Loading...
HomeMy WebLinkAbout500 W Tribella Ct - 20178112 - Plan500 W Tribella Ct - 2017811201/31/23 Project : Project Number: By : Date : `` UNIRAC 1411 Broadway Blvd, NE Albuquerque, NM 87102 RE: Solar Array Installation at 500 W Tribella Ct, Santa Ana, CA 92703, USA To Whom it May Concern, CODE REFERENCES: BUILDING CODE: 2019 CALIFORNIA BUILDING CODE 2018 INTERNATIONAL BUILDING CODE ASCE 7-16 SCOPE OF WORK: DESIGN PARAMETERS RISK CATEGORY : DESIGN WIND SPEED :mph WIND EXPOSURE : GROUND SNOW LOAD :psf SEISMIC DESIGN CATEGORY : EXISTING ROOF STRUCTURE ROOF : 2x4 Rafters @ 24" O.C. ROOF MATERIAL : Flat Tile CONNECTION TO ROOF STRUCTURE MOUNTING CONNECTION : Benjamin Nguyen PE 03-01-2023 Roof structural framing plan has been reviewed for additional loading due to installation of the roof mounted solar PV addition. The structural review that follows, including plans and calculations, only apply to the section of the roof that is directly supporting the solar PV system and its supporting elements. 03 January 2023 Per your request, we have reviewed the existing structure at the above referenced site. The purpose of our review was to determine the adequacy of the existing structure to support the proposed installation of solar panels on the roof per layout plan (2) 1/4" SS LAG BOLTS/ MIN. 2.5" EMBEDMENT INTO (E) 2x FRAMING MEMBER @ MAX. 72" o.c. ALONG RAILS (2) RAILS PER ROW OF PANELS, EVENLY SPACED. PANEL LENGTH PERPENDICULAR TO RAIL NOT TO EXCEED 74" II 95 B 0 *null 500 W Tribella Ct - 2017811201/31/23 OBSERVED CONDITIONS: CONCLUSIONS: LIMITATIONS: Praneet R Erusu, P.E. Principal Engineer Erusu Consultants US Inc. The observed roof framing is described below. If field conditions differ, the contractor shall notify the engineer prior to starting construction. The roof framing is supported by 2x4 Rafters @ 24" O.C are spanning between load bearing walls. The maximum allowed clear span of rafter is 10ft, to be verified in field by the contractor. Based upon our review, we conclude that the existing structure is adequate to support the proposed solar panel installation. In the area of the solar array, other live loads will not be present or will be greatly reduced (2019 CBC, Section 1607.13.5). The gravity loads and the stresses of the structural elements, in the area of the solar array are either decreased or increased by no more than 5%. Therefore, the requirements of Section 503.3 of the 2019 CEBC are met and the structure is permitted to remain unaltered. We conclude that any additional wind loading on the structure related to the addition of the proposed solar array is negligible. The attached calculations verify the capacity of the connections of the solar array to the existing roof against wind (uplift), the governing load case. Regarding seismic loads, we conclude that any additional forces will be small. Conservatively neglecting the weight of existing wall materials, the installation of the solar panels represents an increase in the total weight (and resulting seismic load) of 3.4%. Because the increase in lateral forces is less than 10%, this addition meets the requirements of the exception in Section 503.4 of the 2019 CEBC. Thus the existing lateral force resisting system is permitted to remain unaltered. Installation of the solar panels must be performed in accordance with manufacturer recommendations. All work performed must be in accordance with accepted industry-wide methods and applicable safety standards. Existing Roof and structural members are assumed to be in good and serviceable condition. The contractor must notify Erusu Consultants US Inc. should any damage, deterioration or discrepancies between the as-built condition of the structure and the condition described in this letter be found. The use of solar panel support span tables provided by others are allowed only where the building type, site conditions, site-specific design parameters, and solar panel configuration match the description of the span tables. The design of the solar panel racking (mounts, rails, etc.) and electrical engineering is the responsibility of others. Waterproofing around the roof penetrations is the responsibility of others. Erusu Consultants US Inc. assumes no responsibility for improper installation of the solar array. 03 Jan 2023 EXP : 30 Sep 2023 500 W Tribella Ct - 2017811201/31/23 Project : Project Number: By : Date : Address : Site Plan: Benjamin Nguyen PE 03-01-2023 500 W Tribella Ct, Santa Ana, CA 92703, USA 500 W Tribella Ct - 2017811201/31/23 Project : Project Number: By : Date : Roof Dead Load Roof Slope =: Angle = Roof Live Load Roof Live Load = psf (Refer ASCE 7-16, Table 4.3-1) Roof Live Load with PV Array = psf 2019 CBC, Section 1607.13.5 (Ceiling load and MEP is assumed to be not supported by rafter) 3.06 1/2" Gypsum Ceiling Benjamin Nguyen PE 03-01-2023 DL = Increase due to Roof Slope Plan Projected Material Weight (psf) 12.26 1.12 3.06 0.51Insulation0.5 1.02 2.25 1.50 20.70 1/2" Plywood 1.1 1.02 Framing 3 1.02 Flat Tile 12 1.02 2.5 12 12 Material Material Weight (psf) PV Array 3 1.02 2.2 1.02 MEP & Misc.1.5 20 0 500 W Tribella Ct - 2017811201/31/23 Project : Project Number: By : Date : Benjamin Nguyen PE 03-01-2023 Summary of Gravity Loads Dead Load, D =psf Roof Live Load, Lr =psf Gravity Load Comparison (D + Lr)/Cd =psf (Cd = 0.9 for D, 1.15 for S, 1.25 for Lr) Max Loading =psf Proposed to Current Loading Ratio = Existing With PV Array 20.70 23.77 39.00 26.41 20.00 0.00 Existing With PV Array O.K. Gravity Loading with PV Array is not stressing the current framing system by more that 5% of the original configuration. Per Section 503.3 of 2019 California Existing Building Code the structure is allowed to remain unaltered for gravity loading 39.00 26.41 68% < 105% 500 W Tribella Ct - 2017811201/31/23 Wood Beam LIC# : KW-06014559, Build:20.22.3.31 ERUSU CONSULTANTS US (c) ENERCALC INC 1983-2022 DESCRIPTION: 2x4 Rafters @ 24" o.c. (Wind Condition_Downward) (Strength Check) Project File: 2x4 Joist @ 24 O.C_Copy.ec6 Project Title: Engineer: Project ID: Printed: 17 SEP 2022, 7:02PM Project Descr: CODE REFERENCES Calculations per NDS 2018, IBC 2018, CBC 2019, ASCE 7-16 Load Combination Set : ASCE 7-16 Material Properties Beam Bracing : Beam is Fully Braced against lateral-torsional buckling Repetitive Member Stress Increase Allowable Stress Design Douglas Fir-Larch No.2 900.0 900.0 1,350.0 625.0 1,600.0 580.0 180.0 575.0 31.210 Analysis Method : Eminbend - xx ksi Wood Species : Wood Grade : Fb + psi psi Fv psi Fb - Ft psi Fc - Prll psi psiFc - Perp E : Modulus of Elasticity Ebend- xx ksi Density pcf Load Combination :ASCE 7-16 . Applied Loads Service loads entered. Load Factors will be applied for calculations. Beam self weight NOT internally calculated and added Load for Span Number 1 Uniform Load : D = 0.00810 ksf, Tributary Width = 2.0 ft, (Existing Roof Dead Load) Point Load : D = 0.0370, W = 0.1970 k @ 1.60 ft, (Solar Panel Load) Uniform Load : Lr = 0.020, W = 0.0160 ksf, Extent = 0.0 -->> 0.60 ft, Tributary Width = 2.0 ft, (Existing Wind & Roof Live Load) Load for Span Number 2 Uniform Load : D = 0.00810 ksf, Tributary Width = 2.0 ft, (Existing Roof Dead Load) Point Load : D = 0.0370, W = 0.1970 k @ 3.80 ft, (Solar Panel Load) .DESIGN SUMMARY Design OK Maximum Bending Stress Ratio 0.766: 1 Load Combination +D+0.60W+H Span # where maximum occurs Span # 2 Location of maximum on span 3.799 ft 55.55 psi= = 2,484.00 psi 2x4 Section used for this span Span # where maximum occurs Location of maximum on span Span # 1= Load Combination +D+0.60W+H = = = 288.00 psi== Section used for this span 2x4 Maximum Shear Stress Ratio 0.193 : 1 1.709 ft= = 1,902.86 psi Maximum Deflection 140 >=140 134 Ratio =94 >=93 Max Downward Transient Deflection 0.628 in 191 Ratio =>=140 Max Upward Transient Deflection -0.341 in Ratio = Max Downward Total Deflection 0.889 in Ratio =>=93 Max Upward Total Deflection -0.501 in fb: Actual Fb: Allowable fv: Actual Fv: Allowable Span: 2 : W Only Span: 2 : Lr Only Span: 2 : +D+0.60W+H Span: 1 : +D+0.60W+H .Maximum Forces & Stresses for Load Combinations Span # Moment ValuesLoad Combination C i C L C C C C F/V m r t d Shear ValuesMax Stress Ratios M CV fb M fv F'b V F'vSegment Length +D+H 0.00 0.00 0.000.00 1.00Length = 2.0 ft 1 0.132 0.184 0.90 1.500 1.15 1.00 1.00 0.05 184.95 1397.25 0.10 162.001.00 29.75 1.00Length = 10.0 ft 2 0.706 0.184 0.90 1.500 1.15 1.00 1.00 0.25 987.00 1397.25 0.10 162.001.00 29.75 1.00+D+L+H 1.500 1.15 1.00 1.00 0.00 0.00 0.001.00 0.00 1.00Length = 2.0 ft 1 0.119 0.165 1.00 1.500 1.15 1.00 1.00 0.05 184.95 1552.50 0.10 180.001.00 29.75 1.00Length = 10.0 ft 2 0.636 0.165 1.00 1.500 1.15 1.00 1.00 0.25 987.00 1552.50 0.10 180.001.00 29.75 1.00+D+Lr+H 1.500 1.15 1.00 1.00 0.00 0.00 0.001.00 0.00 500 W Tribella Ct - 2017811201/31/23 Wood Beam LIC# : KW-06014559, Build:20.22.3.31 ERUSU CONSULTANTS US (c) ENERCALC INC 1983-2022 DESCRIPTION: 2x4 Rafters @ 24" o.c. (Wind Condition_Downward) (Strength Check) Project File: 2x4 Joist @ 24 O.C_Copy.ec6 Project Title: Engineer: Project ID: Printed: 17 SEP 2022, 7:02PM Project Descr: Maximum Forces & Stresses for Load Combinations Span # Moment ValuesLoad Combination C i C L C C CCF/V m r td Shear ValuesMax Stress Ratios M CV fb M fv F'b V F'vSegment Length 1.00Length = 2.0 ft 1 0.178 0.137 1.25 1.500 1.15 1.00 1.00 0.09 344.82 1940.63 0.11 225.001.00 30.92 1.00Length = 10.0 ft 2 0.464 0.137 1.25 1.500 1.15 1.00 1.00 0.23 899.86 1940.63 0.11 225.001.00 30.92 1.00+D+S+H 1.500 1.15 1.00 1.00 0.00 0.00 0.001.00 0.00 1.00Length = 2.0 ft 1 0.104 0.144 1.15 1.500 1.15 1.00 1.00 0.05 184.95 1785.38 0.10 207.001.00 29.75 1.00Length = 10.0 ft 2 0.553 0.144 1.15 1.500 1.15 1.00 1.00 0.25 987.00 1785.38 0.10 207.001.00 29.75 1.00+D+0.750Lr+0.750L+H 1.500 1.15 1.00 1.00 0.00 0.00 0.001.00 0.00 1.00Length = 2.0 ft 1 0.157 0.136 1.25 1.500 1.15 1.00 1.00 0.08 304.85 1940.63 0.11 225.001.00 30.63 1.00Length = 10.0 ft 2 0.475 0.136 1.25 1.500 1.15 1.00 1.00 0.24 921.26 1940.63 0.11 225.001.00 30.63 1.00+D+0.750L+0.750S+H 1.500 1.15 1.00 1.00 0.00 0.00 0.001.00 0.00 1.00Length = 2.0 ft 1 0.104 0.144 1.15 1.500 1.15 1.00 1.00 0.05 184.95 1785.38 0.10 207.001.00 29.75 1.00Length = 10.0 ft 2 0.553 0.144 1.15 1.500 1.15 1.00 1.00 0.25 987.00 1785.38 0.10 207.001.00 29.75 1.00+D+0.60W+H 1.500 1.15 1.00 1.00 0.00 0.00 0.001.00 0.00 1.00Length = 2.0 ft 1 0.180 0.193 1.60 1.500 1.15 1.00 1.00 0.11 446.94 2484.00 0.19 288.001.00 55.55 1.00Length = 10.0 ft 2 0.766 0.193 1.60 1.500 1.15 1.00 1.00 0.49 1,902.86 2484.00 0.18 288.001.00 55.55 1.00+D+0.750Lr+0.750L+0.450W+H 1.500 1.15 1.00 1.00 0.00 0.00 0.001.00 0.00 1.00Length = 2.0 ft 1 0.202 0.179 1.60 1.500 1.15 1.00 1.00 0.13 501.35 2484.00 0.18 288.001.00 51.42 1.00Length = 10.0 ft 2 0.643 0.179 1.60 1.500 1.15 1.00 1.00 0.41 1,596.41 2484.00 0.17 288.001.00 51.42 1.00+D+0.750L+0.750S+0.450W+H 1.500 1.15 1.00 1.00 0.00 0.00 0.001.00 0.00 1.00Length = 2.0 ft 1 0.154 0.163 1.60 1.500 1.15 1.00 1.00 0.10 381.45 2484.00 0.16 288.001.00 46.89 1.00Length = 10.0 ft 2 0.673 0.163 1.60 1.500 1.15 1.00 1.00 0.43 1,670.76 2484.00 0.16 288.001.00 46.89 1.00+0.60D+0.60W+0.60H 1.500 1.15 1.00 1.00 0.00 0.00 0.001.00 0.00 1.00Length = 2.0 ft 1 0.150 0.167 1.60 1.500 1.15 1.00 1.00 0.10 372.97 2484.00 0.17 288.001.00 48.15 1.00Length = 10.0 ft 2 0.609 0.167 1.60 1.500 1.15 1.00 1.00 0.39 1,513.07 2484.00 0.14 288.001.00 48.15 1.00+D+0.70E+0.60H 1.500 1.15 1.00 1.00 0.00 0.00 0.001.00 0.00 1.00Length = 2.0 ft 1 0.074 0.103 1.60 1.500 1.15 1.00 1.00 0.05 184.95 2484.00 0.10 288.001.00 29.75 1.00Length = 10.0 ft 2 0.397 0.103 1.60 1.500 1.15 1.00 1.00 0.25 987.00 2484.00 0.10 288.001.00 29.75 1.00+D+0.750L+0.750S+0.5250E+H 1.500 1.15 1.00 1.00 0.00 0.00 0.001.00 0.00 1.00Length = 2.0 ft 1 0.074 0.103 1.60 1.500 1.15 1.00 1.00 0.05 184.95 2484.00 0.10 288.001.00 29.75 1.00Length = 10.0 ft 2 0.397 0.103 1.60 1.500 1.15 1.00 1.00 0.25 987.00 2484.00 0.10 288.001.00 29.75 1.00+0.60D+0.70E+H 1.500 1.15 1.00 1.00 0.00 0.00 0.001.00 0.00 1.00Length = 2.0 ft 1 0.045 0.062 1.60 1.500 1.15 1.00 1.00 0.03 110.97 2484.00 0.06 288.001.00 17.85 1.00Length = 10.0 ft 2 0.238 0.062 1.60 1.500 1.15 1.00 1.00 0.15 592.20 2484.00 0.06 288.001.00 17.85 . Location in SpanLoad Combination Max. "-" Defl Location in Span Load Combination Span Max. "+" Defl Overall Maximum Deflections +D+0.60W+H10.0000 0.000 -0.5007 0.000 +D+0.60W+H 2 0.8892 4.916 0.0000 0.000 . Load Combination Support 1 Support 2 Support 3 Vertical Reactions Support notation : Far left is #1 Values in KIPS Overall MAXimum 0.388 0.129 Overall MINimum 0.349 0.064 +D+H 0.178 0.090 +D+L+H 0.178 0.090 +D+Lr+H 0.206 0.086 +D+S+H 0.178 0.090 +D+0.750Lr+0.750L+H 0.199 0.087 +D+0.750L+0.750S+H 0.178 0.090 +D+0.60W+H 0.388 0.129 +D+0.750Lr+0.750L+0.450W+H 0.356 0.116 +D+0.750L+0.750S+0.450W+H 0.335 0.119 +0.60D+0.60W+0.60H 0.317 0.092 +D+0.70E+0.60H 0.178 0.090 +D+0.750L+0.750S+0.5250E+H 0.178 0.090 +0.60D+0.70E+H 0.107 0.054 D Only 0.178 0.090 Lr Only 0.028 -0.004 W Only 0.349 0.064 H Only 500 W Tribella Ct - 2017811201/31/23 Wood Beam LIC# : KW-06014559, Build:20.22.3.31 ERUSU CONSULTANTS US (c) ENERCALC INC 1983-2022 DESCRIPTION: 2x4 Rafters @ 24" o.c. (Wind Condition_Uplift) (Strength Check) Project File: 2x4 Joist @ 24 O.C_Copy.ec6 Project Title: Engineer: Project ID: Printed: 17 SEP 2022, 7:01PM Project Descr: CODE REFERENCES Calculations per NDS 2018, IBC 2018, CBC 2019, ASCE 7-16 Load Combination Set : ASCE 7-16 Material Properties Beam Bracing : Beam is Fully Braced against lateral-torsional buckling Repetitive Member Stress Increase Allowable Stress Design Douglas Fir-Larch No.2 900.0 900.0 1,350.0 625.0 1,600.0 580.0 180.0 575.0 31.210 Analysis Method : Eminbend - xx ksi Wood Species : Wood Grade : Fb + psi psi Fv psi Fb - Ft psi Fc - Prll psi psiFc - Perp E : Modulus of Elasticity Ebend- xx ksi Density pcf Load Combination :ASCE 7-16 . Applied Loads Service loads entered. Load Factors will be applied for calculations. Beam self weight NOT internally calculated and added Load for Span Number 1 Uniform Load : D = 0.00810 ksf, Tributary Width = 2.0 ft, (Existing Roof Dead Load) Point Load : D = 0.0370, W = -0.5940 k @ 1.60 ft, (Solar Panel Load) Uniform Load : Lr = 0.020, W = -0.0480 ksf, Extent = 0.0 -->> 0.60 ft, Tributary Width = 2.0 ft, (Existing Wind & Roof Live Load) Load for Span Number 2 Uniform Load : D = 0.00810 ksf, Tributary Width = 2.0 ft, (Existing Roof Dead Load) Point Load : D = 0.0370, W = -0.5940 k @ 3.80 ft, (Solar Panel Load) .DESIGN SUMMARY Design OK Maximum Bending Stress Ratio 0.892: 1 Load Combination +0.60D+0.60W+0.60H Span # where maximum occurs Span # 2 Location of maximum on span 3.799 ft 100.89 psi= = 2,484.00 psi 2x4 Section used for this span Span # where maximum occurs Location of maximum on span Span # 1= Load Combination +0.60D+0.60W+0.60H = = = 288.00 psi== Section used for this span 2x4 Maximum Shear Stress Ratio 0.350 : 1 1.609 ft= = 2,215.37 psi Maximum Deflection 63 >=46 108 Ratio =144 >=108 Max Downward Transient Deflection 1.030 in 46 Ratio =>=46 Max Upward Transient Deflection -1.895 in Ratio = Max Downward Total Deflection 0.441 in Ratio =>=108 Max Upward Total Deflection -0.830 in fb: Actual Fb: Allowable fv: Actual Fv: Allowable Span: 1 : W Only Span: 2 : W Only Span: 2 : +D+H Span: 2 : +0.60D+0.60W+0.60H .Maximum Forces & Stresses for Load Combinations Span # Moment ValuesLoad Combination C i C L C C C C F/V m r t d Shear ValuesMax Stress Ratios M CV fb M fv F'b V F'vSegment Length +D+H 0.00 0.00 0.000.00 1.00Length = 2.0 ft 1 0.132 0.184 0.90 1.500 1.15 1.00 1.00 0.05 184.95 1397.25 0.10 162.001.00 29.75 1.00Length = 10.0 ft 2 0.706 0.184 0.90 1.500 1.15 1.00 1.00 0.25 987.00 1397.25 0.10 162.001.00 29.75 1.00+D+L+H 1.500 1.15 1.00 1.00 0.00 0.00 0.001.00 0.00 1.00Length = 2.0 ft 1 0.119 0.165 1.00 1.500 1.15 1.00 1.00 0.05 184.95 1552.50 0.10 180.001.00 29.75 1.00Length = 10.0 ft 2 0.636 0.165 1.00 1.500 1.15 1.00 1.00 0.25 987.00 1552.50 0.10 180.001.00 29.75 1.00+D+Lr+H 1.500 1.15 1.00 1.00 0.00 0.00 0.001.00 0.00 500 W Tribella Ct - 2017811201/31/23 Wood Beam LIC# : KW-06014559, Build:20.22.3.31 ERUSU CONSULTANTS US (c) ENERCALC INC 1983-2022 DESCRIPTION: 2x4 Rafters @ 24" o.c. (Wind Condition_Uplift) (Strength Check) Project File: 2x4 Joist @ 24 O.C_Copy.ec6 Project Title: Engineer: Project ID: Printed: 17 SEP 2022, 7:01PM Project Descr: Maximum Forces & Stresses for Load Combinations Span # Moment ValuesLoad Combination C i C L C C CCF/V m r td Shear ValuesMax Stress Ratios M CV fb M fv F'b V F'vSegment Length 1.00Length = 2.0 ft 1 0.178 0.137 1.25 1.500 1.15 1.00 1.00 0.09 344.82 1940.63 0.11 225.001.00 30.92 1.00Length = 10.0 ft 2 0.464 0.137 1.25 1.500 1.15 1.00 1.00 0.23 899.86 1940.63 0.11 225.001.00 30.92 1.00+D+S+H 1.500 1.15 1.00 1.00 0.00 0.00 0.001.00 0.00 1.00Length = 2.0 ft 1 0.104 0.144 1.15 1.500 1.15 1.00 1.00 0.05 184.95 1785.38 0.10 207.001.00 29.75 1.00Length = 10.0 ft 2 0.553 0.144 1.15 1.500 1.15 1.00 1.00 0.25 987.00 1785.38 0.10 207.001.00 29.75 1.00+D+0.750Lr+0.750L+H 1.500 1.15 1.00 1.00 0.00 0.00 0.001.00 0.00 1.00Length = 2.0 ft 1 0.157 0.136 1.25 1.500 1.15 1.00 1.00 0.08 304.85 1940.63 0.11 225.001.00 30.63 1.00Length = 10.0 ft 2 0.475 0.136 1.25 1.500 1.15 1.00 1.00 0.24 921.26 1940.63 0.11 225.001.00 30.63 1.00+D+0.750L+0.750S+H 1.500 1.15 1.00 1.00 0.00 0.00 0.001.00 0.00 1.00Length = 2.0 ft 1 0.104 0.144 1.15 1.500 1.15 1.00 1.00 0.05 184.95 1785.38 0.10 207.001.00 29.75 1.00Length = 10.0 ft 2 0.553 0.144 1.15 1.500 1.15 1.00 1.00 0.25 987.00 1785.38 0.10 207.001.00 29.75 1.00+D+0.60W+H 1.500 1.15 1.00 1.00 0.00 0.00 0.001.00 0.00 1.00Length = 2.0 ft 1 0.243 0.325 1.60 1.500 1.15 1.00 1.00 0.15 603.87 2484.00 0.33 288.001.00 93.68 1.00Length = 10.0 ft 2 0.735 0.325 1.60 1.500 1.15 1.00 1.00 0.47 1,825.58 2484.00 0.19 288.001.00 93.68 1.00+D+0.750Lr+0.750L+0.450W+H 1.500 1.15 1.00 1.00 0.00 0.00 0.001.00 0.00 1.00Length = 2.0 ft 1 0.115 0.210 1.60 1.500 1.15 1.00 1.00 0.07 286.76 2484.00 0.21 288.001.00 60.62 1.00Length = 10.0 ft 2 0.483 0.210 1.60 1.500 1.15 1.00 1.00 0.31 1,199.92 2484.00 0.13 288.001.00 60.62 1.00+D+0.750L+0.750S+0.450W+H 1.500 1.15 1.00 1.00 0.00 0.00 0.001.00 0.00 1.00Length = 2.0 ft 1 0.164 0.228 1.60 1.500 1.15 1.00 1.00 0.10 406.66 2484.00 0.23 288.001.00 65.76 1.00Length = 10.0 ft 2 0.453 0.228 1.60 1.500 1.15 1.00 1.00 0.29 1,125.57 2484.00 0.13 288.001.00 65.76 1.00+0.60D+0.60W+0.60H 1.500 1.15 1.00 1.00 0.00 0.00 0.001.00 0.00 1.00Length = 2.0 ft 1 0.273 0.350 1.60 1.500 1.15 1.00 1.00 0.17 677.85 2484.00 0.35 288.001.00 100.89 1.00Length = 10.0 ft 2 0.892 0.350 1.60 1.500 1.15 1.00 1.00 0.57 2,215.37 2484.00 0.21 288.001.00 100.89 1.00+D+0.70E+0.60H 1.500 1.15 1.00 1.00 0.00 0.00 0.001.00 0.00 1.00Length = 2.0 ft 1 0.074 0.103 1.60 1.500 1.15 1.00 1.00 0.05 184.95 2484.00 0.10 288.001.00 29.75 1.00Length = 10.0 ft 2 0.397 0.103 1.60 1.500 1.15 1.00 1.00 0.25 987.00 2484.00 0.10 288.001.00 29.75 1.00+D+0.750L+0.750S+0.5250E+H 1.500 1.15 1.00 1.00 0.00 0.00 0.001.00 0.00 1.00Length = 2.0 ft 1 0.074 0.103 1.60 1.500 1.15 1.00 1.00 0.05 184.95 2484.00 0.10 288.001.00 29.75 1.00Length = 10.0 ft 2 0.397 0.103 1.60 1.500 1.15 1.00 1.00 0.25 987.00 2484.00 0.10 288.001.00 29.75 1.00+0.60D+0.70E+H 1.500 1.15 1.00 1.00 0.00 0.00 0.001.00 0.00 1.00Length = 2.0 ft 1 0.045 0.062 1.60 1.500 1.15 1.00 1.00 0.03 110.97 2484.00 0.06 288.001.00 17.85 1.00Length = 10.0 ft 2 0.238 0.062 1.60 1.500 1.15 1.00 1.00 0.15 592.20 2484.00 0.06 288.001.00 17.85 . Location in SpanLoad Combination Max. "-" Defl Location in Span Load Combination Span Max. "+" Defl Overall Maximum Deflections W Only 1 1.0301 0.000 0.0000 0.000 W Only20.0000 0.000 -1.8949 4.749 . Load Combination Support 1 Support 2 Support 3 Vertical Reactions Support notation : Far left is #1 Values in KIPS Overall MAXimum -1.053 -0.192 Overall MINimum 0.028 -0.004 +D+H 0.178 0.090 +D+L+H 0.178 0.090 +D+Lr+H 0.206 0.086 +D+S+H 0.178 0.090 +D+0.750Lr+0.750L+H 0.199 0.087 +D+0.750L+0.750S+H 0.178 0.090 +D+0.60W+H -0.454 -0.025 +D+0.750Lr+0.750L+0.450W+H -0.275 0.001 +D+0.750L+0.750S+0.450W+H -0.296 0.004 +0.60D+0.60W+0.60H -0.525 -0.061 +D+0.70E+0.60H 0.178 0.090 +D+0.750L+0.750S+0.5250E+H 0.178 0.090 +0.60D+0.70E+H 0.107 0.054 D Only 0.178 0.090 Lr Only 0.028 -0.004 W Only -1.053 -0.192 H Only 500 W Tribella Ct - 2017811201/31/23 Project : Project Number: By : Date : Wind Load Calculation Wind Loads - ASCE 7-16 Chapter 26 & 29 Width of the Building, B = ft (Approximate) V = mph Exposure = Average height of building, z = ft - avg (Approximate) ft (Refer ASCE 7-16, Table 26.10-1) α = Zg = ft (Refer ASCE 7-16, Table 26.11-1) Kh & Kz = 2.01(z/Zg)^(2/α) = Kzt =(Refer ASCE 7-16, Equation 26.8-1) Kd =(Refer ASCE 7-16, Table 26.6.1) Ke =(Refer ASCE 7-16, Table 26.9-1) qh ='.00256 KzKztKdKeV² =psf (Refer ASCE 7-16, Section 26.10-1) Building Classification = Solar Panel Components and Cladding p C&C = qh(GCp)(ϒe)(ϒa) ASCE 7-16 Chapter 29.4.4 Module Length = in Module Width = in Area of Module = ft2 Roof Pitch =: Slope = degrees Gable Roof = ϒe= ϒa=(Refer ASCE 7-16, Figure 29.4-8) Benjamin Nguyen PE 03-01-2023 1200 zmin = 30 7 1 35.18 1 0.85 15.45 2.5 41.1 95 B 45 0.79 Enclosed 0.8 21.1 74 7° < θ ≤ 20° 1.5 12 12 500 W Tribella Ct - 2017811201/31/23 Project : Project Number: By : Date : Benjamin Nguyen PE 03-01-2023 Zone 1 Uplift External Wind pressure coefficient GCp = External Wind pressure, qGCp = psf Zone 2 Uplift External Wind pressure coefficient GCp = External Wind pressure, qGCp = psf All Zone Downward External Wind pressure coefficient GCp = External Wind pressure, qGCp = psf Maximum Uplift Wind Pressure, p = psf Minimum Downward Wind Pressure ,p = psf Lag Screw / Bolt Connection Check (ASD) Tributary Width = in (Max Spacing of fasteners along Rails) Tributary Length = in (Half Panel Length) Tributary Area = ft2 Lag Screw/Bolt Size = Cd =(Refer NDS Table 2.3.2) Embedment = in Grade of Wood = #2 ( or better) G = Capacity = lb/in (Refer NDS Table 12.2A) Number of Screws in Tension = Prying Coefficient = Capacity of Fasteners = lb Demand -2.6 (Measured from top of the framing member to tapered tip of lag screw, embedment in sheathing and tapered tip of screw is not included ) DF -48.20 -2 -37.076 -48.20 16.0 37 18.5 1/4 1.6 2.5 72 0.5 9.3 Uplift (lb)Zone 0.5 225 2 1.4 1286 Zone 1 Zone 2 0.42 Pressure ASD (0.6W)(psf) -22.2 -28.9 18.5 535.0 1286 DCR 18.5 411.5 1286 0.32 Capacity (lb) Tributary Area (ft2) 500 W Tribella Ct - 2017811201/31/23 Project : Project Number: By : Date : Seismic Ground Motion Values Benjamin Nguyen PE 03-01-2023 500 W Tribella Ct - 2017811201/31/23 Project : Project Number: By : Date : Seismic Design Force Seismic Loads - ASCE 7-16 Chapter 13 Seismic Force Component Amplification Factor, ap= (Refer ASCE 7-16, Table 13.6 -1) Overstrength Factor, Ωo =(Refer ASCE 7-16, Table 13.6 -1) Component Importance Factor, Ip= SDS = Average roof height of structure,h = ft z/h = z/h should not exceed 1 Frame Weight Wp = psf Seismic Design Force on Solar framing structure Max Fp =1.6 x SDS x Ip X Wp = psf Min Fp =0.3 x SDS x Ip X Wp = psf Seismic Design Load Fp = psf Vertical Seismic Design Load Fp = psf Seismic Coefficients for Mechanical and Electrical components = Component Response Modification Factor, Rp= 1.50 Benjamin Nguyen PE 03-01-2023 12 Other mechanical or electrical components. (Refer ASCE 7-16, Table 13.6 -1) Height in structure at point of attachement, z = 45 ft 1.00 1.50 1.07 1.00 F P = ((0.4 x ap x SDS x Wp)/ (Rp / Ip)) x ((1+2(z/h)) =2.61 psf 45 1 2.61 5.22 0.98 3.06 0.65 500 W Tribella Ct - 2017811201/31/23 Project : Project Number: By : Date : Benjamin Nguyen PE 03-01-2023 Check for Increase in overall seismic loads Array Area = ft2 Number of Arrays = Total Array Area = ft2 Array Load = psf Number of Existing Arrays = Exisitng Area = ft2 Total Array Wt. = lb Total Roof Area = ft2 DL of Roof = psf Total Wt of Roof = lb Increase in Seismic Wt = < 10% Conservatively the Wt. of the Walls tributary to the roof is not included. Seismic weight increase is less than 10% and no seismic retrofit or evaluation of existing lateral system is required per Section 503.4 of 2019 CEBC. 21.1 24 506.9 2133 3.00 1520.7 0 0.00 20.70 44161 3.4% 500 W Tribella Ct - 2017811201/31/23 Rev: 7/15/2021 RESIDENTIAL PHOTOVOLTAIC CHECKLIST SOL-01 CBC 2019 Solar Photovoltaic (PV) Checklist for Detached SINGLE FAMILY RESIDENCES Only Instructions: The licensed contractor of record shall complete all sections, answer the ten questions and sign the certification section below. A copy of this form shall be attached to each of TWO sets of plans, of minimum 11” x 17” size. If answering NO to any of the questions, plan check shall be required. Project Address: Contractor Company Name: Contractor License Number: YES NO Are the following applicable to the proposed project? 1.   Will the PV system layout provide the required three-foot wide clear access pathways per Section 605.11 of the California Fire Code, and is this shown on the roof plan? 2.   Will the PV system be installed on a roof having only one roofing layer with no overlays? 3.   Will the PV array be flush mounted to the existing roof so that the plane of the modules (panels) are parallel to the plane of the roof? 4.   Will the PV system weigh maximum 4 pounds per square feet or less? 5.   Will the PV system be installed where the modules do not overhang any roof edges (such as eaves, gabled ends, ridges and hips)? 6.   Will the PV system be installed with a space of 2” minimum to 10” maximum between the underside of modules and the surface of the roof? 7.   Will the PV system be installed without using any ballast system or counter-weight system? 8.   Will the anchors be installed with a maximum horizontal anchor spacing of 6 feet and is this maximum horizontal spacing shown on the plans? 9.   Will the minimum 5/16” lag screws be installed with a minimum of 2-1/2 inch embedment into roof rafters (with pre-drilled holes) and is this minimum embedment shown on the plans? 10.   Are ALL the structural pages of the plans stamped and signed by a California licensed professional engineer? (including project specific site plan, PV layout, anchorage spacing, anchorage details and manufacturer’s PV support information.) I certify under penalty of perjury under the laws of the State of California that the above is true: Print Name: Signature: Phone Number: Date: Email Address: Planning & Building Agency Building Safety Division 20 Civic Center Plaza P.O. Box 1988 (M-19) Santa Ana, CA 92702 (714) 647-5800 www.santa-ana.org 500 W Tribella Ct, Santa Ana, CA 92703 Solare Power LLC 1079237 Mayra Ruiz (530)780-5141 11/21/2022 ops@solarepwr.com 500 W Tribella Ct - 2017811201/31/23 COVER SHEET PHOTOVOLTAIC ROOF MOUNT SYSTEM 500 W TRIBELLA CT, SANTA ANA, CA 92703 USA REV SHEET NAME SHEET NUMBER DATE DESCRIPTION VERSION PV-0 PROJECT NAME UR09/15/2022 INITIAL RELEASE BE N J A M I N N G U Y E N 50 0 W T R I B E L L A C T , SA N T A A N A , C A 9 2 7 0 3 U S A AP N # 1 9 8 3 5 2 0 1 UT I L I T Y : S C E AH J : C I T Y O F S A N T A A N A SHEET SIZE ANSI B 11" X 17" SOLARE POWER LCC 4518 WEBB RD ANDERSON CA 96007 CSLB# : 1079237 Phone : (559)-936-2123 Email: ops@solarepwr.com SYSTEM SUMMARY:DESIGN CRITERIA:GOVERNING CODES: PROJECT SITE 2 VICINITY MAP SCALE: NTSPV-0 1 AERIAL PHOTO SCALE: NTS PV-0 ARRAY LOCATIONS GENERAL NOTES · THE CONTRACTOR/INSTALLER OF THE SOLAR PV SYSTEM OVER EXISTING ROOF SHALL CONFORM TO OSHA REQUIREMENTS DURING THE CONSTRUCTION PHASE. JOB SAFETY AND CONSTRUCTION PROCEDURES ARE THE SOLE RESPONSIBILITY OF THE CONTRACTOR/INSTALLER. · REFER TO ELECTRICAL DRAWING PV-5 FOR PANEL DETAILED INFORMATION. · IN CASE OF CONFLICT BETWEEN STRUCTURAL DRAWINGS AND ELECTRICAL DRAWINGS, THE MOST RIGID REQUIREMENTS SHALL GOVERN. · THE CONTRACTOR/INSTALLER SHALL VERIFY ALL EXISTING BUILDING INFORMATION SHOWN (DIMENSIONS, ROOF TOP PROJECTIONS, ETC.) AND NOTIFY THE ENGINEER OF ANY DISCREPANCIES PRIOR TO INSTALLATIONS OF PV SYSTEM. · THE CONTRACTOR/INSTALLER SHALL VERIFY AND COORDINATE EXISTING OPENINGS, ROOF TOP UNITS, VENT PIPES, ETC. SHOWN ON DRAWINGS. IF THERE IS A DISCREPANCY BETWEEN DRAWINGS, IT IS THE CONTRACTORS/INSTALLER'S RESPONSIBILITY TO NOTIFY ENGINEER PRIOR TO PERFORMING THE WORK. · ALL CONSTRUCTION IS TO BE PERFORMED IN STRICT CONFORMANCE WITH ALL APPLICABLE TOWN, COUNTY & STATE REGULATIONS AND/OR ANY OTHER GOVERNING BODIES. · DO NOT SCALE THESE DRAWINGS, USE DIMENSIONS. CONTRACTOR MUST CONDUCT ROOF SURVEY TO VERIFY DIMENSIONS SHOWN ON PLAN PRIOR TO INSTALLATION. IF THERE IS A DISCREPANCY IT IS CONTRACTOR/INSTALLER'S RESPONSIBILITY TO NOTIFY THE ENGINEER IMMEDIATELY. · LOCATED IN AREAS NOT REQUIRING PLACEMENT OF GROUND LADDERS OVER OPENINGS SUCH AS DOORS OR WINDOWS. · LOCATED AT STRONG POINTS OF BUILDING CONSTRUCTION IN LOCATIONS WHERE ACCESS POINT DOES NOT CONFLICT WITH OVERHEAD OBSTRUCTIONS SUCH AS TREE LIMBS, WIRES, OR SIGNS. · DISCONNECT MEANS MUST HAVE DEDICATED CLEAR UNOBSTRUCTED WORKING SPACE NOT LESS THAN 3' DEEP BY 2.5' WIDE TO NOT LESS THAN 6.5' ABOVE WALKABLE SURFACES IN FRONT OF DISTRIBUTION PANEL. · ALL SOLAR MODULES, EQUIPMENT, AND METALLIC COMPONENTS TO BE BONDED. ·PV ARRAY NOT TO EXCEED HIGHEST POINT OF THE ROOF. ·RAPID SHUTDOWN IS ACTIVED AT THE INVERTER BY THE AC DISCONNECT. (N) 24 - HANWAH Q CELLS Q.PEAK DUO BLK ML-G10+ (400W) MODULES (N) 24 - ENPHASE ENERGY IQ8PLUS-72-2-US MICRO-INVERTERS (N) JUNCTION BOX (E) 225A MAIN SERVICE PANEL WITH (E) 200A MAIN BREAKER (N) ENPHASE IQ COMBINER BOX 4 (N) 01-ENPHASE IQ BATTERY 10 (N) 200A ENPHASE IQ SYSTEM CONTROLLER 2 (N) 100A BACKUP LOAD PANEL ,MLO 2019 CALIFORNIA ELECTRICAL CODE (CEC) 2019 CALIFORNIA BUILDING CODE (CBC) 2019 CALIFORNIA RESIDENTIAL CODE (CRC) 2019 CALIFORNIA GREEN CODE (CGC) 2019 CALIFORNIA MECHANICAL CODE (CMC) 2019 CALIFORNIA PLUMBING CODE (CPC) 2019 CA FIRE CODE TITLE 24 SUPPLEMENT ANY OTHER LOCAL AMENDMENTS 24 MODULES-ROOF MOUNTED - 9.60 kWDC, 8.77 CEC kW AC ROOF TYPE: - FLAT-TILE ROOF FRAME: - 2"X4" RAFTERS @24" O.C. STORY: - THREE STORY SNOW LOAD : - 0 PSF WIND SPEED :- 95 MPH WIND EXPOSURE:- B RISK CATEGORY:- II COORDINATE:- 33.756060, -117.921723 PV-0 COVER SHEET PV-1 SITE PLAN WITH ROOF PLAN PV-2 ROOF PLAN WITH MODULES PV-3 ATTACHMENT DETAILS PV-4 BRANCH LAYOUT PV-5 ELECTRICAL LINE DIAGRAM PV-6 ELECTRICAL CALCULATION PV-7 PLACARDS & WARNING LABELS PV-8 ADDITIONAL NOTES PV-8.1 LOAD CALCULATION&PANEL SCHEDULE PV-9+ EQUIPMENT SPEC SHEETS SHEET INDEX 03 Jan 2023 EXP : 30 Sep 2023 STRUCTURAL ONLY Bldg permit #101112994 Elect permit #20178112 Issued on 1/31/23 ***The scope of the plans is for the installation of the solar photovoltaic system only and the approval is subject to compliance with all applicable city and state codes and regulations regarding construction. The approval of the plans does not constitute any certification of the accuracy, completeness, or building permit status of the existing buildings and structures as shown.*** 500 W Tribella Ct - 2017811201/31/23 REV SHEET NAME SHEET NUMBER DATE DESCRIPTION VERSION PV-8.1 PROJECT NAME UR09/15/2022 INITIAL RELEASE BE N J A M I N N G U Y E N 50 0 W T R I B E L L A C T , SA N T A A N A , C A 9 2 7 0 3 U S A AP N # 1 9 8 3 5 2 0 1 UT I L I T Y : S C E AH J : C I T Y O F S A N T A A N A SHEET SIZE ANSI B 11" X 17" SOLARE POWER LCC 4518 WEBB RD ANDERSON CA 96007 CSLB# : 1079237 Phone : (559)-936-2123 Email: ops@solarepwr.com LOAD CALCULATION&PANEL SCHEDULE 500 W Tribella Ct - 2017811201/31/23 REV SHEET NAME SHEET NUMBER DATE DESCRIPTION VERSION PV-9 PROJECT NAME UR09/15/2022 INITIAL RELEASE BE N J A M I N N G U Y E N 50 0 W T R I B E L L A C T , SA N T A A N A , C A 9 2 7 0 3 U S A AP N # 1 9 8 3 5 2 0 1 UT I L I T Y : S C E AH J : C I T Y O F S A N T A A N A SHEET SIZE ANSI B 11" X 17" SOLARE POWER LCC 4518 WEBB RD ANDERSON CA 96007 CSLB# : 1079237 Phone : (559)-936-2123 Email: ops@solarepwr.com OPTIMIZER CHART 500 W Tribella Ct - 2017811201/31/23 REV SHEET NAME SHEET NUMBER DATE DESCRIPTION VERSION PV-10 PROJECT NAME UR09/15/2022 INITIAL RELEASE BE N J A M I N N G U Y E N 50 0 W T R I B E L L A C T , SA N T A A N A , C A 9 2 7 0 3 U S A AP N # 1 9 8 3 5 2 0 1 UT I L I T Y : S C E AH J : C I T Y O F S A N T A A N A SHEET SIZE ANSI B 11" X 17" SOLARE POWER LCC 4518 WEBB RD ANDERSON CA 96007 CSLB# : 1079237 Phone : (559)-936-2123 Email: ops@solarepwr.com SPEC SHEETS 500 W Tribella Ct - 2017811201/31/23 REV SHEET NAME SHEET NUMBER DATE DESCRIPTION VERSION PV-11 PROJECT NAME UR09/15/2022 INITIAL RELEASE BE N J A M I N N G U Y E N 50 0 W T R I B E L L A C T , SA N T A A N A , C A 9 2 7 0 3 U S A AP N # 1 9 8 3 5 2 0 1 UT I L I T Y : S C E AH J : C I T Y O F S A N T A A N A SHEET SIZE ANSI B 11" X 17" SOLARE POWER LCC 4518 WEBB RD ANDERSON CA 96007 CSLB# : 1079237 Phone : (559)-936-2123 Email: ops@solarepwr.com SPEC SHEETS 500 W Tribella Ct - 2017811201/31/23 REV SHEET NAME SHEET NUMBER DATE DESCRIPTION VERSION PV-12 PROJECT NAME UR09/15/2022 INITIAL RELEASE BE N J A M I N N G U Y E N 50 0 W T R I B E L L A C T , SA N T A A N A , C A 9 2 7 0 3 U S A AP N # 1 9 8 3 5 2 0 1 UT I L I T Y : S C E AH J : C I T Y O F S A N T A A N A SHEET SIZE ANSI B 11" X 17" SOLARE POWER LCC 4518 WEBB RD ANDERSON CA 96007 CSLB# : 1079237 Phone : (559)-936-2123 Email: ops@solarepwr.com SPEC SHEETS 500 W Tribella Ct - 2017811201/31/23 REV SHEET NAME SHEET NUMBER DATE DESCRIPTION VERSION PV-13 PROJECT NAME UR09/15/2022 INITIAL RELEASE BE N J A M I N N G U Y E N 50 0 W T R I B E L L A C T , SA N T A A N A , C A 9 2 7 0 3 U S A AP N # 1 9 8 3 5 2 0 1 UT I L I T Y : S C E AH J : C I T Y O F S A N T A A N A SHEET SIZE ANSI B 11" X 17" SOLARE POWER LCC 4518 WEBB RD ANDERSON CA 96007 CSLB# : 1079237 Phone : (559)-936-2123 Email: ops@solarepwr.com SPEC SHEETS 500 W Tribella Ct - 2017811201/31/23 REV SHEET NAME SHEET NUMBER DATE DESCRIPTION VERSION PV-14 PROJECT NAME UR09/15/2022 INITIAL RELEASE BE N J A M I N N G U Y E N 50 0 W T R I B E L L A C T , SA N T A A N A , C A 9 2 7 0 3 U S A AP N # 1 9 8 3 5 2 0 1 UT I L I T Y : S C E AH J : C I T Y O F S A N T A A N A SHEET SIZE ANSI B 11" X 17" SOLARE POWER LCC 4518 WEBB RD ANDERSON CA 96007 CSLB# : 1079237 Phone : (559)-936-2123 Email: ops@solarepwr.com SPEC SHEETS 500 W Tribella Ct - 2017811201/31/23 REV SHEET NAME SHEET NUMBER DATE DESCRIPTION VERSION PV-15 PROJECT NAME UR09/15/2022 INITIAL RELEASE BE N J A M I N N G U Y E N 50 0 W T R I B E L L A C T , SA N T A A N A , C A 9 2 7 0 3 U S A AP N # 1 9 8 3 5 2 0 1 UT I L I T Y : S C E AH J : C I T Y O F S A N T A A N A SHEET SIZE ANSI B 11" X 17" SOLARE POWER LCC 4518 WEBB RD ANDERSON CA 96007 CSLB# : 1079237 Phone : (559)-936-2123 Email: ops@solarepwr.com SPEC SHEETS 500 W Tribella Ct - 2017811201/31/23 REV SHEET NAME SHEET NUMBER DATE DESCRIPTION VERSION PV-16 PROJECT NAME UR09/15/2022 INITIAL RELEASE BE N J A M I N N G U Y E N 50 0 W T R I B E L L A C T , SA N T A A N A , C A 9 2 7 0 3 U S A AP N # 1 9 8 3 5 2 0 1 UT I L I T Y : S C E AH J : C I T Y O F S A N T A A N A SHEET SIZE ANSI B 11" X 17" SOLARE POWER LCC 4518 WEBB RD ANDERSON CA 96007 CSLB# : 1079237 Phone : (559)-936-2123 Email: ops@solarepwr.com SPEC SHEETS 500 W Tribella Ct - 2017811201/31/23 REV SHEET NAME SHEET NUMBER DATE DESCRIPTION VERSION PV-17 PROJECT NAME UR09/15/2022 INITIAL RELEASE BE N J A M I N N G U Y E N 50 0 W T R I B E L L A C T , SA N T A A N A , C A 9 2 7 0 3 U S A AP N # 1 9 8 3 5 2 0 1 UT I L I T Y : S C E AH J : C I T Y O F S A N T A A N A SHEET SIZE ANSI B 11" X 17" SOLARE POWER LCC 4518 WEBB RD ANDERSON CA 96007 CSLB# : 1079237 Phone : (559)-936-2123 Email: ops@solarepwr.com SPEC SHEETS 500 W Tribella Ct - 2017811201/31/23 CBMSPUM JB ECS BLP BAT ~60.87' ~3 5 . 1 8 ' ~60.87' ~3 5 . 1 8 ' 3' - 2 " 6'-9" 4'-9" 4' - 5 " SITE PLAN WITH ROOF PLAN REV SHEET NAME SHEET NUMBER DATE DESCRIPTION VERSION PV-1 PROJECT NAME UR09/15/2022 INITIAL RELEASE BE N J A M I N N G U Y E N 50 0 W T R I B E L L A C T , SA N T A A N A , C A 9 2 7 0 3 U S A AP N # 1 9 8 3 5 2 0 1 UT I L I T Y : S C E AH J : C I T Y O F S A N T A A N A SHEET SIZE ANSI B 11" X 17" SOLARE POWER LCC 4518 WEBB RD ANDERSON CA 96007 CSLB# : 1079237 Phone : (559)-936-2123 Email: ops@solarepwr.com SITE PLAN WITH ROOF PLAN 1 SCALE: 3/16" = 1'-0" NOTE: A. ALL ELECTRICAL EQUIPMENT, INVERTERS, DISCONNECTS, MAIN SERVICE PANELS, ETC. SHALL NOT BE INSTALLED WITHIN 3’ OF THE GAS METERS’ SUPPLY OR DEMAND PIPING. ROOF ACCESS POINT SHALL BE LOCATED IN AREAS THAT DO NOT REQUIRE THE PLACEMENT OF GROUND LADDERS OVER OPENINGS SUCH AS WINDOWS OR DOORS, AND LOCATED AT STRONG POINTS OF BUILDING CONSTRUCTION IN LOCATIONS WHERE THE ACCESS POINT DOES NOT CONFLICT WITH OVERHEAD OBSTRUCTIONS SUCH AS TREE LIMBS, WIRES OR SIGNS. PROPERTY LINE PR O P E R T Y L I N E PROPERTY LINE PR O P E R T Y L I N E THREE- STORY HOUSE ROOF ACCESS POINT (E) GATE ROOF #1 (11) HANWAH Q CELLS Q.PEAK DUO BLK ML-G10+ (400W) MODULES ROOF #2 (06) HANWAH Q CELLS Q.PEAK DUO BLK ML-G10+ (400W) MODULES ROOF #3 (03) HANWAH Q CELLS Q.PEAK DUO BLK ML-G10+ (400W) MODULES ROOF #4 (04) HANWAH Q CELLS Q.PEAK DUO BLK ML-G10+ (400W) MODULES (E) 225A MAIN SERVICE PANEL WITH (E) 200A MAIN BREAKER (E) UTILITY METER (N) ENPHASE IQ COMBINER BOX 4 (N) 3/4" OR GREATER EMT CONDUIT RUN (7/8 INCHES ABOVE ROOF) (N) JUNCTION BOX W TRIBELLA CT W T R I B E L L A C T (N) 200A ENPHASE IQ SYSTEM CONTROLLER 2 (N) 125A BACKUP LOAD PANEL (N) ENPHASE ENCHARGE 10 BATTERY LEGEND UTILITY METER JUNCTION BOX UM JB MSP MAIN SERVICE PANEL CONDUIT VENT, ATTIC FAN (ROOFOBSTRUCTION) ENPHASE IQ COMBINER 4CB BACKUP LOAD PANELBPL BATTERYBAT RAFTERS ROOF ATTACHMENT IQ2 ENPHASE IQ CONTROLLER 2 03 Jan 2023 EXP : 30 Sep 2023 STRUCTURAL ONLY 500 W Tribella Ct - 2017811201/31/23 REV SHEET NAME SHEET NUMBER DATE DESCRIPTION VERSION PV-18 PROJECT NAME UR09/15/2022 INITIAL RELEASE BE N J A M I N N G U Y E N 50 0 W T R I B E L L A C T , SA N T A A N A , C A 9 2 7 0 3 U S A AP N # 1 9 8 3 5 2 0 1 UT I L I T Y : S C E AH J : C I T Y O F S A N T A A N A SHEET SIZE ANSI B 11" X 17" SOLARE POWER LCC 4518 WEBB RD ANDERSON CA 96007 CSLB# : 1079237 Phone : (559)-936-2123 Email: ops@solarepwr.com SPEC SHEETS 500 W Tribella Ct - 2017811201/31/23 REV SHEET NAME SHEET NUMBER DATE DESCRIPTION VERSION PV-19 PROJECT NAME UR09/15/2022 INITIAL RELEASE BE N J A M I N N G U Y E N 50 0 W T R I B E L L A C T , SA N T A A N A , C A 9 2 7 0 3 U S A AP N # 1 9 8 3 5 2 0 1 UT I L I T Y : S C E AH J : C I T Y O F S A N T A A N A SHEET SIZE ANSI B 11" X 17" SOLARE POWER LCC 4518 WEBB RD ANDERSON CA 96007 CSLB# : 1079237 Phone : (559)-936-2123 Email: ops@solarepwr.com SPEC SHEETS 500 W Tribella Ct - 2017811201/31/23 REV SHEET NAME SHEET NUMBER DATE DESCRIPTION VERSION PV-20 PROJECT NAME UR09/15/2022 INITIAL RELEASE BE N J A M I N N G U Y E N 50 0 W T R I B E L L A C T , SA N T A A N A , C A 9 2 7 0 3 U S A AP N # 1 9 8 3 5 2 0 1 UT I L I T Y : S C E AH J : C I T Y O F S A N T A A N A SHEET SIZE ANSI B 11" X 17" SOLARE POWER LCC 4518 WEBB RD ANDERSON CA 96007 CSLB# : 1079237 Phone : (559)-936-2123 Email: ops@solarepwr.com SPEC SHEETS 500 W Tribella Ct - 2017811201/31/23 CB MSPUM JB ECS BLP BAT 3' -2 " 23 ' -3 " 6" 3'-0"6'-1" 3'-3" 3'-0" 15'-3" 6'-3" 3'-8" 12'-7" 7" REV SHEET NAME SHEET NUMBER DATE DESCRIPTION VERSION PV-2 PROJECT NAME UR09/15/2022 INITIAL RELEASE BE N J A M I N N G U Y E N 50 0 W T R I B E L L A C T , SA N T A A N A , C A 9 2 7 0 3 U S A AP N # 1 9 8 3 5 2 0 1 UT I L I T Y : S C E AH J : C I T Y O F S A N T A A N A SHEET SIZE ANSI B 11" X 17" SOLARE POWER LCC 4518 WEBB RD ANDERSON CA 96007 CSLB# : 1079237 Phone : (559)-936-2123 Email: ops@solarepwr.com ROOF PLAN WITH MODULES ROOF PLAN WITH MODULES SCALE: 3/16" = 1'-0"1 74.0" 41 . 1 " PHOTOVOLTAIC MODULES HANWAH Q CELLS Q.PEAK DUO BLK ML-G10+ (400W) MODULE TYPE, DIMENSIONS & WEIGHT NUMBER OF MODULES = 24 MODULES MODULE TYPE = HANWAH Q CELLS Q.PEAK DUO BLK ML-G10+ (400W) MODULES MODULE WEIGHT = 48.5 LBS / 22.0 KG. MODULE DIMENSIONS = 74.0"X 41.1" = 21.12 SF UNIT WEIGHT OF ARRAY = 2.30 PSF R324.6.2 - PROVING ARRAYS TAKE LESS THAN 33% OF TOTAL ROOF AREA.WHEN THE ARRAYS TAKE LESS THAN 33% WE CAN JUSTIFY AN 18" SETBACK ON BOTH SIDES OF THE RIDGE. WHEN IT TAKES MORE THAN 33% OF THE ROOF AREA WE MUST USE A 3' SETBACKS AT THE RIDGE. TOTAL ROOF AREA: 2133.0 sqft AREA OF ARRAYS: 74.0"X 41.1" ( PANEL DIMENSIONS) 74.0"X 41.1" = 21.12 sqft (PER PANEL) 21.12 sqft panel X 24 panels = 506.90 sqft (TOTAL PANEL AREA) PERCENTAGE OF TOTAL ROOF AREA: (506.90 sqft / 2133.0 sqft)(100)= 23.76% THE PANELS USE 23.76% OF THE TOTAL ROOF AREA · PLUMBING VENTS, SKYLIGHTS AND MECHANICAL VENTS SHALL NOT BE COVERED, MOVED, RE-ROUTED OR RE-LOCATED. NOTE: ACTUAL ROOF CONDITIONS AND RAFTERS (OR SEAM) LOCATIONS MAY VARY. INSTALL PER MANUFACTURER(S) INSTALLATION GUIDELINES AND ENGINEERED SPANS FOR ATTACHMENTS BILL OF MATERIALS EQUIPMENT QTY DESCRIPTION RAIL 16 UNIRAC SM STANADRD RAIL 168" DARK SPLICE 04 BND SPLICE BAR PRO SERIES DRK MID CLAMP 24 UNIVERSAL AF SERIES MID CLAMP END CLAMP 48 UNIVERSAL AF SERIES END CLAMP ATTACHMENT 70 UNIRAC SOLARHOOKS AT1 GROUNDING LUG 12 GROUND LUG ROOF #1 (11) HANWAH Q CELLS Q.PEAK DUO BLK ML-G10+ (400W) MODULES ROOF #2 (06) HANWAH Q CELLS Q.PEAK DUO BLK ML-G10+ (400W) MODULES ROOF #4 (04) HANWAH Q CELLS Q.PEAK DUO BLK ML-G10+ (400W) MODULES ARRAY AREA & ROOF AREA CALC'S ROOF # OF MODULES ARRAY AREA (Sq. Ft.) ROOF AREA (Sq. Ft.) ROOF AREA COVERED BY ARRAY (%) #1 11 232.33 355.67 65.32 #2 06 126.73 316.22 40.07 #3 03 63.36 202.62 31.27 #4 04 84.48 210.65 40.11 ROOF DESCRIPTION ROOF TYPE FLAT-TILE ROOF ROOF ROOF TILT AZIMUTH RAFTERS SIZE RAFTERS SPACING #1 12°90°2"x4" 24" O.C. #2 12°90°2"x4" 24" O.C. #3 12°180°2"x4" 24" O.C. #4 12°360°2"x4" 24" O.C. REAR YARD W TRIBELLA CT FRONT YARD (E) FLAT-TILE ROOF (TYP.) (N) UNIRAC SM STANADRD RAIL (TYP.) (E) 2"X4" RAFTERS @ 24" O.C. (TYP.) 18 " F I R E P A T H W A Y 18 " F I R E PA T H W A Y 18" FIRE PATHWAY 18" FIRE PATHWAY 36" FIRE PATHWAY 36 " FI R E PA T H W A Y ROOF #1 TILT - 12° AZIMUTH - 90° ROOF #2 TILT - 12° AZIMUTH - 90° ROOF #3 TILT - 12° AZIMUTH - 180° ROOF #4 TILT - 12° AZIMUTH - 360° 36" FI R E P A T H W A Y 36" FI R E P A T H W A Y ROOF #3 (03) HANWAH Q CELLS Q.PEAK DUO BLK ML-G10+ (400W) MODULES (E) 225A MAIN SERVICE PANEL WITH (E) 200A MAIN BREAKER (E) UTILITY METER (N) ENPHASE IQ COMBINER BOX 4 (N) 3/4" OR GREATER EMT CONDUIT RUN (7/8 INCHES ABOVE ROOF) (N) JUNCTION BOX (N) 200A ENPHASE IQ SYSTEM CONTROLLER 2 (N) 125A BACKUP LOAD PANEL (N) ENPHASE ENCHARGE 10 BATTERY (N) (70) UNIRAC SOLARHOOKS AT1 ATTACHMENTS SPACED AT 72" O.C. LEGEND UTILITY METER JUNCTION BOX UM JB MSP MAIN SERVICE PANEL CONDUIT VENT, ATTIC FAN (ROOFOBSTRUCTION) ENPHASE IQ COMBINER 4CB BACKUP LOAD PANELBPL BATTERYBAT RAFTERS ROOF ATTACHMENT IQ2 ENPHASE IQ CONTROLLER 2 03 Jan 2023 EXP : 30 Sep 2023 STRUCTURAL ONLY NOTE:CONTRACTOR TO VERIFY EXISTING FRAMING AND STRUCTURAL LETTER NOTIFY EOR INCASE OF DISCRIPENCIES 500 W Tribella Ct - 2017811201/31/23 REV SHEET NAME SHEET NUMBER DATE DESCRIPTION VERSION PV-3 PROJECT NAME UR09/15/2022 INITIAL RELEASE BE N J A M I N N G U Y E N 50 0 W T R I B E L L A C T , SA N T A A N A , C A 9 2 7 0 3 U S A AP N # 1 9 8 3 5 2 0 1 UT I L I T Y : S C E AH J : C I T Y O F S A N T A A N A SHEET SIZE ANSI B 11" X 17" SOLARE POWER LCC 4518 WEBB RD ANDERSON CA 96007 CSLB# : 1079237 Phone : (559)-936-2123 Email: ops@solarepwr.com ATTACHMENT DETAIL ATTACHMENT DETAIL SCALE: NTS1 ATTACHMENT DETAIL (ENLARGED VIEW) SCALE: NTS2 NOTE: ACTUAL ROOF CONDITIONS AND RAFTERS (OR SEAM) LOCATIONS MAY VARY. INSTALL PER MANUFACTURER(S) INSTALLATION GUIDELINES AND ENGINEERED SPANS FOR ATTACHMENTS (N) PANELS(N) UNIRAC SM STANDARD RAIL ROOF / DECK MEMBRANE UNIRAC SOLAR HOOK AT1 2.5" MIN. EMBEDMENT (2) 1/4” STAINLESS STEEL LAG BOLT AND SS EPDM WASHER; 2.5” MINIMUM EMBEDMENT REQUIRED ENLARGE VIEW (N) PV MODULES (E) 2"X4" RAFTE R S @24" O.C ~8 " ~8 " (E) FLAT-TILE ROOF BUILDING STRUCTURE (E) FLAT-TILE ROOF 1. 2 6 " 1.26 " 03 Jan 2023 EXP : 30 Sep 2023 STRUCTURAL ONLY NOTE TO INSTALLER: VERIFY THE ROOF FRAMING INFO BEFORE INSTALLATION AND NOTIFY EOR IF THERE IS ANY INCONSISTENCY BETWEEN SITE VERIFICATION AND THE FOLLOWING: 2X4 RAFTERS @24" O.C. WITH MAX UNSUPPORTED SPAN EQUAL OR LESS THAN 10 FT. 500 W Tribella Ct - 2017811201/31/23 REV SHEET NAME SHEET NUMBER DATE DESCRIPTION VERSION PV-4 PROJECT NAME UR09/15/2022 INITIAL RELEASE BE N J A M I N N G U Y E N 50 0 W T R I B E L L A C T , SA N T A A N A , C A 9 2 7 0 3 U S A AP N # 1 9 8 3 5 2 0 1 UT I L I T Y : S C E AH J : C I T Y O F S A N T A A N A SHEET SIZE ANSI B 11" X 17" SOLARE POWER LCC 4518 WEBB RD ANDERSON CA 96007 CSLB# : 1079237 Phone : (559)-936-2123 Email: ops@solarepwr.com BRANCH LAYOUT BRANCH LAYOUT SCALE: 1/4"=1'1 (24) HANWAH Q CELLS Q.PEAK DUO BLK ML-G10+ (400W) MODULES (24) ENPHASE ENERGY IQ8PLUS-72-2-US MICRO-INVERTERS (02) BRANCHS OF 12 MODULES CONNECTED IN PARALLEL PER BRANCH 18" RIDGE & 36" FIRE PATHWAY 74.0" 41 . 1 " PHOTOVOLTAIC SOLAR MODULES HANWAH Q CELLS Q.PEAK DUO BLK ML-G10+ (400W) ROOF #1 (11) HANWAH Q CELLS Q.PEAK DUO BLK ML-G10+ (400W) MODULES ROOF #2 (06) HANWAH Q CELLS Q.PEAK DUO BLK ML-G10+ (400W) MODULES ROOF #3 (03) HANWAH Q CELLS Q.PEAK DUO BLK ML-G10+ (400W) MODULES ROOF #4 (04) HANWAH Q CELLS Q.PEAK DUO BLK ML-G10+ (400W) MODULES REAR YARD W TRIBELLA CT FRONT YARD 18 " F I R E P A T H W A Y 18 " FI RE PA T H W A Y 18" FIRE PATHWAY 18" FIRE PATHWAY 36" FIRE PATHWAY 36 " FI RE P A T H W A Y 36" FIRE PATHWAY (24) ENPHASE ENERGY IQ8PLUS-72-2-US MICRO-INVERTERS BRANCH #1 BRANCH #2 36" FIRE PATHWAY 36" FIR E P A T H W A Y 36" F I R E PAT H W A Y 500 W Tribella Ct - 2017811201/31/23 REV SHEET NAME SHEET NUMBER DATE DESCRIPTION VERSION PV-5 PROJECT NAME UR09/15/2022 INITIAL RELEASE BE N J A M I N N G U Y E N 50 0 W T R I B E L L A C T , SA N T A A N A , C A 9 2 7 0 3 U S A AP N # 1 9 8 3 5 2 0 1 UT I L I T Y : S C E AH J : C I T Y O F S A N T A A N A SHEET SIZE ANSI B 11" X 17" SOLARE POWER LCC 4518 WEBB RD ANDERSON CA 96007 CSLB# : 1079237 Phone : (559)-936-2123 Email: ops@solarepwr.com ELECTRICAL LINE DIAGRAM CHANGE AS PER YOUR REQUIREMENT SYSTEM SIZE:- 24 x 400W = 9.60 kWDC SYSTEM SIZE:- (24 x 371.50 x 0.97)/1000 = 8.77 CEC kW AC (24) HANWAH Q CELLS Q.PEAK DUO BLK ML-G10+ (400W) MODULES (24) ENPHASE ENERGY IQ8PLUS-72-2-US MICRO-INVERTERS (02) BRANCHES OF 12 MODULES CONNECTED IN PARALLEL PER BRANCH BILL OF MATERIALS EQUIPMENT QTY DESCRIPTION SOLAR PV MODULE 24 HANWAH Q CELLS Q.PEAK DUO BLK ML-G10+ (400W) MODULES INVERTER 24 ENPHASE ENERGY IQ8PLUS-72-2-US MICRO-INVERTERS JUNCTION BOX 1 600V, 55A MAX, 4 INPUTS, MOUNTED ON ROOF FOR WIRE & CONDUIT TRANSITION COMBINER BOX 1 ENPHASE IQ COMBINER BOX 4 BATTERY 1 ENCHARGE 10 STORAGE SYSTEM BACKUP LOAD PANEL 1 100A BACKUP LOAD PANEL SHUTDOWN SWITCH 1 ENPHASE SYSTEM SHUTDOWN SWITCH SYSTEM CONTROLLER 1 ENPHASE IQ SYSTEM CONTROLLER 2 ELECTRICAL LINE DIAGRAM SCALE: NTS1 UTILITY PROVIDER: MAIN SERVICE VOLTAGE: MAIN PANEL BRAND: MAIN SERVICE PANEL: MAIN CIRCUIT BREAKER RATING: MAIN SERVICE LOCATION: SERVICE FEED SOURCE: SCE 240V N/A (E) 225 A (E) 200 A SOUTH UNDERGROUND SERVICE INFO. 12 MICRO-INVERTERS IN BRANCH CIRCUIT #1 G (4) #10 AWG THWN-2 (1) #10 AWG THWN-2 GND IN 3/4" EMT CONDUIT RUN OR (3) #10 NM-B Q-CABLES WHERE RUN INDOOR (N) JUNCTION BOX G IQ GATEWAY 12 MICRO-INVERTERS IN BRANCH CIRCUIT #2 20A 20A (2) Q-CABLE (1) PV #6 BARE CU GND (N) ENPHASE IQ COMBINER BOX 4 (3) #8 AWG THWN (1) #8 AWG THWN GND IN 3/4" EMT CONDUIT RUN CONSUMPTION CT 40A 20A G CTRL 20A CELL MODEM MOBILE CONNECT WIRELESS COMM. (N) ENPHASE IQ BATTERY 10 3.84kVA, 10KWH CTRL (N) 200A ENPHASE IQ SYSTEM CONTROLLER 2 (N) 40A PV BREAKER (N) 20A ESS BREAKER WITH ESS HOLD DOWN KIT BRHDK125 PER NEC 710.15 (N) ESS INPUT TERMINALS (N) PV INPUT TERMINALS (N) 100A BACKUP LOAD PANEL, MLO (2) #10 AWG THWN (1) #10 AWG THWN GND IN 3/4" EMT CONDUIT RUN (3) #2 AWG THWN (1) #8 AWG THWN GND IN 1-1/4" EMT CONDUIT RUN (3) #2 AWG THWN (1) #8 AWG THWN GND IN 1-1/4" EMT CONDUIT RUN POWER LINE COMMUNICATION ENPHASE RAPID SHUT DOWN P/N: EP200G-NA-02-RSD IMO P/N: SI16-PEL64R-2-ENP TERMINATOR CAP ON LAST CABLE CONNECTOR AC TRUNK CABLE (TYP) MICRO-INVERTER (N) ESS HOLD DOWN KIT EATON BR220B EXISTING GROUNDING SYSTEM 200A 100A L BI-DIRECTIONAL UTILITY METER 1-PHASE, 3-W, 120V/240V, 60Hz (E) 225A MAIN SERVICE PANEL WITH (E) 200A MAIN BREAKER (BOTTOM FED) (N) 100A FEEDER BREAKER 100A 100A (N) 100A MAIN BREAKER (N) 100A FEEDER BREAKER NOTES: FOR BACKUP PANEL 1) SINGLE LARGEST BREAKER IN BACKED UP LOAD PANEL CANNOT EXCEED THE (ESS) STORAGE OUTPUT CAPACITY (6.632A) PER NEC 710.15. 2) LRA OF LARGEST LOAD IN BACKED UP LOAD PANEL CANNOT EXCEED THE (ESS) STORAGE OUTPUT CAPACITY (8.2A) PER NEC 710.15, INSTALL SOFT START DEVICE TO MEET COMPLIANCE. 3) BASELINE LOADOF BACKED UP LOAD PANEL CANNOT EXCEED THE (ESS) STORAGE OUTPUT CAPACITY (5.3A) PER NEC 710.15. 500 W Tribella Ct - 2017811201/31/23 REV SHEET NAME SHEET NUMBER DATE DESCRIPTION VERSION PV-6 PROJECT NAME UR09/15/2022 INITIAL RELEASE BE N J A M I N N G U Y E N 50 0 W T R I B E L L A C T , SA N T A A N A , C A 9 2 7 0 3 U S A AP N # 1 9 8 3 5 2 0 1 UT I L I T Y : S C E AH J : C I T Y O F S A N T A A N A SHEET SIZE ANSI B 11" X 17" SOLARE POWER LCC 4518 WEBB RD ANDERSON CA 96007 CSLB# : 1079237 Phone : (559)-936-2123 Email: ops@solarepwr.com ELECTRICAL CALCULATION SOLAR MODULE SPECIFICATIONS MANUFACTURER / MODEL #hanwah q cells Q.PEAK DUO BLK ML-G10+ (400W) MODULES VMP 37.13 IMP 10.77 VOC 45.30 ISC 11.14 MODULE DIMENSION 74.0"L x 41.1"W x 1.26"D (In Inch) INVERTER SPECIFICATIONS MANUFACTURER / MODEL #ENPHASE ENERGY IQ8PLUS-72-2-US NOMINAL OUTPUT VOLTAGE 240 VAC NOMINAL OUTPUT CURRENT 1.21A AMBIENT TEMPERATURE SPECS WEATHER STATION: TUSTIN MCAF RECORD LOW TEMP 2° AMBIENT TEMP (HIGH TEMP 2%)31° CONDUIT HEIGHT (ABOVE ROOF)7/8" ROOF TOP TEMP 31° CONDUCTOR TEMPERATURE RATE (ON ROOF)90° CONDUCTOR TEMPERATURE RATE (OFF ROOF)75° MODULE TEMPERATURE COEFFICIENT OF Voc -0.27%/°C PERCENT OF VALUES NUMBER OF CURRENT CARRYING CONDUCTORS IN EMT .80 4-6 .70 7-9 .50 10-20 ELECTRICAL CALCULATION SCALE: NTS1 ELECTRICAL NOTES 1.) ALL EQUIPMENT TO BE LISTED BY UL OR OTHER NRTL, AND LABELED FOR ITS APPLICATION. 2.) ALL CONDUCTORS SHALL BE COPPER, RATED FOR 600 V AND 90 AND 75 DEGREE C WET ENVIRONMENT. 3.) WIRING, CONDUIT, AND RACEWAYS MOUNTED ON ROOFTOPS SHALL BE ROUTED DIRECTLY TO, AND LOCATED AS CLOSE AS POSSIBLE TO THE NEAREST RIDGE, HIP, OR VALLEY. 4.) WORKING CLEARANCES AROUND ALL NEW AND EXISTING ELECTRICAL EQUIPMENT SHALL COMPLY WITH CEC 110.26. 5.) DRAWINGS INDICATE THE GENERAL ARRANGEMENT OF SYSTEMS. CONTRACTOR SHALL FURNISH ALL NECESSARY OUTLETS, SUPPORTS, FITTINGS AND ACCESSORIES TO FULFILL APPLICABLE CODES AND STANDARDS. 6.) WHERE SIZES OF JUNCTION BOXES, RACEWAYS, AND CONDUITS ARE NOT SPECIFIED, THE CONTRACTOR SHALL SIZE THEM ACCORDINGLY. 7.) ALL WIRE TERMINATIONS SHALL BE APPROPRIATELY LABELED AND READILY VISIBLE. 8.) MODULE GROUNDING CLIPS TO BE INSTALLED BETWEEN MODULE FRAME AND MODULE SUPPORT RAIL, PER THE GROUNDING CLIP MANUFACTURER'S INSTRUCTION. 9.) MODULE SUPPORT RAIL TO BE BONDED TO CONTINUOUS COPPER G.E.C. VIA WEEB LUG OR ILSCO GBL-4DBT LAY-IN LUG. 10.) THE POLARITY OF THE GROUNDED CONDUCTORS IS NEGATIVE AC CONDUCTOR AMPACITY CALCULATIONS: FROM JUNCTION BOX TO COMBINER BOX: AMBIENT TEMPERATURE ADJUSTMENT FOR EXPOSED CONDUIT PER CEC 310.15(B)(3)(c): (7/8"RULE) EXPECTED WIRE TEMP (°C): 31° TEMP CORRECTION PER TABLE 310.15(B)(2)(a): 0.96 # OF CURRENT CARRYING CONDUCTORS: 4 CONDUIT FILL CORRECTION PER CEC 310.15(B)(3)(a): 0.8 CIRCUIT CONDUCTOR SIZE: 10 AWG CIRCUIT CONDUCTOR AMPACITY: 40A REQUIRED CIRCUIT CONDUCTOR AMPACITY PER CEC 690.8(A&B): 1.25 X # MICRO-INVERTERS (MAX. BRANCH LENGTH) X MAX OUTPUT CURRENT 1.25 X 10 X 1.21A = 15.13A DERATED AMPACITY OF CIRCUIT CONDUCTOR PER CEC TABLE 310.15(B)(2)(a) TEMP CORR. PER CEC TABLE 310.15(B)(2)(a) X CONDUIT FILL CORR. PER CEC 310.15(B)(3)(a) X CIRCUIT CONDUCTOR AMPACITY = 0.96 X 0.8 X 40 = 30.72A AC CONDUCTOR AMPACITY CALCULATIONS: FROM COMBINER BOX TO IQ CONTROLLER 2: # OF INVERTERS: 24 EXPECTED WIRE TEMP (°C): 31° TEMP CORRECTION PER TABLE 310.15(B)(2)(a): 0.94 # OF CURRENT CARRYING CONDUCTORS: 3 CONDUIT FILL PER CEC 310.15(B)(3)(a): 1.0 CIRCUIT CONDUCTOR SIZE: 8 AWG CIRCUIT CONDUCTOR AMPACITY: 50 A REQUIRED CIRCUIT CONDUCTOR AMPACITY PER CEC 690.8(B): 1.25 X # MICRO-INVERTERS X MAX OUTPUT CURRENT = 1.25 X 24 X 1.21 = 36.30A DERATED AMPACITY OF CIRCUIT CONDUCTORS PER CEC TABLE 310.16: TEMP CORR. PER CEC TABLE 310.15(B)(2)(a) X CONDUIT FILL CORR. PER CEC 310.15(B)(3)(a) X CIRCUIT CONDUCTOR AMPACITY = 0.94 X 1 X 50 = 47A RESULT SHOULD BE GREATER THAN (15.13A) OTHERWISE LESS THE ENTRY FOR CIRCUIT CONDUCTOR SIZE AND AMPACITY RESULT SHOULD BE GREATER THAN (36.30A) OTHERWISE LESS THE ENTRY FOR CIRCUIT CONDUCTOR SIZE AND AMPACITY AC CONDUCTOR AMPACITY CALCULATIONS: FROM IQ CONTROLLER 2 TO INTERCONNECTION: # OF INVERTERS: 24 EXPECTED WIRE TEMP (°C): 31° TEMP CORRECTION PER TABLE 310.15(B)(2)(a): 0.94 # OF CURRENT CARRYING CONDUCTORS: 3 CONDUIT FILL PER CEC 310.15(B)(3)(a): 1.0 CIRCUIT CONDUCTOR SIZE: 2 AWG CIRCUIT CONDUCTOR AMPACITY: 115 A REQUIRED CIRCUIT CONDUCTOR AMPACITY PER CEC 690.8(B): 100A DERATED AMPACITY OF CIRCUIT CONDUCTORS PER CEC TABLE 310.16: TEMP CORR. PER CEC TABLE 310.15(B)(2)(a) X CONDUIT FILL CORR. PER CEC 310.15(B)(3)(a) X CIRCUIT CONDUCTOR AMPACITY = 0.94 X 1.0 X 115= 108.1A RESULT SHOULD BE GREATER THAN (100A) OTHERWISE LESS THE ENTRY FOR CIRCUIT CONDUCTOR SIZE AND AMPACITY 500 W Tribella Ct - 2017811201/31/23 REV SHEET NAME SHEET NUMBER DATE DESCRIPTION VERSION PV-7 PROJECT NAME UR09/15/2022 INITIAL RELEASE BE N J A M I N N G U Y E N 50 0 W T R I B E L L A C T , SA N T A A N A , C A 9 2 7 0 3 U S A AP N # 1 9 8 3 5 2 0 1 UT I L I T Y : S C E AH J : C I T Y O F S A N T A A N A SHEET SIZE ANSI B 11" X 17" SOLARE POWER LCC 4518 WEBB RD ANDERSON CA 96007 CSLB# : 1079237 Phone : (559)-936-2123 Email: ops@solarepwr.com WARNING LABELS & PLACARD CAUTION ! POWER TO THIS BUILDING IS ALSO SUPPLIED FROM THE FOLLOWING SOURCES WITH DISCONNECTS LOCATED AS SHOWN AT: MAIN SERVICE PANEL & UTILITY METER, AC DISCONNECT & COMBINER BOX 500 W TRIBELLA CT (E) 225A MAIN SERVICE PANEL WITH (E) 200A MAIN BREAKER (E) UTILITY METER (N) ENPHASE IQ COMBINER BOX 4 (N) PV MODULES WARNING DUAL POWER SOURCES SECOND SOURCE IS PHOTOVOLTAIC SYSTEM WARNING POWER SOURCE OUTPUT CONNECTION - DO NOT RELOCATE THIS OVERCURRENT DEVICE. REQ'D BY & 705.12 (B)(3) APPLY TO: MAIN SERVICE PANEL LOAD CENTER COMBINER BOX INVERTER AT EACH AC DISCONNECTS MEANS [CEC 690.13(B) AND 690.54] AT POINT OF INTERCONNECTION OVERCURRENT DEVICE REQ'D BY CEC 705.12 (B)(2)(3)(B) PHOTOVOLTAIC SYSTEM AC DISCONNECT RATED AC OPERATING CURRENT 29.04 AMPS AC NOMINAL OPERATING VOLTAGE 240 VOLTS LABEL LOCATION: CONDUIT, RACEWAYS, AND J-BOXES (LABELED EVERY 10') (PER CODE: CEC690.31(G)(3) WARNING: PHOTOVOLTAIC POWER SOURCE RAPID SHUTDOWN SWITCH FOR SOLAR PV SYSTEM LABEL LOCATION: RAPID SHUTDOWN (PER CODE: CEC 690.56(C)(3) CAUTION PHOTOVALTAIC SYSTEM CIRCUIT IS BACKFED LABEL LOCATION: AT MAIN SERVICE PANE, PULL BOXES [CEC 705.12(B)(3)] AT RAPID SHUTDOWN SYSTEM [CEC 690.56(C)(1)(A)] LABEL LOCATION SOLAR PV SYSTEM EQUIPPED WITH RAPID SHUTDOWN SOLAR ELECTRIC PV PANELS TURN RAPID SHUTDOWN SWITCH TO THE "OFF" POSITION TO SHUT DOWN PV SYSTEM AND REDUCE SHOCK HAZARD IN THE ARRAY. (N) 100A BACKUP LOAD PANEL (N) 200A ENPHASE IQ SYSTEM CONTROLLER 2 (N) ENHPHASE IQ BATTERY 10 500 W Tribella Ct - 2017811201/31/23 REV SHEET NAME SHEET NUMBER DATE DESCRIPTION VERSION PV-8 PROJECT NAME UR09/15/2022 INITIAL RELEASE BE N J A M I N N G U Y E N 50 0 W T R I B E L L A C T , SA N T A A N A , C A 9 2 7 0 3 U S A AP N # 1 9 8 3 5 2 0 1 UT I L I T Y : S C E AH J : C I T Y O F S A N T A A N A SHEET SIZE ANSI B 11" X 17" SOLARE POWER LCC 4518 WEBB RD ANDERSON CA 96007 CSLB# : 1079237 Phone : (559)-936-2123 Email: ops@solarepwr.com ADDITIONAL NOTES 1. EACH MODULE TO BE GROUNDED USING THE SUPPLIED CONNECTION POINT PER MANUFACTURER'S REQUIREMENTS. ALL SOLAR MODULES, EQUIPMENT, AND METALLIC COMPONENTS ARE TO BE BONDED. IT IS THE CONTRACTOR'S RESPONSIBILITY TO INSTALL A SUPPLEMENTAL GROUNDING ELECTRODE. 2. ALL PLAQUES AND SIGNAGE REQUIRED BY THE LATEST EDITION OF NATIONAL ELECTRICAL CODE. LABEL SHALL BE METALLIC OR PLASTIC, ENGRAVED OR MACHINE PRINTED IN A CONTRASTING COLOR TO THE PLAQUE. PLAQUE SHALL BE UV RESISTANT IF EXPOSED TO SUNLIGHT. 3. AC/DC SOLAR FED CONDUCTORS SHALL BE RUN IN EMT AND SHALL BE LABELED, PER CEC690.31(G)(3). 4. EXPOSED NON-CURRENT CARRYING METAL PARTS OF ELECTRICAL EQUIPMENT SHALL BE GROUNDED IN ACCORDANCE WITH 250.134 OR 250.136(A). 5. CONFIRM LINE SIDE VOLTAGE AT ELECTRIC UTILITY SERVICE PRIOR TO CONNECTING INVERTER. VERIFY SERVICE VOLTAGE IS WITHIN INVERTER VOLTAGE OPERATIONAL RANGE. 6. OUTDOOR EQUIPMENT SHALL BE NEMA-3R RATED OR BETTER. 7. ELECTRICAL CONTRACTOR TO PROVIDE CONDUIT EXPANSION JOINTS AND ANCHOR CONDUIT RUNS AS REQUIRED PER CEC. 8. ALL WIRING MUST BE PROPERLY SUPPORTED BY DEVICES OR MECHANICAL MEANS DESIGNED AND LISTED FOR SUCH USE, AND FOR ROOF-MOUNTED SYSTEMS, PV WIRING MUST BE SECURED AND PROPERLY MANAGED, NOT IN CONTACT WITH ROOF SURFACE. CEC 110.2 - 110.4 / 300.4. WIRE IN CONDUIT NEEDS TO BE MOUNTED > 3.5 IN ABOVE ROOF SURFACE TO MAINTAIN TEMPERATURE DERATE VALUES. 500 W Tribella Ct - 2017811201/31/23