HomeMy WebLinkAbout2710 N Laird St & 2209 W Laramore Ln - PlanA-01
1/16" = 1'-0"
PLOT PLAN
PROJECT SITE
VICINITY MAP
PROJECT SUMMARY
SHEET INDEX
LARAMORE LANE
D E S I G N
2024 JULY 29
DETACHED ADU
DATEISSUED FOR
I S S U E S
2710 LAIRD AVENUE
SANTA ANA, CALIFORNIA 92706
DAVID LE RESIDENCE
A-23-002-008
PROPOSED
HOUSE EXTENSION
+
PLAN CHECK SUBMITTAL 10.25.2023
2ND PLAN CHECK SUBMITTAL 01.05.2024
BUILDING SAFETY SUBMITTAL 01.25.2024
UPDATE PLAN SET FOR PRESCREEN 02.19.2024
2209 W. LARAMORE LANE
SANTA ANA, CALIFORNIA 92706
UPDATE PLAN SET 03.31.2024
BUILDING SAFETY RESUBMITTAL 07.29.2024
10111914-95
LA
I
R
D
AV
E
BLDG # 101119194-95
APPROVALS
BLDG- TLe
PLNG- ASevilla
PD- BMartin
2710 N Laird St & 2209 W
Laramore Ln10/7/2024
GENERAL NOTES
A-02
D E S I G N
2024 JULY 29
DETACHED ADU
DATEISSUED FOR
I S S U E S
2710 LAIRD AVENUE
SANTA ANA, CALIFORNIA 92706
DAVID LE RESIDENCE
A-23-002-008
PROPOSED
HOUSE EXTENSION
+
PLAN CHECK SUBMITTAL 10.25.2023
2ND PLAN CHECK SUBMITTAL 01.05.2024
BUILDING SAFETY SUBMITTAL 01.25.2024
UPDATE PLAN SET FOR PRESCREEN 02.19.2024
2209 W. LARAMORE LANE
SANTA ANA, CALIFORNIA 92706
UPDATE PLAN SET 03.31.2024
BUILDING SAFETY RESUBMITTAL 07.29.2024
10111914-95
2710 N Laird St & 2209 W
Laramore Ln10/7/2024
D E S I G N
2024 JULY 29
DETACHED ADU
DATEISSUED FOR
I S S U E S
2710 LAIRD AVENUE
SANTA ANA, CALIFORNIA 92706
DAVID LE RESIDENCE
A-23-002-008
PROPOSED
HOUSE EXTENSION
+
PLAN CHECK SUBMITTAL 10.25.2023
2ND PLAN CHECK SUBMITTAL 01.05.2024
BUILDING SAFETY SUBMITTAL 01.25.2024
UPDATE PLAN SET FOR PRESCREEN 02.19.2024
2209 W. LARAMORE LANE
SANTA ANA, CALIFORNIA 92706
UPDATE PLAN SET 03.31.2024
BUILDING SAFETY RESUBMITTAL 07.29.2024
10111914-95
A-10
1/8" = 1'-0"
EXISTING SITE PLAN
1EXISTING SITE PLAN
2710 N Laird St & 2209 W
Laramore Ln10/7/2024
D E S I G N
2024 JULY 29
DETACHED ADU
DATEISSUED FOR
I S S U E S
2710 LAIRD AVENUE
SANTA ANA, CALIFORNIA 92706
DAVID LE RESIDENCE
A-23-002-008
PROPOSED
HOUSE EXTENSION
+
PLAN CHECK SUBMITTAL 10.25.2023
2ND PLAN CHECK SUBMITTAL 01.05.2024
BUILDING SAFETY SUBMITTAL 01.25.2024
UPDATE PLAN SET FOR PRESCREEN 02.19.2024
2209 W. LARAMORE LANE
SANTA ANA, CALIFORNIA 92706
UPDATE PLAN SET 03.31.2024
BUILDING SAFETY RESUBMITTAL 07.29.2024
10111914-95
A-11
1/8" = 1'-0"
1
PROPOSED SITE PLAN
PROPOSED SITE PLAN
2710 N Laird St & 2209 W
Laramore Ln10/7/2024
flip up grab bar
5 8 " continuous plywood backing
reinforce full width and height of sides
and back walls of shower and of
back wall of water closet for future
wall mounted grab bar installation
(sec R327.1.1.)
flip up grab bar
A-12
1/4" = 1'-0"
PROPOSED
D E S I G N
2024 JULY 29
DETACHED ADU
DATEISSUED FOR
I S S U E S
2710 LAIRD AVENUE
SANTA ANA, CALIFORNIA 92706
DAVID LE RESIDENCE
A-23-002-008
PROPOSED
HOUSE EXTENSION
+
PLAN CHECK SUBMITTAL 10.25.2023
2ND PLAN CHECK SUBMITTAL 01.05.2024
BUILDING SAFETY SUBMITTAL 01.25.2024
UPDATE PLAN SET FOR PRESCREEN 02.19.2024
2209 W. LARAMORE LANE
SANTA ANA, CALIFORNIA 92706
UPDATE PLAN SET 03.31.2024
BUILDING SAFETY RESUBMITTAL 07.29.2024
10111914-95
BUILDING SAFETY RESUBMITTAL 08.20.2024
bedroom 2 bedroom 1
dining room
bath 2
bath 1
kitchen
living room
FLOOR PLAN
1ADU FLOOR PLAN
2HOUSE EXTENSION FLOOR PLAN
(E) bedroom
(E) bedroom
(E) bedroom
(E) bedroom
(E) living room
(E) bath (E) bath
(N) dining room
(E) kitchen
KITCHEN WALL
DEMO PLAN
(N) layout
3grab bar ready reinforcement
bath 1
2710 N Laird St & 2209 W
Laramore Ln10/7/2024
D E S I G N
2024 JULY 29
DETACHED ADU
DATEISSUED FOR
I S S U E S
2710 LAIRD AVENUE
SANTA ANA, CALIFORNIA 92706
DAVID LE RESIDENCE
A-23-002-008
PROPOSED
HOUSE EXTENSION
+
PLAN CHECK SUBMITTAL 10.25.2023
2ND PLAN CHECK SUBMITTAL 01.05.2024
BUILDING SAFETY SUBMITTAL 01.25.2024
UPDATE PLAN SET FOR PRESCREEN 02.19.2024
2209 W. LARAMORE LANE
SANTA ANA, CALIFORNIA 92706
UPDATE PLAN SET 03.31.2024
BUILDING SAFETY RESUBMITTAL 07.29.2024
10111914-95
BUILDING SAFETY RESUBMITTAL 08.20.2024
A-13
1/4" = 1'-0"
PROPOSED
ROOF PLAN
2HOUSE EXTENSION ROOF PLAN
1ADU ROOF PLAN
2710 N Laird St & 2209 W
Laramore Ln10/7/2024
A-20
1/4" = 1'-0"
ADU
D E S I G N
2024 JULY 29
DETACHED ADU
DATEISSUED FOR
I S S U E S
2710 LAIRD AVENUE
SANTA ANA, CALIFORNIA 92706
DAVID LE RESIDENCE
A-23-002-008
PROPOSED
HOUSE EXTENSION
+
PLAN CHECK SUBMITTAL 10.25.2023
2ND PLAN CHECK SUBMITTAL 01.05.2024
BUILDING SAFETY SUBMITTAL 01.25.2024
UPDATE PLAN SET FOR PRESCREEN 02.19.2024
2209 W. LARAMORE LANE
SANTA ANA, CALIFORNIA 92706
UPDATE PLAN SET 03.31.2024
BUILDING SAFETY RESUBMITTAL 07.29.2024
10111914-95
EXTERIOR ELEVATIONS
COLOR+MATERIAL
BOARD
2710 N Laird St & 2209 W
Laramore Ln10/7/2024
A-21
1/4" = 1'-0"
HOUSE EXTENSION
D E S I G N
2024 JULY 29
DETACHED ADU
DATEISSUED FOR
I S S U E S
2710 LAIRD AVENUE
SANTA ANA, CALIFORNIA 92706
DAVID LE RESIDENCE
A-23-002-008
PROPOSED
HOUSE EXTENSION
+
PLAN CHECK SUBMITTAL 10.25.2023
2ND PLAN CHECK SUBMITTAL 01.05.2024
BUILDING SAFETY SUBMITTAL 01.25.2024
UPDATE PLAN SET FOR PRESCREEN 02.19.2024
2209 W. LARAMORE LANE
SANTA ANA, CALIFORNIA 92706
UPDATE PLAN SET 03.31.2024
BUILDING SAFETY RESUBMITTAL 07.29.2024
10111914-95
EXTERIOR ELEVATIONS
2710 N Laird St & 2209 W
Laramore Ln10/7/2024
A-22
1/4" = 1'-0"
D E S I G N
2024 JULY 29
DETACHED ADU
DATEISSUED FOR
I S S U E S
2710 LAIRD AVENUE
SANTA ANA, CALIFORNIA 92706
DAVID LE RESIDENCE
A-23-002-008
PROPOSED
HOUSE EXTENSION
+
PLAN CHECK SUBMITTAL 10.25.2023
2ND PLAN CHECK SUBMITTAL 01.05.2024
BUILDING SAFETY SUBMITTAL 01.25.2024
UPDATE PLAN SET FOR PRESCREEN 02.19.2024
2209 W. LARAMORE LANE
SANTA ANA, CALIFORNIA 92706
UPDATE PLAN SET 03.31.2024
BUILDING SAFETY RESUBMITTAL 07.29.2024
10111914-95
ADU SECTIONS
HOUSE EXTENSION
SECTIONS
+
2710 N Laird St & 2209 W
Laramore Ln10/7/2024
weep screed @ grade
typical exterior corner
weep screed @ conc. slab
1-hr rated exterior wall assembly
interiorexterior
ASSEMBLY LISTING 1-hr. wall
STUCCO TO SIDING TRANSITION
SCALE: 3"=1'-0"
EXT. CEMENT PLSTR. O/
METAL LATH
S.A.C.F 8" WIDE
O/ W.B.M.
HARDIEPLANK SIDING
OR HARDIESHINGLE
W/ SEALANT O/
BOND RELEASE
TAPE
STUD FRAMING OR
FLAT 2X BACKING
MILCOR PLASTER STOP
SHT'G PER
EXTERIOR ELEV,
NOTES
SEALANT
OUTSIDE CORNER @ HARDIPLANK SIDING / STUCCO
SCALE: 3"=1'-0"
EXT. SHEATHING
(WHERE OCCURS)-
SEE STRUCT. DWGS.
5/4 x 3.5" HARDI TRIM
BOARD
HARDIEPLANK SIDING OR
HARDIESHINGLE (BLIND NAIL) O/
W.R.B.
5/4 x4.5" HARDI TRIM
BOARD
SEALANT TYP.
2X WALL FRAMING
PER STRUCT.
5 8" TYPE "X" GYP SHT'G
WHERE OCCURS
12" WIDE SELF-ADHERED FLEXIBLE
FLASHING CENTER VERTICALLY ON
CORNER
EXTERIOR CEMENT PLASTER
OVER METAL LATH AND (2)
LAYERS OF 60 MIN. GRADE "D"
BUILDING PAPER
5/4 x 3.5" HARDI TRIM
BOARD
INTERIOR INTERIOR
1-HR INTERIOR WALL (SINGLE STUD)
SCALE: 3"=1'-0"
footing detailslab to existing footing
footing detail
interior footing
A-30
FOOTING & WALL
D E S I G N
2024 JULY 29
DETACHED ADU
DATEISSUED FOR
I S S U E S
2710 LAIRD AVENUE
SANTA ANA, CALIFORNIA 92706
DAVID LE RESIDENCE
A-23-002-008
PROPOSED
HOUSE EXTENSION
+
PLAN CHECK SUBMITTAL 10.25.2023
2ND PLAN CHECK SUBMITTAL 01.05.2024
BUILDING SAFETY SUBMITTAL 01.25.2024
UPDATE PLAN SET FOR PRESCREEN 02.19.2024
2209 W. LARAMORE LANE
SANTA ANA, CALIFORNIA 92706
UPDATE PLAN SET 03.31.2024
BUILDING SAFETY RESUBMITTAL 07.29.2024
10111914-95
DETAILS
SEE STRUCTURAL DETAIL DRAWINGS
FOR INFORMATION ON WALL AND
FOOTING
2710 N Laird St & 2209 W
Laramore Ln10/7/2024
horizontal attic forced air unit
THERMAL INSULATION (REFER TO
TITLE-24 ENERGY COMPLIANCE
CALCULATIONS)
ROOF RAFTERS
- SEE STRUCT.
(4) 2"~ HOLES PER BLOCK WITH
|" HARDWARE CLOTH STAPLED TO
BACK OF 2x BLOCK
2x EAVE BLOCK (SEE ELEVATION
AND SECTION BELOW)
AIR
F
L
O
W
T
H
R
U
V
E
N
T
(4) 2 1/4"~ HOLES
PER BLOCK
14" HARDWARE
CLOTH STAPLED
TO BACK OF 2x
BLOCK
section elevation
eave vent block detail
SCALE: N.T.S.
NOTES:
1.SEE GENERAL NOTES AND PLAN SPECIFICATIONS FOR VENTILATION REQUIREMENTS
2.SEE STRUCTURAL DRAWING FOR BLOCKING DETAIL
3.EACH BLOCK PROVIDES APPROXIMATELY 16 SQ. INCHES OF VENTILATION
4.MINIMUM BLOCK SIZE: 2" x 4" x 14 12"
5.TYPICAL ATTIC: 1 VENT BLOCK AT EVERY THIRD BAY (MIN. 10 VENT BLOCKS PER CALC.)
6.SEE ROOF PLAN FOR VENT AREA REQUIREMENTS
7.SLOPING CEILING: 1 VENT BLOCK AT EACH BAY
ROOF INSULATION R-30
ATTIC INSULATION R-15
typical ridge
SCALE: 1 1/2" = 1'-0"
valley
SCALE: 1 1/2" = 1'-0"
typical eaveroof covered extension at entry porch
exterior
interiorexterior
AIR
F
L
O
W
T
H
R
U
V
E
N
T
SHINGLES AND BUILDING
PAPER TO OVERLAP
VENT LIP
PRIMED & PAINTED GALV.
DORMER ROOF ATTIC VENT
BIRD SCREEN
ATTIC VENT
SCALE: 1"=1'-0"
ROOF RAFTER
ATTIC
ROOF SHINGLES
A-31
ROOF
D E S I G N
2024 JULY 29
DETACHED ADU
DATEISSUED FOR
I S S U E S
2710 LAIRD AVENUE
SANTA ANA, CALIFORNIA 92706
DAVID LE RESIDENCE
A-23-002-008
PROPOSED
HOUSE EXTENSION
+
PLAN CHECK SUBMITTAL 10.25.2023
2ND PLAN CHECK SUBMITTAL 01.05.2024
BUILDING SAFETY SUBMITTAL 01.25.2024
UPDATE PLAN SET FOR PRESCREEN 02.19.2024
2209 W. LARAMORE LANE
SANTA ANA, CALIFORNIA 92706
UPDATE PLAN SET 03.31.2024
BUILDING SAFETY RESUBMITTAL 07.29.2024
10111914-95
BUILDING SAFETY RESUBMITTAL 08.20.2024
DETAILS
SEE STRUCTURAL DETAIL DRAWINGS
FOR INFORMATION ON WALL AND
FOOTING
2710 N Laird St & 2209 W
Laramore Ln10/7/2024
jamb @ window
SCALE: 3"=1'-0"
head @ window
SCALE: 3"=1'-0"
egress window requirements
SCALE: NO SCALE
exterior door threshold (swing-in)
SCALE: 3"=1'-0"
exterior door head
SCALE: 3"=1'-0"
exterior door jamb
SCALE: 3"=1'-0"
interior door head (jamb similar)
SCALE: 3"=1'-0"
window sill
SCALE: 3"=1'-0"
self-adhered composite flexible flashing system
SCALE: N.T.S.
threshold pan flashing
SCALE: 1 1/2" = 1'-0"A-32
DOOR & WINDOW
D E S I G N
2024 JULY 29
DETACHED ADU
DATEISSUED FOR
I S S U E S
2710 LAIRD AVENUE
SANTA ANA, CALIFORNIA 92706
DAVID LE RESIDENCE
A-23-002-008
PROPOSED
HOUSE EXTENSION
+
PLAN CHECK SUBMITTAL 10.25.2023
2ND PLAN CHECK SUBMITTAL 01.05.2024
BUILDING SAFETY SUBMITTAL 01.25.2024
UPDATE PLAN SET FOR PRESCREEN 02.19.2024
2209 W. LARAMORE LANE
SANTA ANA, CALIFORNIA 92706
UPDATE PLAN SET 03.31.2024
BUILDING SAFETY RESUBMITTAL 07.29.2024
10111914-95
DETAILS
SEE STRUCTURAL DETAIL DRAWINGS
FOR INFORMATION ON WALL AND
FOOTING
2710 N Laird St & 2209 W
Laramore Ln10/7/2024
sliding glass door threshold
SCALE: 3"=1'-0"
sliding wardrobe door sill
exterior
interior
window sill at hardie lap siding
door / window jamb at hardie lap siding
door / window head at cement board sidingdoor / window head at stucco with wood trim
exterior
interior
door / window jamb at stucco with wood trim
A-33
DOOR & WINDOW
D E S I G N
2024 JULY 29
DETACHED ADU
DATEISSUED FOR
I S S U E S
2710 LAIRD AVENUE
SANTA ANA, CALIFORNIA 92706
DAVID LE RESIDENCE
A-23-002-008
PROPOSED
HOUSE EXTENSION
+
PLAN CHECK SUBMITTAL 10.25.2023
2ND PLAN CHECK SUBMITTAL 01.05.2024
BUILDING SAFETY SUBMITTAL 01.25.2024
UPDATE PLAN SET FOR PRESCREEN 02.19.2024
2209 W. LARAMORE LANE
SANTA ANA, CALIFORNIA 92706
UPDATE PLAN SET 03.31.2024
BUILDING SAFETY RESUBMITTAL 07.29.2024
10111914-95
DETAILS
SEE STRUCTURAL DETAIL DRAWINGS
FOR INFORMATION ON WALL AND
FOOTING
2710 N Laird St & 2209 W
Laramore Ln10/7/2024
EXISTING SITE PLAN
SCALE: NO
NTS
D E S I G N
2024 JANUARY 25
DETACHED ADU
DATEISSUED FOR
I S S U E S
2710 LAIRD AVENUE
SANTA ANA, CALIFORNIA 92706
DAVID LE RESIDENCE
A-23-002-008
PROPOSED
HOUSE EXTENSION
+
PLAN CHECK SUBMITTAL 10.25.2023
2ND PLAN CHECK SUBMITTAL 01.05.2024
BUILDING SAFETY SUBMITTAL 01.25.2024
A-50
EXISTING HOUSE
PHOTOS
65
1
2
3
4
10
9
8
7
11
21 3 4
65 7 8
10 119
PROPOSED ADU
EXISTING HOUSE
EXISTING
GARAGE
Note: Covered patio to be demolished
Note: Covered patio to be demolished
2710 N Laird St & 2209 W
Laramore Ln10/7/2024
STRUCTURAL
NOTES
S0
RE
S
T
R
I
C
T
I
V
E
N
O
T
I
C
E
DA
T
E
RE
V
I
S
I
O
N
S
SHEET
SHEET DESCRIPTION
STAMP
NO
:
8/1/24
LE
A
D
D
I
T
I
O
N
&
D
E
T
A
C
H
E
D
A
D
U
DATE:
22
0
9
W
.
L
A
R
A
M
O
R
E
L
N
.
SA
N
T
A
A
N
A
,
C
A
9
2
7
0
6
TH
E
S
E
D
E
S
I
G
N
S
,
D
R
A
W
I
N
G
S
,
A
N
D
SP
E
C
I
F
I
C
A
T
I
O
N
S
A
R
E
E
X
C
L
U
S
I
V
E
T
O
GE
T
S
T
R
U
C
T
U
R
A
L
T
H
E
S
E
D
R
A
W
I
N
G
S
CA
N
N
O
T
B
E
C
O
P
I
E
D
,
T
R
A
N
S
F
E
R
R
E
D
,
O
R
RE
P
R
O
D
U
C
E
D
N
O
R
C
A
N
A
N
Y
O
T
H
E
R
ST
R
U
C
T
U
R
E
S
B
E
B
U
I
L
T
F
R
O
M
T
H
E
M
WI
T
H
O
U
T
W
R
I
T
T
E
N
C
O
N
S
E
N
T
RE
V
I
S
I
O
N
S
30
0
0
E
.
B
I
R
C
H
S
T
R
E
E
T
SU
I
T
E
2
0
3
BR
E
A
,
C
A
9
2
8
2
1
TE
L
:
(
9
0
9
)
5
6
9
-
1
8
8
6
in
f
o
@
G
e
t
S
t
r
u
c
t
u
r
a
l
.
c
o
m
2
JOB: R23-0943
PHONG TR UONG
STATE OF CALIFORNIA
REGISTERED PROFESSIONAL ENGINEER
NO. C70784
EXP. 06/30/2025
CIV IL
2
08
/
0
1
/
2
0
2
4
PL
A
N
C
H
E
C
K
2
SHEET INDEX:
SHEET TITLE
S0 STRUCTURAL NOTES
S1 FOUNDATION PLAN
S2 ROOF FRAMING PLAN
SD1 FOUNDATION & FRAMING DETAILS
SD2 FRAMING DETAILS
WSWH1.1 STRONG WALL ANCHORAGE DETAIL
WSWH2 STRONG WALL FRAMING DETAIL
1.THE GENERAL CONTRACTOR AND EACH SUBCONTRACTOR SHALL VERIFY ALL DIMENSIONS
AND SITE CONDITIONS BEFORE STARTING ANY WORK. THE ENGINEER ( GET STRUCTURAL )
SHALL BE NOTIFIED OF ANY AND ALL DISCREPANCIES.
2.ARCHITECT/DESIGNER SHALL VERIFY ALL DIMENSIONS AND PLAN LAYOUT PRIOR TO CITY
SUBMITTAL. THE ENGINEER ( GET STRUCTURAL ) SHALL BE NOTIFIED OF ANY AND ALL
DISCREPANCIES.
3.DIMENSIONING SHALL TAKE PRECEDENCE OVER SCALES SHOWN ON DRAWINGS. TYPICAL
DETAILS AND GENERAL NOTES ARE MINIMUM REQUIREMENTS TO BE USED WHEN
CONDITIONS ARE NOT SHOWN OTHERWISE.
4.NOTES AND DETAILS ON DRAWINGS SHALL TAKE PRECEDENCE OVER GENERAL NOTES AND
TYPICAL DETAILS. WHERE NO DETAILS ARE SHOWN CONSTRUCTION SHALL CONFORM TO
SIMILAR WORK ON PROJECT.
5.ALL WORK SHALL CONFORM TO THE MINIMUM STANDARDS OF THE 2022 EDITION OF THE
CALIFORNIA BUILDING CODE (CBC), AND ANY OTHER REGULATING AGENCIES WHICH HAVE
AUTHORITY OVER ANY PORTION OF THE WORK, INCLUDING THE STATE OF CALIFORNIA
DIVISION OF INDUSTRIAL SAFETY, AND THOSE CODES AND STANDARDS LISTED IN THESE
NOTES AND SPECIFICATIONS.
6.APPROVAL BY THE INSPECTOR DOES NOT CONSTITUTE AUTHORITY TO DEVIATE FROM THE
PLANS AND/OR SPECIFICATIONS. ANY DESIGN WHICH FAILS TO BE CLEAR OR IS AMBIGUOUS
MUST BE REFERRED TO THE ENGINEER ( GET STRUCTURAL ) FOR INTERPRETATION OR
CLARIFICATION.
7.SEE ARCHITECTURAL, ELECTRICAL AND MECHANICAL DRAWINGS FOR PITS, TRENCHES,
ROOF OPENINGS, DEPRESSIONS ETC. NOT SHOWN ON STRUCTURAL DRAWINGS.
8.VIBRATION EFFECTS OF MECHANICAL EQUIPMENT HAVE NOT BEEN CONSIDERED BY
ENGINEER.
9.THE DESIGN ADEQUACY AND SAFETY OF ERECTION BRACING, SHORING, TEMPORARY
SUPPORTS, ETC. IS SOLE RESPONSIBILITY OF THE CONTRACTOR, AND HAS NOT BEEN
CONSIDERED BY THE ENGINEER ( GET STRUCTURAL ). THE CONTRACTOR IS RESPONSIBLE
FOR THE STABILITY OF THE STRUCTURE PRIOR TO THE APPLICATION OF ALL SHEAR WALLS,
ROOF AND FLOOR DIAPHRAGMS AND FINISH MATERIALS. HE/SHE SHALL PROVIDE THE
NECESSARY BRACING TO PROVIDE STABILITY PRIOR TO THE APPLICATION OF THE
AFOREMENTIONED MATERIALS. STRUCTURAL OBSERVATION JOBSITE VISITS BY THE
ENGINEER SHALL NOT INCLUDE INSPECTION OF THE ABOVE ITEMS.
10.CONTRACTOR SHALL INVESTIGATE SITE DURING CLEARING AND EARTHWORK OPERATIONS
FOR FILLED EXCAVATIONS OR BURIED STRUCTURES SUCH AS CESSPOOLS, CISTERNS,
FOUNDATIONS, ETC. IF ANY SUCH STRUCTURES ARE FOUND, THE ENGINEER ( GET
STRUCTURAL ) AND THE ARCHITECT SHALL BE NOTIFIED IMMEDIATELY.
11.CONSTRUCTION MATERIALS SHALL BE SPREAD OUT IF PLACED ON FRAMED FLOORS OR
ROOF. LOAD SHALL NOT EXCEED THE DESIGN LIVE LOAD PER SQUARE FOOT. PROVIDE
ADEQUATE SHORING AND/OR BRACING WHERE STRUCTURE HAS NOT ATTAINED DESIGN
STRENGTH.
12.CONSTRUCTION DOCUMENTS IDENTIFIED AS "BID SET" ON ANY OR ALL SHEETS MAY BE
SUBJECT TO REVIEW. THIS REVIEW MAY RESULT IN CHANGES WHICH MAY BE MADE TO THE
PLANS PRIOR TO THE ISSUANCE OF THE FINAL CONSTRUCTION SET WHICH WILL CONTAIN
NO "BID SET" DESIGNATIONS. CONSTRUCTION DOCUMENTS IDENTIFIED AS "BID SET" ARE
NOT CONSTRUED AS BEING THE COMPLETED OR FINAL DRAWINGS AND THEY SHOULD NOT
IN ANY WAY BE USED AS SUCH.
13.ALL GUARD AND HANDRAILS SHALL BE DESIGNED TO WITHSTAND A POINT LOAD OF 200
POUNDS APPLIED IN ANY DIRECTION AND AT ANY POINT TO TOP RAIL. A 50 PLF LOAD IS
REQUIRED AT 3-STORY AND MULTI-FAMILY PROJECTS. IF OCCUPANT LOAD IS LESS THAN 50,
A 20 PLF LOAD MAY BE USED.
14.THESE PLANS ARE INTENDED SOLELY FOR THE USE OF THE OWNER FOR CONSTRUCTION
AND ARE EXPRESSLY NOT INTENDED FOR USE IN MARKETING. EXTERIOR ELEVATIONS AND
OTHER DETAILS ON THESE PLANS ARE ONLY A REPRESENTATION AND MAY VARY
SIGNIFICANTLY FROM THE ACTUAL CONSTRUCTION.
15.SLAB-ON-GRADE REQUIREMENTS TO BE PER THE SOIL ENGINEERS RECOMMENDATIONS
SOLELY, U.N.O. THE SLAB-ON-GRADE IS A NON-STRUCTURAL ITEM AND THEREFORE HAS
NOT BEEN DESIGNED BY THE STRUCTURAL ENGINEER, UNLESS NOTED OTHERWISE.
16.IN THE EVENT OF CONFLICT BETWEEN THE ARCHITECTURAL GENERAL NOTES AND THE
STRUCTURAL GENERAL NOTES (SHT SGN), THE MORE STRINGENT REQUIREMENT SHALL
GOVERN.
1.ALL REINFORCING SHALL BE ASTM A-615 GRADE 40 FOR #4 BARS AND SMALLER. ALL
REINFORCING SHALL BE ASTM A-615 GRADE 60 FOR #5 BARS AND LARGER. WELDED WIRE
FABRIC TO BE ASTM A-185, LAP 1-1/2 SPACES, 9" MIN. FOR STRUCTURAL SLABS ALL
REINFORCING #5 AND LARGER TO BE ASTM A-615 GRADE 60
2.ALL BARS SHALL BE DEFORMED AS PER ASTM A615 / A615M.
3.ALL BARS SHALL BE CLEAN OF LOOSE FLAKY RUST, GREASE OR OR OTHER MATERIALS
LIKELY TO IMPAIR BOND.
4.ALL BENDS SHALL BE MADE COLD.
5.SPLICING OF #3-#6 BARS SHALL HAVE A MIN. LAPPING OF 30 DIA. OR 2'-0" MIN. IN ALL
CONTINUOUS REINFORCEMENT OF FOOTINGS AND CONCRETE WALLS, EXCEPT AS NOTED
ON PLANS. MASONRY REINFORCEMENT SHALL HAVE LAPPINGS OF 40 DIA. FOR GRADE 40
AND 48 DIA. FOR GRADE 60 OR 2'-0" MIN., U.N.O.
6.ALL REINFORCING BARS SHALL BE ACCURATELY AND SECURELY PLACED BEFORE
POURING CONCRETE.
7.CONCRETE PROTECTION FOR REINFORCEMENT SHALL BE AT LEAST EQUAL TO THE
DIAMETER OF THE BARS. COVER SHALL BE AS FOLLOW:
CONCRETE MASONRY
A.POURED AGAINST EARTH 3"2"
B.POURED AGAINST FORM BELOW GRADE 2"2"
#6 AND LARGER 2"2'
#5 AND SMALLER 1 1
2"1 1
2"
C.FORMED SLABS 1"1"
D.SLABS ON GRADE (FROM TOP OF SLAB) 1"1"
E.COLUMNS AND BEAMS TO MAIN BARS 1 1
2"2"
F.WALLS
EXPOSED TO WEATHER 1 1
2"1 1
2"
NOT EXPOSED TO WEATHER,
#11 AND SMALLER 3
4"3
4"
#14 AND #18 1 1
2"1 1
2"
1.ALL SITE PREPARATION, EXCAVATION AND COMPACTION SHALL BE DONE UNDER THE
SUPERVISION OF THE LICENSE CONTRACTOR AND THE SOIL ENGINEER (IF APPLICABLE)
2.SEPARATE PERMITS SHALL BE OBTAINED FOR ALL FENCES, PLANTERS AND WALLS, AS
REQUIRED.
3.PROVIDE NON-EXPANSIVE FILL AS REQUIRED TO LEVEL PAD.
4.SURFACE WATER WILL DRAIN AWAY FROM BUILDING. DRAINAGE SHALL BE 2% (MIN.)
FROM BUILDING TO SWALE LINE. SWALE SHALL DRAIN AT 1% (MIN.) FROM REAR OF
BUILDING TO STREET.
5.THERE SHALL BE NO UTILITY TRENCH NEAR THE BUILDING FOUNDATION WHICH EXTEND
DEEPER THAN A 45 DEGREE LINE PROJECTED DOWN AND AWAY FROM THE BOTTOM
OUTSIDE CORNER OF ANY FOOTING.
6.SLAB SUBGRADE REQUIREMENTS ARE NOT WITHIN THE SCOPE OF WORK AND/OR LIABILITY
OF ENGINEER OF RECORD ( GET STRUCTURAL ).
7.ALL HOLDOWN ANCHORS, POST BASES AND HOLDOWN BOLTS SHALL BE TIED INTO PLACE
PRIOR TO FOUNDATION INSPECTION.
8.PLACE 20'-0" REBAR IN FOUNDATION AT SERVICE LOCATIONS. STUB UP REBAR ABOVE THE
FLOOR BY ELECTRIC SERVICE METERS.
9.FOR THE LOCATION OF CONTROL JOINTS, REFER TO THE FOUNDATION PLAN. (ZIP STRIP OR
EQUAL). MINIMUM OF 20'-0" O.C. EACH WAY IS RECOMMENDED.
10.DRIVEWAY PAVING SHALL BE 4" PORTLAND CEMENT CONCRETE (5 SACKS MIN.), U.N.O.
11.FOR POST-TENSION SLAB, REFER TO APPROVED PLANS PREPARED BY OTHERS (WHEN
OCCURS).
12.MINIMUM SLAB REINFORCEMENT AND PAD REQUIREMENT SHALL CONFORM TO THE LOCAL
AHJ REQUIREMENTS OR THE SOILS ENGINEER'S RECOMMENDATIONS (IF APPLICABLE)
FOUNDATION/SITEWORK
REINFORCING STEEL
GENERAL NOTES
EXPOSURE
REQUIREMENTS FOR CONCRETE BY EXPOSURE CLASS
(ACI 318-19, Table 19.3.2.1)
CLASS
MAX.
W/C
MIN. F'c
(PSI)
ADDITIONAL REQUIREMENTS
AIR CONTENT LIMITS ON CEMENT. MAT'L.
F0 N/A 2,500 N/A N/A
F1 0.45 4,500 ACI 318-19 TABLE 19.3.3.1 N/A
F2 0.45 4,500 N/A
F3 0.45 4,500 ACI 318-19 TABLE 19.2.1.1
EXPOSURE
CLASS
1
1
FREEZING/THAWING
SULFATE
LOW PERMEABILITY
CORROSION
ACI 318-19 TABLE 19.3.3.1
ACI 318-19 TABLE 19.3.3.1
NOTES:
1. FOR LIGHT WEIGHT CONCRETE, SEE ACI 318-19, SECTION 19.2.4.2
2.ALTERNATIVE COMBINATIONS OF CEMENTITIOUS MATERIAL OF THOSE LISTED IN TABLE 19.3.2.1 SHALL BE
PERMITTED WHEN TESTED FOR SULFATE RESISTANCE AND MEETING THE CRITERIA IN SECTION 19.3.1.1
3.FOR SEAWATER EXPOSURE, OTHER TYPES OF PORTLAND CEMENTS WITH TRICALCIUM ALUMINATE (C3A)
CONTENTS UP TO 10% ARE PERMITTED IF THE W/C DOES NOT EXCEED 0.40
4.OTHER AVAILABLE TYPES OF CEMENT SUCH AS TYPE III OR TYPE I ARE PERMITTED IN EXPOSURE CLASSES S1
or S2 IF C3A CONTENTS ARE LESS THAN 8% or 5%, RESPECTIVELY
5.THE AMOUNT OF THE SPECIFIC SOURCE OF POZZOLAN or SLAG TO BE USED SHALL NOT BE LESS THAN THE
AMOUNT DETERMINED BY SERVICE RECORD TO IMPROVE SULFATE RESISTANCE WHEN USED IN CONCRETE
CONTAINING TYPE V CEMENT. ALT: THE AMOUNT OF THE SPECIFIC SOURCE OF THE POZZOLAN or SLAG TO BE
USED SHALL NOT BE LESS THAN THE AMOUNT TESTED PER ASTM C1012 AND MEETING CRITERIA OF ACI 318-19,
SECTION 19.3.1.1
6.WATER SOLUBLE CHLORIDE ION CONTENT THAT IS CONTRIBUTED FROM THE INGREDIENTS INCLUDING
WATER, AGGREGATES, CEMENT AND ADMIXTURES SHALL BE DETERMINED PER ASTM C1218 BETWEEN 28 AND
42 DAYS.
1.ALL CONCRETE SHALL CONFORM TO THE LATEST EDITION OF THE CALIFORNIA RESIDENTIAL CODE (CRC 2022)
2.CONCRETE SHALL CONFORM TO "EXPOSURE CLASS" REQUIREMENTS OF ACI 318-19 REFER TO SOILS REPORT FOR
SOIL CONDITIONS.
3.ALL CEMENT SHALL CONFORM TO ASTM C-150, C-595 OR C-1157. USE CEMENT TYPE TYPE II
4.FINE AND COARSE AGGREGATE SHALL CONFORM TO ASTM C-33 FOR STANDARD WEIGHT
CONCRETE AND ASTM C-330 FOR LIGHTWEIGHT CONCRETE.
5.CONCRETE FOR SLAB-ON-GRADE SHALL HAVE A MAX. SLUMP OF 5" PER ASTM C-143 AND
MAX. SLUMP OF 4" FOR FOOTINGS AND GRADE BEAMS, U.N.O. READY-MIX CONCRETE SHALL
BE MIXED AND DELIVERED PER ASTM C-94.
6.DRYPACK SHALL BE COMPOSED OF ONE PART PORTLAND CEMENT TO NOT MORE THAN
THREE PARTS SAND.
7.ANCHOR BOLTS, HOLDOWN BOLTS, DOWELS, INSERTS, ETC. SHALL BE SECURED INTO
PLACE AND INSPECTED PRIOR TO POURING CONCRETE.
8.CONCRETE SHALL BE CURED BY KEEPING CONTINUOUSLY WET FOR 10-DAYS OR BY AN
APPROVED CURING COMPOUND.
9.REFER TO ARCHITECTURAL, MECHANICAL, ELECTRICAL AND PLUMBING DRAWINGS FOR
MISCELLANEOUS ITEMS TO BE CAST INTO CONCRETE AND FLOOR STEPS, DEPRESSIONS,
PITS, CURBS, ETC.
10.SEE ARCHITECTURAL DRAWINGS FOR LOCATIONS OF EXPANSION JOINTS, A/C PADS,
SCORING, ETC. FOR CONCRETE WALKS AND SLABS.
11.ALL STRUCTURAL CONCRETE f'c = 2500 PSI
ALL SLAB-ON-GRADE f'c = 2500 PSI
ALL CONTINUOUS FOOTINGS AND PADS f'c = 2500 PSI
ALL CONCRETE SHALL REACH MINIMUM COMPRESSIVE STRENGTH 28 - DAYS (MIN. W/C
RATIO=0.5).
CONCRETE LUMBER/CARPENTRY
DESIGN LOADS
1.ALL GLUED LAMINATED MEMBERS SHALL BE MADE OF 1-1/2" DOUGLAS-FIR LARCH (DF)
LAMINATIONS, COMBINATION 24F-V4 PER AITC/APA (U.N.O.).
2.DESIGN VALUES: Fb=2400 PSI; Fv=240 PSI; E=1.8X106 PSI
3.INDUSTRIAL APPEARANCE GRADE PER APA-EWS SHALL BE USED, WITH A MOISTURE
CONTENT BETWEEN 7 - 14 PERCENT, UNLESS NOTED OTHERWISE.
4.FABRICATOR SHALL BE A MEMBER OF AITC AND ALL FABRICATION SHALL BE PERFORMED
IN ACCORDANCE WITH AITC-A190.1 & ASTM-3737. LUMBER SHALL BE MARKED WITH AN
AITC or APA-EWS GRADE STAMP INDICATING CONFORMANCE WITH ALL APPLICABLE
SPECIFICATIONS AND REQUIREMENTS.
5.GLUED LAMINATED MEMBERS SHALL BE ACCOMPANIED BY A CERTIFICATE OF INSPECTION.
CONTRACTOR SHALL BEAR EXPENSES OF INSPECTION AND TESTS. A CERTIFICATE OF
INSPECTION SHALL BE SUBMITTED TO THE BUILDING DEPARTMENT PRIOR TO
INSTALLATION.
6.ALL GLUED LAMINATED BEAMS WILL HAVE A STANDARD CAMBER BASED ON A RADIUS =
3500, UNLESS NOTED OTHERWISE.
PARALLAM PSL 2.2E BY I-LEVEL PER ESR-1387
f b = 2900 PSI; f v = 290 PSI; E = 2.2x106 PSI
TIMBERSTRAND LSL 1.55E BY I-LEVEL PER ESR-1387
f b = 2250 PSI; f v = 310 PSI; E = 1.55x106 PSI
MICROLAM LVL BY I-LEVEL PER ESR-1387
f b = 2600 PSI; f v = 285 PSI; E = 2.0x106 PSI
7.ALTERNATE ENGINEERED WOOD PRODUCTS MUST BE APPROVED IN WRITING BY ENGINEER
( GET STRUCTURAL ) PRIOR TO INSTALLATION.
8.PROVIDE MULTIPLE 2x4 SQUASH BLOCKS UNDER BEARING POINT LOAD (POST) (OR MSB)
FROM ABOVE TO TOP PLATES BELOW AT FLOOR LEVEL.
9.I-LEVEL I-JOISTS PER ICC ESR#1533
10.LOUISIANA PACIFIC I-JOISTS PER ICC ESR#1130
11.BOISE CASCADE I-JOISTS PER ICC ESR#1336
12.ROSEBURG I-JOISTS PER ICC ESR#1251
13.PROVIDE DOUBLE I-JOISTS OR DOUBLE I-JOIST BLOCKS WHEN 16d SOLE PLATE NAILING
(SPN) IS LESS THAN 4" O.C. AT SHEAR WALL ABOVE.
14.REFER TO I-JOIST MANUFACTURER SPECIFICATION FOR DRILLING OF HOLES THRU I-JOIST
WEB. NOTCHING OF I-JOIST FLANGE IS PROHIBITED.
GLULAMS/MFR. WD. PROD.
SIMPSON ICC - ESR REPORTS
1.CONTINUOUS AND PERIODIC SPECIAL INSPECTION IS REQUIRED FOR THE WORK AS
DESCRIBED IN CBC 2022 CHAPTER 17, SEE INSPECTION SCHEDULE BELOW ONLY CHECKED
ITEMS ARE REQUIRED
2.APPROVAL BY THE INSPECTOR DOES NOT MEAN APPROVAL OF FAILURE TO COMPLY WITH
THE PLANS OR SPECIFICATIONS. ANY DETAIL THAT FAILS TO BE CLEAR OR IS AMBIGUOUS
MUST BE REFERRED TO THE STRUCTURAL ENGINEER FOR INTERPRETATION OR
CLARIFICATION
3.FOR VERIFICATION AND INSPECTION OF SOILS SEE SOILS REPORT
4.CONTINUOUS SPECIAL INSPECTION PER AWS D1.1 IS REQUIRED FOR ALL STRUCTURAL
STEEL WELDING, EXCEPT FOR SINGLE PASS FILLET WELDS NOT EXCEEDING 5/16" IN SIZE
WELDING INSPECTORS SHALL BE AWS Q.C.-1 CERTIFIED
5.STRUCTURAL WOOD. PERIODIC SPECIAL INSPECTION IS REQUIRED FOR WOOD SHEAR
WALLS, SHEAR PANELS, AND DIAPHRAGMS, INCLUDING NAILING, BOLTING, ANCHORING,
AND OTHER FASTENING OF COMPONENTS OF THE SEISMIC FORCE RESISTING SYSTEM,
INCLUDING WOOD SHEAR WALLS, WOOD DIAPHRAGMS, DRAG STRUTS, BRACES, SHEAR
PANELS, AND HOLDOWNS EXCEPTION: SPECIAL INSPECTION IS NOT REQUIRED FOR WOOD
SHEAR WALLS, SHEAR PANELS AND DIAPHRAGMS, INCLUDING NAILING, BOLTING,
ANCHORING AND OTHER FASTENING TO OTHER COMPONENTS OF THE
SEISMIC-FORCE-RESISTING SYSTEM, WHERE THE FASTENER SPACING OF THE SHEATHING
IS MORE THAN 4 INCHES ON CENTER (O.C.) INSPECTIONS SHALL BE PERFORMED BEFORE
COVERING
6.CONTRACTORS RESPONSIBLE FOR CONSTRUCTION OF A WIND OR SEISMIC FORCE
RESISTING SYSTEM/COMPONENT LISTED IN THIS STATEMENT OF SPECIAL INSPECTION
SHALL SUBMIT A WRITTEN STATEMENT OF RESPONSIBILITY TO THE LADBS INSPECTORS
AND THE OWNER PRIOR TO THE COMMENCEMENT OF WORK ON SUCH A SYSTEM OR
COMPONENT PER SEC 1704.4.
7.WHERE FABRICATION OF MEMBERS AND ASSEMBLIES IS PERFORMED ON THE PREMISES OF
A FABRICATOR'S SHOP, SPECIAL INSPECTION OF THE FABRICATED ITEMS SHALL BE
REQUIRED BY THIS SECTION, UNLESS THE FABRICATOR IS REGISTERED AND APPROVED
TO PERFORM SUCH WORK WITHOUT SPECIAL INSPECTION. APPROVAL SHALL BE BASED
UPON REVIEW OF THE FABRICATOR'S WRITTEN PROCEDURAL AND QUALITY CONTROL
MANUALS AND PERIODIC AUDITING OF FABRICATION PRACTICES BY AN APPROVED
SPECIAL INSPECTION AGENCY. AT COMPLETION OF FABRICATION, THE APPROVED
FABRICATOR SHALL SUBMIT A CERTIFICATE OF COMPLIANCE TO THE BUILDING OFFICIAL
STATING THAT THE WORK WAS PERFORMED IN ACCORDANCE WITH THE APPROVED
CONSTRUCTION DOCUMENTS. CONTRACTOR SHALL BE RESPONSIBLE OF VERIFYING
APPROVAL OF FABRICATOR.
TYPE OF WORK
CONCRETE WORK
SHOTCRETE WORK
DRIVEN DEEP FOUND. ELEMENT
COLD FORMED STEEL
STRUCTURAL WOOD
HIGH LOAD DIAPHRAGMS
MASONRY WORK
HIGH STRENGTH BOLTING
STRUCTURAL STEEL WELDING
STRUCTURAL STEEL
POST INSTALLED ANCHORS
CAST IN PLACE DEEP FOUND.
REINFORCING STEEL
SOIL CONDITION
CODE REFERENCE
CBC TABLE 1705.3
CBC TABLE 1705.3
CBC 1705.3.1
CBC TABLE 1705.3
CBC 1705.2
CBC 1705.2
CBC 1705.2
CBC 1705.4
CBC 1705.5.1
CBC 1705.11.1
CBC 1705.11.2
SEE NOTE 5 ABOVE
SEE ALSO ICC APPROVAL
REMARKS
INSPECTION SCHEDULE
CBC 1705.7
CBC TABLE 1705.8
CBC TABLE 1705.6 SEE SOILS REPORT FOR COMPLIANCE
SPECIAL INSPECTION
SEISMIC DESIGN DATA
IMPORTANCE FACTOR 1.0
SITE CLASS D
SS 1.345
S1 0.478
SDS 1.076
SD1 0.581
SDC D
LATERAL FORCE RESISTING SYSTEM A.15
BASE SHEAR
CS 0.166
R 6.5
W 2.50
PROCEDURE USED ELF
REDUNDANCY FACTOR 1.3
WIND DESIGN
PROCEDURE USED MWFRS
BASIC WIND SPEED 95 MPH
RISK CATEGORY II
WIND EXPOSURE C
SOIL
1500 PSF PER CBC 2022
ROOF
DL =10 PSF
LL =20 PSF
VAULTED ROOF
DL =15 PSF
LL = 20 PSF
FLOOR
DL =15 PSF
LL =40 PSF
CEILING
DL =5 PSF
LL =10 PSF
EXTERIOR WALL
DL =15 PSF
INTERIOR WALL
DL =10 PSF
IP(MS), IS(<70), (MS)
IP(HS), IS(<70), (HS)
IP(HS)+POZ.orSLAG5
IS(<70), (HS)+POZ.5 HS+POZZOLAN or SLAG5 NOT PERMITTED
NOT PERMITTED
V+POZZOLAN or SLAG5
CEMENTITIOUS MATERIAL TYPE2
HS
MS
---------
---
---
V4
II3
N/AS0 2,500
S1 0.50 4,000
S2 0.45 4,500
4,5000.45S3
P1
P0 N/A
0.50 4,000
2,500
NONE
NONE
MAX.
W/C1
MIN. F'c
(PSI)
MAX. CHLORIDE ION CONTENT % BY WT.6
MAX.
W/C1
MIN. F'c
(PSI)ADDITIONAL REQUIREMENTSEXPOSURE
CLASS
EXPOSURE
CLASS
MAX.
W/C1
MIN. F'c
(PSI)
CALCIUM
CHLORIDEASTM C1157ASTM C595ASTM C150
C0 N/A 2,500 1.00 0.06 ---
C1 N/A 2,500 0.30 0.06 ---
C2 0.40 5,000 0.15 0.06 ACI 19.3.2.1 & 20.6.1.4.2
RELATED
PROVISIONSREINFORCED CONC.PRESTRESSED CONC.
1.ALL STRUCTURAL SAWN LUMBER SHALL BE GRADED BY ONE OF THE FOLLOWING:
W.C.L.I.B., W.W.P.A., N.L.G.A, or PS 20.
2.ALL WOOD BEARING ON CONCRETE OR MASONRY SHALL BE PRESSURE TREATED
DOUGLAS FIR (PTDF), U.N.O
3.HOLES FOR BOLTS SHALL BE BORED WITH A BIT 1/32" TO 1/16" LARGER THAN THE
NOMINAL BOLT DIAMETER.
4.ALL BOLTS SHALL BE RE-TIGHTENED PRIOR TO APPLICATION OF FINISH MATERIALS
(PLYWOOD, PLASTER, DRYWALL, INSULATION, ETC.)
5.STRUCTURAL MEMBERS SHALL NOT BE CUT FOR PIPES, ETC. UNLESS SPECIFICALLY NOTED
OR DETAILED. CONTACT ENGINEER IF NOT SHOWN.
6.CROSS-BRIDGING SHALL BE PROVIDED AT 8'-0" O.C. MAX. FOR ALL 2X FLOOR JOISTS OVER
10" IN DEPTH AND ALL 2X ROOF RAFTERS OVER 10" DEPTH. USE SOLID BLOCKING OR AN
APPROVED METAL TYPE BRIDGING.
7.ALL STRUCTURAL PLYWOOD SHALL BE A.P.A. RATED SHEATHING (OR OSB) EXPOSURE 1 OR
EXTERIOR UNLESS NOTED OTHERWISE AND CONFORM TO DOC PS1 OR PS2. EACH SHEET
SHALL BE IDENTIFIED BY GRADE MARK OF D.F.P.A OR A.P.A.
8.ALL BOLTS BEARING ON WOOD SHALL HAVE STANDARD CUT WASHERS UNDER HEAD AND
NUT UNLESS NOTED OTHERWISE.
9.ALL METAL ANCHORS, FASTENERS AND CONNECTORS ETC. SHALL BE FROM "SIMPSON
STRONG-TIE" (TM). SUBSTITUTIONS MUST BE ICC-ESR PRODUCTS AND PRE-APPROVED IN
WRITING BY ENGINEER ( GET STRUCTURAL ).
11. ALL STRUCTURAL LUMBER SHALL BE DOUGLAS FIR-LARCH (OR BTR.), 19% MAX.
MOISTURE CONTENT, OF THE FOLLOWING GRADES, U.N.O.:
12.FLOOR SHEATHING TO BE NAILED AND GLUED TO THE JOISTS. USE ADHESIVES PER A.P.A.
AFG-01 OR ASTM D3498.
13.FRAMING CONTRACTOR SHALL PROVIDE BACKING AS REQUIRED FOR ALL LIGHT
FIXTURES, CABINETS, WARDROBES, TOWEL BARS, AND HANDRAILS AS REQUIRED AND
REQUESTED BY GENERAL CONTRACTOR.
14.WHEN PLYWOOD SIDING IS USED AS AN EXTERIOR OR INTERIOR WALL COVERING,
PROVIDE SOLID BLOCKING AT ANY HORIZONTAL JOINTS BETWEEN SOLE PLATE AND ANY
TOP PLATE. "Z" BAR METAL SHALL BE USED AT EXTERIOR HORIZONTAL JOINTS.
15.INSTALL FIREBLOCKS TO CUT OFF ALL HORIZONTAL AND VERTICAL DRAFT OPENINGS
BETWEEN TWO STORIES AND ROOF ATTIC SPACES. FIREBLOCKS SHALL BE OF 2 INCH
NOMINAL THICKNESS. LOCATION OF FIREBLOCKS SHALL INCLUDE:
A.STUD WALLS AT FURRED SOFFITS, CEILING AND FLOOR LEVELS.
B.AROUND TOP, BOTTOM, SIDES AND ENDS OF SLIDING POCKET DOORS
C.BETWEEN STAIR STRINGERS AT TOP AND BOTTOM OF RUN AND BETWEEN STUDS IN A
WALL PARALLEL AND ADJOINING RUN OF STAIRS.
22.FASTENING OF MULTIPLE MEMBERS:
DOUBLE & TRIPLE JOISTS;
16d NAILS AT 12" O.C STAGGERED (BOTH SIDES FOR TRIPLES).
FOUR OR MORE JOISTS;
1/2" DIA. M.B's AT 18" O.C STAGGERED.
4X OR LARGER BEAMS;
1/2" DIA. M.B's AT 12" O.C STAGGERED.
23.ALL ROUGH OR RESAWN BEAMS ARE TO BE FREE OF GRADING STAMP LABELS AND FREE
OF HEART CENTER (FOHC).
24.ALL HANGING 2X JOISTS SHALL UTILIZE SIMPSON "LUS" HANGERS, U.N.O. AND SIMPSON
"IUS" FOR I-JOISTS, U.N.O.
25.ALL BEARING WALLS ON A WOOD FLOOR ARE TO BE SUPPORTED WITH DOUBLE JOISTS OR
SOLID BLOCKING, UNLESS NOTED OTHERWISE.
26.ALL BEAMS TO BE SUPPORTED WITH FULL BEARING STUDS OR POSTS, U.N.O.
27.ROOF SHEATHING IS TO CONTINUE UNDER "CALIFORNIA FRAMING", TYP.
28.APPLY SHEAR WALL PLYWOOD PRIOR TO ALL BOX-OUTS, FUR-OUTS, SOFFITS OR ANY
OTHER FRAMING THAT MAY INTERRUPT CONTINUITY OF PLYWOOD.
29.PROVIDE FURRING AS NEEDED TO ALIGN NON-SHEAR WALLS WITH SHEAR WALLS.
30.PROVIDE 4X OR DOUBLE 2X MEMBERS UNDER SOLE PLATE NAILING LESS THAN 4 in. O.C.,
U.N.O.
31.TOP PLATE BREAKS AND SPLICES SHALL OCCUR OVER A STUD OR POST.
32.PROVIDE SOLID BLK'G BETWEEN PERPENDICULAR JOIST AT BEARING AND AT SHEAR
WALLS.
33.ALL EXPOSED BEAMS AND HEAVY TIMBER RECOMMENDED TO BE FREE OF HEART CENTER
(FOHC).
34.ALL CONVENTIONAL FRAME PORTIONS OF STRUCTURE ARE TO BE CONSTRUCTED PER
SECTION 2308 OF THE CALIFORNIA BUILDING CODE (CBC), U.N.O.
35.ALL SHOP DRAWINGS ARE TO BE REVIEWED BY THE GENERAL CONTRACTOR AND THE
ARCHITECT PRIOR TO SUBMITTAL FOR ENGINEER ( GET STRUCTURAL ) REVIEW.
36.COMMON NAILS SHALL BE USED FOR ALL SHEATHING AND TOP PLATE SPLICES. BOX
NAILS MAY BE USED AT SOLE PLATE NAILING. ALL HARDWARE SHALL BE INSTALLED
WITH NAILS PER THE MANUFACTURERS SPECIFICATIONS AND RECOMMENDATIONS.
37.FASTENERS FOR PRESERVATIVE-TREATED OR FIRE-RETARDANT-TREATED WOOD SHALL
BE OF HOT DIPPED ZINC-COATED GALVANIZED STEEL IN ACCORDANCE WITH ASTM A 153
SINGLE/REPTITIVE
2X4 #2: Fb = 1350/1552 PSI ; Fv=180 PSI, E=1.6x106
2X6 #2: Fb = 1170/1345 PSI
2X8 #2: Fb = 1080/1242 PSI
2X10 #2: Fb = 990/1138 PSI
2X12 #2: Fb = 900/1150 PSI
2X14 #2: Fb = 810/ 931 PSI
4X4 #2: Fb = 1350 PSI
4X6 #2: Fb = 1170 PSI
4X8 #2: Fb = 1170 PSI
4X10 #2: Fb = 1080 PSI
4X12 #1: Fb = 1100 PSI ; Fv=180 PSI, E= 1.7x106
4X14 #1: Fb = 1000 PSI
4X16 #1: Fb = 1000 PSI
6X10 #1: Fb = 1350 PSI ; Fv=170 PSI, E=1.6x106
6X12 #1: Fb = 1350 PSI
WALLS
2X4 STUDS (UP TO 8')"STANDARD" OR BETTER
2X4 STUDS (OVER 8')NO.2 OR BETTER
2X PLATES & 3X PLATES "CONSTRUCTION GRADE" OR BETTER
2X6 STUDS NO.2
2X JOIST NO.2
BEAMS AND STRINGERS
4X10 AND SMALLER NO.2
4X12 AND LARGER NO.1
6X AND 8X NO.1
4x POST/TIMBERS AND LARGER NO.1
ROOF PLANKING AND DECKING COM.DEX.
BOARD SHTG. AND STRIPPING SUITABLE FOR INTENDED USE.
2018 NDS STRESS VALUES FOR DOUGLAS FIR-LARCH:
TABLE 2304.10.1 FASTENER SCHEDULE FOR STRUCTURAL MEMBERS
(Table reflects CBC 2022 options see code for more options)
ITEM DESCRIPTION OF BUILDING ELEMENTS
Roof
1 Blocking between ceiling joists, rafters or trusses to top
2
3
4
5
6
8
10
Ceiling joists not attached to parallel rafter, laps over
partitions (no thrust)
Ceiling joist attached to parallel rafter (heel joint)
Collar tie to rafter
Rafter or roof truss to top plate
Wall
Stud to stud (not at braced wall panels)
9
Built-up header (2" to 2" header)
11
12
13
14
15
16d
16d
16d
4-8d
16d
8-16d
16d
Bottom plate to joist, rim joist, band joist or blocking
at braced wall panels
16
17
18
19
20
Floor
21
22
23
24 2" subfloor to joist or girder
25
26
27
28
3-8d
8d
2-8d
2-16d
2-16d
20d
3-16d
3-16d
Toenail
6″ o.c., toenail
Face nail
Face nail
Each bearing, face nail
32" o.c., face nail at top and
End nail
2-16d
4-8d
2-16d
2-16d
2-8d
3-8d
Face nail
Face nail
24″ o.c. face nail
16” o.c. face nail
16″ o.c. each edge, face nail
Toenail
16" o.c. face nail
Each side of end joint, face nail
16" o.c. face nail
16" o.c. face nail
Toenail
Face nail
Face nail
3-8d
3-8d
3-16d
XX
3-10d
3-10d
Each end, toenail
Each joist, toenail
Face nail
Face nail
Face nail
Toenail,c
NUMBER AND TYPE OF
FASTENER SPACING OF FASTENERS
Ceiling joists to top plate
Stud to stud and abutting studs at intersecting wall
Continuous header to stud
Top plate to top plate
Top plate to top plate, at end joints
Bottom plate to joist, rim joist, band joist or blocking
Stud top or bottom plate
Top plates, laps at corners and intersections
1" brace to each stud and plate
1" x 6" sheathing to each bearing
1" x 8" and wider sheathing to each bearing
For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 mile per hour = 0.447 m/s; 1ksi = 6.895 MPa.
a. Nails spaced at 6 inches at intermediate supports where spans are 48 inches or more. For nailing of wood structural panel and particleboard
diaphragms and shear walls, refer to Section 2305. Nails for wall sheathing are permitted to be common, box or casing.
b. Spacing shall be 6 inches on center on the edges and 12 inches on center at intermediate supports for nonstructural applications.
c. Where a rafter is fastened to an adjacent parallel ceiling joist in accordance with this schedule and the ceiling joist is fastened to the top plate
d. RSRS-01 is a Roof Sheathing Ring Shank nail meeting the specifications in ASTM F1667.
Joist to sill, top plate, or girder
Rim joist, band joist, or blocking to top plate
1" x 6" subfloor or less to each joist
2" planks (plank & beam - floor & roof)
Built-up girders and beams, 2" lumber layers
Ledger strip supporting joists or rafters
Joist to band joist or rim joist
Each joist or rafter, face nail
plate or other framing below
Blocking between rafters or truss not at the wall top
plate, to rafter or truss
2-8d Each end, toenail
Flat blocking to truss and web filler 16d @ 6" o.c.Face nail
2-16d End nail
7 Roof rafters to ridge valley or hip rafters; or roof rafter 2-16d End nail
to 2-inch ridge beam 3-10d Toe nail
corners (at braced wall panels)
(minimum 24" lap splice
length each side of end joint)
(not at braced wall panels)
2-16d End nail
bottom staggered on
opposite sides
29 2-8d Each end, toenailBridging or blocking to joist, rafter or truss
Wood structural panels (WSP), subfloor, roof and interior wall sheathing to framing and particleboard wall sheathing to framing,a
EDGES
(INCHES)
INTERMEDIATE
SUPPORTS
(INCHES)
30 6d common nail (subfloor and wall)3/8"-1/2"6 12
8d common nail (roof)
31 8d common nail19/32"-3/4"6 12
32 10d common nail or 8d deformed7/8"-1 1/4"6 12
Other exterior wall sheathing
33 1 1/2" galvanized roofing nail (7/16" head diameter);1/2" fiberboard sheathing, b 3 6
1 1/4" 16 gage staple with 7/16" or 1" crown
34 1 3/4" galvanized roofing nail (7/16" head diameter);25/32" fiberboard sheathing, b 3 6
1 1/2" 16 gage staple with 7/16" or 1" crown
Wood structural panels, combination subfloor underlayment to framing
35 8d common nail3/4" and less 6 12
6d deformed nail
36 8d common nail7/8"-1"6 12
8d deformed nail
37 10d common nail1 1/8"-1 1/4"6 12
8d deformed nail
Panel siding to framing
38 6d corrosion-resistant siding1/2" or less 6 12
6d corrosion-resistant casing
39 8d corrosion-resistant siding5/8"6 12
8d corrosion-resistant casing
Interior paneling
40 4d casing1/4"
4d finish
6 12
41 6d casing3/8"
6d finish (Panel supports at 24 inches)
6 12
Panel supports at 16 inches (20 inches if strength axis in the long direction of the panel, unless otherwise marked).
in accordance with this schedule, the number of toenails in the rafter shall be permitted to be reduced by one nail.
ESR-1056 TITEN HD SCREW ANCHOR
ESL-1168 SET-3G EPOXY ADHESIVE ANCHORS IN CRACKED AND UNCRACKED CONCRETE
ESR-1622 POST BASE CONNECTORS FOR WOOD CONSTRUCTION
ESR-1679 STEEL STRONG-WALL SHEAR PANELS
ESR-2105 STRAPS
ESR-2236 STRONG-DRIVE SDS SCREWS
ESR-2330 SCREW HOLD-DOWN (HOLDOWN) CONNECTORS
ESR-2523 INDEX OF SIMPSON STRONG-TIE STAMPED AND WELDED COLD-FORMED STEEL
PRODUCTS FOR WOOD OR COLD-FORMED STEEL CONSTRUCTION
ESR-2551 ADJUSTABLE HANGERS AND HIP CONNECTORS FOR WOOD FRAMING
ESR-2552 SIMPSON STRONG-TIE® FACE-MOUNT HANGERS FOR SAWN LUMBER,
STRUCTURAL COMPOSITE LUMBER (SCL), PREFABRICATED WOOD I-JOISTS AND
GLULAM BEAMS (ENGINEERED WOOD PRODUCTS)
ESR-2553 TOP-FLANGE HANGERS FOR SAWN LUMBER
ESR-2604 COLUMN CAPS FOR WOOD CONSTRUCTION
ESR-2608 STUD SHOES, PLATE TIES, WALL BRACING, AND JOIST BRIDGING FOR WOOD
CONSTRUCTION
ESR-2611 SSTB SERIES AND SB SERIES CAST-IN-PLACE ANCHOR BOLTS
ESR-2613 HURRICANE AND SEISMIC STRAPS AND TIES FOR WOOD FRAMING
ESR-2615 TOP-FLANGE HANGERS FOR ENGINEERED WOOD PRODUCTS (EWP)
ESR-2616 CONNECTORS ATTACHING WOOD MEMBERS TO CONCRETE CONSTRUCTION
ESR-2652 STRONG-WALL WOOD SHEARWALL PANELS (WSWS) STRONG-WALL SB SHEARWALL
PANELS (SWSBS)
ESR-2920 CAST-IN-PLACE STRAP STYLE HOLDOWNS AND PURLIN ANCHORS IN CONCRETE
ESR-3006 STRONG-DRIVE X AND FPHSD SELF-DRILLING TAPPING SCREWS
ESR-3046 STRONG-DRIVE SD AND SDWF SERIES SCREWS
ESR-3050 EMBEDDED COLUMN BASES IN CONCRETE
ESR-3096 CONNECTORS USING SD-SERIES SCREWS
ESR-4057 SET-3G EPOXY ADHESIVE ANCHORS IN CRACKED AND UNCRACKED CONCRETE
2710 N Laird St & 2209 W
Laramore Ln10/7/2024
EXISTING CONCRETE SLAB ON GRADE
4" CONCRETE SLAB ON GRADE W/ #4 @ 16" O.C.
E.W. CENTERED IN SLAB OVER 10 MIL VISQUEEN
OVER 4" OF 1/2" GRAVEL (CALGREEN 4.505.2.1)
4" CONCRETE SLAB ON GRADE W/ #4
@ 16" O.C. E.W. CENTERED IN SLAB
OVER 10 MIL VISQUEEN OVER 4" OF
1/2" GRAVEL (CALGREEN 4.505.2.1)
1
2
3
A
4'-0"
C
3'-2"
C
2'-11"
C
5'
-
1
"
A
3'
-
9
"
C
3'
-
9
"
A
8'-0"
A CB D E F G
4
5
A
4'-0"
B
8'
-
0
"
C
4'
-
0
"
WSWH 12X8
W/1" STD. A.B.
3
WSWH1.1
5'-8" x24"x24" DEEP CONCRETE GRADE
BEAM W/(4) #5 TOP AND BOTTOM
P30
P30
EXISTING CONCRETE SLAB ON GRADE
1
SD1
HDU
2
4X4
HDU
2
4X4 HDU2
4X4
HDU2
4X4
HDU
2
4X4
HDU
2
4X4
HDU
2
4X4
HDU
2
4X4
HDU
4
4X4
HDU
44X4
HD
U
2
4X
4
HD
U
2
4X
4
HD
U
2
4X
4
HDU2
4X4
1
SD1
1
SD1 1
SD1
1
SD1
1
SD1
1
SD1
3
SD1
3
SD1
3
SD1
3
SD1
3
SD1
3
SD1
3
SD1
3
SD1
3
SD13
SD1
3
SD1
3
SD1
3
SD1
3
SD1
1
SD1HD
U
2
4X
4
6
SD1
HD
U
2
4X
4
6
SD1
HD
U
2
4X
4
HD
U
2
4X
4
HDU2
4X4
HDU2
4X4 4
SD1
8
SD1
9
SD1
7
SD1
10
SD1
10
SD1
8
SD1
11
SD1
11
SD1
11
SD1
11
SD1
12
SD1
12
SD1
2
SD1
4
SD1
4" CONCRETE SLAB
ON GRADE W/ #4 @
16" O.C. E.W.
CENTERED IN SLAB
OVER 4" OF 1/2"
GRAVEL
16
SD1
PP
17
SD1
1'
18" SQ X 18" DEEP PAD FOOTING
W/(3)#4 E.W. TOP AND BOT
18
SD1
18
SD1
P18 P18
P18P18
5
SD1
5
SD1
5
SD1
5
SD1
2'
FOUNDATION
PLAN
RE
S
T
R
I
C
T
I
V
E
N
O
T
I
C
E
DA
T
E
RE
V
I
S
I
O
N
S
SHEET
SHEET DESCRIPTION
STAMP
NO
:
8/1/24
LE
A
D
D
I
T
I
O
N
&
D
E
T
A
C
H
E
D
A
D
U
DATE:
22
0
9
W
.
L
A
R
A
M
O
R
E
L
N
.
SA
N
T
A
A
N
A
,
C
A
9
2
7
0
6
TH
E
S
E
D
E
S
I
G
N
S
,
D
R
A
W
I
N
G
S
,
A
N
D
SP
E
C
I
F
I
C
A
T
I
O
N
S
A
R
E
E
X
C
L
U
S
I
V
E
T
O
GE
T
S
T
R
U
C
T
U
R
A
L
T
H
E
S
E
D
R
A
W
I
N
G
S
CA
N
N
O
T
B
E
C
O
P
I
E
D
,
T
R
A
N
S
F
E
R
R
E
D
,
O
R
RE
P
R
O
D
U
C
E
D
N
O
R
C
A
N
A
N
Y
O
T
H
E
R
ST
R
U
C
T
U
R
E
S
B
E
B
U
I
L
T
F
R
O
M
T
H
E
M
WI
T
H
O
U
T
W
R
I
T
T
E
N
C
O
N
S
E
N
T
RE
V
I
S
I
O
N
S
30
0
0
E
.
B
I
R
C
H
S
T
R
E
E
T
SU
I
T
E
2
0
3
BR
E
A
,
C
A
9
2
8
2
1
TE
L
:
(
9
0
9
)
5
6
9
-
1
8
8
6
in
f
o
@
G
e
t
S
t
r
u
c
t
u
r
a
l
.
c
o
m
2
JOB: R23-0943
PHONG TR UONG
STATE OF CALIFORNIA
REGISTERED PROFESSIONAL ENGINEER
NO. C70784
EXP. 06/30/2025
CIV IL
2
08
/
0
1
/
2
0
2
4
PL
A
N
C
H
E
C
K
2
PAD SCHEDULE
PAD TYPE
FOOTING
REBAR
CONCRETE PAD FOOTING, SEE SCHEDULE
SYM.
1.REFER TO S.0 SHEET FOR MORE INFO.
2.CONTRACTOR SHALL VERIFY ALL EXISTING FOOTINGS AND NOTIFY
TO ENG. OF RECORD FOR ALL DISCREPANCIES.
3.SPECIAL INSPECTION IS REQUIRED FOR INSTALLATION OF EPOXY.
4.CONCRETE COMPRESSIVE STRENGTH SHALL BE f'c = 2500 PSI (U.N.O.)
Scale: 3/16" = 1'-0"
FOUNDATION PLAN1
FOUNDATION NOTES
DESCRIPTION MATERIAL SIZE EDGE
NAILING 1,2
FIELD
6
8d
10d
6"
6"
4"
12"
12"
12"
6"12"
8"
10"
48"
36"
24"
SHEAR WALL SCHEDULE
FOOTNOTES:
1.ALL NAILS TO BE COMMON NAILS. 1.5" PENETRATION IN FRAMING MEMBER OR BLOCKING
2.SOLID BLOCKING SHALL BE PROVIDED AT ALL EDGES AND HORIZONTAL JOINTS.
3.SHT'G APPLIED TO BOTH SIDES SHALL BE OFFSET OR FRAMING SHALL BE 3X AND NAILS ON EACH SIDE SHALL BE STAGGERED.
4.STAGGER NAILS 1/2" & SHT'G. ONE SIDE ONLY.
5.SHEETS SHALL NOT BE LESS THAN 4FT X 8FT, EXCEPT AT BOUNDARIES AND CHANGES WHERE SHEET SHALL BE 24" MINIMUM.
6.3" X 3" X 0.229" SQUARE PLATE WASHERS SHALL BE USED WITH ALL ANCHOR BOLTS.
12"6"16"
LTP4 OR
A35
16"
12"
10"
8"
P 8d 6"12"6"16"--32"
12"--4"12"6"
4"
3/8" PLYWD/OSB, STRUCT. I
W/ 8d @ 6", 12", BLOCKED
15/32" PLYWD/OSB, STRUCT. I
W/ 10d @ 6", 12", BLOCKED
15/32" PLYWD/OSB, STRUCT. I
W/ 10d @ 4", 12", BLOCKED
15/32" PLYWD/OSB, STRUCT. I
W/ 10d @ 3", 12", BLOCKED
15/32" PLYWD/OSB, STRUCT. I
W/ 10d @ 2", 12", BLOCKED
SIMP. SDS
1/4"Ø X 6"
16d A.B.'S
5/8"
SHEAR
SEISMIC / WIND
CONFORMING TO ANSI/AF&PA, SDPWS 2021/CBC 2022
3"
STAGG.
2"
STAGG.
PANEL
JOINT SILL
2X
2X
2X
2X
2X
2X
2X
2X
SILL TO RIM/BLK'G
RIM/BLK'G
TO TOP
PLATE
SILL TO
FOUND.
A
B
C
D
E
10d
10d
10d
X
FRAMING
3"
STAGG.
2"
STAGG.
2,5
4
4
4
4
72"
2X
3X
3X
3X
200 / 280 plf
340 / 476 plf
665 / 931 plf
870 / 1218 plf
510 / 714 plf
3/8" CDX
(EXTERIOR NON-SHEARWALL)
P18 1'-6" SQ. X 18" DEEP PAD W/ (3) #4 E.W. BOTT.
2'-6" SQ. X 18" DEEP PAD W/ (4) #5 E.W. BOTT.
PX
X
SDX
PX
[E] FOOTING
FOUNDATION LEGEND
DETAIL NUMBER DETAIL SHEET NUMBER
S1
2
2
P30
2
2
2
2
2
2
2
2710 N Laird St & 2209 W
Laramore Ln10/7/2024
RR1 RR1
RR
1
RR1
RR1
RR
1
RR
1
4X4 K.P.
4X4
4X
4
4X4
CJ1
4X12 R.B.
4
RR
2
RR
2
4X6 H.
CJ
CJ
4X4
4X4
4X
4
4X4
4X4
4x10 C.B.
1
1
2
3
A
4'-0"
4X4
C
3'-2"
C
2'-11"
C
5'
-
1
"
4X
4
4X4
A
3'
-
9
"
4X4
4X4
4x
D
R
A
G
B
L
K
G
13B
SD2
4X
4
4X
4
C
3'
-
9
"
4X8
H
I
P
4X1
0
H
I
P
4X1
0
H
I
P
4X1
0
H
I
P
4X1
0
H
I
P
4X8
H
I
P
4X4
4X4
A
8'-0"
4x6 H.
2
4x
6
H
.
3
4x
6
H
.
4x
6
H
.
4x
6
H
.
4x
6
H
.
4x
6
H
.
4x
6
H
.
4x
6
H
.
A CB D E F G
4
5
5
4X6 H.4X6 H.
3.
5
X
1
1
.
8
7
5
L
V
L
H
.
6
A
4'-0"4X
4
4X
4
4X4
B
8'
-
0
"
4X
4
4X4
C
4'
-
0
"
WSWH 12X8
W/1" STD. A.B.
6
WSWH2
15B
SD1
15B
SD1
4X4
[E
]
4
X
4
H
.
V
.
I
.
F
.
7
SD2
7
SD2
7
SD2
7
SD2
7
SD2
7
SD2
24
SD3
8
SD2
8
SD2
9
SD2
9
SD2
2X10 RIDGE BOARD
10
SD2
10
SD210
SD2
9
SD2
11
SD2
11
SD2
11
SD2
11
SD2
11
SD2
11
SD2
12
SD2
12
SD2
4x12 C.B.
7
K.
P
.
4X
4
29
SD3
K.P
.
4X
4
29
SD3
K.P.
4X4
5
SD2
4X421
SD3
4x
6
H
.
4x12 C.B.
8
9
4x
6
H
.
K.P.
4X6 22
SD3
2-
2
x
D
R
A
G
R
.
R
.
23A
SD3
2-
2
x
D
R
A
G
R
.
R
.
23A
SD3
6X6
6X6
4x6 H.
7
SD2
RR
1
4x8 D.B.
2-
2
x
R
.
R
.
10
25
SD3
25
SD3
1'
13A
SD2
4x6 H.4x8 H.
CJ
4X4
2x12 R.B.
11
12
4x8 C.B.
26
SD3
4X4
4X4
4X4
4X4 21
SD3
21
SD3
21
SD3
21
SD3
13B
SD2
27
SD3
28
SD3
2'
26
SD3
28
SD3
FRAMING
PLAN
RE
S
T
R
I
C
T
I
V
E
N
O
T
I
C
E
DA
T
E
RE
V
I
S
I
O
N
S
SHEET
SHEET DESCRIPTION
STAMP
NO
:
8/1/24
LE
A
D
D
I
T
I
O
N
&
D
E
T
A
C
H
E
D
A
D
U
DATE:
22
0
9
W
.
L
A
R
A
M
O
R
E
L
N
.
SA
N
T
A
A
N
A
,
C
A
9
2
7
0
6
TH
E
S
E
D
E
S
I
G
N
S
,
D
R
A
W
I
N
G
S
,
A
N
D
SP
E
C
I
F
I
C
A
T
I
O
N
S
A
R
E
E
X
C
L
U
S
I
V
E
T
O
GE
T
S
T
R
U
C
T
U
R
A
L
T
H
E
S
E
D
R
A
W
I
N
G
S
CA
N
N
O
T
B
E
C
O
P
I
E
D
,
T
R
A
N
S
F
E
R
R
E
D
,
O
R
RE
P
R
O
D
U
C
E
D
N
O
R
C
A
N
A
N
Y
O
T
H
E
R
ST
R
U
C
T
U
R
E
S
B
E
B
U
I
L
T
F
R
O
M
T
H
E
M
WI
T
H
O
U
T
W
R
I
T
T
E
N
C
O
N
S
E
N
T
RE
V
I
S
I
O
N
S
30
0
0
E
.
B
I
R
C
H
S
T
R
E
E
T
SU
I
T
E
2
0
3
BR
E
A
,
C
A
9
2
8
2
1
TE
L
:
(
9
0
9
)
5
6
9
-
1
8
8
6
in
f
o
@
G
e
t
S
t
r
u
c
t
u
r
a
l
.
c
o
m
2
JOB: R23-0943
PHONG TR UONG
STATE OF CALIFORNIA
REGISTERED PROFESSIONAL ENGINEER
NO. C70784
EXP. 06/30/2025
CIV IL
2
08
/
0
1
/
2
0
2
4
PL
A
N
C
H
E
C
K
2
MANUFACTURED LUMBER PRODUCTS:
CLEAR SPAN, L
L ≤ 6'-0"6'-0" < L ≤ 10'-0" L ≥ 10'-0"
2-2X4 U.N.O. PER PLAN
THE FOLLOWING BEAMS/HEADERS/RIMS CAN BE FROM ANY MANUFACTURER WITH
CURRENT APPROVED ICC ES - EVALUATION REPORT WITH THE FOLLOWING
MECHANICAL PROPERTIES:
FOR "PSL" BEAMS:
Fb = 2900 psi (MIN)
Fv = 290 psi (MIN)
E = 2.2x106 psi (MIN)
FOR "LVL" BEAMS:
Fb = 2600 PSI (MIN)
Fv = 285 PSI (MIN)
E = 2.0x106 PSI (MIN)
FOR "LSL" BEAMS/HEADERS:
Fb = 2325 psi (MIN)
Fv = 425 psi (MIN)
E = 1.55x106 psi (MIN)
FOR MANUFACTURED RIM BOARD W/ MIN. 11
4" THICK, CONTINUOUSLY SUPPORTED
BY WALL, AND MATCHES JOIST DEPTH:
Fc^ = 680 psi (MIN)
Fc //= 1400 psi (MIN)
Ft = 1075 psi (MIN)
E = 1.3x106 psi (MIN)
GLU-LAM BEAM SHALL BE 24F-V4, DF/DF
Fb = 2400 psi @ BOTTOM
Fb = 1850 psi @ TOP
Fv = 265 psi (MIN)
E = 1.8x106 psi (MIN)
2 x 4 2-2 x 4
1.REFER TO STRUCTURAL GENERAL NOTES AND DETAIL SHEETS S.0 FOR MORE INFORMATION.
2.ALL STRUCTURAL HARDWARE SHALL BE SIMPSON STRONG-TIE OR APPROVED EQUIVALENT.
3.ALL VERTICAL PIPES THROUGH PLATES AND/OR SOLID RIM BEAMS MUST BE DRILLED CLEAN
CUT W/ 1/16" TOLERANCE. DO NOT NOTCH OR CUT PLATES.
4.ALL BEAMS SHOWN ARE DROP (U.N.O.) ON PLANS.
5.HANGERS FOR FLUSH FRAMED MEMBERS SHALL BE SIMPSON STRONG-TIE AS FOLLOWS U.N.O.:
LUS SAWN LUMBER JOIST (FOR SKEWED USE HU)
MIU TJI, LSL, LVL JOIST
HU 4X SAWN LUMBER
HGUS 6X, OR PSL, LSL, GLU-LAM BEAMS
6.THE FOLLOWING TRIMMER SCHEDULE SHOULD BE USED FOR HEADERS IN BEARING WALLS,
U.N.O. ON THE PLAN. REQUIRED TRIMMER MUST BE APPLIED @ EACH END OF HEADER.
7.BUILDING CODE 2308.5.1 BALLOON FRAMED WALLS (NON-BEARING) STUD HEIGHTS:
- 2X4'S @ 16" O.C. MAXIMUM 14'-0" HEIGHT
- 2X6'S @ 16" O.C. MAXIMUM 20'-0" HEIGHT
8. BEARING STUD HEIGHTS:
- 2X4'S @ 16" O.C. MAXIMUM 10'-0" HEIGHT
- 2X6'S @ 16" O.C. MAXIMUM 16'-0" HEIGHT
9. REFER TO DETAIL 4/SD2 FOR TYPICAL DIAPHRAGM SHEATHING LAYOUT AND NAILING PATTERN.
10.DOUBLE TOP PLATE AT ALL SHEAR WALL LINES SHALL BE SPLICED PER DETAIL 2/SD2 .
11.PROVIDE 2X BLK'G @ 8'-0" O.C. FOR CEILING JOIST.
FRAMING NOTES
FRAMING LEGEND
FRAMING SCHEDULE
SYMBOL SIZE & SPACING
RR1 2X6 - RAFTERS @ 16" O.C.
RR2 2X6 - RAFTERS @ 24" O.C.
CJ 2X6 - CEILING JOIST @ 16" O.C.
CJ1 2X6 - CEILING JOIST @ 24" O.C.
DESCRIPTION MATERIAL SIZE EDGE
NAILING 1,2
FIELD
6
8d
10d
6"
6"
4"
12"
12"
12"
6"12"
8"
10"
48"
36"
24"
SHEAR WALL SCHEDULE
FOOTNOTES:
1.ALL NAILS TO BE COMMON NAILS. 1.5" PENETRATION IN FRAMING MEMBER OR BLOCKING
2.SOLID BLOCKING SHALL BE PROVIDED AT ALL EDGES AND HORIZONTAL JOINTS.
3.SHT'G APPLIED TO BOTH SIDES SHALL BE OFFSET OR FRAMING SHALL BE 3X AND NAILS ON EACH SIDE SHALL BE STAGGERED.
4.STAGGER NAILS 1/2" & SHT'G. ONE SIDE ONLY.
5.SHEETS SHALL NOT BE LESS THAN 4FT X 8FT, EXCEPT AT BOUNDARIES AND CHANGES WHERE SHEET SHALL BE 24" MINIMUM.
6.3" X 3" X 0.229" SQUARE PLATE WASHERS SHALL BE USED WITH ALL ANCHOR BOLTS.
12"6"16"
LTP4 OR
A35
16"
12"
10"
8"
P 8d 6"12"6"16"--32"
12"--4"12"6"
4"
3/8" PLYWD/OSB, STRUCT. I
W/ 8d @ 6", 12", BLOCKED
15/32" PLYWD/OSB, STRUCT. I
W/ 10d @ 6", 12", BLOCKED
15/32" PLYWD/OSB, STRUCT. I
W/ 10d @ 4", 12", BLOCKED
15/32" PLYWD/OSB, STRUCT. I
W/ 10d @ 3", 12", BLOCKED
15/32" PLYWD/OSB, STRUCT. I
W/ 10d @ 2", 12", BLOCKED
SIMP. SDS
1/4"Ø X 6"
16d A.B.'S
5/8"
SHEAR
SEISMIC / WIND
CONFORMING TO ANSI/AF&PA, SDPWS 2021/CBC 2022
3"
STAGG.
2"
STAGG.
PANEL
JOINT SILL
2X
2X
2X
2X
2X
2X
2X
2X
SILL TO RIM/BLK'G
RIM/BLK'G
TO TOP
PLATE
SILL TO
FOUND.
A
B
C
D
E
10d
10d
10d
X
FRAMING
3"
STAGG.
2"
STAGG.
2,5
4
4
4
4
72"
2X
3X
3X
3X
200 / 280 plf
340 / 476 plf
665 / 931 plf
870 / 1218 plf
510 / 714 plf
3/8" CDX
(EXTERIOR NON-SHEARWALL)
X
4X6
CJ
RR
X
SDX
INDICATES ROOF RAFTERS, SEE FRAMING SCHEDULE
INDICATES CEILING JOISTS, SEE FRAMING SCHEDULE
DETAIL NUMBER DETAIL SHEET NUMBER
BEAM NUMBER, REFER TO CALCULATIONS.
INDICATES BEAM SIZE (DFL HEADER/DROP) U.N.O.
EXISTING WALL TO BE REMOVED
EXISTING WALL TO REMAIN
NEW WALL
CALIFORNIA FRAMING, SEE DETAIL 10/SD2
H. HEADER
R.B. RIDGE BEAM
BEAM TYPE
Scale: 3/16" = 1'-0"
1ST FLOOR PLAN / ROOF FRAMING PLAN1
UNBLOCKED DIAPHRAGM (180/240 PLF)
15/32" WOOD STRUCTURAL PANEL SHTG, 32/16
8d NAILING, 1.5" PENETRATION INTO FRAMING
6" O.C.BOUNDARY
12" O.C.FIELD
ROOF DIAPHRAGM (U.N.O.)
S2
2
22
2
2
2
2
2
2710 N Laird St & 2209 W
Laramore Ln10/7/2024
FOUNDATION
& FRAMING
DETAILS
SD1
RE
S
T
R
I
C
T
I
V
E
N
O
T
I
C
E
DA
T
E
RE
V
I
S
I
O
N
S
SHEET
SHEET DESCRIPTION
STAMP
NO
:
8/1/24
LE
A
D
D
I
T
I
O
N
&
D
E
T
A
C
H
E
D
A
D
U
DATE:
22
0
9
W
.
L
A
R
A
M
O
R
E
L
N
.
SA
N
T
A
A
N
A
,
C
A
9
2
7
0
6
TH
E
S
E
D
E
S
I
G
N
S
,
D
R
A
W
I
N
G
S
,
A
N
D
SP
E
C
I
F
I
C
A
T
I
O
N
S
A
R
E
E
X
C
L
U
S
I
V
E
T
O
GE
T
S
T
R
U
C
T
U
R
A
L
T
H
E
S
E
D
R
A
W
I
N
G
S
CA
N
N
O
T
B
E
C
O
P
I
E
D
,
T
R
A
N
S
F
E
R
R
E
D
,
O
R
RE
P
R
O
D
U
C
E
D
N
O
R
C
A
N
A
N
Y
O
T
H
E
R
ST
R
U
C
T
U
R
E
S
B
E
B
U
I
L
T
F
R
O
M
T
H
E
M
WI
T
H
O
U
T
W
R
I
T
T
E
N
C
O
N
S
E
N
T
RE
V
I
S
I
O
N
S
30
0
0
E
.
B
I
R
C
H
S
T
R
E
E
T
SU
I
T
E
2
0
3
BR
E
A
,
C
A
9
2
8
2
1
TE
L
:
(
9
0
9
)
5
6
9
-
1
8
8
6
in
f
o
@
G
e
t
S
t
r
u
c
t
u
r
a
l
.
c
o
m
2
JOB: R23-0943
PHONG TR UONG
STATE OF CALIFORNIA
REGISTERED PROFESSIONAL ENGINEER
NO. C70784
EXP. 06/30/2025
CIV IL
2
08
/
0
1
/
2
0
2
4
PL
A
N
C
H
E
C
K
2
1
2
3
4
5
6
7
8
9
10
11
12
13
HDU
5" MIN.
16
"
MI
N
.
RE
T
U
R
N
3"
CL
R
.
le
1 3/4"
MIN.
E
E
le
18"
18
"
1.REBAR PER TABLE, CENTERED @ "HD"
(BEND REBAR @ CORNER). FOR
COND. B, LOCATE TOP REBAR 3" TO 5"
FROM TOP OF CONCRETE.
2.EDGE OF DEEPENED SLAB/FTG FOR
HOLDOWN @ INT. SHEAR WALL.
3.CONCRETE STEM/FOOTING WIDTH (8"
MIN. FOR 7/8"Ø BOLT, 6" MIN. FOR
5/8"Ø BOLT) ENTIRE EMBED. LENGTH.
4.SS BOLTS PER SCHEDULE.
5.FTG WIDTH (13" FOR 7/8"Ø BOLT, 9"
FOR 5/8"Ø BOLT).
6.EXTERIOR FOOTING EDGE.
7.CONCRETE CORNER.
8.CONCRETE END.
9.DEEPEND FOOTING AS REQUIRED TO
ENSURE PROPER EMBEDMENT
10.USE 16D SINKER NAILS. (0.148"X3 1/4").
NOTES:
- SEE PLANS FOR HOLDOWN
TYPES.
- SEE DETAIL #1 FOR LEGEND &
INFORMATION NOT SHOWN.
- REFER TO MANUFACTURER
SPECIFICATIONS FOR
INSTALLATION INFORMATION
NOT SHOWN.
- WHEN 3-2X MEMBER IS USED
FOR HDQ8 & HDU, 1/4"Øx4 1/2"
SDS SCREWS SHOULD BE USED.
SIMPSON
HOLDOWN SB BOLTS #4 BAR X 8'-0"
CENTERED @ HD*le (in.)
IN LIEU OF #4 USE
#5 BAR X 8'-0"
CENTERED @ HD *
HDU2 SS5/8x24 (2) TOP & BOT.(1) TOP & (1) BOT.
HDU4 (2) TOP & BOT.(1) TOP & (1) BOT.
HDU5 / HTT5 (2) TOP & BOT.(1) TOP & (1) BOT.
HDU8 / HDQ8 (2) TOP & BOT.(1) TOP & (1) BOT.
*CONT. FOOTING REINFORCEMENT CAN BE COUNTED AS PART OF REBAR REQUIREMENT
IF BAR SIZE ARE SAME AS THOSE REQUIRED PER SCHEDULE; OTHERWISE, BARS PER
SCHEDULE ARE ADDITIONAL.
SB BOLTS INSTALLATION @
SW @ EXT. FOOTING
SB BOLT INSTALLATION
@ SW @ INT. FTG/SLAB
PLAN VIEW SB @
CONC. CORNER
PLAN VIEW SB @
CONC. END
1
2
5
3
4 9
6
4
1
7
4
8
5"
MIN.
3"
CL
R
.
24"
NOTES:
-4x4 POSTS CAN BE REPLACED
W/ 2-2x4 AS LONG AS NAILS ARE
MAINTAINED W/ MIN. EDGE
DISTANCE AS REQUIRED BY
THE MANUF. SPEC. & S.W. EDGE
NAILS STAGGERED ON BOTH
STUDS.
-FOR NON-MONOPOUR
FOUNDATIONS, USE (2) #5
DOWELS PER EACH SB BOLT,
PLACED WITHIN 2" FROM THE
BOLT.
HOLD DOWN
8"8"
E-E SECTION
le
3"
CL
R
.
9 9
SS5/8x24
SS5/8x24
SS7/8x24
24"
24"
24"
BEND
LAP SPLICE
STIRRUP
TIE OR HOOK
NOTES:
CROSSTIE
WIRE TIE END
D D
90° BEND
R
180° BEND
R12
"
4 db
2 1
2" MIN.
6 d
b
4"
M
I
N
.
6db
3" M
I
N
.
* INCREASE LENGTH BY 30% FOR TOP
BARS (HORIZONTAL BARS SO PLACED
THAT MORE THAN 12" OF FRESH CONC. IS
CAST IN THE MEMBER BELOW, EXCLUDE
WALLS)
DE
T
A
I
L
I
N
G
DI
M
E
N
S
I
O
N
DE
T
A
I
L
I
N
G
DI
M
E
N
S
I
O
N
6 d
b
4"
M
I
N
.
12
d
b F
O
R
#
6
T
H
R
U
#
8
3"
M
I
N
"
D= 4db FOR #3 THRU #5
D= 6db FOR #6 THRU #8
8db
8db
48 db
R= 3db FOR #3 THRU #8
R= 4db FOR #9 THRU #11
R= 5db FOR #14 THRU #18
TYPICAL REBAR DETAIL
1.PUT CROSSTIE W/ EACH STIRRUP
ALT. 135° BENDS (90° FOR CIRCULAR
TIE)
2.ALL BENDS SHALL BE MADE COLD
SINGLE LAYER INTERSECTION & CORNER
L
L
L
L
L
L
L L
L
L = 30 BAR DIAM. MIN. IN CONCRETE.
40 BAR DIAM. MIN. IN MASONRY.
DOUBLE LAYER INTERSECTION & CORNER
CONCRETE FOOTING INTERSECTION
REINF. MAY BE CONT. OR
ADD BARS WITH SAME
SIZE & SPACING AS
WALL/FOOTING REINF.
HDU
5" MIN.
16
"
MI
N
.
RE
T
U
R
N
3"
CL
R
.
le
1 3/4"
MIN.
E
E
le
18"
18
"
1.REBAR PER TABLE, CENTERED @ "HD" (BEND REBAR @
CORNER). FOR COND. B, LOCATE TOP REBAR 3" TO 5"
FROM TOP OF CONCRETE.
2.EDGE OF DEEPENED SLAB/FTG FOR HOLDOWN @ INT.
SHEAR WALL.
3.CONCRETE STEM/FOOTING WIDTH (8" MIN. FOR 7/8"Ø
BOLT, 6" MIN. FOR 5/8"Ø BOLT) ENTIRE EMBED. LENGTH.
4.SS BOLTS PER SCHEDULE.
5.FTG WIDTH (13" FOR 7/8"Ø BOLT, 9" FOR 5/8"Ø BOLT).
6.EXTERIOR FOOTING EDGE.
7.CONCRETE CORNER.
8.CONCRETE END.
9.DEEPEND FOOTING AS REQUIRED TO ENSURE PROPER
EMBEDMENT
10.USE 16D SINKER NAILS. (0.148"X3 1/4").
NOTES:
- SEE PLANS FOR HOLDOWN
TYPES.
- SEE DETAIL #1 FOR LEGEND &
INFORMATION NOT SHOWN.
- REFER TO MANUFACTURER
SPECIFICATIONS FOR
INSTALLATION INFORMATION
NOT SHOWN.
- WHEN 3-2X MEMBER IS USED
FOR HDQ8 & HDU, 1/4"Øx4 1/2"
SDS SCREWS SHOULD BE USED.
SIMPSON
HOLDOWN SB BOLTS #4 BAR X 8'-0"
CENTERED @ HD*le (in.)
HDU2 SS5/8x24 (2) TOP & BOT.
HDU4 (2) TOP & BOT.
HDU5 / HTT5 (2) TOP & BOT.
HDU8 / HDQ8 (2) TOP & BOT.
*CONT. FOOTING REINFORCEMENT CAN BE COUNTED AS PART OF REBAR REQUIREMENT
IF BAR SIZE ARE SAME AS THOSE REQUIRED PER SCHEDULE; OTHERWISE, BARS PER
SCHEDULE ARE ADDITIONAL.
SB BOLTS INSTALLATION @
SW @ EXT. FOOTING
SB BOLT INSTALLATION
@ SW @ INT. FTG/SLAB
PLAN VIEW SSTB
@ CONC. CORNER
PLAN VIEW SSTB
@ CONC. END
1
2
5
3
4
9
6
4
1
7
4
8
5"
MIN.
3"
CL
R
.
24"
NOTES:
-4x4 POSTS CAN BE REPLACED
W/ 2-2x4 AS LONG AS NAILS ARE
MAINTAINED W/ MIN. EDGE
DISTANCE AS REQUIRED BY
THE MANUF. SPEC. & S.W. EDGE
NAILS STAGGERED ON BOTH
STUDS.
-FOR NON-MONOPOUR
FOUNDATIONS, USE (2) #5
DOWELS PER EACH SB BOLT,
PLACED WITHIN 2" FROM THE
BOLT.
HOLD DOWN
8"8"
E-E SECTION
le
3"
CL
R
.
9 9
SS5/8x24
SS5/8x24
SS7/8x24
24"
24"
24"
3
3
3
1
4
SEE PAD SCHEDULE
FOR SIZE & REINF.
6"
MIN.
9"
MIN.#4
12
"
MI
N
.
PAD FOOTING
2
℄EQ.EQ.
3
4
SEE PAD SCHEDULE
FOR SIZE & REINF.
6"
MIN.
9"
MIN.#4
12
"
MI
N
.
℄EQ.EQ.
5
6"
MIN.
6"
MIN.1
2
1.POST PER PLAN
2.SIMP. A34, BOTH SIDES
3.(E) CONC. FOOTING
4.#4 DOWELS BENT AS SHOWN @ 12" O.C.
(MIN. 2) W/ SIMP. SET-3G EPOXY (ICC-ESR
4057), SPECIAL INSPECTION REQ'D
5.DEMO AND REPLACE [E] SLAB AS NEEDED
TO INSTALL UNDERPIN FOOTING. MATCH.
EXISTING SLAB REBAR.
6.(E) CONC. SLAB
7.SIMPSON "SET-3G" EPOXY TIE, ESR # 4057
*SPECIAL INSPECTION REQ'D
INTERIOR EXTERIOR
6 6
77
7"
MI
N
.
2
4
6
13 4"
MIN.
ANCHOR BOLT TO [E] FOOTING
18
"
V.
I
.
F
.
1
3
51.[E] 2X STUDS
2.5/8"Ø A307 THREADED BOLT
3.2X BLK'G BETWEEN STUDS @
LENGHT OF SHEAR WALL W/ (6) 10d
@ EACH BLK'G
4.(E) CONC. SLAB
5.SHEAR WALL PER PLAN
6.DRILL 3/4"Ø W/ SIMP. SET-3G ICC
4057. INSTALL IN ACCORDANCE
WITH SIMPSON STRONG-TIE
RECOMMENDATIONS. SPECIAL
INSPECTION REQUIRED
3
2
13 4"
MIN.
UNDERPINNED HOLD DOWN
5/8"
A.B. Dia.Steel
F1554 Gr36
Plt. Washer
3/8"x2½"x2½"
Holdown
HDU5
CAPACITY (lbs)
5645
3"MI
N
.
5/8" F1554 Gr36 3/8"x2"x2"HDU4 4565
5/8" F1554 Gr36 3/8"x2"x2"HDU2 3075
1
1.THREADED ROD PER TABLE
2.(E) CONC. FOOTING
3.GROUT
7"
MI
N
.
2
4
6
13 4"
MIN.
ANCHOR BOLT TO [E] FOOTING
24
"
V.
I
.
F
.
1
3
5
1.[E] 2X STUDS
2.5/8"Ø A307 THREADED BOLT
3.2X BLK'G BETWEEN STUDS @ LENGTH OF
SHEAR WALL W/ (6) 10d @ EACH BLK'G
4.(E) CONC. SLAB
5.SHEAR WALL PER PLAN
6.DRILL 3/4"Ø W/ SIMP. SET-3G ICC 4057.
INSTALL IN ACCORDANCE WITH SIMPSON
STRONG-TIE RECOMMENDATIONS.
SPECIAL INSPECTION REQUIRED
3
2
13 4"
MIN.
UNDERPINNED HOLD DOWN
5/8"
A.B. Dia.Steel
F1554 Gr36
Plt. Washer
3/8"x2½"x2½"
Holdown
HDU5
CAPACITY (lbs)
5645
3"
MI
N
.
5/8" F1554 Gr36 3/8"x2"x2"HDU4 4565
5/8" F1554 Gr36 3/8"x2"x2"HDU2 3075
1
1.THREADED ROD PER TABLE
2.(E) CONC. FOOTING
3.GROUT
3"
MIN.
14
NOTE:
1.SPRAY BONDING AGENT (INTRALOK OR SIMILAR) AT THE JOINT BETWEEN OLD AND NEW
CONCRETE PRIOR TO POURING NEW CONCRETE.
2.IF POST TENSION FOUNDATION: VERIFY W/ POST TENSION ENGINEER FOR LOCATION OF
STRANDS WHEN PLACING DOWELS INTO EXISTING P.T. FTG. DO NOT CUT STRANDS.
12"24"
2
1
3
[E]
FTG
[N]
FTG
12"24"
[N] FOOTING TO [E] FOOTING
15
°
1.(E) FOOTING
2.#4 DOWELS
3.5/8"Ø HOLE W/ SIMPSON "SET-3G"
EPOXY, ESR-4057 *SPECIAL INSPECTION
REQ'D
14
5
3
2
TOP PLATE DRAG DETAIL
EXISTING NEW
A CS16 11 2" (10) 10d 1705# 11"
B CS14 11 2" (13) 10d 2490# 15"
C CMSTC16 3" (25) 12d 4690# 20"
D CMST14 3"(28) 16d 6475# 26"
E CMST12 3" (37) 16d 9215# 33"
STRAP CAPACITY
MIN. WOOD
MEMBER
THICKNESS
MIN. # OF NAILS @ EACH
END MEMBER PER STRAP
MIN. END
LENGTH
HD
TYPE
1.DBL. TOP PLATE
2.STRAP PER PLAN
3.2X STUDS
4.[E] DBL. TOP PLATE
5.[E] 2X STUDS
15
8"12"
2
1
3
[N] SLAB TO [E] FOOTING
1.#3 DOWELS @ 24" O.C.
2.7/16" Ø HOLE W/ SIMPSON
"SET-3G" EPOXY, ESR-4057
SPECIAL INSPECTION REQ'D
3.[E] CONC.
CONC. FOOTING
EXTERIOR SLAB TO FOOTING
2"
MI
N
.
6"
MIN.
6"
MI
N
.
SLAB PER
PLAN
6"
MIN.
EXPANSION JOIST
16
POST
1"
S
T
A
N
D
O
F
F
71
4"
5" MIN.
SIDECOVER (TYP.)
2"
T
Y
P
.
3"
PE
R
P
L
A
N
18
"
(
M
I
N
.
)
11
2"
TY
P
.
SIMPSON MPBZ MOMENT POST BASE
A A
SIMP.
MPBZ
#4 HORIZONTAL
TIES @ 3" SPACING
(SQUARE AND
DIAMOND SHAPED
TIES)
1'-1" SQUARE
(MIN.)
21 2"
EXTENSION
AT TIE HOOK
(1 2" CLEAR
FROM MPBZ)
(8) #4 VERTICAL
REBAR AT 6"
ON CENTER
3" EXTENSION
AT TIE HOOK (TYP)
SECTION A
REINF., SEE PAD
SCHEDULE ON
FOUNDATION PLAN
PER PLAN
18" MIN.
24"
MIN.
DIAMETER
17
SO
I
L
:
8
"
M
I
N
.
CO
N
C
.
:
4
"
M
I
N
.
W
7"
MI
N
.
EM
B
E
D
1.2X STUD WALL
2.SHEAR WALL AS OCCURS, SEE
PLAN AND SHEAR WALL SCHEDULE
3.P.T.D.F. SILL PLATE W/ 5/8"Ø
ANCHOR BOLTS PER SHEAR WALL
SCHEDULE, (2) BOLTS PER PIECE
WITH (1) BOLT LOCATED NOT MORE
THAT 12" OR LESS THAN 7db. FROM
EACH END AND/OR SPLICE OF THE
PIECE.
4.(2) #4 BARS, TOP AND BOTTOM
5.#3 DOWELS @ 18" O.C. FOR 2 POURS
6.SLAB PER PLAN
7.SUBGRADE AND VAPOR BARRIER
PER PLAN
8.SCREED @ STUCCO FINISH
D
2
1
15"
12"
18"
18"
FOOTING DIMENSIONS
# OF
STORIES
W
WIDTH
D
DEPTH
1
2
3
4
6
5
7
8
7"
FO
R
2
PO
U
R
S
ON
L
Y
FOOTING DETAIL
D
W
4
INTERIOR FOOTING DETAIL
2
1
15"
12"
18"
18"
FOOTING DIMENSIONS
# OF
STORIES
W
WIDTH
D
DEPTH
1.2X STUD WALL
2.SHEAR WALL AS OCCURS, SEE PLAN AND
SHEAR WALL SCHEDULE
3.P.T.D.F. SILL PLATE W/ 5/8"Ø ANCHOR
BOLTS PER SHEAR WALL SCHEDULE, (2)
BOLTS PER PIECE WITH (1) BOLT LOCATED
NOT MORE THAT 12" OR LESS THAN 7D/B.
FROM EACH END AND/OR SPLICE OF THE
PIECE.
4.(2) #4 BARS, TOP AND BOTTOM
5.#3 DOWELS @ 18" O.C. FOR 2 POURS
6.SLAB PER PLAN
7.SUBGRADE AND VAPOR BARRIER PER PLAN
7"
FO
R
2
PO
U
R
S
ON
L
Y
7"
MI
N
.
EM
B
E
D
12
3
5
7
6
18
2
NOTES:
EXTERIORINTERIOR
SEE PLANS
1
2
3
3
1
FACE OF
STUD
NOTES:
- SEE DETAIL #1 FOR INFORMATION NOT SHOWN
- 4x4 POSTS CAN BE REPLACED WITH 2-2x4 AS LONG
AS NAILS ARE MAINTAINED WITH MIN. EDGE
DISTANCE AS REQUIRED BY THE SPEC. & S.W. EDGE
NAILS STAGG ON BOTH STUDS.
1.CENTERLINE OF POST
AND PAD FOOTING
2.POST IN WALL OR
USE COLUMN BASE,
SEE PLAN
3.PAD
REINFORCEMENT,
SEE PLANS
SEE PLANS
PAD FOOTING DETAIL
2
12
3
4
6
5
7
8
7"
FO
R
2
PO
U
R
S
ON
L
Y
GRADE BEAM DETAIL
7"
MI
N
.
EM
B
E
D
24
d
b
4
SE
E
P
L
A
N
S
SEE PLANS
10
9
℄
1.2X STUD WALL
2.SHEAR WALL AS OCCURS,
SEE PLAN AND SHEAR WALL
SCHEDULE
3.P.T.D.F. SILL PLATE
W/ 5/8"Ø ANCHOR BOLTS PER
SHEAR WALL SCHEDULE, (2)
BOLTS PER PIECE WITH (1)
BOLT LOCATED NOT MORE
THAT 12" OR LESS THAN 7db.
FROM EACH END AND/OR
SPLICE OF THE PIECE.
4.LONGITUDINAL BARS, SEE
FOUNDATION PLAN SIZE
AND QUANTITY
5.#3 DOWELS @ 24" O.C. FOR 2
POURS
6.SLAB PER PLAN
7.SUBGRADE AND VAPOR
BARRIER PER PLAN
8.SCREED @ STUCCO FINISH
9.GRADE BEAM SIZE PER PLAN
10.#4 STIRRUPS, SEE
FOUNDATION PLAN FOR
SPACING
2
2710 N Laird St & 2209 W
Laramore Ln10/7/2024
13
1
4"
C
L
R
.
1
4"
C
L
R
.
1
2
3
4
5
NON-BEARING WALL
*PROVIDE ANCHOR 6" FROM ALL CORNERS AND SPLICES. ALL INTERIOR
NON-SHEAR WALLS TO BE SECURED WITH ICC-ESR APPROVED SHOT PINS
WITH CADMIUM WASHERS AT 32" O.C. PER MANUF. SPECS., U.N.O.
6
1.SIMPSON "DTC" @ 48" O.C. MAX.
2.2X BLK'G @ 48" O.C. W/ (3) 16d @
EA. END
3.JOIST OR TRUSS BOT. CHORD
4.NON-BRG WALL
5.*3" RAMSET @ 32" O.C. (ICC 1799)
6.CONC. SLAB PER PLAN
FRAMING
DETAILS
SD2
RE
S
T
R
I
C
T
I
V
E
N
O
T
I
C
E
DA
T
E
RE
V
I
S
I
O
N
S
SHEET
SHEET DESCRIPTION
STAMP
NO
:
8/1/24
LE
A
D
D
I
T
I
O
N
&
D
E
T
A
C
H
E
D
A
D
U
DATE:
22
0
9
W
.
L
A
R
A
M
O
R
E
L
N
.
SA
N
T
A
A
N
A
,
C
A
9
2
7
0
6
TH
E
S
E
D
E
S
I
G
N
S
,
D
R
A
W
I
N
G
S
,
A
N
D
SP
E
C
I
F
I
C
A
T
I
O
N
S
A
R
E
E
X
C
L
U
S
I
V
E
T
O
GE
T
S
T
R
U
C
T
U
R
A
L
T
H
E
S
E
D
R
A
W
I
N
G
S
CA
N
N
O
T
B
E
C
O
P
I
E
D
,
T
R
A
N
S
F
E
R
R
E
D
,
O
R
RE
P
R
O
D
U
C
E
D
N
O
R
C
A
N
A
N
Y
O
T
H
E
R
ST
R
U
C
T
U
R
E
S
B
E
B
U
I
L
T
F
R
O
M
T
H
E
M
WI
T
H
O
U
T
W
R
I
T
T
E
N
C
O
N
S
E
N
T
RE
V
I
S
I
O
N
S
30
0
0
E
.
B
I
R
C
H
S
T
R
E
E
T
SU
I
T
E
2
0
3
BR
E
A
,
C
A
9
2
8
2
1
TE
L
:
(
9
0
9
)
5
6
9
-
1
8
8
6
in
f
o
@
G
e
t
S
t
r
u
c
t
u
r
a
l
.
c
o
m
2
JOB: R23-0943
PHONG TR UONG
STATE OF CALIFORNIA
REGISTERED PROFESSIONAL ENGINEER
NO. C70784
EXP. 06/30/2025
CIV IL
2
08
/
0
1
/
2
0
2
4
PL
A
N
C
H
E
C
K
2
1
2
3
4
5
6
7
8
9
10
11
12
SHEAR WALL
24" MIN.
PLATE LINE
PLA
T
E
L
I
N
E
PLATE LINE
PLA
T
E
L
I
N
E
PLATE LINE
PLA
T
E
L
I
N
E
PLATE LINE
PLA
T
E
L
I
N
E
PLATE LINE
PLA
T
E
L
I
N
E
PLATE LINE
PLA
T
E
L
I
N
E
NOTES:
·PROVIDE 3 8" EDGE DISTANCE FOR NAILS;
·PROVIDE MIN. 2X BLK'G. @ ALL PLYWOOD EDGES OR AS NOTED IN SHEAR SCHEDULE;
·STAGGER NAILS THAT ARE SPACED 2" O.C.;
·FOR SPECIFIC SHEARWALL CONDITIONS SEE PLAN & SCHEDULE;
·NO CUTS OR HOLES IN SHEATHING WITHIN 16" OF CORNERS;
·MAX. ACCUMULATED LENGTH OF OPENINGS SHALL NOT EXCEED 20% OF THE WALL
LENGTH. MAX. LENGTH OF EA. OPENING IS 4-1 2" IN ANY DIRECTION.
1.SHEAR WALL INDICATED ON PLANS AND SCHEDULE
2.EDGE NAIL (E.N.) SHEAR PANEL TO ALL PANEL EDGES
3.FIELD NAIL @ 12" O.C.
4.POST PER PLAN. EDGE NAIL (E.N.) SHEAR PANEL TO POST
5.INSTALL HOLDOWN ON POST
6.TRIMMER WHERE OCCURS
7.SIMPSON LTP4 (OR A35) @ 24" O.C. OR SEE SHEAR WALL SCHEDULE FOR SPACING
8.ROOF RAFTER AND BLOCKING
9.3X MUDSILL
10.2X4 FLAT BLOCK NAILING FOR HORIZONTAL JOINTS
1
2
2
3
44
5
6
7
PLATE LINE
PLA
T
E
L
I
N
E
PLATE LINE
PLA
T
E
L
I
N
E
PLATE LINE
PLA
T
E
L
I
N
E
PLATE LINE
PLA
T
E
L
I
N
E
8
99
41 2"
MAX.
41
2"
MA
X
.
CORNERS TO
BE ROUND
NO
OVERCUTS
16" MIN.
FROM ANY
PANEL
EDGE
OPENING LIMITS
1
2"
1
2"
1
2"3" ³ X
3
4"
3
4"X > 3"
EDGE NAILING SPACING =< 3"
EDGE NAILING SPACING > 3"
SILL NAILING
18"
MAX.
3 8"
1 2"
3 8"
21 2"
MIN.
3 8"
3 8"
3 8"
3 8"
EDGE NAILING SPACING < 4"EDGE NAILING SPACING >= 4"
11 2"
PANEL JOINT NAILING
16d NAILS, SEE
TABLE FOR
SPACING,
STAGGERED
SHEARWALL SPACING
A 6"
B 6"
C 4"
D 4"
E 3"
16d NAILS, SEE
TABLE FOR
SPACING,
STAGGERED
X
SH
E
A
R
W
A
L
L
PE
R
P
L
A
N
POST PER
PLAN
E.N.
E.N.
E.N.
E.N.
E.N.
X
SH
E
A
R
W
A
L
L
PE
R
P
L
A
N
X
SH
E
A
R
W
A
L
L
PE
R
P
L
A
N
X
SH
E
A
R
W
A
L
L
PE
R
P
L
A
N
X
PER PLAN
SHEARWALL
X
PER PLAN
SHEARWALL
X
PER PLAN
SHEARWALL
16d NAILS, SEE TABLE FOR
SPACING, STAGGERED
X
SH
E
A
R
W
A
L
L
PE
R
P
L
A
N
E.
N
.
X
SHEARWALL
PER PLAN
E.N.
POST PER
PLAN
POST PER
PLAN
INTERSECTION AND CORNERS
24
"
MI
N
.
10
NOTCH DEPTH
STUD SIZE EXT. BRN'G WALL NON-BRN'G WALLS
2X4 7
8"1 7
16"
2X6 1 3
8"2 3
16"
BORED HOLES
STUD SIZE EXT. BRN'G WALL NON-BRN'G WALLS
2X4 1 3
8"2 1
8"
2X6 2 3
16"3 5
16"
2-2X4 2 1
8"2 1
8"
2-2X6 3 5
16"3 5
16"
NOTE:
BORED HOLES NOT PERMITTED IN MORE
THAN TWO CONSECUTIVE DOUBLE STUDS
STUD
OU
T
E
R
1
/
3
O
F
SP
A
N
O
N
L
Y
d/4 M
A
X
d M
I
N
.
SILL PLATE
d
BORING, NOTCHES, AND BLOCKING
5/8"
MIN.
BORE HOLE, SEE
TABLE BELOW
1 1
4"X 16 GA STRAP W/ (8) 10d
COMMON NAILS AT EACH
END AT EACH PLATE
51 2"
MAX.
1'-0"
MIN.
1'-0"
MIN.
2X6 SILL
TYP. 2"Ø MAX.
BORED HOLENOTCHES MIN.
6'-0" O.C.
2"
MA
X
.
212"
MI
N
.
1 1
4"X 16 GA STRAP W/ (6) 10d
COMMON NAILS AT EACH
END AT EACH PLATE
3"
MAX.
10"
MIN.
10"
MIN.
2X4 SILL
TYP. 13
4""Ø MAX.
BORED HOLENOTCHES
MIN. 6'-0" O.C.
112"
MA
X
.
112"
MI
N
.
NOTES:
1.NOTCHES DEPTH PER DISTANCE FROM SUPPORT
DEPTH OF JOIST: D/3 MAX.
1/3 SPAN OF JOIST: D/6 MAX.
2.ALL NOTCHES/BORE TO BE WITHIN 1/3 SPAN FROM SUPPORTS (NOT
AT CANTILEVER SUPPORT)
3.MAINTAIN MIN. 6" SPACING BETWEEN ANY NOTCHES/BORED HOLES
D MAX.
2" CLEAR,
MIN.
D/3 JOIST
DEPTH
MAX.
D/3 MAX.
D/4 MAX. AT
SUPPORT ENDS
D/6 MAX.
6" MIN.
D/6 MAX.
1/3 MAX
SPAN
D
JOIST
PER
PLAN
2x BLOCKING,
FULL DEPTH
(2) 16d
OR (3) 8d
INTERMEDIATE BLOCKING
TYP. AT RIDGE
4'-0" LAP MIN.
NOTE:
FULLY NAIL STRAP W/ 16d
SINKER OR 10d COMMON
NAILS SHALL BE STAGGERED
& AT LEAST 2 1/4" APART.
2
5
1
TOP PLATE SPLICE
4
1.PLATE TO STUD NAILING PER C.B.C.
MIN. REQ'D
2.MIN. (2) ROWS 16d
(2) 2x4: TOTAL (44) @ PLATE
SPLICES OR BREAKS
(2) 2x6: TOTAL (68) @ PLATE
SPLICES OR BREAKS
3.LOCATE STUD UNDER SPLICE OR
PROVIDE 2X BLK'G. ATTACHED TO
ADJACENT STUD W/ (3) 16d NAIL @
SIDE
4.SPLICE TO BE OVER STUD
5.MST72, U.N.O.
3
3
TYPICAL WALL OPENING
1.(2) 16d MIN. (ADD (2) 16d FOR EA. 2" OF ADDITION HEADER DEPTH
2.(1) 2X THRU STUD
- OPENING > 6'-0"(2) 2X THRU STUDS
- OPENING > 12'-0 (3) 2X THRU STUDS
- HEADER HT. > 10'-0"(3) 2X THRU STUDS
3.POST @ HOLDOWNS, SEE PLANS
4.2X STUDS @ 16" O.C. U.N.O.
5.2X WINDOW SILL WHERE OCCURS
- OPENING > 6'-0"(2) 2X SILL
- SILL HEIGHT > 10'-0" (2) 2X SILL
6.SILL PLATE
7.SIMP. A34 @ OPENING WIDER THAN 6'-0"
8.(2) 2X TOP PLATE
9.HEADER PER TABLE
10.2X TRIMMER
- OPENING > 6'-0"(2) 2X TRIMMER
- HEADER HT. > 10'-0"(3) 2X THRU STUDS
11.16d @ 12" O.C. STAGGER
12.(4) 8d TOE NAILS
13.KING POST PER PLAN W/ (2) A34, TOP. & BOT.
14.BEAM PER PLAN W/ (2) A34
4'-0"4"
6'-0"4"
8'-0"6"
10'-0"6"
12'-0"8"
MIN. NOMINAL HEADER "D"
NON-BEARING
OPENING
WIDTH MAX.
HEADER SCHEDULE, U.N.O.
NOTE:
PROVIDE 2X FIRE STOPS AT CEILING AND @ 8'-0" O.C. VERTICAL
1
2
3
4
6
7
8
9
11
12
1
2
3
45
6
7
8
10 11
7
12
14
13
1 4"
3 8"18"
3 8"
1 4"
11 2"
PANEL JOINT NAILING
FIELD
NAILING
CONTINUOUS
PANEL EDGE, E.N.
PANEL BOUNDARY
& BOUNDARY
NAILING (B.N.)
PANEL EDGE, EDGE NAILING (E.N.)
FOR BLOCKED DIAPHRAGM ONLY
NOTES:
·STAGGER JOINTS AS SHOWN
·MIN. SIZE OF SHEET SHALL BE 2 FT. X 2 FT.
·NAILS SHALL BE DRIVEN TIGHT BUT SHALL NOT FRACTURE
SURFACE OF SHEATHING
·TOLERANCE ON NAILING SHALL BE 3/4" W/ THE AVERAGE
NAIL SPACING OVER ANY 4 FT. LENGTH BEING AT LEAST
THAT NOTED ON THE PLAN
DIRECTION OF FACE GAIN
PERPENDICULAR TO SUPPORT
2X FRAMING
PER PLAN
PANEL BOUNDARY &
BOUNDARY NAILING
(B.N.)
PANEL LAYOUT
STAGGER
16" MIN.
24" MIN.
8d: 2X4 MIN.
10d: 3X4 MIN.
3/8"
MIN.
3/8"
MIN.
1/8"
1/4"
MIN.
1/4"
MIN.
E.N.
BLOCKED DIAPHRAGM
NAILING
1
7 10
8
10
11
7
1
8
10
11
7
1
9
9
END
L
E
N
G
T
H
ENDLENG
T
H
3
4
1
2 45
END
LENGTH
1 7
8
6
A CS16 112" (10) 10d 1705# 11"
B CS14 112" (13) 10d 2490# 15"
C CMSTC16 3" (25) 12d 4690# 20"
D CMST14 3"(28) 16d 6475# 26"
E CMST12 3" (37) 16d 9215# 33"
STRAP CAPACITY
MIN. WOOD
MEMBER
THICKNESS
MIN. # OF NAILS @ EACH
END MEMBER PER STRAP
MIN. END
LENGTH
HD
TYPE
(5) 10d 8"3
(6) 10d 9"4
(11) 12d 10"8
(13) 16d 14"10
(18) 16d 18"15
MINIMUM FASTENERS
PER SPLICE
MIN. SPLICE
LENGTH
# OF A35 W/
BLK'G @ TOP
PLATE
DRAG DETAILS
1
2
4
12
7
1.STRAP, SEE TABLE BELOW
2.DRAG BLK'G, SEE PLAN FOR DRAG LENGTH
AND TABLE FOR BLK'G THICKNESS REQ'D
3.ROOF SHT'G. W/ E.N. ALONG LINE OF DRAG
4.JOIST/RAFTER PER PLAN
5.HIP BM. OR TOP CHORD OF HIP TRUSS
6.2X @ 48" O.C., BOTH SIDES OF JOIST
7.DBL. TOP PLATE OR BEAM
8.BEAM PER PLAN
9.SIMPSON EPC, U.N.O.
10.POST PER PLAN
11.2X STUD
12.FULL DEPTH BLK'G W/ A35, SEE TABLE FOR
MIN. REQ'D PER STRAP.
13.LUS/HU HANGER PER FRAMING PLAN
NOTES
14.VALLEY BEAM
15.FULL DEPTH DRAG BLK'G
DRAG BLK'G TO TOP PLATE
DRAG BEAM TO TOP PLATEDRAG RAFTER TO TOP PLATE
2
DRAG TOP PLATE TO TOP PLATE
8
13
86
END LENGTH
CLEAR
SPAN
END LENGTH
4 46
1 13
DRAG BEAM TO BEAM
4 6
14
15
4
1
HIP - DRAG RAFTER TO BLK'G
VALLEY - DRAG RAFTER TO BLK'G
5
6
3
8
1
4 7
B.N.
2
5
6
3 8
1
4
SHEAR TRANSFER
7
B.N.
2
9
PARALLELPERPENDICULAR
1.RAFTER PER PLAN
2.ROOF SHEATHING
3.LTP4 (OR A35), SEE SHEAR WALL SCHEDULE
4.SHEAR WALL AS OCCURS
5.(8) 10d NAILS
6.DBL. TOP PLATE
7.BEAM AS OCCURS
8.CEILING JOIST PER PLAN
9.CS14 W/ 2X BLK'G FOR 4 BAY MIN, U.N.O.
E.N.E.N.
1.CEILING JOIST
2.CALIFORNIA FRAMING,
SEE FRAMING NOTES
3.SHEARWALL
4.2X BLK'G
5.2X STUD @ 16" O.C.
6.RAFTER PER PLAN
7.WALL SHEATHING, SAME
AS BELOW
8.2X SOLE W/ 16d @ 6" O.C.
9.SIMP A35 @ 16" O.C.
10.RAFTER PER PLAN
11.SIMP A35 @ 16" O.C.
12.DBL TOP PLATE
13.2X LEDGER W/ (3) 16d @ 16"
O.C.
14.2X BLK'G @ 48" O.C.
E.N.
E.N.
B.
N
.
5
12
9
6
9
8
7
10 5
4
3
2
1
SHEAR TRANSFER
13
1414
E.N.
1
4
B.N
.
B.N
.
5
1
2
3
RIDGE SHEAR TRANSFER
1.LSTA30 @ 24" O.C.
2.A35 @ EA JOIST
3.RIDGE BOARD
4.LUS
5.RIDGE BEAM
6.ROOF JOIST
6 6 6
42
B.N
.
B.N
.
6
RIDGE BOARD RIDGE BEAM
4
6
B.N.
5
CALIFORNIA FRAMING
3
1
2
1.RAFTERS PER PLAN
2.ROOF SHEATHING
3.2x RIDGE BOARD
4.CALIFORNIA FRAMING
5.2X CONT. W/ 2-16d @ EACH RAFTER
6.FRAMING PER PLAN
7.2x @ SLEEPER
7
4
B.N.B.N.
1.BEAM PER PLAN
2.SIMP. A34, EACH SIDE, TOP & BOT.
3.POST PER PLAN
4.DBL TOP PLATE
2
1
3
4
HIP BEAM
2
2
4
4
1
PLANSECTION
3
4
6
POST DETAIL
2
1
5
1.BEAM PER PLAN
2.SIMP. EPC
3.POST PER PLAN
4.SIMP. A35, EACH SIDE, TOP & BOT.
5.TOP PLATE OR BEAM PER PLAN
6.POST TO MATCH ABOVE
2710 N Laird St & 2209 W
Laramore Ln10/7/2024
FRAMING
DETAILS
SD3
RE
S
T
R
I
C
T
I
V
E
N
O
T
I
C
E
DA
T
E
RE
V
I
S
I
O
N
S
SHEET
SHEET DESCRIPTION
STAMP
NO
:
8/1/24
LE
A
D
D
I
T
I
O
N
&
D
E
T
A
C
H
E
D
A
D
U
DATE:
22
0
9
W
.
L
A
R
A
M
O
R
E
L
N
.
SA
N
T
A
A
N
A
,
C
A
9
2
7
0
6
TH
E
S
E
D
E
S
I
G
N
S
,
D
R
A
W
I
N
G
S
,
A
N
D
SP
E
C
I
F
I
C
A
T
I
O
N
S
A
R
E
E
X
C
L
U
S
I
V
E
T
O
GE
T
S
T
R
U
C
T
U
R
A
L
T
H
E
S
E
D
R
A
W
I
N
G
S
CA
N
N
O
T
B
E
C
O
P
I
E
D
,
T
R
A
N
S
F
E
R
R
E
D
,
O
R
RE
P
R
O
D
U
C
E
D
N
O
R
C
A
N
A
N
Y
O
T
H
E
R
ST
R
U
C
T
U
R
E
S
B
E
B
U
I
L
T
F
R
O
M
T
H
E
M
WI
T
H
O
U
T
W
R
I
T
T
E
N
C
O
N
S
E
N
T
RE
V
I
S
I
O
N
S
30
0
0
E
.
B
I
R
C
H
S
T
R
E
E
T
SU
I
T
E
2
0
3
BR
E
A
,
C
A
9
2
8
2
1
TE
L
:
(
9
0
9
)
5
6
9
-
1
8
8
6
in
f
o
@
G
e
t
S
t
r
u
c
t
u
r
a
l
.
c
o
m
2
JOB: R23-0943
PHONG TR UONG
STATE OF CALIFORNIA
REGISTERED PROFESSIONAL ENGINEER
NO. C70784
EXP. 06/30/2025
CIV IL
2
08
/
0
1
/
2
0
2
4
PL
A
N
C
H
E
C
K
2
21
22
24
23
1
2
3
2
4
BEAM POCKET
1.BEAM PER PLAN
2.SIMP. A34, EACH SIDE, TOP & BOT.
3.POST PER PLAN
4.SILL PLATE
5.(2) 10D MINIMUM EACH SIDE, ADD (2) 10D
FOR EA. 2" OF ADDITION BEAM DEPTH
6.STUD TO COLUMN NAIL, 10D @ 12" O.C.
7.RAFTER PER PLAN
8.LTP4, BOTH SIDES
2
3
2
4
6
5
TAPER CONDITION
1
7
4
1
/
2
"
MI
N
.
3
2
PARALLEL CONDITION
PLA
T
E
L
I
N
E
PLATE LINE
1
2 3
8
HIP TO POST CONNECTION
1
1
4
5
1.POST PER PLAN, 4X6 MIN.
2.SIMP. HHRC, 3.11K PER HIP
3.HIP BEAM PER PLAN
4.(2) SIMP. A34
5.CEILING BEAM PER PLAN
2
2
3
3
3
PLAN
ELEVATION
1
2
SEE TABLE FOR OVERLAP MIN.
56
DRAG DETAIL
NOTES:
1.STRAP NAILING AT BLOCKING
TO BE @ 4" O.C. MAX.
2.SEE PLANS FOR LENGTH OF
BLOCKING
A CS16 11 2" (10) 10d 1705# 11"
B CS14 11 2" (13) 10d 2490# 15"
C CMSTC16 3" (25) 12d 4690# 20"
D CMST14 3"(28) 16d 6475# 26"
E CMST12 3" (37) 16d 9215# 33"
STRAP CAPACITY
MIN. WOOD
MEMBER
THICKNESS
MIN. # OF NAILS @ EACH
END MEMBER PER STRAP
MIN. END
LENGTH
HD
TYPE
(5) 10d 8"
(6) 10d 9"
(11) 12d 10"
(13) 16d 14"
(18) 16d 18"
MINIMUM FASTENERS
PER SPLICE
MIN. SPLICE
LENGTH
1.JOIST/RAFTER PER PLAN
2.4x DEPTH BLK'G, SEE TABLE BELOW FOR MIN.
THICKNESS
3.BOUNDARY NAILING PER DIAPHRAGM
4.LOAD BEARING WALL OR CEILING PER PLAN
5.2X FULL DEPTH BLK'G @ 48" O.C., BOTH SIDES
OF COLLECTOR BEAM W/ BOUNDARY NAILING
6.COLLECTOR BEAM/LEDGER PER PLAN
5
DRAG JOIST
DRAG BLOCKING
3
X
2
B.N.B.N.
1 5
6
2
78
4 9
1.2X4 FLAT AT 24" O.C.
2.(2) 16d SINKER OR SHORT NAILS EACH 2X4 FLAT
3.A35 (OR LTP4) PER SW SCHD, @ 32" O.C. MAX. CLIP CAN BE OMITTED IF
SW IS EXTENDED & W/EN. TO RAFTER.
4.SHEAR WALL WHERE OCCURS
5.ROOF RAFTER PER PLAN
6.ROOF SHEATHING
7.2X FULL DEPTH BLOCKING AT 48" OC BETWEEN RIM & 1ST JOIST
BOUNDARY NAIL 1TO BLOCKING
8.(3) 8d COMMON TOENAILS BLOCK TO PLATE
9.2X STUD WALL
10.TOP PLATE
11.CEILING JOIST PER PLAN
12.2X LEDGER W/ (2) 1/4" WOOD SCREWS @ 16" O.C., 2.5" MIN. EMBEDMENT
13.SIMP. LUS
3
E.N.
10
3
5
4
6
B.N.
6
SHEAR TRANSFER
PARALLEL
E.N.
6
9
10
PERPENDICULAR
12
13
11
12
13
11
2
4
3
1
POST TO BEAM
1.BEAM PER PLAN
2.SIMP. ECCQ
3.POST PER PLAN
4.SIMP. CCQ
5.SIMP. CCTQ
6.SIMP. ECCLLQ
7.SIMP. ECCLRQ
5
3
1
6
3
1
7
3
1
25
21
3
FLUSH CEILING JOIST
1.BEAM PER PLAN
2.SIMP. LUS OR EQUIVALENT
3.JOIST PER PLAN
2
3
26
E.N.
9 10
8
2 4
5
3
6
E.N.
B.N.
B.N.
A
SHEAR TRANSFER
1
7
11.2X BLK'G @ 48" O.C., 2 BAY MIN.
2.2X R.R.
3.A35 @16" O.C.
4.ROOF SHTH'G CAL. FRAMING
5.ROOF SHEATHING
6.2X SILL W/ 16d @6" O.C.
7.16d @ 6" O.C.
8.2X BLK'G
9.CEILING BEAM PER PLAN
10.SIMPSON LUS HGR
11.CEILING JOIST
11
12
2
11
7
27
2
2
2X BLK'G
CEILING
JOIST PER
PLAN
LOAD
BEARING
WALL OR
DROP BEAM
LOAD BEARING WALL / DROPBEAM
8"
MIN.
(9) 10d NAILS
AT LAP
28
2
3
11 2"4"
112"
412"
112"
6"
6"
3"
MI
N
.
6"
9"
HIP-RIDGE CONNECTION
1.1/4" PLATES, (4) 3/4" MACH. BOLTS W/ NUT & WASHER
2.HIP BEAM PER PLAN
3.RIDGE BEAM PER PLAN (4X10 MIN.)
4.PLATE ON 3 SIDES OF HIP
2
1
1
2
3
PLAN VIEW ELEVATION
14
ALL WELDING TO BE SHOP
WELDED BY FABRICATOR
REGISTERED. NO SPECIAL
INSPECTION REQUIRED PER
CBC 1704.2.5.1
1/4
TYP
1/4
TYP
29
2
2710 N Laird St & 2209 W
Laramore Ln10/7/2024
2710 N Laird St & 2209 W
Laramore Ln10/7/2024
2710 N Laird St & 2209 W
Laramore Ln10/7/2024
CHAPTER 4
RESIDENTIAL MANDATORY MEASURES
DIVISION 4.1 PLANNING AND DESIGN
DIVISION 4.3 WATER EFFICIENCY AND CONSERVATION
4.406 ENHANCED DURABILITY AND REDUCED MAINTENANCE
4.406.1 RODENT PROOFING. Annular spaces around pipes, electric cables, conduits or other openings in
sole/bottom plates at exterior walls shall be protected against the passage of rodents by closing such
openings with cement mortar, concrete masonry or a similar method acceptable to the enforcing
agency.
4.408 CONSTRUCTION WASTE REDUCTION, DISPOSAL AND RECYCLING
4.408.1 CONSTRUCTION WASTE MANAGEMENT. Recycle and/or salvage for reuse a minimum of 65
percent of the non-hazardous construction and demolition waste in accordance with either Section
4.408.2, 4.408.3 or 4.408.4, or meet a more stringent local construction and demolition waste
management ordinance.
Exceptions:
1. Excavated soil and land-clearing debris.
2. Alternate waste reduction methods developed by working with local agencies if diversion or
recycle facilities capable of compliance with this item do not exist or are not located reasonably
close to the jobsite.
3. The enforcing agency may make exceptions to the requirements of this section when isolated
jobsites are located in areas beyond the haul boundaries of the diversion facility.
4.408.2 CONSTRUCTION WASTE MANAGEMENT PLAN. Submit a construction waste management plan
in conformance with Items 1 through 5. The construction waste management plan shall be updated as
necessary and shall be available during construction for examination by the enforcing agency.
1. Identify the construction and demolition waste materials to be diverted from disposal by recycling,
reuse on the project or salvage for future use or sale.
2. Specify if construction and demolition waste materials will be sorted on-site (source separated) or
bulk mixed (single stream).
3. Identify diversion facilities where the construction and demolition waste material collected will be
taken.
4. Identify construction methods employed to reduce the amount of construction and demolition waste
generated.
5. Specify that the amount of construction and demolition waste materials diverted shall be calculated
by weight or volume, but not by both.
4.408.3 WASTE MANAGEMENT COMPANY. Utilize a waste management company, approved by the
enforcing agency, which can provide verifiable documentation that the percentage of construction and
demolition waste material diverted from the landfill complies with Section 4.408.1.
Note: The owner or contractor may make the determination if the construction and demolition waste
materials will be diverted by a waste management company.
4.408.4 WASTE STREAM REDUCTION ALTERNATIVE [LR]. Projects that generate a total combined
weight of construction and demolition waste disposed of in landfills, which do not exceed 3.4
lbs./sq.ft. of the building area shall meet the minimum 65% construction waste reduction requirement in
Section 4.408.1
4.408.4.1 WASTE STREAM REDUCTION ALTERNATIVE. Projects that generate a total combined
weight of construction and demolition waste disposed of in landfills, which do not exceed 2 pounds
per square foot of the building area, shall meet the minimum 65% construction waste reduction
requirement in Section 4.408.1
4.408.5 DOCUMENTATION. Documentation shall be provided to the enforcing agency which demonstrates
compliance with Section 4.408.2, items 1 through 5, Section 4.408.3 or Section 4.408.4..
Notes:
1. Sample forms found in "A Guide to the California Green Building Standards Code
(Residential)" located at www.hcd.ca.gov/CALGreen.html may be used to assist in
documenting compliance with this section.
2. Mixed construction and demolition debris (C & D) processors can be located at the California
Department of Resources Recycling and Recovery (CalRecycle).
4.410 BUILDING MAINTENANCE AND OPERATION
4.410.1 OPERATION AND MAINTENANCE MANUAL. At the time of final inspection, a manual, compact
disc, web-based reference or other media acceptable to the enforcing agency which includes all of the
following shall be placed in the building:
1. Directions to the owner or occupant that the manual shall remain with the building throughout the
life cycle of the structure.
2. Operation and maintenance instructions for the following:
a. Equipment and appliances, including water-saving devices and systems, HVAC systems,
photovoltaic systems, electric vehicle chargers, water-heating systems and other major
appliances and equipment.
b. Roof and yard drainage, including gutters and downspouts.
c. Space conditioning systems, including condensers and air filters.
d. Landscape irrigation systems.
e. Water reuse systems.
3. Information from local utility, water and waste recovery providers on methods to further reduce
resource consumption, including recycle programs and locations.
4. Public transportation and/or carpool options available in the area.
5. Educational material on the positive impacts of an interior relative humidity between 30-60 percent
and what methods an occupant may use to maintain the relative humidity level in that range.
6. Information about water-conserving landscape and irrigation design and controllers which conserve
water.
7. Instructions for maintaining gutters and downspouts and the importance of diverting water at least 5
feet away from the foundation.
8. Information on required routine maintenance measures, including, but not limited to, caulking,
painting, grading around the building, etc.
9. Information about state solar energy and incentive programs available.
10. A copy of all special inspections verifications required by the enforcing agency or this code.
11. Information from the Department of Forestry and Fire Protection on maintenance of defensible
space around residential structures.
12. Information and/or drawings identifying the location of grab bar reinforcements.
4.410.2 RECYCLING BY OCCUPANTS. Where 5 or more multifamily dwelling units are constructed on a
building site, provide readily accessible area(s) that serves all buildings on the site and are identified for the
depositing, storage and collection of non-hazardous materials for recycling, including (at a minimum) paper,
corrugated cardboard, glass, plastics, organic waster, and metals, or meet a lawfully enacted local recycling
ordinance, if more restrictive.
Exception: Rural jurisdictions that meet and apply for the exemption in Public Resources Code Section
42649.82 (a)(2)(A) et seq. are note required to comply with the organic waste portion of
this section.
DIVISION 4.4 MATERIAL CONSERVATION AND RESOURCE
EFFICIENCY
DIVISION 4.5 ENVIRONMENTAL QUALITY
4.303 INDOOR WATER USE
4.303.1 WATER CONSERVING PLUMBING FIXTURES AND FITTINGS. Plumbing fixtures (water closets and
urinals) and fittings (faucets and showerheads) shall comply with the sections 4.303.1.1, 4.303.1.2, 4.303.1.3,
and 4.303.4.4.
Note: All noncompliant plumbing fixtures in any residential real property shall be replaced with water-conserving
plumbing fixtures. Plumbing fixture replacement is required prior to issuance of a certificate of final
completion, certificate of occupancy, or final permit approval by the local building department. See Civil
Code Section 1101.1, et seq., for the definition of a noncompliant plumbing fixture, types of residential
buildings affected and other important enactment dates.
4.303.1.1 Water Closets. The effective flush volume of all water closets shall not exceed 1.28 gallons per
flush. Tank-type water closets shall be certified to the performance criteria of the U.S. EPA WaterSense
Specification for Tank-type Toilets.
Note: The effective flush volume of dual flush toilets is defined as the composite, average flush volume
of two reduced flushes and one full flush.
4.303.1.2 Urinals. The effective flush volume of wall mounted urinals shall not exceed 0.125 gallons per flush.
The effective flush volume of all other urinals shall not exceed 0.5 gallons per flush.
4.303.1.3 Showerheads.
4.303.1.3.1 Single Showerhead. Showerheads shall have a maximum flow rate of not more than 1.8
gallons per minute at 80 psi. Showerheads shall be certified to the performance criteria of the U.S. EPA
WaterSense Specification for Showerheads.
4.303.1.3.2 Multiple showerheads serving one shower. When a shower is served by more than one
showerhead, the combined flow rate of all the showerheads and/or other shower outlets controlled by
a single valve shall not exceed 1.8 gallons per minute at 80 psi, or the shower shall be designed to only
allow one shower outlet to be in operation at a time.
Note: A hand-held shower shall be considered a showerhead.
4.303.1.4 Faucets.
4.303.1.4.1 Residential Lavatory Faucets. The maximum flow rate of residential lavatory faucets shall
not exceed 1.2 gallons per minute at 60 psi. The minimum flow rate of residential lavatory faucets shall
not be less than 0.8 gallons per minute at 20 psi.
4.303.1.4.2 Lavatory Faucets in Common and Public Use Areas. The maximum flow rate of lavatory
faucets installed in common and public use areas (outside of dwellings or sleeping units) in residential
buildings shall not exceed 0.5 gallons per minute at 60 psi.
4.303.1.4.3 Metering Faucets. Metering faucets when installed in residential buildings shall not deliver
more than 0.2 gallons per cycle.
4.303.1.4.4 Kitchen Faucets. The maximum flow rate of kitchen faucets shall not exceed 1.8 gallons
per minute at 60 psi. Kitchen faucets may temporarily increase the flow above the maximum rate, but not
to exceed 2.2 gallons per minute at 60 psi, and must default to a maximum flow rate of 1.8 gallons per
minute at 60 psi.
Note: Where complying faucets are unavailable, aerators or other means may be used to achieve
reduction.
4.303.1.4.5 Pre-rinse spray valves.
When installed, shall meet the requirements in the California Code of Regulations, Title 20 (Appliance
Efficiency Regulations), Sections 1605.1 (h)(4) Table H-2, Section 1605.3 (h)(4)(A), and Section 1607
(d)(7) and shall be equipped with an integral automatic shutoff.
FOR REFERENCE ONLY: The following table and code section have been reprinted from the California
Code of Regulations, Title 20 (Appliance Efficiency Regulations),Section 1605.1 (h)(4) and Section
1605.3 (h)(4)(A).
Title 20 Section 1605.3 (h)(4)(A): Commercial prerinse spray values manufactured on or after January
1, 2006, shall have a minimum spray force of not less than 4.0 ounces-force (ozf)[113 grams-force(gf)]
4.303.2 Submeters for multifamily buildings and dwelling units in mixed-used residential/commercial
buildings.
Submeters shall be installed to measure water usage of individual rental dwelling units in accordance with the
California Plumbing Code.
4.303.3 Standards for plumbing fixtures and fittings. Plumbing fixtures and fittings shall be installed in
accordance with the California Plumbing Code, and shall meet the applicable standards referenced in Table
1701.1 of the California Plumbing Code.
TABLE - MAXIMUM FIXTURE WATER USE
FIXTURE TYPE FLOW RATE
SHOWER HEADS (RESIDENTIAL)1.8 GMP @ 80 PSI
LAVATORY FAUCETS (RESIDENTIAL)MAX. 1.2 GPM @ 60 PSI MIN. 0.8 GPM @ 20
PSI
LAVATORY FAUCETS IN COMMON & PUBLIC
USE AREAS 0.5 GPM @ 60 PSI
KITCHEN FAUCETS 1.8 GPM @ 60 PSI
METERING FAUCETS 0.2 GAL/CYCLE
WATER CLOSET 1.28 GAL/FLUSH
URINALS 0.125 GAL/FLUSH
4.304 OUTDOOR WATER USE
4.304.1 OUTDOOR POTABLE WATER USE IN LANDSCAPE AREAS. Residential developments shall comply with
a local water efficient landscape ordinance or the current California Department of Water Resources' Model Water
Efficient Landscape Ordinance (MWELO), whichever is more stringent.
NOTES:
1. The Model Water Efficient Landscape Ordinance (MWELO) is located in the California Code Regulations,
Title 23, Chapter 2.7, Division 2. MWELO and supporting documents, including water budget calculator, are
available at: https://www.water.ca.gov/
ABBREVIATION DEFINITIONS:
HCD Department of Housing and Community Development
BSC California Building Standards Commission
DSA-SS Division of the State Architect, Structural Safety
OSHPD Office of Statewide Health Planning and Development
LR Low Rise
HR High Rise
AA Additions and Alterations
N New
NOTE:
THIS TABLE COMPILES THE DATA IN SECTION 4.303.1, AND IS INCLUDED AS A
CONVENIENCE FOR THE USER.
SECTION 4.102 DEFINITIONS
4.102.1 DEFINITIONS
The following terms are defined in Chapter 2 (and are included here for reference)
FRENCH DRAIN. A trench, hole or other depressed area loosely filled with rock, gravel, fragments of brick or similar
pervious material used to collect or channel drainage or runoff water.
WATTLES. Wattles are used to reduce sediment in runoff. Wattles are often constructed of natural plant materials
such as hay, straw or similar material shaped in the form of tubes and placed on a downflow slope. Wattles are also
used for perimeter and inlet controls.
4.106 SITE DEVELOPMENT
4.106.1 GENERAL. Preservation and use of available natural resources shall be accomplished through evaluation
and careful planning to minimize negative effects on the site and adjacent areas. Preservation of slopes,
management of storm water drainage and erosion controls shall comply with this section.
4.106.2 STORM WATER DRAINAGE AND RETENTION DURING CONSTRUCTION. Projects which disturb less
than one acre of soil and are not part of a larger common plan of development which in total disturbs one acre
or more, shall manage storm water drainage during construction. In order to manage storm water drainage
during construction, one or more of the following measures shall be implemented to prevent flooding of adjacent
property, prevent erosion and retain soil runoff on the site.
1. Retention basins of sufficient size shall be utilized to retain storm water on the site.
2. Where storm water is conveyed to a public drainage system, collection point, gutter or similar
disposal method, water shall be filtered by use of a barrier system, wattle or other method approved
by the enforcing agency.
3. Compliance with a lawfully enacted storm water management ordinance.
Note: Refer to the State Water Resources Control Board for projects which disturb one acre or more of soil, or
are part of a larger common plan of development which in total disturbs one acre or more of soil.
(Website: https://www.waterboards.ca.gov/water_issues/programs/stormwater/construction.html)
4.106.3 GRADING AND PAVING. Construction plans shall indicate how the site grading or drainage system will
manage all surface water flows to keep water from entering buildings. Examples of methods to manage surface
water include, but are not limited to, the following:
1. Swales
2. Water collection and disposal systems
3. French drains
4. Water retention gardens
5. Other water measures which keep surface water away from buildings and aid in groundwater
recharge.
Exception: Additions and alterations not altering the drainage path.
4.106.4 Electric vehicle (EV) charging for new construction. New construction shall comply with Sections
4.106.4.1 or 4.106.4.2 to facilitate future installation and use of EV chargers. Electric vehicle supply
equipment (EVSE) shall be installed in accordance with the California Electrical Code, Article 625.
Exceptions:
1. On a case-by-case basis, where the local enforcing agency has determined EV charging and
infrastructure are not feasible based upon one or more of the following conditions:
1.1 Where there is no local utility power supply or the local utility is unable to supply adequate
power.
1.2 Where there is evidence suitable to the local enforcing agency substantiating that additional
local utility infrastructure design requirements, directly related to the implementation of Section
4.106.4, may adversely impact the construction cost of the project.
2. Accessory Dwelling Units (ADU) and Junior Accessory Dwelling Units (JADU) without additional
parking facilities.
4.106.4.1 New one- and two-family dwellings and townhouses with attached private garages. For each
dwelling unit, install a listed raceway to accommodate a dedicated 208/240-volt branch circuit. The raceway
shall not be less than trade size 1 (nominal 1-inch inside diameter). The raceway shall originate at the main
service or subpanel and shall terminate into a listed cabinet, box or other enclosure in close proximity to the
proposed location of an EV charger. Raceways are required to be continuous at enclosed, inaccessible or
concealed areas and spaces. The service panel and/or subpanel shall provide capacity to install a 40-ampere
208/240-volt minimum dedicated branch circuit and space(s) reserved to permit installation of a branch circuit
overcurrent protective device.
Exemption: A raceway is not required if a minimum 40-ampere 208/240-volt dedicated EV branch circuit is
installed in close proximity to the proposed location of an EV charger at the time of original construction in
accordance with the California Electrical Code.
4.106.4.1.1 Identification. The service panel or subpanel circuit directory shall identify the overcurrent
protective device space(s) reserved for future EV charging as "EV CAPABLE". The raceway termination
location shall be permanently and visibly marked as "EV CAPABLE".
CHAPTER 3
GREEN BUILDING
SECTION 301 GENERAL
301.1 SCOPE. Buildings shall be designed to include the green building measures specified as mandatory in
the application checklists contained in this code. Voluntary green building measures are also included in the
application checklists and may be included in the design and construction of structures covered by this code,
but are not required unless adopted by a city, county, or city and county as specified in Section 101.7.
301.1.1 Additions and alterations. [HCD] The mandatory provisions of Chapter 4 shall be applied to
additions or alterations of existing residential buildings where the addition or alteration increases the
building's conditioned area, volume, or size. The requirements shall apply only to and/or within the
specific area of the addition or alteration.
The mandatory provision of Section 4.106.4.2 may apply to additions or alterations of existing parking
facilities or the addition of new parking facilities serving existing multifamily buildings. See Section
4.106.4.3 for application.
Note: Repairs including, but not limited to, resurfacing, restriping and repairing or maintaining existing
lighting fixtures are not considered alterations for the purpose of this section.
Note: On and after January 1, 2014, residential buildings undergoing permitted alterations, additions, or
improvements shall replace noncompliant plumbing fixtures with water-conserving plumbing fixtures.
Plumbing fixture replacement is required prior to issuance of a certificate of final completion, certificate
of occupancy or final permit approval by the local building department. See Civil Code Section 1101.1,
et seq., for the definition of a noncompliant plumbing fixture, types of residential buildings affected and
other important enactment dates.
301.2 LOW-RISE AND HIGH-RISE RESIDENTIAL BUILDINGS. [HCD] The provisions of
individual sections of CALGreen may apply to either low-rise residential buildings high-rise residential
buildings, or both. Individual sections will be designated by banners to indicate where the section applies
specifically to low-rise only (LR) or high-rise only (HR). When the section applies to both low-rise and
high-rise buildings, no banner will be used.
SECTION 302 MIXED OCCUPANCY BUILDINGS
302.1 MIXED OCCUPANCY BUILDINGS. In mixed occupancy buildings, each portion of a building
shall comply with the specific green building measures applicable to each specific occupancy.
Exceptions:
1. [HCD] Accessory structures and accessory occupancies serving residential buildings shall
comply with Chapter 4 and Appendix A4, as applicable.
2. [HCD] For purposes of CALGreen, live/work units, complying with Section 419 of the California
Building Code, shall not be considered mixed occupancies. Live/Work units shall comply with
Chapter 4 and Appendix A4, as applicable.
4.106.4.2 New multifamily dwellings, hotels and motels and new residential parking facilities.
When parking is provided, parking spaces for new multifamily dwellings, hotels and motels shall meet the
requirements of Sections 4.106.4.2.1 and 4.106.4.2.2. Calculations for spaces shall be rounded up to the nearest
whole number. A parking space served by electric vehicle supply equipment or designed as a future EV charging
space shall count as at least one standard automobile parking space only for the purpose of complying with any
applicable minimum parking space requirements established by a local jurisdiction. See Vehicle Code Section 22511.2
for further details.
4.106.4.2.1Multifamily development projects with less than 20 dwelling units; and hotels and motels with less
than 20 sleeping units or guest rooms.
The number of dwelling units, sleeping units or guest rooms shall be based on all buildings on a project site subject to
this section.
1.EV Capable. Ten (10) percent of the total number of parking spaces on a building site, provided for all types
of parking facilities, shall be electric vehicle charging spaces (EV spaces) capable of supporting future Level 2
EVSE. Electrical load calculations shall demonstrate that the electrical panel service capacity and electrical
system, including any on-site distribution transformer(s), have sufficient capacity to simultaneously charge all
EVs at all required EV spaces at a minimum of 40 amperes.
The service panel or subpanel circuit directory shall identify the overcurrent protective device space(s) reserved
for future EV charging purposes as “EV CAPABLE” in accordance with the California Electrical Code.
Exceptions:
1.When EV chargers (Level 2 EVSE) are installed in a number equal to or greater than the required number
of EV capable spaces.
2.When EV chargers (Level 2 EVSE) are installed in a number less than the required number of EV capable
spaces, the number of EV capable spaces required may be reduced by a number equal to the number of
EV chargers installed.
Notes:
a.Construction documents are intended to demonstrate the project’s capability and capacity for facilitating
future EV charging.
b.There is no requirement for EV spaces to be constructed or available until receptacles for EV charging or
EV chargers are installed for use.
2.EV Ready. Twenty-five (25) percent of the total number of parking spaces shall be equipped with low power
Level 2 EV charging receptacles. For multifamily parking facilities, no more than one receptacle is required per
dwelling unit when more than one parking space is provided for use by a single dwelling unit.
Exception: Areas of parking facilities served by parking lifts.
4.106.4.2.2 Multifamily development projects with 20 or more dwelling units, hotels and motels with 20 or more
sleeping units or guest rooms.
The number of dwelling units, sleeping units or guest rooms shall be based on all buildings on a project site subject to
this section.
1.EV Capable. Ten (10) percent of the total number of parking spaces on a building site, provided for all types
of parking facilities, shall be electric vehicle charging spaces (EV spaces) capable of supporting future Level 2
EVSE. Electrical load calculations shall demonstrate that the electrical panel service capacity and electrical
system, including any on-site distribution transformer(s), have sufficient capacity to simultaneously charge all
EVs at all required EV spaces at a minimum of 40 amperes.
The service panel or subpanel circuit directory shall identify the overcurrent protective device space(s) reserved
for future EV charging purposes as “EV CAPABLE” in accordance with the California Electrical Code.
Exception: When EV chargers (Level 2 EVSE) are installed in a number greater than five (5) percent of
parking spaces required by Section 4.106.4.2.2, Item 3, the number of EV capable spaces required may be
reduced by a number equal to the number of EV chargers installed over the five (5) percent required.
Notes:
a.Construction documents shall show locations of future EV spaces.
b.There is no requirement for EV spaces to be constructed or available until receptacles for EV charging or
EV chargers are installed for use.
2.EV Ready. Twenty-five (25) percent of the total number of parking spaces shall be equipped with low power
Level 2 EV charging receptacles. For multifamily parking facilities, no more than one receptacle is required per
dwelling unit when more than one parking space is provided for use by a single dwelling unit.
Exception: Areas of parking facilities served by parking lifts.
3.EV Chargers. Five (5) percent of the total number of parking spaces shall be equipped with Level 2 EVSE.
Where common use parking is provided, at least one EV charger shall be located in the common use parking
area and shall be available for use by all residents or guests.
When low power Level 2 EV charging receptacles or Level 2 EVSE are installed beyond the minimum required,
an automatic load management system (ALMS) may be used to reduce the maximum required electrical
capacity to each space served by the ALMS. The electrical system and any on-site distribution transformers
shall have sufficient capacity to deliver at least 3.3 kW simultaneously to each EV charging station (EVCS)
served by the ALMS. The branch circuit shall have a minimum capacity of 40 amperes, and installed EVSE shall
have a capacity of not less than 30 amperes. ALMS shall not be used to reduce the minimum required electrical
capacity to the required EV capable spaces.
4.106.4.2.2.1 Electric vehicle charging stations (EVCS).
Electric vehicle charging stations required by Section 4.106.4.2.2, Item 3, shall comply with Section 4.106.4.2.2.1.
Exception: Electric vehicle charging stations serving public accommodations, public housing, motels and hotels
shall not be required to comply with this section. See California Building Code, Chapter 11B, for applicable
requirements.
4.106.4.2.2.1.1 Location.
EVCS shall comply with at least one of the following options:
1.The charging space shall be located adjacent to an accessible parking space meeting the requirements of
the California Building Code, Chapter 11A, to allow use of the EV charger from the accessible parking space.
2.The charging space shall be located on an accessible route, as defined in the California Building Code,
Chapter 2, to the building.
Exception: Electric vehicle charging stations designed and constructed in compliance with the California
Building Code, Chapter 11B, are not required to comply with Section 4.106.4.2.2.1.1 and Section
4.106.4.2.2.1.2, Item 3.
4.106.4.2.2.1.2 Electric vehicle charging stations (EVCS) dimensions.
The charging spaces shall be designed to comply with the following:
1.The minimum length of each EV space shall be 18 feet (5486 mm).
2.The minimum width of each EV space shall be 9 feet (2743 mm).
3.One in every 25 charging spaces, but not less than one, shall also have an 8-foot (2438 mm) wide minimum
aisle. A 5-foot (1524 mm) wide minimum aisle shall be permitted provided the minimum width of the EV space is
12 feet (3658 mm).
a.Surface slope for this EV space and the aisle shall not exceed 1 unit vertical in 48 units horizontal (2.083
percent slope) in any direction.
4.106.4.2.2.1.3 Accessible EV spaces.
In addition to the requirements in Sections 4.106.4.2.2.1.1 and 4.106.4.2.2.1.2, all EVSE, when installed, shall
comply with the accessibility provisions for EV chargers in the California Building Code, Chapter 11B. EV ready
spaces and EVCS in multifamily developments shall comply with California Building Code, Chapter 11A, Section
1109A.
4.106.4.2.3 EV space requirements.
1.Single EV space required. Install a listed raceway capable of accommodating a 208/240-volt dedicated branch
circuit. The raceway shall not be less than trade size 1 (nominal 1-inch inside diameter). The raceway shall
originate at the main service or subpanel and shall terminate into a listed cabinet, box or enclosure in close
proximity to the location or the proposed location of the EV space. Construction documents shall identify the
raceway termination point, receptacle or charger location, as applicable. The service panel and/ or subpanel shall
have a 40-ampere minimum dedicated branch circuit, including branch circuit overcurrent protective device
installed, or space(s) reserved to permit installation of a branch circuit overcurrent protective device.
Exception: A raceway is not required if a minimum 40-ampere 208/240-volt dedicated EV branch circuit is
installed in close proximity to the location or the proposed location of the EV space, at the time of original
construction in accordance with the California Electrical Code.
2.Multiple EV spaces required. Construction documents shall indicate the raceway termination point and the
location of installed or future EV spaces, receptacles or EV chargers. Construction documents shall also provide
information on amperage of installed or future receptacles or EVSE, raceway method(s), wiring schematics and
electrical load calculations. Plan design shall be based upon a 40-ampere minimum branch circuit. Required
raceways and related components that are planned to be installed underground, enclosed, inaccessible or in
concealed areas and spaces shall be installed at the time of original construction.
SECTION 4.501 GENERAL
4.501.1 Scope
The provisions of this chapter shall outline means of reducing the quality of air contaminants that are odorous,
irritating and/or harmful to the comfort and well being of a building's installers, occupants and neighbors.
SECTION 4.502 DEFINITIONS
5.102.1 DEFINITIONS
The following terms are defined in Chapter 2 (and are included here for reference)
AGRIFIBER PRODUCTS. Agrifiber products include wheatboard, strawboard, panel substrates and door
cores, not including furniture, fixtures and equipment (FF&E) not considered base building elements.
COMPOSITE WOOD PRODUCTS. Composite wood products include hardwood plywood, particleboard and
medium density fiberboard. "Composite wood products" does not include hardboard, structural plywood,
structural panels, structural composite lumber, oriented strand board, glued laminated timber, prefabricated
wood I-joists or finger-jointed lumber, all as specified in California Code of regulations (CCR), title 17, Section
93120.1.
DIRECT-VENT APPLIANCE. A fuel-burning appliance with a sealed combustion system that draws all air for
combustion from the outside atmosphere and discharges all flue gases to the outside atmosphere.
DISCLAIMER:THIS DOCUMENT IS PROVIDED AND INTENDED TO BE USED AS A MEANS TO INDICATE AREAS OF COMPLIANCE WITH THE CALIFORNIA GREEN BUILDING STANDARDS (CALGREEN) CODE. DUE TO THE VARIABLES BETWEEN BUILDING DEPARTMENT JURISDICTIONS, THIS CHECKLIST IS TO BE USED ON AN INDIVIDUAL PROJECT BASIS AND MAY BE MODIFIED BY THE END USER TO MEET THOSE INDIVIDUAL NEEDS. THE END USER ASSUMES ALL RESPONSIBILITY ASSOCIATED WITH THE USE OF THIS DOCUMENT, INCLUDING VERIFICATION WITH THE FULL CODE.
Y N/AYN/AYN/AYN/A RESPON.
PARTY
RESPON.
PARTY
RESPON.
PARTY
RESPON.
PARTY
2022 CALIFORNIA GREEN BUILDING STANDARDS CODE
RESIDENTIAL MANDATORY MEASURES, SHEET 1 (January 2023)Y = YES
N/A =NOT APPLICABLE
RESPON. PARTY =RESPONSIBLE PARTY (ie: ARCHITECT, ENGINEER,
OWNER, CONTRACTOR, INSPECTOR ETC.)
4.201 GENERAL
4.201.1 SCOPE. For the purposes of mandatory energy efficiency standards in this code, the California Energy
Commission will continue to adopt mandatory standards.
DIVISION 4.2 ENERGY EFFICIENCY
TABLE H-2
STANDARDS FOR COMMERCIAL PRE-RINSE SPRAY
VALUES MANUFACTURED ON OR AFTER JANUARY 28, 2019
PRODUCT CLASS
[spray force in ounce force (ozf)]MAXIMUM FLOW RATE (gpm)
Product Class 1 (≤1.00
Product Class 2 (> 5.0 ozf and ≤1.20
Product Class 3 (> 8.0 ozf)1.28
Exception: A raceway is not required if a minimum 40-ampere 208/240-volt dedicated EV branch circuit is
installed in close proximity to the location or the proposed location of the EV space at the time of original
construction in accordance with the California Electrical Code.
4.106.4.2.4 Identification.
The service panel or subpanel circuit directory shall identify the overcurrent protective device space(s) reserved for
future EV charging purposes as “EV CAPABLE” in accordance with the California Electrical Code.
4.106.4.2.5 Electric Vehicle Ready Space Signage.
Electric vehicle ready spaces shall be identified by signage or pavement markings, in compliance with Caltrans
Traffic Operations Policy Directive 13-01 (Zero Emission Vehicle Signs and Pavement Markings) or its
successor(s).
4.106.4.3 Electric vehicle charging for additions and alterations of parking facilities serving existing
multifamily buildings.
When new parking facilities are added, or electrical systems or lighting of existing parking facilities are added or
altered and the work requires a building permit, ten (10) percent of the total number of parking spaces added or
altered shall be electric vehicle charging spaces (EV spaces) capable of supporting future Level 2 EVSE.
Notes:
1.Construction documents are intended to demonstrate the project’s capability and capacity for facilitating future
EV charging.
2.There is no requirement for EV spaces to be constructed or available until EV chargers are installed for use.
D E S I G N
2024 FEBRUARY 19
DETACHED ADU
DATEISSUED FOR
I S S U E S
2710 LAIRD AVENUE
SANTA ANA, CALIFORNIA 92706
DAVID LE RESIDENCE
A-23-002-008
PROPOSED
HOUSE EXTENSION
+
PLAN CHECK SUBMITTAL 10.25.2023
2ND PLAN CHECK SUBMITTAL 01.05.2024
BUILDING SAFETY SUBMITTAL 01.25.2024
UPDATE PLAN SET FOR PRESCREEN 02.19.2024
2209 W. LARAMORE LANE
SANTA ANA, CALIFORNIA 92706
UPDATE PLAN SET 03.31.2024
A-03
CALIFORNIA
GREEN BUILDING
STANDARD
(SHEET - 1)
2710 N Laird St & 2209 W
Laramore Ln10/7/2024
MAXIMUM INCREMENTAL REACTIVITY (MIR). The maximum change in weight of ozone formed by adding a
compound to the "Base Reactive Organic Gas (ROG) Mixture" per weight of compound added, expressed to
hundredths of a gram (g O³/g ROC).
Note: MIR values for individual compounds and hydrocarbon solvents are specified in CCR, Title 17, Sections 94700
and 94701.
MOISTURE CONTENT. The weight of the water in wood expressed in percentage of the weight of the oven-dry wood.
PRODUCT-WEIGHTED MIR (PWMIR). The sum of all weighted-MIR for all ingredients in a product subject to this
article. The PWMIR is the total product reactivity expressed to hundredths of a gram of ozone formed per gram of
product (excluding container and packaging).
Note: PWMIR is calculated according to equations found in CCR, Title 17, Section 94521 (a).
REACTIVE ORGANIC COMPOUND (ROC). Any compound that has the potential, once emitted, to contribute to
ozone formation in the troposphere.
VOC. A volatile organic compound (VOC) broadly defined as a chemical compound based on carbon chains or rings
with vapor pressures greater than 0.1 millimeters of mercury at room temperature. These compounds typically contain
hydrogen and may contain oxygen, nitrogen and other elements. See CCR Title 17, Section 94508(a).
4.503 FIREPLACES
4.503.1 GENERAL. Any installed gas fireplace shall be a direct-vent sealed-combustion type. Any installed
woodstove or pellet stove shall comply with U.S. EPA New Source Performance Standards (NSPS) emission limits as
applicable, and shall have a permanent label indicating they are certified to meet the emission limits. Woodstoves,
pellet stoves and fireplaces shall also comply with applicable local ordinances.
4.504 POLLUTANT CONTROL
4.504.1 COVERING OF DUCT OPENINGS & PROTECTION OF MECHANICAL EQUIPMENT DURING
CONSTRUCTION. At the time of rough installation, during storage on the construction site and until final
startup of the heating, cooling and ventilating equipment, all duct and other related air distribution component
openings shall be covered with tape, plastic, sheet metal or other methods acceptable to the enforcing agency to
reduce the amount of water, dust or debris which may enter the system.
4.504.2 FINISH MATERIAL POLLUTANT CONTROL. Finish materials shall comply with this section.
4.504.2.1 Adhesives, Sealants and Caulks. Adhesives, sealant and caulks used on the project shall meet the
requirements of the following standards unless more stringent local or regional air pollution or air quality
management district rules apply:
1. Adhesives, adhesive bonding primers, adhesive primers, sealants, sealant primers and caulks
shall comply with local or regional air pollution control or air quality management district rules where
applicable or SCAQMD Rule 1168 VOC limits, as shown in Table 4.504.1 or 4.504.2, as applicable.
Such products also shall comply with the Rule 1168 prohibition on the use of certain toxic
compounds (chloroform, ethylene dichloride, methylene chloride, perchloroethylene and
tricloroethylene), except for aerosol products, as specified in Subsection 2 below.
2. Aerosol adhesives, and smaller unit sizes of adhesives, and sealant or caulking compounds (in
units of product, less packaging, which do not weigh more than 1 pound and do not consist of more
than 16 fluid ounces) shall comply with statewide VOC standards and other requirements, including
prohibitions on use of certain toxic compounds, of California Code of Regulations, Title 17,
commencing with section 94507.
4.504.2.2 Paints and Coatings. Architectural paints and coatings shall comply with VOC limits in Table 1 of
the ARB Architectural Suggested Control Measure, as shown in Table 4.504.3, unless more stringent local limits
apply. The VOC content limit for coatings that do not meet the definitions for the specialty coatings categories
listed in Table 4.504.3 shall be determined by classifying the coating as a Flat, Nonflat or Nonflat-High Gloss
coating, based on its gloss, as defined in subsections 4.21, 4.36, and 4.37 of the 2007 California Air Resources
Board, Suggested Control Measure, and the corresponding Flat, Nonflat or Nonflat-High Gloss VOC limit in
Table 4.504.3 shall apply.
4.504.2.3 Aerosol Paints and Coatings. Aerosol paints and coatings shall meet the Product-weighted MIR
Limits for ROC in Section 94522(a)(2) and other requirements, including prohibitions on use of certain toxic
compounds and ozone depleting substances, in Sections 94522(e)(1) and (f)(1) of California Code of
Regulations, Title 17, commencing with Section 94520; and in areas under the jurisdiction of the Bay Area Air
Quality Management District additionally comply with the percent VOC by weight of product limits of Regulation
8, Rule 49.
4.504.2.4 Verification. Verification of compliance with this section shall be provided at the request of the
enforcing agency. Documentation may include, but is not limited to, the following:
1. Manufacturer's product specification.
2. Field verification of on-site product containers.
CHAPTER 7
INSTALLER & SPECIAL INSPECTOR QUALIFICATIONS
702 QUALIFICATIONS
702.1 INSTALLER TRAINING. HVAC system installers shall be trained and certified in the proper
installation of HVAC systems including ducts and equipment by a nationally or regionally recognized training or
certification program. Uncertified persons may perform HVAC installations when under the direct supervision and
responsibility of a person trained and certified to install HVAC systems or contractor licensed to install HVAC systems.
Examples of acceptable HVAC training and certification programs include but are not limited to the following:
1. State certified apprenticeship programs.
2. Public utility training programs.
3. Training programs sponsored by trade, labor or statewide energy consulting or verification organizations.
4. Programs sponsored by manufacturing organizations.
5. Other programs acceptable to the enforcing agency.
702.2 SPECIAL INSPECTION [HCD]. When required by the enforcing agency, the owner or the
responsible entity acting as the owner's agent shall employ one or more special inspectors to provide inspection or
other duties necessary to substantiate compliance with this code. Special inspectors shall demonstrate competence
to the satisfaction of the enforcing agency for the particular type of inspection or task to be performed. In addition to
other certifications or qualifications acceptable to the enforcing agency, the following certifications or education may be
considered by the enforcing agency when evaluating the qualifications of a special inspector:
1. Certification by a national or regional green building program or standard publisher.
2. Certification by a statewide energy consulting or verification organization, such as HERS raters, building
performance contractors, and home energy auditors.
3. Successful completion of a third party apprentice training program in the appropriate trade.
4. Other programs acceptable to the enforcing agency.
Notes:
1. Special inspectors shall be independent entities with no financial interest in the materials or the
project they are inspecting for compliance with this code.
2. HERS raters are special inspectors certified by the California Energy Commission (CEC) to rate
homes in California according to the Home Energy Rating System (HERS).
[BSC] When required by the enforcing agency, the owner or the responsible entity acting as the owner's agent shall
employ one or more special inspectors to provide inspection or other duties necessary to substantiate compliance with
this code. Special inspectors shall demonstrate competence to the satisfaction of the enforcing agency for the
particular type of inspection or task to be performed. In addition, the special inspector shall have a certification from a
recognized state, national or international association, as determined by the local agency. The area of certification
shall be closely related to the primary job function, as determined by the local agency.
Note: Special inspectors shall be independent entities with no financial interest in the materials or the
project they are inspecting for compliance with this code.
703 VERIFICATIONS
703.1 DOCUMENTATION. Documentation used to show compliance with this code shall include but is not
limited to, construction documents, plans, specifications, builder or installer certification, inspection reports, or other
methods acceptable to the enforcing agency which demonstrate substantial conformance. When specific
documentation or special inspection is necessary to verify compliance, that method of compliance will be specified in
the appropriate section or identified applicable checklist.
4.505 INTERIOR MOISTURE CONTROL
4.505.1 General. Buildings shall meet or exceed the provisions of the California Building Standards Code.
4.505.2 CONCRETE SLAB FOUNDATIONS. Concrete slab foundations required to have a vapor retarder by
California Building Code, Chapter 19, or concrete slab-on-ground floors required to have a vapor retarder by the
California Residential Code, Chapter 5, shall also comply with this section.
4.505.2.1 Capillary break. A capillary break shall be installed in compliance with at least one of the
following:
1. A 4-inch (101.6 mm) thick base of 1/2 inch (12.7mm) or larger clean aggregate shall be provided with
a vapor barrier in direct contact with concrete and a concrete mix design, which will address bleeding,
shrinkage, and curling, shall be used. For additional information, see American Concrete Institute,
ACI 302.2R-06.
2. Other equivalent methods approved by the enforcing agency.
3. A slab design specified by a licensed design professional.
4.505.3 MOISTURE CONTENT OF BUILDING MATERIALS. Building materials with visible signs of water damage
shall not be installed. Wall and floor framing shall not be enclosed when the framing members exceed 19 percent
moisture content. Moisture content shall be verified in compliance with the following:
1. Moisture content shall be determined with either a probe-type or contact-type moisture meter.Equivalent
moisture verification methods may be approved by the enforcing agency and shall satisfy requirements
found in Section 101.8 of this code.
2. Moisture readings shall be taken at a point 2 feet (610 mm) to 4 feet (1219 mm) from the grade stamped end
of each piece verified.
3. At least three random moisture readings shall be performed on wall and floor framing with documentation
acceptable to the enforcing agency provided at the time of approval to enclose the wall and floor framing.
Insulation products which are visibly wet or have a high moisture content shall be replaced or allowed to dry prior to
enclosure in wall or floor cavities. Wet-applied insulation products shall follow the manufacturers' drying
recommendations prior to enclosure.
4.506 INDOOR AIR QUALITY AND EXHAUST
4.506.1 Bathroom exhaust fans. Each bathroom shall be mechanically ventilated and shall comply with the
following:
1. Fans shall be ENERGY STAR compliant and be ducted to terminate outside the building.
2. Unless functioning as a component of a whole house ventilation system, fans must be controlled by a
humidity control.
a. Humidity controls shall be capable of adjustment between a relative humidity range less than or
equal to 50% to a maximum of 80%. A humidity control may utilize manual or automatic means of
adjustment.
b. A humidity control may be a separate component to the exhaust fan and is not required to be
integral (i.e., built-in)
Notes:
1. For the purposes of this section, a bathroom is a room which contains a bathtub, shower or
tub/shower combination.
2. Lighting integral to bathroom exhaust fans shall comply with the California Energy Code.
4.507 ENVIRONMENTAL COMFORT
4.507.2 HEATING AND AIR-CONDITIONING SYSTEM DESIGN. Heating and air conditioning systems shall be
sized, designed and have their equipment selected using the following methods:
1. The heat loss and heat gain is established according to ANSI/ACCA 2 Manual J - 2011 (Residential
Load Calculation), ASHRAE handbooks or other equivalent design software or methods.
2. Duct systems are sized according to ANSI/ACCA 1 Manual D - 2014 (Residential Duct Systems),
ASHRAE handbooks or other equivalent design software or methods.
3. Select heating and cooling equipment according to ANSI/ACCA 3 Manual S - 2014 (Residential
Equipment Selection), or other equivalent design software or methods.
Exception: Use of alternate design temperatures necessary to ensure the system functions are
acceptable.
TABLE 4.504.1 - ADHESIVE VOC LIMIT1,2
(Less Water and Less Exempt Compounds in Grams per Liter)
ARCHITECTURAL APPLICATIONS VOC LIMIT
INDOOR CARPET ADHESIVES 50
CARPET PAD ADHESIVES 50
OUTDOOR CARPET ADHESIVES 150
WOOD FLOORING ADHESIVES 100
RUBBER FLOOR ADHESIVES 60
SUBFLOOR ADHESIVES 50
CERAMIC TILE ADHESIVES 65
VCT & ASPHALT TILE ADHESIVES 50
DRYWALL & PANEL ADHESIVES 50
COVE BASE ADHESIVES 50
MULTIPURPOSE CONSTRUCTION ADHESIVE 70
STRUCTURAL GLAZING ADHESIVES 100
SINGLE-PLY ROOF MEMBRANE ADHESIVES 250
OTHER ADHESIVES NOT LISTED 50
SPECIALTY APPLICATIONS
PVC WELDING 510
CPVC WELDING 490
ABS WELDING 325
PLASTIC CEMENT WELDING 250
ADHESIVE PRIMER FOR PLASTIC 550
CONTACT ADHESIVE 80
SPECIAL PURPOSE CONTACT ADHESIVE 250
STRUCTURAL WOOD MEMBER ADHESIVE 140
TOP & TRIM ADHESIVE 250
SUBSTRATE SPECIFIC APPLICATIONS
METAL TO METAL 30
PLASTIC FOAMS 50
POROUS MATERIAL (EXCEPT WOOD)50
WOOD 30
FIBERGLASS 80
1. IF AN ADHESIVE IS USED TO BOND DISSIMILAR SUBSTRATES TOGETHER,
THE ADHESIVE WITH THE HIGHEST VOC CONTENT SHALL BE ALLOWED.
2. FOR ADDITIONAL INFORMATION REGARDING METHODS TO MEASURE
THE VOC CONTENT SPECIFIED IN THIS TABLE, SEE SOUTH COAST AIR
QUALITY MANAGEMENT DISTRICT RULE 1168.
TABLE 4.504.2 - SEALANT VOC LIMIT
(Less Water and Less Exempt Compounds in Grams per Liter)
SEALANTS VOC LIMIT
ARCHITECTURAL 250
MARINE DECK 760
NONMEMBRANE ROOF 300
ROADWAY 250
SINGLE-PLY ROOF MEMBRANE 450
OTHER 420
SEALANT PRIMERS
ARCHITECTURAL
NON-POROUS 250
POROUS 775
MODIFIED BITUMINOUS 500
MARINE DECK 760
OTHER 750
TABLE 4.504.5 - FORMALDEHYDE LIMITS1
MAXIMUM FORMALDEHYDE EMISSIONS IN PARTS PER MILLION
PRODUCT CURRENT LIMIT
HARDWOOD PLYWOOD VENEER CORE 0.05
HARDWOOD PLYWOOD COMPOSITE CORE 0.05
PARTICLE BOARD 0.09
MEDIUM DENSITY FIBERBOARD 0.11
THIN MEDIUM DENSITY FIBERBOARD2 0.13
1. VALUES IN THIS TABLE ARE DERIVED FROM THOSE SPECIFIED
BY THE CALIF. AIR RESOURCES BOARD, AIR TOXICS CONTROL
MEASURE FOR COMPOSITE WOOD AS TESTED IN ACCORDANCE
WITH ASTM E 1333. FOR ADDITIONAL INFORMATION, SEE CALIF.
CODE OF REGULATIONS, TITLE 17, SECTIONS 93120 THROUGH
93120.12.
2. THIN MEDIUM DENSITY FIBERBOARD HAS A MAXIMUM
THICKNESS OF 5/16" (8 MM).
TABLE 4.504.3 - VOC CONTENT LIMITS FOR
ARCHITECTURAL COATINGS2,3
GRAMS OF VOC PER LITER OF COATING, LESS WATER & LESS EXEMPT
COMPOUNDS
COATING CATEGORY VOC LIMIT
FLAT COATINGS 50
NON-FLAT COATINGS 100
NONFLAT-HIGH GLOSS COATINGS 150
SPECIALTY COATINGS
ALUMINUM ROOF COATINGS 400
BASEMENT SPECIALTY COATINGS 400
BITUMINOUS ROOF COATINGS 50
BITUMINOUS ROOF PRIMERS 350
BOND BREAKERS 350
CONCRETE CURING COMPOUNDS 350
CONCRETE/MASONRY SEALERS 100
DRIVEWAY SEALERS 50
DRY FOG COATINGS 150
FAUX FINISHING COATINGS 350
FIRE RESISTIVE COATINGS 350
FLOOR COATINGS 100
FORM-RELEASE COMPOUNDS 250
GRAPHIC ARTS COATINGS (SIGN PAINTS)500
HIGH TEMPERATURE COATINGS 420
INDUSTRIAL MAINTENANCE COATINGS 250
LOW SOLIDS COATINGS1 120
MAGNESITE CEMENT COATINGS 450
MASTIC TEXTURE COATINGS 100
METALLIC PIGMENTED COATINGS 500
MULTICOLOR COATINGS 250
PRETREATMENT WASH PRIMERS 420
PRIMERS, SEALERS, & UNDERCOATERS 100
REACTIVE PENETRATING SEALERS 350
RECYCLED COATINGS 250
ROOF COATINGS 50
RUST PREVENTATIVE COATINGS 250
SHELLACS
CLEAR 730
OPAQUE 550
SPECIALTY PRIMERS, SEALERS &
UNDERCOATERS 100
STAINS 250
STONE CONSOLIDANTS 450
SWIMMING POOL COATINGS 340
TRAFFIC MARKING COATINGS 100
TUB & TILE REFINISH COATINGS 420
WATERPROOFING MEMBRANES 250
WOOD COATINGS 275
WOOD PRESERVATIVES 350
ZINC-RICH PRIMERS 340
1. GRAMS OF VOC PER LITER OF COATING, INCLUDING WATER &
EXEMPT COMPOUNDS
2. THE SPECIFIED LIMITS REMAIN IN EFFECT UNLESS REVISED LIMITS
ARE LISTED IN SUBSEQUENT COLUMNS IN THE TABLE.
3. VALUES IN THIS TABLE ARE DERIVED FROM THOSE SPECIFIED BY
THE CALIFORNIA AIR RESOURCES BOARD, ARCHITECTURAL COATINGS
SUGGESTED CONTROL MEASURE, FEB. 1, 2008. MORE INFORMATION IS
AVAILABLE FROM THE AIR RESOURCES BOARD.
DIVISION 4.5 ENVIRONMENTAL QUALITY (continued)
4.504.3 CARPET SYSTEMS. All carpet installed in the building interior shall meet the requirements of the California
Department of Public Health, "Standard Method for the Testing and Evaluation of Volatile Organic Chemical Emissions
from Indoor Sources Using Environmental Chambers," Version 1.2, January 2017 (Emission testing method for
California Specification 01350)
See California Department of Public Health's website for certification programs and testing labs.
https://www.cdph.ca.gov/Programs/CCDPHP/DEODC/EHLB/IAQ/Pages/VOC.aspx.
4.504.3.1 Carpet cushion. All carpet cushion installed in the building interior shall meet the requirements of the
California Department of Public Health, "Standard Method for the Testing and Evaluation of Volatile Organic
Chemical Emissions from Indoor Sources Using Environmental Chambers," Version 1.2, January 2017
(Emission testing method for California Specification 01350)
See California Department of Public Health's website for certification programs and testing labs.
https://www.cdph.ca.gov/Programs/CCDPHP/DEODC/EHLB/IAQ/Pages/VOC.aspx.
4.504.3.2 Carpet adhesive. All carpet adhesive shall meet the requirements of Table 4.504.1.
4.504.4 RESILIENT FLOORING SYSTEMS. Where resilient flooring is installed , at least 80% of floor area receiving
resilient flooring shall meet the requirements of the California Department of Public Health, "Standard Method for the
Testing and Evaluation of Volatile Organic Chemical Emissions from Indoor Sources Using Environmental Chambers,"
Version 1.2, January 2017 (Emission testing method for California Specification 01350)
See California Department of Public Health's website for certification programs and testing labs.
hhtps://www.cdph.ca.gov/Programs/CCDPHP/DEODC/EHLB/IAQ/Pages/VOC.aspx.
4.504.5 COMPOSITE WOOD PRODUCTS. Hardwood plywood, particleboard and medium density fiberboard
composite wood products used on the interior or exterior of the buildings shall meet the requirements for
formaldehyde as specified in ARB's Air Toxics Control Measure for Composite Wood (17 CCR 93120 et seq.),
by or before the dates specified in those sections, as shown in Table 4.504.5
4.504.5.1 Documentation. Verification of compliance with this section shall be provided as requested
by the enforcing agency. Documentation shall include at least one of the following:
1. Product certifications and specifications.
2. Chain of custody certifications.
3. Product labeled and invoiced as meeting the Composite Wood Products regulation (see
CCR, Title 17, Section 93120, et seq.).
4. Exterior grade products marked as meeting the PS-1 or PS-2 standards of the Engineered
Wood Association, the Australian AS/NZS 2269, European 636 3S standards, and Canadian CSA
0121, CSA 0151, CSA 0153 and CSA 0325 standards.
5. Other methods acceptable to the enforcing agency.
DISCLAIMER:THIS DOCUMENT IS PROVIDED AND INTENDED TO BE USED AS A MEANS TO INDICATE AREAS OF COMPLIANCE WITH THE CALIFORNIA GREEN BUILDING STANDARDS (CALGREEN) CODE. DUE TO THE VARIABLES BETWEEN BUILDING DEPARTMENT JURISDICTIONS, THIS CHECKLIST IS TO BE USED ON AN INDIVIDUAL PROJECT BASIS AND MAY BE MODIFIED BY THE END USER TO MEET THOSE INDIVIDUAL NEEDS. THE END USER ASSUMES ALL RESPONSIBILITY ASSOCIATED WITH THE USE OF THIS DOCUMENT, INCLUDING VERIFICATION WITH THE FULL CODE.
Y N/AYN/AYN/AYN/A RESPON.
PARTY
RESPON.
PARTY
RESPON.
PARTY
RESPON.
PARTY
2022 CALIFORNIA GREEN BUILDING STANDARDS CODE
RESIDENTIAL MANDATORY MEASURES, SHEET 2 (January 2023)Y = YES
N/A =NOT APPLICABLE
RESPON. PARTY =RESPONSIBLE PARTY (ie: ARCHITECT, ENGINEER,
OWNER, CONTRACTOR, INSPECTOR ETC.)
D E S I G N
2024 FEBRUARY 19
DETACHED ADU
DATEISSUED FOR
I S S U E S
2710 LAIRD AVENUE
SANTA ANA, CALIFORNIA 92706
DAVID LE RESIDENCE
A-23-002-008
PROPOSED
HOUSE EXTENSION
+
PLAN CHECK SUBMITTAL 10.25.2023
2ND PLAN CHECK SUBMITTAL 01.05.2024
BUILDING SAFETY SUBMITTAL 01.25.2024
UPDATE PLAN SET FOR PRESCREEN 02.19.2024
2209 W. LARAMORE LANE
SANTA ANA, CALIFORNIA 92706
UPDATE PLAN SET 03.31.2024
A-04
CALIFORNIA
GREEN BUILDING
STANDARD
(SHEET - 2)
2710 N Laird St & 2209 W
Laramore Ln10/7/2024
ADU - TITLE
24
T24-1
RE
S
T
R
I
C
T
I
V
E
N
O
T
I
C
E
DA
T
E
RE
V
I
S
I
O
N
S
SHEET
SHEET DESCRIPTION
STAMP
NO
:
7/24/24
DE
T
A
C
H
E
D
A
D
U
DATE:
22
0
9
W
.
L
A
R
A
M
O
R
E
L
A
N
E
SA
N
T
A
A
N
A
,
C
A
9
2
7
0
6
TH
E
S
E
D
E
S
I
G
N
S
,
D
R
A
W
I
N
G
S
,
A
N
D
SP
E
C
I
F
I
C
A
T
I
O
N
S
A
R
E
E
X
C
L
U
S
I
V
E
T
O
GE
T
S
T
R
U
C
T
U
R
A
L
T
H
E
S
E
D
R
A
W
I
N
G
S
CA
N
N
O
T
B
E
C
O
P
I
E
D
,
T
R
A
N
S
F
E
R
R
E
D
,
O
R
RE
P
R
O
D
U
C
E
D
N
O
R
C
A
N
A
N
Y
O
T
H
E
R
ST
R
U
C
T
U
R
E
S
B
E
B
U
I
L
T
F
R
O
M
T
H
E
M
WI
T
H
O
U
T
W
R
I
T
T
E
N
C
O
N
S
E
N
T
RE
V
I
S
I
O
N
S
30
0
0
E
.
B
I
R
C
H
S
T
R
E
E
T
SU
I
T
E
2
0
3
BR
E
A
,
C
A
9
2
8
2
1
TE
L
:
(
9
0
9
)
5
6
9
-
1
8
8
6
in
f
o
@
G
e
t
S
t
r
u
c
t
u
r
a
l
.
c
o
m
JOB: R23-0943
PHONG TR UONG
STATE OF CALIFORNIA
REGISTERED PROFESSIONAL ENGINEER
NO. C70784
EXP. 06/30/2025
CIV IL
2710 N Laird St & 2209 W
Laramore Ln10/7/2024
ADU - TITLE
24 (CONT.)
T24-2
RE
S
T
R
I
C
T
I
V
E
N
O
T
I
C
E
DA
T
E
RE
V
I
S
I
O
N
S
SHEET
SHEET DESCRIPTION
STAMP
NO
:
7/24/24
DE
T
A
C
H
E
D
A
D
U
DATE:
22
0
9
W
.
L
A
R
A
M
O
R
E
L
A
N
E
SA
N
T
A
A
N
A
,
C
A
9
2
7
0
6
TH
E
S
E
D
E
S
I
G
N
S
,
D
R
A
W
I
N
G
S
,
A
N
D
SP
E
C
I
F
I
C
A
T
I
O
N
S
A
R
E
E
X
C
L
U
S
I
V
E
T
O
GE
T
S
T
R
U
C
T
U
R
A
L
T
H
E
S
E
D
R
A
W
I
N
G
S
CA
N
N
O
T
B
E
C
O
P
I
E
D
,
T
R
A
N
S
F
E
R
R
E
D
,
O
R
RE
P
R
O
D
U
C
E
D
N
O
R
C
A
N
A
N
Y
O
T
H
E
R
ST
R
U
C
T
U
R
E
S
B
E
B
U
I
L
T
F
R
O
M
T
H
E
M
WI
T
H
O
U
T
W
R
I
T
T
E
N
C
O
N
S
E
N
T
RE
V
I
S
I
O
N
S
30
0
0
E
.
B
I
R
C
H
S
T
R
E
E
T
SU
I
T
E
2
0
3
BR
E
A
,
C
A
9
2
8
2
1
TE
L
:
(
9
0
9
)
5
6
9
-
1
8
8
6
in
f
o
@
G
e
t
S
t
r
u
c
t
u
r
a
l
.
c
o
m
JOB: R23-0943
PHONG TR UONG
STATE OF CALIFORNIA
REGISTERED PROFESSIONAL ENGINEER
NO. C70784
EXP. 06/30/2025
CIV IL
2710 N Laird St & 2209 W
Laramore Ln10/7/2024
MAIN - TITLE
24
T24-3
RE
S
T
R
I
C
T
I
V
E
N
O
T
I
C
E
DA
T
E
RE
V
I
S
I
O
N
S
SHEET
SHEET DESCRIPTION
STAMP
NO
:
9/21/23
LE
A
D
D
I
T
I
O
N
DATE:
27
1
0
L
A
I
R
D
A
V
E
N
U
E
SA
N
T
A
A
N
A
,
C
A
9
2
7
0
6
TH
E
S
E
D
E
S
I
G
N
S
,
D
R
A
W
I
N
G
S
,
A
N
D
SP
E
C
I
F
I
C
A
T
I
O
N
S
A
R
E
E
X
C
L
U
S
I
V
E
T
O
GE
T
S
T
R
U
C
T
U
R
A
L
T
H
E
S
E
D
R
A
W
I
N
G
S
CA
N
N
O
T
B
E
C
O
P
I
E
D
,
T
R
A
N
S
F
E
R
R
E
D
,
O
R
RE
P
R
O
D
U
C
E
D
N
O
R
C
A
N
A
N
Y
O
T
H
E
R
ST
R
U
C
T
U
R
E
S
B
E
B
U
I
L
T
F
R
O
M
T
H
E
M
WI
T
H
O
U
T
W
R
I
T
T
E
N
C
O
N
S
E
N
T
RE
V
I
S
I
O
N
S
30
0
0
E
.
B
I
R
C
H
S
T
R
E
E
T
SU
I
T
E
2
0
3
BR
E
A
,
C
A
9
2
8
2
1
TE
L
:
(
9
0
9
)
5
6
9
-
1
8
8
6
in
f
o
@
G
e
t
S
t
r
u
c
t
u
r
a
l
.
c
o
m
JOB: R23-0943
PHONG TR UONG
STATE OF CALIFORNIA
REGISTERED PROFESSIONAL ENGINEER
NO. C70784
EXP. 06/30/2025
CIV IL
2710 N Laird St & 2209 W
Laramore Ln10/7/2024
MAIN - TITLE
24 (CONT.) &
MANDATORY
T24-4
RE
S
T
R
I
C
T
I
V
E
N
O
T
I
C
E
DA
T
E
RE
V
I
S
I
O
N
S
SHEET
SHEET DESCRIPTION
STAMP
NO
:
9/21/23
LE
A
D
D
I
T
I
O
N
DATE:
27
1
0
L
A
I
R
D
A
V
E
N
U
E
SA
N
T
A
A
N
A
,
C
A
9
2
7
0
6
TH
E
S
E
D
E
S
I
G
N
S
,
D
R
A
W
I
N
G
S
,
A
N
D
SP
E
C
I
F
I
C
A
T
I
O
N
S
A
R
E
E
X
C
L
U
S
I
V
E
T
O
GE
T
S
T
R
U
C
T
U
R
A
L
T
H
E
S
E
D
R
A
W
I
N
G
S
CA
N
N
O
T
B
E
C
O
P
I
E
D
,
T
R
A
N
S
F
E
R
R
E
D
,
O
R
RE
P
R
O
D
U
C
E
D
N
O
R
C
A
N
A
N
Y
O
T
H
E
R
ST
R
U
C
T
U
R
E
S
B
E
B
U
I
L
T
F
R
O
M
T
H
E
M
WI
T
H
O
U
T
W
R
I
T
T
E
N
C
O
N
S
E
N
T
RE
V
I
S
I
O
N
S
30
0
0
E
.
B
I
R
C
H
S
T
R
E
E
T
SU
I
T
E
2
0
3
BR
E
A
,
C
A
9
2
8
2
1
TE
L
:
(
9
0
9
)
5
6
9
-
1
8
8
6
in
f
o
@
G
e
t
S
t
r
u
c
t
u
r
a
l
.
c
o
m
JOB: R23-0943
PHONG TR UONG
STATE OF CALIFORNIA
REGISTERED PROFESSIONAL ENGINEER
NO. C70784
EXP. 06/30/2025
CIV IL
2710 N Laird St & 2209 W
Laramore Ln10/7/2024
2710 N Laird St & 2209 W
Laramore Ln10/7/2024
2710 N Laird St & 2209 W
Laramore Ln10/7/2024
D E S I G N
2024 JANUARY 25
DETACHED ADU
DATEISSUED FOR
I S S U E S
2710 LAIRD AVENUE
SANTA ANA, CALIFORNIA 92706
DAVID LE RESIDENCE
A-23-002-008
PROPOSED
HOUSE EXTENSION
+
PLAN CHECK SUBMITTAL 10.25.2023
2ND PLAN CHECK SUBMITTAL 01.05.2024
BUILDING SAFETY SUBMITTAL 01.25.2024
A-40
1/4" = 1'-0"
PROPOSED
FINISH FLOOR ELEVATION
2HOUSE EXTENSION DRAINAGE PLAN
1ADU SITE DRAINAGE PLAN
EXISTING
1-STORY HOUSE
F.F.E. = 0"
(DATUM)
F.F.E. = + 2"
PROPOSED
1-STORY ADU
SITE DRAINAGE PLAN
2710 N Laird St & 2209 W
Laramore Ln10/7/2024
D E S I G N
2024 JULY 29
DETACHED ADU
DATEISSUED FOR
I S S U E S
2710 LAIRD AVENUE
SANTA ANA, CALIFORNIA 92706
DAVID LE RESIDENCE
A-23-002-008
PROPOSED
HOUSE EXTENSION
+
PLAN CHECK SUBMITTAL 10.25.2023
2ND PLAN CHECK SUBMITTAL 01.05.2024
BUILDING SAFETY SUBMITTAL 01.25.2024
UPDATE PLAN SET FOR PRESCREEN 02.19.2024
2209 W. LARAMORE LANE
SANTA ANA, CALIFORNIA 92706
UPDATE PLAN SET 03.31.2024
BUILDING SAFETY RESUBMITTAL 07.29.2024
10111914-95
BUILDING SAFETY RESUBMITTAL 08.20.2024
A-14
1/4" = 1'-0"
ELECTRICAL PLAN
bedroom bedroom
dining room
bath 2
bath 1
kitchen
living room
1ADU ELECTRICAL PLAN
2 HOUSE EXTENSION ELECTRICAL PLAN
Smoke alarm & Carbon
Monoxide alarm in
hallway
SD
SD
SD
SD
2710 N Laird St & 2209 W
Laramore Ln10/7/2024
D E S I G N
2024 JULY 29
DETACHED ADU
DATEISSUED FOR
I S S U E S
2710 LAIRD AVENUE
SANTA ANA, CALIFORNIA 92706
DAVID LE RESIDENCE
A-23-002-008
PROPOSED
HOUSE EXTENSION
+
PLAN CHECK SUBMITTAL 10.25.2023
2ND PLAN CHECK SUBMITTAL 01.05.2024
BUILDING SAFETY SUBMITTAL 01.25.2024
UPDATE PLAN SET FOR PRESCREEN 02.19.2024
2209 W. LARAMORE LANE
SANTA ANA, CALIFORNIA 92706
UPDATE PLAN SET 03.31.2024
BUILDING SAFETY RESUBMITTAL 07.29.2024
10111914-95
A-15
1/4" = 1'-0"
ELECTRICAL
COMPLY NOTES
ADDED SHEETS 02.19.2024
CALIFORNIA ENERGY
COMPLY NOTES
The following information are required: Energy Code Section 150(a) through 150(v)
(n) Water heating system.
1. Systems using gas or propane water heaters to serve individual dwelling units shall designate a space at least
2.5 feet by 2.5 feet wide and 7 feet tall suitable for the future installation of a heat pump water heater
A. If the designated space is within 3 feet from the water heater:
i. A dedicated 125 volt, 20 amp electrical receptacle that is connected to the electric panel with a 120/240 volt 3
conductor, 10 AWG copper branch circuit, within 3 feet from the water heater.
ii. Isolate both ends of the unused conductor.
iii. A reserved single pole circuit breaker space in the electrical panel adjacent to the circuit breaker
iv. A condensate drain that allows natural draining of the water heater.
B. If the designated space is more than 3 feet from the water heater: see additional Code requirements.
(s) Energy Storage Systems (ESS) ready.
All single-family residences that include one or two dwelling units shall meet the following:
1. At least one of the following shall be provided:
A. ESS ready interconnection equipment [auto transfer switch and panel] with a minimum backed-up capacity of 60
amps and a minimum of four ESS-supplied branch circuits, or
B. A dedicated, minimum 1â raceway from the main service to a subpanel that supplies the branch circuits in
Section 150.0(s)(2).
2. A minimum of four branch circuits shall be supplied by the ESS: the refrigerator, one lighting circuit shall be
located near the primary egress, and at least one circuit shall supply a sleeping room receptacle outlet.
3. The main panelboard shall have a minimum busbar rating of 225 amperes with space to install future isolation
equipment/transfer switch within 3 feet.
(t) Heat pump space heater (Furnace) ready.
Systems using gas or propane furnace to serve individual dwelling units shall include the following:
1. A dedicated 240 volt, minimum 30A branch circuit wiring shall be installed within 3 feet from the furnace for a
future heat pump space heater installation.
(u) Electric cooktop ready.
Systems using gas or propane cooktop to serve individual dwelling units shall include the following:
1. A dedicated 240 volt, minimum 50A branch circuit wiring shall be installed within 3 feet from the cooktop for a
future electric cooktop installation.
(v) Electric clothes dryer ready.
Clothes dryer locations with gas or propane plumbing to serve individual dwelling units shall include the following:
1. A dedicated 240 volt, minimum 30A branch circuit wiring shall be installed within 3 feet from the clothes dryer
location for a future electric clothes dryer installation.
CALIFORNIA ENERGY CODE - SECTION 150.0
MANDATORY FEATURES AND DEVICES
2710 N Laird St & 2209 W
Laramore Ln10/7/2024
D E S I G N
2024 FEBRUARY 19
DETACHED ADU
DATEISSUED FOR
I S S U E S
2710 LAIRD AVENUE
SANTA ANA, CALIFORNIA 92706
DAVID LE RESIDENCE
A-23-002-008
PROPOSED
HOUSE EXTENSION
+
PLAN CHECK SUBMITTAL 10.25.2023
2ND PLAN CHECK SUBMITTAL 01.05.2024
BUILDING SAFETY SUBMITTAL 01.25.2024
UPDATE PLAN SET FOR PRESCREEN 02.19.2024
2209 W. LARAMORE LANE
SANTA ANA, CALIFORNIA 92706
UPDATE PLAN SET 03.31.2024
A-41
1/4" = 1'-0"
PROPOSED
LANDSCAPE PLAN
2HOUSE EXTENSION LANDSCAPE PLAN
1ADU LANDSCAPE PLAN
EXISTING
1-STORY HOUSE
PROPOSED
1-STORY ADU
2710 N Laird St & 2209 W
Laramore Ln10/7/2024
Job#R23-0943 Detached ADU
(909) 569-1886 | info@getstructural.com
3000 E. BIRCH STREET, SUITE 201, BREA, CA 92821
2209 W. Laramore Lane
Santa Ana, CA 92706
7/24/2024
SINGLE FAMILY RESIDENCE ADDITION at:
BUILDING ENERGY ANALYSIS REPORT
2710 N Laird St & 2209 W
Laramore Ln10/7/2024
CERTIFICATE OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE METHOD CF1R-PRF-01-E
Project Name:Detached ADU Calculation Date/Time:2024-07-24T12:25:05-07:00 (Page 1 of 10)
Calculation Description:Title 24 Analysis Input File Name:2209 W. Laramore Lane - T24.ribd22x
Registration Number:Registration Date/Time: HERS Provider:
CA Building Energy Efficiency Standards - 2022 Residential Compliance Report Version: 2022.0.000
Schema Version: rev 20220901
Report Generated: 2024-07-24 12:25:50
GENERAL INFORMATION
01 Project Name Detached ADU
02 Run Title Title 24 Analysis
03 Project Location 2209 W. Laramore Lane
04 City Santa Ana 05 Standards Version 2022
06 Zip code 92706 07 Software Version EnergyPro 9.2
08 Climate Zone 8 09 Front Orientation (deg/ Cardinal)90
10 Building Type Single family 11 Number of Dwelling Units 1
12 Project Scope Newly Constructed 13 Number of Bedrooms 2
14 Addition Cond. Floor Area (ft2)0 15 Number of Stories 1
16 Existing Cond. Floor Area (ft2)n/a 17 Fenestration Average U-factor 0.3
18 Total Cond. Floor Area (ft2)748 19 Glazing Percentage (%)15.24%
20 ADU Bedroom Count n/a 21 ADU Conditioned Floor Area n/a
22 Fuel Type Natural gas 23 No Dwelling Unit:No
COMPLIANCE RESULTS
01 Building Complies with Computer Performance
02 This building incorporates features that require field testing and/or verification by a certified HERS rater under the supervision of a CEC-approved HERS provider.
03 This building incorporates one or more Special Features shown below
424-P010139338A-000-000-0000000-0000 07/24/2024 12:26 CHEERS
NOTICE: This document has been generated by California Home Energy Efficiency Rating Services (CHEERS) using information uploaded by third parties not affiliated with or related to CHEERS. Therefore, CHEERS is not responsible for,
and cannot guarantee, the accuracy or completeness of the information contained in this document.
2710 N Laird St & 2209 W
Laramore Ln10/7/2024
CERTIFICATE OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE METHOD CF1R-PRF-01-E
Project Name:Detached ADU Calculation Date/Time:2024-07-24T12:25:05-07:00 (Page 2 of 10)
Calculation Description:Title 24 Analysis Input File Name:2209 W. Laramore Lane - T24.ribd22x
Registration Number:Registration Date/Time: HERS Provider:
CA Building Energy Efficiency Standards - 2022 Residential Compliance Report Version: 2022.0.000
Schema Version: rev 20220901
Report Generated: 2024-07-24 12:25:50
ENERGY DESIGN RATINGS
Energy Design Ratings Compliance Margins
Source Energy
(EDR1)
Efficiency1 EDR
(EDR2efficiency)
Total2 EDR
(EDR2total)
Source Energy
(EDR1)
Efficiency1 EDR
(EDR2efficiency)
Total2 EDR
(EDR2total)
Standard Design 37.5 38.9 28
Proposed Design 36.2 37.9 27.4 1.3 1 0.6
RESULT3: PASS
1Efficiency EDR includes improvements like a better building envelope and more efficient equipment
2Total EDR includes efficiency and demand response measures such as photovoltaic (PV) system and batteries
3Building complies when source energy, efficiency and total compliance margins are greater than or equal to zero and unmet load hour limits are not exceeded
•Standard Design PV Capacity: 2.07 kWdc
•PV System resized to 2.07 kWdc (a factor of 2.072) to achieve 'Standard Design PV' PV scaling
424-P010139338A-000-000-0000000-0000 07/24/2024 12:26 CHEERS
NOTICE: This document has been generated by California Home Energy Efficiency Rating Services (CHEERS) using information uploaded by third parties not affiliated with or related to CHEERS. Therefore, CHEERS is not responsible for,
and cannot guarantee, the accuracy or completeness of the information contained in this document.
2710 N Laird St & 2209 W
Laramore Ln10/7/2024
CERTIFICATE OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE METHOD CF1R-PRF-01-E
Project Name:Detached ADU Calculation Date/Time:2024-07-24T12:25:05-07:00 (Page 3 of 10)
Calculation Description:Title 24 Analysis Input File Name:2209 W. Laramore Lane - T24.ribd22x
Registration Number:Registration Date/Time: HERS Provider:
CA Building Energy Efficiency Standards - 2022 Residential Compliance Report Version: 2022.0.000
Schema Version: rev 20220901
Report Generated: 2024-07-24 12:25:50
ENERGY USE SUMMARY
Energy Use Standard Design Source
Energy (EDR1) (kBtu/ft2 -yr)
Standard Design TDV Energy
(EDR2) (kTDV/ft2 -yr)
Proposed Design Source
Energy (EDR1) (kBtu/ft2 -yr)
Proposed Design TDV Energy
(EDR2) (kTDV/ft2 -yr)
Compliance
Margin (EDR1)
Compliance
Margin (EDR2)
Space Heating 0.07 0.4 0.94 6.91 -0.87 -6.51
Space Cooling 1.4 32.2 1.16 33.79 0.24 -1.59
IAQ Ventilation 0.46 4.87 0.46 4.87 0 0
Water Heating 2.36 24.92 1.27 15.11 1.09 9.81
Self
Utilization/Flexibility
Credit
0 0
Efficiency Compliance
Total 4.29 62.39 3.83 60.68 0.46 1.71
Photovoltaics -3.04 -91.53 -3.04 -91.1
Battery 0 0
Flexibility
Indoor Lighting 0.96 9.03 0.96 9.03
Appl. & Cooking 6.98 45.15 6.93 44.73
Plug Loads 6.07 61.85 6.07 61.85
Outdoor Lighting 0.21 1.82 0.21 1.82
TOTAL COMPLIANCE 15.47 88.71 14.96 87.01
424-P010139338A-000-000-0000000-0000 07/24/2024 12:26 CHEERS
NOTICE: This document has been generated by California Home Energy Efficiency Rating Services (CHEERS) using information uploaded by third parties not affiliated with or related to CHEERS. Therefore, CHEERS is not responsible for,
and cannot guarantee, the accuracy or completeness of the information contained in this document.
2710 N Laird St & 2209 W
Laramore Ln10/7/2024
CERTIFICATE OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE METHOD CF1R-PRF-01-E
Project Name:Detached ADU Calculation Date/Time:2024-07-24T12:25:05-07:00 (Page 4 of 10)
Calculation Description:Title 24 Analysis Input File Name:2209 W. Laramore Lane - T24.ribd22x
Registration Number:Registration Date/Time: HERS Provider:
CA Building Energy Efficiency Standards - 2022 Residential Compliance Report Version: 2022.0.000
Schema Version: rev 20220901
Report Generated: 2024-07-24 12:25:50
ENERGY USE INTENSITY
Standard Design (kBtu/ft2 - yr )Proposed Design (kBtu/ft2 - yr )Compliance Margin (kBtu/ft2 - yr )Margin Percentage
Gross EUI1 24.1 23.11 0.99 4.11
Net EUI2 8.65 7.66 0.99 11.45
Notes
1. Gross EUI is Energy Use Total (not including PV) / Total Building Area.
2. Net EUI is Energy Use Total (including PV) / Total Building Area.
REQUIRED PV SYSTEMS
01 02 03 04 05 06 07 08 09 10 11 12
DC System Size
(kWdc)Exception Module Type Array Type Power Electronics CFI Azimuth
(deg)
Tilt
Input
Array Angle
(deg)
Tilt: (x in
12)
Inverter Eff.
(%)
Annual
Solar Access
(%)
2.07 NA Standard (14-17%)Fixed none true 150-270 n/a n/a <=7:12 96 98
REQUIRED SPECIAL FEATURES
The following are features that must be installed as condition for meeting the modeled energy performance for this computer analysis.
•Insulation below roof deck
•Northwest Energy Efficiency Alliance (NEEA) rated heat pump water heater; specific brand/model, or equivalent, must be installed
HERS FEATURE SUMMARY
The following is a summary of the features that must be field-verified by a certified HERS Rater as a condition for meeting the modeled energy performance for this computer analysis. Additional
detail is provided in the building tables below. Registered CF2Rs and CF3Rs are required to be completed in the HERS Registry
•Quality insulation installation (QII)
•Indoor air quality ventilation
•Kitchen range hood
•Verified heat pump rated heating capacity
424-P010139338A-000-000-0000000-0000 07/24/2024 12:26 CHEERS
NOTICE: This document has been generated by California Home Energy Efficiency Rating Services (CHEERS) using information uploaded by third parties not affiliated with or related to CHEERS. Therefore, CHEERS is not responsible for,
and cannot guarantee, the accuracy or completeness of the information contained in this document.
2710 N Laird St & 2209 W
Laramore Ln10/7/2024
CERTIFICATE OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE METHOD CF1R-PRF-01-E
Project Name:Detached ADU Calculation Date/Time:2024-07-24T12:25:05-07:00 (Page 5 of 10)
Calculation Description:Title 24 Analysis Input File Name:2209 W. Laramore Lane - T24.ribd22x
Registration Number:Registration Date/Time: HERS Provider:
CA Building Energy Efficiency Standards - 2022 Residential Compliance Report Version: 2022.0.000
Schema Version: rev 20220901
Report Generated: 2024-07-24 12:25:50
BUILDING - FEATURES INFORMATION
01 02 03 04 05 06 07
Project Name Conditioned Floor Area (ft2)Number of Dwelling
Units Number of Bedrooms Number of Zones Number of Ventilation
Cooling Systems
Number of Water
Heating Systems
Detached ADU 748 1 2 1 0 1
ZONE INFORMATION
01 02 03 04 05 06 07
Zone Name Zone Type HVAC System Name Zone Floor Area (ft2)Avg. Ceiling Height Water Heating System 1 Status
ADU Area Conditioned Mini Split1 748 8 DHW Sys 1 New
OPAQUE SURFACES
01 02 03 04 05 06 07 08
Name Zone Construction Azimuth Orientation Gross Area (ft2)Window and Door
Area (ft2)Tilt (deg)
North Wall ADU Area R-15 Wall 0 Right 182 0 90
South Wall ADU Area R-15 Wall 180 Left 182 36 90
East Wall ADU Area R-15 Wall 90 Front 292 74.84 90
West Wall ADU Area R-15 Wall 270 Back 292 54.31 90
Roof ADU Area R-30 + R-15 Roof Attic n/a n/a 748 n/a n/a
ATTIC
01 02 03 04 05 06 07 08
Name Construction Type Roof Rise (x in 12)Roof Reflectance Roof Emittance Radiant Barrier Cool Roof
Attic ADU Area Attic RoofADU Area Ventilated 5 0.1 0.85 No No
424-P010139338A-000-000-0000000-0000 07/24/2024 12:26 CHEERS
NOTICE: This document has been generated by California Home Energy Efficiency Rating Services (CHEERS) using information uploaded by third parties not affiliated with or related to CHEERS. Therefore, CHEERS is not responsible for,
and cannot guarantee, the accuracy or completeness of the information contained in this document.
2710 N Laird St & 2209 W
Laramore Ln10/7/2024
CERTIFICATE OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE METHOD CF1R-PRF-01-E
Project Name:Detached ADU Calculation Date/Time:2024-07-24T12:25:05-07:00 (Page 6 of 10)
Calculation Description:Title 24 Analysis Input File Name:2209 W. Laramore Lane - T24.ribd22x
Registration Number:Registration Date/Time: HERS Provider:
CA Building Energy Efficiency Standards - 2022 Residential Compliance Report Version: 2022.0.000
Schema Version: rev 20220901
Report Generated: 2024-07-24 12:25:50
FENESTRATION / GLAZING
01 02 03 04 05 06 07 08 09 10 11 12 13 14
Name Type Surface Orientation Azimuth Width
(ft)
Height
(ft)Mult.Area
(ft2)U-factor U-factor
Source SHGC SHGC Source Exterior Shading
W1-2046 Window South Wall Left 180 1 9 0.3 NFRC 0.23 NFRC Bug Screen
W1-2046 2 Window South Wall Left 180 1 9 0.3 NFRC 0.23 NFRC Bug Screen
W1-2046 3 Window South Wall Left 180 1 9 0.3 NFRC 0.23 NFRC Bug Screen
W1-2046 4 Window South Wall Left 180 1 9 0.3 NFRC 0.23 NFRC Bug Screen
W1-2046 5 Window East Wall Front 90 1 9 0.3 NFRC 0.23 NFRC Bug Screen
W2-4036 Window East Wall Front 90 1 14 0.3 NFRC 0.23 NFRC Bug Screen
W3-3016 Window East Wall Front 90 1 4.5 0.3 NFRC 0.23 NFRC Bug Screen
W2-4036 2 Window East Wall Front 90 1 14 0.3 NFRC 0.23 NFRC Bug Screen
W1-2046 6 Window West Wall Back 270 1 9 0.3 NFRC 0.23 NFRC Bug Screen
W1-2046 7 Window West Wall Back 270 1 9 0.3 NFRC 0.23 NFRC Bug Screen
W3-3016 2 Window West Wall Back 270 1 4.5 0.3 NFRC 0.23 NFRC Bug Screen
W2-4036 3 Window West Wall Back 270 1 14 0.3 NFRC 0.23 NFRC Bug Screen
OPAQUE DOORS
01 02 03 04
Name Side of Building Area (ft2)U-factor
D1-3068 East Wall 20 0.5
D3-2068 East Wall 13.34 0.5
D2-2868 West Wall 17.81 0.5
424-P010139338A-000-000-0000000-0000 07/24/2024 12:26 CHEERS
NOTICE: This document has been generated by California Home Energy Efficiency Rating Services (CHEERS) using information uploaded by third parties not affiliated with or related to CHEERS. Therefore, CHEERS is not responsible for,
and cannot guarantee, the accuracy or completeness of the information contained in this document.
2710 N Laird St & 2209 W
Laramore Ln10/7/2024
CERTIFICATE OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE METHOD CF1R-PRF-01-E
Project Name:Detached ADU Calculation Date/Time:2024-07-24T12:25:05-07:00 (Page 7 of 10)
Calculation Description:Title 24 Analysis Input File Name:2209 W. Laramore Lane - T24.ribd22x
Registration Number:Registration Date/Time: HERS Provider:
CA Building Energy Efficiency Standards - 2022 Residential Compliance Report Version: 2022.0.000
Schema Version: rev 20220901
Report Generated: 2024-07-24 12:25:50
SLAB FLOORS
01 02 03 04 05 06 07 08
Name Zone Area (ft2)Perimeter (ft)Edge Insul. R-value
and Depth
Edge Insul. R-value
and Depth Carpeted Fraction Heated
Slab-on-Grade ADU Area 748 108.33 none 0 80%No
OPAQUE SURFACE CONSTRUCTIONS
01 02 03 04 05 06 07 08
Construction Name Surface Type Construction Type Framing Total Cavity
R-value
Interior / Exterior
Continuous
R-value
U-factor Assembly Layers
R-15 Wall Exterior Walls Wood Framed Wall 2x4 @ 16 in. O. C.R-15 None / None 0.095
Inside Finish: Gypsum Board
Cavity / Frame: R-15 / 2x4
Exterior Finish: 3 Coat Stucco
Attic RoofADU Area Attic Roofs Wood Framed
Ceiling 2x6 @ 24 in. O. C.R-15 None / 0 0.066
Roofing: Light Roof (Asphalt Shingle)
Roof Deck: Wood
Siding/sheathing/decking
Cavity / Frame: R-15 / 2x6
R-30 + R-15 Roof Attic Ceilings (below
attic)
Wood Framed
Ceiling 2x8 @ 16 in. O. C.R-30 None / None 0.033
Over Ceiling Joists: R-11.2 insul.
Cavity / Frame: R-18.9 / 2x8
Inside Finish: Gypsum Board
BUILDING ENVELOPE - HERS VERIFICATION
01 02 03 04 05
Quality Insulation Installation (QII)High R-value Spray Foam Insulation Building Envelope Air Leakage CFM50 CFM50
Required Not Required N/A n/a n/a
424-P010139338A-000-000-0000000-0000 07/24/2024 12:26 CHEERS
NOTICE: This document has been generated by California Home Energy Efficiency Rating Services (CHEERS) using information uploaded by third parties not affiliated with or related to CHEERS. Therefore, CHEERS is not responsible for,
and cannot guarantee, the accuracy or completeness of the information contained in this document.
2710 N Laird St & 2209 W
Laramore Ln10/7/2024
CERTIFICATE OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE METHOD CF1R-PRF-01-E
Project Name:Detached ADU Calculation Date/Time:2024-07-24T12:25:05-07:00 (Page 8 of 10)
Calculation Description:Title 24 Analysis Input File Name:2209 W. Laramore Lane - T24.ribd22x
Registration Number:Registration Date/Time: HERS Provider:
CA Building Energy Efficiency Standards - 2022 Residential Compliance Report Version: 2022.0.000
Schema Version: rev 20220901
Report Generated: 2024-07-24 12:25:50
WATER HEATING SYSTEMS
01 02 03 04 05 06 07 08 09
Name System Type Distribution Type Water Heater Name Number of Units Solar Heating
System
Compact
Distribution HERS Verification Water Heater
Name (#)
DHW Sys 1 Domestic Hot
Water (DHW)Standard DHW Heater 1 1 n/a None n/a DHW Heater 1 (1)
WATER HEATERS - NEEA HEAT PUMP
01 02 03 04 05 06 07 08
Name # of Units Tank Vol. (gal)NEEA Heat Pump
Brand
NEEA Heat Pump
Model Tank Location Duct Inlet Air Source Duct Outlet Air Source
DHW Heater 1 1 50 A. O. Smith HPTS-50 2** (50 gal,
JA13)Outside ADU Area ADU Area
WATER HEATING - HERS VERIFICATION
01 02 03 04 05 06 07
Name Pipe Insulation Parallel Piping Compact Distribution Compact Distribution
Type Recirculation Control Shower Drain Water Heat
Recovery
DHW Sys 1 - 1/1 Not Required Not Required Not Required None Not Required Not Required
SPACE CONDITIONING SYSTEMS
01 02 03 04 05 06 07 08 09
Name System Type Heating Unit Name Heating Equipment
Count Cooling Unit Name Cooling Equipment
Count Fan Name Distribution Name Required
Thermostat Type
Mini Split1 Heat pump
heating cooling
Heat Pump System
1 1 Heat Pump System
1 1 n/a n/a Setback
424-P010139338A-000-000-0000000-0000 07/24/2024 12:26 CHEERS
NOTICE: This document has been generated by California Home Energy Efficiency Rating Services (CHEERS) using information uploaded by third parties not affiliated with or related to CHEERS. Therefore, CHEERS is not responsible for,
and cannot guarantee, the accuracy or completeness of the information contained in this document.
2710 N Laird St & 2209 W
Laramore Ln10/7/2024
CERTIFICATE OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE METHOD CF1R-PRF-01-E
Project Name:Detached ADU Calculation Date/Time:2024-07-24T12:25:05-07:00 (Page 9 of 10)
Calculation Description:Title 24 Analysis Input File Name:2209 W. Laramore Lane - T24.ribd22x
Registration Number:Registration Date/Time: HERS Provider:
CA Building Energy Efficiency Standards - 2022 Residential Compliance Report Version: 2022.0.000
Schema Version: rev 20220901
Report Generated: 2024-07-24 12:25:50
HVAC - HEAT PUMPS
01 02 03 04 05 06 07 08 09 10 11 12 13
Name System Type Number of
Units
Heating Cooling
Zonally
Controlled
Compressor
Type HERS VerificationHeating
Efficiency
Type
HSPF/HS
PF2/COP Cap 47 Cap 17
Cooling
Efficiency
Type
SEER/SE
ER2
EER/EER
2/CEER
Heat Pump
System 1
Ductless MiniSplit
HP 1 HSPF 8 24000 20000 EERSEER 14 11 Not Zonal Single
Speed
Heat Pump System
1-hers-htpump
HVAC HEAT PUMPS - HERS VERIFICATION
01 02 03 04 05 06 07 08 09
Name Verified Airflow Airflow Target Verified EER/EER2 Verified
SEER/SEER2
Verified Refrigerant
Charge
Verified
HSPF/HSPF2
Verified Heating
Cap 47
Verified Heating
Cap 17
Heat Pump System
1-hers-htpump Not Required 0 Not Required Not Required No No Yes Yes
INDOOR AIR QUALITY (IAQ) FANS
01 02 03 04 05 06 07 08 09
Dwelling Unit Airflow (CFM)Fan Efficacy
(W/CFM)IAQ Fan Type
Includes
Heat/Energy
Recovery?
IAQ Recovery
Effectiveness -
SRE/ASRE
Includes Fault
Indicator Display?HERS Verification Status
SFam IAQVentRpt 45 0.35 Exhaust No n/a / n/a No Yes
424-P010139338A-000-000-0000000-0000 07/24/2024 12:26 CHEERS
NOTICE: This document has been generated by California Home Energy Efficiency Rating Services (CHEERS) using information uploaded by third parties not affiliated with or related to CHEERS. Therefore, CHEERS is not responsible for,
and cannot guarantee, the accuracy or completeness of the information contained in this document.
2710 N Laird St & 2209 W
Laramore Ln10/7/2024
CERTIFICATE OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE METHOD CF1R-PRF-01-E
Project Name:Detached ADU Calculation Date/Time:2024-07-24T12:25:05-07:00 (Page 10 of 10)
Calculation Description:Title 24 Analysis Input File Name:2209 W. Laramore Lane - T24.ribd22x
Registration Number:Registration Date/Time: HERS Provider:
CA Building Energy Efficiency Standards - 2022 Residential Compliance Report Version: 2022.0.000
Schema Version: rev 20220901
Report Generated: 2024-07-24 12:25:50
DOCUMENTATION AUTHOR'S DECLARATION STATEMENT
1. I certify that this Certificate of Compliance documentation is accurate and complete.
Documentation Author Name:Documentation Author Signature:
Company:Signature Date:
Address:CEA/ HERS Certification Identification (If applicable):
City/State/Zip:Phone:
RESPONSIBLE PERSON'S DECLARATION STATEMENT
I certify the following under penalty of perjury, under the laws of the State of California:
1.I am eligible under Division 3 of the Business and Professions Code to accept responsibility for the building design identified on this Certificate of Compliance.
2.I certify that the energy features and performance specifications identified on this Certificate of Compliance conform to the requirements of Title 24, Part 1 and Part 6 of the California Code of Regulations.
3.The building design features or system design features identified on this Certificate of Compliance are consistent with the information provided on other applicable compliance documents, worksheets,
calculations, plans and specifications submitted to the enforcement agency for approval with this building permit application.
Responsible Designer Name:Responsible Designer Signature:
Company:Date Signed:
Address:License:
City/State/Zip:Phone:
Paul Truong
Get Structural 07/24/2024
3000 E Birch St
Brea, CA 92821 9095691886
Paul Truong
Get Structural 07/24/2024
3000 E Birch St
Brea, CA 92821 9095691886
424-P010139338A-000-000-0000000-0000 07/24/2024 12:26 CHEERS
NOTICE: This document has been generated by California Home Energy Efficiency Rating Services (CHEERS) using information uploaded by third parties not affiliated with or related to CHEERS. Therefore, CHEERS is not responsible for,
and cannot guarantee, the accuracy or completeness of the information contained in this document.
Digitally signed by California Home Energy Efficiency Rating Services (CHEERS). This digital signature is provided in order to secure the content of
this registered document, and in no way implies Registration Provider responsibility for the accuracy of the information.
2710 N Laird St & 2209 W
Laramore Ln10/7/2024
Job#R23- 0943 Le Addition & Detached ADU
Design Criteria:
1-Code: CALIFORNIA BLDG CODE 2022
2-Wind: 95 MPH, Exposure: C
3- SITE CLASS D - code default, SEISMIC DESIGN CATEGORY D
4-
ꞏ Douglas Fir Larch with Max 19% Moisture Content prior to installation of finish Materials.
ꞏ 4x Members use No.2 or better
ꞏ 6x, 8x members use No.1 or better
ꞏ Studs, plates and blocking stud grade or better
ꞏ 2x joists and rafters No.2 or better
ꞏ Mud sills pressure treated utility grade or betterꞏ
5-Ultimate strength concrete: 2500 PSI (min)
6-Soils Min. Bearing Pressure: 1500 psf per CBC 2022. CH.18. Per approval of Bldg Dept.
Soils and Geology:
Soils Report by: N/A
Notice: Use restrictions of these calculations.
The attached Calculations are valid only when bearing original signature hereon, photocopy is void.
Contractor/Client to verify existing dimensions/conditions prior to construction.
The use of these calculations is solely intended for the above mentioned project.
(909) 569-1886 | info@getstructural.com
3000 E. BIRCH STREET, SUITE 201, BREA, CA 92821
2209 W Laramore Lane
Santa Ana, CA 92706
8/1/2024
SINGLE FAMILY RESIDENCE REMODEL at:
STRUCTURAL CALCULATIONS FOR
2710 N Laird St & 2209 W
Laramore Ln10/7/2024
Design Loads
Component Weight (psf)
Roof Load
Comp Roofing 4.00
Plywood Sheathing -1/2" 1.50
Roof Framing 2.50
Miscellaneous (Lighting, Mechanical, etc.)2
Dead Load = 10.00 (psf)
Roof Live Load = 20.00 (psf)
Snow Load = 0.00 (psf)
aulted Roof Load
Comp Roofing 4.00
Plywood Sheathing -1/2" 1.50
Roof Framing 2.50
R-19 Batt Insulation 2.00
Gyp. Board 3.00
Miscellaneous (Lighting, Mechanical, etc.)2
Dead Load = 15.00 (psf)
Roof Live Load = 20.00 (psf)
Snow Load = 0.00 (psf)
Exterior Wood Frame Walls:
Stucco 7.00
Plywood Sheathing - 1/2" 1.50
2x Studs @ 16" o.c. 1.50
R-19 Batt Insulation 2.00
Gyp Board 3.00
Dead Load = 15.00 (psf)
Interior Wood Frame Walls:
2x Studs @16" O.C. 1.50
Miscellaneuous 2.50
Gyp Board x2 6.00
Dead Load = 10.00 (psf)
Ceiling Load:
R-19 Batt Insulation 2.00
Gyp. Board 3.00
Dead Load = 5.00 (psf)
Live Load = 10.00 (psf)
Interior Wood Floor Framing
Sheathing 4.00
Framing 4.00
R-19 Batt Insulation 2.00
Gyp Board 3.00
Miscellaneous (Lighting, Mechanical, etc.)2.00
Dead Load = 15.00 (psf)
Live Load = 40.00 (psf)
Deck Floor Framing
Sheathing 4.00
Framing 4.00
R-19 Batt Insulation 2.00
Gyp Board 3.00
Miscellaneous (Lighting, Mechanical, etc.)2.00
Dead Load = 15.00 (psf)
Live Load = 60.00 (psf)
Snow Load = 0.00 (psf)
2710 N Laird St & 2209 W
Laramore Ln10/7/2024
Hip(CA ROOF)
Attic
DF-L No. 2
4x8
Roof Dead Load QD =10 psf
Live Roof Load QLr =20 psf
Length Lproj =10.42 ft
Slope s =5 :12
Degrees θ =22.6
Height H =4.34 ft
Service Load =30.83 psf
Maximum Uniform Load =161 plf
Hip Length =11.29 ft
Maximum Moment =1200 lb-ft
Load Duraction Factor CD =1.25
Bending Stress fb =900 psi
Moment Capacity =2875 lb-ft OK
Max Shear =589 lbs HHRC
Shear Capacity =3806 lbs OK
Live Roof Load Deflection =0.064 in
Transient Deflection Limit L/180 =0.753 in OK
Total Load Deflection =0.098 in
Total Deflection Limit (D+L)/120 =1.129 in OK
Reactions
Higher End D =227 lbs
Lr =362 lbs
Lower End D =129 lbs
Lr =181 lbs
Q = Q + Q I
w .=L Q
2
L =L
COS
M =wcos 𝜃L
9 3
=wL
3
0.00652 w L
EI
0.00652 w L
EI
M = C F S
=2bd C
3
2710 N Laird St & 2209 W
Laramore Ln10/7/2024
Hip(MAIN ADU)
Attic
DF-L No. 2
4x10
Roof Dead Load QD =10 psf
Live Roof Load QLr =20 psf
Length Lproj =15.92 ft
Slope s =5 :12
Degrees θ =22.6
Height H =6.63 ft
Service Load =30.83 psf
Maximum Uniform Load =245 plf
Hip Length =17.25 ft
Maximum Moment =4231 lb-ft
Load Duraction Factor CD =1.25
Bending Stress fb =900 psi
Moment Capacity =4679 lb-ft OK
Max Shear =1363 lbs HHRC
Shear Capacity =4856 lbs OK
Live Roof Load Deflection =0.255 in
Transient Deflection Limit L/180 =1.150 in OK
Total Load Deflection =0.393 in
Total Deflection Limit (D+L)/120 =1.725 in OK
Reactions
Higher End D =518 lbs
Lr =845 lbs
Lower End D =289 lbs
Lr =422 lbs
Q = Q + Q I
w .=L Q
2
L =L
COS
M =wcos 𝜃L
9 3
=wL
3
0.00652 w L
EI
0.00652 w L
EI
M = C F S
=2bd C
3
2710 N Laird St & 2209 W
Laramore Ln10/7/2024
JOIST ANALYSIS
Name LOAD Span, ft Type Size Spacing, in QD QLr QL QS COMB. Moment, lb‐ft Moment
Stress, psi
Allowable
Bending Stress,
psi
DCR Shear, lbs Shear Stress,
psi
Allowable
Shear Stress,
psi
DCR Total Limit Transient Limit
RR1 Roof 11.25 DF-L No. 2 2x6 16 10 20 0 0 D+Lr 632.81 1004.13 1681.88 0.60 225.00 40.91 225.00 0.182 0.325 1.125 0.289 0.750
CJ Ceiling 15.17 DF‐L No. 2 2x6 16 5 0 10 0 D+L 575.09 912.55 1345.50 0.68 151.67 27.58 180.00 0.153 0.537 1.011 0.477 0.758
psf Delfection, in.
2710 N Laird St & 2209 W
Laramore Ln10/7/2024
Wood Beam
LIC# : KW-06014251, Build:20.23.12.07 GET STRUCTURAL ENGINEERING AND CONSULTING (c) ENERCALC INC 1983-2023
DESCRIPTION:1 - C.B.
Project File: 2710 Laird Ave Member Check.ec6
Project Title:
Engineer:
Project ID:
Project Descr:
CODE REFERENCES
Calculations per NDS 2018, IBC 2021, ASCE 7-16
Load Combination Set : ASCE 7-16
Material Properties
Beam Bracing :Beam is Fully Braced against lateral-torsional buckling
Allowable Stress Design
Douglas Fir-Larch
No.2
900.0
900.0
1,350.0
625.0
1,600.0
580.0
180.0
575.0 31.210
Analysis Method :
Eminbend - xx ksi
Wood Species :
Wood Grade :
Fb +
psi
psi
Fv psi
Fb -
Ft psi
Fc - Prll psi
psiFc - Perp
E : Modulus of Elasticity
Ebend- xx ksi
Density pcf
Load Combination :ASCE 7-16
.Applied Loads Service loads entered. Load Factors will be applied for calculations.
Beam self weight calculated and added to loading
Load for Span Number 1
Uniform Load : D = 0.010, Lr = 0.020 ksf, Extent = 0.0 -->> 7.170 ft, Tributary Width = 1.330->5.080 ft, (Roof)
Uniform Load : D = 0.010, Lr = 0.020 ksf, Extent = 6.920 -->> 11.0 ft, Tributary Width = 5.080->1.330 ft, (Roof)
Uniform Load : D = 0.0050, L = 0.010 ksf, Tributary Width = 1.330 ft, (Ceiling)
Uniform Load : D = 0.0050, L = 0.010 ksf, Tributary Width = 7.584 ft, (CEILING)
.DESIGN SUMMARY Design OK
Maximum Bending Stress Ratio 0.604: 1
Load Combination +D+L
Span # where maximum occurs Span # 1
Location of maximum on span 5.580 ft
39.16 psi=
=
1,080.00 psi
4x10Section used for this span
Span # where maximum occurs
Location of maximum on span
Span # 1=
Load Combination +D+L
=
=
=
180.00 psi==
Section used for this span 4x10
Maximum Shear Stress Ratio 0.218 : 1
10.237 ft=
=
652.54 psi
Maximum Deflection
0 <360
689
Ratio =0 <240
Max Downward Transient Deflection 0.080 in 1650Ratio =>=360
Max Upward Transient Deflection 0 in Ratio =
Max Downward Total Deflection 0.191 in Ratio =>=240
Max Upward Total Deflection 0 in
fb: Actual
F'b
fv: Actual
F'v
Span: 1 : L Only
n/a
Span: 1 : +D+0.750Lr+0.750L
n/a
.Maximum Forces & Stresses for Load Combinations
Span #
Moment ValuesLoad Combination
C iCLx CCCMCF rt
Shear ValuesMax Stress Ratios
M CDV fbM fvF'b V F'vSegment Length Cfu
D Only 0.0 0.00 0.00.0
1.00Length = 11.0 ft 1 0.338 0.121 0.90 1.200 1.001.00 1.00 1.37 328.6 972.0 0.42 162.01.00 19.61.00
1.00+D+L 1.200 1.001.00 1.00 0.0 0.00 0.01.00 0.01.00
1.00Length = 11.0 ft 1 0.604 0.218 1.00 1.200 1.001.00 1.00 2.71 652.5 1,080.0 0.85 180.01.00 39.21.00
1.00+D+Lr 1.200 1.001.00 1.00 0.0 0.00 0.01.00 0.01.00
1.00Length = 11.0 ft 1 0.453 0.161 1.25 1.200 1.001.00 1.00 2.54 611.2 1,350.0 0.78 225.01.00 36.11.00
1.00+D+0.750Lr+0.750L 1.200 1.001.00 1.00 0.0 0.00 0.01.00 0.01.00
2710 N Laird St & 2209 W
Laramore Ln10/7/2024
Wood Beam
LIC# : KW-06014251, Build:20.23.12.07 GET STRUCTURAL ENGINEERING AND CONSULTING (c) ENERCALC INC 1983-2023
DESCRIPTION:1 - C.B.
Project File: 2710 Laird Ave Member Check.ec6
Project Title:
Engineer:
Project ID:
Project Descr:
Maximum Forces & Stresses for Load Combinations
Span #
Moment ValuesLoad Combination
C iCLx CCCMCF rt
Shear ValuesMax Stress Ratios
M CDV fbM fvF'b V F'vSegment Length Cfu
1.00Length = 11.0 ft 1 0.580 0.207 1.25 1.200 1.001.00 1.00 3.26 783.2 1,350.0 1.01 225.01.00 46.71.00
1.00+D+0.750L 1.200 1.001.00 1.00 0.0 0.00 0.01.00 0.01.00
1.00Length = 11.0 ft 1 0.460 0.166 1.15 1.200 1.001.00 1.00 2.38 571.5 1,242.0 0.74 207.01.00 34.31.00
1.00+0.60D 1.200 1.001.00 1.00 0.0 0.00 0.01.00 0.01.00
1.00Length = 11.0 ft 1 0.114 0.041 1.60 1.200 1.001.00 1.00 0.82 197.1 1,728.0 0.25 288.01.00 11.81.00
.
Location in SpanLoad CombinationMax. "-" Defl Location in SpanLoad Combination Span Max. "+" Defl
Overall Maximum Deflections
+D+0.750Lr+0.750L 1 0.1914 5.540 0.0000 0.000
.
Load Combination Support 1 Support 2
Vertical Reactions Support notation : Far left is #1 Values in KIPS
Max Upward from all Load Conditions 1.075 1.130
Max Upward from Load Combinations 1.075 1.130
Max Upward from Load Cases 0.490 0.490
D Only 0.453 0.475
+D+L 0.943 0.965
+D+Lr 0.792 0.858
+D+0.750Lr+0.750L 1.075 1.130
+D+0.750L 0.821 0.843
+0.60D 0.272 0.285
Lr Only 0.339 0.383
L Only 0.490 0.490
2710 N Laird St & 2209 W
Laramore Ln10/7/2024
Wood Beam
LIC# : KW-06014251, Build:20.23.08.30 GET STRUCTURAL ENGINEERING AND CONSULTING (c) ENERCALC INC 1983-2023
DESCRIPTION:2 - H.
Project File: 2710 Laird Ave Member Check.ec6
Project Title:
Engineer:
Project ID:
Project Descr:
CODE REFERENCES
Calculations per NDS 2018, IBC 2021, ASCE 7-16
Load Combination Set : ASCE 7-16
Material Properties
Beam Bracing :Beam is Fully Braced against lateral-torsional buckling
Allowable Stress Design
Douglas Fir-Larch
No.2
900.0
900.0
1,350.0
625.0
1,600.0
580.0
180.0
575.0 31.210
Analysis Method :
Eminbend - xx ksi
Wood Species :
Wood Grade :
Fb +
psi
psi
Fv psi
Fb -
Ft psi
Fc - Prll psi
psiFc - Perp
E : Modulus of Elasticity
Ebend- xx ksi
Density pcf
Load Combination :ASCE 7-16
.Applied Loads Service loads entered. Load Factors will be applied for calculations.
Beam self weight calculated and added to loading
Load for Span Number 1
Uniform Load : D = 0.010, Lr = 0.020 ksf, Extent = 0.0 -->> 3.420 ft, Tributary Width = 3.670->5.330 ft, (Roof)
Uniform Load : D = 0.010, Lr = 0.020 ksf, Extent = 3.420 -->> 6.750 ft, Tributary Width = 5.330->3.670 ft, (Roof)
Uniform Load : D = 0.0050, L = 0.010 ksf, Tributary Width = 1.330 ft, (Ceiling)
.DESIGN SUMMARY Design OK
Maximum Bending Stress Ratio 0.408: 1
Load Combination +D+Lr
Span # where maximum occurs Span # 1
Location of maximum on span 3.375 ft
34.09 psi=
=
1,462.50 psi
4x6Section used for this span
Span # where maximum occurs
Location of maximum on span
Span # 1=
Load Combination +D+Lr
=
=
=
225.00 psi==
Section used for this span 4x6
Maximum Shear Stress Ratio 0.151 : 1
6.307 ft=
=
596.92 psi
Maximum Deflection
0 <360
876
Ratio =0 <240
Max Downward Transient Deflection 0.057 in 1414Ratio =>=360
Max Upward Transient Deflection 0 in Ratio =
Max Downward Total Deflection 0.092 in Ratio =>=240
Max Upward Total Deflection 0 in
fb: Actual
F'b
fv: Actual
F'v
Span: 1 : Lr Only
n/a
Span: 1 : +D+Lr
n/a
.Maximum Forces & Stresses for Load Combinations
Span #
Moment ValuesLoad Combination
C iCLx CCCMCF rt
Shear ValuesMax Stress Ratios
M CDV fbM fvF'b V F'vSegment Length Cfu
D Only 0.0 0.00 0.00.0
1.00Length = 6.725 ft 1 0.215 0.080 0.90 1.300 1.001.00 1.00 0.33 226.9 1,053.0 0.17 162.01.00 13.01.00
1.00Length = 0.02464 ft 1 0.003 0.080 0.90 1.300 1.001.00 1.00 0.00 3.1 1,053.0 0.17 162.01.00 13.01.00
1.00+D+L 1.300 1.001.00 1.00 0.0 0.00 0.01.00 0.01.00
1.00Length = 6.725 ft 1 0.238 0.089 1.00 1.300 1.001.00 1.00 0.41 278.4 1,170.0 0.21 180.01.00 16.01.00
1.00Length = 0.02464 ft 1 0.003 0.089 1.00 1.300 1.001.00 1.00 0.01 3.9 1,170.0 0.21 180.01.00 16.01.00
1.00+D+Lr 1.300 1.001.00 1.00 0.0 0.00 0.01.00 0.01.00
1.00Length = 6.725 ft 1 0.408 0.151 1.25 1.300 1.001.00 1.00 0.88 596.9 1,462.5 0.44 225.01.00 34.11.00
2710 N Laird St & 2209 W
Laramore Ln10/7/2024
Wood Beam
LIC# : KW-06014251, Build:20.23.08.30 GET STRUCTURAL ENGINEERING AND CONSULTING (c) ENERCALC INC 1983-2023
DESCRIPTION:2 - H.
Project File: 2710 Laird Ave Member Check.ec6
Project Title:
Engineer:
Project ID:
Project Descr:
Maximum Forces & Stresses for Load Combinations
Span #
Moment ValuesLoad Combination
C iCLx CCCMCF rt
Shear ValuesMax Stress Ratios
M CDV fbM fvF'b V F'vSegment Length Cfu
1.00Length = 0.02464 ft 1 0.006 0.151 1.25 1.300 1.001.00 1.00 0.01 8.2 1,462.5 0.44 225.01.00 34.11.00
1.00+D+0.750Lr+0.750L 1.300 1.001.00 1.00 0.0 0.00 0.01.00 0.01.00
1.00Length = 6.725 ft 1 0.371 0.138 1.25 1.300 1.001.00 1.00 0.80 543.1 1,462.5 0.40 225.01.00 31.11.00
1.00Length = 0.02464 ft 1 0.005 0.138 1.25 1.300 1.001.00 1.00 0.01 7.5 1,462.5 0.40 225.01.00 31.11.00
1.00+D+0.750L 1.300 1.001.00 1.00 0.0 0.00 0.01.00 0.01.00
1.00Length = 6.725 ft 1 0.197 0.074 1.15 1.300 1.001.00 1.00 0.39 265.5 1,345.5 0.20 207.01.00 15.31.00
1.00Length = 0.02464 ft 1 0.003 0.074 1.15 1.300 1.001.00 1.00 0.01 3.7 1,345.5 0.20 207.01.00 15.31.00
1.00+0.60D 1.300 1.001.00 1.00 0.0 0.00 0.01.00 0.01.00
1.00Length = 6.725 ft 1 0.073 0.027 1.60 1.300 1.001.00 1.00 0.20 136.1 1,872.0 0.10 288.01.00 7.81.00
1.00Length = 0.02464 ft 1 0.001 0.027 1.60 1.300 1.001.00 1.00 0.00 1.9 1,872.0 0.10 288.01.00 7.81.00
.
Location in SpanLoad CombinationMax. "-" Defl Location in SpanLoad Combination Span Max. "+" Defl
Overall Maximum Deflections
+D+Lr 1 0.0925 3.400 0.0000 0.000
.
Load Combination Support 1 Support 2
Vertical Reactions Support notation : Far left is #1 Values in KIPS
Max Upward from all Load Conditions 0.492 0.493
Max Upward from Load Combinations 0.492 0.493
Max Upward from Load Cases 0.304 0.304
D Only 0.188 0.189
+D+L 0.233 0.233
+D+Lr 0.492 0.493
+D+0.750Lr+0.750L 0.450 0.450
+D+0.750L 0.222 0.222
+0.60D 0.113 0.113
Lr Only 0.304 0.304
L Only 0.045 0.045
2710 N Laird St & 2209 W
Laramore Ln10/7/2024
Wood Beam
LIC# : KW-06014251, Build:20.23.12.07 GET STRUCTURAL ENGINEERING AND CONSULTING (c) ENERCALC INC 1983-2023
DESCRIPTION:3 - H.
Project File: 2710 Laird Ave Member Check.ec6
Project Title:
Engineer:
Project ID:
Project Descr:
CODE REFERENCES
Calculations per NDS 2018, IBC 2021, ASCE 7-16
Load Combination Set : ASCE 7-16
Material Properties
Beam Bracing :Beam is Fully Braced against lateral-torsional buckling
Allowable Stress Design
Douglas Fir-Larch
No.2
900.0
900.0
1,350.0
625.0
1,600.0
580.0
180.0
575.0 31.210
Analysis Method :
Eminbend - xx ksi
Wood Species :
Wood Grade :
Fb +
psi
psi
Fv psi
Fb -
Ft psi
Fc - Prll psi
psiFc - Perp
E : Modulus of Elasticity
Ebend- xx ksi
Density pcf
Load Combination :ASCE 7-16
.Applied Loads Service loads entered. Load Factors will be applied for calculations.
Beam self weight calculated and added to loading
Uniform Load : D = 0.010, Lr = 0.020 ksf, Tributary Width = 5.420->3.420 ft, (Roof)
Uniform Load : D = 0.0050, L = 0.010 ksf, Tributary Width = 2.0 ft, (Ceiling)
.DESIGN SUMMARY Design OK
Maximum Bending Stress Ratio 0.137: 1
Load Combination +D+Lr
Span # where maximum occurs Span # 1
Location of maximum on span 1.927 ft
18.32 psi=
=
1,462.50 psi
4x6Section used for this span
Span # where maximum occurs
Location of maximum on span
Span # 1=
Load Combination +D+Lr
=
=
=
225.00 psi==
Section used for this span 4x6
Maximum Shear Stress Ratio 0.081 : 1
0.000 ft=
=
199.85 psi
Maximum Deflection
0 <360
4381
Ratio =0 <240
Max Downward Transient Deflection 0.007 in 7275Ratio =>=360
Max Upward Transient Deflection 0 in Ratio =
Max Downward Total Deflection 0.011 in Ratio =>=240
Max Upward Total Deflection 0 in
fb: Actual
F'b
fv: Actual
F'v
Span: 1 : Lr Only
n/a
Span: 1 : +D+Lr
n/a
.Maximum Forces & Stresses for Load Combinations
Span #
Moment ValuesLoad Combination
C iCLx CCCMCF rt
Shear ValuesMax Stress Ratios
M CDV fbM fvF'b V F'vSegment Length Cfu
D Only 0.0 0.00 0.00.0
1.00Length = 4.0 ft 1 0.075 0.045 0.90 1.300 1.001.00 1.00 0.12 79.5 1,053.0 0.09 162.01.00 7.21.00
1.00+D+L 1.300 1.001.00 1.00 0.0 0.00 0.01.00 0.01.00
1.00Length = 4.0 ft 1 0.091 0.054 1.00 1.300 1.001.00 1.00 0.16 106.6 1,170.0 0.12 180.01.00 9.71.00
1.00+D+Lr 1.300 1.001.00 1.00 0.0 0.00 0.01.00 0.01.00
1.00Length = 4.0 ft 1 0.137 0.081 1.25 1.300 1.001.00 1.00 0.29 199.9 1,462.5 0.24 225.01.00 18.31.00
1.00+D+0.750Lr+0.750L 1.300 1.001.00 1.00 0.0 0.00 0.01.00 0.01.00
1.00Length = 4.0 ft 1 0.130 0.077 1.25 1.300 1.001.00 1.00 0.28 190.1 1,462.5 0.22 225.01.00 17.41.00
1.00+D+0.750L 1.300 1.001.00 1.00 0.0 0.00 0.01.00 0.01.00
2710 N Laird St & 2209 W
Laramore Ln10/7/2024
Wood Beam
LIC# : KW-06014251, Build:20.23.12.07 GET STRUCTURAL ENGINEERING AND CONSULTING (c) ENERCALC INC 1983-2023
DESCRIPTION:3 - H.
Project File: 2710 Laird Ave Member Check.ec6
Project Title:
Engineer:
Project ID:
Project Descr:
Maximum Forces & Stresses for Load Combinations
Span #
Moment ValuesLoad Combination
C iCLx CCCMCF rt
Shear ValuesMax Stress Ratios
M CDV fbM fvF'b V F'vSegment Length Cfu
1.00Length = 4.0 ft 1 0.074 0.044 1.15 1.300 1.001.00 1.00 0.15 99.8 1,345.5 0.12 207.01.00 9.11.00
1.00+0.60D 1.300 1.001.00 1.00 0.0 0.00 0.01.00 0.01.00
1.00Length = 4.0 ft 1 0.025 0.015 1.60 1.300 1.001.00 1.00 0.07 47.7 1,872.0 0.06 288.01.00 4.31.00
.
Location in SpanLoad CombinationMax. "-" Defl Location in SpanLoad Combination Span Max. "+" Defl
Overall Maximum Deflections
+D+Lr 1 0.0110 1.985 0.0000 0.000
.
Load Combination Support 1 Support 2
Vertical Reactions Support notation : Far left is #1 Values in KIPS
Max Upward from all Load Conditions 0.314 0.274
Max Upward from Load Combinations 0.314 0.274
Max Upward from Load Cases 0.190 0.163
D Only 0.123 0.110
+D+L 0.163 0.150
+D+Lr 0.314 0.274
+D+0.750Lr+0.750L 0.296 0.263
+D+0.750L 0.153 0.140
+0.60D 0.074 0.066
Lr Only 0.190 0.163
L Only 0.040 0.040
2710 N Laird St & 2209 W
Laramore Ln10/7/2024
Wood Beam
LIC# : KW-06014251, Build:20.23.12.07 GET STRUCTURAL ENGINEERING AND CONSULTING (c) ENERCALC INC 1983-2023
DESCRIPTION:7 - C.B.
Project File: 2710 Laird Ave Member Check.ec6
Project Title:
Engineer:
Project ID:
Project Descr:
CODE REFERENCES
Calculations per NDS 2018, IBC 2021, ASCE 7-16
Load Combination Set : ASCE 7-16
Material Properties
Beam Bracing :Completely Unbraced
Allowable Stress Design
Douglas Fir-Larch
No.1
1000
1000
1500
625
1700
620
180
675 31.21
Analysis Method :
Eminbend - xx ksi
Wood Species :
Wood Grade :
Fb +
psi
psi
Fv psi
Fb -
Ft psi
Fc - Prll psi
psiFc - Perp
E : Modulus of Elasticity
Ebend- xx ksi
Density pcf
Load Combination :ASCE 7-16
.Applied Loads Service loads entered. Load Factors will be applied for calculations.
Beam self weight calculated and added to loading
Uniform Load : D = 0.0050, L = 0.010 ksf, Tributary Width = 7.584 ft, (Ceiling)
Point Load : D = 0.5180, Lr = 0.8450 k @ 4.0 ft, (Hip)
Point Load : D = 0.5180, Lr = 0.8450 k @ 4.0 ft, (Hip)
Point Load : D = 0.180, Lr = 0.360 k @ 4.0 ft, (BEAM 11)
.DESIGN SUMMARY Design OK
Maximum Bending Stress Ratio 0.631: 1
Load Combination +D+Lr
Span # where maximum occurs Span # 1
Location of maximum on span 3.985 ft
80.68 psi=
=
1,350.30 psi
4x12Section used for this span
Span # where maximum occurs
Location of maximum on span
Span # 1=
Load Combination +D+Lr
=
=
=
225.00 psi==
Section used for this span 4x12
Maximum Shear Stress Ratio 0.359 : 1
5.575 ft=
=
851.55 psi
Maximum Deflection
0 <360
1715
Ratio =0 <240
Max Downward Transient Deflection 0.027 in 2901Ratio =>=360
Max Upward Transient Deflection 0 in Ratio =
Max Downward Total Deflection 0.045 in Ratio =>=240
Max Upward Total Deflection 0 in
fb: Actual
F'b
fv: Actual
F'v
Span: 1 : Lr Only
n/a
Span: 1 : +D+Lr
n/a
.Maximum Forces & Stresses for Load Combinations
Span #
Moment ValuesLoad Combination
C iCLx CCCMCF rt
Shear ValuesMax Stress Ratios
M CDV fbM fvF'b V F'vSegment Length Cfu
D Only 0.0 0.00 0.00.0
0.99Length = 6.50 ft 1 0.348 0.201 0.90 1.100 1.001.00 1.00 2.10 340.8 978.2 0.86 162.01.00 32.61.00
0.99+D+L 1.100 1.001.00 1.00 0.0 0.00 0.01.00 0.01.00
0.99Length = 6.50 ft 1 0.371 0.219 1.00 1.100 1.001.00 1.00 2.48 402.6 1,085.1 1.03 180.01.00 39.31.00
0.99+D+Lr 1.100 1.001.00 1.00 0.0 0.00 0.01.00 0.01.00
0.98Length = 6.50 ft 1 0.631 0.359 1.25 1.100 1.001.00 1.00 5.24 851.6 1,350.3 2.12 225.01.00 80.71.00
0.98+D+0.750Lr+0.750L 1.100 1.001.00 1.00 0.0 0.00 0.01.00 0.01.00
0.98Length = 6.50 ft 1 0.570 0.328 1.25 1.100 1.001.00 1.00 4.74 770.2 1,350.3 1.93 225.01.00 73.71.00
2710 N Laird St & 2209 W
Laramore Ln10/7/2024
Wood Beam
LIC# : KW-06014251, Build:20.23.12.07 GET STRUCTURAL ENGINEERING AND CONSULTING (c) ENERCALC INC 1983-2023
DESCRIPTION:7 - C.B.
Project File: 2710 Laird Ave Member Check.ec6
Project Title:
Engineer:
Project ID:
Project Descr:
Maximum Forces & Stresses for Load Combinations
Span #
Moment ValuesLoad Combination
C iCLx CCCMCF rt
Shear ValuesMax Stress Ratios
M CDV fbM fvF'b V F'vSegment Length Cfu
0.98+D+0.750L 1.100 1.001.00 1.00 0.0 0.00 0.01.00 0.01.00
0.98Length = 6.50 ft 1 0.311 0.182 1.15 1.100 1.001.00 1.00 2.38 387.1 1,244.6 0.99 207.01.00 37.71.00
0.98+0.60D 1.100 1.001.00 1.00 0.0 0.00 0.01.00 0.01.00
0.97Length = 6.50 ft 1 0.119 0.068 1.60 1.100 1.001.00 1.00 1.26 204.5 1,715.7 0.51 288.01.00 19.61.00
.
Location in SpanLoad CombinationMax. "-" Defl Location in SpanLoad Combination Span Max. "+" Defl
Overall Maximum Deflections
+D+Lr 1 0.0455 3.464 0.0000 0.000
.
Load Combination Support 1 Support 2
Vertical Reactions Support notation : Far left is #1 Values in KIPS
Max Upward from all Load Conditions 1.407 2.161
Max Upward from Load Combinations 1.407 2.161
Max Upward from Load Cases 0.788 1.262
D Only 0.619 0.899
+D+L 0.865 1.146
+D+Lr 1.407 2.161
+D+0.750Lr+0.750L 1.395 2.030
+D+0.750L 0.804 1.084
+0.60D 0.371 0.540
Lr Only 0.788 1.262
L Only 0.246 0.246
2710 N Laird St & 2209 W
Laramore Ln10/7/2024
Wood Beam
LIC# : KW-06014251, Build:20.23.08.30 GET STRUCTURAL ENGINEERING AND CONSULTING (c) ENERCALC INC 1983-2023
DESCRIPTION:8 - C.B.
Project File: 2710 Laird Ave Member Check.ec6
Project Title:
Engineer:
Project ID:
Project Descr:
CODE REFERENCES
Calculations per NDS 2018, IBC 2021, ASCE 7-16
Load Combination Set : ASCE 7-16
Material Properties
Beam Bracing :Beam is Fully Braced against lateral-torsional buckling
Allowable Stress Design
Douglas Fir-Larch
No.1
1000
1000
1500
625
1700
620
180
675 31.21
Analysis Method :
Eminbend - xx ksi
Wood Species :
Wood Grade :
Fb +
psi
psi
Fv psi
Fb -
Ft psi
Fc - Prll psi
psiFc - Perp
E : Modulus of Elasticity
Ebend- xx ksi
Density pcf
Load Combination :ASCE 7-16
.Applied Loads Service loads entered. Load Factors will be applied for calculations.
Beam self weight calculated and added to loading
Uniform Load : D = 0.010, Lr = 0.020 ksf, Tributary Width = 1.330 ft, (Roof)
Uniform Load : D = 0.0050, L = 0.010 ksf, Tributary Width = 1.330 ft, (Ceiling)
Point Load : D = 0.2270, Lr = 0.3620 k @ 7.170 ft, (Hip)
Point Load : D = 0.2270, Lr = 0.3620 k @ 7.170 ft, (Hip)
.DESIGN SUMMARY Design OK
Maximum Bending Stress Ratio 0.679: 1
Load Combination +D+Lr
Span # where maximum occurs Span # 1
Location of maximum on span 7.184 ft
36.21 psi=
=
1,375.00 psi
4x12Section used for this span
Span # where maximum occurs
Location of maximum on span
Span # 1=
Load Combination +D+Lr
=
=
=
225.00 psi==
Section used for this span 4x12
Maximum Shear Stress Ratio 0.161 : 1
0.000 ft=
=
934.30 psi
Maximum Deflection
0 <360
655
Ratio =0 <240
Max Downward Transient Deflection 0.154 in 1139Ratio =>=360
Max Upward Transient Deflection 0 in Ratio =
Max Downward Total Deflection 0.267 in Ratio =>=240
Max Upward Total Deflection 0 in
fb: Actual
F'b
fv: Actual
F'v
Span: 1 : Lr Only
n/a
Span: 1 : +D+Lr
n/a
.Maximum Forces & Stresses for Load Combinations
Span #
Moment ValuesLoad Combination
C iCLx CCCMCF rt
Shear ValuesMax Stress Ratios
M CDV fbM fvF'b V F'vSegment Length Cfu
D Only 0.0 0.00 0.00.0
1.00Length = 14.527 ft 1 0.395 0.097 0.90 1.100 1.001.00 1.00 2.41 391.4 990.0 0.41 162.01.00 15.71.00
1.00Length = 0.05321 ft 1 0.004 0.097 0.90 1.100 1.001.00 1.00 0.02 3.7 990.0 0.41 162.01.00 15.71.00
1.00+D+L 1.100 1.001.00 1.00 0.0 0.00 0.01.00 0.01.00
1.00Length = 14.527 ft 1 0.408 0.105 1.00 1.100 1.001.00 1.00 2.76 448.8 1,100.0 0.50 180.01.00 19.01.00
1.00Length = 0.05321 ft 1 0.004 0.105 1.00 1.100 1.001.00 1.00 0.03 4.6 1,100.0 0.49 180.01.00 19.01.00
1.00+D+Lr 1.100 1.001.00 1.00 0.0 0.00 0.01.00 0.01.00
1.00Length = 14.527 ft 1 0.679 0.161 1.25 1.100 1.001.00 1.00 5.75 934.3 1,375.0 0.95 225.01.00 36.21.00
2710 N Laird St & 2209 W
Laramore Ln10/7/2024
Wood Beam
LIC# : KW-06014251, Build:20.23.08.30 GET STRUCTURAL ENGINEERING AND CONSULTING (c) ENERCALC INC 1983-2023
DESCRIPTION:8 - C.B.
Project File: 2710 Laird Ave Member Check.ec6
Project Title:
Engineer:
Project ID:
Project Descr:
Maximum Forces & Stresses for Load Combinations
Span #
Moment ValuesLoad Combination
C iCLx CCCMCF rt
Shear ValuesMax Stress Ratios
M CDV fbM fvF'b V F'vSegment Length Cfu
1.00Length = 0.05321 ft 1 0.006 0.161 1.25 1.100 1.001.00 1.00 0.05 8.5 1,375.0 0.93 225.01.00 36.21.00
1.00+D+0.750Lr+0.750L 1.100 1.001.00 1.00 0.0 0.00 0.01.00 0.01.00
1.00Length = 14.527 ft 1 0.612 0.149 1.25 1.100 1.001.00 1.00 5.18 841.7 1,375.0 0.88 225.01.00 33.51.00
1.00Length = 0.05321 ft 1 0.006 0.149 1.25 1.100 1.001.00 1.00 0.05 7.9 1,375.0 0.86 225.01.00 33.51.00
1.00+D+0.750L 1.100 1.001.00 1.00 0.0 0.00 0.01.00 0.01.00
1.00Length = 14.527 ft 1 0.343 0.088 1.15 1.100 1.001.00 1.00 2.67 434.5 1,265.0 0.48 207.01.00 18.11.00
1.00Length = 0.05321 ft 1 0.003 0.088 1.15 1.100 1.001.00 1.00 0.03 4.3 1,265.0 0.47 207.01.00 18.11.00
1.00+0.60D 1.100 1.001.00 1.00 0.0 0.00 0.01.00 0.01.00
1.00Length = 14.527 ft 1 0.133 0.033 1.60 1.100 1.001.00 1.00 1.44 234.8 1,760.0 0.25 288.01.00 9.41.00
1.00Length = 0.05321 ft 1 0.001 0.033 1.60 1.100 1.001.00 1.00 0.01 2.2 1,760.0 0.24 288.01.00 9.41.00
.
Location in SpanLoad CombinationMax. "-" Defl Location in SpanLoad Combination Span Max. "+" Defl
Overall Maximum Deflections
+D+Lr 1 0.2669 7.290 0.0000 0.000
.
Load Combination Support 1 Support 2
Vertical Reactions Support notation : Far left is #1 Values in KIPS
Max Upward from all Load Conditions 1.000 0.981
Max Upward from Load Combinations 1.000 0.981
Max Upward from Load Cases 0.562 0.550
D Only 0.438 0.431
+D+L 0.535 0.528
+D+Lr 1.000 0.981
+D+0.750Lr+0.750L 0.933 0.916
+D+0.750L 0.511 0.504
+0.60D 0.263 0.259
Lr Only 0.562 0.550
L Only 0.097 0.097
2710 N Laird St & 2209 W
Laramore Ln10/7/2024
Wood Beam
LIC# : KW-06014251, Build:20.23.12.07 GET STRUCTURAL ENGINEERING AND CONSULTING (c) ENERCALC INC 1983-2023
DESCRIPTION:9 - H.
Project File: 2710 Laird Ave Member Check.ec6
Project Title:
Engineer:
Project ID:
Project Descr:
CODE REFERENCES
Calculations per NDS 2018, IBC 2021, ASCE 7-16
Load Combination Set : ASCE 7-16
Material Properties
Beam Bracing :Beam is Fully Braced against lateral-torsional buckling
Allowable Stress Design
Douglas Fir-Larch
No.2
900.0
900.0
1,350.0
625.0
1,600.0
580.0
180.0
575.0 31.210
Analysis Method :
Eminbend - xx ksi
Wood Species :
Wood Grade :
Fb +
psi
psi
Fv psi
Fb -
Ft psi
Fc - Prll psi
psiFc - Perp
E : Modulus of Elasticity
Ebend- xx ksi
Density pcf
Load Combination :ASCE 7-16
.Applied Loads Service loads entered. Load Factors will be applied for calculations.
Beam self weight calculated and added to loading
Uniform Load : D = 0.010, Lr = 0.020 ksf, Tributary Width = 12.920 ft, (Roof)
Uniform Load : D = 0.0050, L = 0.010 ksf, Tributary Width = 2.0 ft, (Ceiling)
.DESIGN SUMMARY Design OK
Maximum Bending Stress Ratio 0.210: 1
Load Combination +D+Lr
Span # where maximum occurs Span # 1
Location of maximum on span 1.500 ft
32.91 psi=
=
1,462.50 psi
4x6Section used for this span
Span # where maximum occurs
Location of maximum on span
Span # 1=
Load Combination +D+Lr
=
=
=
225.00 psi==
Section used for this span 4x6
Maximum Shear Stress Ratio 0.146 : 1
0.000 ft=
=
307.38 psi
Maximum Deflection
0 <360
3795
Ratio =0 <240
Max Downward Transient Deflection 0.006 in 5900Ratio =>=360
Max Upward Transient Deflection 0 in Ratio =
Max Downward Total Deflection 0.009 in Ratio =>=240
Max Upward Total Deflection 0 in
fb: Actual
F'b
fv: Actual
F'v
Span: 1 : Lr Only
n/a
Span: 1 : +D+Lr
n/a
.Maximum Forces & Stresses for Load Combinations
Span #
Moment ValuesLoad Combination
C iCLx CCCMCF rt
Shear ValuesMax Stress Ratios
M CDV fbM fvF'b V F'vSegment Length Cfu
D Only 0.0 0.00 0.00.0
1.00Length = 3.0 ft 1 0.104 0.072 0.90 1.300 1.001.00 1.00 0.16 109.7 1,053.0 0.15 162.01.00 11.71.00
1.00+D+L 1.300 1.001.00 1.00 0.0 0.00 0.01.00 0.01.00
1.00Length = 3.0 ft 1 0.107 0.074 1.00 1.300 1.001.00 1.00 0.18 125.0 1,170.0 0.17 180.01.00 13.41.00
1.00+D+Lr 1.300 1.001.00 1.00 0.0 0.00 0.01.00 0.01.00
1.00Length = 3.0 ft 1 0.210 0.146 1.25 1.300 1.001.00 1.00 0.45 307.4 1,462.5 0.42 225.01.00 32.91.00
1.00+D+0.750Lr+0.750L 1.300 1.001.00 1.00 0.0 0.00 0.01.00 0.01.00
1.00Length = 3.0 ft 1 0.184 0.128 1.25 1.300 1.001.00 1.00 0.40 269.4 1,462.5 0.37 225.01.00 28.81.00
1.00+D+0.750L 1.300 1.001.00 1.00 0.0 0.00 0.01.00 0.01.00
2710 N Laird St & 2209 W
Laramore Ln10/7/2024
Wood Beam
LIC# : KW-06014251, Build:20.23.12.07 GET STRUCTURAL ENGINEERING AND CONSULTING (c) ENERCALC INC 1983-2023
DESCRIPTION:9 - H.
Project File: 2710 Laird Ave Member Check.ec6
Project Title:
Engineer:
Project ID:
Project Descr:
Maximum Forces & Stresses for Load Combinations
Span #
Moment ValuesLoad Combination
C iCLx CCCMCF rt
Shear ValuesMax Stress Ratios
M CDV fbM fvF'b V F'vSegment Length Cfu
1.00Length = 3.0 ft 1 0.090 0.063 1.15 1.300 1.001.00 1.00 0.18 121.2 1,345.5 0.17 207.01.00 13.01.00
1.00+0.60D 1.300 1.001.00 1.00 0.0 0.00 0.01.00 0.01.00
1.00Length = 3.0 ft 1 0.035 0.024 1.60 1.300 1.001.00 1.00 0.10 65.8 1,872.0 0.09 288.01.00 7.01.00
.
Location in SpanLoad CombinationMax. "-" Defl Location in SpanLoad Combination Span Max. "+" Defl
Overall Maximum Deflections
+D+Lr 1 0.0095 1.511 0.0000 0.000
.
Load Combination Support 1 Support 2
Vertical Reactions Support notation : Far left is #1 Values in KIPS
Max Upward from all Load Conditions 0.603 0.603
Max Upward from Load Combinations 0.603 0.603
Max Upward from Load Cases 0.388 0.388
D Only 0.215 0.215
+D+L 0.245 0.245
+D+Lr 0.603 0.603
+D+0.750Lr+0.750L 0.528 0.528
+D+0.750L 0.238 0.238
+0.60D 0.129 0.129
Lr Only 0.388 0.388
L Only 0.030 0.030
2710 N Laird St & 2209 W
Laramore Ln10/7/2024
Wood Beam
LIC# : KW-06014251, Build:20.23.08.30 GET STRUCTURAL ENGINEERING AND CONSULTING (c) ENERCALC INC 1983-2023
DESCRIPTION:10 - D.B.
Project File: 2710 Laird Ave Member Check.ec6
Project Title:
Engineer:
Project ID:
Project Descr:
CODE REFERENCES
Calculations per NDS 2018, IBC 2021, ASCE 7-16
Load Combination Set : ASCE 7-16
Material Properties
Beam Bracing :Beam is Fully Braced against lateral-torsional buckling
Allowable Stress Design
Douglas Fir-Larch
No.2
900.0
900.0
1,350.0
625.0
1,600.0
580.0
180.0
575.0 31.210
Analysis Method :
Eminbend - xx ksi
Wood Species :
Wood Grade :
Fb +
psi
psi
Fv psi
Fb -
Ft psi
Fc - Prll psi
psiFc - Perp
E : Modulus of Elasticity
Ebend- xx ksi
Density pcf
Load Combination :ASCE 7-16
.Applied Loads Service loads entered. Load Factors will be applied for calculations.
Beam self weight calculated and added to loading
Uniform Load : D = 0.010, Lr = 0.020 ksf, Tributary Width = 7.250->3.830 ft, (Roof)
.DESIGN SUMMARY Design OK
Maximum Bending Stress Ratio 0.282: 1
Load Combination +D+Lr
Span # where maximum occurs Span # 1
Location of maximum on span 3.321 ft
31.47 psi=
=
1,462.50 psi
4x8Section used for this span
Span # where maximum occurs
Location of maximum on span
Span # 1=
Load Combination +D+Lr
=
=
=
225.00 psi==
Section used for this span 4x8
Maximum Shear Stress Ratio 0.140 : 1
0.000 ft=
=
412.60 psi
Maximum Deflection
0 <360
1600
Ratio =0 <240
Max Downward Transient Deflection 0.034 in 2480Ratio =>=360
Max Upward Transient Deflection 0 in Ratio =
Max Downward Total Deflection 0.052 in Ratio =>=240
Max Upward Total Deflection 0 in
fb: Actual
F'b
fv: Actual
F'v
Span: 1 : Lr Only
n/a
Span: 1 : +D+Lr
n/a
.Maximum Forces & Stresses for Load Combinations
Span #
Moment ValuesLoad Combination
C iCLx CCCMCF rt
Shear ValuesMax Stress Ratios
M CDV fbM fvF'b V F'vSegment Length Cfu
D Only 0.0 0.00 0.00.0
1.00Length = 7.0 ft 1 0.139 0.069 0.90 1.300 1.001.00 1.00 0.37 146.3 1,053.0 0.19 162.01.00 11.11.00
1.00+D+Lr 1.300 1.001.00 1.00 0.0 0.00 0.01.00 0.01.00
1.00Length = 7.0 ft 1 0.282 0.140 1.25 1.300 1.001.00 1.00 1.05 412.6 1,462.5 0.53 225.01.00 31.51.00
1.00+D+0.750Lr 1.300 1.001.00 1.00 0.0 0.00 0.01.00 0.01.00
1.00Length = 7.0 ft 1 0.237 0.117 1.25 1.300 1.001.00 1.00 0.88 346.0 1,462.5 0.45 225.01.00 26.41.00
1.00+0.60D 1.300 1.001.00 1.00 0.0 0.00 0.01.00 0.01.00
1.00Length = 7.0 ft 1 0.047 0.023 1.60 1.300 1.001.00 1.00 0.22 87.8 1,872.0 0.11 288.01.00 6.71.00
.
2710 N Laird St & 2209 W
Laramore Ln10/7/2024
Wood Beam
LIC# : KW-06014251, Build:20.23.08.30 GET STRUCTURAL ENGINEERING AND CONSULTING (c) ENERCALC INC 1983-2023
DESCRIPTION:10 - D.B.
Project File: 2710 Laird Ave Member Check.ec6
Project Title:
Engineer:
Project ID:
Project Descr:
Location in SpanLoad CombinationMax. "-" Defl Location in SpanLoad Combination Span Max. "+" Defl
Overall Maximum Deflections
+D+Lr 1 0.0525 3.474 0.0000 0.000
.
Load Combination Support 1 Support 2
Vertical Reactions Support notation : Far left is #1 Values in KIPS
Max Upward from all Load Conditions 0.661 0.541
Max Upward from Load Combinations 0.661 0.541
Max Upward from Load Cases 0.428 0.348
D Only 0.233 0.193
+D+Lr 0.661 0.541
+D+0.750Lr 0.554 0.454
+0.60D 0.140 0.116
Lr Only 0.428 0.348
2710 N Laird St & 2209 W
Laramore Ln10/7/2024
Wood Beam
LIC# : KW-06014251, Build:20.23.12.07 GET STRUCTURAL ENGINEERING AND CONSULTING (c) ENERCALC INC 1983-2023
DESCRIPTION:11 - RIDGE BEAM (R.B.)
Project File: 2710 Laird Ave Member Check.ec6
Project Title:
Engineer:
Project ID:
Project Descr:
CODE REFERENCES
Calculations per NDS 2018, IBC 2021, ASCE 7-16
Load Combination Set : ASCE 7-16
Material Properties
Beam Bracing :Beam is Fully Braced against lateral-torsional buckling
Allowable Stress Design
Douglas Fir-Larch
No.2
900
900
1350
625
1600
580
180
575 31.21
Analysis Method :
Eminbend - xx ksi
Wood Species :
Wood Grade :
Fb +
psi
psi
Fv psi
Fb -
Ft psi
Fc - Prll psi
psiFc - Perp
E : Modulus of Elasticity
Ebend- xx ksi
Density pcf
Load Combination :ASCE 7-16
.Applied Loads Service loads entered. Load Factors will be applied for calculations.
Beam self weight calculated and added to loading
Uniform Load : D = 0.010, Lr = 0.020 ksf, Tributary Width = 11.210 ft, (Roof)
.DESIGN SUMMARY Design OK
Maximum Bending Stress Ratio 0.144: 1
Load Combination +D+Lr
Span # where maximum occurs Span # 1
Location of maximum on span 1.584 ft
19.56 psi=
=
1,125.00 psi
2x12Section used for this span
Span # where maximum occurs
Location of maximum on span
Span # 1=
Load Combination +D+Lr
=
=
=
225.00 psi==
Section used for this span 2x12
Maximum Shear Stress Ratio 0.087 : 1
0.000 ft=
=
161.65 psi
Maximum Deflection
0 <180
13982
Ratio =0 <120
Max Downward Transient Deflection 0.002 in 21202Ratio =>=180
Max Upward Transient Deflection 0 in Ratio =
Max Downward Total Deflection 0.003 in Ratio =>=120
Max Upward Total Deflection 0 in
fb: Actual
F'b
fv: Actual
F'v
Span: 1 : Lr Only
n/a
Span: 1 : +D+Lr
n/a
.Maximum Forces & Stresses for Load Combinations
Span #
Moment ValuesLoad Combination
C iCLx CCCMCF rt
Shear ValuesMax Stress Ratios
M CDV fbM fvF'b V F'vSegment Length Cfu
D Only 0.0 0.00 0.00.0
1.00Length = 3.167 ft 1 0.068 0.041 0.90 1.000 1.001.00 1.00 0.15 55.0 810.0 0.07 162.01.00 6.71.00
1.00+D+Lr 1.000 1.001.00 1.00 0.0 0.00 0.01.00 0.01.00
1.00Length = 3.167 ft 1 0.144 0.087 1.25 1.000 1.001.00 1.00 0.43 161.6 1,125.0 0.22 225.01.00 19.61.00
1.00+D+0.750Lr 1.000 1.001.00 1.00 0.0 0.00 0.01.00 0.01.00
1.00Length = 3.167 ft 1 0.120 0.073 1.25 1.000 1.001.00 1.00 0.36 135.0 1,125.0 0.18 225.01.00 16.31.00
1.00+0.60D 1.000 1.001.00 1.00 0.0 0.00 0.01.00 0.01.00
1.00Length = 3.167 ft 1 0.023 0.014 1.60 1.000 1.001.00 1.00 0.09 33.0 1,440.0 0.04 288.01.00 4.01.00
.
2710 N Laird St & 2209 W
Laramore Ln10/7/2024
Wood Beam
LIC# : KW-06014251, Build:20.23.12.07 GET STRUCTURAL ENGINEERING AND CONSULTING (c) ENERCALC INC 1983-2023
DESCRIPTION:11 - RIDGE BEAM (R.B.)
Project File: 2710 Laird Ave Member Check.ec6
Project Title:
Engineer:
Project ID:
Project Descr:
Location in SpanLoad CombinationMax. "-" Defl Location in SpanLoad Combination Span Max. "+" Defl
Overall Maximum Deflections
+D+Lr 1 0.0027 1.595 0.0000 0.000
.
Load Combination Support 1 Support 2
Vertical Reactions Support notation : Far left is #1 Values in KIPS
Max Upward from all Load Conditions 0.538 0.538
Max Upward from Load Combinations 0.538 0.538
Max Upward from Load Cases 0.355 0.355
D Only 0.183 0.183
+D+Lr 0.538 0.538
+D+0.750Lr 0.450 0.450
+0.60D 0.110 0.110
Lr Only 0.355 0.355
2710 N Laird St & 2209 W
Laramore Ln10/7/2024
Wood Beam
LIC# : KW-06014251, Build:20.23.12.07 GET STRUCTURAL ENGINEERING AND CONSULTING (c) ENERCALC INC 1983-2023
DESCRIPTION:12 - C.B.
Project File: 2710 Laird Ave Member Check.ec6
Project Title:
Engineer:
Project ID:
Project Descr:
CODE REFERENCES
Calculations per NDS 2018, IBC 2021, ASCE 7-16
Load Combination Set : ASCE 7-16
Material Properties
Beam Bracing :Completely Unbraced
Allowable Stress Design
Douglas Fir-Larch
No.2
900
900
1350
625
1600
580
180
575 31.21
Analysis Method :
Eminbend - xx ksi
Wood Species :
Wood Grade :
Fb +
psi
psi
Fv psi
Fb -
Ft psi
Fc - Prll psi
psiFc - Perp
E : Modulus of Elasticity
Ebend- xx ksi
Density pcf
Load Combination :ASCE 7-16
.Applied Loads Service loads entered. Load Factors will be applied for calculations.
Beam self weight calculated and added to loading
Uniform Load : D = 0.0050, L = 0.010 ksf, Tributary Width = 7.125 ft, (Ceiling)
Point Load : D = 0.5180, Lr = 0.8450 k @ 0.750 ft, (Hip)
Point Load : D = 0.5180, Lr = 0.8450 k @ 0.750 ft, (Hip)
Point Load : D = 0.180, Lr = 0.360 k @ 0.750 ft, (BEAM 11)
.DESIGN SUMMARY Design OK
Maximum Bending Stress Ratio 0.521: 1
Load Combination +D+Lr
Span # where maximum occurs Span # 1
Location of maximum on span 0.754 ft
152.18 psi=
=
1,454.26 psi
4x8Section used for this span
Span # where maximum occurs
Location of maximum on span
Span # 1=
Load Combination +D+Lr
=
=
=
225.00 psi==
Section used for this span 4x8
Maximum Shear Stress Ratio 0.676 : 1
0.000 ft=
=
757.36 psi
Maximum Deflection
0 <360
2436
Ratio =0 <240
Max Downward Transient Deflection 0.010 in 4036Ratio =>=360
Max Upward Transient Deflection 0 in Ratio =
Max Downward Total Deflection 0.016 in Ratio =>=240
Max Upward Total Deflection 0 in
fb: Actual
F'b
fv: Actual
F'v
Span: 1 : Lr Only
n/a
Span: 1 : +D+Lr
n/a
.Maximum Forces & Stresses for Load Combinations
Span #
Moment ValuesLoad Combination
C iCLx CCCMCF rt
Shear ValuesMax Stress Ratios
M CDV fbM fvF'b V F'vSegment Length Cfu
D Only 0.0 0.00 0.00.0
1.00Length = 3.330 ft 1 0.278 0.360 0.90 1.300 1.001.00 1.00 0.75 291.8 1,048.8 0.99 162.01.00 58.31.00
1.00+D+L 1.300 1.001.00 1.00 0.0 0.00 0.01.00 0.01.00
1.00Length = 3.330 ft 1 0.274 0.349 1.00 1.300 1.001.00 1.00 0.81 318.9 1,164.8 1.06 180.01.00 62.81.00
1.00+D+Lr 1.300 1.001.00 1.00 0.0 0.00 0.01.00 0.01.00
0.99Length = 3.330 ft 1 0.521 0.676 1.25 1.300 1.001.00 1.00 1.94 757.4 1,454.3 2.57 225.01.00 152.21.00
0.99+D+0.750Lr+0.750L 1.300 1.001.00 1.00 0.0 0.00 0.01.00 0.01.00
0.99Length = 3.330 ft 1 0.455 0.587 1.25 1.300 1.001.00 1.00 1.69 661.3 1,454.3 2.23 225.01.00 132.11.00
2710 N Laird St & 2209 W
Laramore Ln10/7/2024
Wood Beam
LIC# : KW-06014251, Build:20.23.12.07 GET STRUCTURAL ENGINEERING AND CONSULTING (c) ENERCALC INC 1983-2023
DESCRIPTION:12 - C.B.
Project File: 2710 Laird Ave Member Check.ec6
Project Title:
Engineer:
Project ID:
Project Descr:
Maximum Forces & Stresses for Load Combinations
Span #
Moment ValuesLoad Combination
C iCLx CCCMCF rt
Shear ValuesMax Stress Ratios
M CDV fbM fvF'b V F'vSegment Length Cfu
0.99+D+0.750L 1.300 1.001.00 1.00 0.0 0.00 0.01.00 0.01.00
0.99Length = 3.330 ft 1 0.233 0.298 1.15 1.300 1.001.00 1.00 0.80 312.1 1,338.6 1.04 207.01.00 61.71.00
0.99+0.60D 1.300 1.001.00 1.00 0.0 0.00 0.01.00 0.01.00
0.99Length = 3.330 ft 1 0.094 0.121 1.60 1.300 1.001.00 1.00 0.45 175.1 1,858.1 0.59 288.01.00 35.01.00
.
Location in SpanLoad CombinationMax. "-" Defl Location in SpanLoad Combination Span Max. "+" Defl
Overall Maximum Deflections
+D+Lr 1 0.0164 1.471 0.0000 0.000
.
Load Combination Support 1 Support 2
Vertical Reactions Support notation : Far left is #1 Values in KIPS
Max Upward from all Load Conditions 2.599 0.804
Max Upward from Load Combinations 2.599 0.804
Max Upward from Load Cases 1.588 0.462
D Only 1.011 0.342
+D+L 1.129 0.461
+D+Lr 2.599 0.804
+D+0.750Lr+0.750L 2.291 0.778
+D+0.750L 1.100 0.431
+0.60D 0.606 0.205
Lr Only 1.588 0.462
L Only 0.119 0.119
2710 N Laird St & 2209 W
Laramore Ln10/7/2024
Stud Calc
Stud Height L =8.00 ft
Stud Spacing s =16.00 in
Height of Wall z =8.00 ft
Elevation Height zg =112 ft
Wind Speed V =95 mph
Wind Exposure C
Latera Load
Effective Area =28.4 ft2
Wind Directionality Kd =0.85
Topography Factor Kt =1.00
Ground Elevation Factor Ke =1.00
Velocity Pressure Exposure Coefficient Kz =0.85
Velocity Pressure qz = 0.00256KzKztKdKeV2 =16.60 psf
Internal Pressure Coefficient (GCpi)=-0.18
External Pressure GCp =-1.38
Wind pressure =-25.9 psf
Axial Load D+Lr A
Dead Load PD =473 lbs
Roof Live Load PLr =342 lbs
Live Load PL =0 lbs
Snow Load Ps =0 lbs
Breadth b =1.5 in
Depth d =3.5 in
ASD Load Pa = 815 lbs
Actual Compressive Stress fc = Pa / (bd)=155 psi
Grade No. 2
Compressive Stress Fc =1350 psi
Minimum Modulus of Elasticity Emin =580000 psi
Effective Length le =96 in
Buckling Coefficient k =1.0
Slender Ratio le / d =27.4 < 50 OK
Size Factor CF =1
Load Duration Factor CD =1.25
Compression Stress Design Fc* = Fc bdCDCF =1688 psi
c =0.8
=634 psi
Column Stability Factor =0.34
Compressive Load Allowed F'c = Fc
* * CP =574 psi
Demand Capacity Ratio DCR = fc / F'c =0.270
F 0.822E
l
d
C
1 F
F ∗
2c
1 F
F ∗
2c
F
F ∗
c
A sL
3
p q GC GC
2710 N Laird St & 2209 W
Laramore Ln10/7/2024
Moment D+0.6W
Wind Load Wa = p * s =20.7 plf
Moment =165.5 lb-ft
Section Modulus Sx = bd2 / 6 =3.06 in3
Bending Stress fb = M / Sx =648 psi
Design Bending Stress Fb =900 psi
Repetitive Member Factor Cr =1.15
Load Duration CD =1.6
Size Factor CF =1
F*
b =1656 psi
Effective Length le = 1.63L + 3d =13.9 ft
Slenderness Ratio =16.12 < 50 OK
Beam Stability Factor CL =1.00
F'b = F*b CL =1656 psi
Demand Capacity Ratio DCR = fb / F'b =0.39 < 1 OK
Interaction Equatio D+0.75L+75(0.6W)+0.75Lr
Bending and Compression Capacity =0.32 < 1 OK
R l d
b
f
F
f
F
M wl
8
2710 N Laird St & 2209 W
Laramore Ln10/7/2024
!"#$%!&''()*!"&+ '(,,( )*-&'