Loading...
HomeMy WebLinkAbout2302 & 2304 W Cubbon St - 101118193 - Plan(E) DRIVEWAY AND IMPERVIOUS SURFACE (E) PORCH 104 SF PROPERTY LINE - 48.00' PR O P E R T Y L I N E - 1 0 3 . 9 3 ' (E) GARAGE 427 SF (E) 1-STORY MAIN UNIT 1,332 SF 3 BED/2 BATH PR O P E R T Y L I N E - 6 6 . 9 3 ' 15'-6" 28'-4" 5'-0" 15'-3" 8'-0"5'-0"50'-0" W CUBBON ST FI R E P L . (E ) G A S ME T E R (E) AC 22'-1" 4'-0" 8'-0" 30'-0" TO CENTERLINE 5'-0" 18'-9" 15'-1" 16'-3" 8'-0" (E) WATER METER 6'H METAL GATE 6'H METAL GATE ℄ ℄ 12'-0" (E) 6'H BLOCKWALL 4: 1 2 4: 1 2 4: 1 2 W McFADDEN AVE S D I A M O N D S T 18" (E) LIGHT POST ℄ FRONT YARD LANDSCAPING (PER S.A.M.C. SEC. 41-240) (E) 200A PANEL CHANGED TO 200A SUB-PANEL (N) AC (N) GAS LINE: 1" MDPE PRESSURE PIPE, 18" MIN. BELOW GROUND (N) ADU 749 SF 2 BED/2 BATH (N) WATER LINE: 1" COPPER TYPE "L" OR PVC PIPE, MIN. 18" BELOW GROUND (N ) P O R C H 40 S F (N) MAIN UNIT 200A PANEL ADDRESS NUMBER (N) 4" ABS SEWER LINE, MIN. 2% SLOPE (E ) 4 " S E W E R L I N E TO S T R E E T ( V . I . F . ) 4: 1 2 12" @ ADU 4: 1 2 11 SD-1 1-HR RATED OVERHANG R=15 R=2 5 5'-7" 31'-8" 12" 18" 12" 18'-3" 8'-7" 5'-0" 39'-0" PROPERTY LINE - 48.00' 5'-0" 43'-3" 11'-6" 8'-9" 9'-6" (E) 30"H BLOCKWALL 4'-3" (E) SHED TO BE REMOVED (N) 3/4" WATER METER (N ) G A S ME T E R (N) ADU 100A PANEL 6'-6" 4'-0" 5'-0" 10 SD-1 1-HR RATED OVERHANG IMAGINARY LINE 30'-0" TO CENTERLINE COVER TO BE REMOVED SOLAR ZONE 2 162 SF (27'x6') (N) ADU 749 SF (N ) P O R C H 40 S F SOLAR ZONE 1 90 SF (15'x6') 3'-2" 3'-2" 3'-0" 3'-0" 43'-3" 18'-3" ATTIC VENTILATION CALCULATION TOTAL ATTIC VENTILATION AREA SHALL NOT BE LESS THAN 1/150 OF THE ATTIC SPACE AREA. ADU ATTIC SPACE = 749 + 40 = 789 SF ATTIC VENTS REQUIRED = 789/150 = 5.3 SF ===> PROVIDE (6) OHAGINTM 16" DIAMETER ROOF VENTS (1.07 SF EACH), AS INDICATED ON ROOF PLAN HEREON PROJECT INFORMATION OWNER: NHI NGUYEN TEL.: (714) 818 3959 ADD.: MAIN UNIT: 2302 W CUBBON ST ADU: 2304 W CUBBON ST SANTA ANA, CA 92704 (E) MAIN UNIT = 1,332 SF (E) GARAGE = 427 SF (E) PORCH = 104 SF (N) ADU = 749 SF (EXEMPT FOR LOT COVERAGE) (N) ADU PORCH = 40 SF ADU sf / SFD sf = 749/1,332 = .56 LOT COVERAGE = 1,332 + 427 = 1,759 SF TOTAL LIVING AREA = 2,081 SF LOT SIZE = 6,760 SF % COVERAGE = 1,759/6,760 = 26.0% APN = 407-073-01 ZONE = R1 OCCUPANCY = R3 FLOOD ZONE = X NUMBER OF STORY = 1 TYPE OF CONSTRUCTION = VB (E) UNIT'S FIRE SPRINKLER = NOT EQUIPPED APPLICABLE BUILDING STANDARDS 1. 2022 CALIFORNIA MECHANICAL CODE (CMC) 2. 2022 CALIFORNIA BUILDING CODE (CBC) 3. 2022 CALIFORNIA RESIDENTIAL CODE (CRC) 4. 2022 CALIFORNIA PLUMBING CODE (CPC) 5. 2022 CALIFORNIA ELECTRICAL CODE (CEC) 6. 2022 CALIF. ENERGY EFFICIENCY STANDARD 7. 2022 CALIF. GREEN BUILDING STANDARDS 8. CITY OF SANTA ANA ORDINANCES DRAWING INDEX A1 SITE/ROOF PLAN - GENERAL NOTES SOLAR ZONE DEDICATION A2 EXISTING AND NEW FLOOR PLAN A3 ELEVATION - SECTION A4 DRAINAGE PLAN SN-1 STRUCTURAL GENERAL NOTES S-1 FOUNDATION PLAN - FRAMING PLAN SD-1 STRUCTURAL DETAILS T1-2 TITLE 24 PLAN T3-4 GREEN BUILDING STANDARDS CODE SCOPE OF WORK 1. BUILD NEW DETACHED 749 SF ADU (2 BEDROOM - 2 BATHROOM) WITH 40 SF FRONT PORCH 2. RELOCATE EXISTING 200 AMP. PANEL TO ADU 3. REMOVE EXISTING ATTACHED 400 SF COVER AND A GARDEN SHED CONSTRUCTION NOTES 1. CONSTRUCTION WORK HOURS ARE 7AM - 7PM, M-F; 9AM - 7PM, SATURDAY; NO SUNDAY OR LEGAL HOLIDAYS. 2. THERE SHALL BE NO TRENCHES OR EXCAVATIONS 5' OR MORE IN DEPTH INTO WHICH A PERSON IS REQUIRED TO DESCEND, OR OBTAIN PERMIT FROM STATE OF CA, DIVISION OF OCCUPATIONAL SAFETY AND HEALTH (CAL/OSHA). THIS PERMIT AND ANY OTHER SAFETY PERMIT SHALL BE OBTAINED PRIOR TO COMMENCE OF ANY WORK. VICINITY MAP ADU PARKING EXEMPTION NOTE PROPOSED ADU IS LOCATED WITHIN ONE-HALF MILE TO OCTA ROUTE 66 ALONG W McFADDEN AVE. AT S CENTER ST., PURSUANT TO ASSEMBLY BILL 68, NO PARKING IS REQUIRED FOR THE ADU. GENERAL NOTES 1. ALL WORK PERFORMED SHALL COMPLY WITH THESE GENERAL NOTES (UNLESS NOTED OTHERWISE ON THESE PLANS AND SPECIFICATIONS) AND ALL THE FOLLOWING NOTES, DRAWINGS AND SPECIFICATIONS. GENERAL CONTRACTOR SHALL COORDINATE THE INTENT OF GENERAL NOTES WITH MECHANICAL, ELECTRICAL, AND PLUMBING TRADES. 2. THE GENERAL CONTRACTOR OBTAINS AND PAYS FOR ALL REQUIRED PERMITS AND ARRANGES FOR ALL REQUIRED INSPECTIONS. 3. ALL WORK SHALL COMPLY WITH LATEST EDITION OF BUILDING CODES AS ADOPTED BY THE CITY OF SANTA ANA AND ALL OTHER APPLICABLE REGULATIONS. 4. DO NOT SCALE DRAWINGS. CONTRACTOR SHALL VERIFY ALL SITES CONDITIONS, DIMENSIONS AND ELEVATION BEFORE STARTING THE WORK, AND NOTIFY THE DESIGNER OF ANY DISCREPANCY, IN WRITING, PRIOR TO PROCEEDING. 5. IT SHALL BE THE CONTRACTOR'S RESPONSIBILITY TO LOCATE ALL EXISTING UTILITIES WHETHER SHOWN HEREON OR NOT AND TO PROTECT THEM FROM DAMAGE. THE CONTRACTOR SHALL BEAR ALL EXPENSES OF REPAIR OR REPLACEMENT IN CONJUNCTION WITH THE PROSECUTION OF SUCH WORK. 6. THE CONTRACTOR SHALL DETERMINE THE LOCATION OF THE UTILITY SERVICES IN THE AREA TO BE EXCAVATED PRIOR TO THE EXCAVATION. 7. THE DISCHARGE OF POLLUTANTS TO ANY STORM DRAINAGE SYSTEM IS PROHIBITED. NO SOLID WASTE, PETROLEUM BYPRODUCTS, SOIL PARTICULATE, CONSTRUCTION WASTE MATERIALS, OR WASTEWATER GENERATED ON CONSTRUCTION SITE OR BY THE CONSTRUCTION ACTIVITIES SHALL BE PLACED, CONVEYED OR DISCHARGED INTO THE STREET, GUTTER OR STORM DRAIN SYSTEM. 8. ALL NEW ROOF MATERIALS, STUCCO AND WINDOWS SHALL MATCH EXISTING COLOR AND STYLE. EMERGENCY EGRESS NOTES 1. MIN. SET CLEAR OPENING OF 5.7 SQUARE FEET. 2. MIN. 5 SQUARE FEET FOR GRADE-FLOOR OPENINGS 3. MIN. SET CLEAR HEIGHT OF 24 INCHES. 4. WINDOW TO BOTTOM OF CLEAR OPENING SHALL BE NO MORE THAN 44 INCHES. STUCCO NOTES 1. A CORROSION RESISTANT WEEP SCREED 2" BELOW PLATE, 6" (2" FOR CONCRETE WALKWAY) ABOVE GRADE THAT ALLOWS TRAPPED WATER TO DRAIN TO THE EXTERIOR OF THE BUILDING IS REQUIRED BELOW THE STUCCO AT THE FOUNDATION PLATE LINE. 2. 7/8" MIN. THICK THREE-COAT APPLICATION (SCRATCH, BROWN AND FINISH) OVER SELF-FURRING GALVANIZED WIRE LATH OVER GRADE D BUILDING PAPER AND WIRE BACKING. 3. EXTERIOR LATH: PROVIDE 2 LAYERS OF GRADE D PAPER OVER SHEATHING OR WOOD STUDS SETBACK AND PROPERTY LINE NOTE THE OWNER/CONTRACTOR SHALL CONSULT WITH A LAND SURVEYOR TO DETERMINE IF A LOT/BOUNDARY SURVEY IS NEEDED TO VERIFY SETBACKS OF EXISTING AND PROPOSED STRUCTURES WITH RESPECT TO PROPERTY LINES. IN THE EVENT THERE IS DISCREPANCY BETWEEN PROPOSAL AND FIELD MEASUREMENTS OF SETBACK, THE DESIGNER SHALL BE NOTIFIED; AND REVISION SHALL BE SUBMITTED FOR CITY APPROVAL. FRONT YARD NOTES 1. FRONT YARD LANDSCAPING SHALL COMPLY WITH S.A.M.C. SEC. 41-240. 2. LANDSCAPING AREAS SHALL BE DESIGNED WITH AN AUTOMATIC IRRIGATION SYSTEM WITH POP-UP SPRINKLERS. DRIP, BUBBLER OR OTHER LOW GALLONAGE SYSTEMS MAY BE USED IN BUFFER AREAS AND NARROW STRIPS. 3. FRONT YARD LANDSCAPING, IF NOT PRESENT, SHALL BE RESTORED WITH LIVE VEGETATION (GRASS OR ACCEPTABLE DRY CLIMATE GROUND COVER). 4.FENCE IN FRONT YARD SHALL COMPLY WITH S.A.M.C. SEC. 41-610 AND SHALL NOT EXCEED 3' IN HEIGHT. ELECTRICAL METER RELOCATION NOTE THE CONTRACTOR SHALL CONTACT SOUTHERN CALIFORNIA EDISON (SCE) @ 800-655-4555 TO OBTAIN A NEW METER SPOT APPROVAL AND INSTALLATION INSTRUCTIONS PRIOR TO INSTALLING THE NEW METER SERVICE PANEL. LOCATION AND AMPERAGE OF NEW METER IN THIS PLAN ARE ONLY PROPOSAL AND SUBJECT TO SCE FINAL APPROVAL. PHOTOVOLTAIC SYSTEM NOTE 1. A MINIMUM 2.04 KWdc PHOTOVOLTAIC SYSTEM (PER TITLE 24) SHALL BE INSTALLED ON THE ADU PRIOR TO FINAL INSPECTION SIGN-OFF. THE PV SYSTEM SHALL BE SUBMITTED UNDER A SEPARATE SUBMITTAL. 2. SOLAR PERMIT ISSUANCE IS REQUIRED PRIOR TO PERFORMING FRAMING INSPECTION. SITE/ROOF PLAN SCALE: 1/8" = 1'-0" SI T E P L A N RO O F P L A N GE N E R A L N O T E S SO L A R Z O N E DE D I C A T I O N OW N E R NH I N G U Y E N TE L : ( 7 1 4 ) 8 1 8 3 9 5 9 PR O J E C T A D D R E S S MA I N U N I T : 2 3 0 2 W C U B B O N S T AD U : 2 3 0 4 W C U B B O N S T SA N T A A N A , C A 9 2 7 0 4 DATE 10/10/2023 NE W D E T A C H E D 7 4 9 S F A D U (2 B E D R O O M - 2 B A T H R O O M ) SHEET A1 REVISION DATE BY 1 2 3 PROJECT ENGINEER BEN PHAN 10822 WOODWARD LN GARDEN GROVE, CA 92840 TEL: (714) 251 4537 LANDSCAPING LEGEND GRASS OR ACCEPTABLE DRY CLIMATE GROUND COVER POP-UP SPRINKLER NEW 5 GAL. JUNIPER BUSH (TYP. 10) NEW 1 GAL. ENCORE AZALEA (TYP. 11) FRUIT TREES ( VARIETY - MAX. 20' APART) NEW 24" BOX KING PALM OR SIMILAR, TREE SHALL BE DOUBLE-STAKED DIG ALERT (811) SHALL BE CONTACTED AND COMPLIANCE WITH EXCAVATION SAFETY IN ACCORDANCE WITH GOVERNMENT CODE 4216 SHALL BE FOLLOWED PRIOR TO ANY EXCAVATION TAKING PLACE SOLAR ZONE DEDICATION SCALE: 3/16" = 1'-0" PLANNING NOTE THE APPLICANT/PROPERTY OWNER SHALL BE RESPONSIBLE FOR CONFIRMING ALL EXISTING UTILITY EASEMENTS AND OR CLEARANCE ON-SITE THAT MAY AFFECT THE PROJECT. BUILDING NOTE THE ADU SF / SFD SF RATIO IS FOR PARK & RECREATION FEE PURPOSE ONLY. THE APPLICANT IS RESPONSIBLE FOR THE GIVEN "SFR SF" OF THE EXISTING PRIMARY RESIDENCE; BUILDING SAFETY STAFF ARE NOT RESPONSIBLE FOR THE ACCURACY OF THE GIVEN "SFR SF". Bldg# 101118192-93 APPROVALS: PLNG - ASevilla BLDG - JLo POLICE - BMartin 2302 & 2304 W Cubbon St - 1011181937/24/2024 43'-3" MA I N U N I T 20 0 A P A N E L 240V HEATPUMP INDOOR UNIT IN ATTIC 4'-6"LIVING AREA BEDROOM 1 PO R C H 15'-5" 2'-10" 9'-6" 8'-9" ATTIC ACCESS 30" x 30" BA T H 1 BEDROOM 2 KITCHEN 18'-3" TEMP. GLASS DINING AREA (N) AC CONDENSER ON 3" CONCRETE PAD STACKED W/DWH 1'-6" 1'-7" 3" 3" 10'-7"2'-0"10'-7" 29'-6"4'-3" 4'-11"5'-8"9'-6" 2'-6"7'-0" 30" 1,024 SI 30" 1,024 SI 1'-6" 1'-7"BA T H 2 3'-0" AD U 1 0 0 A PA N E L S-S S-SUFER (SEPARATE 1/2" DIA. REBAR, 20' LONG AT BOTTOM OF NEW FOOTING) CO SD SD CO $VS $ AFCI (TYP.) GFCI (TYP.)WR-GFCI AFCI (TYP.) GRAB BAR REINFORCEMENT, MIN. 2x8 LUMBER, 32"-39.25" ABOVE F.F. (TYP.) 30 AMP. 40 AMP. CO A T CL O S E T EGRESS WINDOW $ WR-GFCI MAX. 48" MEASURED FROM TOP, MIN. 15" MEASURED FROM BOTTOM OF BOX ABOVE F.F. (TYP.) $ AFCI (TYP.) $VS$ 30 AMP., LABELED "240V READY" ON BLANK COVER HOOD VENT THROUGH ROOF INSTALLED PER MANU. SPECS. HOOD SHALL COMPLY W/ ASHRAE 62.2(C) 50 AMP., LABELED "240V READY" ON BLANK COVER SD AFCI (TYP.)AFCI (TYP.) $3$3 $3D $3 $$ ESS READY 60A SUB-PANEL $D $D $D RESERVE SPACE FOR (2) DOUBLE POLE CIRCUIT BREAKERS FOR FUTURE ELECTRIC CLOTHES DRYER AND COOKTOP, MARKED AS "FOR FUTURE 240V USE" $$W/ D $ UL 2034/2075 RATED @ (E) HOUSE (TYP.) CO UL 217 RATED @ (E) HOUSE (TYP.) SD (N) 200 AMP. SUB-PANEL BEDROOM 1 LIVING AREA BEDROOM 2 BEDROOM 3 BATH 1 KITCHEN BATH 2 D W WH ATTIC ACCESS 48 " 4 8 " V I N Y L W I N D O W GARAGE FI R E P L A C E PORCH 15'-3" 50'-0" 72"36" VINYL WINDOW72"36" VINYL WINDOW 96"80" VINYL SLIDING DOOR 72 " 3 6 " V I N Y L W I N D O W 72 " 3 6 " V I N Y L W I N D O W 15.5'7' GARAGE DOOR W/ AUTO. OPENER 60"48" VINYL WINDOW 48"36" VINYL WINDOW 22'-1" 5'-7" 31'-8" 37'-3" 19'-0" 50'-0" 14'-9"16'-3" F. A . U . (E) AC SD CO SD SD SD COVER TO BE REMOVED (N) ADU FLOOR PLAN SCALE: 1/4" = 1'-0" NEW WALL, 2x4 STUDS @ 16" O.C. U.N.O. EXISTING STUD WALL WALL LEGEND CARBON MONOXIDE AND SMOKE DETECTOR NOTES SMOKE DETECTOR SHALL BE PROVIDED IN EACH SLEEPING ROOM AND AREA GIVING ACCESS TO THE SLEEPING ROOMS 1. NEW CONSTRUCTION: CO AND SMOKE DETECTORS SHALL RECEIVE THEIR PRIMARY POWER FROM BUILDING WIRING WITH BATTERY BACKUP. 2. EXISTING MAIN HOUSE: BATTERY POWERED UL 2034/2075 RATED CARBON MONOXIDE ALARM AND UL 217 RATED SMOKE ALARMS SHALL BE INSTALLED IN MARKED LOCATIONS. ELECTRICAL NOTES 1.PROVIDE ONE 20 AMP. CIRCUIT FOR BATHROOM OUTLETS. SUCH CIRCUIT SHALL HAVE NO OTHER OUTLETS. 2.PROVIDE 2 DEDICATED GENERAL APPLIANCE CIRCUITS TO THE KITCHEN AREA. 3.ALL INSTALLED LUMINAIRES MUST BE HIGH EFFICACY IN ACCORDANCE WITH TABLE 150.0-A. 4.ALL RECEPTACLES IN BATHROOMS SHALL BE G.F.C.I. 5.SERVICE PANEL/METER UPGRADE OR NEW: OBTAIN LOCATION APPROVAL FROM THE ELECTRICAL PROVIDER. 6.ALL BRANCH CIRCUITS SUPPLYING RECEPTACLE OUTLETS IN KITCHENS, BEDROOMS, FAMILY ROOMS, DINING ROOMS, LIVING ROOMS, PARLORS, DENS, SUNROOMS, HALLWAYS, CLOSETS AND SIMILAR ROOMS/AREAS SHALL BE PROTECTED BY AN ARC-FAULT CIRCUIT INTERRUPTER (AFCI). 7.NON-HIGH EFFICACY LUMINAIRES SHALL BE SWITCHED ON A SEPARATE CIRCUIT FROM HIGH EFFICACY LUMINAIRES. 8.ELECTRICAL OUTLET BOXES IN OPPOSITE FACES OF SEPARATION WALLS SHALL BE SEPARATED HORIZONTALLY BY 24" . BACK AND SIDES OF BOXES TO BE SEALED WITH 1/8" RESILIENT SEALANT AND BACKED WITH 2" MIN. MINERAL FIBER INSULATION. 9.ALL RECEPTACLE OUTLETS SHALL BE LISTED AS TAMPER-RESISTANT OUTLETS. 10.ALL OUTDOOR LIGHTING MOUNTED TO A RESIDENTIAL BUILDING SHALL BE HIGH EFFICACY LIGHTING OR CONTROLLED BY A PHOTOCELL AND MOTION SENSOR COMBINATION. PLUMBING NOTES 1.BATH FAN SHALL BE CONTROLLED BY HUMIDISTAT WITH ADJUSTMENT BETWEEN A RELATIVE HUMIDITY RANGE 50-80%. 2.SHOWER WALLS ABOVE BATHTUB WITH SHOWER HEADS SHALL BE FINISHED WITH A SMOOTH, NON-ABSORBENT SURFACE TO A HEIGHT NOT LESS THAN 6' ABOVE FLOOR. 3.SHOWER COMPARTMENT SHALL BE MINIMUM 1,024 SQ. IN. AND SHALL BE CAPABLE OF ENCOMPASSING A 30 IN. CIRCLE. 4.PROVIDE A 12"x12" MINIMUM ACCESS PANEL TO BATHTUB TRAP CONNECTION UNLESS PLUMBING IS WITHOUT SLIP JOINTS (CPC 405.2). 5.ALL TOILETS SHALL BE 1.28 GPF, SHOWERHEADS 2.0 GPM, AND FAUCETS 1.2 GPM, KITCHEN FAUCET 1.8 GPM. 6.FOR SHOWERS OR TUB-SHOWERS MAX. TEMPERATURE OF 120 DEGREE TO BE PROVIDED BY THE USE CONTROL VALVE PRESSURE BALANCE OR THERMOSTATIC MIXING VALVE. 7.ALL GLAZING IN ALL DOORS, BATH/SHOWER ENCLOSURES MUST BE IDENTIFIED BY A LABEL AS A SAFETY GLAZING. 8.WALL COVERING IN SHOWERS AND TUBS TO BE CEMENT PLASTER OR TILE EQUAL TO 72" ABOVE DRAIN. ENCLOSURES MUST BE OF APPROVED SAFETY GLAZING AND DOORS MUST SWING OUT OF SHOWERS. WINDOWS IN ENCLOSURE WALLS SHALL BE LABELED SAFETY GLAZING WHEN LESS THAN 60" ABOVE THE DRAIN, TYPICAL FOR ALL BATHROOMS. 9.GREEN BOARD GYPSUM OR WATER RESISTANT GYPSUM BOARD SHALL NOT BE USED AS BACKING FOR CEILING FINISH INSIDE BATHROOM DUE TO CONDENSATION OR VAPOR. 10.WATER HEATER: SIZE PER TITLE 24 WITH VENT THROUGH OUTSIDE. PROVIDE P&T RELIEF VALVE ON WATER HEATER. PROVIDE SMITTY PAN WITH DRAIN INSULATION/CLEARANCE PER MANUFACTURER SPECS. WATER HEATER TANK (IF USED) MUST BE ADEQUATELY BRACED TO RESIST SEISMIC FORCES: PROVIDE 2 STRAPS, 1 STRAP AT TOP 1/3 OF TANK AND 1 STRAP AT BOTTOM 1/3 OF THE TANK. 11.PLUMBING VENT TERMINATIONS SHALL BE AT LEAST 10' FROM FRESH AIR INTAKE OR VENTILATION. 12.B-VENTS SHALL TERMINATE AT LEAST 4' FROM FRESH AIR INTAKE OR VENTILATION. WINDOW SCHEDULE WINDOWS' U-FACTOR AND SHGC PER TITLE 24 SPECIFICATIONS. A 48"x48" SLIDING GLASS W/D, DUAL GLAZING, VINYL FRAME B 36"x48" SLIDING GLASS W/D, DUAL GLAZING, VINYL FRAME C 36"x36" SLIDING GLASS W/D, DUAL GLAZING, VINYL FRAME D 36"x18" S.L. FROSTED GLASS W/D, DUAL GLAZING, VINYL FRAME, TEMPERED GLASS DOOR SCHEDULE 1 30"x80" HOLLOW CORE DOOR 2 36"x80" SOLID CORE ENTRY DOOR W/ TEMPERED GLASS 3 30"x80" EXTERIOR RATED SOLID FRENCH DOOR 4 60"x80" CLOSET SLIDING DOOR 5 36"x80" DOOR WITH LOUVERS DETAILED HEREON FOR GAS DRYER MAKE-UP AIR BATHROOM NOTE CEMENT, FIBER CEMENT, FIBER-MAT REINFORCED CEMENT, GLASS MAT GYPSUM OR FIBER-REINFORCED GYPSUM BACKERS SHALL BE USED AS A BASE FOR WALL TILE IN TUB AND SHOWER AREAS AND WALL AND CEILING PANELS IN SHOWER AREAS. (E ) A N D ( N ) FL O O R P L A N SHEET A2 REVISION DATE BY 1 2 3 PROJECT ENGINEER BEN PHAN 10822 WOODWARD LN GARDEN GROVE, CA 92840 TEL: (714) 251 4537 SD LEGEND GFCI RECEPTACLE WR GFCI WEATHER RESISTANT RECEPTACLE TAMPER RESISTANT RECEPTACLE, 120V SINGLE PHASE, 20A, CONTROLLED BY ARC-FAULT CIRCUIT INTERRUPTER (AFCI) 240V, 30A (10 AWG COPPER) DEDICATED OUTLET FOR WATER HEATER CEILING-MOUNT RECESS LIGHT OUTDOOR WALL-MOUNT LIGHT FIXTURE W/ PHOTOCELL & MOTION SENSOR $LIGHT SWITCH WITH DIMMER (D) WHERE INDICATED $3 3-WAY LIGHT SWITCH WITH DIMMER (D) WHERE INDICATED $vs VACANCY SENSOR LIGHT SWITCH $W/D WASHER/DRYER DISCONNECT SWITCH, 20A, INSTALL PER MANU. SPECS. EXHAUST FAN (100 CFM MINIMUM) W/ HUMIDITY CONTROL IN-SINK DISPOSAL AIR REGISTER ON CEILING SMOKE DETECTOR CARBON MONOXIDE DETECTOR 4" DRYER VENT W/ DAMPER, TERMINATED 30" ABOVE F.F. ON OUTSIDE WALL 4" DRYER EXHAUST VENT W/ APPROVED WALL STRAP, TERMINATED ABOVE ROOF THROUGH APPROVED FLASHING, VENT 14' LONG MAX., 2 ELBOWS MAX. W/H 240V-50 GAL. WATER HEATER TANK, RHEEMTM MODEL XE50T10H22U W CLOTHES WASHER D CLOTHES DRYER HOSE BIB WITH ANTI-SIPHON VALVE AIR RETURN ON CEILING ROOF-MOUNT ATTIC VENT IAQ FAN (PER TITLE 24), 80 CFM MINIMUM CO 15" MIN. 48" MAX. F.F. ELEC. BOX HEIGHT N.T.S. AGING-IN-PLACE NOTES A. REINFORCEMENT FOR GRAB BARS - AT LEAST ONE BATHROOM ON THE ENTRY LEVEL SHALL BE PROVIDED WITH REINFORCEMENT INSTALLED IN ACCORDANCE WITH CRC R327.1. 1) REINFORCEMENT SHALL BE SOLID LUMBER OR OTHER CONSTRUCTION MATERIALS APPROVED BY THE ENFORCING AGENCY. 2) REINFORCEMENT SHALL NOT BE LESS THAN 2 BY 8 INCH NOMINAL LUMBER (1-1/2 INCH BY 7-1/4 INCH ACTUAL DIMENSION) OR OTHER CONSTRUCTION MATERIAL PROVIDING EQUAL HEIGHT AND LOAD CAPACITY. REINFORCEMENT SHALL BE LOCATED BETWEEN 32 INCHES AND 39-1/4 INCHES ABOVE THE FINISHED FLOOR, FLUSH WITH THE WALL FRAMING. 3) WATER CLOSET REINFORCEMENT SHALL BE INSTALLED ON BOTH SIDE WALLS OF THE FIXTURE, OR ONE SIDE WALL AND THE BACK WALL. 4) SHOWER REINFORCEMENT SHALL BE CONTINUOUS WHERE WALL FRAMING IS PROVIDED. 5) BATHTUB AND COMBINATION BATHTUB/SHOWER REINFORCEMENT SHALL BE CONTINUOUS ON EACH END OF THE BATHTUB AND THE BACK WALL. ADDITIONALLY, BACK WALL REINFORCEMENT FOR A LOWER GRAB BAR SHALL BE PROVIDED WITH THE BOTTOM EDGE LOCATED NO MORE THAN 6 INCHES ABOVE THE BATHTUB RIM. 6) WHERE THE WATER CLOSET IS NOT PLACED ADJACENT TO A SIDE WALL CAPABLE OF ACCOMMODATING A GRAB BAR, THE BATHROOM SHALL HAVE PROVISIONS FOR INSTALLATION OF FLOOR-MOUNTED, FOLDAWAY OR SIMILAR ALTERNATE GRAB BAR REINFORCEMENTS APPROVED BY THE ENFORCING AGENCY. 7) REINFORCEMENT SHALL NOT BE REQUIRED IN WALL FRAMING FOR PRE-FABRICATED SHOWER ENCLOSURES AND BATHTUB WALL PANELS WITH INTEGRAL FACTORY- INSTALLED GRAB BARS OR WHEN FACTORY-INSTALLED REINFORCEMENT FOR GRAB BARS IS PROVIDED. 8) SHOWER ENCLOSURES THAT DO NOT PERMIT INSTALLATION OF REINFORCEMENT AND/OR GRAB BARS SHALL BE PERMITTED, PROVIDED REINFORCEMENT FOR INSTALLATION OF FLOOR-MOUNTED GRAB BARS OR AN ALTERNATE METHOD IS APPROVED BY THE ENFORCING AGENCY. 9) BATHTUBS WITH NO SURROUNDING WALLS, OR WHERE WALL PANELS DO NOT PERMIT THE INSTALLATION OF REINFORCEMENT SHALL BE PERMITTED, PROVIDED REINFORCEMENT FOR INSTALLATION OF FLOOR-MOUNTED GRAB BARS ADJACENT TO THE BATHTUB OR AN ALTERNATE METHOD IS APPROVED BY THE ENFORCING AGENCY. 10) REINFORCEMENT OF FLOORS SHALL NOT BE REQUIRED FOR BATHTUBS AND WATER CLOSETS INSTALLED ON CONCRETE SLAB FLOORS. B. DOCUMENTATION FOR GRAB BAR REINFORCEMENT - INFORMATION AND/OR DRAWINGS IDENTIFYING THE LOCATION OF GRAB BAR REINFORCEMENT SHALL BE PLACED IN THE OPERATION AND MAINTENANCE MANUAL IN ACCORDANCE WITH THE CALIFORNIA GREEN BUILDING STANDARDS CODE, CHAPTER 4, DIVISION 4.4. (CRC R327.1.1.1) C. ELECTRICAL RECEPTACLE OUTLET, SWITCH AND CONTROL HEIGHTS - ELECTRICAL RECEPTACLE OUTLETS, SWITCHES AND CONTROLS (INCLUDING CONTROLS FOR HEATING, VENTILATION AND AIR CONDITIONING) INTENDED TO BE USED BY OCCUPANTS SHALL BE LOCATED NO MORE THAN 48 INCHES MEASURED FROM THE TOP OF THE OUTLET BOX AND NOT LESS THAN 15 INCHES MEASURED FROM THE BOTTOM OF THE OUTLET BOX ABOVE THE FINISH FLOOR. (CRC R327.1.2). EXCEPTIONS: 1) DEDICATED RECEPTACLE OUTLETS; FLOOR RECEPTACLE OUTLETS; CONTROLS MOUNTED ON CEILING FANS AND CEILING LIGHTS; AND CONTROLS LOCATED ON APPLIANCES. 2) RECEPTACLE OUTLETS REQUIRED BY THE CALIFORNIA ELECTRICAL CODE ON A WALL SPACE WHERE THE DISTANCE BETWEEN THE FINISHED FLOOR AND A BUILT-IN FEATURE ABOVE THE FINISH FLOOR, SUCH AS A WINDOW, IS LESS THAN 15 INCHES. D. DOORBELL BUTTONS - DOORBELL BUTTONS OR CONTROLS, WHEN INSTALLED, SHALL NOT EXCEED 48 INCHES (1219.2 MM) ABOVE EXTERIOR FLOOR OR LANDING, MEASURED FROM THE TOP OF THE DOORBELL BUTTON ASSEMBLY. WHERE DOORBELL BUTTONS INTEGRATED WITH OTHER FEATURES ARE REQUIRED TO BE INSTALLED ABOVE 48 INCHES (1219.2 MM) MEASURED FROM THE EXTERIOR FLOOR OR LANDING, A STANDARD DOORBELL BUTTON OR CONTROL SHALL ALSO BE PROVIDED AT A HEIGHT NOT EXCEEDING 48 INCHES (1219.2 MM) ABOVE EXTERIOR FLOOR OR LANDING, MEASURED FROM THE TOP OF THE DOORBELL BUTTON OR CONTROL. (CRC R327.1.4) WATER HEATER - DRYER - F.A.U. DOOR DETAIL N.T.S. (E) UNIT FLOOR PLAN SCALE: 3/16" = 1'-0" 18" 18" PER PLAN 100 SQ. IN. MIN. ON EACH LOUVER FOR COMBUSTION AIR (1 SQ. IN. PER 1,000 BTU/HR) 80" OW N E R NH I N G U Y E N TE L : ( 7 1 4 ) 8 1 8 3 9 5 9 PR O J E C T A D D R E S S MA I N U N I T : 2 3 0 2 W C U B B O N S T AD U : 2 3 0 4 W C U B B O N S T SA N T A A N A , C A 9 2 7 0 4 DATE 10/10/2023 NE W D E T A C H E D 7 4 9 S F A D U (2 B E D R O O M - 2 B A T H R O O M ) 2302 & 2304 W Cubbon St - 1011181937/24/2024 2302 2302-#2 (E) LIGHT BROWN COMPOSITION SHINGLE ROOF 14'-5" 15'-5" 12 4 12 4 12 4 12 4 FINISH FLOOR FINISH FLOOR FINISH CURB FINISH GRADE FINISH GRADE FINISH FLOOR FINISH FLOOR 15'-5" 15'-5" 18" 18" 12" OHAGINTM ATTIC VENTS 16" DIA., 1.07 SF (TYP.) EXTERIOR LANDING (3" DROP FROM DOOR THRESHOLD, 2% SLOPE) STUCCO TO MATCH EXISTING UNIT IN COLOR & TEXTURE NEW FASCIA & ROOF TO MATCH EXISTING HOUSE IN COLOR AND SIZE 3'D x 4.5'W EXTERIOR LANDING (3" DROP FROM DOOR THRESHOLD, 2% SLOPE) 9'-0" CEILING HEIGHT COOL ROOF REQUIRED, CRRC # 0676-0139, GAFTM CLASS A ASPHALT SHINGLES (ICC# ESR-1475) W/ DOUBLE LAYERS OF 30 LB. UNDERLAYMENT ON RADIANT BARRIER SHEATHING 12" 12" 5'-8" 2'-8" 12 4 12 4 12 4 12 4 FINISH GRADE FINISH GRADE FINISH FLOOR FINISH FLOOR FINISH FLOOR FINISH FLOOR 13'-3"13'-3" 13'-3" 12"12" 12" 9'-0" CEILING HEIGHT 12" 8'-9" (N) FOUNDATION (PER PLAN) (N) 5" CONC. SLAB O/ VAPOR BARRIER 2x8 C.J. @ 16" O.C. CLASS A ASPHALT SHINGLES (ICC# ESR-1475) W/ DOUBLE LAYERS OF 30 LB. UNDERLAYMENT 2x6 R.R. @ 16" O.C. 7/8" STUCCO OVER SHEARWALL WHERE OCCURS 9 SD-1 7/8" STUCCO (TYP.) 7 SD-1 1 SD-1 6 SD-1 4x6 HEADER D.F. #1 WINDOW (PER PLAN) R15 INSULATION 2x4 STUD @ 16" O.C. (TYP.) 13 SD-1 2 SD-1 7 SD-1 1 SD-1 6 SD-1 12 4 WHERE INDICATED WHERE INDICATED 2x8 RIDGE 10 SD-1 10 SD-1 R30 INSULATION R30 INSULATION 12" 9'-6" (E) MAIN UNIT - SOUTH ELEVATION SCALE: 1/8" = 1'-0" WINDOW NOTE NEW WINDOWS SHALL BE WHITE VINYL WITH GRILL BARS, FRAME FINISH FLUSHED WITH STUCCO. WINDOWS AND TRIMS SHALL MATCH BETWEEN (E) UNIT AND (N) ADU. EL E V A T I O N BU I L D I N G S E C T I O N ADDRESS NUMBER NOTE 1. THE ADDRESS NUMBER SHALL BE ARABIC NUMBERS OR ALPHABETICAL LETTERS, NUMBERS SHALL NOT BE SPELLED OUT. 2. EACH CHARACTER SHALL BE NOT LESS THAN 4" IN HEIGHT WITH A STROKE WIDTH OF NOT LESS THAN 0.5". SHEET A3 REVISION DATE BY 1 2 3 PROJECT ENGINEER BEN PHAN 10822 WOODWARD LN GARDEN GROVE, CA 92840 TEL: (714) 251 4537 (N) ADU - SOUTH ELEVATION SCALE: 1/8" = 1'-0" (N) ADU - NORTH ELEVATION SCALE: 1/8" = 1'-0" (N) ADU - WEST ELEVATION SCALE: 1/8" = 1'-0" (N) ADU - EAST ELEVATION SCALE: 1/8" = 1'-0" (E) MAIN UNIT - WEST ELEVATION SCALE: 1/8" = 1'-0" (E) MAIN UNIT - EAST ELEVATION SCALE: 1/8" = 1'-0" (E) MAIN UNIT - NORTH ELEVATION SCALE: 1/8" = 1'-0" SECTION S-S SCALE: 3/8" = 1'-0" OW N E R NH I N G U Y E N TE L : ( 7 1 4 ) 8 1 8 3 9 5 9 PR O J E C T A D D R E S S MA I N U N I T : 2 3 0 2 W C U B B O N S T AD U : 2 3 0 4 W C U B B O N S T SA N T A A N A , C A 9 2 7 0 4 DATE 10/10/2023 NE W D E T A C H E D 7 4 9 S F A D U (2 B E D R O O M - 2 B A T H R O O M ) ELEVATION NOTE ALL EXTERIOR FINISHES TO MATCH BETWEEN EXISTING MAIN HOUSE AND NEW ADU, INCLUDING TRIMS, COLORS, ROOFS, WINDOWS, DOORS, SIDING, ETC. 2302 & 2304 W Cubbon St - 1011181937/24/2024 (E) DRIVEWAY AND IMPERVIOUS SURFACE (E) PORCH PROPERTY LINE - 48.00' PR O P E R T Y L I N E - 1 0 3 . 9 3 ' (E) GARAGE (E) 1-STORY MAIN UNIT (F.F. = 10.00) PR O P E R T Y L I N E - 6 6 . 9 3 ' 15'-6" 28'-4" 11'-6" 15'-3" W CUBBON ST FI R E P L . 22'-1" 4'-0" 8'-0" 5'-0"18'-9"15'-1"16'-3"8'-0" 12'-0" W McFADDEN AVE S D I A M O N D S T (E) LIGHT POST (N) ADU F.F. = 10.41 (N ) P O R C H R=1 5 R=2 5 18'-3" 8'-7" 5'-0"39'-0" PROPERTY LINE - 48.00' 4'-3" (10.00 FF) (ASSUMED ELEVATION) i= 0 . 2 5 % F L i=0.25% FL i= 0 . 5 % F L i=0.5% FL 2% M I N 2% M I N 2% M I N 2% M I N 9. 4 1 F L i= 0 . 5 % F L 9.91 HAG 9. 5 2 F L 9.60 FS 9.55 FL 9.75 FS (E) PLANTER 9.65 FL 9.68 FS9.78 FS 2% MIN 2% MIN 2% MIN 2% MIN 9.58 FL 9.71 FL 9. 7 8 F L 9.86 FL HP9.86 FS 9.75 FS 2 1 DRAINAGE PLAN SCALE: 1/8" = 1'-0"DR A I N A G E P L A N OW N E R NH I N G U Y E N TE L : ( 7 1 4 ) 8 1 8 3 9 5 9 PR O J E C T A D D R E S S MA I N U N I T : 2 3 0 2 W C U B B O N S T AD U : 2 3 0 4 W C U B B O N S T SA N T A A N A , C A 9 2 7 0 4 DATE 10/10/2023 NE W D E T A C H E D 7 4 9 S F A D U (2 B E D R O O M - 2 B A T H R O O M ) SHEET A4 REVISION DATE BY 1 2 3 PROJECT ENGINEER BEN PHAN 10822 WOODWARD LN GARDEN GROVE, CA 92840 TEL: (714) 251 4537 DIG ALERT (811) SHALL BE CONTACTED AND COMPLIANCE WITH EXCAVATION SAFETY IN ACCORDANCE WITH GOVERNMENT CODE 4216 SHALL BE FOLLOWED PRIOR TO ANY EXCAVATION TAKING PLACE TYPICAL GRAVEL BAG DETAIL N.T.S. 1 EROSION CONTROL NOTES 1 INSTALL TYPICAL GRAVEL BAGS PER STD. SE-6, CALIFORNIA STORM WATER BMP HANDBOOK 2 INSTALL 10'x10' MATERIAL STOCKPILE AREA PER STANDARD WM-3 4" PCC 90% COMPACTED SUBGRADE WALKWAY SECTION N.T.S. 2302 & 2304 W Cubbon St - 1011181937/24/2024 Pr o j e c t N a m e Date Drawing Title Project Number DesignedDrawn DRAWING NUMBER Checked ANY DISCREPANCIES. DO NOT SCALE DRAWINGS; USE FIGURED DIMENSIONS. CONTRACTOR IS TO NOTIFY THE ENGINEER FOR CLARIFICATION OF OR EXISTING FIELD CONDITIONS AGAINST DRAWINGS. CONTRACTORS ARE TO VERIFY ALL DIMENSIONS ON DRAWINGS CALIFORNIA RELATING TO STRUCTURES AND BUILDINGS. RULES, REGULATIONS AND ORDINANCES OF THE STATE OF THE BEST OF MY KNOWLEDGE, THE SAME COMPLIES WITH THE HAS BEEN PREPARED UNDER MY SUPERVISION AND THAT TO I HEREBY CERTIFY THAT THE ENGINEERING ON THESE PLANS NO. DATE REVISION NE W D E T A C H E D A D U OW N E R : N H I N G U Y E N 23 0 4 W C U B B O N S T SA N T A A N A , C A 9 2 7 0 4 S-1 2302 & 2304 W Cubbon St - 1011181937/24/2024 24 23 20 16 12 08 19 15 07 04 03 14 10 06 05 02 011309 11 18 17 22 21 PIPING THRU PLATE FRAMING N.T.S. RIDGE DETAIL N.T.S. BEAM TO POST CONNECTION N.T.S. INTERIOR NON-BRG WALL @ CLG. N.T.S. SHEAR TRANSFER N.T.S. 2-2X CEILING JOISTS @ OPENING 2-2X BLKG AROUND EDGES HU2x-2 HANGER DTC CLIP 2x BLKG. @ 24" O.C. 1/2" CLR. DOUBLE PLATES STUD WALL JOIST OR 3 - 16d RAFTER JOISTS PARALLEL TO WALL PER JST JOISTS PERPENDICULAR TO WALL STUD WALL DTC CLIP 1/2" CLR.JST. OR RR DOUBLE PLATES HEEL CUT TO MATCH RR WHERE NEEDED POST PER PLAN BM. PER PLAN EAVE DETAIL (1-HR FIRE RATED) N.T.S. ATTIC OPENING DETAIL N.T.S. SHEAR TRANSFER N.T.S. PLASTER CREED N.T.S. EXTERIOR BEARING FOOTING N.T.S. NON-BEARING INTERIOR WALL N.T.S. SIMPSON HOLDOWN W/ SSTB BOLT N.T.S. SQUARE FOOTING N.T.S. LANDING DETAIL N.T.S. CONCRETE STEPS AND LANDING N.T.S. EAVE DETAIL (1-HR FIRE RATED) N.T.S. RAKE DETAIL (1-HR FIRE RATED) N.T.S. FOOTING CORNER & INTERSECTION N.T.S. STUD NOTCHING/BORING LIMIT N.T.S. WALL FRAMING N.T.S. PLATE SPLICING N.T.S. RAKE DETAIL (1-HR FIRE RATED) N.T.S. Pr o j e c t N a m e Date Drawing Title Project Number DesignedDrawn DRAWING NUMBER Checked ANY DISCREPANCIES. DO NOT SCALE DRAWINGS; USE FIGURED DIMENSIONS. CONTRACTOR IS TO NOTIFY THE ENGINEER FOR CLARIFICATION OF OR EXISTING FIELD CONDITIONS AGAINST DRAWINGS. CONTRACTORS ARE TO VERIFY ALL DIMENSIONS ON DRAWINGS CALIFORNIA RELATING TO STRUCTURES AND BUILDINGS. RULES, REGULATIONS AND ORDINANCES OF THE STATE OF THE BEST OF MY KNOWLEDGE, THE SAME COMPLIES WITH THE HAS BEEN PREPARED UNDER MY SUPERVISION AND THAT TO I HEREBY CERTIFY THAT THE ENGINEERING ON THESE PLANS NO. DATE REVISION NE W D E T A C H E D A D U OW N E R : N H I N G U Y E N 23 0 4 W C U B B O N S T SA N T A A N A , C A 9 2 7 0 4 SD-1 2302 & 2304 W Cubbon St - 1011181937/24/2024 DESIGN CRITERIA: Pr o j e c t N a m e Date Drawing Title Project Number DesignedDrawn DRAWING NUMBER Checked ANY DISCREPANCIES. DO NOT SCALE DRAWINGS; USE FIGURED DIMENSIONS. CONTRACTOR IS TO NOTIFY THE ENGINEER FOR CLARIFICATION OF OR EXISTING FIELD CONDITIONS AGAINST DRAWINGS. CONTRACTORS ARE TO VERIFY ALL DIMENSIONS ON DRAWINGS CALIFORNIA RELATING TO STRUCTURES AND BUILDINGS. RULES, REGULATIONS AND ORDINANCES OF THE STATE OF THE BEST OF MY KNOWLEDGE, THE SAME COMPLIES WITH THE HAS BEEN PREPARED UNDER MY SUPERVISION AND THAT TO I HEREBY CERTIFY THAT THE ENGINEERING ON THESE PLANS NO. DATE REVISION NE W D E T A C H E D A D U OW N E R : N H I N G U Y E N 23 0 4 W C U B B O N S T SA N T A A N A , C A 9 2 7 0 4 SN-1 2302 & 2304 W Cubbon St - 1011181937/24/2024 TI T L E 2 4 RE P O R T SHEET T1 REVISION DATE BY 1 2 3 PROJECT ENGINEER BEN PHAN 10822 WOODWARD LN GARDEN GROVE, CA 92840 TEL: (714) 251 4537 OW N E R NH I N G U Y E N TE L : ( 7 1 4 ) 8 1 8 3 9 5 9 PR O J E C T A D D R E S S MA I N U N I T : 2 3 0 2 W C U B B O N S T AD U : 2 3 0 4 W C U B B O N S T SA N T A A N A , C A 9 2 7 0 4 DATE 10/10/2023 NE W D E T A C H E D 7 4 9 S F A D U (2 B E D R O O M - 2 B A T H R O O M ) 2302 & 2304 W Cubbon St - 1011181937/24/2024 TI T L E 2 4 RE P O R T SHEET T2 REVISION DATE BY 1 2 3 PROJECT ENGINEER BEN PHAN 10822 WOODWARD LN GARDEN GROVE, CA 92840 TEL: (714) 251 4537 OW N E R NH I N G U Y E N TE L : ( 7 1 4 ) 8 1 8 3 9 5 9 PR O J E C T A D D R E S S MA I N U N I T : 2 3 0 2 W C U B B O N S T AD U : 2 3 0 4 W C U B B O N S T SA N T A A N A , C A 9 2 7 0 4 DATE 10/10/2023 NE W D E T A C H E D 7 4 9 S F A D U (2 B E D R O O M - 2 B A T H R O O M ) 2302 & 2304 W Cubbon St - 1011181937/24/2024 GR E E N B U I L D I N G ST A N D A R D S C O D E SHEET T3 REVISION DATE BY 1 2 3 PROJECT ENGINEER BEN PHAN 10822 WOODWARD LN GARDEN GROVE, CA 92840 TEL: (714) 251 4537 CHAPTER 4 RESIDENTIAL MANDATORY MEASURES DIVISION 4.1 PLANNING AND DESIGN DIVISION 4.3 WATER EFFICIENCY AND CONSERVATION 4.406 ENHANCED DURABILITY AND REDUCED MAINTENANCE 4.406.1 RODENT PROOFING. Annular spaces around pipes, electric cables, conduits or other openings in sole/bottom plates at exterior walls shall be protected against the passage of rodents by closing such openings with cement mortar, concrete masonry or a similar method acceptable to the enforcing agency. 4.408 CONSTRUCTION WASTE REDUCTION, DISPOSAL AND RECYCLING 4.408.1 CONSTRUCTION WASTE MANAGEMENT. Recycle and/or salvage for reuse a minimum of 65 percent of the non-hazardous construction and demolition waste in accordance with either Section 4.408.2, 4.408.3 or 4.408.4, or meet a more stringent local construction and demolition waste management ordinance. Exceptions: 1. Excavated soil and land-clearing debris. 2. Alternate waste reduction methods developed by working with local agencies if diversion or recycle facilities capable of compliance with this item do not exist or are not located reasonably close to the jobsite. 3. The enforcing agency may make exceptions to the requirements of this section when isolated jobsites are located in areas beyond the haul boundaries of the diversion facility. 4.408.2 CONSTRUCTION WASTE MANAGEMENT PLAN. Submit a construction waste management plan in conformance with Items 1 through 5. The construction waste management plan shall be updated as necessary and shall be available during construction for examination by the enforcing agency. 1. Identify the construction and demolition waste materials to be diverted from disposal by recycling, reuse on the project or salvage for future use or sale. 2. Specify if construction and demolition waste materials will be sorted on-site (source separated) or bulk mixed (single stream). 3. Identify diversion facilities where the construction and demolition waste material collected will be taken. 4. Identify construction methods employed to reduce the amount of construction and demolition waste generated. 5. Specify that the amount of construction and demolition waste materials diverted shall be calculated by weight or volume, but not by both. 4.408.3 WASTE MANAGEMENT COMPANY. Utilize a waste management company, approved by the enforcing agency, which can provide verifiable documentation that the percentage of construction and demolition waste material diverted from the landfill complies with Section 4.408.1. Note: The owner or contractor may make the determination if the construction and demolition waste materials will be diverted by a waste management company. 4.408.4 WASTE STREAM REDUCTION ALTERNATIVE [LR]. Projects that generate a total combined weight of construction and demolition waste disposed of in landfills, which do not exceed 3.4 lbs./sq.ft. of the building area shall meet the minimum 65% construction waste reduction requirement in Section 4.408.1 4.408.4.1 WASTE STREAM REDUCTION ALTERNATIVE. Projects that generate a total combined weight of construction and demolition waste disposed of in landfills, which do not exceed 2 pounds per square foot of the building area, shall meet the minimum 65% construction waste reduction requirement in Section 4.408.1 4.408.5 DOCUMENTATION. Documentation shall be provided to the enforcing agency which demonstrates compliance with Section 4.408.2, items 1 through 5, Section 4.408.3 or Section 4.408.4.. Notes: 1. Sample forms found in "A Guide to the California Green Building Standards Code (Residential)" located at www.hcd.ca.gov/CALGreen.html may be used to assist in documenting compliance with this section. 2. Mixed construction and demolition debris (C & D) processors can be located at the California Department of Resources Recycling and Recovery (CalRecycle). 4.410 BUILDING MAINTENANCE AND OPERATION 4.410.1 OPERATION AND MAINTENANCE MANUAL. At the time of final inspection, a manual, compact disc, web-based reference or other media acceptable to the enforcing agency which includes all of the following shall be placed in the building: 1. Directions to the owner or occupant that the manual shall remain with the building throughout the life cycle of the structure. 2. Operation and maintenance instructions for the following: a. Equipment and appliances, including water-saving devices and systems, HVAC systems, photovoltaic systems, electric vehicle chargers, water-heating systems and other major appliances and equipment. b. Roof and yard drainage, including gutters and downspouts. c. Space conditioning systems, including condensers and air filters. d. Landscape irrigation systems. e. Water reuse systems. 3. Information from local utility, water and waste recovery providers on methods to further reduce resource consumption, including recycle programs and locations. 4. Public transportation and/or carpool options available in the area. 5. Educational material on the positive impacts of an interior relative humidity between 30-60 percent and what methods an occupant may use to maintain the relative humidity level in that range. 6. Information about water-conserving landscape and irrigation design and controllers which conserve water. 7. Instructions for maintaining gutters and downspouts and the importance of diverting water at least 5 feet away from the foundation. 8. Information on required routine maintenance measures, including, but not limited to, caulking, painting, grading around the building, etc. 9. Information about state solar energy and incentive programs available. 10. A copy of all special inspections verifications required by the enforcing agency or this code. 11. Information from the Department of Forestry and Fire Protection on maintenance of defensible space around residential structures. 12. Information and/or drawings identifying the location of grab bar reinforcements. 4.410.2 RECYCLING BY OCCUPANTS. Where 5 or more multifamily dwelling units are constructed on a building site, provide readily accessible area(s) that serves all buildings on the site and are identified for the depositing, storage and collection of non-hazardous materials for recycling, including (at a minimum) paper, corrugated cardboard, glass, plastics, organic waster, and metals, or meet a lawfully enacted local recycling ordinance, if more restrictive. Exception: Rural jurisdictions that meet and apply for the exemption in Public Resources Code Section 42649.82 (a)(2)(A) et seq. are note required to comply with the organic waste portion of this section. DIVISION 4.4 MATERIAL CONSERVATION AND RESOURCE EFFICIENCY DIVISION 4.5 ENVIRONMENTAL QUALITY 4.303 INDOOR WATER USE 4.303.1 WATER CONSERVING PLUMBING FIXTURES AND FITTINGS. Plumbing fixtures (water closets and urinals) and fittings (faucets and showerheads) shall comply with the sections 4.303.1.1, 4.303.1.2, 4.303.1.3, and 4.303.4.4. Note: All noncompliant plumbing fixtures in any residential real property shall be replaced with water-conserving plumbing fixtures. Plumbing fixture replacement is required prior to issuance of a certificate of final completion, certificate of occupancy, or final permit approval by the local building department. See Civil Code Section 1101.1, et seq., for the definition of a noncompliant plumbing fixture, types of residential buildings affected and other important enactment dates. 4.303.1.1 Water Closets. The effective flush volume of all water closets shall not exceed 1.28 gallons per flush. Tank-type water closets shall be certified to the performance criteria of the U.S. EPA WaterSense Specification for Tank-type Toilets. Note: The effective flush volume of dual flush toilets is defined as the composite, average flush volume of two reduced flushes and one full flush. 4.303.1.2 Urinals. The effective flush volume of wall mounted urinals shall not exceed 0.125 gallons per flush. The effective flush volume of all other urinals shall not exceed 0.5 gallons per flush. 4.303.1.3 Showerheads. 4.303.1.3.1 Single Showerhead. Showerheads shall have a maximum flow rate of not more than 1.8 gallons per minute at 80 psi. Showerheads shall be certified to the performance criteria of the U.S. EPA WaterSense Specification for Showerheads. 4.303.1.3.2 Multiple showerheads serving one shower. When a shower is served by more than one showerhead, the combined flow rate of all the showerheads and/or other shower outlets controlled by a single valve shall not exceed 1.8 gallons per minute at 80 psi, or the shower shall be designed to only allow one shower outlet to be in operation at a time. Note: A hand-held shower shall be considered a showerhead. 4.303.1.4 Faucets. 4.303.1.4.1 Residential Lavatory Faucets. The maximum flow rate of residential lavatory faucets shall not exceed 1.2 gallons per minute at 60 psi. The minimum flow rate of residential lavatory faucets shall not be less than 0.8 gallons per minute at 20 psi. 4.303.1.4.2 Lavatory Faucets in Common and Public Use Areas. The maximum flow rate of lavatory faucets installed in common and public use areas (outside of dwellings or sleeping units) in residential buildings shall not exceed 0.5 gallons per minute at 60 psi. 4.303.1.4.3 Metering Faucets. Metering faucets when installed in residential buildings shall not deliver more than 0.2 gallons per cycle. 4.303.1.4.4 Kitchen Faucets. The maximum flow rate of kitchen faucets shall not exceed 1.8 gallons per minute at 60 psi. Kitchen faucets may temporarily increase the flow above the maximum rate, but not to exceed 2.2 gallons per minute at 60 psi, and must default to a maximum flow rate of 1.8 gallons per minute at 60 psi. Note: Where complying faucets are unavailable, aerators or other means may be used to achieve reduction. 4.303.1.4.5 Pre-rinse spray valves. When installed, shall meet the requirements in the California Code of Regulations, Title 20 (Appliance Efficiency Regulations), Sections 1605.1 (h)(4) Table H-2, Section 1605.3 (h)(4)(A), and Section 1607 (d)(7) and shall be equipped with an integral automatic shutoff. FOR REFERENCE ONLY: The following table and code section have been reprinted from the California Code of Regulations, Title 20 (Appliance Efficiency Regulations),Section 1605.1 (h)(4) and Section 1605.3 (h)(4)(A). Title 20 Section 1605.3 (h)(4)(A): Commercial prerinse spray values manufactured on or after January 1, 2006, shall have a minimum spray force of not less than 4.0 ounces-force (ozf)[113 grams-force(gf)] 4.303.2 Submeters for multifamily buildings and dwelling units in mixed-used residential/commercial buildings. Submeters shall be installed to measure water usage of individual rental dwelling units in accordance with the California Plumbing Code. 4.303.3 Standards for plumbing fixtures and fittings. Plumbing fixtures and fittings shall be installed in accordance with the California Plumbing Code, and shall meet the applicable standards referenced in Table 1701.1 of the California Plumbing Code. TABLE - MAXIMUM FIXTURE WATER USE FIXTURE TYPE FLOW RATE SHOWER HEADS (RESIDENTIAL)1.8 GMP @ 80 PSI LAVATORY FAUCETS (RESIDENTIAL)MAX. 1.2 GPM @ 60 PSI MIN. 0.8 GPM @ 20 PSI LAVATORY FAUCETS IN COMMON & PUBLIC USE AREAS 0.5 GPM @ 60 PSI KITCHEN FAUCETS 1.8 GPM @ 60 PSI METERING FAUCETS 0.2 GAL/CYCLE WATER CLOSET 1.28 GAL/FLUSH URINALS 0.125 GAL/FLUSH 4.304 OUTDOOR WATER USE 4.304.1 OUTDOOR POTABLE WATER USE IN LANDSCAPE AREAS. Residential developments shall comply with a local water efficient landscape ordinance or the current California Department of Water Resources' Model Water Efficient Landscape Ordinance (MWELO), whichever is more stringent. NOTES: 1. The Model Water Efficient Landscape Ordinance (MWELO) is located in the California Code Regulations, Title 23, Chapter 2.7, Division 2. MWELO and supporting documents, including water budget calculator, are available at: https://www.water.ca.gov/ ABBREVIATION DEFINITIONS: HCD Department of Housing and Community Development BSC California Building Standards Commission DSA-SS Division of the State Architect, Structural Safety OSHPD Office of Statewide Health Planning and Development LR Low Rise HR High Rise AA Additions and Alterations N New NOTE: THIS TABLE COMPILES THE DATA IN SECTION 4.303.1, AND IS INCLUDED AS A CONVENIENCE FOR THE USER. SECTION 4.102 DEFINITIONS 4.102.1 DEFINITIONS The following terms are defined in Chapter 2 (and are included here for reference) FRENCH DRAIN. A trench, hole or other depressed area loosely filled with rock, gravel, fragments of brick or similar pervious material used to collect or channel drainage or runoff water. WATTLES. Wattles are used to reduce sediment in runoff. Wattles are often constructed of natural plant materials such as hay, straw or similar material shaped in the form of tubes and placed on a downflow slope. Wattles are also used for perimeter and inlet controls. 4.106 SITE DEVELOPMENT 4.106.1 GENERAL. Preservation and use of available natural resources shall be accomplished through evaluation and careful planning to minimize negative effects on the site and adjacent areas. Preservation of slopes, management of storm water drainage and erosion controls shall comply with this section. 4.106.2 STORM WATER DRAINAGE AND RETENTION DURING CONSTRUCTION. Projects which disturb less than one acre of soil and are not part of a larger common plan of development which in total disturbs one acre or more, shall manage storm water drainage during construction. In order to manage storm water drainage during construction, one or more of the following measures shall be implemented to prevent flooding of adjacent property, prevent erosion and retain soil runoff on the site. 1. Retention basins of sufficient size shall be utilized to retain storm water on the site. 2. Where storm water is conveyed to a public drainage system, collection point, gutter or similar disposal method, water shall be filtered by use of a barrier system, wattle or other method approved by the enforcing agency. 3. Compliance with a lawfully enacted storm water management ordinance. Note: Refer to the State Water Resources Control Board for projects which disturb one acre or more of soil, or are part of a larger common plan of development which in total disturbs one acre or more of soil. (Website: https://www.waterboards.ca.gov/water_issues/programs/stormwater/construction.html) 4.106.3 GRADING AND PAVING. Construction plans shall indicate how the site grading or drainage system will manage all surface water flows to keep water from entering buildings. Examples of methods to manage surface water include, but are not limited to, the following: 1. Swales 2. Water collection and disposal systems 3. French drains 4. Water retention gardens 5. Other water measures which keep surface water away from buildings and aid in groundwater recharge. Exception: Additions and alterations not altering the drainage path. 4.106.4 Electric vehicle (EV) charging for new construction. New construction shall comply with Sections 4.106.4.1 or 4.106.4.2 to facilitate future installation and use of EV chargers. Electric vehicle supply equipment (EVSE) shall be installed in accordance with the California Electrical Code, Article 625. Exceptions: 1. On a case-by-case basis, where the local enforcing agency has determined EV charging and infrastructure are not feasible based upon one or more of the following conditions: 1.1 Where there is no local utility power supply or the local utility is unable to supply adequate power. 1.2 Where there is evidence suitable to the local enforcing agency substantiating that additional local utility infrastructure design requirements, directly related to the implementation of Section 4.106.4, may adversely impact the construction cost of the project. 2. Accessory Dwelling Units (ADU) and Junior Accessory Dwelling Units (JADU) without additional parking facilities. 4.106.4.1 New one- and two-family dwellings and townhouses with attached private garages. For each dwelling unit, install a listed raceway to accommodate a dedicated 208/240-volt branch circuit. The raceway shall not be less than trade size 1 (nominal 1-inch inside diameter). The raceway shall originate at the main service or subpanel and shall terminate into a listed cabinet, box or other enclosure in close proximity to the proposed location of an EV charger. Raceways are required to be continuous at enclosed, inaccessible or concealed areas and spaces. The service panel and/or subpanel shall provide capacity to install a 40-ampere 208/240-volt minimum dedicated branch circuit and space(s) reserved to permit installation of a branch circuit overcurrent protective device. Exemption: A raceway is not required if a minimum 40-ampere 208/240-volt dedicated EV branch circuit is installed in close proximity to the proposed location of an EV charger at the time of original construction in accordance with the California Electrical Code. 4.106.4.1.1 Identification. The service panel or subpanel circuit directory shall identify the overcurrent protective device space(s) reserved for future EV charging as "EV CAPABLE". The raceway termination location shall be permanently and visibly marked as "EV CAPABLE". CHAPTER 3 GREEN BUILDING SECTION 301 GENERAL 301.1 SCOPE. Buildings shall be designed to include the green building measures specified as mandatory in the application checklists contained in this code. Voluntary green building measures are also included in the application checklists and may be included in the design and construction of structures covered by this code, but are not required unless adopted by a city, county, or city and county as specified in Section 101.7. 301.1.1 Additions and alterations. [HCD] The mandatory provisions of Chapter 4 shall be applied to additions or alterations of existing residential buildings where the addition or alteration increases the building's conditioned area, volume, or size. The requirements shall apply only to and/or within the specific area of the addition or alteration. The mandatory provision of Section 4.106.4.2 may apply to additions or alterations of existing parking facilities or the addition of new parking facilities serving existing multifamily buildings. See Section 4.106.4.3 for application. Note: Repairs including, but not limited to, resurfacing, restriping and repairing or maintaining existing lighting fixtures are not considered alterations for the purpose of this section. Note: On and after January 1, 2014, residential buildings undergoing permitted alterations, additions, or improvements shall replace noncompliant plumbing fixtures with water-conserving plumbing fixtures. Plumbing fixture replacement is required prior to issuance of a certificate of final completion, certificate of occupancy or final permit approval by the local building department. See Civil Code Section 1101.1, et seq., for the definition of a noncompliant plumbing fixture, types of residential buildings affected and other important enactment dates. 301.2 LOW-RISE AND HIGH-RISE RESIDENTIAL BUILDINGS. [HCD] The provisions of individual sections of CALGreen may apply to either low-rise residential buildings high-rise residential buildings, or both. Individual sections will be designated by banners to indicate where the section applies specifically to low-rise only (LR) or high-rise only (HR). When the section applies to both low-rise and high-rise buildings, no banner will be used. SECTION 302 MIXED OCCUPANCY BUILDINGS 302.1 MIXED OCCUPANCY BUILDINGS. In mixed occupancy buildings, each portion of a building shall comply with the specific green building measures applicable to each specific occupancy. Exceptions: 1. [HCD] Accessory structures and accessory occupancies serving residential buildings shall comply with Chapter 4 and Appendix A4, as applicable. 2. [HCD] For purposes of CALGreen, live/work units, complying with Section 419 of the California Building Code, shall not be considered mixed occupancies. Live/Work units shall comply with Chapter 4 and Appendix A4, as applicable. 4.106.4.2 New multifamily dwellings, hotels and motels and new residential parking facilities. When parking is provided, parking spaces for new multifamily dwellings, hotels and motels shall meet the requirements of Sections 4.106.4.2.1 and 4.106.4.2.2. Calculations for spaces shall be rounded up to the nearest whole number. A parking space served by electric vehicle supply equipment or designed as a future EV charging space shall count as at least one standard automobile parking space only for the purpose of complying with any applicable minimum parking space requirements established by a local jurisdiction. See Vehicle Code Section 22511.2 for further details. 4.106.4.2.1Multifamily development projects with less than 20 dwelling units; and hotels and motels with less than 20 sleeping units or guest rooms. The number of dwelling units, sleeping units or guest rooms shall be based on all buildings on a project site subject to this section. 1.EV Capable. Ten (10) percent of the total number of parking spaces on a building site, provided for all types of parking facilities, shall be electric vehicle charging spaces (EV spaces) capable of supporting future Level 2 EVSE. Electrical load calculations shall demonstrate that the electrical panel service capacity and electrical system, including any on-site distribution transformer(s), have sufficient capacity to simultaneously charge all EVs at all required EV spaces at a minimum of 40 amperes. The service panel or subpanel circuit directory shall identify the overcurrent protective device space(s) reserved for future EV charging purposes as “EV CAPABLE” in accordance with the California Electrical Code. Exceptions: 1.When EV chargers (Level 2 EVSE) are installed in a number equal to or greater than the required number of EV capable spaces. 2.When EV chargers (Level 2 EVSE) are installed in a number less than the required number of EV capable spaces, the number of EV capable spaces required may be reduced by a number equal to the number of EV chargers installed. Notes: a.Construction documents are intended to demonstrate the project’s capability and capacity for facilitating future EV charging. b.There is no requirement for EV spaces to be constructed or available until receptacles for EV charging or EV chargers are installed for use. 2.EV Ready. Twenty-five (25) percent of the total number of parking spaces shall be equipped with low power Level 2 EV charging receptacles. For multifamily parking facilities, no more than one receptacle is required per dwelling unit when more than one parking space is provided for use by a single dwelling unit. Exception: Areas of parking facilities served by parking lifts. 4.106.4.2.2 Multifamily development projects with 20 or more dwelling units, hotels and motels with 20 or more sleeping units or guest rooms. The number of dwelling units, sleeping units or guest rooms shall be based on all buildings on a project site subject to this section. 1.EV Capable. Ten (10) percent of the total number of parking spaces on a building site, provided for all types of parking facilities, shall be electric vehicle charging spaces (EV spaces) capable of supporting future Level 2 EVSE. Electrical load calculations shall demonstrate that the electrical panel service capacity and electrical system, including any on-site distribution transformer(s), have sufficient capacity to simultaneously charge all EVs at all required EV spaces at a minimum of 40 amperes. The service panel or subpanel circuit directory shall identify the overcurrent protective device space(s) reserved for future EV charging purposes as “EV CAPABLE” in accordance with the California Electrical Code. Exception: When EV chargers (Level 2 EVSE) are installed in a number greater than five (5) percent of parking spaces required by Section 4.106.4.2.2, Item 3, the number of EV capable spaces required may be reduced by a number equal to the number of EV chargers installed over the five (5) percent required. Notes: a.Construction documents shall show locations of future EV spaces. b.There is no requirement for EV spaces to be constructed or available until receptacles for EV charging or EV chargers are installed for use. 2.EV Ready. Twenty-five (25) percent of the total number of parking spaces shall be equipped with low power Level 2 EV charging receptacles. For multifamily parking facilities, no more than one receptacle is required per dwelling unit when more than one parking space is provided for use by a single dwelling unit. Exception: Areas of parking facilities served by parking lifts. 3.EV Chargers. Five (5) percent of the total number of parking spaces shall be equipped with Level 2 EVSE. Where common use parking is provided, at least one EV charger shall be located in the common use parking area and shall be available for use by all residents or guests. When low power Level 2 EV charging receptacles or Level 2 EVSE are installed beyond the minimum required, an automatic load management system (ALMS) may be used to reduce the maximum required electrical capacity to each space served by the ALMS. The electrical system and any on-site distribution transformers shall have sufficient capacity to deliver at least 3.3 kW simultaneously to each EV charging station (EVCS) served by the ALMS. The branch circuit shall have a minimum capacity of 40 amperes, and installed EVSE shall have a capacity of not less than 30 amperes. ALMS shall not be used to reduce the minimum required electrical capacity to the required EV capable spaces. 4.106.4.2.2.1 Electric vehicle charging stations (EVCS). Electric vehicle charging stations required by Section 4.106.4.2.2, Item 3, shall comply with Section 4.106.4.2.2.1. Exception: Electric vehicle charging stations serving public accommodations, public housing, motels and hotels shall not be required to comply with this section. See California Building Code, Chapter 11B, for applicable requirements. 4.106.4.2.2.1.1 Location. EVCS shall comply with at least one of the following options: 1.The charging space shall be located adjacent to an accessible parking space meeting the requirements of the California Building Code, Chapter 11A, to allow use of the EV charger from the accessible parking space. 2.The charging space shall be located on an accessible route, as defined in the California Building Code, Chapter 2, to the building. Exception: Electric vehicle charging stations designed and constructed in compliance with the California Building Code, Chapter 11B, are not required to comply with Section 4.106.4.2.2.1.1 and Section 4.106.4.2.2.1.2, Item 3. 4.106.4.2.2.1.2 Electric vehicle charging stations (EVCS) dimensions. The charging spaces shall be designed to comply with the following: 1.The minimum length of each EV space shall be 18 feet (5486 mm). 2.The minimum width of each EV space shall be 9 feet (2743 mm). 3.One in every 25 charging spaces, but not less than one, shall also have an 8-foot (2438 mm) wide minimum aisle. A 5-foot (1524 mm) wide minimum aisle shall be permitted provided the minimum width of the EV space is 12 feet (3658 mm). a.Surface slope for this EV space and the aisle shall not exceed 1 unit vertical in 48 units horizontal (2.083 percent slope) in any direction. 4.106.4.2.2.1.3 Accessible EV spaces. In addition to the requirements in Sections 4.106.4.2.2.1.1 and 4.106.4.2.2.1.2, all EVSE, when installed, shall comply with the accessibility provisions for EV chargers in the California Building Code, Chapter 11B. EV ready spaces and EVCS in multifamily developments shall comply with California Building Code, Chapter 11A, Section 1109A. 4.106.4.2.3 EV space requirements. 1.Single EV space required. Install a listed raceway capable of accommodating a 208/240-volt dedicated branch circuit. The raceway shall not be less than trade size 1 (nominal 1-inch inside diameter). The raceway shall originate at the main service or subpanel and shall terminate into a listed cabinet, box or enclosure in close proximity to the location or the proposed location of the EV space. Construction documents shall identify the raceway termination point, receptacle or charger location, as applicable. The service panel and/ or subpanel shall have a 40-ampere minimum dedicated branch circuit, including branch circuit overcurrent protective device installed, or space(s) reserved to permit installation of a branch circuit overcurrent protective device. Exception: A raceway is not required if a minimum 40-ampere 208/240-volt dedicated EV branch circuit is installed in close proximity to the location or the proposed location of the EV space, at the time of original construction in accordance with the California Electrical Code. 2.Multiple EV spaces required. Construction documents shall indicate the raceway termination point and the location of installed or future EV spaces, receptacles or EV chargers. Construction documents shall also provide information on amperage of installed or future receptacles or EVSE, raceway method(s), wiring schematics and electrical load calculations. Plan design shall be based upon a 40-ampere minimum branch circuit. Required raceways and related components that are planned to be installed underground, enclosed, inaccessible or in concealed areas and spaces shall be installed at the time of original construction. SECTION 4.501 GENERAL 4.501.1 Scope The provisions of this chapter shall outline means of reducing the quality of air contaminants that are odorous, irritating and/or harmful to the comfort and well being of a building's installers, occupants and neighbors. SECTION 4.502 DEFINITIONS 5.102.1 DEFINITIONS The following terms are defined in Chapter 2 (and are included here for reference) AGRIFIBER PRODUCTS. Agrifiber products include wheatboard, strawboard, panel substrates and door cores, not including furniture, fixtures and equipment (FF&E) not considered base building elements. COMPOSITE WOOD PRODUCTS. Composite wood products include hardwood plywood, particleboard and medium density fiberboard. "Composite wood products" does not include hardboard, structural plywood, structural panels, structural composite lumber, oriented strand board, glued laminated timber, prefabricated wood I-joists or finger-jointed lumber, all as specified in California Code of regulations (CCR), title 17, Section 93120.1. DIRECT-VENT APPLIANCE. A fuel-burning appliance with a sealed combustion system that draws all air for combustion from the outside atmosphere and discharges all flue gases to the outside atmosphere. DISCLAIMER:THIS DOCUMENT IS PROVIDED AND INTENDED TO BE USED AS A MEANS TO INDICATE AREAS OF COMPLIANCE WITH THE CALIFORNIA GREEN BUILDING STANDARDS (CALGREEN) CODE. DUE TO THE VARIABLES BETWEEN BUILDING DEPARTMENT JURISDICTIONS, THIS CHECKLIST IS TO BE USED ON AN INDIVIDUAL PROJECT BASIS AND MAY BE MODIFIED BY THE END USER TO MEET THOSE INDIVIDUAL NEEDS. THE END USER ASSUMES ALL RESPONSIBILITY ASSOCIATED WITH THE USE OF THIS DOCUMENT, INCLUDING VERIFICATION WITH THE FULL CODE. Y N/AYN/AYN/AYN/A RESPON. PARTY RESPON. PARTY RESPON. PARTY RESPON. PARTY 2022 CALIFORNIA GREEN BUILDING STANDARDS CODE RESIDENTIAL MANDATORY MEASURES, SHEET 1 (January 2023)Y = YES N/A =NOT APPLICABLE RESPON. PARTY =RESPONSIBLE PARTY (ie: ARCHITECT, ENGINEER, OWNER, CONTRACTOR, INSPECTOR ETC.) 4.201 GENERAL 4.201.1 SCOPE. For the purposes of mandatory energy efficiency standards in this code, the California Energy Commission will continue to adopt mandatory standards. DIVISION 4.2 ENERGY EFFICIENCY TABLE H-2 STANDARDS FOR COMMERCIAL PRE-RINSE SPRAY VALUES MANUFACTURED ON OR AFTER JANUARY 28, 2019 PRODUCT CLASS [spray force in ounce force (ozf)]MAXIMUM FLOW RATE (gpm) Product Class 1 (≤1.00 Product Class 2 (> 5.0 ozf and ≤1.20 Product Class 3 (> 8.0 ozf)1.28 Exception: A raceway is not required if a minimum 40-ampere 208/240-volt dedicated EV branch circuit is installed in close proximity to the location or the proposed location of the EV space at the time of original construction in accordance with the California Electrical Code. 4.106.4.2.4 Identification. The service panel or subpanel circuit directory shall identify the overcurrent protective device space(s) reserved for future EV charging purposes as “EV CAPABLE” in accordance with the California Electrical Code. 4.106.4.2.5 Electric Vehicle Ready Space Signage. Electric vehicle ready spaces shall be identified by signage or pavement markings, in compliance with Caltrans Traffic Operations Policy Directive 13-01 (Zero Emission Vehicle Signs and Pavement Markings) or its successor(s). 4.106.4.3 Electric vehicle charging for additions and alterations of parking facilities serving existing multifamily buildings. When new parking facilities are added, or electrical systems or lighting of existing parking facilities are added or altered and the work requires a building permit, ten (10) percent of the total number of parking spaces added or altered shall be electric vehicle charging spaces (EV spaces) capable of supporting future Level 2 EVSE. Notes: 1.Construction documents are intended to demonstrate the project’s capability and capacity for facilitating future EV charging. 2.There is no requirement for EV spaces to be constructed or available until EV chargers are installed for use. OW N E R NH I N G U Y E N TE L : ( 7 1 4 ) 8 1 8 3 9 5 9 PR O J E C T A D D R E S S MA I N U N I T : 2 3 0 2 W C U B B O N S T AD U : 2 3 0 4 W C U B B O N S T SA N T A A N A , C A 9 2 7 0 4 DATE 10/10/2023 NE W D E T A C H E D 7 4 9 S F A D U (2 B E D R O O M - 2 B A T H R O O M ) 2302 & 2304 W Cubbon St - 1011181937/24/2024 GR E E N B U I L D I N G ST A N D A R D S C O D E SHEET T4 REVISION DATE BY 1 2 3 PROJECT ENGINEER BEN PHAN 10822 WOODWARD LN GARDEN GROVE, CA 92840 TEL: (714) 251 4537 MAXIMUM INCREMENTAL REACTIVITY (MIR). The maximum change in weight of ozone formed by adding a compound to the "Base Reactive Organic Gas (ROG) Mixture" per weight of compound added, expressed to hundredths of a gram (g O³/g ROC). Note: MIR values for individual compounds and hydrocarbon solvents are specified in CCR, Title 17, Sections 94700 and 94701. MOISTURE CONTENT. The weight of the water in wood expressed in percentage of the weight of the oven-dry wood. PRODUCT-WEIGHTED MIR (PWMIR). The sum of all weighted-MIR for all ingredients in a product subject to this article. The PWMIR is the total product reactivity expressed to hundredths of a gram of ozone formed per gram of product (excluding container and packaging). Note: PWMIR is calculated according to equations found in CCR, Title 17, Section 94521 (a). REACTIVE ORGANIC COMPOUND (ROC). Any compound that has the potential, once emitted, to contribute to ozone formation in the troposphere. VOC. A volatile organic compound (VOC) broadly defined as a chemical compound based on carbon chains or rings with vapor pressures greater than 0.1 millimeters of mercury at room temperature. These compounds typically contain hydrogen and may contain oxygen, nitrogen and other elements. See CCR Title 17, Section 94508(a). 4.503 FIREPLACES 4.503.1 GENERAL. Any installed gas fireplace shall be a direct-vent sealed-combustion type. Any installed woodstove or pellet stove shall comply with U.S. EPA New Source Performance Standards (NSPS) emission limits as applicable, and shall have a permanent label indicating they are certified to meet the emission limits. Woodstoves, pellet stoves and fireplaces shall also comply with applicable local ordinances. 4.504 POLLUTANT CONTROL 4.504.1 COVERING OF DUCT OPENINGS & PROTECTION OF MECHANICAL EQUIPMENT DURING CONSTRUCTION. At the time of rough installation, during storage on the construction site and until final startup of the heating, cooling and ventilating equipment, all duct and other related air distribution component openings shall be covered with tape, plastic, sheet metal or other methods acceptable to the enforcing agency to reduce the amount of water, dust or debris which may enter the system. 4.504.2 FINISH MATERIAL POLLUTANT CONTROL. Finish materials shall comply with this section. 4.504.2.1 Adhesives, Sealants and Caulks. Adhesives, sealant and caulks used on the project shall meet the requirements of the following standards unless more stringent local or regional air pollution or air quality management district rules apply: 1. Adhesives, adhesive bonding primers, adhesive primers, sealants, sealant primers and caulks shall comply with local or regional air pollution control or air quality management district rules where applicable or SCAQMD Rule 1168 VOC limits, as shown in Table 4.504.1 or 4.504.2, as applicable. Such products also shall comply with the Rule 1168 prohibition on the use of certain toxic compounds (chloroform, ethylene dichloride, methylene chloride, perchloroethylene and tricloroethylene), except for aerosol products, as specified in Subsection 2 below. 2. Aerosol adhesives, and smaller unit sizes of adhesives, and sealant or caulking compounds (in units of product, less packaging, which do not weigh more than 1 pound and do not consist of more than 16 fluid ounces) shall comply with statewide VOC standards and other requirements, including prohibitions on use of certain toxic compounds, of California Code of Regulations, Title 17, commencing with section 94507. 4.504.2.2 Paints and Coatings. Architectural paints and coatings shall comply with VOC limits in Table 1 of the ARB Architectural Suggested Control Measure, as shown in Table 4.504.3, unless more stringent local limits apply. The VOC content limit for coatings that do not meet the definitions for the specialty coatings categories listed in Table 4.504.3 shall be determined by classifying the coating as a Flat, Nonflat or Nonflat-High Gloss coating, based on its gloss, as defined in subsections 4.21, 4.36, and 4.37 of the 2007 California Air Resources Board, Suggested Control Measure, and the corresponding Flat, Nonflat or Nonflat-High Gloss VOC limit in Table 4.504.3 shall apply. 4.504.2.3 Aerosol Paints and Coatings. Aerosol paints and coatings shall meet the Product-weighted MIR Limits for ROC in Section 94522(a)(2) and other requirements, including prohibitions on use of certain toxic compounds and ozone depleting substances, in Sections 94522(e)(1) and (f)(1) of California Code of Regulations, Title 17, commencing with Section 94520; and in areas under the jurisdiction of the Bay Area Air Quality Management District additionally comply with the percent VOC by weight of product limits of Regulation 8, Rule 49. 4.504.2.4 Verification. Verification of compliance with this section shall be provided at the request of the enforcing agency. Documentation may include, but is not limited to, the following: 1. Manufacturer's product specification. 2. Field verification of on-site product containers. CHAPTER 7 INSTALLER & SPECIAL INSPECTOR QUALIFICATIONS 702 QUALIFICATIONS 702.1 INSTALLER TRAINING. HVAC system installers shall be trained and certified in the proper installation of HVAC systems including ducts and equipment by a nationally or regionally recognized training or certification program. Uncertified persons may perform HVAC installations when under the direct supervision and responsibility of a person trained and certified to install HVAC systems or contractor licensed to install HVAC systems. Examples of acceptable HVAC training and certification programs include but are not limited to the following: 1. State certified apprenticeship programs. 2. Public utility training programs. 3. Training programs sponsored by trade, labor or statewide energy consulting or verification organizations. 4. Programs sponsored by manufacturing organizations. 5. Other programs acceptable to the enforcing agency. 702.2 SPECIAL INSPECTION [HCD]. When required by the enforcing agency, the owner or the responsible entity acting as the owner's agent shall employ one or more special inspectors to provide inspection or other duties necessary to substantiate compliance with this code. Special inspectors shall demonstrate competence to the satisfaction of the enforcing agency for the particular type of inspection or task to be performed. In addition to other certifications or qualifications acceptable to the enforcing agency, the following certifications or education may be considered by the enforcing agency when evaluating the qualifications of a special inspector: 1. Certification by a national or regional green building program or standard publisher. 2. Certification by a statewide energy consulting or verification organization, such as HERS raters, building performance contractors, and home energy auditors. 3. Successful completion of a third party apprentice training program in the appropriate trade. 4. Other programs acceptable to the enforcing agency. Notes: 1. Special inspectors shall be independent entities with no financial interest in the materials or the project they are inspecting for compliance with this code. 2. HERS raters are special inspectors certified by the California Energy Commission (CEC) to rate homes in California according to the Home Energy Rating System (HERS). [BSC] When required by the enforcing agency, the owner or the responsible entity acting as the owner's agent shall employ one or more special inspectors to provide inspection or other duties necessary to substantiate compliance with this code. Special inspectors shall demonstrate competence to the satisfaction of the enforcing agency for the particular type of inspection or task to be performed. In addition, the special inspector shall have a certification from a recognized state, national or international association, as determined by the local agency. The area of certification shall be closely related to the primary job function, as determined by the local agency. Note: Special inspectors shall be independent entities with no financial interest in the materials or the project they are inspecting for compliance with this code. 703 VERIFICATIONS 703.1 DOCUMENTATION. Documentation used to show compliance with this code shall include but is not limited to, construction documents, plans, specifications, builder or installer certification, inspection reports, or other methods acceptable to the enforcing agency which demonstrate substantial conformance. When specific documentation or special inspection is necessary to verify compliance, that method of compliance will be specified in the appropriate section or identified applicable checklist. 4.505 INTERIOR MOISTURE CONTROL 4.505.1 General. Buildings shall meet or exceed the provisions of the California Building Standards Code. 4.505.2 CONCRETE SLAB FOUNDATIONS. Concrete slab foundations required to have a vapor retarder by California Building Code, Chapter 19, or concrete slab-on-ground floors required to have a vapor retarder by the California Residential Code, Chapter 5, shall also comply with this section. 4.505.2.1 Capillary break. A capillary break shall be installed in compliance with at least one of the following: 1. A 4-inch (101.6 mm) thick base of 1/2 inch (12.7mm) or larger clean aggregate shall be provided with a vapor barrier in direct contact with concrete and a concrete mix design, which will address bleeding, shrinkage, and curling, shall be used. For additional information, see American Concrete Institute, ACI 302.2R-06. 2. Other equivalent methods approved by the enforcing agency. 3. A slab design specified by a licensed design professional. 4.505.3 MOISTURE CONTENT OF BUILDING MATERIALS. Building materials with visible signs of water damage shall not be installed. Wall and floor framing shall not be enclosed when the framing members exceed 19 percent moisture content. Moisture content shall be verified in compliance with the following: 1. Moisture content shall be determined with either a probe-type or contact-type moisture meter.Equivalent moisture verification methods may be approved by the enforcing agency and shall satisfy requirements found in Section 101.8 of this code. 2. Moisture readings shall be taken at a point 2 feet (610 mm) to 4 feet (1219 mm) from the grade stamped end of each piece verified. 3. At least three random moisture readings shall be performed on wall and floor framing with documentation acceptable to the enforcing agency provided at the time of approval to enclose the wall and floor framing. Insulation products which are visibly wet or have a high moisture content shall be replaced or allowed to dry prior to enclosure in wall or floor cavities. Wet-applied insulation products shall follow the manufacturers' drying recommendations prior to enclosure. 4.506 INDOOR AIR QUALITY AND EXHAUST 4.506.1 Bathroom exhaust fans. Each bathroom shall be mechanically ventilated and shall comply with the following: 1. Fans shall be ENERGY STAR compliant and be ducted to terminate outside the building. 2. Unless functioning as a component of a whole house ventilation system, fans must be controlled by a humidity control. a. Humidity controls shall be capable of adjustment between a relative humidity range less than or equal to 50% to a maximum of 80%. A humidity control may utilize manual or automatic means of adjustment. b. A humidity control may be a separate component to the exhaust fan and is not required to be integral (i.e., built-in) Notes: 1. For the purposes of this section, a bathroom is a room which contains a bathtub, shower or tub/shower combination. 2. Lighting integral to bathroom exhaust fans shall comply with the California Energy Code. 4.507 ENVIRONMENTAL COMFORT 4.507.2 HEATING AND AIR-CONDITIONING SYSTEM DESIGN. Heating and air conditioning systems shall be sized, designed and have their equipment selected using the following methods: 1. The heat loss and heat gain is established according to ANSI/ACCA 2 Manual J - 2011 (Residential Load Calculation), ASHRAE handbooks or other equivalent design software or methods. 2. Duct systems are sized according to ANSI/ACCA 1 Manual D - 2014 (Residential Duct Systems), ASHRAE handbooks or other equivalent design software or methods. 3. Select heating and cooling equipment according to ANSI/ACCA 3 Manual S - 2014 (Residential Equipment Selection), or other equivalent design software or methods. Exception: Use of alternate design temperatures necessary to ensure the system functions are acceptable. TABLE 4.504.1 - ADHESIVE VOC LIMIT1,2 (Less Water and Less Exempt Compounds in Grams per Liter) ARCHITECTURAL APPLICATIONS VOC LIMIT INDOOR CARPET ADHESIVES 50 CARPET PAD ADHESIVES 50 OUTDOOR CARPET ADHESIVES 150 WOOD FLOORING ADHESIVES 100 RUBBER FLOOR ADHESIVES 60 SUBFLOOR ADHESIVES 50 CERAMIC TILE ADHESIVES 65 VCT & ASPHALT TILE ADHESIVES 50 DRYWALL & PANEL ADHESIVES 50 COVE BASE ADHESIVES 50 MULTIPURPOSE CONSTRUCTION ADHESIVE 70 STRUCTURAL GLAZING ADHESIVES 100 SINGLE-PLY ROOF MEMBRANE ADHESIVES 250 OTHER ADHESIVES NOT LISTED 50 SPECIALTY APPLICATIONS PVC WELDING 510 CPVC WELDING 490 ABS WELDING 325 PLASTIC CEMENT WELDING 250 ADHESIVE PRIMER FOR PLASTIC 550 CONTACT ADHESIVE 80 SPECIAL PURPOSE CONTACT ADHESIVE 250 STRUCTURAL WOOD MEMBER ADHESIVE 140 TOP & TRIM ADHESIVE 250 SUBSTRATE SPECIFIC APPLICATIONS METAL TO METAL 30 PLASTIC FOAMS 50 POROUS MATERIAL (EXCEPT WOOD)50 WOOD 30 FIBERGLASS 80 1. IF AN ADHESIVE IS USED TO BOND DISSIMILAR SUBSTRATES TOGETHER, THE ADHESIVE WITH THE HIGHEST VOC CONTENT SHALL BE ALLOWED. 2. FOR ADDITIONAL INFORMATION REGARDING METHODS TO MEASURE THE VOC CONTENT SPECIFIED IN THIS TABLE, SEE SOUTH COAST AIR QUALITY MANAGEMENT DISTRICT RULE 1168. TABLE 4.504.2 - SEALANT VOC LIMIT (Less Water and Less Exempt Compounds in Grams per Liter) SEALANTS VOC LIMIT ARCHITECTURAL 250 MARINE DECK 760 NONMEMBRANE ROOF 300 ROADWAY 250 SINGLE-PLY ROOF MEMBRANE 450 OTHER 420 SEALANT PRIMERS ARCHITECTURAL NON-POROUS 250 POROUS 775 MODIFIED BITUMINOUS 500 MARINE DECK 760 OTHER 750 TABLE 4.504.5 - FORMALDEHYDE LIMITS1 MAXIMUM FORMALDEHYDE EMISSIONS IN PARTS PER MILLION PRODUCT CURRENT LIMIT HARDWOOD PLYWOOD VENEER CORE 0.05 HARDWOOD PLYWOOD COMPOSITE CORE 0.05 PARTICLE BOARD 0.09 MEDIUM DENSITY FIBERBOARD 0.11 THIN MEDIUM DENSITY FIBERBOARD2 0.13 1. VALUES IN THIS TABLE ARE DERIVED FROM THOSE SPECIFIED BY THE CALIF. AIR RESOURCES BOARD, AIR TOXICS CONTROL MEASURE FOR COMPOSITE WOOD AS TESTED IN ACCORDANCE WITH ASTM E 1333. FOR ADDITIONAL INFORMATION, SEE CALIF. CODE OF REGULATIONS, TITLE 17, SECTIONS 93120 THROUGH 93120.12. 2. THIN MEDIUM DENSITY FIBERBOARD HAS A MAXIMUM THICKNESS OF 5/16" (8 MM). TABLE 4.504.3 - VOC CONTENT LIMITS FOR ARCHITECTURAL COATINGS2,3 GRAMS OF VOC PER LITER OF COATING, LESS WATER & LESS EXEMPT COMPOUNDS COATING CATEGORY VOC LIMIT FLAT COATINGS 50 NON-FLAT COATINGS 100 NONFLAT-HIGH GLOSS COATINGS 150 SPECIALTY COATINGS ALUMINUM ROOF COATINGS 400 BASEMENT SPECIALTY COATINGS 400 BITUMINOUS ROOF COATINGS 50 BITUMINOUS ROOF PRIMERS 350 BOND BREAKERS 350 CONCRETE CURING COMPOUNDS 350 CONCRETE/MASONRY SEALERS 100 DRIVEWAY SEALERS 50 DRY FOG COATINGS 150 FAUX FINISHING COATINGS 350 FIRE RESISTIVE COATINGS 350 FLOOR COATINGS 100 FORM-RELEASE COMPOUNDS 250 GRAPHIC ARTS COATINGS (SIGN PAINTS)500 HIGH TEMPERATURE COATINGS 420 INDUSTRIAL MAINTENANCE COATINGS 250 LOW SOLIDS COATINGS1 120 MAGNESITE CEMENT COATINGS 450 MASTIC TEXTURE COATINGS 100 METALLIC PIGMENTED COATINGS 500 MULTICOLOR COATINGS 250 PRETREATMENT WASH PRIMERS 420 PRIMERS, SEALERS, & UNDERCOATERS 100 REACTIVE PENETRATING SEALERS 350 RECYCLED COATINGS 250 ROOF COATINGS 50 RUST PREVENTATIVE COATINGS 250 SHELLACS CLEAR 730 OPAQUE 550 SPECIALTY PRIMERS, SEALERS & UNDERCOATERS 100 STAINS 250 STONE CONSOLIDANTS 450 SWIMMING POOL COATINGS 340 TRAFFIC MARKING COATINGS 100 TUB & TILE REFINISH COATINGS 420 WATERPROOFING MEMBRANES 250 WOOD COATINGS 275 WOOD PRESERVATIVES 350 ZINC-RICH PRIMERS 340 1. GRAMS OF VOC PER LITER OF COATING, INCLUDING WATER & EXEMPT COMPOUNDS 2. THE SPECIFIED LIMITS REMAIN IN EFFECT UNLESS REVISED LIMITS ARE LISTED IN SUBSEQUENT COLUMNS IN THE TABLE. 3. VALUES IN THIS TABLE ARE DERIVED FROM THOSE SPECIFIED BY THE CALIFORNIA AIR RESOURCES BOARD, ARCHITECTURAL COATINGS SUGGESTED CONTROL MEASURE, FEB. 1, 2008. MORE INFORMATION IS AVAILABLE FROM THE AIR RESOURCES BOARD. DIVISION 4.5 ENVIRONMENTAL QUALITY (continued) 4.504.3 CARPET SYSTEMS. All carpet installed in the building interior shall meet the requirements of the California Department of Public Health, "Standard Method for the Testing and Evaluation of Volatile Organic Chemical Emissions from Indoor Sources Using Environmental Chambers," Version 1.2, January 2017 (Emission testing method for California Specification 01350) See California Department of Public Health's website for certification programs and testing labs. https://www.cdph.ca.gov/Programs/CCDPHP/DEODC/EHLB/IAQ/Pages/VOC.aspx. 4.504.3.1 Carpet cushion. All carpet cushion installed in the building interior shall meet the requirements of the California Department of Public Health, "Standard Method for the Testing and Evaluation of Volatile Organic Chemical Emissions from Indoor Sources Using Environmental Chambers," Version 1.2, January 2017 (Emission testing method for California Specification 01350) See California Department of Public Health's website for certification programs and testing labs. https://www.cdph.ca.gov/Programs/CCDPHP/DEODC/EHLB/IAQ/Pages/VOC.aspx. 4.504.3.2 Carpet adhesive. All carpet adhesive shall meet the requirements of Table 4.504.1. 4.504.4 RESILIENT FLOORING SYSTEMS. Where resilient flooring is installed , at least 80% of floor area receiving resilient flooring shall meet the requirements of the California Department of Public Health, "Standard Method for the Testing and Evaluation of Volatile Organic Chemical Emissions from Indoor Sources Using Environmental Chambers," Version 1.2, January 2017 (Emission testing method for California Specification 01350) See California Department of Public Health's website for certification programs and testing labs. hhtps://www.cdph.ca.gov/Programs/CCDPHP/DEODC/EHLB/IAQ/Pages/VOC.aspx. 4.504.5 COMPOSITE WOOD PRODUCTS. Hardwood plywood, particleboard and medium density fiberboard composite wood products used on the interior or exterior of the buildings shall meet the requirements for formaldehyde as specified in ARB's Air Toxics Control Measure for Composite Wood (17 CCR 93120 et seq.), by or before the dates specified in those sections, as shown in Table 4.504.5 4.504.5.1 Documentation. Verification of compliance with this section shall be provided as requested by the enforcing agency. Documentation shall include at least one of the following: 1. Product certifications and specifications. 2. Chain of custody certifications. 3. Product labeled and invoiced as meeting the Composite Wood Products regulation (see CCR, Title 17, Section 93120, et seq.). 4. Exterior grade products marked as meeting the PS-1 or PS-2 standards of the Engineered Wood Association, the Australian AS/NZS 2269, European 636 3S standards, and Canadian CSA 0121, CSA 0151, CSA 0153 and CSA 0325 standards. 5. Other methods acceptable to the enforcing agency. DISCLAIMER:THIS DOCUMENT IS PROVIDED AND INTENDED TO BE USED AS A MEANS TO INDICATE AREAS OF COMPLIANCE WITH THE CALIFORNIA GREEN BUILDING STANDARDS (CALGREEN) CODE. DUE TO THE VARIABLES BETWEEN BUILDING DEPARTMENT JURISDICTIONS, THIS CHECKLIST IS TO BE USED ON AN INDIVIDUAL PROJECT BASIS AND MAY BE MODIFIED BY THE END USER TO MEET THOSE INDIVIDUAL NEEDS. THE END USER ASSUMES ALL RESPONSIBILITY ASSOCIATED WITH THE USE OF THIS DOCUMENT, INCLUDING VERIFICATION WITH THE FULL CODE. Y N/AYN/AYN/AYN/A RESPON. PARTY RESPON. PARTY RESPON. PARTY RESPON. PARTY 2022 CALIFORNIA GREEN BUILDING STANDARDS CODE RESIDENTIAL MANDATORY MEASURES, SHEET 2 (January 2023)Y = YES N/A =NOT APPLICABLE RESPON. PARTY =RESPONSIBLE PARTY (ie: ARCHITECT, ENGINEER, OWNER, CONTRACTOR, INSPECTOR ETC.) OW N E R NH I N G U Y E N TE L : ( 7 1 4 ) 8 1 8 3 9 5 9 PR O J E C T A D D R E S S MA I N U N I T : 2 3 0 2 W C U B B O N S T AD U : 2 3 0 4 W C U B B O N S T SA N T A A N A , C A 9 2 7 0 4 DATE 10/10/2023 NE W D E T A C H E D 7 4 9 S F A D U (2 B E D R O O M - 2 B A T H R O O M ) 2302 & 2304 W Cubbon St - 1011181937/24/2024 O R A N G E C O U N T Y F I R E A U T H O R I T Y Plan Submittal Criteria Form Required for Single Family or Duplex Residences (Use Commercial form for lots with 3+ dwelling units or new residential tracts) Complete the Project Information and Questionnaire below, then sign and date the Applicant Certification. Project Information  New Single Family Residence/Duplex  Addition/Remodel  ADU  Other Address: Unit #: City or Unincorporated County Area: ZIP: Scope of Work: Existing Area: Area to be Added: Total Resulting Area: Stories: Area Added in Past 2 Years (excluding this project): Yes No Questionnaire OCFA Plan Type if “Yes” 1.   New – Is this a new single family residence or duplex? *(PR160) Residential Site with Water Availability (PR400-402) Fire Sprinkler 2.   ADU – Is this a new Accessory Dwelling Unit (ADU) on the same property as a house that already has fire sprinklers or a house that will have fire sprinklers added as part of this project? (PR400-402) Fire Sprinkler 3.   Addition – Is this (A) an addition to a currently sprinklered building, or (B) an addition requiring a fire sprinkler retrofit based on a threshold set by local ordinance? (PR400-402) Fire Sprinkler 4.   Distance – Is the most remote portion of the addition, ADU or other detached structure greater than 140-feet from the fire access roadway? *(PR160) Residential Site 5.   Total Area – Will the addition result in a total area of greater than 3,600 square feet (sf) for non- sprinklered buildings, or greater than 6,200 sf for sprinklered buildings, including the area of all enclosed spaces, such as garages, stairs, and detached structures separated by less than 10-feet? *(PR160) Residential Site with Water Availability 6.   Remodel – Is this a remodel of a sprinklered building with a scope of work that includes adding or removing any interior walls? Note: If “Yes”, then project must be evaluated by a C-16 licensed contractor to determine if a fire sprinkler modification is needed. (PR400-402) Fire Sprinkler 7.   Detached Structure – Is this a new detached utility or accessory structure (not an ADU), such as a garage, workshop, game room, pool house, barn, etc., requiring fire sprinklers based on a threshold set by local ordinance? *(PR160) Residential Site (PR400-402) Fire Sprinkler 8.   Gate – Is a gate being installed across a driveway or road that is designated as a fire department access roadway, or a driveway or road that serves more than a single home/duplex? (PR180) Gate 9.   Methane – Is project located in or less than 100’ from a “Division of Oil, Gas, and Geothermal Resources” (DOGGR) field boundary or well (active or abandoned), less than 300-feet from an oil/gas seep, or less than 1000-feet from a landfill? (Note: For projects in Yorba Linda, this requirement only applies to new homes, enclosed accessory structures, addition to existing structure greater than 1000 sf, and ADU’s). *(PR160) Residential Site *(PR172-174) Methane Test/Mitigation Plans 10.   Vegetation – Is the property/structure (A) on the perimeter of a community containing, or adjacent to slopes or hills, or (B) adjacent to an open space or wildland area containing non-irrigated vegetation, or (C) in a State Responsibility Area or Local Responsibility Area “Fire Hazard Severity Zone”, as defined by the State, or (D) near an area that could be affected by a wildfire in the open space. *(PR125) Fuel Modification (PR182) Accessory Structure *OCFA approval required before issuance of a grading/building permit. All other plans types may be deferred submittals. Applicant Certification I certify, under penalty of perjury, under the laws of the State of California, that the information above is true: Print Name:_______________________________________ Signature:___________________________________________ Date:______________ Phone Number:_____________________________________________ Email:_____________________________________________________________ Attention Building Department Staff – After you’ve verified all questions were answered accurately as “No”, then you may accept this signed form as a written release that an OCFA review is not required. If any questions were answered as “Yes”, then the plan type on the right side may be required. ______If all answers are “No” and the Building Department still requires the applicant to have their plans reviewed by OCFA, or if any answers are “Yes” and the Building Department prefers for OCFA to determine if a review is required, please initial this line and provide an explanation on the Plan Referral Form (on the reverse), to be submitted along with the appropriate plans to OCFA for a determination. For questions and submittal information, please visit ocfa.org, or call OCFA at (714) 573-6100 SFR 2302 & 2304 W Cubbon St - 1011181937/24/2024 O R A N G E C O U N T Y F I R E A U T H O R I T Y Plan Referral Form Required for OCFA to review plans upon the request of the Building Department when the answers on the Plan Submittal Criteria Form (on the reverse) are all “No”. City Official Requesting Review: City Reference #: __________________________ City / County: _____________________________________ Date: __________________________________ Contact Name: _____________________________________ E-Mail: __________________________________ Title: _____________________________________ Phone #: _________________________________ ** Have the applicant complete and sign the OCFA Plan Submittal Criteria Form on the reverse of this form. ** Reason(s) for Review: Please describe why OCFA Plan Review is or may be required by the City/County: OCFA COMMENTS:  No further action required on this specific plan type, based on information provided on: ____/______/______.  Project to be taken in for OCFA Review. Other: Name: _________________________________________ Contact #: ______________________________________ Date: _________________________________ OCFA Authorization Updated: 06/02/2020 rs 2302 & 2304 W Cubbon St - 1011181937/24/2024 2302 & 2304 W Cubbon St - 1011181937/24/2024 2302 & 2304 W Cubbon St - 1011181937/24/2024 STRUCTURAL CALCULATIO NS Date: 0 112 11202 4 Project Location: Owner : Prepared by: Building Code Edition: Concrete: Foundation: Structural Steel : Pipe Columns : Welding: Concrete Masonry: Grout: Reinforcing Steel : Wood Framing: Studs , joists, rafters: Beams and posts: Glulam : Parallam 2 .0 PSL: Microllam LVL : Plywood : TJI: 2304 W . Cubbon St., Santa Ana, CA 92704 Nhi Nguyen (Luan) New Accessory Dwelling Un it ADU Ben Phan , P.E. (714) 251-4537 11541 Elizabeth Street Garden Grove , CA 92840 2022 California Building Code f' c = 2,500 psi @ 28 days Ready-mixed concrete per ASTM C94 Concrete aggregates per ASTM C33 Cement ASMT C150 Type V u.n.o . Minimum allowable soil bearing pressure= 1,500 psf. ASTM A-36 , ASTM a-92 ASTM A-53 , Grade B Electric arc process by certified welders in approved licensed fabrication shop. ASTM C90 , GradeN , f m = 1,500 psi Type M, 1:3:1/4 mix; Cement:Sand:Hydrated Lime or Lime Putty. I :3 :2 mix; Cement:Sand :3/8" pea gravel; f c = 2,000 psi. Deformed bars per ASTM A915 ; Grade 40 for #4 and smaller ; Grade 60 for #5 and larger. WCLffi or WWP A Grading Rules Agency Douglas Fir-Larch #2 Douglas Fir-Larch #1 24F-V4 or 24F-V8 DF/DF (cantilevered) ICC ESR-1387 ICC ESR-1387 4 or more plies , Structural 1 or CD , CC Structural Panel per PS-1-95 ICC ESR-1153 (!Level) All information shown on plans relative to existing conditions are provided as the best present knowledge but without guarantee of accuracy . Where actual conditions conflict with the plans , they shall be reported to the Engineer so that modifications may be made in writing. Modifications of plans and details shall not be made without written approval of the Engineer . By accepting this calculations or report, the Engineer s hall not be held liable for discrepancies not brought up to the attention of the Engineer. The design analysis and calculations were done in accordance with generally accepted engineering principles and practice . 2302 & 2304 W Cubbon St - 1011181937/24/2024 DESIGN LIVE AND DEAD LOADS ROOF DEAD LOAD : ROOF TYPE 1 FLAT LOAD: ROOFTYPE2 Comp. Shingles Roofing = 6.0 PSF RR Comp. Shingles Roofing = 3.0 PSF Sheathing/Insulation = 1.5 PSF RR Sheathing/Insulation = 1.5 PSF 2X RR@ 16" OC = 2.0 PSF RR 2X RR@ 16" OC = 3.0 PSF 2X CJ@ 16" OC = 2.0 PSF CJ = 0.0 PSF Drywall Ceiling = 2.2 PSF CJ = 0.0 PSF MPE = 1.0 PSF CJ MPE = 1.0 PSF Future Solar System = 3.0 PSF CJ = 0.0 PSF MISCELLANEOUS = 1.3 PSF CJ MISCELLANEOUS = 1.5 PSF SUB-TOTAL = 19.0 PSF SUB-TOTAL = 10.0 PSF SLOPE CORRECTION "X:12 " I 4.00 I 1.05 PSF SLOPE CORRECTION "X:12" ~ 1.00 PSF MISCELLANEOUS = O.Oj PSF MISCELLANEOUS o.oj PSF ROOF DEAD LOAD : = 20.0 PSF ROOF DEAD LOAD : = 10.0 PSF ROOF SNOW LOAD : = §PSF ROOF SNOW LOAD : = § PSF ROOF LIVE LOAD : = PSF ROOF LIVE LOAD : = PSF TOTAL ROOF LOAD : = PSF TOTAL ROOF LOAD : = PSF EXTERIOR WALL LOADS: SECOND FLOOR LOADS Stucco = 10.0 PSF Finish flooring = 0.0 PSF 15/32" SHEATHING = 1.4 PSF 3/4" subflooring = 0.0 PSF 2X4@16" OIC = 2.0 P$F 2x12@ 16" oc = 0.0 PSF R191NSULATION = 0.4 PSF Int. non-brg wall = 0.0 PSF 112" GYPSUM BD. = 2.2 PSF 1/2" gypsum board = 0.0 PSF MISCELLANEOUS = 1.0 PSF R19, M/P/E, & others = 0.0 PSF TOTAL EXTERIOR WALL : = 17.0 PSF FLOOR DEAD LOAD : = 0.0 PSF FLOOR LIVE LOAD : = 40 .0 PSF TOTAL FLOOR LOAD = 40.0 PSF INTERIOR SHEAR WALL LOADS: FIRST FLOOR LOADS 1/2" GYPSUM BD. (B.S.) = DPSF I I = D PSF 2x6@ 16" 0/C = PSF = PSF 15/32" SHEATHING = PSF = PSF MISCELLANEOUS = PSF DECK DEAD LOAD = 0.0 PSF TOTAL INTERIOR WALL : = 7.0 PSF DECK LIVE LOAD I o.ol PSF SOILS DATA: SOILS REPORT :I None Provided -Assume Code Minimum - GEOTECHNICAL ENGINEER :I Not Applicable-use code minimums !DATE OF REPORT : I NA BASIC BEARING PRESSURE PADS & CONT . FNDT. = Qa = 1,500 PSF ISOLATED FOUNDATIONS = I ol PSF INCREASE FOR WIDTH = 0.0 % INCREASE FOR DEPTH = 0.0 % MAX . SOIL PRESSURE -Qa = 1,500.0 PSF I o.ol ALLOW PASSIVE PRESSURE = I 0 .01 PCF EQUIV. FLUID PRESSURE = PCF ALLOW SOIL FRICTION = 0 .3 2302 & 2304 W Cubbon St - 1011181937/24/2024 USGS web services were down for some period of time and as a result this tool wasn't operational, resulting in timeout error. USGS web services are now operational so this tool should work as expected . OSH .PD 2302 W Cubbon St , Santa Ana , CA 92704 , USA Latitude , Longitude: 33.7347883, -117.8998 633 ' f Da te ' ! Desi g n Cod e Refere nce Doc ume nt ' i Risk Category [site Class ------ 'Type Value i Ss 1.301 ! S 1 ! i SM s ! i SM1 : Sos t So1 :r;~;- ! SDC l PGAM TL . SsRT 'SsUH ' SsD ; 1 S1RT ' S1UH S1D i PGAd 0.464 1.561 null -See Section 11.4.8 1.041 null -See Section 11.4.8 Value null -See Section 11.4.8 1.2 null -See Section 11 .4.8 0.554 1.2 0.665 8 1.301 1.406 1.602 0.464 0.503 0.6 0.663 Descri pt io n 1/21/2024 , 11 :09 :01 A M ASCE7-16 II D-Default (See Section 11.4.3) MCER ground motion. (for 0 .2 second period) MCER ground motion. (for 1.0s period) Site-mod ified spectral acceleration value Site-mod ified spectral acceleration value Numeric se ismic design value at 0.2 second SA Numeric seismic design value at 1.0 second SA Descript ion Seismic des ign category Site amplification factor at 0.2 second Site amplification factor at 1.0 second MCEG peak ground accelerat ion Site amplification factor at PGA Site modified peak ground acceleration Long-period transit ion period in seconds Probabil istic risk-targeted ground motion. (0.2 second) Factored uniform-hazard (2% probability of exceedance in 50 years) spectral accelerat io n Factored determin ist ic accelera tion value. (0.2 second) Probabil istic risk-targeted ground motion. (1.0 seco nd) Factored uniform-hazard (2% probability of exceedance in 50 years) spectral acceleration. Factored determin istic acceleration value. (1 .0 second) Factored determin istic accelerat ion value . (Peak Ground Acceleration) 2302 & 2304 W Cubbon St - 1011181937/24/2024 SEISMIC LOADS: Latitude = Longtitude = Occupancy Category Important Factor (I) 33.7347883 North -117.89986 West SEISMIC DATA: 1-1--1-.1~-o---il (Table 1.5-2) s1 = Site Class = = 1.301 g 1--------l 0.464 g 1-----::o------l 0 1.20 1.80 R Shear Panels Timber Frames ,--------------,,---,.-----,-------.------+-....:S:::D:::.C=-----1 6.50 1.50 Sms = = 1.561 g 3.00 1.50 Sm1 = 0 .835 g 4.00 1.50 1.041 g D 1.30 1.00 0.557 g D Use Simplified Alternative Structural Design F = I 1.00 I F = I 1.00 I V = (F*S05)/R V = (F*S 05)/R v = 0.21 Shear Panels V = 0.69 Timber Frames WIND DATA: WIND LOADS: DESIGN WIND VELOCITY (V35 ) = 110.0 MPH Roof Height = 4.0 FT v ,m = 110.0 MPH Wall Height (2ndt floor) = 0.0 FT Occupancy Category = II Wall Height (1st floor) = 9.0 FT Important Factor (I) = 1.00 (Table 1.5-2) Total Height = 13.0 FT Exposure Category = c Mean Roof Height = 11.0 FT Adjustment Coefficient (A.) = 1.29 (Figure 28.6-1) Roof Angle = 18.4 0 Kzt = 1.00 Edge (a) Ps = A.Kzt Ps30 Bui lding Width = 18.25 3.0 FT Building Length = 43.25 FT Eave Height = 9.0 FT Mean Roof Height = 11.0 4.4 FT a= 3.0 FT 2a = 6.0 FT MWFRS Design Wind Pressure Ps3o (psf} Horizontal Loads Roof End Zone Int. Zone Load Di rection Angle A B c D # ofSW Lines Transverse (Case B) 0 .0 19 .2 0 .0 12.7 0 .0 2 Longitud inal (Case A) 18.4 26 .6 -7 .0 17.7 -3 .9 2 2a -6 .0 FT Roof Horizonta l Load -I 1,068ILBS I (Transverse ) Roof Horizontal Load -2,217ILBS I (Longitudinal) 2302 & 2304 W Cubbon St - 1011181937/24/2024 LOAD: Roof weights Roof DL (horiz . Proj .) = Ext . Wall DL = Int. Shear Wall DL = Wall Height (1st floor)= Roof Height = Total he ight , hn = N-S Length= E-W Length= Roof Area= Tributary Ext. Walls to Roof= Tributary Int. Shear Walls to Roof = Roof Weight = Tributary Ext . Walls to Roof = Tributary Int. Shear Walls to Roof= W roof = Total DL (W) = Total Base Shear M = Design Base Shear : Period : T=Ct(hn)314 = 0 .02 *(hn)314 = Vertical distributions of seismic forces: Level wx (lb Area (tel Fx N-S (lb, Roof 25 ,793 789 5 ,369 1st Floor - L 25 ,793 5 ,369 Fx E-W (lb~ 5 ,369 5 ,369 Fpx N-S (I b) 5,369 5 ,369 Fx E-W wx 5 ,369 5 ,369 Shear E-W 20 .0 17.0 7 .0 9.0 4 .0 13.0 18.3 789 .3 123.0 18 .3 15 ,808 9,410 575 25,793 2~793 ~369 0 .137 sec V= V= 0.2 S05 W (I b) 5 ,369 0.2 S0 sW _ill)}_ 5 ,369 Use Use N-S 20 .0 17.0 7.0 9 .0 4 .0 13 .0 43 .3 789.3 123.0 43 .3 15 ,808 9 ,410 1,362 26,580 26 580 ~369 E-W 0.21 5 ,369 (I b) 5 ,369 (I b) 5 ,369 Diaphragm E-W 20 .0 17.0 7.0 9.0 4.0 13.0 18.3 - 789 .3 86.5 18.3 15 ,808 6 ,617 575 23,000 23 000 N-S 0.21 w 5 ,369 lbs fx N-S (psf) 6 .80 fx E-W (psf) 6.80 N-5 20.0 17.0 7.0 9.0 4.0 13.0 43.3 - 789.3 36 .5 43 .3 15 ,808 2 ,792 1,362 19,963 19 963 fpx N-S (psf) 6 .80 fpx E-W (psf) 6 .80 psf plf plf ft ft ft sq .ft . ft ft I I I I I I bs . bs . bs . bs . bs bs 2302 & 2304 W Cubbon St - 1011181937/24/2024 Longitudinal Direction: Shear Walls (Vertical): H. h R f L :Jgl 00 eve: 1 1 to 2 2 fx(psf) 6 .80 6 .80 6 .80 Spacing (ft) 18.25 Depth (ft) 43.25 43.25 ' Net D (b , ft) 16.0 15.0 V seismic (lb} 2 ,684 2 ,684 Vwind (lb) 2,217 2,217 V governs (lb} 2 ,684 2 ,684 Vgoverns(PIT) 168 179 Vtactored( plf) 168 179 Vtactore/1 .0 (plf) 168 179 Min . D (ft) 6.00 7.00 M0 (lb-ft) 9 ,060 11 ,275 Wroof (plf) 183 183 Wwa ll (plf) 153 153 0 .6*MR (lb-ft) 3 ,626 4 ,936 Tie-down (6") YES YES Tie-down (lb) 988 975 Tie-down HDU2&SSTB16 HDU2&SSTB16 Comp . Post 2-2x4 2-2x4 D + E/1.4 E = P Eh p = -1.30 Longitudinal Shear Walls Wall (grid line) EFabove (lb) EFx (lb Ftotal v=E/1 .4b Shear# Wall Length Sheathing 1 Allowable Shear (lbl (plf) (ft) or 2 sides (plf) 1 -2 ,684 2,684 168 1 16 .0 1 280 2 -2 ,684 2,684 179 1 15 .0 1 280 Diaphragm (horizontal): Roof Level · 1 1 to 2 2 fp x(psf) 6 .80 6 .80 6 .80 L (ft) 18.25 Depth (ft) 43.25 43.25 Area (ft2 } 789 fseismic(plf) 62 Vwind(plf) 26 Governs Seis. Vgoverned(plf) 62 Roof Panel 1/2" cox Shear 270 Edge Nail 8d@ 6",6",12" 2302 & 2304 W Cubbon St - 1011181937/24/2024 Transverse Direction: Shear Walls (Vertical): Roof Level A A to 8 8 fx(psf) 6 .80 6 .80 6 .80 Spacing (ft) 43.25 Depth (ft) 18.25 18.25 Net D (b , ft) 6.00 8.00 V seismic (lb) 2 ,684 2 ,684 Ywind (lb) 1,068 1,068 Ygovems (lb) 2,684 2 ,684 Vgovems(Pit) 447 336 Vtactored(plf) 447 336 Vtactore/1 .0 (plf) 447 336 Min . D (ft) 6.00 8.00 M0 (lb-ft) 24 ,160 24,160 Wroof (plf) 217 217 Wwall (plf) 153 153 0.6*MR (lb-ft) 3 ,991 7 ,095 Tie-down (6") YES YES Tie-down (lb) 3,667 2,275 Tie-down HDU5&SSTB24 HDU2&SSTB16 Comp . Post 2-2x4 2-2x4 D + E/1.4 E = p Eh p= 1.30 Transverse Shear Walls Wall (grid line) :EFabove (lb) :EFx (lb Ftotal v=E/1.4b Shear# Wall Length Sheathing 1 Allowable (I b) (plf) (ft) or 2 sides Shear (plf) A -2,684 2,684 447 3 6 .0 1 550 B -2 ,684 2,684 336 2 8.0 1 345 Diaphragm (horizontal): Roof Level · A A to 8 8 fpx(psf) 6 .80 6 .80 6.80 L (ft) 43.25 Depth (ft) 18.25 18.25 Area (ff) 789 fseismic(plf) 147 Vwind(plf) 29 Governs Seis. Vgovemed(plf) 147 Roof Panel 1/2" cox Shear 270 Edge Nail 8d@ 6",6",12" 7 2302 & 2304 W Cubbon St - 1011181937/24/2024 I wood Beam LIC#: KW-06017286 , Build :20 .23 .08.30 DESCRIPTION: RR-1@ 16" OC CODE REFERENCES Calculations per NDS 2018 , IBC 2021 , ASCE 7-16 Load Combination Set : IBC 2021 Material Properties Analysis Method : Allowable Stress Design Load Combination IBC 2021 Wood Species Wood Grade Douglas Fir-Larch No .2 Project Title: Engineer: Project ID : Project Oeser: VP HOME Fb + Fb- Fe-Prll Fe-Perp Fv Ft 900.0 psi 900 .0 psi 1,350 .0 psi 625 .0 psi 180.0 psi 575.0 psi Project File : SA Cubbon.ec6 (c) ENERCALC INC 1983-2023 E : Modulus of Elasticity Ebend-xx 1 ,600 .0ksi Eminbend-xx 580 .0ksi Density 31 .210pcf Beam Bracing Beam is Fully Braced against lateral-torsional buckling Repetitive Member Stress Increase 0(0 .019995~ Lr(0 .02666) 2x6 Span = 9 .0 ft Applied Loads Service loads entered . Load Factors will be applied for calculations . Beam self weight calculated and added to loading Uniform Load : D = 0 .0150 , Lr = 0.020 ksf, Tributary Width = 1 .333 ft, (Roof Loads) P_~$.JG._f1 __ $.JlMMAf?Y _______________________ ····---···-·········-·--·······--····-·-·--·······-·-····-... ·-···--··-·-·-·····--------··--···-----Design OK ! Maximum Bending Stress Ratio = 0.463 1 Maximum Shear Stress Ratio = 0.159 : 1 Section used for this span 2x6 Section used for this span 2x6 fb : Actual = 778 .29psi fv : Actual = 35.87 psi F'b = 1 ,681.88psi F'v = 225 .00 psi Load Combination +D+Lr Load Combination +D+Lr Location of maximum on span = 4 .500ft Location of maximum on span = 8.573ft Span # where maximum occurs = Span# 1 Span # where maximum occurs = Span# 1 Maximum Deflection Max Downward Transient Deflection 0 .119 in Ratio= 907>=360 Span : 1 : Lr Only Max Upward Transient Deflection 0 in Ratio= 0<360 n/a Max Downward Total Deflection 0.216 in Ratio= 499>=180 Span : 1 : +D+Lr Max Upward Total Deflection 0 in Ratio= 0<180 n/a Maximum Forces & Stresses for Load Combinations Load Combination l'illax S!ress Ra!1os l'illomen! Values Sfiear Values Segment Length Span# M v CD CM Ct CLx CE Cfu ci cr M fb F'b v fv F'v DOnly 0.0 0.00 0.0 0.0 Length = 9.0 ft 0.289 0.100 0.90 1.00 1.00 1.00 1.300 1.00 1.00 1.15 0.22 350 .0 1,211 .0 0.09 16.1 162 .0 +D+Lr 1.00 1.00 1.00 1.300 1.00 1.00 1.15 0.0 0.00 0.0 0.0 Length= 9.0 ft 0.463 0.159 1.25 1.00 1.00 1.00 1.300 1.00 1.00 .. 1.15 0.49 778 .3 1,681 .9 0.20 35.9 225 .0 +D+0.750Lr 1.00 1.00 1.00 1.300 1.00 1.00 1.15 0.0 0.00 0.0 0.0 Length = 9.0 ft 0.399 0.138 1.25 1.00 1.00 1.00 1.300 1.00 1.00 1.15 0.42 671 .2 1,681.9 0.17 30 .9 225 .0 +0 .60D 1.00 1.00 1.00 1.300 1.00 1.00 1.15 0.0 0.00 0.0 0.0 Length= 9.0 ft 0.098 0.034 1.60 1.00 1.00 1.00 1.300 1.00 1.00 1.15 0.13 210 .0 2 ,152 .8 0.05 9.7 288 .0 2302 & 2304 W Cubbon St - 1011181937/24/2024 !wood Beam LIC# : KW006017286 , Build :20 .23 .08 .30 DESCRIPTION: CJ-1@ 16" OC CODE REFERENCES Calculations per NDS 2018 , IBC 2021, ASCE 7-16 Load Combination Set : ASCE 7-16 Material Properties Ana lysis Method : Allowable Stress Design Load Combination . ASCE 7-16 Wood Species Wood Grade Douglas Fir-Larch No .2 Project Title : Engineer: Project ID : Project Oeser : VP HOME Fb + Fb - Fe -Prll Fe -Perp Fv Ft 900 .0 psi 900 .0 psi 1,350 .0 psi 625.0 psi 180.0psi 575 .0psi Beam Brac ing Beam is Fully Braced against lateral-torsional buckling v 0(0.01333) Lr(0 .01333) v ~ 2x8 Span = 17 _750 ft Project File: SA Cubbon.ecS (c) ENERCALC INC 1983°2023 E : Modulus of Elasticity Ebend-xx 1 ,600 .0ksi Eminbend-xx 580 .0ksi Density 31 .210pcf Repetitive Member Stress Increase v v ~ Applied Loads Service loads entered . Load Factors will be applied fo r calculations . Beam self weight calculated and added to loading Uniform Load : D = 0 .01 0 , Lr = 0 .010 ksf, Tributary Width = 1 .333 ft , (Ceiling Loads) Qf,$._/.f;_N.$.Y.MMAB.Y.. ••••••••••••••• moo--o 00 oo • ooooo-oomoooooooo ooooooooo o moo o o ooooo•-·--•o• •oooOo- :Maximum Bending Stress Ratio · Section used for this span fb : Actual F'b Load Combination Location of maximum on span Span # where maximum occurs Maximum Deflection Max Downward Transient Deflection Max Upward Transient Deflection Max Downward Total Deflection Max Upward Total Deflection = = = = = 0.672 1 2x8 1 ,043 .58psi 1 ,552.50 psi +D+Lr 8.875ft Span# 1 0 .393 in Ratio= 0 in Ratio= 0 .855 in Ratio = 0 in Ratio= Maximum Shear Stress Ratio Section used for this span tv : Actual F'v Load Combination Location of maximum on span Span #where maximum occurs 542 >=360 0<360 249 >=180 0 <180 Span : 1 : Lr Only n/a Span : 1 : +D+Lr n/a Maximum Forces & Stresses for Load Combinations Load Combination l'ii'lax S!ress Ra!1os l'ii'lomen! Values Segment Length Span# M v CD CM Ct CLx CE Cfu ci cr M fb DOnly Length = 17.750 ft 0.505 0.111 0.90 1.00 1.00 1.00 1.200 1.00 1.00 1.15 0.62 564 .2 +D+Lr 1.00 1.00 1.00 1.200 1.00 1.00 1.15 Length= 17 .750 ft 0.672 0.147 1.25 1.00 1.00 1.00 1.200 1.00 1.00 1.15 1.14 1,043 .6 +D+0 .750Lr 1.00 1.00 1.00 1.200 1.00 1.00 1.15 Length= 17 .750 ft 0.595 0 .131 1.25 1.00 1.00 1.00 1.200 1.00 1.00 1.15 1.01 923 .7 +0 .60D 1.00 1.00 1.00 1.200 1.00 1.00 1.15 Length= 17.750 ft 0.170 0.037 1.60 1.00 1.00 1.00 1.200 1.00 1.00 1.15 0.37 338 .5 = = = = = F'b 0.0 1,117.8 0.0 1,552 .5 0.0 1,552 .5 0.0 1,987 .2 Design OK 0.147 : 1 2x8 33.19 psi 225 .00 psi +D+Lr 17.167ft Span# 1 Sliear Values v tv F'v 0.00 0.0 0.0 0.13 17.9 162.0 0.00 0.0 0.0 0.24 33.2 225 .0 0.00 0.0 0.0 0.21 29 .4 225 .0 0.00 0.0 0.0 0.08 10.8 288 .0 2302 & 2304 W Cubbon St - 1011181937/24/2024 I wood Beam LIC#: KW-06017286 . Bu ild :20 .23 .08 .30 DESCRIPTION: HDR-1 -Header CODE REFERENCES Calculations per NOS 2018 , IBC 2021 , ASCE 7-16 Load Combination Set : IBC 2021 Material Properties Analysis Method : Allowable Stress Design Load Combination IBC 2021 Wood Species Wood Grade Douglas Fir-Larch No .2 Project Title: Engineer: Project ID : Project Oeser : VP HOME Fb + Fb- Fe-Prll Fe-Perp Fv Ft 900.0 psi 900.0psi 1,350 .0 psi 625 .0 psi 180.0 psi 575 .0 psi Project Fi~: SA Cubbon.ec6 (c) ENERCALC INC 1983-2023 E : Modulus of Elasticity Ebend-xx 1 ,600 .0 ksi Eminbend-xx 580 .0ksi Density 31 .210pcf Beam Bracing Beam is Fully Braced against lateral-torsional buckling 4 x8 Span= 9 .50 ft Applied Loads Service loads en te red . Load Facto rs wil l be appl ied for ca lcu lations . Beam self weight calculated and added to loading Uniform Load : 0 = 0.020 , Lr = 0.020 ksf, Tributary Width= 4 .0 ft, (Roof Loads) £?/;_SIGN SUMMARY Design OK j Maximum Bending Stress Ratio = 0.500 1 Maximum Shear Stress Ratio = 0.181 : 1 i Section used for this span 4x8 Section used for this span 4x8 fb : Actual = 730 .71 psi fv : Actual = 40 .70 psi F'b = 1 ,462 .50psi F'v = 225.00 psi Load Combination +D+Lr Load Combination +D+Lr Location of maximum on span = 4.750ft Location of maximum on span = 8 .911 ft Span # where maximum occurs = Span# 1 Span #where maximum occurs = Span# 1 Maximum Deflection Max Downward Transient Deflection 0 .083 in Ratio= 137 4>=360 Span : 1 : Lr Only Max Upward Transient Deflection 0 in Ratio= 0<360 nla Max Downward Total Deflection 0 .172 in Ratio= 664 >=180 Span: 1 : +D+Lr Max Upward Total Deflection 0 in Ratio= 0<1 80 nla Maximum Forces & Stresses for Load Combinations Load Combination Max Sfress Raf1os Momenf 'Values Sliear 'Values Segment Length Span# M v CD CM Ct Clx CE Cfu ci cr M fb F'b v fv F'v DOnly 0.0 0 .00 0.0 0.0 Length = 9 .50 ft 0.358 0.130 0.90 1.00 1.00 1.00 1.300 1.00 1.00 1.00 0.96 377.5 1,053 .0 0.36 21 .0 162.0 +D+Lr 1.00 1.00 1.00 1.300 1.00 1.00 1.00 0 .0 0 .00 0 .0 0 .0 Length = 9 .50 ft 0 .500 0 .181 1.25 1.00 1.00 1.00 1.300 1.00 1.00 1.00 1.87 730 .7 1,462 .5 0 .69 40 .7 225 .0 +D+0 .750Lr 1.00 1.00 1.00 1.300 1.00 1.00 1.00 0 .0 0.00 0.0 0.0 Length = 9 .50 ft 0.439 0.159 1.25 1.00 1.00 1.00 1.300 1.00 1.00 1.00 1.64 642 .4 1,462.5 0.61 35 .8 225.0 +0 .60D 1.00 1.00 1.00 1.300 1.00 1.00 1.00 0 .0 0.00 0.0 0.0 Length = 9 .50 ft 0.121 0 .044 1.60 1.00 1.00 1.00 1.300 1.00 1.00 1.00 0.58 226 .5 1,872 .0 0.21 12.6 288 .0 }0 2302 & 2304 W Cubbon St - 1011181937/24/2024 I Wood Beam UC#: KW-06017286 , Build :20 .23 .08 .30 DESCRIPTION: HDR-1-Header Overall Maximum Deflections Load Combination Span +D+Lr Vertical Reactions Load Combination Max Upward from all Load Conditions Max Upward from Load Combinations Max Upward from Load Cases DOnly +D+Lr +D+0.750Lr +0 .600 Lr Only Project Title: Engineer : Project 10 : Project Oeser: Project File: SA Cubbon.ec6 VP HOME (c) ENERCALC INC 1983-2023 Max . "-" Defl Location in Span Load Combination Max . "+" Defl Location in Span 0.1715 4.785 0.0000 0.000 Support notation : Far left is #1 Values in KIPS Support 1 Support 2 0.786 0.786 0.786 0.786 _JL._ 0.406 0.406 "F' (~ 71<b(, if 0.406 0.406 0.786 0.786 0.691 0.691 II I' ~ u ~ ~ {'1, [) 0.244 0.244 0.380 0.380 J I 2302 & 2304 W Cubbon St - 1011181937/24/2024 UNIFORM AND POINT LOAD ON CONTINUOUS FOOTING Footing Width (FW) = Footing Depth (FD) = Soil Bearing (SB) = Max. Soil Bearing = Plain Concrete Design : F'c= Tension Fb = Procedures : 12 in 12 in 1,500 psf 1 ,500 psf 2 ,500 psi 80 psi Fsoil = ((D-FD)/12*1D)+SB F'soil = Fsoii-(D/12 *(150-110)) w = W*F'soil/12 W(") 12 X 12 X 15 X 18 X 21 X 24 X 12 X 15 X 18 X 21 X 24 X 12 X 15 X 18 X 21 X 24 X 12 X 15 X 18 X 21 X 24 X 12 X 15 X 18 X 21 X 24 X 30 X M = Fb*W*d"2/12"/6 L = (2*M/w)"1/2 Pmax = 2*L*w D (") Fsoil (psf) F'soil (psf) 5 1,500 1,483 12 1,500 1,460 12 1,500 1,460 12 1,500 1 ,460 12 1,500 1,460 12 1,500 1,460 15 1,500 1,450 15 1,500 1,450 15 1,500 1,450 15 1,500 1,450 15 1,500 1,450 18 1,500 1,440 18 1,500 1,440 18 1,500 1,440 18 1,500 1,440 18 1,500 1,440 21 1 ,500 1 ,430 21 1 ,500 1 ,430 21 1,500 1,430 21 1,500 1,430 21 1,500 1,430 24 1,500 1,420 24 1 ,500 1,420 24 1 ,500 1 ,420 24 1 ,500 1,420 24 1 ,500 1,420 24 1 ,500 1,420 Soil Density = Concrete Density = Inc . Width (IW) = Inc. Depth (ID) = w {#/ft} M ('#) 1,483 333 1,460 1,920 1,825 2 ,400 2 ,190 2 ,880 2 ,555 3 ,360 2 ,920 3 ,840 1,450 3 ,000 1,813 3 ,750 2 ,175 4 ,500 2 ,538 5 ,250 2 ,900 6 ,000 1 ,440 4 ,320 1 ,800 5 ,400 2 ,160 6 ,480 2 ,520 7 ,560 2 ,880 8 ,640 1,430 5 ,880 1,788 7 ,350 2 ,145 8 ,820 2 ,503 10 ,290 2 ,860 11 ,760 1,420 7 ,680 1,775 9 ,600 2 ,130 11 ,520 2 ,485 13 ,440 2 ,840 15 ,360 3 ,550 19 ,200 110 pcf 150 pcf 0 psf 0 psf L (ft) Pmax {#} 0 .67 1,989 1 .62 4 ,736 1.62 5 ,919 1.62 7 ,103 1 .62 8 ,287 1.62 9,471 2.03 5 ,899 2.03 7 ,374 2 .03 8 ,849 2.03 10 ,324 2 .03 11 ,79ji, 2.45 fi'055 2.45 87Bl8 2.45 10 ,582 2.45 12 ,345 2.45 14 ,109 2 .87 8 ,202 2.87 10,252 2.87 12 ,302 2 .87 14 ,353 2 .87 16 ,403 3.29 9 ,340 3 .29 11 ,676 3.29 14 ,011 3 .29 16 ,346 3 .29 18 ,681 3.29 23,351 Note : For point loads on footings with uniform loads , take the difference between "w" above and the uniform load , then multiply by two and by "L" above for P'max. ~ -~ lv 2302 & 2304 W Cubbon St - 1011181937/24/2024 POINT LOAD ON SQUARE PAD FOOTING Footing Depth (FD) = Soil Bearing (SB) = Max. Soil Bearing = 12 in 1500 psf 1500 psf Soil Density = Concrete Density = Inc . Width (IW) = Inc . Depth (ID) = w (") 12 12 15 18 21 24 18 21 24 30 18 21 24 30 33 36 30 36 42 36 42 48 54 60 66 72 78 84 Plain Concrete Design : L (") 12 12 15 18 21 24 18 21 24 30 18 21 24 30 33 36 30 36 42 36 42 48 54 60 66 72 78 84 F'c = Tension Fb = Procedures: 2 ,500 psi 80 psi Fsoil = ((D-FD)/12 *1D)+SB F'soil = Fsoii-(D/12 *(150-11 0)) A= W*L Pmax = F'soii*A D (") Fsoil (psf} F'soil (psf} 5 1 ,383 1,367 12 1,500 1,460 12 1,500 1,460 12 1,500 1,460 12 1,500 1,460 12 1,500 1,460 15 1,550 1,500 15 1,550 1,500 15 1,550 1,500 15 1,550 1,500 18 1,600 1,500 18 1,600 1,500 18 1,600 1,500 18 1,600 1,500 18 1,600 1,500 18 1,600 1,500 21 1 ,650 1 ,500 21 1 ,650 1 ,500 21 1 ,650 1 ,500 24 1,700 1 ,500 24 1,700 1 ,500 24 1,700 1,500 24 1 ,700 1 ,500 24 1 ,700 1 ,500 24 1 ,700 1,500 24 1,700 1,500 24 1,700 1,500 24 1,700 1,500 A.1!fl 1.00 1.00 1.56 2 .25 3 .06 4 .00 2.25 3 .06 4 .00 6 .25 2.25 3 .06 4.00 6.25 7 .56 9 .00 6 .25 9 .00 12.25 9 .00 12 .25 16.00 20.25 25.00 30.25 36 .00 42 .25 49.00 110 pcf 150 pcf 200 psf 200 psf Pmax {#} Reinforce 1 ,367 2-#4 e.w. 1,460 2-#4 e.w. 2 ,281 3-#4 e.w. 3 ,285 3-#4 e .w . 4,471 3-#4 e.w. 5 ,840 3-#4 e.w. 3 ,375 3-#4 e.w. 4 ,594 3-#4 e.w. 6 ,000 3-#4 e.w. 9 ,375 4-#4 e.w. 3 ,375 3-#4 e .w. 4 ,594 3-#4 e .w. 6 ,000 3-#4 e.w. 9 ,375 4-#4 e.w . 11,344 4-#4 e.w. 13,500 4-#4 e.w. 9,375 4-#5 e.w. 13,500 4-#5 e.w. 18 ,375 5-#5 e .w. 13 ,500 4-#5 e.w. 18 ,375 5-#5 e.w . 24,000 5-#5 e.w. 30 ,375 5-#5 e.w. 37 ,500 6-#5 e.w . 45 ,375 6-#5 e.w . 54,000 7-#5 e.w. 63 ,375 7-#5 e .w. 73 ,500 8-#5 e.w. 2302 & 2304 W Cubbon St - 1011181937/24/2024