HomeMy WebLinkAbout2817 W Brook Street - PlanPHOTOVOLTAIC ROOF MOUNT & ENERGY SYSTEM
14 MODULES - SYSTEM SIZE STC (5.530 kW DC / 4.060 kW AC)
2817 W BROOK ST, SANTA ANA, CA 92704, USA (33.7359372, -117.9083081)
SCOPE OF WORK (5.530 kW DC / 4.060 kW AC)
STC DC: (14) 395W = 5.530 kW
STC AC: (14) 290W = 4.060 kW
STORAGE: (1) 3.84kW 10.1kWh
● (14) CANADIAN SOLAR INC. CS3N 395MS-BLK MODULES
● (14) ENPHASE ENERGY INC. IQ8PLUS-72-2-US 240V MICROINVERTERS
● (1) ENPHASE ENERGY INC. IQ BATTERY 10T FOR USMXCA BATTERIES
● (1) ENPHASE IQ SYSTEM CONTROLLER 2
● 2x BRANCHES OF 7 CONNECTED IN PARALLEL
x ATTACHMENT - SOLARHOOK FLAT 004AT1H
x RAIL: UNIRAC- SOLARMOUNT LIGHT
GOVERNING CODES
● 2022 CALIFORNIA FIRE CODE
● 2022 CALIFORNIA BUILDING CODE
● 2022 CALIFORNIA RESIDENTIAL CODE
● 2022 CALIFORNIA ELECTRICAL CODE
MAIN PANEL REPLACEMENT: EXISTING 100 AMP MAIN PANEL
WITH 100 AMP MAIN BREAKER TO BE REPLACED WITH NEW
225 AMP MAIN PANEL WITH NEW 200 AMP MAIN BREAKER.
DIG ALERT (811) IS TO BE CONTACTED AND COMPLIANCE WITH
EXCAVATION SAFETY IN ACCORDING WITH GOVERNMENT CODE 4216
WILL BE FOLLOWED, PRIOR TO ANY EXCAVATION TAKING PLACE.
THE SURGE PROTECTION DEVICE (SPD) SHALL COMPLY WITH 2022
CALIFORNIA
ELECTRICAL CODE 230.67 THE SPD MUST BE EITHER TYPE 1 OR TYPE 2.
ARRAY LOCATION(S)
PROJECT SITE
GENERAL NOTES
1) ALL PANELS, SWITCHES, ETC. SHALL HAVE SUFFICIENT GUTTER
SPACE AND LUGS IN COMPLIANCE WITH UL REQUIREMENTS TO
ACCOMMODATE CONDUCTORS SHOWN.
2) THIS SYSTEM WILL NOT BE INTERCONNECTED UNTIL APPROVAL
FROM THE LOCAL JURISDICTION AND UTILITY IS OBTAINED.
3) ALL EXTERIOR ELECTRICAL DEVICES AND EQUIPMENT
INCLUDING THOSE THAT ARE EXPOSED TO OUTSIDE
ENVIRONMENT SHALL BE WEATHERPROOF AND SHALL BE
LISTED BY 'UL' FOR THE TYPE OF APPLICATION AND 'UL' LABEL
SHALL APPEAR ON ALL ELECTRICAL EQUIPMENT.
4) WIRING METHOD SHALL BE EMT ABOVE GROUND MOUNTED IN
CONCEALED SPACES (UNLESS APPROVED OTHERWISE) AND
SCHEDULE-40 PVC FOR BELOW GROUND INSTALLATIONS
UNLESS NOTED OTHERWISE.
5) AN OSHA APPROVED LADDER PROVIDING ACCESS TO ALL
PORTIONS OF THE ARRAY SHALL BE SECURED IN PRIOR TO
REQUESTING INSPECTION.
6) IT IS THE CONTRACTOR'S RESPONSIBILITY TO INSTALL A
SUPPLEMENTAL GROUNDING ELECTRODE CONDUCTOR IF
NECESSARY.
7) OCCUPANCY TYPE: R-3
8) CONSTRUCTION TYPE: VB
9) ENPHASE DEVICES ARE WITHIN MANUFACTURER'S REQUIRED
GUIDELINE, PV ARRAY DOES NOT EXCEED MAX DISTANCE OF
150'.
10) ALL ENSEMBLE EQUIPMENT MUST BE WITHIN 50' OF EACH
OTHER.
11) IF THERE ARE COMMUNICATION ISSUES WITH GATEWAY, UB
EXTENDER CAN BE USED TO RELOCATE COMMS KIT NEAR IQ
SYSTEM CONTROLLER & BATTERY.
12) IQ BATTERY UNITS SHOULD NOT BE INSTALLED IN DIRECT
SUNLIGHT.
REV
SHEET NAME
SHEET SIZE
SHEET NUMBER
ANSI B
DATE DESCRIPTION
REVISIONS
PV-1
HOMEOWNER INFO
11" X 17"
SIGNATURE & SEAL
COVER PAGE
CONTRACTOR: COMPLETE SOLARIA
ADDRESS: 3000 EXECUTIVE PKWY, SUITE
504, SAN RAMON, CA 94583
PHONE: 8772994943
LICENSE #: 961988
JO
S
E
G
O
M
E
Z
28
1
7
W
B
R
O
O
K
S
T
,
SA
N
T
A
A
N
A
,
C
A
9
2
7
0
4
,
U
S
A
AP
N
:
1
0
9
-
7
4
1
-
1
6
PH
O
N
E
:
7
1
4
3
2
1
3
5
5
4
EM
A
I
L
:
j
o
s
e
g
o
m
e
z
1
0
1
7
5
7
@
g
m
a
i
l
.
c
o
m
COVER PAGE
HOUSE PHOTO
SCALE: NTS
VICINITY MAP
SCALE: NTS
SHEET INDEX
PV-1 COVER PAGE
PV-2 SITE PLAN
PV-3 ATTACHMENT SHEET
PV-3.1 ATTACHMENT DETAIL
PV-3.2 STRING PLAN WITH MODULES
PV-4 THREE LINE DIAGRAM
PV-4.1 EQUIPMENT ELEVATION
PV-4.2 LOAD CALCULATION
PV-4.3 PANEL SCHEDULES
PV-5 WIRING CALCULATION
PV-6 PLACARDS
PV-7+ EQUIPMENT SPECIFICATION
AHJ: SANTA ANA (CITY OF), CALIFORNIA
UTILITY: SOUTHERN CALIFORNIA EDISON CO
LE
G
E
N
D
NEW PV MODULE
FIRE SETBACK
OPTIMIZER
MICRO-INVERTER
ROOF ATTACHMENT
ROOF ACCESS POINT
DIMENSIONS
PROPERTY LINE
RAFTER/TRUSS
RAIL
FENCE
GATE
MSP MAIN SERVICE PANEL
(NEW, 225A)
UM UTILITY METER
(NEW)
PM PRODUCTION METER
(N/A)
BAT BATTERY
(NEW)
INV (0) INVERTER
(N/A)
LC LOAD CENTER (COMBINER
PANEL) (NEW)
SM SOLAREDGE METER
(N/A)
BLP BACKUP LOAD PANEL
(N/A)
AC AC DISCONNECT UNFUSED
(NEW)
ACF AC DISCONNECT FUSED
(N/A)
JB JUNCTION BOX
(NEW)
AT AUTO TRANSFORMER
(N/A)
SUB SUB PANEL
(NEW)
DCD DC DISCONNECT
(N/A)
DCC DC COMBINER
(N/A)
EE EXISTING EQUIPMENT
STRING
IQ IQ SYSTEM CONTROLLER 2
(NEW)RSD RAPID SHUTDOWN DEVICE
(NEW)
CONDUIT
CEC AC RATING: 5.012
Q
DIRECT
Signed 12/14/2023
Bldg# 101118483
Elec# 20182269
Approvals:
Elec - MSmith
The scope of the plans is for the installation of
the solar photovoltaic system only and the
approval is subject to compliance with all
applicable city and state codes and regulations
regarding construction. The approval of the
plans does not constitute any certification of the
accuracy, completeness, or building permit
status of the existing buildings and structures as
shown.
2817 W Brook St -
201822693/19/2024
18" FIRE SET
B
A
C
K
#1
36" FIRE SET
B
A
C
K
18
"
F
I
R
E
S
E
T
B
A
C
K
#2
18
"
F
I
R
E
S
E
T
B
A
C
K
18" FIRE SET
B
A
C
K
36
"
F
I
R
E
S
E
T
B
A
C
K
36"
F
I
R
E
S
E
T
B
A
C
K
49' 7"
7' 1"
98
'
9
"
76' 11"
13
'
3
"
90
'
2
"
BA
T
JB
JB
MSPUM
AC
RSD SUBIQLC REV
SHEET NAME
SHEET SIZE
SHEET NUMBER
ANSI B
DATEDESCRIPTION
REVISIONS
PV-2
HOMEOWNER INFO
11" X 17"
SIGNATURE & SEAL
SITE PLAN
CONTRACTOR: COMPLETE SOLARIA
ADDRESS: 3000 EXECUTIVE PKWY, SUITE
504, SAN RAMON, CA 94583
PHONE: 8772994943
LICENSE #: 961988
JO
S
E
G
O
M
E
Z
28
1
7
W
B
R
O
O
K
S
T
,
SA
N
T
A
A
N
A
,
C
A
9
2
7
0
4
,
U
S
A
AP
N
:
1
0
9
-
7
4
1
-
1
6
P
H
O
N
E
:
7
1
4
3
2
1
3
5
5
4
EM
A
I
L
:
j
o
s
e
g
o
m
e
z
1
0
1
7
5
7
@
g
m
a
i
l
.
c
o
m
2817 W BROOK ST
SCALE: 3/32" = 1'-0"
SITE PLAN
LE
G
E
N
D
NEW PV MODULE
FIRE SETBACK
OPTIMIZER
MICRO-INVERTER
ROOF ATTACHMENT
ROOF ACCESS POINT
MSP MAIN SERVICE PANEL
(NEW, 225A)
UM UTILITY METER
(NEW)
PM PRODUCTION METER
(N/A)
BAT BATTERY
(NEW)
INV (0) INVERTER
(N/A)
LC LOAD CENTER (COMBINER
PANEL) (NEW)
SM SOLAREDGE METER
(N/A)
BLP BACKUP LOAD PANEL
(N/A)
AC AC DISCONNECT UNFUSED
(NEW)
ACF AC DISCONNECT FUSED
(N/A)
JB JUNCTION BOX
(NEW)
AT AUTO TRANSFORMER
(N/A)
SUB SUB PANEL
(NEW)
DCD DC DISCONNECT
(N/A)
DCC DC COMBINER
(N/A)
EE EXISTING EQUIPMENT
IQ IQ SYSTEM CONTROLLER 2
(NEW)RSD RAPID SHUTDOWN DEVICE
(NEW)
●TOTAL AREA: (14) 76.4" x 41.3" = 306 SF
●TOTAL WEIGHT: (14) 49.6 + (14) 2.4 + (14) 1.5 = 749 LB
●WEIGHT PER CONNECTION: 749 LB / 36 = 20.80 LB
●DISTRIBUTED LOAD: 749 LB / 306 SF = 2.44 PSF
●ROOF AREA COVERED: 306 SF / 2526 SF = 12.1%
ROOF DESCRIPTION TABLE
ROOF
PLANE
ROOF
PITCH
ROOF
AZIMUTH
RAFTER
SIZE
RAFTER
SPACING
ATTACHMENT
SPACING
MODULES
(PITCH)
#1 22°169°2" x 6"
(RAFTER)24" O.C.48" O.C.
(STAGGERED)9 (22°)
#2 23° 259°2" x 6"
(RAFTER)24" O.C.48" O.C.
(STAGGERED)5 (23°)
DRIVEWAY
ACCESS ROOF
ACCESS ROOF
UN-PERMITABLE
SHED NO
ELECTRICAL
CONNECTION
POOL PATIO
DIG ALERT (811) IS TO BE CONTACTED AND COMPLIANCE WITH
EXCAVATION SAFETY IN ACCORDING WITH GOVERNMENT
CODE 4216 WILL BE FOLLOWED, PRIOR TO ANY EXCAVATION
TAKING PLACE.
CEC AC RATING: 5.012
DIMENSIONS
PROPERTY LINE
RAFTER/TRUSS
RAIL
FENCE
GATE STRING
CONDUIT
Signed 12/14/2023
2817 W Brook St -
201822693/19/2024
NEW ELECTRICAL GUTTER
ENPHASE
RSD
ENPHASE
AC
DISCONNECT
FROM ROOF TOP
ENPHASE
IQ BATTERY 10T
REV
SHEET NAME
SHEET SIZE
SHEET NUMBER
ANSI B
DATEDESCRIPTION
REVISIONS
PV-4.1
HOMEOWNER INFO
11" X 17"
SIGNATURE & SEAL
EQUIPMENT
ELEVATION
CONTRACTOR: COMPLETE SOLARIA
ADDRESS: 3000 EXECUTIVE PKWY, SUITE
504, SAN RAMON, CA 94583
PHONE: 8772994943
LICENSE #: 961988
JO
S
E
G
O
M
E
Z
28
1
7
W
B
R
O
O
K
S
T
,
SA
N
T
A
A
N
A
,
C
A
9
2
7
0
4
,
U
S
A
AP
N
:
1
0
9
-
7
4
1
-
1
6
P
H
O
N
E
:
7
1
4
3
2
1
3
5
5
4
EM
A
I
L
:
j
o
s
e
g
o
m
e
z
1
0
1
7
5
7
@
g
m
a
i
l
.
c
o
m
SCALE: NTS
EQUIPMENT ELEVATION
UTILITY METER
AND MAIN
PANEL
NEW SUB-PANEL
IQ SYSTEM CONTROLLER 2
COMBINER PANEL
BATTERY
EAST WALL
NORTH WALL
2817 W Brook St -
201822693/19/2024
2817 W Brook St -
201822693/19/2024
2817 W Brook St -
201822693/19/2024
76 North Meadowbrook Drive
Scott E. Wyssling, PE Alpine, UT 84004
Coleman D. Larsen, SE, PE office (201) 874-3483
Gregory T. Elvestad, PE swyssling@wysslingconsulting.com
December 14, 2023
Complete Solaria
3000 Executive Parkway
Suite 504
San Ramon, CA 94583
Re: Engineering Services
Gomez Residence
2817 W est Brook Street, Santa Ana CA
5.530 kW System
To Whom It May Concern:
We have received information regarding solar panel installation on the roof of the above referenced
structure. Our evaluation of the structure is to verify the existing capacity of the roof system and its ability
to support the additional loads imposed by the proposed solar system.
A. Site Assessment Information
1. Site visit documentation identifying attic information including size and spacing of framing
for the existing roof structure.
2. Design drawings of the proposed system including a site plan, roof plan and connection
details for the solar panels. This information will be utilized for approval and construction
of the proposed system.
B. Description of Structure:
Roof Framing: 2 x 6 dimensional lumber rafters at 24” on center.
Roof Material: Tile roofing
Roof Slope: 22 and 23 degrees
Attic Access: Accessible
Foundation: Permanent
C. Loading Criteria Used
• Dead Load
o Existing Roofing and framing = 14 psf
o New Solar Panels and Racking = 3 psf
o TOTAL = 17 PSF
• Dead Load
o Existing Roofing and framing = 7 psf
o New Solar Panels and Racking = 3 psf
o TOTAL = 10 psf
• Live Load = 20 psf (reducible) – 0 psf at locations of solar panels
• Ground Snow Load = 0 psf
• Wind Load based on ASCE 7-16
o Ultimate Wind Speed = 95 mph (based on Risk Category II)
o Exposure Category C
Analysis performed of the existing roof structure utilizing the above loading criteria is in accordance
with the 2022 California Building Code, including provisions allowing existing structures to not
require strengthening if the new loads do not exceed existing design loads by 105% for gravity
elements and 110% for seismic elements. This analysis indicates that the existing framing will
support the additional panel loading without damage, if installed correctly.
2817 W Brook St -
201822693/19/2024
Page 2 of 2
D. Solar Panel Anchorage
1. The solar panels shall be mounted in accordance with the most recent Unirac installation manual.
If during solar panel installation, the roof framing members appear unstable or deflect non -
uniformly, our office should be notified before proceeding with the installation.
2. The maximum allowable withdrawal force for a 5/16” lag screw is 235 lbs per inch of penetration as
identified in the National Design Standards (NDS) of timber construction specifications. Based on
a minimum penetration depth of 2½”, the allowable capacity per connection is greater than the
design withdrawal force (demand). Considering the variable factors for the existing roof framing
and installation tolerances, the connection using one 5/16” diameter lag screw with a minimum of
2½” embedment will be adequate and will include a sufficient factor of safety.
3. Considering the wind speed, roof slopes, size and spacing of framing members, and condition of
the roof, the panel supports shall be placed no greater than 48” on centers.
Based on the above evaluation, this office certifies that with the racking and mounting specified, the existing
roof system will adequately support the additional loading imposed by the solar system. This evaluation is in
conformance with the 2022 California Building Code, current industry standards, and is based on information
supplied to us at the time of this report.
Should you have any questions regarding the above or if you require further information do not hesitate to
contact me.
Very truly yours,
Scott E. Wyssling, PE
California License No. 83664
2817 W Brook St -
201822693/19/2024
Wyssling Consulting
76 N. Meadowbrook Drive
Alpine, UT 84004
(201) 874-3483
swyssling@wysslingconsulting.com
Existing Gomez Residence
Roof Dead Load 2817 West Brook Street
9.0 psf Clay or Conc Tile Santa Ana , CA
1.6 psf 1/2" Plywood Sheathing
1.3 psf 2x6 @ 24 in. o.c.
1.0 psf Ceiling, Mechanical, Electrical
0.1 psf Miscellaneous
13.0 psf TOTAL
Second Floor Dead Load
0 psf Floor Finishes
0 psf 1 1/8" Subfloor Sheathing
0 psf Joists @ 16' o.c.
0 psf Partitions
0 psf Ceiling, Mechanical, Electrical
0 psf Miscellaneous
0 psf TOTAL
Roof Live Load Floor Live Load
20 psf 0 psf
Roof Snow Load
Ground SnowLoad=0 psf (to be divided by cosine of roof angle for horizontal projection ASCE 7 Sec. 7.4)
pf = 0.7 Ce Ct I pg =0 psf Ce = 1, Ct = 1.1 Flat Roof Snow Load (ASCE 7-16 Eq. 7.3-1)
Cs =0.87 ASCE 7-16 Figure 7.4-1
Additional
Roof Dead Load - New Solar Panels
3 psf
Roof Live Load at Solar Panels
0 psf
Roof Snow Load at Solar Panels
0 psf Sloped Roof Snow Load (ASCE 7-16 Eq. 7.4-1)
Total
Total Existing Roof Load = (DLROOF + Max(LLROOF or S)) AreaROOF
118239 lbs
Total New Roof Load = (DLROOF + DLADD + Max(LLROOF or S)) AreaROOF
113093 lbs
Change in Demand = (Total New Roof Load - Existing Roof Load) / Existing Roof Load
-4.35%
2021 IEBC Section 805.2 states:
"Any existing gravity load-carrying structural element for which an alteration causes an increase in design gravity load
of more than 5 percent shall be strengthened, supplemented, replaced or otherwise altered as needed to carry the
increased gravity load required by this code for new structures."
Gravity Loads
Total New Gravity Loads are less than Existing Loads. OK
Signed 12/14/2023
2817 W Brook St -
201822693/19/2024
Wyssling Consulting
76 N. Meadowbrook Drive
Alpine, UT 84004
(201) 874-3483
swyssling@wysslingconsulting.com
V =95 Basic Wind Speed Gomez Residence
Exposure C ASCE 7-16, Section 26.7 2817 West Brook Street
Kz =0.85 Velocity Pressure Coefficient, ASCE 7-16, Figure 26.10-1 Santa Ana , CA
Kzt =1 Topographic Factor, ASCE 7-16, Section 26.8.2
Kd =0.85 Directionality Factor, ASCE 7-16, Section 26.6
Ke =0.939 Ground Elevation Factor, ASCE 7-16, Section 26.9
qh =15.7 psf qh = 0.00256KzKztKdKeV2 (ASCE 7-16 Eq. 26.10-1)
Roof Angle =22 deg
Roof Type Gable
sanchor =48 in Horizontal spacing of roof anchors
Atrib =12.33 sf Panel Area tributary to each roof anchor
GCp External Pressure Coefficient, ASCE 7-16, Figure 30.3-2
Roof Zone Zone 1 2e 2n 2r 3e 3r
-1.50 -1.50 -2.48 -2.48 -2.48 -3.27
ga =0.79 Pressure Equalization Factor, ASCE 7-16 Figure 29.4.-8
gE =1.00 Edge Array Factor, ASCE 29.4.4 edges < 0.5*building height, and panel spacing < 4ft.
pnet = qhGCpgEga =Design Wind Pressure, ASCE 7-16, Equation 29.4-7
Roof Zone 1 2e 2n 2r 3e 3r
-19 psf -19 psf -31 psf -31 psf -31 psf -41 psf Min Pressure = -16 psf
Use 19 psf Use 19 psf Use 31 psf Use 31 psf Use 31 psf Use 41 psf ULTIMATE
x 0.6 =16 psf 16 psf 18 psf 18 psf 18 psf 24 psf ALLOWABLE
Connection to Existing Roof Framing
F.S. =1 Additional Factor of Safety applied to withdrawl force, if desired
Atrib =12.3 ft2
DLpanel =3 psf
Roof Zone 1 2e 2n 2r 3e 3r
Wuplift =19 psf 19 psf 31 psf 31 psf 31 psf 41 psf
Plag = F.S. x Atrib x (0.6D - 0.6W) =Withdrawl force for each roof anchor
Roof Zone 1 2e 2n 2r 3e 3r
-118.2 lbs -118.2 lbs -207.7 lbs -207.7 lbs -207.7 lbs -280.6 lbs
Connection Capacity
db =5/16 in Lag Screw diameter
Dpen =2 1/2 in Lag Screw penetration into existing framing member
No. of Screws 1 Screws per Connection
Species of wood framing
CD =1.6 Load Duration Factor for Wind Loading, NDS Table 2.3.2
Ct =0.7 Temperature Factor, NDS Table 10.3.4
W =205 lb/in Withdrawl Capacity, NDS Equation 11.2-1
W' = CD x Ct x W =229 lb/in Adjusted withdrawl value
Pallow = Dpen x W' =573 lbs
Roof Zone 1 2e 2n 2r 3e 3r
DEMAND =118 lbs 118 lbs 208 lbs 208 lbs 208 lbs 281 lbs
CAPACITY =573 lbs 573 lbs 573 lbs 573 lbs 573 lbs 573 lbs
up to72in ok up to72in ok up to72in ok up to72in ok up to72in ok up to72in ok
This analysis calculates the
capacity of the lag screws
only. For capacity of the
complete mounting system,
please see manufacturer's
recommendations.
Spruce-Pine-Fir
Wind Uplift
Rooftop Solar Panels Parallel to Roof Surface
ASCE 7-16, Section 29.4.4
Signed 12/14/2023
2817 W Brook St -
201822693/19/2024
#1
#2
BA
T
JB
JB
MSPUM
AC
RSD SUBIQLC
REV
SHEET NAME
SHEET SIZE
SHEET NUMBER
ANSI B
DATEDESCRIPTION
REVISIONS
PV-3.2
HOMEOWNER INFO
11" X 17"
SIGNATURE & SEAL
STRING PLAN
WITH MODULES
CONTRACTOR: COMPLETE SOLARIA
ADDRESS: 3000 EXECUTIVE PKWY, SUITE
504, SAN RAMON, CA 94583
PHONE: 8772994943
LICENSE #: 961988
JO
S
E
G
O
M
E
Z
28
1
7
W
B
R
O
O
K
S
T
,
SA
N
T
A
A
N
A
,
C
A
9
2
7
0
4
,
U
S
A
AP
N
:
1
0
9
-
7
4
1
-
1
6
P
H
O
N
E
:
7
1
4
3
2
1
3
5
5
4
EM
A
I
L
:
j
o
s
e
g
o
m
e
z
1
0
1
7
5
7
@
g
m
a
i
l
.
c
o
m
SCALE: 1/8" = 1'-0"
STRING PLAN WITH MODULES
FRONT OF HOUSE
2817 W BROOK ST
LE
G
E
N
D
NEW PV MODULE
FIRE SETBACK
OPTIMIZER
MICRO-INVERTER
ROOF ATTACHMENT
ROOF ACCESS POINT
DIMENSIONS
PROPERTY LINE
RAFTER/TRUSS
RAIL
FENCE
GATE
MSP MAIN SERVICE PANEL
(NEW, 225A)
UM UTILITY METER
(NEW)
PM PRODUCTION METER
(N/A)
BAT BATTERY
(NEW)
INV (0) INVERTER
(N/A)
LC LOAD CENTER (COMBINER
PANEL) (NEW)
SM SOLAREDGE METER
(N/A)
BLP BACKUP LOAD PANEL
(N/A)
AC AC DISCONNECT UNFUSED
(NEW)
ACF AC DISCONNECT FUSED
(N/A)
JB JUNCTION BOX
(NEW)
AT AUTO TRANSFORMER
(N/A)
SUB SUB PANEL
(NEW)
DCD DC DISCONNECT
(N/A)
DCC DC COMBINER
(N/A)
EE EXISTING EQUIPMENT
STRING
IQ IQ SYSTEM CONTROLLER 2
(NEW)RSD RAPID SHUTDOWN DEVICE
(NEW)
CONDUIT
BRANCH
CIRCUIT #1
BRANCH
CIRCUIT #1
2817 W Brook St -
201822693/19/2024
SYSTEM SUMMARY STC (5.530 kW DC / 4.060 kW AC)
STC DC: (14) 395W = 5.530 kW
STC AC: (14) 290W = 4.060 kW
STORAGE: (1) 3.84kW 10.1kWh
● (14) CANADIAN SOLAR INC. CS3N 395MS-BLK MODULES
● (14) ENPHASE ENERGY INC. IQ8PLUS-72-2-US 240V MICROINVERTERS
● (1) ENPHASE ENERGY INC. IQ BATTERY 10T FOR USMXCA BATTERIES
● (1) ENPHASE IQ SYSTEM CONTROLLER 2
● 2x BRANCHES OF 7 CONNECTED IN PARALLEL
1 2 1
1
2
G
7
MOD: CANADIAN SOLAR INC. CS3N
395MS-BLK
INV: ENPHASE ENERGY INC.
IQ8PLUS-72-2-US 240V
(1 BRANCH X 7 MICRO-INV)
1 2 1
1
2
G
7
MOD: CANADIAN SOLAR INC. CS3N
395MS-BLK
INV: ENPHASE ENERGY INC.
IQ8PLUS-72-2-US 240V
(1 BRANCH X 7 MICRO-INV)
1
2
1
2
G
N
JUNCTION BOX
600V, NEMA 3R
UL LISTED
TO CONSUMPTION CTs
G
N
GATEWAY
CT
CELL
MODEM
WIRELESS
COMMS TO SYSTEM
CONTROLLER
-
-
20A(N)
20A(N)
IQ COMBINER 4/4C
G
N
1
2
1
2
ON OFF
PV VISIBLE LOCKABLE
LABELED DISCONNECT
(30A UNFUSED 1PH 240VAC)
G
N
LOADS MAIN
1
1
2
1
NFT
GEN
21 2 1 2
2
ESS
(NO3)
GENLOADS
MAINPV
(NC3 NC4)
RSD
GEN BREAKER
TO GATEWAY
ESS
PV
40A
15A
20A
25A
IQ SYSTEM CONTROLLER 2
LOADS BREAKER: 100A
100A
SC01
ENPHASE SYSTEM
SHUTDOWN SWITCH
G
1
2
G
1
2
G
1
2
G
1
2
G
1
2
G
1
2
G
1
2
G
1
2
G
1
2
G
1
2
G
1
2
G
1
2
G
1
2
G
1
2
G
1
2
G
1
2
G
1
2
G
1
2
BT01
(1) ENPHASE IQ BATTERY 10T
G
N
SUBPANEL (NEW)
BUS RATING: 125A
G
N
TO
UTILITY
GRIDM
200A(N)
100A(N)
MAIN SERVICE PANEL
(NEW, TOP-FED)
BUS RATING: 225A (N)
MAIN BREAKER: 200A (N)
BI-DIRECTIONAL
UTILITY METER
METER NO:
222013-606723
UTILITY: SOUTHERN
CALIFORNIA EDISON CO
SERVICE: 240V 60HZ 1PH
12 AWG Q-CABLE
06 AWG Cu BARE G (BOND RACKING)
12 AWG Q-CABLE
06 AWG Cu BARE G (BOND RACKING)
CT
MS-01
MS-01
MCB-01
MCB-01
LC-01
LC-01
SP-01
AC wire details
Wire Min Ampacity Live Neutral Ground Min EMT
MS-01 10.59A 12 AWG (Q-Cable) -06 AWG BARE
(NOT IN CONDUIT)-
MCB-01 10.59A (2) 10 AWG THWN-2 - 08 AWG THWN-2 1/2 in
LC-01 21.18A (2) 10 AWG THWN-2 10 AWG THWN-2 10 AWG THWN-2 1/2 in
SP-01 100A (loads) (2) 02 AWG THWN-2 02 AWG THWN-2 08 AWG THWN-2 1-1/4 in
BT01 20A (OCPD) (2) 10 AWG THWN-2 - 10 AWG THWN-2 1/2 in
SC01 100A (OCPD) (2) 02 AWG THWN-2 02 AWG THWN-2 08 AWG THWN-2 1-1/4 in
UTILITY FEED + TOTAL BACKFEED
225A + 41A = 266A
LESS OR EQUAL TO
BUS RATING x 120%
225A x 120% = 270A
INTERCONNECTION 120% RULE
(MAIN PANEL)
CALCULATION ENSURES BUS IS
SAFE REGARDLESS OF LOADS
Isc(25°C) = 11.44A, Tisc = 0.050%/°C
Isc(T) = Isc(25°C) x [1 + Tisc x (T-25°C)]
Isc(3°C) = 11.31A, Isc(28°C) = 11.46A
Voc(25°C) = 44.30V, Tvoc = -0.260%/°C
Voc(T) = Voc(25°C) x [1 + Tvoc x (T-25°C)]
Voc(3°C) = 46.83V, Voc(28°C) = 43.95V
EXTREME CASE MODULE OUTPUT
(Canadian Solar Inc. CS3N 395MS-BLK)
ELECTRICAL NOTES
1) ALL GROUNDING TO COMPLY WITH NEC 690.47.
2) ROOFTOP CONDUIT SHALL BE LOCATED MIN. 7/8" ABOVE ROOF SURFACE.
3) ALL TERMINALS SHALL BE MIN. 75°C RATED.
4) IQ GATEWAY BREAKER DETERMINED AT FACTORY BY MANUFACTURER (10A or 15A).
5) FOR IQ GATEWAY: USE SINGLE CT FOR PV PRODUCTION (L1 FROM ALL PV BRANCH CIRCUITS). USE DOUBLE CTs FOR
CONSUMPTION (L1 AND L2 FEEDING MSP MAIN BREAKER, SERVICE SIDE).
6) WHEN IQ SYSTEM CONTROLLER 2 NOT AT SERVICE ENTRANCE, REMOVE N-G JUMPER WIRE FROM CONTROLLER.
7) SINGLE LARGEST BREAKER, BASELINE LOAD, AND LRA OF LARGEST LOAD IN BACKUP LOAD PANEL CANNOT EXCEED
STORAGE (ESS) OUTPUT CAPACITY, PER NEC 710.15.
8) IQ SYSTEM CONTROLLER 2 MAIN INPUT AND OUTPUT LUGS RATED FOR #1-350 KCMIL, FOR WIRES SMALLER THAN #1
REMOVE LUG AND USE AN APPROVED UL RING TERMINAL.
9) IQ SYSTEM CONTROLLER 2 HOLD DOWN KIT NEEDED FOR ESS & PV BREAKER, PER NEC 705.12(E).
10) THE CITY REQUIRES TWO SOURCES OF GROUND - UFER, TWO GROUND RODS OR COLD WATER GAS BOND.
11) HOLD DOWN KIT BRHDK 125 IS REQUIRED PER NEC 705.12(E)
TO PRODUCTION CTs
DIG ALERT (811) IS TO BE CONTACTED AND COMPLIANCE WITH EXCAVATION SAFETY IN
ACCORDING WITH GOVERNMENT CODE 4216 WILL BE FOLLOWED, PRIOR TO ANY
EXCAVATION TAKING PLACE.
NOTE: SPLICING OF THE WIRE-TYPE GROUNDING ELECTRODE SHALL BE PERMITTED
ONLY BY IRREVERSIBLE COMPRESSION-TYPE CONNECTORS LISTED AS GROUNDING
AND BONDING EQUIPMENT OR BY THE EXOTHERMIC WELDING METAL WATER PIPING
SYSTEM INSTALLED IN OR ATTACHED TO A BUILDING OR STRUCTURE SHALL BE
BONDED PER CEC TABLE 250.66 AND 250.104(A)(1)
THE SURGE PROTECTION DEVICE (SPD) SHALL COMPLY WITH 2022 CALIFORNIA
ELECTRICAL CODE 230.67 THE SPD MUST BE EITHER TYPE 1 OR TYPE 2.
SP
D
PV BREAKER SHALL BE
FURTHEST POSITION
AWAY FROM MAIN
BREAKER PERCEC
705.12(B)(2)(3)(b).
SURGE PROTECTION DEVICE
REV
SHEET NAME
SHEET SIZE
SHEET NUMBER
ANSI B
DATE DESCRIPTION
REVISIONS
PV-4
HOMEOWNER INFO
11" X 17"
SIGNATURE & SEAL
THREE LINE
DIAGRAM
CONTRACTOR: COMPLETE SOLARIA
ADDRESS: 3000 EXECUTIVE PKWY, SUITE
504, SAN RAMON, CA 94583
PHONE: 8772994943
LICENSE #: 961988
J
O
S
E
G
O
M
E
Z
28
1
7
W
B
R
O
O
K
S
T
,
SA
N
T
A
A
N
A
,
C
A
9
2
7
0
4
,
U
S
A
AP
N
:
1
0
9
-
7
4
1
-
1
6
PH
O
N
E
:
7
1
4
3
2
1
3
5
5
4
EM
A
I
L
:
j
o
s
e
g
o
m
e
z
1
0
1
7
5
7
@
g
m
a
i
l
.
c
o
m
SCALE: NTS
ELECTRICAL THREE LINE DIAGRAM
GROUND ROD (N) GROUND
ROD (5/8", 8')
PLACED 6'-0" APPART
CONNECT TO COLD
WATER WITHIN 5'
PLACED 6'-0" APPARTEXISTING GROUNDING
ELECTROD SYSTEM TO
EARTH
NEC 250.52,250.53(A)
NEW #4 CU AUXILIARY GROUND ROD
SHOULD BE MORE THAN 6 FEET FROM
THE EXISTING GEC
MAIN PANEL REPLACEMENT: EXISTING 100 AMP MAIN PANEL
WITH 100 AMP MAIN BREAKER TO BE REPLACED WITH NEW
225 AMP MAIN PANEL WITH NEW 200 AMP MAIN BREAKER.
The maximum current output from the battery in
backup mode is 16A. There can be no single
circuits in the backup loads panel that exceeds
20A nor a load greater than 16A. CEC 705.28(A),
710.15(A)
2817 W Brook St -
201822693/19/2024
REV
SHEET NAME
SHEET SIZE
SHEET NUMBER
ANSI B
DATEDESCRIPTION
REVISIONS
PV-4.2
HOMEOWNER INFO
11" X 17"
SIGNATURE & SEAL
LOAD
CALCULATION
CONTRACTOR: COMPLETE SOLARIA
ADDRESS: 3000 EXECUTIVE PKWY, SUITE
504, SAN RAMON, CA 94583
PHONE: 8772994943
LICENSE #: 961988
JO
S
E
G
O
M
E
Z
28
1
7
W
B
R
O
O
K
S
T
,
SA
N
T
A
A
N
A
,
C
A
9
2
7
0
4
,
U
S
A
AP
N
:
1
0
9
-
7
4
1
-
1
6
P
H
O
N
E
:
7
1
4
3
2
1
3
5
5
4
EM
A
I
L
:
j
o
s
e
g
o
m
e
z
1
0
1
7
5
7
@
g
m
a
i
l
.
c
o
m
SCALE: NTS
LOAD CALCULATION
2817 W Brook St -
201822693/19/2024
EXISTING PANEL SCHEDULE FUTURE PANEL SCHEDULE
1
3
5
7
9
11
13
15
17
19
21
23
25
27
29
2
4
6
8
10
12
14
16
18
20
22
24
26
28
30
200
20
20
20
15
20
15
20
20
20
20
20
20
20
20
50
10
0
NEW PV
BREAKER
1
3
5
7
9
11
13
15
17
19
21
23
25
27
29
2
4
6
8
10
12
14
16
18
20
22
24
26
28
30
200
20
20
20
15
20
15
20
20
20
20
20
20
20
20
50
REV
SHEET NAME
SHEET SIZE
SHEET NUMBER
ANSI B
DATEDESCRIPTION
REVISIONS
PV-4.3
HOMEOWNER INFO
11" X 17"
SIGNATURE & SEAL
PANEL
SCHEDULES
CONTRACTOR: COMPLETE SOLARIA
ADDRESS: 3000 EXECUTIVE PKWY, SUITE
504, SAN RAMON, CA 94583
PHONE: 8772994943
LICENSE #: 961988
JO
S
E
G
O
M
E
Z
28
1
7
W
B
R
O
O
K
S
T
,
SA
N
T
A
A
N
A
,
C
A
9
2
7
0
4
,
U
S
A
AP
N
:
1
0
9
-
7
4
1
-
1
6
P
H
O
N
E
:
7
1
4
3
2
1
3
5
5
4
EM
A
I
L
:
j
o
s
e
g
o
m
e
z
1
0
1
7
5
7
@
g
m
a
i
l
.
c
o
m
SCALE: NTS
PANEL SCHEDULES
2817 W Brook St -
201822693/19/2024
SYSTEM SUMMARY STC (5.530 kW DC / 4.060 kW AC)
STC DC: (14) 395W = 5.530 kW
STC AC: (14) 290W = 4.060 kW
STORAGE: (1) 3.84kW 10.1kWh
●(14) CANADIAN SOLAR INC. CS3N 395MS-BLK MODULES
●(14) ENPHASE ENERGY INC. IQ8PLUS-72-2-US 240V MICROINVERTERS
●(1) ENPHASE ENERGY INC. IQ BATTERY 10T FOR USMXCA BATTERIES
●(1) ENPHASE IQ SYSTEM CONTROLLER 2
●2x BRANCHES OF 7 CONNECTED IN PARALLEL
AC wire details
WireID #Modules Nominal
Voltage
Backfeed *1.25
/cond. set
Min
OCPD
Total
Power
Conductor
sets
ccConductors
/conduit
Expected
max temp
Adjusted ampacity (ampacity x temp
derate x conduit fill derate)
Conductor &
neutral size
EGC size
(Cu)
Conductor
metal
Max
length V drop Min EMT
size
MS-01 7 240 V 10.59 A 20 A 2.0 kW 1 - 28 25 x 1.00 x - = 25.00 A 12 AWG (Q-Cable)06 AWG BARE
(NOT IN CONDUIT)Cu 50 ft 0.60 %-
MCB-01 7 240 V 10.59 A 20 A 2.0 kW 1 2 28 35 x 1.00 x 1.00 = 35.00 A 10 AWG THWN-2 08 AWG THWN-2 Cu 50 ft 0.36 %1/2 in
LC-01 14 240 V 21.18 A 25 A 4.1 kW 1 2 28 35 x 1.00 x 1.00 = 35.00 A 10 AWG THWN-2 10 AWG THWN-2 Cu 10 ft 0.14 %1/2 in
SP-01 14 240 V 41.18 A 100 A 7.9 kW 1 2 28 100 x 1.00 x 1.00 = 100.00 A 02 AWG THWN-2 08 AWG THWN-2 Cu 10 ft 0.06 %1-1/4 in
UTILITY FEED + TOTAL BACKFEED
225A + 41A = 266A
LESS OR EQUAL TO
BUS RATING x 120%
225A x 120% = 270A
INTERCONNECTION 120% RULE
(MAIN PANEL)
CALCULATION ENSURES BUS IS
SAFE REGARDLESS OF LOADS
Isc(25°C) = 11.44A, Tisc = 0.050%/°C
Isc(T) = Isc(25°C) x [1 + Tisc x (T-25°C)]
Isc(3°C) = 11.31A, Isc(28°C) = 11.46A
Voc(25°C) = 44.30V, Tvoc = -0.260%/°C
Voc(T) = Voc(25°C) x [1 + Tvoc x (T-25°C)]
Voc(3°C) = 46.83V, Voc(28°C) = 43.95V
EXTREME CASE MODULE OUTPUT
(Canadian Solar Inc. CS3N 395MS-BLK)
ELECTRICAL NOTES
1) ALL EQUIPMENT TO BE LISTED BY UL OR OTHER NRTL, AND LABELED FOR ITS APPLICATION.
2) ALL CONDUCTORS SHALL BE COPPER, RATED FOR 600V AND 90°C WET ENVIRONMENT.
3) WIRING, CONDUIT, AND RACEWAYS MOUNTED ON ROOFTOPS SHALL BE ROUTED DIRECTLY TO, AND LOCATED AS CLOSE AS POSSIBLE TO THE NEAREST RIDGE, HIP, OR VALLEY.
4) WORKING CLEARANCES AROUND ALL NEW AND EXISTING ELECTRICAL EQUIPMENT SHALL COMPLY WITH NEC 110.26.
5) DRAWINGS INDICATE THE GENERAL ARRANGEMENT OF SYSTEMS. CONTRACTOR SHALL FURNISH ALL NECESSARY OUTLETS, SUPPORTS, FITTINGS AND ACCESSORIES TO FULFILL APPLICABLE CODES AND STANDARDS.
6) WHERE SIZES OF JUNCTION BOXES, RACEWAYS, AND CONDUITS ARE NOT SPECIFIED, THE CONTRACTOR SHALL SIZE THEM ACCORDINGLY.
7) ALL WIRE TERMINATIONS SHALL BE APPROPRIATELY LABELED AND READILY VISIBLE.
8) MODULE GROUNDING CLIPS TO BE INSTALLED BETWEEN MODULE FRAME AND MODULE SUPPORT RAIL, PER THE GROUNDING CLIP MANUFACTURER'S INSTRUCTION.
9) MODULE SUPPORT RAIL TO BE BONDED TO CONTINUOUS COPPER G.E.C.VIA WEEB LUG OR ILSCO GBL-4DBT LAY-IN LUG.
10) PV EQUIPMENT SHALL BE DESIGNED AND INSTALLED IN ACCORDANCE WITH NEC 690.
11) EXACT LOCATION OF AUXILIARY GROUNDING TO BE DETERMINED AT TIME OF INSTALL.
12) EXISTING WIRES MUST BE REPLACED IF SMALLER THAN LISTED MINIMUM SIZES PER NEC 310.15(B)(16).
13) IQ GATEWAY BREAKER DETERMINED AT FACTORY BY MANUFACTURER (10A or 15A).
14) FOR IQ GATEWAY: USE SINGLE CT FOR PV PRODUCTION (L1 FROM ALL PV BRANCH CIRCUITS). USE DOUBLE CTs FOR CONSUMPTION (L1 AND L2 FEEDING MSP MAIN BREAKER, SERVICE SIDE).
15) WHEN IQ SYSTEM CONTROLLER 2 NOT AT SERVICE ENTRANCE, REMOVE N-G JUMPER WIRE FROM CONTROLLER.
16) SINGLE LARGEST BREAKER, BASELINE LOAD, AND LRA OF LARGEST LOAD IN BACKUP LOAD PANEL CANNOT EXCEED STORAGE (ESS) OUTPUT CAPACITY, PER NEC 710.15.
17) IQ SYSTEM CONTROLLER 2 MAIN INPUT AND OUTPUT LUGS RATED FOR #1-350 KCMIL, FOR WIRES SMALLER THAN #1 REMOVE LUG AND USE AN APPROVED UL RING TERMINAL.
18) IQ SYSTEM CONTROLLER 2 HOLD DOWN KIT NEEDED FOR ESS & PV BREAKER, PER NEC 705.12(E).
19) THE CITY REQUIRES TWO SOURCES OF GROUND - UFER, TWO GROUND RODS OR COLD WATER GAS BOND.
20) HOLD DOWN KIT BRHDK 125 IS REQUIRED PER NEC 705.12(E)
ROOF COVERAGE TABLE
●TOTAL AREA: (14) 76.4" x 41.3" = 306 SF
●TOTAL ROOF AREA: 2526 SF
●ROOF AREA COVERED: 306 SF / 2526 SF = 12.1%
REV
SHEET NAME
SHEET SIZE
SHEET NUMBER
ANSI B
DATEDESCRIPTION
REVISIONS
PV-5
HOMEOWNER INFO
11" X 17"
SIGNATURE & SEAL
WIRING
CALCULATIONS
CONTRACTOR: COMPLETE SOLARIA
ADDRESS: 3000 EXECUTIVE PKWY, SUITE
504, SAN RAMON, CA 94583
PHONE: 8772994943
LICENSE #: 961988
JO
S
E
G
O
M
E
Z
28
1
7
W
B
R
O
O
K
S
T
,
SA
N
T
A
A
N
A
,
C
A
9
2
7
0
4
,
U
S
A
AP
N
:
1
0
9
-
7
4
1
-
1
6
P
H
O
N
E
:
7
1
4
3
2
1
3
5
5
4
EM
A
I
L
:
j
o
s
e
g
o
m
e
z
1
0
1
7
5
7
@
g
m
a
i
l
.
c
o
m
SCALE: NTS
WIRING CALCULATIONS
2817 W Brook St -
201822693/19/2024
BA
T
MSPUM ACRSD SUB IQ LC
REV
SHEET NAME
SHEET SIZE
SHEET NUMBER
ANSI B
DATEDESCRIPTION
REVISIONS
PV-6
HOMEOWNER INFO
11" X 17"
SIGNATURE & SEAL
PLACARDS
CONTRACTOR: COMPLETE SOLARIA
ADDRESS: 3000 EXECUTIVE PKWY, SUITE
504, SAN RAMON, CA 94583
PHONE: 8772994943
LICENSE #: 961988
JO
S
E
G
O
M
E
Z
28
1
7
W
B
R
O
O
K
S
T
,
SA
N
T
A
A
N
A
,
C
A
9
2
7
0
4
,
U
S
A
AP
N
:
1
0
9
-
7
4
1
-
1
6
P
H
O
N
E
:
7
1
4
3
2
1
3
5
5
4
EM
A
I
L
:
j
o
s
e
g
o
m
e
z
1
0
1
7
5
7
@
g
m
a
i
l
.
c
o
m
ELECTRICAL SHOCK HAZARD
WARNING!
LABEL LOCATION: INVERTERS, AC DISCONNECTS, AC
COMBINER BOXES
CODE REF: CEC 2022 - 690.13(B)
LABEL LOCATION: UTILITY SERVICE ENTRANCE (MSP OR
AC DISCONNECT IF LINE SIDE TAP), AND WHEREVER
REQUIRED BY AHJ (INVERTERS, DC DISCONNECTS,
OTHER)
CODE REF: CEC 2022 - 690.56(C)(2)
PV SYSTEM DISCONNECT
240.0
16.94
LABEL LOCATION: INTERCONNECTION Placard (MSP
BACKFEED BREAKER OR TAP BOX IF LINE SIDE TAP), AC
DISCONNECTS
CODE REF: CEC 2022 - 690.54
PHOTOVOLTAIC
AC DISCONNECT
LABEL LOCATION: INTERCONNECTION Placard (MSP
BACKFEED BREAKER OR TAP BOX IF LINE SIDE TAP), AC
DISCONNECTS
CODE REF: CEC 2022 - 690.13(B)
MAIN PHOTOVOLTAIC
SYSTEM DISCONNECT
LABEL LOCATION: AC DISCONNECTS FOR UTILITY
ACCESS
CODE REF: CEC 2022 - 690.13(B)
WARNING!
DO NOT RELOCATE THIS
OVERCURRENT DEVICE
LABEL LOCATION: FIRST BACKFEED BREAKER
(MSP/SUBPANEL) IF NO LINE SIDE TAP
CODE REF: CEC 2022 - 705.12(B)(3)(2)
LABEL LOCATION: MSP
CODE REF: CEC 2022 - 690.56(B)
SOLAR PV SYSTEM EQUIPPED
WITH RAPID SHUTDOWN
SOLAR ELECTRIC
PV PANELS
LABEL LOCATION: INTERCONNECTION POINT (MSP OR AC
DISCONNECT IF LINE SIDE TAP)
CODE REFCEC 2022 - 690.56(C)
WARNING
SOLAR SYSTEM CONNECTED AND
ENERGISED
LABEL LOCATION: UTILITY METER
CODE REF: CEC 2022 - 690.13(B)
WARNING
TURN OFF PHOTOVOLTAIC AC
DISCONNECT PRIOR TO WORKING
INSIDE PANEL
!
LABEL LOCATION: MSP
CODE REF: CEC 2022 - 110.27(C)
CAUTION:
MULTIPLE SOURCES OF POWER
LABEL LOCATION: MSP
CODE REF:CEC 2022 - 705.10,CEC 2022 - 710.10
2817 W BROOK ST, SANTA ANA, CA 92704,
USA
(N) UTILITY METER
(N) AC DISCONNECT
(N) IQ BATTERIES
10(T)
(N) IQ SYSTEM CONTROLLER 2
(N) SUB PANEL
(N) RAPID SHUTDOWN
DEVICE
(N) MAIN PANEL
(N) IQ COMBINER 4/4C
PV ARRAY
LABEL LOCATION:
BATTERY
WARNING!
SOURCES: UTILITY GRID,
BATTERY AND PV SOLAR
ELECTRIC SYSTEM
THREE POWER SUPPLY
LABEL LOCATION:
UTILITY SERVICE METER AND MAIN
SERVICE PANEL.
PER CODE(S): CEC 2022: 705.12(C),
706.11(A), & 706.11(B)
NOTES AND SPECIFICATIONS
1) SIGNS AND LABELS SHALL MEET THE
REQUIREMENTS OF CEC 110.21(B),
UNLESS SPECIFIC
INSTRUCTIONS ARE REQUIRED BY
SECTION 690, OR
IF REQUESTED BY THE LOCAL AHJ.
2) SIGNS AND LABELS SHALL ADEQUATELY
WARN OF
HAZARDS USING EFFECTIVE WORDS,
COLORS AND
SYMBOLS.
3) LABELS SHALL BE PERMANENTLY
AFFIXED TO THE
EQUIPMENT OR WIRING METHOD AND
SHALL NOT BE
HAND WRITTEN.
4) LABEL SHALL BE OF SUFFICIENT
DURABILITY TO
WITHSTAND THE ENVIRONMENT
INVOLVED.
5) SIGNS AND LABELS SHALL COMPLY
WITH ANSI Z535.4
- 2011, PRODUCT SAFETY SIGNS AND
LABELS,
UNLESS OTHERWISE SPECIFIED.
6) DO NOT COVER EXISTING
MANUFACTURER LABELS.
2817 W Brook St -
201822693/19/2024
REV
SHEET NAME
SHEET SIZE
SHEET NUMBER
ANSI B
DATEDESCRIPTION
REVISIONS
PV-10
HOMEOWNER INFO
11" X 17"
SIGNATURE & SEAL
EQUIPMENT
SPECIFICATION
CONTRACTOR: COMPLETE SOLARIA
ADDRESS: 3000 EXECUTIVE PKWY, SUITE
504, SAN RAMON, CA 94583
PHONE: 8772994943
LICENSE #: 961988
JO
S
E
G
O
M
E
Z
28
1
7
W
B
R
O
O
K
S
T
,
SA
N
T
A
A
N
A
,
C
A
9
2
7
0
4
,
U
S
A
AP
N
:
1
0
9
-
7
4
1
-
1
6
P
H
O
N
E
:
7
1
4
3
2
1
3
5
5
4
EM
A
I
L
:
j
o
s
e
g
o
m
e
z
1
0
1
7
5
7
@
g
m
a
i
l
.
c
o
m
2817 W Brook St -
201822693/19/2024
REV
SHEET NAME
SHEET SIZE
SHEET NUMBER
ANSI B
DATEDESCRIPTION
REVISIONS
PV-11
HOMEOWNER INFO
11" X 17"
SIGNATURE & SEAL
EQUIPMENT
SPECIFICATION
CONTRACTOR: COMPLETE SOLARIA
ADDRESS: 3000 EXECUTIVE PKWY, SUITE
504, SAN RAMON, CA 94583
PHONE: 8772994943
LICENSE #: 961988
JO
S
E
G
O
M
E
Z
28
1
7
W
B
R
O
O
K
S
T
,
SA
N
T
A
A
N
A
,
C
A
9
2
7
0
4
,
U
S
A
AP
N
:
1
0
9
-
7
4
1
-
1
6
P
H
O
N
E
:
7
1
4
3
2
1
3
5
5
4
EM
A
I
L
:
j
o
s
e
g
o
m
e
z
1
0
1
7
5
7
@
g
m
a
i
l
.
c
o
m
2817 W Brook St -
201822693/19/2024
REV
SHEET NAME
SHEET SIZE
SHEET NUMBER
ANSI B
DATEDESCRIPTION
REVISIONS
PV-12
HOMEOWNER INFO
11" X 17"
SIGNATURE & SEAL
EQUIPMENT
SPECIFICATION
CONTRACTOR: COMPLETE SOLARIA
ADDRESS: 3000 EXECUTIVE PKWY, SUITE
504, SAN RAMON, CA 94583
PHONE: 8772994943
LICENSE #: 961988
JO
S
E
G
O
M
E
Z
28
1
7
W
B
R
O
O
K
S
T
,
SA
N
T
A
A
N
A
,
C
A
9
2
7
0
4
,
U
S
A
AP
N
:
1
0
9
-
7
4
1
-
1
6
P
H
O
N
E
:
7
1
4
3
2
1
3
5
5
4
EM
A
I
L
:
j
o
s
e
g
o
m
e
z
1
0
1
7
5
7
@
g
m
a
i
l
.
c
o
m
2817 W Brook St -
201822693/19/2024
REV
SHEET NAME
SHEET SIZE
SHEET NUMBER
ANSI B
DATEDESCRIPTION
REVISIONS
PV-13
HOMEOWNER INFO
11" X 17"
SIGNATURE & SEAL
EQUIPMENT
SPECIFICATION
CONTRACTOR: COMPLETE SOLARIA
ADDRESS: 3000 EXECUTIVE PKWY, SUITE
504, SAN RAMON, CA 94583
PHONE: 8772994943
LICENSE #: 961988
JO
S
E
G
O
M
E
Z
28
1
7
W
B
R
O
O
K
S
T
,
SA
N
T
A
A
N
A
,
C
A
9
2
7
0
4
,
U
S
A
AP
N
:
1
0
9
-
7
4
1
-
1
6
P
H
O
N
E
:
7
1
4
3
2
1
3
5
5
4
EM
A
I
L
:
j
o
s
e
g
o
m
e
z
1
0
1
7
5
7
@
g
m
a
i
l
.
c
o
m
2817 W Brook St -
201822693/19/2024
REV
SHEET NAME
SHEET SIZE
SHEET NUMBER
ANSI B
DATEDESCRIPTION
REVISIONS
PV-14
HOMEOWNER INFO
11" X 17"
SIGNATURE & SEAL
EQUIPMENT
SPECIFICATION
CONTRACTOR: COMPLETE SOLARIA
ADDRESS: 3000 EXECUTIVE PKWY, SUITE
504, SAN RAMON, CA 94583
PHONE: 8772994943
LICENSE #: 961988
JO
S
E
G
O
M
E
Z
28
1
7
W
B
R
O
O
K
S
T
,
SA
N
T
A
A
N
A
,
C
A
9
2
7
0
4
,
U
S
A
AP
N
:
1
0
9
-
7
4
1
-
1
6
P
H
O
N
E
:
7
1
4
3
2
1
3
5
5
4
EM
A
I
L
:
j
o
s
e
g
o
m
e
z
1
0
1
7
5
7
@
g
m
a
i
l
.
c
o
m
2817 W Brook St -
201822693/19/2024
REV
SHEET NAME
SHEET SIZE
SHEET NUMBER
ANSI B
DATEDESCRIPTION
REVISIONS
PV-7
HOMEOWNER INFO
11" X 17"
SIGNATURE & SEAL
EQUIPMENT
SPECIFICATION
CONTRACTOR: COMPLETE SOLARIA
ADDRESS: 3000 EXECUTIVE PKWY, SUITE
504, SAN RAMON, CA 94583
PHONE: 8772994943
LICENSE #: 961988
JO
S
E
G
O
M
E
Z
28
1
7
W
B
R
O
O
K
S
T
,
SA
N
T
A
A
N
A
,
C
A
9
2
7
0
4
,
U
S
A
AP
N
:
1
0
9
-
7
4
1
-
1
6
P
H
O
N
E
:
7
1
4
3
2
1
3
5
5
4
EM
A
I
L
:
j
o
s
e
g
o
m
e
z
1
0
1
7
5
7
@
g
m
a
i
l
.
c
o
m
2817 W Brook St -
201822693/19/2024
REV
SHEET NAME
SHEET SIZE
SHEET NUMBER
ANSI B
DATEDESCRIPTION
REVISIONS
PV-8
HOMEOWNER INFO
11" X 17"
SIGNATURE & SEAL
EQUIPMENT
SPECIFICATION
CONTRACTOR: COMPLETE SOLARIA
ADDRESS: 3000 EXECUTIVE PKWY, SUITE
504, SAN RAMON, CA 94583
PHONE: 8772994943
LICENSE #: 961988
JO
S
E
G
O
M
E
Z
28
1
7
W
B
R
O
O
K
S
T
,
SA
N
T
A
A
N
A
,
C
A
9
2
7
0
4
,
U
S
A
AP
N
:
1
0
9
-
7
4
1
-
1
6
P
H
O
N
E
:
7
1
4
3
2
1
3
5
5
4
EM
A
I
L
:
j
o
s
e
g
o
m
e
z
1
0
1
7
5
7
@
g
m
a
i
l
.
c
o
m
2817 W Brook St -
201822693/19/2024
REV
SHEET NAME
SHEET SIZE
SHEET NUMBER
ANSI B
DATEDESCRIPTION
REVISIONS
PV-9
HOMEOWNER INFO
11" X 17"
SIGNATURE & SEAL
EQUIPMENT
SPECIFICATION
CONTRACTOR: COMPLETE SOLARIA
ADDRESS: 3000 EXECUTIVE PKWY, SUITE
504, SAN RAMON, CA 94583
PHONE: 8772994943
LICENSE #: 961988
JO
S
E
G
O
M
E
Z
28
1
7
W
B
R
O
O
K
S
T
,
SA
N
T
A
A
N
A
,
C
A
9
2
7
0
4
,
U
S
A
AP
N
:
1
0
9
-
7
4
1
-
1
6
P
H
O
N
E
:
7
1
4
3
2
1
3
5
5
4
EM
A
I
L
:
j
o
s
e
g
o
m
e
z
1
0
1
7
5
7
@
g
m
a
i
l
.
c
o
m
2817 W Brook St -
201822693/19/2024
PV-7
REV
SHEET NAME
SHEET SIZE
SHEET NUMBER
ANSI B
DATEDESCRIPTION
REVISIONS
PV-7
HOMEOWNER INFO
11" X 17"
SIGNATURE & SEAL
EQUIPMENT
SPECIFICATION
CONTRACTOR: COMPLETE SOLARIA
ADDRESS: 3000 EXECUTIVE PKWY, SUITE
504, SAN RAMON, CA 94583
PHONE: 8772994943
LICENSE #: 961988
JO
S
E
G
O
M
E
Z
28
1
7
W
B
R
O
O
K
S
T
,
SA
N
T
A
A
N
A
,
C
A
9
2
7
0
4
,
U
S
A
AP
N
:
10
9
-
7
4
1
-
1
6
P
H
O
N
E
:
71
4
3
2
1
3
5
5
4
EM
A
I
L
:
jo
s
e
g
o
m
e
z
1
0
1
7
5
7
@
g
m
a
i
l
.
c
o
m
2817 W Brook St -
201822693/19/2024
PV-8
REV
SHEET NAME
SHEET SIZE
SHEET NUMBER
ANSI B
DATEDESCRIPTION
REVISIONS
PV-8
HOMEOWNER INFO
11" X 17"
SIGNATURE & SEAL
EQUIPMENT
SPECIFICATION
CONTRACTOR: COMPLETE SOLARIA
ADDRESS: 3000 EXECUTIVE PKWY, SUITE
504, SAN RAMON, CA 94583
PHONE: 8772994943
LICENSE #: 961988
JO
S
E
G
O
M
E
Z
28
1
7
W
B
R
O
O
K
S
T
,
SA
N
T
A
A
N
A
,
C
A
9
2
7
0
4
,
U
S
A
AP
N
:
10
9
-
7
4
1
-
1
6
P
H
O
N
E
:
71
4
3
2
1
3
5
5
4
EM
A
I
L
:
jo
s
e
g
o
m
e
z
1
0
1
7
5
7
@
g
m
a
i
l
.
c
o
m
2817 W Brook St -
201822693/19/2024
PV-9
REV
SHEET NAME
SHEET SIZE
SHEET NUMBER
ANSI B
DATEDESCRIPTION
REVISIONS
PV-9
HOMEOWNER INFO
11" X 17"
SIGNATURE & SEAL
EQUIPMENT
SPECIFICATION
CONTRACTOR: COMPLETE SOLARIA
ADDRESS: 3000 EXECUTIVE PKWY, SUITE
504, SAN RAMON, CA 94583
PHONE: 8772994943
LICENSE #: 961988
JO
S
E
G
O
M
E
Z
28
1
7
W
B
R
O
O
K
S
T
,
SA
N
T
A
A
N
A
,
C
A
9
2
7
0
4
,
U
S
A
AP
N
:
10
9
-
7
4
1
-
1
6
P
H
O
N
E
:
71
4
3
2
1
3
5
5
4
EM
A
I
L
:
jo
s
e
g
o
m
e
z
1
0
1
7
5
7
@
g
m
a
i
l
.
c
o
m
2817 W Brook St -
201822693/19/2024
PV-10
REV
SHEET NAME
SHEET SIZE
SHEET NUMBER
ANSI B
DATEDESCRIPTION
REVISIONS
PV-10
HOMEOWNER INFO
11" X 17"
SIGNATURE & SEAL
EQUIPMENT
SPECIFICATION
CONTRACTOR: COMPLETE SOLARIA
ADDRESS: 3000 EXECUTIVE PKWY, SUITE
504, SAN RAMON, CA 94583
PHONE: 8772994943
LICENSE #: 961988
JO
S
E
G
O
M
E
Z
28
1
7
W
B
R
O
O
K
S
T
,
SA
N
T
A
A
N
A
,
C
A
9
2
7
0
4
,
U
S
A
AP
N
:
10
9
-
7
4
1
-
1
6
P
H
O
N
E
:
71
4
3
2
1
3
5
5
4
EM
A
I
L
:
jo
s
e
g
o
m
e
z
1
0
1
7
5
7
@
g
m
a
i
l
.
c
o
m
2817 W Brook St -
201822693/19/2024
PV-11
REV
SHEET NAME
SHEET SIZE
SHEET NUMBER
ANSI B
DATEDESCRIPTION
REVISIONS
PV-11
HOMEOWNER INFO
11" X 17"
SIGNATURE & SEAL
EQUIPMENT
SPECIFICATION
CONTRACTOR: COMPLETE SOLARIA
ADDRESS: 3000 EXECUTIVE PKWY, SUITE
504, SAN RAMON, CA 94583
PHONE: 8772994943
LICENSE #: 961988
JO
S
E
G
O
M
E
Z
28
1
7
W
B
R
O
O
K
S
T
,
SA
N
T
A
A
N
A
,
C
A
9
2
7
0
4
,
U
S
A
AP
N
:
10
9
-
7
4
1
-
1
6
P
H
O
N
E
:
71
4
3
2
1
3
5
5
4
EM
A
I
L
:
jo
s
e
g
o
m
e
z
1
0
1
7
5
7
@
g
m
a
i
l
.
c
o
m
2817 W Brook St -
201822693/19/2024
PV-12
REV
SHEET NAME
SHEET SIZE
SHEET NUMBER
ANSI B
DATEDESCRIPTION
REVISIONS
PV-12
HOMEOWNER INFO
11" X 17"
SIGNATURE & SEAL
EQUIPMENT
SPECIFICATION
CONTRACTOR: COMPLETE SOLARIA
ADDRESS: 3000 EXECUTIVE PKWY, SUITE
504, SAN RAMON, CA 94583
PHONE: 8772994943
LICENSE #: 961988
JO
S
E
G
O
M
E
Z
28
1
7
W
B
R
O
O
K
S
T
,
SA
N
T
A
A
N
A
,
C
A
9
2
7
0
4
,
U
S
A
AP
N
:
10
9
-
7
4
1
-
1
6
P
H
O
N
E
:
71
4
3
2
1
3
5
5
4
EM
A
I
L
:
jo
s
e
g
o
m
e
z
1
0
1
7
5
7
@
g
m
a
i
l
.
c
o
m
2817 W Brook St -
201822693/19/2024
PV-13
REV
SHEET NAME
SHEET SIZE
SHEET NUMBER
ANSI B
DATEDESCRIPTION
REVISIONS
PV-13
HOMEOWNER INFO
11" X 17"
SIGNATURE & SEAL
EQUIPMENT
SPECIFICATION
CONTRACTOR: COMPLETE SOLARIA
ADDRESS: 3000 EXECUTIVE PKWY, SUITE
504, SAN RAMON, CA 94583
PHONE: 8772994943
LICENSE #: 961988
JO
S
E
G
O
M
E
Z
28
1
7
W
B
R
O
O
K
S
T
,
SA
N
T
A
A
N
A
,
C
A
9
2
7
0
4
,
U
S
A
AP
N
:
10
9
-
7
4
1
-
1
6
P
H
O
N
E
:
71
4
3
2
1
3
5
5
4
EM
A
I
L
:
jo
s
e
g
o
m
e
z
1
0
1
7
5
7
@
g
m
a
i
l
.
c
o
m
2817 W Brook St -
201822693/19/2024
PV-14
REV
SHEET NAME
SHEET SIZE
SHEET NUMBER
ANSI B
DATEDESCRIPTION
REVISIONS
PV-14
HOMEOWNER INFO
11" X 17"
SIGNATURE & SEAL
EQUIPMENT
SPECIFICATION
CONTRACTOR: COMPLETE SOLARIA
ADDRESS: 3000 EXECUTIVE PKWY, SUITE
504, SAN RAMON, CA 94583
PHONE: 8772994943
LICENSE #: 961988
JO
S
E
G
O
M
E
Z
28
1
7
W
B
R
O
O
K
S
T
,
SA
N
T
A
A
N
A
,
C
A
9
2
7
0
4
,
U
S
A
AP
N
:
10
9
-
7
4
1
-
1
6
P
H
O
N
E
:
71
4
3
2
1
3
5
5
4
EM
A
I
L
:
jo
s
e
g
o
m
e
z
1
0
1
7
5
7
@
g
m
a
i
l
.
c
o
m
2817 W Brook St -
201822693/19/2024
2817 W Brook St -
201822693/19/2024
2817 W Brook St -
201822693/19/2024
2817 W Brook St -
201822693/19/2024
To whom it may concern,
This letter serves to confirm I have chosen to have my system installed by Complete
Solar. You have my express permission to move forward with the solar permit
applied for by Complete Solar for my property at 2817 W Brook St, Santa Ana, CA.
Thank you,
Jose Gomez
DocuSign Envelope ID: 62382052-0156-47F2-9C28-23D2ED92D989
3/1/2024
2817 W Brook St -
201822693/19/2024
Certificate Of Completion
Envelope Id: 62382052015647F29C2823D2ED92D989 Status: Completed
Subject: Complete with DocuSign: Copy of Homeowner Authorization Letter (2).pdf
Source Envelope:
Document Pages: 1 Signatures: 1 Envelope Originator:
Certificate Pages: 4 Initials: 0 My Smart House LLC
AutoNav: Enabled
EnvelopeId Stamping: Enabled
Time Zone: (UTC-08:00) Pacific Time (US & Canada)
39809 Avendia Acacias
Ste D
Murrieta, CA 92563
ops@my-smarthouse.com
IP Address: 72.211.70.159
Record Tracking
Status: Original
2/23/2024 2:58:41 PM
Holder: My Smart House LLC
ops@my-smarthouse.com
Location: DocuSign
Signer Events Signature Timestamp
Jose Gomez
johanna1123@sbcglobal.net
Security Level: Email, Account Authentication
(None)
Signature Adoption: Pre-selected Style
Using IP Address: 174.243.154.239
Signed using mobile
Sent: 2/23/2024 3:00:13 PM
Resent: 3/1/2024 12:34:54 PM
Viewed: 3/1/2024 12:48:29 PM
Signed: 3/1/2024 12:48:41 PM
Electronic Record and Signature Disclosure:
Accepted: 3/1/2024 12:48:29 PM
ID: 6bda5eff-e8ce-48db-b334-cd1d4ffcf61d
In Person Signer Events Signature Timestamp
Editor Delivery Events Status Timestamp
Agent Delivery Events Status Timestamp
Intermediary Delivery Events Status Timestamp
Certified Delivery Events Status Timestamp
Carbon Copy Events Status Timestamp
Witness Events Signature Timestamp
Notary Events Signature Timestamp
Envelope Summary Events Status Timestamps
Envelope Sent Hashed/Encrypted 2/23/2024 3:00:13 PM
Envelope Updated Security Checked 3/1/2024 12:34:53 PM
Certified Delivered Security Checked 3/1/2024 12:48:29 PM
Signing Complete Security Checked 3/1/2024 12:48:41 PM
Completed Security Checked 3/1/2024 12:48:41 PM
Payment Events Status Timestamps
Electronic Record and Signature Disclosure
2817 W Brook St -
201822693/19/2024
ELECTRONIC RECORD AND SIGNATURE DISCLOSURE
From time to time, MSH (we, us or Company) may be required by law to provide to you certain
written notices or disclosures. Described below are the terms and conditions for providing to you
such notices and disclosures electronically through the DocuSign system. Please read the
information below carefully and thoroughly, and if you can access this information electronically
to your satisfaction and agree to this Electronic Record and Signature Disclosure (ERSD), please
confirm your agreement by selecting the check-box next to ‘I agree to use electronic records and
signatures’ before clicking ‘CONTINUE’ within the DocuSign system.
Getting paper copies
At any time, you may request from us a paper copy of any record provided or made available
electronically to you by us. You will have the ability to download and print documents we send
to you through the DocuSign system during and immediately after the signing session and, if you
elect to create a DocuSign account, you may access the documents for a limited period of time
(usually 30 days) after such documents are first sent to you. After such time, if you wish for us to
send you paper copies of any such documents from our office to you, you will be charged a
$0.00 per-page fee. You may request delivery of such paper copies from us by following the
procedure described below.
Withdrawing your consent
If you decide to receive notices and disclosures from us electronically, you may at any time
change your mind and tell us that thereafter you want to receive required notices and disclosures
only in paper format. How you must inform us of your decision to receive future notices and
disclosure in paper format and withdraw your consent to receive notices and disclosures
electronically is described below.
Consequences of changing your mind
If you elect to receive required notices and disclosures only in paper format, it will slow the
speed at which we can complete certain steps in transactions with you and delivering services to
you because we will need first to send the required notices or disclosures to you in paper format,
and then wait until we receive back from you your acknowledgment of your receipt of such
paper notices or disclosures. Further, you will no longer be able to use the DocuSign system to
receive required notices and consents electronically from us or to sign electronically documents
from us.
All notices and disclosures will be sent to you electronically
Electronic Record and Signature Disclosure created on: 2/6/2020 1:48:36 PM
Parties agreed to: Jose Gomez 2817 W Brook St -
201822693/19/2024
Unless you tell us otherwise in accordance with the procedures described herein, we will provide
electronically to you through the DocuSign system all required notices, disclosures,
authorizations, acknowledgements, and other documents that are required to be provided or made
available to you during the course of our relationship with you. To reduce the chance of you
inadvertently not receiving any notice or disclosure, we prefer to provide all of the required
notices and disclosures to you by the same method and to the same address that you have given
us. Thus, you can receive all the disclosures and notices electronically or in paper format through
the paper mail delivery system. If you do not agree with this process, please let us know as
described below. Please also see the paragraph immediately above that describes the
consequences of your electing not to receive delivery of the notices and disclosures
electronically from us.
How to contact MSH:
You may contact us to let us know of your changes as to how we may contact you electronically,
to request paper copies of certain information from us, and to withdraw your prior consent to
receive notices and disclosures electronically as follows:
To contact us by email send messages to: britney@my-smarthouse.com
To advise MSH of your new email address
To let us know of a change in your email address where we should send notices and disclosures
electronically to you, you must send an email message to us at britney@my-smarthouse.com and
in the body of such request you must state: your previous email address, your new email
address. We do not require any other information from you to change your email address.
If you created a DocuSign account, you may update it with your new email address through your
account preferences.
To request paper copies from MSH
To request delivery from us of paper copies of the notices and disclosures previously provided
by us to you electronically, you must send us an email to britney@my-smarthouse.com and in
the body of such request you must state your email address, full name, mailing address, and
telephone number. We will bill you for any fees at that time, if any.
To withdraw your consent with MSH
To inform us that you no longer wish to receive future notices and disclosures in electronic
format you may:
2817 W Brook St -
201822693/19/2024
i. decline to sign a document from within your signing session, and on the subsequent page,
select the check-box indicating you wish to withdraw your consent, or you may;
ii. send us an email to britney@my-smarthouse.com and in the body of such request you must
state your email, full name, mailing address, and telephone number. We do not need any other
information from you to withdraw consent.. The consequences of your withdrawing consent for
online documents will be that transactions may take a longer time to process..
Required hardware and software
The minimum system requirements for using the DocuSign system may change over time. The
current system requirements are found here: https://support.docusign.com/guides/signer-guide-
signing-system-requirements.
Acknowledging your access and consent to receive and sign documents electronically
To confirm to us that you can access this information electronically, which will be similar to
other electronic notices and disclosures that we will provide to you, please confirm that you have
read this ERSD, and (i) that you are able to print on paper or electronically save this ERSD for
your future reference and access; or (ii) that you are able to email this ERSD to an email address
where you will be able to print on paper or save it for your future reference and access. Further,
if you consent to receiving notices and disclosures exclusively in electronic format as described
herein, then select the check-box next to ‘I agree to use electronic records and signatures’ before
clicking ‘CONTINUE’ within the DocuSign system.
By selecting the check-box next to ‘I agree to use electronic records and signatures’, you confirm
that:
You can access and read this Electronic Record and Signature Disclosure; and
You can print on paper this Electronic Record and Signature Disclosure, or save or send
this Electronic Record and Disclosure to a location where you can print it, for future
reference and access; and
Until or unless you notify MSH as described above, you consent to receive exclusively
through electronic means all notices, disclosures, authorizations, acknowledgements, and
other documents that are required to be provided or made available to you by MSH
during the course of your relationship with MSH.
2817 W Brook St -
201822693/19/2024
2817 W Brook St -
201822693/19/2024
2817 W Brook St -
201822693/19/2024
Rev: 7/15/2021
RESIDENTIAL
PHOTOVOLTAIC
SOL-01 CBC 2019
Solar Photovoltaic (PV) Checklist for Detached SINGLE FAMILY RESIDENCES Only
Instructions: The licensed contractor of record shall complete all sections, answer the ten questions and
sign the certification section below. A copy of this form shall be attached to each of TWO sets of plans, of
minimum 11” x 17” size. If answering NO to any of the questions, plan check shall be required.
Project Address:
Contractor Company Name:
Contractor License Number:
YES NO Are the following applicable to the proposed project?
1. Will the PV system layout provide the required three-foot wide clear access pathways
per Section 605.11 of the California Fire Code, and is this shown on the roof plan?
2. Will the PV system be installed on a roof having only one roofing layer with no
overlays?
3. Will the PV array be flush mounted to the existing roof so that the plane of the
modules (panels) are parallel to the plane of the roof?
4. Will the PV system weigh maximum 4 pounds per square feet or less?
5. Will the PV system be installed where the modules do not overhang any roof edges
(such as eaves, gabled ends, ridges and hips)?
6. Will the PV system be installed with a space of 2” minimum to 10” maximum between
the underside of modules and the surface of the roof?
7. Will the PV system be installed without using any ballast system or counter-weight
system?
8. Will the anchors be installed with a maximum horizontal anchor spacing of 6 feet
and is this maximum horizontal spacing shown on the plans?
9. Will the minimum 5/16” lag screws be installed with a minimum of 2-1/2 inch
embedment into roof rafters (with pre-drilled holes) and is this minimum embedment
shown on the plans?
10. Are ALL the structural pages of the plans stamped and signed by a California
licensed professional engineer? (including project specific site plan, PV layout,
anchorage spacing, anchorage details and manufacturer’s PV support information.)
I certify under penalty of perjury under the laws of the State of California that the above is true:
Print Name: Signature:
Phone Number: Date:
Email Address:
Planning & Building Agency
Building Safety Division
20 Civic Center Plaza
P.O. Box 1988 (M-19)
Santa Ana, CA 92702
(714) 647-5800
www.santa-ana.org
Complete Solar
961988
2817 W Brook St, Santa Ana
John Carey
2/19/2024(951) 263-7275
permitting@completesolar.com
2817 W Brook St -
201822693/19/2024
Page 1 of 1
EXISTING ONE & TWO FAMILY DWELLINGS
ELECTRICAL SERVICES UNDERGROUND
EXCEPTION
CEC 2019 ELC-04
All new utility connections are required to be installed below grade by Santa Ana Municipal Code 41-
626(b). There is a standing exception for one and two family dwellings. This exception
applies only when the new electrical service is designed to be fed from below grade as well as
overhead.
This diagram is a typical unit. The utility is able to feed this cabinet from the top or the bottom without
interfering with the distribution wiring. All the circuit breakers and branch circuits are contained in the
circuit breaker side of this cabinet.
Only listed combination overhead and underground feed service boxes may be used to connect to
an overhead utility drop. This exception to an underground fed service applies only to existing single
family and two family residences.
Planning & Building Agency
Permits & Plan Check Section
20 Civic Center Plaza
P.O. Box 1988 (M-19)
Santa Ana, CA 92702
(714) 647-5800
Rigid
Conduit
Service
Entrance
Conductor
Riser
Underground
Service
Lateral
METER
Rev. 1/21/2020
2817 W Brook St -
201822693/19/2024