Expedited Permit Process for PV Systems1
Expedited Permit Process for PV Systems
Standard String System
The Solar America Board for Codes and Standards (Solar ABCs) Expedited Permit Pro-
cess provides a means to differentiate systems that can be permitted quickly and easily
due to their similarity with the majority of small-scale PV systems. Those systems with
unique characteristics may be handled with small additions to this Expedited Permit
Process or may require much more information, depending on the uniqueness of the
installation.
The following pages contain forms for the Standard String System to use with the Expe-
dited Permit Process. The Micro-Inverter, AC Module, and Supply-Side Connection forms
are also available as interactive PDF files at www.solarabcs.org/permitting. In jurisdic-
tions that have adopted the Expedited Permit Process for PV Systems, these forms can
be filled out electronically and submitted in either printed form and via email. An elec-
tronic format is used so that the supplied information is standardized and legible for the
local jurisdiction.
729 W Central Ave
02/01/23
Expedited Permit Process for PV Systems2
Expedited Permit Process for Small-Scale PV Systems
Standard String System
The information in this guideline is intended to help local jurisdictions and contractors identify when PV system installations
are simple, needing only a basic review, and when an installation is more complex. It is likely that 50%-75% of all residential
systems will comply with these simple criteria. For projects that fail to meet the simple criteria, resolution steps have been
suggested to provide as a path to permit approval.
Required Information for Permit:
1. Site plan showing location of major components on the property. This drawing need not be exactly to scale, but it
should represent relative location of components at site (see supplied example site plan). PV arrays on dwellings
with a 3’ perimeter space at ridge and sides may not need separate fire service review.
2. Electrical diagram showing PV array configuration, wiring system, overcurrent protection, inverter, disconnects,
required signs, and ac connection to building (see supplied standard electrical diagram).
3. Specification sheets and installation manuals (if available) for all manufactured components including, but not
limited to, PV modules, inverter(s), combiner box, disconnects, and mounting system.
Step 1: Structural Review of PV Array Mounting System
Is the array to be mounted on a defined, permitted roof structure? l Yes l No
If No due to non-compliant roof or a ground mount, submit completed worksheet for the structure WKS1.
Roof Information:
1. Is the roofing type lightweight (Yes = composition, lightweight masonry, metal, etc…)__________________________
____________________________________________________________________________________________________
If No, submit completed worksheet for roof structure WKS1 (No = heavy masonry, slate, etc…).
2. Does the roof have a single roof covering? l Yes l No
If No, submit completed worksheet for roof structure WKS1.
3. Provide method and type of weatherproofing roof penetrations (e.g. flashing, caulk).____________________________
Mounting System Information:
1. Is the mounting structure an engineered product designed to mount PV modules with no more than an 18” gap
beneath the module frames? l Yes l No
If No, provide details of structural attachment certified by a design professional.
2. For manufactured mounting systems, fill out information on the mounting system below:
a. Mounting System Manufacturer ___________Product Name and Model#________________________________
b. Total Weight of PV Modules and Rails ___________lbs
c. Total Number of Attachment Points____________
d. Weight per Attachment Point (b÷c)_________________lbs (if greater than 45 lbs, see WKS1)
e. Maximum Spacing Between Attachment Points on a Rail ______________inches (see product manual for
maximum spacing allowed based on maximum design wind speed)
f. Total Surface Area of PV Modules (square feet)_________________ ft 2
g. Distributed Weight of PV Module on Roof (b÷f)_______________ lbs/ft2
If distributed weight of the PV system is greater than 5 lbs/ft2, see WKS1.
Step 2: Electrical Review of PV System (Calculations for Electrical Diagram)
In order for a PV system to be considered for an expedited permit process, the following must apply:
1. PV modules, utility-interactive inverters, and combiner boxes are identified for use in PV systems.
2. The PV array is composed of 4 series strings or less per inverter.
3. The total inverter capacity has a continuous ac power output 13,440 Watts or less
4. The ac interconnection point is on the load side of service disconnecting means (690.64(B)).
5. One of the standard electrical diagrams (E1.1, E1.1a, E1.1b, or E1.1c) can be used to accurately represent the PV
system. Interactive PDF diagrams are available at www.solarabcs.org/permitting.
Fill out the standard electrical diagram completely. A guide to the electrical diagram is provided to help the applicant
understand each blank to fill in. If the electrical system is more complex than the standard electrical diagram can effectively
communicate, provide an alternative diagram with appropriate detail.
729 W Central Ave
02/01/23
Ex
p
e
d
i
t
e
d
P
e
r
m
i
t
P
r
o
c
e
s
s
f
o
r
P
V
S
y
s
t
e
m
s
3
Standard String System Site Plan
Power4ward
37107 Stratford St Santa Ana
Indio CA 92203 729 C entral Ave
5.22
729 W Central Ave
02/01/23
Ex
p
e
d
i
t
e
d
P
e
r
m
i
t
P
r
o
c
e
s
s
f
o
r
P
V
S
y
s
t
e
m
s
4
Standard String System Electrical Diagram
Power4ward
37107 Stratford St Santa Ana
Indio CA 92203 729 C entral Ave
5.22
729 W Central Ave
02/01/23
Ex
p
e
d
i
t
e
d
P
e
r
m
i
t
P
r
o
c
e
s
s
f
o
r
P
V
S
y
s
t
e
m
s
5
Notes for Standard String System Electrical Diagram
Contractor Name,
Address and Phone:
_________________
_________________
_________________
_________________
Notes for One-Line Standard Electrical
Diagram for Single-Phase PV Systems
Site Name: __________________________
Site Address: ________________________
System AC Size: ______________________
SIZE FSCM NO DWG NO REV
SCALE NTS Date: SHEET
Drawn By:
Checked By:
MAX POWER-POINT CURRENT (IMP)
MAX POWER-POINT VOLTAGE (VMP)
OPEN-CIRCUIT VOLTAGE (VOC)
SHORT-CIRCUIT CURRENT (ISC)
MAX SERIES FUSE (OCPD)
MAXIMUM POWER (PMAX)
MAX VOLTAGE (TYP 600VDC)
VOC TEMP COEFF (mV/oC or %/oC )
IF COEFF SUPPLIED, CIRCLE UNITS
A
V
V
A
A
W
V
MODULE MAKE
MODULE MODEL
PV MODULE RATINGS @ STC (Guide Section 5)
MAX DC VOLT RATING
MAX POWER @ 40oC
NOMINAL AC VOLTAGE
MAX AC CURRENT
MAX OCPD RATING
V
W
V
A
A
INVERTER MAKE
INVERTER MODEL
INVERTER RATINGS (Guide Section 4)
1) IF UTILITY REQUIRES A VISIBLE-BREAK SWITCH, DOES THIS SWITCH MEET THE
REQUIREMENT? YES NO N/A
2) IF GENERATION METER REQUIRED, DOES THIS METER SOCKET MEET THE
REQUIREMENT? YES NO N/A
3) SIZE PHOTOVOLTAIC POWER SOURCE (DC) CONDUCTORS BASED ON MAX
CURRENT ON NEC 690.53 SIGN OR OCPD RATING AT DISCONNECT
4) SIZE INVERTER OUTPUT CIRCUIT (AC) CONDUCTORS ACCORDING TO INVERTER
OCPD AMPERE RATING. (See Guide Section 9)
5) TOTAL OF ______ INVERTER OCPD(s), ONE FOR EACH INVERTER. DOES TOTAL
SUPPLY BREAKERS COMPLY WITH 120% BUSBAR EXCEPTION IN 690.64(B)(2)(a)?
YES NO
NOTES FOR INVERTER CIRCUITS (Guide Section 8 and 9):
1.) LOWEST EXPECT AMBIENT TEMPERATURE BASED ON ASHRAE MINIMUM MEAN
EXTREME DRY BULB TEMPERATURE FOR ASHRAE LOCATION MOST SIMILAR TO
INSTALLATION LOCATION. LOWEST EXPECTED AMBIENT TEMP ______oC
2.) HIGHEST CONTINUOUS AMBIENT TEMPERATURE BASED ON ASHRAE HIGHEST
MONTH 2% DRY BULB TEMPERATURE FOR ASHRAE LOCATION MOST SIMILAR TO
INSTALLATION LOCATION. HIGHEST CONTINUOUS TEMPERATURE _____oC
2.) 2005 ASHRAE FUNDEMENTALS 2% DESIGN TEMPERATURES DO NOT EXCEED
47oC IN THE UNITED STATES (PALM SPRINGS, CA IS 44.1 oC). FOR LESS THAN 9
CURRENT-CARRYING CONDUCTORS IN ROOF-MOUNTED SUNLIT CONDUIT AT
LEAST 0.5" ABOVE ROOF AND USING THE OUTDOOR DESIGN TEMPERATURE OF
47oC OR LESS (ALL OF UNITED STATES),
a) 12 AWG, 90oC CONDUCTORS ARE GENERALLY ACCEPTABLE FOR MODULES
WITH Isc OF 7.68 AMPS OR LESS WHEN PROTECTED BY A 12-AMP OR SMALLER
FUSE.
b) 10 AWG, 90oC CONDUCTORS ARE GENERALLY ACCEPTABLE FOR MODULES
WITH Isc OF 9.6 AMPS OR LESS WHEN PROTECTED BY A 15-AMP OR SMALLER
FUSE.
NOTES FOR ARRAY CIRCUIT WIRING (Guide Section 6 and 8 and Appendix D):
OCPD = OVERCURRENT PROTECTION DEVICE
NATIONAL ELECTRICAL CODE ® REFERENCES
SHOWN AS (NEC XXX.XX)
NOTES FOR ALL DRAWINGS:
SIGNSSEE GUIDE SECTION 7
SIGN FOR DC DISCONNECT
SIGN FOR INVERTER OCPD AND
AC DISCONNECT (IF USED)
RATED MPP CURRENT
RATED MPP VOLTAGE
MAX SYSTEM VOLTAGE
MAX CIRCUIT CURRENT
A
V
V
A
PHOTOVOLTAIC POWER SOURCE
WARNING: ELECTRICAL SHOCK
HAZARDLINE AND LOAD MAY BE
ENERGIZED IN OPEN POSITION
AC OUTPUT CURRENT
NOMINAL AC VOLTAGE
A
V
SOLAR PV SYSTEM
AC POINT OF CONNECTION
THIS PANEL FED BY MULTIPLE
SOURCES (UTILITY AND SOLAR)
Power4ward
37107 Stratford St Santa Ana
Indio CA 92203
729 C entral Ave
5.22
729 W Central Ave
02/01/23
729 W. CENTRAL AVE.
SANTA ANA, CA 92707
DUENAS, JOELJob:
Design Criteria
1- Code: CALIFORNIA BLDG CODE 2019 / ASCE 7-16
2 - Wind: 95 MPH, Exposure: C
3 - Wood Species: DF-L No. 2 (SG = 0.5 )
Notice: Use restrictions of these calculations.
The attached Calculations are valid only when bearing original signature hereon.
Contractor/Client to verify existing dimensions/conditions prior to construction
& solar racking is installed per manufacturer span requirements.
The use of these calculations is solely intended for the above mentioned project.
1-844-PV ELITE | info@yoursolarplans.com
3000 E. Birch Street Suite 201 | Brea CA 92821
10/11/2022
Structural Calculations for
SOLAR POWER SYSTEM CONNECTION CHECK AT:
729 W Central Ave
02/01/23
0120023340163789 8
622 2!2"#$77%03%007& $'00 %(%%)*()&+$%3),+8-+.3/8.38)3%1%.30/8 023
1 ++++2++"8
"++3++"2++4
5 +8
"++"++8/6%'337"
89:;<=>?@A;B:CDA?
EFF;9GGH %3),+8-+4/848)3%1%40/8
IAA;FD?:C9GH 77%03%0074'00 %(%%)*()
JK9L:CDA?H M32
NDB9GC:BOH 3133'01'00 0 %6376711M%P
Q:R:;FNSO9H ,
E8IJTUV W
9XY01'Z+[[\
9XY3*'Z+%0 \
9XY*1'Z+%%\
9XY011'Z+(0 \
X4+ Y ()\
X4+ YY )*\
X4+ YYY 013\
X4+ Y]01[\
E8IJTUV ^
9XY01'Z+%3\
9XY3*'Z+%)\
9XY*1'Z+(*\
9XY011'Z+)0 \
X4+ Y 011 \
X4+ YY 001 \
X4+ YYY'Y]00 *\
E8IJTU^_
8/6%'1*,/++(*\
`abcbdefgdhijhklgbjabcbmnon`cbpfbkgliqdglgbrcfrklflsbijsbigdgrgabtlfebdrcliqjbfhiblghrifhibdsljbjechiugabvehfjhiu
krjbljrwghriwcrkbddxydbcddarefjkriphcsliqregwegrvglhibjpcrsgahdgrrfzhgagabfrklf{egarchgq|lthiu}echdjhkghrivbprcb
wcrkbbjhiuzhgajbdhuix
~fbldbirgbgalggab{`|llcjdvqrklghrizbvdhgbzhffirgvbewjlgbjgrdewwrcg{ xhijregzaqx
DG<K:DB9;
+++2\-+8/6%++++"++ +3+8/6%4
+++++"++2++\++4"++"++
+"++++2+4-+"++ +667+++"'+++
+4++ ++\+-+ "\22+"+++++""'+
++
9+4 +4+\+4+"+ ++\+2"
,++2\+++"++++-+++48\++
¡¢ £¤¥¤¤¤
729 W Central Ave
02/01/23
ASCE 29.4.4 Rooftop Solar Panels Parallel to the Roof Surface on Buildings of All Heights and Roof Slopes.
Roof Slope = 18 °
Roof Shape Gable
Tributary Width s = 4.00 ft
Tributary Length l = 2.79 ft
Effective Area A e = 11.15 ft2
Height of Structure h = 15 ft
Wind Speed V = 95 mph
Exposure Category C
Building Width B = 35 ft
Building Length L = 50 ft
Zone Width a = 3.5 ft
Elevation Height zg = 42 ft
Wind Directionality Kd = 0.85
Topography Factor Kt = 1.00
Ground Elevation Factor Ke = 1.00
Velocity Pressure Exposure Coefficient Kz = 0.85
Velocity Pressure q z = 0.00256KzKztKdKeV2 = 16.65 psf
Solar Array Pressure Equalization a = 0.79
Array Edge Factor E = 1.50
Zone GCp p = qz(GCp)(E)(a)
3 - -
3r 3.58 -70.99
3e 2.99 -59.35
2 - -
2r 2.99 -59.35
2e - -
2n 2.99 -59.35
1 - -
1' - -
729 W Central Ave
02/01/23
LAG SCREW ANALYSIS
Loads
Wind Pressures qz = -59.35 psf
Solar Panel Load QD = 3 psf
Panel Length l = 5.575 ft
Panel Width b 3.3333 ft
Attachment Spacing s = 4 ft
Portrait
Tributary Area At = 11.15 ft2
Wind Load P W = qz * At = -662 lbs
Dead Load P D = Q D * At = 33.45 lbs
Uplift Pa = 0.6 P D + 0.6 Pw = -377 lbs
Landscape
Tributary Area At = b * s = 6.6667 ft2
Wind Load P W = qz * At = -396 lbs
Dead Load P D = Q D * At = 20 lbs
Uplift Pa = 0.6 P D + 0.6 Pw = -225 lbs
Lag Screw
Specific Gravity of Lumber SG = 0.50 (Douglas Fir-Larch)
Diameter of Lag Screw D = 5/16 in
Withdraw Design /in 1800*SG 3/2 *D 3/4 = 266 lbs/in
Depth of Embedment lp = 2.50 in
Total Nominal Withdrawal Value W = W * l p = 665 lbs
Load Duration Factor CD = 1.6
Withdrawal Design Value W' = W * C D = 1064 lbs
Demand Capacity Ratio DCR = Pa / W' = 0.35 < 1 OK
729 W Central Ave
02/01/23
ASCE 30.3.2 Design Wind Pressure Beam/ Top Chord Check
Roof Slope = 18 °
Roof Shape Gable
Tributary Width s = 2.00 ft
Tributary Length L = 18.25 ft
Effective Area A = L ( MAX [ s , L/3] ) = 100 ft2
Height of Structure h = 15 ft
Wind Speed V = 95 mph
Exposure Category C
Building Width B = 35 ft
Building Length L = 50 ft
Zone Width a = 3.5 ft
Elevation Height zg = 42 ft
Wind Directionality Kd = 0.85
Topography Factor Kt = 1.00
Ground Elevation Factor Ke = 1.00
Velocity Pressure Exposure Coefficient Kz = 0.85
Velocity Pressure q z = 0.00256KzKztKdKeV 2 = 16.65 psf
Internal Pressure Coefficient (GCpi) = -0.18
Zone GCp p = q z [(GCp) - (Gcpi)]
3 - -
3r 1.80 -32.96
3e 2.25 -40.45
2 - -
2r 2.25 -40.45
2e - -
2n 2.25 -40.45
1 - -
1' - -
729 W Central Ave
02/01/23
Beam/ Top Chord Check Lumber:
Moment Demand
# of Attachment per Rafter N A = Span : Orientation
Lenght (ft) :
Dead Load Roof Material: Q D = psf
Live Load QLr = psf
Wind Load p = psf
Snow Load QS = psf
Rafter Spacing s = in
Wind Load, Portrait Portrait UL =
Wind Load, Landscape Landscape U W =
Linear Dead Load wd = plf
Live Load wLr = plf Start ft Start ft
End ft End ft
Snow Load ws = plf Start ft Start ft
End ft End ft
Ma, Moment
D lb-ft
D+Lr lb-ft
D+S lb-ft
0.6D+0.6W lb-ft
D+0.45W+0.75Lr lb-ft
D+0.45W+0.75S lb-ft
Moment Capacity Framing Member Size Lumber Grade : DF-L No. 2
C M = 1 Ct = 1 Cr= CF = fb = psi C fu =C i =
Breadth b = in
Depth d = in
Section Modulus Sx = bd 2 / 6 = in3
Bending Stress Capacity Fb = CM * C t * Cr * C F * fb = psi Table 4.3.1 NDS 2015
Deflection Limit E = ksi I = in4
Transient Deflection in
Transient Deflection Allowed > [OKAY]
Total Deflection in
Total Deflection Allowed > [OKAY]
-40.45
DF-L No. 2
6 j lj (ft) pd,j (lbs) pw,j (lbs) ps,j (lbs)
Portrait
1 2.2 33.5 -451 0.0
6.4 33.5 -451
-451 0.0
4 11.9 33.5 -451 0.0
0.0
5.50 11.75 0.00 0.00 1.00
Portrait
3 7.8 33.5
10.00
1 2 3 4 Eave
2
0.0
0.0 0.0 0.0
0.0
0 0.0 0.0 0.0 0.0
0 0.0 0.0 0.0
0.0
6 17.5 33.5 -451 0.0
Portrait
5 13.4 33.5 -451
0.0
20
40
0.0 0.0 0.0 0.0
0 0.0
Portrait
0
0.0 20 -270 0
0
0.0
0
1.5
0
0
0.0
Portrait
1.5
0.0
Portrait
0 0.0 0.0
AT (ft 2)
11.15
6.6667
pd (lbs)
33.45 -451
p w (lbs) ps (lbs)
0
18.23
2X6
1.15 1.3
18.25
18.23
18.25
900
1.50
5.50
402
405
402
964
505
505
DCR
0.9 1211 psi D 638 psi 0.53
7.56
1346
CD Fb' = C D * F b ASD Load Ma * S x
1.15 1547 psi D+S 638 psi 0.41 OKAY
OKAY
1.25 1682 psi D+Lr 643 psi 0.38 OKAY
1.6 2153 psi
0.538
262 120
1600 20.80
0.6D+0.6W 1529 psi 0.71 OKAY
1.0 1
20
0.00
24
Comp
0.471
299 180
1.6 2153 psi D+0.45W+0.75S 802 psi 0.37 OKAY
1.6 2153 psi D+0.45W+0.75Lr 802 psi 0.37 OKAY
ൌ ሺ െ ሻ െ െ െ
‐1500.0
‐1000.0
‐500.0
0.0
500.0
1000.0
1500.0
0.000 5.000 10.000 15.000 20.000
729 W Central Ave
02/01/23
EISMIC WEIGHT COMPARISON / ANALYSIS - (PER CEBC 2019 Part 10 Chapter 5 Section 502.5)
PV System Weight
Module Model LG
Panel Weight Wpanel = 40.8 lbs
Number of Panels NPV = 18
Total PV System Weight W PV = Wpanel * NPV = 734.4 lbs
Existing Roof Weight
Roof Weight QD =10.0 psf
Building Length Lbuild =50 ft
Building Width W build =35 ft
Roof Area Abuild =1750 ft2
Building Perimeter Pbuild = 170 ft
Wall Height ht = 8 ft
Wall weight Qwall = 15 psf
Interior wall weight Qint = 10 psf
Roof Load Wfloor = Abuild * QD = 17500 lbs
Wall LoadWwall = ht /2 * Qwall * Pbuild + Abuild * Qint /2 = 18950 lbs
Total Story Weight Wbuild = Wfloor + Wwall = 36450 lbs
Percentage Weight Increase WPV / Wbuild = 2.01%< 10% OKAY
729 W Central Ave
02/01/23
729 W Central Ave
02/16/23
REV
SHEET NAME
SHEET SIZE
SHEET NUMBER
ANSI B
DATE DESCRIPTION
REVISIONS
PV-10
HOMEOWNER INFO
11" X 17"
SIGNATURE & SEAL
CONTRACTOR
JO
E
L
D
U
E
N
A
S
72
9
W
E
S
T
C
E
N
T
R
A
L
A
V
E
N
U
E
,
SA
N
T
A
A
N
A
,
C
A
9
2
7
0
7
,
U
S
A
NAME: POWER4WARD
ADDRESS: 37107 STRATFORD ST, INDIO,
CA 92203, USA
PHONE: 442-306-0930
CONTRACTORLICENSE #: 1032163
ELECTRICAL LICENSE#: 1032163
EMAIL#: Carlosm@power4ward.com
APN: 14015221
EMAIL: -
PHONE: -
EQUIPMENT
SPECIFICATION
729 W Central Ave
02/01/23
~102'-1"
~6
9
'
-
1
"
~84'-5"
~5
1
'
-
4
"
~27
'
-10
"
~17'-8"
~1
8
'
-
6
"
~29'-9"
~1
7
'
-
2
"
MSPUM AC
JB
LC
PHOTOVOLTAIC ROOF MOUNT SYSTEM
18 MODULES - SYSTEM SIZE STC (6.48 kW DC / 5.22 kW AC)
729 WEST CENTRAL AVENUE, SANTA ANA, CA 92707, USA (33.71271, -117.87796)
GOVERNING CODES
2019 CALIFORNIA ELECTRICAL CODE
2019 CALIFORNIA BUILDING CODE
2019 CALIFORNIA FIRE CODE
2019 CALIFORNIA RESIDENTIALCODE
GENERAL NOTES
1) ALL PANELS, SWITCHES, ETC. SHALL HAVE SUFFICIENT GUTTER SPACE
AND LUGS IN COMPLIANCE WITH UL REQUIREMENTS TO ACCOMMODATE
CONDUCTORS SHOWN.
2) THIS SYSTEM WILL NOT BE INTERCONNECTED UNTIL APPROVAL FROM THE
LOCAL JURISDICTION AND UTILITY IS OBTAINED.
3) ALL EXTERIOR ELECTRICAL DEVICES AND EQUIPMENT INCLUDING THOSE
THAT ARE EXPOSED TO OUTSIDE ENVIRONMENT SHALL BE
WEATHERPROOF AND SHALL BE LISTED BY 'UL' FOR THE TYPE OF
APPLICATION AND 'UL' LABEL SHALL APPEAR ON ALL ELECTRICAL
EQUIPMENT.
4) WIRING METHOD SHALL BE EMT ABOVE GROUND MOUNTED IN
CONCEALED SPACES (UNLESS APPROVED OTHERWISE) AND SCHEDULE-40
PVC FOR BELOW GROUND INSTALLATIONS UNLESS NOTED OTHERWISE.
5) AN OSHA APPROVED LADDER PROVIDING ACCESS TO ALL PORTIONS OF
THE ARRAY SHALL BE SECURED IN PRIOR TO REQUESTING INSPECTION.
6) IT IS THE CONTRACTOR'S RESPONSIBILITY TO INSTALL A SUPPLEMENTAL
GROUNDING ELECTRODE CONDUCTOR IF NECESSARY.
SAFETY PLAN NOTES
- INSTALLERS SHALL DRAW IN DESIGNATED SAFETY AREA AROUND HOME.
- INSTALLERS SHALL UPDATE NAME, ADDRESS AND PHONE NUMBER OF
NEAREST URGENT CARE FACILITY RELATIVE TO THE SITE BEFORE
STARTING WORK.
LOCATION OF NEAREST URGENT CARE FACILITY
(FOR INSTALLER USE ONLY)
- NAME:
- ADDRESS:
- PHONE NUMBER:
SYSTEM SUMMARY STC DC/AC
(6.48 kW DC / 5.22 kW AC)
x 2x STRINGS OF 9 CONNECTED IN PARALLEL
- (18) LG360Q1C-A5 (360W) MODULES
- (18) ENPHASE IQ7PLUS-72-2-US (240V) MICROINVERTERS
STC DC: (18) 360 = 6.48 kW
STC AC: (18) 290 = 5.22 kW
SITE PLAN & SAFETY PLAN
SCALE: 1/16" = 1'1
REV
SHEET NAME
SHEET SIZE
SHEET NUMBER
ANSI B
DATE DESCRIPTION
REVISIONS
PV-1
HOMEOWNER INFO
11" X 17"
SIGNATURE & SEAL
CONTRACTOR
JO
E
L
D
U
E
N
A
S
72
9
W
E
S
T
C
E
N
T
R
A
L
A
V
E
N
U
E
,
SA
N
T
A
A
N
A
,
C
A
9
2
7
0
7
,
U
S
A
NAME: POWER4WARD
ADDRESS: 37107 STRATFORD ST, INDIO,
CA 92203, USA
PHONE: 442-306-0930
CONTRACTORLICENSE #: 1032163
ELECTRICAL LICENSE#: 1032163
EMAIL#: Carlosm@power4ward.com
APN: 14015221
EMAIL: -
PHONE: -
HOUSE PHOTO
SCALE: NTS
VICINITY MAP
SCALE: NTS
COVER PAGE
SHEET INDEX
PV-1 COVER PAGE
PV-2 ROOF PLAN WITH MODULES
PV-3 ATTACHMENT DETAIL
PV-4 SINGLE LINE DIAGRAM
PV-5 WIRING CALCULATION
PV-6 PLACARDS
PV-7+ EQUIPMENT SPECIFICATION
PROJECT SITE
AHJ: CITY OF SANTA ANA
UTILITY: N/A
PROPERTY LINE
FENCE
GATE
DIMENSIONSPV MODULE
AC
JB
MAIN SERVICE PANEL
(EXISTING, 125A)
UTILITY METER
(EXISTING)
AC DISCONNECT UNFUSED
(NEW)
ACF AC DISCONNECT FUSED
(N/A)
PRODUCTION METER
(N/A)
JUNCTION BOX
(NEW)
COMBINER BOX
(NEW)
SOLAREDGE METER
(N/A)
SUBPANEL
(N/A)
DC DISCONNECT
(N/A)
DC COMBINER
(N/A)
EXISTING EQUIPMENT
AT
BACKUP LOAD PANEL
(N/A)
BATTERY
(N/A)
INV
SM
CB
BLP
SUB
DCC
DCD
EE
MSP
PM
UM
BAT
(0) INVERTER
(N/A)
AUTO TRANSFORMER
(N/A)
LE
G
E
N
D
CONDUIT
ARRAY LOCATION
WEST CENTRAL AVENUE
PROPERTY LINE
PR
O
P
E
R
T
Y
L
I
N
E
PROPERTY LINE
PR
O
P
E
R
T
Y
L
I
N
E
(E)GARAGE
(E)STRUCTURE
DRIVEWAY
REGISTER EDPROF ESSIONALENGINEER
C I V IL
No. C70784
Exp. 06/30/2023
STATE OF C ALIFORNIA
BLDG #101112888 ISS. 12/29/2022
ELEC #20178038 ISS. 12/12/2022
The scope of the plans is for the installation of the solar
photovoltaic system only and the approval is subject to
compliance with all applicable city and state codes and
regulations regarding construction. The approval of the plans
does not constitute any certification of the accuracy,
completeness, or building permit status of the existing
buildings and structures as shown.
729 W Central Ave
02/01/23
REV
SHEET NAME
SHEET SIZE
SHEET NUMBER
ANSI B
DATE DESCRIPTION
REVISIONS
PV-11
HOMEOWNER INFO
11" X 17"
SIGNATURE & SEAL
CONTRACTOR
JO
E
L
D
U
E
N
A
S
72
9
W
E
S
T
C
E
N
T
R
A
L
A
V
E
N
U
E
,
SA
N
T
A
A
N
A
,
C
A
9
2
7
0
7
,
U
S
A
NAME: POWER4WARD
ADDRESS: 37107 STRATFORD ST, INDIO,
CA 92203, USA
PHONE: 442-306-0930
CONTRACTORLICENSE #: 1032163
ELECTRICAL LICENSE#: 1032163
EMAIL#: Carlosm@power4ward.com
APN: 14015221
EMAIL: -
PHONE: -
EQUIPMENT
SPECIFICATION
729 W Central Ave
02/01/23
2'-10"
20'-5" 30'-9"
2"
16
'
-
1
"
1'
-
6
"
MSPUMAC
JB
LC
BILL OF MATERIALS
SOLAR PV MODULES 18 LG360Q1C-A5 (360W) MODULES
MICRO INVERTERS 18 ENPHASE IQ7PLUS-72-2-US (240V)
JUNCTION BOX 01 600V, NEMA 3R RATED JBOX
LOAD CENTER 01 ENPHASE IQ COMBINER
3-X-IQ-AM1-AM1-240-3
AC DISCONNECT 01
PV VISIBLE LOCKABLE
LABELED DISCONNECT
(30A UNFUSED 1PH 240VAC)
ATTACHMENTS 36 IRONRIDGE - SLOTTED L-FEET
RAIL 09 IRONRIDGE RESOURCES - XR10
RAIL SPLICE 06 RAIL SPLICE
MID CLAMP 30 MID CLAMP
END CLAMP 12 END CLAMP
GROUNDING LUG 03 GROUNDING LUG
ROOF DESCRIPTION TABLE
ROOF
PLANE
RAFTER
SIZE
RAFTER
SPACING
ATTACHMENT
SPACING
MODULE
COUNT
ARRAY
TILT
AZIMUTH
#1 2" x 6" 24" O.C. 48" O.C. 18 18° 180°
MODULE AREA & WEIGHT CALCULATIONS
PANEL TYPES (COUNT, AREA, WEIGHT):
- (18x) LG360Q1C-A5 (66.93" x 40", 40.8 LBS)
MICRO-INVERTER TYPES (COUNT, WEIGHT):
- (18x) ENPHASE IQ7PLUS-72-2-US (240V) (2.38 LBS)
ATTACHMENT COUNT: 36
MOUNTING SYSTEM WEIGHT/MODULE: 1.5 LBS
TOTAL ROOF AREA: 1782.5 SF
TOTAL ARRAY AREA: (18) 66.9" x 40.0" = 334.65 SF
TOTAL ARRAY WEIGHT: (18) 40.8 + (18) 2.4 + (18) 1.5 = 804 LBS
WEIGHT AT EACH CONNECTION: 804 LBS / 36 = 22.33 LBS
DISTRIBUTED LOAD: 804 LBS / 334.65 SF = 2.40 PSF
ROOF AREA COVERED BY ARRAY: 335 SF / 1782.5 SF = 18.79%
REV
SHEET NAME
SHEET SIZE
SHEET NUMBER
ANSI B
DATE DESCRIPTION
REVISIONS
PV-2
HOMEOWNER INFO
11" X 17"
SIGNATURE & SEAL
CONTRACTOR
JO
E
L
D
U
E
N
A
S
72
9
W
E
S
T
C
E
N
T
R
A
L
A
V
E
N
U
E
,
SA
N
T
A
A
N
A
,
C
A
9
2
7
0
7
,
U
S
A
NAME: POWER4WARD
ADDRESS: 37107 STRATFORD ST, INDIO,
CA 92203, USA
PHONE: 442-306-0930
CONTRACTORLICENSE #: 1032163
ELECTRICAL LICENSE#: 1032163
EMAIL#: Carlosm@power4ward.com
APN: 14015221
EMAIL: -
PHONE: -
ROOF PLAN WITH MODULES
SCALE: 1/8" = 1'-0"
1
ROOF PLAN WITH
MODULES
DESIGN CRITERIA
EXPOSURE CATEGORY = B
WIND SPEED = 95 MPH
SNOW LOAD = 0 PSF
1
ROOF ATTACHMENT
DIMENSIONSPV MODULE
AC
JB
MAIN SERVICE PANEL
(EXISTING, 125A)
UTILITY METER
(EXISTING)
AC DISCONNECT UNFUSED
(NEW)
ACF AC DISCONNECT FUSED
(N/A)
PRODUCTION METER
(N/A)
JUNCTION BOX
(NEW)
COMBINER BOX
(NEW)
SOLAREDGE METER
(N/A)
SUBPANEL
(N/A)
DC DISCONNECT
(N/A)
DC COMBINER
(N/A)
MICRO-INVERTER
EXISTING EQUIPMENT
AT
BACKUP LOAD PANEL
(N/A)
BATTERY
(N/A)
INV
SM
CB
BLP
SUB
DCC
DCD
EE
MSP
PM
UM
BAT
(0) INVERTER
(N/A)
AUTO TRANSFORMER
(N/A)
LE
G
E
N
D
FIRE SETBACK CONDUIT
RAFTER
RAIL
(E) FRONT YARD
WEST CENTRAL AVENUE
(E) REAR YARD
18" FIRE SETBACK
18" FIRE SETBACK
36
"
F
I
R
E
S
E
T
B
A
C
K
36
"
F
I
R
E
S
E
T
B
A
C
K
ROOF #1
PITCH 18°
AZIMUTH 180°REGISTER EDPROF E SSIONALENGINEER
C I V IL
No. C70784
Exp. 06/30/2023
STATE OF C ALIFORNIA
729 W Central Ave
02/01/23
~5
"
REV
SHEET NAME
SHEET SIZE
SHEET NUMBER
ANSI B
DATE DESCRIPTION
REVISIONS
PV-3
HOMEOWNER INFO
11" X 17"
SIGNATURE & SEAL
CONTRACTOR
JO
E
L
D
U
E
N
A
S
72
9
W
E
S
T
C
E
N
T
R
A
L
A
V
E
N
U
E
,
SA
N
T
A
A
N
A
,
C
A
9
2
7
0
7
,
U
S
A
NAME: POWER4WARD
ADDRESS: 37107 STRATFORD ST, INDIO,
CA 92203, USA
PHONE: 442-306-0930
CONTRACTORLICENSE #: 1032163
ELECTRICAL LICENSE#: 1032163
EMAIL#: Carlosm@power4ward.com
APN: 14015221
EMAIL: -
PHONE: -
ATTACHMENT
DETAIL
ATTACHMENT DETAIL
SCALE: NTS
ATTACHMENT DETAIL (ENLARGED SECTION VIEW)
SCALE: NTS
5/16"x3.5" SS LAG BOLT
WITH MIN 2.5" THREAD
EMBEDMENT, SEALED
PENETRATION
PV MODULES
(E) SINGLE LAYER OF
ASPHALT SHINGLE
IRONRIDGE XR10 RAIL
IRONRIDGE INTEGRATED
GROUNDING & END/MID
CLAMP
ALUMN. "L" BRACKET
W/3/8" SS BOLT & NUT
IRONRIDGE FLASH FOOT2
ATTACHMENTS
FLASHING
PV MODULE
SEE ENLARGED VIEW
(E) SINGLE LAYER OF
ASPHALT SHINGLE
2"X6" RAFTER @24"O.C
2"X6" RAFTER @24"O.C
2.5"MIN
.
REGISTER EDPROF ESSIONALENGINEER
C I V IL
No. C70784
Exp. 06/30/2023
STATE OF CALIFORNIA
729 W Central Ave
02/01/23
SYSTEM SUMMARY STC DC/AC
(6.48 kW DC / 5.22 kW AC)
x 2x STRINGS OF 9 CONNECTED IN PARALLEL
- (18) LG360Q1C-A5 (360W) MODULES
- (18) ENPHASE IQ7PLUS-72-2-US (240V) MICROINVERTERS
STC DC: (18) 360 = 6.48 kW
STC AC: (18) 290 = 5.22 kW
211 9
MOD: LG360Q1C-A5 (360W) MODULES
INV: ENPHASE IQ7PLUS-72-2-US (240V)
(1 STRING X 9 MICRO-INV)
2 11 9
MOD: LG360Q1C-A5 (360W) MODULES
INV: ENPHASE IQ7PLUS-72-2-US (240V)
(1 STRING X 9 MICRO-INV)
JUNCTION BOX
600V, NEMA 3R
UL LISTED
15A(N)
15A(N)
ENPHASE
IQ COMBINER PANEL
WITH ENPHASE ENVOY
XAM1-120 (OR EQUIV)
ON OFF
PV VISIBLE LOCKABLE
LABELED DISCONNECT
(30A UNFUSED 1PH 240VAC)
TO
UTILITY
GRIDM
30A(N)
100A(E)
UTILITY METER
METER NO: N/A
UTILITY: NULL
SERVICE: 240V 60HZ 1PH
MAIN SERVICE PANEL
(EXISTING, CENTER-FED)
BUS RATING: 125A
MAIN BREAKER: 100A (E)
12 AWG Q-CABLE
06 AWG Cu BARE G (BOND RACKING)
12 AWG Q-CABLE
06 AWG Cu BARE G (BOND RACKING)
Ground Rod
EE
MS-01
MS-01
MCB-01
MCB-01
LC-01 LC-01
AC wire details
Wire Min Ampacity Live Neutral Ground Min EMT Min PVC Min RMC
MS-01 13.61A 12 AWG (Q-Cable) -06 AWG BARE
(NOT IN CONDUIT)- - -
MCB-01 13.61A (2) 10 AWG THWN-2 10 AWG THWN-2 10 AWG THWN-2 0.50 in 0.50 in 0.50 in
LC-01 27.23A (2) 10 AWG THWN-2 10 AWG THWN-2 10 AWG THWN-2 0.50 in 0.50 in 0.50 in
UTILITY FEED + TOTAL BACKFEED
100A + 30A = 130A
LESS OR EQUAL TO
BUS RATING x 120%
125A x 120% = 150A
INTERCONNECTION 120% RULE
(MAIN PANEL)
CALCULATION ENSURES BUS IS
SAFE REGARDLESS OF LOADS
Isc(25°C) = 10.79A, Tisc = 0.040%/°C
Isc(T) = Isc(25°C) x [1 + Tisc x (T-25°C)]
Isc(2°C) = 10.69A, Isc(31°C) = 10.82A
Voc(25°C) = 42.70V, Tvoc = -0.240%/°C
Voc(T) = Voc(25°C) x [1 + Tvoc x (T-25°C)]
Voc(2°C) = 45.06V, Voc(31°C) = 42.09V
EXTREME CASE MODULE OUTPUT
(LG360Q1C-A5)
10A/15A
REV
SHEET NAME
SHEET SIZE
SHEET NUMBER
ANSI B
DATE DESCRIPTION
REVISIONS
PV-4
HOMEOWNER INFO
11" X 17"
SIGNATURE & SEAL
CONTRACTOR
J
O
E
L
D
U
E
N
A
S
72
9
W
E
S
T
C
E
N
T
R
A
L
A
V
E
N
U
E
,
SA
N
T
A
A
N
A
,
C
A
9
2
7
0
7
,
U
S
A
NAME: POWER4WARD
ADDRESS: 37107 STRATFORD ST, INDIO,
CA 92203, USA
PHONE: 442-306-0930
CONTRACTORLICENSE #: 1032163
ELECTRICAL LICENSE#: 1032163
EMAIL#: Carlosm@power4ward.com
APN: 14015221
EMAIL: -
PHONE: -
ELECTRICAL SINGLE LINE DIAGRAM
SCALE: NTS
SINGLE LINE
DIAGRAM
NOTE:
x ALL GROUNDING TO COMPLY WITH NEC 690.47.
x ROOF TOP CONDUIT SHALL BE LOCATED MIN. 7/8"
ABOVE ROOF SURFACE.
x ALL TERMINALS SHALL BE MIN. 75 DEG. C RATED.
729 W Central Ave
02/01/23
ELECTRICAL NOTES
1) ALL EQUIPMENT TO BE LISTED BY UL OR OTHER NRTL, AND LABELED FOR ITS APPLICATION.
2) ALL CONDUCTORS SHALL BE COPPER, RATED FOR 600 V AND 90 DEGREE C WET ENVIRONMENT.
3) WIRING, CONDUIT, AND RACEWAYS MOUNTED ON ROOFTOPS SHALL BE ROUTED DIRECTLY TO, AND LOCATED AS CLOSE AS POSSIBLE TO THE NEAREST RIDGE, HIP, OR VALLEY.
4) WORKING CLEARANCES AROUND ALL NEW AND EXISTING ELECTRICAL EQUIPMENT SHALL COMPLY WITH NEC 110.26.
5) DRAWINGS INDICATE THE GENERAL ARRANGEMENT OF SYSTEMS. CONTRACTOR SHALL FURNISH ALL NECESSARY OUTLETS, SUPPORTS, FITTINGS AND ACCESSORIES TO FULFILL APPLICABLE CODES AND STANDARDS.
6) WHERE SIZES OF JUNCTION BOXES, RACEWAYS, AND CONDUITS ARE NOT SPECIFIED, THE CONTRACTOR SHALL SIZE THEM ACCORDINGLY.
7) ALL WIRE TERMINATIONS SHALL BE APPROPRIATELY LABELED AND READILY VISIBLE.
8) MODULE GROUNDING CLIPS TO BE INSTALLED BETWEEN MODULE FRAME AND MODULE SUPPORT RAIL, PER THE GROUNDING CLIP MANUFACTURER'S INSTRUCTION.
9) MODULE SUPPORT RAIL TO BE BONDED TO CONTINUOUS COPPER G.E.C.VIA WEEB LUG OR ILSCO GBL-4DBT LAY-IN LUG.
10)PV EQUIPMENT SHALL BE DESIGNED AND INSTALLED IN ACCORDANCE WITH NEC 690.
11)EXACT LOCATION OF AUXILIARY GROUNDING TO BE DETERMINED AT TIME OF INSTALL.
12)EXISTING WIRES MUST BE REPLACED IF SMALLER THAN LISTED MINIMUM SIZES PER NEC 310.15(B)(16).
13)AC DISCONNECT LOCATED WITHIN 10' OR LESS FROM UTILITY METER
14)IF ENVOY PRESENT, ENVOY BREAKER DETERMINED AT FACTORY BY MANUFACTURER.
15)IF ENVOY PRESENT, FOR IQ COMBINER USE SINGLE CT ON L1. AT SYSTEM CONTROLLER MAIN USE DOUBLE CT ON L1 AND L2.
SYSTEM SUMMARY STC DC/AC
(6.48 kW DC / 5.22 kW AC)
x 2x STRINGS OF 9 CONNECTED IN PARALLEL
- (18) LG LG360Q1C-A5 (360W) MODULES
- (18) ENPHASE IQ7PLUS-72-2-US (240V) MICROINVERTERS
STC DC: (18) 360 = 6.48 kW
STC AC: (18) 290 = 5.22 kW
AC wire details
WireID #Modules Nominal
Voltage
Backfeed *1.25
/cond. set
Min
OCPD
Total
Power
Conductor
sets
ccConductors
/conduit
Expected
max temp
Adjusted ampacity (ampacity x temp
derate x conduit fill derate)
Conductor &
neutral size
EGC size
(Cu)
Conductor
metal
Max
length
V drop Min EMT
size
Min PVC
size
Min RMC
size
MS-01 9 240 V 13.61 A 15 A 2.6 kW 1 2 31 25 x 0.94 x - = 23.50 A 12 AWG (Q-Cable)06 AWG BARE
(NOT IN CONDUIT)Cu 50 ft 0.78 % - - -
MCB-01 9 240 V 13.61 A 15 A 2.6 kW 1 2 31 35 x 0.94 x 1.00 = 32.90 A 10 AWG THWN-2 10 AWG THWN-2 Cu 50 ft 0.47 % 0.50 in 0.50 in 0.50 in
LC-01 18 240 V 27.23 A 30 A 5.2 kW 1 2 31 35 x 0.94 x 1.00 = 32.90 A 10 AWG THWN-2 10 AWG THWN-2 Cu 10 ft 0.19 % 0.50 in 0.50 in 0.50 in
UTILITY FEED + TOTAL BACKFEED
100A + 30A = 130A
LESS OR EQUAL TO
BUS RATING x 120%
125A x 120% = 150A
INTERCONNECTION 120% RULE
(MAIN PANEL)
CALCULATION ENSURES BUS IS
SAFE REGARDLESS OF LOADS
Isc(25°C) = 10.79A, Tisc = 0.040%/°C
Isc(T) = Isc(25°C) x [1 + Tisc x (T-25°C)]
Isc(2°C) = 10.69A, Isc(31°C) = 10.82A
Voc(25°C) = 42.70V, Tvoc = -0.240%/°C
Voc(T) = Voc(25°C) x [1 + Tvoc x (T-25°C)]
Voc(2°C) = 45.06V, Voc(31°C) = 42.09V
EXTREME CASE MODULE OUTPUT
(LG360Q1C-A5)
REV
SHEET NAME
SHEET SIZE
SHEET NUMBER
ANSI B
DATE DESCRIPTION
REVISIONS
PV-5
HOMEOWNER INFO
11" X 17"
SIGNATURE & SEAL
CONTRACTOR
JO
E
L
D
U
E
N
A
S
72
9
W
E
S
T
C
E
N
T
R
A
L
A
V
E
N
U
E
,
SA
N
T
A
A
N
A
,
C
A
9
2
7
0
7
,
U
S
A
NAME: POWER4WARD
ADDRESS: 37107 STRATFORD ST, INDIO,
CA 92203, USA
PHONE: 442-306-0930
CONTRACTORLICENSE #: 1032163
ELECTRICAL LICENSE#: 1032163
EMAIL#: Carlosm@power4ward.com
APN: 14015221
EMAIL: -
PHONE: -
WIRING
CALCULATION
729 W Central Ave
02/01/23
REV
SHEET NAME
SHEET SIZE
SHEET NUMBER
ANSI B
DATE DESCRIPTION
REVISIONS
PV-6
HOMEOWNER INFO
11" X 17"
SIGNATURE & SEAL
CONTRACTOR
JO
E
L
D
U
E
N
A
S
72
9
W
E
S
T
C
E
N
T
R
A
L
A
V
E
N
U
E
,
SA
N
T
A
A
N
A
,
C
A
9
2
7
0
7
,
U
S
A
NAME: POWER4WARD
ADDRESS: 37107 STRATFORD ST, INDIO,
CA 92203, USA
PHONE: 442-306-0930
CONTRACTORLICENSE #: 1032163
ELECTRICAL LICENSE#: 1032163
EMAIL#: Carlosm@power4ward.com
APN: 14015221
EMAIL: -
PHONE: -
PLACARDS
NOTES AND SPECIFICATIONS:
x SIGNS AND LABELS SHALL MEET THE REQUIREMENTS OF THE CEC
2019 ARTICLE 110.21(B), UNLESS SPECIFIC INSTRUCTIONS ARE
REQUIRED BY SECTION 690, OR IF REQUESTED BY THE LOCAL AHJ.
x SIGNS AND LABELS SHALL ADEQUATELY WARN OF HAZARDS USING
EFFECTIVE WORDS, COLORS AND SYMBOLS.
x LABELS SHALL BE PERMANENTLY AFFIXED TO THE EQUIPMENT OR
WIRING METHOD AND SHALL NOT BE HAND WRITTEN.
x LABEL SHALL BE OF SUFFICIENT DURABILITY TO WITHSTAND THE
ENVIRONMENT INVOLVED.
x SIGNS AND LABELS SHALL COMPLY WITH ANSI Z535.4-2011,
PRODUCT SAFETY SIGNS AND LABELS, UNLESS OTHERWISE
SPECIFIED.
x DO NOT COVER EXISTING MANUFACTURER LABELS.
SOURCES: UTILITY GRID
AND PV SOLAR ELECTRIC
SYSTEM
DUAL POWER SUPPLY
LABEL LOCATION:
UTILITY SERVICE METER AND MAIN
SERVICE PANEL.
PER CODE(S): CEC 2019: 705.12(D)(3),
NEC 2017: 705.12(D)(3), NEC 2011:
705.12(D)(4)
DO NOT ADD LOADS
PHOTOVOLTAIC SYSTEM
COMBINER PANEL
LABEL LOCATION:
PHOTOVOLTAIC AC COMBINER (IF
APPLICABLE).
PER CODE(S): CEC 2019:
705.12(D)(2)(3)(c), NEC 2017:
705.12(D)(2)(3)(c), NEC 2011: 705.12(D)(4)
LABEL LOCATION:
INTERIOR AND EXTERIOR DC CONDUIT EVERY 1O FT, AT EACH TURN, ABOVE AND
BELOW PENETRATIONS, ON EVERY JB/PULL BOX CONTAINING DC CIRCUITS.
PER CODE(S): CEC 2019: 690.31(G)(3), 690.31(G)(4), NEC 2017: 690.31(G)(3),
690.31(G)(4), NEC 2011: 690.31(E)(3), 690.31(E)(4), IFC 2012: 605.11.1.4
ELECTRICAL SHOCK HAZARD
LABEL LOCATION:
INVERTER(S), ENPHASE ENVOY ENCLOSURE (IF
APPLICABLE).
PER CODE(S): CEC 2019: 690.5(C), NEC 2017: 690.5(C),
NEC 2011: 690.5(C)
PHOTOVOLTAIC AC DISCONNECT
THE DC CONDUCTORS OF THIS
PHOTOVOLTAIC SYSTEM ARE
UNGROUNDED AND MAY BE
ENERGIZED
ELECTRICAL SHOCK HAZARD
WARNING
LABEL LOCATION:
INVERTER(S), DC DISCONNECTS.
PER CODE(S): CEC 2019: 690.35(F), NEC
2017: 690.35(F), NEC 2011: 690.35(F)
ELECTRICAL SHOCK HAZARD
WARNING!
LABEL LOCATION:
INVERTER(S), AC DISCONNECT(S), AC COMBINER PANEL
(IF APPLICABLE).
PER CODE(S): CEC 2019: 690.17(E), NEC 2017: 690.17(E),
NEC 2011: 690.17(4)
DO NOT RELOCATE THIS
OVERCURRENT DEVICE
LABEL LOCATION:
ADJACENT TO PV BREAKER (IF
APPLICABLE).
PER CODE(S): CEC 2019:
705.12(D)(2)(3)(b), NEC 2017:
705.12(D)(2)(3)(b), NEC 2011: 705.12(D)(7)
WARNING
WARNING!
WARNING ! WARNING!
TURN RAPID SHUTDOWN
SWITCH TO THE
"OFF" POSITION TO
SHUT DOWN PV SYSTEM
AND REDUCE
SHOCK HAZARD
IN THE ARRAY
SOLAR PV SYSTEM EQUIPPED
WITH RAPID SHUTDOWN
SOLAR ELECTRIC
PV PANELS
LABEL LOCATION:
AC DISCONNECT, POINT OF INTERCONNECTION
(PER CODE: NEC 690.56(C)(1)(a), IFC 605.11.3.1(1)
LABEL LOCATION:
INVERTER(S), DC DISCONNECT(S).
PER CODE(S): CEC 2019: 690.53, NEC 2017: 690.53, NEC
2011: 690.53!
!
POWER TO THIS BUILDING IS ALSO SUPPLIED FROM THE
FOLLOWING SOURCES WITH DISCONNECTS LOCATED AS SHOWN
AT: MAIN SERVICE PANEL & UTILITY METER
AC DISCONNECT,INVERTER
CAUTION:
MULTIPLE SOURCES OF POWER
(N) COMBINER BOX
(N) AC DISCONNECT
(E) MAIN SERVICE PANEL
(E) UTILITY METER
WEST CENTRAL AVENUE
729 W Central Ave
02/16/23
EQUIPMENT
SPECIFICATION
REV
SHEET NAME
SHEET SIZE
SHEET NUMBER
ANSI B
DATE DESCRIPTION
REVISIONS
PV-7
HOMEOWNER INFO
11" X 17"
SIGNATURE & SEAL
CONTRACTOR
JO
E
L
D
U
E
N
A
S
72
9
W
E
S
T
C
E
N
T
R
A
L
A
V
E
N
U
E
,
SA
N
T
A
A
N
A
,
C
A
9
2
7
0
7
,
U
S
A
NAME: POWER4WARD
ADDRESS: 37107 STRATFORD ST, INDIO,
CA 92203, USA
PHONE: 442-306-0930
CONTRACTORLICENSE #: 1032163
ELECTRICAL LICENSE#: 1032163
EMAIL#: Carlosm@power4ward.com
APN: 14015221
EMAIL: -
PHONE: -
729 W Central Ave
02/01/23
REV
SHEET NAME
SHEET SIZE
SHEET NUMBER
ANSI B
DATE DESCRIPTION
REVISIONS
PV-8
HOMEOWNER INFO
11" X 17"
SIGNATURE & SEAL
CONTRACTOR
JO
E
L
D
U
E
N
A
S
72
9
W
E
S
T
C
E
N
T
R
A
L
A
V
E
N
U
E
,
SA
N
T
A
A
N
A
,
C
A
9
2
7
0
7
,
U
S
A
NAME: POWER4WARD
ADDRESS: 37107 STRATFORD ST, INDIO,
CA 92203, USA
PHONE: 442-306-0930
CONTRACTORLICENSE #: 1032163
ELECTRICAL LICENSE#: 1032163
EMAIL#: Carlosm@power4ward.com
APN: 14015221
EMAIL: -
PHONE: -
EQUIPMENT
SPECIFICATION
729 W Central Ave
02/01/23
REV
SHEET NAME
SHEET SIZE
SHEET NUMBER
ANSI B
DATE DESCRIPTION
REVISIONS
PV-9
HOMEOWNER INFO
11" X 17"
SIGNATURE & SEAL
CONTRACTOR
JO
E
L
D
U
E
N
A
S
72
9
W
E
S
T
C
E
N
T
R
A
L
A
V
E
N
U
E
,
SA
N
T
A
A
N
A
,
C
A
9
2
7
0
7
,
U
S
A
NAME: POWER4WARD
ADDRESS: 37107 STRATFORD ST, INDIO,
CA 92203, USA
PHONE: 442-306-0930
CONTRACTORLICENSE #: 1032163
ELECTRICAL LICENSE#: 1032163
EMAIL#: Carlosm@power4ward.com
APN: 14015221
EMAIL: -
PHONE: -
EQUIPMENT
SPECIFICATION
729 W Central Ave
02/01/23