HomeMy WebLinkAbout2306 N Spinnaker St - PlanPV SYSTEM
AS INDICATED
NOVEMBER 15, 2023
ROSA RAMIREZ
2306 SPINNAKER ST,
SANTA ANA, CA 92706
Clean Energy Solutions Inc.
Address:
1055 West 7th Street
33rd Floor, Los Angeles,
CA 90017
Phone Number:
(800)994 1134
Lic# 998787
Class C-10
CONTRACTOR
Designed By: Inter Solar Cad
www.intersolarcad.com
1. ALL ELECTRICAL MATERIALS SHALL BE NEW AND LISTED BY RECOGNIZED ELECTRICAL TESTING LABORATORY CUSTOM MADE EQUIPMENT SHALL HAVE
COMPLETE TEST DATA SUBMITTED BY THE MANUFACTURER ATTESTING TO ITS SAFETY
2. OUTDOOR EQUIPMENT SHALL BE AT LEAST NEMA 3R RATED
3. ALL METALLIC EQUIPMENT SHALL BE GROUNDED
4. ALL SPECIFIC WIRING IS BASED ON THE USE OF COPPER.
5.CONTRACTOR SHALL OBTAIN ELECTRICAL PERMITS PRIOR TO INSTALLATION AND SHALL COORDINATE ALL INSPECTIONS, TESTING
COMMISSIONING AND ACCEPTANCE WITH THE CLIENT, UTILITY CO. AND CITY INSPECTORS AS NEEDED.
6.THE ELECTRICAL CONTRACTOR SHALL VERIFY THE EXACT LOCATIONS OF SERVICE POINTS AND SERVICE SIZES WITH THE SERVING UTILITY COMPANY
AND COMPLY WITH ALL UTILITY COMPANIES REQUIREMENTS. IF THE SOLAR BACK FED BREAKER IS OVER THE BUSS SIZE 20% LIMIT, CONTRACTOR SHALL
INCLUDE THE COST TO REPLACE MAIN BREAKER OR ENLARGE MAIN CAPACITY.
7. DRAWINGS ARE DIAGRAMMATIC ONLY, ROUTING OF RACEWAYS SHALL BE OPTION OF THE CONTRACTOR UNLESS OTHERWISE NOTED AND SHALL BE
COORDINATED WITH OTHER TRADES.
8. IF THE ROOF MATERIAL OR ROOF STRUCTURE NOT ADEQUATE FOR PV INSTALLATION, CALL ENGINEER PRIOR TO INSTALL. THE CONTRACTOR IS
RESPONSIBLE TO VERIFY THAT THE ROOF IS CAPABLE OF WITHSTANDING THE EXTRA WEIGHT.
9. IF THE DISTANCES FOR CABLE RUNS ARE DIFFERENT THAN SHOWN, THE CONTRACTOR SHALL NOTIFY THE ELECTRICAL ENGINEER TO VALIDATE THE
WIRE SIZE. FINAL DRAWINGS WILL BE RED-LINED AND UPDATED AS APPROPRIATE.
10. WHENEVER A DISCREPANCY IN QUALITY OF EQUIPMENT ARISES ON THE DRAWING OR SPECIFICATIONS, THE CONTRACTOR SHALL BE RESPONSIBLE FOR
PROVIDING AND INSTALLING ALL MATERIAL AND SERVICES REQUIRED BY THE STRICTEST CONDITIONS NOTED ON THE DRAWINGS OR IN THE
SPECIFICATIONS TO ENSURE COMPLETE COMPLIANCE AND LONGEVITY OF THE OPERABLE SYSTEM REQUIRED BY THE ARCHITECT/ENGINEERS.
OWNER
SCOPE
PROJECT
ADDRESS
PROJECT DATA GENERAL NOTES VICINITY MAP
SHEET INDEX
PHOTOVOLTAIC NOTES
SATELLITE VIEW
BUILDING
INFORMATION:
ELECTRICAL
INFORMATION
MAIN SERVICE PANEL
BUSBAR RATING
MAIN SERVICE
BREAKER RATING
1ɸ, 3W, 120/240V
RACKING
INFORMATION
Main Service Panel
Solar Module
Micro Inverter /
Optimizer
EMT / FMT / PVC
/ RMC type conduit/
Romex NM Cable/
FNMT (Fluid non-metalic tube)
36'' SetbackInverter
Utility Meter
Production Meter
PV Load Center
IQ Combiner Box
Junction Box
Sunpower PV Supervisor
18'' Setback
EV Outlet
CONSTRUCTION TYPE: V-B
ROOF
TYPE
AHJ
APN
LOT AREA
LIVING AREA
MSP
UM
PM
INV
PV
PVS6
IQ
J/B
EV
ROSA RAMIREZ
31
1 SOLAR EDGE ENERGY HUB SE10000H-USSNBBL14 (240V)
2306 SPINNAKER ST,
SANTA ANA, CA 92706
AC Disconnect ACD
SSP Service Sub Panel
COMPOSITION SHINGLE
2,944 SQFT
39913226
CITY OF SANTA ANA
ROOF MOUNT INSTALLATION OF
DC PHOTOVOLTAIC SYSTEM
12.40 KW DC
12.40 KW
11.47 KW AC
(DOWNSIZED)
EXISTING
ALL OTHER ORDINANCE ADOPTED BY THE
LOCAL GOVERNING AGENCIES
THE INSTALLATION OF SOLAR ARRAYS AND
PHOTOVOLTAIC POWER SYSTEMS SHALL COMPLY
WITH THE FOLLOWING CODES:
2022 CALIFORNIA BUILDING CODE
2022 CALIFORNIA RESIDENTIAL CODE
2022 CALIFORNIA FIRE CODE
2022 CALIFORNIA PLUMBING CODE
2022 CALIFORNIA ELECTRICAL CODE
2022 CALIFORNIA MECHANICAL CODE
2022 CALIFORNIA ENERGY CODE
2022 CALIFORNIA GREEN BUILDING STANDARDS CODE
2022 CALIFORNIA HISTORICAL CODE
2022 CALIFORNIA EXISTING BUILDING CODE
2022 CALIFORNIA REFERENCED STANDARDS CODE
2022 CALIFORNIA ADMINISTRATIVE STANDARDS CODE
1. ROOFTOP MOUNTED PHOTOVOLTAIC PANELS AND MODULES SHALL BE TESTED, LISTED AND IDENTIFIED UL 1703.
2. SOLAR SYSTEM SHALL NOT COVER ANY PLUMBING OR MECHANICAL VENTS
3. MODULES AND SUPPORT STRUCTURES SHALL BE GROUNDED.
4. SOLAR INVERTER MUST HAVE A MANUFACTURE INSTALLED DISCONNECTING MEANS THAT PREVENTS PARALLEL FEEDING UTILITY LINES DURING POWER
OUTAGE.
5. REMOVAL OF AN INTERACTIVE INVERTER OR OTHER EQUIPMENT SHALL NOT DISCONNECT THE BONDING CONNECTION BETWEEN THE GROUNDING
ELECTRODE CONDUCTOR AND THE PHOTOVOLTAIC SOURCE AND/OR OUTPUT CIRCUIT GROUNDED CONDUCTORS.
6. ALL PV MODULES AND ASSOCIATED EQUIPMENT AND WIRING SHALL BE PROTECTED FROM ANY PHYSICAL DAMAGE.
7. LIVE PARTS OF PV SOURCE CIRCUITS AND PV OUTPUT CIRCUITS OVER 150V TO GROUND SHALL NOT BE
ACCESSIBLE TO OTHER THAN QUALIFIED PERSONS WHILE ENERGIZED.
8 .INVERTER IS EQUIPPED W/ INTEGRATED GFCI, THUS PROVIDING GROUND FAULT PROTECTION
9. ALL CONDUCTORS SHALL BE COPPER AND 90 DEG RATED
10. ALL ELECTRICAL EQUIPMENT SHALL BE LISTED BY A RECOGNIZED ELECTRICAL TESTING LABORATORY OR APPROVED BY THE DEPARTMENT.
11. THE OUTPUT OF A UTILITY INTERACTIVE-INVERTER SHALL BE PERMITTED TO BE CONNECTED TO THE SUPPLY SIDE OF THE SERVICE DISCONNECTING
MEANS AS PER 230.82(6)
12. A SINGLE CONDUCTOR SHALL BE PERMITTED TO BE USED TO PERFORM THE MULTIPLE FUNCTIONS OF DC GROUNDING, AC GROUNDING
AND BONDING BETWEEN AC AND DC SYSTEMS SIZED AS PER CEC 250.122
13. EQUIPMENT GROUND CONDUCTOR REQUIRED IN RACEWAYS SIZED PER CEC 250-122.
14. PER ART 250.92. NON-CURRENT CARRYING METAL PARTS OF EQUIPMENT SHALL BE EFFECTIVELY BONDED TOGETHER. BOND BOTH ENDS OF RACEWAYS
7,072 SQFT
Battery BackupBB
Auto Transformer AT
Solar Edge Meter EnclosureSEM
Distribution PanelDP
Rapid Shutdown Controller RSC
Rapid Shutdown Box RSB
Itron MeterIM
UNIT INDEX
CODE REFERENCES
IRONRIDGE RACKING
TRUSSES 2"X4" @ 24" O.C
OCCUPANCY: R
TWO STORY BUILDING
175A
200A
CANADIAN SOLAR 400W
CS6R-400MS-HL
(don't delete this note)
SOLAREDGE BAT-10K1P ENERGY BANK 10KWH1
COVER SHEET
0 COVER SHEET
SINGLE LINE DIAGRAM
CODE REQUIRED SIGNAGE
E 1.1
PV 2.0
ATTACHMENT LAYOUTS 1.0
PV 2.1
PV 3.0
INVERTER DATA SHEET
MODULE DATA SHEET
RACKING SPECIFICATIONS
ATTACHMENT SPECIFICATIONS
ROOF PLAN
MODULE MAP
INVERTER MAP
GROUNDING SPECIFICATIONS
OPTIMIZER DATA SHEET
PV 0.1
E 1.0
SITE PLANPV 1.0
PV 3.1
PV 4.0
PV 4.1
PV 5.0
PV 5.1
PV 6.0
0
PV 6.1
PV 6.2
RACKING CERTIFICATE
BATTERY DATA SHEET
E 1.2 WIRE SIZE CALCULATIONS
LOAD CALCULATION
BLDG# 101117603
ELECT# 20181637 M.Smith
ISSUED: 12/12/2023
The scope of the plans is for the installation
of the solar photovoltaic system only and
the approval is subject to compliance with
all applicable city and state codes and
regulations regarding construction. The
approval of the plans does not constitute
any certification of the accuracy,
completeness, or building permit status of
the existing buildings and structures as
shown.
2306 N Spinnaker St -
2018163712/18/2023
ROOF PLAN
PV SYSTEM
AS INDICATED
NOVEMBER 15, 2023
ROSA RAMIREZ
2306 SPINNAKER ST,
SANTA ANA, CA 92706
Clean Energy Solutions Inc.
Address:
1055 West 7th Street
33rd Floor, Los Angeles,
CA 90017
Phone Number:
(800) 994 1134
Lic# 998787
Class C-10
CONTRACTOR
Designed By: Inter Solar Cad
www.intersolarcad.com
N
0°
S
180°
E
90°
W
270°
SCALE
0 5
PHOTOVOLTAIC SYSTEM
1 Solar Edge Energy Hub 10.0 Kw Inverter SE10000H-USSNBBL14 (240V)
Solar Edge S440 Power Optimizers31
FROM JUNCTION BOX TO ROOF EAVE EMT TYPE CONDUIT WILL RUN OVER
THE ROOF AT 1 1/2" HEIGHT, THEN UNDER THE EAVE TO PV EQUIPMENT12.40 KW DC
a
31 Canadian Solar 400W Modules (CS6R-400MS-HL)
10ft
ROOF AREA CALCULATIONS
FIRE SPRINKLERS - NO
TOTAL ROOF AREA (SQ.FT.) - 3265
SOLAR AREA (SQ.FT.) - 651
% OF COVERED AREA - 19.9%
1
INV
ACD
Gate
Gate
MSP
18
'
'
f
i
r
e
s
e
t
b
a
c
k
18'' fire setback
18'' fire setback
36'' fire setback
36
'
'
f
i
r
e
s
e
t
b
a
c
k
36
'
'
f
i
r
e
s
e
t
b
a
c
k
3
6
'
'
f
i
r
e
s
e
t
b
a
c
k
18'' fire setback
Sp
i
n
n
a
k
e
r
S
t
Solar Array 4
2 Canadian 400W
2 S440 Optimizers
Tilt: 18 Deg
Azimuth: 180 Deg
Solar Array 3
13 Canadian 400W
13 S440 Optimizers
Tilt: 18 Deg
Azimuth: 180 Deg
Solar Array 2
2 Canadian 400W
2 S440 Optimizers
Tilt: 18 Deg
Azimuth: 180 Deg
Solar Array 1
14 Canadian 400W
14 S440 Optimizers
Tilt: 18 Deg
Azimuth: 90 Deg
SolarEdge EnergyBank Batter
a
aa
aa
aa
a
a
b
bb
b
b b
b
bb
bc
cc
ccc
c
c c
cc
PV 0.1
2306 N Spinnaker St -
2018163712/18/2023
PV SYSTEM
AS INDICATED
NOVEMBER 15, 2023
ROSA RAMIREZ
2306 SPINNAKER ST,
SANTA ANA, CA 92706
Clean Energy Solutions Inc.
Address:
1055 West 7th Street
33rd Floor, Los Angeles,
CA 90017
Phone Number:
(800) 994 1134
Lic# 998787
Class C-10
CONTRACTOR
Designed By: Inter Solar Cad
www.intersolarcad.com
SITE PLAN
N
0°
S
180°
E
90°
W
270°
SCALE
20ft5010
Sp
i
n
n
a
k
e
r
S
t
Gate
Gate
MSP
INV
ACD
SolarEdge EnergyBank Batter
70'
115'
95'
35'
35'
24'
26'
10'
27'
Driveway
Pu
b
l
i
c
S
i
d
e
w
a
l
k
PROPERTY LINE
PV 1.0
2306 N Spinnaker St -
2018163712/18/2023
ATTACHMENT
LAYOUT
PV SYSTEM
AS INDICATED
NOVEMBER 15, 2023
ROSA RAMIREZ
2306 SPINNAKER ST,
SANTA ANA, CA 92706
Clean Energy Solutions Inc.
Address:
1055 West 7th Street
33rd Floor, Los Angeles,
CA 90017
Phone Number:
(800) 994 1134
Lic# 998787
Class C-10
CONTRACTOR
Designed By: Inter Solar Cad
www.intersolarcad.com
STRUCTURAL STAMPROOF
PITCH
ROOFING
TYPE
ATTACHMENT
TYPE
FRAMING
TYPE
FRAMING
SIZE
PENETRATION
PATTERN
18°
RACKING
TYPE
MAX
PENETRATION
SPACING
ROOFING
LAYERS
WIND SPEED 95 MPH
SNOW LOAD 0 PSF
EXPOSURE C
LAG BOLTS MOUNTS AND MOUNTING HARDWARE WILL BE
SEALED WITH CHEM LINK SEALANT OR EQUIVALENT.
MODULE WEIGHT (LBS)
# OF MODULES
TOTAL MODULE WEIGHT (LBS)
RACK WEIGHT (LBS)
TOTAL SYSTEM WEIGHT (LBS)
# OF STANDOFFS
LOADING PER STANDOFF (LBS)
TOTAL MODULE AREA (SQ.FT.)
LOADING (PSF)
WEIGHT LOAD CALCULATION INDEX
ROOF SHEATHED WITH 1/2" PLYWOOD AND UPPER
SURFACE IS FACED WITH FELT PAPER
TOTAL ROOF AREA (Sq. FT)
% OF COVERED AREA
PV MODULE MODEL #
OPTIMIZERS WEIGHT (LBS)
31
Roof 1 Layer Comp Shingle Ironridge XR10 Truss Stacked 72"2"X4" @ 24" O.C
3
1
2
4
ITEM NO.
1
DESCRIPTION
2
3
4
BOLT LAG 5/16 X 4.75"
ASSY, FLASHING
ASSY, CAPFOOT
WASHER, EPDM BACKED
Qty in Kit
4
4
4
4
5/16" X 4.75"
Flash Foot 2
MIN 2.5" EMBEDMENT
RACKING RAIL
ATTACHMENT
ROOF FRAMING
62
651
3265
1531
306
47
1884
30.4
2.89
19.9
2''X6'' Blocking
SOLAR MODULE
ROOF
ASCE 7-16
Max 3.5''
49.4
CS6R-400MS-HL
S 1.0
72"
24"
2306 N Spinnaker St -
2018163712/18/2023
SINGLE LINE
DIAGRAM
PV SYSTEM
AS INDICATED
NOVEMBER 15, 2023
ROSA RAMIREZ
2306 SPINNAKER ST,
SANTA ANA, CA 92706
Clean Energy Solutions Inc.
Address:
1055 West 7th Street
33rd Floor, Los Angeles,
CA 90017
Phone Number:
(800) 994 1134
Lic# 998787
Class C-10
CONTRACTOR
Designed By: Inter Solar Cad
www.intersolarcad.com
ITEM DESCRIPTION QTY#
PV MODULE
MAIN SERVICE PANEL
MAIN SERVICE PANEL
& UTILITY METER
BUSBAR RATING
BREAKER RATING
1
ITEM DESCRIPTION QTY#
PVC JUNCTION BOX 4"x4"x2" UL LISTED WATER TIGHT NEMA TYPE 3
1
1
1
5
3
1
4
6
MAIN
SERVICE
PANEL
120/240V
1P,3W
2
EXISTING
GROUNDING SYSTEM
UTILITY
M
2
3
5700W
INVERTER
PEAK PWR TRACKING VOLTAGE
INVERTER EFFICIENCY
ENCLOSURE :
MAXIMUM INPUT CURRENT
MAXIMUM OUTPUT CURRENT
MAXIMUM INPUT POWER
MAXIMUM OUTPUT POWER
4 1
380 V
99.0 %
NEMA 4
27.0 A
42.0 A
22,000 W
10,000 W
SOLAREDGE ENERGY HUB SE10000H-USSNBBL14 (240V)
SOLAREDGE POWER OPTIMIZER
RATED DC INPUT POWER
MAXIMUM INPUT VOLTAGE
MPPT RANGE
MAXIMUM SHORT CIRCUIT CURRENT (Isc)
MAXIMUM OUTPUT CURRENT
OPTIMIZER WEIGHT
MAXIMUM POWER PER STRING
5
S440
440W
60 Vdc
8 to 60 Vdc
14.5 Adc
15 Adc
1.5 Lbs
31POWER OPTIMIZER
60AAC DISCONNECT NON FUSED AC DISCONNECT LOCKABLE,
BLADE TYPE, NEMA 3R, 120/240V 16
EXISTING
(DOWNSIZED)
EXISTING
2
1
33
175A
200A
200A
FOR WIRE SIZE CALCULATIONS PLEASE SEE PAGE #3
INSTALL 2P
60A CB(PV) AT
OPPOSITE END
OF BUS FROM
MAIN FEEDER CB
31
Canadian Solar 400W
CS6R-400MS-HL
Voc = 36.8V
Vmp = 30.8V
Isc = 13.85A
Imp = 12.99A
(D)175A
String a: (10) Modules, (10) Optimizers
17BATTERY BACKUP SYSTEMS
SOLAR EDGE ENERGY BANK 10kWh, BAT-10K1P 1BATTERY BACKUP
7 (1)#10 AWG (10-12 AWG), 600V insulated
(1) #24 AWG (16-24 AWG), 600V insulated or CAT6
1'' EMT TYPE CONDUIT
String b: (10) Modules, (10) Optimizers
String c: (11) Modules, (11) Optimizers
E 1.0
2306 N Spinnaker St -
2018163712/18/2023
PV SYSTEM
AS INDICATED
NOVEMBER 15, 2023
ROSA RAMIREZ
2306 SPINNAKER ST,
SANTA ANA, CA 92706
Clean Energy Solutions Inc.
Address:
1055 West 7th Street
33rd Floor, Los Angeles,
CA 90017
Phone Number:
(800) 994 1134
Lic# 998787
Class C-10
CONTRACTOR
Designed By: Inter Solar Cad
www.intersolarcad.com
FROM PV MODULES TO JBOX
FROM JBOX TO INVERTER
(6)
WIRE SIZE
CALCULATIONS
1
(1) #6 AWG BARE CU EGC,
2
#8 AWG CU EGC,
(3)
3
(1) #8 AWG CU EGC,
MAXIMUM INVERTER OUTPUT CURRENT (A)
TEMPERATURE FACTOR
TEMPERATURE ADJUSTMENT (A)
OUTPUT CALCULATIONS
PV SYSTEM MAX DC OUTPUT
PV SYSTEM MAX AC OUTPUT
MAXIMUM POWER (W)
PEAK PWR TRACKING VOLTAGE (V)
CONSIDER CONTINUOUS COEFFICIENT
SHORT CIRCUIT CURRENT (A)
ADJUSTED CONDUCTOR AMPACITY (A)
1.25
1.25
1.25
0.91
(6)
(1)
Pmax (PTC Rating)
42.0
380
99.0 %
42.0 * 1.25 / 0.91 57.7
#6 AWG THWN-2
SOLAR EDGE SE10000H-USSNBBL14 (240V)
42.0 * 1.25 52.5
1
1 1/2''
(TEMP - 39 + 22 = 61C)0.58
RACEWAY HEIGHT FROM ROOF
0.8ADJST. FACTOR (4 thru 6 WIRES)
FREE IN THE AIR, 3/4'' EMT TYPE CONDUIT BETWEEN ARRAYS
3/4'' EMT TYPE CONDUIT
1'' EMT TYPE CONDUIT
MAIN SERVICE PANEL RATING
BUSBAR RATING
MAIN BREAKER
PV BACKFEED BREAKER SIZE
120% RULE:
MAX ALLOWED FEED
60A
*/*1.25 *1.2511400 380 18.1
/ /18.1 0.58 0.8 39.0
#10 AWG THWN-2
WIRE CHART WIRE CHART
*31 400 12.40 KW
* *31 373.9 0.99 11.47 KW
CONSIDER CONTINUOUS COEFFICIENT
CONSIDER CONTINUOUS COEFFICIENT
175A
200A
240A
175A ''MB'' + 60A "SOLAR" = 235A ≤240A MAX
FROM INVERTER TO MAIN SERVICE PANEL
CONSIDER CONTINUOUS (A)
MAX NUMBER OF MODULES IN STRING 11
#10 AWG PV-WIRE
31
CS6R-400MS-HL 400 W
373.9 W
400
E 1.1
2306 N Spinnaker St -
2018163712/18/2023
PV SYSTEM
AS INDICATED
NOVEMBER 15, 2023
ROSA RAMIREZ
2306 SPINNAKER ST,
SANTA ANA, CA 92706
Clean Energy Solutions Inc.
Address:
1055 West 7th Street
33rd Floor, Los Angeles,
CA 90017
Phone Number:
(800) 994 1134
Lic# 998787
Class C-10
CONTRACTOR
Designed By: Inter Solar Cad
www.intersolarcad.com
LOAD
CALCULATION
E 1.2
2306 N Spinnaker St -
2018163712/18/2023
DO NOT UPSIZE MAIN BREAKER. MAIN
BREAKER WAS DOWNSIZED TO A
TO ACCOMMODATE PV SYSTEM.
CODE REQUIRED
SIGNAGE
PV SYSTEM
AS INDICATED
NOVEMBER 15, 2023
ROSA RAMIREZ
2306 SPINNAKER ST,
SANTA ANA, CA 92706
Clean Energy Solutions Inc.
Address:
1055 West 7th Street
33rd Floor, Los Angeles,
CA 90017
Phone Number:
(800) 994 1134
Lic# 998787
Class C-10
CONTRACTOR
Designed By: Inter Solar Cad
www.intersolarcad.com
JB
B
O
X
WARNING
ELECTRICAL SHOCK HAZARD
TERMINALS ON THE LINE AND
LOAD SIDES MAY BE ENERGIZED
IN THE OPEN POSITION
CEC 690.13(B)
TURN OFF PHOTOVOLTAIC
AC DISCONNECT PRIOR TO
WORKING INSIDE PANEL
CEC 110.27(C)
DC
D
i
s
c
o
n
n
e
c
t
CEC 690.13(B)
In
v
e
r
t
e
r
/
P
V
L
o
a
d
WARNING
THE DISCONNECTION OF THE
GROUNDING CONDUCTOR(S)
MAY RESULT IN OVERVOLTAGE
ON THE EQUIPMENT
CEC 690.31(E)
CEC 690.54
AC
D
i
s
c
o
n
n
e
c
t
CEC 690.54
WARNING
ELECTRICAL SHOCK HAZARD
TERMINALS ON THE LINE AND
LOAD SIDES MAY BE ENERGIZED
IN THE OPEN POSITION
CEC 690.13(B)
PM
M
E
T
E
R
Ma
i
n
/
S
u
b
P
a
n
e
l
CEC 690.54
CEC 690.13 (E), CEC 705.12(B)(C-D) & CEC 690.59
CEC 690.15 (B) & CEC 690.33(D)(2)
CEC 690.13(B)
SINGLE 120-VOLT SUPPLY
DO NOT CONNECT
MULTIWIRE BRANCH CIRCUIT!
CEC 710.15(C)
TURN OFF PHOTOVOLTAIC
AC DISCONNECT PRIOR TO
WORKING INSIDE PANEL
CEC 110.27(C)
WARNING
ELECTRICAL SHOCK HAZARD
TERMINALS ON THE LINE AND
LOAD SIDES MAY BE ENERGIZED
IN THE OPEN POSITION
CEC 690.13(B)
CEC 705.12 (B)(3)(2)
LABELING REQUIREMENTS FOR ARTICLE 690
CEC 690.13(B) Each PV system disconnecting means shall plainly indicate whether
in the open (off) or closed (on) position and be permanently marked “PV SYSTEM
DISCONNECT” or equivalent. Additional markings shall be permitted based upon
the specific system configuration.
CEC 690.13(E) Type of Disconnect. The PV system disconnecting means shall
simultaneously disconnect the PV system conductors that are not solidly grounded
from all conductors of other wiring systems. The PV system disconnecting means or
its remote operating device or the enclosure providing access to the disconnecting
means shall be capable of being locked in accordance with 110.25.
CEC 690.15(B) An isolating device shall not be required to have an interrupting
rating. Where an isolating device is not rated for interrupting the circuit current, it shall
be marked "Do Not Disconnect Under Load" or "Not for Current Interrupting." An
isolating device shall not be required to simultaneously disconnect all current-carrying
conductors of a circuit.
CEC 690.31(B)(1) PV system dc circuit conductors shall be identified at all
termination, connection, and splice points by color coding, marking tape, tagging, or
other approved means.
CEC 690.31(D)(2) Unless located and arranged so the purpose is evident, the following wiring
methods and enclosures that contain PV system dc circuit conductors shall be marked with the
wording PHOTOVOLTAIC POWER SOURCE or SOLAR PV DC CIRCUIT by means of
permanently affixed labels or other approved permanent marking.
CEC 690.31(D)(2) PV system dc circuit labels shall appear on every section of the wiring
system that is separated by enclosures, walls, partitions, ceilings, or floors. Spacing between
labels or markings, or between a label and a marking, shall not be more than 3 m (10 ft).
Labels required in this section shall be suitable for the environment where they are installed.
CEC 690.31(E) Solidly-grounded bipolar PV systems shall be clearly marked with a
permanent, legible warning notice indicating that the disconnection of the grounded
conductor(s) may result in overvoltage on the equipment.
CEC 690.33(D)(2) Interruption of Circuit. Connectors shall be a type that requires the use of a
tool to open and marked “Do Not Disconnect Under Load” or “Not for Current Interrupting”.
CEC 690.6 Alternating-current (AC) modules and systems: The PV source circuit, conductors,
and inverters shall be considered as internal components of an ac module or ac module
system.
CEC 690.53 A permanent readily visible label indicating the highest
maximum dc voltage in a PV system, calculated in accordance with 690.7,
shall be provided by the installer.
CEC 690.54 All interactive system(s) points of interconnection with other
sources shall be marked at an accessible location at the disconnecting
means as a power source and with the rated ac output current and the
nominal operating ac voltage.
CEC 690.55 The PV system output circuit conductors shall be marked to
indicate polarity where connected to energy storage systems.
CEC 690.56(A) Plaques or directories shall be installed in accordance with
705.10.
CEC 690.56(C)(2) A rapid shutdown switch shall have a label located on
or no more than 1 meter (3 ft) from the switch.
CEC 690.59 PV systems connected to other sources shall be installed in
accordance with Parts I and II of Article 705 and Article 712.
SOLAR ELECTRIC
PV PANELS
SOLAR PV SYSTEM EQUIPPED
WITH RAPID SHUTDOWN
TURN RAPID SHUTDOWN
SWITCH ON THE
"OFF" POSITION TO
SHUTDOWN PV SYSTEM
AND REDUCE
SHOCK HAZARD
IN ARRAY
CFC 1205.4.1(1) & CEC 690.56(C)
CEC 690.56(C)(2)
CEC 690.31(D)(2)
CEC 690.31(D)(2)CO
N
D
U
I
T
RATED AC OPERATING CURRENT:
NOMINAL OPERATING AC VOLTAGE:
PHOTOVOLTAIC AC DISCONNECT
DC DISCONNECT
PHOTOVOLTAIC
WARNING
RATED AC OPERATING CURRENT:
NOMINAL OPERATING AC VOLTAGE:
PHOTOVOLTAIC AC DISCONNECT
RATED AC OPERATING CURRENT:
NOMINAL OPERATING AC VOLTAGE:
PHOTOVOLTAIC AC DISCONNECT MAIN PHOTOVOLTAIC
SYSTEM DISCONNECT WARNING
CAUTION
PHOTOVOLTAIC SYSTEM CIRCUIT IS BACKFED
WARNING
POWER SOURCE OUTPUT
CONNECTION. DO NOT
RELOCATE THIS
OVERCURRENT DEVICE.
WARNING
DO NOT DISCONNECT
UNDER LOAD
RAPID SHUTDOWN SWITCH
FOR SOLAR PV SYSTEM
WARNING: PHOTOVOLTAIC
POWER SOURCE
WARNING
PHOTOVOLTAIC POWER SOURCE
DO NOT REMOVE UNLESS REPLACED IN EXACT LOCATION - PV POWER CIRCUIT DIRECTLY BELOW
FOR SOLAR PHOTOVOLTAIC SYSTEMS THAT SHUT
DOWN THE ARRAY AND THE CONDUCTORS LEAVING
THE ARRAY, A LABEL SHALL BE PROVIDED. THE
FIRST TWO LINES OF THE LABEL SHALL BE
UPPERCASE CHARACTERS WITH A MINIMUM
HEIGHT OF 3/8 INCH (10 MM) IN BLACK ON A
YELLOW BACKGROUND. THE REMAINING
CHARACTERS SHALL BE UPPERCASE WITH A
MINIMUM HEIGHT OF 3/16 INCH (5 MM) IN BLACK ON
A WHITE BACKGROUND. [CFC 1205.4.1(1)]
240 Vac
240 Vac
240 Vac
CEC 690.13(B)
AC DISCONNECT
PHOTOVOLTAIC
42.0 A MAX
42.0 A MAX
42.0 A MAX
WARNING
ELECTRICAL SHOCK HAZARD
TERMINALS ON THE LINE AND
LOAD SIDES MAY BE ENERGIZED
IN THE OPEN POSITION
CEC 690.13(B)
CEC 705.10
CAUTION
MULTIPLE SOURCES OF POWER
CEC 705.10
CAUTION
MULTIPLE SOURCES OF POWER
CEC 690.53
OF PV SYSTEM
MAXIMUM DC VOLTAGE
CEC 690.53
MAXIMUM SYSTEM VOLTAGE
RATED SHORT CIRCUIT CURRENT
N/AMAX RATED AC OPERATING VOLTAGE
N/ARATED AC OPERATING VOLTAGE
MAX RATED AC OPERATING CURRENT
RATED AC OPERATING CURRENT
N/A
N/A
N/A
N/A
CAUTION
N
0°
S
180°
E
90°
W
270°
POWER TO THIS BUILDING IS ALSO SUPPLIED
FROM THE FOLLOWING SOURCES WITH
DISCONNECTS LOCATED AS SHOWN:
CEC 705.10 & CEC 690.56(B)
Permanent directory or plaque providing location of service disconnecting means and
photovoltaic system disconnecting means, if not located at the same location. (Plaques shall
be metal or plastic, with engraved or machine printed letters, or electro-photo plating, in a
contrasting color to the plaque. Plaques shall be permanently attached to the equipment or in the
required location using an approved method that is suitable to withstand the environment to which it
is exposed. Plaques and signage shall meet legibility, defacement, exposure and adhesion
requirements of Underwriters Laboratories marking and labeling system 969(UL969).
Plaques will have red background & white lettering.
SP
I
N
N
A
K
E
R
S
T
PV SYSTEM DISCONNECT
FOR UTILITY OPERATION
SOLAR INVERTER
SOLAREDGE ENERGY
BANK BATTERY
SERVICE POINT &
UTILITY METERING
SOLAR ARRAY
ON THE ROOF
SOLAR ARRAY
ON THE ROOF
175
PV 2.0
2306 N Spinnaker St -
2018163712/18/2023
MODULE
MAP
PV SYSTEM
AS INDICATED
NOVEMBER 15, 2023
ROSA RAMIREZ
2306 SPINNAKER ST,
SANTA ANA, CA 92706
Clean Energy Solutions Inc.
Address:
1055 West 7th Street
33rd Floor, Los Angeles,
CA 90017
Phone Number:
(800) 994 1134
Lic# 998787
Class C-10
CONTRACTOR
Designed By: Inter Solar Cad
www.intersolarcad.com
[FOR INSTALLER USE ONLY]
PHOTOVOLTAIC SYSTEM
1 Solar Edge Energy Hub 10.0 Kw Inverter SE10000H-USSNBBL14 (240V)
Solar Edge S440 Power Optimizers31
12.40 KW DC
31 Canadian Solar 400W Modules (CS6R-400MS-HL)
Solar Array 4
2 Canadian 400W
2 S440 Optimizers
Tilt: 18 Deg
Azimuth: 180 Deg
Solar Array 3
13 Canadian 400W
13 S440 Optimizers
Tilt: 18 Deg
Azimuth: 180 Deg
Solar Array 2
2 Canadian 400W
2 S440 Optimizers
Tilt: 18 Deg
Azimuth: 180 Deg
Solar Array 1
14 Canadian 400W
14 S440 Optimizers
Tilt: 18 Deg
Azimuth: 90 Deg
PV 2.1
2306 N Spinnaker St -
2018163712/18/2023
PV SYSTEM
AS INDICATED
NOVEMBER 15, 2023
ROSA RAMIREZ
2306 SPINNAKER ST,
SANTA ANA, CA 92706
Clean Energy Solutions Inc.
Address:
1055 West 7th Street
33rd Floor, Los Angeles,
CA 90017
Phone Number:
(800) 994 1134
Lic# 998787
Class C-10
CONTRACTOR
Designed By: Inter Solar Cad
www.intersolarcad.com
INVERTER
MAP
INVERTERPHOTOVOLTAIC SYSTEM
1 Solar Edge Energy Hub 10.0 Kw Inverter SE10000H-USSNBBL14 (240V)
Solar Edge S440 Power Optimizers31
12.40 KW DC
[FOR INSTALLER USE ONLY]
31 Canadian Solar 400W Modules (CS6R-400MS-HL)
Solar Array 4
2 Canadian 400W
2 S440 Optimizers
Tilt: 18 Deg
Azimuth: 180 Deg
Solar Array 3
13 Canadian 400W
13 S440 Optimizers
Tilt: 18 Deg
Azimuth: 180 Deg
Solar Array 2
2 Canadian 400W
2 S440 Optimizers
Tilt: 18 Deg
Azimuth: 180 Deg
Solar Array 1
14 Canadian 400W
14 S440 Optimizers
Tilt: 18 Deg
Azimuth: 90 Deg
PV 3.0
2306 N Spinnaker St -
2018163712/18/2023
MODULE
DATA SHEET
PV SYSTEM
AS INDICATED
NOVEMBER 15, 2023
ROSA RAMIREZ
2306 SPINNAKER ST,
SANTA ANA, CA 92706
Clean Energy Solutions Inc.
Address:
1055 West 7th Street
33rd Floor, Los Angeles,
CA 90017
Phone Number:
(800) 994 1134
Lic# 998787
Class C-10
CONTRACTOR
Designed By: Inter Solar Cad
www.intersolarcad.com
PV 3.1
2306 N Spinnaker St -
2018163712/18/2023
INVERTER
DATA SHEET
PV SYSTEM
AS INDICATED
NOVEMBER 15, 2023
ROSA RAMIREZ
2306 SPINNAKER ST,
SANTA ANA, CA 92706
Clean Energy Solutions Inc.
Address:
1055 West 7th Street
33rd Floor, Los Angeles,
CA 90017
Phone Number:
(800) 994 1134
Lic# 998787
Class C-10
CONTRACTOR
Designed By: Inter Solar Cad
www.intersolarcad.com
PV 4.0
2306 N Spinnaker St -
2018163712/18/2023
PV SYSTEM
AS INDICATED
NOVEMBER 15, 2023
ROSA RAMIREZ
2306 SPINNAKER ST,
SANTA ANA, CA 92706
Clean Energy Solutions Inc.
Address:
1055 West 7th Street
33rd Floor, Los Angeles,
CA 90017
Phone Number:
(800) 994 1134
Lic# 998787
Class C-10
CONTRACTOR
Designed By: Inter Solar Cad
www.intersolarcad.com
OPTIMIZER
DATA SHEET
PV 4.1
2306 N Spinnaker St -
2018163712/18/2023
PV SYSTEM
AS INDICATED
NOVEMBER 15, 2023
ROSA RAMIREZ
2306 SPINNAKER ST,
SANTA ANA, CA 92706
Clean Energy Solutions Inc.
Address:
1055 West 7th Street
33rd Floor, Los Angeles,
CA 90017
Phone Number:
(800) 994 1134
Lic# 998787
Class C-10
CONTRACTOR
Designed By: Inter Solar Cad
www.intersolarcad.com
RACKING
SPECIFICATIONS
PV 5.0
2306 N Spinnaker St -
2018163712/18/2023
PV SYSTEM
AS INDICATED
NOVEMBER 15, 2023
ROSA RAMIREZ
2306 SPINNAKER ST,
SANTA ANA, CA 92706
Clean Energy Solutions Inc.
Address:
1055 West 7th Street
33rd Floor, Los Angeles,
CA 90017
Phone Number:
(800) 994 1134
Lic# 998787
Class C-10
CONTRACTOR
Designed By: Inter Solar Cad
www.intersolarcad.com
ATTACHMENT
SPECIFICATIONS
PV 5.1
2306 N Spinnaker St -
2018163712/18/2023
PV SYSTEM
AS INDICATED
NOVEMBER 15, 2023
ROSA RAMIREZ
2306 SPINNAKER ST,
SANTA ANA, CA 92706
Clean Energy Solutions Inc.
Address:
1055 West 7th Street
33rd Floor, Los Angeles,
CA 90017
Phone Number:
(800) 994 1134
Lic# 998787
Class C-10
CONTRACTOR
Designed By: Inter Solar Cad
www.intersolarcad.com
RACKING
CERTIFICATE
PV 6.0
2306 N Spinnaker St -
2018163712/18/2023
PV SYSTEM
AS INDICATED
NOVEMBER 15, 2023
ROSA RAMIREZ
2306 SPINNAKER ST,
SANTA ANA, CA 92706
Clean Energy Solutions Inc.
Address:
1055 West 7th Street
33rd Floor, Los Angeles,
CA 90017
Phone Number:
(800) 994 1134
Lic# 998787
Class C-10
CONTRACTOR
Designed By: Inter Solar Cad
www.intersolarcad.com
GROUNDING
SPECIFICATIONS
PV 6.1
2306 N Spinnaker St -
2018163712/18/2023
PV SYSTEM
AS INDICATED
NOVEMBER 15, 2023
ROSA RAMIREZ
2306 SPINNAKER ST,
SANTA ANA, CA 92706
Clean Energy Solutions Inc.
Address:
1055 West 7th Street
33rd Floor, Los Angeles,
CA 90017
Phone Number:
(800) 994 1134
Lic# 998787
Class C-10
CONTRACTOR
Designed By: Inter Solar Cad
www.intersolarcad.com
BATTERY
DATA SHEET
PV 7
2306 N Spinnaker St -
2018163712/18/2023
2306 N Spinnaker St -
2018163712/18/2023
2306 SPINNAKER ST.
SANTA ANA, CA 92706
RAMIREZ, ROSA
Design Criteria
1- Code: CALIFORNIA BLDG CODE 2022 / ASCE 7-16
2 - Wind: 95 MPH, Exposure: C
3 - Wood Species: DF-L No. 1 (SG = 0.5 )
Notice: Use restrictions of these calculations.
The attached Calculations are valid only when bearing original signature hereon.
Contractor/Client to verify existing dimensions/conditions prior to construction
& solar racking is installed per manufacturer span requirements.
The use of these calculations is solely intended for the above mentioned project.
1-844-PV ELITE | info@yoursolarplans.com
3000 E. Birch Street Suite 201 | Brea CA 92821
10/23/2023
Structural Calculations for
SOLAR POWER SYSTEM CONNECTION CHECK AT:
Job:
2306 N Spinnaker St -
2018163712/18/2023
!"#$%!&'(' )'(*!"&+ ',-) *.&(/0./1/1,'(12/
3
..!..4..$
$..
!.. $4..05
.
$..$!!. . /6'+7 $89:;<=>?@A;B:CDA?(/0.//,'(2/H '(' )'(+ ',-) 4+ +
')(OH S((['