Project :
Project Number:
By :
Date :
UNIRAC
1411 Broadway Blvd, NE
Albuquerque, NM 87102
RE: Solar Array Installation at 2714 W Carlton Pl, Santa Ana, CA 92704, USA
To Whom it May Concern,
CODE REFERENCES:
BUILDING CODE: 2022 CALIFORNIA BUILDING CODE
2021 INTERNATIONAL BUILDING CODE
ASCE 7-16
SCOPE OF WORK:
DESIGN PARAMETERS
RISK CATEGORY :
DESIGN WIND SPEED :mph
WIND EXPOSURE :
GROUND SNOW LOAD :psf
SEISMIC DESIGN CATEGORY :
EXISTING ROOF STRUCTURE
ROOF : 2x6 Rafters @ 24" O.C.
ROOF MATERIAL : Comp Shingle
CONNECTION TO ROOF STRUCTURE
MOUNTING CONNECTION : (1) 5/16" SS LAG BOLT w/ MIN. 2.5" EMBEDMENT INTO (E) 2x FRAMING MEMBER
@ MAX. 48" o.c. ALONG RAILS
(2) RAILS PER ROW OF PANELS, EVENLY SPACED. PANEL LENGTH
PERPENDICULAR TO RAIL NOT TO EXCEED 67.79"
II
95
B
0
*null
John Patrick Alcoran
PE
17-02-2023
Roof structural framing plan has been reviewed for additional loading due to installation of the roof mounted
solar PV addition. The structural review that follows, including plans and calculations, only apply to the section of
the roof that is directly supporting the solar PV system and its supporting elements.
17 February 2023
Per your request, we have reviewed the existing structure at the above referenced site. The purpose of our review
was to determine the adequacy of the existing structure to support the proposed installation of solar panels on the
roof per layout plan.
2714 W Carlton Pl
04/04/23
OBSERVED CONDITIONS:
CONCLUSIONS:
LIMITATIONS:
Praneet R Erusu, P.E.
Principal Engineer
Erusu Consultants US Inc.
The observed roof framing is described below. If field conditions differ, the contractor shall notify the engineer
prior to starting construction. The roof framing is supported by 2x6 Rafters @ 24" O.C are spanning between
load bearing walls. The maximum allowed clear span of rafter is 12.5ft, to be verified in field by the contractor.
Based upon our review, we conclude that the existing structure is adequate to support the proposed solar panel
installation. In the area of the solar array, other live loads will not be present or will be greatly reduced (2022 CBC,
Section 1607.14.4). The gravity loads and the stresses of the structural elements, in the area of the solar array are
either decreased or increased by no more than 5%. Therefore, the requirements of Section 503.3 of the 2022
CEBC are met and the structure is permitted to remain unaltered.
The solar array will be flush-mounted (no more than 6" above the roof surface) and parallel to the roof surface.
Thus, we conclude that any additional wind loading on the structure related to the addition of the proposed solar
array is negligible. The attached calculations verify the capacity of the connections of the solar array to the existing
roof against wind (uplift), the governing load case. Regarding seismic loads, we conclude that any additional forces
will be small. Conservatively neglecting the weight of existing wall materials, the installation of the solar panels
represents an increase in the total weight (and resulting seismic load) of 2.3%. Because the increase in lateral
forces is less than 10%, this addition meets the requirements of the exception in Section 503.4 of the 2022 CEBC.
Thus the existing lateral force resisting system is permitted to remain unaltered.
Installation of the solar panels must be performed in accordance with manufacturer recommendations. All work
performed must be in accordance with accepted industry-wide methods and applicable safety standards. Existing
Roof and structural members are assumed to be in good and serviceable condition. The contractor must notify
Erusu Consultants US Inc. should any damage, deterioration or discrepancies between the as-built condition of
the structure and the condition described in this letter be found. The use of solar panel support span tables
provided by others are allowed only where the building type, site conditions, site-specific design parameters, and
solar panel configuration match the description of the span tables. The design of the solar panel racking (mounts,
rails, etc.) and electrical engineering is the responsibility of others. Waterproofing around the roof penetrations is
the responsibility of others. Erusu Consultants US Inc. assumes no responsibility for improper installation of the
solar array.
17 Feb 2023
EXP : 30 Sep 2023
2714 W Carlton Pl
04/04/23
Project :
Project Number:
By :
Date :
Address :
Site Plan:
John Patrick Alcoran
PE
17-02-2023
2714 W Carlton Pl, Santa Ana, CA 92704, USA
2714 W Carlton Pl
04/04/23
Project :
Project Number:
By :
Date :
Roof Dead Load
Roof Slope =:
Angle =
Roof Live Load
Roof Live Load = psf (Refer ASCE 7-16, Table 4.3-1)
Roof Live Load with PV Array = psf 2022 CBC, Section 1607.14.4
(Ceiling load and MEP is assumed to be not supported by rafter)
20
0
PV Array 3 1.05
2.2 1.05
MEP & Misc.1.5
Comp Shingle 4 1.05
4 12
18
Material
Material Weight
(psf)
2.32
1.50
12.88
1/2" Plywood 1.1 1.05
Framing 3 1.05
3.16
1/2" Gypsum Ceiling
John Patrick Alcoran
PE
17-02-2023
DL =
Increase due to
Roof Slope
Plan Projected Material
Weight (psf)
4.22
1.16
3.16
0.53Insulation0.5 1.05
2714 W Carlton Pl
04/04/23
Project :
Project Number:
By :
Date :
John Patrick Alcoran
PE
17-02-2023
Summary of Gravity Loads
Dead Load, D =psf
Roof Live Load, Lr =psf
Gravity Load Comparison
(D + Lr)/Cd =psf
(Cd = 0.9 for D, 1.15 for S, 1.25 for Lr)
Max Loading =psf
Proposed to Current Loading Ratio =O.K.
Gravity Loading with PV Array is not stressing the current framing system by more that 5% of the original
configuration. Per Section 503.3 of 2022 California Existing Building Code the structure is allowed to remain
unaltered for gravity loading
30.32 17.83
59% < 105%
30.32 17.83
20.00 0.00
Existing With PV Array
Existing With PV Array
12.88 16.05
2714 W Carlton Pl
04/04/23
Wood Beam
LIC# : KW-06014559, Build:20.22.12.28 ERUSU CONSULTANTS US (c) ENERCALC INC 1983-2022
DESCRIPTION: 2x6 Rafters @ 24" o.c. (Wind Condition_Downward) (Strength Check)
Project File: 2x6 Joist @ 24 O.C_ Copy.ec6
Project Title:
Engineer:
Project ID:
Printed: 17 FEB 2023, 12:39PM
Project Descr:
CODE REFERENCES
Calculations per NDS 2018, IBC 2021, ASCE 7-16
Load Combination Set : ASCE 7-16
Material Properties
Beam Bracing : Beam is Fully Braced against lateral-torsional buckling Repetitive Member Stress Increase
Allowable Stress Design
Douglas Fir-Larch
No.2
900.0
900.0
1,350.0
625.0
1,600.0
580.0
180.0
575.0 31.210
Analysis Method :
Eminbend - xx ksi
Wood Species :
Wood Grade :
Fb +
psi
psi
Fv psi
Fb -
Ft psi
Fc - Prll psi
psiFc - Perp
E : Modulus of Elasticity
Ebend- xx ksi
Density pcf
Load Combination :ASCE 7-16
. Applied Loads Service loads entered. Load Factors will be applied for calculations.
Beam self weight NOT internally calculated and added
Load for Span Number 1
Uniform Load : D = 0.00810, Lr = 0.020, W = 0.0160 ksf, Tributary Width = 2.0 ft, (Existing Roof Load)
Load for Span Number 2
Uniform Load : D = 0.00810 ksf, Tributary Width = 2.0 ft, (Existing Roof Dead Load)
Point Load : D = 0.0340, W = 0.1810 k @ 3.70 ft, (Solar Panel Load)
Point Load : D = 0.0340, W = 0.1810 k @ 7.0 ft, (Solar Panel Load)
Uniform Load : Lr = 0.020, W = 0.0160 ksf, Extent = 0.0 -->> 2.70 ft, Tributary Width = 2.0 ft, (Existing Wind & Roof Live Load)
.DESIGN SUMMARY Design OK
Maximum Bending Stress Ratio 0.942: 1
Load Combination +D+0.60W+H
Span # where maximum occurs Span # 2
Location of maximum on span 6.983 ft
59.01 psi=
=
1,656.00 psi
2x6 Section used for this span
Span # where maximum occurs
Location of maximum on span
Span # 1=
Load Combination +D+0.750Lr+0.750L+0.450W+H
=
=
=
288.00 psi==
Section used for this span 2x6
Maximum Shear Stress Ratio 0.205 : 1
2.000 ft=
=
1,559.34 psi
Maximum Deflection
134 >=134
186
Ratio =118 >=117
Max Downward Transient Deflection 0.706 in 212 Ratio =>=134
Max Upward Transient Deflection -0.357 in Ratio =
Max Downward Total Deflection 0.805 in Ratio =>=117
Max Upward Total Deflection -0.400 in
fb: Actual
F'b
fv: Actual
F'v
Span: 2 : W Only
Span: 1 : W Only
Span: 2 : +D+0.60W+H
Span: 1 : +D+0.60W+H
.Maximum Forces & Stresses for Load Combinations
Span #
Moment ValuesLoad Combination
C i CLx CCCM C F r t
Shear ValuesMax Stress Ratios
M CD V fb M fv F'b V F'v Segment Length Cfu
+D+H 0.0 0.00 0.00.0
1.00 Length = 2.0 ft 1 0.055 0.153 0.90 1.300 1.15 1.00 1.00 0.03 51.4 931.5 0.14 162.01.00 24.7 1.00
1.00 Length = 12.50 ft 2 0.781 0.153 0.90 1.300 1.15 1.00 1.00 0.46 727.3 931.5 0.14 162.01.00 24.7 1.00
1.00 +D+L+H 1.300 1.151.00 1.00 0.0 0.00 0.01.00 0.0 1.00
1.00 Length = 2.0 ft 1 0.050 0.137 1.00 1.300 1.15 1.00 1.00 0.03 51.4 1,035.0 0.14 180.01.00 24.7 1.00
2714 W Carlton Pl
04/04/23
Wood Beam
LIC# : KW-06014559, Build:20.22.12.28 ERUSU CONSULTANTS US (c) ENERCALC INC 1983-2022
DESCRIPTION: 2x6 Rafters @ 24" o.c. (Wind Condition_Downward) (Strength Check)
Project File: 2x6 Joist @ 24 O.C_ Copy.ec6
Project Title:
Engineer:
Project ID:
Printed: 17 FEB 2023, 12:39PM
Project Descr:
Maximum Forces & Stresses for Load Combinations
Span #
Moment ValuesLoad Combination
C iCLx CCCM C F r t
Shear ValuesMax Stress Ratios
M CD V fb M fv F'b V F'vSegment Length Cfu
1.00 Length = 12.50 ft 2 0.703 0.137 1.00 1.300 1.15 1.00 1.00 0.46 727.3 1,035.0 0.14 180.01.00 24.7 1.00
1.00 +D+Lr+H 1.300 1.15 1.00 1.00 0.0 0.00 0.01.00 0.0 1.00
1.00 Length = 2.0 ft 1 0.138 0.179 1.25 1.300 1.15 1.00 1.00 0.11 178.4 1,293.8 0.22 225.01.00 40.4 1.00
1.00 Length = 12.50 ft 2 0.601 0.179 1.25 1.300 1.15 1.00 1.00 0.49 777.0 1,293.8 0.22 225.01.00 40.4 1.00
1.00 +D+S+H 1.300 1.15 1.00 1.00 0.0 0.00 0.01.00 0.0 1.00
1.00 Length = 2.0 ft 1 0.043 0.119 1.15 1.300 1.15 1.00 1.00 0.03 51.4 1,190.3 0.14 207.01.00 24.7 1.00
1.00 Length = 12.50 ft 2 0.611 0.119 1.15 1.300 1.15 1.00 1.00 0.46 727.3 1,190.3 0.14 207.01.00 24.7 1.00
1.00 +D+0.750Lr+0.750L+H 1.300 1.15 1.00 1.00 0.0 0.00 0.01.00 0.0 1.00
1.00 Length = 2.0 ft 1 0.113 0.162 1.25 1.300 1.15 1.00 1.00 0.09 146.6 1,293.8 0.20 225.01.00 36.4 1.00
1.00 Length = 12.50 ft 2 0.591 0.162 1.25 1.300 1.15 1.00 1.00 0.48 764.3 1,293.8 0.20 225.01.00 36.4 1.00
1.00 +D+0.750L+0.750S+H 1.300 1.151.00 1.00 0.0 0.00 0.01.00 0.0 1.00
1.00 Length = 2.0 ft 1 0.043 0.119 1.15 1.300 1.15 1.00 1.00 0.03 51.4 1,190.3 0.14 207.01.00 24.7 1.00
1.00 Length = 12.50 ft 2 0.611 0.119 1.15 1.300 1.15 1.00 1.00 0.46 727.3 1,190.3 0.14 207.01.00 24.7 1.00
1.00 +D+0.60W+H 1.300 1.15 1.00 1.00 0.0 0.00 0.01.00 0.0 1.00
1.00 Length = 2.0 ft 1 0.068 0.190 1.60 1.300 1.15 1.00 1.00 0.07 112.3 1,656.0 0.30 288.01.00 54.8 1.00
1.00 Length = 12.50 ft 2 0.942 0.190 1.60 1.300 1.15 1.00 1.00 0.98 1,559.3 1,656.0 0.30 288.01.00 54.8 1.00
1.00 +D+0.750Lr+0.750L+0.450W+H 1.300 1.15 1.00 1.00 0.0 0.00 0.01.00 0.0 1.00
1.00 Length = 2.0 ft 1 0.116 0.205 1.60 1.300 1.15 1.00 1.00 0.12 192.3 1,656.0 0.32 288.01.00 59.0 1.00
1.00 Length = 12.50 ft 2 0.837 0.205 1.60 1.300 1.15 1.00 1.00 0.87 1,385.6 1,656.0 0.32 288.01.00 59.0 1.00
1.00 +D+0.750L+0.750S+0.450W+H 1.300 1.15 1.00 1.00 0.0 0.00 0.01.00 0.0 1.00
1.00 Length = 2.0 ft 1 0.059 0.164 1.60 1.300 1.15 1.00 1.00 0.06 97.1 1,656.0 0.26 288.01.00 47.3 1.00
1.00 Length = 12.50 ft 2 0.816 0.164 1.60 1.300 1.15 1.00 1.00 0.85 1,351.1 1,656.0 0.26 288.01.00 47.3 1.00
1.00 +0.60D+0.60W+0.60H 1.300 1.15 1.00 1.00 0.0 0.00 0.01.00 0.0 1.00
1.00 Length = 2.0 ft 1 0.055 0.156 1.60 1.300 1.15 1.00 1.00 0.06 91.8 1,656.0 0.25 288.01.00 44.9 1.00
1.00 Length = 12.50 ft 2 0.766 0.156 1.60 1.300 1.15 1.00 1.00 0.80 1,268.8 1,656.0 0.25 288.01.00 44.9 1.00
1.00 +D+0.70E+0.60H 1.300 1.15 1.00 1.00 0.0 0.00 0.01.00 0.0 1.00
1.00 Length = 2.0 ft 1 0.031 0.086 1.60 1.300 1.15 1.00 1.00 0.03 51.4 1,656.0 0.14 288.01.00 24.7 1.00
1.00 Length = 12.50 ft 2 0.439 0.086 1.60 1.300 1.15 1.00 1.00 0.46 727.3 1,656.0 0.14 288.01.00 24.7 1.00
1.00 +D+0.750L+0.750S+0.5250E+H 1.300 1.15 1.00 1.00 0.0 0.00 0.01.00 0.0 1.00
1.00 Length = 2.0 ft 1 0.031 0.086 1.60 1.300 1.15 1.00 1.00 0.03 51.4 1,656.0 0.14 288.01.00 24.7 1.00
1.00 Length = 12.50 ft 2 0.439 0.086 1.60 1.300 1.15 1.00 1.00 0.46 727.3 1,656.0 0.14 288.01.00 24.7 1.00
1.00 +0.60D+0.70E+H 1.300 1.15 1.00 1.00 0.0 0.00 0.01.00 0.0 1.00
1.00 Length = 2.0 ft 1 0.019 0.051 1.60 1.300 1.15 1.00 1.00 0.02 30.8 1,656.0 0.08 288.01.00 14.8 1.00
1.00 Length = 12.50 ft 2 0.264 0.051 1.60 1.300 1.15 1.00 1.00 0.28 436.4 1,656.0 0.08 288.01.00 14.8 1.00
.
Location in SpanLoad CombinationMax. "-" Defl Location in Span Load Combination Span Max. "+" Defl
Overall Maximum Deflections
+D+0.60W+H10.0000 0.000 -0.4005 0.000
+D+0.60W+H 2 0.8046 6.215 0.0000 0.000
.
Load Combination Support 1 Support 2 Support 3
Vertical Reactions Support notation : Far left is #1 Values in KIPS
Max Upward from all Load Conditions 0.471 0.223
Max Upward from Load Combinations 0.471 0.223
Max Upward from Load Cases 0.353 0.159
+D+H 0.175 0.128
+D+L+H 0.175 0.128
+D+Lr+H 0.358 0.133
+D+S+H 0.175 0.128
+D+0.750Lr+0.750L+H 0.312 0.132
+D+0.750L+0.750S+H 0.175 0.128
2714 W Carlton Pl
04/04/23
Wood Beam
LIC# : KW-06014559, Build:20.22.12.28 ERUSU CONSULTANTS US (c) ENERCALC INC 1983-2022
DESCRIPTION: 2x6 Rafters @ 24" o.c. (Wind Condition_Downward) (Strength Check)
Project File: 2x6 Joist @ 24 O.C_ Copy.ec6
Project Title:
Engineer:
Project ID:
Printed: 17 FEB 2023, 12:39PM
Project Descr:
Load Combination Support 1 Support 2 Support 3
Vertical Reactions Support notation : Far left is #1 Values in KIPS
+D+0.60W+H 0.387 0.223
+D+0.750Lr+0.750L+0.450W+H 0.471 0.203
+D+0.750L+0.750S+0.450W+H 0.334 0.199
+0.60D+0.60W+0.60H 0.317 0.172
+D+0.70E+0.60H 0.175 0.128
+D+0.750L+0.750S+0.5250E+H 0.175 0.128
+0.60D+0.70E+H 0.105 0.077
D Only 0.175 0.128
Lr Only 0.183 0.005
W Only 0.353 0.159
H Only
2714 W Carlton Pl
04/04/23
Wood Beam
LIC# : KW-06014559, Build:20.22.12.28 ERUSU CONSULTANTS US (c) ENERCALC INC 1983-2022
DESCRIPTION: 2x6 Rafters @ 24" o.c. (Wind Condition_Uplift) (Strength Check)
Project File: 2x6 Joist @ 24 O.C_ Copy.ec6
Project Title:
Engineer:
Project ID:
Printed: 17 FEB 2023, 12:39PM
Project Descr:
CODE REFERENCES
Calculations per NDS 2018, IBC 2021, ASCE 7-16
Load Combination Set : ASCE 7-16
Material Properties
Beam Bracing : Beam is Fully Braced against lateral-torsional buckling Repetitive Member Stress Increase
Allowable Stress Design
Douglas Fir-Larch
No.2
900.0
900.0
1,350.0
625.0
1,600.0
580.0
180.0
575.0 31.210
Analysis Method :
Eminbend - xx ksi
Wood Species :
Wood Grade :
Fb +
psi
psi
Fv psi
Fb -
Ft psi
Fc - Prll psi
psiFc - Perp
E : Modulus of Elasticity
Ebend- xx ksi
Density pcf
Load Combination :ASCE 7-16
. Applied Loads Service loads entered. Load Factors will be applied for calculations.
Beam self weight NOT internally calculated and added
Load for Span Number 1
Uniform Load : D = 0.00810, Lr = 0.020, W = -0.0350 ksf, Tributary Width = 2.0 ft, (Existing Roof Load)
Load for Span Number 2
Uniform Load : D = 0.00810 ksf, Tributary Width = 2.0 ft, (Existing Roof Dead Load)
Point Load : D = 0.0340, W = -0.3980 k @ 3.70 ft, (Solar Panel Load)
Point Load : D = 0.0340, W = -0.3980 k @ 7.0 ft, (Solar Panel Load)
Uniform Load : Lr = 0.020, W = -0.0350 ksf, Extent = 0.0 -->> 2.70 ft, Tributary Width = 2.0 ft, (Existing Wind & Roof Live Load)
.DESIGN SUMMARY Design OK
Maximum Bending Stress Ratio 0.843: 1
Load Combination +0.60D+0.60W+0.60H
Span # where maximum occurs Span # 2
Location of maximum on span 6.983 ft
40.35 psi=
=
1,656.00 psi
2x6 Section used for this span
Span # where maximum occurs
Location of maximum on span
Span # 1=
Load Combination +D+Lr+H
=
=
=
225.00 psi==
Section used for this span 2x6
Maximum Shear Stress Ratio 0.179 : 1
2.000 ft=
=
1,395.64 psi
Maximum Deflection
96 >=60
132
Ratio =213 >=120
Max Downward Transient Deflection 0.784 in 60 Ratio =>=60
Max Upward Transient Deflection -1.552 in Ratio =
Max Downward Total Deflection 0.359 in Ratio =>=120
Max Upward Total Deflection -0.703 in
fb: Actual
F'b
fv: Actual
F'v
Span: 2 : Lr Only
Span: 2 : W Only
Span: 2 : +D+Lr+H
Span: 2 : +0.60D+0.60W+0.60H
.Maximum Forces & Stresses for Load Combinations
Span #
Moment ValuesLoad Combination
C i CLx CCCM C F r t
Shear ValuesMax Stress Ratios
M CD V fb M fv F'b V F'v Segment Length Cfu
+D+H 0.0 0.00 0.00.0
1.00 Length = 2.0 ft 1 0.055 0.153 0.90 1.300 1.15 1.00 1.00 0.03 51.4 931.5 0.14 162.01.00 24.7 1.00
1.00 Length = 12.50 ft 2 0.781 0.153 0.90 1.300 1.15 1.00 1.00 0.46 727.3 931.5 0.14 162.01.00 24.7 1.00
1.00 +D+L+H 1.300 1.151.00 1.00 0.0 0.00 0.01.00 0.0 1.00
1.00 Length = 2.0 ft 1 0.050 0.137 1.00 1.300 1.15 1.00 1.00 0.03 51.4 1,035.0 0.14 180.01.00 24.7 1.00
2714 W Carlton Pl
04/04/23
Wood Beam
LIC# : KW-06014559, Build:20.22.12.28 ERUSU CONSULTANTS US (c) ENERCALC INC 1983-2022
DESCRIPTION: 2x6 Rafters @ 24" o.c. (Wind Condition_Uplift) (Strength Check)
Project File: 2x6 Joist @ 24 O.C_ Copy.ec6
Project Title:
Engineer:
Project ID:
Printed: 17 FEB 2023, 12:39PM
Project Descr:
Maximum Forces & Stresses for Load Combinations
Span #
Moment ValuesLoad Combination
C iCLx CCCM C F r t
Shear ValuesMax Stress Ratios
M CD V fb M fv F'b V F'vSegment Length Cfu
1.00 Length = 12.50 ft 2 0.703 0.137 1.00 1.300 1.15 1.00 1.00 0.46 727.3 1,035.0 0.14 180.01.00 24.7 1.00
1.00 +D+Lr+H 1.300 1.15 1.00 1.00 0.0 0.00 0.01.00 0.0 1.00
1.00 Length = 2.0 ft 1 0.138 0.179 1.25 1.300 1.15 1.00 1.00 0.11 178.4 1,293.8 0.22 225.01.00 40.4 1.00
1.00 Length = 12.50 ft 2 0.601 0.179 1.25 1.300 1.15 1.00 1.00 0.49 777.0 1,293.8 0.22 225.01.00 40.4 1.00
1.00 +D+S+H 1.300 1.15 1.00 1.00 0.0 0.00 0.01.00 0.0 1.00
1.00 Length = 2.0 ft 1 0.043 0.119 1.15 1.300 1.15 1.00 1.00 0.03 51.4 1,190.3 0.14 207.01.00 24.7 1.00
1.00 Length = 12.50 ft 2 0.611 0.119 1.15 1.300 1.15 1.00 1.00 0.46 727.3 1,190.3 0.14 207.01.00 24.7 1.00
1.00 +D+0.750Lr+0.750L+H 1.300 1.15 1.00 1.00 0.0 0.00 0.01.00 0.0 1.00
1.00 Length = 2.0 ft 1 0.113 0.162 1.25 1.300 1.15 1.00 1.00 0.09 146.6 1,293.8 0.20 225.01.00 36.4 1.00
1.00 Length = 12.50 ft 2 0.591 0.162 1.25 1.300 1.15 1.00 1.00 0.48 764.3 1,293.8 0.20 225.01.00 36.4 1.00
1.00 +D+0.750L+0.750S+H 1.300 1.151.00 1.00 0.0 0.00 0.01.00 0.0 1.00
1.00 Length = 2.0 ft 1 0.043 0.119 1.15 1.300 1.15 1.00 1.00 0.03 51.4 1,190.3 0.14 207.01.00 24.7 1.00
1.00 Length = 12.50 ft 2 0.611 0.119 1.15 1.300 1.15 1.00 1.00 0.46 727.3 1,190.3 0.14 207.01.00 24.7 1.00
1.00 +D+0.60W+H 1.300 1.15 1.00 1.00 0.0 0.00 0.01.00 0.0 1.00
1.00 Length = 2.0 ft 1 0.049 0.144 1.60 1.300 1.15 1.00 1.00 0.05 81.9 1,656.0 0.23 288.01.00 41.4 1.00
1.00 Length = 12.50 ft 2 0.667 0.144 1.60 1.300 1.15 1.00 1.00 0.70 1,105.1 1,656.0 0.23 288.01.00 41.4 1.00
1.00 +D+0.750Lr+0.750L+0.450W+H 1.300 1.15 1.00 1.00 0.0 0.00 0.01.00 0.0 1.00
1.00 Length = 2.0 ft 1 0.028 0.042 1.60 1.300 1.15 1.00 1.00 0.03 46.7 1,656.0 0.07 288.01.00 12.0 1.00
1.00 Length = 12.50 ft 2 0.370 0.076 1.60 1.300 1.15 1.00 1.00 0.39 612.7 1,656.0 0.12 288.01.00 22.0 1.00
1.00 +D+0.750L+0.750S+0.450W+H 1.300 1.15 1.00 1.00 0.0 0.00 0.01.00 0.0 1.00
1.00 Length = 2.0 ft 1 0.029 0.086 1.60 1.300 1.15 1.00 1.00 0.03 48.6 1,656.0 0.14 288.01.00 24.8 1.00
1.00 Length = 12.50 ft 2 0.393 0.086 1.60 1.300 1.15 1.00 1.00 0.41 650.1 1,656.0 0.14 288.01.00 24.8 1.00
1.00 +0.60D+0.60W+0.60H 1.300 1.15 1.00 1.00 0.0 0.00 0.01.00 0.0 1.00
1.00 Length = 2.0 ft 1 0.062 0.178 1.60 1.300 1.15 1.00 1.00 0.06 102.4 1,656.0 0.28 288.01.00 51.3 1.00
1.00 Length = 12.50 ft 2 0.843 0.178 1.60 1.300 1.15 1.00 1.00 0.88 1,395.6 1,656.0 0.28 288.01.00 51.3 1.00
1.00 +D+0.70E+0.60H 1.300 1.15 1.00 1.00 0.0 0.00 0.01.00 0.0 1.00
1.00 Length = 2.0 ft 1 0.031 0.086 1.60 1.300 1.15 1.00 1.00 0.03 51.4 1,656.0 0.14 288.01.00 24.7 1.00
1.00 Length = 12.50 ft 2 0.439 0.086 1.60 1.300 1.15 1.00 1.00 0.46 727.3 1,656.0 0.14 288.01.00 24.7 1.00
1.00 +D+0.750L+0.750S+0.5250E+H 1.300 1.15 1.00 1.00 0.0 0.00 0.01.00 0.0 1.00
1.00 Length = 2.0 ft 1 0.031 0.086 1.60 1.300 1.15 1.00 1.00 0.03 51.4 1,656.0 0.14 288.01.00 24.7 1.00
1.00 Length = 12.50 ft 2 0.439 0.086 1.60 1.300 1.15 1.00 1.00 0.46 727.3 1,656.0 0.14 288.01.00 24.7 1.00
1.00 +0.60D+0.70E+H 1.300 1.15 1.00 1.00 0.0 0.00 0.01.00 0.0 1.00
1.00 Length = 2.0 ft 1 0.019 0.051 1.60 1.300 1.15 1.00 1.00 0.02 30.8 1,656.0 0.08 288.01.00 14.8 1.00
1.00 Length = 12.50 ft 2 0.264 0.051 1.60 1.300 1.15 1.00 1.00 0.28 436.4 1,656.0 0.08 288.01.00 14.8 1.00
.
Location in SpanLoad CombinationMax. "-" Defl Location in Span Load Combination Span Max. "+" Defl
Overall Maximum Deflections
W Only 1 0.7842 0.000 0.0000 0.000
W Only20.0000 0.000 -1.5525 6.145
.
Load Combination Support 1 Support 2 Support 3
Vertical Reactions Support notation : Far left is #1 Values in KIPS
Max Upward from all Load Conditions 0.358 0.133
Max Upward from Load Combinations 0.358 0.133
Max Upward from Load Cases 0.183 0.128
Max Downward from all Load Conditio -0.775 -0.350
Max Downward from Load Combinations -0.360 -0.133
Max Downward from Load Cases (Resis -0.775 -0.350
+D+H 0.175 0.128
+D+L+H 0.175 0.128
+D+Lr+H 0.358 0.133
2714 W Carlton Pl
04/04/23
Wood Beam
LIC# : KW-06014559, Build:20.22.12.28 ERUSU CONSULTANTS US (c) ENERCALC INC 1983-2022
DESCRIPTION: 2x6 Rafters @ 24" o.c. (Wind Condition_Uplift) (Strength Check)
Project File: 2x6 Joist @ 24 O.C_ Copy.ec6
Project Title:
Engineer:
Project ID:
Printed: 17 FEB 2023, 12:39PM
Project Descr:
Load Combination Support 1 Support 2 Support 3
Vertical Reactions Support notation : Far left is #1 Values in KIPS
+D+S+H 0.175 0.128
+D+0.750Lr+0.750L+H 0.312 0.132
+D+0.750L+0.750S+H 0.175 0.128
+D+0.60W+H -0.290 -0.082
+D+0.750Lr+0.750L+0.450W+H -0.037 -0.026
+D+0.750L+0.750S+0.450W+H -0.174 -0.030
+0.60D+0.60W+0.60H -0.360 -0.133
+D+0.70E+0.60H 0.175 0.128
+D+0.750L+0.750S+0.5250E+H 0.175 0.128
+0.60D+0.70E+H 0.105 0.077
D Only 0.175 0.128
Lr Only 0.183 0.005
W Only -0.775 -0.350
H Only
2714 W Carlton Pl
04/04/23
Project :
Project Number:
By :
Date :
Wind Load Calculation
Wind Loads - ASCE 7-16 Chapter 26 & 29
Width of the Building, B = ft (Approximate)
V = mph
Exposure =
Average height of building, z = ft - avg (Approximate)
ft (Refer ASCE 7-16, Table 26.10-1)
α = Zg = ft (Refer ASCE 7-16, Table 26.11-1)
Kh & Kz = 2.01(z/Zg)^(2/α) =
Kzt =(Refer ASCE 7-16, Equation 26.8-1)
Kd =(Refer ASCE 7-16, Table 26.6.1)
Ke =(Refer ASCE 7-16, Table 26.9-1)
qh ='.00256 KzKztKdKeV² =psf (Refer ASCE 7-16, Section 26.10-1)
Building Classification =
Solar Panel
Components and Cladding p C&C = qh(GCp)(ϒe)(ϒa) ASCE 7-16 Chaper 29.4.4
Module Length = in
Module Width = in
Area of Module = ft2
Roof Pitch =:
Slope = degrees
Gable Roof =
ϒe=
ϒa=(Refer ASCE 7-16, Figure 29.4-8)
12
18
21.0
67.79
7° < θ ≤ 20°
1.5
11.29
4.0
44.64
95
B
15
0.57
Enclosed
0.8
zmin = 30
7
1
47.2
1
0.85
John Patrick Alcoran
PE
17-02-2023
1200
2714 W Carlton Pl
04/04/23
Project :
Project Number:
By :
Date :
John Patrick Alcoran
PE
17-02-2023
Zone 1 Uplift
External Wind pressure coefficient GCp =
External Wind pressure, qGCp = psf
Zone 2 Uplift
External Wind pressure coefficient GCp =
External Wind pressure, qGCp = psf
All Zone Downward
External Wind pressure coefficient GCp =
External Wind pressure, qGCp = psf
Maximum Uplift Wind Pressure, p = psf
Minimum Downward Wind Pressure ,p = psf
Lag Screw / Bolt Connection Check (ASD)
Tributary Width = in (Max Spacing of fasteners along Rails)
Tributary Length = in (Half Panel Length)
Tributary Area = ft2
Lag Screw/Bolt Size =
Cd =(Refer NDS Table 2.3.2)
Embedment = in
Grade of Wood = #2 ( or better)
G =
Capacity = lb/in (Refer NDS Table 12.2A)
Number of Screws in Tension =
Prying Coefficient =
Capacity of Fasteners = lb
Demand
Zone 1
Zone 2 0.31
Pressure ASD (0.6W)(psf)
-16.3
-21.1 11.3 238.7 760
DCR
11.3 183.6 760 0.24
Capacity (lb)Tributary Area (ft2) Uplift (lb) Zone
0.5
266
1
1.4
760
48
0.5
6.8
(Measured from top of the framing member to tapered tip of lag screw,
embedment in sheathing and tapered tip of screw is not included)
DF
-35.21
-2
-27.09
-35.21
16.0
33.895
11.3
5/16
1.6
2.5
-2.6
2714 W Carlton Pl
04/04/23
Project :
Project Number:
By :
Date :
Seismic Ground Motion Values
John Patrick Alcoran
PE
17-02-2023
2714 W Carlton Pl
04/04/23
Project :
Project Number:
By :
Date :
Seismic Design Force
Seismic Loads - ASCE 7-16 Chapter 13
Seismic Force
Component Amplification Factor, ap= (Refer ASCE 7-16, Table 13.6 -1)
Overstrength Factor, Ωo =(Refer ASCE 7-16, Table 13.6 -1)
Component Importance Factor, Ip=
SDS =
Average roof height of structure,h = ft
z/h = z/h should not exceed 1
Frame Weight Wp = psf
Seismic Design Force on Solar framing structure
Max Fp =1.6 x SDS x Ip X Wp = psf
Min Fp =0.3 x SDS x Ip X Wp = psf
Seismic Design Load Fp = psf
Vertical Seismic Design Load Fp = psf0.66
2.64
5.28
0.99
3.16
F P = ((0.4 x ap x SDS x Wp)/ (Rp / Ip)) x
((1+2(z/h)) =2.64 psf
15
1
Height in structure at point of attachment,
z =
15 ft
1.00
1.50
1.04
1.00
Seismic Coefficients for Mechanical
and Electrical components =
Component Response Modification
Factor, Rp=
1.50
John Patrick Alcoran
PE
17-02-2023
12 Other mechanical or electrical components.
(Refer ASCE 7-16, Table 13.6 -1)
2714 W Carlton Pl
04/04/23
Project :
Project Number:
By :
Date :
John Patrick Alcoran
PE
17-02-2023
Check for Increase in overall seismic loads
Array Area = ft2
Number of Arrays =
Total Array Area = ft2
Array Load = psf
Number of Existing Arrays =
Exisitng Area = ft2
Total Array Wt. = lb
Total Roof Area = ft2
DL of Roof = psf
Total Wt of Roof = lb
Increase in Seismic Wt = <
12.88
30673
2.3% 10%
Conservatively the Wt. of the Walls tributary to the roof is not included. Seismic weight increase is less than
10% and no seismic retrofit or evaluation of existing lateral system is required per Section 503.4 of 2022
CEBC.
21.0
11
231.16
2380.7
3.00
693.49
0
0.00
2714 W Carlton Pl
04/04/23
2714 W Carlton Pl
04/04/23
2714 W Carlton Pl
04/04/23
John Patrick Alcoran- Auth Letter
Final Audit Report 2023-02-17
Created:2023-02-17
By:Empower Solar (mandy@mpwrsolar.com)
Status:Signed
Transaction ID:CBJCHBCAABAAlcMy0dNvlATL_fFPCMa9_mS-tAnkXQUM
"John Patrick Alcoran- Auth Letter" History
Document created by Empower Solar (mandy@mpwrsolar.com)
2023-02-17 - 7:47:50 PM GMT- IP address: 108.88.56.142
Document e-signed by Empower Solar (mandy@mpwrsolar.com)
Signature Date: 2023-02-17 - 7:48:38 PM GMT - Time Source: server- IP address: 108.88.56.142
Document emailed to patrickalc27@gmail.com for signature
2023-02-17 - 7:48:39 PM GMT
Email viewed by patrickalc27@gmail.com
2023-02-17 - 9:21:54 PM GMT- IP address: 172.226.184.20
Signer patrickalc27@gmail.com entered name at signing as John Patrick Alcoran
2023-02-17 - 9:42:57 PM GMT- IP address: 172.56.185.238
Document e-signed by John Patrick Alcoran (patrickalc27@gmail.com)
Signature Date: 2023-02-17 - 9:42:59 PM GMT - Time Source: server- IP address: 172.56.185.238
Agreement completed.
2023-02-17 - 9:42:59 PM GMT
2714 W Carlton Pl
04/04/23
Signature:
Email:
Empower Solar (Feb 17, 2023 11:48 PST)
Empower Solar
mandy@mpwrsolar.com
John Patrick Alcoran (Feb 17, 2023 13:42 PST)
02/17/2023
2714 W Carlton Pl
04/04/23
U-BUILDER PROJECT REPORT
APPLICATION VERSION: 6.0.4
PROJECT VERSION: 0.0.27
PROJECT TITLE
NXT UMOUNT
PROJECT ID
2BD797E1
LAST UPDATED
Mar. 29, 2023
ORIGINALLY CREATED
Mar. 29, 2023
NAME John Patrick Alcoran
ADDRESS 2714 West Carlton Place Santa Ana, California - 92704
CITY, STATE Santa Ana, CA
MODULE JA Solar JAM54S31 390/MR
Designed by parley@mpwrsolar.com
NXT UMOUNT
JA Solar
11 - JAM54S31 390/MR
231.16 ft
4.29 KW
2
NOTE: Installation of the project is intended to happen within the year of project designed in UBuilder. If it's past one year please
rerun the design or contact Unirac Engineering Services.
2714 W Carlton Pl
04/04/23
ENGINEERING REPORT
* Distributed Dead Load 2.51psf
* Average Roof Point Dead Load 24.22 lbs
Plan review
TOTAL NUMBER OF MODULES 11
TOTAL KW 4.29 KW
TOTAL AREA ~231 ft
Loads Used for Design
BUILDING CODE ASCE 7-16
BASIC WIND SPEED 95.00 mph
GROUND SNOW LOAD 0.00 psf
SEISMIC (SS)1.462
ELEVATION 55.00 ft
WIND EXPOSURE B
TOPOGRAPHICAL FACTOR KZT 1.00
RISK CATEGORY II
VELOCITY PRESSURE, QZ 12.21 psf
2
Inspection
PRODUCT NXT UMOUNT
MODULE MANUFACTURER JA Solar
MODEL 11 - JAM54S31 390/MR
MODULE WATTS 390 watts
MODULE LENGTH 67.79"
MODULE WIDTH 44.64"
MODULE THICKNESS 1.18"
MODULE WEIGHT 47.39 lbs
EXPANSION JOINTS Every 40'
RAILS DIRECTION EW
BUILDING HEIGHT 20.00 ft
SHORTEST BUILDING LENGTH 20.00 ft
ROOF TYPE Shingle
ATTACHMENT TYPE StrongHold Att Kit Comp
RAFTER SPACING 24.00"
* TOTAL WEIGHT 581.37 lbs
ROW SPACING 0.50"
COLUMN SPACING 0.50"
MID CLAMP NXT UMOUNT COMBO CLAMP
END CLAMP NXT UMOUNT COMBO CLAMP
* Calculated based on suggested quantity given on part list.
2714 W Carlton Pl
04/04/23
Roof Area 1: Array 1
Portrait Modules - Rails Running Across Slope
Clamp Checks - Exposed zones
ZONES 1, 2E 2N, 2R, 3E 3R
CONNECTION-TYPE End-End End-Mid Mid-Mid End-End End-Mid Mid-Mid End-End End-Mid Mid-Mid
Up Load N/A 268 268 N/A N/A N/A N/A N/A N/A
Check OK OK OK OK OK OK OK OK OK
Side Load N/A 268 268 N/A N/A N/A N/A N/A N/A
Check OK OK OK OK OK OK OK OK OK
Lateral Load N/A 268 268 N/A N/A N/A N/A N/A N/A
NXT UMOUNT RAIL SPANS
[IN]
1, 2E 2N, 2R, 3E 3R
DESIGN SPAN (NON-
EXPOSED)
48 48 48
DESIGN SPAN (EXPOSED)48 48 48
Max Cantilever (Non-
Exposed)
16 16 16
Max Cantilever
(Exposed)
16 16 16
Max Span (Non-
Exposed)
86 86 81
Max Span (Exposed)85 74 69
ZONES 1, 2E 2N, 2R, 3E 3R
NO OF RAILS(EXPOSED)2 2 2
NO OF RAILS(NON-
EXPOSED)
2 2 2
DESIGN PRESSURES [PSF]1, 2E 2N, 2R, 3E 3R
Up (Non-Exposed)-8.0 -12.2 -15.0
Up (Exposed)-12.6 -19.1 -23.3
Down (Non-Exposed)12.3 12.3 12.3
Down (Exposed)12.3 12.3 12.3
Downslope 2.4 2.4 2.4
Lateral 1.5 1.5 1.5
MAXIMUM POINT LOADS [LBS]1, 2E 2N, 2R, 3E 3R
Up (Non-Exposed)-90.5 -138.2 -169.1
Up (Exposed)-142.2 -216.2 -262.7
Down (Non-Exposed)138.5 138.5 138.5
Down (Exposed)138.5 138.5 138.5
Downslope (Non-Exposed)27.5 27.5 27.5
Downslope (Exposed)27.5 27.5 27.5
Lateral (Non-Exposed)17.2 17.2 17.2
Lateral (Exposed)17.2 17.2 17.2
Tributary Area (Non-Exposed) [ft ] 11.3 11.3 11.3
Tributary Area (Exposed) [ft ] 11.3 11.3 11.3
ROOF PITCH:18°
2
2
2714 W Carlton Pl
04/04/23
Check OK OK OK OK OK OK OK OK OK
Clamp Checks - Non-Exposed zones
ZONES 1, 2E 2N, 2R, 3E 3R
CONNECTION-TYPE End-End End-Mid Mid-Mid End-End End-Mid Mid-Mid End-End End-Mid Mid-Mid
Up Load N/A N/A N/A N/A N/A N/A N/A N/A N/A
Check OK OK OK OK OK OK OK OK OK
Side Load N/A N/A N/A N/A N/A N/A N/A N/A N/A
Check OK OK OK OK OK OK OK OK OK
Lateral Load N/A N/A N/A N/A N/A N/A N/A N/A N/A
Check OK OK OK OK OK OK OK OK OK
N/A stands for not applicable
2714 W Carlton Pl
04/04/23
NXT UMOUNT U-BUILDER PRODUCT ASSUMPTIONS
Limitations of Responsibility: It is the user’s responsibility to ensure that inputs are correct for your specific project.
Unirac is not the solar, electrical, or building engineer of record and is not responsible for the solar, electrical, or building design for this
project.
Building Assumptions
1. Mean Roof Height = 0 – 60 ft unless otherwise specified.
2. Roof Pitch: 5° - 45° for ASCE 7-10 and 9° - 45° for ASCE 7-16
Wind Design Assumptions
1. Exposure Category B, C, or D
2. Basic Wind Speed 95 – 190 mph for ASCE 7-10, and 85-190 mph for ASCE 7-16.
3. Wind speeds are LRFD values
4. γE = 1.0 for ‘Interior’ spans, γE = 1.5 for ‘Exposed’ spans (ASCE 7-16 Sec. 29.4.3, Fig. 29.4-7)
Snow and Seismic Design Assumptions
1. Ground Snow Load = 0-100 psf
2. Thermal Factor = 1.0
3. Results based on uniform snow load
4. 0.2-s Spectral Response Acceleration, SS ≤ 3
Array Assumptions
1. Dead Load ≤ 5 psf (including PV Modules and Racking)
2. Module orientation and Rail direction per user selection
3. Module height above roof surface 5” to 10” depending on attachment type
4. Gaps between module rows and columns is 0.25”-1.0”
5. Modules are parallel to the roof surface and within 10 in. of it.
6. ‘Exposed’ spans shall be used when any part of an exposed module or panel as is attributed to that span.
7. The most restrictive of all roof zone spans shall be used when any part of the module is attributed to that span.
Intermediary Span Distances: Roof attachment point loads be reduced linearly if the installed distance between the attachments is less
than the selected span. For example, if the spacing is half the amount shown in the results, then the point loads may also be reduced by
half.
Spans greater than 72 in.: While our products are valid for greater spans in many instances, we do not recommend this mounting
configuration. Typical residential roofs are not designed for the larger point loads that might result from such excessive spans and we
recommend final design by a licensed professional engineer of responsible charge.
2714 W Carlton Pl
04/04/23
2714 W Carlton Pl
04/04/23
Bldg permit 101114494
Elect permit #20179204
Issued on 4/3/23
***The scope of the plans is for the
installation of the solar
photovoltaic system only and the
approval is subject to compliance
with all applicable city and state
codes and regulations regarding
construction. The approval of the
plans does not constitute any
certification of the accuracy,
completeness, or building permit
status of the existing buildings and
structures as shown.***
2714 W Carlton Pl
04/04/23
2714 W Carlton Pl
04/04/23
2714 W Carlton Pl
04/04/23
2714 W Carlton Pl
04/04/23
2714 W Carlton Pl
04/04/23
2714 W Carlton Pl
04/04/23
2714 W Carlton Pl
04/04/23
2714 W Carlton Pl
04/04/23
2714 W Carlton Pl
04/04/23
2714 W Carlton Pl
04/04/23
2714 W Carlton Pl
04/04/23
2714 W Carlton Pl
04/04/23
2714 W Carlton Pl
04/04/23
2714 W Carlton Pl
04/04/23
2714 W Carlton Pl
04/04/23