HomeMy WebLinkAbout215 W 4th St - PlanT-1.0
WATER CLOSETS
(FIXTURES PER PERSON)
MALE
1: 1-50
TYPE OF BUILDING
OR OCCUPANCY
RESTAURANT
OCC. B
FEMALE
1: 15
URINALS
(FIXTURES PER PERSON)
MALE
-
LAVATORIES
(FIXTURES PER PERSON)
MALE
1: 1-75
FEMALE
1: 1- 50
MALE
1
FEMALE
1
MIN. REQUIRED:
PROVIDED:MALE
-
MALE
1
FEMALE
1
PLUMBING OCCUPANT LOAD FACTOR 30 / 2 =15 15 MALE l 15 FEMALE
FD
#
&
<
NUMBER
AND
ANGLE
@ AT
A
A.B. ANCHOR BOLT
A.C. ASPHALTIC
COVERING
A.P. ACCESS PANEL
A/C AIR CONDITIONING
ACOUS ACOUSTIC
ACT ACOUSTIC TILE
ADJ ADJUSTABLE
AFF ABOVE FINISH FLOOR
ALT ALTER OR
ALTERNATE
ALUM ALUMINUM
ANOD ANNODIZED
APPROX APPROXIMATE
ARCH ARCHITECTURE
ASPH ASPHALT
B
B.U.R. BUILT UP ROOFING
BD BOARD
BITUM BITUMINOUS
BLDG BUILDING
BLK BLOCK
BLKG BLOCKING
BOT BOTTOM
C
C.B. CATCH BASIN
CIP CAST-IN-PLACE
CLG CEILING
CLOS. CLOSET
CLR CLEAR(ANCE)
CMU CONCRETE MASONRY
UNIT
COL COLUMN
CONC CONCRETE
CONN. CONNECTION
CONST CONSTRUCTION
CONSTR CONSTRUCTION
CONT CONTINUOUS
CONTR. CONTRACTOR
CTR CENTER
CTSK COUNTERSUNK
CW COLD WATER
D
D
E
(E)
EA
EJ
EL
EXISTING
EACH
EXPANSION JOINT
ELEVATION
ELEC ELECTRICAL
ELEV ELEVATION
ENCL ENCLOSURE
EOS EDGE OF SLAB
EQ EQUAL
EQUIP EQUIPMENT
EW EACH WAY
EXP EXPANSION
EXPO EXPOSED
EXT EXTERIOR
F
FA FIRE ALARM
FAU FORCED AIR UNIT
DEEP, DEPTH
DBL DOUBLE
DET DETAIL
DIM DIMENSION
DN
DS
DOWN
DOWNSPOUT
DWG DRAWING
DWR DRAWER
FLOOR DRAIN
FDN FOUNDATION
FG FINISH GRADE
FIN FINISH
FLASH FLASHING
FLR FLOOR
FLUOR FLOURESCENT
FOC FACE OF CONCRETE
FOF FACE OF FINISH
FOM FACE OF MASONRY
FOS FACE OF STUD
FPRF FIREPROOFING
FRMG FRAMING
FS
FT
FULL SIZE
FOOT, FEET
FTG FOOTING
FURR FURRING, FURRED
G
G NATURAL GAS
GA GAUGE
GALV GALVANIZED
GND GROUND
GR GRADE
GYP GYPSUM
H
H
HB
HC
HIGH
HOSE BIB
HOLLOW CORE
HDWD HARDWOOD
HDWR HARDWARE
HORIZ HORIZONTAL
HR
HT
HOUR
HEIGHT
HVAC HEATING,
VENTILATION & AIR
CONDITIONING
HW HOT WATER
I
ID
INCL
INSIDE DIAMETER
INLCUDE, INCLUDING
INSUL INSULTATION
INT INTERIOR
J
JST
JT
T
T
JOIST
JOINT
L
LAM LAMINATE
LF
LVR LOUVER
M
MATL MATERIAL
MAX MAXIMUM
MECH MECHANICAL
MEMB MEMBRANE
MFG MANUFACTURING
MFR MANUFACTURER
MIN MINIMUM
MISC MISCELLANEOUS
MO MASONRY OPENING
MTD MOUNTED
MTL METAL
MULL MULLION
N
N NORTH
N/A NOT APPLICABLE
NIC NOT IN CONTRACT
NO NUMBER
NOM NOMINAL
NTS NOT TO SCALE
O
O/ OVER
OA OVERALL
W
W WEST
W/ WITH
W/O WITHOUT
WD WOOD
WH WATER HEATER
WP WATERPROOFING
WPM WATERPROOFING
MEMBRANE
WT WEIGHT
TREAD
T&B TOP & BOTTOM
T&G TONGUE & GROOVE
TEL TELEPHONE
TEMP TEMPERATURE,
TEMPORARY
LINEAR FEET THK THICK, THICKNESS
THRES THRESHOLD
TOS TOP OF SLAB
TOW TOP OF WALL
TP
TS
TV
TYP TYPICAL
U
UNF UNFINISHED
UON UNLESS OTHERWISE
NOTED
V
VERT VERTICAL
VIF
VOL VOLUME
R
RAD RADIUS
RD ROOF DRAIN
REF REFERENCE
REINF REINFORCED
REQ REQUIRED
RESIL RESILIENT
REV REVISION
RFG ROOFING
RM ROOM
RO ROUGH OPENING
S
S
SC
SOUTH
SOLID CORE
SCHED SCHEDULE
SECT SECTION
SEP SEPARATION,
SEPARATE
SHT SHEET
SIM SIMILAR
SLDG SLIDING
SPEC SPECIFICATION
SQ SQUARE
STD STANDARD
STL STEEL
STRUCT STRUCTURAL
SUSP SUSPENDED
SYS SYSTEM
OBSC OBSCURE
OC ON CENTER
OD OUTSIDE DIAMTER
OD OVERFLOW DRAIN
OPNG OPENING
OPP OPPOSITE
P
PERIM PERIMETER
PL
PLAS PLASTER
PLBG PLUMBING
PLYWD PLYWOOD
PR PAIR
PROPERTY LINE
TOP OF PAVEMENT
TOP OF STEEL
TELEVISION
VERIFY IN FIELD
1
A
X.XDM
DEMOLITION GRIDLINE
WINDOW SYMBOL
100.A REFERENCE N0.
ROOM NO.
SHEET NO.
MATCH LINE
SIDE CONSIDERED
PORTION IS THE
THE SHADED
BUILDING GRID
LINES
DEMOLITION
GRID NUMBER
FLOOR LEVEL 3
REVISION CLOUD
(CLOUD AROUND
REVISION NO.
REV. OPTIONAL)
DOOR SYMBOL
100.1 REFERENCE N0.
ROOM NO.
ROOM LABEL
ROOM NAME
ROOM NAME
101
FLOOR LEVEL
ROOM NO.
DETAIL
AREA REFERENCE
A9.2
5 DETAIL NO.
SHEET NO.
4
A3-3.01
SHEET NO.
SECTION
SECTION NO.
EXTERIOR
X
XX-XX
ELEVATION
ELEVATION NO.X SHEET NO.
WALL TYPE
PARTITION NUMBER
INTERIOR
ELEVATION
4 XX-XX
1
3
SHEET NO.
CEILING HEIGHT
123
8'-0"CEILING HEIGHT
OR EQUIPMENT
EQUIPMENT NO.
ARCHITECTURAL NORTH
WORK POINT,
CONTROL POINT
OR DATUM POINT
NORTH ARROW
14'-2 1/2"
2 ELEVATION NO.
DIMENSION STRING
TRUE
N
O
R
T
H
SYMBOL LEGEND N.T.S. ABBREVIATIONS N.T.S
SHEET INDEX
VICINITY MAP
SCOPE OF WORK
TENANT IMPROVEMENT FOR NEW RESTAURANT/TAKE OUT
FOOD. INTERIOR REMODEL TO ADD (N) 3 TYPE I HOODS,
(1) AC UNIT, COOKING EQUIPMENT, NON BEARING
PARTITION WALLS, OFFICE, STORAGE , COUNTER PREP
AREAS & SEATING.
BUILDING CODE NOTES:
1. REFERENCE CODES:
1.1 2022 CALIFORNIA BUILDING CODE
1.2 2022 CALIFORNIA MECHANICAL CODE
1.3 2022 CALIFORNIA PLUMBING CODE
1.4 2022 CALIFORNIA ELECTRICAL CODE
1.5 2022 CALIFORNIA TITLE-24 ENERGY CODE
1.6 2022 CALIFORNIA FIRE CODE
1.7 2022 CALIFORNIA GREEN BUILDING STANDARDS
1.8 2024 CITY OF SANTA ANA AMENDMENTS
CODES
2. LEGAL DESCRIPTION
APN#: 398-257-07
LOT 2/13
TRACT No: 783
BLOCK: 13
LOT SIZE: 2,098 SQ.FT
AREA OF WORK. 1,867 SQ.FT
3. (EX.) OCCUPANCY GROUP : B (RETAIL)
(N) OCCUPANCY GROUP : B (FOOD
ESTABLISHMENT )
4. OCCUPANT LOAD : 30
5. (EX.)CONSTRUCTION TYPE: TYPE III-B ( NON
SPRINKLERED)
6. # OF STORIES: 1
7. PARKING :NO CHANGE IN PARKING
8. (EX.) # EXITS: 2
THIS DRAWING, SPECIFICATIONS AND
IDEAS, DESIGNS THEREBY ARE AND SHALL
REMAIN THE PROPERTY OF IG DRAFTING &
DESIGN AND NO PART THEREOF SHALL BE
COPIED DISCLOSED TO OTHERS OR USED
IN CONNECTION WITH ANY WORK OR
PROJECT FOR WHICH THERE HAVE BEEN
PREPARED AND DEVELOPED, WITHOUT THE
WRITTEN CONSENT OF IG DRAFTING &
DESIGN, VISUAL CONTACT WITH THESE
DRAWINGS SHALL CONSTITUTE EVIDENCE
OF ACCEPTANCE OF THESE RESTRICTIONS.
DO
N
C
H
U
R
R
O
S
1
2
3
4
TENANT:
MECHANICAL
PLUMBING:
IMAGINE ARCHITECTURE
MEHRDAD HAJILOO
P: (818) 826-1627
E: imagine.archla@gmail.com
ELECTRICAL: Joseph Zhang JS Engineering
705 Los Olivos Dr.,
San Gabriel, CA 91775
626-497-0558
DESIGNER: IMAGINE ARCHITECTURE/
Steven Garcia
P: (818) 826-1627
E: imagine.archla@gmail.com
PROJECT CONTACT INFORMATION
PROJECT DESCRIPTION
Jaime Nunez Gomez
donchurrosgomez@gmail.com
714-717-7946
T-1.0 ARCHITECTURAL -VICINITY MAP, SITE PLAN
-STANDARD ABBREVIATIONS
-SCOPE OF WORK, SHEET INDEX
T-1.1 ARCHITECTURAL -GENERAL NOTES
T-1.2 ARCHITECTURAL -ACCESSIBLE NOTES & DETAILS
T-1.3 ARCHITECTURAL -ACCESSIBLE NOTES & DETAILS
T-1.4 ARCHITECTURAL -ACCESSIBLE NOTES & DETAILS
A-0.0 ARCHITECTURAL -SITE PLAN
A-1.0 ARCHITECTURAL -EXISTING PLAN, GEN. NOTES
-PROPOSED FLOOR PLAN
A-1.1 ARCHITECTURAL -REFLECTED CEILING PLAN
-EGRESS PLAN
A-1.2 ARCHITECTURAL -DIMENSIONAL PLAN
-OCCUPANT LOAD PLAN
A-1.3 ARCHITECTURAL -ROOF PLAN
-EQUIPMENT SCHEDULE
A-2.0 ARCHITECTURAL -DETAILS, RESTROOM PLAN/ELEV.
A-3.0 ARCHITECTURAL -INTERIOR ELEVATIONS, SECTIONS
A-4.0 ARCHITECTURAL -FRAMING DETAILS, DOOR SCHEDULE
KIT-1 ARCHITECTURAL -EQUIPMENT PLAN, EQUIPMENT SCHEDULE,
HEALTH NOTES, SITE PLAN
S-1.1 STRUCTURAL -GENERAL NOTES & SCHEDULE
S-1.2 STRUCTURAL -GENERAL NOTES & SCHEDULE
S-2.1 STRUCTURAL -FOUNDATION PLAN & DETAILS
S-2.2 STRUCTURAL -ROOF FRAMING PLAN & DETAILS
E-1 ELECTRICAL -NOTES, EQUIPMENT PLAN, SINGLE LINE DIAGRAM,
PANEL LOAD SCHED.
E-2 ELECTRICAL -POWER PLAN, LIGHTING PLAN, ROOF PLAN.
E-3 ELECTRICAL -TITLE 24
M-0.1 MECHANICAL -STANDARD DETAILS, GENERAL NOTES
M-0.2 MECHANICAL -STANDARD DETAILS
M-1.0 MECHANICAL -HVAC PLAN & HOOD PLAN
M-1.1 MECHANICAL -ROOF PLAN, EQUIPMENT SCHEDULE
M-1.2 MECHANICAL -HOOD ELEVATIONS & SECTIONS
M-2.0 MECHANICAL -UL LISTED HOOD SPEC SHEET
M-2.1 MECHANICAL -UL LISTED HOOD SPEC SHEET
M-2.1 MECHANICAL -FAN SPEC SHEETS
M-3.0 MECHANICAL -TITLE 24
M-3.1 MECHANICAL -TITLE 24
P-0.1 PLUMBING -GENERAL NOTES, STANDARD DETAILS
P-0.2 PLUMBING -TITLE 24
P-1.0 PLUMBING -WASTE & VENT PLAN, SPEC SHEET
P-1.1 PLUMBING - WASTE & VENT RISER DIAGRAM
P-2.0 PLUMBING -HOT & COLD WATER PLAN
P-3.0 PLUMBING -GAS PLAN & RISER DIAGRAM
MEP & FIRE SUPPRESSION SYSTEM - UL 300 ARE DEFERRED
SUBMITTALS AND ARE THE RESPONSIBILITY OF THE TENANT.
IG DRAFTING & DESIGN SCOPE OF WORK DOES NOT INCLUDE
THESE ITEMS. AND IS NOT RESPONSIBLE FOR ANY CHANGES,
MODIFICATIONS, OR ADDITIONS TO FIRE SUPPRESSION SYSTEM.
ANY SIGN RELATED WORK IS UNDER A SEPARATE PERMIT
NOTE: UNISEX RESTROOM PROVIDED
215 W. 4TH ST,
SANTA ANA, CA 92701
SEE OCCUPANT LOAD PLAN ON SHEET A-1.2
OWNER:Luis Soto
lsrbuilders@icloud.com
858-437-4247
4
4
STEVEN GARCIA
DESIGNER
Bldg #101120043
Elect #20183405
Plumb #30147491
Mech #40139290
APPROVALS:
PLNG - H. Jacinto
BLDG - CSG
POLICE - B. Martin
PUBLIC WORKS - B. Sarlak
ELECT/PLUMB/MECH - CSG
215 W 4th St
1/22/2025
T-1.1
THIS DRAWING, SPECIFICATIONS AND
IDEAS, DESIGNS THEREBY ARE AND SHALL
REMAIN THE PROPERTY OF IG DRAFTING &
DESIGN AND NO PART THEREOF SHALL BE
COPIED DISCLOSED TO OTHERS OR USED
IN CONNECTION WITH ANY WORK OR
PROJECT FOR WHICH THERE HAVE BEEN
PREPARED AND DEVELOPED, WITHOUT THE
WRITTEN CONSENT OF IG DRAFTING &
DESIGN, VISUAL CONTACT WITH THESE
DRAWINGS SHALL CONSTITUTE EVIDENCE
OF ACCEPTANCE OF THESE RESTRICTIONS.
DO
N
C
H
U
R
R
O
S
1
2
3
4
GENERAL CONDITIONS
1. THE CONTRACTOR SHALL BE RESPONSIBLE FOR DELIVERING A COMPLETE AND USABLE
FACILITY WHICH WILL FUNCTION PER THE DESIGN INTENT OF THE CONSTRUCTION DOCUMENTS.
THE INTENT OF THESE DRAWINGS IS TO PROVIDE DIRECTION TO BUILD AND COMPLETE THE
CONSTRUCTION OF TENANT IMPROVEMENTS OF AN EXISTING GROUND FLOOR LEASED AREA
FOR FOOD SERVICE PURPOSES AND LOCATED IN CALIFORNIA.
2. EXECUTE WORK IN ACCORDANCE WITH ANY AND ALL APPLICABLE FEDERAL, STATE &
LOCAL CODES, REGULATIONS, LAWS, ORDINANCES AND MANUFACTURER'S
RECOMMENDATIONS AND TRADE AND REFERENCE STANDARDS. IN CASE OF CONFLICT, MOST
STRINGENT REQUIREMENTS SHALL APPLY. REFER TO BUILDING AND SITE DATA AND PROJECT
STATISTICS FOR REFERENCE CODE INFORMATION.
3. THE DRAWINGS AND SPECIFICATIONS WERE PREPARED TO THE BEST OF OUR
KNOWLEDGE TO CONFORM WITH 2022 CALIFORNIA BUILDING CODE AS ADAPTED AND
AMENDED BY THE GOVERNING REGULATORY AGENCIES. SHOULD THE CONSTRUCTION BE
DELAYED BEYOND IMMEDIATE PERMITTING, THESE DRAWINGS SHOULD BE REVIEWED FOR
CONFORMITY WITH LOCAL AND NATIONAL REQUIREMENTS. IN THE EVENT OF A CONFLICT
BETWEEN APPLICABLE CODES AND REGULATIONS AND REFERENCED STANDARDS OF THESE
DRAWINGS, THE MORE STRINGENT PROVISIONS SHALL APPLY AND THE GREATER QUANTITY
AND THE HIGHER QUALITY (AS DETERMINED BY ARCHITECT) SHALL BE FURNISHED. NO
VARIATION REQUIRED BY A BUILDING OFFICIAL SHALL BE BINDING ON THE DESIGNER.
4. REFERENCE AND INCORPORATE PROJECT MANUAL AND ALL CONSULTANT/OWNER
SPECIFICATIONS, SURVEYS, AND TESTING REPORTS AS PART OF THE COMPLETE
CONSTRUCTION DOCUMENT SET.
5. EACH AND EVERY PART OF THE BUILDING (FRAMING, FINISHES, EQUIPMENT, ELECTRICAL,
PLUMBING, MECHANICAL AND STRUCTURAL BUILDING SYSTEMS) SHALL BE INSTALLED AND
CONNECTED BY THE CONTRACTOR AND BE FULLY OPERATIONAL. CONTRACTOR IS REQUIRED
TO PROVIDE AND CONNECT ALL UTILITIES REQUIRED FOR SUCH ITEMS. ALL WORK AND
NECESSARY RELATED WORK REQUIRED TO PROVIDE A FULLY OPERATIONAL BUILDING WITHIN
THE SCOPE OF WORK SHALL BE INCLUDED IN THE TOTAL BID, INCLUDING ALL NECESSARY
LABOR, MATERIALS, EQUIPMENT, TAXES, FEES, SPECIAL INSPECTIONS, INSURANCE, ETC.
6. CONTRACTOR IS FULLY RESPONSIBLE FOR COORDINATING SUBCONTRACTORS AND ALL
MEANS AND METHODS OF INSTALLATION AND SEQUENCING RELATED TRADES.
7. CONTRACTOR SHALL VERIFY ALL EXISTING CONDITIONS AND ALL DIMENSIONS BY FIELD
MEASUREMENT AND SHALL TAKE ANY AND ALL MEASUREMENTS NECESSARY TO VERIFY THE
DRAWINGS OR PERFORM THE WORK PROPERLY . IMMEDIATELY NOTIFY THE DESIGNER OF ANY
DISCREPANCIES AND OBTAIN CLARIFICATION BEFORE PROCEEDING WITH THE AFFECTED
WORK. ANY DISCREPANCIES SHALL BETWEEN THE DRAWINGS AND THE DIMENSIONS SHALL
NOT BE THE REASON FOR ANY EXTRA COST OR DELAY IN THE EXECUTION OF THE WORK AND
SHALL BE PERFORMED PER THE INTENT OF THE CONTRACT DOCUMENTS AT NO EXTRA COST
TO THE OWNER (THE ARCHITECT SHALL B E CONSULTED IN ALL CASES WHERE CUTTING INTO A
PORTION OF THE BUILDING IS EITHER DESIRABLE OR NECESSARY SO THAT THE SATISFACTORY
REINFORCEMENT MAY BE PROVIDED)
8. OTHER WORK NOT INCLUDED IN THIS CONTRACT WILL BE EXECUTED DURING THE
CONTRACT TIME, INCLUDING BUT NOT EXCLUSIVE TO FURNITURE INSTALLATION AND
TELECOMMUNICATION CABLING. MAKE ALL PROVISIONS FOR NOT IN CONTRACT (N.I.C.) ITEMS,
COOPERATE WITH PERSONNEL AND PROVIDE ACCESS TO AREAS, SERVICES, ETC.
COORDINATED CONSTRUCTION ACTIVITIES UNDER THIS CONTRACT WITH N.I.C. ACTIVITIES SO AS
NOT TO IMPEDE THEIR WORK AND SCHEDULE.
9. COORDINATE SPACE REQUIREMENTS AND INSTALLATION OF ELECTRICAL,
TELECOMMUNICATION, PLUMBING, MECHANICAL, AND SECURITY SYSTEM WORK. ESTABLISH
ROUTING FOR PIPING, WIRING, DUCTWORK, AND CONDUIT PARALLEL WITH THE LINE OF THE
BUILDING U.O.N. UTILIZE SPACES EFFICIENTLY TO MAXIMIZE ACCESSIBILITY FOR OTHER
INSTALLATIONS, FOR MAINTENANCE, AND FOR REPAIRS. IN FINISHED AREAS CONCEAL PIPING,
DUCTWORK WIRING AND CONDUITS.
10. THE CONTRACTOR SHALL APPLY FOR AND OBTAIN AT HIS EXPENSE, ALL PERMITS
REQUIRED BY REGULATORY AGENCIES. THE CONTRACTOR'S COSTS SHALL INCLUDE THE COST
OF PROPER INSURANCE AS REQUIRED BY STATE AND LOCAL LAWS. NATIONAL BUILDING
REGULATIONS OR CODES TO ADEQUATELY PROTECT PERSONS AND PROPERTY. A COPY OF
SUCH INSURANCE COVERAGE SHALL BE FURNISHED TO THE OWNER AND LANDLORD PRIOR TO
COMMENCEMENT OF ANY WORK.
11. PRIOR TO BEGINNING WORK, PROVIDE CERTIFICATE OF INSURANCE, PAYMENT AND
PERFORMANCE BONDS AS REQUIRED.
12. LIEN WAIVERS AND PAYMENT AFFIDAVITS SHALL BE REQUIRED FROM THE CONTRACTOR,
SUBCONTRACTOR, AND VENDORS AT ALL PROGRESS PAYMENTS AND FINAL PAYMENT BEFORE
ANY PAYMENT NEED BE MADE BY THE OWNER.
13. ALL WORK PERFORMED BY CONTRACTOR AND SUBCONTRACTORS SHALL BE
WARRANTED FOR CORRECTION OR REPLACEMENT OF DEFECTIVE WORK FOR THE PERIOD OF
1 YEAR FROM THE DATE OF SUBSTANTIAL COMPLETION.
14. THE CONTRACTOR SHALL NOT DETAIL, ORDER AND/OR FABRICATE ANY MATERIAL
WITHOUT FIRST COORDINATING THE SAME WITH ACTUAL FIELD CONDITIONS. THE CONTRACTOR
ALONE IS RESPONSIBLE THE PROPER FITTING AND CONNECTION OF MATERIALS AND
EQUIPMENT.
15. INSTALL PREFABRICATED ITEMS AND FINISHES IN ACCORDANCE WITH MANUFACTURER'S
RECOMMENDATIONS. PREPARE ALL ADJOINING FINISHES, FRAMING AND FLASHINGS PER
MANUFACTURER'S RECOMMENDATIONS WHERE MAINTENANCE OR INSTALLATION
INSTRUCTIONS ARE NOT PROVIDED OR ARE IN CONFLICT WITH THE DRAWINGS OR
SPECIFICATIONS, THE FURNISHING CONTRACTOR SHALL PROVIDE COPIES TO ALL AFFECTED
SUBCONTRACTORS
16. ALL ITEMS LISTED OR CALLED OUT ON THE DRAWINGS BY MANUFACTURER AND MODEL
NUMBER ARE TO SET PERFORMANCE STANDARDS FOR QUALITY AND FUNCTION. ALTERNATE
ITEM TYPES MAY BE SUBMITTED TO THE DESIGNER FOR REVIEW. FOR ITEMS SPECIFIED "OR
EQUAL" THE ARCHITECT OR DESIGNER ALONE SHALL DETERMINE EQUALITY BASED ON
INFORMATION SUBMITTED BY CONTRACTOR.
17. CHANGES IN THE WORK: DO NOT PROCEED WITH ANY WORK REQUIRING ADDITIONAL
COMPENSATION BEYOND THE CONTRACT AMOUNT WITHOUT WRITTEN AUTHORIZATION FROM
THE OWNER. FAILURE TO OBTAIN AUTHORIZATION SHALL INVALIDATE ANY CLAIM FOR EXTRA
COMPENSATION
18. WHEREVER THE WORD "PROVIDE" IS USED IT SHALL MEAN CONTRACTOR TO PROVIDE
AND INSTALL U.O.N.
19. OWNER FURNISHED ITEMS OR ITEMS "BY OTHERS" ARE TO BE PURCHASED BY OWNER
AND INSTALLED BY THE CONTRACTOR. CONTRACTOR IS RESPONSIBLE FOR COORDINATING
DIMENSIONS, POWER AND OTHER SPECIAL REQUIREMENTS WITH THE PROVIDER OF SUCH
PRODUCTS.
21. SUBMITTALS: SUBMIT SAMPLES, SHOP DRAWING, & PRODUCT DATA TO DESIGNER FOR
REVIEW PRIOR TO FABRICATION. SEE ENGINEER CONSULTANT AND INTERIOR DESIGN
DRAWINGS FOR ADDITIONAL SUBMITTAL REQUIREMENTS
22.1. PROCEDURES SUBMITTAL PREPARATION - CONTRACTOR MAY USE ANY OR ALL OF THE
FOLLOWING OPTIONS:
A. SUBCONTRACTORS AND SUPPLIERS PROVIDE ELECTRONIC (PDF) SUBMITTALS TO
CONTRACTOR VIA THE SUBMITTAL EXCHANGE WEBSITE.
B. SUBCONTRACTORS AND SUPPLIERS PROVIDE PAPER SUBMITTALS TO GENERAL
CONTRACTOR WHO ELECTRONICALLY SCANS AND CONVERTS TO PDF FORMAT.
C. SUBCONTRACTORS AND SUPPLIERS PROVIDE PAPER SUBMITTALS TO SCANNING
SERVICE WHICH ELECTRONICALLY SCANS AND CONVERTS TO PDF FORMAT.
22.1. CONTRACTOR SHALL REVIEW AND APPLY ELECTRONIC STAMP CERTIFYING THAT THE
SUBMITTAL COMPLIES WITH THE REQUIREMENTS OF THE CONTRACT DOCUMENTS INCLUDING
VERIFICATION OF MANUFACTURER / PRODUCT, DIMENSIONS AND COORDINATION OF
INFORMATION WITH OTHER PARTS OF THE WORK.
22.2. CONTRACTOR SHALL TRANSMIT EACH SUBMITTAL TO ARCHITECT USING THE SUBMITTAL
EXCHANGE WEBSITE, WWW.SUBMITTALEXCHANGE.COM.
22.3. ALLOW DESIGNER ONE WEEK TO REVIEW AND COMMENT. DESIGNER REVIEW WILL BE
FOR CONFORMANCE WITH DESIGN CONCEPT ONLY.
22.4. DESIGNER REVIEW COMMENTS WILL BE MADE AVAILABLE ON THE SUBMITTAL
EXCHANGE WEBSITE FOR DOWNLOADING. CONTRACTOR WILL RECEIVE EMAIL NOTICE OF
COMPLETED REVIEW.
22.5. DISTRIBUTION OF REVIEWED SUBMITTALS TO SUBCONTRACTORS AND SUPPLIERS IS THE
RESPONSIBILITY OF THE CONTRACTOR.
22.6. THE COST OF SUBMITTAL EXCHANGE SERVICES HAS BEEN PAID IN FULL BY THE OWNER.
23. PRODUCT DATA SUBMITTALS:
CONTRACTOR SHALL SUBMIT ALL PRODUCT INFORMATION, OPERATION AND MAINTENANCE
MANUALS, MATERIAL SAFETY DATA SHEETS AND WARRANTEE INFORMATION FOR ALL
PRODUCTS PRODUCT SUBMITTALS SHALL INCLUDE
A. LIGHT FIXTURES, SWITCHING, SENSORS
B. EQUIPMENT, APPLIANCES AND FIXTURES PROVIDED BY CONTRACTOR
C. HVAC EQUIPMENT
D. PONT OF SALE EQUIPMENT
E. HARDWARE CUT SHEETS
F. DOOR AND HARDWARE SCHEDULE AND CUT SHEETS
G. PLUMBING FIXTURES, DEVICES, ACCESSORIES AND EQUIPMENT
H. OUTDOOR SEATING, BARRIERS, TABLES
25. SHOP DRAWINGS SUBMITTALS:
SHALL BE SCALED SHOWING EQUIPMENT IN RELATION TO BUILDING COMPONENTS WALLS,
FINISHES AND RELATED EQUIPMENT, DRAWINGS SHALL INDICATED (MANUFACTURER, MAKE &
MODEL #) AND PIPE/DUCT SIZES AND LAYOUT, MOUNTING REQUIREMENTS, AND CLEARANCES.
PROVIDE SHOP DRAWINGS IN .DWG AND .PDF FORMAT.
A. CASEWORK AND MILLWORK SHOP DRAWINGS
B. HVAC DUCT LAYOUT AND EQUIPMENT
C. FIRE SPRINKLER LAYOUT
D. AV EQUIPMENT AND MENU BOARD
E. CUSTOM KITCHEN EQUIPMENT
F. SIGNAGE (SUBMIT ONE ADDITIONAL COPY TO LANDLORD)
26. WORK SCHEDULE:
CONTRACTOR MUST SUBMIT A WORK SCHEDULE TO THE DESIGNER PRIOR TO BEGINNING THE
WORK. THE SCHEDULE WILL INCLUDE SHOP DRAWING REVIEW PERIODS, SUBCONTRACTORS,
INSPECTIONS AND APPLICATIONS FOR PAYMENTS AND DATE OF SUBSTANTIAL COMPLETION.
THE SCHEDULE SHALL INCLUDE CRITICAL PATH ACTIVITIES. CONTRACTOR SHALL PROVIDE AN
UPDATED PROGRESS SCHEDULE WITH EACH APPLICATION FOR PAYMENT.
27. CLOSEOUT:
WITHIN 14 DAYS OF SCHEDULED COMPLETION, CONTRACTOR SHALL SUBMIT REQUEST FOR
PAYMENT FOR SUBSTANTIAL COMPLETION WITH A PUNCH LIST OF ITEMS REMAINING FOR
FINAL COMPLETION. WITHIN 5 DAYS OF RECEIPT OF CONTRACTOR'S PUNCH LIST, ARCHITECT
AND OWNER SHALL OBSERVE PROGRESS AND PROVIDE A FINAL PUNCH LIST FOR
COMPLETION.
28. FINAL PAYMENT:
PRIOR TO RELEASE OF FINAL PAYMENT CONTRACTOR SHALL SUPPLY TO THE OWNER A
PROJECT MANUAL IN A 3 RING BINDER CONTAINING THE FOLLOWING:
A. FINAL INSPECTION RECORDS AND CERTIFICATE OF OCCUPANCY
B. ALL PAYMENT APPLICATIONS AND RECEIPTS
C. LIST OF SUBCONTRACTORS AND CONTACT INFORMATION
D. RELEASE OF LIENS FOR ALL WORK COMPLETED BY CONTRACTOR AND
SUBCONTRACTOR.
E. STATEMENT OF WARRANTEE ON LABOR
F. BINDER OF OPERATION AND MAINTENANCE DATA FOR ALL PRODUCTS, MATERIALS
AND EQUIPMENT ALL PRODUCT LITERATURE, WARRANTEES, AND MANUFACTURER CONTACT
INFORMATION FOR ALL PRODUCTS AND ASSEMBLIES.
G. SPARE PARTS, REPLACEMENT PARTS AND MATERIALS AS PROVIDED BY EQUIPMENT
MFR'S FINAL CLEANING OF SURFACES BY A PROFESSIONAL SERVICE.
H. REPRODUCIBLE DRAWINGS WITH AS-BUILT CONDITIONS NOTED.
I. SPECIFIED QUANTITIES OF MAINTENANCE MATERIALS.
J. HVAC BALANCE REPORT.
29. DEFERRED PERMIT SUBMITTALS & APPROVALS:
PRIOR TO COMMENCING WORK SPECIFIED BELOW, CONTRACTOR SHALL SUBMIT ALL
DOCUMENTATION, ENGINEERING AND TRADE PERMIT APPLICATIONS, AND FEES AS REQUIRED
TO THE GOVERNING AGENCY FOR PERMIT. CONTRACTOR SHALL VERIFY AND COORDINATE
ALL DRAWINGS AND SPECIFICATIONS OF WORK PRIOR TO SUBMITTING AND SHALL SUBMIT 2
COPIES TO THE ARCHITECT FOR REVIEW. DIFFERED SUBMITTAL ITEMS SHALL INCLUDE:
A. MODIFICATIONS TO FIRE SPRINKLER AND FIRE ALARM
30. CONTRACTOR SHALL RETAIN A COMPETENT FULL-TIME REPRESENTATIVE SATISFACTORY
TO THE OWNER AND TENANT, TO BE PRESENT AT THE JOB SITE DURING CONSTRUCTION
ACTIVITY ON THE PROJECT. THE REPRESENTATIVE SHALL NOT BE CHANGED EXCEPT WITH THE
CONSENT OF THE OWNER. THE REPRESENTATIVE SHALL BE IN FULL CHARGE OF THE WORKS
AND ALL INSTRUCTIONS GIVEN TO THE REPRESENTATIVE SHALL BE BINDING.
31. THE CONTRACTOR SHALL MAINTAIN A COMPLETE SET OF THE CONTRACT DRAWINGS FOR
RECORD MARK-UP PURPOSES THROUGHOUT THE CONTRACT TIME. MARK UP THESE
DRAWINGS DURING THE COURSE OF WORK TO SHOW BOTH CHANGES AND ACTUAL
INSTALLATION IN SUFFICIENT FORM TO COMPRISE A COMPLETE RECORD FOR THE OWNER'S
PURPOSES. GIVE PARTICULAR ATTENTION TO WORK WHICH WILL BE CONCEALS AND
DIFFICULT TO MEASURE AND RECORD AT A LATER DATE, AND TO WORK WHICH MAY REQUIRE
SERVICING OR REPLACEMENT DURING THE LIFE OF THE PROJECT. BIND PRINTS INTO
MANAGEABLE SETS WITH DURABLE PAPER COVERS LABELED "AS-BUILT DRAWINGS", AND
TRANSMIT TO OWNER.
32. THE ARCHITECT OF RECORD SHALL BE THE LEAD POINT OF CONTACT FOR ALL
QUESTIONS, CLARIFICATIONS, AND REQUESTS FOR INFORMATION. ALL CHANGES TO THE
CONTRACT DOCUMENT AND RESULTING CHANGES TO THE CONTRACT SUM (IF ANY) OR
CHANGES IN THE PROJECT DURATION (IF ANY) WILL BE ISSUED AND/OR APPROVED BY
OWNER AND ARCHITECT OF RECORD.
33. CONSTRUCTION PROGRESS MEETINGS SHALL OCCUR WEEKLY AND BE ATTENDED BY
CONTRACTOR, ARCHITECT AND/OR OWNER. MEETINGS SHALL BE AT THE JOB SITE OR BY
TELECONFERENCE
JOB SITE PREPARATION, PROTECTION AND MAINTENANCE
1. BEFORE BEGINNING WORK VERIFY LOCATION OF ALL EXISTING UTILITIES. MAINTAIN ALL
SYSTEMS, SUCH AS BUT NOT LIMITED TO, WATER, SEWER, POWER, TELEPHONE, ETC. THAT
SUPPLY THIS AND OTHER BUILDINGS ON THE SITE OR ADJACENT SITES DURING ALL PHASES
OF THE WORK.
2. SCHEDULE AND PERFORM WORKS SO THAT OTHER TENANTS IN THE BUILDING ARE NOT
DISTURBED. SCHEDULE ALL WORK FOR REGULAR BUSINESS HOURS UNLESS OTHERWISE
NOTED BY BUILDING REGULATIONS OR THE CONTRACT DOCUMENTS. PROVIDE 48 HOURS
NOTIFICATION TO ALL AFFECTED PARTIES OF ANY INTERRUPTIONS REQUESTED. PROVIDE
LOOP SERVICE AS REQUIRED UNLESS ALL AFFECTED PARTIES ACCEPT THE INTERRUPTION
REQUEST.
3. CONSTRUCTION OPERATION PROCEDURES AND METHODS ARE THE RESPONSIBILITY OF
THE CONTRACTOR INSOFAR AS THEY DO NOT PRESENT HAZARDS TO PERSONNEL OR
PROPERTY OR INFRINGE ON WORK SCHEDULES FOR NORMAL SITE ACTIVITIES, OTHER
CONTRACTORS, VENDORS AND THE BUILDING'S STANDARDS FOR CONSTRUCTION ACTIVITIES.
4. VERIFY ACCESS TO JOB SITE, FREIGHT ELEVATION USE, SCHEDULE AND SIZE, AND
CLEARANCES INTO AND OUT OF THE BUILDING. MAINTAIN AND PROVIDE SERVICE ACCESS AT
ALL TIMES FOR ALL EQUIPMENT PER MFR. RECOMMENDATIONS.
5. PROJECT AREA SITE AND SIDEWALK SHALL BE MAINTAINED A CLEAN AND SAFE AT ALL
TIMES. KEEP PROJECT AREA BROOM CLEAN. ALL DEBRIS SHALL BE REMOVED TO A LEGAL
DISPOSAL AREA ON A REGULAR BASIS. PROVIDE CONSTRUCTION BARRIERS AND DUST
CONTROL. PROVIDE VEHICLE GRAVEL MUD TRAP AT SITE ENTRANCE. ADJACENT ROADWAYS
DRIVEWAYS AND SIDEWALKS SHALL BE KEPT CLEAR AND MUD AND GRAVEL AT ALL TIMES.
PROVIDE PEDESTRIAN PROTECTION AS REQUIRED FOR SAFETY OF TENANTS, PEDESTRIANS
AND JOBSITE PERSONNEL.
6. MAINTAIN ALL BUILDING LIFE SAFETY, FIRE PROTECTION, AND SECURITY SYSTEMS AT ALL
TIMES. DO NOT BLOCK EXITS.
7. REPORT ANY HAZARDOUS MATERIALS ENCOUNTERED TO THE OWNER/LANDLORD.
8. DO NOT ALLOW ADHESIVE ODOR AND OTHER FUMES FROM CONSTRUCTION ACTIVITIES TO
ENTER HVAC SYSTEM.
9. DAMAGE TO SIDEWALK OR ADJACENT PROPERTIES RESULTING FROM CONSTRUCTION
ACTIVITY IS THE SOLE RESPONSIBILITY OF THE CONTRACTOR. VERIFY SIDEWALK
MAINTENANCE AND REPAIRS WITH GOVERNING ADJACENCY PRIOR TO COMMENCING WORK.
TENANT'S CONTRACTOR WILL REPAINT AND/OR REPAIR LANDLORD'S PROPERTY (BULKHEADS,
NEUTRAL PIERS, REAR CORRIDORS, ETC) DAMAGED DURING TENANT IMPROVEMENT.
12. CONTRACTOR SHALL BE RESPONSIBLE FOR A THOROUGH PROFESSIONAL CLEANING OF
THE ENTIRE FACILITY PRIOR TO OWNER TAKEOVER DATE. ALL EXPOSED HORIZONTAL AND
VERTICAL SURFACES INCLUDING BUT NOT LIMITED TO THE FOLLOWING MUST BE WIPED CLEAN
AND FREE OF DUST: WALLS, EXPOSED STRUCTURAL MEMBERS STAIRS AND RAILINGS,
CABINETRY, DUCT WORK, SPRINKLER PIPES, INTERIOR AND EXTERIOR GLAZING. ALL FLOORS
MUST BE MOPPED CLEAN.
13. PROVIDE ALL NECESSARY SHORING AND BRACING IN ORDER TO PERFORM THE WORK.
CONTRACTOR IS RESPONSIBLE FOR ANY STRUCTURAL CALCULATIONS OR DRAWINGS
REQUIRED FOR TEMPORARY SHORING OR BRACING.
14. ALL PERSONS WORKING AT THIS SITE MUST IMPLEMENT APPLICABLE PORTIONS OF THE
STATE STORM WATER BEST MANAGEMENT PRACTICES MANUAL FOR CONSTRUCTION TO THE
MAXIMUM EXTENT PRACTICABLE TO PREVENT EROSION AND SEDIMENT FROM ENTERING INTO
THE STORM DRAIN SYSTEM. FAILURE TO UTILIZE ADEQUATE CONTROLS IS A VIOLATION OF
LOCAL CODES AND ORDINANCES. A COPY OF THE MANUAL IS AVAILABLE UPON REQUEST AT
THE PERMIT SERVICE CENTER AND AVAILABLE ONLINE AT WWW.CABMPHANDBOOKS.COM
DEMOLITION AND WASTE MANAGEMENT
1. CONTRACTOR SHALL SUBMIT A WASTE REDUCTION MANAGEMENT PLAN PER LOCAL WASTE
MANAGEMENT AUTHORITY REQUIREMENTS. PLAN SHALL INCLUDE PROJECT ADDRESS,
DESCRIPTION, TYPE AND QUANTITY OF MATERIALS TO BE DISCARDED AND METHOD OF
DISPOSAL (REUSE, RECYCLE, LANDFILL). PLAN MUST INDICATE MEANS AND METHODS FOR
(ON-SITE) SEPARATION AND (OFF-SITE) LANDFILL DIVERSION DESIGNATING SPACE FOR
SEPARATION AND DESCRIBING ENVIRONMENTAL CONTROL MEASURES (MUD, DUST, ODOR,
AND NOISE CONTROL)
A. REUSED (FIXTURES, EQUIPMENT, DOORS, WINDOWS, ETC.)
B. RECYCLED (CONCRETE, EARTH, WOOD, METALS, GYPSUM, PAPER, CARPET)
C. % OF MATERIALS TO LANDFILL
2. PRIOR TO BEGINNING WORK CONTRACTOR SHALL DESIGNATE AN AREA OF THE JOBSITE
FOR WASTE MANAGEMENT AND RECYCLING THAT SHALL BE MAINTAINED SOLELY FOR THIS
PURPOSE FOR THE DURATION OF THE PROJECT.
3. SEPARATE CONSTRUCTION DEBRIS AND SALVAGE FOR REUSE, RECYCLING AND REFUSE.
REUSABLE ITEMS SHALL BE KEPT SECURE AND PROTECTED FROM WEATHER OR CONSTRUCTION
AND SHALL INCLUDE BUT NOT LIMITED TO WINDOWS, DOORS, FIXTURES, TILE, LUMBER,
FURNISHINGS AND EQUIPMENT. RECYCLABLE ITEMS SHALL INCLUDE BUT NOT LIMITED TO
CARDBOARD, PAPER, SCRAP METAL, GLASS, UNPAINTED WOOD (NAILS OK), PALLETS, UNPAINTED
SHEETROCK, LANDSCAPING COMPOSITE (SEPARATED FROM RUBBISH), CONCRETE, CARPET PAD.
4. IF USING A DEBRIS BOX, HAULING COMPANY MUST BE HAVE NON-EXCLUSIVE FRANCHISE
APPROVED BY THE APPROPRIATE CITY WASTE MANAGEMENT AGENCIES.
5. WHERE NEW DOOR OR WINDOW IS SHOWN IN EXISTING OPENING VERIFY ROUGH OPENING
REQUIREMENTS, REMOVE FRAMING AS REQUIRED.
6. PRIOR TO DEMOLITION CONTRACTOR TO WALK JOBSITE WITH OWNER TO CLEARLY INDICATE
ITEMS TO BE SALVAGED FOR OWNER RE-USE. DISPOSAL OF ITEMS NOT SALVAGED SHALL BE THE
RESPONSIBILITY OF THE CONTRACTOR AND SHALL BE SUBJECT TO PROJECT WASTE REDUCTION
PLAN.
7. REMOVE AND DISPOSE OF ALL ITEMS IN THE WAY OF NEW WORK WHETHER SHOWN OR NOT,
U.O.N. PROTECT (E) WORK TO REMAIN. REPLACE ANY DAMAGED WORK TO REMAIN. PROTECT ITEMS
TO BE REMOVED AND RELOCATED, SEE FURNISHING FIXTURE AND EQUIPMENT SCHEDULE FOR
ITEMS TO BE SALVAGED AND RELOCATED. CONTRACTOR IS RESPONSIBLE FOR PROTECTION
AND/OR
REPLACEMENT OF ANY ITEMS DAMAGED AS THE RESULT OF DEMOLITION OR CONSTRUCTION.
8. IF USING A DEBRIS BOX, HAULING COMPANY MUST HAVE NON-EXCLUSIVE FRANCHISE
APPROVED BY THE APPROPRIATE CITY WASTE MANAGEMENT AGENCIES.
PREPARATION FOR NEW WORK
1. DISCONNECT ALL UTILITIES, WATER, SEWER, ELECTRIC AND GAS, AT LOCATIONS CLEAR OF
PROJECT WORK AREAS. CLEARLY STAKE/DEMARK SERVICE DISCONNECT LOCATIONS. PROVIDE
HOSE BIB WITH VACUUM BREAKER TYPE BACKFLOW PREVENTION DEVICE FOR DUST CONTROL.
[CBC
3306] MAINTAIN ALL UTILITIES IN SAFE AND WORKING CONDITIONS AT ALL TIMES. REMOVE ALL
ABANDONED UTILITIES AND CAP AT NEAREST BRANCH TO REMAIN. PROTECT EXISTING UTILITIES TO
REMAIN. CAP OR EXTEND (E) UTILITIES TO FOR NEW WORK. DEACTIVATE AND DEMOLISH EXISTING
OUTLETS THAT ARE NOT NOTED TO REMAIN, U.O.N.
2. FILL AND LEVEL ALL DAMAGED FINISHES AND SUBSTRATE. REPLACE EXISTING SUBSTRATES AS
REQUIRED. PROVIDE SUBSTRATE FOR ALL FINISHES WITHIN MANUFACTURER'S DIMENSIONAL AND
MOISTURE CONTENT TOLERANCES. VERIFY REQUIREMENTS WITH FINISH MFR.
3. SURFACES TO REMAIN, WHEN CUT, DAMAGED, OR OTHERWISE DISTURBED DURING
DEMOLITION, INSTALLATION OF NEW WORK OR REMOVAL AND REINSTALLATION OF EXISTING ITEMS
TO REMAIN SHALL BE RESTORED AS NECESSARY TO PROVIDE A SMOOTH, CLEAN, COMPLETELY,
PROPERLY DETAILED AND FINISHED INSTALLATION WITH APPEARANCE, FUNCTION, AND WEARING
QUALITIES EQUAL TO NEW WORK. REPAIR FIREPROOFING ON STRUCTURAL ELEMENTS AND FIRE
RATED ASSEMBLIES. THE CONTRACTOR SHALL PROVIDE AND MAINTAIN THE INTEGRITY OF ALL
SCAFFOLDING, DUST BARRIERS, BARRICADES, BRACING, SHORING, AND STRUCTURAL SYSTEMS
REQUIRED FOR INSTALLATION OF NEW WORK.
4. CUT AND PATCH AND FINISH NEW MATERIAL TO MATCH ADJACENT (EXISTING) SURFACES TO
REMAIN. REFINISH (E) ADJACENT FINISHES TO NEAREST MATERIAL BREAK POINT OR PLANAR
TRANSITION I.E. INSIDE CORNER, EXISTING JOINT OR LOCATION APPROVED BY ARCHITECT. USE
MATERIALS THAT ARE IDENTICAL TO EXISTING MATERIAL, U.O.N. USE MATERIALS WHOSE INSTALLED
PERFORMANCE WILL EQUAL OR SURPASS THAT OF EXISTING MATERIALS INCLUDING SOUND AND
FIRE RATINGS. IN NO CASES SHALL ANY CUT AND PATCHED MATERIALS IN EXPOSED OR OCCUPIED
SPACES REDUCE THE BUILDING'S AESTHETIC QUALITIES, OR RESULT IN VISUAL EVIDENCE OF
CUTTING AND PATCHING. WORK THAT IS CUT AND/OR PATCHED IN AN UNSATISFACTORY MANNER
SHALL BE REPLACED TO THE ARCHITECT'S AND BUILDING OWNER'S SATISFACTION AT THE
CONTRACTOR'S EXPENSE.
5. ANY THROUGH SLAB ELECTRICAL, MECHANICAL, OR PLUMBING PENETRATIONS THAT ARE TO BE
REMOVED OR ABANDONED MUST BE DONE SO FOLLOWING LANDLORD RULES AND REGULATIONS,
AND SHALL MAINTAIN ALL FIRE RATINGS AND TENANT BARRIERS ANY NEW CORING THROUGH SLAB
WILL REQUIRE SCANNING PROCEDURES OF SLAB PRIOR TO WORK. REVIEW WITH LANDLORD
BUILDING ENGINEERS PRIOR TO CORING FOR ANY NEW ELECTRICAL, MECHANICAL, OR PLUMBING.
6. ALL MATERIAL, EQUIPMENT AND HARDWARE BEING INSTALLED AND/OR CONNECTED INTO THE
BUILDING RISERS, SYSTEMS AND INFRASTRUCTURE, SHALL BE APPROVED IN ADVANCE BY THE
BUILDING MANAGEMENT PRIOR TO CONTRACTOR INSTALLING IT
7. ALL "KITCHEN AND WET AREAS" AREAS ON ALL FLOORS ABOVE GRADE SHALL INCLUDE A WATER
TIGHT MEMBRANE TO PREVENT WATER MIGRATION TO THE FLOOR BELOW. THIS MEMBRANE SHALL
COVE UP THE WALLS AND PIPE PENETRATIONS INSIDE WALLS SHALL ALSO BE SEALED WATER
TIGHT.
LATICRETE 9235 SYSTEM AND/OR ELASTO-DECK 5500 SYSTEM. VERIFY APPROPRIATE SYSTEM WITH
THE BUILDING CHIEF ENGINEER PRIOR TO PROCEEDING.
FRAMING
1. DIMENSIONS SHOWN ARE TO FACE OF FINISH U.O.N. FOLLOW NUMERICAL DIMENSIONS. DO NOT
SCALE DRAWINGS. WRITTEN DIMENSIONS TAKE PRECEDENCE. DIMENSION LINES SHOW FACE OF
FINISH UNLESS OTHERWISE NOTED. HEIGHTS ARE DIMENSIONED FROM TOP OF FINISHED FLOOR,
U.O.N. DIMENSIONS ARE NOT ADJUSTABLE WITHOUT PRIOR APPROVAL FROM ARCHITECT.
2. ALL CLEAR DIMENSIONS SHALL BE CONSTRUCTED TO WITHIN 1/8" TOLERANCE ALONG THE
FULL DIMENSIONED LENGTH. DIMENSIONS NOT INDICATED AS CLEAR SHALL BE EXACT WITHIN 1/8" IN
10'-0" ALONG FULL HEIGHT AND LENGTH OF PARTITIONS. CONTRACTOR SHALL NOT ADJUST
DIMENSIONS MARKED "CLEAR" OR "CLR" WITHOUT APPROVAL FROM THE ARCHITECT.
3. DETAILS SHOWN ARE TYPICAL, SIMILAR DETAILS OCCUR IN SIMILAR CONDITIONS.
4. ARCHITECT TO REVIEW FRAMING, PLUMING, AND ELECTRICAL PRIOR TO DRYWALL. CHARGES TO
REFRAME UNREVIEWED PARTITIONS WILL NOT BE ACCEPTED.
5. PROVIDE STRUCTURAL BACKING/BLOCKING FOR ALL WALL AND CEILING MOUNTED/BRACED
COMPONENTS PER EQUIP. MFR. REQUIREMENTS, UNLESS OTHERWISE NOTED. SEE PLANS AND
ELEVATIONS FOR LOCATIONS AND TYPICAL MOUNTING HEIGHTS.
6. PROVIDE THERMAL INSULATION WITH MOISTURE BARRIER ON INSIDE AT NEW WALLS AND
WALLS/CEILINGS OPENED FOR CONSTRUCTION IN THERMAL ENVELOPE. R-19 INSULATION AT ALL
EXTERIOR WALLS AT WALLS, R-30 AT EXTERIOR FLOORS AND ROOF. SEE TITLE 24 REQUIREMENTS.
SEE BUILDING SECTIONS AND TITLE 24 REQUIREMENTS FOR BUILDING INSULATION AND THERMAL
MOISTURE PROTECTION.
7. ONLY MATERIALS PERMITTED BY CONSTRUCTION TYPE STATED, ARE ALLOWED. PER CBC TABLE
601 AND SECTION 603 FOR TYPE I AND TYPE II BUILDINGS WHEN APPLICABLE.
8. ALL LUMBER SHALL BE D.F.-LARCH #2 OR BETTER, S.S.D. U.O.N. WHERE POSSIBLE USE WOOD
BASED MATERIALS AND PRODUCTS CERTIFIED IN ACCORDANCE WITH THE FORESTRY
STEWARDSHIP
COUNCIL'S PRINCIPLES AND CRITERIA FOR WOOD COMPONENTS INCLUDING, BUT NOT LIMITED TO
STRUCTURAL FRAMING, GENERAL DIMENSIONAL FRAMING, FLOORING, FINISHES, FURNISHINGS,
BRACING AND FORM WORK.PROVIDE CHAIN OF CUSTODY DOCUMENTATION FOR ALL NON-FSC
CERTIFIED WOOD.
9. FLUSH FRAMED JOISTS SHALL BE ATTACHED W/ STL. JOIST HANGERS, SIMPSON OR EQ.
EXPOSED HARDWARE TO BE SIMPSON APG SPECIALTY COLLECTION (SHOP PAINTED)
10. ALL FRAMING LUMBER IN CONTACT WITH EARTH OR CONCRETE SHALL BE PRESSURE TREATED
WITH ALKALINE COPPER QUAT (ACQ) OR COPPER AZOLE (CBA-A, CBA-B). NO COPPER CHROMATED
COPPER ARSENATE (CCA). FASTENERS, FRAMING HARDWARE AND ALL METALS IN CONTACT WITH
PRESSURE TREATED TO BE GALVANIZED SPECIFIED BY MANUFACTURER FOR USE WITH PRESSURE
TREATED LUMBER.
11. ALL WOOD NAILERS, BLOCKING, RAISED PLATFORM FRAMING, PLYWOOD AND WHERE DETAILED
OR REQUIRED FOR THE ATTACHMENT OF FINISHED MATERIALS SHALL BE PRESSURE TREATED WITH
FIRE RETARDANT CHEMICALS IN ACCORDANCE WITH ASTM #84-77. THE MATERIAL SHALL BEAR THE
IDENTIFICATION OF AN AUTHORITATIVE TESTING OR INSPECTION AGENCY ACCEPTABLE TO THE
GOVERNING AGENCY WITH THE PERFORMANCE RATING THEREOF.
12. WOOD MOLDINGS, TRIM PANELS, SHALL BE DIRECTLY ATTACHED TO A FIRE-RESISTIVE
SUBSTRATE WITH MECHANICAL FASTENERS AND/OR ADHESIVE. FURRING IF REQUIRED, SHALL BE
FIRE-STOPPED WITH SOLID BLOCKING SPACED A MAXIMUM OF 8' ON CENTER. WOOD FURRING
WHERE REQUIRED SHALL BE FIRE-TREATED LUMBER CONFORMING WITH ASTM E84 AND HAVING
THICKNESS NOT LESS THAN 1-1/4"
13. PROVIDE BACKING AND/OR BLOCKING CONCEALED IN WALLS FOR WALL MOUNTED
ACCESSORIES AND ITEMS.
14. VERIFY PARTITION THICKNESS FOR INTERNAL INCLUSIONS SUCH AS PLUMBING, PANEL BOXES,
FIRE EXTINGUISHER CABINETS, ETC
15. LOCATE AND PROVIDE SERVICE ACCESS FOR ALL EQUIPMENT PER MFR. RECOMMENDATIONS
AND AS REQUIRED BY CODE FOR ALL UNOCCUPIED SPACES. MIN. SIZES FOR ATTIC ACCESS 20x30
w/30" HEADROOM AND CRAWLSPACE 18x24 (CBC 1209) ACCESS PANELS SHALL BE TIGHT FITTING
FLUSH TRIMMED AND PAINT. TEXTURE AND FINISH TO MATCH ADJACENT WALL TEXTURE., TYP.
U.O.N.
HINGES AND HARDWARE SHALL BE CONCEALED WITH MAGNETIC CATCH. ATTIC,
16. INSULATE WALLS WITH PLUMBING WITH ACOUSTIC FACED BATT INSULATION U.O.N. AND
ACOUSTIC SEALANT, WRAP ALL PLASTIC WASTE LINES. SEE TITLE 24 FOR THERMAL REQUIREMENTS.
17. CAULK OR SEAL ALL ACCESSIBLE MAJOR CRACKS AND JOINTS AND OTHER OPENINGS IN
BUILDING EXTERIOR. SEAL ALL ACCESSIBLE MAJOR OPENINGS FROM THE CONDITIONED LIVING
SPACE INTO UNHEATED AREAS, INCLUDING, BUT NOT LIMITED TO, THOSE FOUND AROUND
PLUMBING
VENT PIPES, ELECTRICAL WIRING, OR FURNACE FLUE PIPES.
FINISHES D
1. SEE FINISH SCHEDULE FOR ALL INTERIOR FINISHES. SEE EXTERIOR ELEVATIONS FOR EXTERIOR
FINISHES.
2. TOILET AND BATHROOM FLOORS SHALL HAVE A SMOOTH, HARD NONABSORBENT SURFACE
EXTENDING UP WALLS A MIN OF 6". TUB AND SHOWER WALLS TO BE A SMOOTH, HARD,
NONABSORBENT SURFACE OVER MOISTURE RESISTANT UNDERLAYMENT TO A MIN. HT. OF 72"
ABOVE
DRAIN INLET. TOILET ROOM WALLS WITHIN 24" OF URINALS OR TOILETS SHALL HAVE SMOOTH HARD,
NONABSORBENT SURFACE TO MIN 48" ABOVE FLOOR. (CBC 1210). SEE FIN. SCHEDULE AND DETAILS.
3. THRESHOLDS OR CHANGES IN FLOOR SURFACES SHALL NOT EXCEED 1/4" VERTICAL. CHANGES
IN ELEVATION BETWEEN 1/4" AND 1/2" SHALL BE SLOPED NO GREATER THAN 1:2. (CBC 11B-303)
CHANGES GREATER THAN 1/2" SHALL BE RAMPED 1:12 (CBC 11B-303.4)
4. WHERE NO THRESHOLD OR SILL IS INDICATED, FLOORING SHALL BE CONTIGUOUS BETWEEN
ADJOINING ROOMS WITH NO TRANSITIONS, BREAKS, OR THRESHOLDS U.O.N. CLOSET FLOORING
SHALL BE SAME MATERIAL AS ADJOINING ROOM U.O.N.
5. MARINE GRADE PLYWOOD SHALL BE USED AT ALL WET LOCATIONS INCLUDING SUBSTRATES
FOR STONE AND TILE FINISHES . U.O.N.
6. GYP. BD. SHALL NOT BE STORED ON SITE WITHOUT WEATHER AND MOISTURE PROTECTION. DO
NOT INSTALL UNTIL WEATHER PROTECTION FOR THE INSTALLATION IS PROVIDED.
7. GYPSUM BOARD THICKNESS TO BE 5/8" THICK TYPE X MOLD/MILDEW RESISTANT TYPICAL.
TYPE-X AT FIRE RATED LOCATIONS. MOISTURE RESISTANT AT HIGH HUMID/DAMP LOCATIONS.
INSTALL GYP. BD. WITH LONG DIMENSION PERPENDICULAR TO FRAMING.
8. NEW AND EXISTING GYP. BD. SHALL BE TAPED AND SANDED TO BE LEVEL 4 TYP. LEVEL 3 AT
CEILINGS, U.O.N. WITH NO VISIBLE JOINTS, TAPE, SEAMS OR TROWEL MARKS. SURFACES ARE TO BE
FREE OF IMPERFECTIONS AND MARKINGS SUBJECT TO BLEED THROUGH, AND SHALL HAVE SMOOTH
SURFACE READY TO RECEIVE SCHEDULED FINISH. APPLY NON-STAINING MOISTURE RESISTANT
PRIMER/SEALER. WHERE DEEP TONE PAINT IS SCHEDULED, SKIM COAT FULL SURFACE OF
SUBSTRATE LEVEL 5 FINISH.
9. PROVIDE TRIMS, REGLETS, MOULDINGS, TRANSITIONS, ACCESSORIES AND MOLDINGS, BY
FINISH MFR. U.O.N.
10. ALL PAINTED SURFACES TO BE ROLLER OR SPRAY APPLIED, NO BRUSH STROKES, NAP MARKS.
PRIMER SHALL BE APPROVED FOR SUBSTRATE AND PERM < 1. VERIFY PAINT COLOR AND TEXTURE
WITH OWNER. SWATCH PAINT EACH ROOM WITH SELECTED COLOR FOR OWNER APPROVAL.
SWATCH TO BE 24"X24" MIN. PROVIDE LOW/NO VOC PAINTS WHEN AVAILABLE.
11. PRIME AND PAINT ALL EXPOSED AND SEMI-EXPOSED GYP. BD. A MINIMUM OF 2 COLOR COATS
OF ACRYLIC LATEX, EGGSHELL SHEEN,USE 3 COLOR COATS FOR DARK COLORS. SEMIGLOSS AT
BASE AND TRIM, AND HIGH GLOSS AT WET LOCATIONS.
12. APPLY ONE COAT OF BITUMINOUS PAINT TO CONCEALED ALUMINUM SURFACES IN CONTACT
WITH CEMENTITIOUS OR OTHER DISSIMILAR MATERIALS.
13. FINISH SEALED WOOD AND ADHESIVES SHALL BE FORMALDEHYDE FREE, LOW/NO VOC.
14. INSTALL ALL FINISHES AND SUBSTRATES PER MANUFACTURER RECOMMENDATIONS. PRIOR TO
INSTALLATION VERIFY MOISTURE CONTENT, DIMENSIONAL TOLERANCES AND MATERIAL
STABILITY/ACCLIIMATION AND ADHESIVE/FASTENERS WITH MANUFACTURER. 4% MAX. DIFF. IN
MOISTURE CONTENT FOR WOOD FLOORING AND SUBSTRATE.
15. CAULK JOINTS COLOR TO MATCH DARKER OF ANY ADJOINING MATERIAL. CONTRACTOR SHALL
COMPLETE THE CLOSURE AND PROTECTION OF PENETRATIONS IN SHAFTS, ROOFS, WALLS, CEILING
AND FLOORS BY SEALING ALL CRACKS AROUND DOORS, LOUVERS, CONDUIT PIPES, DUCTS AND
THE
LIKE, WITH FIRE SEALANT, FIRE SAFING, FIRESTOP FOAM OR OTHER FIRE-RESISTIVE MATERIALS
ACCEPTABLE TO THE FIRE MARSHAL, BUILDING OFFICIALS AND THE ARCHITECT TO CONTAIN ROOM
ENVIRONMENTS, COMPLETE FIRE RATED ASSEMBLIES, AND PROVIDE WEATHERTIGHT ENCLOSURE.
16. GENERAL INTERIOR BUILDING SEALANT SHALL BE SINGLE COMPONENT, PAINTABLE,
ACRYLICLATEX
SEALANT TREMCO ACRYLIC LATEX OR APPROVED EQUAL WITH COLOR WHITE.
17. SEALANT BACK-UP: NON-STAINING, CLOSED-CELL FOAM COMPATIBLE WITH SEALANT TO BE
USED. SIZE AND SHAPE TO CONTROL DEPTH OF SEALANT AND TO ALLOW 20 TO 50 PERCENT
COMPRESSION UPON INSERTION.
18. PROVIDE SILICONE RUBBER-BASED SEALANT: ONE-PART, NONSAG ELASTOMERIC SEALANT
RESISTANT TO MILDEW. PROGLAZE BY TREMCO, 786 MILDEW RESISTANT SILICONE SEALANT BY
DOW CORNING. USE AT WALL MOUNTED URINALS, WATER CLOSETS, LAVATORIES, SINKS, DRINKING
FOUNTAINS, COUNTERTOPS, AND SPLASHES.
19. PROVIDE NON-HARDENING ACOUSTICAL SEALANT: TREMCO ACOUSTICAL SEALANT, USG
ACOUSTICAL SEALANT. USE AT PERIMETER AND PENETRATIONS OF ACOUSTICAL-TYPE INTERIOR
PARTITIONS. PROVIDE SHEET CAULKING AND ELECTRICAL BOX SEALER. USE AT ELECTRICAL AND
TELECOMMUNICATION BOX PENETRATIONS OF ACOUSTICAL-TYPE INTERIOR PARTITIONS.
20. GLAZING SEALANT SHALL BE ASTM C920, TYPE S, GRADE NS CLASS 25, USE G, ONE-PART,
STRUCTURAL STRENGTH SILICONE RUBBER BUILDING SEALANT WITHIN MINIMUM PLUS-OR-MINUS 50
PERCENT JOINT MOVEMENT CAPABILITY. DOW CORNING 11795 SILICONE BUILDING SEALANT, "G.E.
SILGLAZE N," OR APPROVED EQUAL WITH COLOR BLACK FOR FRAMED GLAZING AND CLEAR FOR
BUTT GLAZED JOINTS, U.O.N.
21. INSTALL RESILIENT TILE USING MANUFACTURER'S RECOMMENDED ADHESIVE. NO PERIMETER
TILES SHALL BE LESS THAN HALL OF FULL WIDTH, U.O.N.
22. INSTALL WALLCOVERING USING MANUFACTURER'S RECOMMENDED ADHESIVE. WALLCOVERING
SHALL BE CONTINUOUS BEHIND COUNTERTOPS, CHAIR RAILS, ETC. SEAMS SHALL BE TIGHT, NEAT
AND NOT LESS THAN 12" FROM CORNERS. DO NOT END WALLCOVERING AT AN OUTSIDE CORNER.
23. INTERIOR WALL AND CEILING FINISHES SHALL BE CLASSIFIED IN ACCORDANCE WITH ASTM E
84 OR UL723 PER CBC SECTION 803. THE MAXIMUM FLAME SPREAD SHALL NOT EXCEED THE LIMITS
OF TABLE 803.13 FOR THE FINISH MATERIALS ON THE CEILING AND INTERIOR WALLS. A
CERTIFICATION OF MATERIALS SHALL BE REQUIRED TO PASS INSPECTION IN THE FIELD.
24. FIBROUS INTERIOR FLOOR MATERIALS SHALL BE A MINIMUM OF CLASS II IN ACCORDANCE WITH
NFPA 253 PER CBC 804 AND SHALL COMPLY WITH ASTM STANDARD E 648 HAVING A SPECIFIC
OPTICAL DENSITY SMOKE RATING NOT TO EXCEED 450 PER ASTM E 662. CERTIFICATION OF
MATERIALS SHALL BE REQUIRED TO PASS INSPECTION IN THE FIELD.
25. INTERIOR DECORATIVE MATERIALS, TRIM AND FABRICS S HALL MEET FLAME PROPAGATION
CRITERIA OF NFPA 701 OR SHALL BE NON-COMBUSTIBLE. SUBMIT MANUFACTURER TEST RESULTS
PRIOR TO INSTALLATION. (CBC 806)
26. GUARDS SHALL BE PROVIDED WHEREVER ELEVATION CHANGES IS 30" OR GREATER. MIN .
LOADS FOR HANDRAILS AND GUARDS IS 50# PER LIN. FOOT IN ANY DIRECTION AND 200#
CONCENTRATED POINT LOAD AT THE TOP. MINIMUM LOAD FOR INFILL COMPONENTS IS 50# PER
SQUARE FOOT.
27. MAXIMUM INFILL OPENING SHALL OCCLUDE THE PASSAGE OF A 4" SPHERE AT ANY POINT. 6" AT
THE OPENING FORMED BY THE TREAD AND RISER.
28. DISSIMILAR METALS SHALL BE EFFECTIVELY ISOLATED FROM EACH OTHER TO PREVENT
GALVANIC ACTION.
29. ALL EXPOSED STONE EDGES ARE TO BE FINISHED TO CREATE A STRAIGHT AND SMOOTH JOINT,
UNLESS NOTED OTHERWISE. FINISH ON EDGES TO MATCH FINISH ON FACE OF STONE U.O.N.
30. SMOOTH, DURABLE, EASILY CLEANABLE, LIGHT-COLORED AND NONABSORBENT FINISHES WILL
BE REQUIRED WHERE FOOD IS PREPARED/PACKAGED, CUSTOMER SELF-SERVE LOCATIONS WHERE
FOOD IS DISPENSED, WAIT STATIONS, UTENSILS ARE WASHED/STORED, JANITORIAL AREAS,
RESTROOMS, EMPLOYEE LOCKER ROOMS, WALK-IN FRIDGE/FREEZERS, FOOD STORAGE, GARBAGE
AND REFUSE STORAGE. FLOORS MUST ALSO EXTEND INTEGRALLY UP WALLS MIN. 4" WITH A MIN.
3/8" RADIUS.
DOORS AND WINDOWS
1. SEE DOOR SCHEDULE AND WINDOW SCHEDULE FOR SIZES AND TYPES OF FENESTRATION AND
DAYLIGHT AND VENTILATION PROVISIONS. VERIFY R.O. REQUIREMENTS WITH WINDOW/DOOR
MANUFACTURER.
2. UNDERCUT ALL DOORS TO CLEAR TOP OF FINISHED FLOOR, INCLUDING, BUT NOT LIMITED TO
CARPET, TILES, ETC. AS APPLICABLE BY 1/4' MAXIMUM, U.O.N.
3. DOOR HANDLES PULLS AND LATCHES AND LOCKS, SHALL BE ACCESSIBLE AND NOT REQUIRE
TIGHT GRASPING, TIGHT PINCHING OR TWISTING OF THE WRIST TO OPERATE. HARDWARE SHALL BE
COMMERCIAL GRADE ADA COMPLIANT AND PROVIDED BY DOOR/WINDOW MANUFACTURER U.O.N.
SEE DOOR SCHEDULE.
4. HARDWARE SETS SHALL BE APPROVED BY DOOR MANUFACTURER FOR LOCATION AND
BACKSETS, FUNCTION, DOOR THICKNESS, WEIGHT AS INDICATED.
5. EXTERIOR DOORS SHALL BE WEATHER-STRIPPED AND HAVE WATER TIGHT FLASHING.
6. HINGES SHALL BE HEAVY DUTY QTY. OF 3 PER LEAF, 4 AT DOORS GREATER THAN 7' FINISH
SHALL MATCH DOOR HARDWARE U.O.N.
FIRE SPRINKLER
1. A PERMIT BY A LICENSED FIRE PROTECTION ENGINEER FOR ALL LIFE SAFETY WORK,
IS REQUIRED PRIOR TO WORK ON ANY FIRE PROTECTION SYSTEM OR COMPONENT (NEW
SYSTEM OR MODIFICATIONS TO EXISTING) AS REQUIRED TO COMPLY WITH APPLICABLE
CODES, SUBMIT THREE (3) SETS OF SHOP DRAWINGS, CALCULATIONS AND
SPECIFICATIONS FOR AUTOMATIC FIRE EXTINGUISHING SYSTEM FOR PERMIT TO THE
APPROPRIATE MUNICIPAL AGENCY FOR APPROVAL. SPRINKLER SYSTEM IS TO COMPLY
WITH NFPA 13 LOCAL FIRE PROTECTION SPRINKLER ORDINANCE.
2. ALL AUTOMATIC SPRINKLER SYSTEMS SHALL BE SUPERVISED BY AN APPROVED
CENTRAL PROPRIETARY OR REMOTE STATION SERVICE OR A LOCAL ALARM WHICH WILL
GIVE AN AUDIBLE SIGNAL AT A CONSTANTLY ATTENDED LOCATION. FIRE SPRINKLER
SYSTEMS TO BE TIED INTO AN ALARM SYSTEM PER C.B.C. 903.4 AND NFPA-13
3. FIRE DEPARTMENT ACCESS MUST BE PROVIDED AND MAINTAINED SERVICEABLE
PRIOR TO AND DURING CONSTRUCTION.
4. THE INSPECTION, HYDROSTATIC TEST AND FLUSHING OF THE A.F.E.S. SHALL BE
WITNESSED BY THE BUILDING INSPECTOR SPECIALIST/FIRE MARSHAL, AND NO PIPING
SHALL BE COVERED OR HIDDEN FROM VIEW UNTIL AN INSPECTION HAS BEEN
COMPLETED. ALLOW APPROPRIATE TIME FOR SCHEDULING AN APPOINTMENT.
5. PROVIDE AN EMERGENCY TELEPHONE ON THE JOB SITE PRIOR TO ANY
CONSTRUCTION.
6. ALL A.F.E.S AND LIFE SAFETY EQUIP. IS SHOWN FOR DESIGN INTENT ONLY. G.C.
SHALL SUBMIT ENGINEERED DRAWINGS TO ALL PARTIES HAVING JURISDICTION,
INCLUDING ARCHITECTS, AND SHALL OBTAIN ALL APPLICATIONS, PERMITS AND PAY ALL
RELATED FEES.
7. FIRE SPRINKLER HEADS SHALL BE FLUSH-MOUNT TYPE TO MATCH BUILDING
STANDARD AND CENTERED IN CLG. TILES, U.N.O. NOTIFY ARCHITECT OF QUESTIONABLE
LOCATIONS PRIOR TO INSTALLATION.
10. CHANGES TO FIRE SPRINKLER SYSTEM FOR NEW PARTITION LAYOUT TO BE
ENGINEERED AND PROVIDED BY THE CONTRACTOR.
11. SEE MEP DRAWINGS FOR ADDITIONAL FIRE SPRINKLER AND ALARM NOTES NOTES
ELECTRICAL
1. PROVIDE ALL DEVICE ROUGH-IN INCLUDING CONDUIT, BOXES, PANELS, WITH A PULL
STRING AT EACH TELEPHONE/DATA, COMMUNICATION AND/OR SECURITY DEVICE
LOCATION, U.O.N. VERIFY REQ. OF DATA, TELCOM AND SECURITY CABLE WITH
ARCHITECT AND CABLE MFR. PROVIDE MIN. SEPARATION OR ADEQUATE
INSULATION/SPACING TO MINIMIZE INTERFERENCE BETWEEN DATA/SIGNAL AND LINE
VOLTAGE ELECTRICAL CURRENTS. CROSS LINES SHALL BE MADE AT 90°. PROVIDE HOME
RUNS TO AV/COM DISTRIBUTION PANEL. PROVIDE CONDUIT FROM TELECOM. RISER
CLOSET TO TENANT SPACE VERIFY LOCATION WITH ARCHITECT U.O.N.COORDINATE THE
TELEPHONE/DATA SYSTEMS AND INTEGRATE SECURITY SYSTEMS AND SPECIAL
INSTALLATIONS AS REQUIRED, U.O.N.. CONFIRM LOW VOLTAGE, DATA, SECURITY, AND
AUDIO VISUAL WIRING REQUIREMENTS WITH CLIENT'S PROJECT MANAGER AND I.T.
MANAGER
2. ARCHITECTURAL DRAWINGS ARE TO BE USED FOR DEVICE LOCATION ONLY. LOCATE
WALL OUTLETS AT DIMENSION NOTED OR ON STUD WITHIN 12" OF LOCATION SHOWN ON
DOCUMENTS IF NOT NOTED. HORIZONTAL DIMENSIONS ARE TO THE CENTERLINE OF
SINGLE OUTLETS, AND TO THE MIDPOINT OF MULTIPLE ADJACENT OUTLETS. EXCEPT
ISOLATED GROUNDS AND DEDICATED OUTLETS. ALL ELECTRICAL DEVICES SHALL BE
MOUNTED VERTICALLY, U.O.N.
3. PROVIDE ACCESS TO ALL JUNCTION BOXES AND PANELS AND SERVICEABLE
EQUIPMENT. PROVIDE WITH BLANK FLUSH FITTING COVERS TO MATCH FINISH WALL
SURFACE. VERIFY LOCATIONS WITH ARCHITECT. ACCESS PANELS TO BE PAINTABLE,
SQUARE AND FLUSH WITH ADJACENT SURFACE, WITH MAGNETIC PUSH RELEASE LATCH.
PROVIDE ACOUSTICAL SEAL AND INSULATION AT PANELS CONCEALING MOTORS, PUMPS
AND MAGNETIC BALLASTS.
4. ALL CONDUIT THROUGH ROOF AND EXTERIOR WALLS SHALL BE WATERTIGHT. AT
FIRE RATED WALLS, SLEEVES ARE REQUIRED AT BOTH TELEPHONE AND POWER
PENETRATIONS AND ALL PENETRATIONS SHALL BE FIREPROOFED.
5. PROVIDE GROUND FAULT CIRCUIT INTERRUPT PROTECTION AT ALL OUTLET WET
LOCATIONS AS REQUIRED BY CODE, IN BATHROOMS, EXTERIOR, KITCHEN COUNTERTOPS
AND WITHIN 6' OF SINKS.
6. FLOOR OUTLETS WHERE EXPOSED ARE TO BE FULLY FLUSH WITH FINISH SURFACE
WHEN IN CLOSED POSITION. WHERE EXPOSED TO WEATHER OR CONCRETE, PLATE AND
BOX SHALL BE APPROVED BY MANUFACTURER FOR EXTERIOR/CONCRETE INSTALLATION.
COVERS SHALL HAVE METAL COVER PLATE WITH CORD DOOR ALLOWING COVER TO BE
CLOSED WHEN IN USE. (CARLON OR EQ.) FINISH COLOR SHALL MATCH FLOOR COLOR AND
BE SUITABLE FOR HIGH TRAFFIC. WHERE REQUIRED, COLOR FINISHES SHALL BE
FACTORY/SHOP APPLIED ELECTROPLATING/ELECTRODEPOSITON. SUBMIT PRODUCT CUT
SHEET. VERIFY LOCATIONS PRIOR WITH ARCHITECT PRIOR TO ROUGH-IN.
7. CONTRACTOR TO LAYOUT FLOOR OUTLETS FOR ARCHITECT'S REVIEW BEFORE
CORING. CHARGES TO CORRECT UNREVIEWED OUTLETS WILL NOT BE ACCEPTED. ALL
CORING NECESSARY SHALL BE COORDINATED WITH BUILDING LL OR MANAGEMENT TO
SCHEDULE TIME FOR CORE DRILLING.
8. PROVIDE WEATHER PROOF GFCI PROTECTED OUTLETS AT ALL EXTERIOR
LOCATIONS, COLOR TO MATCH EXTERIOR COLOR.
9. PROVIDE TAMPER RESISTANT TWIST LOCK CHILD SAFETY COVER PLATES AT ALL
OUTLETS WITHIN 48" OF FLOOR.
10. FINISH ELECTRICAL OUTLETS AND SWITCHES TO BE IMPACT-RESISTANT AND
OPERABLE WITH ONE HAND WITHOUT GRASPING, PINCHING OR TWISTING OF THE WRIST
WITH A MAXIMUM OPERABLE FORCE OF 5LBS (CBC 111B.6) ROCKER/PUSH PLATE SNAPON
TYPE U.O.N. COLOR OF COVERPLATES SHALL BE WHITE, U.O.N. ALL ELECTRICAL
DEVICES (SWITCHES, PLUGS, ETC.) TO BE U.L. LABELED AND THE SAME COLOR AS
COVERPLATE, U.O.N.
11. DIMMERS TO BE COMPATIBLE WITH FIXTURE AND LIGHTING AND HEATING LOADS.
PROVIDE ADDITIONAL COMPONENTS AS REQUIRED BY DIMMER MANUFACTURER FOR
SPECIFIC APPLICATION. DIMMERS SHALL ALLOW USER PRESET LEVEL CONTROL AND
HAVE LED NIGHTLITE U.O.N.. PROVIDE MINIMUM 1YEAR WARRANTY ON ALL DIMMERS.
12. LIGHTING LOADS SHALL NOT BE INCREASED. EXISTING FIXTURES WILL BE
RELOCATED AS SHOWN. NO NEW FIXTURES SHALL BE ADDED OR REPLACED WITHOUT
APPROVAL FROM ARCHITECT. T-24 MANDATORY MEASURES APPLY.
13. RECESSED LIGHT FIXT. SHALL BE IC RATED AT INSULATED CEILINGS, WITH
THERMALLY MANAGED HEAT-SINKED BALLASTS. TYP.
14. PROVIDED EMERGENCY LIGHTING FOR THE MEANS OF EGRESS ILLUMINATION WITH
BATTERY BACK-UP CAPABLE TO MAINTAIN 1FT CANDLE PATH ILLUMINATION FOR 90
MINUTE DURATION INSTALLED IN ACCORDANCE WITH CBC 2702 NFPA 110 AND 111 (CBC
1008.3)
15. LIGHTING FIXTURES SHALL HAVE A MINIMUM OF 2 YEAR PARTS AND LABOR
WARRANTY. SUBMIT WARRANTY LITERATURE.
16. FLUORESCENT LAMPS SHALL BE WARM WHITE LAMP CCT 2700K-3000K TYP. U.O.N.
LANDLORD PROVIDED FIXTURES SHALL BE LAMPED ACCORDING TO LANDLORD LAMP
STANDARDS
17. ELECTRICAL PANELS, ROUGH IN BOXES TO BE INSTALLED FLUSH TO FINISH. FIRE
RATING OF WALLS MUST BE MAINTAINED AT RECESSED EQUIPMENT. VERIFY ALL
SURFACE MOUNTED BOXES OR PANELS WITH ARCHITECT AND MEP PRIOR TO
INSTALLATION.
7. NEW DOOR AND WINDOW FRAMES TO BE PAINTED SHALL BE FINISHED WITH 2 COATS
BONDING AGENT, 1 LACQUER UNDERCOAT, 2 COLOR COATS ACRYLIC LACQUER WITH
SCHEDULED SHEEN.
8. MASK U.L. LABEL ON DOORS, FRAMES AND FINISHES. DO NOT APPLY FINISHES TO DOOR
OR FRAME LABELS, U.O.N.
9. FINISH VERTICAL EDGES OF DOORS TO MATCH FACES, SEAL TOP AND BOTTOM EDGES.
10. PAINT ASTRAGALS AT FIRE RATED DOORS TO MATCH DOOR COLORS.
11. PANIC HARDWARE, WHERE REQUIRED, SHALL BE LISTED UL305 AND MOUNTED BETWEEN
34 AND 44" ABOVE FLOOR AND EXTEND A MINIMUM OF 1/2 THE OPERABLE LEAF AND HAVE
MAXIMUM OPERABLE FORCE OF 15LBS. U.O.N.
12. INTERIOR, NON-RATED EGRESS DOORS SHALL HAVE A MAX. OPERABLE FORCE OF 5LBS.
U.O.N.
13. EGRESS DOORS SHALL HAVE LANDINGS ON EACH SIDE OF THE DOOR WITH A MIN. WIDTH
OF STAIRWAY OR DOOR (WHICHEVER IS GREATER) AND MIN LENGTH OF 44" IN THE DIRECTION
OF TRAVEL. (CBC 1010). U.O.N.
14. EXITS AND EGRESS DOORS SHALL BE MARKED WITH ILLUMINATED EXIT SIGNS PER CBC
1013, EXIT SIGNS MUST BE READILY VISIBLE FROM THE EGRESS PATH OF TRAVEL AND
MARKED TO INDICATE THE DIRECTION OF TRAVEL WHERE THE EXIT IS NOT IMMEDIATELY
VISIBLE. EXIT SIGNS SHALL BE PLACED SO THAT NO POINT IN AN EXIT ACCESS IS MORE
THAN 100' VIEWING DISTANCE U.O.N. PROVIDE TACTILE EXIT SIGNS AT EXIT DOORS AND
EXIT ACCESS DOORS PER 1013.4
15. EGRESS DOORS SHALL NOT PREVENT OPERATION IN THE DIRECTION OF EGRESS AND
ARE TO BE OPERABLE WITHOUT THE USE OF A KEY OR SPECIAL KNOWLEDGE OR A SIGN
SHALL BE PROVIDED STATING, "THIS DOOR TO REMAIN UNLOCKED WHEN THIS SPACE IS
OCCUPIED." THE SIGN SHALL BE IN LETTERS 1" HIGH ON A CONTRASTING BACKGROUND
(CBC1010.2.4
16. FIRE RATED DOORS AND FRAMES ARE TO BE LABELED BY MANUFACTURER AND MEET
POSITIVE PRESSURE REQUIREMENTS PER UL10C AND UL10B AND SHALL HAVE SELF CLOSING
HINGES OR CLOSERS ADJUSTED FOR TIGHT FITTING FULL CLOSURE WITH CONTINUOUS
SMOKE SEALS AND DRAFT CONTROL ASSEMBLIES
17. PROVIDE SAFETY GLAZING AT THE FOLLOWING LOCATIONS:
A. GLAZING IN DOORS AND GUARDS
B. GLAZING ADJACENT TO DOORS LOCATED LESS THAN 24" FROM DOORS OR
WHEN EXPOSED EDGE IS LESS THAN 60" ABOVE FLOOR
C. DOORS ENCLOSING WET AREAS SERVED BY A DRAIN WITHIN 60" OF FLOOR
D. GLASS PANES WITHIN 18" OF FLOOR OR GREATER THAN 9 SQ. FT.
E. GLAZING ADJACENT TO STAIRWAYS WITHIN 60" OF A TREAD
18. INSTALL SAFETY GLASS WITH MANUFACTURER'S SEAL LOCATED AT THE LOWER RIGHT
CORNER OF THE LITE. CONCEAL TONG MARKS, IF ANY. COMPLY WITH FGMA GLAZING
MANUAL AND THE MANUFACTURER'S PRINTED INSTALLATION INSTRUCTIONS.
19. DISSIMILAR METALS SHALL BE EFFECTIVELY ISOLATED FROM EACH OTHER TO
PREVENT GALVANIC ACTION.
CEILING
1. MINIMUM CEILING HEIGHT AT EGRESS PATH OF TRAVEL TO BE 7'-6" ABOVE FLOOR.
ALLOWABLE PROJECTIONS FOR STRUCTURE OR EQUIPMENT, SHALL NOT REDUCE CEILING
HEIGHT BELOW 6'-8"
2. GENERAL CONTRACTOR SHALL COORDINATE THE WORK OF ALL SUBCONTRACTORS TO
ENSURE CLEARANCES FOR DUCTS, PIPES, CONDUITS, FIXTURES, SUSPENSION SYSTEMS,
ETC. NECESSARY TO MAINTAIN THE FINISHED CEILING HEIGHT NOTED. CONTACT ARCHITECT
TO RESOLVE CONFLICTS BEFORE PROCEEDING. CEILING GRID AND REFRAMING CHARGES
DUE TO CEILING CONFLICTS WILL NOT BE ACCEPTED.
3. VERIFY FIELD CONDITIONS AND LOCATIONS OF ALL NEW AND EXISTING PLUMBING,
MECHANICAL DUCTS, STRUCTURAL ELEMENTS AND OTHER APPLICABLE ITEMS. INSTALL
APPLICABLE NEW PLUMBING, MECHANICAL FANS, DUCTS, CONDUITS, AND OTHER RELATED
ITEMS SO AS TO NOT CONFLICT WITH LIGHT FIXTURES AND OTHER EXISTING AND NEW
CONDITIONS.
4. ARCHITECTURAL PLAN SHALL GOVERN THE LOCATION OF ALL EXPOSED ITEMS. IN THE
EVENT OF DISCREPANCIES, ENGINEERING DRAWINGS TO GOVERN QUANTITY OF LIGHT
FIXTURES FOR COMPLIANCE WITH APPLICABLE CODES.
5. PROVIDE CODE ACCEPTABLE & APPROPRIATE SUSPENSION AND BRACING FOR
INTEGRATION OF CEILING GRID, FIXTURES, AND ABOVE CEILING ITEMS WHEN APPLICABLE.
SUSPENDED ACOUSTIC CEILINGS SHALL BE INSTALLED AND BRACED IN ACCORDANCE WITH
ASTM C635 AND ASTM C636
FIRE PROTECTION
1. PROVIDE PORTABLE FIRE EXTINGUISHERS AS REQUIRED BY CA FIRE CODE AND AS
REQUIRED BY THE LOCAL JURISDICTION.. LOCATIONS SHOWN ON PLANS ARE TO BE VERIFIED
WITH LOCAL FIRE MARSHALL. ARE PORTABLE FIRE EXTINGUISHERS SHALL BE IN
ACCORDANCE WITH CFC 906
2. WHERE FIRE EXSTINGUISHERS ARE REQUIRED IN PUBLIC AREAS OR TO MAINTAIN
REUIRED FLOOR CLEARANCES, PROVIDE PROVIDE RECESSED METAL CABINETS WITH FIRE
EXTINGUISHERS AT LOCATIONS INDICATED ON THE DRAWINGS OR AS REQUIRED BY
OFFICIALS.
3. PENETRATIONS IN FIRE RATED WALLS SHALL BE FIRESTOPPED WITH APPROVED
PENETRATION SYSTEM TESTED IN ACCORDANCE WITH ASTM E814 OR UL 1479 WITH A
MINIMUM POSITIVE PRESSURE DIFFERENTIAL OF .01" AND AN F RATING NOT LESS THAN THAT
OF THE WALL ASSEMBLY. PROVIDE APPROVED LISTING OF ASSEMBLY AND SYSTEM PRIOR
TO INSTALLATION. (CBC 714.4.1)
5. FIRE STOP SEALANT SHALL BE, ONE-PART SILICONE ELASTOMERIC SEALANT, AND FIRE
STOP FOAM, TWO-PART SILICONE RTV FOAM: U.L. RATED FOR 1, 2, AND 3 HOUR FIRE
RESISTIVE RATINGS PER ASTM E-814/UL 1479. DOW CORNING FIRE STOP SEALANT OR 3M
BARRIER CAULK (COORDINATE WITH SPECS). FIRE STOP SEALANT MUST BE ACCEPTABLE TO
LOCAL CODE ENFORCEMENT OFFICIALS.
6. MECHANICAL DUCTS IN FIRE RATED WALLS SHALL BE EQUIPPED WITH SMOKE AND/OR
FIRE DAMPERS (CBC 717)
7. PROVIDE FIRE-BLOCKING AT THE FOLLOWING LOCATIONS (CBC 718.2)ALL WALL/CEILING
CAVITIES AT 10'MAX. INTERVALS BOTH HORIZONTAL AND VERTICAL. (2) PLANAR
TRANSITIONS AT SOFFITS, DROP CEILINGS, COVE CEILINGS (3) STAIR STRINGER WALLS AT
TREADS (4) AT FLOOR LEVEL PENETRATIONS AROUND VENTS, PIPES, DUCTS, CHIMNEYS,
TYP. (5) AT OPENINGS BETWEEN ATTIC AND FACTORY BUILT CHIMNEYS.
8. WHERE FIRE RESISTANCE RATED SEPARATIONS ARE REQUIRED FOR EXTERIOR WALLS
ASSEMBLY SHALL BE IN ACCORDANCE WITH TABLE 601 AND 705.5 FOR EXPOSURE TO FIRE ON
BOTH SIDES. (CBC 705) WHERE ONE SIDE EXPOSURE IS ALLOWED AND FIRE RESISTIVE
EXTERIOR CONSTRUCTION IS REQUIRED BY LOCAL ORDINANCES PROVIDE 5/8" TYPE X
EXTERIOR FIRE RESISTANT GYPSUM BOARD, U.O.N.
9. MAINTAIN EXISTING FIRE RATED CONSTRUCTION OF ALL EGRESS ELEMENTS AND
COMPONENTS WHERE OCCURS.
10. INTERIOR EXIT STAIRWAYS SHALL BE ENCLOSED BY FIRE RATED CONSTRUCTION IN
ACCORDANCE WITH CBC 707 AND SHALL MAINTAIN A MINIMUM FIRE RATING OF NOT LESS
THAN 1 HOUR WHEN SERVING LESS THAN 4 STORIES PER CBC 713.4
11. ENCLOSED AREAS UNDER STAIRWAYS SHALL BE PROTECTED BY 1 HOUR FIRE RESISTIVE
RATING OR THAT OF THE STAIRWAY ENCLOSURE WHICHEVER IS GREATER PER CBC 1011.7.3
12. DOORS, OPENINGS, AND GLAZING ASSEMBLIES IN FIRE RATED CONSTRUCTION SHALL
BE TESTED AND CLEARLY LABELED IN ACCORDANCE WITH CBC 716 AND INSTALLED PER
NFPA 80
13. KITCHEN FIRE SUPRESSION SYSTEM AND HVAC DUCT DETECTORS TO BE CONNECTED
TO THE BUILDING ALARM SYSTEM.
14. EXIT DOORS TO BE PROVIDED WITH PANIC HARDWARE IN ACCORDANCE WITH CBC
1010.2.9
15. POST OCCUPANT LOAD NEAR MAIN ENTRANCE.
16. PROVIDE FIRE DEPARTMENT LOCK BOX.
17. EXIT SIGNS, EMERGENCY LIGHTING, FIRE EXTINGUISHERS, FIRE DEPARTMENT LOCK
BOX AND ADDRESS POSTING TO BE FIELD VERIFIED BY FIRE INSPECTOR.
STEVEN GARCIA
DESIGNER
215 W 4th St
1/22/2025
T-1.2
THIS DRAWING, SPECIFICATIONS AND
IDEAS, DESIGNS THEREBY ARE AND SHALL
REMAIN THE PROPERTY OF IG DRAFTING &
DESIGN AND NO PART THEREOF SHALL BE
COPIED DISCLOSED TO OTHERS OR USED
IN CONNECTION WITH ANY WORK OR
PROJECT FOR WHICH THERE HAVE BEEN
PREPARED AND DEVELOPED, WITHOUT THE
WRITTEN CONSENT OF IG DRAFTING &
DESIGN, VISUAL CONTACT WITH THESE
DRAWINGS SHALL CONSTITUTE EVIDENCE
OF ACCEPTANCE OF THESE RESTRICTIONS.
DO
N
C
H
U
R
R
O
S
1
2
3
4
RAMPS:
A. THE MAXIMUM SLOPE OF A RAMP THAT SERVES ANY EXIT
WAY, PROVIDES ACCESS FOR PERSONS WITH DISABILITIES,
OR IS IN THE PATH OF TRAVEL SHALL BE 1” RISE IN 12” OF
HORIZONTAL RUN CROSS SLOPE OF RAMP RUNS SHALL NOT
BE STEEPER THAN 1:48. (11B-405.2 & 11B-405.5)
B. THE CLEAR WIDTH OF A RAMP RUN SHALL BE 48” MINIMUM.
SEE EXCEPTIONS. (11B-405.5)
C. RAMP SURFACES SHALL BE STABLE, FIRM & SLIP RESISTANT
AND SHALL COMPLY WITH SECTION 11B-302. (11B- 405.4)
D. INTERMEDIATE LANDINGS SHALL BE PROVIDED AT
INTERVALS NOT EXCEEDING 30” OF VERTICAL RISE AND AT
EACH CHANGE OF DIRECTION IN EXCESS OF 30 DEGREES.
(11B-405.6 & 11B-405.7.4)
E. TOP LANDINGS SHALL BE AT LEAST AS WIDE AS THE WIDEST
RAMP RUN AND NOT LESS THAN 60” WIDE MINIMUM.
LANDINGS SHALL HAVE A LENGTH OF NOT LESS THAN 60” IN
THE DIRECTION OF RAMP RUN. (11B-405.7.3).
F. BOTTOM LANDINGS SHALL EXTEND 72” MINIMUM IN THE
DIRECTION OF THE RAMP RUN. (11B-405.7.3.1 & FIGURE
11B-405.7)
G. DOORS IN ANY POSITION SHALL NOT REDUCE THE MINIMUM
DIMENSION OF THE RAMP LANDING TO LESS THAN 42” AND
SHALL NOT REDUCE THE REQUIRED WIDTH BY MORE THAN 3”
WHEN FULLY OPEN. (11B-405.7.5)
H. MANEUVERING CLEARANCES REQUIRED BY SECTIONS
11B-404.2.4 & 11B-404.3.2 SHALL BE PERMITTED TO OVERLAP
REQUIRED LANDING AREA. THE WIDTH OF THE LANDING
SHALL EXTEND 24” PAST THE STRIKE EDGE OF ANY DOOR OR
GATE FOR EXTERIOR RAMPS AND 18” PAST THE STRIKE EDGE
FOR INTERIOR RAMPS. (11B-405.7.5 & TABLE 11B-404.2.4.1)
i.RAMPS THAT CHANGE DIRECTION BETWEEN RUNS SHALL HAVE A
CLEAR LANDING 60” MIN BY 72” MIN IN THE DIRECTION OF
DOWNWARD TRAVEL FROM THE UPPER RAMP RUN. (11B-405.7.4)
j.RAMP RUNS SHALL HAVE HANDRAILS COMPLYING WITH SECTION
11B-505. HANDRAILS ARE REQUIRED ON RAMPS THAT PROVIDE
ACCESS IF THE RAMP SLOPE EXCEEDS 1” RISE IN 20” OF
HORIZONTAL RUN, EXCEPT THAT AT EXTERIOR DOOR LANDINGS,
HANDRAILS ARE NOT REQUIRED ON RAMPS LESS THAN 6” RISE
OR 72” IN LENGTH. (11B-402.2 & 11B-405.8)
k.HANDRAILS SHALL BE PLACED ON EACH SIDE OF EACH RAMP AND
SHALL BE CONTINUOUS THE FULL LENGTH OF THE RAMP,
SHALL BE 34” TO 38” ABOVE THE RAMP SURFACE,
SHALL EXTEND HORIZONTALLY ABOVE THE LANDING FOR 12” MIN
BEYOND THE TOP AND THE BOTTOM OF RAMP RUN. EXTENSIONS
SHALL RETURN TO A WALL, GUARD OR THE LANDING SURFACE OR
SHALL BE CONTINUOUS TO THE HANDRAIL OF AN ADJACENT RAMP
RUN (11B-505.10.1 & FIGURE11B-505.10.1).
l.HANDRAIL GRIPPING SURFACES WITH A CIRCULAR CROSS
SECTION SHALL HAVE AN OUTSIDE DIAMETER OF 1¼” MINIMUM
AND 2” MAXIMUM. NON-CIRCULAR CROSS SECTIONS SHALL HAVE A
PERIMETER DIMENSION OF 4”
MINIMUM AND 6¼” MAXIMUM, AND A CROSS SECTION OF 2¼”
MAXIMUM. (11B-505.7 & FIGURE 11B- 505.7.2).
m.GRIPPING SURFACES (TOP AND SIDES) SHALL BE CONTINUOUS
ALONG THEIR LENGTH AND SHALL BE
UNINTERRUPTED BY NEWEL POSTS, OTHER CONSTRUCTION
ELEMENTS, OR OBSTRUCTIONS. BOTTOM OF GRIPPING
SURFACES SHALL NOT BE OBSTRUCTED FOR MORE THAN 20% OF
THEIR LENGTH. ANY WALL OR OTHER SURFACE
ADJACENT TO THE HANDRAIL SHALL BE FREE OF SHARP OR
ABRASIVE ELEMENTS AND SHALL HAVE ROUNDED
EDGES (11B-505.6, 11B-505.8).
n.HANDRAIL PROJECTING FROM A WALL SHALL HAVE A SPACE OF 1
½” BETWEEN THE WALL AND THE HANDRAIL.
(11B -505.5).
o.HANDRAIL EXTENSION RETURN BOTTOM SHALL BE 27 INCHES
MAXIMUM ABOVE FINISHED FLOOR. (11B-307.2)
p.EDGE PROTECTION SHALL BE PROVIDED ON EACH SIDE OF THE
RAMP RUN AND AT EACH SIDE OF THE RAMP
LANDING. WHERE THE RAMP SURFACE IS NOT BOUNDED BY A
WALL, THE RAMP SHALL HAVE A CURB AT
MINIMUM OF 2” IN HEIGHT OR A BARRIER THAT PREVENTS THE
PASSAGE OF A 4” DIAMETER SPHERE WITHIN
4” OF THE FINISH FLOOR (11B-405.9.2).
REACH RANGES: PLEASE SHOW AND/OR PROVIDE NOTES:
a.ELECTRICAL REACH (11B-308.1.1, 11B-308.1.2):
a)CONTROLS, SWITCHES, & RECEPTACLE OUTLETS LOW REACH
SHALL BE MEASURED TO THE BOTTOM OF THE OUTLET BOX AND THE
HIGH REACH SHALL BE MEASURED TO THE TOP OF THE OUTLET BOX.
b.FORWARD REACH (11B-308.2):
a)UNOBSTRUCTED HIGH REACH SHALL BE 48 INCHES MAXIMUM AND
LOW SHALL BE 15 INCHES MINIMUM ABOVE THE FINISHED FLOOR.
b)OBSTRUCTED HIGH REACH SHALL BE 48 INCHES MAXIMUM WHEN
REACH DEPTH IS 20 INCHES MAXIMUM.
c)OBSTRUCTED HIGH REACH SHALL BE 44 INCHES MAXIMUM WHEN
REACH DEPTH IS GREATER THAN 20 INCHES BUT LESS THAN 25 INCHES.
c.SIDE REACH (11B-308.3):
a)UNOBSTRUCTED HIGH REACH SHALL BE 48 INCHES MAXIMUM AND
LOW SHALL BE 15 INCHES MINIMUM ABOVE THE FINISHED FLOOR.
b)OBSTRUCTED HIGH REACH SHALL BE 48 INCHES MAXIMUM WHEN
REACH DEPTH IS 10 INCHES MAXIMUM.
c)OBSTRUCTED HIGH REACH SHALL BE 46 INCHES MAXIMUM WHEN
REACH DEPTH IS GREATER THAN 10 INCHES BUT LESS THAN 24 INCHES.
4
STEVEN GARCIA
DESIGNER
215 W 4th St
1/22/2025
T-1.3
THIS DRAWING, SPECIFICATIONS AND
IDEAS, DESIGNS THEREBY ARE AND SHALL
REMAIN THE PROPERTY OF IG DRAFTING &
DESIGN AND NO PART THEREOF SHALL BE
COPIED DISCLOSED TO OTHERS OR USED
IN CONNECTION WITH ANY WORK OR
PROJECT FOR WHICH THERE HAVE BEEN
PREPARED AND DEVELOPED, WITHOUT THE
WRITTEN CONSENT OF IG DRAFTING &
DESIGN, VISUAL CONTACT WITH THESE
DRAWINGS SHALL CONSTITUTE EVIDENCE
OF ACCEPTANCE OF THESE RESTRICTIONS.
DO
N
C
H
U
R
R
O
S
1
2
3
4
4
STEVEN GARCIA
DESIGNER
215 W 4th St
1/22/2025
T-1.4
THIS DRAWING, SPECIFICATIONS AND
IDEAS, DESIGNS THEREBY ARE AND SHALL
REMAIN THE PROPERTY OF IG DRAFTING &
DESIGN AND NO PART THEREOF SHALL BE
COPIED DISCLOSED TO OTHERS OR USED
IN CONNECTION WITH ANY WORK OR
PROJECT FOR WHICH THERE HAVE BEEN
PREPARED AND DEVELOPED, WITHOUT THE
WRITTEN CONSENT OF IG DRAFTING &
DESIGN, VISUAL CONTACT WITH THESE
DRAWINGS SHALL CONSTITUTE EVIDENCE
OF ACCEPTANCE OF THESE RESTRICTIONS.
DO
N
C
H
U
R
R
O
S
1
2
3
4
4
STEVEN GARCIA
DESIGNER
215 W 4th St
1/22/2025
40'-0"
100'-0"
20
.
9
7
'
21
.
5
3
'
42
.
5
'
94'-7"
50'-0"A-0.0
THIS DRAWING, SPECIFICATIONS AND
IDEAS, DESIGNS THEREBY ARE AND SHALL
REMAIN THE PROPERTY OF IG DRAFTING &
DESIGN AND NO PART THEREOF SHALL BE
COPIED DISCLOSED TO OTHERS OR USED
IN CONNECTION WITH ANY WORK OR
PROJECT FOR WHICH THERE HAVE BEEN
PREPARED AND DEVELOPED, WITHOUT THE
WRITTEN CONSENT OF IG DRAFTING &
DESIGN, VISUAL CONTACT WITH THESE
DRAWINGS SHALL CONSTITUTE EVIDENCE
OF ACCEPTANCE OF THESE RESTRICTIONS.
DO
N
C
H
U
R
R
O
S
1
2
3
4
Scale: 3/16"=1'-0"
SITE PLAN1
Scale: 3/16"=1'-0"
LINE OF SIGHT 2
4
4
4
4
4
4
STEVEN GARCIA
DESIGNER
215 W 4th St
1/22/2025
WALL LEGENDMARK
KEY DESCRIPTION
??
1.THE WORD 'CONTRACTOR' MEANS THE GENERAL CONTRACTOR, AND WHERE APPLICABLE
BY TRADE, SUBCONTRACTORS. IT IS THE SOLE RESPONSIBILITY OF THE GENERAL
CONTRACTOR TO COORDINATE THE WORK OF ALL TRADES AS THEY AFFECT ONE
ANOTHER.
2.CONTRACTOR SHALL BE USED TO REPRESENT ALL THE SUBCONTRACTORS, MATERIAL
SUPPLIERS AND OTHER TRADES NECESSARY FOR THE SUCCESSFUL COMPLETION OF THE
WORK.
3.CONTRACTOR SHALL BE RESPONSIBLE FOR REVIEWING ALL NOTES PRIOR TO FINALIZING
CONSTRUCTION CONTRACT.
4.CONTRACTOR SHALL BE RESPONSIBLE FOR ALL REQUIRED SAFETY PRECAUTIONS AND
THE METHODS, TECHNIQUES, OR PROCEDURES TO PERFORM HIS/HER WORK.
5.CONTRACTOR IS TO PROVIDE THE ARCHITECT AND ANY OTHER MEMBER OF THE DESIGN
TEAM, A 48-HOUR MINIMUM ADVANCE NOTICE PERIOD FOR ALL REQUESTED AND
REQUIRED FIELD REVIEWS.
6.THE CONTRACTOR SHALL MAINTAIN LIABILITY INSURANCE TO PROTECT HIMSELF AND
HOLD THE OWNER AND ARCHITECT HARMLESS FROM ANY AND ALL CLAIMS FOR DAMAGES
OF PERSONAL OR BODILY INJURY, OR DEATH, OR PROPERTY DAMAGE DURING
THE COURSE OF THE CONTACT. NOTHING CONTAINED IN THESE DRAWINGS OR
IN ANY ACCOMPANYING CONTRACT DOCUMENTS SHALL CREATE ANY CONTRACTUAL
RELATIONSHIP BETWEEN.
7.THE CONTRACTOR AND THE ARCHITECT. THE APPROVAL OF PLANS AND SPECIFICATIONS
DOES NOT PERMIT THE VIOLATION OF ANY APPLICABLE CODE, CITY ORDINANCES OR
STATE LAWS. IF THE CONTRACTOR PERFORMS ANY WORK CONTRARY TO APPLICABLE
LAWS, ORDINANCES, AND RULES AND REGULATIONS, WITHOUT GIVING PRIOR WRITTEN
NOTICE TO THE ARCHITECT , S/HE SHALL ASSUME FULL RESPONSIBILITY THEREIN, AND
WILL BEAR ALL COST ATTRIBUTABLE HERETO.
8.CONTRACTOR SHALL BE RESPONSIBLE FOR OBTAINING APPROVAL BY THE BUILDING
INSPECTOR OF ALL CONCEALED WORK BEFORE CLOSING UP. THE OWNER SHALL PAY FOR
AND THE CONTRACTOR SHALL ACQUIRE THE BUILDING PERMIT. THE CONTRACTOR SHALL
ACQUIRE ALL OTHER PERMITS, COMPLIANCE REQUIREMENTS, AND INSPECTIONS
NECESSARY FOR THE PROPER EXECUTION OF THE WORK IN ACCORDANCE WITH
APPLICABLE CODES AND GOVERNING REGULATIONS.
9.ALL MATERIALS AND WORK SHALL CONFORM TO ALL GOVERNING BUILDING CODES AND
REGULATIONS.
10.ALL PAINT, STAIN AND OTHER MATERIALS MUST COMPLY WITH LOCAL, STATE, AND
FEDERAL AIR POLLUTION CONTROL MANDATES. THE CONTRACTOR SHALL PROVIDE
TEMPORARY BRACES, SHORING AND GUYS REQUIRED TO SUPPORT ALL LOADS TO WHICH
THE BUILDING STRUCTURE AND COMPONENTS, ADJACENT SOILS AND STRUCTURES,
UTILITIES AND RIGHTS-OF-WAY MAY BE SUBJECTED DURING CONSTRUCTION.
11.CONTRACTOR SHALL KEEP PREMISES SECURE, CLEAN AND HAZARD FREE AT ALL TIMES
WITH ALL DEBRIS REMOVED AT THE END OF THE DAY.
12.WORK SHALL BE PERFORMED IN A SAFE MANNER OBSERVING ALL STANDARD OSHA
CODES.
13.CONTRACTOR SHALL BE RESPONSIBLE FOR MAINTAINING EQUIPMENT, MATERIALS AND
WORK IN NEAT, CLEAN, ORDERLY AND SAFE CONDITION AT ALL TIMES. AT THE
COMPLETION OF CONSTRUCTION, REMOVE ALL EXCESS MATERIALS AND REFUSE FROM
THE SITE. LEAVE ALL SURFACES WITHIN CONSTRUCTION SITE FREE FROM DUST, DIRT,
AND STAINS. THE CONTRACTOR SHALL REPAIR OR REPLACE ANY SURFACES OR ITEMS
DAMAGED BY CONSTRUCTION TO THE SATISFACTION OF THE ARCHITECT AND OWNER.
UPON COMPLETION OF WORK, ALL WORK AREAS SHALL BE LEFT BROOM CLEAN AND
DEBRIS SHALL BE REMOVED FROM THE SITE BY THE CONTRACTOR.
14.THE CONTRACTOR SHALL PROVIDE THE NECESSARY STORAGE SPACE FOR THE
PROTECTION OF DOCUMENTS, TOOLS, AND MATERIALS AT THE SITE.
15.CONTRACTOR SHALL PROVIDE TEMPORARY POWER, WATER, AND TOILET FACILITIES ON
THE JOB SITE IF NECESSARY OR REQUIRED BY LOCAL CODE. BUILDING ADDRESS SHALL
BE PROVIDED ON THE BUILDING IN SUCH A POSITION AS TO BE LEGIBLE FROM THE
STREET. (SECTION 501.2) THE PLUMBING AND ELECTRICAL SUBCONTRACTORS SHALL
PROVIDE AND INSTALL ROUGH PLUMBING AND FINAL HOOK-UP FOR ALL THE SPECIFIED
FIXTURES, EQUIPMENT, CABINETRY, FURNISHINGS AND ALL OTHER ITEMS REQUIRED BY
LOCAL CODES.
16.THE CONTRACTOR SHALL COORDINATE AND SCHEDULE ALL WORK WITH THE APPROVAL
OF THE OWNER. CONTRACTOR SHALL PROVIDE THE OWNER WITH A FULL CONSTRUCTION
SCHEDULE PRIOR TO THE START OF ANY WORK.
17.THE CONSTRUCTION SCHEDULE SHALL BE UP TO DATE AT ALL TIMES AND BE PRINTED
AND ON SITE AND/OR AVAILABLE TO THE OWNER AT ALL TIMES.
18.THE CONTRACTOR SHALL NOTIFY THE OWNER OF ANY DELAYS OR CHANGE OF SCHEDULE.
19.THE GENERAL CONTRACTOR SHALL MAINTAIN A FULL SET OF DRAWINGS, SPECIFICATIONS,
AND APPROVED SHOP DRAWINGS AND ALL REQUIRED PERMITS AND PERMIT DRAWINGS
ON THE JOBSITE AT ALL TIMES. THEY SHALL BE MADE AVAILABLE TO THE OWNER AND
ARCHITECT ON REQUEST. BEFORE SUBMITTING ANY PROPOSAL, IT SHALL BE THE
RESPONSIBILITY OF THE GENERAL CONTRACTOR TO FAMILIARIZED HIM/HERSELF WITH ALL
CONDITIONS AT THE SITE RELATIVE TO EXITING WORK, MATERIALS TO BE MATCHED,
WORKING SPACE AVAILABLE, ACCESS, AND ALL OTHER ASPECTS AFFECTING THE SCOPE
OF THE WORK TO THE MAKING OF AN INTELLIGENT BID. NO INCREASE IN COST OR
EXTENSION IN PERFORMANCE TIME WILL BE CONSIDERED FOR FAILURE TO KNOW THE
SITE CONDITIONS.
20.CONTRACTOR SHALL ERECT AND MAINTAIN TEMPORARY BARRICADES AND DUST-PROOF
PARTITIONS A NEEDED FOR PROTECTION AGAINST ACCIDENT, AND SHALL CONTINUOUSLY
MAINTAIN ADEQUATE PROTECTION OF HIS WORK AND THE OWNER'S PROPERTY FROM
DAMAGE OR LOSS ARISING IN CONNECTION WITH CONSTRUCTION.
21.UNLESS ITEMS ARE SPECIFICALLY ITEMIZED IN CONTRACT DOCUMENTS AS NOT IN
CONTRACT (NIC), THEY WILL BE ASSUMED TO BE INCLUDED IN THE ESTIMATE OR
CONTRACT PRICE.
22.ANY ALLOWANCE ITEMS SHALL BE SPECIFICALLY IDENTIFIED AS ALLOWANCE AND
INCLUDED IN THE ESTIMATE OR CONTRACT PRICE.
23.CONTRACTOR SHALL IMMEDIATELY NOTIFY THE OWNER OF ANY EXTRA COSTS ARISING
FROM THE EXECUTION OF HIS CONTRACT OR SUBCONTRACTS AND SHALL RECEIVE
OWNER'S WRITTEN APPROVAL OF SAME PRIOR TO STARTING THE WORK.
24.CONTRACTOR SHALL NOT USE ANY POTENTIALLY HAZARDOUS MATERIAL OR PRODUCTS IN
THE CONSTRUCTION AND SHALL ADVISE OWNER OF ANY POTENTIALLY HAZARDOUS
MATERIAL OR PRODUCTS RECOMMENDED, SELECTED, OR SPECIFIED PRIOR TO
PURCHASING OR INSTALLING.
25. NO HAZARDOUS MATERIALS WILL BE STORED AN/OR USED WITHIN THE BUILDING WHICH
EXCEED THE QUANTITIES AS REGULATED BY APPLICABLE CODES OR GREEN BUILDING
PRACTICES, WHICH EVER IS MORE STRICT. THE CONTRACTOR SHALL HAVE A
SUPERINTENDENT AT THE JOB SITE WHENEVER ANY WORK UNDER THIS CONTRACT IS
BEING PERFORMED IN ORDER TO PROVIDE CONSTANT SUPERVISION.
26.THE CONTRACTOR SHALL FURNISH AND INSTALL ALL PARTITIONS INDICATED ON THE
DRAWINGS.
27. PARTITION DIMENSIONS ARE FINISH FACE U.O.N CENTER LINE OF PARTITION SHALL ALIGN
WITH CENTER LINE OF MULLION WHERE OCCURS, U.O.N.
28.PARTITIONS SHOWN ALIGNED WITH EXISTING BASE BUILDING ELEMENTS SHALL BE
INSTALLED FLUSH AND SMOOTH WITH BASE BUILDING ELEMENTS.
29.THE CONTRACTOR SHALL USE CORNER BEADS AT ALL EXPOSE CORNERS AND EXPOSED
ENDS IN PLASTER AND DRYWALL PARTITIONS.
30.ALL PARTITIONS SHALL BE ANCHORED PER MANUFACTURES' SPECIFICATIONS AND AS
REQUIRED BY APPLICABLE BUILDING CODES.
31.THE CONTRACTOR SHALL SUPPLY ALL RETURN AIR OPENINGS IN SLAB TO SLAB
PARTITIONS ABOVE CEILINGS AS REQUIRED BY ENGINEERING DRAWINGS. ALL OPENINGS
IN DEMISING AND SOUND-ATTENUATED PARTITIONS SHALL HAVE SOUND BOOTS AND ALL
OPENINGS IN FIRE-RATED PARTITIONS SHALL HAVE FIRE DAMPERS AS REQUIRED BY
LOCAL BUILDINGS CODES. CONTRACTOR SHALL COORDINATE WITH ENGINEERING
DRAWINGS AND INFORM MOSAIC OF DISCREPANCIES PRIOR TO BIDDING.
32.THE CONTRACTOR SHALL PROVIDE SUFFICIENT FRAMING IN PARTITIONS FOR ALL DUCT
WORK. RETURN AIR OPENINGS AND GRILLS ABOVE AND BELOW CEILINGS SHALL BE
COORDINATED WITH MECHANICAL ENGINEERING DRAWINGS AND MECHANICAL
CONTRACTOR'S SHOP DRAWINGS. ALL OPENINGS SHALL BE PROPERLY SEALED FOR
SOUNDPROOFING AND AGAINST VIBRATION.
33.THE CONTRACTOR SHALL PROVIDE AND INSTALL ACCESS PANELS AS REQUIRED FOR
MECHANICAL, ELECTRICAL, AND PLUMBING INSTALLATIONS PER APPLICABLE BUILDING
CODES, CONTRACTOR SHALL COORDINATE TYPE AND LOCATION OF ACCESS PANELS WITH
MOSAIC PRIOR TO INSTALLATION.
34. THE PLUMBING CONTRACTOR SHALL FURNISH AND INSTALL ALL PLUMBING ROUGH-INS,
FIXTURES, AND ACCESSORIES INDICATED IN THE DRAWINGS.
35.THE PLUMBING CONTRACTOR SHALL COORDINATE AND INSTALL HIS WORK IN
ACCORDANCE WITH MANUFACTURERS' SPECIFICATIONS.
36.THE PLUMBING CONTRACTOR SHALL FURNISH AND INSTALL ALL VALVES AS INDICATED IN
THE DRAWINGS AND/OR AS REQUIRED FOR THE PROPER CONTROL OF THE PIPING AND
APPARATUS INSTALLED AS PART OF THIS REPAIRED WITHOUT INTERFERENCE OR
INTERRUPTION OF SERVICE TO THE REMAINDER OF THE BUILDING.
37.BEFORE COVERED UP OR BUILT-IN, ALL PIPING SHALL BE TESTED AND INSPECTED AS
REQUIRED BY THE AUTHORITIES HAVING JURISDICTION.
38.PROVIDE NEW SEMI-RECESSED FIRE EXTINGUISHER CABINETS AND BOTTLES.
39.THE CONTRACTOR SHALL PROVIDE 3 5/8' METAL STUDS AT PLUMBING WALLS.
3'-11"
3'
-
8
"
Scale: 1/4"=1'-0"
EXISTING FLOOR PLAN1
Scale: 1/4"=1'-0"
PROPOSED FLOOR PLAN2
WALL BACKING LEGEND
WB1
WB2
WB3
WB4
WB5
1
2
3
4
4
5
WB1
WB2
WB2
WB2
WB3
WB4WB5
WB1
2
A-3.0
4
A-3.03
S-2.2
6/A-A
A-3.0
3
A-3.0
1
A-3.0
6/A-A
A-3.0
1 4"MAX
1 4"MAX
1 4"MAX
1'-11"
1'
-
8
"
2'
-
0
"
4"
1'-0"
1'-0"
1
A-4.0
1'-0"4'-0"
BUILDING SECURITY REGULATION NOTE:
FOR NEW BUILDINGS AND ADDITIONS, ALTERATIONS, AND REPAIRS WITHIN
ANY TWELVE-MONTH PERIOD EXCEED FIFTY (50 %) PERCENT OF THE VALUE
OF ANY EXISTING BUILDING OR
STRUCTURE, EACH BUILDING OR STRUCTURE SHALL BE MADE TO
CONFORM TO THE REQUIREMENTS FOR NEW
BUILDINGS OR STRUCTURES AND COMPLY WITH THE BUILDING SECURITY
REGULATIONS. SANTA ANA MUNICIPAL
CODE CHAPTER 8, DIVISION 3.
A-1.0
THIS DRAWING, SPECIFICATIONS AND
IDEAS, DESIGNS THEREBY ARE AND SHALL
REMAIN THE PROPERTY OF IG DRAFTING &
DESIGN AND NO PART THEREOF SHALL BE
COPIED DISCLOSED TO OTHERS OR USED
IN CONNECTION WITH ANY WORK OR
PROJECT FOR WHICH THERE HAVE BEEN
PREPARED AND DEVELOPED, WITHOUT THE
WRITTEN CONSENT OF IG DRAFTING &
DESIGN, VISUAL CONTACT WITH THESE
DRAWINGS SHALL CONSTITUTE EVIDENCE
OF ACCEPTANCE OF THESE RESTRICTIONS.
DO
N
C
H
U
R
R
O
S
1
2
3
4
4
4
4
4
4
4
4
4
4
4
STEVEN GARCIA
DESIGNER
4
4
215 W 4th St
1/22/2025
MAKE UP AIR
6" RECESSED FIXTURE LITHONIA LIGHTING
OR EQUIV.
EMERGENCY LIGHT
LIGHTING SCHEDULE
MECHANICAL
VENTILATION LIGHT
ACTIVATED
EXIT SIGN
ILLUMINATED SIDE
SUSPENDED LIGHTS LITHONIA LIGHTING
OR EQUIV.
Scale: 1/4"=1'-0"
EGRESS PLAN3
EXIT ACCESS TRAVEL DISTANCE
PER TABLE 1006.2.1 CBC
A 80'-4"
B 51'-6"
MAXIMUM P.O.T DISTANCE 100'-0"
OCC B OL < 30
3'-11"
3'
-
8
"
3'-11"
3'
-
8
"
Scale: NTS
COMPRESSION STRUT DETAIL6
Scale: NTS
T-BAR SUSPENSION5
Scale: NTS
T-BAR SUSPENSION DETAIL4
+/- 10'-0"H TO
(N) HARD CEILING
(N) 10'-9"X4'-6" TYPE I
EXHAUST HOOD #1
(N) 8'-0"X4'-6" TYPE I
EXHAUST HOOD #2 +/- 11'-0"H TO
HARD CEILING
+/- 11'-0"H TO
HARD CEILING
6
S-2.1
+/- 10'-0"H TO
(N) HARD CEILING
1
A-4.0
Scale: 1/4"=1'-0"
REFLECTED CEILING PLAN 1
A
B
1
A-3.1
+/- 14'-0"H
REPLACE HARD CEILING
ON EXISTING C.J.
+/- 14'-0"H
REPLACE HARD CEILING
ON EXISTING C.J.
+/- 14'-0"H
REPLACE HARD CEILING
ON EXISTING C.J.(N) 7'-8"X5'-0" TYPE I
EXHAUST HOOD #3
+/- 16'-0"H
OPEN CEILING
+/- 16'-0"H
OPEN CEILING
5'
-
1
1
"
4'
-
0
"
8'
-
2
"
5'
-
4
"
A-1.1
THIS DRAWING, SPECIFICATIONS AND
IDEAS, DESIGNS THEREBY ARE AND SHALL
REMAIN THE PROPERTY OF IG DRAFTING &
DESIGN AND NO PART THEREOF SHALL BE
COPIED DISCLOSED TO OTHERS OR USED
IN CONNECTION WITH ANY WORK OR
PROJECT FOR WHICH THERE HAVE BEEN
PREPARED AND DEVELOPED, WITHOUT THE
WRITTEN CONSENT OF IG DRAFTING &
DESIGN, VISUAL CONTACT WITH THESE
DRAWINGS SHALL CONSTITUTE EVIDENCE
OF ACCEPTANCE OF THESE RESTRICTIONS.
DO
N
C
H
U
R
R
O
S
1
2
3
4
4
4
4
4
4
4
STEVEN GARCIA
DESIGNER
215 W 4th St
1/22/2025
3'-11"
3'
-
8
"
3'-11"
3'
-
8
"
Scale: 1/4"=1'-0"
DIMENSIONAL FLOOR PLAN 1
Scale: 1/4"=1'-0"
OCCUPANT LOAD PLAN 2
28'-4"
41'-3"
2'-0"
2'
-
0
"
5'
-
0
"
7'-5"
10'-2"4'-7"4'-5"4'-7"
25'-9"
24'-11"
3'
-
0
"
2'
-
6
"
3'-0"
14'-4"
2'
-
6
"
7'
-
0
"
9'
-
1
"
6'
-
7
"
2'
-
6
"
7'-0"
10
'
-
5
"
3'-0"
3'-9"
6'
-
1
0
"
12
'
-
6
"
5'
-
6
"
3'
-
0
"
4'
-
0
"
7'
-
0
"
3'
-
0
"
1'
-
0
"
3'
-
8
"
7'-6"
1'-6"
5'-1"
1'-6"
4'
-
8
"
7'
-
0
"
7'-6"
15'-10"
3'-0"
13'-4"2'-0"
20'-0"
2'
-
5
"
12
'
-
1
"
9'
-
8
"
5'-0"
4'
-
0
"
1'-0"
9'
-
3
"
25'-4"
3"3'-0"
22'-1"
26'-3"
7'
-
1
0
"
6'
-
1
1
"
3'-0"7"
36'-2"41'-3"
9'-10"10'-6"8'-0"
10
'
-
3
"
3'-2"7'-8"
5'
-
0
"
16'-0"
1'-1"
1'-11"
4'
-
0
"
3'
-
0
"
3'
-
3
"
3'
-
3
"
1'
-
8
"
2'
-
0
"
3'
-
0
"
6'
-
1
"
6'-0"
4'
-
0
"
11'-7"
1'-0"
A-1.2
THIS DRAWING, SPECIFICATIONS AND
IDEAS, DESIGNS THEREBY ARE AND SHALL
REMAIN THE PROPERTY OF IG DRAFTING &
DESIGN AND NO PART THEREOF SHALL BE
COPIED DISCLOSED TO OTHERS OR USED
IN CONNECTION WITH ANY WORK OR
PROJECT FOR WHICH THERE HAVE BEEN
PREPARED AND DEVELOPED, WITHOUT THE
WRITTEN CONSENT OF IG DRAFTING &
DESIGN, VISUAL CONTACT WITH THESE
DRAWINGS SHALL CONSTITUTE EVIDENCE
OF ACCEPTANCE OF THESE RESTRICTIONS.
DO
N
C
H
U
R
R
O
S
1
2
3
4
STEVEN GARCIA
DESIGNER
215 W 4th St
1/22/2025
TOILET EXHAUST FAN SCHEDULE
SYMB AREA
SERVING MANUF.MODEL TYPE CFM
TOTAL
STATIC
(IN WC)
RPM ELECTRICAL
VOLT PH AMPS
OPERATION
WEIGHT
(LB)
REMARKS
RESTROOM GREENHECK SP-A50 CEILING
MOUNT 50 0.33 1100 120 1 .6 35 PROVIDE BACKDRAFT DAMPER,
FAN SHALL BE INTERLOCKED WITH LIGHT SWITCH
QTY.
1
(N)5 TON
10
'
-
0
"
M
I
N
3'
-
0
"
3'
-
3
"
655 LBS
692 LBS
403 LBS 296 LBS
238 LBS
REPLACED W/ NEW ELECTRIC PACKAGED ROOFTOP UNIT SCHEDULE
SYMB MAKE
GOODMAN
MODEL
GPGM560
08041AA
TONS
5
CFM
NOM.
2000
ESP
(IN)
0.4"
OUTSIDE AIR
(CFM)
900 58.0
HEATING (MBH)
80
INBUT (KBH)OUTPUT (KBH)
63
ELECTRICAL
208/230
VOLTAGE
1
PHASE
35.5
TOT. AMPS
43.3
AMPS
MCA
70
AMPS
FUSE
SEER
EER
14.2
10.1
OPERATION
WEIGHT
(LB)
655
DUCT CONNECTIONS
MANUFAC.
SUPPLY RETURN
REMARKS
PROVIDE SMOKE DETECTOR IN SUPPLY DUCT & POWER
EXH. ECONOMIZER. SET MIN. O.S.A @ 900 CFM
AFUE %
81
TOTAL COOL'G
(KBH)
MANUFAC.
N/E
N
N
N
N
N/E
N
N/E
N
N/E
Scale: 1/4"=1'-0"
ROOF PLAN 1
10'-0
"
M
I
N
A-1.3
THIS DRAWING, SPECIFICATIONS AND
IDEAS, DESIGNS THEREBY ARE AND SHALL
REMAIN THE PROPERTY OF IG DRAFTING &
DESIGN AND NO PART THEREOF SHALL BE
COPIED DISCLOSED TO OTHERS OR USED
IN CONNECTION WITH ANY WORK OR
PROJECT FOR WHICH THERE HAVE BEEN
PREPARED AND DEVELOPED, WITHOUT THE
WRITTEN CONSENT OF IG DRAFTING &
DESIGN, VISUAL CONTACT WITH THESE
DRAWINGS SHALL CONSTITUTE EVIDENCE
OF ACCEPTANCE OF THESE RESTRICTIONS.
DO
N
C
H
U
R
R
O
S
1
2
3
4
STEVEN GARCIA
DESIGNER
4
215 W 4th St
1/22/2025
1
4"
M
A
X
.
1
2"
M
A
X
.
@
1
:
2
S
L
O
P
E
Scale: NTS
INTERNATIONAL SYMBOL OF ACCESSIBILITY SIGNS3
Scale: NTS
DOOR SIGN4
Scale: NTS
THRESHOLD DETAIL8
TYPICAL RESTROOM SIGNAGE REQUIREMENTS
NOTE:
LETTERS & NUMBERS ON SIGNS SHALL BE RAISED, CONTRASTING IN COLOR & HAVE A WIDTH-TO-
HEIGHT RATIO OF BETWEEN 3:5 & 1:1 & A STROKE WIDTH-TO-HEIGHT RATIO BETWEEN 1:5 & 1:10,
& RAISED 1/32" MIN. & BE ACCOMPANIED BY BRAILLE RAISED LETTERING. WHERE PERMANENT
SIGNAGE IS PROVIDED FOR ROOMS & SPACES, SIGNAGE AS DESCRIBED ABOVE SHALL BE
PROVIDED ON THE STRIKE/LATCH SIDE OF THE DOOR.
MIN. 6"x6"x1/4" FIELD WITH
SYMBOLS
8" MAX.2"
RESTROOM
MIN. 2"x6"x1/4" FIELD WITH TEXT
& GRADE 2 BRAILLE PLACED
BELOW PICTOGRAM.
ADA RESTROOM SIGNAGE
5/8" HIGH MIN. & 2" MAX. TYPE,
RAISED 1/32" HELVETICA
MEDIUM UPPERCASE
LETTERS.
5'
-
0
"
C
GENDER
NEUTRAL
Scale: NTS
TYP. GRAB BAR DETAIL6
Scale: NTS
TACTILE EXIT SIGN7
Scale: NTS
INTERNATIONAL ACCESSIBILITY SYMBOL5
2'-0"1'-0"
3'-0"
1'
-
2
"
11"
27
"
M
I
N
.
2'
-
1
0
"
M
A
X
.
ELEVATION 1
1'
-
2
"
1'-6"
MIN.
33
"
-
3
6
"
17"-18"
1'
-
7
"
5"-6" min
40
"
M
A
X
TO
R
E
F
L
E
C
T
I
N
G
S
U
R
F
A
C
E
40
"
M
A
X
TO
R
E
F
L
E
C
T
I
N
G
S
U
R
F
A
C
E
9"
M
I
N
6"
ELEVATION 3
17
"
-
1
9
"
2'-4"
33
"
-
3
6
"
7"-9"
1'
-
7
"
1'-0"3'-6"
ELEVATION 2
5
DOOR SCHEDULE
TEMPERED
GLASS TYP.1 2
4
7'
-
0
"
10
"
S
M
O
O
T
H
TEMPERED
GLASS TYP.3
PANIC
HARDWARE
Scale: NTS
WALL BACKING DETAIL10 Scale: NTS
DOOR AIR CURTAIN DETAIL 9
7'-6"
7'
-
0
"
1'-6"17"-18"
5'-1"
4'
-
8
"
3'
-
8
"
3'
-
0
"
5'-0"
Scale: 1/2"=1'-0"
RESTROOM ELEVATIONS2
Scale: 1/2"=1'-0"
ENLARGED RESTROOM PLAN 1
OCCUPANCY LOAD MUST BE POSTED NEAR THE MAIN ENTRY.
G.C. TO PROVIDE VISIBLE SIGN STATING THE FOLLOWING:
300 PACIFIC COAST HWY,
STE 113 H.B. , CA 92648
SIGN TO BE A MINIMUM SIZE OF 8 1
2"x 11"
MAXIMUM CAPACITY
2"
3/
8
"
3/
8
"
00
Scale: NTS
OCCUPANT LOAD SIGN11
PLAN CHECK NOTES:
a.HAND-ACTIVATED DOOR OPENING HARDWARE
SHALL BE CENTERED BETWEEN 34 INCHES AND
44 INCHES ABOVE THE FLOOR.
b.DOOR HANDLE SHALL BE OPERABLE WITHOUT
REQUIRING TIGHT GRASPING, PINCHING OR
TWISTING OF THE WRIST (I.E., LEVER TYPE OR
PANIC BAR).
c. MAXIMUM EFFORT TO OPERATE DOORS SHALL
NOT EXCEED 5 POUNDS.
12" M
A
X
NOTE:
FLOOR OR GROUND SURFACES WITHIN REQUIRED DOOR MANEUVERING CLEARANCES SHALL BE STABLE, FIRM, AND SLIP RESISTANT.
SURFACES SHALL BE LEVEL WITH A SLOPE NOT STEEPER THAN 1:48. CHANGES IN LEVEL ARE NOT PERMITTED EXCEPT AT
THRESHOLDS. OPENING IN FLOOR SHALL NOT ALLOW PASSAGE OF SPHERE MORE THAN ½” DIAMETER. (11B-302.2) (11B-404.2.4.4).
A-2.0
THIS DRAWING, SPECIFICATIONS AND
IDEAS, DESIGNS THEREBY ARE AND SHALL
REMAIN THE PROPERTY OF IG DRAFTING &
DESIGN AND NO PART THEREOF SHALL BE
COPIED DISCLOSED TO OTHERS OR USED
IN CONNECTION WITH ANY WORK OR
PROJECT FOR WHICH THERE HAVE BEEN
PREPARED AND DEVELOPED, WITHOUT THE
WRITTEN CONSENT OF IG DRAFTING &
DESIGN, VISUAL CONTACT WITH THESE
DRAWINGS SHALL CONSTITUTE EVIDENCE
OF ACCEPTANCE OF THESE RESTRICTIONS.
DO
N
C
H
U
R
R
O
S
1
2
3
4
4
4
4
4
4
4
STEVEN GARCIA
DESIGNER
215 W 4th St
1/22/2025
SUSPENDED WALL
(N) 10'-9"X4'-6" TYPE I
EXHAUST HOOD #1
(N) 8'-0"X4'-6" TYPE I
EXHAUST HOOD #2
11
'
-
0
"
3'
-
0
"
2'
-
1
0
"
3'-0"
2'
-
1
0
"
2'
-
2
"
5'
-
0
"
(N) 7'-8"X5'-0" TYPE I
EXHAUST HOOD #3
6'
-
8
"
12
'
-
0
"
ALL HOODS SHALL BE
FLASHED TO THE CEILING
S/S SKIRT
ALL HOODS SHALL BE
FLASHED TO THE CEILING
TV MENUTV MENUTV MENUTV MENU
6"6"
48
"
M
A
X
6"6"
(N) 10'-9"X4'-6" TYPE I
EXHAUST HOOD #1
FRYER FRYER FRYER FRYERSTAINLESS STEEL PREP TABLE
S/S SKIRT
6" COVEBASE
W/ 3/8" R
6" COVEBASE
W/ 3/8" R
(N) 8'-0"X4'-6" TYPE I
EXHAUST HOOD #2
48
"
M
A
X
6'
-
8
"
48
"
M
A
X
6" MIN6" MIN 11
'
-
0
"
3 DOOR
REACH IN FREEZER
6" COVEBASE
W/ 3/8" R
6" COVEBASE
W/ 3/8" R
DRYWALL WITH
SEMI-GLOSS PAINT
SMOOTH,
DURABLE,
NON-ABSORBENT,
WASHABLE
DRYWALL WITH
SEMI-GLOSS PAINT
SMOOTH,
DURABLE,
NON-ABSORBENT,
WASHABLE
DRYWALL WITH
SEMI-GLOSS PAINT
SMOOTH,
DURABLE,
NON-ABSORBENT,
WASHABLE
1'-0"
1'-0"
19"MIN DEEP
27
"
M
I
N
.
34
"
M
A
X
A
.
F
.
F
.
A-3.0
THIS DRAWING, SPECIFICATIONS AND
IDEAS, DESIGNS THEREBY ARE AND SHALL
REMAIN THE PROPERTY OF IG DRAFTING &
DESIGN AND NO PART THEREOF SHALL BE
COPIED DISCLOSED TO OTHERS OR USED
IN CONNECTION WITH ANY WORK OR
PROJECT FOR WHICH THERE HAVE BEEN
PREPARED AND DEVELOPED, WITHOUT THE
WRITTEN CONSENT OF IG DRAFTING &
DESIGN, VISUAL CONTACT WITH THESE
DRAWINGS SHALL CONSTITUTE EVIDENCE
OF ACCEPTANCE OF THESE RESTRICTIONS.
DO
N
C
H
U
R
R
O
S
1
2
3
4
Scale: 1/2"=1'-0"
HOOD #3 ELEVATION1 Scale: 1/2"=1'-0"
FRONT COUNTER ELEVATION2
Scale: 1/2"=1'-0"
HOOD #1 & #2 ELEVATION3
Scale: 3/4"=1'-0"
ACCESSIBLE COUNTER DETAIL 4
Scale: 1/4"=1'-0"
A-A SECTION6
6
S-2.1
Scale: 3/4"=1'-0"
ACCESSIBLE SEATING 5
4
4
4
STEVEN GARCIA
DESIGNER
215 W 4th St
1/22/2025
5'-0"16'-0"6'-0"
1'
-
4
"
3'
-
0
"
1'-0"
3'
-
0
"
1'-0"
10
'
-
0
"
T
O
H
A
R
D
C
E
I
L
I
N
G
11
'
-
6
"
11
'
-
0
"
T
O
(
N
)
H
A
R
D
C
E
I
L
I
N
G
DETAIL 1
HORIZONTAL CROSS SECTION
SEE DETAIL 1
A-4.0
THIS DRAWING, SPECIFICATIONS AND
IDEAS, DESIGNS THEREBY ARE AND SHALL
REMAIN THE PROPERTY OF IG DRAFTING &
DESIGN AND NO PART THEREOF SHALL BE
COPIED DISCLOSED TO OTHERS OR USED
IN CONNECTION WITH ANY WORK OR
PROJECT FOR WHICH THERE HAVE BEEN
PREPARED AND DEVELOPED, WITHOUT THE
WRITTEN CONSENT OF IG DRAFTING &
DESIGN, VISUAL CONTACT WITH THESE
DRAWINGS SHALL CONSTITUTE EVIDENCE
OF ACCEPTANCE OF THESE RESTRICTIONS.
DO
N
C
H
U
R
R
O
S
1
2
3
4
STEVEN GARCIA
DESIGNER
Scale: NTS
NEW PARTITION WALL 1 Scale: NTS
NEW FUR WALL DETAIL 2
Scale: 1/2"=1'-0"
RAMP ELEVATION4
4
Scale: 1/2"=1'-0"
SKYLIGHT CURB DETAIL3
215 W 4th St
1/22/2025
ENVIRONMENTAL HEALTH NOTES
1. A CONCRETE SLAB IS PROVIDED FOR TRASH, GARBAGE, AND GREASE CONTAINER STORAGE. IF WALLS ENCLOSE AREA,
THE INTERIOR WALL SURFACES WILL BE SMOOTH, SEALED AND WASHABLE (E.G., PLASTERED SMOOTH AND PAINTED,
ETC.).
2. ALL FOOD-RELATED AND UTENSIL-RELATED EQUIPMENT SHALL MEET OR BE EQUIVALENT TO SANITATION STANDARDS
ESTABLISHED BY AN AMERICAN NATIONAL STANDARDS INSTITUTE (ANSI) ACCREDITED PROGRAM.
3. ALL FLOOR MOUNTED EQUIPMENT WILL BE INSTALLED ON MINIMUM 6" SANITARY LEGS, CASTORS, OR COMPLETELY
SEALED IN POSITION ON A 4 " HIGH CURB WITH CONTINUOUSLY COVED BASE. COUNTERTOP EQUIPMENT WILL BE ON
4-INCH SANITARY LEGS OR SEALED TO THE COUNTER UNLESS READILY MOVABLE.
4. IF SOFT DRINK, ICE OR OTHER DISPENSERS ARE SELF-SERVICE, OR IF REFILLS ARE PROVIDED THEY MUST BE PUSH
BUTTON TYPES, OR LEVER TYPES WHERE THE LEVER CONTACTS THE CONTAINER AT LEAST ONE INCH BELOW THE RIM.
5. ANY OPENABLE WINDOWS VENT OPENINGS OR OTHER SIMILAR OPENINGS MUST BE PROVIDED WITH TIGHT FITTING
SCREENS OF MINIMUM 16-MESH TO THE INCH. WINDOWS TO BE FIXED AT FOOD PREP, UTENSIL-WASHING, OPEN FOOD
AND UTENSIL STORAGE AREAS.
6. ALL EXTERIOR DOORS OPEN OUTWARD AND ARE SELF-CLOSING AND TIGHT FITTING.
7. BI-FOLD, FRENCH, ACCORDION STYLE AND ROLL-UP DOORS CANNOT OPEN INTO THE FOOD PREP, UTENSIL WASHING OR
UNPACKAGED FOOD SERVICE AREAS.
8. TOILET ROOM AND DRESSING ROOM DOORS MUST BE SELF-CLOSING, TIGHT FITTING.
9. DELIVERY DOORS TO HAVE AIR CURTAIN FANS THAT SPAN THE WIDTH OVER THE DOOR. THE FAN MUST ACTIVATE VIA A
MICROSWITCH PROVIDING A MINIMUM VELOCITY OF 1600 FPM MEASURED 3 FEET ABOVE THE GROUND.
10. A MINIMUM OF 10 FOOT-CANDLES OF LIGHT MEASURED 30" OFF FLOOR IS PROVIDED IN WALK-IN REFRIGERATED
STORAGE AND DRY STORAGE ROOMS AND AT LEAST 20-FOOT CANDLES IS PROVIDED WHERE FOOD IS PROVIDED FOR
CONSUMER SELF-SERVICE, WHERE FRESH PRODUCE OR PREPACKAGED FOODS ARE SOLD OR OFFERED FOR
CONSUMPTION; INSIDE EQUIPMENT SUCH AS REACH-IN AND UNDER-COUNTER REFRIGERATORS; IN AREAS USED FOR
HANDWASHING, WAREWASHING, EQUIPMENT AND UTENSIL STORAGE, AND IN TOILET ROOMS.
11. A MINIMUM OF 50 FOOT-CANDLES OF LIGHT MEASURED 30" OFF FLOOR IS PROVIDED WHEN WORKING WITH FOOD OR
WORKING WITH UTENSILS OR EQUIPMENT SUCH AS KNIVES, SLICERS, GRINDERS, OR SAWS WHERE EMPLOYEE SAFETY
IS A FACTOR AND IN ALL AREAS DURING PERIODS OF CLEANING.
12. SHATTERSHIELDS FOR ALL LIGHTS ABOVE FOOD PREPARATION, WORK, AND STORAGE AREAS WILL BE PROVIDED.
13. ALL WAREWASHING SINKS TO HAVE 3 COMPARTMENTS THAT ARE A MINIMUM SIZE OF AT LEAST 18"X18"X12" DEEP (OR
16"X20"X12" DEEP) WITH A MINIMUM 18" DRAINBOARD AT EACH END. IF AGAINST A WALL, IT MUST HAVE AN 8" INTEGRAL
BACKSPLASH. HOWEVER, IT MUST BE CAPABLE OF ACCOMMODATING THE LARGEST UTENSIL TO BE WASHED. A
WAREWASHING MACHINE DOES NOT SUBSTITUTE FOR THE SINK REQUIREMENT.
14. SINKS TO HAVE SPOUT(S) CAPABLE OF REACHING EACH COMPARTMENT.
15. FOOD PREP SINK COMPARTMENT(S) TO BE AT LEAST 18"X18"X12" DEEP (OR 16"X20"X12" DEEP) WITH A MINIMUM 18"
DRAINBOARD. SEPARATE FOOD PREP SINKS TO BE PROVIDED FOR MEATS AND PRODUCE.
16. THE 3 OR 4 COMPARTMENT BAR SINK TO BE AT LEAST 12"X12"X10" DEEP (OR 10"X14"X10" DEEP) WITH A MINIMUM 18"
DRAINBOARD AT EACH END.
17. A SEPARATE WET WASTE DUMP FIXTURE SHALL BE PROVIDED FOR DISPOSAL OF DRINK OR WASTE ICE OR COFFEE
WASTE.
18. EACH HANDWASHING SINK MUST HAVE PERMANENTLY MOUNTED SINGLE-SERVICE SOAP AND PAPER TOWEL
DISPENSERS.
19. THE HOT WATER HEATER WILL BE A COMMERCIAL TYPE CAPABLE OF CONSTANTLY SUPPLYING HOT WATER AT A
TEMPERATURE OF 120ºF TO ALL SINKS. IN SIZING THE WATER HEATER, THE PEAK HOURLY DEMAND FOR ALL SINKS, ETC.,
ARE ADDED TOGETHER TO DETERMINE THE MINIMUM REQUIRED RECOVERY RATE.
20. ALL LAVATORIES OR HAND SINKS WILL HAVE A COMBINATION FAUCET OR PREMIXING FAUCET CAPABLE OF SUPPLYING
WATER TEMPERED TO 100ºF. SELF-CLOSING OR METERED FAUCET TO PROVIDE AT LEAST 15 SECONDS OF WATER
WITHOUT REACTIVATION.
21. ALL PLUMBING, ELECTRICAL AND GAS LINES SHALL BE CONCEALED WITHIN THE BUILDING STRUCTURE TO AS GREAT AN
EXTENT AS POSSIBLE. ALL EXPOSED CONDUITS, PLUMBING, ETC. SHALL BE INSTALLED AT LEAST 6" OFF FLOOR AND 3/4"
FROM WALLS USING STANDOFF BRACKETS.
22. CONDUITS, PLUMBING OR PIPING CANNOT BE INSTALLED ACROSS ANY AISLE WAY, TRAFFIC AREA OR DOOR OPENING.
23. MULTIPLE RUNS OR CLUSTERS OF CONDUIT OR PIPELINES SHALL BE FURRED IN OR ENCASED IN AN APPROVED
SEALED ENCLOSURE
24. ALL LIQUID WASTE SHALL BE DRAINED BY MEANS OF INDIRECT WASTE PIPES INTO A FLOOR SINK. FLOOR SINKS ARE
TO BE INSTALLED FLUSH WITH THE FINISHED FLOOR SURFACE AND HAVE SUITABLE EASILY REMOVABLE SAFETY
COVER GRATES.
25. FLOOR SINK TO BE 50% EXPOSED WHEN NO ACCESS IS PROVIDED FOR CLEANING AND SERVICING OR BE IN LINE WITH
THE FRONT FACE OF ELEVATED FREESTANDING EQUIPMENT.
26. APPROVED BACKFLOW PREVENTION DEVICES SHALL BE PROPERLY INSTALLED UPSTREAM OF ANY POTENTIAL
HAZARD BETWEEN THE POTABLE WATER SUPPLY AND A SOURCE OF CONTAMINATION. HOSES SHALL NOT BE
ATTACHED TO A FAUCET OR HOSE BIBB UNLESS AN APPROVED BACKFLOW PREVENTER IS PROVIDED.
27. WATER SUPPLY TO CARBONATORS SHALL BE PROTECTED BY AN APPROVED REDUCED PRESSURE PRINCIPLE
BACKFLOW PREVENTER AND INSTALLED IN AN AREA READILY ACCESSIBLE FOR TESTING. THE RELIEF VALVE SHALL
DRAIN INDIRECTLY TO SEWER WITH A LEGAL AIR GAP.
28. FOR CLEANING FLOOR MATS, THE JANITORIAL SINK TO BE A MINIMUM 24" BY 36" FLOOR-MOUNTED TYPE. MOPS SHALL
BE PLACED IN A POSITION THAT ALLOWS THEM TO AIR-DRY WITHOUT SOILING WALLS, EQUIPMENT, OR SUPPLIES.
29. THE JANITORIAL SINK FAUCET WILL HAVE A THREADED OUTER LIP FOR HOSE ATTACHMENT AND AN APPROVED
BACKFLOW PREVENTION DEVICE. NO CHEMICAL DISPENSING SYSTEMS OR SHUTOFF VALVES TO BE ATTACHED TO MOP
SINK FAUCET OUTLET (UNLESS A "SIDEKICK" PLUMBING DEVICE IS INSTALLED).
30. NO CONDENSATE OR WASTEWATER INCLUDING HVAC WILL DRAIN INTO THE JANITORIAL SINK.
31. GREASE TRAP TO BE LOCATED OUTSIDE THE FOOD SERVICE ACTIVITY AREA, FLUSH WITH THE FINISHED FLOOR WHEN
INDOORS. LOCAL WASTEWATER DISTRICT OR BUILDING DEPARTMENT TO BE CONTACTED FOR GREASE REMOVAL
REQUIREMENTS.
32. FLOOR DRAINS SHALL BE INSTALLED IN FLOORS THAT ARE WATER-FLUSHED FOR CLEANING AND IN AREAS WHERE
PRESSURE SPRAY METHODS FOR CLEANING EQUIPMENT ARE USED, IN RESTROOMS, JANITORIAL ROOMS, SCULLERIES,
AND AT BARS WITH WAREWASHING. FLOOR SURFACES IN AREAS PURSUANT TO THIS SHALL BE SLOPED 1:50 TO THE
FLOOR DRAINS.
33. ADEQUATE VENTILATION IS TO BE PROVIDED TO ALL TOILET ROOMS, JANITOR CLOSETS WITH MOP SINKS, AND
INDOOR TRASH ROOMS AND IN DRESSING/CHANGE ROOM(S).
34. THE FLOOR FINISH WILL HAVE A SMOOTH SURFACE UNDER ALL EQUIPMENT AND WALKWAYS WILL HAVE A LIGHT
TEXTURE ONLY.
35. THE PAINT USED ON WALLS AND CEILINGS OF ALL KITCHEN, FOOD PREPARATION, WORK, AND STORAGE AREAS WILL
BE A GLOSS OR SEMI-GLOSS ENAMEL. FINISH MATERIAL SHALL BE A LIGHT COLOR IN FOOD PREP AREAS FOR EASY
CLEANING.
36. PRIOR TO INSTALLATION, SAMPLES OF FINISHES TO BE SUBMITTED TO ENVIRONMENTAL HEALTH FOR APPROVAL AS
NEEDED.
37. COLD STORAGE ROOMS SHALL BE PROVIDED WITH A SECTION OF SHELVING INSTALLED TO HOLD SHALLOW COOL
DOWN PANS -NOT TO EXCEED 4" IN HEIGHT. SPACE BETWEEN SHELVING TO BE AT LEAST 8" HIGH.
38. BACKUP DRY STORAGE SHELVING SHALL BE A MINIMUM OF 96 LINEAR FEET (MEASURED WITH TIERS) OR 25% OF
KITCHEN, FOOD PREP, AND WORK AREAS, WHICHEVER IS GREATER. SHELVING SHALL BE AT LEAST 18 INCHES DEEP
AND START A MINIMUM SIX INCHES OFF THE FLOOR SURFACE.
39. SHELVING OVER WET AREAS (SINKS, MOP SINKS ETC.) AND FOOD PREP SURFACES WILL BE METAL.
40. ALL SEAMS, GAPS, OPENINGS TO BE PROPERLY SEALED.
41. GREASE TRAPS INSTALLED BELOW FLOOR GRADE SHALL BE POSITIONED SO THAT THE LID IS FLUSH WITH THE
FINISHED FLOOR.
42. AN INTERLOCKING SWITCH WILL BE PROVIDED BETWEEN HOOD EXHAUST AND MAKE UP AIR SYSTEMS.
43. THE TRASH ROOM OR AREA IS INSIDE THE FACILITY, THE ROOM/AREA WILL REQUIRE EASILY CLEANABLE, SMOOTH,
LIGHT COLORED CEILING WITH WATER RESISTANT WALLS, AND THE FLOOR SURFACE MUST BE OF DURABLE,
NON-ABSORBENT MATERIAL(CONCRETE, QUARRY TILE, ETC.,) THAT SLOPES 1:50 (APPROXIMATELY 14" PER FOOT) TO A
FLOOR DRAIN. THE BASE AT THE FLOOR AND WALL JUNCTURES MUST BE CONTINUOUS UP THE WALL 4" WITH A 3 8"
MINIMUM RADIUS COVE. HOSE BIBB WITH BACKFLOW PREVENTION TO BE AT THIS ROOM.
E/NITEM #QTY.EQUIPMENT MANUFACTURE MODEL #
EQUIPMENT SCHEDULE
PLUMBING
C.W.H.W.DIRECTDRAIN INDIRECTDRAIN
GAS
(KBTU)
ELECTRICAL
NSF ULCOMMENT
AMPVOLT
EQUIPMENT
DIMENSION
TENANT IMPROVEMENT TO NEW
RESTAURANT, ADD (N) 3 TYPE I HOODS &
KITCHEN EQUIPMENT.
AREA OF WORK: 1,869 S.F.
NEW OWNERSHIP
3'-11"
3'
-
8
"
Scale: 1/4"=1'-0"
EQUIPMENT FLOOR PLAN1
3 N LOT 5 TIER STORAGE SHELVING 1848NSMETRO 18"WX48"L
7
9
8
N 1 MOP BASIN SINK SE18181PGSW 18"LX18"WX13"H
N 1 CHEMICAL SHELF WS-W1224GSW PER PLAN
N 1 MOP & BROOM HOLDER 2-223 X 24BOBRICK 24"L
2 N 2 EMPLOYEE LOCKER 6 TIERGLOBAL
13
11
12
N 1 WAREWASH 3 COMP. SINK SH24243DGSW 120"LX30"DX45"H
N 1 PRE RINSE W/ FAUCET AA-984GGSW 12" NPT FEMALE INLETS
N 1 OVERHEAD DOUBLE SHELF GSW PER PLANPER PLAN
23 N 3 STAINLESS STEEL PREP TABLE WT-EE3060GSW 30"LX60"WX35"H
21
22
20
N 4 SURFACED MOUNTED SOAP DISPENSER B-2111BOBRICK 4"WX3"DX8"H
N 4 SURFACE MOUNTED TOWEL DISPENSER B-262BOBRICK 10"WX3"DX14"H
N 4 HAND SINK W/ SPLASH GUARDS HS-0810SGSW 12"WX12"DW12"H
10 N 1 VEGETABLE PREPARATION SINK SE18181LGSW 39"LX24"DX36"H
1 N 1 AIR CURTAIN LPV242-1UMARS 42"L 115/60/1 2.4 A
6 N 1 WATER HEATER U-75T-80R-3NBRADFORD WHITE 76 KBTU
27.1 N 2 STAINLESS STEEL PREP TABLE WT-E7230GSW 30"LX72"WX35"H
33 N 2 POS OWNER ----
FINISH SCHEDULE
LOCATION FLOOR
COVE BASE
3 8" RADIUS WALLS CEILING
SERVICE
AREA
6"H CERAMIC TILE
COVE BASE
3 8" RADIUS
COVE BASE MANUF:
A. B & W SLIMFOOT
S3619TN
FRONT COUNTER
FINISH STAINLESS STEEL
WASH/PREP AREA
STORAGE
CUSTOMER AREA OPEN CEILING-
STAINLESS STEEL AT
THE HOOD AREA
4 FT H FRP DRYWALL
WITH SEMI-
GLOSS WHITE PAINT
SMOOTH FINISH
CONCRETE FLOOR W/
DHS APPROVED
SEALANT. MONOPOLE
INC., PERMASEAL OR EQ.
CONCRETE FLOOR W/
DHS APPROVED
SEALANT. MONOPOLE
INC., PERMASEAL OR EQ.
SMOOTH, DURABLE NON
ABORBANT & EASLY
CLEANABLE.
DRYWALL WITH
SEMI-GLOSS PAINT
SMOOTH, DURABLE,
NON-ABSORBENT,
WASHABLE
DRYWALL WITH
SEMI-GLOSS PAINT
SMOOTH, DURABLE,
NON-ABSORBENT,
WASHABLE
CONCRETE FLOOR W/
DHS APPROVED
SEALANT. MONOPOLE
INC., PERMASEAL OR EQ.
SMOOTH, DURABLE NON
ABORBANT & EASLY
CLEANABLE.
6"H CERAMIC TILE
COVE BASE
3 8" RADIUS
FIBERGLASS
REINFORCED
PLASTIC(FRP)
RESTROOMS
6" CERAMIC TILE
COVE BASE
3 8" RADIUS
4FT H CERAMIC TILE
WITH SEMI-GLOSS
WHITE PAINT SMOOTH
FINISH WASHABLE .
CLEANABLE
CONCRETE FLOOR W/
DHS APPROVED
SEALANT. MONOPOLE
INC., PERMASEAL OR EQ.
SMOOTH, DURABLE NON
ABORBANT & EASLY
CLEANABLE.
DRYWALL WITH
SEMI-GLOSS PAINT
SMOOTH, DURABLE,
NON-ABSORBENT,
WASHABLE
FINISH NOTES:
FLOORING: FLOORING SHALL BE SMOOTH, DURABLE, NONABSORBANT AND EASILY
CLEANABLE. FLOORING MUST BE SMOOTH ON BASE COVING AND UNDER EQUIPMENT,
SHELVING, SINKS, AND COUNTERS. THE FLOORING SHALL BE OF AN APPROVED TYPE
THAT CONTINUES UP THE WALL FOUR (4) INCHES, IN A SEAMLESS MANNER, FORMING A
3/8 INCH MINIMUM RADIUS COVE AS AN INTEGRAL UNIT. VINYL/RUBBER TOPSET COVED
BASE AND/OR THE VINYL COMPOSITION TILES (VCT) ARE NOT ACCEPTABLE. SOME SLIM
FOOT CERAMIC, QUARRY AND METAL TOPSET COVE BASES ARE GENERALLY
ACCEPTABLE. SUBMIT SAMPLES OF THE PROPOSED FLOORING AND BASE COVE FOR
APPROVAL PRIOR TO INSTALLATION. CONCRETE FLOORS ARE TO BE PATCHED SO AS
TO REMOVE CRACKS AND DIVOTS. IF FLOOR SEALER IS TO BE USED, PROVIDE DETAILED
SPECIFICATIONS ON THE PROPOSED FLOOR SEALER FOR EVALUATION AND APPROVAL.
THE SEALER MUST BE AN APPROVED CLEAR PENETRATING SEALER THAT IS OIL, ACID,
AND WATER RESISTANT; PIGMENTED SEALERS AND EPOXY PAINTS ARE NOT
ACCEPTABLE. WHEN EXCESSIVE AMOUNTS OF SLIP RESISTANT AGENTS ARE USED, A
HIGH PRESSURE CLEANING SYSTEM OR EQUIVALENT MUST BE PROVIDED WITH
DRAINAGE TO FLOOR DRAINS. (114268, 114269)
CEILING: APPROVED CEILINGS ARE REQUIRED OVER ALL FOOD AND UTENSIL
HANDLING AREAS, IN RESTROOMS AND
JANITORIAL AREAS. EXPOSED BEAMS MUST BE FLUSH AND SEALED TO THE CEILING TO
PREVENT ANY GAPS WHERE DUST OR VERMIN CAN ACCUMULATE. HANGING BEAMS,
PIPES, FIRE SPRINKLER LINES, CONDUIT, DÉCOR, OR OTHER DUST-AND-VERMIN
COLLECTING ITEMS ARE NOT PERMITTED OVER FOOD AND UTENSIL HANDLING AREAS.
(113980, 113984, 114179, 114271)
WALLS: THE WALL SURFACES BEHIND SINKS SHALL BE COVERED WITH FIBERGLASS
REINFORCED PLASTIC (FRP), STAINLESS STEEL, OR THE EQUIVALENT. THE APPROVED
WALL COVER MUST EXTEND UP THE WALL AT LEAST FOUR (4) FEET FROM THE BACK
SPLASH AND COVER THE WALLS BEHIND THE SINK AND ACCOMPANYING DRAINBOARDS.
THE WALL SURFACE IN THE AREA WHERE THE DISH MACHINE IS INSTALLED SHALL BE
COVERED WITH FRP, STAINLESS STEEL, OR THE EQUIVALENT. THE APPROVED WALL
COVER MUST EXTEND UP THE WALL AT LEAST EIGHT FEET FROM THE FLOOR AND
COVER THE WALLS BEHIND THE DISH MACHINE AND ACCOMPANYING DRAINBOARDS. IF
HIGH PRESSURE SPRAY CLEANING EQUIPMENT IS PROPOSED OR REQUIRED TO CLEAN
NONSKID FLOORING, THEN WALL SURFACES IN THESE AREAS MUST BE COVERED WITH
AN APPROVED WATER RESISTANT COVERING (I.E., FRP, STAINLESS STEEL, OR THE
EQUIVALENT) TO A MINIMUM OF FOUR (4) FEET ABOVE THE BASE COVE. INDICATE
APPROVED WALL SURFACES IF YOU WILL BE INSTALLING HIGH PRESSURE SPRAY
CLEANING EQUIPMENT. (§114268,
114269, 114271).
1
22
3
4
5
69
8 7
10
14
1312
11
3
18
31922
20 21
15
242525
20
22 21
232326
18
29
27272727
30
31 33
33
3 3
24
23
4 N 1 3 DOOR REACH IN FREEZER AVANTCO SS-3F-HC 815 16"WX32"DX82"H SELF CONTAINED115/60/1 6.9 A
5 N 1 WASHER AND DRYER COMBO LG WM6998HBA 27’’W x 39”H x 33 1/8’’D 120/60/1 12 A
76/80 GAL
14 N 1 GREASE TRAP 35 GALZURN
15.1 N 1 WATER FILTER 175/16 REVERSEPENTAIR BWS 15 5
8 "D X 23 3
16 "H
15 N 1 FILTERED WATER FAUCET DELFIELD 12"LX12"DX9.5"H307
10 GAL TANK
15.2 N 1 S/S CABINET CTD-2436HGSW 24"D X 36"W X 35"H
15.2171717
20
22 21
32
28 N 1 TYPE I EXHAUST HOOD #1 CAPTIVE AIR 10'-6" X 4'-6"
28
33
29 N 1 TYPE I EXHAUST HOOD #1 CAPTIVE AIR 8'-6" X 4'-6"
16 N 1 TYPE I EXHAUST HOOD #1 CAPTIVE AIR 7'-6" X5'-0"
16
N 3 STOCK POT RANGE CPG-SP-18-NCPG 18"WX25"DX22"H 80 KBTU17
18 N 2 STAINLESS STEEL PREP TABLE WT-EB3084GSW 30"LX84"WX35"H
19 N LOT 5 TIER STORAGE SHELVING 1836NSMETRO 18"WX36"L
24 N 2 DOUGH MIXER 30QT 16"Ø BOWL D330HOBART 24"LX23"DX52"H 208/60/1 14 A
25 N 2 DOUGH MIXER 30QT 16"Ø BOWL D300HOBART 21"LX20"DX45"H 115/60/1 10.2 A
26 N 1 3 DOOR REACH IN REFRIGERATOR AVANTCO SS-3R-HC 815 16"WX32"DX82"H SELF CONTAINED115/60/1 3.37 A
27 N 4 FRYERS CASTLE 2932 SF 32"WX28.5"DX20"H
27.127.1
75 KBTU
30 N 1 STAINLESS STEEL PREP TABLE CUSTOMGSW -
32 N 1 2 DOOR U/C REFRIGERATOR TRUE TUC-60-32-HC 60"WX32"DX29"H SELF CONTAINED115/60/1 1.7 A
31 N 1 2 DOOR U/C FREEZER TRUE TUC-60-32F-HC 60"WX32"DX29"H SELF CONTAINED115/60/1 5.8 A
BACK ROOM
PREP AREA
CONCRETE FLOOR W/
DHS APPROVED
SEALANT. MONOPOLE
INC., PERMASEAL OR EQ.
SMOOTH, DURABLE NON
ABORBANT & EASLY
CLEANABLE.
6"H CERAMIC TILE
COVE BASE
3 8" RADIUS
STAINLESS STEEL
BEHIND THE HOOD &
FIBERGLASS
REINFORCED
PLASTIC(FRP)
OFFICE -
CONCRETE FLOOR W/
DHS APPROVED
SEALANT. MONOPOLE
INC., PERMASEAL OR EQ.
DRYWALL WITH
SEMI-GLOSS PAINT
SMOOTH, DURABLE,
NON-ABSORBENT,
WASHABLE
DRYWALL WITH
SEMI-GLOSS PAINT
SMOOTH, DURABLE,
NON-ABSORBENT,
WASHABLE
DRYWALL WITH
SEMI-GLOSS PAINT
SMOOTH, DURABLE,
NON-ABSORBENT,
WASHABLE
DRYWALL WITH
SEMI-GLOSS PAINT
SMOOTH, DURABLE,
NON-ABSORBENT,
WASHABLE
6"6"
20
22 21 15.1
KIT-1
THIS DRAWING, SPECIFICATIONS AND
IDEAS, DESIGNS THEREBY ARE AND SHALL
REMAIN THE PROPERTY OF IG DRAFTING &
DESIGN AND NO PART THEREOF SHALL BE
COPIED DISCLOSED TO OTHERS OR USED
IN CONNECTION WITH ANY WORK OR
PROJECT FOR WHICH THERE HAVE BEEN
PREPARED AND DEVELOPED, WITHOUT THE
WRITTEN CONSENT OF IG DRAFTING &
DESIGN, VISUAL CONTACT WITH THESE
DRAWINGS SHALL CONSTITUTE EVIDENCE
OF ACCEPTANCE OF THESE RESTRICTIONS.
DO
N
C
H
U
R
R
O
S
1
2
3
4
1
1
1
1
1
STEVEN GARCIA
DESIGNER
215 W 4th St
1/22/2025
S-1.1
General Notes
20 PsfROOF LIVE LOAD:
10.0 PsfROOF DEAD LOAD:
STRUCTURAL PLANS - SHEET INDEX
S-1.1 General Notes
S-1.2 Notes and Nailing Schedule
S-2.1 Roof Framing Plan & Details
S-2.2 Foundation Plan & Details
1. ALL INFORMATION SHOWN ON THE DRAWINGS IS GIVEN AS THE BEST
PRESENT KNOWLEDGE WITHIN GENERALLY ACCEPTED ENGINEERING
PRACTICE BUT WITHOUT GUARANTEE OF ACCURACY. WHERE ACTUALLY
CONDITIONS CONFLICT WITH THE DRAWINGS, THEY SHALL BE REPORTED TO
THE ENGINEER SO THAT THE PROPER REVISIONS MAY BE MADE PRIOR TO
PROCEEDING WITH THE WORK. MODIFICATIONS OF DETAILS OF
CONSTRUCTION OR DEVIATIONS FROM THE PLANS SHALL BE MADE ONLY
WITH THE WRITTEN APPROVAL FROM THE STRUCTURAL ENGINEER.
2. THE CONTRACTOR SHALL VERIFY AND BE RESPONSIBLE FOR:
A. ALL CONTRACT DOCUMENTS.
B.OMISSIONS AND/OR CONFLICTS BETWEEN THE VARIOUS ELEMENTS OF
THE CONTRACT DOCUMENTS.
C. ALL DIMENSIONS AND CONDITIONS AT THE SITE.
D.ANY CONDITION WHICH IN HIS OPINION MIGHT ENDANGER THE STABILITY
OF THE STRUCTURE.
E. INSURING PROPER ALIGNMENT OF FINAL STRUCTURE. THE CONTRACTOR
SHALL IMMEDIATELY NOTIFY THE ARCHITECT AND THE STRUCTURAL
ENGINEER OF ANY DISCREPANCY OR OMISSION BEFORE PROCEEDING WITH
THE WORK AND GET WRITTEN APPROVAL FOR ALTERNATE CONSTRUCTION.
3.ALL WORK SHALL CONFORM TO THE REQUIREMENTS OF ALL REGULATING
AGENCIES EXERCISING AUTHORITY OVER ANY PORTION OF THE WORK, I.E.
STATE OF CALIFORNIA DIVISION OF INDUSTRIAL SAFETY AND CAL/OSHA, ETC.,
AND SHALL CONFORM TO THE CURRENT CALIFORNIA BUILDING CODE OR
LOCAL CODES.
4. ALL WORK SHALL CONFORM TO THE BEST PRACTICE PREVAILING IN THE
VARIOUS TRADES COMPRISING THE WORK.
5. THE DESIGN, ADEQUACY AND SAFETY OF ERECTION, BRACING, SHORING,
TEMPORARY SUPPORTS, ETC., IS THE SOLE RESPONSIBILITY OF THE
CONTRACTOR AND HAS NOT BEEN CONSIDERED BY THE ENGINEER.
6. THE CONTRACTOR SHALL PROVIDE SAFE AND ADEQUATE BRACES AND
CONNECTIONS TO SUPPORT THE COMPONENT PARTS OF THE STRUCTURE
UNTIL THE STRUCTURE ITSELF (INCLUDING THE ROOF AND FLOOR
DIAPHRAGMS) IS COMPLETE ENOUGH TO ADEQUATELY SUPPORT ITSELF.
7. SPECIFIC NOTES AND DETAILS SHALL TAKE PRECEDENCE OVER GENERAL
NOTES AND TYPICAL DETAILS. OPTIONS, IF PROVIDED HEREIN, ARE FOR THE
CONTRACTOR'S CONVENIENCE. THE CONTRACTOR SHALL BE RESPONSIBLE
FOR ALL CHANGES NECESSARY, SHALL COORDINATE ALL DETAILS, SHALL
OBTAIN ALL REQUIRED APPROVALS, AND PAY ALL COSTS INCIDENT THERETO.
8. NO PIPES, DUCTS, SLEEVES, CHASES, ETC., SHALL BE PLACED IN BEAMS,
SLABS, OR WALLS UNLESS SPECIFICALLY SHOWN OR NOTED. NOR SHALL
ANY STRUCTURAL MEMBER BE CUT FOR PIPES, DUCTS, ETC., UNLESS
OTHERWISE NOTED. CONTRACTOR SHALL OBTAIN PRIOR APPROVAL FOR
INSTALLATION OF ANY ADDITIONAL PIPES, DUCTS, ETC. REFER TO
ARCHITECTURAL AND MECHANICAL DRAWINGS FOR LOCATIONS.
9. WORK THESE DRAWINGS WITH ARCHITECTURAL, MECHANICAL, ELECTRICAL,
CIVIL, AND OTHER DESIGN DRAWINGS.
10. WHERE REFERENCE IS MADE TO VARIOUS TEST STANDARDS FOR
MATERIALS, SUCH AS STANDARDS SHALL BE THE LATEST EDITION AND ALL
ADDENDUM.
11. AS A CONVENIENCE TO THE CONTRACTOR, THE ENGINEER SHALL REVIEW
SHOP DRAWINGS AS TO THEIR CONFORMANCE TO THE DESIGN CONCEPT.
THE CONTRACTOR SHALL BE RESPONSIBLE FOR ALL DIMENSIONS,
QUANTITIES, TECHNIQUES OF CONSTRUCTION AND COORDINATION WITH
OTHER TRADES. SHOP DRAWINGS ARE REQUIRED FOR THE FOLLOWING:
PRECAST CONCRETE ELEMENTS
STRUCTURAL STEEL
GLUED LAMINATED WOOD
NON-STANDARD TIMBER CONNECTIONS
12. VIBRATIONAL EFFECTS OF MECHANICAL EQUIPMENT HAVE NOT BEEN
CONSIDERED BY THE STRUCTURAL ENGINEER IN THE DESIGN OF THE
STRUCTURE. MECHANICAL EQUIPMENT SHALL THEREFORE BE ISOLATED TO
ELIMINATE VIBRATIONAL EFFECTS.
13. WHERE DESIGN AND DETAIL OF PLATE GIRDERS, TRUSSES, ETC. IS TO BE
PROVIDED BY THE FABRICATOR, CONTRACTOR SHALL SUBMIT
CALCULATIONS PREPARE BY A LICENSED CIVIL ENGINEER OR STRUCTURAL
ENGINEER TO THE PROJECT ENGINEER AND THE BUILDING DEPARTMENT
OFFICIAL FOR REVIEW, PRIOR TO FABRICATION.
14. OPTIONS, IF PROVIDED HEREIN, ARE FOR THE CONTRACTOR'S
CONVENIENCE. THE CONTRACTOR SHALL BE RESPONSIBLE FOR ALL CHANGE
NECESSARY, SHALL COORDINATE ALL DETAILS, SHALL OBTAIN ALL REQUIRED
APPROVALS, AND PAY ALL COSTS INCIDENT THERETO.
15. NON-STRUCTURAL FRAMING REQUIREMENTS ARE NOT SPECIFIED ON
STRUCTURAL DRAWINGS. SEE ARCHITECTURAL DRAWINGS FOR ANY
ADDITIONAL FRAMING REQUIRED.
16. MATERIAL TESTS AND STAGES OF BUILDING CONSTRUCTION INSPECTIONS
AS REQUIRED BY THE LOCAL CODE ARE TO BE STRICTLY ADHERED TO. THIS
INCLUDES, BUT IS NOT LIMITED TO, CONCRETE BLOCK, REINFORCING STEEL,
ELECTRICAL, MECHANICAL, PLUMBING, ETC.
17. SPECIFICATIONS TO PRECEDE PLANS AND DIMENSIONS. DIMENSIONS TO
PRECEDE PLANS.
18. THE CONTRACTOR SHALL INFORM THE ENGINEER IN WRITING ANY
DISCPREPANCIES OR OMISSIONS NOTED ON THE DRAWINGS OR IN THE
SPECIFICATIONS OR OF ANY VARIATIONS NEEDED IN ORDER TO CONFORM
TO BUILDING CODES, RULES AND REGULATIONS.
19. ALL DECK DRAINAGE SHALL BE COLLECTED AND CONDUCTED TO AN
APPROVED LOCATION IN A NON-EROSIVE MANNER.
20. ALL ROOF AND PAD DRAINAGE SHALL BE CONDUCTED TO THE STREET IN AN
ACCEPTABLE MANNER.
21. NO SUBSTITUTION SHALL BE MADE FOR ANY MATERIAL, ARTICLE, METHOD
OR PROCESS HEREIN SPECIFIED OR SHOWN ON PLANS UNLESS APPROVED
BY THE OWNER AND THE ARCHITECT/ENGINEER.
GENERAL NOTES
1. ALL LUMBER SHALL BE STRESS GRADE DOUGLAS FIR LARCH, U.N.O.
2. ALL WOOD IN DIRECT CONTACT WITH THE GROUND, MASONRY OR
CONCRETE SHALL BE TREATED WITH PRESERVATIVE, OR SHALL BE DECAY
RESISTANT WOOD AS PRESCRIBED IN DIVISION 31 (WOOD PRESERVATIVE).
3. ALL WALLS SHALL BE BOLTED TO FOUNDATION (CONCRETE OR CONCRETE
BLOCK) WITH 5 8" DIAMETER ANCHOR BOLTS EMBEDDED 7" INTO FOOTING
WITHIN 12" OF THE ENDS OF EACH WALL PANEL AND NOT MORE THAN 6'-O"
O.C. AND HAVE MINIMUM TWO BOLTS PER PIECE OF SILL PLATE AND ONE
LOCATED WITHIN 12" AND NOT LESS THAN 7 BOLT DIAMETER OR 4-3/8" OF
EACH END OF EACH SILL PLATE WITH 3"X3"X14" PLATE WASHERS EXCEPT AS
CALLED OUT FOR SHEAR WALLS.
4. ALL NAILING SHALL BE DONE IN ACCORDANCE WITH THE MINIMUM
REQUIREMENTS (TABLE 2304.9.1) LOCAL BUILDING CODE, EXCEPT AS
OTHERWISE SHOWN, AND SHALL BE DONE WITH COMMON WIRE NAILS
UNLESS OTHER TYPE OF NAIL IS ALLOWED BY THE L.A.C.B.C.
5. EXTERIOR WALLS AND BEARING PARTITIONS SHALL BE FRAMED OF 2X4
STUDS @ 16" O.C. WHEN SUPPORTING LOADS FROM ROOF AND TWO OR
MORE FLOORS ABOVE UNLESS OTHERWISE NOTED ON DRAWING. AT
STAGGERED STUD WALLS USE 2X4 @ 16" EACH SIDE TYPICAL @ ALL
FLOORS UNLESS NOTED OTHERWISE ON PLANS.
6. EVERY WOOD STUD BEARING WALL OR BEARING PARTITION SHALL BE
BRACED AT EACH END OR AS NEAR AS POSSIBLE, AND AT LEAST EVERY 25
FEET OF ITS LENGTH. THE TYPE OF BRACING SHALL MEET THE CODE
REQUIREMENTS FOR THIS PURPOSE.
7. FLOOR JOISTS SHALL BE DOUBLED UNDER PARTITIONS RUNNING PARALLEL
TO THE JOISTS. USE DOUBLE STUDS OR 4X4 POSTS UNDER DOUBLE JOISTS
OR 4X BEAMS, U.N.O. ON FRAMING PLANS.
8. BOLTS SHALL BE UNFINISHED BOLTS CONFORMING TO ASTM A-307.
9. PLYWOOD SHALL BE INTERIOR TYPE WITH EXTERIOR GLUE CONFORMING
TO APA 32/16 "PS I-95" OF GRADE CALLED FOR BELOW. LAID WITH FACE
GRAIN PERPENDICULAR TO SUPPORTS. USE COMMON NAILS ONLY UNLESS
OTHERWISE APPROVED BY THE STRUCTURAL ENGINEER AND LOCAL
BUILDING OFFICIAL.
A. ROOF SHEATHING SHALL BE: 12" THICK PLYWOOD, STRUCT. I, NAILS
WITH 10d NAILS @ 6" O.C. AT ALL DIAPHRAGM AND WALL BOUNDARIES.
CONTINUOUS PANEL EDGES ARE NOT BLOCKED, 10d NAILS @ 6" O.C. AT
PLYWOOD PANEL EDGES AND 10d NAILS @ 12" O.C. TO INTERMEDIATE
SUPPORTS.
B. FLOOR SHEATHING SHALL BE 5 8" PLYWOOD, (T&G), NAILED WITH 10d
NAILS @ 6" O.C. AT PLYWOOD PANEL EDGES AND 10d NAILS @ 10" O.C.
TO INTERMEDIATE SUPPORTS.
C. PLYWOOD SHEATHING SHALL BE INSPECTED AND APPROVED BY
BUILDING INSPECTOR PRIOR TO COVERING WITH FLOOR OR ROOF
MATERIAL.
D. SOLID BLOCKING AT EDGES REQUIRED FOR PLYWOOD ONLY WHERE
CALLED FOR ON DRAWING.
11. CUTTING, NOTCHING OR DRILLING OF BEAMS OR JOISTS TO BE PERMITTED
ONLY AS DETAILED OR APPROVED BY THE ENGINEER.
12. FRAMING HARDWARE SPECIFIED TO BE MANUFACTURED BY "SIMPSON
STRONG TIE COMPANY, INC." WITH NAIL SIZE AND NUMBER AS SPECIFIED IN
THE SIMPSON CATALOG LATEST EDITION, U.N.O.
2.RAFTER TIES SPACED 48" O.C. MAX ON CENTERS ARE REQUIRED
IMMEDIATELY ABOVE CEILING JOISTS WHICH ARE NOT PARALLEL TO THE
RAFTERS.
3. PROVIDE 2X BLOCKING UNDER PARTITIONS PERPENDICULAR TO FLOOR
JOISTS.
4. ROOF PURLINS MUST NOT BE SMALLER THAN RAFTERS THEY SUPPORT.
THE MAXIMUM SPAN FOR 2X4/2X6 ROOF PURLINS ARE 4'/6'. PROVIDE STRUTS
NOT SMALLER THAN 2X4 WITH AN UNBRACED LENGTH NOT OVER 8' AND
NOT FLATTER THAN 45 DEGREES FROM THE HORIZONTAL TO BEARING
WALLS AND PARTITIONS.
5. INTERIOR WALLS USED FOR SHEAR WALLS SHALL BE BALLOON FRAMED TO
RAFTERS.
6. ALL BEAMS TO BE SUPPORTED WITH SAME FULL WIDTH BEARING, U.N.O.
7. STRUCTURAL MEMBERS SHALL NOT BE CUT FOR PIPES, ETC, UNLESS
SPECIFICALLY DETAILED.
8. BEARING WALL STUDS CANNOT BE NOTCHED MORE THAN 25% OF THEIR
WIDTH. BORED HOLES CANNOT HAVE A DIAMETER GREATER THAN 40% OF
THE STUD WIDTH.
9. AT FLOOR LEVELS USE SOLID BLOCKING BELOW TRIMMERS AND POSTS
FROM BEARING HEADERS AND BEAMS.
10. ROOF DIAPHRAGM NAILING TO BE INSPECTED BEFORE COVERING. FACE
GRAIN OF PLYWOOD SHALL BE PERPENDICULAR TO SUPPORTS. FLOOR
SHALL HAVE TONGUE AND GROOVE OR BLOCKED PANEL EDGES.
1. FINISHED EXCAVATIONS FOR FOUNDATIONS SHALL BE NEAT AND TRUE
TO LINE, WITH ALL LOOSE MATERIAL AND STANDING WATER REMOVED
FROM EXCAVATIONS.
2. BEFORE ANY CONCRETE IS PLACED, EXCAVATIONS SHALL BE
CHECKED AND APPROVED BY A QUALIFIED SOILS ENGINEER TO
INSURE COMPLIANCE WITH THE REPORT REQUIREMENTS.
3. ALL FILL MATERIAL IS TO BE APPROVED BY THE SOILS ENGINEER AND
IS TO BE COMPACTED TO 90% OF MAXIMUM DENSITY ASTM METHOD
D-1557 (OR MORE AS DIRECTED). INSPECTION IS REQUIRED DURING
FILL AND COMPACTION.
4. NOTIFY THE STRUCTURAL ENGINEER OF ANY UNUSUAL SOIL
CONDITIONS THAT ARE IN VARIANCE WITH THE DATA HEREIN CITED.
5. STEP FOOTINGS WHERE REQUIRED AT A RATE OF 1 VERTICAL TO 2
HORIZONTAL, WITH A MAXIMUM VERTICAL STEP OF 2'-0".
6. SLAB ON GRADE SHALL BE PLACED ON FIRM, MOISTENED COMPACT
EARTH (BELOW SUBBASE) AND SHALL HAVE CONSTRUCTION JOINTS
SPACED NO FURTHER APART THAN 25 FEET IN EACH DIRECTION,
UNLESS OTHERWISE NOTED.
7. ALL WOOD BEARING WALL, SHEAR WALL AND EXTERIOR WALL
FOUNDATION PLATES OR SILLS SHALL BE BOLTED TO THE
FOUNDATION OR FOUNDATION WALL WITH NOT LESS THAN 5 8"
DIAMETER X 12" ANCHOR BOLTS WITH 3" X 3" X 0.229" SQUARE PLATE,
EMBEDDED AT LEAST 9" INTO CONCRETE AND SPACED NOT MORE
THAN 4'-0" APART UNLESS OTHERWISE NOTED. THERE SHALL BE A
MINIMUM OF TWO BOLTS PER PIECE WITH ONE BOLT LOCATION WITHIN
12" OF EACH END OF EACH PIECE.
8. DIMENSIONS ARE NOT FURNISHED TO SIMPSON HD, LCB, CB OR PA
TYPE HOLDOWNS. IT IS THE RESPONSIBILITY OF THE CONTRACTOR'S
SUPERINTENDENT, THE FRAMING CONTRACTOR AND THE CONCRETE
CONTRACTOR TO LOCATE THESE ANCHORS IN THE EXACT LOCATION.
9. ALL SIMPSON PA, HD, LCB AND CB HOLDOWNS TO BE FASTENED TO
MIN 4X4 POST.
10. ALL ISOLATED POSTS AND BEAMS TO HAVE SIMPSON PB'S AND PC'S
MINIMUM UNLESS OTHERWISE NOTED.
11. SIMPSON PA, HD, LCB AND CB ANCHORS TO BE TIED IN PLACE PRIOR
TO CALLING FOR INSPECTION.
12. SLABS SHALL HAVE MINIMUM THICKNESS OF 4 INCHES AND
REINFORCEMENT OF #4 @ 16" OC EACH WAY OR APPROVED EQUAL,
PLACED AT THE CENTER OF THE SLAB. FOR MOISTURE SENSITIVE
SLABS, A VAPOR BARRIER MEMBRANE COVERED WITH A 2" MINIMUM
OF CLEAN SAND SHOULD BE PLACED BELOW THE SLAB.
13. LAG BOLTS: PROVIDE LEAD HOLE 70% OF THREADED SHANK DIAMETER
AND FULL DIAMETER FOR SMOOTH SHANK PORTION. SOAP, PARAFFIN,
OR OTHER APPROVED LUBRICANT SHALL BE USED ON THREADS.
INSTALLATION SHALL BE BY SCREWING NOT HAMMERING. CARE SHALL
BE TAKEN TO AVOID OVER TORQUING BOLT.
14. PLATE WASHERS ARE REQUIRED FOR ALL HOLDOWNS.
15. ALL HOLDOWN ANCHOR NUTS SHALL BE TIGHTENED JUST PRIOR TO
COVERING OF THE WALL FRAMING.
16. THE FOUNDATION SILLS SHALL BE PRESSURE TREATED OR
FOUNDATION GRADE REDWOOD.
17. FOUNDATIONS FOR ALL BUILDINGS WHERE THE SURFACE OF THE
GROUND SLOPES MORE THAN 1 UNIT VERTICAL IN 10 UNITS
HORIZONTAL (10% SLOPE) SHALL BE LEVEL OR SHALL BE STEPPED SO
THAT BOTH TOP AND BOTTOM OF SUCH FOUNDATION ARE LEVEL.
18. EXPANSIVE SOIL REQUIREMENTS:
IF SOIL IS FOUND TO BE EXPANSIVE, THE FOOTINGS MUST MEET THE
FOLLOWING MINIMUM REQUIREMENTS:
A. DEPTH OF FOOTINGS BELOW THE NATURAL AND FINISH GRADES
SHALL NOT BE LESS THAN 24" FOR EXTERIOR AND 24" FOR INTERIOR
FOOTINGS.
B. EXTERIOR WALLS AND INTERIOR BEARING WALLS SHALL BE
SUPPORTED ON CONTINUOUS FOOTINGS.
C. FOOTINGS SHALL BE REINFORCED WITH A MINIMUM FOUR 12"
DIAMETER DEFORMED REINFORCING BARS. TWO BARS SHALL BE
PLACED 4 INCHES OF THE BOTTOM OF THE FOOTING AND TWO BARS
WITHIN 4 INCHES OF THE TOP OF THE FOOTINGS.
D. THE SOIL BELOW AN INTERIOR CONCRETE SLAB SHALL BE
SATURATED WITH MOISTURE TO A DEPTH OF 18" PRIOR TO PLACING OF
CONCRETE.
E. CONCRETE SLABS ON GRADE ON EXPANSIVE SOIL OR COMPACTED
FILL SHALL BE PLACED ON A 4" FILL OF COARSE AGGREGATE OR ON A
2" SAND BED COVERED MOISTURE BARRIER MEMBRANE. THE SLABS
SHALL BE AT LEAST 4" THICK AND SHALL BE REINFORCED WITH #4
BARS SPACED AT INTERVALS NOT EXCEEDING 16" EACH WAY.
19. HOLDOWN CONNECTOR BOLT HOLES SHALL NOT BE MORE THAN 116"
OVERSIZED AT THE CONNECTOR OF THE HOLDOWN TO THE POST.
FOUNDATION NOTES STRUCTURAL WOOD NOTES
GENERAL NOTES AND SPECIFICATIONS
ME
C
H
.
U
N
I
T
AT
T
A
C
H
E
M
E
N
T
:
21
5
W
.
4
t
h
.
S
t
.
Sa
n
t
a
A
n
a
,
C
A
9
2
7
0
1
Sheet #
Sheet title
Date :
Project #:
Phase:
10-10-2024
24-186
2nd submittal
#Date
Revisions:
1
2
3
4
St
r
u
c
t
u
r
a
l
E
n
g
i
n
e
e
r
i
n
g
+
D
e
s
i
g
n
5
10 PsfCEILING LIVE LOAD:
SEISMIC DESIGN CATEGORY:
SEISMIC SITE CLASS:
SPECTRAL RESPONSE ACCELERATION
SPECTRAL RESPONSE ACCELERATION
AT SHORT PERIODS
AT 1-SECOND PERIOD
SEISMIC VALUES (FOR AREAS A)
MAPPED SPECTRAL RESPONSE ACCELERATION
MAPPED SPECTRAL RESPONSE ACCELERATION
AT SHORT PERIODS
AT 1-SECOND PERIOD
a.1
b.
d.
e.
c.
IMPORTANCE FACTOR 1
a.2 RISK CATEGORY II
SDC="D"
"D"
SDS=1.17g
SD1=0.8g
SS=1.48g
S1=0.51g
LATITUDE:
LONGITUDE:
33.7482 °N
-117.8692 °W
DESIGN PARAMETERS
2022 CBC : CALIFORNIA BUILDING CODE
7-16 ASCE : MINIMUM DESIGN LOADS FOR BUILDINGS & OTHER STRUCTURES
2021 IBC : INTERNATIONAL BUILDING CODE
DEAD & LIVE LOADS
7.0 PsfCEILING DEAD LOAD:
215 W 4th St
1/22/2025
TABLE R602.3(1)FASTENING SCHEDULE
Roof
1 Each end toe nail
End nail
6" o.c. face nail
2 Ceiling joists to top plate Per joist, toe nail
3
4
SPACING AND LOCATION
Face nail
Face nail
5
Collar tie to rafter, face nail
6
Rafter or roof truss to plate
i
7
End nail
Wall
8
Stud to stud (not at braced
wall panels)
9
10
11
Continuous header to stud Toe nail
12 End nail
12" o.c. ea. edge face nail
12" o.c. face nail
16" o.c. face nail
16" o.c. ea. edge face nail
24" o.c. face nail
16" o.c. face nail
Face nail each rafter
Toe nail
Top plate to top plate
14 Double top plate splice
15
12" o.c. face nail
Roof
16 16" o.c. face nail
17 Top or bottom plate to
stud
Toe nail
End nail
18
19 Face nail
16" o.c. face nail
12" o.c. face nail
16" o.c. face nail
Face nail
20
1" × 6" sheathing to each
bearing Face nail
21
Floor
22
Joist to sill, top plate or girder Toe nail
23
6" o.c. toe nail
24 1" × 6" sub Face nail
25 2" sub Blind and face nail
26 2" planks (plank & beam At each bearing, face
nail
Face nail
4" o.c. toe nail
27 Band or rim joist to joist
28
29 Ledger strip supporting joists
or rafters
At each joist or rafter, face nail
30 Each end, toe nail
End nail
Face nail at ends and at
each splice
NUMBER AND TYPE OF
FASTENER a, b, c
R602.3 Design and Construction
Exterior walls of wood-frame construction shall be designed and constructed in accordance with the provisions of this chapter
and Figures R602.3(1) and R602.3(2), or in accordance with AWC NDS. Components of exterior walls shall be fastened in accordance
with Tables R602.3(1) through R602.3(4). Wall sheathing shall be fastened directly to framing members and, where placed on the
exterior side of an exterior wall, shall be capable of resisting the wind pressures listed in Table R301.2.1(1) adjusted for height and
exposure using Table R301.2.1(2) and shall conform to the requirements of Table R602.3(3). Wall sheathing used only for exterior wall
covering purposes shall comply with Section R703.
Studs shall be continuous from support at the sole plate to a support at the top plate to resist loads perpendicular to the wall.
The support shall be a foundation or
Exception: Jack studs, trimmer studs and cripple studs at openings in walls that comply with Tables R602.7(1) and R602.7(2).
California Residential Code 2022
DESCRIPTION OF BUILDING
ELEMENTSITEM
Blocking between ceiling joists,
rafters or trusses to top plate
or other framing below
Blocking between rafters or
truss not at the wall top plates,
to rafter or truss
Flat blocking to truss and web
4-8d box (2.5" x 0.113") or
3-8d common (2.5" x 0.131") or
3-10d box (3" x 0.128") or
3-3" x 0.131" nails
Ceiling joist not attached to
parallel rafter, laps over
partitions [see Section R802.5.2
and Table R802.5.2(1)]
Ceiling joist attached to parallel
rafter (heel joint) [see Section
R802.5.2 and Table R802.5.2(1)]
Roof rafters to ridge, valley or
hip rafters or roof rafter to
minimum 2" ridge beam
Stud to stud and abutting
studs at intersecting wall
corners (at braced wall panels)
Built-up header (2" to 2"
header with 1/2" spacer)
Adjacent full-height stud to end
of header
Bottom plate to joist, rim joist,
band joist or blocking (not at
braced wall panels)
2 toe nails on one side and 1
toe nail on opposite side of
each rafter or truss
Face nail on each side of end
joint (minimum 24" lap splice
length each side of end joint)
2-8d common (2.5" x 0.131") or
2-3" x 0.131" nails
2-16d common (3.5" x 0.162") or
3-3" x 0.131" nails
16d common (3.5" x 0.162") or
3" x 0.131" nails
4-8d box (2.5" x 0.113") or
3-8d common (2.5" x 0.131") or
3-10d box (3" x 0.128") or
3-3" x 0.131" nails
4-10d box (3" x 0.128") or
3-16d common (3.5" x 0.162") or
4-3" x 0.131" nails
Table R802.5.2(1)
4-10d box (3" x 0.128") or
3-10d common (3" x 0.148") or
4-3" x 0.131" nails
3-16d box (3.5" x 0.135") or
3-10d common (3" x 0.148") or
4-10d box (3" x 0.128") or
4-3" x 0.131" nails
4-16d box (3.5" x 0.135") or
3-10d common (3" x 0.148") or
4-10d box (3" x 0.128") or
4-3" x 0.131" nails
3-16d box (3.5" x 0.135") or
2-16d common (3.5" x 0.162") or
3-10d box (3" x 0.128") or
3-3" x 0.131" nails
16d common (3.5" x 0.162")
10d box (3" x 0.128") or
3" x 0.131" nails
16d box (3.5" x 0.135") or
3" x 0.131" nails
16d common (3.5" x 0.162")
16d common (3.5" x 0.162")
16d box (3.5" x 0.135")
5-8d box (2.5" x 0.113") or
4-8d common (2.5" x 0.131") or
4-10d box (3" x 0.128")
4-16d box (3.5" x 0.135") or
2-16d common (3.5" x 0.162") or
4-10d box (3" x 0.128") or
4-3" x 0.131" nails
16d common (3.5" x 0.162")
10d box (3" x 0.128") or
3" x 0.131" nails
8-16d box (3.5" x 0.135") or
12-16d common (3.5" x 0.162") or
12-10d box (3" x 0.128") or
12-3" x 0.131" nails
16d common (3.5" x 0.162")
16d box (3.5" x 0.135") or
3" x 0.131" nails
For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 mile per hour = 0.447 m/s; 1 ksi = 6.895 MPa.
a. Nails are smooth-common, box or deformed shanks except where otherwise stated. Nails used for framing and sheathing
connections are carbon steel and shall have minimum average bending yield strengths as shown: 80 ksi for shank
diameter of 0.192 inch (20d common nail), 90 ksi for shank diameters larger than 0.142 inch but not larger than 0.177
inch, and 100 ksi for shank diameters of 0.142 inch or less. Connections using nails and staples of other materials, such
as stainless steel, shall be designed by accepted engineering practice or approved under Section R104.11.
b. RSRS-01 is a Roof Sheathing Ring Shank nail meeting the speci
c. Nails shall be spaced at not more than 6 inches on center at all supports where spans are 48 inches or greater.
d. Four-foot by 8-foot or 4-foot by 9-foot panels shall be applied vertically.
e. Spacing of fasteners not included in this table shall be based on Table R602.3(2).
f. For wood structural panel roof sheathing attached to gable end roof framing and to intermediate supports within 48 inches
of roof edges and ridges, nails shall be spaced at 4 inches on center where the ultimate design wind speed is greater
than 130 mph in Exposure B or greater than 110 mph in Exposure C.
g. Gypsum sheathing shall conform to ASTM C1396 and shall be installed in accordance with ASTM C1280 or GA 253.
Fiberboard sheathing shall conform to ASTM C208.
h. Spacing of fasteners on required blocking and at edges supported by framing members and required blocking. Blocking
of roof or perpendicular to the framing members need not be provided except as required by other provisions of this code.
Floor perimeter shall be supported by framing members or solid blocking.
i. Where a rafter is fastened to an adjacent parallel ceiling joist in accordance with this schedule, provide two toe nails on
one side of the rafter and toe nails from the ceiling joist to top plate in accordance with this schedule. The toe nail on the
opposite side of the rafter shall not be required.
ADDITIONAL NOTES
1. CONTRACTORS RESPONSIBLE FOR THE CONSTRUCTION OF A WIND OF SEISMIC
FORCE RESISTING SYSTEM/COMPONENT LISTED IN THE "STATEMENT OF SPECIAL
INSPECTION" SHALL SUBMIT A WRITTEN STATEMENT OF RESPONSIBILITY TO THE
LADBS INSPECTORS AND THE OWNER PRIOR TO THE COMMENCEMENT OF WORK
ON SUCH SYSTEM OR COMPONENT PER SEC 1709.1.
2. CONTINUOUS SPECIAL INSPECTION BY A REGISTERED DEPUTY INSPECTOR IS
REQUIRED FOR FIELD WELDING, POST-INSTALLED ADHESIVE ANCHORS INSTALLED
HORIZONTALLY OR UPWARDLY INCLINED TO RESIST SUSTAINED TENSION LOADS,
SHOTCRETE PLACEMENT, CONCRETE STRENGTH f=c>2500 PSI, SPRAYED-ON
FIREPROOFING, ENGINEERING MASONRY, HIGH-LIFT GROUTING, HIGH LOAD
DIAPHRAGMS AND SPECIAL MOMENT-RESISTING CONCRETE FRAMES, AND
HELICAL PILE FOUNDATIONS.
3. FOUNDATION SILLS SHALL BE NATURALLY DURABLE OR PRESERVATIVE-TREATED
WOOD. FIELD WELDING TO BE DONE BY WELDERS CERTIFIED BY THE LADBS FOR
4. (STRUCTURAL STEEL)(REINFORCING STEEL)(LIGHT GAUGE STEEL).CONTINUOUS
INSPECTION BY A DEPUTY INSPECTOR IS REQUIRED.
5. SHOP WELDS MUST BE PERFORMED IN A LADBS LICENSED FABRICATORS SHOP.
6. LADBS LICENSED FABRICATOR IS REQUIRED FOR (TRUSSES),(STRUCTURAL STEEL)
7. GLUED-LAMINATED TIMBERS MUST BE FABRICATED IN A LADBS LICENSED SHOP.
IDENTIFY GRADE SYMBOL AND LAMINATION SPECIES PER 2015 NDS SUPPLEMENT
TABLE 5A.
8. PROVIDE LEAD HOLE 40%-70% OF THREADED SHANK DIAMETER AND FULL
DIAMETER FOR SMOOTH SHANK PORTION.
9. PERIODIC SPECIAL INSPECTION IS REQUIRED FOR WOOD SHEAR WALLS, SHEAR
PANELS, AND DIAPHRAGMS, INCLUDING NAILING, BOLTING, ANCHORING, AND
OTHER FASTENING TO COMPONENTS OF THE SEISMIC FORCE RESISTING SYSTEM.
SPECIAL INSPECTION BY A DEPUTY INSPECTOR IS REQUIRED WHERE THE
FASTENER SPACING OF THE SHEATHING IS 4 INCHES ON CENTER OR LESS.
10. SPECIAL ACTIVITY INSPECTION IS REQUIRED FOR (BUILDINGS OVER 5 STORIES OR
60' IN HEIGHT)(BUILDINGS OVER 50,OOO SQ.FT. OF GROUND FLOOR
AREA)(BUILDINGS OVER 200,000 SQ.FT. OF TOTAL FLOOR AREA.
11. A COPY OF THE LOS ANGELES RESEARCH REPORT AND/OR CONDITIONS OF
LISTING SHALL BE MADE AVAILABLE AT THE JOB SITE.
12. IF ADVERSE SOIL CONDITIONS ARE ENCOUNTERED, A SOILS INVESTIGATION
REPORT MAY BE REQUIRED.
13. HOLD-DOWN CONNECTOR BOLTS INTO WOOD FRAMING REQUIRE APPROVED 1
PLATE WASHERS; AND HOLD-DOWNS SHALL BE FINGER TIGHT AND WRENCH 2
TURN JUST PRIOR TO COVERING THE WALL FRAMING. CONNECTOR BOLTS INTO
FRAMING REQUIRE STEEL PLATE WASHERS ON THE POST ON THE OPPOSITE SIDE
OF THE ANCHORAGE DEVICE. PLATE SIZE SHALL BE A MINIMUM OF 0.299 INCH BY 3
INCHES BY 3 INCHES.
14. ROOF DIAPHRAGM NAILING TO BE INSPECTED BEFORE COVERING. FACE GRAIN OF
PLYWOOD SHALL BE PERPENDICULAR TO SUPPORTS. FLOOR SHALL HAVE TONGUE
AND GROOVE OR BLOCKED PANEL EDGES. PLYWOOD SPANS SHALL CONFORM
WITH TABLE 2304.7.
15. ALL DIAPHRAGM AND SHEAR WALL NAILING SHALL UTILIZE COMMON NAILS OR
GALVANIZED BOX.
16. ALL BOLTS SHALL BE DRILLED 1/32" TO 1/16" OVERSIZED.
17. HOLD-DOWN HARDWARE MUST BE SECURED IN PLACE PRIOR TO FOUNDATION
INSPECTION.
Bottom plate to joist, rim
joist, band joist or blocking
(at braced wall panel)
Top plates, laps at corners and
intersections
1" brace to each stud and plate
1" × 8" and wider sheathing to
each bearing
Rim joist, band joist or
blocking to sill or top plate
(roof applications also)
Built-up girders and beams,
2-inch lumber layers
Bridging or blocking to joist,
rafter or truss
3-16d box (3.5" x 0.135") or
2-16d common (3.5" x 0.162") or
4-3" x 0.131" nails
4-8d box (2.5" x 0.113") or
3-16d box (3.5" x 0.135") or
4-8d common (2.5" x 0.131") or
4-10d box (3" x 0.128") or
4-3" x 0.131" nails
3-16d box (3.5" x 0.135") or
2-16d common (3.5" x 0.162") or
3-10d box (3" x 0.128") or
4-3" x 0.131" nails
3-10d box (3" x 0.128") or
2-16d common (3.5" x 0.162") or
3-3" x 0.131" nails
3-8d box (2.5" x 0.113") or
2-8d common (2.5" x 0.131") or
2-10d box (3" x 0.128") or
2 staples 1.75"
3-8d box (2.5" x 0.113") or
2-8d common (2.5" x 0.131") or
2-10d box (3" x 0.128") or
2 staples, 1" crown, 16" ga., 1.75" long
3-8d box (2.5" x 0.113") or
3-8d common (2.5" x 0.131") or
3-10d box (3" x 0.128") or
3 staples, 1" crown, 16" ga., 1.75" long
Wider than 1"x8"
4-8d box (2.5" x 0.113") or
3-8d common (2.5" x 0.131") or
3-10d box (3" x 0.128") or
4 staples, 1" crown, 16" ga., 1.75" long
Nail each layer as follows: 32" o.c.
at top and bottom and staggered.
24" o.c. face nail at top and bottom
staggered on opposite sides
4-8d box (2.5" x 0.113") or
3-8d common (2.5" x 0.131") or
3-10d box (3" x 0.128") or
3-3" x 0.131" nails
8d box (2.5" x 0.131")
8d common (2.5" x 0.131") or
10d box (3" x 0.128") or
3" x 0.131" nails
3-8d box (2.5" x 0.113") or
2-8d common (2.5" x 0.131") or
3-10d box (3" x 0.128") or
2 staples, 1" crown, 16" ga., 1.75" long
3-16d box (3.5" x 0.135") or
2-16d common (3.5" x 0.162")
3-16d box (3.5" x 0.135") or
2-16d common (3.5" x 0.162")
3-16d common (3.5" x 0.162") or
4-10d box (3" x 0.128") or
4-3" x 0.131" nails
4-3" x 14ga. staples, 7/16" crown
20d common (4" x 0.192") or
10d box (3" x 0.128") or
3" x 0.131" nails
And:
2-20d comon (4" x 0.192") or
3-10d box (3" x 0.128") or
3-3" x 0.131" nails
4-16d box (3.5" x 0.135") or
3-16d common (3.5" x 0.162") or
4-10d box (3" x 0.128") or
4-3" x 0.131" nails
2-10d common (3" x 0.148") or
2-8d box (2.5" x 0.131") or
2-3" x 0.131" nails
HARDWARE LARR REPORT#
1. SIMPSON HDU - LARR 25720
2. SIMPSON SSTB - LARR 25827
3. SIMPSON HU/HUTF HANGER - LARR 25807/25803
4. SIMPSON MST STRAP - LARR 25713
5. SIMPSON A35/LTP4 FRAMING CLIPS - LARR 25814
6. SIMPSON SDS WOOD SCREWS - LARR 25711
7. SIMPSON CC/CCQ, ECC/ECCQ, PC, EPC - LARR 25714
8. SIMPSON EPOXY SET - LARR 25279
10. HARDY FRAMES - LARR 25759-T
11. SIMPSON STRONG WALLS - LARR 25427
11. SIMPSON ADJUSTABLE HANGERS - LARR 25804
S-1.2
Nailing schedules
and Additional
Notes
ME
C
H
.
U
N
I
T
AT
T
A
C
H
E
M
E
N
T
:
21
5
W
.
4
t
h
.
S
t
.
Sa
n
t
a
A
n
a
,
C
A
9
2
7
0
1
Sheet #
Sheet title
Date :
Project #:
Phase:
10-10-2024
24-186
2nd submittal
#Date
Revisions:
1
2
3
4
St
r
u
c
t
u
r
a
l
E
n
g
i
n
e
e
r
i
n
g
+
D
e
s
i
g
n
5
215 W 4th St
1/22/2025
P.L.P.L.
SCALE: 1/4"=1'-0"
FOUNDATION PLAN
(E)FOOTING (E)FOOTING (E)FOOTING (E)FOOTING (E)FOOTING
(E)FOOTING
(E)FOOTING (E)FOOTING
(E)FOOTING (E)FOOTING (E)FOOTING
(E)FOOTING
(E)FOOTING (E)FOOTING (E)FOOTING (E)FOOTING (E)FOOTING (E)FOOTING
(E)FOOTING (E)FOOTING (E)FOOTING (E)FOOTING (E)FOOTING (E)FOOTING
(E
)
G
R
A
D
E
B
E
A
M
(E
)
G
R
A
D
E
B
E
A
M
(E)PAD
(E
)
2
x
8
F
.
J
.
@1
6
"
o
.
c
.
(E
)
2
x
8
F
.
J
.
@1
6
"
o
.
c
.
(E
)
2
x
8
F
.
J
.
@1
6
"
o
.
c
.
SNEEZE GUARD
60"H A.F.F.
(N)RAMP
1:12 SLOPE
(N)RAILING 36"H
SEE DET.5/S-2.1
(N
)
2
x
8
F
.
J
.
A
T
T
A
C
H
E
D
T
O
(E
)
F
.
J
.
,
A
L
I
G
N
E
D
W
I
T
H
PA
R
T
I
T
I
O
N
W
A
L
L
A
B
O
V
E
(N)2x8 F.J. @16" o.c.
SUPPORTED AT EACH
F.J. BELOW
(E
)
F
O
O
T
I
N
G
(E
)
F
O
O
T
I
N
G
(E
)
F
O
O
T
I
N
G
(E
)
F
O
O
T
I
N
G
72"x48"
LANDING
60"x60"
LANDING
(N)2x8 F.J.
@16" o.c.
(N)4x4
K.P.
(N)4x4
K.P.
(N)2-2x8 F.J.
UNDER RAILING
(N)2-2x8 F.J.
UNDER RAILING
(N
)
4
x
8
D
.
F
.
#
2
BE
A
M
(N
)
4
x
8
D
.
F
.
#
2
BE
A
M
4 PARTITION WALL ON RAISED FOUND.
(E)STEEL
COLUMN
(N)1'-6"x1'-6"x18"D
PAD w/(4)#4
REBAR @ BOTTOM
FOR SISTERING
DETAIL SEE DET.
1/S-2.2
’
(N)2x8 F.J. PER PLAN,
SUPPORTED AT EACH
F.J. BELOW
(E)2x8 F.J.
PER PLAN
SIMPSON HANGER
FOR F.J. TO BEAM
(E)FOOTING
SIMPSON BC4 SIMPSON BC4
(N)2x CRIPPLE STUD
/ FILLER TO MATCH
F.J. BELOW w/8d
NAIL AT EACH SIDE
(N)2x8 F.J.
PER PLAN
(N)2x8 F.J.
PER PLAN
BE
A
M
P
E
R
P
L
A
N
BE
A
M
P
E
R
P
L
A
N
(N)36"H. METAL
RAILING PER
DET. 5/S-2.1
(N)2x8 F.J.
PER PLAN
(N)2-2x8 F.J.
PER PLAN
(N)2-2x8 F.J.
PER PLAN
(N)2-2x8 F.J.
PER PLAN
(N)2-2x8 F.J.
PER PLAN
(N)2-2x8 F.J.
PER PLAN
(N)2-2x8 F.J.
PER PLAN
(E)FOOTING
(E)FOOTING (E)FOOTING
RAMP DETAIL 3
SECTION VIEW
PLAN VIEW
60"x60" LANDING
2"
2"
16d COMMON NAIL
@16" O.C. STAGGERED
SISTERED RAFTER DETAIL
REBAR
PER PLAN
SIMPSON PB44
4x4 KING POST
EXISTING
FOOTING
(2)#4 REBAR DRILL AND
USE SIMPSON SET-XP
EPOXY ICC-ES ESR-2508
(DEPUTY INSPEC.
REQUIRED)
1
(N)PAD TO (E)FOOTING2
5 RAILING AT RAMP
(N)36"H. METAL
RAILING PER
DET. 5/S-2.1
(N)36"H. METAL
RAILING PER
DET. 5/S-2.1
(N)36"H. METAL
RAILING PER
DET. 5/S-2.1
(N)36"H. METAL
RAILING PER
DET. 5/S-2.1
(N)36"H. METAL
RAILING PER
DET. 5/S-2.1
SIMPSON HANGER
FOR F.J. TO BEAM
(N)2x CRIPPLE STUD
/ FILLER TO MATCH
F.J. BELOW w/8d
NAIL AT EACH SIDE
(N)36"H. METAL
RAILING PER
DET. 5/S-2.1
(N)2-2x8 F.J.
UNDER RAILING
ME
C
H
.
U
N
I
T
AT
T
A
C
H
E
M
E
N
T
:
21
5
W
.
4
t
h
.
S
t
.
Sa
n
t
a
A
n
a
,
C
A
9
2
7
0
1
Sheet #
Sheet title
Date :
Project #:
Phase:
10-10-2024
24-186
2nd submittal
#Date
Revisions:
1
2
3
4
St
r
u
c
t
u
r
a
l
E
n
g
i
n
e
e
r
i
n
g
+
D
e
s
i
g
n
5
Foundation Plan
S-2.1
215 W 4th St
1/22/2025
(NEW)
SKYLIGHT
4'X4'
(EX.) SKYLIGHT
5'X6'
P.L.P.L.
EF UNIT 2
403 LBS
(E
)
2
x
6
R
.
R
.
@2
4
"
O
.
C
.
(E
)
2
x
1
2
C
.
J
.
@2
4
"
O
.
C
.
(E) SUPPORT POINT RAFTER
(E) SUPPORT POINT RAFTER
SCALE: 1/4"=1'-0"
ROOF FRAMING PLAN
EF UNIT 3
238 LBS
EF UNIT 1
296 LBS
MUA UNIT 1
692 LBS
2 31
B
2"
2"
16d COMMON NAIL
@16" O.C. STAGGERED
A
10"x12"x1/4" PLATE
CROSS SECTION A-A
1/4" STEEL PLATE
BOTH SIDES
A
WOOD JOIST
PER PLAN
2x12 C.J. PER PLAN 4"
BOTH SIDES
12"
11.25"
OPENING IN JOIST
10"5"
2.5"
2.5"
LUS210-2
SIMPSON HANGER
2-2x12
ROOF RAFTER
PER PLAN
(E) ROOF RAFTER
PER PLAN
(E) CEILING JOIST
PER PLAN
(E) ROOF
SHEATHING
(E) LEDGER
OR BLK'G
5
(R
.
R
.
#
3
)
6
(E) BRICK
WALL
(N)2x4 DIAGONAL
BRACE w/(8)10d
EA.END
(E) 2x6 R.R. +
(N) 2x12 R.R.
SISTERED
OR (N) 2-2x12 R.R.
WHERE OCCURS
(E) 2x12 C.J.
LUS210-2
SIMPSON HANGER
7
B
2"
2"
16d COMMON NAIL
@16" O.C. STAGGERED
(E) LEDGER
OR BLK'G
AL
I
G
N
(
N
)
2
-
2
x
1
2
R
.
R
.
OR
(
N
)
2
x
1
2
S
I
S
T
E
R
E
D
T
O
(
E
)
2
X
6
(R
.
R
.
#
3
)
AL
I
G
N
(
N
)
2
-
2
x
1
2
R
.
R
.
OR
(
N
)
2
x
1
2
S
I
S
T
E
R
E
D
T
O
(
E
)
2
X
6
(R
.
R
.
#
3
)
AL
I
G
N
(
N
)
2
-
2
x
1
2
R
.
R
.
OR
(
N
)
2
x
1
2
S
I
S
T
E
R
E
D
T
O
(
E
)
2
X
6
(R
.
R
.
#
3
)
AL
I
G
N
(
N
)
2
-
2
x
1
2
R
.
R
.
OR
(
N
)
2
x
1
2
S
I
S
T
E
R
E
D
T
O
(
E
)
2
X
6
(R
.
R
.
#
2
)
AL
I
G
N
(
N
)
2
-
2
x
1
2
R
.
R
.
OR
(
N
)
2
x
1
2
S
I
S
T
E
R
E
D
T
O
(
E
)
2
X
6
(R
.
R
.
#
2
)
AL
I
G
N
(
N
)
2
-
2
x
1
2
R
.
R
.
OR
(
N
)
2
x
1
2
S
I
S
T
E
R
E
D
T
O
(
E
)
2
X
6
(R
.
R
.
#
1
)
AL
I
G
N
(
N
)
2
-
2
x
1
2
R
.
R
.
OR
(
N
)
2
x
1
2
S
I
S
T
E
R
E
D
T
O
(
E
)
2
X
6
(R
.
R
.
#
1
)
AL
I
G
N
(
N
)
2
-
2
x
1
2
R
.
R
.
OR
(
N
)
2
x
1
2
S
I
S
T
E
R
E
D
T
O
(
E
)
2
X
6
(R
.
R
.
#
4
)
AL
I
G
N
(
N
)
2
-
2
x
1
2
R
.
R
.
OR
(
N
)
2
x
1
2
S
I
S
T
E
R
E
D
T
O
(
E
)
2
X
6
(R
.
R
.
#
4
)
AL
I
G
N
(
N
)
2
-
2
x
1
2
R
.
R
.
OR
(
N
)
2
x
1
2
S
I
S
T
E
R
E
D
T
O
(
E
)
2
X
6
AC. UNIT 1
655 LBS
2x
1
2
S
I
S
T
E
R
E
D
T
O
(
E
)
2
X
1
2
C
.
J
.
#
1
(E
)
2
X
1
2
C
.
J
.
4x6 BLK'G4x6 BLK'G
4x6 BLK'G4x6 BLK'G
8
4 JOIST REINFORCEMENT
ME
C
H
.
U
N
I
T
AT
T
A
C
H
E
M
E
N
T
:
21
5
W
.
4
t
h
.
S
t
.
Sa
n
t
a
A
n
a
,
C
A
9
2
7
0
1
Sheet #
Sheet title
Date :
Project #:
Phase:
10-10-2024
24-186
2nd submittal
#Date
Revisions:
1
2
3
4
St
r
u
c
t
u
r
a
l
E
n
g
i
n
e
e
r
i
n
g
+
D
e
s
i
g
n
5
Roof Framing Plan
S-2.2
ESR-4108
215 W 4th St
1/22/2025
E-3
21
5
W
.
4
T
H
S
T
,
S
A
N
T
A
A
N
A
,
C
A
9
2
7
0
1
215 W 4th St
1/22/2025
E/NITEM #QTY.EQUIPMENT MANUFACTURE MODEL #
EQUIPMENT SCHEDULE
EQUIPMENT
DIMENSION
3 N LOT 5 TIER STORAGE SHELVING 1848NSMETRO 18"WX48"L
7
9
8
N 1 MOP BASIN SINK SE18181PGSW 18"LX18"WX13"H
N 1 CHEMICAL SHELF WS-W1224GSW PER PLAN
N 1 MOP & BROOM HOLDER 2-223 X 24BOBRICK 24"L
2 N 2 EMPLOYEE LOCKER 6 TIERGLOBAL
13
11
12
N 1 WAREWASH 3 COMP. SINK SH24243DGSW 120"LX30"DX45"H
N 1 PRE RINSE W/ FAUCET AA-984GGSW 12" NPT FEMALE INLETS
N 1 OVERHEAD DOUBLE SHELF GSW PER PLANPER PLAN
23 N 3 STAINLESS STEEL PREP TABLE WT-EE3060GSW 30"LX60"WX35"H
21
22
20
N 3 SURFACED MOUNTED SOAP DISPENSER B-2111BOBRICK 4"WX3"DX8"H
N 3 SURFACE MOUNTED TOWEL DISPENSER B-262BOBRICK 10"WX3"DX14"H
N 3 HAND SINK W/ SPLASH GUARDS HS-0810SGSW 12"WX12"DW12"H
10 N 1 VEGETABLE PREPARATION SINK SE18181LGSW 39"LX24"DX36"H
1 N 1 AIR CURTAIN LPV242-1UMARS 42"L
6 N 1 WATER HEATER U-75T-80R-3NBRADFORD WHITE
27.1 N 2 STAINLESS STEEL PREP TABLE WT-E7230GSW 30"LX72"WX35"H
33 N 2 POS OWNER --
4 N 1 3 DOOR REACH IN FREEZER AVANTCO SS-3F-HC 815 16"WX32"DX82"H
5 N 1 WASHER AND DRYER COMBO LG WM6998HBA 27’’W x 39”H x 33 1/8’’D
76/80 GAL
14 N 1 GREASE TRAP 35 GALENDURA
15.1 N 1 WATER FILTER 175/16 REVERSEPENTAIR BWS 15 5
8 "D X 23 3
16 "H
15 N 1 FILTERED WATER FAUCET DELFIELD 12"LX12"DX9.5"H307
15.2 N 1 S/S CABINET CTD-2436HGSW 24"D X 36"W X 35"H
28 N 1 TYPE I EXHAUST HOOD #1 CAPTIVE AIR 10'-6" X 4'-6"
29 N 1 TYPE I EXHAUST HOOD #1 CAPTIVE AIR 8'-6" X 4'-6"
16 N 1 TYPE I EXHAUST HOOD #1 CAPTIVE AIR 7'-6" X5'-0"
N 4 STOCK POT RANGE CPG-SP-18-NCPG 18"WX25"DX22"H17
18 N 2 STAINLESS STEEL PREP TABLE WT-E8430GSW 30"LX84"WX35"H
19 N LOT 5 TIER STORAGE SHELVING 1836NSMETRO 18"WX36"L
24 N 2 DOUGH MIXER 30QT 16"Ø BOWL D330HOBART 24"LX23"DX52"H
25 N 2 DOUGH MIXER 30QT 16"Ø BOWL D300HOBART 21"LX20"DX45"H
26 N 1 3 DOOR REACH IN REFRIGERATOR AVANTCO SS-3R-HC 815 16"WX32"DX82"H
27 N 4 FRYERS CASTLE 2932 SF 32"WX28.5"DX20"H
30 N 1 STAINLESS STEEL PREP TABLE CUSTOMGSW -
32 N 1 2 DOOR U/C REFRIGERATOR TRUE TUC-60-32-HC 60"WX32"DX29"H
31 N 1 2 DOOR U/C FREEZER TRUE TUC-60-32F-HC 60"WX32"DX29"H
ELECTRICAL
NSF ULCOMMENT
AMPVOLT
115/60/1 2.4 A
- -
SELF CONTAINED115/60/1 6.9 A
120/60/1 12 A
10 GAL TANK
208/60/1 14 A
115/60/1 10.2 A
SELF CONTAINED115/60/1 3.37 A
SELF CONTAINED115/60/1 1.7 A
SELF CONTAINED115/60/1 5.8 A
3P
200A
M
A
EXISTING "MS"
(E)
120/208V, 3Ø,4W
SINGLE LINE DIAGRAM
(E)
(E)
REVISIONS
J
S
E
N
G
I
N
E
E
R
I
N
G
,
I
N
C
.
STAMP
E-1
21
5
W
.
4
T
H
S
T
,
S
A
N
T
A
A
N
A
,
C
A
9
2
7
0
1
TE
N
A
N
T
I
M
P
R
O
V
E
M
E
N
T
-
D
O
N
C
H
U
R
R
O
S
215 W 4th St
1/22/2025
18x48
5-tier
18x48
5-tier
18x36
5-tier
18x48
5-tier
18x48
5-tier
18x48
5-tier
18x48
5-tier
18x48
5-tier
1
22
3
4569
8 7
10
14
1312
11
3
18
31922
20 21
15
24
17
2525
20
22 21
232326
18
29
27272727
30
31 33
33
3 3
24
23 15.1
15.2171717
20
22 21
32
28
33
16
27.127.1
+/- 10'-0"H TO
(N) HARD CEILING
(N) 10'-6"X4'-6" TYPE I
EXHAUST HOOD #1
(N) 8'-0"X4'-6" TYPE I
EXHAUST HOOD #2+/- 11'-0"H TO
HARD CEILING
2X4 CLNG JOIST
EVERY 16" O.C.
2X LEDGER
+/- 10'-0"H TO
(N) HARD CEILING
2X LEDGER
2X4 CLNG JOIST
EVERY 16" O.C.
2X4 CLNG JOIST
EVERY 16" O.C.
2X4 CLNG JOIST
EVERY 16" O.C.
(N) 7'-8"X5'-0" TYPE I
EXHAUST HOOD #3
+/- 16'-0"H
OPEN CEILING
+/- 16'-0"H
OPEN CEILING
TV TV TV TV
+/- 14'-0"H
HARD CEILING
ON EXISTING C.J.
+/- 14'-0"H
HARD CEILING
ON EXISTING C.J.
LIGHTING PLAN
1/4"=1'-0"
POWER PLAN
1/4"=1'-0"
+/- 14'-0"H
HARD CEILING
ON EXISTING C.J.
TV TV TV TV
ROOF PLAN
1/4"=1'-0"
S
S
S
REVISIONS
J
S
E
N
G
I
N
E
E
R
I
N
G
,
I
N
C
.
STAMP
E-2
21
5
W
.
4
T
H
S
T
,
S
A
N
T
A
A
N
A
,
C
A
9
2
7
0
1
TE
N
A
N
T
I
M
P
R
O
V
E
M
E
N
T
-
D
O
N
C
H
U
R
R
O
S
215 W 4th St
1/22/2025
M-0.1
THIS DRAWING, SPECIFICATIONS AND
IDEAS, DESIGNS THEREBY ARE AND SHALL
REMAIN THE PROPERTY OF IG DRAFTING &
DESIGN AND NO PART THEREOF SHALL BE
COPIED DISCLOSED TO OTHERS OR USED
IN CONNECTION WITH ANY WORK OR
PROJECT FOR WHICH THERE HAVE BEEN
PREPARED AND DEVELOPED, WITHOUT THE
WRITTEN CONSENT OF IG DRAFTING &
DESIGN, VISUAL CONTACT WITH THESE
DRAWINGS SHALL CONSTITUTE EVIDENCE
OF ACCEPTANCE OF THESE RESTRICTIONS.
DO
N
C
H
U
R
R
O
S
1
2
3
4REFERENCE CODES:
2022 CALIFORNIA BUILDING CODE
2022 CALIFORNIA MECHANICAL CODE
2022 CALIFORNIA PLUMBING CODE
2022 CALIFORNIA ELECTRICAL CODE
2022 CALIFORNIA TITLE-24 ENERGY CODE
2022 CALIFORNIA FIRE CODE
2022 CALIFORNIA GREEN BUILDING STANDARDS
2023 CITY OF SANTA ANA AMENDMENTS
CODES
215 W 4th St
1/22/2025
TOP OF
THERMOSTAT
24" MAX
FINISHED
FLOOR
OVER
OBSTRUCTION
FINISHED
FLOOR
MOUNT HEIGHT
TOP OF
THERMOSTAT
34
"
M
A
X
48
"
M
A
X
48
"
M
A
X
36
"
M
I
N
USE 3 8" LAG PER SUPPORT LOCATION
W/ 3" EMBED. INTO 4x MEMBER
NEW ROOF EQUIPMENT
4x8 W/ A35 @ EA.
SIDE
PENETRATION SEAL BY
ROOF MANUFACTURER
EXTENSION BAR AND ANCHOR
BY ROOF MANUFACTURER
GALVANIZED SHEET
METAL COVER
SEAL STRIP
EXISTING TRUSSES
EXISTING ROOF
SHEATHING
2x BLK'G
4x8 @24" O.C.
DEMOLITION / ALTERATION NOTES
1. IT SHALL BE THE CONTRACTORS RESPONSIBILITY TO VISIT THE EXISTING PROJECT SITE, ACQUAINT HIMSELF WITH
ALL EXISTING CONDITIONS, AND ASCERTAIN THE EXTENT OF WORK INVOLVED IN REMOVING EXISTING EQUIPMENT AND
INSTALLING NEW EQUIPMENT, DUCTWORK AIR DISTRIBUTION DEVICES, PIPING CONTROLS, AND ALL OTHER
APPURTENANCES PERTAINING TO THE ABOVE. HE SHALL PROVIDE ALL LABOR, MATERIALS, ETC. REQUIRED FOR THE
COMPLETE NEW INSTALLATION, ALTERATIONS, ETC. FOR THE COMPLETION OF THE PROJECT. BY THE ACT OF
SUBMITTING A BID,
THE CONTRACTOR SHALL BE DEEMED TO HAVE MADE SUCH AN EXAMINATION TO HAVE ACCEPTED SUCH CONDITIONS,
AND TO HAVE MADE ALLOWANCES THEREFORE IN PREPARING HIS FIGURE.
2. WHERE INDICATED ON THE DRAWINGS, THE CONTRACTOR SHALL DISCONNECT THE EXISTING EQUIPMENT NOT TO BE
USED FOR THE REHABILITATION OF THIS PROJECT INCLUDING HEATING UNITS, VENTS, CONTROLS, PIPING, CONDUITS
SUPPORTS ETC. PREPARING THE EXISTING ABOVE EQUIPMENT FOR REMOVAL.
3. ALL MATERIALS, EQUIPMENT, PIPING, DUCTWORK, ETC., WHICH ARE TO BE REMOVED, SHALL BECOME THE PROPERTY
OF THE CONTRACTOR, UNLESS INDICATED OTHERWISE AND SHALL BE REMOVED FROM THE SITE. WHERE SUCH
MATERIALS, EQUIPMENT, ETC., ARE TO BE REMOVED, IT SHALL BE REMOVED, IT ITS ENTIRETY, FROM THE PREMISES,
AND CARE TAKEN TO ENSURE THAT NO OPEN ENDS EXIST IN PIPING, DUCTWORK, ETC., WHICH REMAIN IN PLACE OR IN
SERVICE. BLANKED OR OTHER APPROVED MEANS OF CLOSURE METHOD.
4. THE DRAWINGS ARE DIAGRAMMATIC ONLY, DO NOT SCALE THE DRAWINGS TO DETERMINE THE LOCATIONS OF
EQUIPMENT, DUCTS, OR PIPING. LOCATIONS OF EXISTING EQUIPMENT, DUCTS, PIPES, ETC., ARE APPROXIMATE AND ARE
INDICATED FOR REFERENCE ONLY. EXACT LOCATIONS AND SIZES SHALL BE VERIFIED IN THE FIELD.
5. THE EXISTING CONDITIONS SHOWN ARE FROM AVAILABLE RECORD DRAWINGS AND SHOWN FOR REFERENCE ONLY.
CONTRACTOR SHALL VERIFY ACTUAL EXISTING CONDITIONS AT SITE PRIOR TO SUBMITTING THE BID. ALL DEMOLITION,
ALTERNATION, EXTENSION, RELOCATION, REHABILITATION WORK SHALL BE INCLUDED IN BASE CONTRACT. NO
ADDITIONAL ALLOWANCE OR CHANGE ORDERS WILL BE ACCEPTED.
6. CONTRACTOR IS RESPONSIBLE TO RELOCATE OR REMOVE FROM WALLS, CEILINGS, FLOOR SPACE, ETC. ANY EXISTING
DUCTS, GRILLS, EQUIPMENT, PIPING, OR OTHER EQUIPMENT WHICH INTERFERES WITH PLANNED REMODEL WORK.
7. NOTIFY THE ENGINEER IMMEDIATELY WHEREVER EXISTING EQUIPMENT IS ENCOUNTERED WHICH MUST BE
RELOCATED DUE TO THE NEW CONSTRUCTION, OR NOT INDICATED ON "AS-BUILT" DRAWINGS OR WAS BURIED
UNDERGROUND OR EMBEDDED IN STRUCTURAL WALLS.
8. CAREFULLY PROTECT ALL WALLS, TRIM, FLOORS, EQUIPMENT, UTILITY LINES, AND MATERIALS. WHEN WORKING ON
FINISHED SURFACES, LIMIT DAMAGE TO THE SMALLER AREA IF POSSIBLE AND RESTORE TO THE ORIGINAL CONDITION
ALL SURFACES WHICH ARE DAMAGED BECAUSE OF THE INSTALLATION OF THIS WORK.
9. EQUIPMENT, MATERIALS AND SUPPLIES TEMPORARILY REMOVED FOR PROTECT ION SHALL BE REPLACED IN
ORIGINAL LOCATIONS. ANY MATERIALS DAMAGED SHALL BE REPLACED WITH NEW MATERIALS OF LIKE KIND AND
QUALITY.
10. DEMOLITION WORK SHALL BE DONE IN A MANNER WHICH W ILL NOT CAUSE UNNECESSARY INCONVENIENCE OR
DANGER TO USERS OF THE PREMISES AND ADJACENT SITE, AND NOT INTERFERE WITH ITS OPERATION. ANY DEMOLITION
WORK TO BE PERFORMED MUST BE PLANNED IN ADVANCE. ALL DEBRIS SHALL BE DISPOSED OF IN AN APPROVED
MANNER.
11. DO ALL DRILLING, CUTTING, ETC REQUIRED TO DEMOLISH WORK AS INDICATED OR PROVIDE BLANK COVER PLATE
ON ALL OUTLETS EXPOSED BY REMOVAL OF FIXTURE OR DEVICE.
12. RESEAL ALL PENETRATIONS OR OPENINGS THROUGH WALLS, CEILINGS, FLOORS, ETC., TO MAINTAIN THE RATING OF
THE STRUCTURE.
13. ALL REMOVED MATERIALS AND EQUIPMENT WHICH ARE SALVAGED MATERIALS SHALL REMAIN IN THE PROPERTY OF
THE OWNER. DELIVER SUCH SALVAGED MATERIALS AND EQUIPMENT ON THE PREMISES AS DIRECTED BY THE OWNER
AND NEATLY PILE OR STORE THEM AND PROTECT FROM DAMAGE. DISPOSE OF ALL HAZARDOUS MATERIALS PER
GUIDELINES OF THE STATE OF CALIFORNIA,
DEPARTMENT OF HEALTH SERVICES AND OTHER AGENCIES HAVING JURISDICTION.
14. CONTRACTOR SHALL FIELD VERIFY EXISTING EQUIPMENT, DUCTS, PIPES, REGISTERS, ETC., AS REQUIRED AND
REMOVED ALL MARKED TO BE DEMOLISHED IN A NEAT AND ORDERLY MANNER AND CAP AT NEAREST ACTIVE TEE.
15. SCHEDULE AND COORDINATE INSTALLATION AND DEMOLITION WORK WITH OWNERS REPRESENTATIVE TO MEET
REQUIRED PHASING OF THE PROJECT.
KITCHEN HOOD NOTES
1.
a.ALL WORK SHALL COMPLY WITH STATE AND LOCAL CODES. A FIRE EXTINGUISHING SYSTEM IS
REQUIRED PER SECTION 513 CMC. HOOD SYSTEM MUST HAVE FIRE DEPARTMENT APPROVAL.
HOOD MUST HAVE A MINIMUM CLEARANCE OF 18” FROM COMBUSTIBLES OR A MINIMUM OF 3”
FROM PROTECTED COMBUSTABLES. ROOF BLOWERS MUST BE A MINIMUM OF 10’ FROM AIR
CONDITIONERS, EVAP. COOLERS, AND/OR ADJACENT PROPERTY LINES THE BOTTOM OF THE
EXHAUST OUTLET SHALL BE A MINIMUM OF 24” ABOVE THE ROOF. IF A SCOOP IS INSTALLED ON
THE DISCHARGE SIDE OF A CENTRIFUGAL FAN.
b. THE DUCT SHALL BE CONSTRUCTED OF METAL IN COMPLIANCE WITH CHAPTER 5 OF
CMC 2022.
c.THE DUCT SHALL HAVE ADEQUATE OPENINGS AT THE LOWEST POINT TO PERMIT DRAINAGE OF
GREASE TO A SUITABLE COLLECTION DEVICE.
d.THE DISTANCE FROM THE BOTTOM OF THE CEILING TO THE TOP OF THE HOOD IS TO BE A 3”
MINIMUM. IF DISTANCE IS LESS THAN 18” EXTEND A SOLID FIRE RATED CEILING (TYPE X GYP BD
OR PLASTER) 18” BEYOND OUTER EDGES OF HOOD
e.WEATHER PROTECTION FOR OPENINGS TO BE A MINIMUM 26 GA. GALV. METAL SHIELD. ( OR
COLLAR ) TO SEAL DUCT AT POINT OF PENETRATION OF CEILING AND/OR WALLS
f.ALL CANOPY TYPE HOODS SHALL OVERHANG A MINIMUM OF 6” BEYOND THE COOKING
SURFACE ON ALL SIDES.
g.THE EXHAUST AND MAKE-UP AIR SYSTEMS SHALL BE CONNECTED BY AN INTERLOCKING
SWITCH THE FIRE EXTINGUISHING SYSTEM SHALL BE INTERCONNECTED TO THE FUEL AND/OR
THE CURRENT SUPPLY SHALL BE AUTOMATICALLY SHUT OFF WHEN FIRE EXTINGUISHING
SYSTEM IS ACTIVATED.
h.FIRE DEPARTMENT APPROVAL ON FIRE PROTECTION SYSTEMS FOR GREASE HOODS AND
DUCTS ARE REQUIRED BY SECTION 513 CMC OF THE MECHANICAL CODE AND IS REQUIRED BY
FIRE CODE.
i.ALL FIRE-EXTINGUISHING SYSTEMS SHALL BE INTERCONNECTED TO THE FUEL OR CURRENT
SUPPLY SO THAT THE FUEL OR CURRENT IS AUTOMATICALLY SHUT OFF TO ALL EQUIPMENT
UNDER THE HOOD WHEN THE SYSTEM IS ACTIVATED.
j.ALL SEAMS, JOINTS, AND PENETRATIONS OF THE HOOD ENCLOSURE THAT DIRECT & CAPTURE
GREASE-LADEN VAPORS & EXHAUST GASES SHALL HAVE A LIQUID TIGHT CONTINUOUS
EXTERNAL WELD TO THE LOWER OUTERMOST PERIMETER OF THE HOOD.
2.QUANTITY AND SIZE OF LISTED GREASE FILTERS TESTED IN ACCORDANCE WITH UL1046.
3.DUCT ENCLOSURE SHALL BE VENTILATED TO THE EXTERIOR THROUGH WEATHER PROTECTED
OPENINGS.
4.ALL CANOPY TYPE HOODS SHALL OVERHANG A MINIMUM OF 6” BEYOND THE COOKING SURFACE
ON ALL OPENING SIDES. EXCEPTION: LISTED EXHAUST HOODS IF NOTED AS PART OF THEIR
LISTING.
5.THE DISTANCE BETWEEN THE LOWEST EDGE OF GREASE REMOVAL DEVICE AND THE COOKING
SURFACE SHALL NOT BE LESS THAN 18”. GREASE REMOVAL DEVICES SERVING CHARBROILERS
SHALL HAVE A MINIMUM VERTICAL DISTANCE OF FOUR(4) FEET. EXCEPTION: GREASE
REMOVAL DEVICES SUPPLIED AS PART OF LISTED HOOD ASSEMBLIES INSTALLED IN
ACCORDANCE WITH THE TERMS OF THE LISTING AND MANUFACTURER INSTALLATION
INSTRUCTIONS.
6.FILTERS SHALL BE INSTALLED AT AN ANGLE NOT LESS THAN 45 FROM THE HORIZONTAL
7.DUCT AIR VELOCITY SHALL BE SUFFICIENT FOR CAPTURE AND REMOVAL OF GREASE-LADEN
COOKING VAPORS, THE AIR VELOCITY THROUGH ANY DUCT SHALL BE NOT LESS THAN 500 FPM
AND NOT MORE THAN 2500 FEET PER MINUTE.
8.THE OWNER OF ESTABLISHMENT SHALL BE RESPONSIBLE FOR CLEANLINESS, MAINTENANCE &
INSPECTION OF KITCHEN EXHAUST SYSTEM, FIRE PROTECTION, COOKING EQUIPMENT
9.A DRAWING OF THE EXHAUST SYSTEM(S) INSTALLATION ALONG WITH A COPY OF OPERATION
INSTRUCTIONS FOR SUBASSEMBLIES & COMPONENTS USED IN THE EXHAUST SYSTEM(S)
INCLUDING ELECTRICAL SCHEMATICS, SHALL BE AVAILABLE ON THE PREMISES.
10.HOOD EXHAUST FAN SHALL CONTINUE TO OPERATE AFTER THE EXTINGUISHING SYSTEM HAS
BEEN ACTIVATED UNLESS FAN SHUT DOWN IS REQUIRED BY A LISTED COMPONENT OF THE
VENTILATION SYSTEM.
11.THE HOOD, DUCT AND EXHAUST OUTLET SHALL BE INSTALLED IN ACCORDANCE WITH CHAPTER
5 & 6 OF CURRENT EDITION OF C.M.C AS ADOPTED BY THE LOCAL BUILDING & SAFETY
DEPARTMENT.
12.EXPOSED DUCT SYSTEMS SHALL HAVE A CLEARANCE OF AT LEAST 18" FROM UNPROTECTED
COMBUSTIBLE CONSTRUCTION, PER C.M.C 2022 SECTION 507.4.
13.HOOD EXH.(GEASE)DUCTS SHALL BE MIN. 16 GAUGE GALV. STEEL (OR 18 GUAGE STAINLESS
STEEL) WELDED AIR TIGHT@EXTERIOR SEAMS.
14.SLOPE ALL GREASE DUCTS@ MINIMUM 14" PER FT. (2%)TOWARDS HOOD.
15.PROVIDE UL 300 FIRE PROTECTION SYSTEM.
16.THE EXHAUST AND MAKEUP AIR SYSTEMS SHALL BE CONNECTED BY AN ELECTRICAL
INTERLOCKING SWITCH.
17.DUCTS AT EXTERIOR LOCATION SHALL BE PROTECTED ON EXTERIOR BY PAINT OR OTHER
SUITABLE WEATHER-PROTECTIVE COATING OR BE CONSTRUCTED OF STAINLESS STEEL.
18.DUCT SYSTEM SHOULD BE INSTALLED SO GREASE CANNOT BE POCKETED. THE SYSTEM SHALL
SLOPE NOT LESS THAN 14" PER FOOT TOWARD THE HOOD OR TOWARD THE GREASE RESERVOIR.
(WHERE HORIZONTAL DUCTS EXCEED 75' IN LENGTH THE SLOPE SHALL BE MINIMUM
19.GENERAL SPECIFICATIONS IN LIEU OF THE ACTUAL SECTIONAL ELEVATION VIEWS ARE NOT
ACCEPTABLE.
20.THE DUCT ENCLOSURE SHALL BE SEALED AROUND THE DUCT AT THE POINT OF PENETRATION.
(CMC 510.7)
21.THE FIRE EXTINGUISHING SYSTEM SHALL BE INTERCONNECTED TO THE FUEL OR CURRENT
SUPPLY SO THAT THE FUEL OR CURRENT IS AUTOMATICALLY SHUT OFF TO ALL EQUIPMENT
UNDER THE HOOD WHEN THE SYSTEM IS ACTUATED. (LAMC 513.4)
24.THE FIRE-EXTINGUISHED SYSTEM SHALL BE INTERCONNECTED TO THE FUEL OR CURRENT
SUPPLY SO THAT THE FUEL OR CURRENT IS AUTOMATICALLY SHUT OFF TO ALL EQUIPMENT
UNDER THE HOOD WHEN THE SYSTEM IS ACTUATED.
25.EXPOSED GREASE HOOD SYSTEMS SERVING A TYPE -I HOOD SHALL HAVE A CLEARANCE FROM
UNPROTECTED COMBUSTIBLE CONSTRUCTION AT LEAST 18 INCHES. CLEARANCE MAY BE
REDUCED TO NOT LESS THAN 3 INCHES WHEN THE COMBUSTIBLE CONSTRUCTION IS
PROTECTED WITH MATERIAL REQUIRED FOR ONE- HOUR FIRE-RESISTIVE CONSTRUCTION.
26.ACCESS OPENINGS FOR CLEANING, MAINTENANCE, AND INSPECTION SHALL BE PROVIDED IN
ACCORDANCE WITH CMC 510.3
27.A CERTIFIED AIR BALANCE REPORT, INCLUDING OUTSIDE AIR VENTILATION, WILL BE PROVIDED
TO THE INSPECTOR AT THE TIME OF INSPECTION SHOWING COMPLIANCE WITH THE DESIGN
VALUES.
28.AT THE TIME OF ROUGH INSTALLATION ALL DUCT AND OTHER RELATED AIR DISTRIBUTION
COMPONENT OPENINGS SHALL BE COVERED TO REDUCE THE AMOUNT OF DUST OR DEBRIS
WHICH MAY COLLECT IN THE SYSTEM.
29.CONDENSATE DRAINS SHALL CONNECT INDIRECTLY TO THE DRAINAGE SYSTEM THROUGH AN
AIR GAP OR AIR BREAK TO PROPERLY TRAPPED AND VENTED RECEPTORS, DRY WELLS, LEACH
PITS, OR THE TAILPIECE OF PLUMBING FIXTURES.
M-0.2
THIS DRAWING, SPECIFICATIONS AND
IDEAS, DESIGNS THEREBY ARE AND SHALL
REMAIN THE PROPERTY OF IG DRAFTING &
DESIGN AND NO PART THEREOF SHALL BE
COPIED DISCLOSED TO OTHERS OR USED
IN CONNECTION WITH ANY WORK OR
PROJECT FOR WHICH THERE HAVE BEEN
PREPARED AND DEVELOPED, WITHOUT THE
WRITTEN CONSENT OF IG DRAFTING &
DESIGN, VISUAL CONTACT WITH THESE
DRAWINGS SHALL CONSTITUTE EVIDENCE
OF ACCEPTANCE OF THESE RESTRICTIONS.
DO
N
C
H
U
R
R
O
S
1
2
3
4
215 W 4th St
1/22/2025
3'-11"
3'
-
8
"
Scale: 1/4"=1'-0"
HVAC PLAN1
3'-11"
3'
-
8
"
Scale: 1/4"=1'-0"
HOOD PLAN 2
BDD
AIR BALANCE SCHEDULE
1- SUPPLY AIR (A/C)
·(N)AC-1 UNIT (O.S.A) 900 (CFM)
TOTAL O.S.A 900 (CFM)
2- SUPPLY (MAKE-UP AIR) 5,516 (CFM)
3- TOTAL SUPPLY TO SPACE 6416 (CFM)
4- EXHAUST AIR
·KITCHEN HOOD #1 3000 (CFM)
·KITCHEN HOOD #2 1800 (CFM)
·KITCHEN HOOD #2 1533 (CFM)
·TOILETS EXH. 50 (CFM)
TOTAL EXH. 6383 (CFM)
TENANT SPACE AIR BALANCE:
6416 CFM(+VE) - 6383 CFM(-VE)= 33(CFM) +VE) FOR
NET EXFILTRATION
AIR BALANCE REPORT
AN AIR BALANCE REPORT BY A QUALIFIED "NEBB" OR
"AABC" CONTRACTOR SHALL BE PROVIDED TO THE
BUILDING DIVISION FOR HVAC SYSTEMS PERFORMANCE
TOGETHER. WITH COMPLETED TITLE-24 TESTING AND
DOCUMENTATION FORMS (MECH-2-A), (MECH-3-A) AND
(MECH-4-A) ATTACHED FOR REVIEW AND ACCEPTANCE
PRIOR TO FINAL INSPECTION OR OCCUPANCY
(C.G.B. C.S. 5. 410.4.3.1, CMC 407.3 & 511.3).
T
MVD MVD MVD
10"Ø 10"Ø 12"Ø 8"Ø
8"
Ø
10"Ø12"Ø
8"Ø
12"Ø
MVD MVD
MVD MVD
MVD
MVD
MVD
MVD
8"Ø 8"Ø 10"Ø
8"Ø 8"Ø 8"Ø
10
"
Ø
MINIMUM VENTILATION RATES IN BREATHING ZONE TABLE 402.1 - 403.2.2 ASHRE 62.1: TABLE 6.2.2.1) (6.2.2.2)
1'-8"
1'
-
0
"
1'-8"
1'
-
0
"
2'-4"
1'
-
0
"
2'-4"
1'
-
0
"
2'-4"2'-4"2'-4"
HOOD #1 CALCULATIONS
HOOD SIZE : ............................................. 10'-6" X 4'-6"
TOTAL CFM : ............................................. 3,000 CFM
DUCT SIZE:............................................. 12"X22"
VELOCITY: .....................3000 / 1.83 = 1,636 FPM
VELOCITY PRESSURE (Pv) (1636
4005)² = 0.16 "W.C.
FITTING LOSS = Σ CxPv = 2.5 X0.16= 0.4 "W.C.
DUCT LOSS ................= 50'X0.18/100= 0.1 "W.C.
HOOD & FILTER LOSS (MANUFAC.)= 1.013 "W.C.
TOTAL LOSSES..........0.4+0.1+1.013 = 1.513 "W.C.
REQUIRED FAN CAPACITY
MINIMUM FAN CAPACITY SHALL BE
3000 CFM @ 1.513 (" W.C.) E.S.P.
PROVIDED
3000 CFM @ 1.6 (" W.C.) E.S.P.
HOOD #2 CALCULATIONS
HOOD SIZE : ............................................. 8'-0" X 4'-6"
TOTAL CFM : ............................................. 1,800 CFM
DUCT SIZE:............................................. 10"X16"
VELOCITY: .....................1800 / 1.11 = 1,620 FPM
VELOCITY PRESSURE (Pv) (1620
4005)² = 0.16 "W.C.
FITTING LOSS = Σ CxPv = 2.0 X0.16= 0.3 "W.C.
DUCT LOSS ................= 50'X0.18/100= 0.1 "W.C.
HOOD & FILTER LOSS (MANUFAC.)= 0.66 "W.C.
TOTAL LOSSES..........0.3 + 0.1 + 0.66 = 1.0 "W.C.
REQUIRED FAN CAPACITY
MINIMUM FAN CAPACITY SHALL BE
1800 CFM @ 1.0 (" W.C.) E.S.P.
PROVIDED
1800 CFM @ 1.0 (" W.C.) E.S.P.
HOOD #3 CALCULATIONS
HOOD SIZE : ............................................. 8'-0" X 4'-6"
TOTAL CFM : ............................................. 1,533 CFM
DUCT SIZE:............................................. 12"X12"
VELOCITY: .....................1533 / 1 = 1,533 FPM
VELOCITY PRESSURE (Pv) (1533
4005)² = 0.14 "W.C.
FITTING LOSS = Σ CxPv = 2.0 X0.14= 0.28 "W.C.
DUCT LOSS ................= 50'X0.18/100= 0.1 "W.C.
HOOD & FILTER LOSS (MANUFAC.)= 0.596 "W.C.
TOTAL LOSSES.......0.28 + 0.1 + 0.596 = 0.976 "W.C.
REQUIRED FAN CAPACITY
MINIMUM FAN CAPACITY SHALL BE
1533 CFM @ 0.976 (" W.C.) E.S.P.
PROVIDED
1533 CFM @ 1.0 (" W.C.) E.S.P.
M-1.0
THIS DRAWING, SPECIFICATIONS AND
IDEAS, DESIGNS THEREBY ARE AND SHALL
REMAIN THE PROPERTY OF IG DRAFTING &
DESIGN AND NO PART THEREOF SHALL BE
COPIED DISCLOSED TO OTHERS OR USED
IN CONNECTION WITH ANY WORK OR
PROJECT FOR WHICH THERE HAVE BEEN
PREPARED AND DEVELOPED, WITHOUT THE
WRITTEN CONSENT OF IG DRAFTING &
DESIGN, VISUAL CONTACT WITH THESE
DRAWINGS SHALL CONSTITUTE EVIDENCE
OF ACCEPTANCE OF THESE RESTRICTIONS.
DO
N
C
H
U
R
R
O
S
1
2
3
4
3
3
3
215 W 4th St
1/22/2025
TOILET EXHAUST FAN SCHEDULE
SYMB AREA
SERVING MANUF.MODEL TYPE CFM
TOTAL
STATIC
(IN WC)
RPM ELECTRICAL
VOLT PH AMPS
OPERATION
WEIGHT
(LB)
REMARKS
RESTROOM GREENHECK SP-A50 CEILING
MOUNT 50 0.33 1100 120 1 .6 35 PROVIDE BACKDRAFT DAMPER,
FAN SHALL BE INTERLOCKED WITH LIGHT SWITCH
QTY.
1
(N)5 TON
10
'
-
0
"
M
I
N
3'
-
0
"
3'
-
3
"
655 LBS
692 LBS
403 LBS 296 LBS
238 LBS
REPLACED W/ NEW ELECTRIC PACKAGED ROOFTOP UNIT SCHEDULE
SYMB MAKE
GOODMAN
MODEL
GPGM560
08041AA
TONS
5
CFM
NOM.
2000
ESP
(IN)
0.4"
OUTSIDE AIR
(CFM)
900 58.0
HEATING (MBH)
80
INBUT (KBH)OUTPUT (KBH)
63
ELECTRICAL
208/230
VOLTAGE
1
PHASE
35.5
TOT. AMPS
43.3
AMPS
MCA
70
AMPS
FUSE
SEER
EER
14.2
10.1
OPERATION
WEIGHT
(LB)
655
DUCT CONNECTIONS
MANUFAC.
SUPPLY RETURN
REMARKS
PROVIDE SMOKE DETECTOR IN SUPPLY DUCT & POWER
EXH. ECONOMIZER. SET MIN. O.S.A @ 900 CFM
AFUE %
81
TOTAL COOL'G
(KBH)
MANUFAC.
N/E
N
N
N
N
N/E
N
N/E
N
N/E
Scale: 1/4"=1'-0"
ROOF PLAN 1
10'-0
"
M
I
N
M-1.1
THIS DRAWING, SPECIFICATIONS AND
IDEAS, DESIGNS THEREBY ARE AND SHALL
REMAIN THE PROPERTY OF IG DRAFTING &
DESIGN AND NO PART THEREOF SHALL BE
COPIED DISCLOSED TO OTHERS OR USED
IN CONNECTION WITH ANY WORK OR
PROJECT FOR WHICH THERE HAVE BEEN
PREPARED AND DEVELOPED, WITHOUT THE
WRITTEN CONSENT OF IG DRAFTING &
DESIGN, VISUAL CONTACT WITH THESE
DRAWINGS SHALL CONSTITUTE EVIDENCE
OF ACCEPTANCE OF THESE RESTRICTIONS.
DO
N
C
H
U
R
R
O
S
1
2
3
4
3
215 W 4th St
1/22/2025
#1 #2
(N) 10'-9"X4'-6" TYPE I
EXHAUST HOOD #1
FRYER FRYER FRYER FRYERSTAINLESS STEEL PREP TABLE
S/S SKIRT
6" COVEBASE
W/ 3/8" R
6" COVEBASE
W/ 3/8" R
(N) 8'-0"X4'-6" TYPE I
EXHAUST HOOD #2
48
"
M
A
X
6'
-
8
"
48
"
M
A
X
6" MIN6" MIN 11
'
-
0
"
(N) 7'-8"X5'-0" TYPE I
EXHAUST HOOD #3
6'
-
8
"
12
'
-
0
"
ALL HOODS SHALL BE
FLASHED TO THE CEILING
S/S SKIRT
6"6"
48
"
M
A
X
6"6"
M-1.2
THIS DRAWING, SPECIFICATIONS AND
IDEAS, DESIGNS THEREBY ARE AND SHALL
REMAIN THE PROPERTY OF IG DRAFTING &
DESIGN AND NO PART THEREOF SHALL BE
COPIED DISCLOSED TO OTHERS OR USED
IN CONNECTION WITH ANY WORK OR
PROJECT FOR WHICH THERE HAVE BEEN
PREPARED AND DEVELOPED, WITHOUT THE
WRITTEN CONSENT OF IG DRAFTING &
DESIGN, VISUAL CONTACT WITH THESE
DRAWINGS SHALL CONSTITUTE EVIDENCE
OF ACCEPTANCE OF THESE RESTRICTIONS.
DO
N
C
H
U
R
R
O
S
1
2
3
4
Scale: NTS
HOOD #1 SECTION1 Scale: NTS
HOOD #2 SECTION2
Scale: NTS
HOOD #3 SECTION3
Scale: NTS
HOOD # 1 & 2 ELEVATION4
Scale: NTS
HOOD # 3 ELEVATION5
215 W 4th St
1/22/2025
SHEET NO.
SCALE:
DWG.#:
DRAWN
DATE:
BY:
REVISIONS
ww
w
.
c
a
p
t
i
v
e
a
i
r
e
.
c
o
m
MASTER DRAWING
So
u
t
h
e
r
n
C
a
l
i
f
o
r
n
i
a
O
f
f
i
c
e
30
0
2
D
o
w
A
v
e
.
,
S
u
i
t
e
2
0
2
,
T
u
s
t
i
n
,
C
A
,
9
2
7
8
0
P
H
O
N
E
:
(
7
1
4
)
9
5
7
-
1
5
0
0
F
A
X
:
9
1
9
2
2
7
5
9
7
5
E
M
A
I
L
:
r
e
g
8
6
@
c
a
p
t
i
v
e
a
i
r
e
.
c
o
m
M-2.0
THIS DRAWING, SPECIFICATIONS AND
IDEAS, DESIGNS THEREBY ARE AND SHALL
REMAIN THE PROPERTY OF IG DRAFTING &
DESIGN AND NO PART THEREOF SHALL BE
COPIED DISCLOSED TO OTHERS OR USED
IN CONNECTION WITH ANY WORK OR
PROJECT FOR WHICH THERE HAVE BEEN
PREPARED AND DEVELOPED, WITHOUT THE
WRITTEN CONSENT OF IG DRAFTING &
DESIGN, VISUAL CONTACT WITH THESE
DRAWINGS SHALL CONSTITUTE EVIDENCE
OF ACCEPTANCE OF THESE RESTRICTIONS.
DO
N
C
H
U
R
R
O
S
1
2
3
4
215 W 4th St
1/22/2025
SHEET NO.
SCALE:
DWG.#:
DRAWN
DATE:
BY:
REVISIONS
ww
w
.
c
a
p
t
i
v
e
a
i
r
e
.
c
o
m
MASTER DRAWING
So
u
t
h
e
r
n
C
a
l
i
f
o
r
n
i
a
O
f
f
i
c
e
30
0
2
D
o
w
A
v
e
.
,
S
u
i
t
e
2
0
2
,
T
u
s
t
i
n
,
C
A
,
9
2
7
8
0
P
H
O
N
E
:
(
7
1
4
)
9
5
7
-
1
5
0
0
F
A
X
:
9
1
9
2
2
7
5
9
7
5
E
M
A
I
L
:
r
e
g
8
6
@
c
a
p
t
i
v
e
a
i
r
e
.
c
o
m
M-2.1
THIS DRAWING, SPECIFICATIONS AND
IDEAS, DESIGNS THEREBY ARE AND SHALL
REMAIN THE PROPERTY OF IG DRAFTING &
DESIGN AND NO PART THEREOF SHALL BE
COPIED DISCLOSED TO OTHERS OR USED
IN CONNECTION WITH ANY WORK OR
PROJECT FOR WHICH THERE HAVE BEEN
PREPARED AND DEVELOPED, WITHOUT THE
WRITTEN CONSENT OF IG DRAFTING &
DESIGN, VISUAL CONTACT WITH THESE
DRAWINGS SHALL CONSTITUTE EVIDENCE
OF ACCEPTANCE OF THESE RESTRICTIONS.
DO
N
C
H
U
R
R
O
S
1
2
3
4
215 W 4th St
1/22/2025
SHEET NO.
SCALE:
DWG.#:
DRAWN
DATE:
BY:
REVISIONS
ww
w
.
c
a
p
t
i
v
e
a
i
r
e
.
c
o
m
MASTER DRAWING
So
u
t
h
e
r
n
C
a
l
i
f
o
r
n
i
a
O
f
f
i
c
e
30
0
2
D
o
w
A
v
e
.
,
S
u
i
t
e
2
0
2
,
T
u
s
t
i
n
,
C
A
,
9
2
7
8
0
P
H
O
N
E
:
(
7
1
4
)
9
5
7
-
1
5
0
0
F
A
X
:
9
1
9
2
2
7
5
9
7
5
E
M
A
I
L
:
r
e
g
8
6
@
c
a
p
t
i
v
e
a
i
r
e
.
c
o
m
M-2.2
THIS DRAWING, SPECIFICATIONS AND
IDEAS, DESIGNS THEREBY ARE AND SHALL
REMAIN THE PROPERTY OF IG DRAFTING &
DESIGN AND NO PART THEREOF SHALL BE
COPIED DISCLOSED TO OTHERS OR USED
IN CONNECTION WITH ANY WORK OR
PROJECT FOR WHICH THERE HAVE BEEN
PREPARED AND DEVELOPED, WITHOUT THE
WRITTEN CONSENT OF IG DRAFTING &
DESIGN, VISUAL CONTACT WITH THESE
DRAWINGS SHALL CONSTITUTE EVIDENCE
OF ACCEPTANCE OF THESE RESTRICTIONS.
DO
N
C
H
U
R
R
O
S
1
2
3
4
215 W 4th St
1/22/2025
M-3.0
THIS DRAWING, SPECIFICATIONS AND
IDEAS, DESIGNS THEREBY ARE AND SHALL
REMAIN THE PROPERTY OF IG DRAFTING &
DESIGN AND NO PART THEREOF SHALL BE
COPIED DISCLOSED TO OTHERS OR USED
IN CONNECTION WITH ANY WORK OR
PROJECT FOR WHICH THERE HAVE BEEN
PREPARED AND DEVELOPED, WITHOUT THE
WRITTEN CONSENT OF IG DRAFTING &
DESIGN, VISUAL CONTACT WITH THESE
DRAWINGS SHALL CONSTITUTE EVIDENCE
OF ACCEPTANCE OF THESE RESTRICTIONS.
DO
N
C
H
U
R
R
O
S
1
2
3
4
IMAGINE ARCHITECTURE
STEVEN GARCIA
23448 VANOWEN ST
WEST HILLS CA, 91307
2024-05-16
818-826-1627
MIKE HAJILOO
M27303
MIKE HAJILOO PE
19562 VENTURA BLVD. STE #234
TARZANA, CA 91356 818-826-1627
215 W. 4TH ST, SANTA ANA, CA 92701
215 W. 4TH ST, SANTA ANA, CA 92701
2024-05-16
3
215 W 4th St
1/22/2025
M-3.1
THIS DRAWING, SPECIFICATIONS AND
IDEAS, DESIGNS THEREBY ARE AND SHALL
REMAIN THE PROPERTY OF IG DRAFTING &
DESIGN AND NO PART THEREOF SHALL BE
COPIED DISCLOSED TO OTHERS OR USED
IN CONNECTION WITH ANY WORK OR
PROJECT FOR WHICH THERE HAVE BEEN
PREPARED AND DEVELOPED, WITHOUT THE
WRITTEN CONSENT OF IG DRAFTING &
DESIGN, VISUAL CONTACT WITH THESE
DRAWINGS SHALL CONSTITUTE EVIDENCE
OF ACCEPTANCE OF THESE RESTRICTIONS.
DO
N
C
H
U
R
R
O
S
1
2
3
4
STEVEN GARCIA
23448 VANOWEN ST
WEST HILLS CA, 91307
2024-05-16
818-826-1627
MIKE HAJILOO
M27303
MIKE HAJILOO PE
19562 VENTURA BLVD. STE #234
TARZANA, CA 91356 818-826-1627
215 W. 4TH ST, SANTA ANA, CA 92701
2024-05-16
215 W. 4TH ST, SANTA ANA, CA 92701
3
215 W 4th St
1/22/2025
PLUMBING SPECIFICATIONS:
1.ALL WORK SHALL BE DONE IN ACCORDANCE WITH ALL GOVERNING CODES AND
REQUIREMENTS. NOTHING IN THIS SPECIFICATION SHALL BE CONSTRUED TO PERMIT
DEVIATION FROM THE REQUIREMENTS OF THE GOVERNING CODES.
2.THE PLUMBING CONTRACTOR SHALL VISIT THE SITE AND SHALL VERITY ALL EXISTING
CONDITIONS AND DIMENSIONS PRIOR TO COMMENCING ANY WORK. ALL DISCREPANCIES
SHALL BE REPORTED TO ARCHITECT IMMEDIATELY UPON DISCOVERY.
3.AFTER THE CONTRACT HAS BEEN AWARDED THE OWNER SHALL NOT BE HELD
RESPONSIBLE FOR INADEQUATE FIELD INVESTIGATION OR IMPROPER EVALUATION OF
THE CONTRACT DOCUMENTS WHICH RESULT IN ADDITIONAL COST.
4.THE PLUMBING CONTRACTOR SHALL FURNISH ALL MATERIAL AND EQUIPMENT AND
PERFORM ALL LABOR TO INSTALL PLUMBING SYSTEMS COMPLETELY, AS INDICATED ON
THE DRAWINGS, AS REQUIRED BY CODE, AND AS SPECIFIED HEREIN. THE WORK INCLUDES
FINAL CONNECTIONS TO EQUIPMENT AND FIXTURES PROVIDED BY OTHERS.
5.THE PLUMBING CONTRACTOR SHALL OBTAIN PERMIT, LICENSES, AND PAY FOR ALL FEES
REQUIRED TO PERFORM THE CONTRACT WORK AND SHALL PROVIDE TO OWNER
ACCEPTABLE RECORD COPIES.
6.ALL MATERIAL AND EQUIPMENT SHALL BE NEW, FULL WEIGHT, AND OF THE BEST QUALITY
WITH THE SAME BRAND OR MANUFACTURER USED FOR EACH CLASS OD MATERIAL OR
EQUIPMENT. MATERIAL SHALL BE INSTALLED IN A NEAT AND PROPER MANNER BY
COMPETENT,SKILLED SPECIALISTS.
7.THE PLUMBING CONTRACTOR SHALL PROVIDE ALL FIXTURES UNLESS OTHERWISE NOTED
AND SHALL COORDINATE WITH THE KITCHEN EQUIPMENT CONTRACTOR. THE PLUMBING
CONTRACTOR SHALL MAKE ALL ROUGH-IN AND FINAL CONNECTIONS, AND PROVIDE ALL
INTERCONNECTING PARTS INCLUDING VALVES, PRESSURE REGULATORS, TEMPERATURE
AND PRESSURE SAFETY RELIEF VALES, TRAPS, STRAINERS AND SUPPLY SHUT-OFF
VALVES.
8.REFER TO ROUGH-IN DRAWINGS FURNISHED BY THE KITCHEN EQUIPMENT CONTRACTOR
FOR EXACT LOCATION OF WATER PIPING SUPPLIES AND DRAIN LOCATIONS TO SERVE
FOOD SERVICE EQUIPMENT.
9.COORDINATE WITH THE WORK OF OTHER SECTIONS AND TRADES, WITH EQUIPMENT
FURNISHED BY OTHERS, AND WITH THE CONSTRAINTS OF THE EXISTING CONDITIONS OF
THE PROJECT SITE.
10. THE PLUMBING CONTRACTOR SHALL PROVIDE FLOOR DRAINS A SHOWN ON THE
DRAWINGS AND AS REQUIRED BY CODE, AND SHALL SET FLOOR DRAINS TO ALLOW
POSITIVE DRAINAGE IN A 6'-0" DIA. CIRCULAR PATTERN.
11.THE PLUMBING CONTRACTOR SHALL PROVIDE AND INSTALL FLOOR SINKS AS SHOWN ON
THE DRAWINGS AND AS REQUIRED BY CODE. FLOOR SINKS SHALL BE SET TO ALLOW
POSITIVE DRAINAGE AND SHALL BE ACCESSIBLE FOR CLEANING, FOR EXAMPLE, HALF
UNDER EQUIPMENT AND HALF EXPOSED.
12.THE PLUMBING CONTRACTOR SHALL PROVIDE PRESSURE REDUCING VALVES, IF
REQUIRED, TO MAINTAIN GENERAL WATER PRESSURE IN KITCHEN AT 50 P.S.L.
13.THE HOOD FIRE SUPPRESSION SYSTEM SHALL BE CONNECTED TO THE GAS SUPPLY LINE
WITH O VALVE TO AUTOMATICALLY SHUT OFF GAS SUPPLY WHEN ACTIVATED.
14.WASTE PIPING: PROVIDE ALL DRAIN, WASTE AND SEWER PIPING WITHIN THE PROJECT
SPACE WITH CONNECTION TO THE BASE BUILDING'S EXISTING SANITARY WASTE SYSTEM
ON SITE. ALL PIPING BELOW FLOOR SLAB SHALL BE SERVICE WEIGH HUB AND SPIGOT PIPE
AND FITTINGS WITH NEOPRENE GASKET JOINTS. ALL PIPING SHALL BE SLOPED UNIFORMLY
AT 2% UNLESS OTHERWISE REQUIRED BY EXISTING CONDITIONS.
15.VENTS: PROVIDE A COMPLETE SYSTEM OF VENT PIPING, OF SERVICE WEIGHT COST IRON
HUBLESS PIPE, CONNECTORS AND FITTINGS, COMBINE THE VENT RISERS IN THE CEILING
SPACE AND PROVIDE A VENT THROUGH EXISTING ROOF PER LANDLORD REQUIREMENTS.
LOCATE VTR MINIMUM 10" FROM ROOF - TOP UNIT FRESH AIR INTAKE. COORDINATE WITH
LANDLORD'S ROOFING CONTRACTOR.
16.WATER PIPING: CONNECT TO LANDLORD'S EXISTING VALVED SERVICE WATER PIPING.
PROVIDE A NEW DOMESTIC HOT AND COLD WATER PIPING SYSTEM INSIDE THE SPACE AS
SHOWN ON THE DRAWINGS, LAY OUT WATER PIPING SO THAT THE ENTIRE SYSTEM CAN BE
DRAINED, HOT AND COLD WATER PIPING SHALL BE TYPE "L" COPPER TUBING ASTM B-88'
WITH WROUGHT COPPER FITTINGS AND SWEAT CONNECTIONS USING LEAD-FREE
SOLDER. PROVIDE 18" TALL AIR CHAMBER AT EACH FIXTURE STOP, OR WATER HAMMER
ARRESTERS AT CONTRACTOR'S OPTION. FLUSH THE WATER PIPING CLEAR OF DEBRIS AND
CLEAN THE AERATORS AND STRAINERS AT THE TERMINATION OF THE INSTALLATION.
17.NATURAL GAS PIPING: INSIDE THE BUILDING ABOVE GRADE SHALL BE SCHEDULE 40 BLACK
STEEL PIPE ASTM A-53 AND MALLEABLE IRON SCREWED FITTINGS WITH SCREWED
JOINTS. FITTINGS WITH SCREWED JOINTS. PROVIDE ALL UNIONS, SHUT OFF VALVES AND
DRIP LEGS REQUIRED BY NFPA-54 AND GOVERNING CODES. PROVIDE ALL TESTS,
INSPECTIONS, HANGERS AND APPURTENANCES REQUIRED FOR A COMPLETE AND
OPERATING SYSTEM. INSTALL PER LANDLORD'S SPECIAL REQUIREMENTS.
18.CLEANOUTS: PROVIDE CLEANOUTS AT THE END OF EACH HORIZONTAL RUN, AND AT THE
BASE OF ALL VERTICAL WASTE PIPES, AND/OR AS REQUIRED BY CODE. CLEANOUTS SHALL
BE THE SAME SIZE AS THE PIPES THEY SERVE, UP TO 4" SIZE
19. PIPE INSULATION: INSULATE ALL COLD WATER PIPING WITH 1/2" AND HOT WATER PIPING
WITH 1", PREFORMED FIBERGLASS WITH ALL- SERVICE JACKET WITH VAPOR BARRIER
(BY-CT, OC, JM,PPG OR KINAUF) AT CONTRACTOR'S OPTION, FLEXIBLE UNICELLULAR
ELECTROMETRIC CLOSET-CELL INSULATION (BY ARMSTRONG, BUBATEX OR EQUAL) WITH
A MAXIMUM FLAME SPREAD ROOTING OF 25 AND SMOKE DEVELOPED RATING OF 50 MAY
BE USED.
20. ACCESS PANELS: TO BE PROVIDED IN CEILINGS OR WALLS WHERE CONCEALED CONTROL
DEVICES ARE LOCATED. WHERE ACCESS FOR ADJUSTMENT AND MAINTENANCE IS
POSSIBLE THROUGH LAY - IN CEILINGS, ACCESS PANELS ARE NOT REQUIRED.
21. SHUT - OFF VALVES WITH UNIONS SHALL BE PROVIDED BY THE PLUMBING CONTRACTOR
ON THE SERVICE TO FIXTURES AND FOOD SERVICE ITEMS AS REQUIRED TO FACILITATE
ISOLATION FOR REPAIR OR REPLACEMENT AND AS SHOWN ON THE DRAWINGS.
22.DRAIN PIPING SHALL BE TYPE M COPPER WITH WROUGHT COPPER FITTINGS.
23.THE PLUMBING CONTRACTOR SHALL: THOROUGHLY CLEAN ITEMS BEFORE
INSTALLATIONS. CAP PIPE OPENINGS TO EXCLUDE DIRT UNTIL FIXTURES ARE INSTALLED
AND FINAL CONNECTIONS HAVE BEEN MODE. PROCEED AS RAPIDLY AS CONSTRUCTION
WILL PERMIT. SET FIXTURES LEVEL AND IN PROPER ALIGNMENT, INSTALL SUPPLIES IN
PROPER ALIGNMENT WITH FIXTURES, PER MANUFACTURE'S ROUGH-IN DIMENSIONS.
INSTALL SILICONE SEALANT BETWEEN FIXTURES AND ADJACENT MATERIAL FOR SANITARY
JOIN. REPAIR ANY DAMAGE DONE TO EXISTING FEATURES AND RESTORE TO ORIGINAL
CONDITIONS. PROVIDE CLEAN CONDITIONS AT TERMINATION OF WORK.
24.ALL WATER PIPING SHALL BE INSTALLED TO PREVENT UNUSUAL NOISES FROM THE FLOW
OF WATER. FURNISH AND INSTALL APPROVED ISOLATION MATERIAL (1" THICK STRIP OF
WAFFLE PATTERN HAIR FELT ) TO ISOLATE ALL PIPING FROM DIRECT CONTACT WITH
BUILDING, CONDUIT, ETC.
25. PROVIDE SEPARATE STOPS FOR EACH INDIVIDUAL HOT AND COLD WATER CONNECTION
IN ADDITION TO ANY FAUCETS OR VALVES THAT ARE PART OF THE FIXTURE TRIM. EACH
GAS OUTLET SHALL BE PROVIDED WITH A SHUT OFF COCK. PROVIDE GATE VALVES AND
UNIONS FOR WATER HEATER.
26.ALL PIPING SHALL BE TESTED IN ACCORDANCE WITH APPLICABLE CODES. TEST WATER
SYSTEM UNDER 150 PSIG HYDROSTATIC PRESSURE FOR FOUR HOURS MINIMUM. WHEN
TESTING INDICATES MATERIALS OR WORKMANSHIP ARE DEFICIENT, REPLACE OR REPAIR
AS REQUIRED, AND REPEAT TEST TILL STANDARDS ARE ACHIEVED.
27.THE PLUMBING CONTRACTOR SHALL VERIFY EXACT LOCATION, SIZE, DEPTH, AND
AVAILABILITY OF ALL UTILITIES CONCERNED .
28. THE PROPRIETARY NAME AND/ OR MODEL NOTED ON THE DRAWINGS IS THE MAKE AND/
OR MODEL USED IN THE DESIGN, MODEL CHANGES MAY AFFECT THE DESIGN.
29.THE PLUMBING CONTRACTOR SHALL MAKE ABSOLUTELY. WATERTIGHT ANY OPENING
THROUGH WATERPROOFED CONSTRUCTION CAUSED BY THE PENETRATION OF
DUCTWORK OR PIPING. ALL WORK SHALL BE IN A MANNER APPROVED BY THE ARCHITECT
AND THE LANDLORD.
30. THE PLUMBING CONTRACTOR SHALL RUN ALL INDIRECT WASTE LINES FROM KITCHEN
EQUIPMENT AND CONDENSATE DRAIN LINES FROM AIR CONDITIONING UNITS. INSULATES
LINES WITH JOHNS -- MANVILLE 1
2' AERO- TUBE OR EQUAL TO PREVENT CONDENSATE DRIP.
31. ALL EXPOSED DOMESTIC PIPES SHALL HAVE MARKERS WITH DIRECTION OF FLOW
ARROWS AND COLOR CODES WITH CLEARLY PRINTED LEGEND IDENTIFYING THE
CONTENTS OF THE PIPS. ALL VALVES SHALL HAVE BRASS TAG IDENTIFYING THE
APPROPRIATE SERVICE.
32. WATER HEATER SHALL BE GLASS LINED STEEL TANK WITH A STORAGE VOLUME OF
______________ GALLONS AND RATED INPUT OF _______________BTU PER HOUR. WATER
HEATER SHALL WRAPPED WITH INSULATION WITH A THERMAL RESISTANCE OF R-12.
FURNISH AND INSTALL A FLUE VENT SYSTEM COMPLETE WITH VENT PIPE, SPACERS,
FLASHING, COUNTERFLASHING, COP, ETC. AND IN ACCORDANCE WITH LANDLORD
REQUIREMENTS.
33.GREASE INTERCEPTOR SHALL BE MODEL_________________________.20 GPM FLOW AND 40
LB. GREASE CAPACITY, WITH LIFT OUT SEDIMENT BUCKET AND ALUMINUM COVER.
INTERCEPTORS SHALL BE SET ON THE FLOOR UNLESS CONDITIONS ALLOW FOR BELOW
FLOOR INSTALLATION.
REMARKSSERVICE
ROUGH-INS
WASTE VENT H.W.C.W
MARK DESCRIPTION
WC-1
ADA
ADA FLOOR MOUNTED PRESSURE ASSIST FLUSH TANK
TOILET,AMERICAN STANDARD MODEL 2467.100, WHITE
VITREROUS CHINA, ELONGATED BOWL, 1.1 GPF, WITH
SEAT AND ANGLE STOP VALVE.
-
L-1
WALL MOUNT LAVATORY, WHITE VITREROUS CHINA,
KHOLER MODEL K-2861, 4" CENTERSET, WITH SENSOR
ACTIVATED FAUCET SLOAN MODEL EFT-600, 0.5 GPM
SET TIMER AT 12 SECONDS ENSURING 0.10 GALLONS
PER CYCLE. INSTALLWITH KOHLER DRAIN MODEL
K-7129-A A INSTALL THERMOSTACTIC MIXING VALVE
EQUAL TO WATTS MODEL L111 TO LIMIT THE FAUCET
OUTLET TEMPERATURE TO MAX 110 DEGREES. ( ASEE
1070APPROVED.
FD-1 FLOOR DRAIN BY ZURN MODEL Z415B, DURA COATED
CAST IRON WITH BOTTOM OUTLET, COMBINATION
INVERTIBLE MEMBRANE CLAMP AND ADJUSTABLE
COLLAR WITH SEEPAGE SLOTS AND 'TYPE B' POLISHED
BRONZED. 6" LIGHT DUTY STRAINER.
-
FS-1 JR SMITH MODEL 3440, CAST IRON BODY AND GRATE
WITH ENAMELED PORCELAIN COATING
-
PLUMBING FIXTURE SCHEDULE
WATER
WASTE
ROOF DRAIN
GREASE DRAIN
VENT
INDIRECT WASTE
CONDENSATE DRAIN
GAS
INSIDE
BEL. GRADE.
ABV. FLR.
BEL. FLR.
ABV. FLR.
BEL. FLR.
ABV. FLR.
BEL. FLR.
ABV. FLR.
BEL. FLR.
INSIDE.
OUTSIDE.
INSIDE.
OUTSIDE.
INSIDE.
OUTSIDE.
OUTSIDE BEL GRADE.
LOCATION
MATERIALS
TY
P
E
'
L
'
C
O
P
P
E
R
TY
P
E
'
M
'
C
O
P
P
E
R
NO
-
H
U
B
C
A
S
T
IR
O
N
SC
H
.
4
0
B
L
A
C
K
.
ST
E
E
L
SC
H
.
4
0
G
A
L
V
.
ST
E
E
L
PO
L
Y
E
T
H
Y
L
E
N
E
SC
H
.
4
0
P
V
C
AB
S
S
C
H
E
D
U
L
E
4
0
TY
P
E
K
C
O
P
P
E
R
SC
H
E
D
U
L
E
8
0
P
V
C
SC
H
E
D
U
L
E
4
0
P
V
C
LEAD FREE SOLDER JONTS
SCHEDULE 80 PVC EXTERNAL TO BUILDING IF PERMITED
NO-HUB CAST IRON WHER SOIL ANALYSIS
ALLOWS TO USE IT.
NO HUB WITH SS BAND FOR CAST IRON.
ABS SCHEDULE 40 WHERE PERMITED
NO HUB WITH SS BAND FOR CAST IRON
NO HUB WITH SS BAND FOR CAST IRON
NO HUB WITH SS BAND FOR CAST IRON
95-5 SOLDERED FITTINGS
USE DWV COPPER FOR PLUMBING FIXTURE IN
KITCHENS
95-5 SOLDERED FITTINGS
95-5 SOLDERED FITTINGS
SCH.40 THREADED FITTINGS
SCH.40 THREADED FITTINGS
SOLVENT WELD FITTINGS
PIPE SCHEDULE AND MATERIAL
4"2"12"
2"2"12"
2"2"
2"2"
12"
MOP
SINK
STAINLESS STEEL FLOOR MOUNT MOP BASIN SINK ,
GSW MODEL SE2024 FM
12"2"3"12"
PREP.
SINK
SINK, ONE COMPARTMENT, 39-1/8"W X 24"D X 45"H,
18-GAUGE STAINLESS STEEL CONSTRUCTION, 18" X 18"
X 12" DEEP COMPARTMENT, 18" DRAINBOARD ON LEFT,
11-1/2"H BACKSPLASH, 8" OC SPLASH MOUNT FAUCET
HOLES, INCLUDES STRAINER WITH 3-5/8" DIA. OPENING,
STAINLESS STEEL LEGS & CROSSBRACING, ETL
12"2"2"12"
3 COMP.
SINK
GSW MODEL SH24243D STAINLESS STEEL LEGS WITH
CROSS BRACING EXTRA WELDED UNDER TUBS FOR
LONGEVITY THREE-TUB SINK WITH LEFT & RIGHT DRAIN
BOARDS 8" WALL MOUNTED FAUCET HOLES
STRAINER INCLUDED STRAINER OPENING DIAMETER
3-5/8" FAUCET NOT INCLUDED NSF CERTIFIED ETL
CERTIFIED
3 4"2"3"3 4"
HAND
SINK
GSW MODEL HS-0810S HAND SINK, WALL MOUNT, 10"W X
8" FRONT-TO-BACK X 5" DEEP BOWL, INCLUDES: NO LEAD
FAUCET & STRAINER, WITH WELDED SPLASH GUARDS,
SS304 STAINLESS STEEL, ETL
12"2"2"12"
CLOTH
WASHER
LG WM6998HBA, VENTLESS WASHER/DRYER COMBO LG
WASHCOMBO™ ALL-IN-ONE 5.0 CU. FT. MEGA CAPACITY
WITH INVERTER HEATPUMP™ TECHNOLOGY AND DIRECT
DRIVE MOTOR
12"2"2"12"
P-0.1
THIS DRAWING, SPECIFICATIONS AND
IDEAS, DESIGNS THEREBY ARE AND SHALL
REMAIN THE PROPERTY OF IG DRAFTING &
DESIGN AND NO PART THEREOF SHALL BE
COPIED DISCLOSED TO OTHERS OR USED
IN CONNECTION WITH ANY WORK OR
PROJECT FOR WHICH THERE HAVE BEEN
PREPARED AND DEVELOPED, WITHOUT THE
WRITTEN CONSENT OF IG DRAFTING &
DESIGN, VISUAL CONTACT WITH THESE
DRAWINGS SHALL CONSTITUTE EVIDENCE
OF ACCEPTANCE OF THESE RESTRICTIONS.
DO
N
C
H
U
R
R
O
S
1
2
3
4
2
2
215 W 4th St
1/22/2025
P-0.2
THIS DRAWING, SPECIFICATIONS AND
IDEAS, DESIGNS THEREBY ARE AND SHALL
REMAIN THE PROPERTY OF IG DRAFTING &
DESIGN AND NO PART THEREOF SHALL BE
COPIED DISCLOSED TO OTHERS OR USED
IN CONNECTION WITH ANY WORK OR
PROJECT FOR WHICH THERE HAVE BEEN
PREPARED AND DEVELOPED, WITHOUT THE
WRITTEN CONSENT OF IG DRAFTING &
DESIGN, VISUAL CONTACT WITH THESE
DRAWINGS SHALL CONSTITUTE EVIDENCE
OF ACCEPTANCE OF THESE RESTRICTIONS.
DO
N
C
H
U
R
R
O
S
1
2
3
4
STEVEN GARCIA
23448 VANOWEN ST
WEST HILLS CA, 91307
2024-05-16
818-826-1627
MIKE HAJILOO
M27303
MIKE HAJILOO PE
19562 VENTURA BLVD. STE #234
TARZANA, CA 91356 818-826-1627
215 W. 4TH ST, SANTA ANA, CA 92701
2024-05-16
215 W. 4TH ST, SANTA ANA, CA 92701
215 W 4th St
1/22/2025
3'-11"
3'
-
8
"
Scale: 1/4"=1'-0"
WASTE WATER PLAN1
PIPE LEGEND
UNDERGROUND S.S. OR GREASE WASTE, APPROVED ABS SCHEDULE 40
APPROVED ABS VENT PIPING AND FITTINGS
CONDENSATE LINE
(E)UNDERGROUND S.S. APPROVED ABS SCHEDULE 40
SIZE OF GREASE INTERCEPTOR
MAXIMUM
FULL PIPE
FLOW (GPM)
Step 1: Determine the flow rate from each fixture.
[Length] X [Width] X [Depth] / [231] = Gallons X [.75 fill factor] / [Drain Period (1 min or 2 min)]
Step 2: Calculate the total load from all fixtures that discharge into the interceptor.
For SI units: 1 inch = 25 mm, 1 gallon per minute = 0.06 L/s
Notes:
1- For interceptor sizing by fixture capacity see the example below.
2- 1 4 inch slope per foot (20.8 mm/m) based on Manning's formula with friction factor N = .012.
For SI units: 1 inch = 25.4 mm, 1 gallon per minute = 0.06 L/s, 1 gallon = 3.785 L
3-COMP SINK (FS)
P-1.0
THIS DRAWING, SPECIFICATIONS AND
IDEAS, DESIGNS THEREBY ARE AND SHALL
REMAIN THE PROPERTY OF IG DRAFTING &
DESIGN AND NO PART THEREOF SHALL BE
COPIED DISCLOSED TO OTHERS OR USED
IN CONNECTION WITH ANY WORK OR
PROJECT FOR WHICH THERE HAVE BEEN
PREPARED AND DEVELOPED, WITHOUT THE
WRITTEN CONSENT OF IG DRAFTING &
DESIGN, VISUAL CONTACT WITH THESE
DRAWINGS SHALL CONSTITUTE EVIDENCE
OF ACCEPTANCE OF THESE RESTRICTIONS.
DO
N
C
H
U
R
R
O
S
1
2
3
4
1
215 W 4th St
1/22/2025
F.D.
2"
2"
Scale: NTS
GREASE TRAP & 3 COMP DIAGRAM 2
F.S.
3"
UNDERGROUND S.S. OR GREASE WASTE, APPROVED ABS SCHEDULE 40
APPROVED ABS VENT PIPING AND FITTINGS
(E)UNDERGROUND S.S. APPROVED ABS SCHEDULE 40
(2)
F.D
(2)
H.S.
2"
F.C.O.
3"
W.C.O.
(2)
F.D
(2)
H.S.
(2)
H.S.
2"
F.C.O.
3"
W.C.O.
(2)
F.S
(2)
F.D
(2)
H.S.
(2)
F.D
(3)
MOP. SK.
(2)
F.S(2)
F.D
3 COMP
(4)
(2)
F.S
GREASE TRAP
GT2700 35GPM
4"
F.C.O.
(1)
LAV
(4)
W.C.
Scale: NTS
WASTE & VENT WATER RISER DIAGRAM 1
P-1.1
THIS DRAWING, SPECIFICATIONS AND
IDEAS, DESIGNS THEREBY ARE AND SHALL
REMAIN THE PROPERTY OF IG DRAFTING &
DESIGN AND NO PART THEREOF SHALL BE
COPIED DISCLOSED TO OTHERS OR USED
IN CONNECTION WITH ANY WORK OR
PROJECT FOR WHICH THERE HAVE BEEN
PREPARED AND DEVELOPED, WITHOUT THE
WRITTEN CONSENT OF IG DRAFTING &
DESIGN, VISUAL CONTACT WITH THESE
DRAWINGS SHALL CONSTITUTE EVIDENCE
OF ACCEPTANCE OF THESE RESTRICTIONS.
DO
N
C
H
U
R
R
O
S
1
2
3
4
215 W 4th St
1/22/2025
Scale: 1/4"=1'-0"
HOT & COLD WATER PLAN1
3'-11"
3'
-
8
"
PIPE LEGEND
COLD WATER, COPPER-(L) WITH BRAZED / OR / SOLDERED FITTINGS UNDERGROUND OVERHEAD
HOT WATER, COPPER-(L) WITH BRAZED / OR / SOLDERED FITTINGS UNDERGROUND OVERHEAD
Scale: NTS
HOT & COLD ISOMETRIC PLAN2
U-75T-80R-3N
76 KBTU
PIPE LEGEND
COLD WATER, COPPER-(L) WITH BRAZED / OR / SOLDERED FITTINGS UNDERGROUND OVERHEAD
HOT WATER, COPPER-(L) WITH BRAZED / OR / SOLDERED FITTINGS UNDERGROUND OVERHEAD
U-75T-80R-3N
76 KBTU
P-2.0
THIS DRAWING, SPECIFICATIONS AND
IDEAS, DESIGNS THEREBY ARE AND SHALL
REMAIN THE PROPERTY OF IG DRAFTING &
DESIGN AND NO PART THEREOF SHALL BE
COPIED DISCLOSED TO OTHERS OR USED
IN CONNECTION WITH ANY WORK OR
PROJECT FOR WHICH THERE HAVE BEEN
PREPARED AND DEVELOPED, WITHOUT THE
WRITTEN CONSENT OF IG DRAFTING &
DESIGN, VISUAL CONTACT WITH THESE
DRAWINGS SHALL CONSTITUTE EVIDENCE
OF ACCEPTANCE OF THESE RESTRICTIONS.
DO
N
C
H
U
R
R
O
S
1
2
3
4
WATER CLOSETS
(FIXTURES PER PERSON)
MALE
1: 1-50
TYPE OF BUILDING
OR OCCUPANCY
RESTAURANT
OCC. B
FEMALE
1: 15
URINALS
(FIXTURES PER PERSON)
MALE
1: 1-100
LAVATORIES
(FIXTURES PER PERSON)
MALE
1: 1-75
FEMALE
1: 1- 50
MALE
1
FEMALE
1
MIN. REQUIRED:
PROVIDED:MALE
-
MALE
1
FEMALE
1
PLUMBING OCCUPANT LOAD FACTOR 30 / 2 =2 15 MALE l 15 FEMALE
NOTE: UNISEX RESTROOM PROVIDED
2022 CPC TABLE 422.1
1
PLAN CHECK NOTES:
1.NEW/REPAIRED/ALTERED POTABLE WATER SYSTEMS ARE REQUIRED TO BE
DISINFECTED BY CHLORINATION. 2022 CPC SEC. 609.10 (1, 2, 3, 4).
2.BACTERIOLOGICAL TESTING OF POTABLE WATER SYSTEM REQUIRED TO BE
PERFORMED BY AN INDEPENDENT THIRDPARTY
TESTING LABORATORY. 2022 CPC SEC. 609.10(4).
1
215 W 4th St
1/22/2025
PIPE LEGEND
NEW GAS PIPE, SCHED.-40 BLACK STEEL WITH THREADED FITTINGS
Scale: 1/4"=1'-0"
GAS PLAN1
GAS PIPE: (SCHED-40, BLACK STEEL)
1/2 3/4"1"1-1/4"
34 71 134 275
PIPE SIZE
(INCH)
MAX. ALLOWED
(CFH)
1-1/2"
412
GAS PIPE SIZE @ 200' T.D.L. (TABLE 1215.2(1) CAL. PLUM'G CODE 2022)
2"
794
2 1 2 "
1270
GAS: NATURAL
INLET PRESSURE: LESS THAN 2 PSI
PRESSURE DROP : 0.5 IN. W.C
Scale: NTS
ISOMETRIC GAS PLAN2
(N) GAS APPLIANCES
N
N
N
4
3
1
CHURROS FRYERS .................. 75KBTU
STOCK POTS ...............................80 KBTU
WATER HEATER...........................76 KBTU
300 KBTU
240 KBTU
76 KBTU
3'-11"
3'
-
8
"
TOTAL GAS APPLIANCES 756 CFH
N 1 A/C..................................................100 KBTU 100 KBTU
273 CFH
218 CFH
69 CFH
687CFH
91 CFH
TOTAL BTU TOTAL CFH
N 1
N 1 DRYER............................................40 KBTU 40 KBTU 36 CFH
P-3.0
THIS DRAWING, SPECIFICATIONS AND
IDEAS, DESIGNS THEREBY ARE AND SHALL
REMAIN THE PROPERTY OF IG DRAFTING &
DESIGN AND NO PART THEREOF SHALL BE
COPIED DISCLOSED TO OTHERS OR USED
IN CONNECTION WITH ANY WORK OR
PROJECT FOR WHICH THERE HAVE BEEN
PREPARED AND DEVELOPED, WITHOUT THE
WRITTEN CONSENT OF IG DRAFTING &
DESIGN, VISUAL CONTACT WITH THESE
DRAWINGS SHALL CONSTITUTE EVIDENCE
OF ACCEPTANCE OF THESE RESTRICTIONS.
DO
N
C
H
U
R
R
O
S
1
2
3
4
2
215 W 4th St
1/22/2025
GREASE INTERCEPTOR MEMORANDUM
To: Jaime Nunez – Applicant Date: May 28, 2024
From: Hector Medina – Assistant Engineer, PWA
Water Resource Division
Location: 215 W. 4TH ST. – DON CHURROS
The above referenced food service establishment (FSE) must comply with the Fats, Oils, and Grease
(FOG) Control Program Rules and Regulations as identified in Ordinance NS-2921 and as follows:
A Hydro-Mechanical Grease Interceptor (HGI) is required at this FSE.
☒ This FSE shall install a Hydro-Mechanical Grease Interceptor (HGI).
☐ This FSE shall maintain the existing Hydro-Mechanical Grease Interceptor (HGI).
This FSE qualifies for at least one of the following condition(s):
The FSE discharges to a documented Enhanced Maintenance Location sewer but the proposed FSE’s
FOG discharges are projected to be negligible and will not likely cause a significant impact to the sewer
system, or;
A gravity grease interceptor (GGI) cannot be installed due to physical site limitations or inadequate
slope between the interceptor and private and/or public sewer lines.
C/c: Water Resources Division
Planning & Building Agency
OC Health Care Agency
Public Works Agency (Development)
EEC Environmental
Applicant
215 W 4th St
1/22/2025
YES NO
INSTRUCTIONS:
ORAN GE COUNTY FI RE AUTHORI TY
Plan Submittal Criteria
COMMERCIAL projects, MULTIFAMILY RESIDENTIAL projects
and RESIDENTIAL TRACT developments
· Fill in the project/business address and provide a brief description of the scope of work and type of business operation that will take place.
· Answer questions 1 through 10, read and initial items 11 and 12, then complete and sign the certification section.
· If you answer: - “YES” to any part of questions 1 through 10, submit the type of plan indicated in italics to OCFA.
· In some cases, other plan types not indicated herein may also be necessary depending on specific conditions or operations.
· Visit www.ocfa.org for submittal information and locations. If you need assistance in filling out this form or have questions regarding
requirements for review, please contact OCFA at 714-573-6108 or visit us at 1 Fire Authority Road, Irvine, CA 92602.
Address Suite City
Project Scope/Business Description
1. Construction of a new building, a new story, or increase the footprint of an existing building? Changes to roadways,
curbs, or drive aisles? Addition, relocation, or modification of fire hydrants or fences/gates? Construction within
300 feet of an active or proposed oil well? Fire Master Plan (PR145)
2. Property is adjacent to a wildland area or non-irrigated native vegetation?
Fire Master Plan (PR145); a Fuel Modification Plan may also be required. (PR120, PR124)
3. Located in or < 100’ from a Division of Oil, Gas, and Geothermal Resources (DOGGR) field boundary, < 300’ from
an oil/gas seep, or < 1000’ from a landfill? Methane Work Plan. (PR170)
4. Installation/modification/repair of underground piping, backflow preventers, or fire department connections serving
private fire hydrant/sprinkler/standpipe systems? Underground Plan. (PR470, PR475)
5. Drinking/dining/recreation/meetings/training/religious functions or other gatherings in a room > 750 sq.ft. (> 1,000
sq.ft. for training/adulteducation) or > 49 people? Healthcare/outpatient services for > 5 people who may be unable
to immediately evacuate without assistance? Education for children (academic tutoring for ages 5+ is exempt unless
classified as an E occupancy by the Building Official)? Adult/child daycare? 24-hour care/supervision? Incarceration
or restraint? Hotel/apartment or residential facility with 3+ units and 3+ stories (3-story townhouses/rowhouses
where an independent direct exit to grade is provided for dwelling are exempt)? Congregate housing/dormitories
with 17+ people? High-rise structure (55+ feet to highest occupied floor level)? Architectural Plan (PR200-PR285)
6. Installation/modification of locks delaying or preventing occupants from leaving a space or requiring use of a card,
button, or similar action to open a door in the direction of exit travel? Architectural, Sprinkler, and/or Alarm Plan
depending on the occupancy and type of device installed (PR200-PR280, PR420-PR425, PR500-PR520)
7. Installation/modification/use of spray booths; dust collection; dry cleaning; industrial ovens/drying equipment;
industrial/commercial refrigeration systems; compressed gasses; tanks for cryogenic or flammable/combustible
liquids; vapor recovery; smoke control; battery back-up/charging systems (> 50 gal. electrolyte, > 1,000 lb. lithium
ion); welding/brazing/soldering, open flame torches, cutting/grinding; or other similar operations?
Special Equipment Plan (PR315, PR340-PR382)
8. Storage/use/research with flammable/combustible liquids or other chemicals? Motor vehicle/aircraft
maintenance/repair? Cabinetry/woodworking/finishing facility? Chem Class & floor plan (full architectural plan if
H occupancy); Special Equipment Plans may be necessary. (PR315-PR360, PR232-PR240)
9. Storage or merchandizing areas in excess of 500 sq. ft. where items are located higher than 12’ (6’ for high-hazard
commodities, plastic, rubber, foam, etc.)? High-piled Storage Plan (PR330)
10. Cooking under a Type I commercial hood; installation or modification of a fire extinguishing system located in a
commercial cooking hood? Hood & Duct Extinguishing System, not just the hood mechanical plan. (PR335)
Initial each of the following two items indicating that you have read and understand the statement:
11. *Sprinklers/Alarms: Consult Building/Fire Codes and ordinances to determine sprinkler/alarm requirements; if a system is
required, plans shall be submitted for OCFA review. Existing buildings undergoing remodel must be evaluated by a licensed
Initials contractor to determine if modification is needed; if so, contractor shall submit plans prior to making modifications.
12. Fire Hazard Severity Zone: Consult maps available at building department or on OCFA website to determine if your site is located
in a FHSZ. Buildings in a FHSZ may be subject to special construction requirements detailed in CBC Chapter 7A or CRC R327—
Initials the building department will determine specific requirements.
I certify under penalty of perjury under the laws of the State of California that the above is true:
Print Name Signature
Phone Number ( ) Date / /
Building Department: If you have verified that all of the questions have been answered accurately as “NO”, and the project does not otherwise require OCFA
review of sprinkler or alarm plans*, then you may accept this signed form as a written release that OCFA review is not required. Should you still require that the
applicant have plans approved by OCFA, please initial here or attach an OCFA referral form and have the applicant submit the form along with the
appropriate plans and fees for OCFA review. 10-08-14 EE
COM
215 W 4th St
1/22/2025
Project No. 24-186
Prepared For:
215 W 4th St.,
Santa Ana, CA 92701
21731 Ventura Blvd. Suite 110
Woodland Hills, CA 91364
Ph. (818)633-3290
www.rombengineers.com
September 12th, 2024
Page 1 of 28
215 W 4th St
1/22/2025
Appendix
I.Mech. Unit Attachment Calculations
II.Roof Joist Calculations
III.Floor Joist Calculations
IV.Pad Calculations
Page 2 of 28
215 W 4th St
1/22/2025
Appendix I
Mech. Unit Attachment Calculations
Page 3 of 28
215 W 4th St
1/22/2025
ASCE Hazards Report
Address:
215 W 4th St
Santa Ana, California
92701
Standard:ASCE/SEI 7-22 Latitude:33.748252
Risk Category:II Longitude:-117.869278
Soil Class:Default Elevation:119.8701196002794 ft
(NAVD 88)
Page 1 of 4https://ascehazardtool.org/Wed May 15 2024
Page 4 of 28
215 W 4th St
1/22/2025
PGA M : 0.66
SMS : 1.75
SM1 : 1.2
SDS : 1.17
SD1 : 0.8
T L : 8
SS : 1.48
S1 : 0.51
VS30 : 260
Seismic Design Category:D
Multi-Period Design Spectrum
S (g) vs T(s)a
Multi-Period MCE SpectrumR
S (g) vs T(s)a
Two-Period Design Spectrum
S (g) vs T(s)a
Two-Period MCE SpectrumR
S (g) vs T(s)a
Design Vertical Response Spectrum
Vertical ground motion data has not yet been made
available by USGS.
MCE Vertical Response SpectrumR
Vertical ground motion data has not yet been made
available by USGS.
Seismic
DefaultSite Soil Class:
Results:
Page 2 of 4https://ascehazardtool.org/Wed May 15 2024
Page 5 of 28
215 W 4th St
1/22/2025
PROJECT : PAGE :
CLIENT : DESIGN BY :
JOB NO. : DATE : REVIEW BY :
INPUT DATA & DESIGN SUMMARY
EQUIPMENT WEIGHT W = 0.692 kips
CM HEIGHT H = 2.36 ft, 2/3 total height
LAG SCREW DIAMETER f = 1/4 in, NDS APP. L
LAG SCREW LENGTH Long = 5 in, NDS APP. L
ANCHORAGE LENGTH L = 4.83 ft
LAG SCREWS ALONG L EDGE NL = 3 per line
LAG SCREW SPACING SL = L / (NL - 1) =29 in
ANCHORAGE WIDTH B = 3.67 ft
LAG SCREWS ALONG B EDGE NB = 3 per line
LAG SCREW SPACING SB = B / (NB - 1) =22 in
[THE ANCHORAGE, USING 1/4" x 5" LAG SCREWS, IS ADEQUATE.]
ANALYSIS
ALLOWABLE TENSION & SHEAR VALUES
ZII' = CD Cd Cg ZII =431 lbs
where CD =1.6 (NDS Tab 2.3.2)
Cd = p / (8D) =1.628
p = S + (T-E) - (Diaphragm Thk) - ts = 3.256 in
S + (T-E) = 3.688 in (NDS Appendix L2)
Diaphragm Thk = 0.298 in (0.298 for 15/32, 0.319 for 19/32, UBC Table 23-2-H, page 3-420)
ts = 0.134 in (10 gage, NDS Tab 12K)
Cg =0.92 (NDS 10.3.6)
ZII =180 lbs (NDS Tab 12K)
Z^' = CD Cd Cg Z^ =311 lbs
Z^ = 130 lbs (NDS Tab 12K)
(W ' p) = CD W (T-E) =1024 lbs
where W = 225 lbs / in (NDS Tab 12.2A)
(T-E) = 2.844 in (NDS Appendix L2)
DESIGN LOADS
FH = Fp = (KH) MAX{ 0.3SDSIpW , MIN[ 0.4CARSDSIp(1+2.5z/h)/Rpo W , 1.6SDSIpW ] }, (ASCE 7-22, Sec. 13.3.1)
= 1 MAX{ 0.53W , MIN[ 1.40W , 2.81W ]} where SDS =1.17 (ASCE 7-22 Sec 11.4.5)
= 1.64 W , (SD)Ip =1.5 (ASCE Sec. 13.1.3)
= 1.17 W , (ASD) = 0.81 kips CAR =1 (ASCE Tab. 13.6-1)
Rpo =1.5 (ASCE Tab. 13.6-1)
FV = KV W =0.17 W , (ASD) = 0.12 kips, up & down z = h ft
h =10 ft
KH =1 (ASCE Sec. 13.4.2)
KV = KH 0.2 SDS / 1.4 =0.17 (vertical seismic factor)
MAXIMUM OVERTURNING MOMENT AT ANCHOR EDGE
MOT = Fp H =1.91 ft-kips
MRES,L = (0.9W - Fv ) (0.5L) =1.22 ft-kips <MOT ,therefore design tension anchors.
MRES,B = (0.9W - Fv ) (0.5B) =0.93 ft-kips <MOT ,therefore design tension anchors.
TENSION LOAD AT CORNER LAG SCREW
TL = (FV -0.9 W) / A + MOT y / I =68 lbs / bolt TB = (FV -0.9 W) / A + MOT y / I =110 lbs / bolt
where A = 2(NL + NB) -4 =8 (total bolts) where I = SYi
2 =2909 in2-bolts
I = SXi
2 =5039 in2-bolts y = 0.5 B = 22.02 in
y = 0.5 L = 28.98 in
SHEAR LOAD AT EACH LAG SCREW
V = FH / A =101 lbs / bolt
CHECK CORNER SCREW CAPACITY AT COMBINED LATERAL AND WITHDRAWAL LOADS
Za' = ZII'(W' p) / (ZII'sin2a + W'p cos2a)(NDS 12.4-1)
= 527 lbs / bolt > [TL
2 + V2 ]0.5 =122 lbs / bolt [SATISFACTORY]
where a = tan-1(TL / V) =34.08 o
Zq' = Z^'(W' p) / (Z^'sin2a + W'p cos2a) (NDS 12.4-1)
= 500 lbs / bolt > [TB
2 + V2 ]0.5 =150 lbs / bolt [SATISFACTORY]
where q = tan-1(TB / V) =47.42 o
215 W 4th. St.
24-186
Equipment Anchorage to Wood Roof Based on NDS 2018 / 2021 IBC / 2022 CBC
H
B
No. Bolts per Input
where Occurs
Frame (not shown) by MFR
S
S
Page 6 of 28
215 W 4th St
1/22/2025
Appendix II
Roof Joist Calculations
Page 7 of 28
215 W 4th St
1/22/2025
Multiple Simple Beam
LIC# : KW-06017019, Build:20.23.12.07 ROMB STRUCTURAL ENGINEERING (c) ENERCALC INC 1983-2023
Project File: 215 W 4th.ec6
Project Title:215 W 4th St.
Engineer:ROMB
Project ID:24-186
Project Descr:
ROOF RAFTERDescription :
BEAM Size :2-2x12, Sawn, Fully Braced
Using Load Resistance Factor Design with ASCE 7-16 Load Combinations, Major Axis Bending
Wood Beam Design :
Calculations per NDS 2018, IBC 2018, CBC 2019, ASCE 7-16
Douglas Fir-Larch (North)No.2
875.0
875.0
600.0
625.0
1,300.0
470.0
170.0
425.0
30.590
Eminbend - xx ksi
Wood Species :Wood Grade :
Fb - Tension
psi
psi Fv psi
Fb - Compr Ft psi
Fc - Prll psi
psiFc - Perp
Ebend- xx ksi Density pcf
R.R.#1
Applied Loads
Beam self weight calculated and added to loads
Unif Load: D = 0.010, Lr = 0.020 k/ft, Trib= 2.0 ft
1Point: D = 0.150 k @ 10.250 ft
2Point: D = 0.150 k @ 13.830 ft
.Design Summary
Max fb/Fb Ratio =0.615 : 1
Max Reactions (k)HEWSLLr
+1.20D+1.60LrLoad Comb :
Span # 1
Left Support
D
in
10.342 inft
50.73 psi
Fb : Allowable :2,173.50 psi
Right Support
Fv : Allowable :Span # 1
Load Comb :+1.20D+1.60Lr
367.20 psi
fb : Actual :
Max fv/FvRatio =0.138 : 1 20.329 ft
1,336.14 psi at
atfv : Actual :
Ratio 9999 Ratio 9999
Max Deflections
Transient Downward 0.399 in
Transient Upward 0.000 in
Total Downward 0.881 in
Total Upward 0.000 in
0.42 0.430.46 0.43 Ratio 639 289Ratio
LC: Lr Only LC: +D+Lr
LC:LC:
BEAM Size :2-2x12, Sawn, Fully Braced
Using Load Resistance Factor Design with ASCE 7-16 Load Combinations, Major Axis Bending
Wood Beam Design :
Calculations per NDS 2018, IBC 2018, CBC 2019, ASCE 7-16
Douglas Fir-Larch (North)No.2
875.0
875.0
600.0
625.0
1,300.0
470.0
170.0
425.0
30.590
Eminbend - xx ksi
Wood Species :Wood Grade :
Fb - Tension
psi
psi Fv psi
Fb - Compr Ft psi
Fc - Prll psi
psiFc - Perp
Ebend- xx ksi Density pcf
R.R.#2
Applied Loads
Beam self weight calculated and added to loads
Unif Load: D = 0.010, Lr = 0.020 k/ft, Trib= 2.0 ft
1Point: D = 0.060 k @ 9.90 ft
2Point: D = 0.060 k @ 11.50 ft
.Design Summary
Max fb/Fb Ratio =0.537 : 1
Max Reactions (k)HEWSLLr
+1.20D+1.60LrLoad Comb :
Span # 1
Left Support
D
in
10.625 inft
44.89 psi
Fb : Allowable :2,173.50 psi
Right Support
Fv : Allowable :
Span # 1
Load Comb :+1.20D+1.60Lr
367.20 psi
fb : Actual :
Max fv/FvRatio =0.122 : 1 20.329 ft
1,168.16 psi at
atfv : Actual :
Ratio 9999 Ratio 9999
Max Deflections
Transient Downward 0.399 in
Transient Upward 0.000 in
Total Downward 0.759 in
Total Upward 0.000 in
0.35 0.430.35 0.43 Ratio 639 336Ratio
LC: Lr Only LC: +D+Lr
LC:LC:
Page 8 of 28
215 W 4th St
1/22/2025
Multiple Simple Beam
LIC# : KW-06017019, Build:20.23.12.07 ROMB STRUCTURAL ENGINEERING (c) ENERCALC INC 1983-2023
Project File: 215 W 4th.ec6
Project Title:215 W 4th St.
Engineer:ROMB
Project ID:24-186
Project Descr:
BEAM Size :2-2x12, Sawn, Fully Braced
Using Load Resistance Factor Design with ASCE 7-16 Load Combinations, Major Axis Bending
Wood Beam Design :
Calculations per NDS 2018, IBC 2018, CBC 2019, ASCE 7-16
Douglas Fir-Larch (North)No.2
875.0
875.0
600.0
625.0
1,300.0
470.0
170.0
425.0
30.590
Eminbend - xx ksi
Wood Species :Wood Grade :
Fb - Tension
psi
psi Fv psi
Fb - Compr Ft psi
Fc - Prll psi
psiFc - Perp
Ebend- xx ksi Density pcf
R.R.#3
Applied Loads
Beam self weight calculated and added to loads
Unif Load: D = 0.010, Lr = 0.020 k/ft, Trib= 2.0 ft
1Point: D = 0.10 k @ 10.0 ft
2Point: D = 0.10 k @ 12.0 ft
.Design Summary
Max fb/Fb Ratio =0.577 : 1
Max Reactions (k)HEWSLLr
+1.20D+1.60LrLoad Comb :
Span # 1
Left Support
D
in
10.554 inft
47.19 psi
Fb : Allowable :2,173.50 psi
Right Support
Fv : Allowable :Span # 1
Load Comb :+1.20D+1.60Lr
367.20 psi
fb : Actual :
Max fv/FvRatio =0.129 : 1 20.329 ft
1,253.05 psi at
atfv : Actual :
Ratio 9999 Ratio 9999
Max Deflections
Transient Downward 0.399 in
Transient Upward 0.000 in
Total Downward 0.817 in
Total Upward 0.000 in
0.39 0.43
0.39 0.43 Ratio 639 311Ratio
LC: Lr Only LC: +D+Lr
LC:LC:
BEAM Size :2-2x12, Sawn, Fully Braced
Using Load Resistance Factor Design with ASCE 7-16 Load Combinations, Major Axis Bending
Wood Beam Design :
Calculations per NDS 2018, IBC 2018, CBC 2019, ASCE 7-16
Douglas Fir-Larch (North)No.2
875.0
875.0
600.0
625.0
1,300.0
470.0
170.0
425.0
30.590
Eminbend - xx ksi
Wood Species :Wood Grade :
Fb - Tension
psi
psi Fv psi
Fb - Compr Ft psi
Fc - Prll psi
psiFc - Perp
Ebend- xx ksi Density pcf
R.R.#4
Applied Loads
Beam self weight calculated and added to loads
Unif Load: D = 0.010, Lr = 0.020 k/ft, Trib= 2.0 ft
1Point: D = 0.1730 k @ 3.250 ft
2Point: D = 0.1730 k @ 6.670 ft
.Design Summary
Max fb/Fb Ratio =0.570 : 1
Max Reactions (k)HEWSLLr
+1.20D+1.60LrLoad Comb :
Span # 1
Left Support
D
in
9.633 inft
55.81 psi
Fb : Allowable :2,173.50 psi
Right Support
Fv : Allowable :Span # 1
Load Comb :+1.20D+1.60Lr
367.20 psi
fb : Actual :
Max fv/FvRatio =0.152 : 1 0.000 ft
1,238.49 psi at
atfv : Actual :
Ratio 9999 Ratio 9999
Max Deflections
Transient Downward 0.399 in
Transient Upward 0.000 in
Total Downward 0.834 in
Total Upward 0.000 in
0.55 0.430.37 0.43 Ratio 639 305Ratio
LC: Lr Only LC: +D+Lr
LC:LC:
Page 9 of 28
215 W 4th St
1/22/2025
Multiple Simple Beam
LIC# : KW-06017019, Build:20.23.12.07 ROMB STRUCTURAL ENGINEERING (c) ENERCALC INC 1983-2023
Project File: 215 W 4th.ec6
Project Title:215 W 4th St.
Engineer:ROMB
Project ID:24-186
Project Descr:
BEAM Size :2-2x12, Sawn, Fully Braced
Using Load Resistance Factor Design with ASCE 7-16 Load Combinations, Major Axis Bending
Wood Beam Design :
Calculations per NDS 2018, IBC 2018, CBC 2019, ASCE 7-16
Douglas Fir-Larch (North)No.2
875.0
875.0
600.0
625.0
1,300.0
470.0
170.0
425.0
30.590
Eminbend - xx ksi
Wood Species :Wood Grade :
Fb - Tension
psi
psi Fv psi
Fb - Compr Ft psi
Fc - Prll psi
psiFc - Perp
Ebend- xx ksi Density pcf
C.J.#1
Applied Loads
Beam self weight calculated and added to loads
Unif Load: D = 0.010, Lr = 0.020 k/ft, Trib= 2.0 ft
1Point: D = 0.050, Lr = 0.130 k @ 17.50 ft
2Point: D = 0.0350, Lr = 0.130 k @ 13.250 ft
3Point: D = 0.020 k @ 17.50 ft
4Point: D = 0.030 k @ 13.250 ft
.Design Summary
Max fb/Fb Ratio =0.574 : 1
Max Reactions (k)HEWSLLr
+1.20D+1.60LrLoad Comb :
Span # 1
Left Support
D
in
11.702 inft
59.40 psi
Fb : Allowable :2,173.50 psi
Right Support
Fv : Allowable :Span # 1
Load Comb :+1.20D+1.60Lr
367.20 psi
fb : Actual :
Max fv/FvRatio =0.162 : 1 19.526 ft
1,248.38 psi at
atfv : Actual :
Ratio 9999 Ratio 9999
Max Deflections
Transient Downward 0.452 in
Transient Upward 0.000 in
Total Downward 0.740 in
Total Upward 0.000 in
0.31 0.47
0.38 0.60 Ratio 542 331Ratio
LC: Lr Only LC: +D+Lr
LC:LC:
Page 10 of 28
215 W 4th St
1/22/2025
Multiple Simple Beam
LIC# : KW-06017019, Build:20.23.08.30 ROMB STRUCTURAL ENGINEERING (c) ENERCALC INC 1983-2023
Project File: 215 W 4th.ec6
Project Title:215 W 4th St.
Engineer:ROMB
Project ID:24-186
Project Descr:
NEW CEILING JOISTSDescription :
BEAM Size :2-2x12, Sawn, Fully Braced
Using Load Resistance Factor Design with ASCE 7-16 Load Combinations, Major Axis Bending
Wood Beam Design :
Calculations per NDS 2018, IBC 2018, CBC 2019, ASCE 7-16
Douglas Fir-Larch (North)No.2
875.0
875.0
600.0
625.0
1,300.0
470.0
170.0
425.0
30.590
Eminbend - xx ksi
Wood Species :Wood Grade :
Fb - Tension
psi
psi Fv psi
Fb - Compr Ft psi
Fc - Prll psi
psiFc - Perp
Ebend- xx ksi Density pcf
(N)2-2x12 C.J. #2 (with Hood load)
Applied Loads
Beam self weight calculated and added to loads
Unif Load: D = 0.010, Lr = 0.020 k/ft, Trib= 2.0 ft
1Point: D = 0.0320 k @ 5.820 ft
2Point: D = 0.0320 k @ 6.640 ft
3Point: D = 0.050, Lr = 0.130 k @ 17.50 ft
4Point: D = 0.350, Lr = 0.130 k @ 13.250 ft
5Point: D = 0.020 k @ 17.50 ft
6Point: D = 0.030 k @ 13.250 ft
.Design Summary
Max fb/Fb Ratio =0.733 : 1
Max Reactions (k)HEWSLLr
+1.20D+1.60LrLoad Comb :
Span # 1
Left Support
D
in
12.790 inft
71.35 psi
Fb : Allowable :2,173.50 psi
Right Support
Fv : Allowable :Span # 1
Load Comb :+1.20D+1.60Lr
367.20 psi
fb : Actual :
Max fv/FvRatio =0.194 : 1 19.526 ft
1,592.48 psi at
atfv : Actual :
Ratio 9999 Ratio 9999
Max Deflections
Transient Downward 0.452 in
Transient Upward 0.000 in
Total Downward 0.958 in
Total Upward 0.000 in
0.47 0.470.60 0.60 Ratio 542 255Ratio
LC: Lr Only LC: +D+Lr
LC:LC:
Page 11 of 28
215 W 4th St
1/22/2025
PROJECT : PAGE :
CLIENT : DESIGN BY :
JOB NO. : DATE: REVIEW BY :
INPUT DATA & DESIGN SUMMARY
SECTION & SPACING 350S162-43 (33 ksi)@ 16 in o.c
( 33 ksi)
JOIST SPAN L =9.25 ft
DEAD LOAD DL =10 psf
LIVE LOAD LL =10 psf
LATERAL SUPPORTED ?1 compression flange
(0=No, 1=compression flange, 2=tension flange)
DEFLECTION LIMITATION FOR LIVE LOAD ?1 L /240 THE DESIGN IS ADEQUATE.
(0=No., 1= L /240, 2= L /360, 3= L /180, 4= L /120)
ANALYSIS
SECTION PROPERTIES OF EACH METAL STUD (SSMA page 8 to 14)
t = 0.0451 in Fy = 33 ksi Ixx = 0.654 in4 Mn/Wb = 7.05 in-kips
h = 3.5 in Wt = 1.14 lb/ft Sxx = 0.357 in3 Vn/Wv = 631 lbs
A = 0.334 in2 rx = 1.4 in ry = 0.612 in xo = -1.312 in
J =0.000227 in4 Cw = 0.35 in6
CHECK MAX WEB DEPTH-TO-THICKNESS RATIO (AISI B1.2)
h / t = 77.61 <200 [Satisfactory]
CHECK FLEXURAL CAPACITY (AISI C3.1)
Mn/Wb =7.05 in-kips >M [Satisfactory]
Where M = [(DL+LL) S + Wt ] L2 / 8 =3.57 in-kips
S = 16 in o.c., spacing as given.
CHECK SHEAR CAPACITY (AISI C3.2)
Vn/WV =631 lbs >V [Satisfactory]
Where V = [(DL+LL) S + Wt ] L / 2 = 129 lbs
CHECK LATERAL-TORSIONAL BUCKLING (AISI C3.1.2)
CASE 1: BOTH TOP & BOTTOM FLANGES UNSUPPORTED <== Does not apply.
15.1 ksi <2.78 Fy = 91.7 ksi
<0.56 Fy = 18.5 ksi
Where Cb = 1.0
ro = (rx
2 + ry
2 + xo
2)0.5 = 2.014 in
Sf = 0.37 in3 8.851 ksi
E = 29500 ksi (AISI pg xiv)
G = 11300 ksi (AISI pg xvi)
Ky = 1.0
Kt = 1.0 7.999 ksi
Ly = 111 in
Lt = 111 in
=15.1 ksi
Joist Design Based on AISI S100/SI-10 & ESR-3064P
ACrobFe ey tSf
s s= =
( )
2
2/
E
ey
K L ry y y
ps= =
( )
21
2 2
E C wGJtAroK Lt t
ps
= + =
- CEILING JOISTS AT HARD CEILING LOCATION
Page 12 of 28
215 W 4th St
1/22/2025
(cont'd)
Mn/Wb =3.39 in-kips <M [Satisfactory]
Where Sc = 0.37 in3 from SSMA page 8 to 14
Wb = 1.67
Mn = ScFc = 5.66 in-kips
M = [(DL+LL) S/12 + Wt ] L2 / 8 =3.57 in-kips
CASE 2: BOTTOM FLANGE SUPPORTED ONLY <== Does not apply.
Mn/Wb =4.94 in-kips >M [Satisfactory]
Where Se = 0.36 in3, from Sxx
Wb = 1.67
R = 0.70 (AISI Table D6.1.1-1)
Mn = RSeFy = 8.25 in-kips
CHECK CAPACITY COMBINED BENDING & SHEAR AT ANY SAME SECTION (AISI C3.3.1)
= 0.5457 <1.0 [Satisfactory]
Where M = 3.57 in-kips
V = 129 lbs
Vn/Wv = 631 lbs
Wb = 1.67
Mn = MIN( Bending , Buckling) = 11.774 in-kips
Mn/Wb = 7.05 in-kips, from SSMA page 8 to 14 for bending only.
=0.51 >0.5 =0.20 <0.7
= 0.5075 <1.3 [Satisfactory]
CHECK DEFLECTION
0.11 in <L /240 = 0.46 in [Satisfactory]
DETERMINE SCREWS AT EACH LEG OF CONNECTION (SSMA page 70)
Vmax = 129 lbs
vallow = 244 lbs / screw, for # 8 screws.= = >(1)- # 8 screws required.
263 lbs / screw, for # 10 screws.= = >(1)- # 10 screws required.
280 lbs / screw, for # 12 screws.= = >(1)- # 12 screws required.
Technical References:
1. AISI S100/SI-10, North American Specification for the Design of Cold-formed Steel Structural Members, with Supplement 1, 2010.
2. SSMA_Product_Technical_Guide, ESR-3064P, Steel Stud Manufactures Association, 2015.
22M Vb v
VMn n
W W+
0.6 M Vb v
VMn n
W W+
Mb
M n
W
Vv
V n
W
( )45
384
LL S L
LL EI xx
= =D
Page 13 of 28
215 W 4th St
1/22/2025
PROJECT : PAGE :
CLIENT : DESIGN BY :
JOB NO. : DATE: REVIEW BY :
INPUT DATA & DESIGN SUMMARY
SECTION & SPACING 550S137-43 (33 ksi)@ 16 in o.c
WALL HEIGHT h =16 ft
hp =0 ft
GRAVITY LOAD (ASD level) P =175 lbs / ft
LATERAL LOAD (SD level) w1 =16 psf
PARAPET LOAD (SD level) w2 =16 psf
ECCENTRICITY e =0 in
DEFLECTION LIMITATION ?1 h /240
(0=No., 1= h /240, 2= h /360, 3= h /180, 4= h /120)
THE DESIGN IS ADEQUATE.
ANALYSIS
SECTION PROPERTIES OF EACH METAL STUD (SSMA page 8 to 14)
thk = 0.0451 in Fy = 33 ksi Ixx = 1.655 in4 Mn/Wb = 11.6 in-kips
t = 5.5 in Wt = 1.33 lb/ft Sxx = 0.592 in3 Vn/Wv = 1199 lbs
A = 0.391 in2 rx = 2.059 in ry = 0.467 in xo = -0.83 in
J =0.000265 in4 Cw = 0.52 in6
CHECK MAX WEB DEPTH-TO-THICKNESS RATIO (AISI B1.2)
t / (thk) = 121.95 <200 [Satisfactory]
CHECK FLEXURAL CAPACITY (AISI C3.1)
Mn/Wb =11.60 in-kips / stud >M [Satisfactory]
Where 8.00 ft
8.19 in-kips / stud
S = 1.333 ft o.c., spacing as given.
0.00 in-kips / stud
M = (1/1.4) MAX( M1 , M2) = 5.85 in-kips / stud, (1/1.4 for wind/seismic, from AISI App. A4.1.2, typical)
CHECK SHEAR CAPACITY (AISI C3.2)
Vn/WV =1199 lbs / stud >V [Satisfactory]
Where 171 lbs / stud
V2 = h w1 S - V1 =171 lbs / stud
V3 = hp w2 S = 0 lbs / stud
V = (1/1.4) MAX( V1 , V2 , V3) = 122 lbs / stud
CHECK CAPACITY COMBINED BENDING & SHEAR AT ROOF/FLOOR SECTION (AISI C3.3.1)
= 0.1017 <1.0 [Satisfactory]
Where M = 0.00 in-kips / stud, (1/1.4 included)
V = 122 lbs / stud, (1/1.4 included)
Vn/Wv = 1199 lbs / stud, from SSMA page 8 to 14.
Mn/Wb =11.6 in-kips / stud, from SSMA page 8 to 14.
Wall Stud Design Based on AISI S100/SI-10 & ESR-3064P
( )2
12
p
p
h h Pex h h h h w
+ = + - - =
( )
2
1 2 2
1 2
1
1
22 p
wPe Sh hM
w h
= + - =
2
2
2 2
pw h SM= =
( )( )2
1
1 1 2
p
p
h h w Peh SV h w h h
+ = + - + =
- PARTITION WALL STUDS
Page 14 of 28
215 W 4th St
1/22/2025
(cont'd)
=0.00 <0.5 =0.10 <0.7
= 0.1017 <1.3 [Satisfactory]
CHECK COMPRESSION CAPACITY WITH, AT LEAST, ONE FLANGE THROUGH-FASTENED TO SHEATHING (AISI D6.1.3)
Pn/Wc =3.50 kips / stud >P [Satisfactory]
Where Wc = 1.8
Pn = C1C2C3 AE / 29500 = 6.30 kips / stud
C1 = (0.79 x + 0.54) =0.951
C2 = (1.17 a t + 0.93) =0.983
C3 = a (2.5b - 1.63d) + 22.8 =17.260
E = 29500 ksi (AISI pg xiv)
P = 0.43 kips / stud (included wall weight, 18psf.)
CHECK CAPACITY COMBINED AXIAL LOAD & BENDING (AISI C5.2.1)
0.66 <1.0 [Satisfactory]
Where M = 5.85 in-kips / stud, (1/1.4 included)
P = 0.43 kips / stud
Pn/Wc = 3.50 kips / stud
Mn/Wb = 11.6 in-kips / stud
Cm = 1.0
13.07 kips / stud
0.941
CHECK DEFLECTION
0.64 in <h /240 = 0.80 in [Satisfactory]
NOTE :1. STUD FLANGES SHALL BE FASTENED TO SHEATHING AT EACH SIDE OF WALL BEFORE VERTICAL LOAD ADDED.
Technical References:
1. AISI S100/SI-10, North American Specification for the Design of Cold-formed Steel Structural Members, with Supplement 1, 2010.
2. SSMA_Product_Technical_Guide, ESR-3064P, Steel Stud Manufactures Association, 2015.
0.6 M Vb v
VMn n
W W+
Mb
M n
W
Vv
V n
W
( )451
384
Sw L
EI xx
D = =
MPCbc m
P Mn na
WW+ =
( )
2
2
E I xPEx
K Lx x
p= =
1
Pc
P Ex
a W= - =
Page 15 of 28
215 W 4th St
1/22/2025
PROJECT : PAGE :
CLIENT : DESIGN BY :
JOB NO. : DATE: REVIEW BY :
INPUT DATA & DESIGN SUMMARY
SECTION & SPACING 350S162-43 (33 ksi)@ 16 in o.c
WALL HEIGHT h =1 ft
hp =2 ft
GRAVITY LOAD (ASD level) P =-175 lbs / ft
LATERAL LOAD (SD level) w1 =10 psf
PARAPET LOAD (SD level) w2 =10 psf
ECCENTRICITY e =0 in
DEFLECTION LIMITATION ?1 h /240
(0=No., 1= h /240, 2= h /360, 3= h /180, 4= h /120)
THE DESIGN IS ADEQUATE.
ANALYSIS
SECTION PROPERTIES OF EACH METAL STUD (SSMA page 8 to 14)
thk = 0.0451 in Fy = 33 ksi Ixx = 0.654 in4 Mn/Wb = 7.05 in-kips
t = 3.5 in Wt = 1.14 lb/ft Sxx = 0.357 in3 Vn/Wv = 631 lbs
A = 0.334 in2 rx = 1.4 in ry = 0.612 in xo = -1.312 in
J =0.000227 in4 Cw = 0.35 in6
CHECK MAX WEB DEPTH-TO-THICKNESS RATIO (AISI B1.2)
t / (thk) = 77.61 <200 [Satisfactory]
CHECK FLEXURAL CAPACITY (AISI C3.1)
Mn/Wb =7.05 in-kips / stud >M [Satisfactory]
Where -1.50 ft
0.18 in-kips / stud
S = 1.333 ft o.c., spacing as given.
0.32 in-kips / stud
M = (1/1.4) MAX( M1 , M2) = 0.23 in-kips / stud, (1/1.4 for wind/seismic, from AISI App. A4.1.2, typical)
CHECK SHEAR CAPACITY (AISI C3.2)
Vn/WV =631 lbs / stud >V [Satisfactory]
Where -20 lbs / stud
V2 = h w1 S - V1 =33 lbs / stud
V3 = hp w2 S = 27 lbs / stud
V = (1/1.4) MAX( V1 , V2 , V3) = 24 lbs / stud
CHECK CAPACITY COMBINED BENDING & SHEAR AT ROOF/FLOOR SECTION (AISI C3.3.1)
= 0.0497 <1.0 [Satisfactory]
Where M = 0.23 in-kips / stud, (1/1.4 included)
V = 24 lbs / stud, (1/1.4 included)
Vn/Wv = 631 lbs / stud, from SSMA page 8 to 14.
Mn/Wb =7.05 in-kips / stud, from SSMA page 8 to 14.
Wall Stud Design Based on AISI S100/SI-10 & ESR-3064P
( )2
12
p
p
h h Pex h h h h w
+ = + - - =
( )
2
1 2 2
1 2
1
1
22 p
wPe Sh hM
w h
= + - =
2
2
2 2
pw h SM= =
( )( )2
1
1 1 2
p
p
h h w Peh SV h w h h
+ = + - + =
- STEEL BRACE / TENSION LOAD
Page 16 of 28
215 W 4th St
1/22/2025
(cont'd)
=0.03 <0.5 =0.04 <0.7
= 0.0572 <1.3 [Satisfactory]
CHECK COMPRESSION CAPACITY WITH, AT LEAST, ONE FLANGE THROUGH-FASTENED TO SHEATHING (AISI D6.1.3)
Pn/Wc =3.70 kips / stud >P [Satisfactory]
Where Wc = 1.8
Pn = C1C2C3 AE / 29500 = 6.66 kips / stud
C1 = (0.79 x + 0.54) =0.959
C2 = (1.17 a t + 0.93) =0.983
C3 = a (2.5b - 1.63d) + 22.8 =21.145
E = 29500 ksi (AISI pg xiv)
P = -0.13 kips / stud (included wall weight, 18psf.)
CHECK CAPACITY COMBINED AXIAL LOAD & BENDING (AISI C5.2.1)
-0.02 <1.0 [Satisfactory]
Where M = 0.13 in-kips / stud, (1/1.4 included)
P = -0.13 kips / stud
Pn/Wc = 3.70 kips / stud
Mn/Wb = 7.05 in-kips / stud
Cm = 1.0
1322.32 kips / stud
1.000
CHECK DEFLECTION
0.00 in <h /240 = 0.05 in [Satisfactory]
NOTE :1. STUD FLANGES SHALL BE FASTENED TO SHEATHING AT EACH SIDE OF WALL BEFORE VERTICAL LOAD ADDED.
Technical References:
1. AISI S100/SI-10, North American Specification for the Design of Cold-formed Steel Structural Members, with Supplement 1, 2010.
2. SSMA_Product_Technical_Guide, ESR-3064P, Steel Stud Manufactures Association, 2015.
0.6 M Vb v
VMn n
W W+
Mb
M n
W
Vv
V n
W
( )451
384
Sw L
EI xx
D = =
MPCbc m
P Mn na
WW+ =
( )
2
2
E I xPEx
K Lx x
p= =
1
Pc
P Ex
a W= - =
Page 17 of 28
215 W 4th St
1/22/2025
PROJECT : PAGE :
CLIENT : DESIGN BY :
JOB NO. : DATE: REVIEW BY :
INPUT DATA & DESIGN SUMMARY
SECTION & SPACING 550S137-43 (33 ksi)@ 16 in o.c
WALL HEIGHT h =5 ft
hp =0 ft
GRAVITY LOAD (ASD level) P =150 lbs / ft
LATERAL LOAD (SD level) w1 =5 psf
PARAPET LOAD (SD level) w2 =5 psf
ECCENTRICITY e =0 in
DEFLECTION LIMITATION ?1 h /240
(0=No., 1= h /240, 2= h /360, 3= h /180, 4= h /120)
THE DESIGN IS ADEQUATE.
ANALYSIS
SECTION PROPERTIES OF EACH METAL STUD (SSMA page 8 to 14)
thk = 0.0451 in Fy = 33 ksi Ixx = 1.655 in4 Mn/Wb = 11.6 in-kips
t = 5.5 in Wt = 1.33 lb/ft Sxx = 0.592 in3 Vn/Wv = 1199 lbs
A = 0.391 in2 rx = 2.059 in ry = 0.467 in xo = -0.83 in
J =0.000265 in4 Cw = 0.52 in6
CHECK MAX WEB DEPTH-TO-THICKNESS RATIO (AISI B1.2)
t / (thk) = 121.95 <200 [Satisfactory]
CHECK FLEXURAL CAPACITY (AISI C3.1)
Mn/Wb =11.60 in-kips / stud >M [Satisfactory]
Where 2.50 ft
0.25 in-kips / stud
S = 1.333 ft o.c., spacing as given.
0.00 in-kips / stud
M = (1/1.4) MAX( M1 , M2) = 0.18 in-kips / stud, (1/1.4 for wind/seismic, from AISI App. A4.1.2, typical)
CHECK SHEAR CAPACITY (AISI C3.2)
Vn/WV =1199 lbs / stud >V [Satisfactory]
Where 17 lbs / stud
V2 = h w1 S - V1 =17 lbs / stud
V3 = hp w2 S = 0 lbs / stud
V = (1/1.4) MAX( V1 , V2 , V3) = 12 lbs / stud
CHECK CAPACITY COMBINED BENDING & SHEAR AT ROOF/FLOOR SECTION (AISI C3.3.1)
= 0.0099 <1.0 [Satisfactory]
Where M = 0.00 in-kips / stud, (1/1.4 included)
V = 12 lbs / stud, (1/1.4 included)
Vn/Wv = 1199 lbs / stud, from SSMA page 8 to 14.
Mn/Wb =11.6 in-kips / stud, from SSMA page 8 to 14.
Wall Stud Design Based on AISI S100/SI-10 & ESR-3064P
( )2
12
p
p
h h Pex h h h h w
+ = + - - =
( )
2
1 2 2
1 2
1
1
22 p
wPe Sh hM
w h
= + - =
2
2
2 2
pw h SM= =
( )( )2
1
1 1 2
p
p
h h w Peh SV h w h h
+ = + - + =
- STUDS BELOW SNEEZE GUARDS
Page 18 of 28
215 W 4th St
1/22/2025
(cont'd)
=0.00 <0.5 =0.01 <0.7
= 0.0099 <1.3 [Satisfactory]
CHECK COMPRESSION CAPACITY WITH, AT LEAST, ONE FLANGE THROUGH-FASTENED TO SHEATHING (AISI D6.1.3)
Pn/Wc =3.50 kips / stud >P [Satisfactory]
Where Wc = 1.8
Pn = C1C2C3 AE / 29500 = 6.30 kips / stud
C1 = (0.79 x + 0.54) =0.951
C2 = (1.17 a t + 0.93) =0.983
C3 = a (2.5b - 1.63d) + 22.8 =17.260
E = 29500 ksi (AISI pg xiv)
P = 0.26 kips / stud (included wall weight, 18psf.)
CHECK CAPACITY COMBINED AXIAL LOAD & BENDING (AISI C5.2.1)
0.09 <1.0 [Satisfactory]
Where M = 0.18 in-kips / stud, (1/1.4 included)
P = 0.26 kips / stud
Pn/Wc = 3.50 kips / stud
Mn/Wb = 11.6 in-kips / stud
Cm = 1.0
133.85 kips / stud
0.997
CHECK DEFLECTION
0.00 in <h /240 = 0.25 in [Satisfactory]
NOTE :1. STUD FLANGES SHALL BE FASTENED TO SHEATHING AT EACH SIDE OF WALL BEFORE VERTICAL LOAD ADDED.
Technical References:
1. AISI S100/SI-10, North American Specification for the Design of Cold-formed Steel Structural Members, with Supplement 1, 2010.
2. SSMA_Product_Technical_Guide, ESR-3064P, Steel Stud Manufactures Association, 2015.
0.6 M Vb v
VMn n
W W+
Mb
M n
W
Vv
V n
W
( )451
384
Sw L
EI xx
D = =
MPCbc m
P Mn na
WW+ =
( )
2
2
E I xPEx
K Lx x
p= =
1
Pc
P Ex
a W= - =
Page 19 of 28
215 W 4th St
1/22/2025
Load, f =20.00 plf
Screw spacing =8.00 in O.C.
H =26.00 in.
b =2.75 in.
e =4.00 in.
F = 20 plf * 8 in / 12 =13 Lbs.
M = 13 Lbs. * 26 in =346 in.-Lbs.
Use =5/8 in Dia. Screw
Grade:A36
Yield Limit:36 ksi
Fb = 0.66 * 36 ksi =23.76 ksi
Fv = 0.4 * 36 ksi =14.40 ksi
Section modulus = S = π * R3 /4 =0.02 in³
Bending Stress = fb = M/S =14436 Psi.
fb =14436 Psi.<Fb =23760 Psi.OK
Shear Stress = fv = F/A = F/(π*d2/4) =43 Psi.
fv =43 Psi.<Fv =14400 Psi.OK
126 Lbs.
Use =1 5/8" ø LAG SCREWS
WITHDRAWAL VALUE = w =447 Lbs/in * Per NDS 2018 Table 12.2A
EMBEDMENT =4 in
W = w*Pw = 447Lbs./in x 4in =1788 Lbs.
w =126 Lbs.<W =1788 Lbs.OK
Withdrawal = 346 in.-Lbs / 2.8 in =
Shear Stress
Withdrawal Design
GLASS SNEEZE GUARD CALCULATION
FASTENER VERIFICATION
Allowable Bending Stress
Allowable Shear Stress
Bending Stress
H
f
M
E
e
b
Page 20 of 28
215 W 4th St
1/22/2025
Appendix III
Floor Joist Calculations
Page 21 of 28
215 W 4th St
1/22/2025
Multiple Simple Beam
LIC# : KW-06017019, Build:20.23.08.30 ROMB STRUCTURAL ENGINEERING (c) ENERCALC INC 1983-2023
Project File: 215 W 4th.ec6
Project Title:215 W 4th St.
Engineer:ROMB
Project ID:24-186
Project Descr:
FLOOR JOISTS - PARTITION WALL / SNEEZE GUARD SUPPORT, BEAMDescription :
BEAM Size :2-2x8, Sawn, Fully Braced
Using Load Resistance Factor Design with ASCE 7-16 Load Combinations, Major Axis Bending
Wood Beam Design :
Calculations per NDS 2018, IBC 2018, CBC 2019, ASCE 7-16
Douglas Fir-Larch (North)No.2
875.0
875.0
600.0
625.0
1,300.0
470.0
170.0
425.0
30.590
Eminbend - xx ksi
Wood Species :Wood Grade :
Fb - Tension
psi
psi Fv psi
Fb - Compr Ft psi
Fc - Prll psi
psiFc - Perp
Ebend- xx ksi Density pcf
2-2x8 F.J. (longer joist) / PARTITION WALL ONLY
Applied Loads
Unif Load: D = 0.0140, L = 0.040 k/ft, Trib= 1.330 ft
Unif Load: D = 0.010 k/ft, Trib= 14.0 ft
.Design Summary
Max fb/Fb Ratio =0.593 : 1
Max Reactions (k)HEWSLLr
+1.20D+0.50Lr+1.60L+1.60HLoad Comb :
Span # 1
Left Support
D
in
4.625 inft
76.73 psi
Fb : Allowable :2,268.00 psi
Right Support
Fv : Allowable :Span # 1
Load Comb :+1.20D+0.50Lr+1.60L+1.60H
367.20 psi
fb : Actual :
Max fv/FvRatio =0.209 : 1 8.664 ft
1,345.22 psi at
atfv : Actual :
Ratio 9999 Ratio 9999
Max Deflections
Transient Downward 0.071 in
Transient Upward 0.000 in
Total Downward 0.283 in
Total Upward 0.000 in
0.73 0.250.73 0.25 Ratio 1560 391Ratio
LC: L Only LC: +D+L+H
LC:LC:
BEAM Size :2x8, Sawn, Fully Braced
Using Load Resistance Factor Design with ASCE 7-16 Load Combinations, Major Axis Bending
Wood Beam Design :
Calculations per NDS 2018, IBC 2018, CBC 2019, ASCE 7-16
Douglas Fir-Larch (North)No.2
875.0
875.0
600.0
625.0
1,300.0
470.0
170.0
425.0
30.590
Eminbend - xx ksi
Wood Species :Wood Grade :
Fb - Tension
psi
psi Fv psi
Fb - Compr Ft psi
Fc - Prll psi
psiFc - Perp
Ebend- xx ksi Density pcf
(E)2x8 F.J. (longer joist) / LOW WALL
Applied Loads
Unif Load: D = 0.0140, L = 0.040 k/ft, Trib= 1.330 ft
Unif Load: D = 0.010 k/ft, Trib= 2.820 ft
.Design Summary
Max fb/Fb Ratio =0.609 : 1
Max Reactions (k)HEWSLLr
+1.20D+0.50Lr+1.60L+1.60HLoad Comb :
Span # 1
Left Support
D
in
4.625 inft
78.72 psi
Fb : Allowable :2,268.00 psi
Right Support
Fv : Allowable :Span # 1
Load Comb :+1.20D+0.50Lr+1.60L+1.60H
367.20 psi
fb : Actual :
Max fv/FvRatio =0.214 : 1 8.664 ft
1,380.11 psi at
atfv : Actual :
Ratio 9999 Ratio 9999
Max Deflections
Transient Downward 0.142 in
Transient Upward 0.000 in
Total Downward 0.267 in
Total Upward 0.000 in
0.22 0.25
0.22 0.25 Ratio 780 414Ratio
LC: L Only LC: +D+L+H
LC:LC:
Page 22 of 28
215 W 4th St
1/22/2025
Multiple Simple Beam
LIC# : KW-06017019, Build:20.23.08.30 ROMB STRUCTURAL ENGINEERING (c) ENERCALC INC 1983-2023
Project File: 215 W 4th.ec6
Project Title:215 W 4th St.
Engineer:ROMB
Project ID:24-186
Project Descr:
BEAM Size :2x8, Sawn, Fully Braced
Using Load Resistance Factor Design with ASCE 7-16 Load Combinations, Major Axis Bending
Wood Beam Design :
Calculations per NDS 2018, IBC 2018, CBC 2019, ASCE 7-16
Douglas Fir-Larch (North)No.2
875.0
875.0
600.0
625.0
1,300.0
470.0
170.0
425.0
30.590
Eminbend - xx ksi
Wood Species :Wood Grade :
Fb - Tension
psi
psi Fv psi
Fb - Compr Ft psi
Fc - Prll psi
psiFc - Perp
Ebend- xx ksi Density pcf
(E)2x8 F.J. (longer joist) / LOW WALL + SNEEZE GUARD
Applied Loads
Unif Load: D = 0.0140, L = 0.040 k/ft, Trib= 1.330 ft
Unif Load: D = 0.010 k/ft, Trib= 2.820 ft
Unif Load: D = 0.010 k/ft, Trib= 2.170 ft
.Design Summary
Max fb/Fb Ratio =0.721 : 1
Max Reactions (k)HEWSLLr
+1.20D+0.50Lr+1.60L+1.60HLoad Comb :
Span # 1
Left Support
D
in
4.625 inft
93.23 psi
Fb : Allowable :2,268.00 psi
Right Support
Fv : Allowable :Span # 1
Load Comb :+1.20D+0.50Lr+1.60L+1.60H
367.20 psi
fb : Actual :
Max fv/FvRatio =0.254 : 1 8.664 ft
1,634.44 psi at
atfv : Actual :
Ratio 9999 Ratio 9999
Max Deflections
Transient Downward 0.142 in
Transient Upward 0.000 in
Total Downward 0.326 in
Total Upward 0.000 in
0.32 0.250.32 0.25 Ratio 780 341Ratio
LC: L Only LC: +D+L+H
LC:LC:
BEAM Size :2-2x8, Sawn, Fully Braced
Using Load Resistance Factor Design with ASCE 7-16 Load Combinations, Major Axis Bending
Wood Beam Design :
Calculations per NDS 2018, IBC 2018, CBC 2019, ASCE 7-16
Douglas Fir-Larch (North)No.2
875.0
875.0
600.0
625.0
1,300.0
470.0
170.0
425.0
30.590
Eminbend - xx ksi
Wood Species :Wood Grade :
Fb - Tension
psi
psi Fv psi
Fb - Compr Ft psi
Fc - Prll psi
psiFc - Perp
Ebend- xx ksi Density pcf
(E)2x8 F.J. (shorter joist) / PARTITION WALL ONLY
Applied Loads
Unif Load: D = 0.0140, L = 0.040 k/ft, Trib= 1.330 ft
Unif Load: D = 0.010 k/ft, Trib= 14.0 ft
.Design Summary
Max fb/Fb Ratio =0.316 : 1
Max Reactions (k)HEWSLLr
+1.20D+0.50Lr+1.60L+1.60HLoad Comb :
Span # 1
Left Support
D
in
3.375 inft
53.00 psi
Fb : Allowable :2,268.00 psi
Right Support
Fv : Allowable :Span # 1
Load Comb :+1.20D+0.50Lr+1.60L+1.60H
367.20 psi
fb : Actual :
Max fv/FvRatio =0.144 : 1 6.165 ft
716.34 psi at
atfv : Actual :
Ratio 9999 Ratio 9999
Max Deflections
Transient Downward 0.020 in
Transient Upward 0.000 in
Total Downward 0.080 in
Total Upward 0.000 in
0.54 0.180.54 0.18 Ratio 4015 1008Ratio
LC: L Only LC: +D+L+H
LC:LC:
Page 23 of 28
215 W 4th St
1/22/2025
Multiple Simple Beam
LIC# : KW-06017019, Build:20.23.08.30 ROMB STRUCTURAL ENGINEERING (c) ENERCALC INC 1983-2023
Project File: 215 W 4th.ec6
Project Title:215 W 4th St.
Engineer:ROMB
Project ID:24-186
Project Descr:
BEAM Size :2x8, Sawn, Fully Braced
Using Load Resistance Factor Design with ASCE 7-16 Load Combinations, Major Axis Bending
Wood Beam Design :
Calculations per NDS 2018, IBC 2018, CBC 2019, ASCE 7-16
Douglas Fir-Larch (North)No.2
875.0
875.0
600.0
625.0
1,300.0
470.0
170.0
425.0
30.590
Eminbend - xx ksi
Wood Species :Wood Grade :
Fb - Tension
psi
psi Fv psi
Fb - Compr Ft psi
Fc - Prll psi
psiFc - Perp
Ebend- xx ksi Density pcf
(N)2x8 F.J. (AT RAMP) - DIST. BETWEEN SUPPORTS
Applied Loads
Unif Load: D = 0.0140, L = 0.040 k/ft, Trib= 1.330 ft
.Design Summary
Max fb/Fb Ratio =0.010 : 1
Max Reactions (k)HEWSLLr
+1.20D+0.50Lr+1.60L+1.60HLoad Comb :
Span # 1
Left Support
D
in
0.665 inft
0.92 psi
Fb : Allowable :2,268.00 psi
Right Support
Fv : Allowable :Span # 1
Load Comb :+1.20D+0.50Lr+1.60L+1.60H
367.20 psi
fb : Actual :
Max fv/FvRatio =0.003 : 1 0.727 ft
21.70 psi at
atfv : Actual :
Ratio 9999 Ratio 9999
Max Deflections
Transient Downward 0.000 in
Transient Upward 0.000 in
Total Downward 0.000 in
Total Upward 0.000 in
0.01 0.040.01 0.04 Ratio 9999 9999Ratio
LC:LC:
LC:LC:
BEAM Size :2x8, Sawn, Fully Braced
Using Load Resistance Factor Design with ASCE 7-16 Load Combinations, Major Axis Bending
Wood Beam Design :
Calculations per NDS 2018, IBC 2018, CBC 2019, ASCE 7-16
Douglas Fir-Larch (North)No.2
875.0
875.0
600.0
625.0
1,300.0
470.0
170.0
425.0
30.590
Eminbend - xx ksi
Wood Species :Wood Grade :
Fb - Tension
psi
psi Fv psi
Fb - Compr Ft psi
Fc - Prll psi
psiFc - Perp
Ebend- xx ksi Density pcf
(N)2x8 F.J. (AT RAMP LANDING)
Applied Loads
Unif Load: D = 0.0140, L = 0.040 k/ft, Trib= 1.330 ft
.Design Summary
Max fb/Fb Ratio =0.135 : 1
Max Reactions (k)HEWSLLr
+1.20D+0.50Lr+1.60L+1.60HLoad Comb :
Span # 1
Left Support
D
in
2.500 inft
28.16 psi
Fb : Allowable :2,268.00 psi
Right Support
Fv : Allowable :Span # 1
Load Comb :+1.20D+0.50Lr+1.60L+1.60H
367.20 psi
fb : Actual :
Max fv/FvRatio =0.077 : 1 4.400 ft
306.67 psi at
atfv : Actual :
Ratio 9999 Ratio 9999
Max Deflections
Transient Downward 0.012 in
Transient Upward 0.000 in
Total Downward 0.016 in
Total Upward 0.000 in
0.05 0.130.05 0.13 Ratio 4940 3659Ratio
LC: L Only LC: +D+L+H
LC:LC:
Page 24 of 28
215 W 4th St
1/22/2025
Multiple Simple Beam
LIC# : KW-06017019, Build:20.23.08.30 ROMB STRUCTURAL ENGINEERING (c) ENERCALC INC 1983-2023
Project File: 215 W 4th.ec6
Project Title:215 W 4th St.
Engineer:ROMB
Project ID:24-186
Project Descr:
BEAM Size :4x8, Sawn, Fully Braced
Using Load Resistance Factor Design with ASCE 7-16 Load Combinations, Major Axis Bending
Wood Beam Design :
Calculations per NDS 2018, IBC 2018, CBC 2019, ASCE 7-16
Douglas Fir-Larch (North)No.2
875.0
875.0
600.0
625.0
1,300.0
470.0
170.0
425.0
30.590
Eminbend - xx ksi
Wood Species :Wood Grade :
Fb - Tension
psi
psi Fv psi
Fb - Compr Ft psi
Fc - Prll psi
psiFc - Perp
Ebend- xx ksi Density pcf
(N)4x8 BEAM AT RAMP
Applied Loads
Beam self weight calculated and added to loads
Unif Load: D = 0.0140, L = 0.040 k/ft, Trib= 4.50 ft
.Design Summary
Max fb/Fb Ratio =0.104 : 1
Max Reactions (k)HEWSLLr
+1.20D+0.50Lr+1.60L+1.60HLoad Comb :
Span # 1
Left Support
D
in
1.880 inft
33.36 psi
Fb : Allowable :2,457.00 psi
Right Support
Fv : Allowable :Span # 1
Load Comb :+1.20D+0.50Lr+1.60L+1.60H
367.20 psi
fb : Actual :
Max fv/FvRatio =0.091 : 1 3.400 ft
254.59 psi at
atfv : Actual :
Ratio 5944 Ratio 4308
Max Deflections
Transient Downward 0.006 in
Transient Upward -0.004 in
Total Downward 0.008 in
Total Upward -0.006 in
0.13 0.340.21 0.56 Ratio 7800 5652Ratio
LC: L Only LC: +D+L+H
LC: L Only LC: +D+L+H
Page 25 of 28
215 W 4th St
1/22/2025
Appendix IV
Pad Calculations
Page 26 of 28
215 W 4th St
1/22/2025
General Footing
LIC# : KW-06017019, Build:20.23.08.30 ROMB STRUCTURAL ENGINEERING (c) ENERCALC INC 1983-2023
DESCRIPTION:PAD AT RAMP
Project File: 215 W 4th.ec6
Project Title:215 W 4th St.
Engineer:ROMB
Project ID:24-186
Project Descr:
Code References
Calculations per ACI 318-14, IBC 2018, CBC 2019, ASCE 7-16
Load Combinations Used : IBC 2021
General Information
Material Properties Soil Design Values
1.50
Analysis Settings
100.0
ksi No
ksfAllowable Soil Bearing =
=
2.50
60.0
3,122.0
145.0
=0.250Flexure=0.90
Shear =
ValuesM
0.00180
Soil Passive Resistance (for Sliding)
1.0
=
Increases based on footing plan dimension
Add Pedestal Wt for Soil Pressure No:
Use Pedestal wt for stability, mom & shear No:
Allowable pressure increase per foot of depth
=ksfwhen max. length or width is greater than
=ft
:
=
Add Ftg Wt for Soil Pressure Yes
Yes:Use ftg wt for stability, moments & shears
when footing base is below ft
pcf Increase Bearing By Footing Weight
=pcf
Min. Overturning Safety Factor
=
: 1
Increases based on footing Depth0.750
=
Soil/Concrete Friction Coeff.
Ec : Concrete Elastic Modulus
=
=Footing base depth below soil surface ft
=Allow press. increase per foot of depth ksf
=
: 11.0Min. Sliding Safety Factor =
=
Concrete Density
=
Min Allow % Temp Reinf.
ksif'c : Concrete 28 day strength
fy : Rebar Yield ksi
Min Steel % Bending Reinf.
Soil Density =110.0 pcf
#
Dimensions
Width parallel to X-X Axis 1.50 ft
Length parallel to Z-Z Axis
=
1.50 ft
=Pedestal dimensions...
px : parallel to X-X Axis in
pz : parallel to Z-Z Axis in
Height ==
in
Footing Thickness
=
18.0 in=
Rebar Centerline to Edge of Concrete...
=inat Bottom of footing 3.0
Reinforcing
#
Bars parallel to X-X Axis
Reinforcing Bar Size
=
4
Number of Bars
=
4.0
Bars parallel to Z-Z Axis
Reinforcing Bar Size =4
Number of Bars =4
Bandwidth Distribution Check (ACI 15.4.4.2)
Direction Requiring Closer Separation
n/a
# Bars required within zone n/a
# Bars required on each side of zone n/a
Applied Loads
0.210 0.560
D Lr
ksf
L S
P : Column Load
OB : Overburden =
k
W E
M-zz
V-x
=
=k
V-z k
M-xx =
k-ft=
k-ft
H
=
Page 27 of 28
215 W 4th St
1/22/2025
General Footing
LIC# : KW-06017019, Build:20.23.08.30 ROMB STRUCTURAL ENGINEERING (c) ENERCALC INC 1983-2023
DESCRIPTION:PAD AT RAMP
Project File: 215 W 4th.ec6
Project Title:215 W 4th St.
Engineer:ROMB
Project ID:24-186
Project Descr:
PASS n/a Sliding - X-X 0.0 k 0.0 k No Sliding
PASS n/a Sliding - Z-Z 0.0 k 0.0 k No Sliding
DESIGN SUMMARY Design OK
Governing Load CombinationMin. Ratio Item Applied Capacity
PASS 0.3731 Soil Bearing 0.5597 ksf 1.50 ksf +D+L about Z-Z axis
PASS n/a Overturning - X-X 0.0 k-ft 0.0 k-ft No Overturning
PASS n/a Overturning - Z-Z 0.0 k-ft 0.0 k-ft No Overturning
PASS n/a Uplift 0.0 k 0.0 k No Uplift
PASS 0.004160 Z Flexure (+X)0.1435 k-ft/ft 34.494 k-ft/ft +1.20D+1.60L
PASS 0.004160 Z Flexure (-X)0.1435 k-ft/ft 34.494 k-ft/ft +1.20D+1.60L
PASS 0.004160 X Flexure (+Z)0.1435 k-ft/ft 34.494 k-ft/ft +1.20D+1.60L
PASS 0.004160 X Flexure (-Z)0.1435 k-ft/ft 34.494 k-ft/ft +1.20D+1.60L
PASS n/a 1-way Shear (+X)0.0 psi 75.0 psi n/a
PASS 0.0 1-way Shear (-X)0.0 psi 0.0 psi n/a
PASS n/a 1-way Shear (+Z)0.0 psi 75.0 psi n/a
PASS n/a 1-way Shear (-Z)0.0 psi 75.0 psi n/a
PASS n/a 2-way Punching 0.3755 psi 75.0 psi +1.20D+1.60L
Page 28 of 28
215 W 4th St
1/22/2025