HomeMy WebLinkAbout2030 W Summer Wind - PlanExpedited Permit Process for PV Systems - Micro-Inverter1 Expedited Permit Process for PV Systems Micro-Inverter The Solar America Board for Codes and Standards (Solar ABCs) Expedited Permit Pro- cess provides a means to differentiate systems that can be permitted quickly and easily due to their similarity with the majority of small-scale PV systems. Those systems with unique characteristics may be handled with small additions to this Expedited Permit Process or may require much more information, depending on the uniqueness of the installation. The following pages contain forms for the Micro-Inverter to use with the Expedited Per- mit Process. The Standard String, AC Module, and Supply-Side Connection forms are also available as interactive PDF files at www.solarabcs.org/permitting. In jurisdic- tions that have adopted the Expedited Permit Process for PV Systems, these forms can be filled out electronically and submitted in either printed form and via email. An elec- tronic format is used so that the supplied information is standardized and legible for the local jurisdiction. 2030 W Summer Wind03/28/23 Expedited Permit Process for PV Systems — Micro-Inverter2 Expedited Permit Process for Small-Scale PV Systems Micro-Inverter The information in this guideline is intended to help local jurisdictions and contractors identify when PV system installations are simple, needing only a basic review, and when an installation is more complex. It is likely that 50%-75% of all residential systems will comply with these simple criteria. For projects that fail to meet the simple criteria, resolution steps have been suggested to provide as a path to permit approval. Required Information for Permit: 1. Site plan showing location of major components on the property. This drawing need not be exactly to scale, but it should represent relative location of components at site (see supplied example site plan). PV arrays on dwellings with a 3’ perimeter space at ridge and sides may not need separate fire service review. 2. Electrical diagram showing PV array configuration, wiring system, overcurrent protection, inverter, disconnects, required signs, and ac connection to building (see supplied standard electrical diagram). 3. Specification sheets and installation manuals (if available) for all manufactured components including, but not limited to, PV modules, inverter(s), combiner box, disconnects, and mounting system. Step 1: Structural Review of PV Array Mounting System Is the array to be mounted on a defined, permitted roof structure? l Yes l No If No due to non-compliant roof or a ground mount, submit completed worksheet for the structure WKS1. Roof Information: 1. Is the roofing type lightweight (Yes = composition, lightweight masonry, metal, etc…)__________________________ ____________________________________________________________________________________________________ If No, submit completed worksheet for roof structure WKS1 (No = heavy masonry, slate, etc…). 2. Does the roof have a single roof covering? l Yes l No If No, submit completed worksheet for roof structure WKS1. 3. Provide method and type of weatherproofing roof penetrations (e.g. flashing, caulk).____________________________ Mounting System Information: 1. Is the mounting structure an engineered product designed to mount PV modules with no more than an 18” gap beneath the module frames? l Yes l No If No, provide details of structural attachment certified by a design professional. 2. For manufactured mounting systems, fill out information on the mounting system below: a. Mounting System Manufacturer ___________Product Name and Model#________________________________ b. Total Weight of PV Modules and Rails ___________lbs c. Total Number of Attachment Points____________ d. Weight per Attachment Point (b÷c)_________________lbs (if greater than 45 lbs, see WKS1) e. Maximum Spacing Between Attachment Points on a Rail ______________inches (see product manual for maximum spacing allowed based on maximum design wind speed) f. Total Surface Area of PV Modules (square feet)_________________ ft 2 g. Distributed Weight of PV Module on Roof (b÷f)_______________ lbs/ft2 If distributed weight of the PV system is greater than 5 lbs/ft2, see WKS1. Step 2: Electrical Review of PV System (Calculations for Electrical Diagram) In order for a PV system to be considered for an expedited permit process, the following must apply: 1. PV modules, utility-interactive inverters, and combiner boxes are identified for use in PV systems. 2. The PV array is composed of 4 series strings or less per inverter. 3. The total inverter capacity has a continuous ac power output 13,440 Watts or less 4. The ac interconnection point is on the load side of service disconnecting means (690.64(B)). 5. One of the standard electrical diagrams (E1.1, E1.1a, E1.1b, or E1.1c) can be used to accurately represent the PV system. Interactive PDF diagrams are available at www.solarabcs.org/permitting. Fill out the standard electrical diagram completely. A guide to the electrical diagram is provided to help the applicant understand each blank to fill in. If the electrical system is more complex than the standard electrical diagram can effectively communicate, provide an alternative diagram with appropriate detail. 2030 W Summer Wind03/28/23 Ex p e d i t e d P e r m i t P r o c e s s f o r P V S y s t e m s 3 Micro-Inverter Site Plan                                                        CA Solar Group Paul Czajka7647 Hayvenhurst Ave Unit 26 Van Nuys CA 91406 2030 W Summer Wind, Santa Ana, CA 92704 6.11 2030 W Summer Wind03/28/23 Ex p e d i t e d P e r m i t P r o c e s s f o r P V S y s t e m s 4 Micro-Inverter Electrical Diagram Contractor Name, Address and Phone: One-Line Standard Electrical Diagram for Micro-Inverter PV Systems Site Name: Site Address: System AC Size: SIZE FSCM NO DWG NO REV E1.1a SCALE NTS Date: SHEET Drawn By: Checked By: DESCRIPTION OR CONDUCTOR TYPE USE-2 or PV WIRE GEC EGC X ALL THAT APPLY EXTERIOR CABLE LISTED W/ INV. THWN-2 or XHHW-2 or RHW-2 GEC EGC X ALL THAT APPLY NO DC GEC IF 690.35 SYSTEM THWN-2 or XHHW-2 or RHW-2 GEC EGC X ALL THAT APPLY TAG 1 2 3 4 5 CONDUIT AND CONDUCTOR SCHEDULE COND. GAUGE MFG MFG NUMBER OF CONDUCTORS MFG Cable MFG Cable CONDUIT TYPE N/A N/A N/A SAME SAME CONDUIT SIZE N/A N/A N/A SAME SAME DESCRIPTION PV DC or AC MODULE DC/AC INVERTER (MICRO) J-BOX (IF USED) PV ARRAY AC COMB. PANEL (IF USED) GEN METER (IF USED) AC DISCONNECT (IF USED) SERVICE PANEL TAG 1 2 3 4 5 6 7 8 PART NUMBER NOTES FOR UNUSED MODULES PUT "N/A” in BLANK ABOVE 1 1 3 2 3 EQUIPMENT SCHEDULE 2 _____ MICRO-INVERTERS IN BRANCH- CIRCUIT MOD ____ DC AC MOD ____ DC AC MOD ____ DC AC MOD ____ DC AC MOD ____ DC AC MOD ____ DC AC J-BOX 4 AC DISCO M BUILDING GROUNDING ELECTRODE G M UTILITY SERVICE MAIN SERVICE PANEL MAIN OCPD INVERTER OCPD 6 7 8 5 4 5 G SEE GUIDE APPENDIX D FOR INFORMATION ON MODULE AND ARRAY GROUNDING AC COMBINER PANEL G ____ MICRO-INVERTERS IN BRANCH- CIRCUIT CA Solar Group 7647 Hayvenhurst Ave Unit 26 Van Nuys CA 91406 Paul Czajka 6.11 2030 W Summer Wind, Santa Ana, CA 92704 2030 W Summer Wind03/28/23 Ex p e d i t e d P e r m i t P r o c e s s f o r P V S y s t e m s 5 Contractor Name, Address and Phone: Notes for One-Line Standard Electrical Diagram for Single-Phase PV Systems Site Name: Site Address: System AC Size: SIZE FSCM NO DWG NO REV E1.2a SCALE NTS Date: SHEET Drawn By: Checked By: MAX POWER-POINT CURRENT (IMP) MAX POWER-POINT VOLTAGE (VMP) OPEN-CIRCUIT VOLTAGE (VOC) SHORT-CIRCUIT CURRENT (ISC) MAX SERIES FUSE (OCPD) MAXIMUM POWER (PMAX) MAX VOLTAGE (TYP 600VDC) VOC TEMP COEFF (mV/oC or %/oC ) IF COEFF SUPPLIED, CIRCLE UNITS MODULE MAKE MODULE MODEL PV MODULE RATINGS @ STC (Guide Section 5) MAX DC VOLT RATING MAX POWER @ 40oC NOMINAL AC VOLTAGE MAX AC CURRENT MAX OCPD RATING INVERTER MAKE INVERTER MODEL INVERTER RATINGS (Guide Section 4) 1) IF UTILITY REQUIRES A VISIBLE-BREAK SWITCH, DOES THIS SWITCH MEET THE REQUIREMENT? YES NO N/A 2) IF GENERATION METER REQUIRED, DOES THIS METER SOCKET MEET THE REQUIREMENT? YES NO N/A 3) SIZE PHOTOVOLTAIC POWER SOURCE (DC) CONDUCTORS BASED ON MAX CURRENT ON NEC 690.53 SIGN OR OCPD RATING AT DISCONNECT 4) SIZE INVERTER OUTPUT CIRCUIT (AC) CONDUCTORS ACCORDING TO INVERTER OCPD AMPERE RATING. (See Guide Section 9) 5) TOTAL OF ______ INVERTER OUTPUT CIRCUIT OCPD(s), ONE FOR EACH MICRO- INVERTER CIRCUIT. DOES TOTAL SUPPLY BREAKERS COMPLY WITH 120% BUSBAR EXCEPTION IN 690.64(B)(2)(a)? YES NO NOTES FOR INVERTER CIRCUITS (Guide Section 8 and 9): 1.) LOWEST EXPECT AMBIENT TEMPERATURE BASED ON ASHRAE MINIMUM MEAN EXTREME DRY BULB TEMPERATURE FOR ASHRAE LOCATION MOST SIMILAR TO INSTALLATION LOCATION. LOWEST EXPECTED AMBIENT TEMP ____oC 2.) HIGHEST CONTINUOUS AMBIENT TEMPERATURE BASED ON ASHRAE HIGHEST MONTH 2% DRY BULB TEMPERATURE FOR ASHRAE LOCATION MOST SIMILAR TO INSTALLATION LOCATION. HIGHEST CONTINUOUS TEMPERATURE ____oC 2.) 2009 ASHRAE FUNDAMENTALS 2% DESIGN TEMPERATURES DO NOT EXCEED 47oC IN THE UNITED STATES (PALM SPRINGS, CA IS 44.1 oC). FOR LESS THAN 9 CURRENT-CARRYING CONDUCTORS IN ROOF-MOUNTED SUNLIT CONDUIT AT LEAST 0.5" ABOVE ROOF AND USING THE OUTDOOR DESIGN TEMPERATURE OF 47oC OR LESS (ALL OF UNITED STATES), a) 12 AWG, 90 oC CONDUCTORS ARE GENERALLY ACCEPTABLE FOR MODULES WITH Isc OF 7.68 AMPS OR LESS WHEN PROTECTED BY A 12-AMP OR SMALLER FUSE. b) 10 AWG, 90oC CONDUCTORS ARE GENERALLY ACCEPTABLE FOR MODULES WITH Isc OF 9.6 AMPS OR LESS WHEN PROTECTED BY A 15-AMP OR SMALLER FUSE. NOTES FOR ARRAY CIRCUIT WIRING (Guide Section 6 and 8 and Appendix E): OCPD = OVERCURRENT PROTECTION DEVICE NATIONAL ELECTRICAL CODE®REFERENCES SHOWN AS (NEC XXX.XX) NOTES FOR ALL DRAWINGS: SIGNS–SEE GUIDE SECTION 7 SIGN FOR DC DISCONNECT SIGN FOR INVERTER OCPD AND AC DISCONNECT (IF USED) No sign necessary since 690.51 marking on PV module covers needed information AC OUTPUT CURRENT NOMINAL AC VOLTAGE SOLAR PV SYSTEM AC POINT OF CONNECTION THIS PANEL FED BY MULTIPLE SOURCES (UTILITY AND SOLAR) Notes for Micro-Inverter Electrical Diagram CA Solar Group 7647 Hayvenhurst Ave Unit 26 Van Nuys CA 91406 Paul Czajka 2030 W Summer Wind, Santa Ana, CA 92704 6.11 2030 W Summer Wind03/28/23 Certificate Of Completion Envelope Id: 6B3C59C715A34C1BB55DE57CD00FE212 Status: Completed Subject: Complete with DocuSign: 2030 Signature form.pdf Source Envelope: Document Pages: 1 Signatures: 1 Envelope Originator: Certificate Pages: 4 Initials: 0 Armen (California Solar Group) Vahanyan AutoNav: Enabled EnvelopeId Stamping: Enabled Time Zone: (UTC-08:00) Pacific Time (US & Canada) 7647 Hayvenhurst Ave Unit 26 Van Nuys, CA 91406 info@casolargroup.com IP Address: 104.34.141.59 Record Tracking Status: Original 3/8/2023 1:42:51 PM Holder: Armen (California Solar Group) Vahanyan info@casolargroup.com Location: DocuSign Signer Events Signature Timestamp Paul Czajka paulmczajka@yahoo.com Security Level: Email, Account Authentication (None) Signature Adoption: Pre-selected Style Using IP Address: 76.81.86.146 Signed using mobile Sent: 3/8/2023 1:44:15 PM Viewed: 3/8/2023 1:48:50 PM Signed: 3/8/2023 1:49:14 PM Electronic Record and Signature Disclosure: Accepted: 3/8/2023 1:48:50 PM ID: a7757847-d179-4782-bab8-25752ce3e00c In Person Signer Events Signature Timestamp Editor Delivery Events Status Timestamp Agent Delivery Events Status Timestamp Intermediary Delivery Events Status Timestamp Certified Delivery Events Status Timestamp Carbon Copy Events Status Timestamp Witness Events Signature Timestamp Notary Events Signature Timestamp Envelope Summary Events Status Timestamps Envelope Sent Hashed/Encrypted 3/8/2023 1:44:15 PM Certified Delivered Security Checked 3/8/2023 1:48:50 PM Signing Complete Security Checked 3/8/2023 1:49:14 PM Completed Security Checked 3/8/2023 1:49:14 PM Payment Events Status Timestamps Electronic Record and Signature Disclosure 2030 W Summer Wind03/28/23 ELECTRONIC RECORD AND SIGNATURE DISCLOSURE From time to time, CA Solar (we, us or Company) may be required by law to provide to you certain written notices or disclosures. Described below are the terms and conditions for providing to you such notices and disclosures electronically through the DocuSign system. Please read the information below carefully and thoroughly, and if you can access this information electronically to your satisfaction and agree to this Electronic Record and Signature Disclosure (ERSD), please confirm your agreement by selecting the check-box next to ‘I agree to use electronic records and signatures’ before clicking ‘CONTINUE’ within the DocuSign system. Getting paper copies At any time, you may request from us a paper copy of any record provided or made available electronically to you by us. You will have the ability to download and print documents we send to you through the DocuSign system during and immediately after the signing session and, if you elect to create a DocuSign account, you may access the documents for a limited period of time (usually 30 days) after such documents are first sent to you. After such time, if you wish for us to send you paper copies of any such documents from our office to you, you will be charged a $0.00 per-page fee. You may request delivery of such paper copies from us by following the procedure described below. Withdrawing your consent If you decide to receive notices and disclosures from us electronically, you may at any time change your mind and tell us that thereafter you want to receive required notices and disclosures only in paper format. How you must inform us of your decision to receive future notices and disclosure in paper format and withdraw your consent to receive notices and disclosures electronically is described below. Consequences of changing your mind If you elect to receive required notices and disclosures only in paper format, it will slow the speed at which we can complete certain steps in transactions with you and delivering services to you because we will need first to send the required notices or disclosures to you in paper format, and then wait until we receive back from you your acknowledgment of your receipt of such paper notices or disclosures. Further, you will no longer be able to use the DocuSign system to receive required notices and consents electronically from us or to sign electronically documents from us. All notices and disclosures will be sent to you electronically Electronic Record and Signature Disclosure created on: 8/20/2020 7:10:58 PM Parties agreed to: Paul Czajka 2030 W Summer Wind03/28/23 Unless you tell us otherwise in accordance with the procedures described herein, we will provide electronically to you through the DocuSign system all required notices, disclosures, authorizations, acknowledgements, and other documents that are required to be provided or made available to you during the course of our relationship with you. To reduce the chance of you inadvertently not receiving any notice or disclosure, we prefer to provide all of the required notices and disclosures to you by the same method and to the same address that you have given us. Thus, you can receive all the disclosures and notices electronically or in paper format through the paper mail delivery system. If you do not agree with this process, please let us know as described below. Please also see the paragraph immediately above that describes the consequences of your electing not to receive delivery of the notices and disclosures electronically from us. How to contact CA Solar: You may contact us to let us know of your changes as to how we may contact you electronically, to request paper copies of certain information from us, and to withdraw your prior consent to receive notices and disclosures electronically as follows: To contact us by email send messages to: armen@casolargroup.com To advise CA Solar of your new email address To let us know of a change in your email address where we should send notices and disclosures electronically to you, you must send an email message to us at armen@casolargroup.com and in the body of such request you must state: your previous email address, your new email address. We do not require any other information from you to change your email address. If you created a DocuSign account, you may update it with your new email address through your account preferences. To request paper copies from CA Solar To request delivery from us of paper copies of the notices and disclosures previously provided by us to you electronically, you must send us an email to armen@casolargroup.com and in the body of such request you must state your email address, full name, mailing address, and telephone number. We will bill you for any fees at that time, if any. To withdraw your consent with CA Solar To inform us that you no longer wish to receive future notices and disclosures in electronic format you may: 2030 W Summer Wind03/28/23 i. decline to sign a document from within your signing session, and on the subsequent page, select the check-box indicating you wish to withdraw your consent, or you may; ii. send us an email to armen@casolargroup.com and in the body of such request you must state your email, full name, mailing address, and telephone number. We do not need any other information from you to withdraw consent.. The consequences of your withdrawing consent for online documents will be that transactions may take a longer time to process.. Required hardware and software The minimum system requirements for using the DocuSign system may change over time. The current system requirements are found here: https://support.docusign.com/guides/signer-guide- signing-system-requirements. Acknowledging your access and consent to receive and sign documents electronically To confirm to us that you can access this information electronically, which will be similar to other electronic notices and disclosures that we will provide to you, please confirm that you have read this ERSD, and (i) that you are able to print on paper or electronically save this ERSD for your future reference and access; or (ii) that you are able to email this ERSD to an email address where you will be able to print on paper or save it for your future reference and access. Further, if you consent to receiving notices and disclosures exclusively in electronic format as described herein, then select the check-box next to ‘I agree to use electronic records and signatures’ before clicking ‘CONTINUE’ within the DocuSign system. By selecting the check-box next to ‘I agree to use electronic records and signatures’, you confirm that: You can access and read this Electronic Record and Signature Disclosure; and You can print on paper this Electronic Record and Signature Disclosure, or save or send this Electronic Record and Disclosure to a location where you can print it, for future reference and access; and  Until or unless you notify CA Solar as described above, you consent to receive exclusively through electronic means all notices, disclosures, authorizations, acknowledgements, and other documents that are required to be provided or made available to you by CA Solar during the course of your relationship with CA Solar. 2030 W Summer Wind03/28/23 Rev: 7/15/2021 RESIDENTIAL PHOTOVOLTAIC CHECKLIST SOL-01 CBC 2019 Solar Photovoltaic (PV) Checklist for Detached SINGLE FAMILY RESIDENCES Only Instructions: The licensed contractor of record shall complete all sections, answer the ten questions and sign the certification section below. A copy of this form shall be attached to each of TWO sets of plans, of minimum 11” x 17” size. If answering NO to any of the questions, plan check shall be required. Project Address: Contractor Company Name: Contractor License Number: YES NO Are the following applicable to the proposed project? 1.   Will the PV system layout provide the required three-foot wide clear access pathways per Section 605.11 of the California Fire Code, and is this shown on the roof plan? 2.   Will the PV system be installed on a roof having only one roofing layer with no overlays? 3.   Will the PV array be flush mounted to the existing roof so that the plane of the modules (panels) are parallel to the plane of the roof? 4.   Will the PV system weigh maximum 4 pounds per square feet or less? 5.   Will the PV system be installed where the modules do not overhang any roof edges (such as eaves, gabled ends, ridges and hips)? 6.   Will the PV system be installed with a space of 2” minimum to 10” maximum between the underside of modules and the surface of the roof? 7.   Will the PV system be installed without using any ballast system or counter-weight system? 8.   Will the anchors be installed with a maximum horizontal anchor spacing of 6 feet and is this maximum horizontal spacing shown on the plans? 9.   Will the minimum 5/16” lag screws be installed with a minimum of 2-1/2 inch embedment into roof rafters (with pre-drilled holes) and is this minimum embedment shown on the plans? 10.   Are ALL the structural pages of the plans stamped and signed by a California licensed professional engineer? (including project specific site plan, PV layout, anchorage spacing, anchorage details and manufacturer’s PV support information.) I certify under penalty of perjury under the laws of the State of California that the above is true: Print Name: Signature: Phone Number: Date: Email Address: Planning & Building Agency Building Safety Division 20 Civic Center Plaza P.O. Box 1988 (M-19) Santa Ana, CA 92702 (714) 647-5800 www.santa-ana.org 2030 W Summer Wind, Santa Ana, CA 92704 CA Solar Group 1067781 // C-10 Logan Weinberg 310-402-4962 info@casolargroup.com 03/08/2023 2030 W Summer Wind03/28/23 CITY OF SANTA ANA SOLAR PERMIT APPLICATION WORKSHEET PLEASE PRINT REV: 8/29/19 PROJECT ADDRESS: SUITE: SAPIN # USE OF BUILDING: RESIDENTIAL COMMERCIAL INDUSTRIAL OTHER MASTER ID# NATURE OF WORK: SOLAR P.V. SYSTEM SOLAR WATER HEATING/COLLECTOR SYSTEM OTHER JOB DESCRIPTIO N : ________________________________________________________________________________________________________________ ________________________________________________________________________________________________________________ ________________________________________________________________________________________________________________ ________________________________________________________________________________________________________________ ________________________________________________________________________________________________________________ ________________________________________________________________________________________________________________ ________________________________________________________________________________________________________________ BUILDING OWNER’S NAME: PHONE NO: ADDRESS:CITY: STATE:ZIP: TENANT’S NAME (Comm/Ind):PHONE NO: CONTRACTOR’S NAME:STATE CONTR. #:LICENSE CLASS: PHONE NO: ADDRESS:CITY: STATE: ZIP: WORKERS COMP. POLICY#: EXP. DATE:INSURANCE COMPANY: SANTA ANA BUS. LIC. #: ARCHITECT/ENGINEER: STATE LICENSE #: PHONE NO: ADDRESS:CITY: STATE:ZIP: CONTACT NAME:PHONE NO: E-MAIL ADDRESS: BLDG. FEE $ OCC. GROUP:P/C FEE PD $ VALUATION: $ SUBMITTAL DATE:____________________TYPE OF CONSTR: FLOOD ZONE:___________________PROCESSED________________________ PLANNING OK TO CHECK & DATE:__________________________ BLDG. DEPT. APPROVAL & DATE:___________________________ PLNG CONDITIONS: _________________________________________________________________________________________________ NUMBER OF PANELS:___________________ SYSTEM kWA:_________________________ 2030 W Summer Wind, Santa Ana, CA 92704 SYSTEM SIZE: DC STC: 6.56 / kWAC SIZE: 6.11 kWSOLAR MODULES: (16) Silfab 410W Modules (SIL-410BG) INVERTER: (16) ENPHASE IQ8A MICROINVERTER (IQ8A-72-2-US (120/240V) [240] [SI1]) EXISTING MSP BUS: 125A EXISTING MAIN BREAKER: _125A_ NEW PV BREAKER: 30A_ 16 DC STC: 6.56 / kWAC SIZE: 6.11 Paul Czajka 2030 W Summer Wind, Santa Ana, CA 92704 Santa Ana CA 92704 3107174342 CA Solar Group 1067781 C-10 310-402-4962 7647 HAYVENHURST AVE STE #26 Van Nuys CA 91406 9286543 10/22/23 State Comp. Insurance fund Logan Weinberg 310-402-4962 info@casolargroup.com SFD Residential NO 15,000 2030 W Summer Wind03/28/23 CITY OF SANTA ANA DEVELOPMENT FEES WORKSHEET -- ELECTRICAL PERMIT APP FOR ELECTRICAL 06-30-2020 APP-02 CEC2019 Project Address:Contractor: Tenant Name:Address: Building Owner: City: St.: Zip: Address: Contractor License No.: City: St.: Zip:Contractor Email: Phone: Phone: Contact Person: Contact E-Mail Strongly Recommended PLEASE PRINT: Contact Phone: NEW BUILDING OCCUPANCY CHANGE ELECTRICAL ITEM Count $ EACH ELECTRICAL ITEM Count $ EACH 125 Volt Receptacle Outlets 1.57 LOW VOLTAGE SYSTEMS – EACH: phone, data outlet, speaker, thermostat, door holder, doorbell, pull station, smoke detector, alarm device, card reader, etc. (circle items)Light Switches, Occupancy Sensors 1.70 Light Fixtures 1.13 COMMERCIAL: Air Conditioners, Heat Pumps 104.40 FIRST 10 devices or outlets 36.50 Factory-Wired Units (Solid Hook-Ups) 26.71 Additional devices, each 3.45 Dedicated Circuits (15 or 20 AMP Receptacles) 26.71 Each control panel, power supply annunciator, switch or aux equip.17.39Time Clock, Photo-Cell, Time Switch 13.03 Track-Light, Cable Tray, Special Raceway, Plugmold, Under-Floor Duct, Plug-In Busway, Surface Duct, Etc. (Each 100 Feet or any fraction thereof) 26.71 RESIDENTIAL: Single Dwelling unit 39.56 Each add’l dwelling unit (2 to 20) 34.80 Each add’l unit (over 20) 21.24 SERVICE METERS & PANELS: Service Meter, Reset Meter, Subpanel, Switchboard, Motor Control Center, Transfer Switch, Busduct, or other Distribution Equipment changes or modifications. (circle items as needed) MISCELLANEOUS Light Standard (Pole) with 1 Fixture 26.72 Additional Fixtures – same pole 0.00 Power Pole (Temporary) 111.04 Use this column if a Service All others here Additional distribution poles 26.72 Under 400 amperes 57.40 Swimming Pool, Spa, Fountain 130.46 400 amperes to 1199 amperes 156.51 Above ground spa 56.37 1200 amperes and over 260.79 Demolition 52.21 POWER APPARATUS: Motor, Transformer, Welder, Industrial Equipment, Oven, Rectifier, Generator, Surge Arrestor, Water Heater, Photovoltaic Panel, or other Power Equipment changes or modifications. (circle items as needed) Per HP, kW, or kVA SIGNS & neon/LED decorative lighting ($200 refundable sign bond) 80.95 NEW or TOTAL REWIRE for SINGLE FAMILY DWELLINGS SFD Per square foot .16 0 to 1 3.84 Garage Per square foot .16 Over 1 to 10 25.09 SUBTOTAL $ Over 10 to 50 49.78 P/C 65% of SUBTOTAL $ Over 50 to 100 113.06 MIN. FEE – (Nonresidential) $ 79.06 Over 100 to 500 162.45 ISSUANCE & General Plan Surcharge $ 59.30 + 23.79 = $8 3.09 Over 500 202.92 TOTAL $ OFFICE USE ONLY BLDG PMT RECEIPT BY DATE OCCUPANCY TYPE P/CPAID 2030 W Summer Wind, Santa Ana, CA 92704 Paul Czajka 2030 W Summer Wind, Santa Ana, CA 92704 Santa Ana CA 92704 3107174342 CA Solar Group 7647 HAYVENHURST AVE STE #26 VAN NUYS, CA 91406 C-10 /// 1067781 info@casolargroup.com 310-402-4962 Logan Weinberg 310-402-4962 2030 W Summer Wind03/28/23 Rev: 7/15/2021 RESIDENTIAL PHOTOVOLTAIC CHECKLIST SOL-01 CBC 2019 Solar Photovoltaic (PV) Checklist for Detached SINGLE FAMILY RESIDENCES Only Instructions: The licensed contractor of record shall complete all sections, answer the ten questions and sign the certification section below. A copy of this form shall be attached to each of TWO sets of plans, of minimum 11” x 17” size. If answering NO to any of the questions, plan check shall be required. Project Address: Contractor Company Name: Contractor License Number: YES NO Are the following applicable to the proposed project? 1.   Will the PV system layout provide the required three-foot wide clear access pathways per Section 605.11 of the California Fire Code, and is this shown on the roof plan? 2.   Will the PV system be installed on a roof having only one roofing layer with no overlays? 3.   Will the PV array be flush mounted to the existing roof so that the plane of the modules (panels) are parallel to the plane of the roof? 4.   Will the PV system weigh maximum 4 pounds per square feet or less? 5.   Will the PV system be installed where the modules do not overhang any roof edges (such as eaves, gabled ends, ridges and hips)? 6.   Will the PV system be installed with a space of 2” minimum to 10” maximum between the underside of modules and the surface of the roof? 7.   Will the PV system be installed without using any ballast system or counter-weight system? 8.   Will the anchors be installed with a maximum horizontal anchor spacing of 6 feet and is this maximum horizontal spacing shown on the plans? 9.   Will the minimum 5/16” lag screws be installed with a minimum of 2-1/2 inch embedment into roof rafters (with pre-drilled holes) and is this minimum embedment shown on the plans? 10.   Are ALL the structural pages of the plans stamped and signed by a California licensed professional engineer? (including project specific site plan, PV layout, anchorage spacing, anchorage details and manufacturer’s PV support information.) I certify under penalty of perjury under the laws of the State of California that the above is true: Print Name: Signature: Phone Number: Date: Email Address: Planning & Building Agency Building Safety Division 20 Civic Center Plaza P.O. Box 1988 (M-19) Santa Ana, CA 92702 (714) 647-5800 www.santa-ana.org 2030 W Summer Wind, Santa Ana, CA 92704 CA Solar Group 1067781 // C-10 Logan Weinberg 310-402-4962 info@casolargroup.com 03/08/2023 2030 W Summer Wind03/28/23 Hello Santa Ana Building and Safety, I am writing to confirm that CA Solar Group is authorized to submit, pull permits, install solar, and host inspection for my property at 2030 W Summer Wind in Santa Ana. Please reach out to CA Solar Group in regards to any questions or concerns about the Solar project. If you need to speak to me, you may contact me at paulmczajka@yahoo.com or 310-717-4342. Thank you in advance for your assistance. Homeowner: Paul Czajka Signature: Date DocuSign Envelope ID: 6B3C59C7-15A3-4C1B-B55D-E57CD00FE212 3/8/2023 | 13:49 PST 2030 W Summer Wind03/28/23 Unique Solar Design 13535 Valerio Street Apt 204 Van Nuys CA, 91405 USA 8088008238 USER:Hrach Ghambaryan COMPANY NAME:Unique Solar Design SRC JOB ID:38754 JOB REPORT DATE:2023-03-09/Rev A JOB NUMBER:904 JOB NAME:Paul Czajka JOB ADDRESS:2030 West Summer Wind Santa Ana, CA 92704 Phong Truong, P.E. Date: 2023.03.09 10:37:36 -0800 Program Version: 2020-05-08:7 2030 W Summer Wind03/28/23 1/2 gyp. Bd. 0 23.4 2x6@24 0 0.0 5/16 2.5 40 2.68 7 2Rail Flat Tile 25 18 InteriorBearingWall No 6.00 3.08 Yes C 110 74 41 Gable Roof Yes 2.00 Both 36 2030 W Summer Wind03/28/23 2030 W Summer Wind03/28/23 9.30 1.50 1.00 1.00 0.65 0.50 2.20 12.80 3.35 25.60 N/A N/A 1.00 110 0.85 C 1.00 1.00 0.94 24.72 0.63 2030 W Summer Wind03/28/23 18.50 0.63 2.00 31.21 2.50 58.52 2.62 61.27 10.25 0.79 2.00 39.13 2.50 73.37 2.98 87.59 2030 W Summer Wind03/28/23 42.00 0.49 1.31 16.00 42.00 0.49 0.39 16.00 235.00 940.00 318.13 295.5% 621.27 151.3% 651.86 144.2% 2030 W Summer Wind03/28/23 40.00 49.58 N/A 240.81 105.68 N/A 346.50 2.35 321.1% 224.75 586.15 3.11 243.0% 2030 W Summer Wind03/28/23 0 49.58 240.81 1.78 425.0% 0 180.35 499.81 2.65 284.9% 21.65 22.28 2.9% 2030 W Summer Wind03/28/23 149.31 200.85 1.07 709.0% 2030 W Summer Wind03/28/23 3.60 7.56 1.05 900 2030 W Summer Wind03/28/23 6 Ft.6 Ft. 1. Installers to verify rafter size, spacing and sloped spans, and notify the E.O.R of any discrepancies before proceeding. 2. Any rotted or damaged rafters shall be replaced prior to proceeding. 6 Ft. Phong Truong, P.E. Date: 2023.03.09 10:37:37 -0800 SRC Job Id: 38754 Ceiling Type: 1/2 gyp. Bd. Collar Tie Space: 0 Coverage %: 23.4 Frame Size: 2x6@24 Ground Snow (psf): 0 Sloped Roof Snow Load (psf): 0 Lag Screw Diameter (in): 5/16 Lag Screw Embedment (in): 2.5 Overall Span (ft): 40 PV Orientation: Both PV Weight (psf): 2.68 Rafter Sloped Span (ft): 7 Rail System: 2Rail Roofing Type: Flat Tile Roof Mean Height (ft): 25 Roof Slope (degrees): 18 Roof Type: InteriorBearingWall Sloped Ceiling?: No Standoff Max. Horz. Space (ft): 6 Standoff Max. Vert. Space (ft): 3.083 Standoff Staggered?: Yes Wind Exposure: C Wind Speed (mph): 110 Unique Solar Design 13535 Valerio Street Apt 204 Van Nuys, CA 91405 USA 904 Paul Czajka 2030 West Summer Wind Santa Ana, CA 92704 03-09-2023 2030 W Summer Wind03/28/23 DATE: 03-09-2023/Rev A FOR: Unique Solar Design JOB: Paul Czajka 13535 Valerio Street Apt 204 2030 West Summer Wind Van Nuys, CA 91405 Santa Ana, CA 92704 USA To Whom It May Concern This letter is to certify that we have performed a structural analysis of the existing roof members that are to support photovoltaic panels, as shown on the attached report. The calculations were performed in accordance with the latest editions of IBC, NDS, ASCE/SEI, CBC, and IRC, and the latest edition of the building codes for the state of California. Our analysis was based on the following design criteria: Ground Snow (psf)0 psf Sloped Snow (psf), reduced per ASCE, Sect. 7.4 0 psf Basic Wind Speed (mph):110 mph Roof Slope:18 degrees The PV module orientation:Both The maximum horizontal roof mount spacing:6 ft. The maximum vertical roof mount spacing:3.083 ft. Staggered roof mounts required?Yes Based on this analysis, we can certify that the individual existing roof framing members that support the PV panels; and the individual roof members as described in the attached report; are adequate to support the design loads as required by the various codes. This includes Dead Loads (including the weight of the PV panels), Live Loads, Snow Loads, and Wind Loads, on the roof members that support the PV panels, combined as required in the codes. If you have any questions on this or need further clarification, please contact us at your convenience. Sincerely, Paul Truong, P.E. NOTE: 1. Prior to commencement of work, the Solar Installer shall verify that the roof framing sizes, spacing, and spans (between supports), are as noted in these plans. The Engineer of Record must be notified if any discrepancies are discovered, before proceeding. 2. These plans are Stamped for Structural Code compliance of the roof members that support the PV solar system only. 3. These plans are not stamped for rain water leakage prevention. 4. As a precaution, old or wet snow should be removed from the roof, if the snow builds up to 18" or more. Phong Truong, P.E. Date: 2023.03.09 10:37:36 -0800 2030 W Summer Wind03/28/23 Date of Report: 03-09-2023/Rev A Job Name: Paul Czajka Data Input by: Hrach Ghambaryan Job Number: 904 Contact E-mail: hrach@uniquesolardesign.com Job Address: 2030 West Summer Wind Contact Phone: ​(747) 217-1107 Santa Ana, CA 92704 ABSTRACT This Report is based on Engineering calculations using the input data supplied by the user, listed under Current Input Data. The user input has not been independently reviewed by a licensed Professional Engineer for appropriateness or accuracy, unless Stamped by a P.E. This Report indicates Compliance/Non-Compliance with the reference Codes listed below. The following items have been checked for Code Compliance: - Load Combination #1: Wind Uplift on the Standoff attachment to the Roof Framing members: Wind Uplift - 0.6 * DL Solar - Load Combination #2: Supporting Rafter Strength with: DL Rf + DL Solar + Roof Live Load - Load Combination #3: Supporting Rafter Strength with: DL Rf + DL Solar + Wind Down - Load Combination #4: Supporting Rafter Strength with: DL Rf + DL Solar + Snow - Load Combination #5: Supporting Rafter Strength with: DL Rf + DL Solar + .75Wind + .75Snow - Load Combination #6: Check Additional Seismic Load - Load Combination #7: Supporting Rafter Strength with: Wind Up - 0.6 * (DL Rf + DL Solar) Job Information Data Input By:Hrach Ghambaryan Job Number:904 Job Name:Paul Czajka Job Address:2030 West Summer Wind City, State:Santa Ana, CA 92704 Current Input Data Payment Method Invoice Roof Type InteriorBearingWall Ceiling Type 1/2 gyp. Bd. Collar Tie Space 0 Coverage % 23.4 Frame Size 2x6@24 Ground Snow (psf) 0 Sloped Roof Snow Load (psf) 0 Lag Screw Diam. (in) 5/16 Lag Screw Embed. (in) 2.5 Overall Span (ft) 40 PV Weight (psf) 2.68 PV Module Orientation Both Rafter Span (ft) 7 Rail System 2Rail Roof Mean Height (ft) 25 Roof Slope (degrees) 18 Roofing Type Flat Tile Sloped Ceiling No Max. Horizontal Roof Mount(ft) 6 Max. Vertical Roof Mounts (ft) 3.083 Standoff Staggered Yes Wind Exposure C Wind Speed (mph) 110 2030 W Summer Wind03/28/23 PV SYSTEM AS INDICATED Project Name Project Address Project Description SHEET SIZE 11'' X 17'' ANSI B SHEET NUMBER General Notes Date Scale Project MARCH 06, 2023 Paul Czajka 2030 W Summer Wind, Santa Ana, CA 92704 D1 Drawn By: Unique Solar Design California Solar Group CSLB # 1067781 C-10 Contractor Note 7647 Hayvenhurst Ave., Unit 26 Van Nuys, CA 91406 casolargroup.com info@casolargroup.com Phone Number: +1 818 658 2362 Address & Phone Number Signature Company Logo 6.56KW DC Roof Mounted PV Electrical System 16-Silfab 410W PV Modules 16-IQ8A Enphase Microinverters 2030 W Summer Wind03/28/23 PV SYSTEM AS INDICATED Project Name Project Address Project Description SHEET SIZE 11'' X 17'' ANSI B SHEET NUMBER General Notes Date Scale Project MAY 19, 2023 Paul Czajka 2030 W Summer Wind, Santa Ana, CA 92704 D1 Drawn By: Unique Solar Design California Solar Group CSLB # 1067781 C-10 Contractor Note 7647 Hayvenhurst Ave., Unit 26 Van Nuys, CA 91406 casolargroup.com info@casolargroup.com Phone Number: +1 818 658 2362 Address & Phone Number Signature Company Logo 6.56KW DC Roof Mounted PV Electrical System 16-Silfab 410W PV Modules 16-IQ8A Enphase Microinverters 2030 W Summer Wind06/06/23 PV SYSTEM AS INDICATED Project Name Project Address Project Description SHEET SIZE 11'' X 17'' ANSI B SHEET NUMBER General Notes Date Scale Project MARCH 06, 2023 Paul Czajka 2030 W Summer Wind, Santa Ana, CA 92704 D2 Drawn By: Unique Solar Design California Solar Group CSLB # 1067781 C-10 Contractor Note 7647 Hayvenhurst Ave., Unit 26 Van Nuys, CA 91406 casolargroup.com info@casolargroup.com Phone Number: +1 818 658 2362 Address & Phone Number Signature Company Logo 6.56KW DC Roof Mounted PV Electrical System 16-Silfab 410W PV Modules 16-IQ8A Enphase Microinverters 2030 W Summer Wind03/28/23 PV SYSTEM AS INDICATED Project Name Project Address Project Description SHEET SIZE 11'' X 17'' ANSI B SHEET NUMBER General Notes Date Scale Project MAY 19, 2023 Paul Czajka 2030 W Summer Wind, Santa Ana, CA 92704 D2 Drawn By: Unique Solar Design California Solar Group CSLB # 1067781 C-10 Contractor Note 7647 Hayvenhurst Ave., Unit 26 Van Nuys, CA 91406 casolargroup.com info@casolargroup.com Phone Number: +1 818 658 2362 Address & Phone Number Signature Company Logo 6.56KW DC Roof Mounted PV Electrical System 16-Silfab 410W PV Modules 16-IQ8A Enphase Microinverters 2030 W Summer Wind06/06/23 PV SYSTEM AS INDICATED Project Name Project Address Project Description SHEET SIZE 11'' X 17'' ANSI B SHEET NUMBER General Notes Date Scale Project MARCH 06, 2023 Paul Czajka 2030 W Summer Wind, Santa Ana, CA 92704 Drawn By: Unique Solar Design California Solar Group CSLB # 1067781 C-10 Contractor Note 7647 Hayvenhurst Ave., Unit 26 Van Nuys, CA 91406 casolargroup.com info@casolargroup.com Phone Number: +1 818 658 2362 Address & Phone Number Signature Company Logo D3 6.56KW DC Roof Mounted PV Electrical System 16-Silfab 410W PV Modules 16-IQ8A Enphase Microinverters 2030 W Summer Wind03/28/23 PV SYSTEM AS INDICATED Project Name Project Address Project Description SHEET SIZE 11'' X 17'' ANSI B SHEET NUMBER General Notes Date Scale Project MAY 19, 2023 Paul Czajka 2030 W Summer Wind, Santa Ana, CA 92704 Drawn By: Unique Solar Design California Solar Group CSLB # 1067781 C-10 Contractor Note 7647 Hayvenhurst Ave., Unit 26 Van Nuys, CA 91406 casolargroup.com info@casolargroup.com Phone Number: +1 818 658 2362 Address & Phone Number Signature Company Logo D3 6.56KW DC Roof Mounted PV Electrical System 16-Silfab 410W PV Modules 16-IQ8A Enphase Microinverters 2030 W Summer Wind06/06/23 PV SYSTEM AS INDICATED Project Name Project Address Project Description SHEET SIZE 11'' X 17'' ANSI B SHEET NUMBER General Notes Date Scale Project MARCH 06, 2023 Paul Czajka 2030 W Summer Wind, Santa Ana, CA 92704 D4 Drawn By: Unique Solar Design California Solar Group CSLB # 1067781 C-10 Contractor Note 7647 Hayvenhurst Ave., Unit 26 Van Nuys, CA 91406 casolargroup.com info@casolargroup.com Phone Number: +1 818 658 2362 Address & Phone Number Signature Company Logo 6.56KW DC Roof Mounted PV Electrical System 16-Silfab 410W PV Modules 16-IQ8A Enphase Microinverters 2030 W Summer Wind03/28/23 PV SYSTEM AS INDICATED Project Name Project Address Project Description SHEET SIZE 11'' X 17'' ANSI B SHEET NUMBER General Notes Date Scale Project MAY 19, 2023 Paul Czajka 2030 W Summer Wind, Santa Ana, CA 92704 D4 Drawn By: Unique Solar Design California Solar Group CSLB # 1067781 C-10 Contractor Note 7647 Hayvenhurst Ave., Unit 26 Van Nuys, CA 91406 casolargroup.com info@casolargroup.com Phone Number: +1 818 658 2362 Address & Phone Number Signature Company Logo 6.56KW DC Roof Mounted PV Electrical System 16-Silfab 410W PV Modules 16-IQ8A Enphase Microinverters 2030 W Summer Wind06/06/23 PV SYSTEM AS INDICATED Project Name Project Address Project Description SHEET SIZE 11'' X 17'' ANSI B SHEET NUMBER General Notes Date Scale Project MARCH 06, 2023 Paul Czajka 2030 W Summer Wind, Santa Ana, CA 92704 D5 Drawn By: Unique Solar Design California Solar Group CSLB # 1067781 C-10 Contractor Note 7647 Hayvenhurst Ave., Unit 26 Van Nuys, CA 91406 casolargroup.com info@casolargroup.com Phone Number: +1 818 658 2362 Address & Phone Number Signature Company Logo 6.56KW DC Roof Mounted PV Electrical System 16-Silfab 410W PV Modules 16-IQ8A Enphase Microinverters 2030 W Summer Wind03/28/23 PV SYSTEM AS INDICATED Project Name Project Address Project Description SHEET SIZE 11'' X 17'' ANSI B SHEET NUMBER General Notes Date Scale Project MAY 19, 2023 Paul Czajka 2030 W Summer Wind, Santa Ana, CA 92704 D5 Drawn By: Unique Solar Design California Solar Group CSLB # 1067781 C-10 Contractor Note 7647 Hayvenhurst Ave., Unit 26 Van Nuys, CA 91406 casolargroup.com info@casolargroup.com Phone Number: +1 818 658 2362 Address & Phone Number Signature Company Logo 6.56KW DC Roof Mounted PV Electrical System 16-Silfab 410W PV Modules 16-IQ8A Enphase Microinverters 2030 W Summer Wind06/06/23 PV SYSTEM AS INDICATED Project Name Project Address Project Description SHEET SIZE 11'' X 17'' ANSI B SHEET NUMBER General Notes Date Scale Project MARCH 06, 2023 Paul Czajka 2030 W Summer Wind, Santa Ana, CA 92704 D6 Drawn By: Unique Solar Design California Solar Group CSLB # 1067781 C-10 Contractor Note 7647 Hayvenhurst Ave., Unit 26 Van Nuys, CA 91406 casolargroup.com info@casolargroup.com Phone Number: +1 818 658 2362 Address & Phone Number Signature Company Logo 6.56KW DC Roof Mounted PV Electrical System 16-Silfab 410W PV Modules 16-IQ8A Enphase Microinverters 2030 W Summer Wind03/28/23 PV SYSTEM AS INDICATED Project Name Project Address Project Description SHEET SIZE 11'' X 17'' ANSI B SHEET NUMBER General Notes Date Scale Project MAY 19, 2023 Paul Czajka 2030 W Summer Wind, Santa Ana, CA 92704 D6 Drawn By: Unique Solar Design California Solar Group CSLB # 1067781 C-10 Contractor Note 7647 Hayvenhurst Ave., Unit 26 Van Nuys, CA 91406 casolargroup.com info@casolargroup.com Phone Number: +1 818 658 2362 Address & Phone Number Signature Company Logo 6.56KW DC Roof Mounted PV Electrical System 16-Silfab 410W PV Modules 16-IQ8A Enphase Microinverters 2030 W Summer Wind06/06/23 PV SYSTEM AS INDICATED Project Name Project Address Project Description SHEET SIZE 11'' X 17'' ANSI B SHEET NUMBER General Notes Date Scale Project MARCH 06, 2023 Paul Czajka 2030 W Summer Wind, Santa Ana, CA 92704 T GENERAL NOTES:APPLICABLE CODES SHEET INDEX TITLE PAGE LINE DIAGRAM CODE REQUIRED SIGNAGE ATTACHMENT LAYOUT MODULE DATA SHEET SITE PLAN PROJECT VICINITY MAP PROJECT SATELLITE VIEW T PV1 PV2 PV3 PV4 D1 D2 D3 D4 D5 D6 D7 INVERTER DATA SHEET ALL ELECTRICAL WORK TO BE INSTALLED BY A QUALIFIED AND LICENSED ELECTRICAL CONTRACTOR. ALL SOLAR MODULES SHALL BE UL LISTED 1703 & CEC APPROVED. ALL INVERTERS SHALL BE UL LISTED 1741 CERTIFIED & CEC APPROVED. ALL ELECTRICAL COMPONENTS AND MATERIALS SHALL BE LISTED FOR IT'S PURPOSE AND INSTALLED IN A WORKMAN LIKE MANNER. ALL OUTDOOR EQUIPMENT SHALL MEET APPROPRIATE NEMA STANDARDS. THE ELECTRICAL CONTRACTOR IS ADVISED THAT ALL DRAWINGS AND COMPONENT MANUALS ARE TO BE UNDERSTOOD PRIOR TO INSTALLATION. THE CONTRACTOR IS ADVISED TO HAVE ALL SWITCHES IN THE OFF POSITION AND FUSES REMOVED PRIOR TO INSTALLATION OF FUSE-BEARING COMPONENTS. THIS SYSTEM IS INTENDED TO BE OPERATED IN PARALLEL WITH THE UTILITY SERVICE PROVIDER. ANTI-ISLANDING PROTECTION IS A REQUIREMENT OF UL 1741 AND IS INTENDED TO PREVENT THE OPERATION OF THE PV SYSTEM WHEN THE UTILITY GRID IS NOT OPERATIONAL. PERMISSION TO OPERATE THE SYSTEM IS NOT AUTHORIZED UNTIL FINAL INSPECTIONS AND APPROVALS ARE OBTAINED FROM THE LOCAL AUTHORITY HAVING JURISDICTION AND THE LOCAL UTILITY SERVICE PROVIDER. THE METHOD OF ATTACHMENT CREATES A UNIFIED STRUCTURE TO MEET DEAD LOAD, WIND LOAD, AND SEISMIC REQUIREMENTS. SOLAR MODULES WILL BE SECURED TO THE EXISTING ROOF AS SPECIFIED ON THE STRUCTURAL SHEETS. EXISTING ROOF EQUIPMENT WILL NOT BE EFFECTED BY THE PV SYSTEM. ALL STRUCTURAL DESIGN AND INSTALLATION COMPONENTS ARE THE RESPONSIBILITY OF OTHERS AND OUTSIDE THE SCOPE OF THIS DOCUMENT. ALL FASTENERS SHALL BE CORROSION RESISTANT APPROPRIATE FOR SITE CONDITIONS. CONNECTORS SHALL BE TORQUED PER DEVICE LISTING OR ENGINEERING RECOMMENDATIONS. ALL ROOFING REPAIR MUST MAINTAIN EXISTING CLASS AND TYPE OF ROOF AND ALL WORK SHALL BE IN ACCORDANCE WITH THE ROOF IN MANUFACTURER'S INSTALLATION REQUIREMENTS. PROJECT DESCRIPTION: SYSTEM SIZE: DC STC: ____ kW AC SIZE: ____ kW SOLAR MODULES: (___) INVERTER: (___) MOUNTING SYSTEM: EXISTING MSP BUS: ____ EXISTING MAIN BREAKER: ____ NEW PV BREAKER: ____ RACKING DATA SHEET GROUNDING SPECS RACKING DETAILSD8 PROPERTY DETAILS: TWO STORY BUILDING BUILDING OCCUPANCY GROUPS (R-3) TYPE OF CONSTRUCTION (V-B) AUTOMATIC FIRE SPRINKLERS (NO) ROOF TYPE: ROOF STRUCTURE: PARCEL NUMBER: 41222216 LOT AREA: 3,078 SQFT LIVING AREA: 1,379 SQFT SMOKE ALARMS AND CARBON MONOXIDE ALARMS SHALL BE PROVIDED FOR THE DWELLING PER CRC R314 AND R315 Drawn By: Unique Solar Design California Solar Group CSLB # 1067781 C-10 Contractor Note 7647 Hayvenhurst Ave., Unit 26 Van Nuys, CA 91406 casolargroup.com info@casolargroup.com Phone Number: +1 818 658 2362 Address & Phone Number Signature Company Logo 16 2022 CALIFORNIA RESIDENTIAL CODE 2022 CALIFORNIA ELECTRICAL CODE 2022 CALIFORNIA BUILDING CODE 2022 CALIFORNIA GREEN BUILDING STANDARDS CODE 2022 CALIFORNIA ENERGY CODE 2022 CALIFORNIA MECHANICAL CODE 2022 CALIFORNIA PLUMBING CODE 125A 125A 30A 6.56 6.11 RAFTERS 2'' x 6'' @ 24'' O.C FLAT CONCRETE TILE ENPHASE IQ8A MICROINVERTER (IQ8A-72-2-US (120/240V) [240] [SI1]) IRONRIDGE XR10 RACKING RACKING CERTIFICATIONS 16 6.56KW DC Roof Mounted PV Electrical System 16-Silfab 410W PV Modules 16-IQ8A Enphase Microinverters ENPHASE COMBINER DATA SHEET Silfab 410W Modules (SIL-410BG) ATTACHMENT DATA SHEET N BLDG # 101114405 ISS. 03/24/23 ELEC # 20179136 ISS. 03/24/23 The scope of the plans is for the installation of the solar photovoltaic system only and the approval is subject to compliance with all applicable city and state codes and regulations regarding construction. The approval of the plans does not constitute any certification of the accuracy, completeness, or building permit status of the existing buildings and structures as shown. 2030 W Summer Wind03/28/23 PV SYSTEM AS INDICATED Project Name Project Address Project Description SHEET SIZE 11'' X 17'' ANSI B SHEET NUMBER General Notes Date Scale Project MAY 19, 2023 Paul Czajka 2030 W Summer Wind, Santa Ana, CA 92704 T GENERAL NOTES:APPLICABLE CODES SHEET INDEX TITLE PAGE LINE DIAGRAM CODE REQUIRED SIGNAGE ATTACHMENT LAYOUT MODULE DATA SHEET SITE PLAN PROJECT VICINITY MAP PROJECT SATELLITE VIEW T PV1 PV2 PV3 PV4 D1 D2 D3 D4 D5 D6 D7 INVERTER DATA SHEET ALL ELECTRICAL WORK TO BE INSTALLED BY A QUALIFIED AND LICENSED ELECTRICAL CONTRACTOR. ALL SOLAR MODULES SHALL BE UL LISTED 1703 & CEC APPROVED. ALL INVERTERS SHALL BE UL LISTED 1741 CERTIFIED & CEC APPROVED. ALL ELECTRICAL COMPONENTS AND MATERIALS SHALL BE LISTED FOR IT'S PURPOSE AND INSTALLED IN A WORKMAN LIKE MANNER. ALL OUTDOOR EQUIPMENT SHALL MEET APPROPRIATE NEMA STANDARDS. THE ELECTRICAL CONTRACTOR IS ADVISED THAT ALL DRAWINGS AND COMPONENT MANUALS ARE TO BE UNDERSTOOD PRIOR TO INSTALLATION. THE CONTRACTOR IS ADVISED TO HAVE ALL SWITCHES IN THE OFF POSITION AND FUSES REMOVED PRIOR TO INSTALLATION OF FUSE-BEARING COMPONENTS. THIS SYSTEM IS INTENDED TO BE OPERATED IN PARALLEL WITH THE UTILITY SERVICE PROVIDER. ANTI-ISLANDING PROTECTION IS A REQUIREMENT OF UL 1741 AND IS INTENDED TO PREVENT THE OPERATION OF THE PV SYSTEM WHEN THE UTILITY GRID IS NOT OPERATIONAL. PERMISSION TO OPERATE THE SYSTEM IS NOT AUTHORIZED UNTIL FINAL INSPECTIONS AND APPROVALS ARE OBTAINED FROM THE LOCAL AUTHORITY HAVING JURISDICTION AND THE LOCAL UTILITY SERVICE PROVIDER. THE METHOD OF ATTACHMENT CREATES A UNIFIED STRUCTURE TO MEET DEAD LOAD, WIND LOAD, AND SEISMIC REQUIREMENTS. SOLAR MODULES WILL BE SECURED TO THE EXISTING ROOF AS SPECIFIED ON THE STRUCTURAL SHEETS. EXISTING ROOF EQUIPMENT WILL NOT BE EFFECTED BY THE PV SYSTEM. ALL STRUCTURAL DESIGN AND INSTALLATION COMPONENTS ARE THE RESPONSIBILITY OF OTHERS AND OUTSIDE THE SCOPE OF THIS DOCUMENT. ALL FASTENERS SHALL BE CORROSION RESISTANT APPROPRIATE FOR SITE CONDITIONS. CONNECTORS SHALL BE TORQUED PER DEVICE LISTING OR ENGINEERING RECOMMENDATIONS. ALL ROOFING REPAIR MUST MAINTAIN EXISTING CLASS AND TYPE OF ROOF AND ALL WORK SHALL BE IN ACCORDANCE WITH THE ROOF IN MANUFACTURER'S INSTALLATION REQUIREMENTS. PROJECT DESCRIPTION: SYSTEM SIZE: DC STC: ____ kW AC SIZE: ____ kW SOLAR MODULES: (___) INVERTER: (___) MOUNTING SYSTEM: EXISTING MSP BUS: ____ EXISTING MAIN BREAKER: ____ NEW PV BREAKER: ____ RACKING DATA SHEET GROUNDING SPECS RACKING DETAILSD8 PROPERTY DETAILS: TWO STORY BUILDING BUILDING OCCUPANCY GROUPS (R-3) TYPE OF CONSTRUCTION (V-B) AUTOMATIC FIRE SPRINKLERS (NO) ROOF TYPE: ROOF STRUCTURE: PARCEL NUMBER: 41222216 LOT AREA: 3,078 SQFT LIVING AREA: 1,379 SQFT SMOKE ALARMS AND CARBON MONOXIDE ALARMS SHALL BE PROVIDED FOR THE DWELLING PER CRC R314 AND R315 Drawn By: Unique Solar Design California Solar Group CSLB # 1067781 C-10 Contractor Note 7647 Hayvenhurst Ave., Unit 26 Van Nuys, CA 91406 casolargroup.com info@casolargroup.com Phone Number: +1 818 658 2362 Address & Phone Number Signature Company Logo 16 2022 CALIFORNIA RESIDENTIAL CODE 2022 CALIFORNIA ELECTRICAL CODE 2022 CALIFORNIA BUILDING CODE 2022 CALIFORNIA GREEN BUILDING STANDARDS CODE 2022 CALIFORNIA ENERGY CODE 2022 CALIFORNIA MECHANICAL CODE 2022 CALIFORNIA PLUMBING CODE 125A 125A 30A 6.56 6.11 RAFTERS 2'' x 6'' @ 24'' O.C FLAT CONCRETE TILE ENPHASE IQ8A MICROINVERTER (IQ8A-72-2-US (120/240V) [240] [SI1]) IRONRIDGE XR10 RACKING RACKING CERTIFICATIONS 16 6.56KW DC Roof Mounted PV Electrical System 16-Silfab 410W PV Modules 16-IQ8A Enphase Microinverters ENPHASE COMBINER DATA SHEET Silfab 410W Modules (SIL-410BG) ATTACHMENT DATA SHEET N The scope of the plans is for the installation of the solar photovoltaic system only and the approval is subject to compliance with all applicable city and state codes and regulations regarding construction. The approval of the plans does not constitute any certification of the accuracy, completeness, or building permit status of the existing buildings and structures as shown. REVISED 101114405/20179136 Issued 03/24/23 20179807 Issued 06/06/23 2030 W Summer Wind06/06/23 PV SYSTEM AS INDICATED Project Name Project Address Project Description SHEET SIZE 11'' X 17'' ANSI B SHEET NUMBER General Notes Date Scale Project MARCH 06, 2023 Paul Czajka 2030 W Summer Wind, Santa Ana, CA 92704 PV1 Drawn By: Unique Solar Design California Solar Group CSLB # 1067781 C-10 Contractor Note 7647 Hayvenhurst Ave., Unit 26 Van Nuys, CA 91406 casolargroup.com info@casolargroup.com Phone Number: +1 818 658 2362 Address & Phone Number Signature Company Logo 90 120 150 180 210 240 270 300 330 0 30 60 W E S N 80 70 50 4O 2010350 80 320 310 290 280 260 250 230 220 200 190 170 160 140 130 110 100 340 0 5 10ft1 SCALE 1 2 3 4 5 EQUIPMENT INFORMATION 16 (N) Silfab 410W (SIL-410BG) Modules (Page D1) 16 (N) Enphase Microinverters IQ8A-72-2-US (120/240V) [240] [SI1] (Page D2) 1 (N) Junction-Box 1 (N) Enphase IQ Combiner Box With IQ Gateway IQ MODEL# X-IQ-AM1-240-4 [CRD-PCS NEM] (120/240V) (Page D3) (Inside The Garage) 1 (N) 30A Non-Fused AC Disconnect (120/240V) (N) 125A Service Sub Panel (120/240V, 1ɸ, 3W) (Inside The Garage) (E) 125A Main Service Panel (120/240V, 1ɸ, 3W) A 9 (N) Silfab 410W / 9 IQ8A Microinverters, Roof Pitch 18° / Az. 265° B 7(N) Silfab 410W / 7 IQ8A Microinverters, Roof Pitch 18° / Az. 85 6.56KW DC Roof Mounted PV Electrical System 16-Silfab 410W PV Modules 16-IQ8A Enphase Microinverters PROPERTY LINE Dr ive wa y S O c e a n C r es t Pu b l i c S i d e w a l k St r e e t 18 ' ' fir e s e t ba c k 18 ' ' fire s e t b a c k 18 ' ' fir e se t ba c k 3' fire setback 3' fire setback 3' fire setback 3' fire setback (A) W Summer Wind (B) (1) (2) (5) 50' 45' 55' 13' 25' 6''Roof Access Roof Access Roof access is not located in areas that require placement of ground ladders over exterior wall openings. TOTAL SOLAR AREA (sqft) 337 TOTAL ROOF AREA (sqft) 1440 % OF COVERED AREA 23.4 B.O.S ELEVATION (5) INSIDE THE GARAGE (3)(2) NORTH EAST WALL (4) (4) (3) 1 1 1 1 1 1 1 1 1 2 2 2 2 2 2 2 2030 W Summer Wind03/28/23 PV SYSTEM AS INDICATED Project Name Project Address Project Description SHEET SIZE 11'' X 17'' ANSI B SHEET NUMBER General Notes Date Scale Project MAY 19, 2023 Paul Czajka 2030 W Summer Wind, Santa Ana, CA 92704 PV1 Drawn By: Unique Solar Design California Solar Group CSLB # 1067781 C-10 Contractor Note 7647 Hayvenhurst Ave., Unit 26 Van Nuys, CA 91406 casolargroup.com info@casolargroup.com Phone Number: +1 818 658 2362 Address & Phone Number Signature Company Logo 90 120 150 180 210 240 270 300 330 0 30 60 W E S N 80 70 50 4O 2010350 80 320 310 290 280 260 250 230 220 200 190 170 160 140 130 110 100 340 0 5 10ft1 SCALE 1 2 3 4 5 EQUIPMENT INFORMATION 16 (N) Silfab 410W (SIL-410BG) Modules (Page D1) 16 (N) Enphase Microinverters IQ8A-72-2-US (120/240V) [240] [SI1] (Page D2) 1 (N) Junction-Box 1 (N) Enphase IQ Combiner Box With IQ Gateway IQ MODEL# X-IQ-AM1-240-4 [CRD-PCS NEM] (120/240V) (Page D3) (Inside The Garage) 1 (N) 30A Non-Fused AC Disconnect (120/240V) (N) 125A Service Sub Panel (120/240V, 1ɸ, 3W) (Inside The Garage) (E) 125A Main Service Panel (120/240V, 1ɸ, 3W) A 8 (N) Silfab 410W / 8 IQ8A Microinverters, Roof Pitch 18° / Az. 265° B 8 (N) Silfab 410W / 8 IQ8A Microinverters, Roof Pitch 18° / Az. 85 6.56KW DC Roof Mounted PV Electrical System 16-Silfab 410W PV Modules 16-IQ8A Enphase Microinverters PROPERTY LINE Dr ive wa y S O c e a n C r es t Pu b l i c S i d e w a l k St r e e t 18 ' ' fir e s e t ba c k 18 ' ' fire s e t b a c k 18 ' ' fir e se t ba c k 3' fire setback 3' fire setback 3' fire setback 3' fire setback (A) W Summer Wind (B) (1) (2) (5) 50' 45' 55' 6''Roof Access Roof Access Roof access is not located in areas that require placement of ground ladders over exterior wall openings. TOTAL SOLAR AREA (sqft) 337 TOTAL ROOF AREA (sqft) 1440 % OF COVERED AREA 23.4 B.O.S ELEVATION (5) INSIDE THE GARAGE (3)(2) NORTH EAST WALL (4) (4) (3) 2 2 2 36'' setbacks 18'' setbacks 1 1 1 1 1 1 1 1 2 2 2 2 2 13' 30' 5' 8' 2030 W Summer Wind06/06/23 Drawn By: Unique Solar Design California Solar Group CSLB # 1067781 C-10 Contractor Note 7647 Hayvenhurst Ave., Unit 26 Van Nuys, CA 91406 casolargroup.com info@casolargroup.com Phone Number: +1 818 658 2362 Address & Phone Number Signature Company Logo PV SYSTEM AS INDICATED Project Name Project Address Project Description SHEET SIZE 11'' X 17'' ANSI B SHEET NUMBER General Notes Date Scale Project MARCH 06, 2023 Paul Czajka 2030 W Summer Wind, Santa Ana, CA 92704 Photovoltaic system is rapid shut down ready L2 L1N G INSTALL 2P ____ CB(PV)30A L1 L2 N G L1 L2 5 7 [C] M TO UTILITY GRID L2 L1 (N) 2P 100A G N L2 L1 _____ CENTER FEED MAIN OCPD 125A 8' Minimum Embedment Rod at 6' From Equipment Ground Conductor Unless Existing Ground is UFER. WIRE TAG # WIRE TYPE/QTY/SIZE COPPER GRD SIZE WIRE AMP TERMINAL RATING CONDUIT TYPE CONDUIT RUN TEMP. CORRECTION TABLE 310.15(B)(3)(A) AMP. ADJ. C.C.C CONDUCTOR AMPACITY 310.15(B)(16) AND B.C. / STRING OUTPUT CURRENT A Q CABLE (2) #10 #6, BARE CU 40 90° OPEN AIR >3.5 - 12''0.71 N/A 1 28.4 > =16.3 B THWN-2 (4) #10 ((2)L1, (2)L2)#8, EGC CU 40 90° 3/4'' EMT >3.5 - 12'' 0.71 4 WIRES 0.8 22.7 > =16.3 C THWN-2 (3) #8 (L1,L2,N)#8, EGC CU 40 90° 3/4'' EMT ALONG THE WALL 0.91 N/A 1 36.4 > =29.0 PV SYSTEM OUTPUT CALCULATION DC SYSTEM CALCULATION PV SOLAR MODULE WATTAGE PV SOLAR MODULE QUANTITY MAX DC OUTPUT (KW ) 410 16 6.56 AC SYSTEM CALCULATION PTC WATTAGE PV SOLAR MODULE QUANTITY CEC EFFICIENCY (%) MAX AC OUTPUT (KW ) 391.7 16 0.975 6.11 SERVICE SUB PANEL CALCULATION SSP BUS SIZE (A) SSP CONTROLLER BREAKER SIZE (A) MAX ALLOWED SOLAR BREAKER (A) SOLAR BREAKER (A) 125 100 50.0 > =30.0 1 2 3 4 5 6 7 EQUIPMENT INFORMATION 16 (N) Silfab 410W (SIL-410BG) Modules (Page D1) 16 (N) Enphase Microinverters IQ8A-72-2-US (120/240V) [240] [SI1] (Page D2) 1 (N) Junction-Box 1 (N) Enphase IQ Combiner Box With IQ Gateway IQ MODEL# X-IQ-AM1-240-4 [CRD-PCS NEM] (120/240V) (Page D3) (Inside The Garage) 1 (N) 30A Non-Fused AC Disconnect (120/240V) (N) 125A Service Sub Panel (120/240V, 1ɸ, 3W) (Inside The Garage) (E) 125A Main Service Panel (120/240V, 1ɸ, 3W) [C] 4 (N)2P 20A 15A N G (N)2P 20A[B] (2) #14 AWG THWN (1) #10 AWG CU EGC J BOX NEMA 3R PV ARRAY (__) MODULES WIRED IN (2ND) SERIES OF (__) MICROINVERTERS ... 1 PV ARRAY (__) MODULES WIRED IN (1ST) SERIES OF (__) MICROINVERTERS ... 1 [A] (1st) SERIES OF __ MICROINVERTERS (2nd) SERIES OF __ MICROINVERTERS 9 9 9 9 7 7 7 7 2 PV2 6.56KW DC Roof Mounted PV Electrical System 16-Silfab 410W PV Modules 16-IQ8A Enphase Microinverters 6 NEW WIRING THWN-2 (3) #3 (L1, L2, N) #4, BARE CU 1 1/4'' EMT TYPE CONDUIT 1 3 2030 W Summer Wind03/28/23 Drawn By: Unique Solar Design California Solar Group CSLB # 1067781 C-10 Contractor Note 7647 Hayvenhurst Ave., Unit 26 Van Nuys, CA 91406 casolargroup.com info@casolargroup.com Phone Number: +1 818 658 2362 Address & Phone Number Signature Company Logo PV SYSTEM AS INDICATED Project Name Project Address Project Description SHEET SIZE 11'' X 17'' ANSI B SHEET NUMBER General Notes Date Scale Project MAY 19, 2023 Paul Czajka 2030 W Summer Wind, Santa Ana, CA 92704 Photovoltaic system is rapid shut down ready L2 L1N G INSTALL 2P ____ CB(PV)30A L1 L2 N G L1 L2 5 7 [C] M TO UTILITY GRID L2 L1 (N) 2P 100A G N L2 L1 _____ CENTER FEED MAIN OCPD 125A 8' Minimum Embedment Rod at 6' From Equipment Ground Conductor Unless Existing Ground is UFER. WIRE TAG # WIRE TYPE/QTY/SIZE COPPER GRD SIZE WIRE AMP TERMINAL RATING CONDUIT TYPE CONDUIT RUN TEMP. CORRECTION TABLE 310.15(B)(3)(A) AMP. ADJ. C.C.C CONDUCTOR AMPACITY 310.15(B)(16) AND B.C. / STRING OUTPUT CURRENT A Q CABLE (2) #10 #6, BARE CU 40 90° OPEN AIR >3.5 - 12''0.71 N/A 1 28.4 > =14.5 B THWN-2 (4) #10 ((2)L1, (2)L2)#8, EGC CU 40 90° 3/4'' EMT >3.5 - 12'' 0.71 4 WIRES 0.8 22.7 > =14.5 C THWN-2 (3) #8 (L1,L2,N)#8, EGC CU 40 90° 3/4'' EMT ALONG THE WALL 0.91 N/A 1 36.4 > =29.0 PV SYSTEM OUTPUT CALCULATION DC SYSTEM CALCULATION PV SOLAR MODULE WATTAGE PV SOLAR MODULE QUANTITY MAX DC OUTPUT (KW ) 410 16 6.56 AC SYSTEM CALCULATION PTC WATTAGE PV SOLAR MODULE QUANTITY CEC EFFICIENCY (%) MAX AC OUTPUT (KW ) 391.7 16 0.975 6.11 SERVICE SUB PANEL CALCULATION SSP BUS SIZE (A) SSP CONTROLLER BREAKER SIZE (A) MAX ALLOWED SOLAR BREAKER (A) SOLAR BREAKER (A) 125 100 50.0 > =30.0 1 2 3 4 5 6 7 EQUIPMENT INFORMATION 16 (N) Silfab 410W (SIL-410BG) Modules (Page D1) 16 (N) Enphase Microinverters IQ8A-72-2-US (120/240V) [240] [SI1] (Page D2) 1 (N) Junction-Box 1 (N) Enphase IQ Combiner Box With IQ Gateway IQ MODEL# X-IQ-AM1-240-4 [CRD-PCS NEM] (120/240V) (Page D3) (Inside The Garage) 1 (N) 30A Non-Fused AC Disconnect (120/240V) (N) 125A Service Sub Panel (120/240V, 1ɸ, 3W) (Inside The Garage) (E) 125A Main Service Panel (120/240V, 1ɸ, 3W) [C] 4 (N)2P 20A 15A N G (N)2P 20A[B] (2) #14 AWG THWN (1) #10 AWG CU EGC J BOX NEMA 3R PV ARRAY (__) MODULES WIRED IN (2ND) SERIES OF (__) MICROINVERTERS ... 1 PV ARRAY (__) MODULES WIRED IN (1ST) SERIES OF (__) MICROINVERTERS ... 1 [A] (1st) SERIES OF __ MICROINVERTERS (2nd) SERIES OF __ MICROINVERTERS 8 8 8 8 8 8 8 8 2 PV2 6.56KW DC Roof Mounted PV Electrical System 16-Silfab 410W PV Modules 16-IQ8A Enphase Microinverters 6 NEW WIRING THWN-2 (3) #3 (L1, L2, N) #4, BARE CU 1 1/4'' EMT TYPE CONDUIT 1 3 NEW 50A BREAKER RELOCATED FROM MAIN PANEL NEW WIRING THWN-2 (3) #6 (L1, L2, N) #8, BARE CU 3/4'' EMT TYPE CONDUIT 2030 W Summer Wind06/06/23 PV SYSTEM AS INDICATED Project Name Project Address Project Description SHEET SIZE 11'' X 17'' ANSI B SHEET NUMBER General Notes Date Scale Project MARCH 06, 2023 Paul Czajka 2030 W Summer Wind, Santa Ana, CA 92704 PV3 Drawn By: Unique Solar Design California Solar Group CSLB # 1067781 C-10 Contractor Note 7647 Hayvenhurst Ave., Unit 26 Van Nuys, CA 91406 casolargroup.com info@casolargroup.com Phone Number: +1 818 658 2362 Address & Phone Number Signature Company Logo CAUTION POWER TO THIS BUILDING IS ALSO SUPPLIED FROM THE FOLLOWING SOURCES WITH DISCONNECTS LOCATED AS SHOWN: EW S N JB B O X WARNING ELECTRICAL SHOCK HAZARD TERMINALS ON THE LINE AND LOAD SIDES MAY BE ENERGIZED IN THE OPEN POSITION CEC 690.13(B) TURN OFF PHOTOVOLTAIC AC DISCONNECT PRIOR TO WORKING INSIDE PANEL CEC 110.27(C) & OSHA 1910.145(f)(7) WARNING DC D i s c o n n e c t WARNING ELECTRICAL SHOCK HAZARD TERMINALS ON THE LINE AND LOAD SIDES MAY BE ENERGIZED IN THE OPEN POSITION CEC 690.13(B) DC VOLTAGE IS ALWAYS PRESENT WHEN SOLAR MODULES ARE EXPOSED TO SUNLIGHT MAXIMUM VOLTAGE MAXIMUM CIRCUIT CURRENT MAX RATED OUTPUT CURRENT OF THE CHARGE CONTROLLER OR DC-TO-DC CONVERTER (IF INSTALLED) CEC 690.53 CEC 690.13(B) In v e r t e r / P V L o a d WARNING THE DISCONNECTION OF THE GROUNDING CONDUCTOR(S) MAY RESULT IN OVERVOLTAGE ON THE EQUIPMENT CEC 690.31(I) CEC 690.54 RATED AC OUTPUT CURRENT: NOMINAL OPERATING AC VOLTAGE: PHOTOVOLTAIC AC DISCONNECT AC D i s c o n n e c t CEC 690.54 RATED AC OUTPUT CURRENT: NOMINAL OPERATING AC VOLTAGE: PHOTOVOLTAIC AC DISCONNECTWARNING ELECTRICAL SHOCK HAZARD TERMINALS ON THE LINE AND LOAD SIDES MAY BE ENERGIZED IN THE OPEN POSITION CEC 690.13(B) PM M E T E R CEC 705.12(D)(3) & CEC 690.59 WARNING DUAL POWER SOURCE SECOND SOURCE IS PHOTOVOLTAIC SYSTEM Ma i n / S u b P a n e l CEC 690.54 RATED AC OUTPUT CURRENT: NOMINAL OPERATING AC VOLTAGE: PHOTOVOLTAIC AC DISCONNECT CEC 690.13 (F), CEC 705.12(B)(3-4) & CEC 690.59 CAUTION PHOTOVOLTAIC SYSTEM CIRCUIT IS BACKFED CEC 705.12(D)(3) & CEC 690.59 WARNING DUAL POWER SOURCE SECOND SOURCE IS PHOTOVOLTAIC SYSTEM CEC 690.13(B) MAIN PHOTOVOLTAIC SYSTEM DISCONNECT TURN OFF PHOTOVOLTAIC AC DISCONNECT PRIOR TO WORKING INSIDE PANEL WARNING CEC 110.27(C) & OSHA 1910.145(f)(7) WARNING ELECTRICAL SHOCK HAZARD TERMINALS ON THE LINE AND LOAD SIDES MAY BE ENERGIZED IN THE OPEN POSITION CEC 690.13(B) POWER SOURCE OUTPUT CONNECTION. DO NOT RELOCATE THIS OVERCURRENT DEVICE. WARNING CEC 705.12 (B)(2)(c) CEC 705.10(B) & CEC 690.56(B) Permanent directory or plaque providing location of service disconnecting means and photovoltaic system disconnecting means, if not located at the same location. (Plaques shall be metal or plastic, with engraved or machine printed letters, or electro-photo plating, in a contrasting color to the plaque. Plaques shall be permanently attached to the equipmenq or in the required location using an approved method that is suitable to withstand the environment to which it is exposed. Plaques and signage shall meet legibility, defacemet, exposure and adhesion requirements of Underwriters Laboratories marking and labeling system 969(UL969). Plaques will have red background & white lettering. Only present if required by either the AHJ and/or utility company SOLAR ELECTRIC PV PANELS SOLAR PV SYSTEM EQUIPPED WITH RAPID SHUTDOWN TURN RAPID SHUTDOWN SWITCH ON THE "OFF" POSITION TO SHUTDOWN PV SYSTEM AND REDUCE SHOCK HAZARD IN ARRAY IFC 605.11.3.1(1) & 690.56(C)(1)(a) CEC 690.31(G)(1) WARNING PHOTOVOLTAIC POWER SOURCE DO NOT REMOVE UNLESS REPLACED IN EXACT LOCATION - PV POWER CIRCUIT DIRECTLY BELOW CO N D U I T 240V N/A N/A N/A 240V 240V FOR PV SYSTEMS THAT SHUT DOWN THE ARRAY AND CONDUCTORS LEAVING THE ARRAY: SIGH TO BE LOCATED ON OR NO MORE THAN 3 FT AWAY FROM SERVICE DISCONNECTING MEANS TO WHICH THE PV SYSTEMS ARE CONNECTED AND SHALL INDICATE THE LOCATION OF ALL IDENTIFIED RAPID SHUTDOWN SWITCHES IF NOT AT THE SAME LOCATION. [CEC 690.56(C)(1)(A)] LABELING REQUIREMENTS FOR ARTICLE 690 CEC 690.13(B) Each PV system disconnecting means shall plainly indicate whether in the open (off) or closed (on) position and be permanently marked “PV SYSTEM DISCONNECT” or equivalent. Additional markings shall be permitted based upon the specific system configuration. For PV system disconnecting means where the line and load terminals may be energized in the open position, the device shall be marked with the following words or equivalent. CEC 690.13(F) Type of Disconnect. A dc PV system disconnecting means shall be marked for use in PV systems or be suitable for backfeed operation. CEC 690.15(C) An isolating device shall be rated to open the maximum circuit current under load or be marked “Do Not Disconnect Under Load” or “Not for Current Interrupting.” CEC 690.31(B)(1) PV system circuit conductors shall be identified at all accessible points of termination, connection and splices. The means of identification shall be permitted by separate color coding, marking tape, tagging or other approved means. CEC 690.31(G)(1) Where circuits are embedded in build up, laminate or membrane roofing materials not covered by PV modules and associated equipment, the location of the circuits shall be clearly marked. CEC 690.31(G)(4) PV dc system circuit labels shall appear on every section of the wiring system that is separated by enclosures, walls, partitions, ceilings, or floors. Spacing between labels or markings, or between a label and a marking, shall not be more than 3 m (10 ft). Labels required in this section shall be suitable for the environment where they are installed. CEC 690.31(I) Solidly-grounded bipolar PV systems shall be clearly marked with a permanent, legible warning notice indicating that the disconnection of the grounded conductor(s) may result in overvoltage on the equipment. CEC 690.33(E)(2) Interruption of Circuit. Connectors shall be a type that requires the use of a tool to open and marked “Do Not Disconnect Under Load” or “Not for Current Interrupting.” CEC 690.52 Alternating-current modules shall be marked with identification of terminals or leads and with identification of the following ratings. CEC 690.53A permanent label for the dc PV power source indicating items (1) through (3) shall be provided by the installer at dc PV system disconnecting means and at each dc equipment disconnecting means required by 690.15. Where a disconnecting means has more than one dc PV power source, the values in 690.53 (1) through (3) shall be specified for each source. CEC 690.56(C)(3) RAPID SHUT DOWN SWITCH FOR SOLAR PV SYSTEM DC DISCONNECT PHOTOVOLTAIC CEC 690.13(B) DC DISCONNECT PHOTOVOLTAIC 23.2A 23.2A 23.2A 6.56KW DC Roof Mounted PV Electrical System 16-Silfab 410W PV Modules 16-IQ8A Enphase Microinverters W Summer Wind SERVICE POINT & UTILITY METERING IQ COMBINER BOX SOLAR DISCONNECT SERVICE SUB PANEL SOLAR MODULES 2030 W Summer Wind03/28/23 PV SYSTEM AS INDICATED Project Name Project Address Project Description SHEET SIZE 11'' X 17'' ANSI B SHEET NUMBER General Notes Date Scale Project MAY 19, 2023 Paul Czajka 2030 W Summer Wind, Santa Ana, CA 92704 PV3 Drawn By: Unique Solar Design California Solar Group CSLB # 1067781 C-10 Contractor Note 7647 Hayvenhurst Ave., Unit 26 Van Nuys, CA 91406 casolargroup.com info@casolargroup.com Phone Number: +1 818 658 2362 Address & Phone Number Signature Company Logo CAUTION POWER TO THIS BUILDING IS ALSO SUPPLIED FROM THE FOLLOWING SOURCES WITH DISCONNECTS LOCATED AS SHOWN: EW S N JB B O X WARNING ELECTRICAL SHOCK HAZARD TERMINALS ON THE LINE AND LOAD SIDES MAY BE ENERGIZED IN THE OPEN POSITION CEC 690.13(B) TURN OFF PHOTOVOLTAIC AC DISCONNECT PRIOR TO WORKING INSIDE PANEL CEC 110.27(C) & OSHA 1910.145(f)(7) WARNING DC D i s c o n n e c t WARNING ELECTRICAL SHOCK HAZARD TERMINALS ON THE LINE AND LOAD SIDES MAY BE ENERGIZED IN THE OPEN POSITION CEC 690.13(B) DC VOLTAGE IS ALWAYS PRESENT WHEN SOLAR MODULES ARE EXPOSED TO SUNLIGHT MAXIMUM VOLTAGE MAXIMUM CIRCUIT CURRENT MAX RATED OUTPUT CURRENT OF THE CHARGE CONTROLLER OR DC-TO-DC CONVERTER (IF INSTALLED) CEC 690.53 CEC 690.13(B) In v e r t e r / P V L o a d WARNING THE DISCONNECTION OF THE GROUNDING CONDUCTOR(S) MAY RESULT IN OVERVOLTAGE ON THE EQUIPMENT CEC 690.31(I) CEC 690.54 RATED AC OUTPUT CURRENT: NOMINAL OPERATING AC VOLTAGE: PHOTOVOLTAIC AC DISCONNECT AC D i s c o n n e c t CEC 690.54 RATED AC OUTPUT CURRENT: NOMINAL OPERATING AC VOLTAGE: PHOTOVOLTAIC AC DISCONNECTWARNING ELECTRICAL SHOCK HAZARD TERMINALS ON THE LINE AND LOAD SIDES MAY BE ENERGIZED IN THE OPEN POSITION CEC 690.13(B) PM M E T E R CEC 705.12(D)(3) & CEC 690.59 WARNING DUAL POWER SOURCE SECOND SOURCE IS PHOTOVOLTAIC SYSTEM Ma i n / S u b P a n e l CEC 690.54 RATED AC OUTPUT CURRENT: NOMINAL OPERATING AC VOLTAGE: PHOTOVOLTAIC AC DISCONNECT CEC 690.13 (F), CEC 705.12(B)(3-4) & CEC 690.59 CAUTION PHOTOVOLTAIC SYSTEM CIRCUIT IS BACKFED CEC 705.12(D)(3) & CEC 690.59 WARNING DUAL POWER SOURCE SECOND SOURCE IS PHOTOVOLTAIC SYSTEM CEC 690.13(B) MAIN PHOTOVOLTAIC SYSTEM DISCONNECT TURN OFF PHOTOVOLTAIC AC DISCONNECT PRIOR TO WORKING INSIDE PANEL WARNING CEC 110.27(C) & OSHA 1910.145(f)(7) WARNING ELECTRICAL SHOCK HAZARD TERMINALS ON THE LINE AND LOAD SIDES MAY BE ENERGIZED IN THE OPEN POSITION CEC 690.13(B) POWER SOURCE OUTPUT CONNECTION. DO NOT RELOCATE THIS OVERCURRENT DEVICE. WARNING CEC 705.12 (B)(2)(c) CEC 705.10(B) & CEC 690.56(B) Permanent directory or plaque providing location of service disconnecting means and photovoltaic system disconnecting means, if not located at the same location. (Plaques shall be metal or plastic, with engraved or machine printed letters, or electro-photo plating, in a contrasting color to the plaque. Plaques shall be permanently attached to the equipmenq or in the required location using an approved method that is suitable to withstand the environment to which it is exposed. Plaques and signage shall meet legibility, defacemet, exposure and adhesion requirements of Underwriters Laboratories marking and labeling system 969(UL969). Plaques will have red background & white lettering. Only present if required by either the AHJ and/or utility company SOLAR ELECTRIC PV PANELS SOLAR PV SYSTEM EQUIPPED WITH RAPID SHUTDOWN TURN RAPID SHUTDOWN SWITCH ON THE "OFF" POSITION TO SHUTDOWN PV SYSTEM AND REDUCE SHOCK HAZARD IN ARRAY IFC 605.11.3.1(1) & 690.56(C)(1)(a) CEC 690.31(G)(1) WARNING PHOTOVOLTAIC POWER SOURCE DO NOT REMOVE UNLESS REPLACED IN EXACT LOCATION - PV POWER CIRCUIT DIRECTLY BELOW CO N D U I T 240V N/A N/A N/A 240V 240V FOR PV SYSTEMS THAT SHUT DOWN THE ARRAY AND CONDUCTORS LEAVING THE ARRAY: SIGH TO BE LOCATED ON OR NO MORE THAN 3 FT AWAY FROM SERVICE DISCONNECTING MEANS TO WHICH THE PV SYSTEMS ARE CONNECTED AND SHALL INDICATE THE LOCATION OF ALL IDENTIFIED RAPID SHUTDOWN SWITCHES IF NOT AT THE SAME LOCATION. [CEC 690.56(C)(1)(A)] LABELING REQUIREMENTS FOR ARTICLE 690 CEC 690.13(B) Each PV system disconnecting means shall plainly indicate whether in the open (off) or closed (on) position and be permanently marked “PV SYSTEM DISCONNECT” or equivalent. Additional markings shall be permitted based upon the specific system configuration. For PV system disconnecting means where the line and load terminals may be energized in the open position, the device shall be marked with the following words or equivalent. CEC 690.13(F) Type of Disconnect. A dc PV system disconnecting means shall be marked for use in PV systems or be suitable for backfeed operation. CEC 690.15(C) An isolating device shall be rated to open the maximum circuit current under load or be marked “Do Not Disconnect Under Load” or “Not for Current Interrupting.” CEC 690.31(B)(1) PV system circuit conductors shall be identified at all accessible points of termination, connection and splices. The means of identification shall be permitted by separate color coding, marking tape, tagging or other approved means. CEC 690.31(G)(1) Where circuits are embedded in build up, laminate or membrane roofing materials not covered by PV modules and associated equipment, the location of the circuits shall be clearly marked. CEC 690.31(G)(4) PV dc system circuit labels shall appear on every section of the wiring system that is separated by enclosures, walls, partitions, ceilings, or floors. Spacing between labels or markings, or between a label and a marking, shall not be more than 3 m (10 ft). Labels required in this section shall be suitable for the environment where they are installed. CEC 690.31(I) Solidly-grounded bipolar PV systems shall be clearly marked with a permanent, legible warning notice indicating that the disconnection of the grounded conductor(s) may result in overvoltage on the equipment. CEC 690.33(E)(2) Interruption of Circuit. Connectors shall be a type that requires the use of a tool to open and marked “Do Not Disconnect Under Load” or “Not for Current Interrupting.” CEC 690.52 Alternating-current modules shall be marked with identification of terminals or leads and with identification of the following ratings. CEC 690.53A permanent label for the dc PV power source indicating items (1) through (3) shall be provided by the installer at dc PV system disconnecting means and at each dc equipment disconnecting means required by 690.15. Where a disconnecting means has more than one dc PV power source, the values in 690.53 (1) through (3) shall be specified for each source. CEC 690.56(C)(3) RAPID SHUT DOWN SWITCH FOR SOLAR PV SYSTEM DC DISCONNECT PHOTOVOLTAIC CEC 690.13(B) DC DISCONNECT PHOTOVOLTAIC 23.2A 23.2A 23.2A 6.56KW DC Roof Mounted PV Electrical System 16-Silfab 410W PV Modules 16-IQ8A Enphase Microinverters W Summer Wind SERVICE POINT & UTILITY METERING IQ COMBINER BOX SOLAR DISCONNECT SERVICE SUB PANEL SOLAR MODULES 2030 W Summer Wind06/06/23 SYSTEM MECHANICAL DETAILS MOUNTING RAIL TYPE ATTACHMENT TYPE ROOF FRAMING ATTACHMENT SPACING FINISHED ROOF SURFACE IS ONE LAYER OF ROOF SHEATHED WITH 1/2'' PLYWOOD AND UPPER SURFACE IS FACED WITH FELT PAPER. PV SYSTEM AS INDICATED Project Name Project Address Project Description SHEET SIZE 11'' X 17'' ANSI B SHEET NUMBER General Notes Date Scale Project MARCH 06, 2023 Paul Czajka 2030 W Summer Wind, Santa Ana, CA 92704 PV4 Drawn By: Unique Solar Design California Solar Group CSLB # 1067781 C-10 Contractor Note 7647 Hayvenhurst Ave., Unit 26 Van Nuys, CA 91406 casolargroup.com info@casolargroup.com Phone Number: +1 818 658 2362 Address & Phone Number Signature Company Logo PV Railing 72'' Max Rail Span Roof Attachment on 24'' O.C. Rafter RAFTERS 2'' x 6'' @ 24'' O.C FLAT CONCRETE TILE IRONRIDGE XR10 RACKING SYSTEM MECHANICAL CALCULATIONS PV SOLAR MODULE WEIGHT (lbs)45.8 PV SOLAR MODULE QUANTITY 16 PV SOLAR ARRAY WEIGHT (lbs)732.8 23.2 PV SOLAR RACKING WEIGHT (lbs)146.6 TOTAL SYSTEM WEIGHT (lbs)902.6 SOLAR ATTACHMENT QUANTITY 43 PV SOLAR ARRAY WEIGHT PER ATTACHMENT (lbs)21.0 SOLAR ARRAY DEAD LOAD (lbs/ft2)2.68 TOTAL SOLAR AREA (sqft)337 TOTAL ROOF AREA (sqft)1440 % OF COVERED AREA 23.4 WIND SPEED (mph)110 SNOW LOAD (psf)0 72'' MAX STAGGERED MICROINVERTERS WEIGHT (lbs) 6.56KW DC Roof Mounted PV Electrical System 16-Silfab 410W PV Modules 16-IQ8A Enphase Microinverters PV MODULE, BY OTHERS PV MODULE, BY OTHERS IRONRIDGE RAIL (E) TILE IRONRIDGE ATH IRONRIDGE RAIL (E) TILE IRONRIDGE ATH SIDE-FACING SLOT INTERNAL SPLICE IRONRIDGE DECK FLASHING (OPTIONAL) (E) BUILDING STRUCTURE ATH DETAIL Scale: 3"=1'-0"J ATH DETAIL Scale: 3"=1'-0" M IRONRIDGE DECK FLASHING (OPTIONAL) (E) BUILDING STRUCTURE DETAIL, SPLICE, XR1000 1'-0"=1'-0"N DETAIL, SPLICE, XR100 1'-0"=1'-0"O DETAIL, SPLICE, XR10 1'-0"=1'-0" INTERNAL SPLICE SIDE-FACING SLOT SIDE-FACING SLOT INTERNAL SPLICE SIDE-FACING SLOT TOP-FACING SLOT TOP-FACING SLOT TOP-FACING SLOT XR100 RAIL BONDING SPRING XR100 INTERNAL SPLICE DETAIL, SPLICE CONNECTION, XR100 6"=1'-0" XR100 RAIL Q BONDING SPRING XR100 INTERNAL SPLICE 1.00 IRONRIDGE ATH 7 116" P IRONRIDGE ATH WITH DECK FLASHING, FRONT VIEW 1'-2" 9" DETAIL, THERMAL EXPANSION CONNECTION, XR100 6"=1'-0" 51 712" 2" 7 116" 31316" R IRONRIDGE ATH WITH DECK FLASHING, SIDE VIEW S IRONRIDGE ATH WITH DECK FLASHING, PLAN VIEW H K L IronRidge All Tile Hook SOLAR MODULE Exterior Load Bearing Wall Exterior Load Bearing Wall . max 5'' 5/16'' Lag Bolts with 2.5'' EmbedmentRAFTERS 2'' x 6'' @ 24'' O.C 2''x4'' Purlin 18° 2'' BY 4'' @ 48'' O.C.2''x4'' Support 2''x6'' Blocking 2030 W Summer Wind03/28/23 SYSTEM MECHANICAL DETAILS MOUNTING RAIL TYPE ATTACHMENT TYPE ROOF FRAMING ATTACHMENT SPACING FINISHED ROOF SURFACE IS ONE LAYER OF ROOF SHEATHED WITH 1/2'' PLYWOOD AND UPPER SURFACE IS FACED WITH FELT PAPER. PV SYSTEM AS INDICATED Project Name Project Address Project Description SHEET SIZE 11'' X 17'' ANSI B SHEET NUMBER General Notes Date Scale Project MAY 19, 2023 Paul Czajka 2030 W Summer Wind, Santa Ana, CA 92704 PV4 Drawn By: Unique Solar Design California Solar Group CSLB # 1067781 C-10 Contractor Note 7647 Hayvenhurst Ave., Unit 26 Van Nuys, CA 91406 casolargroup.com info@casolargroup.com Phone Number: +1 818 658 2362 Address & Phone Number Signature Company Logo RAFTERS 2'' x 6'' @ 24'' O.C FLAT CONCRETE TILE IRONRIDGE XR10 RACKING SYSTEM MECHANICAL CALCULATIONS PV SOLAR MODULE WEIGHT (lbs)45.8 PV SOLAR MODULE QUANTITY 16 PV SOLAR ARRAY WEIGHT (lbs)732.8 23.2 PV SOLAR RACKING WEIGHT (lbs)146.6 TOTAL SYSTEM WEIGHT (lbs)902.6 SOLAR ATTACHMENT QUANTITY 26 PV SOLAR ARRAY WEIGHT PER ATTACHMENT (lbs)34.7 SOLAR ARRAY DEAD LOAD (lbs/ft2)2.68 TOTAL SOLAR AREA (sqft)337 TOTAL ROOF AREA (sqft)1440 % OF COVERED AREA 23.4 WIND SPEED (mph)110 SNOW LOAD (psf)0 72'' MAX STAGGERED MICROINVERTERS WEIGHT (lbs) 6.56KW DC Roof Mounted PV Electrical System 16-Silfab 410W PV Modules 16-IQ8A Enphase Microinverters PV MODULE, BY OTHERS PV MODULE, BY OTHERS IRONRIDGE RAIL (E) TILE IRONRIDGE ATH IRONRIDGE RAIL (E) TILE IRONRIDGE ATH SIDE-FACING SLOT INTERNAL SPLICE IRONRIDGE DECK FLASHING (OPTIONAL) (E) BUILDING STRUCTURE ATH DETAIL Scale: 3"=1'-0"J ATH DETAIL Scale: 3"=1'-0" M IRONRIDGE DECK FLASHING (OPTIONAL) (E) BUILDING STRUCTURE DETAIL, SPLICE, XR1000 1'-0"=1'-0"N DETAIL, SPLICE, XR100 1'-0"=1'-0"O DETAIL, SPLICE, XR10 1'-0"=1'-0" INTERNAL SPLICE SIDE-FACING SLOT SIDE-FACING SLOT INTERNAL SPLICE SIDE-FACING SLOT TOP-FACING SLOT TOP-FACING SLOT TOP-FACING SLOT XR100 RAIL BONDING SPRING XR100 INTERNAL SPLICE DETAIL, SPLICE CONNECTION, XR100 6"=1'-0" XR100 RAIL Q BONDING SPRING XR100 INTERNAL SPLICE 1.00 IRONRIDGE ATH 7 116" P IRONRIDGE ATH WITH DECK FLASHING, FRONT VIEW 1'-2" 9" DETAIL, THERMAL EXPANSION CONNECTION, XR100 6"=1'-0" 51 712" 2" 7 116" 31316" R IRONRIDGE ATH WITH DECK FLASHING, SIDE VIEW S IRONRIDGE ATH WITH DECK FLASHING, PLAN VIEW H K L IronRidge All Tile Hook SOLAR MODULE Exterior Load Bearing Wall Exterior Load Bearing Wall . max 5'' 5/16'' Lag Bolts with 2.5'' EmbedmentRAFTERS 2'' x 6'' @ 24'' O.C 2''x4'' Purlin 18° 2'' BY 4'' @ 48'' O.C.2''x4'' Support 2''x6'' Blocking PV Railing 72'' Max Rail Span Roof Attachment on 24'' O.C. Rafter 2030 W Summer Wind06/06/23 PV SYSTEM AS INDICATED Project Name Project Address Project Description SHEET SIZE 11'' X 17'' ANSI B SHEET NUMBER General Notes Date Scale Project MARCH 06, 2023 Paul Czajka 2030 W Summer Wind, Santa Ana, CA 92704 D7 Drawn By: Unique Solar Design California Solar Group CSLB # 1067781 C-10 Contractor Note 7647 Hayvenhurst Ave., Unit 26 Van Nuys, CA 91406 casolargroup.com info@casolargroup.com Phone Number: +1 818 658 2362 Address & Phone Number Signature Company Logo 6.56KW DC Roof Mounted PV Electrical System 16-Silfab 410W PV Modules 16-IQ8A Enphase Microinverters 2030 W Summer Wind03/28/23 PV SYSTEM AS INDICATED Project Name Project Address Project Description SHEET SIZE 11'' X 17'' ANSI B SHEET NUMBER General Notes Date Scale Project MAY 19, 2023 Paul Czajka 2030 W Summer Wind, Santa Ana, CA 92704 D7 Drawn By: Unique Solar Design California Solar Group CSLB # 1067781 C-10 Contractor Note 7647 Hayvenhurst Ave., Unit 26 Van Nuys, CA 91406 casolargroup.com info@casolargroup.com Phone Number: +1 818 658 2362 Address & Phone Number Signature Company Logo 6.56KW DC Roof Mounted PV Electrical System 16-Silfab 410W PV Modules 16-IQ8A Enphase Microinverters 2030 W Summer Wind06/06/23 PV SYSTEM AS INDICATED Project Name Project Address Project Description SHEET SIZE 11'' X 17'' ANSI B SHEET NUMBER General Notes Date Scale Project MARCH 06, 2023 Paul Czajka 2030 W Summer Wind, Santa Ana, CA 92704 D8 Drawn By: Unique Solar Design California Solar Group CSLB # 1067781 C-10 Contractor Note 7647 Hayvenhurst Ave., Unit 26 Van Nuys, CA 91406 casolargroup.com info@casolargroup.com Phone Number: +1 818 658 2362 Address & Phone Number Signature Company Logo 6.56KW DC Roof Mounted PV Electrical System 16-Silfab 410W PV Modules 16-IQ8A Enphase Microinverters 2030 W Summer Wind03/28/23 PV SYSTEM AS INDICATED Project Name Project Address Project Description SHEET SIZE 11'' X 17'' ANSI B SHEET NUMBER General Notes Date Scale Project MAY 19, 2023 Paul Czajka 2030 W Summer Wind, Santa Ana, CA 92704 D8 Drawn By: Unique Solar Design California Solar Group CSLB # 1067781 C-10 Contractor Note 7647 Hayvenhurst Ave., Unit 26 Van Nuys, CA 91406 casolargroup.com info@casolargroup.com Phone Number: +1 818 658 2362 Address & Phone Number Signature Company Logo 6.56KW DC Roof Mounted PV Electrical System 16-Silfab 410W PV Modules 16-IQ8A Enphase Microinverters 2030 W Summer Wind06/06/23