HomeMy WebLinkAbout801 E Santa Ana Blvd - Plan 29.20kW ROOF TOP PHOTOVOLTAIC SYSTEM PV System Summary:Site Location: House Aerial View: SYSTEM SIZE (DC) : 73 X 400 = 29.20kW DC : PTC: 73 X 376.55 = 27.49kW DC SYSTEM SIZE (AC) : 73 X 376.55 X 97% = 26.66kW AC MODULES : 73 X URECO FMB400MFG-BB INVERTER : 73 X ENPHASE IQ8PLUS-72-2-US MAIN SERVICE PANEL : (E) 800A BUS WITH (E) 800A MAIN BREAKER INTERCONNECTION : TIED TO PV BREAKER IN MSP OCPD RATING : 150A/2P BREAKER STRINGING : 1 X STRING OF 7 MODULES 6 X STRING OF 1 1 MODULES UTILITY : SOUTHERN CALIFORNIA EDISON (SCE) SHEET:TITLE:CLIENT:REVISIONS: JOB NO.: DESIGN BY: DESCRIPTION DATE REVISION HOMEAID FX RESIDENCE 801 SANTA ANA BLVD SANTA ANA, CA TEL: 949-220-1136 CSS2212-001 TMG C: \ U s e r s \ A d m i n \ D e s k t o p \ d i a b l o \ 1 2 - 0 2 - 2 2 H o m e A i d F X R e s i d e n c e _ C S S - 2 2 - 1 2 - 0 0 1 \ 1 2 - 0 2 - 2 2 H o m e A i d F X R e s i d e n c e _ C S S - 2 2 - 1 2 - 0 0 1 . d w g DATE: 12/2/2022 PV-1 CALSTATE SOLAR 29990 TECHNOLOGY DRIVE, #14 & #15 MURRIETA, CA 92563 License # 1006247 INSTALLER: CALSTATE SOLAR 29990 TECHNOLOGY DRIVE, #14 & #15 MURRIETA, CA 92563 License # 1006247 COVER SHEET General Notes: 2022 CALIFORNIA BUILDING CODE (CBC) 2022 CALIFORNIA RESIDENTIAL CODE (CRC) 2022 CALIFORNIA ELECTRICAL CODE (CEC) 2022 CALIFORNIA MECHANICAL CODE (CMC) 2022 CALIFORNIA PLUMBING CODE (CPC) 2022 CALIFORNIA FIRE CODE (CFC) AS ADOPTED BY CITY OF SANTA ANA Installation Notes: Project Complies with Following Codes: PV-1 COVER SHEET PV-2 SITE PLAN PV-2A ROOF PLAN WITH MODULE LAYOUT PV-3 STRINGING DIAGRAM PV-4 ELECTRICAL LINE DIAGRAM PV-5 ATT. DETAIL, EQUIP. ELEV & MAT. LIST PV-6 LABELS PV-7 DATA SHEET: MODULE PV-8 DATA SHEET: INVERTER PV-9 DATA SHEET: ENVOY MONITORING PV-10 DATA SHEET: MOUNT Sheet Index: CONSTRUCTION TYPE = VB NUMBER OF STORIES = 2 STORIES OCCUPANCY GROUP = R2 FIRE SPRINKLERS = Y PV-11 DATASHEET: MOUNT TEST CERTIFICATE PV-12 DATASHEET: MOUNT TEST CERTIFICATE PV-13 DATASHEET: MOUNT TEST CERTIFICATE PV-14 DATASHEET: RAIL PV-15 DATASHEET: RAIL FIRE RATING THE PV BREAKER SHALL NOT EXCEED 120% OF THE ALLOWABLE BACK FEED OF THE MAIN SERVICE BUSS RATING. PV WIRE SHALL BE USED ON DC RUNS FOR UNGROUNDED/TRANSFORMERLESS INVERTERS. INSTALL CREW TO VERIFY ROOF STRUCTURE PRIOR TO COMMENCING WORK. THE PV BREAKER SHALL NOT EXCEED 120% OF THE ALLOWABLE BACK FEED OF THE MAIN SERVICE BUSS RATING. PV WIRE SHALL BE USED ON DC RUNS FOR UNGROUNDED/TRANSFORMERLESS INVERTERS. INSTALL CREW TO VERIFY ROOF STRUCTURE PRIOR TO COMMENCING WORK. RESIDENTIAL BUILDING UNDERGROUND ADDITION OR IMPROVEMENTS SHALL REPLACE NON-COMPLIANT PLUMBING FIXTURES WITH WATER CONSERVING PLUMBING FIXTURES IN ACCORDANCE WITH CGBSC SECTION301.1.1 AND CIVIL CODE 1101.1 AS FOLLOWS: ~WATER CLOSETS: 1.6 GPF (GPF= GALLONS PER FLUSH) ~FAUCETS (ALL INTERIOR) 2.2 ( GPM = GALLIONS PER MINUTE) ~URINALS 1.0 GPF ~SHOWER HEADS 2.5 GPM MODULES SHALL BE TESTED , LISTED AND INDENTIFIED WITH FIRE CLASSIFICATION IN ACCORDANCE WITH UL 1703. THE FIRE CLASSIFICATION SHALL COMPLY WITH TABLE 1505.1OF THE CALIFORNIA BUILDING CODE BASED ON THE TYPE OF CONSTRUCTION OF THE BUILDING. CRC SECTION R902.4 SMOKE AND CARBON MONOXIDE ALARMS ARE REQUIRED PER CRC SECTION R314 AND 315 TO BE VERIFIED AND INSPECTED BY INSPECTOR IN THE FIELD. 1. CONDUIT RUNS ARE DIAGRAMMATIC, SUBJECT TO FIELD CONDITIONS AND INSTALLATION CONTRACTOR'S FINAL LOCATIONS THAT MEET NEC REQUIREMENTS. 2. ALL EQUIPMENT INSTALLED SHALL BE IN ACCORDANCE WITH ALL LOCAL BUILDING AND ELECTRICAL CODES. 3. THIS SYSTEM HAS BEEN DESIGNED IN COMPLIANCE WITH THE CBC SECTION 1609 TO WITHSTAND 85MPH WINDLOADS. REFER TO RACKING DATASHEET. 4. THE INSTALLATION CONTRACTOR SHALL BE RESPONSIBLE FOR READING AND UNDERSTANDING THE SECTION OF THE INVERTERS OPERATION AND MAINTENANCE MANUAL THAT PERTAINS TO THE SAFETY AND PROPER INSTALLATION. 5. THIS SYSTEM SALL NOT BE INTERCONNECTED UNTIL APPROVAL FROM LOCAL JURISDICTION AND THE UTILITY IS OBTAINED. 6. ALL CONDUCTORS TO BE COPPER UNLESS SPECIFIED OTHERWISE. 7. THE SOLAR PHOTOVOLTAIC INSTALLATION WILL NOT OBSTRUCT ANY PLUMBING, MECHANICAL OR EASEMENTS. 8. LIQUID TIGHT FLEXIBLE CONDUITS SHALL BE SUNLIGHT RESISTANT. 9. THIS IS A UTILITY INTERACTIVE SYSTEM WITH NO STORAGE BATTERIES. N/A N/A BLDG# 101116032 ELECT# 20180445 M.Smith ISSUED: 12/12/2023 APPROVALS PLNG - H. Jacinto BLDG - J. Lo 801 E Santa Ana Blvd - 101116032 & 2018044512/18/2023 SHEET:TITLE:CLIENT:REVISIONS:JOB NO.: DESIGN BY: DESCRIPTION DATE REVISIONHOMEAID FX RESIDENCE 801 SANTA ANA BLVD SANTA ANA, CA TEL: 949-220-1136 CSS2212-001 TMG C: \ U s e r s \ A d m i n \ D e s k t o p \ d i a b l o \ 1 2 - 0 2 - 2 2 H o m e A i d F X R e s i d e n c e _ C S S - 2 2 - 1 2 - 0 0 1 \ 1 2 - 0 2 - 2 2 H o m e A i d F X R e s i d e n c e _ C S S - 2 2 - 1 2 - 0 0 1 . d w g DATE:12/2/2022 PV-9 CALSTATE SOLAR 29990 TECHNOLOGY DRIVE, #14 & #15 MURRIETA, CA 92563 License # 1006247 INSTALLER: CALSTATE SOLAR 29990 TECHNOLOGY DRIVE, #14 & #15 MURRIETA, CA 92563 License # 1006247 DATA SHEET: ENVOY MONITORING 801 E Santa Ana Blvd - 101116032 & 2018044512/18/2023 SHEET:TITLE:CLIENT:REVISIONS:JOB NO.: DESIGN BY: DESCRIPTION DATE REVISIONHOMEAID FX RESIDENCE 801 SANTA ANA BLVD SANTA ANA, CA TEL: 949-220-1136 CSS2212-001 TMG C: \ U s e r s \ A d m i n \ D e s k t o p \ d i a b l o \ 1 2 - 0 2 - 2 2 H o m e A i d F X R e s i d e n c e _ C S S - 2 2 - 1 2 - 0 0 1 \ 1 2 - 0 2 - 2 2 H o m e A i d F X R e s i d e n c e _ C S S - 2 2 - 1 2 - 0 0 1 . d w g DATE:12/2/2022 PV-10 CALSTATE SOLAR 29990 TECHNOLOGY DRIVE, #14 & #15 MURRIETA, CA 92563 License # 1006247 INSTALLER: CALSTATE SOLAR 29990 TECHNOLOGY DRIVE, #14 & #15 MURRIETA, CA 92563 License # 1006247 DATA SHEET: MOUNT 801 E Santa Ana Blvd - 101116032 & 2018044512/18/2023 SHEET:TITLE:CLIENT:REVISIONS:JOB NO.: DESIGN BY: DESCRIPTION DATE REVISIONHOMEAID FX RESIDENCE 801 SANTA ANA BLVD SANTA ANA, CA TEL: 949-220-1136 CSS2212-001 TMG C: \ U s e r s \ A d m i n \ D e s k t o p \ d i a b l o \ 1 2 - 0 2 - 2 2 H o m e A i d F X R e s i d e n c e _ C S S - 2 2 - 1 2 - 0 0 1 \ 1 2 - 0 2 - 2 2 H o m e A i d F X R e s i d e n c e _ C S S - 2 2 - 1 2 - 0 0 1 . d w g DATE:12/2/2022 PV-11 CALSTATE SOLAR 29990 TECHNOLOGY DRIVE, #14 & #15 MURRIETA, CA 92563 License # 1006247 INSTALLER: CALSTATE SOLAR 29990 TECHNOLOGY DRIVE, #14 & #15 MURRIETA, CA 92563 License # 1006247 DATASHEET: MOUNT TEST CERTIFICATE 801 E Santa Ana Blvd - 101116032 & 2018044512/18/2023 SHEET:TITLE:CLIENT:REVISIONS:JOB NO.: DESIGN BY: DESCRIPTION DATE REVISIONHOMEAID FX RESIDENCE 801 SANTA ANA BLVD SANTA ANA, CA TEL: 949-220-1136 CSS2212-001 TMG C: \ U s e r s \ A d m i n \ D e s k t o p \ d i a b l o \ 1 2 - 0 2 - 2 2 H o m e A i d F X R e s i d e n c e _ C S S - 2 2 - 1 2 - 0 0 1 \ 1 2 - 0 2 - 2 2 H o m e A i d F X R e s i d e n c e _ C S S - 2 2 - 1 2 - 0 0 1 . d w g DATE:12/2/2022 PV-12 CALSTATE SOLAR 29990 TECHNOLOGY DRIVE, #14 & #15 MURRIETA, CA 92563 License # 1006247 INSTALLER: CALSTATE SOLAR 29990 TECHNOLOGY DRIVE, #14 & #15 MURRIETA, CA 92563 License # 1006247 DATASHEET: MOUNT TEST CERTIFICATE 801 E Santa Ana Blvd - 101116032 & 2018044512/18/2023 SHEET:TITLE:CLIENT:REVISIONS:JOB NO.: DESIGN BY: DESCRIPTION DATE REVISIONHOMEAID FX RESIDENCE 801 SANTA ANA BLVD SANTA ANA, CA TEL: 949-220-1136 CSS2212-001 TMG C: \ U s e r s \ A d m i n \ D e s k t o p \ d i a b l o \ 1 2 - 0 2 - 2 2 H o m e A i d F X R e s i d e n c e _ C S S - 2 2 - 1 2 - 0 0 1 \ 1 2 - 0 2 - 2 2 H o m e A i d F X R e s i d e n c e _ C S S - 2 2 - 1 2 - 0 0 1 . d w g DATE:12/2/2022 PV-13 CALSTATE SOLAR 29990 TECHNOLOGY DRIVE, #14 & #15 MURRIETA, CA 92563 License # 1006247 INSTALLER: CALSTATE SOLAR 29990 TECHNOLOGY DRIVE, #14 & #15 MURRIETA, CA 92563 License # 1006247 DATASHEET: MOUNT TEST CERTIFICATE 801 E Santa Ana Blvd - 101116032 & 2018044512/18/2023 SHEET:TITLE:CLIENT:REVISIONS:JOB NO.: DESIGN BY: DESCRIPTION DATE REVISIONHOMEAID FX RESIDENCE 801 SANTA ANA BLVD SANTA ANA, CA TEL: 949-220-1136 CSS2212-001 TMG C: \ U s e r s \ A d m i n \ D e s k t o p \ d i a b l o \ 1 2 - 0 2 - 2 2 H o m e A i d F X R e s i d e n c e _ C S S - 2 2 - 1 2 - 0 0 1 \ 1 2 - 0 2 - 2 2 H o m e A i d F X R e s i d e n c e _ C S S - 2 2 - 1 2 - 0 0 1 . d w g DATE:12/2/2022 PV-14 CALSTATE SOLAR 29990 TECHNOLOGY DRIVE, #14 & #15 MURRIETA, CA 92563 License # 1006247 INSTALLER: CALSTATE SOLAR 29990 TECHNOLOGY DRIVE, #14 & #15 MURRIETA, CA 92563 License # 1006247 DATASHEET: RAIL 801 E Santa Ana Blvd - 101116032 & 2018044512/18/2023 SHEET:TITLE:CLIENT:REVISIONS:JOB NO.: DESIGN BY: DESCRIPTION DATE REVISIONHOMEAID FX RESIDENCE 801 SANTA ANA BLVD SANTA ANA, CA TEL: 949-220-1136 CSS2212-001 TMG C: \ U s e r s \ A d m i n \ D e s k t o p \ d i a b l o \ 1 2 - 0 2 - 2 2 H o m e A i d F X R e s i d e n c e _ C S S - 2 2 - 1 2 - 0 0 1 \ 1 2 - 0 2 - 2 2 H o m e A i d F X R e s i d e n c e _ C S S - 2 2 - 1 2 - 0 0 1 . d w g DATE:12/2/2022 PV-15 CALSTATE SOLAR 29990 TECHNOLOGY DRIVE, #14 & #15 MURRIETA, CA 92563 License # 1006247 INSTALLER: CALSTATE SOLAR 29990 TECHNOLOGY DRIVE, #14 & #15 MURRIETA, CA 92563 License # 1006247 DATASHEET: RAIL FIRE RATING 801 E Santa Ana Blvd - 101116032 & 2018044512/18/2023 IQ C MS P JB AC D 1'6 " F I R E M A R S H A L S E T B A C K 1'6 " F I R E M A R S H A L S E T B A C K 1'6" FI R E M A R S H A L S E T B A C K 1'6" FI R E S E T B A C K 1'6 " F I R E S E T B A C K 1'6 " F I R E S E T B A C K 1'6 " F I R E S E T B A C K 1'6 " F I R E S E T B A C K 1'6" FI R E S E T B A C K 1'6" F I R E S E T B A C K 1'6 " F I R E S E T B A C K SHEET:TITLE:CLIENT:REVISIONS:JOB NO.: DESIGN BY: DESCRIPTION DATE REVISIONHOMEAID FX RESIDENCE 801 SANTA ANA BLVD SANTA ANA, CA TEL: 949-220-1136 CSS2212-001 TMG C: \ U s e r s \ A d m i n \ D e s k t o p \ d i a b l o \ 1 2 - 0 2 - 2 2 H o m e A i d F X R e s i d e n c e _ C S S - 2 2 - 1 2 - 0 0 1 \ 1 2 - 0 2 - 2 2 H o m e A i d F X R e s i d e n c e _ C S S - 2 2 - 1 2 - 0 0 1 . d w g DATE:12/2/2022 PV-2 CALSTATE SOLAR 29990 TECHNOLOGY DRIVE, #14 & #15 MURRIETA, CA 92563 License # 1006247 INSTALLER: CALSTATE SOLAR 29990 TECHNOLOGY DRIVE, #14 & #15 MURRIETA, CA 92563 License # 1006247 SITE PLAN REAR Y A R D DRIVE W A Y 2 STORY HOUSE PROPERTY LINE ROOF LINE (E) 800A MSP (N)URECO FMB400MFG-BB MODULES FRON T SANT A A N A B L V D GARA G E SCALE: 1/16" = 1'-0" Site Plan R1 R2 R3 R4 801 E Santa Ana Blvd - 101116032 & 2018044512/18/2023 IQ C MS P JB AC D 1'6 " F I R E M A R S H A L S E T B A C K 1'6 " F I R E M A R S H A L S E T B A C K 1'6" FI R E M A R S H A L S E T B A C K 1'6" F I R E S E T B A C K 1'6 " F I R E S E T B A C K 1'6 " F I R E S E T B A C K 1'6 " F I R E S E T B A C K 1'6 " F I R E S E T B A C K 1'6" FI R E S E T B A C K 1'6" F I R E S E T B A C K 1'6 " F I R E S E T B A C K SHEET:TITLE:CLIENT:REVISIONS:JOB NO.: DESIGN BY: DESCRIPTION DATE REVISIONHOMEAID FX RESIDENCE 801 SANTA ANA BLVD SANTA ANA, CA TEL: 949-220-1136 CSS2212-001 TMG C: \ U s e r s \ A d m i n \ D e s k t o p \ d i a b l o \ 1 2 - 0 2 - 2 2 H o m e A i d F X R e s i d e n c e _ C S S - 2 2 - 1 2 - 0 0 1 \ 1 2 - 0 2 - 2 2 H o m e A i d F X R e s i d e n c e _ C S S - 2 2 - 1 2 - 0 0 1 . d w g DATE:12/2/2022 PV-2A CALSTATE SOLAR 29990 TECHNOLOGY DRIVE, #14 & #15 MURRIETA, CA 92563 License # 1006247 INSTALLER: CALSTATE SOLAR 29990 TECHNOLOGY DRIVE, #14 & #15 MURRIETA, CA 92563 License # 1006247 ROOF PLAN WITH MODULE LAYOUT VENT PIPES CHIMNEY (N)JUNCTION BOX (N)150A LOAD CENTER DORMER VENTS VENT/SKYLIGHT (N)URECO FMB400MFG-BB (N) ENPHASE IQ8PLUS-72-2-US MICRO-INVERTER IRONRIDGE XR10 RAIL (N)3/4" EMT CONDUIT EXTERNAL RUN (N) ATTACHMENT POINTS @ 48" O.C. MAX. ATTACH CLAMPS AT 25% FROM EDGE AND 50% FROM CENTER OF MODULES 1 JUNCTION BOX MOUNTED TO THE RAIL 2 3 EMT CONDUIT SUPPORTED BY PIPE HANGERS (N)200A AC DISCONNECT 2X4@24" RAFTERS (TYP.) (E) 800A MSP 1 2 3 SCALE: 1/16" = 1'-0" Module Layout Notes: Legend: ROOF: TYPE: ATTACHMENT : ROOF AREA : % OF COVERED AREA: MODULE QTY: PV AREA : SPRINKLERED:Y N RAFTER:AZIMUTH: PITCH: % SQFTSQFT478.04 13 COMP-SHINGLE UNIRAC 2-PIECE STANDOFF 274.56 57.43 R1 18°248°2X4@24" TOTAL ROOF SURFACE AREA TOTAL ROOF AREA SQ.FT: % OF COVERED TOTAL AREA: TOTAL ARRAY AREA SQ.FT: SQ.FT SQ.FT % 9793.00 1541.76 15.74 1 X STRINGS OF 7 & X 6 STRINGS OF 11 URECO FMB400MFG-BB MODULES WITH ENPHASE IQ8PLUS-72-2-US (208V) MICRO-INVERTER UNDERNEATH EACH MODULE Roof and Array Details: R1 System Configuration ROOF: TYPE: ATTACHMENT : ROOF AREA : % OF COVERED AREA: MODULE QTY: PV AREA : SPRINKLERED:Y N RAFTER:AZIMUTH: PITCH: % SQFTSQFT1017.73 28 COMP-SHINGLE UNIRAC 2-PIECE STANDOFF 591.36 58.11 R2 18°158°2X4@24" ROOF: TYPE: ATTACHMENT : ROOF AREA : % OF COVERED AREA: MODULE QTY: PV AREA : SPRINKLERED:Y N RAFTER:AZIMUTH: PITCH: % SQFTSQFT461.21 10 COMP-SHINGLE UNIRAC 2-PIECE STANDOFF 211.20 45.79 R3 18°248°2X4@24" ROOF: TYPE: ATTACHMENT : ROOF AREA : % OF COVERED AREA: MODULE QTY: PV AREA : SPRINKLERED:Y N RAFTER:AZIMUTH: PITCH: % SQFTSQFT822.86 22 COMP-SHINGLE UNIRAC 2-PIECE STANDOFF 464.64 56.47 R4 18°248°2X4@24" 8'- 6 " 8'- 3 " 11 ' - 1 0 " 7'- 2 " 5'-10" 8'-7" 9'-11" 3'-1" R2 R3 R4 3'-6" 3'-2" 801 E Santa Ana Blvd - 101116032 & 2018044512/18/2023 CLIENT:REVISIONS:JOB NO.:TITLE:SHEET: DESIGN BY: HOMEAID FX RESIDENCE DESCRIPTION DATE REVISION 801 SANTA ANA BLVD SANTA ANA, CA TEL: 949-220-1136 CSS2212-001 TMG DATE:12/2/2022 PV-3 CALSTATE SOLAR 29990 TECHNOLOGY DRIVE, #14 & #15 MURRIETA, CA 92563 License # 1006247 INSTALLER: CALSTATE SOLAR 29990 TECHNOLOGY DRIVE, #14 & #15 MURRIETA, CA 92563 License # 1006247 ELECTRICAL LINE DIAGRAM PV MODULE G G G G G G G G G G G LOAD CENTER JB 14 - #12 AWG, BRANCH CABLES INTEGRAL TO INVERTERS 1 - #6 AWG, BARE COPPER GROUND 14 - #10 AWG, THWN-2, HOT 1 - #10 AWG, THWN-2, GND 2 - #1 AWG, THWN-2, HOT 1 - #4 AWG, THWN-2, GND 1 - #1 AWG, THWN-2, NEUT 1-1/2" EMT CONDUIT, EXTERNAL OR ENPHASE MICRO-INVERTER G G G G G G G G G G G G G G G G G G G G G G G G G G G G G G G G G PV ARRAY: 29.20 kW PHOTOVOLTAIC ARRAY MFG: URECO MODEL: URECO FMB400MFG-BB 1 STRINGS OF 7 URECO FMB400MFG-BB MODULES AND 6 STRINGS OF 11 URECO FMB400MFG-BB MODULES ATTACHED WITH ENPHASE IQ8PLUS-72-2-US (208V) INVERTER OPEN CIRCUIT VOLTAGE PER MODULE (VOC): 45.30V MAX. POWER VOLATE PER MODULE (VMP): 37.13V SHORT CIRCUIT CURRENT PER MODULE (ISC) : 11.14A MAX. POWER CURRENT PER MODULE (IMP): 10.77A ARRAY NOTES: 1.EQUIPMENT INSTALLED IN ACCORDANCE WITH THE NEC SECTION 690 AND ALL APPLICABLE REQUIREMENTS OF SERVICE UTILITY AND AUTHORITY HAVING JURISDICTION (AHJ). 2.GROUND WIRE MUST BE CONTINUOUS AND INSTALLED TO ALLOW FOR PANEL REMOVAL WITHOUT DISRUPTING CONTINUITY. ALL MODULE GROUND CONNECTIONS SHALL BE MADE IN ACCORDANCE WITH NEC 690.4 (C). 3.FOLLOW MANUFACTURERS SUGGESTED INSTALLATION PRACTICES AND WIRING SPECIFICATIONS. 4.WIRES SHALL BE RATED AND LABELED "SUNLIGHT RESISTANT" WHERE EXPOSED TO AMBIENT CONDITIONS. G G G G G G G G G G G G G G G G G G G G G G JB JB G G G G G G G 1-1/2" FMC CONDUIT, INTERNAL 801 E Santa Ana Blvd - 101116032 & 2018044512/18/2023 +- AC DC +-AC DC +-AC DC +-AC DC CLIENT:REVISIONS:JOB NO.:TITLE:SHEET: DESIGN BY: HOMEAID FX RESIDENCE DESCRIPTION DATE REVISION 801 SANTA ANA BLVD SANTA ANA, CA TEL: 949-220-1136 CSS2212-001 TMG DATE:12/2/2022 PV-4 CALSTATE SOLAR 29990 TECHNOLOGY DRIVE, #14 & #15 MURRIETA, CA 92563 License # 1006247 INSTALLER: CALSTATE SOLAR 29990 TECHNOLOGY DRIVE, #14 & #15 MURRIETA, CA 92563 License # 1006247 ELECTRICAL LINE DIAGRAM MODULE SPEC: URECO FMB400MFG-BB QTY WATTS PTC WATTS VOC (V) VMP (V) ISC (A) IMP (A) 73 400 376.55 45.30 37.13 11.14 10.77 INVERTER SPEC: ENPHASE IQ8PLUS-72-2-US QTY WATTS AMPS VOLTS CEC EFFICIENCY 73 290 1.21 208 97% CONDUCTOR / CONDUIT SCHEDULE TAG CONDUCTOR CONDUCTOR SIZE # OF CONDUCTORS CONDUIT/CABLE TYPE CONDUIT SIZE A ENPHASE Q CABLE #12 AWG 2 FREE AIR N/A EGC/GEC: BARE COPPER #6 AWG 1 A1 ENPHASE Q CABLE #12 AWG 2 FREE AIR N/A EGC/GEC: BARE COPPER #6 AWG 1 B LINE: THHN/THWN-2 #10 AWG 2 EMT 3/4" EGC/GEC: THHN/THWN-2 #8 AWG 1 B1 LINE: THHN/THWN-2 #10 AWG 2 EMT 3/4" EGC/GEC: THHN/THWN-2 #8 AWG 1 C LINE & NEUTRAL: THHN/THWN-2 #1 AWG 3 EMT 1-1/2" EGC/GEC: THHN/THWN-2 #4 AWG 1 C CONDUCTOR AMPS CALCULATION CONDUCTOR AMPS TEMP DERATE CONDUIT FILL INV. QTY INV. AMPS NEC STRING AMPS DERATED CONDUCTOR AMPS 30 0.8 1 13 1.21 1.25 19.66 24.00 30 0.8 1 12 1.21 1.25 18.15 24.00 40 0.8 0.8 13 1.21 1.25 19.66 25.60 40 0.8 0.8 12 1.21 1.25 18.15 25.60 145 0.8 1 73 1.39 1.25 126.83 130.5 BACKFEED CALCULATION 800 X 1.2 = 960 AMPS 960 -800 = 160A MAX. BACKFEED OCPD CALCULATION INV QTY X INV CURRENT X1.25 73 X 1.39 X 1.25 = 126.83A = 150A OCPD 150A =< 160A = OK STRING-3 STRING-4 STRING-5 STRING-6 SYSTEM SUMMARY :29.20 kW DC / 26.66 kW AC N GN D L2L1 +-AC DC +- AC DC (11) URECO FMB400MFG-BB MODULES (7) URECO FMB400MFG-BB MODULES A B STRING-1 STRING-2 (11) URECO FMB400MFG-BB MODULES (11) URECO FMB400MFG-BB MODULES (11) URECO FMB400MFG-BB MODULES (11) URECO FMB400MFG-BB MODULES enphase 15A/2P 20A/2P 20A/2P 20A/2P 20A/2P 20A/2P 20A/2P (N)150A, LOAD CENTER (N)200A, AC DISCONNECT 240V NEMA-3R 2 - #12 AWG 1 - #10 AWG, GND IN 1/2" EMT CONDUIT +-AC DC A1 B1 STRING-7 (11) URECO FMB400MFG-BB MODULES 20A/2P 801 E Santa Ana Blvd - 101116032 & 2018044512/18/2023 IRONRIDGE XR10 RAIL 5/16" SS LAG BOLT AT THE CENTER OF RAFTER WITH A MIN. PENETRATION OF 2.5" 2X4@24" O.C. RAFTERS (TYP.) CURVED-TILE 3" PV MODULE UNIRAC 2-PIECE STANDOFF "L" BRACKET SHEET:TITLE:CLIENT:REVISIONS:JOB NO.: DESIGN BY: DESCRIPTION DATE REVISIONHOMEAID FX RESIDENCE 801 SANTA ANA BLVD SANTA ANA, CA TEL: 949-220-1136 CSS2212-001 TMG C: \ U s e r s \ A d m i n \ D e s k t o p \ d i a b l o \ 1 2 - 0 2 - 2 2 H o m e A i d F X R e s i d e n c e _ C S S - 2 2 - 1 2 - 0 0 1 \ 1 2 - 0 2 - 2 2 H o m e A i d F X R e s i d e n c e _ C S S - 2 2 - 1 2 - 0 0 1 . d w g DATE:12/2/2022 PV-5 CALSTATE SOLAR 29990 TECHNOLOGY DRIVE, #14 & #15 MURRIETA, CA 92563 License # 1006247 INSTALLER: CALSTATE SOLAR 29990 TECHNOLOGY DRIVE, #14 & #15 MURRIETA, CA 92563 License # 1006247 ATT. DETAIL, EQUIP. ELEV & MAT. LIST 73 MODULE URECO FMB400MFG-BB 73 INVERTER ENPHASE IQ8PLUS-72-2-US 3 JUNCTION BOX 600VDC, NEMA 3R, UL LISTED 1 PV BREAKER 2 POLE, 208V, 150A 1 AC DISCONNECT 600VAC, DU324RB 3R, 200A,2P 120/240VAC 1 LOAD CENTER 150A LOAD CENTER, NEMA 3R 126 ATTACHMENTS UNIRAC 2-PIECE STANDOFF 41 RAIL IRONRIDGE XR10 RAIL-168" 116 CLAMP MID CLAMPS 60 CLAMP END CLAMPS 200' CONDUIT 3/4", 1-1/2" EMT CONDUIT AC DISCONNECT MAIN SERVICE PANEL ROOFTOP JUNCTION BOX TO ARRAY LOAD CENTER Material List:ELECTRICAL EQUIPMENT ELEVATION: ATTACHMENT DETAIL FLOOR LEVEL TO UNDERGROUND SERVICE ACD 200A 150A LOAD CENTER 801 E Santa Ana Blvd - 101116032 & 2018044512/18/2023 SHEET:TITLE:CLIENT:REVISIONS:JOB NO.: DESIGN BY: DESCRIPTION DATE REVISIONHOMEAID FX RESIDENCE 801 SANTA ANA BLVD SANTA ANA, CA TEL: 949-220-1136 CSS2212-001 TMG C: \ U s e r s \ A d m i n \ D e s k t o p \ d i a b l o \ 1 2 - 0 2 - 2 2 H o m e A i d F X R e s i d e n c e _ C S S - 2 2 - 1 2 - 0 0 1 \ 1 2 - 0 2 - 2 2 H o m e A i d F X R e s i d e n c e _ C S S - 2 2 - 1 2 - 0 0 1 . d w g DATE:12/2/2022CALSTATE SOLAR 29990 TECHNOLOGY DRIVE, #14 & #15 MURRIETA, CA 92563 License # 1006247 INSTALLER: CALSTATE SOLAR 29990 TECHNOLOGY DRIVE, #14 & #15 MURRIETA, CA 92563 License # 1006247 PV-6LABELS LABEL SPECIFICATION: 1. ALL CAPITAL LETTERS 2. MINIMUM 3/8" LETTER HEIGHT 3. AERIAL OR SIMILAR NON-BOLD 4. WHITE LETTERING IN RED BACKGROUND 5. WEATHER RESISTANT MATERIAL SUITABLE FOR THE ENVIRONMENT DURABLE ADHESIVE MATERIALS MUST MEET THIS REQUIREMENT 6. ALL SIGNS SHOULD BE REFLECTIVE PHOTOVOLTAIC SIGNAGE REQUIREMENTS PER NEC 2017 NATIONAL ELECTRIC CODE (NEC) #05-102 : 2014 NEC 690.17(E) WARNING ELECTRIC SHOCK HAZARD DO NOT TOUCH TERMINALS TERMINALS ON BOTH THE LINE AND LOAD SIDES MAY BE ENERGIZED IN THE OPEN POSITION PHOTOVOLTAIC MODULES PRONOUNCE DC VOLTAGE WHENEVER THEY ARE EXPOSED TO SUN LIGHT WARNING PHOTOVOLTAIC SYSTEM COMBINER PANEL #05-355 COMBINER PANEL DO NOT ADD LOADS #02-317 : 2014 NEC 690.56(C) PHOTOVOLTAIC SYSTEM EQUIPPED WITH RAPID SHUTDOWN JUNCTION BOX PHOTOVOLTAIC ARRAY ON ROOF SOLAR LOAD CENTER / COMBINER BOX WARNING METER AC DISCONNECTWARNING : PHOTOVOLTAIC POWER SOURCE #02-314 : 2014 NEC 690.31(G)(3) SOLAR ELECTRIC PV PANELS SOLAR PV SYSTEM EQUIPPED WITH RAPID SHUTDOWN #05-112 : 2017 NEC 690.56(C)(1)(a) TURN RAPID SHUTDOWN SWITCH TO THE "OFF" POSITION TO SHUT DOWN PV SYSTEM AND REDUCE SHOCK HAZARD IN THE ARRAY PHOTOVOLTAIC SOLAR AC DISCONNECT AC DISCONNECT #05-393, #05-323 : 2014 NEC 690.31 (B) RATED AC OUTPUT CURRENT:126.83 A NOMINAL OPERATING AC VOLTAGE : 208 V #05-211 : DUAL POWER SUPPLY DUAL POWER SUPPLY SOURCES: UTILITY GRID AND PV SOLAR ELECTRIC SYSTEM CAUTION SOLAR POINT OF CONNECTION #02-348-2017 NEC 690.13(B)(2) RAPID SHUTDOWN #05-338-PONIT OF CONNECTION CAUTION POWER TO THIS BUILDING IS ALSO SUPPLIED FROM THE FOLLOWING SOURCES WITH DISCONNECTS LOCATED AS SHOWN N MAIN SERVICE PANEL PHOTOVOLTAIC SYSTEM AC DISCONNECT #05-210 : 2014 NEC 690.54 SANT A A N A B L V D 1 - MAIN SERVICE PANEL 2 - AC DISCONNECT 3 - LOAD CENTER 4 - SOLAR ARRAY 2 3 1 4 801 E Santa Ana Blvd - 101116032 & 2018044512/18/2023 SHEET:TITLE:CLIENT:REVISIONS:JOB NO.: DESIGN BY: DESCRIPTION DATE REVISIONHOMEAID FX RESIDENCE 801 SANTA ANA BLVD SANTA ANA, CA TEL: 949-220-1136 CSS2212-001 TMG C: \ U s e r s \ A d m i n \ D e s k t o p \ d i a b l o \ 1 2 - 0 2 - 2 2 H o m e A i d F X R e s i d e n c e _ C S S - 2 2 - 1 2 - 0 0 1 \ 1 2 - 0 2 - 2 2 H o m e A i d F X R e s i d e n c e _ C S S - 2 2 - 1 2 - 0 0 1 . d w g DATE:12/2/2022 PV-7 CALSTATE SOLAR 29990 TECHNOLOGY DRIVE, #14 & #15 MURRIETA, CA 92563 License # 1006247 INSTALLER: CALSTATE SOLAR 29990 TECHNOLOGY DRIVE, #14 & #15 MURRIETA, CA 92563 License # 1006247 DATA SHEET: MODULE 801 E Santa Ana Blvd - 101116032 & 2018044512/18/2023 SHEET:TITLE:CLIENT:REVISIONS:JOB NO.: DESIGN BY: DESCRIPTION DATE REVISIONHOMEAID FX RESIDENCE 801 SANTA ANA BLVD SANTA ANA, CA TEL: 949-220-1136 CSS2212-001 TMG C: \ U s e r s \ A d m i n \ D e s k t o p \ d i a b l o \ 1 2 - 0 2 - 2 2 H o m e A i d F X R e s i d e n c e _ C S S - 2 2 - 1 2 - 0 0 1 \ 1 2 - 0 2 - 2 2 H o m e A i d F X R e s i d e n c e _ C S S - 2 2 - 1 2 - 0 0 1 . d w g DATE:12/2/2022 PV-8 CALSTATE SOLAR 29990 TECHNOLOGY DRIVE, #14 & #15 MURRIETA, CA 92563 License # 1006247 INSTALLER: CALSTATE SOLAR 29990 TECHNOLOGY DRIVE, #14 & #15 MURRIETA, CA 92563 License # 1006247 DATA SHEET: INVERTER 801 E Santa Ana Blvd - 101116032 & 2018044512/18/2023 801 E Santa Ana Blvd - 101116032 & 2018044512/18/2023 801 E Santa Ana Blvd - 101116032 & 2018044512/18/2023 Domus Structural Engineering, LLC P.O. Box 6986 Broomfield, CO 80021 530-864-7055 To: CALSTATE Solar 19 Goddard Irvine, CA. 92618 Subject: Certification Lette HomeAid FX Residence 801 Santa Ana Blvd Santa Ana, CA.  To Whom It May Concern, Design Criteria: ●Applicable Codes = 2022 CBC, ASCE 7‐16 ●Roof Dead Load = 13 psf (Roof 1) ●Roof Live Load = 20 psf ●Wind Speed = 110 mph (Vult), Exposure C ● Sincerely, John Calvert, P.E. Project Engineer The scope of this report is strictly limited to an evaluation of the fastener attachment only.  All panels, racking and hardware  shall be installed per manufacturer specifications and within specified design limitations. All waterproofing shall be provided by  the manufacturer.  Domus Structural Engineering assumes no responsibility for misuse or improper installation of the solar PV  panels or racking. Please contact me with any further questions or concerns regarding this project. Attachment: 2 ‐ 5/16 dia. lag screw with 2.5 inch min. embedment  depth, at spacing shown above. Domusstructural@gmail.com ___________________________________________________________________________________________ September 9th, 2023 The spacing of the solar standoffs should be kept at 72" o.c. for landscape and 72" o.c. for portrait orientation. A jobsite observation of the condition of the existing framing system was performed by an audit team of CALSTATE Solar as a  request from  Domus Structural Engineering. All review is based on these observations and the design criteria listed below and  only deemed valid if provided information is true and accurate. On the above referenced project, the fastener attachment has been reviewed for wind loading. If field conditions differ,  contractor to notify engineer prior to starting construction. HomeAid FX Residence Santa Ana CA.xlsm 1 801 E Santa Ana Blvd - 101116032 & 2018044512/18/2023 ___________________________________________________________________________________________________________ Domus Structural Engineering, LLC P.O. Box 6986 Broomfield, CO 80021 530-864-7055 Domusstructural@gmail.com 110 mph C Gable Roof 18 degrees 20 ft 21.3 ft 0 ft (Eq. 26.10-1) 0.90 (Table 30.3-1) 1.00 (Fig. 26.8-1) 0.85 (Table 26.6-1) 1.00 110 mph (Fig. 26.5-1A) II (Table 1.5-1) qh = 23.75 Zone 1 Zone 2 Zone 3 Positive ya =0.71 0.71 0.77 0.71 GCp =-2.00 -2.63 -3.45 0.47 (Fig. 30.3) Uplift Pressure =-33.8 psf -44.4 psf -63.1 psf 8.0 psf (Eq. 29.4-7) ASD Uplift Pressure =-20.3 psf -26.6 psf -37.9 psf 9.6 psf X Standoff Spacing = 6.00 6.00 4.00 Y Standoff Spacing = 3.04 3.04166667 3.04166667 Tributary Area = 18.25 18.25 12.17 Dead Load on attachment = 55 lb 55 lb 37 lb Footing Uplift (0.6D+0.6W) = -338 lb -454 lb -439 lb Zone 1 Zone 2 Zone 3 Positive ya =0.79 0.79 0.80 0.79 GCp =-2.00 -2.97 -3.60 0.53 (Fig. 30.3) Uplift Pressure =-37.7 psf -55.9 psf -68.4 psf 10.0 psf (Eq. 29.4-7) ASD Uplift Pressure (0.6W)=-22.6 psf -33.5 psf -41.0 psf 9.6 psf X Standoff Spacing = 6.00 6.00 4.00 Y Standoff Spacing = 1.75 1.75 1.75 Tributary Area = 10.50 10.50 7.00 Dead Load on attachment = 31.50 31.50 21.00 Footing Uplift (0.6D+0.6W) = -218 lb -333 lb -275 lb -454 lb 460 lb Therefore, OK Fastener =2 - 5/16" dia. lag Number of Fasteners = 2 Embedment Depth = 2.5 Pullout Capacity Per Inch = 250 lb Fastener Capacity = 1250 lb w/ F.S. of 1.5 & DOL of 1.6= 1334 lb Therefore, OK Wind Calculations Maximum Design Uplift = Design Wind Pressure Calculations qh = 0.00256 * Kz * Kzt * Kd * Ke * V^2 Kz (Exposure Coefficient) = Kzt (topographic factor) = Wind Speed Exposure Category Roof Shape Roof Slope Effective Wind Area Per ASCE 7‐16 Components and Cladding Input Variables Fastener Capacity Check Mean Roof Height Ground Elevation Kd (Wind Directionality Factor) = 1334.4 lb capacity > 454 lb demand Ke (Ground Elevation Factor) = V (Design Wind Speed) = Risk Category = Standoff Uplift Calculations-Portrait Standoff Uplift Calculations-Landscape Standoff Uplift Check Standoff Uplift Capacity = 460 lb capacity > 454 lb demand HomeAid FX Residence Santa Ana CA.xlsm 2 801 E Santa Ana Blvd - 101116032 & 2018044512/18/2023