHEET NAME SHEET SIZE SHEET NUMBER ANSI B 11" X 17" DATE DESCRIPTION REVISIONS Signature with Seal PROJECT NAME & ADDRESS PV-8 PROJECT ID DA N I E L S C H E I N B E R G 20 2 6 N O L I V E S T , SA N T A A N A , C A 9 2 7 0 6 , U S A FRESH10/26/2022 ORIGINAL PLAN 2065 W OBISPO AVE #102 GILBERT, AZ 85233 USA 866-572-2637 LIC # CA-1019100 ABHISHEK MAHESH OPTIMIZER CHART 1-10 1 2 3 4 11-20 21-30 31-40 41-50 51-60 5 6 7 8 9 10 OPTIMIZER CHART PAGE 8 OF 18 N O L I V E S T 2026 N Olive St - 2017829803/10/23 REV SHEET NAME SHEET SIZE SHEET NUMBER ANSI B 11" X 17" DATE DESCRIPTION REVISIONS Signature with Seal PROJECT NAME & ADDRESS PV-9 PROJECT ID DA N I E L S C H E I N B E R G 20 2 6 N O L I V E S T , SA N T A A N A , C A 9 2 7 0 6 , U S A FRESH10/26/2022 ORIGINAL PLAN 2065 W OBISPO AVE #102 GILBERT, AZ 85233 USA 866-572-2637 LIC # CA-1019100 ABHISHEK MAHESH EQUIPMENTS ELEVATION PAGE 9 OF 18 EQUIPMENTS ELEVATION SCALE: NTS 1 PV-9 (N) MAIN SERVICE PANEL, 200A RATED, 240V, SOLAR READY (SURFACE MOUNT) (N) SOLAREDGE TECHNOLOGY : SE7600H-US INVERTER-2 INTEGRATED RAPID SHUTDOWN (N) AC DISCONNECT (E) UTILITY METER (N) SOLAREDGE TECHNOLOGY : SE7600H-US INVERTER-1 INTEGRATED RAPID SHUTDOWN (N) COMBINER BOX 2026 N Olive St - 2017829803/10/23 REV SHEET NAME SHEET SIZE SHEET NUMBER ANSI B 11" X 17" DATE DESCRIPTION REVISIONS Signature with Seal PROJECT NAME & ADDRESS PV-10 PROJECT ID FRESH10/26/2022 ORIGINAL PLAN 2065 W OBISPO AVE #102 GILBERT, AZ 85233 USA 866-572-2637 LIC # CA-1019100 ABHISHEK MAHESH EQUIPMENT SPECIFICATION PAGE 10 OF 18 2026 N Olive St - 2017829803/10/23 REV SHEET NAME SHEET SIZE SHEET NUMBER ANSI B 11" X 17" DATE DESCRIPTION REVISIONS Signature with Seal PROJECT NAME & ADDRESS PV-11 PROJECT ID DA N I E L S C H E I N B E R G 20 2 6 N O L I V E S T , SA N T A A N A , C A 9 2 7 0 6 , U S A FRESH10/26/2022 ORIGINAL PLAN 2065 W OBISPO AVE #102 GILBERT, AZ 85233 USA 866-572-2637 LIC # CA-1019100 ABHISHEK MAHESH EQUIPMENT SPECIFICATION PAGE 11 OF 18 2026 N Olive St - 2017829803/10/23 REV SHEET NAME SHEET SIZE SHEET NUMBER ANSI B 11" X 17" DATE DESCRIPTION REVISIONS Signature with Seal PROJECT NAME & ADDRESS PV-12 PROJECT ID FRESH10/26/2022 ORIGINAL PLAN 2065 W OBISPO AVE #102 GILBERT, AZ 85233 USA 866-572-2637 LIC # CA-1019100 ABHISHEK MAHESH EQUIPMENT SPECIFICATION PAGE 12 OF 18 2026 N Olive St - 2017829803/10/23 ACD INV MSP UM INVCB JB 7'-11"9'-11"64'-11" 10 ' - 0 " 9' - 1 1 " 9' - 3 " 7' - 2 " 6' - 1 1 " 9' - 0 " 6" 23 ' - 3 " 13 ' - 0 " JB REV SHEET NAME SHEET SIZE SHEET NUMBER ANSI B 11" X 17" DATE DESCRIPTION REVISIONS Signature with Seal PROJECT NAME & ADDRESS PV-2 PROJECT ID DA N I E L S C H E I N B E R G 20 2 6 N O L I V E S T , SA N T A A N A , C A 9 2 7 0 6 , U S A FRESH10/26/2022 ORIGINAL PLAN 2065 W OBISPO AVE #102 GILBERT, AZ 85233 USA 866-572-2637 LIC # CA-1019100 ABHISHEK MAHESH ROOF PLAN & MODULES ROOF DESCRIPTION ROOF TYPE COMP SHINGLE ROOF ROOF TILT AZIMUTH RAFTERS SIZE RAFTERS SPACING #1 2"x4"24" o.c. #2 2"x4"24" o.c. #3 2"x4"24" o.c. #4 2"x4"24" o.c. #5 2"x4"24" o.c. LEGEND - JUNCTION BOX MSP - MAIN SERVICE PANEL - VENTS, DISH (ROOF OBSTRUCTION) - ROOF ATTACHMENT - RAFTERS - CONDUIT - UTILITY METER SCALE: 3/32" = 1'-0" - SOLAREDGE OPTIMIZER MODULE TYPE, DIMENSIONS & WEIGHT ACD - AC DISCONNECT - INVERTER 1 PV-2 NUMBER OF MODULES = 52 MODULES MODULE TYPE = LONGI SOLAR LR4-60HPB 355M 355W MODULES MODULE WEIGHT = 42.99 LBS / 19.5 KG. COMPONENT WEIGHT: 1.5 LBS. PER MODULE TOTAL DEAD LOAD: 2313.48 LBS. POINT LOAD PER STANDOFF.: 2313.48 LBS / 139 STANDOFF = 16.64 LBS MODULE DIMENSIONS = 69.09"x 40.87" = 19.61 SF UNIT WEIGHT OF ARRAY = 2.27 PSF UM JB INV ARRAY AREA WITH TOTAL ROOF AREA ROOF # OF MODULES ARRAY AREA (Sq. Ft.) TOTAL ROOF AREA (Sq. Ft.) ROOF AREA COVERED BY ARRAY (%) #1 3 58.83 205.59 28.61 #2 6 117.65 752.85 15.63 #3 2 39.22 124.81 31.42 #4 20 392.18 863.59 45.41 #5 21 411.79 889.90 46.27 ROOF PLAN & MODULES PAGE 2 OF 18 ARRAY AREA WITH WHOLE ROOF AREA ROOF # OF MODULES ARRAY AREA (Sq. Ft.) TOTAL ROOF AREA (Sq. Ft.) ROOF AREA COVERED BY ARRAY (%) #1-5 52 1019.67 4166.09 24.48 LONGI SOLAR LR4-60HPB 355M 355W MODULES 40.87" 69 . 0 9 " (E ) F R O N T O F R E S I D E N C E N O L I V E S T (E ) B A C K O F R E S I D E N C E ROOF #01 (03) LONGI SOLAR LR4-60HPB 355M 355W MODULES ROOF ACCESS POINT ROOF #03 (02) LONGI SOLAR LR4-60HPB 355M 355W MODULES ROOF #04 (20) LONGI SOLAR LR4-60HPB 355M 355W MODULES (N) MAIN SERVICE PANEL, 200A RATED, 240V,SOLAR READY (SURFACE MOUNT) (N) AC DISCONNECT (N) SOLAREDGE TECHNOLOGY : SE7600H-US INVERTER-2 INTEGRATED RAPID SHUTDOWN (N) SOLAREDGE TECHNOLOGY : SE7600H-US INVERTER-1 INTEGRATED RAPID SHUTDOWN (N) COMBINER BOX ROOF #02 (06) LONGI SOLAR LR4-60HPB 355M 355W MODULES ROOF #05 (21) LONGI SOLAR LR4-60HPB 355M 355W MODULES (E) UTILITY METER 3/4" EMT CONDUIT RUN ON ROOF (TYP.) (N) JUNCTION BOX-1 (52) SOLAREDGE POWER OPTIMIZERS S-440 (139) CHIKOUSA COMPOSITION L-FOOT ATTACHMENTS @48"O.C. (E) CHIMNEY (N) CHIKO ASPHALT ROOF RACKING SYSTEM ROOF #3 TILT - 20 AZIM. - 270 ROOF #2 TILT - 20 AZIM. - 270 ROOF #1 TILT - 20 AZIM. - 270 ROOF #4 TILT - 20 AZIM. - 180 ROOF #5 TILT - 20 AZIM. - 90 18" FIRE SETBACK 18" FIRE SETBACK 18" FIRE SETBACK 18" FIRE SETB ACK 18" FI RE SETBA CK 18" FIRE SETBA CK 18" FIRE S ETBACK 18" FI RE SETB ACK 18" FIRE SETBACK 18" FIRE SETBACK 18" FIRE SETBACK 18" FIRE SETBACK 18" FIRE SET BACK 18" FIRE SET B ACK 18 " F I R E S E T B A C K 18 " F I R E S E T B A C K 18 " F I R E S E T B A C K 18 " F I R E S E T B A C K 18" FIRE SETBACK 18" FIRE SETBACK 18" F I R E SETBA C K 18" FI RE S E TBACK 18" FIRE SET BACK 18" FIRE SETBACK 36" FIRE SETBACK36" FIRE SETBACK 36" FIRE SETBA CK 36" FIRE SETBACK (N) JUNCTION BOX-2 - COMBINER BOXCB Structural Only Signed 11/10/2022 2026 N Olive St - 2017829803/10/23 REV SHEET NAME SHEET SIZE SHEET NUMBER ANSI B 11" X 17" DATE DESCRIPTION REVISIONS Signature with Seal PROJECT NAME & ADDRESS PV-4 PROJECT ID DA N I E L S C H E I N B E R G 20 2 6 N O L I V E S T , SA N T A A N A , C A 9 2 7 0 6 , U S A FRESH10/26/2022 ORIGINAL PLAN 2065 W OBISPO AVE #102 GILBERT, AZ 85233 USA 866-572-2637 LIC # CA-1019100 ABHISHEK MAHESH ATTACHMENT DETAIL PAGE 4 OF 18 SCALE: NTS 2 PV-4 ATTACHMENT DETAIL SCALE: NTS 1 PV-4 ATTACHMENT DETAIL(enlarged view) PV MODULE SEE (2/PV-4) FOR ENLARGED VIEW (E) SINGLE LAYER OF COMP SHINGLE PV MODULES CHIKOUSA 7 RAILS FLASHING COMPOSITION L FOOT ATTACHMENT (E) SINGLE LAYER OF COMP SHINGLE GROUNDING & END/MID CLAMP CHIKO ASPHALT ROOF RACKING SYSTEM 2"x4" RAFTERS @ 24" O.C. 5/16" x 3 1/2" SS LAG BOLT INTO RAFTER(S) 2 1/2" MIN. PENETRATION SEALED W/ GEOCEL. CHIKOUSA CHANNEL NUT 2"X4" RAFTERS @ 24"O.C. 6" Structural Only Signed 11/10/2022 2026 N Olive St - 2017829803/10/23 REV SHEET NAME SHEET SIZE SHEET NUMBER ANSI B 11" X 17" DATE DESCRIPTION REVISIONS Signature with Seal PROJECT NAME & ADDRESS PV-13 PROJECT ID DA N I E L S C H E I N B E R G 20 2 6 N O L I V E S T , SA N T A A N A , C A 9 2 7 0 6 , U S A FRESH10/26/2022 ORIGINAL PLAN 2065 W OBISPO AVE #102 GILBERT, AZ 85233 USA 866-572-2637 LIC # CA-1019100 ABHISHEK MAHESH EQUIPMENT SPECIFICATION PAGE 13 OF 18 2026 N Olive St - 2017829803/10/23 REV SHEET NAME SHEET SIZE SHEET NUMBER ANSI B 11" X 17" DATE DESCRIPTION REVISIONS Signature with Seal PROJECT NAME & ADDRESS PV-14 PROJECT ID DA N I E L S C H E I N B E R G 20 2 6 N O L I V E S T , SA N T A A N A , C A 9 2 7 0 6 , U S A FRESH10/26/2022 ORIGINAL PLAN 2065 W OBISPO AVE #102 GILBERT, AZ 85233 USA 866-572-2637 LIC # CA-1019100 ABHISHEK MAHESH EQUIPMENT SPECIFICATION PAGE 14 OF 18 2026 N Olive St - 2017829803/10/23 REV SHEET NAME SHEET SIZE SHEET NUMBER ANSI B 11" X 17" DATE DESCRIPTION REVISIONS Signature with Seal PROJECT NAME & ADDRESS PV-15 PROJECT ID FRESH10/26/2022 ORIGINAL PLAN 2065 W OBISPO AVE #102 GILBERT, AZ 85233 USA 866-572-2637 LIC # CA-1019100 ABHISHEK MAHESH EQUIPMENT SPECIFICATION PAGE 15 OF 18 2026 N Olive St - 2017829803/10/23 REV SHEET NAME SHEET SIZE SHEET NUMBER ANSI B 11" X 17" DATE DESCRIPTION REVISIONS Signature with Seal PROJECT NAME & ADDRESS PV-16 PROJECT ID FRESH10/26/2022 ORIGINAL PLAN 2065 W OBISPO AVE #102 GILBERT, AZ 85233 USA 866-572-2637 LIC # CA-1019100 ABHISHEK MAHESH EQUIPMENT SPECIFICATION PAGE 16 OF 18 2026 N Olive St - 2017829803/10/23 REV SHEET NAME SHEET SIZE SHEET NUMBER ANSI B 11" X 17" DATE DESCRIPTION REVISIONS Signature with Seal PROJECT NAME & ADDRESS PV-17 PROJECT ID FRESH10/26/2022 ORIGINAL PLAN 2065 W OBISPO AVE #102 GILBERT, AZ 85233 USA 866-572-2637 LIC # CA-1019100 ABHISHEK MAHESH EQUIPMENT SPECIFICATION PAGE 17 OF 18 2026 N Olive St - 2017829803/10/23 Rev: 8/29/19 SOL-01 CBC 2016 Solar Photovoltaic (PV) Checklist for Detached SINGLE FAMILY RESIDENCES Only Instructions: The licensed contractor of record shall complete all sections, answer the ten questions and sign the certification section below. A copy of this form shall be attached to each of TWO sets of plans, of minimum 11” x 17” size. If answering NO to any of the questions, plan check shall be required. Project Address: Contractor Company Name: Contractor License Number: YES NO Are the following applicable to the proposed project? 1.   Will the PV system layout provide the required three-foot wide clear access pathways per Section 605.11 of the California Fire Code, and is this shown on the roof plan? 2.   Will the PV system be installed on a roof having only one roofing layer with no overlays? 3.   Will the PV array be flush mounted to the existing roof so that the plane of the modules (panels) are parallel to the plane of the roof? 4. Will the PV system weigh maximum 4 pounds per square feet or less? 5. Will the PV system be installed where the modules do not overhang any roof edges (such as eaves, gabled ends, ridges and hips)? 6.   Will the PV system be installed with a space of 2” minimum to 10” maximum between the underside of modules and the surface of the roof? 7.   Will the PV system be installed without using any ballast system or counter-weight system? 8.   Will the anchors be installed with a maximum horizontal anchor spacing of 6 feet and is this maximum horizontal spacing shown on the plans? 9.   Will the minimum 5/16” lag screws be installed with a minimum of 2-1/2 inch embedment into roof rafters (with pre-drilled holes) and is this minimum embedment shown on the plans? 10.   Are ALL the structural pages of the plans stamped and signed by a California licensed professional engineer? (including project specific site plan, PV layout, anchorage spacing, anchorage details and manufacturer’s PV support information.) I certify under penalty of perjury under the laws of the State of California that the above is true: Print Name: Signature: Phone Number: Date: Email Address: Planning & Building Agency Building Safety Division 20 Civic Center Plaza P.O. Box 1988 (M-19) Santa Ana, CA 92702 (714) 647-5800 www.santa-ana.org RESIDENTIAL PHOTOVOLTAIC CHECKLIST Dillon Blake (602) 842-3881 Nerd Power LLC 1019100 caprocessing@nerdpower.energy 2026 N Olive St 12/16/2022 2026 N Olive St - 2017829803/10/23 2026 N Olive St - 2017829803/10/23 Date: _______________________________________________________________________ Name: ______________________________________________________________________ Address: ____________________________________________________________________ To whom it may concern; I hereby grant permission to Nerd Power LLC and it’s employees to obtain permits and install a roof-mounted solar system on my home. Thank you, ______________________________________________________________________ (signature) DocuSign Envelope ID: DAB538C6-C31F-4430-B680-CF31A7F70EBE 12/16/2022 Daniel Scheinberg 2026 N Olive St Santa Ana CA 92706 2026 N Olive St - 2017829803/10/23 REV SHEET NAME SHEET SIZE SHEET NUMBER ANSI B 11" X 17" DATE DESCRIPTION REVISIONS Signature with Seal PROJECT NAME & ADDRESS PV-19 PROJECT ID DA N I E L S C H E I N B E R G 20 2 6 N O L I V E S T , SA N T A A N A , C A 9 2 7 0 6 , U S A FRESH10/26/2022 ORIGINAL PLAN 2065 W OBISPO AVE #102 GILBERT, AZ 85233 USA 866-572-2637 LIC # CA-1019100 ABHISHEK MAHESH A12/30/2022 REV EQUIPMENT SPECIFICATION PAGE 19 OF 18 Exp. Date: 09/30/24 2/3/23 2026 N Olive St - 2017829803/10/23 11/10/2022 RE: Structural Certification for Installation of Residential Solar DANIEL SCHEINBERG:2026 N OLIVE ST,, SANTA ANA, CA 92706,USA Attn: To Whom It May Concern Design Criteria Code 2019 California Building Code (ASCE 7-16) Risk category II Wind Load (component and Cladding) Roof Dead Load Dr 10 psf V 95 mph PV Dead Load DPV 3 psf Exposure C Roof Live Load Lr 20 psf Ground Snow S 0 psf If you have any questions on the above, please do not hesitate to call. Sincerely, Eugene Munyanziza, P.E. EV Engineering, LLC Signed :11/10/2022 projects@evengineersnet.com http://www.evengineersnet.com Exp: 06/30/2024 This Letter is for the existing roof framing which supports the new PV modules as well as the attachment of the PV system to existing roof framing. From the field observation report, the roof is made of Single layer composition shingle roofing over roof plywood supported by 2X4 Rafters at 24 inches. The slope of the roof was approximated to be 20 degrees and the allowable maximum rafter span is 6 feet between supports. After review of the field observation data and based on our structural capacity calculation, the existing roof framing has been determined to be adequate to support the imposed loads without structural upgrades. Contractor shall verify that existing framing is consistent with the described above before install. Should they find any discrepancies, a written approval from SEOR is mandatory before proceeding with install. Capacity calculations were done in accordance with applicable building codes. projects@evengineersnet.com http://www.evengineersnet.com 2026 N Olive St - 2017829803/10/23 Structural Letter for PV Installation Date: 11/10/2022 Job Address: 2026 N OLIVE ST, SANTA ANA, CA 92706,USA Job Name: DANIEL SCHEINBERG Job Number: 221110DS Scope of Work Table of Content Sheet 1 Cover 2 Attachment Uplift checks 3 Roof Framing Check 4 Seismic Check and Scope of work Engineering Calculations Summary Code 2019 California Building Code (ASCE 7-16) Risk category II Roof Dead Load Dr 10 psf PV Dead Load DPV 3 psf Roof Live Load Lr 20 psf Ground Snow S 0 psf Wind Load (component and Cladding) V 95 mph Exposure C References NDS for Wood Construction Sincerely, Eugene Munyanziza, P.E.Signed :11/10/2022 EV Engineering, LLC projects@evengineersnet.com http://www.evengineersnet.com Exp: 06/30/2024 This Letter is for the existing roof framing which supports the new PV modules as well as the attachment of the PV system to existing roof framing. All PV mounting equipment shall be designed and installed per manufacturer's approved installation specifications. projects@evengineersnet.com http://www.evengineersnet.com 2026 N Olive St - 2017829803/10/23 Wind Load Cont. 95 mph ASCE 7-16 Figure 26.5-1B C 1.0 ASCE 7-16 Sec 26.8.2 0.85 ASCE 7-16 Table 26.10-1 0.85 ASCE 7-16 Table 26.6-1 1.00 ASCE 7-16 Table 26.9-1 16.62 psf 20.0 Degrees 1.5 Conservatively assuming all exposed 0.8 conservatively assuming 10 ft2 effective area Uplift (W)Zone(1) Zone(2r) Zone(2e)Zone(3) Fig. 30-3-2 GCp=-2.1 -2.6 -2.7 -2.7 Eq. 29.4-7 P=qh(GCp)(γE)(γa)=-41.88 -51.85 -53.84 -53.84 GCp=0.3 Figure 30.3-2 P=qh(GCp)(γE)(γa)=4.49 Equation 29.4-7 Rafter Attachments: 0.6D+0.6W (CD=1.6) Connection Check Attachment max. spacing= 4 ft 5/16" Lag Screw Withdrawal Value= 266 lbs/in Table 12.2A - NDS 2.5 in DFL Assumed Prying Coefficient 1.4 Allowable Capacity= 760 lbs Zone Trib Width Area (ft) Uplift (lbs) Down (lbs) Zone(1) 4 11.0 222.1 82.4 Zone(2r) 4 11.0 271.5 82.4 Zone(2e) 4 11.0 281.4 82.4 Zone(3) 4 11.0 281.4 82.4 Conservative Max= 281.4 < 760 CONNECTION IS OK 2. Embedment is measured from the top of the framing member to the tapered tip of a lag screw. Embedment in sheading or other material does not count. II V= Exposure = 1. Pv seismic dead weight is negligible to result in significant seismic uplift, therefore the wind uplift governs γE= γa= KZt = qh= 0.00256KzKztKdKeV2= Pitch = Lag Screw Penetration Risk Category = KZ = Kd = Ke = projects@evengineersnet.com http://www.evengineersnet.com 2026 N Olive St - 2017829803/10/23 Vertical Load Resisting System Design Roof Framing Rafters Snow Load Fully Exposed pg= 0 psf Ct =1.1 Ce = 0.9 Is =1.0 pf = 0 psf pfmin. = 0.0 psf ps =0 psf Conservatively (Cs=1) 0 plf Max Length, L = 6.0 ft (Rafter maximum Allowable Horizontal Span) Tributary Width, WT = 24in Dr = 10 psf 20 plf PvDL = 3 psf 12 plf Load Case: DL+0.75(0.6W+S) 0.75(Pnet+Ps)+ Ppvcos(θ)+PDL= 36 plf Mdown= 162 lb-ft Mallowable = Sx x Fb' (wind)= 456 lb-ft > 162 lb-ft OK Load Case: DL+S Ps+ Ppvcos(θ)+PDL= 32 plf Mdown= 144 lb-ft Mallowable = Sx x Fb' (wind)= 456 lb-ft > 144 lb-ft OK Load Case: DL+0.6W Pnet+ Ppvcos(θ)+PDL= 37.4 plf Max Moment, Mu= 168 lb-ft Mallowable = Sx x Fb' (wind)= 634 lb-ft > 168 lb-ft OK Pv max Shear= 82.4 lbs Shear, Vu=wL/2+Pv Point Load = 178 lbs Max Shear, Vu=wL/2+Pv Point Load = 178 lb Member Capacity DF-L No.2 2X4 CL CF Ci Cr KF φ λ Fb = 900 psi 1.0 1.5 1.0 1.15 2.54 0.85 0.8 1553 psi Fv = 180 psi N/A N/A 1.0 N/A 2.88 0.75 0.8 180 psi E = 1600000 psi N/A N/A 1.0 N/A N/A N/A N/A 1600000 psi Emin = 580000 psi N/A N/A 1.0 N/A 1.76 0.85 N/A 580000 psi Depth, d = 3.5 in Width, b = 1.5 in Cross-Sectonal Area, A = 5.25 in2 Moment of Inertia, Ixx = 5.35938 in4 Section Modulus, Sxx = 3.0625 in Allowable Moment, Mall = Fb'Sxx = 396.2 lb-ft DCR=Mu/Mall = 0.36 < 1 Satisfactory Allowable Shear, Vall = 2/3Fv'A = 630.0 lb DCR=Vu/Vall = 0.28 < 1 Satisfactory Design Value Adjusted Value projects@evengineersnet.com http://www.evengineersnet.com 2026 N Olive St - 2017829803/10/23 Siesmic Loads Check Roof Dead Load 10psf % or Roof with Pv 24% Dpv and Racking 3 psf Average Total Dead Load 10.7 psf Increase in Dead Load 2.9%OK Limits of Scope of Work and Liability The increase in seismic Dead weight as a result of the solar system is less than 10% of the existing structure and therefore no further seismic analysis is required. We have based our structural capacity determination on information in pictures and a drawing set titled PV plans - DANIEL SCHEINBERG. The analysis was according to applicable building codes, professional engineering and design experience, opinions and judgments. The calculations produced for this dwelling's assessment are only for the proposed solar panel installation referenced in the stamped plan set and were made according to generally recognized structural analysis standards and procedures. projects@evengineersnet.com http://www.evengineersnet.com 2026 N Olive St - 2017829803/10/23